This document provides details of a federal contract opportunity for construction services. The Department of Veterans Affairs will issue a solicitation on November 30th for a firm fixed price construction contract between $1-2 million to renovate a portion of Building 7 at the VA Medical Center in Battle Creek, Michigan to house Mental Health programs and staff. Interested service-disabled veteran-owned small businesses have until the solicitation due date, to be specified later, to submit a response. The work must be completed within 280 calendar days. All bid documents will be available for download at Contract Opportunities and interested parties should register at that site to receive notifications.
View the file
Other files
Show all 20
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
3.7
2ND FLOOR - ORIGINAL
111'-4"
2ND FLOOR - ADDITION
112'-4"
REMOVE EXISTING MASONRY
KNEE WALL CONSTRUCTION
REMOVE EXISTING LOW WALL
FURRED CONSTRUCTION
REMOVE EXISTING DOUBLE METAL STUD
WITH GYP BD WALL CONSTRUCTION
REMOVE WALL BASE - SEE DEMO NOTES
REMOVE EXISTING FLOOR FINISH -
SEE DEMO NOTES
REMOVE EXISTING METAL STUD HEADER
REMOVE EXISTING SUSPENDED CEILING SYSTEM -
SEE DEMO NOTES
EXISTING BEAM ENCLOSURE TO REMAIN
EXISTING RAMP
EXISTING EXPANSION JOINT
EXISTING COLUMN
EXISTING ALUMINUM
CURTAIN WALL
NOTE:
CONTRACTOR TO VERIFY IN FIELD EXISTING WALL
CONSTRUCTION AND TO NOTIFY THE ARCHITECT
OF ANY MAJOR DISCREPENCIES
REMOVE EXISTING WOOD ON BEAM
ENCLOSURE ALONG ENTIRE WALL (PIER
TO PIER)
3.7
2ND FLOOR - ORIGINAL
111'-4"
2ND FLOOR - ADDITION
112'-4"
EXISTING RAMP - FEATHER OUT
SLOPE TO BE 2.86° (1:20) SLOPE
EXISTING EXPANSION JOINT
EXISTING COLUMN WITH NEW
BREAK METAL ENCLOSURE
EXISTING ALUMINUM
CURTAIN WALL
NEW EXPANSION JOINT COVER
BUILD OUT A WOOD CURB TO
MATCH OVERALL SIZE OF
EXISTING CURB
PROVIDE NEW EXPANSION JOINT COVER
WALL BASE
NEW CONCRETE LANDING
PARTITION TYPES
SEE PLAN FOR
2-HR WALL CONSTRUCTION
NEW SUSPENDED CEILING SYSTEM
NEW SUSPENDED CEILING
SYSTEM - RUN GYP. BD. UNDER
EXISTING BEAM ENCLOSURE
NEW EXPANSION JOINT COVER
SEE REFLECTED CEILING PLAN
8 1/16" ±
LEVEL
6' - 0" 6' - 2 19/128" ±
NOTE:
CONTRACTOR TO VERIFY IN FIELD EXISTING WALL
CONSTRUCTION AND TO NOTIFY THE ARCHITECT
OF ANY MAJOR DISCREPENCIES
NEW CONCRETE RAMP - 2.86° (1:20) SLOPE
PROVIDE SPRAY APPLIED FIRE PROOFING
INSIDE BEAM CAVITY. SPRAY AROUND
STEEL BEAM, ON BACK WALL, FULL HEIGHT
UP TO ROOF STRUCTURE ABOVE (FROM
PIER TO PIER) TO MAINTAIN 2HR FIRE
RATING
NEW 3/4" PARTICLE BOARD (PIER TO PIER)
architecture · engineering
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERS · SURVEYORS · CONSULTANTS ·
LANDSCAPE ARCHITECTS · LAND PLANNERS
298 VETERANS DRIVE
FOWLERVILLE,
MICHIGAN 48836
(OFFICE) 517-223-3512
(FAX) 517-223-9987
211 E. Water Street, Suite 213L
Kalamazoo, MI 49007 269.216.0222
VA STATION
Battle Creek VA Medical Center
5500 Armstrong Road
Battle Creek, MI 49037
Defining
EXCELLENCE
in the 21st Century
HEALTH
CARE
C :\R ev it\
\1
4_
A _m ic he lle .b ur ri.
rv t
5/
/2
:2 5:
A
M
39-A311
WALL SECTIONS RENOVATE B39-2 WEST
FOR PATIENT PRIVACY
BATTLE CREEK, MI
515-20-102
05/20/2021 KJH MRB/MMN
100% BID DOCUMENTS190134
3/4" = 1'-0"39-AD102
1 CONNECTOR RAMP SECTION - DEMOLITION
3/4" = 1'-0"39-A133
2 CONNECTOR RAMP SECTION - NEW (THROUGH WALL)
Revisions: Date:
65% DESIGN DEVELOPMENT 03/06/2020
RESUBMIT WITH OWNER CHANGES 10/02/2020
95% CONSTRUCTION DOCUMENTS 04/12/2021
100% BID DOCUMENTS 05/20/2021
SOLID SURFACE WALL PANEL
SEALANT
RECESSED SOLID
SURFACE SHOWER PAN
EXISTING CONCRETE SLAB
FIN. FLOOR
RECESS
EXISTING 2" DEPRESSION,
PLUMBER TO INSTALL PAN
& ADD FILLER TO ADJUST
PAN TO PROPER DEPTH AS
PER MANUFACTURER
SPECIFICATIONS
0'
1/
8"
SHOWER PAN TO BE FLUSH WITH
FINISHED FLOORING
SEE FLOOR PLANS
2.0° SLOPE (AVG.)
0'
2"
FOR PARTITION TYPE
REFER TO PLANS
NEW CONCRETE TO
INFILL REMAINDER OF 2"
DEPRESSION
5/8" TYPE 'X' HIGH IMPACT
GYP. BD. OVER Z-FURRING.
EMBED Z-FURRING IN
FIREPROOFING, PATCH
FIREPROOFING AS REQUIRED
TO MAINTAIN FIRE RATING.
EXISTING FIREPROOFED STEEL
COLUMN
EXISTING TRTD. WOOD BLOCKING
EXISTING ALUM CURTAIN
WALL
EXISTING EIFS (3"
INSULATION) ON 5/8" GLASS-
MAT GYPSUM SHEATHING ON
4" METAL STUDS
1'
4"
1' - 4"
SEALANT
0.8
F
EXISTING STEEL COLUMN
WRAPPED IN 2 LAYERS OF 5/8"
TYPE 'X' HIGH IMPACT GYP. BD.
EXISTING ALUM.
CURTAIN WALL
MTL COLUMN COVER,
COLOR TO MATCH
EXISTING CURTAINWALL -
BONE WHITE
3/
4"
9 3/4" ±
3.7
A.9
5/8" TYPE 'X' HIGH
IMPACT GYP. BD.
EXIST STEEL COLUMN
EXISTING TRTD. WOOD BLOCKING
EXISTING ALUM CURTAIN
WALL
EXISTING EIFS ON 2 1/2"
DENSGLASS 8" MTL STUD
AND 5/8" GYP. BD.
A
REMOVE EXISTING SPRAY APPLIED FIRE
PROOFING AND SHEATHING AS REQ'D FOR
NEW WORK
EXIST TYP MTL STUD, TYP.
TREATED WOOD BLOCKING
PARTITION TYPES
SEE PLAN FOR
P A
R T
IT
IO
N T
Y P
E S
S E
E P
LA
N
F O
R
5/8" TYPE 'X' HIGH
IMPACT GYP. BD. OVER
1 5/8" METAL STUD
EXISTING STEEL COLUMN
ADJUSTABLE METAL CORNER
BEAD, TYP.
ADJUSTABLE METAL CORNER
BEAD, TYP.
P A
R T
IT
IO
N T
Y P
E S
S E
E P
LA
N
F O
R
REMOVE EXISTING SPRAY
APPLIED FIRE PROOFING AS
REQ'D FOR NEW WORK
I
SEAMLESS ACOUSTICAL
CEILING SYSTEM
WALL CONSTRUCTION,
REFER TO FLOOR PLAN
FOR PARTITION TYPE
GYPSUM BOARD CEILING SYSTEM
METAL CORNER BEAD, TYP.
SEE REFLECTED
CEILING PLAN
SEAMLESS ACOUSTICAL
CEILING SYSTEM
SEE REFLECTED
CEILING PLAN
SEE REFLECTED
CEILING PLAN
SEE REFLECTED
CEILING PLAN
METAL CORNER BEAD, TYP.
SEE REFLECTED
CEILING PLAN
SEAMLESS ACOUSTICAL
CEILING SYSTEM
SEAMLESS ACOUSTICAL
CEILING SYSTEM
SEAMLESS ACOUSTICAL
CEILING SYSTEM
GYPSUM BOARD
CEILING SYSTEM
CEILING PLAN
VARES- SEE REFLECTED METAL CORNER BEAD, TYP.
EXIST LT. GA. METAL BOX
HEADER
EXIST 2X WD NAILER
5/8" TYPE 'X' HIGH IMPACT
GYP. BD.
METAL CORNER BEAD
TRIM
GYP. BD. JAMB BEYOND
EXIST ALUMINUM WINDOW
EXISTING EXTERIOR WALL
CONSTRUCTION. EIFS/ BRICK
5/8" TYPE 'X' HIGH IMPACT
GYP. BD.
EXIST DOUBLE METAL
STUD @ EA. JAMB
EXIST 2X WD NAILER
SOLID SURFACE SILL BELOW
EXIST ALUMINUM WINDOW
5/8" TYPE 'X' HIGH
IMPACT GYP. BD.
5/8" TYPE 'X' HIGH
IMPACT GYP. BD.
METAL CORNER BEAD
TRIM
EXISTING EXTERIOR WALL
CONSTRUCTION. EIFS/ BRICK
EXIST ALUMINUM WINDOW
SOLID SURFACE SILL
EXIST 2X WD NAILER
3"
5/8" TYPE 'X' HIGH
IMPACT GYP. BD.
EXISTING EXTERIOR WALL
CONSTRUCTION. EIFS/ BRICK
SEALANT
GYP. BD. JAMB BEYOND
5/8" TYPE 'X' HIGH
IMPACT GYP. BD. EXIST STEEL COLUMN
EXISTING TRTD. WOOD BLOCKING
EXISTING ALUM CURTAIN
WALL
EXISTING EIFS ON 2 1/2"
DENSGLASS 8" MTL STUD
AND 5/8" GYP.
EXIST 5/8" GYP. BD.
METAL CORNER BEAD
1.8
A
MTL STUDS @ 48" O.C. MAX.
FACE OF WALL
MTL STUDS @ 16" O.C. MAX.
WOOD SHIM - SCRIBE TO FIT (TYP.)
CASEWORK TYP. - REFER TO
CASEWORK DETAILS
1"
UNLESS
SHOWN
OTHERWISE
SEE REFLECTED
CEILING PLAN
PLAM FACED WOOD
STOP - SCRIBE TO FIT
(TYP.)
GYP. BD.
1' - 1"
6"
SEAMLESS ACOUSTICAL
CEILING SYSTEM
SEE REFLECTED
CEILING PLAN
1/4" SOLID SURFACE
MATERIAL (SSM-2) TYP.
EASED EDGE, TYP. ALL
EXPOSED EDGES
3 3/4" 3 3/4"
1' - 1 1/2"
1/
2"
1/ 2"
7"
39-A501
39-A501
INSIDE OF BOX BEHIND
SOLID SURFACE MATERIAL
3/ 8"
4" 3/
8"
TAMPER RESISTANT
FASTENER, TYP
1/
2" 4"
1/
2"
4"
2x WOOD BLOCKING
1/4" SOLID SURFACE
MATERIAL (SSM-2) TYP.
