Drawings -589A4-18-186- 20 Pages.pdf
PDF 11 MB Posted
- Solicitation number
- 36C25521R0007
About this file
This document outlines a federal contract opportunity for replacement of air handling units at a Veterans Affairs medical center. The scope of work involves replacing two roof-mounted air handlers and associated ductwork. Temporary units will be used to maintain airflow during demolition and installation of the new permanent units, requiring careful phasing and coordination. The project is estimated to cost between $1-2 million and will be awarded as a total small business set-aside to a service-disabled veteran-owned small business. The contract duration is up to 270 calendar days from notice to proceed. Interested offerors should monitor the Federal Business Opportunities website for solicitation details and attend the scheduled site visit. Proposals will be due on or around December 21, 2020 and evaluated using best value tradeoff source selection procedures.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C25521R0007 0004.docx | DOCX document | |
| Amendment 4-Drawings-Correct Fire Life Safety Deficiencies for reference.pdf | ||
| 36C25521R0007 0003.docx | DOCX document | |
| Specification Section 230593.pdf | ||
| 36C25521R0007 0002_1.docx | DOCX document | |
| VA-AC 3_4 - Mechanical set.pdf | ||
| 36C25521R0007 0002.docx | DOCX document | |
| VA Colubia AC 3-4 Grate Infill Detail.pdf | ||
| 589A4-18-186 Specs 1 35 26 Safety Requirements Revised.pdf | ||
| 589A4-18-186 Specs 23 09 23 Direct Digital Controls Revised.pdf | ||
| Attendance Sign-In Site Visit Walk Thru.pdf | ||
| 36C25521R0007 0001.docx | DOCX document | |
| PREBID MEETING ATTENDENCE LIST.pdf | ||
| 36C25521R0007_1.docx | DOCX document | |
| Specifications-589A4-18-186-437 pages.pdf |
Show all 15
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
BUILDING 1
HOSPITAL DRIVE
M O
N K
D R
IV
E
STADIUM BLVD (HWY 740)
T
IG
E R
A V
E N
U E
SERVICE ROAD
Project Area Building 1 Mechanical Penthouse
N
Campus Site Map
NTS
Office of Facilities
Management
Project Number
Building Number
Drawing Number
DrawnCheckedDate
Location
Project TitleDrawing Title
ARCHITECT/ENGINEERS:
VA Project #
CONSULTANTS:
Revisions: Date:
VA FORM 08-6231 OCT 1978
on e ei gh th in ch o ne fo ot qu ar te r th re ig ht s on e h al f i nc h f oo t th qu ar te rs
6" on e i nc h f oo t
6" a nd h al f
6" th re e i nc he s f oo t
6" 6"
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
VeteransA sffair Depa frtmento
Department of Veterans Affairs Medical Center
4/15/2020 9:54:19 AM
FCA Replace Air Handlers (AC-S3, AC-S4)
800 Hospital Drive Columbia, MO 65201
Harry S Truman Memorial Veterans' Hospital
589A4-18-186
589A4-18-186
04/14/2020 BD ZF
G0.0 800 Hospital Drive Columbia, MO 65201
Bid Set Drawings
FCA Replace Air Handlers
(AC-S3, AC-S4)
Cover
INDEX OF DRAWINGS
General
Architectural
Director Assistant Director
Chief of Staff
Infection Control Practitioner
Chief of Facilities ManagementAssociate Director
Signature Date Signature Date Signature Date
Signature DateSignature DateSignature Date
SIGN-OFF LIST
G0.0 Cover G0.1 General Information
A1.0 Upper Level Penthouse Floor Plans A1.1 Lower Level Penthouse Floor Plans A1.2 Exterior Elevations and Details
Mechanical
M0.1 Mechanical Notes, Symbols and Abbreviations M0.2 Mechanical Schedules M0.3 Mechanical Details M0.4 Mechanical Points List, Flow and Control Diagrams M1.1 Mechanical Penthouse AC-S4 Ductwork Plans M1.2 Mechanical Penthouse AC-S4 Piping Plans M2.1 Mechanical Penthouse AC-S3 Ductwork Plans M2.2 Mechanical Penthouse AC-S3 Piping Plans
Electrical
E0.1 Electrical Notes, Symbols, Abbreviations and Schedules E1.1 Electrical Lower Penthouse Plans E1.2 Electrical Upper Penthouse Plans
Structural
S0.1 Structural General Notes S2.1 Structural Framing Plans and Details
Lower Upper AC-S3 & A-20 Plans
AC-S4 Plans
Fire Sprinkler
FX0.1
FX1.1
Fire Sprinkler Schedules and Diagrams Fire Sprinkler Lower & Upper Penthouse Plans
06/02/2020
KNEE BRACE
LAVATORY
LINEAR FEET
LINTEL
MASONRY
MATERIAL
MAXIMUM
MEDIUM DENSITY FIBERBOARD
MECHANICAL
MANUFACTURER
MANHOLE
MINIMUM
MIRROR
MISCELLANEOUS
MASONRY OPENING
MOUNTED
METAL
NOT IN CONTRACT
NOMINAL
NOT TO SCALE
ON CENTER
OUTSIDE FACE
OPENING
OPPOSITE
PAINT
PARTICLE BOARD
PLASTIC LAMINATE
PLUMBING
PLASTIC
PAIR
PREFINISHED
PROPERTY
PRESSURE TREATED
PAINTED
PARTITION
PLYWOOD
RISER OR RADIUS
RUBBER BASE
ROOF DRAIN
REFERENCE
REINFORCED
REQUIRED
REVISION
RAILING
ROOM
ROUGH OPENING
SOLID CORE
SCHEDULE
SECTION
SHEATHING
SIMILAR
SINK
SHEET METAL
SOFFIT
SPECIFICATIONS
SQUARE
SOLID SURFACING MATERIAL
STAINLESS STEEL
STANDARD
STEEL
STRUCTURE
SUSPENDED
SLAT WALL
SYSTEM
TREAD
TOP OF CONCRETE
TELEPHONE
TEMPERED GLASS LITE
TOP OF JOIST
TOP OF STEEL
TOP OF WALL
TYPICAL
UNFINISHED
UNLESS OTHERWISE NOTED
URINAL
VINYL BASE
VINYL COMPOSITION TILE
VERTICAL
VERIFY IN FIELD
WIDTH
WITH
WATER CLOSET
WOOD
WINDOW
WIDE FLANGE
WITHOUT
WATERPROOFING
YARD
KB
LAV
LF
LNTL
MAS
MAT
MAX
MDF
MECH
MFR
MH
MIN
MIR
MISC
MO
MTD
MTL
NIC
NOM
NTS
OC
OF
OPNG
OPP
P
PBD
PLAM, PL
PLBG
PLS
PR
PREF
PROP
PT
PTD
PTN
PWD
R
RB
RD
REF
REINF
REQD
REV
RLG
RM
RO
SC
SCH
SECT
SHTH
SIM
SK
SM
SOF
SPEC
SQ
SSM
SST
STD
STL
STR
SUSP
SW
SYS
T
TC
TEL
TGL
TJ
TS
TW
TYP
UF
UON
UR
VB
VCT
VERT
VIF
W W/
WCL
WD
WDW
WF
WO
WPG
YD
ACT
ADJ
ADJC
AFF
ALT
ALUM
ARCH
AVG
BD
BL
BLDG
BLKG
BOD
BR
BTWN
C
CAB
CB
CC
CG
CJ
CL
CLG
CMU
COL
CONC
CONST
CONT
CP
CRT
CS
CSJ
CST
CT
DEMO
DIA
DIM
DN
DR
DS
DTL
DWG
EA
EJ
ELECT
ELEV
EP
EQ
EQUIP
EWC
EXT
EXTG
FAB
FCU
FD
FDN
FEC
FF
FG
FHC
FIN
FLR
FLG
FLT
FPG
FR
FRP
FSK
FT
FTG
FTWD
FWP
G
GA
GL
GR
GT
GWB
HC
HD
HDBD
HDW
HDWD
HM
HOR
HR
HT
HWH
IF
INSUL
JT
REFER TO THE MATERIAL LEGEND FOR ABBREVIATIONS RELATED TO FINISHES NOT HERE LISTED
ABBREVIATIONS LIST
ACOUSTIC CEILING TILE
ADJUSTABLE
ADJACENT
ABOVE FINISHED FLOOR
ALTERNATE
ALUMINUM
ARCHITECTURAL
AVERAGE
BOARD
BLINDS
BUILDING
BLOCKING
BOTTOM OF DECK
BRICK
BETWEEN
CARPET
CABINET
CATCH BASIN
CONCRETE, COLORED
CORNER GUARD
CONTROL JOINT
CENTERLINE
CEILING
CONCRETE MASONRY UNIT
COLUMN
CONCRETE
CONSTRUCTION
CONTINUOUS
COMMUNICATIONS PANEL
CATHODE RAY TUBE
CONSTRUCTION JOINT
CONCRETE, SEALED
CONCRETE, STAINED
CERAMIC TILE
DEMOLITION
DIAMETER
DIMENSION
DOWN
DOOR
DOWNSPOUT
DETAIL
DRAWING
EACH
EXPANSION JOINT
ELECTRICAL
ELEVATION
ELECTRICAL PANEL
EQUAL
EQUIPMENT
ELECTRIC WATER COOLER
EXTERIOR
EXISTING
FABRICATED
FAN COIL UNIT
FLOOR DRAIN
FOUNDATION
FIRE EXTINGUISHER CABINET
FINISH FLOOR
FINISH GRADE
FIRE HOSE CABINET
FINISH
FLOOR
FLASHING
FLOOR TILE
FIREPROOFING
FIRE RATING
FIBERGLASS REINFORCED PANEL
FLOOR SINK
FEET
FOOTING
FIRE TREATED WOOD
FABRIC WRAPPED PANEL
GRANITE
GAUGE
GLASS
GRADE
GROUT
GYPSUM WALLBOARD
HOLLOW CORE
HEAD
HARDBOARD
HARDWARE
HARDWOOD
HOLLOW METAL
HORIZONTAL
HANDRAIL
HEIGHT
HOT WATER HEATER
INSIDE FACE
INSULATION
JOINT
X
XX
LEGEND - SYMBOLSLEGEND - SYMBOLS
XX
XX
XXX
XX
XX
T.O.
