This is a Comprehensive Asbestos Building Survey report for Building 14 (Boiler House) at the Department of Veterans Affairs New Jersey Health Care System in Lyons, New Jersey, prepared by Briggs Associates and dated November 15, 2013. The survey identified one asbestos-containing material (ACM) in the building: magnesium pipe insulation (15 linear feet) located in the lower level vault, designated as HSA# 14-08. Eight homogeneous materials were sampled with twenty-two total samples collected, analyzed using Polarized Light Microscopy (PLM) and Transmission Electron Microscopy (TEM). All other materials tested—including old and new tank insulation, window glazing, vinyl floor tiles, mastic, and roofing shingles—were determined to be non-asbestos containing. The identified ACM material is in good condition with no damage and poses low potential for human exposure and disturbance.
The recommended response action is implementation of an Operations and Maintenance Plan including six key elements: employee training and notification, worker protection measures, cleaning and maintenance operations, fiber release episode management, periodic surveillance, and record keeping with documentation and labeling. The survey documents all sampling locations with photographic records and detailed floor plans showing sample locations throughout the building. Laboratory analytical results from IATL (International Asbestos Testing Laboratories) with NIST-NVLAP accreditation confirm the presence of asbestos in the pipe insulation while confirming all other suspect materials tested negative for asbestos content exceeding the 1% EPA regulatory threshold.
View the file
Other files
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
COMPREHENSIVE ASBESTOS
BUILDING SURVEY
Subject Site:
DEPARTMENT OF VETERAN AFFAIRS
New Jersey Health Care System 151 Knollcroft Avenue Lyons, New Jersey 07939
BUILDING 14 - BOILER HOUSE
Prepared For:
BBLM ARCHITECTS
924 Cherry Street Philadelphia, Pa 19107
Prepared By:
BRIGGS ASSOCIATES
3 Crosswicks Street Bordentown, NJ 08505
VA Project No: 561A4-10-130 BBLM Project No: 1012 Briggs Project No: 100-BBLM-10
November 15, 2013
COMPREHENSIVE ASBESTOS
BUILDING SURVEY
Subject Site:
New Jersey Health Care System 151 Knollcroft Avenue
Lyons, New Jersey 07939
BUILDING 14
BOILER HOUSE
Prepared For:
BBLM ARCHITECTS
924 Cherry Street Philadelphia, Pa 19107
Prepared By:
BRIGGS ASSOCIATES
3 Crosswicks Street
Bordentown, NJ 08505
Douglas Ferry
EPA Asbestos Investigator
#ACC-0408-6-002
VA Project No: 561A4-10-130
BBLM Project No: 1012 Briggs Project No: 100-BBLM-10
November 15, 2013
COMPREHENSIVE ASBESTOS INSPECTION REPORT
VETERAN’S MEDICAL CENTER, LYONS, NEW JERSEY
BRIGGS ASSOCIATES 1 PROJECT NO: 100-BBLM-10
19.0 BUILDING 14 - BOILER HOUSE
19.01 Discussion
Building 14 is a two-story brick boiler house and is approximately 3,500 square feet. Building 14 consists of a lower level, main ground floor and an upper mezzanine level, accessible via a metal catwalk. According to the building manager, an extensive asbestos abatement project of the boiler house was conducted in the early 1990’s.
19.02 Results
The criterion used for determining the status of a suspect material as ACM is the USEPA and OSHA criterion of being “asbestos-containing”, which is that the material is determined to contain greater than 1% by weight of actinolite, amosite, anthophyllite, chrysotile, crocidolite, tremolite asbestiform fibers. A total of eight (8) homogeneous materials were identified from which twenty-two (22) samples were collected. The analytical laboratory was instructed to analyze to the "first positive". That is, once a sample of a given homogenous material sample set was determined to contain asbestos at a concentration greater than 1% (the EPA definition of ACM), no more samples within that set were analyzed, and the remaining samples were assumed to be positive. Following PLM analysis, a total of five (5) samples were re-submitted for analysis by the TEM NOB method.
Refer to the attached Table 1.1 Summary of Homogeneous Materials, Bulk Sample Locations & Analytical Results (Appendix A-14) for a listing of the materials identified and the laboratory analytical results. Table 2.1 is a Photographic Record of homogeneous materials (Appendix B-14). Table 3.1 is an Inventory of Asbestos Containing Materials and Material Assessment findings (Appendix C-14). Color drawings in AutoCAD format are provided in Appendix D-14 Floor Plans. Laboratory data results are attached in Appendices E-14 & F-14.
