This notice is for a federal construction contract solicitation to renovate and expand pharmacy spaces at the Northport VA Medical Center in Northport, New York. The scope of work includes abatement, demolition, general construction, alterations, mechanical, plumbing, electrical, and fire protection work to renovate existing pharmacy spaces totaling approximately 5,000 square feet. The work will be conducted in phases to allow continued pharmacy operations. The contract is set aside for Service-Disabled Veteran Owned Small Businesses and has an estimated value between $1 million to $5 million. The base period of performance is 455 calendar days from notice to proceed. Interested SDVOSBs must register in SAM.gov, D&B, and VIP and submit capability statements by the due date. The solicitation will be released on or around September 30, 2021 via SAM.gov and responses must be submitted in hard copy by the date and time specified in the solicitation.
View the file
Other files
Show all 15
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SEQUENCE OF OPERATION FOR VARIABLE AIR VOLUME
AIR HANDLING UNIT AHU-1 WITH MINIMUM OUTSIDE AIR
1. GENERAL
1.1 UNIT IS NORMALLY STARTED AND STOPPED REMOTELY AT THE ECC. H-O-A SWITCH SHALL BE KEPT IN THE "AUTO" POSITION. "HAND" AND "OFF" POSITIONS SHALL BE USED ONLY FOR MAINTENANCE. WHEN THE UNIT IS "OFF" D-1, D-2 & D-3 SHALL BE FULLY CLOSED. WHEN THE UNIT IS "ON" D-1, D-2 & D-3 SHALL BE FULLY OPEN.
2. TEMPERATURE CONTROL
2.1
3. AIR FLOW CONTROL
3.1
3.2
3.3
4. HUMIDITY CONTROL
4.1
4.2
5. FREEZE PROTECTION
5.1
SUPPLY AIR TEMPERATURE, SENSED BY TT-1, SHALL BE MAINTAINED AT SETPOINT VIA DIGITAL CONTROL PANEL
BY MODULATING V-1 OR V-2 IN SEQUENCE.
THE SUPPLY AIR FLOW SHALL BE CONTROLLED BY THE DIGITAL CONTROL PANEL MODULATING THE SUPPLY FANS SPEED IN UNISON TO MAINTAIN 1.5" OF DUCT STATIC PRESSURE (FIELD ADJUSTABLE), SENSED BY SPS-1.
THE DIGITAL CONTROL PANEL, USING TOTAL SUPPLY AIR AND RELIEF AIR FLOW SIGNALS, SHALL RESET THE RELIEF AIR FAN'S CONTROLLER IN UNISON TO MAINTAIN A CONSTANT AIR FLOW DIFFERENCE BETWEEN THE
SUPPLY AIR AND THE RELIEF AIR FLOWS EQUAL TO MINIMUM OUTSIDE AIR AND RELIEF AIR.
USING HIGH PRESSURE SENSOR SPS-2 LOCATED AT THE SUPPLY FAN DISCHARGE, SHALL PREVENT THE SUPPLY FAN FROM DEVELOPING OVER 3" OF STATIC PRESSURE (FIELD ADJUSTABLE). IF STATIC PRESSURE AT SPS-2 DOES EXCEED 3" THE SUPPLY AIR FAN SHALL STOP. SPS-2 SHALL BE HARDWIRED TO THE SUPPLY FAN CONTROLLER AND UNIT SHALL BE SHUTDOWN IN HAND,AUTO OR BYPASS MODE. SPS-2 WILL REQUIRE MANUAL
RESET AT THE DEVICE.
IF THE PREHEAT AIR TEMPERATURE AS SENSED BY TT-3 FALLS BELOW 45°F [7°C], AN ALARM SIGNAL SHALL INDICATE AT THE DCP AND ECC. IF THIS TEMPERATURE FALLS BELOW 40°F [4.4°C], AS SENSED BY THE TSL THE SUPPLY AND RELIEF FANS SHALL SHUT DOWN AND A CRITICAL ALARM SHALL INDICATE AT THE DIGITAL CONTROL PANEL AND ECC. TSL SHALL BE HARDWIRED TO THE SUPPLY FAN CONTROLLER AND UNIT SHALL BE SHUTDOWN IN HAND,AUTO OR BYPASS MODE. TSL WILL REQUIRE MANUAL RESET AT THE DEVICE.
