Facility Survey
4 MB Posted
- Solicitation number
- DOLJ11SA00003
Text of this file
Los Angeles
Job Corps Center Los Angeles, CA
Life Safety Survey Report
June 2010
Department of Labor/ Office of Job Corps
Los Angeles
Job Corps Center Los Angeles, CA
Life Safety Survey Report
June 2010
Lodi Place Building 5 Courtyard
CONTENTS
LOS ANGELES JOB CORPS CENTER
LIFE SAFETY SURVEY REPORT
INTRODUCTION
• Purpose
• Report Contents
• Vicinity Map
• Location Maps
• Existing Site Plans
• Center Statistics
A. EXECUTIVE SUMMARY
• Signifi cant Issues
• Recommendations
B. EXISTING CONDITIONS
• Background
• Ownership
• General Site Conditions
• General Building Conditions
• General Programmatic Conditions
• Facility Assessment by Building
• Health and Life Safety Issues
• Summary of Defi ciencies
C. RECOMMENDATIONS
• Signifi cant Issues
• PY09 Plan Overview
• Regional Projects
D. BUILDING DESCRIPTIONS AND DEFICIENCIES
• Photos, Floor Plans and Descriptions of Buildings
• Defi ciency Text
E. CORRESPONDENCE AND REPORTS
• Survey Brief
• Life Safety Defi ciencies Transmittal and Lists
INTRODUCTION
LOS ANGELES JOB CORPS CENTER
JUNE 2010
PURPOSE
The Program Year 2009 Los Angeles Job Corps Center Life Safety Survey was conducted the week of April 5, 2010 by a team of an architect and two engineers.
Of the eight buildings at the center, three are owned by DOL and fi ve are leased. Building 1, the largest building on center, is a leased building. Structural building evaluation reports have shown this thirteen-story 105,000 GSF structure that was constructed in 1929, cannot be seismically certi-fi ed without a major retrofi t. In compliance with Executive Order 12941, DOL is prohibited from leasing (or renewing existing leases for) any facilities not meeting Federal seismic criteria.
As a result, YWCA, the center operator, is constructing a new building under an agreement with DOL. This building will replace Building 1 and Lodi Place Building 5. The site of the new build-ing is close to existing Buildings 2, 3, 4, 12 and 16 in the downtown campus. Consequently, a full survey of these two buildings was not warranted; rather, an abbreviated survey was accomplished to document existing conditions impacting Health and Life Safety. A full survey of the three DOL-owned buildings and the remaining three leased buildings was conducted as these are expected to remain part of the center for the long term. Documentation of the two tasks consisted of:
• Identifying facility defi ciencies and the corresponding funding requirements to correct them. The goal is to keep the center operating in safe conditions that meet present Life Safety and Building Code standards during an interim occupancy until a suitable replace-ment facility is found.
• Documenting and/or verifying the general conditions and space utilization of leased build-ings and sites.
• Documenting and/or verifying the physical features, detailed building conditions, and space utilization of DOL-owned buildings and sites and leased buildings to remain in use for the center.
REPORT CONTENTS
The survey information contains a summary of data collected and verifi ed during the facility sur-vey, analyzes portions of that data, and then recommends corrective action articulated in a short term plan. It also includes a narrative which outlines the funded health and life safety issues as well as other major non-funded signifi cant issues. Current center information is also provided as well as some background data and general existing conditions.
Center Statistics Date: 07/01/2010
Combination of Owned & Leased 1965Activation Date:
Ownership Status:
Site & Utilities
Water Source:
Sanitary Sewer:
Electrical Service:
Gas Type:
Telephone Service:
Public Water Authority
Municipal
City of LA Dept of Water & Power
Natural
AT&T
No. of Vacant Buildings:
Gross Sq. Footage:
Net Sq. Footage:
Net / Gross (%):
Building Age > 50 yrs:
Building Age 20-50yrs:
Building Age 10-20yrs:
Building Age < 10 yrs:
252,743
Bldgs with Asbestos:
Asbestos Survey Date:
Bldgs with Radon:
11/26/1990
Site Access: Yes
3Buildings with Access:
Regulated:
Non-Regulated:
Above Ground Tanks:
Sewage Treatment:
Publicly Owned Treatment Works
Air Pollution Sources: None
Ruby Brown
(213)748-0135Phone No.:
Center Director:
YWCA Of Greater Los AngelesOperating Contractor:
Contract Strength: Resident Men: Resident Women: Non-residents:
Business Office Technologies 180 Non-Technical Trades (Off-Ctr) 94 Health Occupations 60 TCU Transportation 50 Building & Apt. Maint. 48 Technical Trades (Off-Ctr) 44
No. Of Buildings:
735 148 232 355
Real Estate Management
Buildings
Program
JCC# 901 LOS ANGELES 1031 Hill St., Los Angeles, CA 90015
Accessibility
Environmental
Site Area (Acres):
Bldg to Site Coverage:
8.33
18%
0Building Age Unknown :
(213)741-5309Fax No.:
Under Ground Tanks: 0
Vacant (NSF):
Energy Actual - BTU/GSF/YR: 79,363
Energy Audit Done: Deferred (planned relocation)
1,000
64%
162,456
Buildings with Access to Services: 2
5Buildings with Accessible Restrooms:
Buildings with Other Accessible Features: 2
1Buildings in Total Compliance:
230,543
GSF
16,300 6 5,900 2
Average Building Age: 77
Vocations (476):
Radon Surveys Reqd: 2
Age Distribution
Mitigated: 0
A Executive Summary
LAJCC Downtown campus and surroundings
Buildings 2 (right) and 3 from above
Buildings 12 (right) and 16
Historic Building 5
The Los Angeles Job Corps Center was activated in 1965 and currently has 735 students consist-ing of 380 resident students and 355 nonresident students. The center consists of eight buildings on fi ve acres at three separate sites. The center is currently operated by the YWCA of Greater Los Angeles. Of the eight buildings, DOL owns Buildings 2, 3, and 4 representing 64,350 gross square feet (GSF) of the total 252,743 GSF.
A summary of defi ciencies identifi ed or validated this survey is stated below.