The following materials, identified within the facility, have been determined to be asbestos-containing materials
(ACM):
i. magnesium pipe insulation (HSA# 14-08) found in the lower level vault;
19.03 Recommended Response Actions
Overall, all of the asbestos containing materials that exist within Building 14 have been determined to be non-damaged and in good condition. The VA should implement the Operations and Maintenance Plan (O&M) which includes the following elements:
1) Employee training and notification.
2) Worker protection.
3) Cleaning and maintenance operations.
4) Fiber release episode management.
5) Periodic surveillance.
6) Record keeping, documentation and labelling
APPENDIX A-14
TABLE 1.1 - SUMMARY OF HOMOGENEOUS MATERIALS,
BULK SAMPLE LOCATIONS & ANALYTICAL RESULTS
VALy_Summary Lab Results.xls Page 1 of 1
Name of Inspector:
Property Name:
Property Address: Bldg. No.: 14
14-P01 14-1
14-1
14-P03 14-1
14-P04 14-1
14-P05 14-1
14-1
14-1 14-P07 14-1
(a) All analysis performed at IATL, 9000 Commerce Parkway, Mt. Laurel, NJ (d)
(e) NA = Sample Not Analyzed
(b) (f)
(c) (g)
TABLE 1.1 SUMMARY OF HOMOGENEOUS MATERIALS, BULK
SAMPLE LOCATIONS & ANALYTICAL RESULTS
Douglas Ferry / Michael Hoodak Field Dates: 4/26/11 Dept. of Veterans Affairs, VA Medical Center Lyons Briggs Project No.: 100-BBLM-10 151 Knollcroft Road, Lyons, New Jersey VA Project No.: 561A4-10-130
HSA# Material Description Sample Location Sample
No.
PLM
Results
TEM
Results Photo
No.
Floor
Plan No.
14-01 Tank insulation - old Main Boiler Room 14-01A ND
14-01B ND
14-01C ND
14-02 Window glazing Main Boiler Room 14-02A ND ND
14-02B ND
14-02C ND
14-03 Tank insulation - new Main Boiler Room 14-03A ND
14-03B ND
14-03C ND
14-04B ND
14-04 Bathroom 14-04A ND ND
14-04C ND
14-05 Mastic under 12"x12" white speckled
VFT - black Bathroom 14-05A ND ND
14-05B ND
14-05C ND
14-061 Roofing shingles Roof 14-06A ND ND
14-06B1 ND
14-07C ND
14-06C ND
14-1
14-07B ND
14-08 Pipe insulation - main steam
OSHA ACM - >1% Asbestos Result Ch = Chrysotile, Am = Amosite, Cr = Crocidolite, An = Anthophylilite, Ac = Actinolite, Tr = Tremolite Trace Result - Not ACM
ND
14-P08
Exterior 14-07A ND ND14-07 Window glazing - white
TABLE NOTES:
ND = None Detected
Lower Level Vault Assumed Positive
12"x12" vinyl floor tile - white speckled
14-062 Roofing shingles Roof 14-06B2
HSA # is specific to each building NIST-NVLAP No. 101165-0; NY-DOH No. 11021; AIHA Lab No. 100188
APPENDIX B-14
TABLE 2.1 – PHOTOGRAPHIC RECORD
Bldg 14 VALy_Photo_Log_12-19.xls Page 1 of 3
Property Name:
Property Address: 14
Tank insulation - old
Tank insulation - new
TABLE 2.1 PHOTOGRAPHIC RECORD
Douglas Ferry / Michael Hoodak Field Dates: 4/26/11 Dept. of Veterans Affairs, VA Medical Center Lyons Briggs Proj No.: 100-BBLM-10 151 Knollcroft Road, Lyons, New Jersey Bldg. No.: VA Project No.: 561A4-10-130
Photo No.: 14-P00 HSA No.: NA
ACM? Y/N NA
Location: Building 14 Description: Boiler House
Photo No.: 14-P01 HSA No.: 14-01 ACM? Y/N No Location: Main Boiler Room Description:
Photo No.: 14-P03 HSA No.: 14-03 ACM? Y/N No Location: Main Boiler Room Description:
Bldg 14 VALy_Photo_Log_12-19.xls Page 2 of 3
Property Name:
Property Address: 14
TABLE 2.1 PHOTOGRAPHIC RECORD
Douglas Ferry / Michael Hoodak Field Dates: 4/26/11 Dept. of Veterans Affairs, VA Medical Center Lyons Briggs Proj No.: 100-BBLM-10 151 Knollcroft Road, Lyons, New Jersey Bldg. No.: VA Project No.: 561A4-10-130
12"x12" vinyl floor tile - white speckled
Window glazing - white
ACM? Y/N No Location: Lower Level Bathroom Description:
Photo No.: 14-P04 HSA No.: 14-04