WHEN THE DIGITAL CONTROL PANEL IS NOT CALLING FOR HUMIDITY, SENSED BY RELIEF AIR HUMIDITY H-1, 2-WAY "ON-OFF" CONTROL VALVE V-3 SHALL REMAIN CLOSED. WHEN THE DIGITAL CONTROL PANEL IS CALLING
FOR HUMIDITY, V-3 SHALL REMAIN OPEN.
RELIEF AIR HUMIDITY SHALL BE MAINTAINED AT SETPOINT OF 35% RH (ADJ) VIA DIGITAL CONTROL PANEL BY MODULATING CONTROL VALVE V-4 TO MAINTAIN THE DESIRED HUMIDITY. THE DCP SHALL OVERRIDE THIS CONTROL TO MAINTAIN HUMIDITY OF 80% AS SENSED BY H-2. DCP SHALL CLOSE VALVE V-3 WHENEVER THE SUPPLY FAN IS OFF. VALVE V-4 SHALL BE INTERLOCKED WITH A TEMPERATURE SWITCH TO KEEP THE
HUMIDIFIER OFF UNTIL CONDENSATE TEMPERATURE APPROACHES STEAM TEMPERATURE.
ALARM
PROCESSING
DU
TY
C
YC
LE
FU
NC
TI
O
N
SC
HE
DU
LE
S
TA
RT
/S
TO
P
HUMIDITY HIGH LIMIT
RELIEF FAN ALARM
SUPPLY FAN ALARM
RELIEF FAN STATUS
STATIC PRESSURE HIGH LIMIT
SUPPLY AIR FLOW (CFM)
RELIEF LOW PRESSURE
ST
AT
US
SYSTEM
AL
AR
M
PR
IO
RI
TY
/A
DD
-A
LT
ER
NA
TE
N
O.
EL
EC
TR
IC
D
EV
IC
E
SP
EE
D
CO
M M
AN
D
PO
IN
T
ID
DISCHARGE STATIC PRESSURE
DISCHARGE AIR HUMIDITY
DISCHARGE AIR TEMPERATURE
PRE-HEAT TEMPERATURE
COOILING COIL TEMPERATURE
SYSTEM COMPONENT:
RELIEF AIR FLOW (CFM)
RELIEF AIR TEMPERATURE
-- O
PE
N/
CL
O
SE
ST
AR
T/
ST
O P
VF
D
BY
PA
SS
VA
LV
E
PO
SI
TI
O
N
DA
M
PE
R
PO
SI
TI
O
NVAV AIR HANDLER AHU-1
POINTS LIST
SYSTEM:
LEGEND
POINT
BINARY
TE
M
PE
RA
TU
RE
(T I)
Lo ca l A la rm P an el
M as te r A la rm
P an el
Ar ea
A la rm P an el
HI
G
H
ST
AT
IC
P
RE
SS
UR
E
HI
G
H
HU
M
ID
IT
Y
PR
ES
SU
RE
--LO
W
T
EM
PE
RA
TU
RE
PE
RC
EN
T
PR
ES
SU
RE
PO
SI
TI
O
N
FL
O W
HI
G
H
LI
M
IT
LO
W
L
IM
IT
SYSTEM INPUTS
ANA- BINARY ANALOG
SP
AC
E
TE
M P.
