Drawings_561A4-18-113 Correct FCA D and F Deficienc.pdf
PDF 24 MB Posted
- Attached to
- Correct FCA D & F Deficiencies Boiler Plant.
- Solicitation number
- 36C24226R0032
About this file
This is a Structural General Notes and Architectural Drawing document for the "Correct FCA D & F Deficiencies Boiler Plant" project at Lyons VA Medical Center in Lyons, New Jersey (Project No. 561A4-18-113). The drawings and specifications are dated April 11, 2025, and were prepared by Harrell Design Group, PC, the architect/engineer of record, with Britt Peters serving as the structural consultant.
The document establishes comprehensive structural design and construction requirements governing codes, standards, design loads, concrete, reinforcing steel, structural steel, and inspection protocols. All work must comply with the 2021 International Building Code New Jersey Edition, ASCE 7-16, AISC 360-16 and 341-16, and AWS D1.1-18 and D1.4-18 standards. The project is classified as Risk Category IV with seismic design category C and wind speeds of 126 mph. Key structural requirements include: concrete with 4,500 psi compressive strength and 145 pcf density for exterior elements; reinforcing steel conforming to ASTM A615 Grade 60 or A706 (for welded reinforcement); structural steel fabricated by AISC-certified plants with minimum ten successful projects of equal magnitude over five years; and steel erectors with equivalent qualifications. Bolted connections require A325SC or A490SC slip-critical bolts for moment connections and A325N or A490N bearing-type bolts for other connections, with domestic fasteners mandated. The contractor must submit shop drawings for concrete reinforcement and structural steel with minimum fifteen working days review time, notify the Contracting Officer 48 hours before concrete pours, and submit fabricator/erector credentials within 48 hours of bid. An independent testing laboratory is required to perform testing of concrete, welding, and structural materials in accordance with ACI 301, AWS D1.1, and project specifications.
View the file
Other files
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1.0. CODES AND STANDARDS:
1.1. 2021 INTERNATIONAL BUILDING CODE NEW JERSEY EDITION INCLUDING ALL SUBSEQUENT
SUPPLEMENTS AND AMENDMENTS THERETO.
1.2. "MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER STRUCTURES", AMERICAN
SOCIETY OF CIVIL ENGINEERS, ASCE 7-16.
1.3. "SPECIFICATIONS FOR STRUCTURAL STEEL BUILDINGS", PUBLICATION 360-16 BY THE
AMERICAN INSTITUTE OF STEEL CONSTRUCTION, AND AS AMENDED IN SPECIFICATIONS.
1.4. "SEISMIC PROVISIONS FOR STRUCTURAL STEEL BUILDINGS", PUBLICATION 341-16 BY
THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION.
1.5. "STRUCTURAL WELDING CODE - STEEL (AWS D1.1-18)" AND "STRUCTURAL WELDING
CODE REINFORCING STEEL (AWS D1.4-18)", AMERICAN WELDING SOCIETY.
1.6 "BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE (ACI 318-19)",
AMERICAN CONCRETE INSTITUTE AND ALL SUCCEEDING REVISIONS.
2.0. SPECIFICATIONS:
2.1. THE STRUCTURAL GENERAL NOTES ARE NOT A SUBSTITUTE OR A REPLACEMENT
FOR THE PROJECT SPECIFICATIONS. THESE NOTES ARE INTENDED AS A GUIDE TO
THE DESIGN AND/OR CONSTRUCTION REQUIREMENTS ESTABLISHED FOR THIS PROJECT.
NO CONTRACTOR SHOULD ATTEMPT TO DESIGN, BID, OR CONSTRUCT ANY PORTION OF
THE WORK HEREIN WITHOUT CONSULTING THE PROJECT SPECIFICATIONS. WHERE
CONFLICTS OCCUR BETWEEN THESE NOTES AND THE SPECIFICATIONS, THE MORE
STRINGENT REQUIREMENT SHALL APPLY UNLESS A WRITTEN CLARIFICATION IS
ISSUED BY THE COR.
2.2. CONTRACTOR AND STRUCTURAL STEEL FABRICATOR SHOULD ACQUAINT THEMSELVES WITH
THE REQUIREMENTS FOR DOMESTICALLY PRODUCED BOLTS AND FOR STEEL CONNECTION
DESIGN REQUIREMENTS, INCLUDING SIGNED AND SEALED SHOP DRAWINGS AND
CONNECTION DESIGN CALCULATIONS, NOTED HEREIN AND IN THE STRUCTURAL STEEL
SPECIFICATIONS. REQUIREMENTS ARE MANDATORY. REFER TO SPECIFICATION
SECTION 051200 "STRUCTURAL STEEL"
2.3. STRUCTURAL STEEL SHALL BE FABRICATED BY A QUALIFIED FABRICATOR WHO PARTICIPATES
IN THE AISC CERTIFICATION PROGRAM AND IS DESIGNATED AS AN AISC CERTIFIED
PLANT "STANDARD FOR STEEL BUILDING STRUCTURES (STD)" AND THE STRUCTURAL
STEEL FABRICATOR MUST DEMONSTRATE A CONSISTENT RECORD OF AT LEAST TEN (10)
SUCCESSFUL PROJECTS OF EQUAL OR GREATER MAGNITUDE OVER THE PRECEDING FIVE
(5) YEARS. CONTRACTOR SHALL SUBMIT EVIDENCE TO THE ARCHITECT VERIFYING
HIS PROPOSED FABRICATOR'S COMPLIANCE. FABRICATOR'S CREDENTIALS MUST BE IN
COMPLIANCE WITHIN 48 HOURS OF BID.
2.4. STRUCTURAL STEEL SHALL BE ERECTED BY A QUALIFIED INSTALLER WHO MUST
DEMONSTRATE A CONSISTENT RECORD OF AT LEAST TEN (10) SUCCESSFUL
PROJECTS OF EQUAL OR GREATER MAGNITUDE OVER THE PRECEDING FIVE (5) YEARS.
CONTRACTOR SHALL SUBMIT EVIDENCE TO THE ARCHITECT VERIFYING HIS ERECTOR'S
COMPLIANCE. ERECTOR'S CREDENTIALS MUST BE IN COMPLIANCE WITHIN 48 HOURS OF BID.
3.0. DESIGN LOADS:
3.1. SUPERIMPOSED GRAVITY LOADS:
AREA LIVE LOAD DEAD LOAD
MECHANICAL AREAS 150 PSF -
SLAB ON GRADE 200 PSF -
LIVE LOADS ARE REDUCED IN CONFORMANCE WITH ASCE 7-16
SECTION 4.8 "REDUCTION IN LIVE LOADS"
3.2. SEISMIC LOADS:
RISK CATEGORY IV
RISK IMPORTANCE FACTOR "IE" 1.50
SITE SOIL CLASSIFICATION D (ASSUMED)
MAPPED SPECTRAL RESPONSE "Ss/S1" 0.258g/0.056g DESIGN SPECTRAL RESPONSE "Sds/Sd1" 0.274g/0.090g
SEISMIC DESIGN CATEGORY C
THE WORK IN THIS PROJECT WILL NOT IMPACT THE EXISTING SEISMIC
RESISTANCE CAPACITY.
3.3. WIND LOADS PER ASCE 7-16:
BASIC WIND SPEED (3-SECOND GUST) 126 MPH
RISK CATEGORY IV
ASCE 7 EXPOSURE CATEGORY B
THE WORK IN THIS PROJECT WILL NOT IMPACT THE EXISTING WIND
RESISTANCE CAPACITY.
6.0. REINFORCING STEEL:
6.1. REINFORCING SHALL BE DOMESTIC NEW BILLET STEEL CONFORMING TO ASTM A615,
GRADE 60 OR 60S INCLUDING STIRRUPS AND TIES, EXCEPT THAT REINFORCING WHICH
IS REQUIRED TO BE WELDED SHALL CONFORM TO ASTM A706.
6.2. FIELD BENDING OF CONCRETE REINFORCING STEEL IS NOT PERMITTED WITHOUT
WRITTEN APPROVAL OF THE COR.
6.3. WELDED WIRE REINFORCING SHALL CONFORM TO ASTM A1064.
6.4. ALL REINFORCING SHALL BE DETAILED, FABRICATED AND PLACED IN ACCORDANCE
WITH ACI SP-66 "ACI DETAILING MANUAL - 2004" AND THE "CRSI MANUAL OF
STANDARD PRACTICE", LATEST EDITION.
6.5. MINIMUM CONCRETE COVER OVER REINFORCING SHALL BE U.N.O.:
A. UNFORMED SURFACE CAST AGAINST EARTH........................ 3 IN.
B. FORMED SURFACE EXPOSED TO EARTH/WEATHER.................... 2 IN.
C. FORMED SLABS AND WALLS NOT EXPOSED TO
EARTH/WEATHER FOR #11 AND SMALLER BAR.................... 3/4 IN.
D. ALL OTHER FORMED ELEMENTS NOT EXPOSED
TO EARTH/WEATHER....................................... 1-1/2 IN.
6.6. DEVELOPMENT LENGTHS AND LAP SPLICES SHALL BE IN ACCORDANCE WITH
ACI 318 CHAPTER 25 AS INDICATED BELOW AND AS INDICATED ON THE DRAWINGS.