CURRENT SURVEY PY 09
Defi ciency Type Number of Defi ciencies Funded Amount or Amount Estimated
Funded IA/IIA 7 $15,408
O&M IA/IIA 31 $0
Lessor IA/IIA 2 $0 Unfunded NON - IA/IIA 14 $182,698
O&M NON - IA/IIA 20 $0
Lessor NON - IA/IIA 3 $0
PRIOR YEARS FUNDED NOT CORRECTED
Defi ciency Type Number of Defi ciencies Funded Amount Funded IA/IIA 5 $175,413 Funded NON- IA/IIA 5 $396,680
Subsequent to the survey, defi ciencies and projects may have been funded through the American Recovery and Reinvestment Act (ARRA) or through supplemental redirects. Where applicable, these changes are refl ected in the Defi ciency Analysis section of this report.
Signifi cant Issues
Issues Being Addressed
• Building 1, the largest building on center (a leased building), does not meet Federal seismic criteria. YWCA, the center operator, is constructing a new building to replace Buildings 1 and 5 under an agreement with DOL.
• DOL-Owned Buildings 2, 3, and 4 also require structural bracing to satisfy seismic require-ments. Exterior masonry walls of Buildings 2 and 3 are deteriorated. Funded National
EXECUTIVE SUMMARY
EXECUTIVE SUMMARY - 1
Project 2981 and funded defi ciencies will address these issues. In addition, the HVAC sys-tem and controls in Building 4 are severely deteriorated and the fi re alarm detection system needs upgrading. Funded defi ciencies will address these issues.
Issues That Need To Be Addressed
• Building 4 electrical panelboard is undersized and the conference room raised fl oor creaks and is not even.
• Electrical capacity and distribution system in Building 16 is inadequate.
• An additional classroom is needed in Building 16.
Recommended Plan
A new building under construction will replace defi cient Buildings 1 and 5. Therefore no National project is proposed.
Life safety defi ciencies will be corrected by the Region, the center, and the Lessor as identifi ed in the Correspondents and Reports section.
Building 4 electrical capacity and distribution would be improved by providing new panelboards and circuits. The sagging and creaking raised fl oor in the Center Director’s conference room would be replaced.
Building 16 electrical capacity and distribution would be improved by providing new panelboards and circuits at an estimated cost of $17,383. A classroom would be created on the fi rst fl oor at an estimated cost of $42,592.
Summary of Proposed Projects
Proposed Regional Projects
• Improve electrical circuits and panelboard in Building 4 $20,240 (Defi ciencies 78748, 78754 and 78755)
• Replace damaged raised fl oor in Building 4 $6,580 (Defi ciency 78790)
• Improve electrical circuits and panelboard in Building 16 $81,241 Defi ciencies 78751, 78752 and 78756)
• Create a classroom in Building 16 $42,592 (Defi ciency 78794)
EXECUTIVE SUMMARY - 2
B Existing Conditions
Building 4 from above
Building 3 with outdoor canopy
Building 5 historic citation
Background
The Los Angeles Job Corps Center was activated in 1965 and currently has 380 resident students and 355 nonresident students. The center consists of eight buildings on fi ve acres at three separate sites. The main site is located in downtown Los Angeles and contains six buildings (1, 2, 3, 4, 12 and 16). The second site is in Lodi Place (West Hollywood), located seven miles northwest of downtown Los Angeles, and is the location of Building 5. The third site is located in East Los An-geles, four miles southeast of the downtown Los Angeles site, and contains one building and two structures (Building 11, Structures 13, and 14). The center is operated by the YWCA of Greater Los Angeles.
The entire center currently consists of 252,743 gross square feet collectively at all three sites. The aggregate NSF is 162,456 compared to a suggested range of 140,000 to 178,000 NSF for a center with this student population.
Ownership
DOL ownership is limited to the land and buildings designated Buildings 2, 3, and 4. The remain-ing fi ve buildings are leased. Building 1 Lessor is Pan Pacifi c Ventures. The YWCA is the Lessor of Building 5. Building 11 is leased by the YWCA directly and provided for Job Corps use. The Lessor of Building 12 is Mr. Homero Mereulo. A California General Partnership is the Lessor of the Olive Center, Building 16.
General Site Conditions
Downtown Campus: All of the buildings are located on city blocks and are landlocked except for Building 3, which has a recreation area in a tent on a converted parking lot. YWCA has acquired a lot to the west of Building 4 and is constructing a new building to replace Buildings 1 and 5. There is no center-provided parking for the students. Non-resident students usually commute by public transportation.
At the downtown site, two separate parcels of DOL-owned land occupied by Buildings 2, 3 and 4 total approximately one-half acre. The parcels are in a commercial urban area that has an array of commercial building types that vary according to their age. This southern-most sub region in downtown Los Angeles is undergoing transformation that has accelerated recently. City planners view it as a mixed development, having both residential and commercial functions. At its south-west corner is the vast Los Angeles Convention Center and Staples Center complex, near the free-way intersection of state highways 10 and 110. The city envisions future development as a sports and entertainment district.
Buildings 2 and 3 form an “L” shape around two small fast food restaurants at the intersection of East 11th and South Hill Streets. Building 4 is located on Hill Street and is separated from the Building 3 property by a 98’ wide lot. There is a 6’ easement from the property line to the Build-
EXISTING CONDITIONS - 1
EXISTING CONDITIONS
ing Restriction Line on South Hill Street and a 3’ easement on 11th Street. Buildings 2 and 4 oc-cupy their available building sites while Building 3 occupies approximately half of the available building site; the other half is a tent-covered semi-outdoor space used by students for informal gathering.
Lodi Place: Building 5 is located seven miles northwest of the downtown campus. This is the only location with some open space for outdoor recreation in the form of a basketball court. The site for this court was carved out of an existing parking lot.
East Olympic Street: Building 11 is located four miles southeast of the downtown campus. Two smaller structures 13 and 14 were constructed by VST (Vocational Skills Training) behind this building. This facility has off-street parking behind the building.
General Building Conditions
Many life safety and other code defi ciencies had been corrected since an interim life safety survey of Building 1 conducted in November 2006 and the last Life Safety Survey of the total center con-ducted in February 2007. New code defi ciencies identifi ed in the April 2010 Life Safety Survey and remaining defi ciencies previously identifi ed include: inadequate fi re detection systems, inad-equate emergency lighting, expired tritium gas exit signs, inadequate illumination of egress routes and other miscellaneous life safety defi ciencies. Structural building evaluation reports have shown that Building 1 cannot be seismically certifi ed. In addition, egress is cumbersome. At Building 5, the structural condition of the balconies – some of which are part of egress routes – is suspect.