C O
NT
RO
L
--ST
AT
IC
P
RE
SS
UR
E
RE
SE
T
--DE
M
AN
D
LI
M
IT
IN
G
TE
M
PE
RA
TU
RE
R
ES
ET
TE
M
PE
RA
TU
RE
O
VE
RR
ID
E
EN
TH
AL
PY
E
CO
NO
M
IZ
ER
TE
M
PE
RA
TU
RE
E
CO
NO
M
IZ
ER
FA
IL
UR
E
M O
DE
PR
ES
SU
RE
/V
OL
UM
E
CO
NT
RO
L
REMARKS
FU
LL
C O
M M
UN
IC
AT
IO
N
SYSTEM SOFTWARE/CONTROL
APPLICATION/FUNCTION
PAGE:
RELIEF AIR HUMIDITY
SUPPLY FAN STATUS
PREHEAT AIR LOW LIMIT
RELIEF FAN START/STOP
STEAM HUMIDIFIER VALVE V-4
PRE-HEAT VALVE V-2
RELIEF AIR DAMPER
MINIMUM OUTSIDE AIR DAMPER
SUPPLY FAN SPEED CONTROL
OUTSIDE AIR DAMPER
RELIEF FAN SPEED CONTROL
ST
AT
IC
P
RE
SS
UR
E
CA
RB
O N
M O
NO
XI
DE
HU
M
ID
IT
Y
VA
CU
UM
STEAM ISOLATION VALVE V-3
SUPPLY FAN START/STOP
AI-1
AI-2
AI-3
AI-5
AI-6
AI-7
AI-8
AI-9
AI-10
TR
EN
DI
NG
OUTSIDE AIR TEMPERATURE AI-11
BI-1
BI-2
BI-3
BI-4
BI-5
BI-6
BI-7
BI-8
AO-1
AO-2
AO-3
AO-5
AO-7
AO-8
AO-10
BO-1
BO-2
BO-3
FULL COMMUNICATION/TYP FOR 2
AB
BR
EV
IA
TI
O
N
RAT
RAH
RAF
PHT
CCT
DAT
DASP
DAH
SAF
OAT
RLP
RF-STS
SF-STS
TSL-1
SPS-2
HSH
SF-ALA
RF-ALA
RF-SPD
SF-SPD
OAD
RAD
MIN-OAD
PHT-V1
HUM-V4
RF-SST
SF-SST
HUM-ISO-V3
OUTPUTS
LOG
COOLING VALVE V-1 AO-9 CLG-V1
RELIEF AIR
4600 CFM
D-3
D-2
PR
E-
F
IL
TE
R
OUTSIDE
AIR
4600 CFM
D-1
CO
IL
P
RE
HE
AT
CO
O
LI
NG
C O
IL
LOCATE SENSOR
OUTSIDE UNDER
SHIELD
LPS
V-2
CHWR CHWS
RELIEF FAN # 1
SUPPLY FAN # 1
M
ER
V
FI
NA
L
FI
LT
ER
LPS
V-4
STEAM
HUMIDIFIERTT
TT
TT TT
HT
TT HT
AF
M
S
MINIMUM
OUTSIDE
AIR
3300 CFM
CST-5
T-2
T-3 T-6
H-1
IT
DSD
STEAM IFB COIL
CURRENT
TRANSMITTER
FOR FAN STATUS
PRESSURE SWITCH LOW
TO DISABLE RELIEF FAN WHEN LOW
PRESSURE LIMIT SET POINT IS REACHED
PRESSURE SWITCH HIGH
TO DISABLE FAN WHEN HIGH PRESSURE
LIMIT SETPOINT IS REACHED
PSH
SMOKE DETECTOR
CONTROL PANEL, TYP.
D1-C
D3-C
D2-C
FT DPS
TT
T-1
V4-C
HHL
DPS
PSL
CST4
SPS
TSL
TSL-1
PRE-FILTER
FINAL MERV 14 FILTER IN THE AHU
MIN. OUTSIDE AIR FLOW
AI-14
AI-15
AI-12 PRE-FILTER
FINAL FILTER
MIN. OA
DIRTY ALARM @ 0.6" WC
DIRTY ALARM @ 1.0" WC
TYPICAL FOR 2
TYPICAL FOR 2
TYPICAL FOR 2
TYPICAL FOR 2
TYPICAL FOR 2
TYPICAL FOR 2
POINTS LIST FOR VAV AIR HANDLING UNIT AHU-1 WITH MINIMUM OUTSIDE AIR
NTS
6. AUTOMATIC SHUTDOWN/RESTART
6.1 WHEN SMOKE IS DETECTED BY DUCT SMOKE DETECTOR, SD, THE SUPPLY AND RELIEF FANS SHALL SHUT "OFF"
AND AN ALARM SIGNAL SHALL BE TRANSMITTED TO THE FIRE ALARM SYSTEM.
