Drawings 515-20-102 Section 1 of 2.pdf

PDF 17 MB Posted

Attached to
Z1DA--Renovate B39-2 West Patient Privacy 515-20-102
Solicitation number
36C25021B0060
Issued by

About this file

This document provides details of a federal solicitation for construction renovation services. The Department of Veterans Affairs will issue an invitation for bid on or around November 30, 2020 for Project 515-20-103 to renovate a portion of Building 7 at the VA Medical Center in Battle Creek, Michigan to house Mental Health programs and staff. The project is set aside solely for Service-Disabled Veteran Owned Small Businesses. The contractor will have 280 days to complete the work with a firm fixed price contract valued between $1-2 million to be awarded within 180 days of bid receipt. Interested parties should register at Contract Opportunities to access solicitation documents including specifications and drawings as of November 30th, with responses due per the solicitation. Firms must be registered in SAM and VetBiz, and have a current VETS-4212 report if applicable.

View the file

Other files

Show all 20

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

VICINITY MAP

NOT TO SCALE

SK

YL

INE

DR

HI

LL

B

RA

DY

R

D.

AR

MS

TR

ON

G

RD

.FORT CUSTER DR.

RIVER RD. W.

W. MICHIGAN AVE.

S.

BE

DF

OR

D

RD

.96

89 E. D AVE.

AU

GUSTA

DR.

E. B

EC

KW

ITH

DR.

NORTH BRANCH KALAMAZOO RIVER

E. MICHIGAN AVE.

8 MILE RD.

94 94

GALESBURG

AUGUSTA

BATTLE

CREEK

W. DICKMAN RD

W. DICKMAN RD

W. DICKMAN RD

N

EW

S

CAMPUS MAP

NOT TO SCALE

LAKE ERIE

GRAND

RAPIDS

TRAVERSE

CITY

LAKE SUPERIOR

UPPER PENINSULA

MACKINAW

CITY LAKE HURONALPENA

PETOSKEY

GAYLORD

GRAYLING

LA

KE

M

IC

HI

GA

N

SAGINAW

FLINT

LANSING

DETROIT

KALAMAZOO ANN

ARBOR

BATTLE

CREEK

LOCATION MAP

NOT TO SCALE

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

211 E. Water Street, Suite 213L Kalamazoo, MI 49007

269.216.0222

VA STATION

EXCELLENCEHEALTH

CARE

DEPARTMENT OF VETERANS AFFAIRS - BATTLE CREEK VA MEDICAL CENTER

BATTLE CREEK, MICHIGAN

RENOVATE B39-2 WEST FOR PATIENT PRIVACY

AND B39-1 NORTH & SOUTH, B39-2 NORTH & SOUTH, AND B39-1

WEST NURSE STATION REMODEL AND EXISTING PORCH BARRIER

SIGNATURE DATE

Director

Associated Director

Chief of Staff

Associate Director for Patient Care Services

Chief, FMS

Chief, Engineering Section

Chief, Police Service

Chief, Fire Service

Union Safety Representative

Chief, Environmental Management Section

Infection Control Officer

Patient Safety Manager

GEMS Coordinator

Safety Specialist

Contracting Officer

COR

SIGNATURE BLOCK

POSITION DATESIGNATUREPOSITION

Associate Chief of Staff for Mental Health

C:

\R ev it\2

0\1

4_ A_ mi ch ell e.b urr i.rv t 5/2

1/2

1 1 0:2

0:3 0 A

M

39-G001

COVER SHEET RENOVATE B39-2 WEST

FOR PATIENT PRIVACY

BATTLE CREEK, MI

515-20-102

05/20/2021 KJH MRB/MMN

100% BID DOCUMENTS190134

515-20-102

05/20/2021

100% BID DOCUMENTS

515-20-102

SHEET

NO. SHEET NAME

FIRE PROTECTION PLAN

39-FP100 FIRE PROTECTION PLANS

PLUMBING

39-PL102 SECOND FLOOR DOMESTIC PLUMBING PLAN

39-PL112 SECOND FLOOR SANITARY, VENT & STORM PLAN

39-PL400 ENLARGED PLUMBING PLANS

39-PL600 PLUMBING SCHEDULES AND DETAILS

MECHANICAL

39-M000 MECHANICAL GENERAL INFORMATION

39-MD102 SECOND FLOOR MECHANICAL DEMOLITION PLAN

39-MH102 SECOND FLOOR MECHANICAL HVAC PLAN

39-MP102 SECOND FLOOR MECHANICAL PIPING PLAN

39-M500 MECHANICAL DETAILS

39-M600 MECHANICAL SCHEDULES

39-M800 CONTROL DIAGRAMS

ELECTRICAL

39-E000 ELECTRICAL GENERAL INFORMATION

39-ED101 FIRST FLOOR ELECTRICAL DEMOLITION PLAN

39-ED102 SECOND FLOOR ELECTRICAL DEMOLITION PLAN

39-EL101 FIRST FLOOR LIGHTING PLAN

39-EL102 SECOND FLOOR LIGHTING PLAN

39-EP101 FIRST FLOOR POWER PLAN

39-EP102 SECOND FLOOR POWER PLAN

39-ET102 SECOND FLOOR TECHNOLOGY PLAN

39-E400 ENLARGED ELECTRICAL PLANS

39-E401 ENLARGED ELECTRICAL PLANS

39-E402 ENLARGED ELECTRICAL PLANS

39-E600 PANEL SCHEDULES

39-E700 ELECTRICAL RISER DIAGRAM

TOTAL SHEETS: 57

SHEET

NO. SHEET NAME

GENERAL

39-G001 COVER SHEET

39-G101 LIFE SAFETY PLANS

39-G111 PARTIAL SECOND FLOOR ASBESTOS REMOVAL PLAN

39-G121 INFECTION CONTROL RISK ASSESSMENT & PHASING PLANS

39-G131 DEDUCTIVE ALTERNATES

LANDSCAPE

39-L101 LANDSCAPE PLAN

39-L102 LANDSCAPE DETAILS

ARCHITECTURAL

39-A001 ARCHITECTURAL LEGENDS, SYMBOLS, AND ABBREVIATIONS

39-A002 PARTITION TYPES

39-AD101 PARTIAL FIRST FLOOR DEMOLITION PLAN

39-AD102 PARTIAL SECOND FLOOR DEMOLITION PLAN

39-A101 PARTIAL FIRST FLOOR PLAN

39-A102 PARTIAL SECOND FLOOR PLAN

39-A111 PARTIAL FIRST FLOOR REFLECTED CEILING PLAN

39-A112 PARTIAL SECOND FLOOR REFLECTED CEILING PLAN

39-A122 PARTIAL SECOND FLOOR EQUIPMENT PLAN

39-A130 ENLARGED PLANS - NURSE STATIONS

39-A131 ENLARGED PLANS - NURSE STATIONS

39-A132 ENLARGED PLANS

39-A133 ENLARGED PLANS

39-A311 WALL SECTIONS

39-A501 ARCHITECTURAL DETAILS

39-A502 NURSE STATION DETAILS

39-A503 DETAILS

39-A601 SCHEDULES & DIAGRAMS

INTERIORS

39-I102 PARTIAL FINISH PLAN - SECOND LEVEL

39-I121 SIGNAGE DETAILS

39-I122 SIGNAGE PLAN - SECOND LEVEL

39-I201 INTERIOR ELEVATIONS - NURSE STATIONS

39-I202 INTERIOR ELEVATIONS - NURSE STATIONS

39-I203 INTERIOR ELEVATIONS - SECOND LEVEL

39-I601 SCHEDULES & DIAGRAMS

Revisions: Date:

SCHEMATIC DESIGN - 35% 11/25/2019

65% DESIGN DEVELOPMENT 03/06/2020

RESUBMIT WITH OWNER CHANGES 10/02/2020

95% CONSTRUCTION DOCUMENTS 04/12/2021

100% BID DOCUMENTS 05/20/2021

ST

ATE OF MICHIGAN

L

IC

E N

SED PROFESSIONAL E

NG

IN

E E

RENGINEER

No.

5040000000000

SCOTT E.

TOWNSEND

05/20/2021

ST

ATE OF MICHIGAN

L

IC

EN

SED PROFESSIONAL E

NG

IN

E E

RENGINEER

No.

51101

NATHANIEL

STALKER

SS

NNNNNNN

SSESS D

S

PPP

N

SSSSS

NNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNN

S

NNN

S

NN

S

NN

S

NNN

S

NN

SSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSEEEEEEEEEEEEEEEEEDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDD

PPPPPP

DDDDDDDDDDDDDDDD

PPPP

DDDDDDDDDDDD

PPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPP

NNNNNNNNNNNNNN

DDD

PPPPPPPPPPPPPPPPPPPPPPPPPPPPPPP

SESSSSSSSSSSSSSSSSSSSSSS

NNNNNNNNNNNNNNN

SSSSSSSSSSSS

DDDD

SSSSSSSSSSSS

NENENNNN

L

EENN

L

NNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNNEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEE

LLLLLLL

EEEEEEEEEEEEEE

LLLLLLLLLLLLLL

EEEE

LLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLL

EE

05/20/20215/20/2021 kristy.baisch Typewritten Text

DN DN

UP DN DN UP DN DN

UPUP UP UP

2'

-0

'-0

84'-0" 93'-0"

11'-8"

X X

F.E.

F.E.

F.E.

X

Z O

N E

2"

Z O

N E

1"

72 6

FIRE CODE RATINGS

SMOKE BARRIER - 1-HR

FIRE RESISTANCE RATED

FIRE BARRIER - 2-HR FIRE

RESISTANCE RATED

EXISTING SMOKE BARRIER - 1-HR

FIRE RESISTANCE RATED

EXISTING FIRE BARRIER - 2-HR

FIRE RESISTANCE RATED

NOTE: EXISTING RATED WALL SHOWN SCREENED ON PLAN. - V.I.F. WALLS MEET DESIGNATED

REQUIREMENTS & ADD OPENING & PENETRATION PROTECTIVES AS REQ'D

SMOKE COMPARTMENT AREA

NO SIGNIFICANT CHANGES TO GROSS SQUARE FOOTAGE OF

SMOKE COMPARTMENTS

FIRE BARRIER - 1-HR FIRE

RESISTANCE RATED

SMOKE PARTITION - 1/2-HR

FIRE RESISTANCE RATED

EXISTING FIRE BARRIER - 1-HR

FIRE RESISTANCE RATED

EXISTING SMOKE PARTITION -

1/2-HR FIRE RESISTANCE RATED

APPLICABLE CODES AND STANDARDS

BUILDING CODES: EDITION:

NFPA 101 LIFE SAFETY CODE 2018

INTERNATIONAL BUILDING CODE 2018

ARCHITECTURAL BARRIERS ACT ACCESSIBILITY STANDARDS (ABAAS) 2014

VA SUPPLEMENT: BARRIER FREE DESIGN 01/01/2017 REVISED 11/01/2018

PLUMBING CODE: EDITION:

INTERNATIONAL PLUMBING CODE 2018

HVAC CODE: EDITION:

ASME BOILER AND PRESSURE VESSEL CODE 2019

ASME CODE FOR PRESSURE PIPING VARIES

ASHREA STANDARD 62.1 - VENTILATION FOR

ACCEPTABLE INDOOR AIR QUALITY 2004

ASHREA STANDARD 15 - SAFETY STANDARD FOR

REFRIGERATION SYSTEMS 2007

ELECTRICAL CODE: EDITION:

NFPA 70 NATIONAL ELECTRICAL CODE 2020

FIRE CODES: EDITION:

NFPA NATIONAL FIRE CODES (EXCEPT NFPA 500 & NFPA 900) VARIES

CODE SUMMARY

FIRE EXTINGUISHER CABINET

SYMBOL LEGEND

DIST. TO

EXIT

PERSONS

TO EXIT EGRESS PATH COMPUTATION

HE HORIZONTAL EXIT

EXIT

F.E.