Location: Lower Level Bathroom Description:
Photo No.: 14-P05 HSA No.: 14-05 ACM? Y/N No
Photo No.: 14-P07 HSA No.: 14-07 ACM? Y/N No Location: Exterior Description:
Mastic under 12"x12" white speckled VFT -black
Bldg 14 VALy_Photo_Log_12-19.xls Page 3 of 3
Property Name:
Property Address: 14
TABLE 2.1 PHOTOGRAPHIC RECORD
Douglas Ferry / Michael Hoodak Field Dates: 4/26/11 Dept. of Veterans Affairs, VA Medical Center Lyons Briggs Proj No.: 100-BBLM-10 151 Knollcroft Road, Lyons, New Jersey Bldg. No.: VA Project No.: 561A4-10-130
Main steam pipe insulation
ACM? Y/N Yes Location: Lower Level Vault Description:
Photo No.: 14-P08 HSA No.: 14-08
APPENDIX C-14
TABLE 3.1 – ASBESTOS CONTAINING MATERIALS
INVENTORY / ASSESSMENT
VALy_ACM Inventory.xls Page 1 of 1
Name of Inspector: 4/26/11 Property Name: 100-BBLM-10 Property Address: Bldg. No.: 14 561A4-10-130
LL V 14-08 Pipe insulation - main steam 15 lf Assumed TSI F Good 0 lf Low Low 1 Labeled "ACM"
(a) (b) (c) (d)
TABLE 3.1 ASBESTOS CONTAINING MATERIALS INVENTORY / ASSESSMENT
Douglas Ferry / Michael Hoodak Field Dates:
Dept. of Veterans Affairs, VA Medical Center Lyons Briggs Project No.:
151 Knollcroft Road, Lyons, New Jersey VA Project No.:
Potential for Human
Exposure
R es po ns e A ct io n
Fl oo r
Fu nc tio na l Sp ac e
Room Description
H
SA
Material Description Quantity Estimate
Vault
Type of
ACM
Material Category
ACM Assessment
Notes Friability Condition Amount of
Damage Potential for Disturbance
TSI = Thermal Systems Insulation; Misc = Miscellaneous (h) Response Action - 1 = lowest priority; 5 = highest priority
TABLE KEY:
HSA # is specific to each building (e) F = Friable; NF I = Non-Friable Category I; NF II = Non-Friable Category II sf = square feet; lf = linear feet; ea = each (f) Good = No Damage; D = Damaged = >10% Damage; SD = Significantly Damaged = >25% Damage Ch = Chrysotile; Am = Amosite; Cr = Crocidolite; An = Anthophylilite; Ac = Actiniloite (g) Potential for Disturbance / Human Exposure - Low, Mod = Moderate, High
APPENDIX D-14
FLOOR PLANS
APPENDIX E-14
PLM LABORATORY
ANALYTICAL RESULTS
9000 Commerce Parkway, Ste B Mount Laurel, NJ 08054
Toll Free 877-428-4285 Local: 856-231-9449
Fax: 856-231-9818CERTIFICATE OF ANALYSIS
Client: Report Date:
Project No.:
Project:
BULK SAMPLE ANALYSIS SUMMARY
Briggs Associates
3 Crosswicks St
Bordentown NJ 08505
561A4-10-130
VA Lyons Bldg 14
5/13/2011
Report No: 239218
% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material
Client No.:
Lab No.:
14-01A 4293208 Description / Location:
Main Boiler Room, Tank-Old
None Detected None Detected 10
Fibrous Glass
Synthetic
Tan/Grey Insulation
% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material
Client No.:
Lab No.:
14-01B 4293209 Description / Location:
Main Boiler Room, Tank-Old
None Detected None Detected 5
Cellulose
Synthetic
Tan/Grey Insulation
% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material
Client No.:
Lab No.:
14-01C 4293210 Description / Location:
Main Boiler Room, Tank-Old
None Detected None Detected 5
Cellulose
Synthetic
Tan/Grey Insulation
% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material
Client No.:
Lab No.:
14-02A 4293211 Description / Location:
Main Boiler Room
None Detected None Detected None Detected None Detected 100
Off-White Window Glazing
NIST-NVLAP No. 101165-0 NY-DOH No. 11021 AIHA-LAP, LLC No. 100188 This confidential report relates only to those item(s) tested and does not represent an endorsement by NIST-NVLAP, AIHA or any agency of the U.S. government
This report shall not be reproduced except in full, without written approval of the laboratory.
