VA-AC 3_4 - Mechanical set.pdf
PDF 2 MB Posted
- Solicitation number
- 36C25521R0007
About this file
This presolicitation notice is for a construction project to replace two air handling units at the Harry S Truman Medical Center in Columbia, Missouri. The scope of work includes demolishing the existing units AC-S3 and AC-S4 located in the 7th floor penthouse, installing new replacement units, and temporarily providing conditioned air to the spaces served during phasing through use of a temporary air handling unit located on the roof. Phasing will require carefully coordinating ductwork connections to minimize downtime of conditioned air. The project is estimated to cost between $1-2 million and will be awarded as a total small business set-aside to a service-disabled veteran-owned small business. The North American Industry Classification code is 236220 for general construction contractors up to $39.5 million in size. The contract duration is up to 270 calendar days from notice to proceed. The solicitation and drawings will be available on or around November 20, 2020 with proposals due on or around December 21, 2020. Only one organized site visit will be scheduled.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C25521R0007 0004.docx | DOCX document | |
| Amendment 4-Drawings-Correct Fire Life Safety Deficiencies for reference.pdf | ||
| 36C25521R0007 0003.docx | DOCX document | |
| Specification Section 230593.pdf | ||
| 36C25521R0007 0002_1.docx | DOCX document | |
| 36C25521R0007 0002.docx | DOCX document | |
| VA Colubia AC 3-4 Grate Infill Detail.pdf | ||
| 589A4-18-186 Specs 1 35 26 Safety Requirements Revised.pdf | ||
| 589A4-18-186 Specs 23 09 23 Direct Digital Controls Revised.pdf | ||
| Attendance Sign-In Site Visit Walk Thru.pdf | ||
| 36C25521R0007 0001.docx | DOCX document | |
| PREBID MEETING ATTENDENCE LIST.pdf | ||
| 36C25521R0007_1.docx | DOCX document | |
| Specifications-589A4-18-186-437 pages.pdf | ||
| Drawings -589A4-18-186- 20 Pages.pdf |
Show all 15
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SD
S D
SD
S D
SD
S D
SD
M
SD
S D
SD
S D
SD
S D
SD
SD
S D
SD
S D
SD
S D
SD
6.7
HHbJJbKL
5.4
6.2
M1.1
AC
LVR
"ø
"x
70"x36"
40"x24"
32"ø
102"x10"
XRF
SD
6.7
HHbJJbKL
5.4
6.2
XAC
2 3 7
M1.1
M1.1
XRF
40"x24"
45"x28"
"x
34"x40" 30"ø
"ø
SD16
6.7
HHbJJbKL
5.4
6.2
XAC
TEMP
M1.1
M1.1
32"ø
XRF
30"ø
"ø
TEMPORARY DUCT
301"
UPPER PENTHOUSE
440"
PENTHOUSE ROOF
55.466.2
AC
24"x40"
LVR
34"x34"
70"x36"
MD
144"
LOWER PENTHOUSE/ROOF
301"
UPPER PENTHOUSE
440"
PENTHOUSE ROOF
55.4
M1.1
"ø
30"x24"
XRF
144"
LOWER PENTHOUSE/ROOF
301"
UPPER PENTHOUSE
440"
PENTHOUSE ROOF
K L
M1.1
"ø
40"x34"30"ø
34"ø
James C Cornett Professional Engineer MO LIC#:PE-029361 Exp:12/31/2021
Drawing Title Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
Office of Facilities
Management o n e e ig h th in c h o n e fo o t 1
BBBB
AAAA
CCCC
DDDD
EEEE
FFFF
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231, OCT 1978
1111 2222 3333 4444 5555 6666 88887777 9999
FFFF
EEEE
DDDD
CCCC
BBBB
AAAA
99997777 8888666655554444333322221111
VVVVeteeteeteeterrrrananananssss AAAA ssssffffffffaaaaiiiirrrr
DepaDepaDepaDepa ffffrrrrttttmmmmeeeennnntttt oooo
1 Memorial Dr. STE 1800 Saint Louis, MO 63102
Tel
Fax
314.621.4343 314.621.0261
FCA Replace Air Handlers (AC-S3, AC-S4)
Bid Set Drawings
589A4-18-186
220 N College Ave Indianapolis, IN 46202
Tel
Fax
317.464.9090 317.464.9393
Structural, Mechanical & Electrical Engineer
S S
C #2
NOLOPLOMOM=OWROWQN=mj
MECHANICAL UPPER
PENTHOUSE AC-S3
DUCTWORK PLANS
M1.1 800 Hospital Drive Columbia, MO 65201
06/02/2020 jcc SSC
MECHANICAL GENERAL NOTES:
1.