CODE SUMMARY IS BASED ON THE FOLLOWING CRITERIA:

• EXISTING BUILDING IS SPRINKLED THROUGHOUT AND MEETS THE REQUIREMENTS OF 2018 NFPA 101, CHAPTER 18 -

EXISTING HEALTH CARE OCCUPANCIES.

OCCUPANCY CLASSIFICATION:

NS BUILDING WEST BUILDING

• SECOND FLOOR: EX HEALTH CARE OCCUPANCY (UNCHANGED) EX HEALTH CARE OCCUPANCY (UNCHANGED)

• FIRST FLOOR: EX HEALTH CARE OCCUPANCY (UNCHANGED) EX HEALTH CARE OCCUPANCY (UNCHANGED)

• BASEMENT: EX BUSINESS (UNCHANGED) EX BUSINESS (UNCHANGED)

BUILDING AREA:

NS BUILDING WEST BUILDING

• SECOND FLOOR: 17,386 SF 12,846 SF

• FIRST FLOOR: 17,386 SF 12,846 SF

• BASEMENT: 17,386 SF 12,636 SF

• TOTAL 52,158 SF 38,328 SF

TYPES OF CONSTRUCTION:

• NS BUILDING TYPE: II (222) (UNCHANGED) (NFPA - 19.1.6.1)

• WEST BUILDING TYPE: II (111) (UNCHANGED) (NFPA - 19.1.6.1)

AUTOMATIC SPRINKLER SYSTEM:

• YES, EXISTING BUILDING FULLY SPRINKLED, RENOVATION TO REWORK EXISTING SYSTEM FOR PLAN CHANGES.

FIRE ALARM SYSTEM AND SMOKE DETECTION:

• YES, RENOVATION TO TIE INTO EXISTING FIRE ALARM SYSTEM

EGRESS REQUIREMENTS:

• NO CHANGES OR RESTRICTIONS TO EXISTING EXIT ACCESS COMPONENTS

• NO CHANGES TO EXISTING TRAVEL DISTANCES

OCCUPANCY LOAD: (NFPA 7.3.1.2)

• ASSEMBLY - LESS CONCENTRATED 15 SQ FT / PERSON NET

• HEALTH CARE - SLEEPING DEPARTMENTS 120 SQ FT / PERSON GROSS

• STORAGE 500 SQ FT / PERSON GROSS

• BUSINESS AREAS 150 SQ FT / PERSON GROSS

• BUSINESS AREAS - CONCENTRATED 50 SQ FT / PERSON GROSS

OCCUPANCY LOAD SUMMARY:

WEST BUILDING NS BUILDING

• BASEMENT

• STORAGE:........................................24 OCCUPANTS UNCHANGED

• 1ST FLOOR

• ASSEMBLY:......................................72 OCCUPANTS UNCHANGED

• BUSINESS:.......................................13 OCCUPANTS UNCHANGED

• BUSINESS

CONCENTRATED:............................6 OCCUPANTS UNCHANGED

• HEALTHCARE

SLEEPING DEPARTMENTS:..........70 OCCUPANTS UNCHANGED

• STORAGE:.........................................1 OCCUPANTS UNCHANGED

• 2ND FLOOR

• ASSEMBLY:.....................................62 OCCUPANTS UNCHANGED

• BUSINESS:......................................14 OCCUPANTS UNCHANGED

• BUSINESS

CONCENTRATED:............................5 OCCUPANTS UNCHANGED

• HEALTHCARE

SLEEPING DEPARTMENTS:..........70 OCCUPANTS UNCHANGED

• STORAGE:..........................................1 OCCUPANTS UNCHANGED

• TOTAL..................................................338 OCCUPANTS UNCHANGED

HAZARDOUS AREA PROTECTION (NFPA 18.2.3.1)

• SOILED LINEN > 64 GAL: 1HR

• STORAGE ROOMS > 50 SQFT AND < 100 SQFT: SMOKE PARTITION AND DOOR- CLOSING DEVICES REQUIRED

SUBDIVISION OF BUILDING SPACES (NFPA 18)

• NUMBER OF SMOKE COMPARTMENTS 2 REQUIRED

• MAX. SIZE OF SMOKE COMPARTMENTS 22.500 SQFT

• TRAVEL DISTANCE TO SMOKE BARRIER 200 FT

• MEANS OF EGRESS (DOORS) = 0.2"/OCCUPANCY NFPA 7.3.3.1

• DEAD END CORRIDOR = 30' MAX NFPA 18.2.5.2

• TRAVEL DISTANCE BETWEEN EXISTING = 200' MAX NFPA 18.2.5.7.2

ASSEMBLY - LESS CONCENTRATED

BUSINESS AREA

BUSINESS AREA - CONCENTRATED

HEALTH CARE - SLEEPING DEPARTMENTS

STORAGE

OCCUPANCY COUNT

(TOTAL IS OCCUPANCY TYPE FOR ENTIRE FLOOR)

X

3'

-6

'-5

81'-3" 95'-0"

X X

F.E.

F.E. F.E.

X

Z O

N E

2"

Z O

N E

1"

X

47'-6"

'-6

95'-7"

'-4

X

F.E.

F.E.

X

ZONE "1"

ZONE "2"

architecture · engineering

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERS · SURVEYORS · CONSULTANTS ·

LANDSCAPE ARCHITECTS · LAND PLANNERS

298 VETERANS DRIVE

FOWLERVILLE,

MICHIGAN 48836

(OFFICE) 517-223-3512

(FAX) 517-223-9987

211 E. Water Street, Suite 213L

Kalamazoo, MI 49007 269.216.0222

VA STATION

Battle Creek VA Medical Center

5500 Armstrong Road

Battle Creek, MI 49037

Defining

EXCELLENCE

in the 21st Century

HEALTH

CARE

C :\R ev it\

\1

4_

A _m ic he lle .b ur ri.

rv t

5/

/2

:2 0:

A

M

39-G101

LIFE SAFETY PLANS RENOVATE B39-2 WEST

FOR PATIENT PRIVACY

BATTLE CREEK, MI

515-20-102

05/20/2021 KJH MRB/MMN

100% BID DOCUMENTS190134

1/16" = 1'-0"

LIFE SAFETY - FIRST FLOOR PLAN

1/16" = 1'-0"

LIFE SAFETY - SECOND FLOOR PLAN

1/16" = 1'-0"

LIFE SAFETY - BASEMENT FLOOR PLAN

Revisions: Date:

SCHEMATIC DESIGN - 35% 11/25/2019

65% DESIGN DEVELOPMENT 03/06/2020

RESUBMIT WITH OWNER CHANGES 10/02/2020

95% CONSTRUCTION DOCUMENTS 04/12/2021

100% BID DOCUMENTS 05/20/2021

DN

DN

3.7

KA B C D E G H IA.5 A.9 E.3 E.7 J.1 J.5

2.1

1.7

1.8

0 .8

F

DAY ROOM

B218

MEDS

B241

ELEVATOR

TREATMENT

B206

OFFICE

B208

OFFICE

B212

GROUP ROOM

B214

OFFICE

B207

OFFICE

B209

CORRIDOR

BC-23

PRIVATE

B230

PRIVATE

B228

SEMI

B223

SEMI

B225

SEMI

B227

S. TOILET

B221

QUIET

B222

MEDICAL

BEDROOM

B226

ANTE ROOM

B224

PRIVATE

B243

PRIVATE

B245

PRIVATE

B249

PRIVATE

B247

SEMI

B242

SEMI

B244

SEMI

B246

HSK

B240STORAGE

B251

STAIR

STAIR

SOILED UTILITY

B253

SOILED LINEN

B202 STAFF LOCKER

RM / LOUNGE

B201

CLEAN LINEN

B205

HSK EQUIP.

B204

BATHROOM

B246A

BATHROOM

B244A

BATHROOM

B242A

BATHROOM

B247A

BATHROOM

B243A

BATHROOM

B245A

BATHROOM

B223A

BATHROOM

B224A

BATHROOM

B225A

BATHROOM

B227A

BATHROOM

B230A

CORRIDOR

BC-22

ELECTRICAL

B255

ELECTRICAL

B236

CORRIDOR

BC-23

CORRIDOR

C-24

CORRIDOR

C-30

CORRIDOR

BC-21

STORAGE

B213A

STORAGE

B218A

CORRIDOR

BC-27.2

CORRIDOR

BC-24

CORRIDOR

BC-25.2

DAY ROOM

NOURISHMENT

232E

MED ROOM

207A

STAFF ROOM

NURSE

STATION

C23A

CLEAN UTILITY

206B

LAUNDRY

206A

SOILED UTILITY

PHYSICIAN

PHYSICIAN

ASST.

OFFICE

NURSING 2

BED

NURSING 2

BED

NURSING 2

BED

PHYSICIAN

ASSISTANT

NURSING 1

BED

NURSING 1

BED

NURSING 1

BED

NURSING 1

BED

LAUNDRY

SOILED UTILITY

247A

STAFF ROOM

243NURSE

STATION

C28A

MED ROOM

243A

NOURISHMENT

245E

DAY ROOM

CORRIDOR

BC-27.1

CORRIDOR

BC-25.1

39-A130

2 SIM

39-A130

STAFF TOILET

245D

SECLUSION

STAFF TOILET

208D

SECLUSION

E X

IS

T

IN

G R

A M

P

E X

IS

T

IN

G R

A M

P

E X

IS

T

IN

G R

A M

P

CORRIDOR

BC-22.2

148 SF

NOURISH

B220

CORRIDOR

C22

CORRIDOR

C23

CORRIDOR

C21

CORRIDOR

C28

STORAGE

B234

LAUNDRY

B232

SIM

NURSE

STATION

B213

NURSE OFFICE

B211

OFFICE

B210

CORRIDOR

BC-26

E X

IS

T

IN

G R

A M

P

E X

IS

T

IN

G R

A M

P

GENERAL ABATEMENT NOTES:

1. ALL ENVIRONMENTAL ABATEMENT SHALL BE CONDUCTED IN ACCORDANCE

WITH REQUIRED VA TECHNICAL SPECIFICATIONS AND ALL APPLICABLE

FEDERAL, STATE, AND LOCAL REGULATIONS IN EFFECT AT THE TIME THE

WORK IS DONE.