Accreditation
EPA 600/R-93/116Analytical Method:
Comments: (PC) Indicates Stratified Point Count Method performed. Method not performed unless stated. Quantification at <0.25% by volume is possible with this method. (PC–Trace) represents this limit of quantitation. (PC-Trace) means that asbestos was detected but is not quantifiable under the Point Counting regimen. Analysis includes all distinct separable layers in accordance with EPA 600 Method. If not reported or otherwise noted, layer is either not present or the client has specifically requested that it not be analyzed. Small asbestos fibers may be missed by PLM due to resolution limitations of the optical microscope. Therefore, negative PLM results cannot be guaranteed. Electron Microscopy can be used as a confirming technique. Regulatory Limit is based upon the sample matrix.
Analysis Performed By:
Approved By:
Frank E. Ehrenfeld, III Laboratory Director
5/13/2011
J. Haremza
Date:
Toll Free 877-428-4285 Local: 856-231-9449
Fax: 856-231-9818CERTIFICATE OF ANALYSIS
Client: Report Date:
Project No.:
Project:
BULK SAMPLE ANALYSIS SUMMARY
Briggs Associates
3 Crosswicks St
Bordentown NJ 08505
561A4-10-130
VA Lyons Bldg 14
5/13/2011
Report No: 239218
% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material
Client No.:
Lab No.:
14-02B 4293212 Description / Location:
Main Boiler Room
None Detected None Detected None Detected None Detected 100
Off-White Window Glazing
% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material
Client No.:
Lab No.:
14-02C 4293213 Description / Location:
Main Boiler Room
None Detected None Detected None Detected None Detected 100
Off-White Window Glazing
% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material
Client No.:
Lab No.:
14-03A 4293214 Description / Location:
Main Boiler Room, Tank-New
None Detected None Detected 5
Fibrous Glass
Synthetic
Tan Insulation
% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material
Client No.:
Lab No.:
14-03B 4293215 Description / Location:
Main Boiler Room, Tank-New
None Detected None Detected 5
Fibrous Glass
Synthetic
Tan Insulation
NIST-NVLAP No. 101165-0 NY-DOH No. 11021 AIHA-LAP, LLC No. 100188 This confidential report relates only to those item(s) tested and does not represent an endorsement by NIST-NVLAP, AIHA or any agency of the U.S. government
This report shall not be reproduced except in full, without written approval of the laboratory.
Accreditation
EPA 600/R-93/116Analytical Method:
Comments: (PC) Indicates Stratified Point Count Method performed. Method not performed unless stated. Quantification at <0.25% by volume is possible with this method. (PC–Trace) represents this limit of quantitation. (PC-Trace) means that asbestos was detected but is not quantifiable under the Point Counting regimen. Analysis includes all distinct separable layers in accordance with EPA 600 Method. If not reported or otherwise noted, layer is either not present or the client has specifically requested that it not be analyzed. Small asbestos fibers may be missed by PLM due to resolution limitations of the optical microscope. Therefore, negative PLM results cannot be guaranteed. Electron Microscopy can be used as a confirming technique. Regulatory Limit is based upon the sample matrix.
Analysis Performed By:
5/13/2011
J. Haremza
Toll Free 877-428-4285 Local: 856-231-9449
Fax: 856-231-9818CERTIFICATE OF ANALYSIS
Client: Report Date:
Project No.:
Project:
BULK SAMPLE ANALYSIS SUMMARY
Briggs Associates
3 Crosswicks St
Bordentown NJ 08505
561A4-10-130
VA Lyons Bldg 14
5/13/2011
Report No: 239218
% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material
Client No.:
Lab No.:
14-03C 4293216 Description / Location:
Main Boiler Room, Tank-New
None Detected None Detected 5
Fibrous Glass
Synthetic
Tan Insulation
% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material
Client No.:
Lab No.:
14-04A 4293217 Description / Location:
Bathroom
None Detected None Detected None Detected None Detected 100
Tan Floor Tile; 12x12
% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material
Client No.:
Lab No.:
14-04B 4293218 Description / Location:
Bathroom
None Detected None Detected None Detected None Detected 100
Tan Floor Tile; 12x12
% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material
Client No.:
Lab No.:
14-04C 4293219 Description / Location:
Bathroom
None Detected None Detected None Detected None Detected 100
Tan Floor Tile; 12x12
NIST-NVLAP No. 101165-0 NY-DOH No. 11021 AIHA-LAP, LLC No. 100188 This confidential report relates only to those item(s) tested and does not represent an endorsement by NIST-NVLAP, AIHA or any agency of the U.S. government
This report shall not be reproduced except in full, without written approval of the laboratory.