2.
3.
REFER TO SHEET M0.1 FOR SYMBOLS, ABBREVIATIONS AND GENERAL CONSTRUCTION
NOTES.
ALL DUCTWORK AND PIPING BELOW 10'-0" A.F.F. SHALL BE INSULATED AND COVERED WITH
SHEET METAL. REFER TO SPECIFICATION 23 07 11.
TYPICAL EXISTING LOUVER SIZE IS 8'6"x6'8", CONTRACTOR SHALL VERIFY.
MECHANICAL KEYED NOTES:
EXISTING HVAC TO REMAIN.
REMOVE HVAC SHOWN BOLD-DASHED.
BASIS OF DESIGN INCLUDES DEMOLITION OF EXISTING PAD AND CURB BY CONTRACTOR TO
ACCOMMODATE THE REMOVAL AND REPLACEMENT OF THE AIR HANDLING UNIT WHICH HAS
VERY LIMITED CLEARANCE WITH EXISTING SURROUNDING UTILITES. COORDINATE WITH GC.
REFER TO GENERAL NOTES ON M0.1 FOR LIMITATIONS ON SEVERE NOISE PRODUCING
WORK.
NOT USED.
REMOVE EXISTING DUCTWORK AND PREPARE FOR RECONNECTION.
RETURN AIR TO BE 100% EXHAUSTED DURING INSTALLATION OF AC-3.
DEMOLISH EXISTING LOUVER. EXISTING OPENING SHALL BE USED FOR DEMOLITION OF
EXISTING UNIT AND INSTALLATION OF NEW UNIT.
NOT USED.
EXISTING TEMPERATURE CONTROL PANELS FOR AC-S3 TO REMAIN. PROVIDE UPS POWER
SUPPLY AS REQUIRED TO PROVIDE MINIMUM 15 MINUTES OF BACKUP POWER TO AC-S3
ACCESSORIES. REFER TO ELECTRICAL DRAWINGS FOR RE-CIRCUITING TO EMERGENCY
PANEL.
COORDINATE REMOVAL AND REINSTALLATION OF CAST CONCRETE PANELS WITH GC.
FIELD FABRICATED AND INSULATED DUCT PLENUM BOX TO TRANSITION FROM LVR-3 TO
INTAKE OF AC-S3.
SUPPLY FAN VFD LOCATION. COORDINATE WITH TCC AND EC.
RETURN FAN VFD LOCATION. COORDINATE WITH TCC AND EC.
EXISTING XAC-TEMP CONTROLS PANEL. EXTEND EXISTING CONTROLS WIRING FROM AC-3
PANEL TO AC-TEMP PANEL. COORDINATE WITH TCC.
RECONNECT EXISTING CONTROLS TO AC-3 PANEL.
RELOCATE SMOKE DETECTOR FOR TEMPORARY PHASE. EXTEND CONTROLS WIRING TO
NEW LOCATION.
RELOCATE SMOKE DETECTOR BACK TO ORIGINAL LOCATION FOR FINAL CONNECTION.
REMOVE AC-4 TEMPORARY DUCT AND MODIFY FOR AC-3.
SEE M2.1 FOR AC-20.
PROVIDE RATED SCAFFOLDING SYSTEM. SCAFFOLDING SYSTEM GETS MOUNTED TO ROOF.
ROOF TO BE PATCHED. "GARLEN" OWNS ROOF WARRANTY AND IS TYPICALLY SUB-
CONTRACTED VIA WATKINS ROOFING. CONTRACTOR TO MAINTAIN ROOF WARRANTY.
REMOVE EXISTING LOUVER (32" WIDE BY 36" TALL), REPLACE WITH NEW.
REMOVE EXISTING LOUVER (39" WIDE BY 78" TALL), REPLACE WITH NEW.
UTILIZE SMOKE DETECTOR IN EXISTING TEMP UNIT FOR SUPPLY, REPROGRAM AS
REQUIRED.
