Drawing_and_Plan.pdf

PDF 6 MB Posted

Attached to
Construction, CCADF Sprinkler Heads Replacement
Solicitation number
2026-389
Issued by
Collin County, Texas

About this file

This document consists of architectural drawings and plans for the Collin County Adult Detention Facility (CCADF) sprinkler head replacement project in McKinney, Texas, prepared by a registered engineering firm and issued by Collin County. The drawings depict fire protection systems across multiple clusters (Clusters 1, 3, 4, and 5) and levels within the detention facility, showing the locations of existing sprinkler heads to be replaced with new tamper-resistant institutional sprinkler heads. The project involves removing existing sprinkler heads and installing new Tyco Raven tamper-resistant horizontal or pendant sprinkler heads that will be mounted tightly against walls to prevent tampering while meeting all applicable fire codes. The contractor must complete one pod or cluster before proceeding to the next and is responsible for modifying pipe armovers as needed at no additional cost to the owner, based on an allowance of 500 feet of armover piping included in the bid. The contractor must visit the site prior to starting work to identify any concerns in writing, notify the owner and fire department 48 hours before making connections to the existing fire system, and ensure the fire protection design and nomenclature match existing Collin County facility standards. All work must comply with NFPA 13 requirements, and the contractor must make the system ready at the end of each work day.

The opinion of probable construction cost for this replacement project is $150,000, with work to commence within ten consecutive calendar days after issuance of Notice to Proceed and liquidated damages of $500 per calendar day applying for failure to meet the completion deadline. Bid security of 5 percent of the total bid amount is required prior to bid opening, and upon award, the contractor must furnish a performance bond and payment bond each equal to 100 percent of the contract price plus a one-year maintenance bond of 10 percent of contract price. Insurance requirements include workers' compensation at statutory limits with employer's liability of not less than $1 million, commercial general liability with minimum $2 million general aggregate and per-occurrence limits, automobile liability of $1 million combined limit, and umbrella liability of $2 million per occurrence and aggregate. Collin County is exempt from state sales tax and federal excise tax, and prevailing wage requirements under Texas Government Code Title 10, Chapter 2258 apply. E-Verify employment eligibility verification compliance is mandated.

View the file

Other files

Show all 14

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

INDEX OF DRAWINGS

B I D D O C U M E N T S

TRUE NORTH

COLLIN COUNTY

PROJECT

LOCATION

Texas Registered Firm No. F-7489 1255 West 15th Street, Suite 300 Plano, TX 75075 469.467.0200 Email: mdengca@md-eng.com Project Number: 251786

ADULT DETENTION FACILITY

MCKINNEY, TEXAS

950 W Be t ha ny D r . , Su i te 37 0 Allen, TX 75013 469.443.7200

OUTDOOR

RECREATION

ELEC.

ROOM

CELLCELLCELLCELLCELLCELLCELL

CELL

CELL

CELL

CELL

DAYROOM

DAYROOM

CONTROL

CELL CELL CELL CELL CELL CELL

CELL

CELL

CELL

CELL

CELL

CELL

CELLCELLCELL

CELL

CELL

CELL

C O

RR

ID

O R

CELL

CELL

CELL

CELL

CELL

CELL

CELLCELLCELLCELLCELLCELLCELLCELL

CELL

CELL

CELL

CELL

CELL

CELL

CELL

CELL

CELL CELL CELL CELL

CELL

CELL

CELL

CELL

CELL CELL CELL CELL CELL CELL

CELL

CELL

CELL

CELL

CELL

CELL

CELLCELLCELL

CELL

CELL

CELL

CELL CELL

CELLCELL

CELL

CELL

CELL

CELL

CELL

CELL

CELL

CELL CELL

DN CHASE

DAYROOM

CHASE

OUTDOOR

DN

ROOM

ELEC.

CHASE

MEDICAL

JAN.

STOR.

CHASE

ELEC.

ROOM

CHASE

ELEC.

ROOM

CHASE

DESK

DAYROOM

DN

UP

STAFF

TOILET

CHASE

DN

DESK

DAYROOM

DN

CORRIDOR

STAFF

TOILET

SA

FE

TY

VE

ST

SA

FE

TY

VE

ST

SAFETY

VEST.

SAFETY

VEST.