Accreditation
EPA 600/R-93/116Analytical Method:
Comments: (PC) Indicates Stratified Point Count Method performed. Method not performed unless stated. Quantification at <0.25% by volume is possible with this method. (PC–Trace) represents this limit of quantitation. (PC-Trace) means that asbestos was detected but is not quantifiable under the Point Counting regimen. Analysis includes all distinct separable layers in accordance with EPA 600 Method. If not reported or otherwise noted, layer is either not present or the client has specifically requested that it not be analyzed. Small asbestos fibers may be missed by PLM due to resolution limitations of the optical microscope. Therefore, negative PLM results cannot be guaranteed. Electron Microscopy can be used as a confirming technique. Regulatory Limit is based upon the sample matrix.
Analysis Performed By:
5/13/2011
Toll Free 877-428-4285 Local: 856-231-9449
Fax: 856-231-9818CERTIFICATE OF ANALYSIS
Client: Report Date:
Project No.:
Project:
BULK SAMPLE ANALYSIS SUMMARY
Briggs Associates
3 Crosswicks St
Bordentown NJ 08505
561A4-10-130
VA Lyons Bldg 14
5/13/2011
Report No: 239218
% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material
Client No.:
Lab No.:
14-05A 4293220 Description / Location:
Bathroom
None Detected None Detected None Detected None Detected 100
Black Mastic Under 12x12 FT
% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material
Client No.:
Lab No.:
14-05B 4293221 Description / Location:
Bathroom
None Detected None Detected None Detected None Detected 100
Black Mastic Under 12x12 FT
% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material
Client No.:
Lab No.:
14-05C 4293222 Description / Location:
Bathroom
None Detected None Detected None Detected None Detected 100
Black Mastic Under 12x12 FT
% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material
Client No.:
Lab No.:
14-07A 4293223 Description / Location:
Exterior
None Detected None Detected None Detected None Detected 100
Tan Window Glazing
NIST-NVLAP No. 101165-0 NY-DOH No. 11021 AIHA-LAP, LLC No. 100188 This confidential report relates only to those item(s) tested and does not represent an endorsement by NIST-NVLAP, AIHA or any agency of the U.S. government
This report shall not be reproduced except in full, without written approval of the laboratory.
Accreditation
EPA 600/R-93/116Analytical Method:
Comments: (PC) Indicates Stratified Point Count Method performed. Method not performed unless stated. Quantification at <0.25% by volume is possible with this method. (PC–Trace) represents this limit of quantitation. (PC-Trace) means that asbestos was detected but is not quantifiable under the Point Counting regimen. Analysis includes all distinct separable layers in accordance with EPA 600 Method. If not reported or otherwise noted, layer is either not present or the client has specifically requested that it not be analyzed. Small asbestos fibers may be missed by PLM due to resolution limitations of the optical microscope. Therefore, negative PLM results cannot be guaranteed. Electron Microscopy can be used as a confirming technique. Regulatory Limit is based upon the sample matrix.
Analysis Performed By:
5/13/2011
Toll Free 877-428-4285 Local: 856-231-9449
Fax: 856-231-9818CERTIFICATE OF ANALYSIS
Client: Report Date:
Project No.:
Project:
BULK SAMPLE ANALYSIS SUMMARY
Briggs Associates
3 Crosswicks St
Bordentown NJ 08505
561A4-10-130
VA Lyons Bldg 14
5/13/2011
Report No: 239218
% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material
Client No.:
Lab No.:
14-07B 4293224 Description / Location:
Exterior
None Detected None Detected None Detected None Detected 100
Off-White Window Glazing
% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material
Client No.:
Lab No.:
14-07C 4293225 Description / Location:
Exterior
None Detected None Detected None Detected None Detected 100
Off-White Window Glazing
NIST-NVLAP No. 101165-0 NY-DOH No. 11021 AIHA-LAP, LLC No. 100188 This confidential report relates only to those item(s) tested and does not represent an endorsement by NIST-NVLAP, AIHA or any agency of the U.S. government
This report shall not be reproduced except in full, without written approval of the laboratory.