2. COORDINATE ALL ASBESTOS ABATEMENT WORK WITH THE COR.

3. ASBESTOS- CONTAINING MATERIALS (ACM) MAY BE PRESENT IN PREVIOUSLY

INACCESSIBLE SPACES. ANY DISTURBANCE, REMOVAL, OR DEMOLITION OF

ACM SHALL BE CONDUCTED IN ACCORDANCE WITH APPLICABLE VA

SPECIFICATIONS, AND ALL LOCAL, STATE, AND FEDERAL REGULATIONS. ANY

DISTURBANCE OF ACM SHALL BE PERFORMED BY TRAINED, MEDICALLY

QUALIFIED, AND LICENSED PERSONNEL WHO WILL FOLLOW THE APPROVED

WRITTEN SITE SPECIFIC HEALTH AND SAFETY PLAN AS COORDINATED WITH

THE VA COR.

4. IN THE EVENT THAT ADDITIONAL QUANTITIES OF SUSPECT ASBESTOS -

CONTAINING MATERIALS (ACM) OR OTHER SUSPECT HAZARDOUS MATERIALS

NOT PREVIOUSLY IDENTIFIED ARE DISCOVERED THE CONTRACTOR SHALL

STOP WORK AND IMMEDIATELY NOTIFY THE CONTRACTING OFFICER.

5. ALL PAINT IS ASSUMED TO BE LEAD BASE PAINT (LBP). ALL LOOSE AND

FLAKING PAINT MUST BE REMOVED PRIOR TO REMOVAL AND DISPOSAL/

RECYCLING. HOT WORK ON SURFACES COVERED WITH LBP IS PROHIBITED.

THE CONTRACTOR SHALL BE RESPONSIBLE FOR TAKING ENVIRONMENTAL

SAFETY AND HEALTH PRECAUTIONS DURING THE DEMOLITION ACTIVITIES

FOR SURFACES COVERED WITH LBP INCLUDING WELDING, CUTTING, AND

DEMOLITION. THE REQUIREMENTS FOR THE HANDLING, USE, REMOVAL, AND

DISPOSAL OF LBP SHALL BE CONDUCTED IN ACCORDANCE WITH APPLICABLE

VA SPECIFICATION AND ALL LOCAL STATE AND FEDERAL REGULATIONS.

6. REMOVE ALL OZONE DEPLETING REFRIGERANTS IN ACCORDANCE WITH

APPLICABLE TECHNICAL SPECIFICATIONS.

7. REFER TO LIFE SAFETY PLANS FOR FIRE CODE RATINGS.

ASBESTOS LEGEND

AREA OF POSSIBLE DISTURBANCE

ASBESTOS CEILING TILE MASTIC

architecture · engineering

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERS · SURVEYORS · CONSULTANTS ·

LANDSCAPE ARCHITECTS · LAND PLANNERS

298 VETERANS DRIVE

FOWLERVILLE,

MICHIGAN 48836

(OFFICE) 517-223-3512

(FAX) 517-223-9987

211 E. Water Street, Suite 213L

Kalamazoo, MI 49007 269.216.0222

VA STATION

Battle Creek VA Medical Center

5500 Armstrong Road

Battle Creek, MI 49037

Defining

EXCELLENCE

in the 21st Century

HEALTH

CARE

C :\R ev it\

\1

4_

A _m ic he lle .b ur ri.

rv t

5/

/2

:2 0:

A

M

39-G111

PARTIAL SECOND FLOOR

ASBESTOS REMOVAL PLAN

RENOVATE B39-2 WEST

FOR PATIENT PRIVACY

BATTLE CREEK, MI

515-20-102

05/20/2021 KJH MRB/MMN

100% BID DOCUMENTS190134

1/8" = 1'-0"

PARTIAL SECOND FLOOR ASBESTOS REMOVAL PLAN

NOT TO SCALE

KEY PLAN SECOND FLOOR

Revisions: Date:

65% DESIGN DEVELOPMENT 03/06/2020

RESUBMIT WITH OWNER CHANGES 10/02/2020

UP DN DN UP

DAY ROOM

MEDS

ELEVATOR

TREATMENT

OFFICE

OFFICE

GROUP

ROOM

OFFICE

OFFICE

CORRIDOR

PRIVATEPRIVATE

SEMI SEMI SEMI

S. TOILET

QUIET

MEDICAL

BEDROOM

ANTE ROOM

NOURISH

PRIVATEPRIVATEPRIVATE PRIVATE

SEMISEMISEMI

HSK

STORAGE

STAIRSTAIR

SOILED

UTILITY

SOILED

LINEN

STAFF

LOCKER RM

/ LOUNGE

CLEAN

LINEN

HSK EQUIP.

BATHROOM

BATHROOM

BATHROOM

BATHROOM

BATHROOM

BATHROOM

BATHROOM

BATHROOM

BATHROOM

BATHROOM

BATHROOM

CORRIDOR

ELECTRICAL ELECTRICAL

CORRIDOR

CORRIDOR

CORRIDOR

CORRIDOR

STORAGE

CORRIDOR

CORRIDOR

CORRIDOR

DAY ROOM

NOURISHMENT

MED ROOM

STAFF

ROOM

NURSE

STATION

CLEAN

UTILITY

LAUNDRY SOILED

UTILITY

PHYSICIAN

PHYSICIAN

ASST.

OFFICE

NURSING 2

BED

NURSING 2

BED

NURSING 2

BED

PHYSICIAN

ASSISTANT

NURSING 1

BED

NURSING 1

BED

NURSING 1

BED

NURSING 1

BED

LAUNDRY

SOILED

UTILITY

STAFF

ROOM

NURSE

STATION

MED ROOM

NOURISHMENT

DAY ROOM

CORRIDOR CORRIDOR

STAFF

TOILET

SECLUSION

STAFF

TOILET SECLUSION

CORRIDOR

PHASE 1 - SEAL EXISTING DOOR TO

PROVIDE TEMPORARY INFECTION

CONTROL MEASURES. COMPLY

WITH SPECIFICATIONS REGARDING

INFECTION CONTROL

MAJORITY OF THE WORK TO BE

COMPLETED IN PHASE 1, WORK

RELATED TO THE EAST WALL AND

FINISHES TO BE COMPLETED IN

PHASE 2

PHASE 2 - SEAL NEWLY INSTALLED

DOOR TO PROVIDE TEMPORARY

INFECTION CONTROL MEASURES.

COMPLY WITH SPECIFICATIONS

REGARDING INFECTION CONTROL

PHASE 2 - PROVIDE 1HR RATED TEMPORARY

CONSTRUCTION WALL FOR INFECTION

CONTROL, COMPLY WITH SPECIFICATIONS

REGARDING INFECTION CONTROL, SEE

PARTITION TYPES

PHASE 3 - PROVIDE 1HR RATED TEMPORARY

CONSTRUCTION WALL FOR INFECTION

CONTROL, COMPLY WITH SPECIFICATIONS

REGARDING INFECTION CONTROL, SEE

PARTITION TYPES

PHASE 1 - SEAL EXISTING DOOR

TO PROVIDE TEMPORARY

INFECTION CONTROL MEASURES.

COMPLY WITH SPECIFICATIONS

REGARDING INFECTION CONTROL

MAJORITY OF THE WORK TO BE

COMPLETED IN PHASE 1, WORK

RELATED TO THE EAST WALL AND

FINISHES TO BE COMPLETED IN

PHASE 2

PHASE 2 - SEAL NEWLY INSTALLED

DOOR TO PROVIDE TEMPORARY

INFECTION CONTROL MEASURES.

COMPLY WITH SPECIFICATIONS

REGARDING INFECTION CONTROL

NURSE

STATION

NURSE

OFFICE

OFFICE

STORAGE

STORAGE

LAUNDRY

PROVIDE WALKOFF MATS

DURING CONSTRUCTION

PROVIDE WALKOFF MATS

DURING CONSTRUCTION

DAY ROOM

MEDS

STORAGE

ELEVATOR

TREATMENT

OFFICE

OFFICE

OFFICE

GROUP

ROOM

OFFICE

OFFICE

STAFF

OFFICE

NURSE

STATION

PRIVATEPRIVATE

SEMI SEMI

S. TOILET

RESTRAINT ISOL.

ANTE ROOM

NOURISHPRIVATEPRIVATEPRIVATE PRIVATE

SEMISEMISEMI

HSK

LAUNDRY

STORAGE

STAIR

LAUNDRY

SOILED

LINEN

STAFF

LOCKER RM

/ LOUNGE

CLEAN

LINEN

HSK EQUIP.

BATHROOM

BATHROOM

BATHROOM BATHROOM

BATHROOM

BATHROOM

BATHROOM

BATHROOM

BATHROOM

BATHROOM

BATHROOM BATHROOM

BATHROOM

CORRIDOR

STAIR

ELECTRICAL

ELECTRICAL

CORRIDOR

CORRIDOR

CORRIDOR

CORRIDOR

GROUP

ROOM

SEMI

STORAGE

STORAGE

CORRIDOR

CORRIDORCORRIDOR

DAY ROOM

NOURISHMENT

MED ROOM

STAFF

NURSE

STATION

CLEAN

UTILITY

LAUNDRY

NURSING 2

BED

NURSING 2

BED

NURSING 2

BED

FEMALE

TREATMENT

NURSING 2

BED

EXIT

VESTIBULE

UNIT

CORR./CHARGE

NURSE

AMM/SPD

STORAGE

NURSING 2

BED

NURSING 1

BED

NURSING 3

BED

CLEAN

UTILITY

LAUNDRY

STAFF

ROOM

NURSE

STATION

DAY ROOM

MED ROOM

NOURISHMENT

CORRIDOR

SECLUSION

TOILET

TOILET SECLUSION CORRIDOR

CORRIDOR

CORRIDOR

CORRIDOR

PHASE 4 - PROVIDE 1HR RATED TEMPORARY

CONSTRUCTION WALL FOR INFECTION

CONTROL, COMPLY WITH SPECIFICATIONS

REGARDING INFECTION CONTROL, SEE

PARTITION TYPES

PHASE 3 - PROVIDE 1HR RATED TEMPORARY

CONSTRUCTION WALL FOR INFECTION

CONTROL, COMPLY WITH SPECIFICATIONS

REGARDING INFECTION CONTROL, SEE

PARTITION TYPES

PHASE 1 - PROVIDE 1HR RATED TEMPORARY

CONSTRUCTION WALL FOR INFECTION

CONTROL, COMPLY WITH SPECIFICATIONS

REGARDING INFECTION CONTROL, SEE

PARTITION TYPES

PROVIDE WALKOFF MATS

DURING CONSTRUCTION

PROVIDE WALKOFF MATS

DURING CONSTRUCTION

PROVIDE WALKOFF MATS

DURING CONSTRUCTION

SEAL EXISTING DOOR TO

PROVIDE TEMPORARY

INFECTION CONTROL

MEASURES. COMPLY WITH

SPECIFICATIONS REGARDING

INFECTION CONTROL.