NORTH
SCALE: 1/8" = 1'-0"
MECHANICAL UPPER PENTHOUSE AC-3 PLAN - RENOVATION
NORTH
SCALE: 1/8" = 1'-0"
MECHANICAL UPPER PENTHOUSE AC-3 PLAN - TEMPORARY - DEMOLITION
NORTH
SCALE: 1/8" = 1'-0"
MECHANICAL UPPER PENTHOUSE AC-3 PLAN - TEMPORARY - RENOVATION
SCALE: 1/4" = 1'-0"4
AC-3 SECTION
SCALE: 1/8" = 1'-0"5
MECHANICAL AC-3 SECTION
SCALE: 1/8" = 1'-0"6
MECHCANICAL AC-3 ELEVATION - EXTERIOR DUCTWORK
MECHANICAL KEYED NOTES:
MECHANICAL GENERAL NOTES:
MECHANICAL UPPER
PENTHOUSE PIPING
JCC SSC
M1.2
PLANS - AC-S3
REPLACEMENT
MECHANICAL UPPER PENTHOUSE PIPING PLAN - DEMOLITION MECHANICAL UPPER PENTHOUSE PIPING PLAN - RENOVATION
Drawing Title Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Revisions: Date CONSULTANTS: ARCHITECT/ENGINEERS:
Office of Facilities
Management o n e e ig h th in c h o n e fo o t 1
C th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231, OCT 1978
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
9/27/2016 1:23:55 PM
FCA Replace Air Handlers (AC-S3, AC-S4)
800 Hospital Drive Columbia, MO 65201
Bid Set Drawings 589A4-18-186
SS
C#
S S
C #2
06/02/2020
1 Memorial Dr. STE 1800 Saint Louis, MO 63102 Tel Fax
314.621.4343 314.621.0261
220 N College Ave Indianapolis, IN 46202 Tel Fax
317.464.9090 317.464.9393
Structural, Mechanical & Electrical Engineer
James C Cornett Professional Engineer MO LIC#:PE-029361 Exp:12/31/2021
M
SD
M
SD
SD
M
SD
SD
M
SD
SD
M
M
SD
SD
M
SD
M
SD
SD
M
SD
SD
M
SD
SD
M
M
SD
SD
M
SD
M
SD
SD
M
SD
SD
M
SD
SD
M
M
SD
SD
SD SD SD
6.7
HHb
JJbKL
5.4
6.2
EXISTING 108"x80"
OA LOUVER
SA UP
24"ø
36"ø
36"ø
"x
60"x40"
24"x56"
44"x24"
24"ø
96"x18"1
EXISTING STEAM
CONDENSATE UP
AC
AC
LVR
4a
M2.1
"x
"x
6.7
HHbJJbKL
5.4
6.2
EXISTING
33"Lx113"Hx160"W
OA PLENUM BOX
EXISTING 108"x80"
OA LOUVER
24"x56"
"x
36"ø
XRF
44"x24"
96"x18"
M2.1
LOWER
PENTHOUSE
40"x24"
24"x28"
34"ø
17"ø
24"ø
22"x40"
32"x24"
LOWER
PENTHOUSE
40"x24"
24"x28"
34"ø
17"ø
24"ø
22"x40"
32"x24"
XAC
XRF
36"x30"
24"ø
7 10
6.7
HHbJJbKL
5.4
6.2
M2.1
M2.1
LOWER
PENTHOUSE
40"x24"
24"x28"
34"ø
17"ø
24"ø
22"x40"
32"x24"
RF
AC4
144"
LOWER PENTHOUSE/ROOF
301"
UPPER PENTHOUSE
K L
M2.1
144"
LOWER PENTHOUSE/ROOF
301"
UPPER PENTHOUSE
55.4
144"
LOWER PENTHOUSE/ROOF
301"
UPPER PENTHOUSE
440"
PENTHOUSE ROOF
6.7 6.278
AC
LVR
4a
LVR
4b
SD
6.7
HHbJ
"x
AC
6.7
HHbJ
AC-4
AC-20
6.7
HHbJ
M2.1
LVR
4b
James C Cornett Professional Engineer MO LIC#:PE-029361 Exp:12/31/2021
Drawing Title Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
Office of Facilities
Management o n e e ig h th in c h o n e fo o t 1
BBBB
AAAA
CCCC
DDDD
EEEE
FFFF
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231, OCT 1978
1111 2222 3333 4444 5555 6666 88887777 9999
FFFF
EEEE
DDDD
CCCC
BBBB
AAAA
99997777 8888666655554444333322221111
VVVVeteeteeteeterrrrananananssss AAAA ssssffffffffaaaaiiiirrrr
DepaDepaDepaDepa ffffrrrrttttmmmmeeeennnntttt oooo
1 Memorial Dr. STE 1800 Saint Louis, MO 63102
Tel
Fax
314.621.4343 314.621.0261
FCA Replace Air Handlers (AC-S3, AC-S4)
Bid Set Drawings
589A4-18-186
220 N College Ave Indianapolis, IN 46202
Tel
Fax
317.464.9090 317.464.9393
Structural, Mechanical & Electrical Engineer
S S
C #2
NOLOPLOMOM=OWROWRO=mj
MECHANICAL PENTHOUSE
AC-S4 DUCTWORK PLANS
M2.1 800 Hospital Drive Columbia, MO 65201
06/02/2020 JCC SSC
MECHANICAL GENERAL NOTES:
1.