Accreditation
EPA 600/R-93/116Analytical Method:
Comments: (PC) Indicates Stratified Point Count Method performed. Method not performed unless stated. Quantification at <0.25% by volume is possible with this method. (PC–Trace) represents this limit of quantitation. (PC-Trace) means that asbestos was detected but is not quantifiable under the Point Counting regimen. Analysis includes all distinct separable layers in accordance with EPA 600 Method. If not reported or otherwise noted, layer is either not present or the client has specifically requested that it not be analyzed. Small asbestos fibers may be missed by PLM due to resolution limitations of the optical microscope. Therefore, negative PLM results cannot be guaranteed. Electron Microscopy can be used as a confirming technique. Regulatory Limit is based upon the sample matrix.
Analysis Performed By:
5/13/2011
Toll Free 877-428-4285 Local: 856-231-9449
Fax: 856-231-9818CERTIFICATE OF ANALYSIS
Client: Report Date:
Project No.:
Project:
BULK SAMPLE ANALYSIS SUMMARY
Briggs Associates
3 Crosswicks St
Bordentown NJ 08505
561A4-10-130
VA Lyons Bldg 14
10/3/2011
Report No: 253386
% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material
Client No.:
Lab No.:
14-06A 4440034 Description / Location:
Roof
None Detected None Detected 10 Fibrous Glass 90
Grey/Black Shingle
% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material
Client No.:
Lab No.:
14-06B 4440035 Description / Location:
Roof
None Detected None Detected 10 Fibrous Glass 90
Grey/Green/Black Shingle
% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material
Client No.:
Lab No.:
14-06B 4440035 Description / Location:
Roof
None Detected None Detected 10 Fibrous Glass 90
Grey/Tan/Black Shingle Layer No.: 2
% Asbestos Type % Non-Asbestos Fibrous Material Type % Non-Fibrous Material
Client No.:
Lab No.:
14-06C 4440036 Description / Location:
Roof
None Detected None Detected 10 Fibrous Glass 90
Grey/Green/Black Shingle
NIST-NVLAP No. 101165-0 NY-DOH No. 11021 AIHA-LAP, LLC No. 100188 This confidential report relates only to those item(s) tested and does not represent an endorsement by NIST-NVLAP, AIHA or any agency of the U.S. government
This report shall not be reproduced except in full, without written approval of the laboratory.
Accreditation
EPA 600/R-93/116Analytical Method:
Comments: (PC) Indicates Stratified Point Count Method performed. Method not performed unless stated. Quantification at <0.25% by volume is possible with this method. (PC–Trace) represents this limit of quantitation. (PC-Trace) means that asbestos was detected but is not quantifiable under the Point Counting regimen. Analysis includes all distinct separable layers in accordance with EPA 600 Method. If not reported or otherwise noted, layer is either not present or the client has specifically requested that it not be analyzed. Small asbestos fibers may be missed by PLM due to resolution limitations of the optical microscope. Therefore, negative PLM results cannot be guaranteed. Electron Microscopy can be used as a confirming technique. Regulatory Limit is based upon the sample matrix.
Analysis Performed By:
Approved By:
Frank E. Ehrenfeld, III Laboratory Director
10/3/2011
L. Solebello
APPENDIX F-14
TEM LABORATORY
ANALYTICAL RESULTS
CERTIFICATE OF ANALYSIS
561A4-10-130
VA Lyons Bldg 14
Project No.:
Project:
Report Date:
Bordentown
3 Crosswicks St
Briggs AssociatesClient:
TEM BULK SAMPLE ANALYSIS SUMMARY
08505NJ
9000 Commerce Parkway, Suite B Mount Laurel, NJ 08054
Toll Free 877-428-4285 Local: 856-231-9449
Fax: 856-231-9818
5/19/2011
Report No.: 240043
Description / Location:
Client No.:
IATL No.: 114293211A
14-02A
Off-White Window Glazing Main Boiler Room
Gravimetrically Reduced Subsample:
Percent Asbestos Detected:
Percent Non-Asbestos Fibrous Material:
Percent Non-Fibrous Material:
ND
2.20 %
41.6 %
None Detected
SiMg, Talc
Other
Organic Fraction: 56.2 %
43.8 %
Comments:
NIST-NVLAP No. 101165-0 AIHA-LAP, LLC No. 100188 NYS-DOH No. 11021
IATL assumes that all sampling methods and data upon which these results are based have been accurately supplied by the client.