RELIEF FAN # 2
CS
SUPPLY FAN # 2
CS
IT
V2-C
AF
M
S
FT
AF
M
S
FT
AF
M
S
FT
AF
M
S
FT
CURRENT
TRANSMITTER
FOR FAN STATUS
ENTERING CHWS TEMPERATURE AI-12 NORM CC TEMP
TYPICAL FOR 3 & TOTAL
TYPICAL FOR 2 & TOTAL
FULL COMMUNICATION/TYP FOR 2
V-3
V3-C V1-C
CONTROL PANEL, TYP.
CONTROL PANEL, TYP.
SC
CONTROL PANEL, TYP.
SC
RELIEF
AIR
PRE-FILTER AI-12 PRE-FILTER DIRTY ALARM @ 0.9" WC
SC
SC
HUMIDIFICATION CONTROL
V -1
SUPPLY AIR
STEAM
CONDENSATE
RETURN
STEAM
SUPPLY
RELIEF AIR
PC
STEAM HUMIDIFIER
RELATIVE HUMIDITY AS MEASURED BY HUMIDISTATS LOCATED IN THE SIX CLEAN ROOMS AND HD STORAGE SHALL MODULATE THE CONTROL VALVE THROUGH THE BMS IN ORDER TO MAINTAIN THE
SPACE RELATIVE HUMIDITY SO IT DOES NOT FALL BELOW 30% RH. ON A CALL FOR
HUMIDIFICATION, HUMIDIFIER VALVE V-1 SHALL MODULATE TO MAINTAIN THE AIR HUMIDITY SET POINT TO 30% (ADJUSTABLE). THE HIGH LIMIT HUMIDITY SENSOR, LOCATED IN THE SUPPLY AIR DUCT 10 FEET AWAY FROM THE HUMIDIFIER SHALL DISABLE THE HUMIDIFIER AND GIVE AN ALARM SIGNAL TO THE ECC, IF THE SUPPLY AIR HUMIDITY EXCEEDS 90% RH (ADJUSTABLE). THE AIRFLOW
SWITCH SHALL PROVE AIRFLOW BEFORE HUMIDITY CONTROLS ARE ACTIVATED.
TSH
RAH
ZC
AFS HHL
PR
E-
F
IL
TE
R
DPS
P-1
FREEZE PROTECTION COOLING COIL PUMP P-1 P-1
SUPPLY FAN # 3
CS
IT
AF
M
S
FT
CONTROL PANEL, TYP.
SC
AHU-1 VARIABLE AIR VOLUME AIR HANDLING UNIT CONTROL DIAGRAM
TU
REHEAT
COIL
AIR
TERMINAL
UNIT
MERV 17 TERMINAL FILTER
FLUSH WITH THE CEILINGS OF
THE CLEAN ROOMS SERVED
MERV 17 TERMINAL FILTER
Freezestat set at 36deg F (adjustable through the BMS).
V-1
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h 6/
/2
:3
9:
P M
BID DOCUMENTS
Office of
Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
MPE Consultants:
Project Director
23 MARCH 2021Revisions: Date:
632-19-106
79 MIDDLEVILLE ROAD, NORTHPORT, NY 11768
RENOVATE PHARMACY SPACES
THINKFORM DESIGN ARCHITECT LLC
38 EAST BROAD STREET
HOPEWELL, NJ 08525
T:855.821.0274 F:609.644.4397 Russell DiNardo, AIA NY 031521-1
MGENGINEERING D.P.C.
116 W 32ND STREET
NEW YORK, NEW YORK 10001
P: 212.643.9055
NORTHPORT VAMC
AUTOMATIC TEMPERATURE
CONTROL DIAGRAM
200-MH8000
SB YK OF35 52
AutoCAD SHX Text
NTS
AutoCAD SHX Text
NTS
| _632-19-106 BID 31-36of52 Mech B |
| 9030MH5000-5003 5002 (1) |
| 9030MH1000-2000-5000-8000 |
| Sheets and Views |
| 9030MH1000-MH1000 |
| 9030MH2000-MH2000 |
| 9030MH5000-5003-5000 |
| 9030MH8000-8000 |
File details come from the government source that posted it. Updated .