SEAL EXISTING DOOR TO

PROVIDE TEMPORARY

INFECTION CONTROL

MEASURES. COMPLY WITH

SPECIFICATIONS REGARDING

INFECTION CONTROL.

AREA OF

WORK

PHASE 1

PHASING LEGEND

PHASE 2

PHASE 3

PHASE 4

1. VA PREFERS THE USE OF HARD WALL

PARTITIONS OVER THE USE OF PLASTIC

SHEETING FOR SEPARATION BETWEEN

CONSTRUCTION AND EXISTING SPACES TO

REMAIN FUNCTIONING. CONTRACTOR TO

SUBMIT PROPOSED PLAN FOR TEMPORARY

CONSTRUCTION PARTITION LOCATIONS FOR

COR APPROVAL. TEMPORARY PARTITION

LOCATIONS SHOWN HERE ARE RECOMMENDED

LOCATIONS BASED ON WORK NEEDING TO BE

COMPLETED, BUT DOES NOT CONSTITUTE FINAL

LOCATIONS OR QUANITITIES.

2. REFER TO LIFE SAFETY PLANS FOR FIRE CODE

RATINGS.

GENERAL NOTES

PHASE 1&2

INFECTION CONTROL RISK MITIGATION REQUIREMENTS MATRIX

TYPE OF CONSTRUCTION / PROJECT ACTIVITY TABLE

Inspection and Non-Invasive Activities Includes, but is not limited to:

- Removal of ceiling tiles for visual inspection limited to 20 Ln Ft tile per 160 sq. ft. space.

- Painting (but not sanding).

- Wallcovering, electrical trim work, minor plumbing, and activities which no not generate dust or require cutting of walls or access to ceilings other than for visual inspection.

- Patching walls - not exceeding 8 sq. ft.

TYPE

A

Small scale, short duration activities which create minimal dust Includes, but is not limited to:

- Installation of telephone and computer cabling.

- Access to chase spaces.

- Cutting of walls or ceiling where dust migration can be controlled.

- Patching walls - exceeding 8 sq. ft.

TYPE

B

Work that generates a moderate to high level of dust or requires demolition or removal of any fixed building components and assemblies or new construction Includes, but is not limited to:

- Sanding of walls for painting or wall covering exceeding 32 sq. ft., or vacant areas.

- Removal of floor coverings, ceiling tiles and casework.

- New wall construction.

- Uncontained duct, HVAC or electrical work above ceilings.

- Major cabling activities.

- Any other project where high levels or dust are generated.

TYPE

C

Major demolition and construction projects Includes, but is not limited to:

- Activities that require consecutive work shifts.

- Requires heavy demolition or removal of a complete cabling system.

- New Construction.

TYPE

D

PATIENT RISK GROUP TABLE

- ADMINISTRATIVE OFFICES

- PUBLIC CORRIDORS

- ELEVATORS

- DAY ROOMS

- CANTEEN RETAIL STORE

- VACANT WARDS OR VACANT

ICU'S ECT.

GROUP 1

LOW RISK

- OUTPATIENT, URGENT CARE &

PRIMARY CARE CLINICS

- LABORATORY

- CARDIOLOGY

- ECHOCARDIOGRAPHY

- ENDOSCOPY

- FOOD SERVICES

- INTERIM CARE & MEDICAL

UNITS

- NUCLEAR MEDICINE

- PHARMACY

- PHYSICAL THERAPY

- RADIOLOGY & NUCLEAR

MEDICINE

- RESPIRATORY THERAPY

GROUP 2

MEDIUM RISK

- CCU

- EMERGENCY ROOM

- LABORATORY

- OUTPATIENT SURGERY

- PHARMACY

- POST ANESTHESIA CARE UNIT

- SURGICAL UNITS

GROUP 3

HIGH RISK

- ANY AREA CARING FOR

IMMUNICOMPROMISED

PATIENTS

- SPD STORAGE / STERILIZATION

- INTENSIVE CARE UNITS

- TB NEGATIVE PRESSURE

ISOLATION ROOMS

- OPERATING ROOM

GROUP 4

HIGHEST RISK

IT IS THE CONTRACTOR'S RESPONSIBILITY TO PROVIDE THE FOLLOWING INFECTION CONTROL PRECAUTIONS DEPENDING UPON THE AREA CLASS DESIGNATION

DURING CONSTRUCTION PROJECT

1. EXECUTE WORK BY METHODS TO MINIMIZE RAISING DUST FROM CONSTRUCTION OPERATIONS.

2. IMMEDIATELY REPLACE A CEILING TILE DISPLACED FOR VISUAL INSPECTIONS.

C L A

S S

I

UPON COMPLETION OF PROJECT

1. PROVIDE ACTIVE MEANS TO PREVENT AIRBORNE DUST FROM DISPERSING INTO ATMOSPHERE.

2. WATER MIST WORK SURFACES TO CONTROL DUST WHILE CUTTING.

3. SEAL UNUSED DOORS WITH DUCT TAPE.

4. BLOCK OFF AND SEAL AIR VENTS.

5. PLACE DUST MAT AT ENTRANCE AND EXIT OF WORK AREA.

6. REMOVE OR ISOLATE HVAC SYSTEM IN AREAS WHERE WORK IS BEING PERFORMED.

C L

A S

S

II

1. WIPE WORK SURFACES WITH DISINFECTANT.

2. CONTAIN CONSTRUCTION WASTE BEFORE TRANSPORT IN TIGHTLY COVERED CONTAINERS.

3. WIPE WORK SURFACES WITH DISINFECTANT, WET MOP AND / OR VACUUM WITH HEPA VACUUM BEFORE LEAVING

WORK AREA.

4. REMOVE ISOLATION OF HVAC.

1. REMOVE OR ISOLATE HVAC SYSTEM IN AREA WHERE WORK IS BEING DONE TO PREVENT CONTAMINATION OF DUCT SYSTEM.

2. COMPLETE ALL CRITICAL BARRIERS, I.E., SHEETROCK, PLYWOOD, PLASTIC, TO SEAL AREA FROM NON-WORK AREA OR IMPLEMENT CONTROL CUBE METHOD (CART WITH PLASTIC COVERING AND SEALED CONNECTION TO WORK SITE WITH HEPA

VACUUM FOR VACUUMING PRIOR TO EXIT) BEFORE CONSTRUCTION BEGINS.

3. MAINTAIN NEGATIVE AIR PRESSURE WITHIN WORK SITE UTILIZING HEPA EQUIPPED AIR FILTRATION UNITS.

4. CONTAIN CONSTRUCTION WASTE BEFORE TRANSPORT IN TIGHTLY COVERED CONTAINERS.

5. COVER TRANSPORT RECEPTACLES OR CARTS. TAPE COVERING UNLESS SOLID LID.

C L

A S

S I

II

1. DO NOT REMOVE BARRIERS FROM WORK AREA UNTIL COMPLETED PROJECT IS INSPECTED BY THE ENVIRONMENTAL HEALTH AND SAFETY AND INFECTION CONTROL AND THOROUGHLY CLEANED BY ENVIRONMENTAL

SANITATION SECTION.

2. REMOVE BARRIER MATERIALS CAREFULLY TO MINIMIZE SPREADING OF DIRT AND DEBRIS ASSOCIATED WITH

CONSTRUCTION.

3. VACUUM WORK AREA WITH HEPA FILTERED VACUUMS.

4. WET MOP AREA WITH DISINFECTANT.

5. REMOVE ISOLATION OF HVAC SYSTEM IN AREAS WHERE WORK IS BEING PERFORMED.

1. OBTAIN INFECTION CONTROL PERMIT BEFORE CONSTRUCTION BEGINS.

2. ISOLATE HVAC SYSTEMS IN AREA WHERE WORK IS BEING DONE TO PREVENT CONTAMINATION OF DUCT SYSTEM.

3. COMPLETE ALL CRITICAL BARRIERS OR IMPLEMENT CONTROL CUBE METHOD BEFORE CONSTRUCTION BEGINS.

4. MAINTAIN NEGATIVE AIR PRESSURE WITHIN WORK SITE UTILIZING HEPA EQUIPPED AIR FILTRATION UNITS.

5. SEAL HOLES, PIPES, CONDUITS AND PUNCTURES APPROPRIATELY.

6. CONSTRUCT ANTEROOM AND REQUIRE ALL PERSONNEL TO PASS THROUGH THIS ROOM SO THEY CAN BE VACUUMED USING A HEPA VACUUM CLEANER BEFORE LEAVING WORK SITE OR THEY CAN WEAR CLOTH OR PAPER COVERALLS THAT ARE REMOVED

EACH TIME THEY LEAVE THE WORK SITE.

7. ALL PERSONNEL ENTERING WORK SITE ARE REQUIRED TO WEAR SHOE COVERS.

C L A

S S

I V

1. DO NOT REMOVE BARRIERS FROM WORK AREA UNTIL COMPLETED PROJECT IS THOROUGHLY CLEANED BY

ENVIRONMENTAL MANAGEMENT.

2. VACUUM WORK AREA WITH HEPA FILTERED VACUUMS.

3. WET MOP AREA WITH DISINFECTANT.

4. REMOVE BARRIER MATERIALS CAREFULLY TO MINIMIZE SPREADING OF DIRT AND DEBRIS ASSOCIATED WITH

CONSTRUCTION.