X'-X" A.F.F.
T.O.
X'-X" A.F.F.
X
YY.Y
X
X
X
XYY.Y
X
YY.Y
X
YY.Y
X
X
X
XYY.Y
X
YY.Y
XX
CONTROL POINT
KEYED NOTE
CENTER LINE MARK
REVISION NUMBER
ELEVATION DATUM
NEW COLUMN LINE
EXTERIOR ELEVATION MARK
X = ELEVATION NUMBER
Y = SHEET NUMBER
WINDOW NUMBER
PARTITION TYPE DETAIL MARK
X = DETAIL NUMBER
Y = SHEET NUMBER
NORTH ARROW
SECTION MARK
X = SECTION NUMBER
Y = SHEET NUMBER
EXISTING
PARTITION INTERIOR ELEVATION MARK
X = ELEVATION NUMBER
Y = SHEET NUMBER
CONTROL POINT
KEYED NOTE
CENTER LINE MARK
REVISION NUMBER
ELEVATION DATUM
EXISTING COLUMN LINE
EXTERIOR ELEVATION MARK
X = ELEVATION NUMBER
Y = SHEET NUMBER
NEW
PARTITION
NEW DOOR
W/ DOOR
NUMBER
ROOM NAME &
NUMBER
WINDOW NUMBER
PARTITION TYPE
DEMOLISHED
DOOR
EXISTING
DOOR
DETAIL MARK
X = DETAIL NUMBER
Y = SHEET NUMBER
NORTH ARROW
SECTION MARK
X = SECTION NUMBER
Y = SHEET NUMBER
DEMOLISHED
PARTITION
INTERIOR ELEVATION MARK
X = ELEVATION NUMBER
Y = SHEET NUMBER
XXEQUIPMENT TAG FLOOR MATERIAL
TRANSITION
X
YY.Y
xxxxxx
Drawing Title Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
Office of Facilities
Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231, OCT 1978
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
VeteransA sffair Depa frtmento
4/15/2020 9:54:19 AM
General Information
G0.1 800 Hospital Drive Columbia, MO 65201
04/14/2020
Bid Set Drawings
BD ZF
589A4-18-186FCA Replace Air Handlers
(AC-S3, AC-S4)
STEEL
CONCRETE
ALUMINUM
BRICK
WOOD (FINISHED)
COMPACTED GRAN. FILL
BATT INSULATION
GYPSUM WALL BOARD
(SMALL SCALE)
CONTINUOUS
WOOD BLOCKING
HATCH INDICATIONS SHOWN AS GUIDE ONLY; HATCHING SCALES MAY NEED TO BE MODIFIED DEPENDING UPON SCALE USED
MATERIALS INDICATION
NON-CONTINUOUS
WOOD BLOCKING
EARTH
GYPSUM WALL BOARD
(LARGE SCALE)
PLYWOOD
RIGID INSULATION
SAND
PRECAST
ASPHALT
GENERAL NOTES
PHASE ALL DEMOLITION & CONSTRUCTION TO BE SEQUENCED & COORDINATED TO ENSURE THAT
THE BUILDING OWNER'S OPERATIONS ARE CONTINUOUSLY MAINTAINED.
2. THESE PLANS REFLECT INFORMATION GATHERED FROM EXISTING CONDITIONS DRAWINGS &
ARCHITECT'S FIELD VERIFICATION. CONTRACTOR SHALL VERIFY ACCURACY OF INFORMATION
PRIOR TO COMMENCEMENT OF ANY DEMOLITION AND/OR CONSTRUCTION ACTIVITIES AND
REPORT ANY DISCREPANCIES TO COR.
3. ITEMS TO BE DEMOLISHED, REMOVED, OR RELOCATED ARE SHOWN DASHED. EXISTING ITEMS
TO REMAIN SHALL BE PROTECTED DURING CONSTRUCTION BY CONTRACTOR. PATCH & REPAIR
ALL RESULTING SURFACES TO REMAIN.
4.
1.
COORDINATE ALL WORK BETWEEN TRADES AS REQUIRED TO ENSURE TIMELY & PROPER
INSTALLATION OF ALL BUILDING SYSTEMS.
5.
6.
ACCESS TO EMPLOYEE ENTRY AND EXIT DOORS MUST BE MAINTAINED THROUGHOUT
CONSTRUCTION. PROVIDE ALL VA REQUIRED BARRIERS AND SIGNAGE AT THE LIMITS OF THE
CONSTRUCTION SITE.
7.
PROVIDE FULLY SEALED DUST PARTITIONS AS REQUIRED AT ALL LOCATIONS WHERE
CONSTRUCTION MEETS THE EXISTING BUILDING IN ORDER TO MAINTAIN A CLEAN DUST-FREE
ENVIRONMENT INSIDE THE BUILDING.
8.
ALL GYPSUM BOARD USED IN THIS PROJECT SHALL BE TYPE "X"
CONTRACTORS SHALL VISIT THE SITE TO FAMILIARIZE THEMSELVES WITH THE EXISTING
CONDITIONS AND INCLUDE THE WORK NECESSARY TO COMPLY WITH THE SCOPE OF THE WORK.
ADDITIONAL COMPENSATION WILL NOT BE CONSIDERED FOR EXTRA WORK WHEN SUCH WORK
COULD HAVE BEEN REASONABLY ASCERTAINED FROM THE PRE BID SITE VISIT REVIEW OF THE
EXISTING CONDITIONS AND THE WORK SCOPE DESCRIBED IN THE DOCUMENTS.
10.
COORDINATION OF ALL WORK AS DESCRIBED ON THE DOCUMENTS IS THE GENERAL
CONTRACTOR'S RESPONSIBILITY.
11.
PERFORM WORK IN ACCORDANCE WITH ALL APPLICABLE CODES, REGULATIONS, AND
ORDINANCES HAVING JURISDICTION.
12.
IMMEDIATELY REPORT DISCREPANCIES BETWEEN CONTRACT DOCUMENTS AND FIELD
CONDITIONS, CONFIRM THE WORK IS BUILDABLE AS SHOWN.
ALL DIMENSIONS ARE FROM COLUMN CENTER LINE TO FACE OF PARTITION U.O.N. UNDER
NO CIRCUMSTANCES SHALL ANY MEASUREMENT BE SCALED FROM THE DRAWINGS. ANY
MEASUREMENT NOT GIVEN AN ACTUAL NUMBER DIMENSION SHOULD BE BROUGHT TO THE
ATTENTION OF THE COR/ARCHITECT BEFORE PROCEEDING.
13. ALL WOOD USED IN THIS PROJECT SHALL BE FIRE-RETARDANT TREATED
14. ALL NEW PARTITIONS, UNLESS OTHERWISE SHOWN, SHALL BE 20 GA. MTL STUDS
15. COORDINATE & PROVIDE BLOCKING AS REQUIRED FOR MILLWORK & ITEMS ATTACHED OR
MOUNTED TO WALLS & CEILINGS
16. ALL INSULATING MATERIALS WITHIN WALLS & IN UNCONCEALED SPACES SHALL HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 25 AND A SMOKE-DEVELOPED INDEX OF NOT MORE THAN 450
17. ALL MATERIAL EXPOSED WITHIN PLENUMS ARE REQUIRED TO BE NON-COMBUSTIBLE OR SHALL
HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 25 AND A SMOKE DEVELOPED INDEX OF NOT
MORE THAN 50 AS DETERMINED IN ACCORDANCE WITH ASTM E-84.
18. PROJECT LIMIT LINES INDICATE THE AREA OF A MAJORITY OF THE PROJECT WORK. BUT SOME
WORK WILL BE REQUIRED OUTSIDE OF THE PROJECT LIMITS. REFER TO DRAWINGS AND
SPECIFICATIONS FOR INFORMATION.
THE CONTRACTING OFFICER’S REPRESENTATIVE (COR) WILL PERFORM FIELD VERIFICATION AS
REQUIRED FOR THE DURATION OF THE PROJECT TO MONITOR PROJECT PROGRESS.
UTILITY SHUT DOWNS WILL BE COORDINATED BY IPT (INTEGRATED PROJECT TEAM); INCLUDING: COR, VA FACILITY OPERATIONS, AND GENERAL CONTRACTOR.
ANY INTEGRATED PROJECT TEAM MEMBER (IPT), INCLUDING BUT NOT LIMITED TO: CONTRACTORS / SUB-CONTRACTORS, ARCHITECTS AND/OR ENGINEERS WHO ENTER THE PROJECT BOUNDARY SHALL WEAR ALL PROPER PERSONAL PROTECTIVE EQUIPMENT (PPE’S: CERTIFIED BY OSHA) AT ALL TIMES.
SUCH PPE’S INCLUDE: HARD HATS, SAFETY GLASSES, ETC.
IF THE PROJECT AREA AND AREAS AFFECTED BY THE PROJECT INCLUDE EXISTING EQUIPMENT, SURFACES, FINISHES, MATERIALS, ETC., NOT TO BE REMOVED, THE CONTRACTOR MUST PROTECT THIS EQUIPMENT FROM DUST, DEBRIS, DAMAGE, ETC. THE CONTRACTOR MUST ALSO CLEAN THESE ITEMS/SURFACES TO THE ORIGINAL CONDITION FOUND AT THE START OF THE PROJECT PRIOR TO FINAL INSPECTION. CONTRACTOR IS RESPONSIBLE TO REPAIR/REPLACE ANY DAMAGED EQUIPMENT, ITEMS, ETC.
PATCH ALL FINISHES WHERE DISTURBED BY THE WORK AND WHERE UNFINISHED SURFACES HAVE
BEEN EXPOSED BY DEMOLITION. PATCHING MUST MATCH ADJACENT MATERIALS, COLORS, AND
FINISHES. WALL SURFACES THAT ARE PATCHED SHALL HAVE THE FINISHES (PAINT, VINYL WALL
COVERING, ETC.) REPLACED FROM CORNER TO CORNER AND FLOOR TO CEILING.