EASED EDGE, TYP. ALL
EXPOSED EDGES
2x WOOD BLOCKING
TAMPER RESISTANT FASTENER, TYP
PARTITION TYPES
SEE PLAN FOR
1 1/2"10 1/2"1 1/2"
4"
1/4" SOLID SURFACE
MATERIAL (SSM-2) TYP.
EASED EDGE, TYP. ALL
EXPOSED EDGES
2x WOOD BLOCKING
BELOW BOX
2 1/4" 6" 2 1/4"
P A
R T
IT
IO
N T
Y P
E S
S E
E P
LA
N
F O
R
2'
0"
1' - 6"
6" 4"
WOOD SIDE PANEL
WOOD CABINET
BULKHEAD, TYP. SEE TYP.
BULKHEAD DETAIL AT
CASEWORK
WOOD SHIM -
SCRIBE TO FIT (TYP.)
PLAM FACED WOOD STOP -
SCRIBE TO FIT (TYP.)
ELECTRICAL
OUTLET, TYP.
1/ 4"
WALL CONSTRUCTION,
REFER TO PLANS FOR
SPECIFIC PARTITION TYPE.
5/8" TYPE 'X' HIGH IMPACT
GYP. BD.
J BEAD, TYP.
CAULK, ENTIRE PERIMETER
FLOORING, TYP
1/4"
RIGID WALL PROTECTION,
SEE FINISH SCHEDULE
5/8" TYPE 'X' HIGH IMPACT
GYP. BD. OVER EXIST. STUDS.
PATCH FIREPROOFING AS
REQUIRED TO MAINTAIN FIRE
RATING.
EXISTING ALUM CURTAIN
WALL
EXISTING EIFS (3"
INSULATION) ON 5/8" GLASS-
MAT GYPSUM SHEATHING ON
4" METAL STUDS
SEALANT
GYP. BD. & METAL STUD
PARTITION - SEE PARTITION
TYPES
REMOVE FIN TUBE - SEE
MECHANICAL
REMOVE EXISTING SOLID
SURFACE CORNER GUARD
REMOVE WALL BASE - SEE DEMO NOTES
REMOVE EXISTING FLOOR FINISH -
SEE DEMO NOTES
NOTE:
CONTRACTOR TO VERIFY IN FIELD EXISTING WALL
CONSTRUCTION AND TO NOTIFY THE ARCHITECT
OF ANY MAJOR DISCREPENCIES
REMOVE EXISTING SOLID
SURFACE SILL
REMOVE TOP LAYER OF GYPSUM
BOARD
EXISTING WALL BEYOND TO
REMAIN
EXISTING WINDOW
SYSTEM TO REMAIN
EXISTING SOLID
SURFACE TRIM TO
REMAIN
EXISTING WALL
CONSTRUCTION TO REMAIN
EXISTING FLOOR SLAB
TO REMAIN
NOTE:
CONTRACTOR TO VERIFY IN FIELD EXISTING WALL
CONSTRUCTION AND TO NOTIFY THE ARCHITECT
OF ANY MAJOR DISCREPENCIES
FIN TUBE & LOUVERS - SEE
MECHANICAL DRAWINGS
CONCRETE RAMP
1/2" SOLID SURFACE SILL
SOLID SURFACE CORNER
GUARD BEYOND, MATCH
EXISTING COLOR AND SIZE
EXISTING WINDOW
SYSTEM TO REMAIN
EXISTING WALL
CONSTRUCTION TO REMAIN
EXISTING FLOOR SLAB
TO REMAIN
EXISTING SOLID
SURFACE TRIM TO
REMAIN
SEALANT
4"
2 1/2" METAL STUD
HIGH IMPACT GYP. BD.
architecture · engineering
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERS · SURVEYORS · CONSULTANTS ·
LANDSCAPE ARCHITECTS · LAND PLANNERS
298 VETERANS DRIVE
FOWLERVILLE,
MICHIGAN 48836
(OFFICE) 517-223-3512
(FAX) 517-223-9987
211 E. Water Street, Suite 213L
Kalamazoo, MI 49007 269.216.0222
VA STATION
Battle Creek VA Medical Center
5500 Armstrong Road
Battle Creek, MI 49037
Defining
EXCELLENCE
in the 21st Century
HEALTH
CARE
C :\R ev it\
\1
4_
A _m ic he lle .b ur ri.
rv t
5/
/2
:2 6:
A
M
39-A501
ARCHITECTURAL DETAILS RENOVATE B39-2 WEST
FOR PATIENT PRIVACY
BATTLE CREEK, MI
515-20-102
05/20/2021 KJH MRB/MMN
100% BID DOCUMENTS190134
3" = 1'-0"39-A132
16 SHOWER PAN DETAIL
1" = 1'-0"39-A102
3 COLUMN PLAN DETAIL
1 1/2" = 1'-0"39-A102
5 COLUMN PLAN DETAIL
1 1/2" = 1'-0"39-A102
8 A/2 COLUMN PLAN DETAIL (K/2 OPP.)
1 1/2" = 1'-0"39-A132
4 COLUMN PLAN DETAIL
1 1/2" = 1'-0"39-A112
10 CEILING BULKHEAD DETAIL
1 1/2" = 1'-0"39-A112
9 CEILING BULKHEAD DETAIL
1 1/2" = 1'-0"39-A102
12 WINDOW HEAD DETAIL AT EXISTING EXTERIOR WALL
1 1/2" = 1'-0"39-A102
7 WINDOW JAMB DETAIL AT EXISTING EXTERIOR WALL
1 1/2" = 1'-0"39-A102
1 WINDOW SILL DETAIL AT EXISTING EXTERIOR WALL
1 1/2" = 1'-0"39-A102
2 A/1.8 COLUMN PLAN DETAIL (K/1.8 OPP.)
1 1/2" = 1'-0"
11 TYPICAL BULKHEAD DETAIL AT CASEWORK
3" = 1'-0"39-I203
17 PAPER TOWEL DISPENSER - FRONT
3" = 1'-0"39-A501
18 PAPER TOWEL DISPENSER - SECTION
3" = 1'-0"39-A501
19 PAPER TOWEL DISPENSER - PLAN
1" = 1'-0"
6 MICROWAVE CABINET DETAIL
12" = 1'-0"39-I203
13 TOILET ROOM TYP. WALL TO FLOOR TRANSITION
1 1/2" = 1'-0"39-A132
20 STOREFRONT END PLAN DETAIL
1 1/2" = 1'-0"39-A133
14 RADIANT HEAT ENCLOSURE DEMOLITION
1 1/2" = 1'-0"39-A133
15 RADIANT HEAT ENCLOSURE NEW
Revisions: Date:
65% DESIGN DEVELOPMENT 03/06/2020
RESUBMIT WITH OWNER CHANGES 10/02/2020
10"
4 1/4" 1"
4 3/4"
/2
1"
A C
R Y
L
IC
G L
A Z
IN
G
R E
C E
S S
E D
1"
SOLID SURFACE COUNTERTOP
ON WD SUBSTRATE
1/2" RADIUS, BOTH SIDES
SEALANT, BOTH SIDES
METAL ANGLE, SECURED TO TOP
OF 2X WD BLOCKING, PROVIDE
CONTINUOUS PRESSURE TO
SECURE ACRYLIC GLAZING
2X WD BLOCKING
NEOPRENE SEAL, TYP. BETWEEN
METAL ANGLE AND ACRYLIC
GLAZING
RIGID WALL PROTECTION OVER
1/2" WD SUBSTRATE
1/2" x 4" HORIZONTAL RIGID WALL
PROTECTION TRIM TYP.
3/8" x 4" VERTICAL RIGID WALL
PROTECTION TRIM, TYP. BEYOND
RIGID WALL PROTECTION
OVER 3/4" WD SUBSTRATE
RIGID WALL PROTECTION
OVER 1/2" WD SUBSTRATE
1/4" RESIN PANEL
1/2" CLEAR CAST ACRYLIC SHEET
GLAZING
GROMMET
10"
4 1/4" 1"
4 3/4"
/2
1"
A C
R Y
L
IC
G L
A Z
IN
G
R E
C E
S S
E D
1"
SOLID SURFACE COUNTERTOP ON
WD SUBSTRATE
1/2" RADIUS, BOTH SIDES
SEALANT, BOTH SIDES
METAL ANGLE, SECURED TO TOP OF
2X WD BLOCKING, PROVIDE
CONTINUOUS PRESSURE TO SECURE
ACRYLIC GLAZING
2X WD BLOCKING
NEOPRENE SEAL, TYP. BETWEEN
METAL ANGLE AND ACRYLIC GLAZING
RIGID WALL PROTECTION OVER 1/2"
WD SUBSTRATE
1/2" x 4" HORIZONTAL RIGID WALL
PROTECTION TRIM TYP.
3/8" x 4" VERTICAL RIGID WALL
PROTECTION TRIM, TYP. BEYOND
RIGID WALL PROTECTION
OVER 3/4" WD SUBSTRATE
RIGID WALL PROTECTION
OVER 1/2" WD SUBSTRATE
1/2" CLEAR CAST ACRYLIC SHEET
GLAZING
3/4" WD SUBSTRATE
7"
4" 4"
E Q
4"
E Q
4"
E Q
1/ 2"
1/2" CLEAR CAST ACRYLIC
SHEET GLAZING
10" 24"
/2
GROMMET
SOLID SURFACE
COUNERTOP ON
WD SUBSTRATE
COUNTERTOP SUPPORT
BRACKET
CUT-OUT FOR
ELECTRICAL CONDUIT
RIGID WALL PROTECTION OVER
3/4" WD SUBSTRATE
BASE
39-A502
RIDGID WALL PROTECTION OVER
1/2" WD SUBSTRATE
1/2" x 4" HORIZONTAL RIGID WALL
PROTECTION TRIM TYP.
3/8" x 4" VERTICAL RIGID WALL
PROTECTION TRIM, TYP. BEYOND
1/4" RESIN PANEL
RIDGID WALL PROTECTION OVER
1/4" WD SUBSTRATE
3/4" SUBSRATE
1"1"
FINISHED FLOOR
7"
/2
/2
1/2" CLEAR CAST ACRYLIC
SHEET GLAZING
10" 24"
/2
GROMMET
SOLID SURFACE
COUNERTOP ON
WD SUBSTRATE
COUNTERTOP SUPPORT
BRACKET
CUT-OUT FOR ELECTRICAL
CONDUIT
RIGID WALL PROTECTION OVER
3/4" WD SUBSTRATE
BASE
39-A502
1/2" x 4" HORIZONTAL RIGID
WALL PROTECTION TRIM TYP.
3/8" x 4" VERTICAL RIGID WALL
PROTECTION TRIM, TYP. BEYOND
RIDGID WALL PROTECTION
OVER 1/2" WD SUBSTRATE
3/4" SUBSRATE
1"1"
FINISHED FLOOR
7"
4" 4"
E Q
4"
E Q
4"
E Q
1/ 2"
1/2" CLEAR CAST ACRYLIC
SHEET GLAZING
10"
/2
EXISTING SOLID SURFACE
COUNERTOP MODIFIED TO
FIT NEW DESK LAYOUT
EXISTING COUNTERTOP SUPPORT
BRACKET
MODIFY EXISTING VERTICAL
SUPPORTS AS REQUIRED FOR NEW
DESK DESIGN
BASE
39-A502
RIGID WALL PROTECTION OVER
1/2" WD SUBSTRATE
1/2" x 4" HORIZONTAL RIGID WALL
PROTECTION TRIM TYP.