CLUSTER

TRAP

CHASE

BARBER

MULTI-PURPOSE

VISIT

VISIT

VEST.

VISIT

SAFETY

VISIT

DF

DN

CELL

H.C.

H.C. H.C.

H.C.

CELL

CHASE

CORR

CELL

H.C.

VEST

VEST.

RECREATION

DN DN

OUTDOOR

RECREATION

OUTDOOR

RECREATION

DN

STAFF

TOILET

CHASE

DNCHASE DN CHASE

STAFF

TOILET

CLUSTER

CONTROL

CONT.

ATT.

VISIT

DN

DN

ELEC.

CHASE

DAYROOM

DAYROOM

N.I.C.

1. CONTRACTOR TO REMOVE EXISTING SPRINKLER HEADS AND

REPLACE WITH NEW INSTITUTIONAL HORIZONTAL/PENDANT

TAMPER RESISTANT SPRINKLER HEAD. NEW HEAD SHALL BE

INSTALLED TIGHT AGAINST WALL TO PREVENT TAMPERING AND

MEET ALL APPLICABLE CODES. CONTRACTOR SHALL MAKE SYSTEM

READY AFTER EACH WORK DAY AND IS TO COMPLETE ONE POD

BEFORE MOVING TO THE NEXT ONE. IF THE CONTRACTOR PLANS TO

WORK IN MULTIPLE PODS EACH POD SHALL BE COMPLETED BEFORE

MOVING TO ANOTHER POD. IF PIPE ARMOVER TO SPRINKLER HEAD

IS REQUIRED TO BE MODIFIED CONTRACTOR SHALL BE

RESPONSIBLE FOR MODIFICATION OF ARMOVER LENGTH WITHOUT

ADDITIONAL COST TO OWNER (BASED ON 500' OF ARMOVE PIPING)

ALLOWANCE IN BID DOCUMENT. PIPE THREADER WILL BE ALLOWED

TO REMAIN IN ADJACENT EXERCISE YARDS OF EACH POD DURING

THE DAY AND STORED WHEN CONTRACTOR IS NOT WORKING IN

THE POD.

2. THE CONTRACTOR SHALL VISIT THE SITE, AND IDENTIFY ANY

CONCERNS IN WRITING PRIOR TO STARTING WORK.

3. THE OWNER AND FIRE DEPARTMENT SHALL BE NOTIFIED 48 HOURS

PRIOR TO ANY CONNECTIONS TO THE EXISTING FIRE SYSTEM.

4. FIRE PROTECTION DESIGN AND NOMENCLATURE SHALL MATCH

EXISTING COLLIN COUNTY FACILITY STANDARDS.

REPLACE EXISTING SPRINKLER HEAD WITH NEW TAMPER RESISTANT

SPRINKLER HEAD.

GENERAL NOTES

LEGEND

OUTDOOR

RECREATION

ELEC.

ROOM

CELLCELLCELLCELLCELLCELLCELL

CELL

CELL

CELL

CELL

DAYROOM

DAYROOM

CONTROL

CELL CELL CELL CELL CELL CELL

CELL

CELL

CELL

CELL

CELL

CELL

CELLCELLCELL

CELL

CELL

CELL

C O

RR

ID

O R

CELL

CELL

CELL

CELL

CELL

CELL

CELLCELLCELLCELLCELLCELLCELLCELL

CELL

CELL

CELL

CELL

CELL

CELL

CELL

CELL

CELL CELL CELL CELL

CELL

CELL

CELL

CELL

CELL CELL CELL CELL CELL CELL

CELL

CELL

CELL

CELL

CELL

CELL

CELLCELLCELL

CELL

CELL

CELL

CELL CELL

CELLCELL

CELL

CELL

CELL

CELL

CELL

CELL

CELL

CELL CELL

DN CHASE

DAYROOM

CHASE

OUTDOOR

DN

ROOM

ELEC.

CHASE

MEDICAL

JAN.

STOR.

CHASE

ELEC.

ROOM

CHASE

ELEC.

ROOM

CHASE

DESK

DAYROOM

DN

UP

STAFF

TOILET

CHASE

DN

DESK

DAYROOM

DN

CORRIDOR

STAFF

TOILET

SA

FE

TY

VE

ST

SA

FE

TY

VE

ST

SAFETY

VEST.