WHERE SPLICES ARE NOT CALLED OUT ON THE DRAWINGS, USE CLASS "B". THE BASIC
DEVELOPMENT LENGTH (LD) IS SHOWN AS A MULTIPLE OF THE BAR DIAMETER (DB) IN
THE TABLE BELOW. THE TENSION DEVELOPMENT LENGTHS SHALL BE MULTIPLIED
BY EACH OF THE APPLICABLE FACTORS IN PARAGRAPH "C" AS INDICATED FOR TENSION.
THE COMPRESSION DEVELOPMENT LENGTHS DO NOT REQUIRE ANY MODIFICATION. THE
COMPRESSION LAP SPLICE LENGTH IS NOTED IN PARAGRAPH "C". FINAL LENGTHS SHALL
BE ROUNDED UP TO THE NEAREST WHOLE INCH.
A. TWO TENSION DEVELOPMENT LENGTH CASES ARE NOTED IN THE TABLE BELOW. THESE
TWO CASES ADDRESS CONDITIONS OF MINIMUM BAR SPACING AND MINIMUM CLEAR
CONCRETE COVER. BOTH SPACING AND COVER MUST COMPLY IN SELECTING CASE 1 OF
THE TENSILE DEVELOPMENT LENGTH. WHERE THERE IS ANY QUESTION OF SPACING OR
COVER THE LARGER DEVELOPMENT LENGTH (CASE 2) SHALL BE USED.
CASE 1: BAR SPACING GREATER THAN 2DB AND CLEAR COVER GREATER THAN DB
CASE 2: BAR SPACING EQUAL/LESS THAN 2DB OR CLEAR COVER EQUAL/LESS THAN DB
B. DEVELOPMENT LENGTHS (LD) FOR REINFORCING FY = 60 KSI:
F'C COMPRESSION TENSION
PSI ALL CASES CASE 1 CASE 2
4500 19 DB 48 DB 72 DB
C. DEVELOPMENT LENGTH MODIFIERS: MULTIPLICATION FACTORS APPLY TO
THE BASIC "LD" INDICATED ABOVE AND ARE CUMULATIVE OVER EACH OF THE
REQUIREMENTS NOTED BELOW.
I. COMPRESSION: CLASS "C" LAP SPLICE REQUIREMENT.......... 30 DB
II. TENSION: CLASS "A" LAP SPLICE REQUIREMENT (EQUALS LD).... 1.0
III. TENSION: CLASS "B" LAP SPLICE REQUIREMENT................ 1.3
IV. TENSION: TOP BARS WITH > 12" OF CONCRETE BELOW........... 1.3
V. TENSION: BARS SMALLER THAN #7............................ 0.8
6.7. A CLASS "B" SPLICE IS REQUIRED WHEREVER ALL REINFORCING BARS CROSSING
A SECTION ARE SPLICED.
6.8. REINFORCING BARS SHALL BE WELDED ONLY WHERE SHOWN ON THE STRUCTURAL
DRAWINGS AND WELDS SHALL BE IN ACCORDANCE WITH THE "STRUCTURAL WELDING
CODE - REINFORCING STEEL" (AWS D1.4). NO OTHER REINFORCING MAY BE WELDED
WITHOUT THE APPROVAL OF THE COR. TACK WELDING OF ANY
REINFORCING IS STRICTLY PROHIBITED.
6.9. WELDED WIRE MAT/FABRIC SHALL BE LAPPED 1'-0" AT ALL SPLICES.
6.10. ALL REINFORCING TERMINATING AT THE TOPS OF COLUMNS AND PILASTERS SHALL
BE HOOKED, U.N.O.
6.11. SUBMIT SHOP DRAWINGS FOR FABRICATION, BENDING, AND PLACEMENT OF CONCRETE
REINFORCEMENT. COMPLY WITH ACI DETAILING MANUAL (SP-66) SHOWING BAR
SCHEDULES, STIRRUP SPACING, DIAGRAMS OF BENT BARS, ARRANGEMENT OF CONCRETE
REINFORCEMENT. INCLUDE SPECIAL REINFORCEMENT REQUIRED AT OPENINGS THROUGH
CONCRETE STRUCTURES. INCLUDE ALL ACCESSORIES SPECIFIED/REQUIRED TO
SUPPORT REINFORCING. THE SHOP DRAWING SHOULD INCLUDE ELEVATIONS OF ALL WALLS.
6.12. SHOP DRAWINGS SHALL BE REVIEWED BY THE CONTRACTOR PRIOR TO SUBMISSION
AND SHALL BEAR THE CONTRACTOR'S APPROVAL STAMP ACCEPTING RESPONSIBILITY
FOR DIMENSIONS, QUANTITIES AND COORDINATION WITH THE OTHER TRADES.
6.13. DRAWINGS MAY BE ELECTRONICALLY SUBMITTED, PROVIDED LEGIBILITY IS MAINTAINED.
REVIEW COMMENTS ONLY WILL BE ELECTRONICALLY FORWARDED TO THE CONTRACTOR.
6.14. CONTRACTOR SHALL PROVIDE IN HIS SCHEDULE FOR A SHOP DRAWING REVIEW AND
RETURN TIME OF A MINIMUM OF FIFTEEN (15) WORKING DAYS IN THE STRUCTURAL
ENGINEER'S OFFICE.
6.15. CONTRACTOR SHALL NOTIFY THE COR A MINIMUM OF 48 HOURS
PRIOR TO ALL CONCRETE POURS IN ORDER TO PERMIT REINFORCING STEEL REVIEW
IF REQUIRED BY THE COR.
5.0. CONCRETE:
5.1. CONCRETE SHALL HAVE 28-DAY COMPRESSIVE STRENGTHS AND DENSITIES AS FOLLOWS:
ELEMENT/MEMBER STRENGTH F'C DENSITY WC
EXTERIOR CONCRETE OR CONCRETE
EXPOSED TO WEATHER 4.5 KSI 145 PCF
5.2. CONCRETE MIX DESIGNS:
A. SUBMITTALS: SUBMIT WRITTEN REPORTS OF EACH PROPOSED CONCRETE MIX NOT
LESS THAN 15 DAYS PRIOR TO THE START OF WORK. DESIGN MIXES PREPARED
MORE THAN TWENTY-FOUR (24) MONTHS PRIOR TO THE DATE OF THE SUBMITTAL ARE
NOT PERMITTED.
B. MIX DESIGNS, INCLUDING W/C RATIOS AND SLUMPS, SHALL BE PREPARED IN
ACCORDANCE WITH THE MOST CURRENT ACI 301 CHAPTER 4, EXCEPT WHERE
NOTED OTHERWISE IN THE PROJECT SPECIFICATIONS. CEMENT SHALL CONFORM TO
ASTM C 150 TYPE I OR AT CONTRACTOR'S OPTION, ASTM C 595 TYPE IP WHERE
FLY ASH IS PERMITTED IN ACCORDANCE WITH THE SPECIFICATIONS. NORMAL
WEIGHT AGGREGATE SHALL CONFORM TO ASTM C 33 AND LIGHT WEIGHT AGGREGATE
SHALL CONFORM TO ASTM C 330. NO ADMIXTURES CONTAINING CALCIUM CHLORIDE
SHALL BE PERMITTED IN ANY CONCRETE.
C. AGGREGATE SIZES SHALL BE:
FORMED CONCRETE ELEMENTS, U.N.O. #67 STONE (3/4" MAX.)
D. WATER REDUCING ADMIXTURE SHALL BE USED IN ALL CONCRETE.
E. AIR ENTRAINING ADMIXTURE IN ACCORDANCE WITH ACI 301 TABLE 4.4.1.
SHALL BE USED IN ALL CONCRETE EXPOSED TO FREEZING AND THAWING DURING
CONSTRUCTION OR SERVICE CONDITIONS.
F. WATER/CEMENT RATIO SHALL NOT EXCEED 0.45 FOR ANY CONCRETE SUBJECTED TO
FREEZING/THAWING.
G. ALL PUMPED CONCRETE SHALL HAVE A WATER/CEMENT RATIO LESS THAN 0.50 AND
SHALL CONTAIN A HIGH RANGE WATER REDUCING ADMIXTURE (SUPERPLASTICIZER).
H. IN NO CASE SHALL A WATER/CEMENT RATIOS EXCEED THE FOLLOWING:
F'C 4500 PSI 0.42 MAX. W/C RATIO
5.3. CURING:
A. LIQUID MEMBRANE CURING COMPOUND WITH A MINIMUM 30% SOLIDS CONTENT SHALL
BE APPLIED WITHIN TWO (2) HOURS AFTER COMPLETION OF FINISHING TO ALL
CONCRETE FLATWORK AND WALLS, U.N.O., OTHER THAN FOOTINGS AND GRADE BEAMS.
B. FLOORS IN AREAS RECEIVING QUARRY TILE, CERAMIC TILE AND LIQUID FLOOR
HARDENER SHALL BE CURED WITH SPECIFIED DISSIPATING LIQUID MEMBRANE
CURING COMPOUND OR WET CURED BY USE OF MOISTURE RETAINING COVER.
DISSIPATING CURING COMPOUND SHALL BE THOROUGHLY BROOMED AND WASHED
OFF PRIOR TO APPLICATION OF FLOOR FINISH.