3/8" x 4" VERTICAL RIGID WALL
PROTECTION TRIM, TYP. BEYOND
1/4" RESIN PANEL
RIGID WALL PROTECTION OVER
1/4" WD SUBSTRATE
3/4" SUBSRATE
1"1"
FINISHED FLOOR
SIM
EXISTING DESK CONSTRUCTION TO
REMAIN, CONTRACTOR TO VERIFY
IN FIELD ACTUAL CONSTRUCTION
EXISTING 2x6 BOTTOM PLAE, MODIFY
AS REQ'D FOR NEW DESK DESIGN
EXISTING BASE CABINET TO BE
RELOCATED AS SHOWN IN ELEVATION
FINISH ENDS TO MATCH
SOLID SURFACE COUNERTOP
ON WD SUBSTRATE
RIGID WALL PROTECTION
OVER 3/4" WD SUBSTRATE
BASE
FINISHED FLOOR
5"
SOLID SURFACE COUNTERTOP
ON WD SUBSTRATE
1/2" RADIUS, BOTH SIDES
7"
1" 1"
/2
7"
/2
/2
1/2" CLEAR CAST ACRYLIC
SHEET GLAZING
10"
/2
"SOLID SURFACE
COUNERTOP ON
WD SUBSTRATE
CUT-OUT FOR ELECTRICAL
CONDUIT
BASE
1/2" x 4" HORIZONTAL RIGID WALL
PROTECTION TRIM TYP.
3/8" x 4" VERTICAL RIGID WALL
PROTECTION TRIM, TYP. BEYOND
RIGID WALL PROTECTION OVER
1/2" WD SUBSTRATE
3/4" SUBSRATE
1"1"
FINISHED FLOOR
BASE CABINET -
HARDWOOD VENEERED
PLYWOOD, BOX/ BOX/
FILE DRAWERS
WALL BASE
1"
25"
7"
4" 4"
E Q
4"
E Q
4"
E Q
1/ 2"
1/2" CLEAR CAST ACRYLIC
SHEET GLAZING
10"
RIDGID WALL PROTECTION OVER
1/2" WD SUBSTRATE
1/2" x 4" HORIZONTAL RIGID
WALL PROTECTION TRIM TYP.
3/8" x 4" VERTICAL RIGID WALL
PROTECTION TRIM, TYP. BEYOND
1/4" RESIN PANEL
RIDGID WALL PROTECTION OVER
1/4" WD SUBSTRATE
3/4" SUBSRATE
1"1"
FINISHED FLOOR
SOLID SURFACE
COUNERTOP ON
WD SUBSTRATE
BASE CABINET -
HARDWOOD VENEERED
PLYWOOD, BOX/ BOX/
FILE DRAWERS
WALL BASE
0"24"
/2
25"
7"
/4
FINISHED WALL
ANCHOR METAL STUD TO EXISTING
COLUMN OR NEW WD BLOCKING
RIGID WALL PROTECTION OVER 3/4" WD
SUBSTRATE, TYP.
DOUBLE METAL STUD @ JAMB - 550S200-68 (GRADE 33)
DOOR SEE DOOR SCHEDULE
1 x 2 WOOD STOP, COORDINATE LOCATION
WITH DOOR AND DOOR HARDWARE
1" WD SUBSTRATE
7"
RIGID WALL PROTECTION OVER 3/4"
WD SUBSTRATE, TYP.
DOUBLE METAL STUD @ JAMB - 550S200-68 (GRADE 33)
DOOR SEE DOOR SCHEDULE
1 x 2 WOOD STOP, COORDINATE
LOCATION WITH DOOR AND DOOR
HARDWARE
SIMPSON STRONG TIE RCKW5.5 W/ STIFFENER;
FASTEN TO STUD W/ (10) #12 SCREWS - PATTERN 4B
(2) 3/8" DIA. A193, GR B7 ANCHOR ROD; ADHESIVE
ANCHORED W/ SIMPSON STRONG TIE SET-3G AND 2
3/4" MIN. EFFECTIVE EMBDMENT
9"
1" 7"
1"
CONTINUOUS SILICONE SEALANT - ALL VERTICAL EDGES
SOLID SURFACE COUNTERTOP OVER WD SUBSTRATE
EDGE OF DESK BELOW
1/2" CLEAR CAST ACRYLIC SHEET GLAZING10"
7"
RIGID WALL PROTECTION OVER 3/4"
WD SUBSTRATE, TYP.
DOUBLE METAL STUD @ JAMB - 550S200-68 (GRADE 33)
DOOR SEE DOOR SCHEDULE
1 x 2 WOOD STOP, COORDINATE
LOCATION WITH DOOR AND DOOR
HARDWARE
SIMPSON STRONG TIE RCKW5.5 W/ STIFFENER;
FASTEN TO STUD W/ (10) #12 SCREWS - PATTERN 4B
(2) 3/8" DIA. A193, GR B7 ANCHOR ROD; ADHESIVE
ANCHORED W/ SIMPSON STRONG TIE SET-3G AND 2
3/4" MIN. EFFECTIVE EMBDMENT
9"
1" 7"
1"
10"
3/8" x 4" VERTICAL RIGID WALL
PROTECTION TRIM, TYP.
1" WD SUBSTRATE
DOOR SEE DOOR SCHEDULE
1 x 2 WOOD STOP, COORDINATE
LOCATION WITH DOOR AND DOOR
HARDWARE
7"
V.I.F
VARIES
SEALANT, ALONG ENTIRE TOP EDGE
SEALANT
CONTRACTOR TO VERIFY OVERALL HEAD
HEIGHT. SECURE HEAD TO BULKHEAD
FRAMING FOR STABILIZATION
METAL STUD BRACING @ 48" O.C.
EXISTING BULKHEAD - CONTRACTOR TO
VERIFY IN FIELD HEIGHT
2 1/2" METAL STUD
JAMB BEYOND
DOUBLE METAL STUD BOX HEADER -
550S162
5 1/2" METAL STUD
DOOR SEE DOOR SCHEDULE
1 x 2 WOOD STOP, COORDINATE LOCATION
WITH DOOR AND DOOR HARDWARE
SIMPSON STRONG TIE RCKW5.5 W/ STIFFENER;
FASTEN TO STUD W/ (10) #12 SCREWS - PATTERN 4B
(2) 3/8" DIA. A193, GR B7 ANCHOR ROD; ADHESIVE
ANCHORED W/ SIMPSON STRONG TIE SET-3G AND 2
3/4" MIN. EFFECTIVE EMBDMENT
7"
V A
R
IE
S S
E E
P
LA
N 7"
RIGID WALL PROTECTION OVER 3/4"
WD SUBSTRATE, TYP.
DOUBLE METAL STUD @ JAMB - 550S200-68 (GRADE 33)
7"
5 1/2" METAL STUD
DOUBLE METAL STUD @ JAMB - 550S200-68 (GRADE 33)
DOOR SEE DOOR SCHEDULE
1 x 2 WOOD STOP, COORDINATE
LOCATION WITH DOOR AND DOOR
HARDWARE
SIMPSON STRONG TIE RCKW5.5 W/
STIFFENER; FASTEN TO STUD W/
(10) #12 SCREWS - PATTERN 4B
EXISTING CONSTRUCTION TO
REMAIN, MODIFY AS REQUIRED
FOR NEW DESK DESIGN7"
7"
SOLID SURFACE
COUNTERTOP ABOVE
1 x 4 HARDWOOD TRIM, TYP.
7"
(2) 3/8" DIA. A193, GR B7 ANCHOR ROD; ADHESIVE
ANCHORED W/ SIMPSON STRONG TIE SET-3G AND 2
3/4" MIN. EFFECTIVE EMBDMENT
V A
R
IE
S
PLAM ON 3/4" SUBSTRATE
DOOR SEE DOOR SCHEDULE
1 x 2 WOOD STOP, COORDINATE
LOCATION WITH DOOR AND DOOR
HARDWARE
VARIES 7"
SEALANT, ALONG ENTIRE
TOP EDGE, BOTH SIDES
EXISTING BULKHEAD - CONTRACTOR TO
VERIFY OVERALL HEAD HEIGHT.
SECURE HEAD TO BULKHEAD FRAMING
FOR STABILIZATION
JAMB BEYOND
DOUBLE METAL STUD BOX HEADER -
550S162
V A
R
IE
S architecture · engineering
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERS · SURVEYORS · CONSULTANTS ·
LANDSCAPE ARCHITECTS · LAND PLANNERS
298 VETERANS DRIVE
FOWLERVILLE,
MICHIGAN 48836
(OFFICE) 517-223-3512
(FAX) 517-223-9987
211 E. Water Street, Suite 213L
Kalamazoo, MI 49007 269.216.0222
VA STATION
Battle Creek VA Medical Center
5500 Armstrong Road
Battle Creek, MI 49037
Defining
EXCELLENCE
in the 21st Century
HEALTH
CARE
C :\R ev it\
\1
4_
A _m ic he lle .b ur ri.
rv t
5/
/2
:2 6:
A
M
39-A502
NURSE STATION DETAILS RENOVATE B39-2 WEST
FOR PATIENT PRIVACY
BATTLE CREEK, MI
515-20-102
05/20/2021 KJH MRB/MMN
100% BID DOCUMENTS190134
3" = 1'-0"39-A502
5 ENLARGED DESK DETAIL 1W & 2W
3" = 1'-0"39-A502
6 ENLARGED DESK DETAIL 1 N/S & 2N/S
1" = 1'-0"39-A131
1 2 W NURSE STATION
1" = 1'-0"39-A130
2 1 N/S & 2 N/S NURSE STATION
1" = 1'-0"39-A131
3 1 W NURSE STATION
1 1/2" = 1'-0"39-A130
4 NURSE STATION END WALL
1" = 1'-0"39-I202
7 1 N/S & 2 N/S NURSE STATION FILE
1" = 1'-0"39-A131
8 2 W NURSE STATION FILE
1 1/2" = 1'-0"39-A130
9 1 N/S, 2 N/S, 1 W NURSE STATION - DOOR JAMB
1 1/2" = 1'-0"39-A130
10 1 N/S & 2 N/S NURSE STATION - DOOR JAMB HIGH
1 1/2" = 1'-0"39-A130
12 1 N/S & 2 N/S NURSE STATION - DOOR JAMB LOW
1 1/2" = 1'-0"39-A130
13 1 N/S & 2 N/S NURSE STATION - DOOR HEAD 1
1 1/2" = 1'-0"39-A130
14 1 N/S & 2 N/S NURSE STATION - DOOR JAMB1 1/2" = 1'-0"39-A131
15 1 W NURSE STATION - JAMB
1 1/2" = 1'-0"39-A130
11 1 N/S & 2 N/S NURSE STATION - DOOR HEAD 2
Revisions: Date:
EXISTING T.V. CABINET TO BE RELOCATED. MODIFY AS REQ'D
FOR NEW LOCATION AND ADDITION OF THE FIREPLACE. SECURE
TO WALL WITH CONCEALED SECURITY FASTENERS, BRACKETS,
AND ANCHORS. REFER TO DETAILS ON THIS SHEET FOR
ADDITIONAL INFORMATION ON MODIFICATIONS REQUIRED.
PROVIDE NEW END PANEL,
TYP. BOTH SIDES. MATCH
EXISTING MATERIAL AND
STAIN
REMOVE METAL WIRE MESH
REMOVE SOLID INFILL
FOR INSTALLATION OF
NEW WIRE MESH, BOTH
SIDES
CONTRACTOR TO VERIFY
MATERIAL BEHIND FLAT
SCREEN TV.