Both buildings will be replaced by a new building currently under construction.
General Programmatic Conditions
The center has generally adequate space for most functions but the building fl oor plates are inad-equately laid out. Functions located at three sites cause operational diffi culties.
The center lacks reasonable space for recreation. The center does not have a gymnasium and limited indoor facilities in Buildings 1, 5, and 16. The only outdoor facilities are a tent pavilion next to Building 3 located in the downtown campus, and a basketball court adjacent to Building 5 located seven miles from the downtown campus.
Student housing conditions are not good. The two dormitories, located in Buildings 1 and 5 suffer from inadequate egress routes, inadequate vertical circulation, deteriorated fi nishes, improperly confi gured lounge spaces, non-functional windows, and inadequate air conditioning.
Facility Assessment by Building
As this report focuses primarily on life safety issues, the assessment is organized by buildings rather than functions.
EXISTING CONDITIONS - 2
Building 1
Building 1 is a leased building that will be vacated when the new building is completed. Building 1, a thirteen-story 105,000 GSF structure that was erected in 1929, sustained minor damage dur-ing the 1994 Northridge earthquake and the Lessor had completed repairs. However, subsequent structural building evaluation reports have shown that Building 1 cannot be seismically certifi ed (per Executive Order 12941) without a major retrofi t. In addition, only one regular stair serves fl oors 7 – 13. Occupants on these fl oors, including dormitory residents on fl oors 8 – 13, must de-pend on two escape stairs on the exterior of the building for second means of escape.
Building 1, which accounts for 41% of the entire square footage of the center, is a multi-use facility and contains virtually every functional Job Corps use group except hard vocations.
Building 2
Building 2 is owned by DOL. It is a two story masonry structure with stucco fi nish and a fl at roof, originally constructed in 1920. The excessive interior height of each of the fi rst fl oor suggests that the building was originally built as a commercial or light industrial structure. It has 7,500 GSF and is connected to Building 3 by a breezeway. Its present use for academic education functions does not take advantage of the vertical space. There have been some minor renovations to enlarge classrooms. Building 2 exterior walls are spalling and deteriorated. The exterior walls have been painted over without fully correcting the problem and the deteriorated condition is now hidden.
Building 3
Building 3 is owned by DOL. It is a three story brick masonry structure with a fl at roof, originally constructed in 1920. It has 11,880 GSF and is connected to Building 2 by a breezeway. It houses academic education functions and has had some renovations to improve the classroom sizes. A close examination and comparison with Building 2 reveal that Building 3 fi rst fl oor was also a high bay space and the second fl oor was created within this space. As a result, at the second fl oor, fl oor to underside of the third fl oor slab is only 7’-2”, and the fl oor to ceiling height is only 6’-8”.
Exterior masonry on the south wall of Building 3 is cracked in certain areas and joints are losing mortar. The seismic project will address structural cracks, but not the whole wall.
Building 4
Building 4 is owned by DOL. Originally constructed in 1930, it is a six story reinforced concrete structure with a fl at roof. It has 44,970 GSF in fi ve full fl oors and a second level mezzanine. It houses administration, education, soft vocations, security, and warehouse functions, which appear to have adequate space. Building 4 has been renovated on three fl oors which resulted in reconfi g-ured spaces and larger classrooms. However HVAC system and controls are severely deteriorated.
These will be corrected in conjunction with the seismic upgrade project for Buildings 2, 3, and 4.
EXISTING CONDITIONS - 3
Building 4 electrical panelboard is undersized and the conference room raised fl oor creaks and is not even. Otherwise, the building is in good condition and functions well.
Building 5
Building 5 is a 41,570 GSF leased facility that will be vacated when the new building in the down-town campus is constructed. Building 5 is a three story building with dormitories on second and third fl oors and food service, recreation facilities, some administration functions and storage on the fi rst fl oor and in the basement. This building is in fair condition and generally functions adequately.
Building 11
Building 11 is a 16,300 GSF leased facility. Building and Apartment Maintenance vocation and a warehouse are located in this building.
Building 12
Building 12 is a 5,900 GSF leased facility. It houses parts of non-academic education and admin-istration. The building is generally in good condition and functions well.
Building 16
Building 16 is a 19,623 GSF leased facility. It has two stories and a basement. It houses parts of academic education and recreation functions. Electrical capacity and distribution are inadequate for current and projected needs. The SiaTech program is increasing its activities due to State of California education requirements. As a result, it is running out of classrooms. Otherwise, the building is generally in good condition and functions well.
Health and Life Safety Issues
A summary of defi ciencies identifi ed or validated during this survey can be found below.
The Current Survey table identifi es all Health and Life Safety Defi ciencies funded subsequent to or as a result of the survey visit, as well as previous defi ciencies that were validated during this survey. There are six categories in the Current Survey table:
• Funded Health and Life Safety (IA/IIA) defi ciencies,
• O&M IA/IIA defi ciencies,
• Lessor IA/IIA defi ciencies
• Unfunded non- IA/IIA defi ciencies,
• O&M non-IA/IIA defi ciencies, and
• Lessor non-IA/IIA defi ciencies.
The Prior Years Funded Not Corrected table shows two categories:
EXISTING CONDITIONS - 4
• Funded Health and Life Safety defi ciencies and
• Funded non-Health and Life safety defi ciencies.
The survey team may have identifi ed IIC defi ciencies related to the accessibility of buildings as de-fi ned by ADA/UFAS guidelines. In accordance with DOL policy, these defi ciencies are typically only corrected during major renovations, or in order to make essential accommodations. These defi ciencies are not included in the summary, but, when funded, may be found at the FNC website.
Summary of Defi ciencies
CURRENT SURVEY PY 09
Defi ciency Type Number of Defi ciencies Funded Amount or Amount Estimated
Funded IA/IIA 7 $15,408
O&M IA/IIA 31 $0
Lessor IA/IIA 2 $0 Unfunded NON - IA/IIA 14 $182,698
O&M NON - IA/IIA 20 $0
Lessor NON - IA/IIA 3 $0
PRIOR YEARS FUNDED NOT CORRECTED
Defi ciency Type Number of Defi ciencies Funded Amount Funded IA/IIA 5 $175,413 Funded NON- IA/IIA 5 $396,680
Subsequent to the survey, defi ciencies and projects may have been funded through the American Recovery and Reinvestment Act (ARRA) or through supplemental redirects. Where applicable, these changes are refl ected in the Defi ciency Analysis section of this report.