5.4. WHEN COLD WEATHER CONDITIONS EXIST, PLACE AND CURE CONCRETE IN ACCORDANCE
WITH ACI 306 "COLD WEATHER CONCRETING". WHERE USE IS DESIRED, SUBMIT FOR
ENGINEER'S APPROVAL A NON-CORROSIVE, NON-CHLORIDE, ACCELERATING ADMIXTURE
FOR CONCRETE EXPOSED TO TEMPERATURES BELOW 40 DEGREES. UNIFORMLY HEAT WATER
AND AGGREGATES TO A TEMPERATURE OF NOT LESS THAN 50 DEGREES.
5.5. WHEN HOT WEATHER CONDITIONS EXIST, PLACE AND CURE CONCRETE IN ACCORDANCE
WITH ACI 305 "HOT WEATHER CONCRETING". COOL MATERIALS BEFORE MIXING TO
MAINTAIN CONCRETE PLACEMENT TEMPERATURE BELOW 90 DEGREES.
5.6. ALL CONSTRUCTION JOINTS SHOWN ON THE DRAWINGS SHALL BE INCORPORATED INTO
THE STRUCTURE UNLESS THE STRUCTURAL ENGINEER APPROVES THEIR ELIMINATION.
5.7. ADDITIONAL CONSTRUCTION JOINTS, REQUIRED TO FACILITATE CONSTRUCTION, ARE
SUBJECT TO THE APPROVAL OF THE STRUCTURAL ENGINEER AND MAY REQUIRE
ADDITIONAL REINFORCING. SUCH JOINTS SHALL BE CLEARLY DETAILED ON THE SHOP
DRAWINGS AND ALL REINFORCING SHALL PASS CONTINUOUSLY THROUGH THE JOINT.
5.8. REINFORCING IN ALL ABUTTING CONCRETE, INCLUDING FOOTINGS, SHALL BE
CONTINUOUS THROUGH OR AROUND ALL CORNERS OR INTERSECTIONS. DOWELS OR
SPLICES SHALL BE EQUAL IN SIZE AND SPACING TO THE REINFORCING IN THE
ABUTTING MEMBERS.
5.9. REFER TO ARCHITECTURAL DRAWINGS FOR DOOR AND WINDOW OPENINGS, DRIPS,
REGLETS, WASHES, MASONRY ANCHORS, BRICK LEDGE ELEVATIONS, SLAB DEPRESSIONS
AND MISCELLANEOUS EMBEDDED PLATES, BOLTS, ANCHORS, ANGLES, ETC.
5.10. REFER TO ARCHITECTURAL DRAWINGS FOR CONCRETE FINISHES. WHERE FINISH IS
NOT SPECIFIED, CONFORM TO REQUIREMENTS OF ACI 301.
5.11. REFER TO PLUMBING, MECHANICAL AND ELECTRICAL DRAWINGS FOR UNDERFLOOR,
PERIMETER AND OTHER DRAINS AND FOR SLEEVES, OUTLET BOXES, CONDUIT, ANCHORS,
ETC. THE VARIOUS TRADES ARE RESPONSIBLE FOR THEIR ITEMS.
5.12. BASE PLATES, ANCHOR BOLTS, SUPPORT ANGLES AND OTHER STEEL EXPOSED TO EARTH
OR GRANULAR FILL SHALL BE COVERED WITH A MINIMUM OF 3" OF CONCRETE.
5.13. FILL SLABS, NOT SHOWN ON THE STRUCTURAL DRAWINGS, SHALL BE REINFORCED WITH
A MINIMUM OF 6X6-W1.4XW1.4 WWM UNLESS NOTED OTHERWISE ON OTHER DRAWINGS
OR IN THE SPECIFICATIONS.
5.14. FINISHING TOLERANCE SHALL BE WITHIN CLASS B IN ACCORDANCE WITH ACI 301
AND CONSIDERATION SHALL BE GIVEN TO SEQUENCING OF CONCRETE PLACEMENT TO
FACILITATE CONTROL OF FINISH ELEVATIONS.
5.15. NON-SHRINK GROUT SHALL BE PRE-MIXED, NON-CORROSIVE, NON-METALLIC,
NON-STAINING CONTAINING SILICA SANDS, PORTLAND CEMENT, SHRINKAGE
COMPENSATING AND WATER REDUCING AGENTS. PRODUCT SHALL ONLY REQUIRE THE
ADDITION OF WATER. MINIMUM COMPRESSIVE STRENGTH SHALL BE 2500 PSI AFTER
ONE DAY AND 7000 PSI AFTER 28 DAYS. GROUT SHALL BE FREE OF GAS PRODUCING
OR AIR RELEASING AND OXIDIZING AGENTS AND CONTAIN NO CORROSIVE IRON,
ALUMINUM OR GYPSUM.
5.16. TOLERANCE FOR ANCHOR BOLTS AND OTHER EMBEDDED ITEMS SHALL BE PER THE
AISC CODE OF STANDARD PRACTICE SECTION 7.5.
5.17. UNLESS OTHERWISE SHOWN IN THE ARCHITECTURAL DRAWINGS, PROVIDE 3/4" CHAMFERS
AT ALL COLUMN, WALL, SLAB OR BEAM EDGES THAT ARE EXPOSED TO VIEW IN THE
FINISHED STRUCTURE.
7.0. STRUCTURAL STEEL:
7.1. ALL STRUCTURAL STEEL SHALL BE OF THE GRADES INDICATED BELOW, UNLESS NOTED
OTHERWISE ON PLANS OR DETAILS:
A. WIDE FLANGE SHAPES ASTM A992 GR50.
B. OTHER ROLLED SHAPES ASTM A36 TYPICALLY, U.N.O.
C. ANCHOR BOLTS ASTM F1554 GR36 U.N.O.
D. STRUCTURAL TUBING (SQUARE AND RECTANGULAR) ASTM A500, GRADE B, FY=46 KSI.
E. STRUCTURAL TUBING (ROUND) ASTM A500, GRADE B, FY=42 KSI.
F. PLATES AND BARS ASTM A36 U.N.O.
G. MISCELLANEOUS ASTM A36 U.N.O.
7.2. ALL STRUCTURAL STEEL SHALL BE DETAILED AND, FABRICATED IN ACCORDANCE WITH
THE AISC CODE OF STANDARD PRACTICE AS MODIFIED IN THESE NOTES AND THE
PROJECT SPECIFICATIONS.
7.3. SUBMIT SHOP DRAWINGS FOR DETAILS, FABRICATION, AND ERECTION OF STRUCTURAL
STEEL. COMPLY WITH AISC "STEEL CONSTRUCTION MANUAL", AISC "DETAILING FOR
STEEL CONSTRUCTION", AND AISC "ENGINEERING FOR STEEL CONSTRUCTION"
PUBLICATIONS.
7.4. SHOP DRAWINGS SHALL BE REVIEWED BY THE CONTRACTOR PRIOR TO SUBMISSION.
DRAWINGS SHALL BEAR THE CONTRACTOR'S APPROVAL STAMP ACCEPTING
RESPONSIBILITY FOR DIMENSIONS, QUANTITIES AND COORDINATION WITH THE OTHER
TRADES.
7.5. DRAWINGS MAY BE ELECTRONICALLY SUBMITTED, PROVIDED LEGIBILITY IS MAINTAINED.
REVIEW COMMENTS ONLY WILL BE ELECTRONICALLY FORWARDED TO THE CONTRACTOR.
7.6. CONTRACTOR SHALL PROVIDE IN HIS SCHEDULE FOR A SHOP DRAWING REVIEW AND
RETURN TIME OF A MINIMUM OF FIFTEEN (15) WORKING DAYS IN THE STRUCTURAL
ENGINEER'S OFFICE.
7.7. CONNECTION DESIGN: SEE SPECIFICATIONS FOR SPECIFIC REQUIREMENTS.
A. FABRICATOR IS RESPONSIBLE FOR THE DESIGN OF CONNECTIONS NOT DESIGNED
ON THE STRUCTURAL DRAWINGS.
B. ALL CONNECTIONS SHALL BE DESIGNED BY A PROFESSIONAL ENGINEER REGISTERED
IN THE STATE WHERE THE PROJECT IS LOCATED. SHOP DRAWING CONTAINING
CONNECTION DESIGNS SHALL BE SIGNED AND SEALED. A NOTE INDICATING
"CONNECTION DESIGN ONLY" SHOULD ACCOMPANY THE SEAL. FABRICATOR SHALL
SUBMIT SIGNED AND SEALED CALCULATIONS FOR ALL CONNECTIONS DESIGNED AS
PART OF HIS WORK AND APPEARING ON HIS SHOP DRAWINGS.
C. GENERALLY, CONNECTIONS SHOWN ON THE DRAWINGS ARE SCHEMATIC AND ARE
INTENDED TO SHOW THE RELATIONSHIP OF THE MEMBERS.
D. CONNECTIONS SHALL BE DESIGNED FOR THE REACTIONS AS SHOWN ON THE DRAWINGS,
WITH A MINIMUM REACTION OF 10 KIPS. IF NO REACTION IS SHOWN ON PLAN, DESIGN
CONNECTIONS FOR ONE-HALF (1/2) THE MAXIUMUM TOTAL UNIFORM LOAD ON THE MEMBER,
AS DEFINED IN TABLE 3-6, "MAXIUMUM TOTAL UNIFORM LOAD" IN THE AISC "SPECIFICATIONS
FOR STRUCTURAL STEEL BUILDINGS", PUBLICATION 360-16.