5. CONTAIN CONSTRUCTION WASTE BEFORE TRANSPORT IN TIGHTLY COVERED CONTAINERS.

6. COVER TRANSPORT RECEPTACLES OR CARTS, TAPE COVERING.

7. REMOVE ISOLATION OF HVAC SYSTEM IN AREAS WHERE WORK IS BEING PERFORMED.

INFECTION CONTROL MATRIX - CLASS OF PRECAUTIONS:

CONSTRUCTION PROJECT BY PATIENT RISK

PATIENT RISK GROUP

TYPE OF CONSTRUCTION / PROJECT

TYPE A

LOW RISK GROUP 1

MEDIUM RISK GROUP 2

HIGH RISK GROUP 3

HIGHEST RISK GROUP 4

TYPE B TYPE C TYPE D

I II II III / IV

I II II IV

I II III / IV IV

II III / IV III / IV IV

NOTE: INFECTION CONTROL APPROVAL WILL BE REQUIRED WHEN THE CONSTRUCTION ACTIVITY

AND RISK LEVEL INDICATE THAT CLASS III OR IV CONTROL PROCEDURES ARE NECESSARY

architecture · engineering

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERS · SURVEYORS · CONSULTANTS ·

LANDSCAPE ARCHITECTS · LAND PLANNERS

298 VETERANS DRIVE

FOWLERVILLE,

MICHIGAN 48836

(OFFICE) 517-223-3512

(FAX) 517-223-9987

211 E. Water Street, Suite 213L

Kalamazoo, MI 49007 269.216.0222

VA STATION

Battle Creek VA Medical Center

5500 Armstrong Road

Battle Creek, MI 49037

Defining

EXCELLENCE

in the 21st Century

HEALTH

CARE

C :\R ev it\

\1

4_

A _m ic he lle .b ur ri.

rv t

5/

/2

:2 0:

A

M

39-G121

INFECTION CONTROL RISK

ASSESSMENT & PHASING PLANS

RENOVATE B39-2 WEST

FOR PATIENT PRIVACY

BATTLE CREEK, MI

515-20-102

05/20/2021 KJH MRB/MMN

100% BID DOCUMENTS190134

1/16" = 1'-0"

SECOND FLOOR NEW CONSTRUCTION

NOT TO SCALE

KEY PLAN SECOND FLOOR

1/16" = 1'-0"

FIRST FLOOR NEW CONSTRUCTION

NOT TO SCALE

KEY PLAN FIRST FLOOR

Revisions: Date:

65% DESIGN DEVELOPMENT 03/06/2020

RESUBMIT WITH OWNER CHANGES 10/02/2020

UP DN DN UP

DEDUCTIVE ALTERNATE 1DEDUCTIVE ALTERNATE 1

DAY ROOM

MEDS

ELEVATOR

TREATMENT

OFFICE

OFFICE

GROUP

ROOM

OFFICE

OFFICE

CORRIDOR

PRIVATEPRIVATE

SEMI SEMI SEMI

S. TOILET

QUIET

MEDICAL

BEDROOM

ANTE ROOM

NOURISHPRIVATEPRIVATEPRIVATE PRIVATE

SEMISEMISEMI

HSK

STORAGE

STAIRSTAIR

SOILED

UTILITY

SOILED

LINEN

STAFF

LOCKER RM

/ LOUNGE

CLEAN

LINEN

HSK EQUIP.

BATHROOM

BATHROOM

BATHROOM

BATHROOM

BATHROOM

BATHROOM

BATHROOM

BATHROOM

BATHROOM

BATHROOM

BATHROOM

CORRIDOR

ELECTRICAL ELECTRICAL

CORRIDOR

CORRIDOR

CORRIDOR

CORRIDOR

STORAGE

CORRIDOR

CORRIDOR

CORRIDOR

DAY ROOM

NOURISHMENT

MED ROOM

STAFF

ROOM

NURSE

STATION

CLEAN

UTILITY

LAUNDRY SOILED

UTILITY

PHYSICIAN

PHYSICIAN

ASST.

OFFICE

NURSING 2

BED

NURSING 2

BED

NURSING 2

BED

PHYSICIAN

ASSISTANT

NURSING 1

BED

NURSING 1

BED

NURSING 1

BED

NURSING 1

BED

LAUNDRY

SOILED

UTILITY

STAFF

ROOM

NURSE

STATION

MED ROOM

NOURISHMENT

DAY ROOM

CORRIDOR CORRIDOR

STAFF

TOILET

SECLUSION

STAFF

TOILET SECLUSION

CORRIDOR

OFFICE

NURSE

OFFICE

NURSE

STATION

STORAGE

STORAGE

LAUNDRY

CORRIDOR

DEDUCTIVE ALTERNATE 2DEDUCTIVE ALTERNATE 2

DEDUCTIVE ALTERNATE 3

DAY ROOM

MEDS

STORAGE

ELEVATOR

TREATMENT

OFFICE

OFFICE

OFFICE

GROUP

ROOM

OFFICE

OFFICE

STAFF

OFFICE

NURSE

STATION

PRIVATEPRIVATE

SEMI SEMI

S. TOILET

RESTRAINT ISOL.

ANTE ROOM

NOURISHPRIVATEPRIVATEPRIVATE PRIVATE

SEMISEMISEMI

HSK

LAUNDRY

STORAGE

STAIR

LAUNDRY

SOILED

LINEN

STAFF

LOCKER RM

/ LOUNGE

CLEAN

LINEN

HSK EQUIP.

BATHROOM

BATHROOM

BATHROOM BATHROOM

BATHROOM

BATHROOM

BATHROOM

BATHROOM

BATHROOM

BATHROOM

BATHROOM BATHROOM

BATHROOM

CORRIDOR

STAIR

ELECTRICAL

ELECTRICAL

CORRIDOR

CORRIDOR

CORRIDOR

CORRIDOR

GROUP

ROOM

SEMI

STORAGE

STORAGE

CORRIDOR

CORRIDORCORRIDOR

DAY ROOM

NOURISHMENT

MED ROOM

STAFF

NURSE

STATION

CLEAN

UTILITY

LAUNDRY

NURSING 2

BED

NURSING 2

BED

NURSING 2

BED

FEMALE

TREATMENT

NURSING 2

BED

EXIT

VESTIBULE

UNIT

CORR./CHARGE

NURSE

AMM/SPD

STORAGE

NURSING 2

BED

NURSING 1

BED

NURSING 3

BED

CLEAN

UTILITY

LAUNDRY

STAFF

ROOM

NURSE

STATION

DAY ROOM

MED ROOM

NOURISHMENT

CORRIDOR

SECLUSION TOILETTOILET SECLUSION

CORRIDOR

CORRIDOR

• DEDUCTIVE ALTERNATE 1 - NURSE STATION BUILDING 39-2 NORTH AND BUILDING 39-2 SOUTH

• DEDUCTIVE ALTERNATE 2 - EVERYTHING IN DEDUCTIVE ALTERNATE 1 PLUS NURSE STATION

BUILDING 39-1 NORTH AND BUILDING 39-1 SOUTH

• DEDUCTIVE ALTERNATE 3 - EVERYTHING IN DEDUCTIVE ALTERNATE 1 & 2 PLUS NURSE

STATION BUILDING 39-1 WEST

DEDUCTIVE ALTERNATE LEGEND:

AREA OF

WORK

architecture · engineering

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERS · SURVEYORS · CONSULTANTS ·

LANDSCAPE ARCHITECTS · LAND PLANNERS

298 VETERANS DRIVE

FOWLERVILLE,

MICHIGAN 48836

(OFFICE) 517-223-3512

(FAX) 517-223-9987

211 E. Water Street, Suite 213L

Kalamazoo, MI 49007 269.216.0222

VA STATION

Battle Creek VA Medical Center

5500 Armstrong Road

Battle Creek, MI 49037

Defining

EXCELLENCE

in the 21st Century

HEALTH

CARE

C :\R ev it\

\1

4_

A _m ic he lle .b ur ri.

rv t

5/

/2

:2 0:

A

M

39-G131

DEDUCTIVE ALTERNATES RENOVATE B39-2 WEST

FOR PATIENT PRIVACY

BATTLE CREEK, MI

515-20-102

05/20/2021 KJH MRB/MMN

100% BID DOCUMENTS190134

1/16" = 1'-0"

DEDUCTIVE ALTERNATES SECOND FLOOR PLAN

1/16" = 1'-0"

DEDUCTIVE ALTERNATES FIRST FLOOR PLAN

NOT TO SCALE

KEY PLAN SECOND FLOOR

NOT TO SCALE

KEY PLAN FIRST FLOOR

Revisions: Date:

65% DESIGN DEVELOPMENT 03/06/2020

RESUBMIT WITH OWNER CHANGES 10/02/2020

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

39-L101

LANDSCAPE PLAN

A

FULLY SPRINKLED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

RENOVATE B39-2 WEST

FOR PATIENT PRIVACY

BATTLE CREEK, MI

515-20-102

05/20/2021 KJH JMM

Revisions: Date:

100% BID DOCUMENTS

NO

T

FO

R

CO

NS

TR

UC

TI

ON

ENGINEERS · SURVEYORS · CONSULTANTS ·

LANDSCAPE ARCHITECTS · LAND PLANNERS

298 VETERANS DRIVE

FOWLERVILLE,

MICHIGAN 48836

(OFFICE) 517-223-3512

(FAX) 517-223-9987

211 E. Water Street, Suite 213L

Kalamazoo, MI 49007 269.216.0222 architecture · engineering

VA STATION

Battle Creek VA Medical Center

5500 Armstrong Road

Battle Creek, MI 49037

Defining

EXCELLENCE

in the 21st Century

HEALTH

CARE

LANDSCAPE NOTES

LANDSCAPE LEGEND

LANDSCAPE KEY

SCHEMATIC DESIGN - 35% 11/25/2019

65% DESIGN DEVELOPMENT 03/06/2020

RESUBMIT WITH OWNER CHANGES 10/02/2020

PAVING PATTERN AND PLANTER LAYOUT

PLANTING PLAN

PLANTER PLANT SCHEDULE

Feet 0 5 10

Feet 0 2 4

ARCANA CUT EDGE PAVER BY UNILOCK

(TYP, CUT TO FIT)

24"X24" ARCARNA PAVER BY UNILOCK (TYP)

CONTRACTOR TO FIELD VERIFY

PROPOSED POC. VERIFY CAPACITY

FOR ADDITIONAL ZONES IN EXISTING

CONTROLLER AND ADEQUATE

PRESSURE IN EXISTING IRRIGATION

SYSTEM. CONNECTION SHALL BE

MADE TO MINIMIZE VISIBILITY AND

DISRUPTION OF EXISTING

STRUCTURES AND LANDSCAPING.