39-A503
Sim
NOTE: CONTRACTOR TO MATCH THE DESIGN INTENT OF THE EXISTING T.V. CABINET IN
2 SOUTH, DAY ROOM 245. ALL DIMENSIONS SHOWN ARE FOR REFERENCE ONLY.
CONTRACTOR IS RESPONSIBLE TO IDENTIFY AND VERIFY ALL DIMENSIONS REQUIRED
TO DUPLICATE CABINET.
56"
9" 37 1/2" 9"
1/
2"
/4
3/ 4"
5" 5"
/2
62"
39-A503
39-A503
METAL MESH TO
MATCH EXISTING
WOOD BASE, ALL SIDES,
MATCH EXISTING MATERIAL
AND FINISH
E Q
E Q
ACRYLIC SHEET, ANTI-GLARE,
IN FRONT OF FIREPLACE
INSERT
2x HARD WOOD LUMBER TO
MATCH EXISTING MATERIAL
AND FINISH
39-A503
AT DAY ROOM 245
REPLACE MESH COVER ON
EXISTING TV VOLUME BUMPOUT
TO MATCH NEW MESH BELOW, DO
NOT ROUTE HOLES INTO MESH.
AT DAY ROOM 208
PROVIDE METAL MESH TO MATCH
EXISTING
ELECTRICAL OUTLET & TV
SERVICE CONNECTION
METAL MESH TO
MATCH EXISTING
AIR CIRCULATION AND
SOUND TRANSMISSION
BOX
CROWN MOLDING TO
MATCH EXISTING
ACRYLIC SHEET,
ANTI-GLARE
CROWN MOLDING TO
MATCH EXISTING
FIREPLACE INSERT. BASIS OF
DESIGN DIMPLEX "OPTI-V
SOLO BUILT IN FIREPLACE,
MODEL VF2927L"
9 1/2"
7"
T.V. CAVITY
ACRYLIC SHEET, ANTI-GLARE
NOTE: CONTRACTOR TO MATCH THE DESIGN INTENT OF THE EXISTING T.V. CABINET IN
2 SOUTH, DAY ROOM 245. ALL DIMENSIONS SHOWN ARE FOR REFERENCE ONLY.
CONTRACTOR IS RESPONSIBLE TO IDENTIFY AND VERIFY ALL DIMENSIONS REQUIRED
TO DUPLICATE CABINET.
39-A503
/4
ACRYLIC SHEET, ANTI-GLARE
ATTACH TO ROUTED WOOD, TYP.
MUST BE ABLE TO REMOVE
ACRYLIC AND TRIM UNIT TO
ALLOW MAINTENANCE TO
FIREPLACE BEYOND. SECURE
WITH TAMPER RESISTANT
SCREWS
FINISHED FACE PLYWOOD,
PAINTED BLACK, TYP.
2x HARDWOOD LUMBER TRIM
MATCH EXISTING CONSTRUCTION
AND FINISH, TYP.
WOOD TRIM BASE, MATCH
EXISTING CONSTRUCTION AND
FINISH
FINISHED FACE PLYWOOD,
PAINTED BLACK, TYP.
2x WOOD BLOCKING
METAL STUD & GYP. BD.
PARTITION - SEE
PARTITION TYPES
2x WOOD BLOCKING
1" 1"
5/8"
1' - 1 3/4"
1 3/8"
FIREPLACE INSERT.
BASIS OF DESIGN
DIMPLEX "OPTI-V SOLO
BUILT IN FIREPLACE,
MODEL VF2927L"
39-A503
ALIGN
FINISHED FACE PLYWOOD,
PAINTED BLACK, TYP.
WOOD TRIM BASE, MATCH
EXISTING CONSTRUCTION
AND FINISH
METAL STUD & GYP. BD.
PARTITION - SEE
PARTITION TYPES
BLACK METAL MESH
FIREPLACE INSERT. BASIS
OF DESIGN DIMPLEX "OPTI-V
SOLO BUILT IN FIREPLACE,
MODEL VF2927L"
ACRYLIC SHEET, ANTI-
GLARE ATTACH TO ROUTED
WOOD, TYP.
EQ EQ
1/
2"
10" 3' - 0 1/2" 10"
1/
2"
1/
4" 1'
1"
3/
8"
NOTE: CONTRACTOR TO MATCH THE DESIGN INTENT OF THE EXISTING T.V. CABINET IN
2 SOUTH, DAY ROOM 245. ALL DIMENSIONS SHOWN ARE FOR REFERENCE ONLY.
CONTRACTOR IS RESPONSIBLE TO IDENTIFY AND VERIFY ALL DIMENSIONS REQUIRED
TO DUPLICATE CABINET.
39-A503
ALIGN
FINISHED FACE PLYWOOD,
PAINTED BLACK, TYP.
WOOD TRIM, MATCH
EXISTING CONSTRUCTION
AND FINISH
METAL STUD & GYP. BD.
PARTITION - SEE
PARTITION TYPES
ACRYLIC SHEET, ANTI-
GLARE ATTACH TO ROUTED
WOOD, TYP.
EQ EQ
3/
8"
3" 4' - 8" 3"
3/
8"
NOTE: CONTRACTOR TO MATCH THE DESIGN INTENT OF THE EXISTING T.V. CABINET IN
2 SOUTH, DAY ROOM 245. ALL DIMENSIONS SHOWN ARE FOR REFERENCE ONLY.
CONTRACTOR IS RESPONSIBLE TO IDENTIFY AND VERIFY ALL DIMENSIONS REQUIRED
TO DUPLICATE CABINET.
ALIGN
ROLL-UP DOOR -
SEE SCHEDULE
METAL GUIDE
5/8" GYPSUM BOARD
ON METAL STUD
FRAMING
5/8" 6" 5/8"
ROLL-UP DOOR -
SEE SCHEDULE
1' - 0"
/2
5/8" GYPSUM BOARD
ON METAL STUD
FRAMING
ROLL-UP DOOR - SEE
SCHEDULE
5/8" GYPSUM BOARD ON
METAL STUD FRAMING
1/2" SOLID SURFACE SILL ON
2 LAYERS OF 1/2" PLYWOOD
SUBSTRATE
1/4" EASED PENCIL EDGE
(BOTH SIDES)
1/
2"
EQ.
8"
EQ.
LT. GA. METAL BOX HEADER
METAL STUD AND GYP. BD. PARTITION -
SEE PARTITION TYPES
ALUMINUM FRAME, TYP.
SEALANT ENTIRE
PERIMETER, TYP.
SHIM
DOOR (AS SCHEDULED)
2"
ALUMINUM FRAME
DOOR SEE DOOR SCHEDULE
GLAZING, TYP.
2"
4 1/2"
LT. GA. METAL BOX HEADER
METAL STUD AND GYP. BD. PARTITION -
SEE PARTITION TYPES
ALUMINUM FRAME, TYP.
SEALANT ENTIRE
PERIMETER, TYP.
SHIM
GLAZING, TYP.
2"
4 1/2"
ALUMINUM FRAME
SEALANT & BACKER ROD
CONT'S @ PERIM. (BOTH SIDES)
DOUBLE METAL STUD @ EA. JAMB
METAL STUD AND GYP. BD. PARTITION -
SEE PARTITION TYPES
SHIM
GLAZING, TYP.
2"
4 1/2"
ALUMINUM FRAME, TYP.
SEALANT ENTIRE
PERIMETER, TYP.
SHIM
GLAZING, TYP.
4"
4 1/2"
EXISTING CMU WALL
CONSTRUCTION TO REMAIN.
MODIFY AS REQURED FOR NEW
DOOR OPENING. CONTRACTOR
TO VERIFY IN FIELD ACTUAL WALL
CONDITION AND REPORT BACK
TO ARCHITECT OF ANY
DISCREPANCIES.
(2) 4"X6"X5/16" STEEL ANGLE LINTELS
EXISTING PLASTER
PLASTER TO MATCH EXISTING
4" METAL STUD
LT. GA. METAL BOX
HEADER
SECURITY ANCHOR AT
HEAD FOR FRAMES
WIDER THAN 3'-0"
SEALANT & BACKER ROD
CONT'S @ PERIM. (BOTH
SIDES)
1/4"
HOLLOW METAL FRAME
DOOR (AS SCHEDULED)
GYP. BD. TO MATCH
EXISTING OVER 4"
METAL STUD INFILL
MODIFY EXISTING
FURRING AS REQ'D
FOR NEW WORK
EXISTING CMU WALL
CONSTRUCTION TO REMAIN.
MODIFY AS REQURED FOR NEW
DOOR OPENING. CONTRACTOR
TO VERIFY IN FIELD ACTUAL WALL
CONDITION AND REPORT BACK
TO ARCHITECT OF ANY
DISCREPANCIES.
EXISTING PLASTER
WOOD BLOCKING
PLASTER TO MATCH EXISTING
SECURITY ANCHOR AT
JAMBS FOR FRAMES
WIDER THAN 3'-0"
HOLLOW METAL FRAME
DOOR (AS SCHEDULED)
GYP. BD. TO MATCH
EXISTING OVER
METAL FURRING,
MODIFY AS REQ'D
FOR NEW WORK
EXISTING GYP. BD. OVER
METAL FURRING
SEALANT & BACKER ROD
CONT'S @ PERIM. (BOTH
SIDES)
1/4" architecture · engineering
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERS · SURVEYORS · CONSULTANTS ·
LANDSCAPE ARCHITECTS · LAND PLANNERS
298 VETERANS DRIVE
FOWLERVILLE,
MICHIGAN 48836
(OFFICE) 517-223-3512
(FAX) 517-223-9987
211 E. Water Street, Suite 213L
Kalamazoo, MI 49007 269.216.0222
VA STATION
Battle Creek VA Medical Center
5500 Armstrong Road
Battle Creek, MI 49037
Defining
EXCELLENCE
in the 21st Century
HEALTH
CARE
C :\R ev it\
\1
4_
A _m ic he lle .b ur ri.