EXISTING CONDITIONS - 5
C Recommendations
Building 4 needs electrical upgrade
Building 16 needs electrical upgrade and renovation to create a classroom
New building site
RECOMMENDATIONS
RECOMMENDATIONS - 1
Status of the Previous (PY06) Plan
The PY 06 survey was a Life Safety Survey only. In addition to correcting life safety defi ciencies it recommended the following Regional project.
REGIONAL
Repair exterior masonry walls of Buildings 2 and 3 This project was funded but has not been corrected yet.
Signifi cant Issues
Issues Being Addressed
• Building 1, the largest building on center (a leased building), does not meet Federal seismic criteria. YWCA, the center operator, is constructing a new building to replace Buildings 1 and 5 under an agreement with DOL.
• DOL-Owned Buildings 2, 3, and 4 also require structural bracing to satisfy seismic require-ments. Exterior masonry walls of Buildings 2 and 3 are deteriorated. Funded National Project 2981 and funded defi ciencies will address these issues. In addition, the HVAC sys-tem and controls in Building 4 are severely deteriorated and the fi re alarm detection system needs upgrading. Funded defi ciencies will address these issues.
Issues That Need To Be Addressed
• Building 4 electrical panelboard is undersized and the conference room raised fl oor creaks and is not even.
• Electrical capacity and distribution system in Building 16 is inadequate.
• An additional classroom is needed in Building 16.
PY 09 Plan Overview
A new building under construction will replace defi cient Buildings 1 and 5. Therefore no National project is proposed.
Life safety defi ciencies will be corrected by the Region, the center, and the Lessor as identifi ed in the Correspondents and Reports section.
RECOMMENDATIONS - 2
Building 4 electrical capacity and distribution would be improved by providing new panelboards and circuits. The sagging and creaking raised fl oor in the Center Director’s conference room would be replaced.
Building 16 electrical capacity and distribution would be improved by providing new panelboards and circuits and a classroom would be created on the fi rst fl oor by taking space from the recreation room.
Regional Projects
The cost of unfunded defi ciencies amount to approximately $180,000. Each remaining defi ciency is considered for funding on an annual basis and will be funded based on the center/Regional/ National priorities. Regional and center projects recommended to be addressed in the short term include the following:
Estimated Cost
• Improve electrical circuits and panelboard in Building 4 $20,240 (Defi ciencies 78748, 78754 and 78755)
• Replace damaged raised fl oor in Building 4 $6,580 (Defi ciency 78790)
• Improve electrical circuits and panelboard in Building 16 $81,241 (Defi ciencies 78751, 78752 and 78756)
• Create a classroom in Building 16 $42,592 (Defi ciency 78794)
D Building Description
BUILDINGS AND STRUCTURES
00901 LOS ANGELES 24-JUN-10
1Page:
0001 - 1106 SOUTH BROADWAY
0002 - 215 WEST 11TH STREET
0003 - 1049 SOUTH HILL STREET
0004 - 1031 SOUTH HILL STREET
0005 - 1215 LODI PLACE
0011 - 3695 EAST OLYMPIC STREET (not DOL lease)
0012 - 217-219 WEST 11TH STREET
0016 - 1056-1060 S. OLIVE STREET
0013 - 3695 EAST OLYMPIC STREET (not DOL lease) 0014 - 3695 EAST OLYMPIC STREET (not DOL lease)
Name GSF
105,000 7,500
11,880 44,970 41,570 16,300
5,900 19,623
Active Active Active Active Active Active
Active Active Active
Active
StatusType
Building Building Building Building Building Building
Building Building Structure
Structure
Use Group Built Flrs Const
Residential Business Business Business Residential Business
Business Assembly Storage
Storage
Fair Good Fair
Good Fair
Good
Good Good Good
Good
ConditionAsset Number
0090100002 0090100003 0090100004 0090100005 0090100006 0090100009
0090100011 0090100015 0090100012
0090100013
8 252,743
2 750
10 253,493
Buildings
Structures
Total
GSF
GSF
GSF
Summary
Building Descriptions and Utilities Los Angeles Job Corps Center
BUILDING 1 - 1106 SOUTH BROADWAY
Building Descriptions Date: Jun. 24, 2010Center : Los Angeles (00901) Page: 1 of 41
Building: 0001 - 1106 SOUTH BROADWAY
BUILDING ENVELOPE
Foundation RoofBuilding
Concrete Concrete Steel, Wood
Brick Masonry
Comments: Additionally, the building has stucco over the brick on the south side.
Wall Roof None Rigid
Metal Units - Metal Frame Storefront - Metal Frame Wood Units - steel Frame
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership#Floors
Residential 105,000 66,897 13 Leased 1929 Candidate
Comments: Audio/visual device coverage is inconsistent throughout the building, in most public bathrooms and in some public areas. Pay phones for student use are provided at the dorm floors.
REAL ESTATE
Access to Building
Ramps
Entrance
2nd Egress
Visual Alarm
Corridor/Aisle
Rooms
Stairs
Elevator
Restrooms
Drinking Fountain
Telephone
Yes
N/A
Yes
No
Yes
Yes
No
No
Yes
No
No
Yes
ACCESSIBILITY
Structural Systems1.
Exterior Walls2.
Insulation4.
Exterior Doors5.
Material
Asbestos: Yes
Drainage Year Life
Remaining Type Area Served
Built-up Roofing Interior Roof Drains 2002 12 Flat Entire Building
3. Roof
Entire Building
Area Served
Page: 2 of 41
Building: 0001 - 1106 SOUTH BROADWAY
INTERIOR FINISH
Carpet Ceramic Tile Concrete Marble Terrazzo Vinyl Tile Wood
CMU & clay tile block Ceramic Tile Drywall Exposed Structure Plaster
Metal Units - Metal Frame Wood Units - Metal Frame
VERTICAL CIRCULATION
Concrete Stairs Elevator Metal Stairs
Comments: There are also metal ladders and steel fire escapes.
Casement - Steel Frame; Single Glazing; Double Hung - Metal Frame; Single Glazing;
Double Hung - Wood Frame; Single Glazing; Fixed - Aluminum Frame; Double Glazing;
Acoustical Tile Concrete Gypsum Board Plaster
Windows6.