Transmission Electron Microscopy (TEM) In Accordance With :
ELAP 198.4 "Method For Identifying And Quantitating Asbestos In Non-Friable Organically Bound Bulk Samples", Revised 1/11/2005. EPA-600/R- 93/116 Section 2.5 "Asbestos In Bulk Building Materials By TEM Gravimetry."
This confidential report relates only to those item(s) tested and does not represent an endorsement by NIST-NVLAP, AIHA or any agency of the U.S. government.
Results are verifiable for only those operations and analyses performed in the laboratory.
Methodology:
The "Gravimetrically Reduced Subsample" is the portion of the submitted sample remaining following the ashing and acid treatment processes. TEM analysis occurs on this portion of the sample. Final results are calculated to represent the sample as submitted.
Analysis Performed By:
Date:
Approved By:
Frank E. Ehrenfeld, III Laboratory Director
J. Silcox
5/19/2011
VA Lyons Bldg 14
Project No.:
Project:
Report Date:
Bordentown
3 Crosswicks St
Briggs AssociatesClient:
TEM BULK SAMPLE ANALYSIS SUMMARY
08505NJ
9000 Commerce Parkway, Suite B Mount Laurel, NJ 08054
Toll Free 877-428-4285 Local: 856-231-9449
Fax: 856-231-9818
5/19/2011
Report No.: 240043
Description / Location:
Client No.:
IATL No.: 114293217A
14-04A
Tan Floor Tile;12x12 Bathroom
Gravimetrically Reduced Subsample:
Percent Asbestos Detected:
Percent Non-Asbestos Fibrous Material:
Percent Non-Fibrous Material:
ND
ND
20.9 %
None Detected
None Detected
Other
Organic Fraction: 79.1 %
20.9 %
Comments:
NIST-NVLAP No. 101165-0 AIHA-LAP, LLC No. 100188 NYS-DOH No. 11021
IATL assumes that all sampling methods and data upon which these results are based have been accurately supplied by the client.
Transmission Electron Microscopy (TEM) In Accordance With :
ELAP 198.4 "Method For Identifying And Quantitating Asbestos In Non-Friable Organically Bound Bulk Samples", Revised 1/11/2005. EPA-600/R- 93/116 Section 2.5 "Asbestos In Bulk Building Materials By TEM Gravimetry."
This confidential report relates only to those item(s) tested and does not represent an endorsement by NIST-NVLAP, AIHA or any agency of the U.S. government.
Results are verifiable for only those operations and analyses performed in the laboratory.
Methodology:
The "Gravimetrically Reduced Subsample" is the portion of the submitted sample remaining following the ashing and acid treatment processes. TEM analysis occurs on this portion of the sample. Final results are calculated to represent the sample as submitted.
Analysis Performed By:
Date:
J. Silcox
5/19/2011
VA Lyons Bldg 14
Project No.:
Project:
Report Date:
Bordentown
3 Crosswicks St
Briggs AssociatesClient:
TEM BULK SAMPLE ANALYSIS SUMMARY
08505NJ
9000 Commerce Parkway, Suite B Mount Laurel, NJ 08054
Toll Free 877-428-4285 Local: 856-231-9449
Fax: 856-231-9818
5/19/2011
Report No.: 240043
Under 12x12 FT
Description / Location:
Client No.:
IATL No.: 114293220A
14-05A
Black Mastic Bathroom
Gravimetrically Reduced Subsample:
Percent Asbestos Detected:
Percent Non-Asbestos Fibrous Material:
Percent Non-Fibrous Material:
ND
ND
11.6 %
None Detected
None Detected
Other
Organic Fraction: 88.4 %
11.6 %
Comments:
NIST-NVLAP No. 101165-0 AIHA-LAP, LLC No. 100188 NYS-DOH No. 11021
IATL assumes that all sampling methods and data upon which these results are based have been accurately supplied by the client.
Transmission Electron Microscopy (TEM) In Accordance With :
ELAP 198.4 "Method For Identifying And Quantitating Asbestos In Non-Friable Organically Bound Bulk Samples", Revised 1/11/2005. EPA-600/R- 93/116 Section 2.5 "Asbestos In Bulk Building Materials By TEM Gravimetry."