95% CONSTRUCTION DOCUMENTS 04/12/2021

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

39-L102

LANDSCAPE DETAILS

A

FULLY SPRINKLED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

RENOVATE B39-2 WEST

FOR PATIENT PRIVACY

BATTLE CREEK, MI

515-20-102

KJH EEC

Revisions: Date: NO

T

FO

R

CO

NS

TR

UC

TI

ON

ENGINEERS · SURVEYORS · CONSULTANTS ·

LANDSCAPE ARCHITECTS · LAND PLANNERS

298 VETERANS DRIVE

FOWLERVILLE,

MICHIGAN 48836

(OFFICE) 517-223-3512

(FAX) 517-223-9987

211 E. Water Street, Suite 213L

Kalamazoo, MI 49007 269.216.0222 architecture · engineering

VA STATION

Battle Creek VA Medical Center

5500 Armstrong Road

Battle Creek, MI 49037

Defining

EXCELLENCE

in the 21st Century

HEALTH

CARE

SCHEMATIC DESIGN - 35% 11/25/2019

65% DESIGN DEVELOPMENT 03/06/2020

RESUBMIT WITH OWNER CHANGES 10/02/2020

PRUNE OUT ANY DEAD OR BROKEN

BRANCHES. CUT ANY GIRDLING ROOTS

OFF CLOSE TO THE CROWN. PRY LONG

ROOTS OUT TO DIRECT INTO NEW SOIL

PLACE SHRUB OR PERENNIAL SO CROWN IS

AT SOIL LEVEL

FILL PLANTER WITH AMENDED SOIL MIX

ACCORDING TO NOTE 4 SHEET L01. CONSTRUCT

RING AROUND PLANTS TO FORM SAUCER

NOTES:

1. REFER TO NOTE 4 SHEET L01 FOR PLANTER MIX.

2. CONTRACTOR TO WATER THOROUGHLY AFTER PLANTING

3. INSTALLATION TO BE IN ACCORDANCE WITH PLANTING SPECIFICATIONS

2 NURSERY CONTAINER (TYP)

SECTION

PLANTER

NOTES:

1. CONTRACTOR TO INSTALL PAVER SYSTEM IN ACCORDANCE WITH

MANUFACTURE'S SPECIFICATIONS

2. CONTRACTOR TO COORDINATE WITH INSTALLATION OF IRRIGATION

SYSTEM TO FOR ACCESS TO LANDSCAPE PLANTERS TO BE PLACED

FOLLOWING PAVER INSTALLATION.

NOTES:

1. CONTRACTOR TO INSTALL PLANTERS IN ACCORDANCE WITH

MANUFACTURE'S SPECIFICATIONS.

2. CONTRACTOR TO COORDINATE WITH INSTALLATION OF PEDESTAL

PAVER SYSTEM FOR PLACEMENT FOLLOWING PAVER INSTALLATION.

3. CONTRACTOR TO COORDINATE PLANTER PLACEMENT WITH DRIP

IRRIGATION SYSTEM.

UNILOCK ARCANA PAVERS AND PEDESTAL PAVER SYSTEM

05/20/2021

100% BID DOCUMENTS

95% CONSTRUCTION DOCUMENTS 04/12/2021

MOUNTING HEIGHT

COORDINATION

ARCHITECTURAL,

MECHANICAL &

ELECTRICAL TRADES

SHALL COORDINATE

LOCATIONS OF WALL

MOUNTED ITEMS TO ALIGN

EITHER VERTICALLY OR

HORIZONTALLY.

FINISH FLOOR LINE

DRAWING REFERENCE SYMBOLS RECOMMENDED MOUNTING HEIGHTS (UNLESS OTHERWISE NOTED)

MAX

REACH

DEPTH

MAX

REACH

HEIGHT

0.5"

48"

2"

46"

5"

42"

6"

40"

9"

36"

11"

34"

GENERAL MAXIMUM REACH DEPTH AND HEIGHT

FOR HAND DRYERS / TOWEL DISPENSERS

MAX REACH DEPTH

F O

R R

E A

C H

D E

P T

H M

A X

H E

IG

H

T

M

IR

R O

R O

R

M

IR

R O

R

S H

E

LF

(M

A X

T O

W E

L D

IS

P

E N

S E

M U

LT

I- P

U R

P O

S

U

N

IT

T O

W E

L D

IS

P

E N

S

E C

E P

T A

C

LE

W A

S T

C

E P

T A

C

LE

C O

A T H

O O

K S

S A

N

IT

A R

Y N

A P

K

IN

V

N

D O

R

S O

A P

D

IS

P

E N

S E

R

M

A X

M O

P S

T R

IP

H E

LF

12"

A D

A

N D

A

E

LF

C

A T R

O D

M A

X

24"

BOTTOM OF

OUTLET

BOTTOM OF

LIGHT FIXTURE

M

A X

24" MIN

36" MAX

M

IN

M

IN

24" MIN

42" MAX

M

A X

36" MAX

M

IN

24" MIN

42" MAX

/2

M

IN

P R

O T R

U D

G

IL

E

T P

A P

P

E N

S

LO

A T

IO

N

R E

C E

S S

IL

E

T P

A P

P

E N

S

A T

IO

N

P R

O T R

U D

IL

E

T P

A P

P

E N

S

A T

IO

N

M

IN

7"-9"

M

A X

S A

N

IT

A

Y

P K

P O

S A

L

22"

/2

M

IN

P R

O T R

U D

IL

E

T P

A P

P

E N

S

A T

IO

N

E

LE

V A

T O

R W

LL

B

T

T O

N S

(M

IN

" S E

E E

L E

C T

E

LE

C T R

IC

N E

L C

A B

IN

E

T

P O

W E

R P

A N

E L

E

LE

C T R

IC

T E

LE

P

H O

N E

O R

T

LE

T

S W

IT

C

H

P U

S H

B U

T T O

N

F

IR

E A

LA

R

M B

O X

T H

E R

M O

S T A

T

C A

R D

R E

A D

E R

M E

C H

A N

IC

A

L P

A N

E

LS

I

F

IS

H

E D

S P

A C

E S

S E

LE

C

T O

R S

W

IT

C H

R

S

S W

IT

C

H O

R W

LL

T

LE

T

A B

O

B

IN

E T

SS

SEE PLAN

12" 12"

H A

N D

R A

IL

R A

M P

T O

C A

B

IN

E T

H A

N D

L E

F

IR

E E

X T

IN

G

U

IS

H E

R

F

IR

E E

X T

IN

G U

IS

H

B

IN

E

T F

IR

E H

O S

E

O R

C O

M B

IN

A

T

IO

B

IN

E T

54" MIN

GRAB BAR

GRAB BAR

'-8

M

A X

6" MAX 36"

(MIN)

18"

GRAB BAR

40"

13" MAX

42" 42"

W A

T E

R C

LO

S

E T

W A

T E

R C

LO

S

E T

(M A

X

(M

A X

B A

R R

IE

E E

U R

IN

A

L

S T A

N D

A R

IN

A L

GRAB BAR

18"

T R

A N

S F E

R

T Y

P E

S H

O W

E R

FOLDING

SHOWER SEAT

R O

LL

-I N

-T Y

O

W E

R

M

IN

T R

A N

S F E

R

T Y

P E

S H

O W

E R

(M

IN

(M A

X

T O

P S

P O

U T

M A

X S

IN

K

D E

P T

H

11"

(MIN)

17"

3" (MAX)

WALL

SPACE

AVAILABLE

NOTE:

WATER SUPPLY & DRAIN

PIPES BELOW LAVATORIES

AND SINKS MUST BE

INSULATED OR OTHERWISE

CONFIGURED TO PROTECT

AGAINST CONTACT.

E W

C

IN

K

U N

T A

IN

W A

LL

H

U N

G L

A V

B A

R R

IE

E E

L A

U

N T E

R

M

IN

MAX

4"

6" MAX

ALIGN WITH EDGE OF SEAT

6'

0"

ENLARGED PLAN OR DETAIL

WALL SECTION

X-###

X

X

X-###

BUILDING SECTION

EXTERIOR ELEVATIONS

INTERIOR ELEVATIONS

DEMO KEYNOTE##

REVISION CLOUD AND TAG

VIEW TITLE & REFERENCE

EXISTING COLUMN LINE

NEW COLUMN LINE

DETAIL

LEVEL OR ELEVATION

XX

DEMARCATION LINE

X-###

X-###

X-###

X-###

X-###

X-###

X## EQUIPMENT TAG

WALL TAG

###.# DOOR TAG

ROOM NAME

ROOM TAG

WINDOW TAG

X#

## ARCHITECTURAL KEYNOTE

#' - #" CEILING SPOT ELEVATION

XX# FURNITURE TAG

FINISH TAG

SPECIALITY EQUIPMENT TAG

XX-#

XX- #

architecture · engineering

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERS · SURVEYORS · CONSULTANTS ·

LANDSCAPE ARCHITECTS · LAND PLANNERS

298 VETERANS DRIVE

FOWLERVILLE,

MICHIGAN 48836

(OFFICE) 517-223-3512

(FAX) 517-223-9987

211 E. Water Street, Suite 213L

Kalamazoo, MI 49007 269.216.0222

VA STATION

Battle Creek VA Medical Center

5500 Armstrong Road

Battle Creek, MI 49037

Defining

EXCELLENCE

in the 21st Century

HEALTH

CARE

C :\R ev it\

\1

4_

A _m ic he lle .b ur ri.

rv t

5/

/2

:2 5:

A

M

39-A001

ARCHITECTURAL LEGENDS,

SYMBOLS, AND ABBREVIATIONS

RENOVATE B39-2 WEST

FOR PATIENT PRIVACY

BATTLE CREEK, MI

515-20-102

05/20/2021 KJH MRB/MMN

100% BID DOCUMENTS190134

ABBREVIATIONS

ABBREV. FULL TEXT

SUSP SUSPENDED

SYM SUSPENSION SYMMETRICAL

T

T TREAD

T&G TONGUE AND GROOVE

T.O.C. OR T/C TOP OF CONCRETE

T.O.F. OR T/F TOP OF FOOTING

T.O.M. OR T/M TOP OF MASONRY

T.O.P. OR T/P TOP OF PAVEMENT

T.O.S. OR T/S TOP OF STEEL

T.O.W. OR T/W TOP OF WALL

T/ TOP OF

TB TRUSS BEARING

TG TEMPERED GLASS

THK THICK

THRESH THRESHOLD

TLT TOILET

TP TOILET PARTITION

TR TRACK

TYP TYPICAL

TYP TYPICAL

U

UNF UNFINISHED

UNO UNLESS NOTED OTHERWISE

V

VCT VINYL COMPOSITION TILE

VERT VERTICAL

VEST VESTIBULE

VIF VERIFY IN FIELD

W

W WEST

W/ WITH

W/O WITHOUT

WC WATER CLOSET

WCO WALL CLEAN OUT

WD WOOD

WP WATERPROOFING

WP WORKPOINT

WP WALL PROTECTION

WS WINDOW SHADE

WT WEIGHT

ABBREVIATIONS

ABBREV. FULL TEXT

S

S SOUTH

SA SUPPLY AIR

SAB SOUND ATTENUATION BLANKETS

SACS SEAMLESS ACOUSTICAL CEILING

SYSTEM

SC SOLID CORE

SCH SCHEDULE

SCONC SEALED CONCRETE

SCWD SOLID CORE WOOD

SECT SECTION

SER.RECPT SERVICE RECEPTOR

SH SHELF

SHT SHEET

SHWR SHOWER

SIM SIMILAR

SLR CONCRETE SEALER

SLV SHORT LEG VERTICAL

SPEC SPECIFICATION

SQ SQUARE

SS STAINLESS STEEL

SSK SERVICE SINK

SSM SOLID SURFACING MATERIAL

SSM SOLID SURFACE

STD STANDARD

STDW STANDARD WEIGHT (STEEL PIPE)