Floors1. Asbestos: Yes
Interior Walls2.
3. Asbestos: Yes
Interior Doors4.
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
There are three boilers (Rite #A200S, 1950 MBH input) in the basement, lower level mechanical equipment room.
This unit heater is located in the CPP space.
Comments:
Comments:
HVAC
Heat1. Asbestos: Yes
Gas-Fired Steam Boiler
Electric Resistance
Steam Radiators
Unit Heater
Two-Pipe
None
Electric
Electric
Natural
Natural
None
None
Entire Building
Classrooms
Ceilings
Page: 3 of 41
Building: 0001 - 1106 SOUTH BROADWAY
Mechanical
Mechanical
Toilet/Shower
Kitchen
Comments: There are four large utility set type exhaust fans in the penthouse ventilating the toilet/shower rooms.
A steam-water exchanger, in the penthouse, is used to heat domestic water supply. Two storage tanks are also in the penthouse.
Comments:
Cast Iron None Cast Iron
Bathtub Electric Water Cooler Lavatory Shower Sink Water Closet (Flush Valve)
Gas (Natural)
Comments:
Ventilation Area Served
Copper Copper Steam/Hot Water Heat Exch.
Water Softener Yes
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Heat Pump
Split Direct Expansion (Air
Source)
Split Direct Expansion (Air
Source)
Window Unit
Single Duct
Fan Coil
Refrigerant
Refrigerant
Refrigerant
Electric
Electric
Electric
Natural
Natural
Natural
None
None
None
Offices
Offices
Offices
PLUMBING
Exhaust Ventilation
There are about 40 window units serving offices and other spaces, including six in the dining hall.
There are several split systems serving offices, the elevator equipment room and other spaces.
There are several ductless split systems serving offices and other spaces.
Comments:
Comments:
Comments:
Ventilation2.
System Type
Number of Deficiencies = 1
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Water Distribution1.
Sanitary Distribution2.
Fixtures3.
Fuel Distribution4.
3. Air Conditioning
There are three meters in the basement upper level gas meter room.
Page: 4 of 41
Building: 0001 - 1106 SOUTH BROADWAY
Wet Wet ABC Type Fire Extinguisher, Dry Chemical
Comments: The sprinkler coverage is limited to the eight floor and above (dorm floors) and the stairwells.
Comments: The service from a utility company transformer station located in the building is fed to a 2500A three-section switchgear (Cutler-Hummer, 02/2002) with a 2500A disconnect switch. The switchgear is located on the first floor in the main electrical room adjacent to the utility transformer station. The utility meter is located at the switchgear location. Typical dorm floor (8 through 13) is served by a 225A panelboard (Cutler-Hummwer, 6610C75G10, 65 kA, 02/2002) with a 150A main circuit breaker (MCB). The building is provided with three elevators (40HP, 177A FLA motor), each served from a 70 kVA isolation transformer (11-03-1999). Lightning protection on the upper roof consists of the 30' high metal mast.
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
High Intensity Discharge (HID)
Comments: Building-mounted HID light fixtures are controlled by individual photocells. The center is an open campus environment; the street lighting contributes to exterior illumination.
Main Switchboard 120/208V, 3-Phase, 4-Wire Panelboards, Loadcenters Receptacles, GFCI, Switches
Sprinkler System Stand Pipe System Fire Suppression
Number of Deficiencies = 2FIRE PROTECTION
ELECTRICAL SERVICES Number of Deficiencies = 4
Exterior Lighting1.
Location UL300 Compliance Status Fourth-floor kitchen. Compliant
UL300 COMMERCIAL KITCHEN HOOD FIRE SUPPRESSION
LIGHTING
Page: 5 of 41
Building: 0001 - 1106 SOUTH BROADWAY
FIRE ALARM
Comments: The fire alarm control/annunciator panel is a Fire Lite Alarm Sensiscan 1000 located on the first floor at the main entrance by security desk. Sleeping rooms are provided with stand-alone smoke alarms.
Audible Alarm Control/Annunciator Panel Duct Smoke Detector Flow Switch Heat Detector Magnetic Door Holder Manual Pull Station Outside Water Bell Smoke Detector Tamper Switch Visual Alarm
Comments: Recorded footcandle levels include natural lighting contribution. Incandescent lighting is also utilized in the storage/support areas. T12 fluorescent lighing is utilized in some offices, electrical/mechanical rooms and some storage/support areas.
T12 and T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T12 - Fluorescent
T8 - Fluorescent
Compact Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T12 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
Compact Fluorescent
T8 - Fluorescent
T12 - Fluorescent
Incandescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
Offices
Classrooms
Food Preparation
Medical/Dental
Recreation
Sleeping Rooms
Storage/Warehouse-Inactive
Offices
Dining/Lunch Rooms
Dishwashing
Wards (Patient)
Recreation
Toilets
Storage/Warehouse-Active
Storage Rooms
Storage Rooms
Corridors & Stairs
Maintenance Shop
Equipment Rooms (Elec/Mech)
Laundry Room
Conference Rooms
Reception
Area Recommended Level
Recorded Level Light Type
Battery Backup Battery Backup
Emergency Exit
Number of Deficiencies = 3
Interior Lighting2. Number of Deficiencies = 1
Emergency /Exit Lighting3. Number of Deficiencies = 3
Page: 6 of 41
Building: 0001 - 1106 SOUTH BROADWAY
Comments: There are pay phones on the dorm floors (8 through 13). A security system consists of a Sonitrol security panel, Sonitrol annunciator panel and color monitor located at the main entrance by the security desk, security cameras sporadically located on the building exterior and interior (in cafeteria, recreation floor and at the main entrance), and magnetic door alarms provided in the Med/Dental area.
Two T1 lines are provided by AT&T to the main telephone and data equipment Demarcation point located in the data closet on the first floor by the main entrance. This is a stand-alone system. Fiber optic cabling and Cat 5/6E Ethernet cabling are utilized for switch to switch connection. VoIP is utilized for long distance and toll calls (through the JCDC), data and voice communication. The telephone system is an Avaya PBX system. This building's data system has a capability to communicate with independent data systems in Buildings 4, 5 and 11.
Connected to Main System Magnetic Door/Alarm Connected to Main System Satellite Dish
Telephone Security Public Address Television
GENERAL BUILDING CONDITION
Rating
Comments:
X Good Fair Poor
The structure does not meet current seismic requirements. The ventilation systems are not operational and the dorm heating system controls are inadequate. Main building fire alarm panel is obsolete.