This confidential report relates only to those item(s) tested and does not represent an endorsement by NIST-NVLAP, AIHA or any agency of the U.S. government.
Results are verifiable for only those operations and analyses performed in the laboratory.
Methodology:
The "Gravimetrically Reduced Subsample" is the portion of the submitted sample remaining following the ashing and acid treatment processes. TEM analysis occurs on this portion of the sample. Final results are calculated to represent the sample as submitted.
Analysis Performed By:
Date:
J. Silcox
VA Lyons Bldg 14
Project No.:
Project:
Report Date:
Bordentown
3 Crosswicks St
Briggs AssociatesClient:
TEM BULK SAMPLE ANALYSIS SUMMARY
08505NJ
9000 Commerce Parkway, Suite B Mount Laurel, NJ 08054
Toll Free 877-428-4285 Local: 856-231-9449
Fax: 856-231-9818
5/19/2011
Report No.: 240043
Description / Location:
Client No.:
IATL No.: 114293223A
14-07A
Tan Window Glazing Exterior
Gravimetrically Reduced Subsample:
Percent Asbestos Detected:
Percent Non-Asbestos Fibrous Material:
Percent Non-Fibrous Material:
ND
1.10 %
54.4 %
None Detected
SiMg, Talc
Other
Organic Fraction: 44.5 %
55.5 %
Comments:
NIST-NVLAP No. 101165-0 AIHA-LAP, LLC No. 100188 NYS-DOH No. 11021
IATL assumes that all sampling methods and data upon which these results are based have been accurately supplied by the client.
Transmission Electron Microscopy (TEM) In Accordance With :
ELAP 198.4 "Method For Identifying And Quantitating Asbestos In Non-Friable Organically Bound Bulk Samples", Revised 1/11/2005. EPA-600/R- 93/116 Section 2.5 "Asbestos In Bulk Building Materials By TEM Gravimetry."
This confidential report relates only to those item(s) tested and does not represent an endorsement by NIST-NVLAP, AIHA or any agency of the U.S. government.
Results are verifiable for only those operations and analyses performed in the laboratory.
Methodology:
The "Gravimetrically Reduced Subsample" is the portion of the submitted sample remaining following the ashing and acid treatment processes. TEM analysis occurs on this portion of the sample. Final results are calculated to represent the sample as submitted.
Analysis Performed By:
Date:
J. Silcox
VA Lyons Bldg 14
Project No.:
Project:
Report Date:
Bordentown
3 Crosswicks St
Briggs AssociatesClient:
TEM BULK SAMPLE ANALYSIS SUMMARY
08505NJ
9000 Commerce Parkway, Suite B Mount Laurel, NJ 08054
Toll Free 877-428-4285 Local: 856-231-9449
Fax: 856-231-9818
10/12/2011
Report No.: 254375
Description / Location:
Client No.:
IATL No.: 114440034A
14-06A
Grey/Black Shingle Roof
Gravimetrically Reduced Subsample:
Percent Asbestos Detected:
Percent Non-Asbestos Fibrous Material:
Percent Non-Fibrous Material:
ND
ND
56.1 %
None Detected
None Detected
Other
Organic Fraction: 43.9 %
56.1 %
Comments:
NIST-NVLAP No. 101165-0 AIHA-LAP, LLC No. 100188 NYS-DOH No. 11021
IATL assumes that all sampling methods and data upon which these results are based have been accurately supplied by the client.
Transmission Electron Microscopy (TEM) In Accordance With :
ELAP 198.4 "Method For Identifying And Quantitating Asbestos In Non-Friable Organically Bound Bulk Samples", Revised 1/11/2005. EPA-600/R- 93/116 Section 2.5 "Asbestos In Bulk Building Materials By TEM Gravimetry."
This confidential report relates only to those item(s) tested and does not represent an endorsement by NIST-NVLAP, AIHA or any agency of the U.S. government.
Results are verifiable for only those operations and analyses performed in the laboratory.
Methodology:
The "Gravimetrically Reduced Subsample" is the portion of the submitted sample remaining following the ashing and acid treatment processes. TEM analysis occurs on this portion of the sample. Final results are calculated to represent the sample as submitted.
Analysis Performed By:
Date:
Approved By:
Frank E. Ehrenfeld, III Laboratory Director
C. Liska
10/12/2011