E. MEMBER FORCES AND REACTIONS HAVE BEEN REDUCED IN CONFORMANCE TO CODE
PROVISIONS RELATED TO COMBINATIONS OF LOADS THAT INCLUDE WIND AND SEISMIC
FORCES. NO FURTHER REDUCTIONS IN FORCES OR INCREASES IN ALLOWABLE STRESSES
ARE PERMITTED.
F. CONNECTIONS SHOWN ON DRAWINGS ARE ULTIMATE (LRFD) LOAD REACTIONS.
G. CONNECTIONS MAY BE BOLTED OR WELDED, U.N.O. ON THE DRAWINGS.
7.8. BOLTED CONNECTIONS:
A. SLIP CRITICAL CONNECTIONS WITH A325SC OR A490SC BOLTS SHALL BE USED IN ALL
BOLTED MOMENT PLATE CONNECTIONS. OVERSIZED OR LONG-SLOTTED HOLES ARE
PERMITTED.
B. BEARING-TYPE CONNECTIONS WITH A325N OR A490N BOLTS SHALL BE USED FOR ALL OTHER
BOLTED CONNECTIONS. OVERSIZED AND LONG-SLOTTED HOLES ARE NOT PERMITTED U.N.O.
IN SINGLE TAB PLATE CONNECTIONS ONLY BEARING-TYPE FASTENERS ARE PERMITTED,
FASTENERS SHALL NOT BE TORQUED, AND SHORT SLOTTED HOLES ARE REQUIRED.
C. ANCHOR BOLTS OR OTHER BOLTS, WHERE INDICATED, SHALL CONFORM TO ASTM
F1554 GR36 U.N.O.
D. PROTRUDING BOLT HEADS, SHAFTS OR NUTS SHALL NOT EXTEND NOR PROHIBIT
THE APPLICATION OF ARCHITECTURAL FINISHES OR PLACEMENT OF STEEL DECK
AT ITS CORRECT LOCATION AND ELEVATION.
E. CONNECTION DESIGNER IS RESPONSIBLE FOR VERIFYING THE AXIAL CAPACITY
AFTER A SECTION IS REDUCED FOR BOLT HOLES. MEMBER SIZE MAY BE
INCREASED OR PLATES ADDED TO MAINTAIN REQUIRED CAPACITY.
F. SHOP DRAWINGS SHALL INDICATE THE TYPE OF BOLT USED IN EACH CONNECTION,
ALLOWABLE VALUES FOR THE VARIOUS BOLT TYPES AND CAPACITY OF EACH CONNECTION
SHOWN.
G. DOMESTIC FASTENERS (AMERICAN OR CANADIAN) ARE REQUIRED IN ALL
STRUCTURAL STEEL WORK ON THIS PROJECT. IMPORTED FASTENERS ARE
PROHIBITED.
7.9. WELDED CONNECTIONS:
A. ALL WELDING SHALL BE IN ACCORDANCE WITH THE "STRUCTURAL WELDING CODE
- STEEL" (AWS D1.1) OF THE AMERICAN WELDING SOCIETY.
B. ELECTRODES FOR WELDING SHALL COMPLY WITH THE REQUIREMENTS OF AWS
D1.1 TABLE 4.1.1.
C. SHOP DRAWINGS SHALL INDICATE WELD TYPE, REQUIRED ELECTRODES AND
CAPACITY FOR EACH CONNECTION DETAILED ON THE SHOP DRAWINGS.
D. PERFORM VISUAL INSPECTIONS OF ALL WELDS.
E. PERFORM NON-DESTRUCTIVE TESTS OF WELDS AS FOLLOWS:
1. PARTIAL PENETRATION WELDS - ONE SPOT TEST PER WELD USING MAGNETIC PARTICLE
TESTING TECHNIQUES.
2. FULL PENETRATION WELDS - TEST ENTIRE LENGTH OF ALL WELDS.
USE RADIOGRAPHIC OR ULTRASONIC TESTING TECHNIQUES.
7.10. WHERE CANTILEVER BEAMS OCCUR ON PLAN AND THE SIZE IS NOTED ONLY FOR THE
BACK-SPAN, THE CANTILEVER IS INTENDED TO BE THE SAME SIZE AS THE BACK-SPAN.
7.11. SPLICING OF STEEL MEMBERS, UNLESS SHOWN ON THE DRAWINGS, IS PROHIBITED
WITHOUT WRITTEN APPROVAL OF THE COR.
7.12. NO CHANGE IN SIZE OR POSITION OF ANY STRUCTURAL ELEMENT NOR HOLES, SLOTS, CUTS, ETC. SHALL BE MADE UNLESS DETAILED AND NOTED AS A PROPOSED CHANGE ON THE SHOP
DRAWINGS AND REVIEWED AND ACCEPTED BY THE STRUCTURAL ENGINEER.
7.13. NO FINAL BOLTING OR WELDING SHALL BE PERFORMED UNTIL AS MUCH OF THE
STRUCTURE AS WILL BE STIFFENED THEREBY HAS BEEN PROPERLY ALIGNED.
7.14. FABRICATE ALL BEAMS WITH MILL CAMBERS UP.
7.15. U.N.O. BEAMS ARE EQUALLY SPACED BETWEEN COLUMNS.
7.16. MINIMUM PLATE THICKNESS SHALL BE 3/8" U.N.O.; MINIMUM BOLT DIAMETER SHALL
BE 3/4" U.N.O.; MINIMUM SHOP WELD SHALL BE 3/16" AND MINIMUM FIELD WELD
SHALL BE 1/4" U.N.O.
7.17. ALL RE-ENTRANT CORNERS (SUCH AS COPES AND BLOCKS) SHALL BE CUT AND SHAPED
NOTCH FREE WITH A RADIUS OF AT LEAST 1/2".
7.18. FIELD USE OF GAS CUTTING TORCHES IS PROHIBITED FOR CORRECTING FABRICATION
ERRORS IN PRIMARY STRUCTURAL FRAMING.
7.19. PARAGRAPH 4.4.1 OF THE AISC CODE OF STANDARD PRACTICE SHALL BE SUPERSEDED
BY THE FOLLOWING: INDICATION OF COMPLIANCE BY THE
OWNER OF SHOP DRAWINGS PREPARED BY THE FABRICATOR INDICATES THAT THE
FABRICATOR HAS CORRECTLY INTERPRETED THE CONTRACT REQUIREMENTS. SUCH
INDICATION DOES NOT RELIEVE THE FABRICATOR OF THE RESPONSIBILITY ASSIGNED
TO HIM FOR THE DESIGN AND DETAILING OF CONNECTIONS ASSIGNED TO HIM, NOR
FOR THE ACCURACY OF DIMENSIONS ON THE SHOP DRAWINGS, NOR FOR GENERAL FIT
UP OF PARTS TO BE ASSEMBLED IN FIELD.
7.20. PARAGRAPHS 7.2 THROUGH 7.6 OF THE AISC CODE OF STANDARD PRACTICE SHALL BE
SUPERSEDED AS FOLLOWS: ALL REFERENCES TO "OWNER" SHALL BE REPLACED
WITH REFERENCES TO "CONTRACTOR".
7.21. EXPANSION BOLTS SHALL PROVIDE A MINIMUM SAFETY FACTOR OF FOUR (4) TIMES
THE FOLLOWING MINIMUM SERVICE LOAD CAPACITIES, U.N.O.
SLEEVE ANCHORS (2000 PSI MASONRY) WEDGE ANCHORS (3000 PSI CONCRETE)
DIA. SHEAR TENSION DIA. SHEAR TENSION
1/4" 270 LB. 300 LB. 1/2" 1950 LB. 1250 LB.
1/2" 930 LB. 600 LB. 3/4" 3750 LB. 2250 LB.
8.0. INSPECTION AND TESTING:
8.1. AN INDEPENDENT TESTING LABORATORY SHALL BE RETAINED IN ACCORDANCE WITH
THE PROJECT SPECIFICATIONS TO PERFORM TESTING OF FOUNDATION BEARING
STRATA, ENGINEERED FILLS, CONCRETE, GROUT, STEEL, AND WELDING. SEE
PROJECT SPECIFICATIONS FOR REQUIREMENTS.
8.2. THE CONTRACTOR, IN CONJUNCTION WITH THE TESTING LABORATORY AND IN
ACCORDANCE WITH THE PROJECT SPECIFICATIONS, SHALL DETERMINE THE FREQUENCY
OF THE TESTING NECESSARY TO INSURE THAT THE DESIGN REQUIREMENTS ARE
BEING MET.
8.3. THE TESTING AGENCY SHALL VERIFY THAT ALL WELDERS HAVE SATISFACTORILY
PASSED AWS QUALIFICATION TESTS FOR THE WELDS WHICH THEY WILL PERFORM.
8.4. THE CONTRACTOR AND TESTING AGENCY SHALL REQUIRE THAT AWS QUALIFICATION
TESTS FOR WELDING OF MATERIAL LESS THAN 1/8" IN THICKNESS ARE PASSED
BY WELDERS EXPECTED TO ERECT LIGHTGAGE FRAMING MATERIALS. THESE
TESTS ARE NOT THE SAME AS FOR MATERIALS 1/8" OR GREATER IN THICKNESS (I.E.