2.
3.
REFER TO SHEET M0.1 FOR SYMBOLS, ABBREVIATIONS AND GENERAL CONSTRUCTION
NOTES.
ALL DUCTWORK AND PIPING BELOW 10'-0" A.F.F. SHALL BE INSULATED AND COVERED WITH
SHEET METAL. REFER TO SPECIFICATION 23 07 11.
TYPICAL EXISTING LOUVER SIZE IS 8'6"x6'8", CONTRACTOR SHALL VERIFY.
MECHANICAL KEYED NOTES:
EXISTING HVAC TO REMAIN.
REMOVE HVAC SHOWN BOLD-DASHED.
BASIS OF DESIGN INCLUDES DEMOLITION OF EXISTING PAD AND CURB BY CONTRACTOR TO
ACCOMMODATE THE REMOVAL AND REPACEMENT OF THE AIR HANDLING UNIT WHICH HAS
VERY LIMITED CLEARANCE WITH EXISTING SURROUNDING UTILITES. AC-20 REQUIRES THE
REMOVAL & REPLACEMENT/RECONFIGURATION OF STEEL GRATING. A CREDIT SHALL BE
PROVIDED TO THE VA IF IT IS DETERMINED THE NEW UNIT CAN BE INSTALLED WITHOUT THE
DEMOLITION OF THE EXISTING PAD AND CURB. IF THE EXISTING PAD AND CURB ARE TO
REMAIN, NEW CONCRETE BRIDGING SHALL TO BE PROVIDED TO ALIGN WITH NEW AIR
HANDLING UNIT SHIPPING SPLITS. COORDINATE WITH GC. REFER TO GENERAL NOTES ON
M0.1 FOR LIMITATIONS ON SEVERE NOISE PRODUCING WORK.
RELOCATION OF EXISTING PIPING AT CONTRACTORS DISCRETION TO AID INSTALLATION OF
NEW AIR HANDLER. COORDINATE IMPACT ON PHASING WITH COR.
REMOVE EXISTING DUCTWORK AND PREPARE FOR RECONNECTION.
REMOVE TWO (2) ADDITIONAL COILS (128"x32"x12") STORED IN CORNER.
DEMOLISH EXISTING 84" WIDE BY 26" TALL LOUVER. EXISTING OPENING SHALL BE USED
FOR DEMOLITION OF EXISTING UNIT AND INSTALLATION OF NEW UNIT.
PROVIDE A "TEE" CONNECTION SO AS TO BACK-FEED AIR & CONNECT (TEMPORARILY) TO
OLD AC-20 SUPPLY DUCT.
EXISTING TEMPERATURE CONTROL PANELS FOR AC-S4 TO REMAIN. PROVIDE UPS POWER
SUPPLY AS REQUIRED TO PROVIDE MINIMUM 15 MINUTES OF BACKUP POWER TO AC-S4
ACCESSORIES. REFER TO ELECTRICAL DRAWINGS FOR RE-CIRCUITING TO EMERGENCY
PANEL.
COORDINATE REMOVAL AND REINSTALLATION OF CAST CONCRETE PANELS WITH GC.
FIELD FABRICATED AND INSULATED DUCT PLENUM BOX TO TRANSITION FROM LVR-4 TO
INTAKE OF AC-S4.