STL STEEL

STOR STORAGE

STRL STRUCTURAL

SUPP SUPPORT

ABBREVIATIONS

ABBREV. FULL TEXT

P

P PAINT

PART PARTITION

PB PARTICLE BOARD

PC PRECAST

PCS PIECES

PERM PERMANENT

PL PLATE

PLAM PLASTIC LAMINATE

PLAS PLASTER

PLBG PLUMBING

PLY PLYWOOD

PT PORCELAIN TILE

PTB PORCELAIN TILE BASE

Q

QT QUARRY TILE

QTB QUARTZ TILE BASE

QTZ QUARTZ

R

R RISER

RA RETURN AIR

RB RUBBER BASE

RC ROOF CONDUCTOR

RD ROOF DRAIN

RD ROUND

RECVG RECEIVING

REF REFRIGERATOR

REINF REINFORCED

REQ'D REQUIRED

RF RESILIENT FLOORING

RH RIGHT HAND

RL ROOF LADDER

RM ROOM

RO ROUGH OPENING

RS ROOF SUMP

ABBREVIATIONS

ABBREV. FULL TEXT

M

MA MEDICAL AIR

MANUF MANUFACTURER

MAS MASONRY

MATL MATERIAL

MAX MAXIMUM

MBH THOUSAND BTU/HR

MC MEDICINE CABINET

MCA MINIMUM CIRCUIT AMPACITY

MCC MULTI-COLOR COATING

MDO MEDIUM DENSITY OVERLAY

MECH MECHANICAL

MEMBWP MEMBRANE WATERPROOFING

MET METAL

MEZZ MEZZANINE

MFR MANUFACTURER

MFS MAXIMUM FUSE SIZE

MG MEDICAL GAS

MH MANHOLE

MHP MOTOR HORSEPOWER

MIN. MINIMUM

MIRR MIRROR

MISC MISCELLANEOUS

MM MISCELLANEOUS METALS

MO MASONRY OPENING

MOCP MAXIMUM OVERCRRENT PROTECTION

MPC MICHIGAN PLUMBING CODE

MR MANUFACTURER'S RECOMMENDATIONS

MT MARBLE TILE

MTD MOUNTED

MUL. MULLION

N

N NORTH

N.S. NEAR SIDE

NF NO FINISH

NIC NOT IN CONTRACT

NO NUMBER

NPSH NET POSITIVE SUCTION HEAD

NSNS NON SHRINK NON STAIN GROUT

NTS NOT TO SCALE

NTS NOT TO SCALE

O

O.C. OR OC ON CENTER

OBSGL OBSCURE GLASS

OD OUTSIDE DIAMETER

OHDR SECTIONAL OVERHEAD DOOR

OPNG OPENING

OPP OPPOSITE

ABBREVIATIONS

ABBREV. FULL TEXT

G

G.B. GRAB BAR, GRADE BEAM

G.O. GRILL OPENING

GA GAUGE

GALV GALVANIZED

GFCI GROUND FAULT CIRCUIT INTERRUPTER

GL GLASS

GND. GROUND

GR. GRADE

GRTG. GRATING

GSCFT GLAZED STRUCTURAL CLAY FACING TILE

GT GROUT

GYP. BD. GYPSUM BOARD

H

HC HOLLOW CORE

HCWD HOLLOW CORE WOOD

HDPB HIGH DENSITY PARTICLEBOARD

HM HOLLOW METAL

HORIZ HORIZONTAL

HP HIGH POINT

HR HOUR

HT HEIGHT

HWD HARDWARE

I

I.D. OR ID INSIDE DIAMETER

I.E. INVERT ELEVATION

IG INSULATING GLASS

IN INCHES

INCL INCLUDING, INCLUSIVE

INSUL INSULATION

INT INTERIOR

IPS INTERIOR PAINT SYSTEM

J

JAN JANITOR

JT JOINT

K kW KILOWATTS kWh KILOWATT HOURS

L

LAD LADDER

LAM LAMINATED

LAV LAVATORY

LF LINEAR FEET

LGTH LENGTH

LH LEFT HAND

LKR LOCKER

LLH LONG LEG HORIZONTAL

LLV LONG LEG VERTICAL

LO LOUVER OPENING

LP LIGHTING PANEL

LPG LIQUID PETROLEUM GAS

LPS LOW PRESSURE STEAM

LT LIGHT

LWT LEAVING WATER TEMPERATURE

ABBREVIATIONS

ABBREV. FULL TEXT

D

DEXS DOUBLE EXTRA STRONG (STEEL PIPE)

DF DRINKING FOUNTAIN

DIA DIAMETER

DIFF DIFFUSER

DN DOWN

DO DOOR OPENING

DR DOOR

DS DOWN SPOUT

DT DRAIN TILE

DWG DRAWING

DWR DRAWER

E

E EAST

EA EACH

EIFS EXTERIOR INSULATION AND FINISH

SYSTEMS

EJ EXPANSION JOINT

EL ELEVATION

ELECT ELECTRICAL

ELEV ELEVATOR OR ELEVATION

ENCL ENCLOSURE

EP EPOXY PAINT

EPS EXTERIOR PAINT SYSTEM

EQ EQUAL

EQUIP EQUIPMENT

ES EXPOSED STRUCTURE

EW EACH WAY

EWC ELECTRICAL WATER COOLER

EX EXISTING

EXGR EXISTING GRADE

EXP EXPANSION

EXS EXTRA STRONG (STEEL PIPE)

EXT EXTERIOR

F

FA FIRE ALARM

FAB FABRIC/UPHOLSTERY

FD FLOOR DRAIN

FDN FOUNDATION

FE FIRE EXTINGUISHER

FEC FIRE EXTINGUISHER CABINET

FHC FIRE HOSE CABINET

FIN FINISH

FL FLOOR

FLL FLOOR LINE

FLUOR FLUORESCENT

FOC FACE OF COLUMN

FOCONC FACE OF CONCRETE

FRC FIBER REINFORCED CONCRETE

FRP FIELD REINFORCED PANEL

FRPFG FIREPROOFING

FS FULL SIZE

FT FOOT, FEET

FTG FOOTING

FUR FURRING

FV FIELD VERIFY

ABBREVIATIONS

ABBREV. FULL TEXT

A

AB ANCHOR BOLT

ABI ADDITIVE BID ITEM

AC ACOUSTICAL

ACP ACOUSTICAL CEILING PANEL

AD AREA DRAIN

AFF ABOVE FINISHED FLOOR

AL ALUMINUM

ALUM ALUMINUM

AP ACCESS DOORS

APPROX APPROXIMATE

ARCH ARCHITECTURAL

ASPH ASPHALT

AWP ACOUSTICAL WALL PANEL

B

B/ BOTTOM OF

BD BOARD

BF BARRIER FREE

BIT BITUMINOUS

BL BUILDING LINE

BLDG BUILDING

BLKHD BULKHEAD

BOTT BOTTOM

BP BASE PLATE

BS BOTH SIDES

BUR BUILT UP ROOFING

C

CAB CABINET

CB CATCH BASIN

CEM CEMENT

CG CORNER GUARD

CH CHANNEL

CHKDPL CHECKERED PLATE

CJ CONTROL JOINT

CL CENTERLINE

CL TO CL CENTERLINE TO CENTERLINE

CLG CEILING

CLK CAULKING

CLR CLEAR

CMU CONCRETE MASONRY UNIT

CO CASED OPENING OR CLEAN OUT

COL COLUMN

COMP COMPRESSIBLE

COMPO COMPOSITION

CONC CONCRETE

CONN CONNECT, CONNECTION

CONST CONSTRUCTION

CONST JT CONSTRUCTION JOINT

CONT CONTINUOUS

CONTR CONTRACTOR

CPT CARPET TILE

CTR COUNTER

CTSK COUNTERSINK

Revisions: Date:

SCHEMATIC DESIGN - 35% 11/25/2019

65% DESIGN DEVELOPMENT 03/06/2020

RESUBMIT WITH OWNER CHANGES 10/02/2020

CEILING - SEE ROOM

FINISH SCHEDULE

METAL STUDS @ 16" O.C.

CONTINUOUS ACOUSTIC

SEALANT EACH SIDE

METAL RUNNER CHANNEL

SECURE TO FLOOR

SOUND ATTENUATION

BATT INSULATION

IMPACT RESISTANT

GYPSUM BOARD

PARTITION TYPE 'S1R'

(1-HR RATED / 4" METAL STUDS / DESIGN UL-U419)

PARTITION TYPE 'S2R'

(2-HR RATED / 4" METAL STUDS / INSULATED / DESIGN UL-U419)

METAL STUD FIRESTOPPING

@ CEILING

FILL VOIDS W/ SAFING

INSULATION

UNDERSIDE OF METAL

DECK ABOVE

FIRESTOPPING & SEALANT

SYSTEM

GYP. BD. CLOSURE CUT

TO DECK PROFILE

2 1/2" DEEP SLOTTED

METAL DEFLECTION &

FIRESTOP TRACK

FASTENED TO DECK @

2'-0" O.C.

WALL BASE

(2) LAYERS 5/8" TYPE 'X'

GYP. BD. AS REQ'D FOR

2 HR. RATING

CONTINUOUS ACOUSTIC

SEALANT EACH SIDE

2 1/2" DEEP SLOTTED

METAL DEFLECTION

TRACK FASTENED TO

DECK @ 2'-0" O.C.

CEILING - SEE ROOM

FINISH SCHEDULE

METAL STUDS @ 16" O.C.

CONTINUOUS ACOUSTIC

SEALANT EACH SIDE METAL RUNNER CHANNEL

SECURE TO FLOOR

SOUND ATTENUATION

BATT INSULATION

IMPACT RESISTANT

GYPSUM BOARD

NOTE: EXTEND GYPSUM

BOARD AND FINISHES TO

UNDERSIDE OF DECK (DO

NOT SECURE GYP. BD TO

TRACK)

UNDERSIDE OF DECK ABOVE

PARTITION TYPE 'S1S'

(NON-RATED / 4" METAL STUDS / INSULATED - SMOKE PARTITION)

WALL BASE

METAL STUD @ CEILING

2 1/2" DEEP SLOTTED METAL

DEFLECTION TRACK FASTENED

TO DECK @ 2'-0" O.C.

CEILING - SEE ROOM

FINISH SCHEDULE

METAL STUDS @ 16" O.C.