rv t
5/
/2
:2 6:
A
M
39-A503
DETAILS RENOVATE B39-2 WEST
FOR PATIENT PRIVACY
BATTLE CREEK, MI
515-20-102
05/20/2021 KJH MRB/MMN
100% BID DOCUMENTS190134
1/2" = 1'-0"
1 245 DAY ROOM - EXISTING TV & FIREPLACE
3/4" = 1'-0"39-A503
2 208 & 245 DAY ROOM - TV CABINET & FIREPLACE DETAIL
3/4" = 1'-0"39-A503
3 TV CABINET FIREPLACE DETAIL SECTION
1 1/2" = 1'-0"39-A503
4 FIREPLACE PLAN DETAIL
1 1/2" = 1'-0"39-A503
5 TV CABINET FIREPLACE PLAN DETAIL
1 1/2" = 1'-0"J6
OVERHEAD DOOR JAMB
1 1/2" = 1'-0"H5
OVERHEAD DOOR HEAD
1 1/2" = 1'-0"S1
OVERHEAD DOOR SILL
Revisions: Date:
RESUBMIT WITH OWNER CHANGES 10/02/2020
95% CONSTRUCTION DOCUMENTS 04/12/2021
100% BID DOCUMENTS 05/20/2021
1 1/2" = 1'-0"H6
ALUMINUM DOOR HEAD DETAIL
1 1/2" = 1'-0"J7
ALUMINUM DOOR JAMB DETAIL
1 1/2" = 1'-0"H7
ALUMINUM DOOR HEAD DETAIL
1 1/2" = 1'-0"J8
ALUMINUM DOOR JAMB DETAIL
1 1/2" = 1'-0"S2
ALUMINUM SILL DETAIL
1 1/2" = 1'-0"H8
HM DOOR HEAD AT EXISTING WALL
1 1/2" = 1'-0"J9
HM DOOR JAMB AT EXISTING WALL
(GLAZING AS
SCHEDULED)
NL
NARROW LITE
F
FLUSH
6" M
A X
. P E
R A
D A
4'
0"
HALF LITE
3'
6" 3'
2"
6"
7"7"
SCHEDULE
SEE
HL
SCHEDULE
SEE
S E
E S
C H
E D
U
LE
S E
E S
C H
E D
U
LE
S E
E S
C H
E D
U
LE
SCHEDULE
SEE
CCDD
4'
0"
3 1/2" +/-
1/
2"
(GLAZING AS
SCHEDULED)
MS
SCHEDULE
SEE
S E
E S
C H
E D
U
LE
MEDIUM STILE DUTCH DOOR COILING COUNTER DOOR
SCHEDULE
SEE
S E
E S
C H
E D
U
LE
SCHEDULE
SEE
S E
E S
C H
E D
U
LE
S E
E S
C H
E D
U
LE
SCHEDULE
SEE
DD2
3'
6"
4" 4"
4" 4"
DUTCH DOOR 2
NL2
NARROW LITE
6" M
A X
. P E
R A
D A
4'
0"
S E
E S
C H
E D
U
LE
SCHEDULE
SEE
6" 7"
(GLAZING AS
SCHEDULED)
12" 7"
(GLAZING AS
SCHEDULED)
(GLAZING AS
SCHEDULED)
1. ALL DOOR AND WINDOW FRAMES SHALL HAVE SEALANT & BACKER
ROD AT ENTIRE PERIMETER (BOTH SIDES,) UNO
2. REFER TO SPECIFICATIONS FOR HARDWARE SETS
3. ALL OUTSIDE DIMENSIONS OF FRAME TYPES ARE ROUGH OPENING
SIZES
4. MAINTAIN 4" MIN BETWEEN EDGE OF DOOR JAMB (HINGE SIDE) AND
NEAREST PERPENDICULAR SURFACE
5. ALL HOLLOW METAL FRAMES TO BE 2" PROFILE, UNO
6. STYLES & DIMENSIONS FOR DOOR TYPES & LITES ARE
REFLECTING DESIGN INTENT, DOOR MANUFACTURER TO SUBMIT
THEIR STANDARD TYPES, UNO
7. HM = HOLLOW METAL
8. WD = WOOD
9. AL = ALUMINUM
10. REFER TO SPECIFICATION FOR GLASS SCHEDULES AND
DESIGNATIONS
DOOR & FRAME GENERAL NOTES
IBG: INTEGRAL BLIND GLAZING
FR20: FIRE-RATED GLAZING - 20 MIN
FR90: FIRE-RATED GLAZING - 90 MIN
TG: TEMPERED GLAZING
LG: TEMPERED LAMINATED GLAZING
OWV: ONE-WAY-VISION LAMINATED GLAZING
ACR: ACRYLIC PANELS
RSN-1: LAMINATED RESIN PANELS
GLAZING NOTES
DOUBLE EGRESS
2" S
E E
D O
O R
S C
H E
D U
LE
2"
SCHEDULE
SEE DOOR 2"
S E
E D
O O
R S
C H
E D
U
LE
2"
2"
SCHEDULE
SEE DOOR 2"
01 03
2" S
E E
D O
O R
S C
H E
D U
LE
2"
SCHEDULE
SEE DOOR 2"
NO DOOR
STOP
SECURITY ANCHOR AT HEAD FOR
FRAMES WIDER THAN 3'-0"
SEALANT & BACKER ROD
CONT'S @ PERIM. (BOTH SIDES)
LT. GA. METAL BOX HEADER
METAL STUD AND GYP. BD. PARTITION -
SEE PARTITION TYPES
PARTITION THICKNESS + 1/8"
FRAME THROAT OPENING =
DOOR (AS SCHEDULED)
PAINTED WRAP-AROUND HOLLOW
METAL DRYWALL FRAME
DOOR (AS SCHEDULED)
LT. GA. METAL BOX HEADER
PAINTED WRAP-AROUND HOLLOW
METAL DRYWALL FRAME
SEALANT & BACKER ROD CONT'S
@ PERIM. (BOTH SIDES)
SECURITY ANCHOR AT HEAD
FOR FRAMES WIDER THAN 3'-0"
PARTITION THICKNESS + 1/8"
FRAME THROAT OPENING =
METAL STUD AND GYP. BD. PARTITION -
SEE PARTITION TYPES
PARTITION THICKNESS + 1/8"
FRAME THROAT OPENING =
LT. GA. METAL BOX HEADER
SEALANT & BACKER ROD
CONT'S @ PERIMETER
(BOTH SIDES)
PAINTED WRAP-AROUND
HOLLOW METAL DOUBLE
EGRESS DRYWALL FRAME
DOOR STOP (BEYOND)
DOOR (AS SCHEDULED)
A B
C
NOTE: SHOWING SWING
OF DOUBLE EGRESS
PLAN
NOTE: SHOWING
THE SWING OF
DOUBLE EGRESS
DOORS
C
DOUBLE EGRESS DOOR FRAME
A B
METAL STUD AND GYP. BD. PARTITION -
SEE PARTITION TYPES
DOOR SEE DOOR SCHEDULE
WRAP-AROUND HOLLOW METAL FRAME,
PAINT - SEE DOOR SCHEDULE
JAMB ANCHORS (2 PER JAMB &
ADJ. BASE ANCHORS - TYP.)
SEALANT & BACKER ROD
CONT'S @ PERIM. (BOTH SIDES)
DOUBLE METAL STUD @ EA. JAMB
METAL STUD AND GYP. BD. PARTITION -
SEE PARTITION TYPES
PARTITION THICKNESS + 1/8"
FRAME THROAT OPENING =
DOOR (AS SCHEDULED)
DOUBLE METAL STUD @ EA.
JAMB
JAMB ANCHORS (2 PER JAMB-
& ADJ. BASE ANCHORS - TYP.)
PAINTED WRAP-AROUND
HOLLOW METAL DRYWALL
FRAME
SEALANT & BACKER ROD
CONT'S @ PERIM. (BOTH
SIDES)
PARTITION THICKNESS + 1/8"
FRAME THROAT OPENING =
A
B
PLAN
NOTE: SHOWING
THE SWING OF
DOUBLE EGRESS
DOORS
3/
8" S
E E
D O
O R
S
C H
E D
U
LE
DETAIL 'A'
DETAIL 'B'
DOOR (AS SCHEDULED)
DOUBLE METAL STUD @ EA.
JAMB
JAMB ANCHORS (2 PER JAMB-
& ADJ. BASE ANCHORS - TYP.)
PAINTED WRAP-AROUND
HOLLOW METAL DRYWALL
FRAME
SEALANT & BACKER ROD
CONT'S @ PERIM. (BOTH SIDES)
DOOR SEE DOOR SCHEDULE
WRAP-AROUND HOLLOW METAL FRAME,
PAINT - SEE DOOR SCHEDULE
JAMB ANCHORS (2 PER JAMB &
ADJ. BASE ANCHORS - TYP.)
SEALANT & BACKER ROD
CONT'S @ PERIM. (BOTH SIDES)
DOUBLE METAL STUD @ EA. JAMB
METAL STUD AND GYP. BD. PARTITION -
SEE PARTITION TYPES
PARTITION THICKNESS + 1/8"
FRAME THROAT OPENING =
DOOR SEE DOOR SCHEDULE
WRAP-AROUND HOLLOW METAL FRAME,
PAINT-SEE DOOR SCHEDULE
SECURITY ANCHOR AT HEAD FOR
FRAMES WIDER THAN 3'-0"
SEALANT & BACKER ROD
CONT'S @ PERIM. (BOTH SIDES)
LT. GA. METAL BOX HEADER
METAL STUD AND GYP. BD. PARTITION -
SEE PARTITION TYPES
PARTITION THICKNESS + 1/8"
FRAME THROAT OPENING =
W1
RSN-1
LG
RSN-1
LG
RSN-1
LG
RSN-1
LG
RSN-1
LG
RSN-1
LG
RSN-1
LG
RSN-1
LG
RSN-1
LG
RSN-1
LG
RSN-1
LG
RSN-1
LG
RSN-1
LG
RSN-1
LG
RSN-1
LG
RSN-1
LG
RSN-1
OPEN
EQ.EQ.EQ.EQ.7' - 1 1/2"EQ.EQ.EQ.EQ.
CURVED
35' 0 1/2" N.T.S.
E Q
E Q
E Q
1'
8"
8'
8"
W2
RSN-1
LG
RSN-1
LG
8'
8"
EQ. EQ.
RSN-1
LG
RSN-1
LG
E Q
E Q
E Q
1'
8"
FLOOR LINE
W3
3'
6" 3'
8"
7'
2"
6' - 0"
ALUMINUM STOREFRONTALUMINUM STOREFRONTALUMINUM STOREFRONT
LG
EQ.
SCHEDULE
SEE DOOR EQ.
LG LG
W4
ALUMINUM STOREFRONT
S E
E D
O O
R S
C H
E D
U
LE
4"
EXISTING TO REMAIN
DOOR FRAME - SEE
FRAME TYPES, TYP.
BACKER ROD &
SEALANT, TYP.
SEALANT
GYP. BD. OVER
EXISTING
CONSTRUCTION
SEE REFLECTED
CEILING PLAN
SEE REFLECTED
CEILING PLAN
SEE REFLECTED
CEILING PLAN
EXISTING TO REMAIN, TYP.
EXISTING LINTEL TO
REMAIN, PAINT
GYP. BD. OVER EXISTING
CONSTRUCTION
BACKER ROD &
SEALANT, TYP.
HOLLOW METAL FRAME -
SEE FRAME TYPES
SEALANT, TYP.
SEALANT CONT'S @ PERIM.
(BOTH SIDES)
DOUBLE METAL STUD @ EA. JAMB
METAL STUD AND GYP. BD. PARTITION -
SEE PARTITION TYPES
DOOR SEE DOOR SCHEDULE
DOOR STOP LEAF
STRIKE
architecture · engineering
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERS · SURVEYORS · CONSULTANTS ·
LANDSCAPE ARCHITECTS · LAND PLANNERS
298 VETERANS DRIVE
FOWLERVILLE,
MICHIGAN 48836
(OFFICE) 517-223-3512
(FAX) 517-223-9987
211 E. Water Street, Suite 213L
Kalamazoo, MI 49007 269.216.0222
VA STATION
Battle Creek VA Medical Center
5500 Armstrong Road
Battle Creek, MI 49037
Defining
EXCELLENCE
in the 21st Century
HEALTH
CARE
C :\R ev it\
\1
4_
A _m ic he lle .b ur ri.
rv t
5/
/2
:2 6:
A
M
39-A601
SCHEDULES & DIAGRAMS RENOVATE B39-2 WEST
FOR PATIENT PRIVACY
BATTLE CREEK, MI
515-20-102
05/20/2021 KJH MRB/MMN
100% BID DOCUMENTS190134
DOOR AND FRAME SCHEDULE
DOOR
NO.