SUPPLY FAN VFD LOCATION. COORDINATE WITH TCC AND EC.
RETURN FAN VFD LOCATION. COORDINATE WITH TCC AND EC.
EXISTING XAC-TEMP CONTROLS PANEL. EXTEND EXISTING CONTROLS WIRING FROM AC-4
PANEL TO AC-TEMP PANEL. COORDINATE WITH TCC.
RECONNECT EXISTING CONTROLS TO AC-4 PANEL.
RELOCATE SMOKE DETECTOR FOR TEMPORARY PHASE. EXTEND CONTROLS WIRING TO
NEW LOCATION.
RELOCATE SMOKE DETECTOR.
REMOVE ALL PIPING, DUCTWORK, CONTROLS, DX PIPING, ETC. FOR COMPLETE REMOVAL
OF AC-20. AC-20 AND AC-4 WILL BE COMBINED AS ONE UNIT.
PATCH WALL OPENING.
TEMPORARY EXHAUST FAN UTILIZED FOR INSTALL OF AC-4 ONLY.
PROVIDE RATED SCAFFOLDING SYSTEM. SCAFFOLDING SYSTEM GETS MOUNTED TO ROOF.
ROOF TO BE PATCHED. "GARLEN" OWNS ROOF WARRANTY AND IS TYPICALLY SUB-
CONTRACTED VIA WATKINS ROOFING. CONTRACTOR TO MAINTAIN ROOF WARRANTY.
RELOCATION OF REPEATER, TRANSMITTER AND EMERGENCY MANAGEMENT CABINETS
INCLUDING RERATING OF CABLING SHALL BE BY OTHERS. CONTRACTOR TO PROTECT
EQUIPMENT AS NEEDED.
NORTH
SCALE: 1/8" = 1'-0"
MECHANICAL LOWER PENTHOUSE AC-4 PLAN - RENOVATION
NORTH
SCALE: 1/8" = 1'-0"
MECHANICAL LOWER PENTHOUSE AC-4 PLAN - TEMPORARY - DEMOLITION
NORTH
SCALE: 1/8" = 1'-0"
MECHANICAL LOWER PENTHOUSE AC-4 PLAN - TEMPORARY - RENOVATION
SCALE: 1/8" = 1'-0"10
MECHANICAL ELEVATION - EXTERIOR DUCTWORK
SCALE: 1/8" = 1'-0"11
MECHANICAL SECTION
SCALE: 1/4" = 1'-0"4
AC-4 SECTION
NORTH
SCALE: 1/8" = 1'-0"
MECHANICAL UPPER PENTHOUSE AC-20
PLAN - TEMPORARY - DEMOLITION
NORTH
SCALE: 1/8" = 1'-0"
MECHANICAL UPPER PENTHOUSE AC-20
PLAN - TEMPORARY - RENOVATION
NORTH
SCALE: 1/8" = 1'-0"
MECHANICAL UPPER PENTHOUSE AC-20
PLAN - RENOVATION
MECHANICAL KEYED NOTES:
MECHANICAL GENERAL NOTES:
MECHANICAL
PENTHOUSE PIPING
SSC SSC
M2.2
PLANS - AC-S4
REPLACEMENT
MECHANICAL LOWER PENTHOUSE PIPING PLAN - DEMOLITION MECHANICAL LOWER PENTHOUSE PIPING PLAN - RENOVATION
Drawing Title Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Revisions: Date CONSULTANTS: ARCHITECT/ENGINEERS:
Office of Facilities
Management o n e e ig h th in c h o n e fo o t 1 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231, OCT 1978
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
9/27/2016 1:23:55 PM
FCA Replace Air Handlers (AC-S3, AC-S4)
800 Hospital Drive Columbia, MO 65201
Bid Set Drawings 589A4-18-186
SS
C#
S S
C #2
06/02/2020
1 Memorial Dr. STE 1800 Saint Louis, MO 63102 Tel Fax
314.621.4343 314.621.0261
220 N College Ave Indianapolis, IN 46202 Tel Fax
317.464.9090 317.464.9393
Structural, Mechanical & Electrical Engineer
James C Cornett Professional Engineer MO LIC#:PE-029361 Exp:12/31/2021
MECHANICAL UPPER PENTHOUSE PIPING PLAN - DEMOLITION