SAFETY

VEST.

CLUSTER

TRAP

CHASE

BARBER

MULTI-PURPOSE

VISIT

VISIT

VEST.

VISIT

SAFETY

VISIT

DF

DN

CELL

H.C.

H.C. H.C.

H.C.

CELL

CHASE

CORR

CELL

H.C.

VEST

VEST.

RECREATION

DN DN

OUTDOOR

RECREATION

OUTDOOR

RECREATION

DN

STAFF

TOILET

CHASE

DNCHASE DN CHASE

STAFF

TOILET

CLUSTER

CONTROL

CONT.

ATT.

VISIT

DN

DN

ELEC.

CHASE

DAYROOM

DAYROOM

N.I.C.

CLUSTER 1 LEVEL 1 PLAN - FIRE PROTECTION01 SCALE: 1/16"=1'-0"

A B C D E

NORTH

Project No.

251786

Sheet No.

Re vi si o ns

C O

LL

IN

C O

U N

TY

A D

U

LT

D

ET

EN

TI

O N

F A C

IL

IT

Y

C

O M

M U

N

IT

Y A V E, M C

K

IN

N

EY

, T X

Te xa s Re g is te re d F irm N o

F

-7

W e st th S tr e e t, S u ite

Pl a no , T

X

.4

.0

Em a il:

m d e ng c a m d -e ng .c o m

Pr o je c t N um b e r:

W

B e th a n y

D r.

Su it e

Al le n, T X

.4

.7

FP1.1

CLUSTER 1 - FIRE

PROTECTION

CLUSTER 1 LEVEL 2 PLAN - FIRE PROTECTION02 SCALE: 1/16"=1'-0"

TYPICAL SPRINKLER HEAD ON CHASE03 SCALE: NTS

TYPICAL SPRINKLER HEAD ON CHASE - CLOSE UP04 SCALE: NTS

7/15/2026

OUTDOOR

RECREATION

ELEC.

ROOM

CELLCELLCELLCELLCELLCELLCELL

CELL

CELL

CELL

CELL

DAYROOM

DAYROOM

UP

CONTROL

CELL CELL CELL CELL CELL CELL

CELL

CELL

CELL

CELL

CELL

CELL

CELLCELLCELL

CELL

CELL

CELL

C O

RR

ID

O R

CELL

CELL

CELL

CELL

CELL

CELL

CELLCELLCELLCELLCELLCELLCELLCELL

CELL

CELL

CELL

CELL

CELL

CELL

CELL

CELL

CELL CELL CELL CELL

CELL

CELL

CELL

CELL

CELL CELL CELL CELL CELL CELL

CELL

CELL

CELL

CELL

CELL

CELL

CELLCELLCELL

CELL

CELL

CELL

CELL CELL

CELLCELL

CELL

CELL

CELL

CELL

CELL

CELL

CELL

CELL CELL

DN CHASE

UP

DAYROOM

CHASE

OUTDOOR

DN

ROOM

ELEC.

CHASE

MEDICAL

JAN.

STOR.

CHASE

ELEC.

ROOM

CHASE

ELEC.

ROOM

CHASE

DESK

DAYROOM

DN

UP

STAFF

TOILET

CHASE

DN

DESK

DAYROOM

DN

CORRIDOR

STAFF

TOILET

SA

FE

TY

VE

ST

SA

FE

TY

VE

ST

SAFETY

VEST.

SAFETY

VEST.

CLUSTER

TRAP

CHASE

BARBER

MULTI-PURPOSE

VISIT

VISIT

VEST.

VISIT

SAFETY

VISIT

DF

DN

CELL

H.C.

H.C. H.C.

H.C.

CELL

CHASE

CORR

CELL

H.C.

VEST

VEST.

RECREATION

DN DN

OUTDOOR

RECREATION

OUTDOOR

RECREATION

DN

STAFF

TOILET

CHASE

DNCHASE DN CHASE

STAFF

TOILET

CLUSTER

CONTROL

CONT.

ATT.

VISIT

DN

DN

ELEC.

CHASE

11"

DAYROOM

DAYROOM

UP

DAYROOM

N.I.C.

REPLACE EXISTING SPRINKLER HEAD WITH NEW TAMPER RESISTANT

SPRINKLER HEAD.