COMMUNICATION
The facility condition is not impacting the functional use of the facility.
The facility condition IS impacting the functional use of the facility.
The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.
Electric Water Gas Yes YesYes
BUILDING UTILITY METERING
Structure: Poor Exterior: Good Interior: Good Mechanical: Good Electrical: Good
Type Location None None
Comments: Carbon monoxide detectors are not provided.
CARBON MONOXIDE DETECTION
BUILDING 2 - 215 WEST 11TH STREET
Page: 7 of 41
Building: 0002 - 215 WEST 11TH STREET
BUILDING ENVELOPE
Foundation RoofBuilding
Concrete Loadbearing Masonry Wood
Brick Masonry Storefront
Comments: There is plaster finish over part of the brick masonry.
Wall Roof None Rigid
Metal Units - Metal Frame Storefront - Metal Frame Storefront - Storefront Frame
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership#Floors
Business 7,500 4,643 2 Owned 1920 Unevaluated
REAL ESTATE
Access to Building
Ramps
Entrance
2nd Egress
Visual Alarm
Corridor/Aisle
Rooms
Stairs
Elevator
Restrooms
Drinking Fountain
Telephone
Yes
N/A
Yes
Yes
Yes
Yes
Yes
No
No
No
No
N/A
ACCESSIBILITY
Structural Systems1.
Exterior Walls2.
Insulation4.
Exterior Doors5.
Material Drainage Year Life
Remaining Type Area Served
Single Ply Interior Roof Drains 2001 11 Flat Entire Building
3. Roof
Page: 8 of 41
Building: 0002 - 215 WEST 11TH STREET
INTERIOR FINISH
Carpet Concrete Vinyl Tile
Brick Drywall
Metal Units - Metal Frame Wood Units - Metal Frame
Wood Unit - Wood Frame
Mechanical Toilet
Ventilation Area Served
VERTICAL CIRCULATION
Concrete Stairs Metal Ladder
Comments: The metal ladder provides access from the second floor to the attic and roof.
Awning Units - Aluminum Frame; Single Glazing; Fixed - Aluminum Frame; Single Glazing;
Acoustical Tile Plaster
Exhaust Ventilation
Windows6.
Floors1.
Interior Walls2.
3.
Interior Doors4.
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
The building is heated by two packaged rooftop units (a Carrier #48TJC028 and a #48TJD025, both 206 MBH output).
Comments:
HVAC
Heat1.
Gas-Fired Packaged
Single Duct None Electric Mechanical None Entire Building
Ventilation2.
Page: 9 of 41
Building: 0002 - 215 WEST 11TH STREET
There are two hot water heaters in this building, one on each floor. The second floor unit (40 gallon, 38 MBH input) serves Building 2. The first floor unit is dedicated to supplying the domestic hot water demand of Building 3 (50 gallon, 40 MBH input). The water meter is in a pit in the sidewalk outside the building.
Comments:
Cast Iron None Cast Iron
Electric Water Cooler Hose Bibb Lavatory Service Sink Sink Urinal Water Closet (Tank)
Gas (Natural)
Wet Wet ABC Type Fire Extinguisher
Comments: There is a fire hose at the midpoint of the corridor on each floor.
Copper Copper Gas-Fired None No
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Packaged Direct
Expansion (Air Source)
Single Duct None Electric Mechanical None Entire Building
Sprinkler System Stand Pipe System Fire Suppression
PLUMBING
The building is cooled by two packaged rooftop units (a Carrier #48TJC028 and a #48TJD025, both 25 ton).
Comments:
System Type
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Water Distribution1.
Sanitary Distribution2.
Fixtures3. Number of Deficiencies = 1
Fuel Distribution4.
Number of Deficiencies = 1FIRE PROTECTION
Page: 10 of 41
Building: 0002 - 215 WEST 11TH STREET
Comments: The building has two electrical services both of which are connected to main switchboards, both located in the first floor electrical room. A 120/240V, 3-phase, 3 wire service energizes a 400A main switchboard with a 400A main disconnect switch. This switchboard has one 225A and one 150A switch and serves two roof-mounted AHU units. A 120/240V, 1-phase, 3 wire service energizes a 400A main switchboard with a 400A main switch. This switchboard has two 150A and one 125A switch and is utilized for the building general power requirements. Two utility meters are provided by the switchboards location.
FIRE ALARM
Comments: The fire alarm system devices are connected and monitored by the fire alarm control panel in Building 3 (1049 South Hill Street). Fire alarm (FA) annunciator panel is Light Engineering Display LD-05 located in the first floor lobby (facing the 11th street). FA power supply unit (FCPS-24F) is located in the main electrical room.
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
Audible Alarm Duct Smoke Detector Flow/Tamper Switch Heat Detector Manual Pull Station Remote Annunciator Panel Smoke Detector Visual Alarm
Comments: Recorded footcandle levels include natural lighting contribution.
Halogen High Intensity Discharge (HID)
Comments: Building-mounted light fixtures are controlled by time clock and building-mounted photocell.
T8 - Fluorescent
T8 - Fluorescent
Compact Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
Classrooms
Offices
Storage Rooms
Toilets
Corridors & Stairs
Equipment Rooms (Elec/Mech)
Area Recommended Level
Recorded Level Light Type
Battery Backup Battery Backup
Main Switchboard 120/240V, 3-Phase, 3 Wire Panelboards, Loadcenters Receptacles, GFCI, Switches
Emergency Exit
ELECTRICAL SERVICES Number of Deficiencies = 1
Exterior Lighting1.
Interior Lighting2. Number of Deficiencies = 1
Emergency /Exit Lighting3.
Type Location Battery Operated Corridor
Comments: Carbon monoxide detector is provided on the first floor just outside the mechanical room.
Page: 11 of 41
Building: 0002 - 215 WEST 11TH STREET
Comments: The building is connected to the LAN system in Building 4 by fiber optic cable. The building is provided with two Cisco 3800 series routers, one Cisco 4400 series wireless LAN controller, Cisco WS C6500 switch, Blue Coat Proxy SG series module for web communication, backed up by UPS unit APC 2000 VA. The security control/annunciator panel is a Sonitrol unit located at the building entrance from the 11th street.