UNLESS OTHERWISE INDICATED, FINISH ALL NEW FRAMES AND PARTITIONS TO MATCH
SURROUNDING. NEW HOLLOW METAL DOORS SHALL BE PAINTED SAME COLOR AS FRAMES.
EXISTING PARTITIONS RECEIVING NEW DOOR FRAMES THAT HAVE VINYL WALL COVERING (VWC)
SHALL HAVE THE VWC COMPLETELY REMOVED AND REPLACED WITH NEW VWC OF MATCHING
TEXTURE AND COLOR.
CORRIDOR WALLS AND PLUMBING PARTITIONS SHALL BE CONSIDERED 1 HOUR FIRE / SMOKE RATED WALLS AND NEW OR EXISTING PENETRATIONS MUST BE SEALED ACCORDINGLY WITH UL APPROVED FIRE STOPPING MATERIAL THE SAME DAY THE PENETRATION IS MADE OR DISCOVERED. ALL FLOOR SLABS, VERTICAL SHAFTS AND STAIRWELLS SHALL BE CONSIDERED 2 HOUR FIRE / SMOKE RATED
SEPARATIONS AND SHALL BE SEALED ACCORDINGLY IN THE MANNER LISTED HEREIN.
PENETRATIONS THROUGH THE EXTERIOR WALLS SHALL BE SEALED WATERTIGHT.
IF EXISTING WALLS ARE TO BE USED AS DUST OR SMOKE BARRIERS SEPARATING THE
CONSTRUCTION AREA FROM THE MEDICAL CENTER, THE CONTRACTOR IS RESPONSIBLE FOR
SEALING ALL EXISTING PENETRATIONS IN THIS WALL, EXTENDING WALL TO CEILING SLAB AND ANY
OTHER WORK TO ENSURE THE WALL MEETS THE REQUIREMENTS IN THE GENERAL REQUIREMENTS
SPECIFICATIONS FOR CONSTRUCTION BARRIERS.
WHENEVER EXISTING EQUIPMENT, PIPING, DUCTS, ETC., ARE REQUIRED TO BE REMOVED, SUCH
REMOVAL SHALL INCLUDE ALL ANCHORS, HANGERS, FOUNDATIONS, ETC., UNLESS NOTED
OTHERWISE. AFTER REMOVAL; FLOORS, WALLS, AND CEILINGS SHALL BE FINISHED TO MATCH
ADJOINING SURFACES.
UTILITY WORK THAT WILL REQUIRE A SHUTDOWN OF EXISTING SERVICE WILL BE DONE AT TIMES
OTHER THAN NORMAL WORKING HOURS AT NO ADDITIONAL COST TO THE GOVERNMENT. WORK
MUST BE SCHEDULED WITH THE COR 72 HOURS IN ADVANCE OF SHUTDOWN.
ALL NEW VERTICAL AND HORIZONTAL DUCTS, PIPES, CONDUITS, ETC., IN FINISHED ROOMS OR AREAS
THROUGHOUT BUILDING, NOT ENCASED IN MASONRY OR CONCRETE CONSTRUCTION, SHALL BE
ENCLOSED IN METAL STUDS AND DRYWALL CHASE WALLS AS DETAILED IN THE DRAWINGS AND
FINISHED TO MATCH THE ROOM FINISH.
WORK THAT MUST OCCUR IN OCCUPIED AREAS OF THE MEDICAL CENTER OR DISRUPT A MEDICAL
CENTER FUNCTION, WILL BE DONE AT TIMES OTHER THAN NORMAL WORKING HOURS AT NO
ADDITIONAL COST TO THE GOVERNMENT. WORK MUST BE SCHEDULED WITH THE VA COR 72 HOURS
IN ADVANCE OF WORK TO TAKE PLACE
CONTRACTOR SHALL NOT INSTALL CONDUIT, PIPING, LIGHTING, OR OTHER OBSTRUCTIONS UNDER
ADJACENT HVAC EQUIPMENT THAT WILL ELIMINATE OR OBSTRUCT ACCESS TO COILS, MOTORS,
VALVES, SWITCHES, PANELS, ETC.
BEFORE THE CONTRACTOR BEGINS WORK, CONTRACTOR SHALL RECORD ANY EXISTING
SYSTEM INFORMATION SUCH AS TEMPERATURE, FLOW RATE, PRESSURE, CURRENT, VOLTAGE,
OR ANY OTHER INFORMATION NECESSARY FOR HIM TO RETURN THE AFFECTED SYSTEM TO
ORIGINAL OPERATING CONDITION. UNLESS NOTED OTHERWISE, IT IS ASSUMED THAT ALL
SYSTEMS (HVAC, ELECTRICAL, PLUMBING, ETC.) ARE WORKING PROPERLY IN EVERY MANNER
AT THE BEGINNING OF THE PROJECT. THE CONTRACTOR'S RECORDED MEASUREMENTS MUST
BE SUBMITTED TO THE COR FOR REVIEW AND ACCEPTANCE BEFORE ANY DEMOLITION OR
OTHER RELATED WORK CAN PROCEED.
THE CONTRACTOR WILL BE RESPONSIBLE FOR MAINTAINING ALL EXISTING ACCESS DOORS TO
CONSTRUCTION AREAS, EXISTING MECHANICAL AND ELECTRICAL AREAS, ASSIGNED STORAGE
AREAS, EQUIPMENT ACCESS AREAS, ETC. DOORS MUST BE RESTORED TO THE CONDITION
ENCOUNTERED AT BEGINNING OF PROJECT. THIS INCLUDES DOOR REPLACEMENT, HARDWARE
REPLACEMENT, HARDWARE REPAIR, DOOR REPAIR, ETC.
CONTRACTOR MUST PROVIDE HIS OWN EQUIPMENT FOR MOVING OF MATERIALS, EQUIPMENT
AND TRASH. THIS INCLUDES CARTS FOR REMOVAL OF DEMOLITION MATERIALS, PALLET JACKS
FOR EQUIPMENT MOVING, TWO OR FOUR WHEEL CARTS FOR EQUIPMENT TRANSFER, ETC.
CONTRACTOR MAY NOT BORROW VA OWNED EQUIPMENT FOR THIS PURPOSE.
SEVERE NOISE PRODUCING WORK WILL NOT BE ALLOWED DURING NORMAL WORKING HOURS
AND MUST BE SCHEDULED WITH THE COR FOR OTHER TIMES 72 HOURS IN ADVANCE OF WORK
TAKING PLACE. THIS INCLUDES JACK-HAMMERING CONCRETE, SAW-CUTTING CONCRETE,
REPETITIVE HAMMER DRILLING OF CONCRETE, ETC.
THE VA DOES NOT PROVIDE PHONES FOR THE CONTRACTOR’S USE. IT IS THE CONTRACTOR’S
RESPONSIBILITY TO COVER THE COSTS OF A CELLUALR PHONE TO BE HELD BY THE
SUPERINTENDENT THROUGHOUT THE PROJECT. PROVIDE DIRECT PHONE NUMBER TO COR
BEFORE THE START OF THE PROJECT.
ALL ELECTRICAL CIRCUITRY TO BE CONCEALED UNLESS OTHERWISE SPECIFIED. CIRCUITING
FOR ELECTRIC DOOR HOLD OPENS IN MASONRY WALLS SHALL BE SURFACE RACEWAY.
DRAWINGS ARE DIAGRAMMATIC AND SHOW ONLY THE GENERAL ARRANGEMENT OF EACH
SYSTEM. BECAUSE OF SMALL SCALE OF DRAWINGS IT IS NOT POSSIBLE TO SHOW OR
INDICATE ALL BRANCHES, OFFSETS, FITTINGS, BOXES, AND ACCESSORIES WHICH MAY BE
REQUIRED. CONTRACTOR MUST CAREFULLY INVESTIGATE STRUCTURAL AND FINISH
CONDITIONS AFFECTING ALL WORK, FURNISHING SUCH FITTINGS, TRAPS, VALVES, BOXES,
ACCESSORIES, ETC., AS MAY BE REQUIRED.
LOCATIONS OF NEW EQUIPMENT, PIPING, AND ASSOCIATED ITEMS SHOWN ON THE DRAWINGS
ARE SCHEMATIC ONLY. THE CONTRACTOR SHALL FIELD VERIFY EXACT LOCATION AND
ELEVATION FOR ALL WORK, INCLUDING CONNECTIONS TO EXISTING WORK. ALL OFFSETS,
FITTINGS, TRANSITIONS, EXTENSIONS, ETC., REQUIRED FOR A COMPLETE AND FUNCTIONAL
SYSTEM SHALL BE PROVIDED AT NO ADDITIONAL COST.
ALL EXISTING DUCTWORK, ELECTRICAL OR MECHANICAL PIPING, CABLE TRAYS, ETC., IS NOT
NECESSARILY SHOWN ON THE DRAWINGS. PRIOR TO ANY DEMOLITION AND CONSTRUCTION
WORK, THE CONTRACTOR SHALL FIELD VERIFY THE EXACT LOCATION OF ALL EXISTING
EQUIPMENT, DUCTWORK, PIPING, ETC., AND REPORT ANY DISCREPANCIES TO THE COR.
IF THERE IS ANY WORK TO BE DONE ON EXISTING ROOFS, SUCH AS ROOF PENETRATIONS OR
STANDS, OR ANYTHING THAT DAMAGES THE INTEGRITY OF THE ROOF, THIS WORK MUST BE
DONE BY A CONTRACTOR LICENSED BY THE ROOFING MEMBRANE MANUFACTURER. HE/SHE
MUST BE APPROVED BY THE MEMBRANE MANUFACTURER SO AS TO NOT VOID OR INTERRUPT
EXISTING SINGLE PLY MEMBRANE ROOF WARRANTIES.
IF ASBESTOS INSULATION IS REMOVED ON THIS PROJECT ALL PIPING AND OTHER MECHANICAL
ITEMS THAT HAD THE ASBESTOS INSULATION REMOVED MUST BE RE-INSULATED WITH
MATERIALS ACCORDING TO THE SPECIFICATIONS.