STRUCTURAL STEEL MATERIALS)
8.5. ALL WELDING SHALL BE INSPECTED AND TESTED IN ACCORDANCE WITH AWS D1.1 OR
D1.3 AS APPROPRIATE TO THE MATERIAL THICKNESS.
8.6. THE TESTING AGENCY SHALL VERIFY THAT THE METAL DECK IS ATTACHED TO THE
STRUCTURAL STEEL IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS AND
APPROVED SHOP DRAWINGS.
8.7. CONCRETE TESTING SHALL BE IN ACCORDANCE WITH ACI 301 CHAPTER 16 AND
APPROPRIATE AND WITH THE PROJECT SPECIFICATIONS.
9.0. CONSTRUCTION AND SAFETY:
9.1. THE CONTRACTOR IS SOLELY RESPONSIBLE FOR ALL SAFETY REGULATIONS, PROGRAMS
AND PRECAUTIONS RELATED TO ALL WORK ON THIS PROJECT.
9.2. THE CONTRACTOR IS SOLELY RESPONSIBLE FOR THE PROTECTION OF PERSONS AND
PROPERTY EITHER ON OR ADJACENT TO THE PROJECT AND SHALL PROTECT SAME
AGAINST INJURY, DAMAGE OR LOSS.
9.3. MEANS AND METHODS OF CONSTRUCTION AND ERECTION OF STRUCTURAL MATERIALS ARE
SOLELY THE CONTRACTOR'S RESPONSIBILITY.
9.4. STRUCTURAL DRAWINGS ARE INTENDED TO BE USED IN CONJUNCTION WITH THE
DRAWINGS OF OTHER CONSULTANTS AND TRADES. THE CONTRACTOR SHALL COORDINATE
THE VARIOUS REQUIREMENTS.
9.5. NO OPENINGS NOR ANY CHANGES IN SIZE, DIMENSION OR LOCATION SHALL BE MADE
IN ANY STRUCTURAL ELEMENTS WITHOUT WRITTEN APPROVAL OF THE STRUCTURAL
ENGINEER.
9.6. OPENINGS 1'-0" OR LESS ON A SIDE ARE GENERALLY NOT SHOWN ON THE STRUCTURAL
DRAWINGS. REFER TO DRAWINGS OF OTHER CONSULTANTS FOR SUCH OPENINGS.
9.7. FIREPROOFING OF STRUCTURAL ELEMENTS IS NOT SHOWN ON THE STRUCTURAL
DRAWINGS. REFER TO THE SPECIFICATIONS AND ARCHITECTURAL DRAWINGS FOR FIRE
RATING REQUIREMENTS, MATERIALS AND METHODS.
9.8. THE CONTRACTOR IS RESPONSIBLE FOR LIMITING THE AMOUNT OF CONSTRUCTION LOAD
IMPOSED ON THE STRUCTURE. SUCH LOADS SHALL NOT EXCEED THE CAPACITY OF THE
STRUCTURE AT ANY TIME.
9.9. THE STRUCTURE IS DESIGNED TO FUNCTION AS A UNIT UPON COMPLETION, AND ANY
TEMPORARY BRACING OR SUPPORT REQUIRED TO ACCOMMODATE THE CONTRACTOR'S
MEANS AND METHODS ARE THE RESPONSIBILITY OF THE CONTRACTOR.
9.10. THE CONTRACTOR SHALL INFORM THE COR, CLEARLY AND
EXPLICITLY IN WRITING, OF ANY DEVIATION OR SUBSTITUTION OF REQUIREMENTS
OF THE CONTRACT DOCUMENTS. CONTRACTOR IS NOT RELIEVED OF ANY REQUIREMENTS
OF THE CONTRACT DOCUMENTS BY VIRTUE OF THE STRUCTURAL ENGINEER'S REVIEW
OF SHOP DRAWINGS, PRODUCT DATA, ETC., UNLESS THE CONTRACTOR HAS CLEARLY
AND EXPLICITLY INFORMED THE COR IN WRITING OF ANY
DEVIATIONS OR SUBSTITUTIONS AT TIME OF SUBMISSION, AND THE STRUCTURAL
ENGINEER HAS GIVEN WRITTEN APPROVAL FOR THE SPECIFIC DEVIATIONS OR
SUBSTITUTIONS.
9.11. ALL THINGS WHICH, IN THE OPINION OF THE CONTRACTOR, APPEAR TO BE
DEFICIENCIES, OMISSIONS, CONTRADICTIONS OR AMBIGUITIES IN THE DRAWINGS OR
SPECIFICATIONS, SHALL BE BROUGHT TO THE ATTENTION OF THE STRUCTURAL
ENGINEER. CORRECTIONS OR WRITTEN INTERPRETATIONS SHALL BE ISSUED BEFORE
AFFECTED WORK MAY PROCEED.
9.12. IF THE CONTRACTOR CANNOT CONSTRUCT ANY PORTION OF THE WORK IDENTIFIED IN
THE DRAWINGS IN ACCORDANCE WITH THESE DRAWINGS AND SPECIFICATIONS, THEN
THE CONTRACTOR IS RESPONSIBLE FOR CONTACTING THE COR PRIOR
TO PROCEEDING WITH THE WORK. WORK THAT DOES NOT COMPLY WITH THE DRAWINGS
MAY REQUIRE REMOVAL, TESTING, OR ENGINEERING EVALUATION AT THE
CONTRACTOR'S EXPENSE.
9.13. CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS PRIOR TO ORDERING
MATERIALS OR PROCEEDING WITH NEW WORK IN AREAS AFFECTED BY EXISTING
CONDITIONS. COR SHALL BE INFORMED IN WRITING OF
CONFLICTS BETWEEN EXISTING AND PROPOSED NEW CONSTRUCTION.
9.14 CONTRACTOR IS RESPONSIBLE FOR COORDINATING ALL DIMENSIONS SHOWN ON THE
CONTRACT DOCUMENTS. INCONSISTENCIES ON THE STRUCTURAL DRAWINGS OR
BETWEEN THE STRUCTURAL DRAWINGS AND ANY OTHER CONTRACT, SHOP, FABRICATION,
OR OTHER DRAWINGS OR INFORMATION SHALL BE BROUGHT TO THE ATTENTION OF THE
COR PRIOR TO PROCEEDING WITH AFFECTED WORK.
9.15. DO NOT SCALE THESE DRAWINGS, USE THE DIMENSIONS SHOWN.
9.16. CONTRACTOR SHALL PROVIDE IN HIS SCHEDULE FOR A SHOP DRAWING REVIEW AND
RETURN TIME OF A MINIMUM OF FIFTEEN (15) WORKING DAYS IN THE STRUCTURAL
ENGINEER'S OFFICE.
9.17 FOR METAL STAIRS, PROVIDE A DELEGATED DESIGN SUBMITTAL INCLUDING
CALCULATIONS SIGNED AND SEALED BY A PROFESSIONAL ENGINEER LICENSED
IN THE STATE OF THE PROJECT. SHOP DRAWINGS REFLECTING THIS DESIGN
SHALL BE SUBMITTED WITH THE CALCULATIONS.
10.0 STRUCTURAL ABBREVIATIONS:
ABBREV. DEFINITION ABBREV. DEFINITION
A.B. ANCHOR BOLTS HOF HORIZONTAL OUTER FAC
ABV ABOVE HK HOOK
ADDNL ADDITIONAL HORZ HORIZONTAL
AFF ABOVE FINISHED FLOOR IF INNER FACE
ALT ALTERNATE INT INTERIOR
ARCH ARCHITECTURAL JT JOINT
B, BOT BOTTOM K KIPS (1000 LBS)