ROOM
NO. ROOM NAME
DOOR FRAME
FIRE
RATING
HARDWARE
SET NO. NOTES
SIZE
MATL TYPE GLAZING MATL TYPE
DETAIL
WD. HGT HEAD JAMB SILL
01.0
B113.A B113 NURSE STATION 3' - 0" 7' - 0" WD DD2 LG - - 11 / 39-A502 9 &15 / 39-A502 - - 19 REFER TO NURSE STATION DETAILS FOR HEAD AND JAMB FRAME DETAILS
B113.B B113 NURSE STATION 3' - 0" 7' - 0" WD DD2 LG - - 11 / 39-A502 9 &15 / 39-A502 - - 19 REFER TO NURSE STATION DETAILS FOR HEAD AND JAMB FRAME DETAILS
BC-13.A BC-13 CORRIDOR 7' - 0" 7' - 0" WD NL LG HM 03 J3 / 39-A601 H3 / 39-A601 - - 28 PAIR OF DOORS
C14A.A C14A NURSE STATION 3' - 0" 6' - 8" WD HL LG - - 13 / 39-A502 9 &14 / 39-A502 - - 24 REFER TO NURSE STATION DETAILS FOR HEAD AND JAMB FRAME DETAILS
C14A.B C14A NURSE STATION 3' - 0" 6' - 8" WD DD2 LG - - 11 / 39-A502 9,10,&12 / 39-A502 - - 19 REFER TO NURSE STATION DETAILS FOR HEAD AND JAMB FRAME DETAILS
C18A.A C18A NURSE STATION 3' - 0" 6' - 8" WD HL LG - - 13 / 39-A502 9 &14 / 39-A502 - - 24 REFER TO NURSE STATION DETAILS FOR HEAD AND JAMB FRAME DETAILS
C18A.B C18A NURSE STATION 3' - 0" 6' - 8" WD DD2 LG - - 11 / 39-A502 9,10,&12 / 39-A502 - - 19 REFER TO NURSE STATION DETAILS FOR HEAD AND JAMB FRAME DETAILS
02.0 ORIGINAL
208A.A 208A GROUP ROOM 4' - 0" 7' - 0" WD NL - HM 01 H1 / 39-A601 J1 / 39-A601 - - 04
245A.A 245A GROUP ROOM 4' - 0" 7' - 0" WD NL - HM 01 H1 / 39-A601 J1 / 39-A601 - - 04
C23A.B C23A NURSE STATION 3' - 0" 6' - 8" WD DD2 LG - - 11 / 39-A502 9,10,&12 / 39-A502 - - 19 REFER TO NURSE STATION DETAILS FOR HEAD AND JAMB FRAME DETAILS
C23A.A C23A NURSE STATION 3' - 0" 6' - 8" WD HL LG - - 13 / 39-A502 9 &14 / 39-A502 - - 24 REFER TO NURSE STATION DETAILS FOR HEAD AND JAMB FRAME DETAILS
C28A.B C28A NURSE STATION 3' - 0" 6' - 8" WD DD2 LG - - 11 / 39-A502 9,10,&12 / 39-A502 - - 19 REFER TO NURSE STATION DETAILS FOR HEAD AND JAMB FRAME DETAILS
C28A.A C28A NURSE STATION 3' - 0" 6' - 8" WD HL LG - - 13 / 39-A502 9 &14 / 39-A502 - - 24 REFER TO NURSE STATION DETAILS FOR HEAD AND JAMB FRAME DETAILS
C-24.A C-24 CORRIDOR 4' - 0" 7' - 0" WD NL - HM 01 H8 / 39-A503 J9 / 39-A503 - - 17
C-30.A C-30 CORRIDOR 4' - 0" 7' - 0" WD NL - HM 01 H8 / 39-A503 J9 / 39-A503 - - 17
02.0 ADDITION
B201.A B201 STAFF LOCKER RM / LOUNGE 3' - 4" 7' - 0" WD F - HM 01 H1 / 39-A601 J1 / 39-A601 - - 20
B202.A B202 SOILED LINEN 3' - 4" 7' - 0" WD F - HM 01 H1 / 39-A601 J1 / 39-A601 - 45 MIN 10 1 HR FIRE RESISTANCE RATED FIRE BARRIER
B204.A B204 HSK EQUIP. 3' - 4" 7' - 0" WD F - HM 01 H1 / 39-A601 J1 / 39-A601 - 45 MIN 10 1 HR FIRE RESISTANCE RATED FIRE BARRIER
B205.A B205 CLEAN LINEN 3' - 4" 7' - 0" WD F - HM 01 H1 / 39-A601 J1 / 39-A601 - 45 MIN 10 1 HR FIRE RESISTANCE RATED FIRE BARRIER
B206.A B206 TREATMENT 3' - 6" 7' - 0" WD NL LG HM 01 H1 / 39-A601 J1 / 39-A601 - - 14
B207.A B207 OFFICE 3' - 0" 7' - 0" WD NL LG HM 01 H1 / 39-A601 J1 / 39-A601 - - 13
B208.A B208 OFFICE 3' - 0" 7' - 0" WD NL LG HM 01 H1 / 39-A601 J1 / 39-A601 - - 13
B209.A B209 OFFICE 3' - 0" 7' - 0" WD NL LG HM 01 H1 / 39-A601 J1 / 39-A601 - - 13
B210.A B210 OFFICE 3' - 0" 7' - 0" WD NL LG HM 01 H1 / 39-A601 J1 / 39-A601 - - 13
B211.B B211 NURSE OFFICE 3' - 0" 7' - 0" WD HL IBG HM 01 H1 / 39-A601 J1 / 39-A601 - - 16
B211.A B211 NURSE OFFICE 3' - 0" 7' - 0" WD HL IBG HM 01 H1 / 39-A601 J1 / 39-A601 - - 13
B212.A B212 OFFICE 3' - 0" 7' - 0" WD NL LG HM 01 H1 / 39-A601 J1 / 39-A601 - - 13
B213.A B213 NURSE STATION 3' - 3" 7' - 0" WD DD2 LG HM 01 H1 / 39-A601 J1 / 39-A601 - - 19
B213A.A B213A STORAGE 3' - 0" 7' - 0" WD F - HM 01 H1 / 39-A601 J1 / 39-A601 - - 07
B218A.A B218 DAY ROOM 3' - 0" 7' - 0" WD F - HM 01 H1 / 39-A601 J1 / 39-A601 - - 08
B220.A B220 NOURISH 3' - 4" 7' - 0" WD NL LG HM 01 H1 / 39-A601 J1 / 39-A601 - - 21
B220.B B220 NOURISH 3' - 0" 7' - 0" WD NL LG HM 01 H1 / 39-A601 J1 / 39-A601 - - 22
B220.C B220 NOURISH 4' - 0" 4' - 2" STL CC - STL - H5 / 39-A503 J6 / 39-A503 S1 / 39-A503 - 29 OVERHEAD DOOR
B221.A B221 S. TOILET 3' - 6" 7' - 0" WD F - HM 01 H1 / 39-A601 J1/39-A601 - - 03
B222.A B222 QUIET 3' - 10" 7' - 0" WD F - HM 01 H1 / 39-A601 J1/39-A601 - - 26
B222.B B222 QUIET 3' - 6" 7' - 0" WD HL OWV HM 01 H1 / 39-A601 J1/39-A601 - - 26
B223.A B223 SEMI 3' - 10" 7' - 0" WD HL IBG HM 02 H2 / 39-A601 J5 / 39-A601 - - 15
B223A.A B223A BATHROOM 3' - 6" 7' - 0" - - - HM 02 H2 / 39-A601 J2 / 39-A601 - - 30 FRAME ONLY
B224.A B224 ANTE ROOM 3' - 6" 7' - 0" WD F IBG HM 01 H1 / 39-A601 J1 / 39-A601 - - 05
B224A.A B224A BATHROOM 3' - 6" 7' - 0" WD F - HM 01 H1 / 39-A601 J1 / 39-A601 - - 01
B225.A B225 SEMI 3' - 10" 7' - 0" WD HL IBG HM 02 H2 / 39-A601 J5 / 39-A601 - - 15
B225A.A B225A BATHROOM 3' - 6" 7' - 0" - - - HM 02 H2 / 39-A601 J2 / 39-A601 - - 30 FRAME ONLY
B226.A B226 MEDICAL BEDROOM 3' - 10" 7' - 0" WD F - HM 01 H1 / 39-A601 J1 / 39-A601 - - 26
B226.B B226 MEDICAL BEDROOM 3' - 6" 7' - 0" WD HL OWV HM 01 H1 / 39-A601 J1 / 39-A601 - - 26
B227.A B227 SEMI 3' - 10" 7' - 0" WD HL IBG HM 02 H2 / 39-A601 J5 / 39-A601 - - 15
B227A.A B227A BATHROOM 3' - 6" 7' - 0" - - - HM 02 H2 / 39-A601 J2 / 39-A601 - - 30 FRAME ONLY
B228.A B228 PRIVATE 3' - 10" 7' - 0" WD HL IBG HM 02 H2 / 39-A601 J5 / 39-A601 - - 15
B228A.A B228A BATHROOM 3' - 6" 7' - 0" - - - HM 02 H2 / 39-A601 J2 / 39-A601 - - 30 FRAME ONLY
B230.A B230 PRIVATE 3' - 10" 7' - 0" WD HL IBG HM 02 H2 / 39-A601 J5 / 39-A601 - - 15
B230A.A B230A BATHROOM 3' - 6" 7' - 0" - - - HM 02 H2 / 39-A601 J2 / 39-A601 - - 30 FRAME ONLY
B232.A B232 LAUNDRY 3' - 0" 7' - 0" WD F - HM 01 H1 / 39-A601 J1 / 39-A601 - - 06
B234.A B234 STORAGE 3' - 0" 7' - 0" WD F - HM 01 H1 / 39-A601 J1 / 39-A601 - - 11
B240.A B240 HSK 3' - 6" 7' - 0" WD F - HM 01 H1 / 39-A601 J1 / 39-A601 - 20 MIN 12 1/2 HR FIRE RESISTANCE RATED SMOKE PARTITION
B241.A B241 MEDS 3' - 4" 7' - 0" WD DD - HM 01 H1 / 39-A601 J1 / 39-A601 - - 18
B242.A B242 SEMI 3' - 10" 7' - 0" WD HL IBG HM 02 H2 / 39-A601 J5 / 39-A601 - - 15
B242A.A B242A BATHROOM 3' - 6" 7' - 0" - - - HM 02 H2 / 39-A601 J2 / 39-A601 - - 30 FRAME ONLY
B243.A B243 PRIVATE 3' - 10" 7' - 0" WD HL IBG HM 02 H2 / 39-A601 J5 / 39-A601 - - 15
B243A.A B243A BATHROOM 3' - 6" 7' - 0" - - - HM 02 H2 / 39-A601 J2 / 39-A601 - - 30 FRAME ONLY
B244.A B244 SEMI 3' - 10" 7' - 0" WD HL IBG HM 02 H2 / 39-A601 J5 / 39-A601 - - 15
B244A.A B244A BATHROOM 3' - 6" 7' - 0" - - - HM 02 H2 / 39-A601 J2 / 39-A601 - - 30 FRAME ONLY
B245.A B245 PRIVATE 3' - 10" 7' - 0" WD HL IBG HM 02 H2 / 39-A601 J5 / 39-A601 - - 15