WHEN WORKING IN OCCUPIED AREAS OF THE MEDICAL CENTER THE CONTRACTOR CANNOT
LEAVE TOOLS, EQUIPMENT, LADDERS, ETC., UNATTENDED WHERE THEY ARE ACCESSIBLE TO
PATIENTS, STAFF, VISITORS, ETC. CEILING TILES AND CEILING ACCESS PANELS MUST ALSO BE
REPLACED WHEN UNATTENDED, FOR SAFETY REASONS.
WATER OR LIQUIDS MUST NOT BE ALLOWED TO COME INTO CONTACT WITH NEW OR EXISTING
DRYWALL FROM CONSTRUCTION RELATED ACTIVITIES. REMOVE AND REPLACE ANY DRYWALL
THAT HAS COME INTO CONTACT WITH WATER OR OTHER LIQUIDS.
LIVE ELECTRICAL CIRCUITS ARE BURIED WITHIN THE CONCRETE FLOOR SLABS AND THERE IS
NO RECORD OF THE EXACT LOCATIONS. THE CONTRACTOR SHALL X-RAY THE FLOOR
WHEREVER THE CONTRACTOR PLANS ON DRILLING THROUGH THE CONCRETE FLOOR SLABS.
IT WILL BE THE CONTRACTOR'S RESPONSIBILITY TO IMMEDIATELY REPAIR ANY CIRCUIT THAT
HAS BEEN CUT OR DAMAGED.
WHEN AN EXIT IS CLOSED BECAUSE OF THIS PROJECT THE CONTRACTOR MUST INSTALL
BARRICADES AND SIGNAGE AT THE EXIT DOOR. THE CONTRACTOR MUST ALSO COVER OR
REMOVE THE LIGHTED EXIT SIGN.
CONTRACTOR SHALL PROVIDE BOXES, CONDUIT, WIRE, AND RECONNECTIONS AS REQUIRED TO
RECONNECT ANY AND ALL EXISTING LIGHT FIXTURES, RECEPTACLES, OR DEVICES REMAINING
IN USE. REMOVAL OF ANY ELECTRICAL EQUIPMENT SHALL NOT AFFECT THE OPERATION OF
EQUIPMENT REMAINING IN USE.
CONTINUITY OF ALL SERVICES TO AND FROM THE FACILITIES IN THE EXISTING BUILDING SHALL
BE MAINTAINED WITHOUT INTERRUPTION, EXCEPT FOR SUCH PERIODS OF TIME WHICH THE
V.A. MAY DESIGNATE. IF TEMPORARY CONNECTIONS, ETC. ARE NECESSARY TO ASSURE THE
CONTINUITY OF SERVICE, THEY SHALL BE FURNISHED WITHOUT ADDITIONAL CHARGE TO THE
V.A. AND SHALL BE REMOVED WHEN NO LONGER NECESSARY.
ALL EXISTING CONDUIT AND WIRING MADE ABANDONED BY THIS PROJECT OR FOUND TO BE
ABANDONED DURING DEMOLITION SHALL BE REMOVED BACK TO PANEL, BOARD, OR SWITCH.
COORDINATE THE PROVISION AND INSTALLATION OF ALL CONTROL WIRING FOR MECHANICAL
EQUIPMENT WITH THE GENERAL CONTRACTOR AND MECHANICAL CONTRACTOR.
FOR SAFETY PURPOSES THE CONTRACTOR WILL NOT WORK ON ANY ELECTRICAL EQUIPMENT
HOT. ALL SHUTDOWNS WILL BE SCHEDULED IN ADVANCE WITH THE COR.
CONTRACTOR SHALL BE RESPONSIBLE FOR ALL OPENINGS REQUIRED IN WALLS. ALL
OPENINGS SHALL BE REPAIRED TO MATCH EXISTING BY A QUALIFIED CONTRACTOR AT THE
EXPENSE OF THIS CONTRACTOR. ALL CONDUITS IN WALLS SHALL BE GROUTED OR SEALED
INTO OPENINGS.
CONTRACTOR SHALL COORDINATE ‘IN-WALL’ & ‘OVERHEAD CEILING’ INSPECTIONS WITH COR
PRIOR TO THE INSTALLATION OF FINISHES. IN-WALL INSPECTIONS REQUIRE 24 HOUR
NOTIFICATION. OVERHEAD CEILING INSPECTIONS REQUIRE 48 HOUR NOTIFICATION.
CONTRACTOR TO SUPPLY A CART WITH A LOG SHEET AND FULL SET OF HARD COPY DRAWINGS
FOR ALL INSPECTIONS. LOG SHEET SHALL BE ITEMIZED BY TYPE OF INSPECTION AND BY
ROOM. NO SUCH FINISHES SHALL BE INSTALLED WITHOUT INSPECTION APPROVAL FROM COR
19. CONSTRUCTION MATERIALS AND INSTALLATION METHODS PROVIDED AND PERFORMED BY ALL CONTRACTORS SHALL BE IN COMPLIANCE WITH VAMC FACILITY OPERATIONS, NFPA, ICRA, ILSM, VA SPECIFICATIONS, AND AS FURTHER DESCRIBED IN THIS SCOPE.
20. PAINT ALL EXPOSED NEW AND EXISTING PIPING, CONDUIT, WIRE MOLD, ELECTRICAL PANELS, ACCESS PANELS, ETC., TO MATCH WALL FINISH UNLESS OTHERWISE NOTED.
22.
23.
24.
21.
25.
26.
27.
28.
29.
30.
31.
32.
33.
34.
35.
36.
37.
38.
39.
40.
41.
42.
43.
44.
45.
47.
48.
46.
49.
50.
51.
52.
53.
54.
55.
06/02/2020
STRUCTURAL STEEL:
1. STEEL SHALL CONFORM TO THE FOLLOWING GRADES:
ALL WF (U.N.O.): A992 GRADE 50 (FY=50)
ALL ANGLE, BASE PLATES, CONN. PLATES (U.N.O.): A36 (FY=36)
STRUCTURAL PIPE: A53 (FY=35)
STRUCTURAL TUBE: A500 GRADE B (FY=46)
HEADED STUDS AWS D1.1, TYPE B
THREADED ROD A36
ANCHOR ROD F1554,GR36 OR 55 PER DETAILS
BOLTS A325 / F1852
ELECTRODES MATCHING STRENGTH, 70KS: MIN.
2. ALL STRUCTURAL STEEL SHALL BE DETAILED, FABRICATED AND ERECTED IN
ACCORDANCE WITH THE LATEST A.I.S.C. CODE OF STANDARD PRACTICE, EXCEPT AS
MODIFIED IN THESE NOTES AND THE PROJECT SPECIFICATIONS.
3. CONNECTIONS MAY BE BOLTED OR WELDED. THE FABRICATOR IS RESPONSIBLE FOR
THE DESIGN, OF CONNECTIONS NOT DESIGNED ON THE DRAWINGS. GENERALLY,
CONNECTIONS SHOWN ON THE STRUCTURAL DRAWINGS ARE SCHEMATIC AND ARE
ONLY INTENDED TO SHOW THE RELATIONSHIP OF MEMBERS CONNECTED. ANY
CONNECTION THAT IS NOT SHOWN OR IS NOT COMPLETELY DETAILED ON THE STRUCTURAL
DRAWINGS SHALL BE DESIGNED BY AN ENGINEER, REGISTERED IN THE STATE OF
MISSOURI,
RETAINED BY THE FABRICATOR. COMPLETELY DETAILED MEANS THE FOLLOWING
INFORMATION IS SHOWN ON THE DETAIL:
A. ALL PLATE DIMENSIONS AND GRADES.
B. ALL WELD SIZES, LENGTHS, PITCHES, AND RETURNS.
C. ALL HOLE SIZES AND SPACINGS.
D. NUMBER AND TYPES OF BOLTS: WHERE BOLTS ARE SHOWN BUT NO NUMBER
IS GIVEN, THE CONNECTION HAS NOT BEEN COMPLETELY DETAILED.
E. WHERE PARTIAL INFORMATION IS GIVEN, IT SHALL BE THE MINIMUM
REQUIREMENT FOR THE CONNECTION.
DESIGN CALCULATIONS FOR TYPICAL BEAM CONNECTIONS AND ALL PRIMARY BRACING AND
HANGER CONNECTIONS SHALL BE SUBMITTED TO THE ENGINEER FOR REVIEW AND
APPROVAL
PRIOR TO FABRICATION.
4. CONNECTION DESIGN FORCES:
A. BEAMS, GREATER OF:
1. 55% OF TOTAL ALLOWABLE UNIFORM LOAD CAPACITY FROM A.I.S.C 9TH
EDITION TABLES FOR ALLOWABLE LOADS ON BEAMS, Wc/L
2. REACTIONS SHOWN ON DRAWINGS.
3. 10 KIPS.
B. CONNECTION FORCE NOTATION:
P = AXIAL FORCE IN KIPS: (+) TENSION, (-) COMPRESSION
V OR [ ] = SHEAR IN KIPS
M = MOMENT IN FOOT KIPS
T = TORSION IN FOOT KIPs
1. LOADS SHOWN INCLUDE COMPENSATION FOR CODE PERMITTED
STRESS INCREASES AND LOAD REDUCTIONS FOR CONNECTION DESIGN.
5. THE MINIMUM PLATE THICKNESS SHALL BE 3/8"
6. BOLTED CONNECTIONS:
A. MINIMUM BOLT DIAMETER = 3/4"
B. ALL OTHER BOLTED CONNECTIONS SHALL BE BEARING TYPE USING A325N OR
A490N BOLTS. OVERSIZED HOLES AND LONG-SLOTTED HOLES ARE NOT
ALLOWED UNLESS SHOWN ON THE DRAWINGS.
C. A307 BOLTS MAY BE USED WHERE INDICATED ON THE DRAWINGS.
D. PROTRUDING BOLT HEADS, SHAFTS OR NUTS SHALL NOT EXTEND INTO NOR
PROHIBIT THE APPLICATION OF ARCHITECTURAL FINISHES AND THEY SHALL
NOT EXTEND INTO NOR PROHIBIT THE PLACEMENT OF STEEL DECKING TO THE
CORRECT LINE AND ELEVATION.
E. SHOP DRAWINGS SHALL INDICATE THE TYPE OF BOLT USED IN EACH
CONNECTION AND THE ALLOWABLE VALUES USED FOR THE VARIOUS BOLT
TYPES.