B/XXX BOTTOM OF XXX L, LEN LENGTH
BAL. BALANCE LAT LATERAL
BB BOND BEAM LBS POUNDS
BCX BOTTOM CHORD EXTENSION LE LEFT END
BL BRICK LEDGE LLH LONG LEG HORIZONTAL
BLDG BUILDING LLO LONG LEG OUTSTANDING
BLW BELOW LLV LONG LEG VERTICAL
BM BEAM LONG LONGITUDINAL
BRG BEARING MAS MASONRY
BRK BRICK MAX MAXIMUM
BTWN BETWEEN MECH MECHANICAL
CFMF COLD-FORMED METAL FRAMING MFR MANUFACTURER
CJ CONST., CONTROL JOINT MIN MINIMUM
CL,CLR CLEAR MTL METAL
CMU CONC. MASONRY UNIT NOM NOMINAL
COL COLUMN OC, O/C ON CENTER
CONC CONCRETE OF OUTER FACE, OPP. FACE
CONN CONNECTION OH OPPOSITE HAND
CONST CONSTRUCTION OPP OPPOSITE
CONT CONTINUOUS OPNG OPENING
CTR CENTER PC PRECAST
CTRD CENTERED PL PLATE
DBA DEFORMED BAR ANCHOR RE RIGHT END
DET,DTL DETAIL REINFG REINFORCING
DIM DIMENSION REINF REINFORCEMENT
DK DECK REQD REQUIRED
DWGS DRAWINGS RET RETAINING
DWL DOWEL SOG SLAB ON GRADE
EA EACH SC SLIP CRITICAL
EE EACH END SCHED SCHEDULE
EF EACH FACE SECT SECTION
EFF EFFECTIVE S, SHRT SHORT
EJ EXPANSION JOINT SL SLAB
EL,ELEV ELEVATION SPA SPACING
EOC EDGE OF CONCRETE STFNR STIFFENER
EOD EDGE OF DECK STL STEEL
EOM EDGE OF MASONRY SUPPL SUPPLIER
EOS EDGE OF SLAB SUPT SUPPORT
ES EACH SIDE T TOP
EW EACH WAY T/XXX TOP OF XXX
EXIST EXISTING TCX TOP CHORD EXTENSION
EXP EXPANSION THK THICK, THICKNESS
EXT EXTERIOR, EXTENSION TO THROUGHOUT
FK FOOT-KIPS TRAN TRANSVERSE
FL, FLR FLOOR TYP TYPICAL
FOB FACE OF BRICK UNO UNLESS NOTED OTHERWISE
FOM FACE OF MASONRY VERT VERTICAL
FOS FACE OF STUD VEF VERTICAL EACH FACE
FP FULL PENETRATION VIF VERTICAL INNER FACE
FS FOOTING STEP VOF VERTICAL OUTER FACE
FT FOOT, FEET W WIDE, WIDTH
FTG FOOTING WWF WELDED WIRE FABRIC
GB GRADE BEAM WWM WELDED WIRE MAT
GEN GENERAL XE EXTENDED END JOIST
HEF HORIZONTAL EACH FACE
HIF HORIZONTAL INNER FACE
1435 W. Morehead St.
Suite 140 Charlotte, NC 28208
(704) 522-0495 www.brittpeters.com BPA Project No. 21240
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTSOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10720 SIKES PLACE, SUITE 100
CHARLOTTE, NC 28277
P 704.814.1320 F 704.321.0833
HDG PROJECT: 21009
COPYRIGHT © 2025 HARRELL DESIGN GROUP, PC
A u to d e s k D o c s /B
P A
C o lla b o ra te
R
/2
S
T R
U V
A M
C L y o n s R
.r v t
/1
/2
:5
:1
A
M
S0.01
STRUCTURAL GENERAL NOTES,
AND ABREVIATIONS
CORRECT FCA
D & F DEFICIENCIES
BOILER PLANT
LYONS VA MEDICAL CENTER, LYONS, NJ
561A4-18-113
APRIL 11, 2025 MSR JACRevisions: Date:
EXISTING
PULLBOX
EXISTING
PANEL C
EXISTING
ATS 14TS1
PANEL
BOARD
EMDP
EXISTING
ATS 14MTS1
PANEL
BOARD
PANEL
BOARD B
PANEL
BOARD A
ATS
14-MTS2
ATS
14-TS2
PANELBOARD
PANEL
BOARD
UP
UP
UP
UP
BREAK ROOM
I.T.
TOILET
LOCKERS
GAS
VALVE
ROOM/
STORAGE
ELEC. RM.
TO
ADJOINING
BUILDING
EXISTING EMERGENCY
SWITCHBOARD
BASEMENT
B01 B02
B03
MECHANICAL
B04
B05
B06
B07
ENTRY
B08
B09
EXISTING NORMAL
SWITCHBOARD
LOUVER
-12'
-12'
-12'
7" HIGH
CONC PAD
6" HIGH
CONC
PAD
6" HIGH
CONC PAD
4" HIGH
CONC
PAD
-10'-8"
-9'
6" HIGH
CONC PAD
C1
S3.01
C3
S3.01
C1
S3.01
C3
S3.01
EXISTING FLOOR SLAB TO
BE REMOVED PRIOR TO
NEW CONC REPAIR
1 2 3 4 5 6 7 8
A
B
C
D
A.9
B.9
C.9
NEW HSS 5x5x5/16 POST. REF
FOR BASE PLATE
F3/S3.01
1435 W. Morehead St.
Suite 140 Charlotte, NC 28208
(704) 522-0495 www.brittpeters.com BPA Project No. 21240
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTSOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10720 SIKES PLACE, SUITE 100
CHARLOTTE, NC 28277
P 704.814.1320 F 704.321.0833
HDG PROJECT: 21009
COPYRIGHT © 2025 HARRELL DESIGN GROUP, PC
A u to d e s k D o c s /B
P A
C o lla b o ra te
R
/2
S
T R
U V
A M
C L y o n s R
.r v t
/1
/2
:5
:1
A
M
S1.01
STRUCTURAL BASEMENT LEVEL CORRECT FCA
D & F DEFICIENCIES
BOILER PLANT
LYONS VA MEDICAL CENTER, LYONS, NJ
561A4-18-113
APRIL 11, 2025 MSR JAC
1/4" = 1'-0"1
BASEMENT LEVEL RENOVATION PLAN
Revisions: Date:
UP
TRANSFORMER
UP
UP
COVERED STORAGE
STORAGE
CONTAINER
ADJACENT
BUILDING
ADJACENT
BUILDING
ADJACENT
BUILDING
ADJACENT
BUILDING
EXISTING
ELECTRICAL
VAULT
STORM
DRAIN
SAN
MH
DN
+11'-6"
+11'-0"
+11'-0"
CATWALK ABOVE
DN
CONTROL ROOM
ROLL-UP
DOOR
ROLL-UP
DOOR ROLL-UP
DOOR
ROLL-UP
DOOR
ROLL-UP
DOOR
BOILER
ROOM
BOILER
ROOM
+14"
0'
UP
DN
DN
UP
DN
0'W4X13W4X13
W4X13W4X13
B3
S3.01
W
X
W10X39
W
X
W10X30
W10X30
W10X30
B5
S3.01
C5
S3.01
C5
S3.01
C7
S3.01
C7
S3.01
REF E1/S3.01
E5
S3.01
W10X30
B7
S3.01
B9
S3.01
E3
S3.01
USE 30mmX30mmX11 GAUGE DOUBLE-TWIST
HEXAGONAL NETTING AT UNDERSIDE OF EXISTING
SLAB. AT PERIMETER AND SEAM LOCATIONS PROVIDE
3/16" DIA WIRE ROPE CABLES. SECURE NETTING TO
STEEL COLUMNS AT EACH CORNER WITH WELDED I-
BOLTS. AT CONCRETE/CMU WALL USE EPOXIED I-
BOLTS (REF E1/S3.01 FOR EPOXY INFORMATION).
NETTING SHALL BE LOCATED 2" BELOW EXISTING
STRUCTURE.
(E) STEEL BEAM
(E
S T
E E
L B
E A
M
B1
S3.01
GC TO VERIFY EXISTING BEAM CONNECTION IS (3) 3/4"
DIA BOTLS SINGLE PLATE SHEAR CONNECITON MIN. IF
(3) 3/4" BOLTS ARE NOT PRESENT AT EXITSING
CONNECTION, WELD SHEAR TAB TO EXISTING BEAM
ALL AROUNG WITH 1/4" FILLET WELD.
PROVIDE (2) C10X25 DIRECTLY BELOW CHEMICAL
TREATMENT TANKS. MAX WEIGHT = 2,000LBS
C
X
25C10X25LOCATE CHANNEL FRAMING TO PROVIDE OPENING
AROUND EXISTING PIPES
E3
S3.01
OH
E5
S3.01
1 2 3 4 5 6 7 8 9
A A
B
C
D
A.9
B.9
C.9
1'-0"
1' -0
HSS POST-UP
REF DETAIL
C
X
PROVIDE L4X4X3/8 EA SIDE OF OPENING
GW-125 (19-W-4) 1 1/4"x3/16"
GALVANIZED GRATING BY
McNICHOLS OR APPROVED EQUAL
PLAN LEGEND
DENOTES NEW BAR GRATING DECK SPAN DIRECTION
DENOTES EXISTING GRATING
DENOTES NEW NETTING
1435 W. Morehead St.
Suite 140 Charlotte, NC 28208
(704) 522-0495 www.brittpeters.com BPA Project No. 21240
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTSOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10720 SIKES PLACE, SUITE 100
CHARLOTTE, NC 28277
P 704.814.1320 F 704.321.0833
HDG PROJECT: 21009
COPYRIGHT © 2025 HARRELL DESIGN GROUP, PC
A u to d e s k D o c s /B
P A
C o lla b o ra te
R
/2
S
T R
U V
A M
C L y o n s R
.r v t
/1
/2
:5
:1
A
M
S1.02
STRUCTURAL GROUND LEVEL
FRAMING PLAN
CORRECT FCA
D & F DEFICIENCIES
BOILER PLANT
LYONS VA MEDICAL CENTER, LYONS, NJ
561A4-18-113
APRIL 11, 2025 MRS JAC
1/4" = 1'-0"1
GROUND LEVEL RENOVATION PLAN
Revisions: Date:
LOCATE NEW HSS ABOVE
STEEL COLUMN
HSS4x4X5/16 W/ 1/4" CAP PL
HSS COLUMN,
REF PLAN
BASE PL 3/4"x12"x12" W/ (4) 1/2"
DIA HILTI KWIK HUS ANCHORS
W/ 3" MIN EMBEDMENT
1/4
STEEL BEAM
REF PLAN
EXISTING
CONCRETE SLAB
GRATING REF C7/S3.01
L3X3X3/8 X 8" LONG EA EF
FLUSH WITH EXISTING
CONCRETE SLAB
1/4
TYP
RAIL DESIGN BY SUPPLIER,
REF ARCH
L4x4x3/8 @ EACH
PERPENDICULAR BEAM
FULL DEPTH
STIFF PLATE 3/8"
L4x4x5/16 BETWEEN L4x4.