Connected to Main System Motion Detector/Door Alarms Not Connected to Main System
TV w/VCR
Telephone Security Public Address Television
GENERAL BUILDING CONDITION
Rating
Comments:
X Good Fair Poor
The structure does not meet current seismic requirements.
COMMUNICATION
The facility condition is not impacting the functional use of the facility.
The facility condition IS impacting the functional use of the facility.
The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.
Electric Water Gas Zone YesYes
BUILDING UTILITY METERING
Structure: Fair Exterior: Good Interior: Good Mechanical: Good Electrical: Good
BUILDING 3 - 1049 SOUTH HILL STREET
Page: 12 of 41
Building: 0003 - 1049 SOUTH HILL STREET
BUILDING ENVELOPE
Foundation RoofBuilding
Concrete Loadbearing Masonry Wood
Brick Masonry
Wall Roof None Rigid
Metal Units - Metal Frame Storefront - Metal Frame
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership#Floors
Business 11,880 7,307 3 Owned 1920 Unevaluated
Comments: The elevator does not meet the cab clearance requirements for accessibility. Men's restroom is accessible, women's restroom does not have adequate clearance at entry door. The second accessible egress is through Building 2 which is connected to Building 3.
REAL ESTATE
Access to Building
Ramps
Entrance
2nd Egress
Visual Alarm
Corridor/Aisle
Rooms
Stairs
Elevator
Restrooms
Drinking Fountain
Telephone
Yes
N/A
Yes
Yes
Yes
Yes
Yes
No
No
Yes
No
N/A
ACCESSIBILITY
Structural Systems1.
Exterior Walls2.
Insulation4.
Exterior Doors5.
Material Drainage Year Life
Remaining Type Area Served
Single Ply Interior Roof Drains 2001 11 Flat Entire Building
3. Roof
Page: 13 of 41
Building: 0003 - 1049 SOUTH HILL STREET
INTERIOR FINISH
Carpet Concrete Vinyl Tile
Drywall Exposed Structure
Metal Units - Metal Frame Wood Units - Metal Frame
Mechanical Toilet
Ventilation Area Served
VERTICAL CIRCULATION
Concrete Stairs Elevator
Comments: There are three interior stairs and one elevator.
Casement - Steel Frame; Single Glazing; Fixed - Aluminum Frame; Single Glazing;
Single Hung - Wood Frame; Single Glazing;
Acoustical Tile Plaster Wood Fiber
Exhaust Ventilation
Number of Deficiencies = 1
Number of Deficiencies = 1
Windows6.
Floors1. Asbestos: Yes
Interior Walls2.
3. Asbestos: Yes
Interior Doors4.
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
The building is heated and cooled by three rooftop units (a Carrier #48HJD012, 147 MBH output, a #48HJD015, 186 MBH output and a 48HJD025, 223 MBH output).
Comments:
HVAC
Heat1.
Gas-Fired Packaged
Single Duct None Electric Mechanical None Entire Building
Page: 14 of 41
Building: 0003 - 1049 SOUTH HILL STREET
The hot water heater (50 gallon, 40 MBH input) and recirculating pump for this building is located in Building 2 (215 West 11th Street). The water meter is located in a pit in the sidewalk outside that building.
Comments:
Cast Iron None Cast Iron
Electric Water Cooler Lavatory Service Sink Sink Urinal Water Closet (Flush Valve) Water Closet (Tank)
Gas (Natural)
None Wet ABC Type Fire Extinguisher
Comments: There is a fire hose at the midpoint of the corridor on each floor.
Copper Copper Gas-Fired None No
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Packaged Direct
Expansion (Air Source)
Single Duct None Electric Mechanical Economizer Entire Building
Sprinkler System Stand Pipe System Fire Suppression
PLUMBING
The building is cooled by three rooftop units (a Carrier #48HJD012, 10 ton, a #48HJD015, 12-1/2 ton and a 48HJD025, 20 ton). All units are furnished with economizers and power exhaust.
Comments:
System Type
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Water Distribution1.
Sanitary Distribution2.
Fixtures3. Number of Deficiencies = 1
Fuel Distribution4.
FIRE PROTECTION
Page: 15 of 41
Building: 0003 - 1049 SOUTH HILL STREET
Comments: The building has two electrical services both of which are connected to main switchboards manufactured by Zinsco, located in the first floor small electrical closets near the main entrance. A 120/240V, 3-phase, 3 wire service energizes a 400A main switchboard with a 400A main disconnect switch. This switchboard has one 225A, one 125A, one 100A and one 40A switch and serves three roof-mounted AHU units and elevator. A 120/240V, 1-phase, 3 wire service energizes a 400A main switchboard with a 400A main switch. This switchboard has one 175A and three 125A switches, serves two 225A MLO panels (Zinsco, CTL) on the second and third floors, and is utilized for the building general power requirements. Two utility meters are provided by the switchboards location.
FIRE ALARM
Comments: The fire alarm control/annunciator panel is a Fire-Lite MS-9200 addressable unit. The panel also monitors the fire alarm system devices in Building 2 (215 West 11th Street). A fire alarm (FA) annunciator panel Light Engineering Display LD-05 and a FA power supply unit (FCPS-24F) both are located at the main entrance near the main FA panel.
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
Audible Alarm Control/Annunciator Panel Duct Smoke Detector Flow Switch Heat Detector Manual Pull Station Remote Annunciator Panel Smoke Detector Tamper Switch Visual Alarm
Comments: Recorded footcandle levels include natural lighting contribution. Incandescent fixtures are also utilized in the storage/support areas.
High Intensity Discharge (HID)
Comments: Building-mounted light fixtures are controlled by roof-mounted photocell.
T8 - Fluorescent
T8 - Fluorescent
T12 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
Offices
Classrooms
Storage Rooms
Storage Rooms
Corridors & Stairs
Toilets
Reception
Area Recommended Level
Recorded Level Light Type
Battery Backup Battery Backup
Main Switchboard 120/240V, 3-Phase, 3 Wire Panelboards, Loadcenters Receptacles, GFCI, Switches
Emergency Exit
ELECTRICAL SERVICES Number of Deficiencies = 2
Exterior Lighting1. Number of Deficiencies = 1
Interior Lighting2. Number of Deficiencies = 1
Emergency /Exit Lighting3.