7. WELDED CONNECTIONS:
A. WELDS ARE CONTINUOUS UNLESS NOTED.
B. ALL FILLET WELDS: A.I.S.C. MINIMUM BUT NOT LESS THAN 1/8" UNLESS NOTED
OTHERWISE.
C. ALL WELDING SHALL BE IN ACCORDANCE WITH THE LATEST "STRUCTURAL
WELDING CODE" (A.W.S. D1.1) PUBLISHED BY THE AMERICAN WELDING SOCIETY.
ELECTRODES FOR WELDING SHALL COMPLY WITH THE LATEST REQUIREMENTS
OF TABLE 4.1.1 OF (A.W.S. D1.1).
D. ALL GROOVE WELDS SHALL BE COMPLETE PENETRATION UNLESS NOTED
OTHERWISE.
8. SPLICING OF STEEL MEMBERS, UNLESS SHOWN ON THE DRAWINGS, IS PROHIBITED
WITHOUT WRITTEN APPROVAL OF THE ENGINEER.
9. NO CHANGE IN SIZE OR POSITION OF THE STRUCTURAL ELEMENTS SHALL BE MADE OF
HOLES, SLOTS, CUTS, ETC., AND ARE NOT PERMITTED THROUGH ANY MEMBER UNLESS
THEY ARE DETAILED ON THE APPROVED SHOP DRAWINGS.
10. NO FINAL BOLTING OR WELDING SHALL BE MADE UNTIL AS MUCH OF THE STRUCTURE
HAS BEEN PROPERLY ALIGNED AND WILL THEREBY BE STIFFENED.
11. UNLESS NOTED OTHERWISE, BEAMS SHALL BEAR 8" MINIMUM ON CONCRETE OR
MASONRY. ANCHOR BEAMS TO MASONRY WITH A GOVERNMENT-TYPE ANCHOR.
12. FABRICATE ALL BEAMS WITH THE MILL CAMBER UP.
13. EXPANSION BOLTS:
UNLESS NOTED OTHERWISE, EXPANSION BOLTS SHALL HAVE THE FOLLOWING
MINIMUM ULTIMATE LOAD CAPACITIES WHEN DRILLED INTO CONCRETE WITH A
MINIMUM DESIGN STRENGTH OF 4000 P.S.I. ULTIMATE LOAD CAPACITIES SHALL
PROVIDE FOR A MINIMUM FACTOR OF SAFETY = 4.
DIAMETER SHEAR TENSION EFFECTIVE EMBEDMENT
1/2" 3570 LBS. 4040 LBS 3 1/4"
3/4" 7635 LBS 5075 LBS 3 3/4"
14. TESTING OF EXPANSION BOLTS AND EPOXY ANCHORS.
A. EXPANSION BOLTS: THE CONTRACTOR SHALL TEST 25% OF ALL EXPANSION
BOLTS ACCORDING TO THE MANUFACTURER'S REQUIRED TORQUES.
B. EPOXY ANCHORS: THE CONTRACTOR SHALL TEST 25% OF ALL EPOXY ANCHORS
WITH PULL TEST EQUAL TO 150% TIMES THE ALLOWABLE BOLT TENSILE
CAPACITIES.
C. NOTE: THE EPOXY ANCHORS ARE TO BE STORED IN A COOL LOCATION
ACCORDING TO THE MANUFACTURES SPECIFICATIONS.
15. SEE MISC. NOTES FOR EPOXY / ADHESIVE ANCHORS.
ADDITIONAL ADDL.
ALUMINUM ALUM.
ANCHOR BOLT A.B.
AND &
ANGLE L
ARCHITECTURAL ARCH.
AT @
BASEMENT BSMT.
BASE PLATE B. P.
BEAM BM.
BEARING BRG.
BETWEEN BETWN.
BLOCK BLK.
BOARD BD
BOTTOM BOT.
BOTTOM FACE B/FACE
BOTTOM OF METAL DECK BOD
BOTTOM OF FOOTING BOF
BOTTOM OF WALL BOW
BRICK BRK.
BRICK SHELF B/S
BRIDGING BRDG.
BUILDING BLDG.
CANTILEVER CANTL.
CAST IN PLACE C.I.P.
CEILING CLG.
CEMENT CEM.
CENTER LINE CL.
CENTER TO CENTER C/C
CENTERED CTR'D.
CLEAR CL. or CLR.
CONCRETE CONC
COLUMN COL.
CONNECTION CONN.
CONSTRUCTION CONST.
CONSTRUCTION JOINT C.J.
CONTINUOUS CONT.
CONTRACTOR CONTR.
DEAD LOAD D.L.
DECK DK.
DIAGONAL DIAG.
DIAMETER DIA.
DIMENSION DIM.
DOWELS DWLS.
DOWN DN.
DRAWINGS DWGS.
EACH EA.
EACH FACE E.F.
EACH WAY E.W.
ELECTRICAL ELECT.
ELEVATION EL.
ELEVATOR ELEV.
EMBEDDED EMBE'D.
EQUAL EQ
EQUIPMENT EQUIP.
EXISTING EXIST.
EXPANSION JOINT E.J.
EXTERIOR EXT.
FAR FACE F.F.
FINISH FIN.
FINISH FLOOR FIN. FLR.
FLOOR FL.
FOOTING FTG.
FOUNDATION FND.
FRAMING FRMG.
GALVANIZED GALV.
GAUGE GA.
GENERAL CONTRACTOR G.C.
GIRDER GIR.
GRADE GR.
GYPSUM GYP.
HEIGHT HT.
HIGH POINT H.P.
HORIZONTAL HORIZ.
INSIDE FACE I.F.
INTERIOR INT.
JOINT JT.or JNT.
JOIST JST.
STRUCTURAL ABBREVIATIONS:
KIP = 1000 lbs. K
KNOCKOUT KO
POUND lb.
LIGHT WEIGHT LT. WT.
LIVE LOAD L.L.
LONG LG.
LONGITUDINAL LONG.
LONG LEG HORIZONTAL L.L.H.
LONG LEG VERTICAL L.L.V.
LONG WAY L.W.
LOW POINT L.P.
MANUFACTURER MFG.
MARK MK.
MASONRY MAS.
MASONRY OPENING M.O.
MATERIAL MAT'L
MAXIMUM MAX.
MECHANICAL MECH
METAL MTL.
MINIMUM MIN.
MISCELLANEOUS MISC.
MOMENT CONNECTION M.C.
NEAR FACE N.F.
NOMINAL NOM.
NOT IN CONTRACT N.I.C.
NOT TO SCALE N.T.S.
ON CENTER O.C.
OPENING OPNG .
OPPOSITE HAND OPP.H.
OUTSIDE FACE O.F.
PANEL PNL.
PENTHOUSE P.H.
PLATE PL.
PLUMBING PLBG
PRECAST CONCRETE P.C.
POCKET PCK'T.
POST TENSION P.T.
RADIUS RAD.
RECTANGULAR RECT.
REFERENCE REF.
REFER TO RE:
REINFORCING REINF.
REQUIRED REQ'D
REVISION REV.
ROOF RF.
ROOM RM
SCHEDULE SCHD.
SECTION SECT.
SHORT WAY S.W.
SIMILAR SIM.
SLAB SL.
SLAB ON GRADE S.O.G.
SPACE, SPACING, SPACES SPA.
SPECIFICATIONS SPECS
SQUARE SQ.
STANDARD STD.
STEEL STL.
STRUCTURE OR STRUCTURAL STRUC
SUPPORT SUPPT.
SYMMETRICAL SYMM.
THICKNESS THK.
TOP FACE T.FACE
TOP OF BRICK LEDGE T/BL
TOP OF FOOTING TOF
TOP OF CONCRETE TOC
TOP OF PIER TOP
TOP OF JOIST T/JST
TOP OF SLAB TSL
TOP OF STRUCTURAL STEEL TOS
TOP OF WALL TOW
TRUSS BEARING T/BRG.
TYPICAL TYP.
UNLESS NOTED OTHERWISE U.N.O.
VERTICAL VERT
VERIFY IN FIELD VIF
WIND BRACE W.B.
WELDED WIRE FABRIC W.W.F.
WITH W/
EXISTING CONDITIONS:
1. THE CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS, SUCH AS DIMENSIONS, ELEVATIONS, CONFIGURATION, AND DETAILS OF EXISTING STRUCTURES AND CONDITIONS
WHERE THEY AFFECT NEW CONSTRUCTION. NOTIFY ENGINEER IMMEDIATELY IF ANY
DEVIATIONS FROM ANTICIPATED CONDITIONS ARE DISCOVERED.
2. COORDINATION W/ COMPLETE SET OF CONTRACT DOCUMENTS: THE CONTRACT
DOCUMENTS ARE ONE COMPLETE, COMPREHENSIVE AND INCLUSIVE DOCUMENT
CONSISTING OF THE AGGREGATE COLLECTION OF DRAWINGS AND SPECIFICATIONS FOR
ALL OF THE DISCIPLINES' DIVISIONS (E.G. SITE, CIVIL, ARCHITECTURAL, STRUCTURAL,
MECHANICAL, PLUMBING, ELECTRICAL, ETC.). NO SINGLE DISCIPLINE DIVISION IS
AUTONOMOUS NOR DOES IT STAND-ALONE FROM ANY OR ALL OTHER DISCIPLINE
DIVISIONS.
3. VERIFY ALL DIMENSIONS, ELEVATIONS, DEPRESSIONS, INSERTS, EMBEDDED ITEMS.
EQUIPMENT PADS AND SUPPORTS, OPENINGS, DETAILS, AND CONDITIONS BY CROSS-
REFERENCING TO ARCHITECTURAL AND ALL OTHER DISCIPLINE SECTION DRAWINGS,
PARTICULARLY CIVIL, MECHANICAL, AND ELECTRICAL SECTIONS.
4. SEE ARCHITECTURAL AND ALL OTHER DISCIPLINE SECTION DRAWINGS FOR DIMENSIONS
NOT SHOWN ON STRUCTURAL DRAWINGS..