1/4
TYP
RAIL DESIGN BY SUPPLIER,
REF ARCH
GRATING
REF C7/S3.01
16"
EXISTING CONC WALL
EXISTING STEEL COLUMN
3/4" DIA x 6" LONG HEADED
STUDS @ 12" OC FOR FULL
HEIGHT OF COLUMN
START STUDS 24" ABOVE
BOTTOM OF COLUMN.
STOP STUDS 12" BELOW
BOTTOM OF FRAMING
#4 @ 12" OC DRILL &
EPOXY INTO EXIST
CONC WALL.
USE HILTI HIT-RE 500
V3 EPOXY. MIN 10"
EMBEDMENT
#4 TIES @ 12" OC
5-#9 VERT FULL HEIGHT
w/ #7 DOWELS INTO
EXISTING FOOTING
18"
NOTES:
1. SHORE ALL STRUCTURE PRIOR
TO BEGINNING ANY WORK.
2. AFTER SHORING IS IN PLACE,
WIRE BRUSH RUST FROM
EXISTING COLUMN.
3. G.C. IS RESPONSIBLE FOR
SHORING DESIGN
4. CONC TO EXTEND TO BOTTOM
OF EXISTING STEEL FRAMING
5. COR AND AE TO OBSERVE INITIAL
EPOXY INSTALLATION AND EMBEDMENT
DEPTH. NOTIFY AE A MINIMUM 10 DAYS
PRIOR SO SITE VISIT CAN BE SCHEDULED
#3 DOWELS @ 12" OC
AROUND SLAB CUT
MIN 6" EMBEDMENT
USE HILTI HIT-RE 500 EPOXY
EXISTING FOOTING
#7 DOWELS DRILL & EPOXY
INTO EXIST FTG w/ HILTI
HIT-RE 500 V3 EPOXY MIN
8" EMBEDMENT
*NEW CENTER BAR
NOT SHOWN FOR
CLARITY
AS REQ'D BY G.C.
TO INSTALL NEW
DOWELS & COLUMN
G.C. TO FIELD
VERIFY PRIOR
TO PROCURING
DOWELS
2"
EXISTING FLOOR FRAMING
NEW GRATING
EXISTING COLUMN AND
BASE PLATE. CUT ANCHOR
BOLTS FREE AT BASEPLATE.
EXISTING
CONCRETE SLAB
1/4
GW-125 (19-W-4) 1 1/4"x3/16"
GALVANIZED GRATING BY
McNICHOLS OR APPROVED EQUAL
C10x25 EACH
SIDE OF COLUMN
1' -2
GRATING
EXISTING WALL
(4) 3/4" DIA A36 RODS W/
HILTI HIT-HY 200 EPOXY
6" EMBEDMENT MIN
2" 8"
2"
2" 8" 2"
12"
T/ WALL
PL 3/4"
EXISTING
CONCRETE SLAB
1/4
1' -2
EXISTING
STAIRS
GRATING REF C7/S3.01
C10x25
L6x6x1/2 TREAD
AS REQUIRED
EXISTING
CONCRETE SLAB
EXISTING
STAIRS
GRATING
REF C7/S3.01
L2X2X5/16 AT EA
EXISTING STRINGER
TO SUPPORT GRATING
CHANNEL BEYOND,
REF PLAN
C10x25
CUT EXISTING
ANCHORS
BOLTS FREE
NOTE: STEEL MEMBERS ARE SHOWN AT
LOCATIONS TO MISS EXISTING STAIRS. GC
SHOULD DETERMINE DIMENSIONS BASED
ON FIELDS MEASUREMENTS.
1/4
ANGLE TO
STRINGER
EXISTING
CONCRETE SLAB
GRATING
REF C7/S3.01
STEEL BEAM, REF
PLAN. FULL DEPTH
STIFFENER
STAIR AND HANDRAIL
DESIGNED BY FABRICATOR.
RAIL DESIGN BY SUPPLIER,
REF ARCH
EXISITNG STEEL BEAM AND
CONNECTION TO EXISTING
STRUCTURE. GC TO VIF
EXISTING
STEEL COLUMN
STEEL BEAM
REF PLAN
EXISTING
CONCRETE SLAB
GRATING REF C7/S3.01 RAIL DESIGN BY SUPPLIER,
REF ARCH
PL 1 1/4"X2"X CONT. ALONG
TOP OF EXISTING STEEL
BEAM.
1/4 2-12
1/4 2-12
3/16 TYP
1/4 TYP
L4X4X5/16. TYP
SECTION A-A OPTION 1
3/16 TYP
1/4 TYP
SECTION A-A OPTION 2
A A
NOTES:
1. FOR SIZE AND LOCATION OF REQUIRED OPENINGS VERIFY W/
MECHANICAL DWGS.
COPE ANGLE AND BEAR ON
TOP OF BEAM OR JOIST
CL BEAM OR JOIST
RAIL DESIGN BY SUPPLIER,
REF ARCH
STEEL BEAM, REF PLAN.
FULL DEPTH STIFFENER PL 1/4"
AT EA GUARDRAIL POST
GRATING
REF C7/S3.01
2" T
Y P
1'-0"
1' -0
1/4
NEW HSS 5x5 POST W/ BASE PL 3/4"x12"x12" WITH (4) 1/2" DIA HILTI KWIK
HUS ANCHORS, MIN 3" EMBEDMENT.
BEAR POST ON SLAB
1435 W. Morehead St.
Suite 140 Charlotte, NC 28208
(704) 522-0495 www.brittpeters.com BPA Project No. 21240
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTSOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10720 SIKES PLACE, SUITE 100
CHARLOTTE, NC 28277
P 704.814.1320 F 704.321.0833
HDG PROJECT: 21009
COPYRIGHT © 2025 HARRELL DESIGN GROUP, PC
A u to d e s k D o c s /B
P A
C o lla b o ra te
R
/2
S
T R
U V
A M
C L y o n s R
.r v t
/1
/2
:5
:1
A
M
S3.01
STRUCTURAL DETAILS CORRECT FCA
D & F DEFICIENCIES
BOILER PLANT
LYONS VA MEDICAL CENTER, LYONS, NJ
561A4-18-113
APRIL 11, 2025 MSR JAC
3/4" = 1'-0"B1
SECTION
3/4" = 1'-0"B5
SECTION
3/4" = 1'-0"C1
SECTION
3/4" = 1'-0"C3
SECTION
3/4" = 1'-0"C5
SECTION
3/4" = 1'-0"C7
SECTION
3/4" = 1'-0"E1
SECTION
3/4" = 1'-0"B7
SECTION
3/4" = 1'-0"B9
SECTION
3/4" = 1'-0"E3
SECTION
3/4" = 1'-0"B3
SECTION
3/4" = 1'-0"F1
TYPICAL GRATING SUPPORT AT OPENINGS
3/4" = 1'-0"E5
SECTION
Revisions: Date:
3/4" = 1'-0"F3
BASE PLATE DETAIL
CORRECT FCA
D & F DEFICIENCIES
BOILER PLANT
561A4-18-113 Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTSOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
LYONS VA MEDICAL CENTER, LYONS, NJ
Project Director
APRIL 11, 2025Revisions: Date:
10720 SIKES PLACE, SUITE 100
CHARLOTTE, NC 28277
P 704.814.1320 F 704.321.0833
HDG PROJECT: 21009
cCOPYRIGHT 2025 HARRELL DESIGN GROUP, PC
PL501
DETAILS - PLUMBING
DMWGG
1/2"
1-1/4"
ADJUSTABLE HANGER
WITH ROLLER
LOCKING NUT
SUPPORT NUT INSULATION
PIPE
PIPE COVERING
PROTECTION
16 GA SADDLE
GALVANIZED
INSULATION
SHIELD 12"LONG.
NOTES:
1. SEE SPECIFICATION FOR HANGER SIZES.
2. PIPE 8" AND LARGER SHALL HAVE ROLLER SUPPORTED WITH DUAL RODS.
MIN.9 lb/cft
DENSITY RIGID
INSULATION AT
SHIELD
CLEVIS HANGER
(FOR 1/2" UP TO
HEAVY DUTY
& INCL. 3" PIPE)
(FOR 4" TO 6" PIPE)
LOCK NUT
HANGER
PIPING
INSULATION
THREADED ROD
12" 6"6"
INSULATION SHIELD
METAL CHANNEL STRUT
UNINSULATED COPPER LINES AND LARGER.
INSULATION SHIELD ON 3"
PIPE CLAMP. PROVIDE
INSULATED PIPE LINE WITH
HANGER ROD
OR NYLON INSULATOR
PIPE CLAMPS WITH ELASTOMER
FINISHED FLOOR.
SECURED RIM FLUSH WITH
FINISHED FLOOR.
ADJUSTABLE HOUSING.
INSIDE CAULK.