CONTINUOUS ACOUSTIC

SEALANT EACH SIDE METAL RUNNER CHANNEL

SECURE TO FLOOR

SOUND ATTENUATION

BATT INSULATION

IMPACT RESISTANT

GYPSUM BOARD

UNDERSIDE OF

DECK ABOVE

PARTITION TYPE 'S1'

(NON-RATED / 4" METAL STUDS / INSULATED)

PARTITION TYPE 'S2'

(NON-RATED / 4" METAL STUDS / NON-INSULATED / GYP. BD.

ONE SIDE ONLY )

WALL BASE

T Y

P

6"METAL STUD @ CEILING

PARTITION TYPE 'S3'

(NON-RATED / 6" METAL STUDS / INSULATED)

CONTINUOUS ACOUSTIC

SEALANT EACH SIDE

2 1/2" DEEP SLOTTED

METAL DEFLECTION

TRACK FASTENED TO

DECK @ 2'-0" O.C.

CEILING - SEE ROOM

FINISH SCHEDULE

METAL STUDS @ 16" O.C.

CONTINUOUS ACOUSTIC

SEALANT EACH SIDE METAL RUNNER CHANNEL

SECURE TO FLOOR

SOUND ATTENUATION

BATT INSULATION, ONE

SIDE ONLY

IMPACT RESISTANT

GYPSUM BOARD

NOTE: EXTEND GYPSUM

BOARD AND FINISHES TO

UNDERSIDE OF DECK (DO

NOT SECURE GYP. BD TO

TRACK)

UNDERSIDE OF DECK ABOVE

PARTITION TYPE 'D1S'

(NON-RATED / 4" METAL STUDS / INSULATED - SMOKE PARTITION)

WALL BASE

PARTITION TYPE 'D2S'

(NON-RATED / 2 1/2" METAL STUDS / INSULATED - SMOKE PARTITION)

METAL STUD @ CEILING

SEE PLAN

VARIES

2 1/2" DEEP SLOTTED

METAL DEFLECTION

TRACK FASTENED TO

DECK @ 2'-0" O.C.

CEILING - SEE ROOM

FINISH SCHEDULE

METAL STUDS @ 16" O.C.

CONTINUOUS ACOUSTIC

SEALANT EACH SIDE METAL RUNNER CHANNEL

SECURE TO FLOOR

SOUND ATTENUATION

BATT INSULATION, ONE

SIDE ONLY

IMPACT RESISTANT

GYPSUM BOARD

NOTE: EXTEND GYPSUM

BOARD AND FINISHES TO

UNDERSIDE OF DECK (DO

NOT SECURE GYP. BD TO

TRACK)

UNDERSIDE OF DECK ABOVE

PARTITION TYPE 'D1'

(NON-RATED / 4" METAL STUDS / INSULATED - SMOKE PARTITION)

WALL BASE

PARTITION TYPE 'D2'

(NON-RATED / 2 1/2" METAL STUDS / INSULATED - SMOKE PARTITION)

METAL STUD @ CEILING

T Y

P

6"

SEE PLAN

VARIES

PARTITION TYPE 'X1'

(EXISTING EXTERIOR WALL CONSTRUCTION / GYP. BD. / INSULATED)

CONTINUOUS ACOUSTIC

SEALANT

WALL BASE

IMPACT RESISTANT GYPSUM

BOARD

CEILING - SEE ROOM

FINISH SCHEDULE

EXISTING 8" METAL STUDS

TO REMAIN

EXISTING EXTERIOR WALL

CONSTRUCTION, EIFS OR

BRICK VENEER

EXISTING DEFLECTION TRACK

TO REMAIN

UNDERSIDE OF DECK

THERMAL INSULATION, MIN. R-13

TYPICAL TEMPORARY CONSTRUCTION

PARTITION

UNDERSIDE OF EXISTING

DECK

1 HR RATED TEMPORARY

PARTITION. HI-IMPACT 5/8" GYP.

BOARD ON 3 5/8" METAL STUDS.

FINISH OCCUPIED SIDE PER

ROOM FINISH SCHEDULE

PLASTER TAPE ALL GYP. BD.

JOINTS. SECURE ALL TAPE

WITH RAM-TACK HIGH TACK

SPRAY OR EQUAL.

OCCUPIED SIDERENOVATION SIDE

2 1/2" DEEP SLOTTED

METAL DEFLECTION

TRACK FASTENED TO

DECK @ 2'-0" O.C.

COMPRESSIBLE

INSULATION

SEAL PERIMETER

COMPRESSIBLE

INSULATION

SEAL PERIMETER

MECHANICALLY FASTEN

BOTTOM TRACK TO FLOOR

PARTITION TYPE GENERAL NOTES

1. PROVIDE 5/8" TYPE 'X' IMPACT RESISTANT GYPSUM BOARD UNLESS NOTED

OTHERWISE

2. PROVIDE HI-IMPACT CEMENT BACKERBOARD AT ALL SHOWER WALLS, TYP.

3. PROVIDE GLASS MAT WATER RESISTANT BACKER BOARD AT ALL WALLS WITH

TILE FINISH, EXCEPT SHOWER WALLS, TYP.

4. IF NOT SHOWN ON DRAWINGS, PROVIDE CONTROL JOINTS IN GYPSUM BOARD

ASSEMBLIES AS DESCRIBED IN ASTM C 840-08 OR GA-216-2013.

architecture · engineering

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERS · SURVEYORS · CONSULTANTS ·

LANDSCAPE ARCHITECTS · LAND PLANNERS

298 VETERANS DRIVE

FOWLERVILLE,

MICHIGAN 48836

(OFFICE) 517-223-3512

(FAX) 517-223-9987

211 E. Water Street, Suite 213L

Kalamazoo, MI 49007 269.216.0222

VA STATION

Battle Creek VA Medical Center

5500 Armstrong Road

Battle Creek, MI 49037

Defining

EXCELLENCE

in the 21st Century

HEALTH

CARE

C :\R ev it\

\1

4_

A _m ic he lle .b ur ri.

rv t

5/

/2

:2 5:

A

M

39-A002

PARTITION TYPES RENOVATE B39-2 WEST

FOR PATIENT PRIVACY

BATTLE CREEK, MI

515-20-102

05/20/2021 KJH MRB/MMN

100% BID DOCUMENTS190134

Revisions: Date:

65% DESIGN DEVELOPMENT 03/06/2020

RESUBMIT WITH OWNER CHANGES 10/02/2020

UP DN DN

UP

DEMO PLAN LEGEND:

EXISTING WALL OR

PARTITION TO REMAIN

EXISTING DOOR TO

REMAIN

EXISTING BUILDING

COMPONENT &

STRUCTURE TO REMAIN

EXISTING WALL/PARTITION

OR EXISTING ITEMS TO BE

REMOVED

EXISTING DOOR & FRAME TO

BE REMOVED

EXISTING ASSEMBLY TO BE

REMOVED

NOTE: ALL ITEMS SHOWN IN

RED AND DASHED ARE TO BE

DEMOLISHED - U.N.O.

GENERAL DEMOLITION NOTES:

1. ALL EXISTING ITEMS TO BE RETAINED BY THE OWNER WILL BE REMOVED PRIOR TO

DEMOLITION. ANY ITEMS LEFT IN THE DEMOLITION AREA BECOME THE PROPERTY OF THE

DEMOLITION SUBCONTRACTOR.

2. REFER TO ALL CONTRACT DOCUMENTS FOR ADDITIONAL DEMOLITION NOTES AND

INFORMATION.

3. SHORE AND BRACE ALL WORK REQUIRED TO REMAIN.

4. CONTRACTOR AND SUBCONTRACTORS SHALL VISIT THE SITE PRIOR TO SUBMITTING A BID TO

BECOME FAMILIAR WITH EXISTING CONDITIONS

5. CONTRACTOR AND DEMOLITION SUBCONTRACTOR TO COORDINATE DEMOLITION WORK WITH

OWNER PRIOR TO START OF WORK.

6. PATCH/REPAIR/REPLACE ALL MATERIALS AFFECTED BY RENOVATION TO MATCH ORIGINAL

EXISTING MATERIAL, FINISH, COLOR, ETC., U.N.O.

7. PATCH, REPAIR, REPLACE EXISTING MATERIALS AS REQUIRED TO RECEIVE NEW FINISHES.

8. U.N.O. PATCH AND PREPARE FLOOR W/CONCRETE (OR FLORSTONE) FLUSH WITH ADJACENT

FLOOR SURFACE. FILL ANY SLOPING OR RECESSED AREAS LEVEL TO TYPICAL FINISH FLOOR

ELEVATION TO ACCOMMODATE NEW FLOOR COVERINGS.

3.7

KA B C D E G H IA.5 A.9 E.3 E.7 J.1 J.5

2.1

1.7

1.8

0 .8

F

DAY ROOM

B118

MEDS

B120

STORAGE

B132

ELEVATOR

TREATMENT

B106

OFFICE

B108

OFFICE

B110

OFFICE

B112

GROUP ROOM

B114

OFFICE

B107

OFFICE

B109

STAFF OFFICE

B111

NURSE

STATION

B113

PRIVATE

B130

PRIVATE

B128

SEMI

B125

SEMI

B127

S. TOILET

B121

RESTRAINT

B122

ISOL.

B126

ANTE ROOM

B124

NOURISH

B141

PRIVATE

B143

PRIVATE

B145

PRIVATE

B149

PRIVATE

B147

SEMI

B142SEMI

B144

SEMI

B146

HSK

B140

LAUNDRY

B134

STORAGE

B151

STAIR

LAUNDRY

B153

SOILED LINEN

B102

STAFF LOCKER

RM / LOUNGE

B101

CLEAN LINEN

B105

HSK EQUIP.

B104

BATHROOM

B146A

BATHROOM

B144A

BATHROOM

B142A

BATHROOM

B123A

BATHROOM

B125A

BATHROOM

B127A

BATHROOM

B128A

BATHROOM

B130A

BATHROOM

B124A

BATHROOM

B149A

BATHROOM

B147A

BATHROOM

B145A

BATHROOM

B143A

CORRIDOR

BC-12

STAIR

ELECTRICAL

B155

ELECTRICAL

B136

CORRIDOR

BC-11

CORRIDOR

C-20CORRIDOR

C-21

CORRIDOR

BC-13

GROUP ROOM

141A

GROUP ROOM

105A

SEMI

B123

STORAGE

B113A

STORAGE

B118A

CORRIDOR

BC-15.2

CORRIDOR

BC-14

CORRIDOR

BC-16

CORRIDOR

BC-17.2

DAY ROOM

NOURISHMENT

105E

MED ROOM

107A

STAFF

NURSE

STATION

C14A

CLEAN UTILITY

104B

LAUNDRY

104A

NURSING 2

BED

NURSING 2

BED

103A

NURSING 2

BED FEMALE

TREATMENT

NURSING 2

BED

EXIT

VESTIBULE

C11 UNIT

CORR./CHARGE

NURSE

AMM/SPD

ST…