Page: 16 of 41
Building: 0003 - 1049 SOUTH HILL STREET
Comments: The building is connected to the LAN system in Building 4 by fiber optic cable. The security system consists of motion detectors and security cameras, which report to a Sonitrol security control panel equipped with an ADEMCO dialer. Roof-mounted dish is disconnected and currently not in use.
Connected to Main System CCTV/Door Alarms None TV w/VCR
Telephone Security Public Address Television
GENERAL BUILDING CONDITION
Rating
Comments:
X Good Fair Poor
The structure does not meet current seismic requirements. Mortar joints in the exterior brick masonry wall are deteriorated but hidden behind coats of paint.
COMMUNICATION
The facility condition is not impacting the functional use of the facility.
The facility condition IS impacting the functional use of the facility.
The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.
Electric Water Gas Zone YesYes
Structure: Fair Exterior: Fair Interior: Good Mechanical: Good Electrical: Good
BUILDING 4 - 1031 SOUTH HILL STREET
Page: 17 of 41
Building: 0004 - 1031 SOUTH HILL STREET
BUILDING ENVELOPE
Foundation RoofBuilding
Concrete Concrete Concrete
CMU Masonry Concrete Painted Plaster
Wall Roof None Rigid
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership#Floors
Business 44,970 26,202 5 Owned 1930 Unevaluated
Comments: The entrance door lacks adequate side clearance for wheelchair approach. The elevators do not meet the cab clearance requirements for accessibility. No visual devices, bells only are provided through the mezzanine level and second floor. Audio/visual devices are not provided in the public bathrooms on some floors.
REAL ESTATE
Access to Building
Ramps
Entrance
2nd Egress
Visual Alarm
Corridor/Aisle
Rooms
Stairs
Elevator
Restrooms
Drinking Fountain
Telephone
Yes
N/A
No
Yes
Yes
Yes
Yes
No
No
Yes
No
N/A
ACCESSIBILITY
Structural Systems1.
Exterior Walls2. Number of Deficiencies = 1
Insulation4.
Material Drainage Year Life
Remaining Type Area Served
Single Ply Interior Roof Drains 2006 16 Flat Entire Building
3. Roof
Page: 18 of 41
Building: 0004 - 1031 SOUTH HILL STREET
INTERIOR FINISH
Carpet Concrete Vinyl Tile Wood
Drywall Exposed Structure
Aluminum Storefront - Aluminum Frame Wood Units - Metal Frame
Mechanical Toilet
Ventilation Area Served
VERTICAL CIRCULATION
Concrete Stairs Elevator Metal Stairs
Metal Rollup - Metal Frame Metal Units - Metal Frame
Awning Units - Wood Frame; Single Glazing; Casement - Wood Frame; Single Glazing;
Fixed - Wood Frame; Single Glazing; Hopper - Wood Frame; Single Glazing;
Acoustical Tile Plaster
Exhaust Ventilation
Exterior Doors5.
Windows6.
Floors1. Asbestos: Yes Number of Deficiencies = 1
Interior Walls2.
3. Number of Deficiencies = 1
Interior Doors4.
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
The building utilizes a variable air volume system with hot water reheat coils in the terminal air units.
The air handler (+/- 40,000 CFM), a boiler (1000 MBH output), the hot water coil and HW circulators are mounted on the roof.
Comments:
HVAC
Heat1.
Gas-Fired Hot Water Boiler
Variable Air Volume
Two-Pipe Pneumatic Mechanical None Entire Building
Ventilation2. Number of Deficiencies = 1
Page: 19 of 41
Building: 0004 - 1031 SOUTH HILL STREET
The water heater was built by Rheem (60 gallon). The water meter is located in a pit in the sidewalk, outside the building.
Comments:
Cast Iron None Cast Iron
Electric Water Cooler Lavatory Service Sink Urinal Water Closet (Flush Valve)
Gas (Natural)
Wet Wet ABC Type Fire Extinguisher
Comments: The stand pipe system extends to the roof.
Copper Copper Gas-Fired None No
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Split Direct Expansion (Air
Source)
Variable Air Volume
Refrigerant Pneumatic Mechanical None Entire Building
Sprinkler System Stand Pipe System Fire Suppression
PLUMBING
The air conditioning system utilizes a variable volume air handling unit with a DX condensing unit (Trane #RAUCD124BJ132D, 100 ton, eight compressors).
Comments:
System Type
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Water Distribution1.
Sanitary Distribution2.
Fixtures3. Number of Deficiencies = 3
Fuel Distribution4.
Number of Deficiencies = 1FIRE PROTECTION
Page: 20 of 41
Building: 0004 - 1031 SOUTH HILL STREET
Comments: There is a utility company transformer room near the loading dock service entrance. From this room the electrical service is provided to a 1600A, 120/208V, 3-phase main switchboard (by Sierra, B8750A) with a 1600A main bolted disconnect switch. The switchboard has one 1200A, seven 200A, four 100A and one 60A switch and one 60A spare switch, and serves a 1000A roof-mounted motor control center, six 200A MLO and four 100A MLO floor panels, elevator (200A) and 60A MLO emergency panel. The 1000A, 120/208V, 3-phase, 3 wire roof-mounted motor control center (by Sierra) with an 800A main disconnect switch provides for two water pumps and a 300 kVA (208V primary/460V secondary) transformer, which in turn energizes a 400A, 277/480V disconnect switch fused by 400A and serving a 40 ton packaged condensing unit. Utility meter is provided at the main switchboard location.
FIRE ALARM
Comments: The fire alarm control panel is a Simplex 2001-8001 panel (24V DC, 16 zones, 09/10/1979) located at the security desk by the main entrance. The panel does not have battery backup capability.
This is the start of the file's text. The full file is on GovTribe.
Other files
| File | Type | Posted |
|---|---|---|
| Amendment 2.pdf | ||
| Amendment 1.pdf | ||
| Description of Pre-proposal Conference Walk-thru.doc | DOC document | |
| Map for Walk-through.pdf | ||
| Inventory Estimate.doc | DOC document | |
| Regional Career Pathway Plan.doc | DOC document | |
| National Staff Compensation Report.pdf | ||
| Site Map and Utilities.pdf | ||
| Computerized Property Management Listing.pdf | ||
| Monthly Center Summary Report.pdf | ||
| Educational Attainment Report.pdf | ||
| Center Report Card.pdf | ||
| Career Transition Services Report Card.pdf | ||
| Career Technical Training Report Card.pdf | ||
| Solicitation.doc | DOC document |
Show all 15