5. STRUCTURAL DRAWINGS DO NOT SHOW ALL REQUIRED OPENINGS THROUGH STRUCTURAL
MEMBERS.
6. VERIFY SIZE AND LOCATION OF ALL OPENINGS WITH ARCHITECTURAL AND ALL OTHER
DISCIPLINE SECTION DRAWINGS.
7. NOTES REGARDING USE OF DRAWINGS:
DRAWING SCALES ARE NOTED FOR REFERENCE ONLY. NOT ALL ITEMS ARE DRAWN TO
SCALE, AND DRAWINGS SHOULD NOT BE SCALED TO OBTAIN DIMENSIONS OR ELEVATIONS
NOT INDICATED..
EXISTING REWORK NOTES:
MISCELLANEOUS:
1. STRUCTURAL DRAWINGS ARE INTENDED TO BE USED WITH ARCHITECTURAL AND
MECHANICAL DRAWINGS. CONTRACTOR IS RESPONSIBLE FOR COORDINATING SUCH
REQUIREMENTS INTO THEIR SHOP DRAWINGS AND WORK.
2. NO OPENING SHALL BE MADE IN ANY STRUCTURAL MEMBER WITHOUT THE WRITTEN
APPROVAL OF THE ENGINEER.
3. NO CHANGE IN SIZE OR DIMENSION OF STRUCTURAL MEMBERS SHALL BE MADE
WITHOUT
THE WRITTEN APPROVAL OF THE ENGINEER.
4. OPENINGS 1'-4" AND LESS ON A SIDE ARE GENERALLY NOT SHOWN ON THE
STRUCTURAL
DRAWINGS. REFER TO ARCHITECTURAL AND MECHANICAL DRAWINGS FOR SUCH
OPENINGS.
5. THE CONTRACTOR IS RESPONSIBLE FOR LIMITING THE AMOUNT OF CONSTRUCTION
LOAD
IMPOSED UPON STRUCTURAL FRAMING. CONSTRUCTION LOADS SHALL NOT EXCEED
THE
DESIGN CAPACITY OF THE FRAMING AT THE TIME THE LOADS ARE IMPOSED.
6. THE STRUCTURE IS DESIGNED TO FUNCTION AS A UNIT UPON COMPLETION. THE
CONTRACTOR IS RESPONSIBLE FOR FURNISHING ALL TEMPORARY BRACING AND/OR
SUPPORT THAT MAY BE REQUIRED AS THE RESULT OF THE CONTRACTOR'S
CONSTRUCTION METHODS AND/OR SEQUENCES.
7. UNLESS OTHERWISE NOTED, FIRE PROOFING METHODS AND MATERIALS FOR
STRUCTURAL MEMBERS ARE NOT SHOWN ON STRUCTURAL DRAWINGS. REFER TO
ARCHITECTURAL DRAWINGS AND SPECIFICATIONS FOR FIRE RATING REQUIREMENTS,
FIRE PROOFING METHODS AND MATERIALS.
8. DO NOT SCALE THESE DRAWINGS, USE DIMENSIONS.
9. CONTRACTOR'S CONSTRUCTION AND/OR ERECTION SEQUENCES SHALL RECOGNIZE
AND
CONSIDER THE EFFECTS OF THERMAL MOVEMENTS OF STRUCTURAL ELEMENTS
DURING
THE CONSTRUCTION PERIOD. EXPANSION JOINTS SHOWN ON THE DRAWINGS HAVE
BEEN
DESIGNED TO ACCOMMODATE ANTICIPATED THERMAL MOVEMENT AFTER THE
BUILDING
IS COMPLETE.
10. THE CONTRACTOR SHALL INFORM THE ENGINEER IN WRITING OF ANY DEVIATION
FROM
THE CONTRACT DOCUMENTS. THE CONTRACTOR SHALL NOT BE RELIEVED OF THE
RESPONSIBILITY FOR SUCH DEVIATION BY THE ENGINEER'S APPROVAL OF SHOP
DRAWINGS, PRODUCT DATA, ETC., UNLESS HE HAS SPECIFICALLY INFORMED THE
ENGINEER OF SUCH DEVIATION AT THE TIME OF SUBMISSION, AND THE ENGINEER HAS
GIVEN WRITTEN APPROVAL TO THE SPECIFIC DEVIATION.
11. ALL THINGS WHICH, IN THE OPINION OF THE CONTRACTOR, APPEAR TO BE
DEFICIENCIES,
OMISSIONS, CONTRADICTIONS, OR AMBIGUITIES, IN THE PLANS AND SPECIFICATIONS
SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER. PLANS AND/OR
SPECIFICATIONS WILL BE CORRECTED, OR WRITTEN INTERPRETATION OF THE
ALLEGED
DEFICIENCY, OMISSION, CONTRADICTION OR AMBIGUITY WILL BE MADE BY THE
ENGINEER BEFORE THE EFFECTED WORK PROCEEDS.
12. CHECK ALL DIMENSIONS AGAINST REQUIREMENTS OF OTHER CONTRACT
DOCUMENTS.
FIELD VERIFY DIMENSIONS RELATING TO EXISTING CONDITIONS PRIOR TO ORDERING
MATERIALS AND FABRICATION.
13. WHERE DIMENSIONS OR WEIGHTS OF EQUIPMENT OR SYSTEMS ARE VARIABLE FROM
MANUFACTURER TO MANUFACTURER, VERIFY DIMENSIONS AND WEIGHTS SHOWN ON
DRAWINGS WITH SELECTED MANUFACTURER PRIOR TO ORDERING MATERIALS.
NOTIFY
STRUCTURAL ENGINEER OF DISCREPANCIES. DO NOT PLACE EQUIPMENT WHEN
SHIPPING OR OPERATING WEIGHT EXCEEDS WEIGHT INDICATED ON STRUCTURAL
DRAWINGS.
14. NO MODIFICATION, ALTERATION OR REPAIR SHALL BE MADE WITHOUT PRIOR REVIEW
BY
STRUCTURAL ENGINEER. SUBMIT DETAILS AND CALCULATIONS PREPARED BY A
PROFESSIONAL ENGINEER REGISTERED IN STATE WHERE PROJECT IS LOCATED AND
EMPLOYED BY CONTRACTORS.
15. EPOXY/ADHESIVE ANCHORS SHALL BE INSTALLED WITHIN THE TEMPERATURE
REQUIREMENTS PROVIDED BY THE EPOXY/ADHESIVE MANUFACTURER. THE GENERAL
CONTRACTOR SHALL NOTIFY THE ARCHITECT/ENGINEER IF THE TEMPERATURES ARE
NOT WITHIN THE PROPER RANGE.
GENERAL NOTES
DESIGN CRITERIA:
1. CODES AND STANDARDS:
2015 IBC
2. DESIGN GRAVITY LOADS:
DEAD LOADS:
ROOF:
DEAD LOAD: 110 PSF @ 8" SLAB
15 PSF @ GRATING
LIVE LOADS:
ROOF:
LIVE LOAD: 22 PSF @ ROOF + SNOW DRIFT
3. WIND LOAD: INTERIOR MODIFICATION NOT SUBJECT TO WIND PRESSURES
4. SEISMIC LOAD:
SPECTRAL ACCELERATIONS: Ss = 0.168
SPECTRAL ACCELERATIONS: S1 = 0.093
DESIGN SPECTRAL RESPONSE ACCELERATION: Sds = 0.179 DESIGN SPECTRAL RESPONSE ACCELERATION: Sd1 = 0.150
OCCUPANCY CATEGORY: IV
SEISMIC DESIGN CATEGORY: D
SITE CLASS: D
SITE COEFFICIENTS: Fa = 1.60 Fv =2.4 IMPORTANCE FACTOR: Ie = 1.5
5. COMPONENT IMPORTANCE FACTOR:
Ip = 1.5
6. BASIC STRUCTURAL SYSTEMS:
A.) FRAME SYSTEM
7. SEISMIC - RESISTING SYSTEM: SEISMIC UPGRADE HAS NOT BEEN DESIGNED
MICHAEL VALERE VANDE VELDE
PE: 2004017260
Drawing Title Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
Office of Facilities
Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231, OCT 1978
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
VeteransA sffair Depa frtment o
1 Memorial Dr. STE 1800 Saint Louis, MO 63102
Tel
Fax
314.621.4343 314.621.0261
FCA Replace Air Handlers (AC-S3, AC-S4)
Bid Set Drawings
589A4-18-186
220 N College Ave Indianapolis, IN 46202
Tel
Fax
317.464.9090 317.464.9393
Structural, Mechanical & Electrical Engineer
S S
C #2
6/2/2020 1:04:04 PM
STRUCTURAL GENERAL
NOTES
S0.1 800 Hospital Drive Columbia, MO 65201
06/02/2020 MVV JMH
STRUCTURAL SHEET INDEX
SHEET NUMBERS SHEET NAME
S0.1 STRUCTURAL GENERAL NOTES
S2.1 STRUCTURAL FRAMING PLANS AND DETAILS
H
JK
K
L
L
Hb
Hb
Ja
Ja
6.7 6.7
7 7
8 8
/2
/8
/2
/8
/8
/8
5' - 7" 11' - 0" 5' - 1" 13' - 5" 8' - 3" 4' - 8" 17' - 0"
1' - 3" 1' - 9"
6 6
5 5
5.4 5.4
6.2 6.2
21' - 8" 13' - 5" 12' - 11" 17' - 0"
/8
/2
S2.1
TYP
S2.1
W x
W x
W x
W x
DEMO EXISTING BEAM
W12x19
DEMO EXISTING BEAM
S2.1
S2.1
"x
C O
N C
B M
"x
C O
N C
B M
"x
C O
N C
B M
"x
C O
N C
B M
20"x18" CONC BM
24"x18" CONC BM
18"x18" CONC BMEXIST
EXIST
EXIST
E X
IS
T
E X
IS
T
E X
IS
T
E X
IS
T
"x
C O
N C
B M
"x
C O
N C
B M
E X
IS
T
E X
IS
T
S2.1
OPP HAND
SEE NOTE 5
4' - 8 1/2" 2' - 10" 6' - 0 1/2" 2' - 11 1/2" SEE NOTE 7
(E
W
(E
W
(E)-W12
(E
W
(E
W
NEW W12x14
(E)-W12
(E)-W12
SEE NOTE 6
S2.1
IN FIELD
4' - 6" VERIFY
SEE
NOTE 6
EXIST GRATE
TO REMAIN
EXIST GRATE
TO REMAIN
EQ EQ
SEE NOTE 8 TYP
3' - 10" 3' - 10" 3' - 10" 5' - 1"
SEE NOTE 7
1/2"
5' - 0 7/8"
/2
NEW BEAM PER PLAN
EXIST BEAM
L4x4x3/8 x 0'-11" w/ (3)-3/4"Ø TITEN HD (4" EMBED)
& (3)-3/4"Ø A325 BOLTS EA END
EXISTING GRATING
1. SEE SHEET 1-S0.1 FOR STRUCTURAL GENERAL NOTES, INCLUDING
MATERIAL.