GENERAL NOTES

LEGEND

1. CONTRACTOR TO REMOVE EXISTING SPRINKLER HEADS AND

REPLACE WITH NEW INSTITUTIONAL HORIZONTAL/PENDANT

TAMPER RESISTANT SPRINKLER HEAD. NEW HEAD SHALL BE

INSTALLED TIGHT AGAINST WALL TO PREVENT TAMPERING AND

MEET ALL APPLICABLE CODES. CONTRACTOR SHALL MAKE SYSTEM

READY AFTER EACH WORK DAY AND IS TO COMPLETE ONE POD

BEFORE MOVING TO THE NEXT ONE. IF THE CONTRACTOR PLANS TO

WORK IN MULTIPLE PODS EACH POD SHALL BE COMPLETED BEFORE

MOVING TO ANOTHER POD. IF PIPE ARMOVER TO SPRINKLER HEAD

IS REQUIRED TO BE MODIFIED CONTRACTOR SHALL BE

RESPONSIBLE FOR MODIFICATION OF ARMOVER LENGTH WITHOUT

ADDITIONAL COST TO OWNER (BASED ON 500' OF ARMOVE PIPING)

ALLOWANCE IN BID DOCUMENT. PIPE THREADER WILL BE ALLOWED

TO REMAIN IN ADJACENT EXERCISE YARDS OF EACH POD DURING

THE DAY AND STORED WHEN CONTRACTOR IS NOT WORKING IN

THE POD.

2. THE CONTRACTOR SHALL VISIT THE SITE, AND IDENTIFY ANY

CONCERNS IN WRITING PRIOR TO STARTING WORK.

3. THE OWNER AND FIRE DEPARTMENT SHALL BE NOTIFIED 48 HOURS

PRIOR TO ANY CONNECTIONS TO THE EXISTING FIRE SYSTEM.

4. FIRE PROTECTION DESIGN AND NOMENCLATURE SHALL MATCH

EXISTING COLLIN COUNTY FACILITY STANDARDS.

OUTDOOR

RECREATION

ELEC.

ROOM

CELLCELLCELLCELLCELLCELLCELL

CELL

CELL

CELL

CELL

DAYROOM

DAYROOM

UP

CONTROL

CELL CELL CELL CELL CELL CELL

CELL

CELL

CELL

CELL

CELL

CELL

CELLCELLCELL

CELL

CELL

CELL

C O

RR

ID

O R

CELL

CELL

CELL

CELL

CELL

CELL

CELLCELLCELLCELLCELLCELLCELLCELL

CELL

CELL

CELL

CELL

CELL

CELL

CELL

CELL

CELL CELL CELL CELL

CELL

CELL

CELL

CELL

CELL CELL CELL CELL CELL CELL

CELL

CELL

CELL

CELL

CELL

CELL

CELLCELLCELL

CELL

CELL

CELL

CELL CELL

CELLCELL

CELL

CELL

CELL

CELL

CELL

CELL

CELL

CELL CELL

DN CHASE

UP

DAYROOM

CHASE

OUTDOOR

DN

ROOM

ELEC.

CHASE

MEDICAL

JAN.

STOR.

CHASE

ELEC.

ROOM

CHASE

ELEC.

ROOM

CHASE

DESK

DAYROOM

DN

UP

STAFF

TOILET

CHASE

DN

DESK

DAYROOM

DN

CORRIDOR

STAFF

TOILET

SA

FE

TY

VE

ST

SA

FE

TY

VE

ST

SAFETY

VEST.

SAFETY

VEST.

CLUSTER

TRAP

CHASE

BARBER

MULTI-PURPOSE

VISIT

VISIT

VEST.

VISIT

SAFETY

VISIT

DF

DN

CELL

H.C.

H.C. H.C.

H.C.

CELL

CHASE

CORR

CELL

H.C.

VEST

VEST.

RECREATION

DN DN

OUTDOOR

RECREATION

OUTDOOR

RECREATION

DN

STAFF

TOILET

CHASE

DNCHASE DN CHASE

STAFF

TOILET

CLUSTER

CONTROL

CONT.

ATT.

VISIT

DN

DN

ELEC.