B245A.A B245A BATHROOM 3' - 6" 7' - 0" - - - HM 02 H2 / 39-A601 J2 / 39-A601 - - 30 FRAME ONLY
B246.A B246 SEMI 3' - 10" 7' - 0" WD HL IBG HM 02 H2 / 39-A601 J5 / 39-A601 - - 15
B246A.A B246A BATHROOM 3' - 6" 7' - 0" - - - HM 02 H2 / 39-A601 J2 / 39-A601 - - 30 FRAME ONLY
B247.A B247 PRIVATE 3' - 10" 7' - 0" WD HL IBG HM 02 H2 / 39-A601 J5 / 39-A601 - - 15
B247A.A B247A BATHROOM 3' - 6" 7' - 0" - - - HM 02 H2 / 39-A601 J2 / 39-A601 - - 30 FRAME ONLY
B249.A B249 PRIVATE 3' - 10" 7' - 0" WD HL IBG HM 02 H2 / 39-A601 J5 / 39-A601 - - 15
B249A.A B249A BATHROOM 3' - 6" 7' - 0" - - - HM 02 H2 / 39-A601 J2 / 39-A601 - - 30 FRAME ONLY
B251.A B251 STORAGE 3' - 0" 7' - 0" WD F - HM 01 H1 / 39-A601 J1 / 39-A601 - 20 MIN 11 1/2 HR FIRE RESISTANCE RATED SMOKE PARTITION
B253.A B253 SOILED UTILITY 3' - 0" 7' - 0" WD F LG HM 01 H1 / 39-A601 J1 / 39-A601 - - 09
BC-22.A BC-22 CORRIDOR 7' - 0" 7' - 0" WD NL LG HM 03 H3 / 39-A601 J3 / 39-A601 - - 27
BC-23.A BC-23 CORRIDOR 7' - 0" 7' - 0" WD NL LG HM 03 H3 / 39-A601 J3 / 39-A601 - - 27
BC-25.2.A BC-24 CORRIDOR 3' - 6" 7' - 0" AL MS LG AL W4 H6 & H7 /
39-A503
J7 & J8 / 39-A503 S2 / 39-A503 - 23
BC-25.1.B BC-25.1 CORRIDOR 3' - 4" 7' - 0" WD NL FR-90 HM 01 H4 / 39-A601 J4 / 39-A601 - 90 MIN 25 2 HR FIRE RESISTANCE RATED FIRE BARIER
BC-25.2.1 BC-25.2 CORRIDOR 7' - 2" 7' - 0" - - - HM 02 2 / 39-A601 1 / 39-A601 - - 30 FRAME ONLY
BC-27.2.A BC-26 CORRIDOR 3' - 6" 7' - 0" AL MS LG AL W4 H6 & H7 /
39-A503
J7 & J8 / 39-A503 S2 / 39-A503 - 23
BC-26.A BC-26 CORRIDOR 7' - 0" 7' - 0" WD NL FR-20 HM 03 H3 / 39-A601 J3 / 39-A601 - 20 MIN 02 1 HR FIRE RESISTANCE RATED SMOKE BARRIER
BC-27.1.B BC-27.1 CORRIDOR 3' - 4" 7' - 0" WD NL FR-90 HM 01 H4 / 39-A601 J4 / 39-A601 - 90 MIN 25 2 HR FIRE RESISTANCE RATED FIRE BARRIER
BC-27.2.1 BC-27.2 CORRIDOR 7' - 2" 7' - 0" - - - HM 02 2 / 39-A601 1 / 39-A601 - - 30 FRAME ONLY
1/4" = 1'-0"
DOOR TYPES
1/4" = 1'-0"
DOOR FRAME TYPES
1 1/2" = 1'-0"
H1 DOOR HEAD DETAIL
1 1/2" = 1'-0"
H2 DOOR HEAD DETAIL @ NO DOOR STOP
1 1/2" = 1'-0"
H3 DOOR HEAD DETAIL @ DOUBLE EGRESS
1 1/2" = 1'-0"
J1 DOOR JAMB DETAIL
1 1/2" = 1'-0"
J2 DOOR JAMB DETAIL @ NO DOOR STOP
1 1/2" = 1'-0"
J3 DOOR JAMB DETAIL @ DOUBLE EGRESS
1 1/2" = 1'-0"
J4 DOOR JAMB DETAIL @ 2-HR WALL
1 1/2" = 1'-0"
H4 DOOR HEAD DETAIL @ 2-HR WALL
1/4" = 1'-0"
STOREFRONT TYPES
1 1/2" = 1'-0"39-A133
1 WALL OPENING JAMB DETAIL
1 1/2" = 1'-0"39-A112
2 WALL OPENING DETAIL
1 1/2" = 1'-0"
J5 DUAL EGRESS JAMB DETAIL
Revisions: Date:
65% DESIGN DEVELOPMENT 03/06/2020
RESUBMIT WITH OWNER CHANGES 10/02/2020
DN DN
DAY ROOM
B218
MEDS
B241
ELEVATOR
TREATMENT
B206
OFFICE
B208
OFFICE
B212
GROUP ROOM
B214
OFFICE
B207
OFFICE
B209
CORRIDOR
BC-22.2
PRIVATE
B230
PRIVATE
B228
SEMI
B223
SEMI
B225
SEMI
B227
S. TOILET
B221
QUIET
B222
MEDICAL
BEDROOM
B226
ANTE ROOM
B224
NOURISH
B220
PRIVATE
B243PRIVATE
B245
PRIVATE
B249
PRIVATE
B247
SEMI
B242SEMI
B244
SEMI
B246
HSK
B240
STORAGE
B251
STAIR
STAIR
SOILED UTILITY
B253
SOILED LINEN
B202
STAFF LOCKER
RM / LOUNGE
B201
CLEAN LINEN
B205
HSK EQUIP.
B204
BATHROOM
B246A
BATHROOM
B244A
BATHROOM
B242A
BATHROOM
B247A
BATHROOM
B243A
BATHROOM
B245A
BATHROOM
B223A
BATHROOM
B224A
BATHROOM
B225A
BATHROOM
B227A
BATHROOM
B230A
CORRIDOR
BC-22
ELECTRICAL
B255
ELECTRICAL
B236
CORRIDOR
BC-23
CORRIDOR
C-24 CORRIDOR
C-30
CORRIDOR
BC-21
STORAGE
B213A
STORAGE
B218A
CORRIDOR
BC-27.2
CORRIDOR
BC-24
CORRIDOR
BC-25.2
DAY ROOM
NOURISHMENT
232E
MED ROOM
207A
STAFF ROOM
CLEAN UTILITY
206B
LAUNDRY
206A
SOILED UTILITY
PHYSICIAN
PHYSICIAN
ASST.
OFFICE
NURSING 2
BED
NURSING 2
BED
NURSING 2
BED
PHYSICIAN
ASSISTANT
NURSING 1
BED
NURSING 1
BED
NURSING 1
BED
NURSING 1
BED
LAUNDRY
SOILED UTILITY
247A
STAFF ROOM
MED ROOM
243A
NOURISHMENT
245E
DAY ROOM
CORRIDOR
BC-27.1
CORRIDOR
BC-25.1
STAFF TOILET
208D
SECLUSION
CORRIDOR
C22 STAFF TOILET
245D
SECLUSION
CORRIDOR
C21
39-I102
39-I102
EXISTING FLOORING
TO REMAIN
EXISTING MATERIALS
TO REMAIN
NURSE
STATION
C23A
NURSE
STATION
C28A
CORRIDOR
C28
MB-2MB-2
WP-1WP-1
CORRIDOR
BC-22.2
P-3P-3 P-3P-3
P-2P-2
P-3P-3
NURSE OFFICE
B211
NURSE
STATION
B213
3' - 0"
2' - 0" 2' - 0"
2'
0"
2'
0"
STORAGE
B234
LAUNDRY
B232
OFFICE
B210
P-2P-2
3'
0"
39-I601
39-I601
39-I601
39-I601
39-I601
39-I601
P-3P-3
BATHROOM
B228A
BATHROOM
B249A
39-I102
SIM.
39-I102
SIM.
39-I102
SIM.
39-I102
SIM.
39-I102
SIM.
39-I102
SIM.
39-I102
SIM.
39-I102
SIM.
39-I102
SIM.
39-I102
SIM.
P-2P-2
P-2P-2
CORRIDOR
BC-26
P-3P-3
P-2P-2
P-2P-2
P-3P-3
2 NORTH
2 SOUTH
INFILL
FLOORING
TO MATCH
EXISTING
P-2P-2
P-2P-2
2' - 0" 2' - 0"
2'
0"
2' - 0"
P-1P-1
PATCH USING
ATTIC STOCK
2' - 0" 2' - 0"
2' - 0"
9'
4"
9'
4"
5'
4"
MATERIALS LEGEND
RF-2
RF-5
RF-3 (DIRECTION OF PATTERN
NOTES DIRECTION OF FLOORING)
RF-4
RF-6
RF-1
CPT-1
RF-7
ROOM FINISH GENERAL NOTES
1. DOOR FRAME COLOR CHANGES SHALL OCCUR ON STOP AS IF DOOR IS IN CLOSED POSITION WITH THE DOOR AND FRAME SHOWING
AS ONE COLOR.
2. FLOORING TRANSITIONS SHALL BE CENTERED UNDER DOOR WHILE IN CLOSED POSITION. PROVIDE TRANSITION STRIP BETWEEN ALL
FLOORING MATERIAL TRANSITIONS.
3. ALL EXPOSED STRUCTURAL, PLUMBING, MECHANICAL AND ELECTRICAL ELEMENTS ARE TO BE PAINTED TO MATCH ADJACENT WALL, U.N.O.
4. ALL CEILING GRIDS ARE TO BE CENTERED IN THE SPACE IN BOTH DIRECTIONS (AS SHOWN) UNLESS NOTED OTHERWISE.
5. ELECTRICAL DEVICES SUCH AS PLUG MOLDS, CHASES, PANELS, ETC. SHALL BE PAINTED TO MATCH ADJACENT WALL COLOR.
ELECTRICAL RECEPTACLE COVER PLATES (EXCEPT IN WOOD), SWITCH PLATES & TOGGLES, TELEPHONE/DATA COVERPLATES (EXCEPT IN WOOD) SHALL BE NYLON, COLOR: WHITE. THERMOSTAT COVERS SHALL BE COLOR: WHITE. ANY ELECTRICAL DEVICES MOUNTED IN WOOD PANELING, WAINSCOT OR TRIM SHALL MATCH THE FINISH/COLOR OF THE ADJACENT WOOD.
6. FIRE EXTINGUISHER CABINETS SHALL BE PAINTED TO MATCH ADJACENT WALL SURFACE COLOR. FIRE ALARMS SHALL BE RED.
7. ANY EXPOSED MECHANICAL GRILLES, METAL PANELS, TRIM DEVICES SHALL BE PAINTED TO MATCH ADJACENT SURFACE COLOR.
8. WINDOW SILLS SHALL BE SOLID SURFACE, SEE MATERIALS SCHEDULE FINISH SSM-1.
9. INTERIOR HOLLOW METAL DOORS, DOOR FRAMES, AND WINDOW FRAMES SHALL BE PAINTED P-5, U.N.O.
10. WOOD DOORS, DOOR FRAMES AND WINDOW FRAMES SHALL BE STAINED.
11. TRANSITION STRIP BETWEEN CARPET AND RESILIENT FLOORING AND/OR CONCRETE SHALL BE JOHNSONITE TA7 RUSTY NAIL.
12. GYP. BD. CEILINGS AND BULKHEADS TO BE PAINTED, BOTTOM OF BULKHEADS TO BE PAINTED TO MATCH CEILING, SIDES TO MATCH
ADJACENT WALL U.N.O, SEE ROOM FINISH AND MATERIALS SCHEDULES, I-601.