2. REFER TO THE ARCHITECTURAL DRAWINGS AND/OR COORDINATE WITH
THE ARCHITECT REGARDING MISSING DIMENSIONS
3. INDICATES SPAN DIRECTION OF GRATING.
4. T/BEAM ELEVATION TO MATCH EXIST CONCRETE BEAMS.
5. EXISTING 1" x 1/8" GRATING. REUSE TO GREATEST EXTENT POSSIBLE
ATTACH GRATING TO NEW BEAMS. MIN (2)-ATTACHMENT PER GRATING
PANEL. INFILL WITH NEW 1" x 1/8" GRATING TO MATCH EXIST AS
REQUIRED.
6. NEW 1" x 3/16 GRATING. ATTACH TO EXISTING BEAMS MIN (2)-ATTACHMENT
PER GRATING PANEL.
7. (3)-CONC BEAM REINF @ 8"O.C. PER SECTION 7/S2.1
8. FIELD VERIFY EXIST BEAMS 12" DEPTH.
6 6.2
L4x4x3/8 x 0'-6" w/ (2) 3/4"Ø A325 BOLTS
1/4
SIDES
TYP
NEW BEAM PER PLAN
EXIST CONC BEAM
EXIST GRATE DEMO
AS REQUIRED
NEW BEAM PER PLAN
EXIST GRATING - CUT @ NEW BEAM LOCATION & RE-ATTACH
TO NEW BEAM @ 24"O.C. MIN (2) CONNECTIONS PER
GRATING PANEL APPLY GALVANIZED REPAIR PAINT @ ALL
CUT ENDS - TYP. PROVIDE NEW END BAR @ CUT ENDS.
PROVIDE NEW GALVANIZED GRATING MATCHING EXISTING
GRATING WHERE ABANDONED PIPING HOLES EXIST
L4x4x3/8 x 0'-6" w/ (2) 3/4"Ø
TITEN HD (4" EMBED)
1/4
SIDES
TYP
NEW AHU CURB ATTACHMENT BY
MECHANICAL CONTRACTOR
HSS 2 1/2 x 1" x 3/16 x CONT
3/16 2-12
EXIST GRATING - CUT @ NEW BEAM
LOCATION & RE-ATTACH TO NEW
BEAM @ 24"O.C. MIN (2)
CONNECTIONS PER GRATING PANEL
APPLY GALVANIZED REPAIR PAINT @
ALL CUT ENDS - TYP. PROVIDE NEW
END BAR @ CUT ENDS. PROVIDE NEW
GALVANIZED GRATING MATCHING
EXISTING GRATING WHERE
ABANDONED PIPING HOLES EXIST
NEW BEAM
PER PLAN
NEW AHU CURB
ATTACHMENT
BY MECHANICAL
CONTRACTOR
HSS 2 1/2 x 1" x 3/16 x CONT
3/16 2-12
DEMO EXIST BEAM
DEMO EXIST CONC CURB
EXIST CONC BEAM
EXIST GRATING
/2
DEMO HOUSE KEEPING PAD
± 5
/4
DEMO EXIST RIBBED CURB
DEMO EXIST HOUSEKEEPING PAD
EXISTING STRUCTURAL SLAB
EXIST W12 BEAM
NEW W12 BEAM PER PLAN
EXIST SLAB
GROUT - MATCH
DEPTH OF EXIST
NEW GRATING
EXIST GRATING
3/16
SIDES
L4x3x5/16 x 0'-8"
EXIST SLAB
L3x3x1/4 x 0'-4" W/(1)-1/2"Ø
TITEN HD EA SIDE EMBED 3
3/8"
1/2"Ø A307 ROD
EA SIDE DOUBLE
NUT TOP AND BOT
L3x3x1/4 x 2'-0"
1"
H
H
Hb
Hb
6.7 6.7
7 7
8 8
Jb
Jb
/8
/2
30' - 8"
S2.1
TYP ALL
SIDES
MICHAEL VALERE VANDE VELDE
PE: 2004017260
Drawing Title Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
Office of Facilities
Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231, OCT 1978
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
VeteransA sffair Depa frtment o
1 Memorial Dr. STE 1800 Saint Louis, MO 63102
Tel
Fax
314.621.4343 314.621.0261
FCA Replace Air Handlers (AC-S3, AC-S4)
Bid Set Drawings
589A4-18-186
220 N College Ave Indianapolis, IN 46202
Tel
Fax
317.464.9090 317.464.9393
Structural, Mechanical & Electrical Engineer
S S
C #2
6/2/2020 1:04:07 PM
STRUCTURAL FRAMING
PLANS AND DETAILS
S2.1 800 Hospital Drive Columbia, MO 65201
06/02/2020 MVV JMH
NORTH
SCALE: 3/16" = 1'-0"
PARTIAL FRAMING PLAN @ EXISTING PENTHOUSE LOWER LEVEL
SCALE: 3/4" = 1'-0"
NEW W14 TO EXIST CONC BM DETAIL
NOTE:
EXIST CONC BEAMS TO BE SCANNED TO LOCATE EXIST
REINF PRIOR TO DRILLING. DO NOT CUT EXIST REINF
WHEN DRILLING. ADJUST LOCATION OF CONNECTION TO
AVOID INTERFERENCE W/ EXIST REINF. IF ADJUSTMENT IS
NOT POSSIBLE THEN NOTIFY CONTRACING OFFICER FOR
ALTERNATIVE CONNECTION.
SCALE: 3/4" = 1'-0"
NEW W12 PARALLEL TO EXIST BM
SCALE: 3/4" = 1'-0"
SECTION @ NEW AHU SUPPORT
SCALE: 3/4" = 1'-0"
SECTION @ EXIST CONC CURB
SCALE: 3/4" = 1'-0"
DETAIL @ EXISTING RIBBED CURB
SCALE: 3/4" = 1'-0"
SECTION
SCALE: 3/4" = 1'-0"
SECTION
NORTH
SCALE: 3/16" = 1'-0"
PARTIAL FRAMING PLAN @ EXISTING ROOF/PENTHOUSE LL
SD
S D
SD
S D
SD
S D
SD
S D
SD
S D
SD
S D
SD
S D
SD
S D
SD
S D
M
5 5
5.4 5.4
6 6
6.2
6.7 6.7
7 7
8 8
H
H
Hb
Hb
J
JJb
K
K
L
L
Ja
A1.2
Remove Existing Air Handler AC-S3 and Associated Ducts - See MEP Drawings for Additional Information and Full Scope of Work
Contractor to coordinate with COR the removal and storage of precast grill panels, brick, and CMU wall and louver for Air Handler removal.
Prepare Existing Temporary Duct for temporary connection
3'-0"
Remove wall at area of Temporary Duct Penetration;
See Elevation for additional information
1 / A1.2
Temporary AC Unit
5 5
5.4 5.4
6 6
6.2
6.7 6.7
7 7
8 8
H
H
Hb
Hb
J
JJb
K
K
L
L
Ja
A1.2
Contractor to coordinate with COR the removal and storage of precast grill panels, brick, and CMU wall and louver for Duct Penetration.
Temporary Duct Connections; See MEP Drawings for Full Scope
Temporary AC Unit
5 5
5.4 5.4
6 6
6.2
6.7 6.7
7 7
8 8
H
H
Hb
Hb
J
JJb
K
K
L
L
Ja
Infill Temporary Duct Penetration; See Elevation for Additional Information
Replace Precast Grill Panels
Temporary AC Unit
Temporary ductwork to be removed;
See MEP Drawings for additional information and Full Scope of Work
New Air Handler AC-34 - See MEP Drawings for Additional Information and Full Scope of Work
Drawing Title Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
Office of Facilities
Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231, OCT 1978
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
VeteransA sffair Depa frtmento
4/15/2020 9:54:16 AM
Upper Level Penthouse Floor Plans
A1.0 800 Hospital Drive Columbia, MO 65201
04/14/2020
Bid Set Drawings
Checker Author
589A4-18-186FCA Replace Air Handlers
(AC-S3, AC-S4)
N
1/8" = 1'-0"1 Penthouse Upper Level Plan - Demolition N
1/8" = 1'-0"2 Penthouse Upper Level Plan - Temporary
N
1/8" = 1'-0"3 Penthouse Upper Level Plan - Renovation
06/02/2020 BD ZF
M
M
SD
SD
M
SD
SD
M
SD
SD
M
M
SD
SD
M
SD
M
SD
SD
M
SD
SD
M
SD
SD
M
M
SD
SD
M
SD
M
SD
SD
M
SD
SD
M
SD
SD
M
M
SD
SD
5 5
5.4 5.4
6 6
6.2 6.2
6.7 6.7
7 7
8 8
H
H
Hb
Hb
J
JJb
K
K
L
L
Ja
Remove Existing Air Handler AC-S4 and Ducts - See MEP Drawings for Additional Information and Full Scope of Work
Contractor to coordinate with COR the removal and storage of precast grill panels, brick, and CMU wall for Air Handler removal.