CAST IRON 1/8 BEND.
CAST IRON SANITARY WYE FITTING.THIS POINT
OF LINE, PLUG WYE AT
FOR CLEANOUT AT END
DEEP SEAL "P" TRAP
NEW SLAB
NEW FLOOR DRAINGRATE
NEW SLAB
DEEP SEAL "P" TRAP
NEW FLOOR SINK
FIELD DETERMINE
THE USE OF 1/2 OR
3/4 GRATE LID.
DEBRIS SCREEN
1/2" CW
P-528
COUNTER MOUNTED SINK
H W
°F
KEY STOP
SHUT-OFF
VALVE (TYP.)
C W
1/2" HW
FIN. FLOOR
NEW STAINLESS STEEL CABINET CABINET
MAXIMUM PIPE/TUBING SUPPORT SPACING
NOTE: FOR TRAPEZE HANGER TAKE SPACING OF SMALLEST SIZE ON TRAPEZE.
mm
[IN]
mm
[FT]
mm
[FT]
SIZE OF LEGEND LETTERS
A
8 to 10 over 10
2-1/2 to 6
1-1/2 to 2
3/4 to 1-1/4
LEGEND
LEGENDLEGEND
OUTSIDE DIA. OF
PIPE OR COVERING
(INCH)
2-1/2
3-1/2
12 1-1/4
3/48
8 1/2
LETTER HEIGHT
[B] (INCH)
LENGTH OF
COLOR FIELD
[A] (INCH)
NOTE
1. SEE PAINTING SPECIFICATION FOR
FINISH COLOR OF PIPE.
2. LABELS SHALL BE INSTALLED AT A
MINIMUM OF EVERY 50' AND AT
ANY WALL OR FLOOR PENETRATION.
3. INDICATE FLOW ARROWS AT EACH
PIPE DESIGNATIONS SIMILAR TO
DIAGRAM PROVIDED.
EXPANSION ANCHORS (2, MIN.)
SEE SPEC. ITEM 14 FOR SPACING.
NOTE: ALL BLACK STEEL ITEMS SHALL BE PRIMED
& PAINTED WITH 2 COATS OF BLACK ENAMEL PAINT.
GALV. SHT. MTL.
WELDED TO STEEL PLATES
1/4" THICK STEEL PLATE
SCHEDULE 40 BLACK STEEL PIPE
BLACK STEEL PLATE
INSULATION SHIELD
CONCRETE FLOOR
PIPE
PIPE INSULATION
316SS
LIFTING
CHAIN
LAG
LEAD
OFF
316SS CABLE
BRACKET
PUMP DISCONNECT
SWITCH FURNISHED
BY DIV. 26.
CONTROL PANEL
FLOAT SWITCHES
(1" RIGID CONDUIT)
TO POWER SERVICE
HLA
SP-1
SP-1
INSTALL NEW
PIPING AND POWER
CONDUITS WITHIN
EXISTING PIPE
CHANNEL.
STAINLESS STEEL.
Z-RAIL BRACKET
STAINLESS STEEL.
Z-RAIL BRACKET
316SS CABLE
BRACKET
PUMP CONTROLS
DISCONNECT
SWITCH FURNISHED
BY DIV. 26.
FLOAT SWITCHES
TYPICAL
PUMP POWER
CABLES (1-1/2" RIGID
CONDUITS)
SEQUENCE OF OPERATION:
1. PUMPS SHALL REMAIN INACTIVE WHEN THE WATER LEVEL IS BELOW THE (STOP) FLOAT.
2. THE LEAD PUMP SHALL ACTIVATE WHEN THE (STOP) FLOAT AND THE (LEAD) FLOAT ARE
LIFTED BY THE SURFACE OF THE WATER. THE LEAD PUMP SHALL CONTINUE TO RUN UNTIL
THE WATER LEVEL IS BELOW THE (LEAD) FLOAT.
3. THE LAG PUMP SHALL ACTIVATE WHEN THE (STOP) FLOAT, THE (LEAD) FLOAT AND THE
(LAG) FLOAT ARE LIFTED BY THE SURFACE OF THE WATER. THE LEAD AND LAG PUMPS
SHALL CONTINUE TO RUN UNTIL THE WATER LEVEL IS BELOW THE (LAG) FLOAT. THE LAG
PUMP SHALL DEACTIVATE AND THE LEAD PUMP SHALL REMAIN ACTIVATED UNTIL THE
WATER LEVEL IS BELOW THE (LEAD) FLOAT AND THE LEAD PUMP SHALL DEACTIVATE.
4. THE HIGH LEVEL ALARM SHALL ACTIVATE WHEN THE (HLA) FLOAT IS LIFTED BY THE
SURFACE OF THE WATER. THE STROBE ON THE TOP OF THE CONTROLS PANEL SHALL
FLASH AND THE HORN SHALL ACTIVATE INDICATING TOTAL SYSTEM FAILURE. A SIGNAL
SHALL BE SENT TO THE CAMPUS WIDE BUILDING AUTOMATION SYSTEM INDICATING SUMP
PUMP FAILURE. THE HIGH WATER ALARM SHALL CONTINUE UNTIL MANUALLY RESET BY VA
STAFF REGARDLESS IF THE HIGH WATER CONDITION IS ALLEVIATED.
5. PUMP CONTROLER SHALL BE SET TO AUTOMATICALY SWITCH LEAD/LAG PUMP ACTIVATION
ON A WEEKLY BAIS TO BALANCE RUN HOURS ACROSS EQUIPMENT.
6. IN THE EVENT OF LEAD PUMP FAILURE TO START, THE LAG PUMP SHALL AUTOMATICALLY
SWITCH TO LEAD PUMP OPERATION AND THE STROBE AND HORN SHALL ACTIVATE
INDICATING A PUMP FAILURE. THE HORN AND STROBE SHALL CONTINUE UNTIL MANUALLY
RESET BY VA STAFF.
3/4" STAINLESS
STEEL PIPE.
EXISTING CONCRETE SUMP
NOTE:
CONTRACTOR SHALL MEASURE THE DEPTH AND INSIDE DIAMETER OF EXISTING
SUMP AND COORDINATING THOSE DIMENSIONS WITH THE PLUMB
MANUFACTURER PRIOR TO ORDERING OF NEW PUMP EQUIPMENT.
COORDINATE
DIMENSION WITH
MANUFACTURER
COORDINATE
DIMENSION WITH
MANUFACTURER
COORDINATE
DIMENSION WITH
MANUFACTURER
COORDINATE
DIMENSION WITH
MANUFACTURERFLOW CONTROL
VALVE
REMOTE HIGH WATER
ALARM PANEL WITH
STROBE AND HORN.
LOCATE IN
CONTROL
ROOM 103.
TV-1
DWV COPPER
PIPINGDWV COPPER
PIPING
PRE-MOLDED PIPE
INSULATION UNDER
SUPPORTS (220711 PAR. 2.9.A)
PRE-MOLDED PIPE
INSULATION UNDER
SUPPORTS (220711 PAR. 2.9.A)
PRE-MOLDED PIPE
INSULATION UNDER
SUPPORTS (220711 PAR. 2.9.A)
PRE-MOLDED PIPE
INSULATION UNDER
SUPPORTS (220711 PAR. 2.9.A)
EXISTING SLABEXISTING SLAB
EXISTING SLAB
EXISTING SLAB
REDUCED PRESSURE PRINCIPLE
BACKFLOW PREVENTER WITH
ISOLATION VALVES.
ELEVATION
PLAN VIEW
AIR GAP
FITTING
COLD WATER
TO SYSTEM
COLD WATER
TO SYSTEMREDUCED PRESSURE PRINCIPLE BACKFLOW
PREVENTER WITH ISOLATION VALVES.
EXISTING PIPE
SUPPORT (TYP.)
PIPE SUPPORT (TYP.)
PIPE TO
NEAREST
FLOOR DRAIN
(TYP.)
FINISHED
FLOOR
ROTATE VALVE ASSEMBLY TO
FACILITATE EQUIPMENT
INSTALLATION. (TYP.)
ELEVATION TO MATCH
EXISTING PIPING. (TYP.)
RELIEF VALVE
(REDUCE PRESSURE BACKFLOW PREVENTION ASSEMBLY)
3" RPBFP
REFER TO PL101 FOR EQUIPMENT REPLACEMENT PHASING SEQUENCE.
BASIS OF DESIGN SHALL BE: WATTS SERIES LF909
DOUBLE CHECK VALVE (TYP.)
Marco J. Brancker PE
Digitally signed by Marco J. Brancker
PE
DN: C=US,
E=mbrancker@harrelldg.com, O=Harrell Design Group, CN=Marco J. Brancker PE Date: 2025.05.16 08:56:26-04'00'
| GI001print and seal |
| Arch print and seal |
| Plumbing |
| Mechanical |
| Electrical |
| 220043_STRU_VAMC Lyons_2025-04-14.pdf |
| Sheets |
| S0.01 - STRUCTURAL GENERAL NOTES, AND ABREVIATIONS |
| S1.01 - STRUCTURAL BASEMENT LEVEL |
| S1.02 - STRUCTURAL GROUND LEVEL FRAMING PLAN |
| S3.01 - STRUCTURAL DETAILS |
File details come from the government source that posted it. Updated .