13. CORNER GUARDS TO BE LOCATED AT ALL OUTSIDE CORNERS. SEE I-601 MATERIALS SCHEDULE CODE CG-1.
14. CONVECTOR, CABINET UNIT HEATERS AND FIN-TUBE UNITS SHALL BE PAINTED TO MATCH ADJACENT WALL COLOR, U.N.O.
15. SEE INTERIOR ELEVATIONS FOR ADDITIONAL INFORMATION REGARDING INTERIOR FINISHES.
16. ALL EXPOSED WOOD TRIM AND VENEER SHALL BE HARDWOOD, STAINED, AND VARNISHED.
17. CHEMICAL WELD SEAM BETWEEN DISSIMILAR MATERIALS (IE: RESILIENT SHEET TO RESILIENT TILE) AND HEAT WELD SEAM BETWEEN
SIMILAR MATERIALS (IE: RESILIENT SHEET TO RESILIENT SHEET).
18. ALL MARKERBOARDS TO BE INSTALLED AT 7’-0” A.F.F TO TOP OF BOARD U.N.O.
19. ALL TV MONITORS TO BE INSTALLED AT 5’-0” A.F.F. TO CENTER OF MONITOR U.N.O.
E Q
6'
9" E
Q
8' - 6"
7' - 2"
0"
P-3P-3
CHEMICAL WELD SEAM BETWEEN
MATERIAL TRANSITION
EQ EQ
WP-2WP-2
E Q
6'
9" 3'
6'
9"
E Q
8' - 6"
CENTERED ON DOOR
7' - 2"
CHEMICAL WELD SEAM BETWEEN
MATERIAL TRANSITION
8' - 6"
P-3P-3
WP-2WP-2
NURSE
STATION
C14A
INFILL
FLOORING
TO MATCH
EXISTING
NURSE
STATION
C18A
CORRIDOR
C18
INFILL
FLOORING
TO MATCH
EXISTING
NURSE
STATION
B113
INFILL
FLOORING
TO MATCH
EXISTING
architecture · engineering
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERS · SURVEYORS · CONSULTANTS ·
LANDSCAPE ARCHITECTS · LAND PLANNERS
298 VETERANS DRIVE
FOWLERVILLE,
MICHIGAN 48836
(OFFICE) 517-223-3512
(FAX) 517-223-9987
211 E. Water Street, Suite 213L
Kalamazoo, MI 49007 269.216.0222
VA STATION
Battle Creek VA Medical Center
5500 Armstrong Road
Battle Creek, MI 49037
Defining
EXCELLENCE
in the 21st Century
HEALTH
CARE
C :\R ev it\
\1
4_
A _m ic he lle .b ur ri.
rv t
5/
/2
:2 6:
A
M
39-I102
PARTIAL FINISH PLAN - SECOND
LEVEL
RENOVATE B39-2 WEST
FOR PATIENT PRIVACY
BATTLE CREEK, MI
515-20-102
05/20/2021 AAP CJA
100% BID DOCUMENTS190134
1/8" = 1'-0"
PARTIAL SECOND FLOOR FINISH PLAN
1/4" = 1'-0"39-I102
5 ENLARGED PLAN PRIVATE PATIENT ROOMS, TYP FINISH PLAN
1/4" = 1'-0"39-I102
4 ENLARGED PLAN SEMI-PRIVATE PATIENT, TYP FINISH PLAN
NOT TO SCALE
KEY PLAN SECOND FLOOR1/8" = 1'-0"39-A101
3 NURSE STATION 1 NORTH - FINISH PLAN
1/8" = 1'-0"39-A101
1 NURSE STATION 1 SOUTH - FINISH PLAN
1/8" = 1'-0"39-A101
2 NURSE STATION 1 WEST - FINISH PLAN
Revisions: Date:
65% DESIGN DEVELOPMENT 03/06/2020
RESUBMIT WITH OWNER CHANGES 10/02/2020
0' - 9"
0'
3"
0' - 0 25/32"
GRADE 2 BRAILLE
ROOM NO. 1-1/4" HIGH
RAISED HELVETICA TEXT
TAMPER RESISTANT FASTENER TYP.
RADIUS CORNERS TYP.
XXXXXXX
XXXXXXX
0' - 9"
9"
ROOM NO. 11/4" HIGH
RAISED HELVETICA TEXT
ROOM NAME. 1"
HIGH RAISED
HELVETICA TEXT
GRADE 2 BRAILLE
GRADE 2 BRAILLE
TAMPER RESISTANT
FASTENER TYP
RADIUS CORNERS
TYP.
0' - 9"
0'
9"
ROOM NO. 11/4" HIGH
RAISED HELVETICA TEXT
GRADE 2 BRAILLE
TAMPER RESISTANT
FASTENER TYP.
RADIUS CORNERS TYP.
1/
2"
1/ 2"
MARKER BOARD
0' - 0 3/8"
0'
3/
8" 0'
3/
0'
3/ 8"
9" HIGH
HELVETICA
TEXT
1" HIGH HELVETICA
TEXT BOLD
20"
E Q
E Q
E Q
E Q
E Q
E Q
TEXT
TEXT
13/8" HIGH HELVETICA TEXT, TYP.
LEFT JUSTIFY
REMOVABLE INSERT
TYP.
TAMPER RESISTANT
FRAME
NO EXPOSED FASTENERS
TYP.
TEXT
TEXT
2 1/2" ARROW TYP.
20"
E Q
E Q
E Q
E Q
E Q
E Q
TEXT
TEXT
13/8" HIGH HELVETICA TEXT, TYP.
LEFT JUSTIFY
REMOVABLE INSERT
TYP.
TAMPER RESISTANT
FRAME
NO EXPOSED
FASTENERS TYP.
TEXT
TEXT
2 1/2" ARROW TYP.
0' - 9"
0'
9"
XXX TOILET
3/4" HIGH
HELVETICA TEXT
GRADE 2 BRAILLE
SYMBOL
TAMPER
RESISTANT
FASTENER TYP.
RADIUS
CORNERS TYP.
0' - 9"
0'
9"
0'
3/
STAIRS
0'
1/
3/4" HIGH
HELVETICA TEXT
GRADE 2 BRAILLE
SYMBOL
RADIUS
CORNERS TYP.
TAMPER
RESISTANT
FASTENER TYP.
0'
6"
40"
3" HIGH HELVETICA
TEXT. ARROW AND
TEXT BOTH SIDES
ELEVATOR
E Q
E Q
G.Y.P. CEILING
ELEV. = 9'-0" (TYP.) U.N.O.
BOTTOM OF SIGN
ELEV. = 7'-0" (MIN.)
ANGLE BRACKETS
BOTH SIDES
0' - 2"
5'
3"
SIGNAGE GENERAL NOTES
1. ALL COPY TO BE VERIFIED WITH CLIENT PRIOR TO FABRICATION
2. ANY SIGNAGE APPLIED TO GLASS NEEDS A BACKER PANEL
3. DETAIL VIEW TITLES INDICATES VA SIGN FAMILY AND NUMBER
96"
VA
U.S. Department of Veterans Affairs
Battle Creek
VA Medical Center
GENERAL CONTRACTOR
Construction Firm Name City State
ARCHITECT / ENGINEER
Architect/ Engineering Firm Name City State
VA Office of Construction & Facilities Management
FRAMED SIGN PANEL - ALUMINUM SKIN
LAMINATED TO A WOOD CORE WITH
PHYSICALLY SEALED EDGES
TY
P
6" M
IN
TYP
6" MIN
TYP
6" MIN
VA BLUE (PANTONE 541) BACKGROUND
DEPARTMENT OF VETERAN AFFAIRS
LOGO - SURFACE APPLIED VINYL OR
SCREENED GRAPHICS - COLOR WHITE
SURFACE APPLIED VINYL OR SCREENED
GRAPHICS - COLOR BLACK
WHITE BACKGROUND
PLAN VIEW
ELEVATION VIEW
4"x6" WOOD POSTS
GRADE
CONCRETE FOOTING
NOTES:
1. ALL VISIBLE SURFACE TO BE PRIMED
AND PAINTED. SURFACES NOT CALLED
OUT TO BE A SPECIFIC COLOR ARE TO
BE PAINTED WHITE.
2. SIGN TO BE ATTACHED TOGETHER
WITH WOOD SCREWS AND LAG BOLTS.
4"x6" POSTS
2"x4" FRAMING
SIGN FACE
48"
VA
U.S. Department of Veterans Affairs
This Project Has Worked Days
FRAMED SIGN PANEL - ALUMINUM SKIN
LAMINATED TO A WOOD CORE WITH
PHYSICALLY SEALED EDGES
TY
P
6" M
IN
TYP
6" MIN
TYP
6" MIN
VA BLUE (PANTONE 541) BACKGROUND
DEPARTMENT OF VETERAN AFFAIRS
LOGO - SURFACE APPLIED VINYL OR
SCREENED GRAPHICS - COLOR WHITE
SURFACE APPLIED VINYL OR SCREENED
GRAPHICS - COLOR RED
WHITE BACKGROUND
PLAN VIEW
ELEVATION VIEW
4"x4" WOOD POSTS
GRADE
CONCRETE FOOTING
NOTES:
1. ALL VISIBLE SURFACE TO BE PRIMED
AND PAINTED. SURFACES NOT CALLED
OUT TO BE A SPECIFIC COLOR ARE TO
BE PAINTED WHITE.
2. SIGN TO BE ATTACHED TOGETHER
WITH WOOD SCREWS AND LAG BOLTS.
4"x4" POSTS
2"x4" FRAMING
SIGN FACE
ZERO IN
ON SAFETY
00 0 Without a Lost Time Accident
THE LIFE YOU SAVE MAY BE YOUR OWN
General Contractors Firm Name CHANGEABLE NUMBERS
SURFACE APPLIED VINYL OR SCREENED
GRAPHICS - COLOR BLACK
architecture · engineering
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERS · SURVEYORS · CONSULTANTS ·
LANDSCAPE ARCHITECTS · LAND PLANNERS
298 VETERANS DRIVE
FOWLERVILLE,
MICHIGAN 48836
(OFFICE) 517-223-3512
(FAX) 517-223-9987
211 E. Water Street, Suite 213L
Kalamazoo, MI 49007 269.216.0222
VA STATION
Battle Creek VA Medical Center
5500 Armstrong Road
Battle Creek, MI 49037
Defining
EXCELLENCE
in the 21st Century
HEALTH
CARE
C :\R ev it\
\1
4_
A _m ic he lle .b ur ri.
rv t
5/
/2
:2 6:
A
M
39-I121
SIGNAGE DETAILS RENOVATE B39-2 WEST
FOR PATIENT PRIVACY
BATTLE CREEK, MI
515-20-102
05/20/2021 AAP CJA
100% BID DOCUMENTS190134
3" = 1'-0"
1 3.01
3" = 1'-0"
2 4.01
3" = 1'-0"
3 4.02
3" = 1'-0"
4 14.06
3" = 1'-0"
5 14.04
3" = 1'-0"
6 9.03
3" = 1'-0"
7 9.07
3" = 1'-0"
8 15.01 1/4" = 1'-0"
11 SIGNAGE MOUNTING DETAIL 2
SIGNAGE SCHEDULE
SIGNAGE SCHEDULE
ROOM
NO. ROOM NAME INSERT/TEXT
19 ELEVATOR 4 - TBD, 8 - "ELEVATOR"
35 STAIR STAIR GRAPHIC
36 STAIR STAIR GRAPHIC
208 DAY ROOM ROOM NUMBER, ROOM NAME
208A GROUP ROOM ROOM NUMBER, ROOM NAME
245 DAY ROOM ROOM NUMBER, ROOM NAME
245A…