3'-0"
Remove wall at area of Temporary Duct Penetration;
See Elevation for additional information
1 / A1.2
Prepare temporary ducts;
See Mechanical Plan for Additional Information
A1.2
A1.2
Temporary AC Unit
VA to relocate cabinets and other equipment from this are prior to contractor beinning work
5 5
5.4 5.4
6 6
6.2 6.2
6.7 6.7
7 7
8 8
H
H
Hb
Hb
J
JJb
K
K
L
L
Ja
Temporary ductwork to be removed;
See MEP Drawings for additional information and Full Scope of Work
New Air Handler AC-S4
- See MEP Drawings for Additional Information and Full Scope of Work
Reinstall Salvaged Precast Grill Panels, Brick, and CMU Wall after installation of Air Handler installation. Match Existing Assembly Method and Grout Color as Adjacent Grill Panel Walls.
A1.2
A1.2
Infill Temporary Opening; See Elevation for more information
Temporary AC Unit
5 5
5.4 5.4
6 6
6.2 6.2
6.7 6.7
7 7
8 8
H
H
Hb
Hb
J
JJb
K
K
L
L
Ja
Temporary ductwork to be installed and removed once permanent AC-S4 replacement is installed; See MEP Drawings for additional information and Full Scope of Work
A1.2
A1.2
Temporary AC Unit
Drawing Title Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
Office of Facilities
Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231, OCT 1978
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
VeteransA sffair Depa frtmento
4/15/2020 9:54:17 AM
Lower Level Penthouse Floor Plans
A1.1 800 Hospital Drive Columbia, MO 65201
04/14/2020
Bid Set Drawings
Checker Author
589A4-18-186FCA Replace Air Handlers
(AC-S3, AC-S4)
N
1/8" = 1'-0"1 Penthouse Lower Level / Roof Plan - Demolition
N
1/8" = 1'-0"3 Penthouse Lower Level / Roof Plan - Renovation
N
1/8" = 1'-0"2 Penthouse Lower Level / Roof Plan - Temporary
6" ± 3'-0" 6"
1) Saw-cut opening around temporary duct penetration;
coordinate with MEP drawings for exact location.
2) In-fill around duct with 3 5/8" MTL Stud Framing with Exterior Grade Plywood on both sides of studs. Apply Weather-tight caulk around plywood.
3) After temporary ducts are removed; infill entire opening with Brick and CMU to match the existing wall construction. Brick to match Adjacent Brick
New ductwork shown dashed; RE: MEP Drawings for Additional Information
Existing Roof
See MEP Drawings for the Full Scope of Work
Temporary Steel Lintel Supports; See for Detail
7 / A1.2
A1.2
Remove and Salavage Precast Grill Panels for future reinstallation. Provide additional support of panels as required.
Coordinate with COR storage location for panels.
Wall Beyond to be removed and reinstalled for installation of new Air Handling Unit. Remove as required for Installation.
6" 3'-0" 6"
Opening for
AC-S4
Temporary Connections
Opening for
AC-S3
Temporary Connections
Temporary Steel Lintel Supports; See for Detail
7 / A1.2
Existing CMU Block Wall
Existing Brick Veneer
Exterior Grade Plywood
(3)-L6x3-1/2x5/16 (LLV) with 6" extention at ends.
Saw Cut into Existing.
Temporary Duct; RE: MECH
R E
M
E C
H
D u c t S iz e
Exterior Grade Caulking All Around Perimeter of Opening
Exterior Grade Caulking All Around Perimeter of Opening
Exterior Grade Caulking All Around Perimeter of Duct
Exterior Grade Caulking All Around Perimeter of Duct
Exterior Grade Plywood 3 5/8" MTL Studs to Frame Opening
Remove and Salvage Pre-cast grill panels shown dashed. Provide Support at bottom row of panels as required. Coordinate with VA COR area of storage for later re-installation.
New Louver; See MEP drawings for additional information
Wall beyond to be removed and reinstalled for installation of new Air Handling Unit. Remove as much as required for Installation.
Existing Door to remain
Remove Existing Precast Grill Panels. Provide (3) Steel Lintels to support remaining Precast Grill Panels above. See S-Series Drawings for Additional Details
Install New Louver per MEP Drawings
Drawing Title Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
Office of Facilities
Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231, OCT 1978
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
VeteransA sffair Depa frtmento
4/15/2020 9:54:18 AM
Exterior Elevations and Details
A1.2 800 Hospital Drive Columbia, MO 65201
04/14/2020
Bid Set Drawings
Checker Author
589A4-18-186FCA Replace Air Handlers
(AC-S3, AC-S4)
1/2" = 1'-0"1 Elevation - Duct Penetration - North
1 1/2" = 1'-0"7 Detail - Temporary Opening
1/2" = 1'-0"2 Elevation - Louver and Precast Grill- South
1/2" = 1'-0"8 Detail - Louver Install
MECHANICAL ABBREVIATIONS MECHANICAL GENERAL DEMOLITION NOTES:GENERAL NOTES:
MECHANICAL GENERAL RENOVATION NOTES:
MECHANICAL SYMBOLS LEGEND MECHANICAL SYMBOLS LEGEND (CONT.)
Drawing Title Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Revisions: Date CONSULTANTS: ARCHITECT/ENGINEERS:
Office of Facilities
Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231, OCT 1978
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
9/27/2016 1:23:55 PM
FCA Replace Air Handlers (AC-S3, AC-S4)
800 Hospital Drive Columbia, MO 65201
Bid Set Drawings 589A4-18-186
SS
C#
SS
C
#2
06/02/2020
1 Memorial Dr. STE 1800 Saint Louis, MO 63102 Tel Fax
314.621.4343 314.621.0261
220 N College Ave Indianapolis, IN 46202 Tel Fax
317.464.9090 317.464.9393
Structural, Mechanical & Electrical Engineer
James C Cornett Professional Engineer MO LIC#:PE-029361 Exp:12/31/2021 MECHANICAL NOTES, SYMBOLS AND
JCC SSC
M0.1
ABBREVIATIONS
SECTION NOTES:
CHILLED WATER COIL SCHEDULE
STEAM HEATING COIL SCHEDULE
AIR HANDLING UNIT SCHEDULE
HUMIDIFIER SCHEDULE
LOUVER SCHEDULE
STEAM TRAP SCHEDULE
AIRFLOW MEASURING STATION SCHEDULE
VARIABLE FREQUENCY DRIVE SCHEDULE (REFERENCE ONLY)
HEAT RECOVERY COIL SCHEDULEFAN SCHEDULE
VIBRATION ISOLATION AND SEISMIC RESTRAINT SCHEDULE
REQUIRED SHUT DOWNS
EXISTING PUMP SCHEDULE
AC UNIT DETAIL (AC-S4)
SECTION NOTES:
AC UNIT DETAIL (AC-S3)
TEST AND BALANCE
22.5
CW
U V
Drain Conn.
Drain Conn.
A1
A1
A1
S9
HR
C
Drain Conn.
SA
R
S
R
S
DD
R
S
R
S
D
S
R
OSAOSA
RA
OSA
OSA
PLAN
ELEVATION
D
.5
CW
U V
Drain Conn.
Drain Conn.
A1
A1
A1
S1
6 8
SC
HR
C
Drain Conn.
RA
A1
A1
A1
R
S
DD
SA
R
SR
SR
S
D
RA
RA
OSA
EXH
LOWER PLAN
ELEVATION
.5
1 32
A1
A1
A1
UPPER PLAN
D
EA
Drawing Title Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Revisions: Date CONSULTANTS: ARCHITECT/ENGINEERS:
Office of Facilities
Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231, OCT 1978
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
9/27/2016 1:23:55 PM
FCA Replace Air Handlers (AC-S3, AC-S4)
800 Hospital Drive Columbia, MO 65201
Bid Set Drawings 589A4-18-186
SS
C#
SS
C
#2
06/02/2020
1 Memorial Dr. STE 1800 Saint Louis, MO 63102 Tel Fax
314.621.4343 314.621.0261
220 N College Ave Indianapolis, IN 46202 Tel Fax
317.464.9090 317.464.9393
Structural, Mechanical & Electrical Engineer
James C Cornett Professional Engineer MO LIC#:PE-029361 Exp:12/31/2021 MECHANICAL
SCHEDULES
SSC SSC
M0.2
DUCT ELBOW
NO SCALE NO SCALE
AREA OF OPENING =
FL
O
W
EXHAUST RETURN BRANCH CONNECTION TO MAIN
NO SCALE
SUPPLY DUCT TAKEOFF - AIR TERMINAL UNIT
NO SCALE
TYPICAL METHOD OF SECURING HANGER RODS
NO SCALE
DUCT ACCESS DOORS AND PANELS
NO SCALE
ROUND DUCT FITTINGS
FLOAT AND THERMOSTAT STEAM TRAP ASSEMBLY
INSTALLATION OF THERMOMETER WELLSWATER COILS - PIPING CONNECTIONS AIR HANDLING UNIT DRAIN TRAP DETAIL
PIPE HANGER SUPPORT DETAILS
STEAM COIL - PIPING CONNECTIONS DISPERSION TUBE (JACKETED) HUMIDIFIER
CLEVIS TYPE HANGER PIPE SUPPORT TRAPEZE HANGER PIPE SUPPORTROLLER HANGER
FLOOR MOUNTED PIPING PROTECTION DETAIL
END OF STEAM LINE DRIP TRAP
AIR HANDLING UNIT SUPPORT DETAIL
NO SCALE
Drawing Title Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Revisions: Date CONSULTANTS: ARCHITECT/ENGINEERS:
Office of Facilities
Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231, OCT 1978
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
9/27/2016 1:23:55 PM
FCA Replace Air Handlers (AC-S3, AC-S4)
800 Hospital Drive Columbia, MO 65201
Bid Set Drawings 589A4-18-186
SS
C#
SS
C
#2
06/02/2020
1 Memorial Dr. STE 1800 Saint Louis, MO 63102 Tel Fax
314.621.4343 314.621.0261
220 N College Ave Indianapolis, IN 46202 Tel Fax
317.464.9090 317.464.9393
Structural, Mechanical & Electrical Engineer
James C Cornett Professional Engineer MO LIC#:PE-029361 Exp:12/31/2021 MECHANICAL
DETAILS
JCC SSC
M0.3
C
AC - S3 & S4 CONTROL DIAGRAM
AC-S3 & AC-S4 SEQUENCE OF OPERATION
COORDINATE ALL SEQUENCE OF OPERATIONS WITH TEST AND
BALANCING…