CHASE

11"

DAYROOM

DAYROOM

UP

DAYROOM

N.I.C.

CLUSTER 3 LEVEL 1 FLOOR PLAN - FIRE PROTECTION01 SCALE: 1/16"=1'-0"

A B C D E

NORTH

Project No.

251786

Sheet No.

Re vi si o ns

C O

LL

IN

C O

U N

TY

A D

U

LT

D

ET

EN

TI

O N

F A C

IL

IT

Y

C

O M

M U

N

IT

Y A V E, M C

K

IN

N

EY

, T X

Te xa s Re g is te re d F irm N

W e st th S tr e e t, S u ite

Pl a no , T

X

.4

.0

Em e ng c a m d -e ng .c o m

Pr o je c t N um b e r:

W

B e th a n y

D r.

S u it e

Al le n, T

X

.4

.7

FP1.3

CLUSTER 3 PLAN

- FIRE

PROTECTION

CLUSTER 3 LEVEL 2 FLOOR PLAN - FIRE PROTECTION02 SCALE: 1/16"=1'-0"

TYPICAL SPRINKLER HEAD ON CHASE03 SCALE: NTS

TYPICAL SPRINKLER HEAD ON CHASE - CLOSE UP04 SCALE: NTS

zone #5 zone #1 zone #1 zone #6 zone #4

FHR

FHR

FHR

FHR

zone #2

N.I.C.

REPLACE EXISTING SPRINKLER HEAD WITH NEW TAMPER RESISTANT

SPRINKLER HEAD.

GENERAL NOTES

LEGEND

1. CONTRACTOR TO REMOVE EXISTING SPRINKLER HEADS AND

REPLACE WITH NEW INSTITUTIONAL HORIZONTAL/PENDANT

TAMPER RESISTANT SPRINKLER HEAD. NEW HEAD SHALL BE

INSTALLED TIGHT AGAINST WALL TO PREVENT TAMPERING AND

MEET ALL APPLICABLE CODES. CONTRACTOR SHALL MAKE SYSTEM

READY AFTER EACH WORK DAY AND IS TO COMPLETE ONE POD

BEFORE MOVING TO THE NEXT ONE. IF THE CONTRACTOR PLANS TO

WORK IN MULTIPLE PODS EACH POD SHALL BE COMPLETED BEFORE

MOVING TO ANOTHER POD. IF PIPE ARMOVER TO SPRINKLER HEAD

IS REQUIRED TO BE MODIFIED CONTRACTOR SHALL BE

RESPONSIBLE FOR MODIFICATION OF ARMOVER LENGTH WITHOUT

ADDITIONAL COST TO OWNER (BASED ON 500' OF ARMOVE PIPING)

ALLOWANCE IN BID DOCUMENT. PIPE THREADER WILL BE ALLOWED

TO REMAIN IN ADJACENT EXERCISE YARDS OF EACH POD DURING

THE DAY AND STORED WHEN CONTRACTOR IS NOT WORKING IN

THE POD.

2. THE CONTRACTOR SHALL VISIT THE SITE, AND IDENTIFY ANY

CONCERNS IN WRITING PRIOR TO STARTING WORK.

3. THE OWNER AND FIRE DEPARTMENT SHALL BE NOTIFIED 48 HOURS

PRIOR TO ANY CONNECTIONS TO THE EXISTING FIRE SYSTEM.

4. FIRE PROTECTION DESIGN AND NOMENCLATURE SHALL MATCH

EXISTING COLLIN COUNTY FACILITY STANDARDS.

zone #5 zone #1 zone #1 zone #6 zone #4

FHR

FHR

FHR

FHR

zone #2

N.I.C.

CLUSTER 4 LEVEL 1 PLAN - FIRE PROTECTION01 SCALE: 1/16"=1'-0"

A B C D E

NORTH

Project No.

251786

Sheet No.

Re vi si o ns

C O

LL

IN

C O

U N

TY

A D

U

LT

D

ET

EN

TI

O N

F A C

IL

IT

Y

C

O M

M U

N

IT

Y A V E, M C

K

IN

N

EY

, T X

Te xa s Re g is te re d F irm N

W e st th S tr e e t, S u ite

Pl a no , T

X

.4

.0

Em e ng c a m d -e ng .c o m

Pr o je c t N um b e r:

W

B e th a n y

D r.

S u it e

Al le n, T

X

.4

.7

FP1.4

CLUSTER 4 PLAN

- FIRE

PROTECTION

CLUSTER 4 LEVEL 2 PLAN - FIRE PROTECTION02 SCALE: 1/16"=1'-0"

TYPICAL SPRINKLER HEAD ON CHASE03 SCALE: NTS

TYPICAL SPRINKLER HEAD ON FURR DOWN IN DORM AREA04 SCALE: NTS

zone #5 zone #1 zone #1 zone #6 zone #4

FHR

FHR

FHR

FHR

zone #2

N.I.C.

REPLACE EXISTING SPRINKLER HEAD WITH NEW TAMPER RESISTANT

SPRINKLER HEAD.

GENERAL NOTES

LEGEND

1. CONTRACTOR TO REMOVE EXISTING SPRINKLER HEADS AND

REPLACE WITH NEW INSTITUTIONAL HORIZONTAL/PENDANT

TAMPER RESISTANT SPRINKLER HEAD. NEW HEAD SHALL BE

INSTALLED TIGHT AGAINST WALL TO PREVENT TAMPERING AND

MEET ALL APPLICABLE CODES. CONTRACTOR SHALL MAKE SYSTEM

READY AFTER EACH WORK DAY AND IS TO COMPLETE ONE POD

BEFORE MOVING TO THE NEXT ONE. IF THE CONTRACTOR PLANS TO

WORK IN MULTIPLE PODS EACH POD SHALL BE COMPLETED BEFORE

MOVING TO ANOTHER POD. IF PIPE ARMOVER TO SPRINKLER HEAD

IS REQUIRED TO BE MODIFIED CONTRACTOR SHALL BE

RESPONSIBLE FOR MODIFICATION OF ARMOVER LENGTH WITHOUT

ADDITIONAL COST TO OWNER (BASED ON 500' OF ARMOVE PIPING)

ALLOWANCE IN BID DOCUMENT. PIPE THREADER WILL BE ALLOWED

TO REMAIN IN ADJACENT EXERCISE YARDS OF EACH POD DURING

THE DAY AND STORED WHEN CONTRACTOR IS NOT WORKING IN

THE POD.

2. THE CONTRACTOR SHALL VISIT THE SITE, AND IDENTIFY ANY

CONCERNS IN WRITING PRIOR TO STARTING WORK.

3. THE OWNER AND FIRE DEPARTMENT SHALL BE NOTIFIED 48 HOURS

PRIOR TO ANY CONNECTIONS TO THE EXISTING FIRE SYSTEM.

4. FIRE PROTECTION DESIGN AND NOMENCLATURE SHALL MATCH

EXISTING COLLIN COUNTY FACILITY STANDARDS.

zone #5 zone #1 zone #1 zone #6 zone #4

FHR

FHR

FHR

FHR

zone #2

N.I.C.

CLUSTER 5 LEVEL 1 FLOOR PLAN - FIRE PROTECTION01 SCALE: 1/16"=1'-0"

A B C D E

NORTH

Project No.

251786

Sheet No.

Re vi si o ns

C O

LL

IN

C O

U N

TY

A D

U

LT

D

ET

EN

TI

O N

F A C

IL

IT

Y

C

O M

M U

N

IT

Y A V E, M C

K

IN

N

EY

, T X

Te xa s Re g is te re d F irm N

W e st th S tr e e t, S u it e

Pl a no

, T X

.4

.0

Em e ng c a m d

-e ng

.c o m Pr o je c t N um b e r:

W

B e th a n y

D r.

S u it e

Al le n, T

X

.4

.7

FP1.5

CLUSTER 5 PLAN

- FIRE

PROTECTION

CLUSTER 5 LEVEL 2 FLOOR PLAN - FIRE PROTECTION02 SCALE: 1/16"=1'-0"

TYPICAL SPRINKLER HEAD ON LEFT SIDE OF CHASE05 SCALE: NTS

TYPICAL SPRINKLER HEAD ON FRONT OF CHASE04 SCALE: NTS

TYPICAL SPRINKLER HEAD ON RIGHT SIDE OF CHASE03 SCALE: NTS

Sheets and Views
COVER

File details come from the government source that posted it. Updated .