J-8_Blue_Ridge_Facility_Survey_Vol._2_September_2015.pdf
PDF 9 MB Posted
- Attached to
- Blue Ridge JCC Operations
- Solicitation number
- DOL-ETA-16-R-00116
About this file
Attachment J-8 Facility Survey Vol. II
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Blue_Ridge_16-R-00116_Amend_01.pdf | ||
| J-10_Blue_Ridge_Utilities_Usage_and_Cost_Form.xls | XLS spreadsheet | |
| J-9_Blue_Ridge_Master_Property_List_20160316.pdf | ||
| J-8_Blue_Ridge_Facility_Survey_Vol._1_September_2015.pdf | ||
| Blue_Ridge_Synopsized_RFP_16-R-00116.pdf | ||
| J-11_Blue_Ridge_Vehicle_Log.xls | XLS spreadsheet | |
| J-3_ETA_Form_2110.docx | DOCX document | |
| J-4_Staffing_Chart.docx | DOCX document | |
| J-6_Past_Performance_Questionnaire.docx | DOCX document | |
| J-2_Statement_of_Financlial_Capability.docx | DOCX document | |
| J-7_SF_1413.docx | DOCX document | |
| J-1_Cost_Details.docx | DOCX document | |
| J-5_Subcontracting_Summary.docx | DOCX document |
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
BLUE RIDGE
Job Corps Center Marion, VA
Facility Planning Report Volume II
Supporting Data
Final September 2015
Department of Labor/ Office of Job Corps
BLUE RIDGE
Job Corps Center Marion, VA
Facility Planning Report Volume II
Supporting Data
Final September 2015
Building 13 Gymnasium
VOLUME II - SUPPORTING DATA
EXECUTIVE SUMMARY
1.0 SITE LAYOUT AND PLANS
• Location Map
• Exisiting Site Plan
2.0 DESCRIPTIONS
• Buildings and Structures
• Space Utilization By Function
• NSF by Building
• Environmental Management Report
• Asbestos Report
• Radon Report
• Site Descriptions
• Building Descriptions
3.0 DEFICIENCIES
APPENDICES - CORRESPONDENCE AND REPORTS
Appendix A.
• Center Review Meeting Minutes
• Survey Brief
• Student Questionnaire
Appendix B.
• Life Safety Defi ciencies and List
Appendix C.
• O&M Defi ciencies List
Appendix D.
• Active Warranty List
Executive Summary
The facility survey for the Blue Ridge JCC was completed the week of March 2, 2015.
The information presented in Volume II, Supporting Data, represents the current status of the campus.
The information includes the following:
Existing site layout Overall status of existing building and structures Space utilization by building and function compared to recommended standards Status of environmental elements of the Center’s operations Details on the site and buildings and structures based on architectural, electrical, and mechanical survey and supporting documentation Presentation of the status of historical deficiencies and compilation of deficiencies documented through this survey Supporting documentation, as presented in the appendices of the center review meeting; survey brief and student questionnaire; life safety IA/IIA transmittal;
active warranties; and Federal Real Property Council (FRPC) Measures Matrix
Section 1.0 of this volume addresses site layout and plans while Section 2.0 presents details on the buildings and structures. Section 3.0 presents historic deficiencies and their status as well as new ones identified in this survey. The appendices provide additional information as noted below:
Appendix A. Survey Brief Questionnaire Appendix B. Life Safety Deficiencies and List Appendix C. O&M Deficiencies List Appendix D. Active Warranty Report Appendix E. FRPC Performance Measures Matrix
EXECUTIVE SUMMARY
1.0 - Site Layout and Plans
BLUE RIDGE
JOB CORPS CENTER
MARION, VIRGINIA
BLUE RIDGE JCC
20 MI100
2.0 - Descriptions
BUILDINGS AND STRUCTURES
00302 BLUE RIDGE 09/29/2015
1Page: of Date:
0001 - MAIN (ALESHIRE)
0002 - ACADEMICS/REC (RUSSELL)
0003 - ARTS AND CRAFTS
0004 - MAINTENANCE SHOP
0004A - MAINTENANCE STORAGE
0005 - TRANSITIONAL LIVING (WARREN
HOUSE)
0006 - ADMINISTRATION OFFICE
0007 - NURSING/MEDICAL ASSISTANT
0008 - TEAP CLASSROOM
0011 - MEDICAL
0013 - GYMNASIUM
0014 - PICNIC SHELTER (16Ft x 32Ft) 0015 - COVERED WALKWAY (6Ft X 60Ft)
Name GSF
52,100 8,100 2,476 1,630
4,130
1,060 5,940
3,020
11,180
Active Active Active Active Active Active
Active Active Active Active Active Active Active
StatusType
Building Building Building Building Building Building
Building Building Building Building Building Structure Structure
Use Group Built Flrs Const
A-3,A-2,R-2,B A-3,B A-3,B B,S-1 S-1 R-2
B B B B A-3 Assembly Business
Good Good Fair
Good Good Good
Good Good Good Good Good Good Good
ConditionAsset Number
0030200002 0030200003 0030200004 0030200005 0030200008 0030200006
0030200007 0030200012 0030200009 0030200013 0030200014 0030208110 0030208111
11 90,786
2 872
13 91,658
Buildings
Structures
Total
GSF
GSF
GSF
Summary
09/29/2015
Space Utilization By Function 00302 Blue Ridge Page: 1 of Date:
HOUSING
EDUCATION
FOOD SERVICE
RECREATION
SUGGESTED
NSF/
ENROLLEE
SUGGESTED
TOTAL
NSF
ACTUAL
TOTAL
NSF
TYPE OF SPACE
SUB TOTAL
SUB TOTAL
SUB TOTAL
SUB TOTAL
Resident Men Resident Women Total Residents
Residents 160 Non Residents 32
192Total Students
(160)
(200)
(192)
(192)
DIFFERENCE
17,280
10,100
3,456
8,480
18,367
14,087
3,673
16,330
Lounge Other Shower/Toilet Sleeping excl. SPD( rooms; beds) Storage
Academic (200) Non-Academic
11 -- ACT (Off-Ctr)
20 -- LPN +
40 -- Medical Assistant 30 -- Medical Office Specialist 60 -- Nursing Assistant +
15 -- OCT
Vocational Theory (80)
Dining (2 Servings) Food Preparation Food Storage
Activity Room Arts & Crafts Auditorium Gymnasium Miscellaneous Recreation Recreation Office Recreation Storage Student Store
1,646 2,201
12,870
6,309
1,080 1,739 1,627 1,080
1,280
1,754
3,250
2,535 7,450 1,685
1,600 1,280 1,920
11,520
2,000 2,000
1,200
2,400
1,536 1,152
-645
1,350 -265
-1,028 4,309
-1,320
-157
3,250
2,535 7,450 1,685
Vocations
RESIDENT
NON-RESIDENT
(160)
(32) 15
50 8,000
1,087
3,987
7,850
09/29/2015
Space Utilization By Function 00302 Blue Ridge Page: 2 of Date:
MEDICAL/DENTAL
ADMINISTRATION
STORAGE/SUPPORT
VACANT
SUGGESTED
NSF/
ENROLLEE
SUGGESTED
TOTAL
NSF
ACTUAL
TOTAL
NSF
TYPE OF SPACE
SUB TOTAL
SUB TOTAL
SUB TOTAL
SUB TOTAL
TOTAL 251.31 48,251 66,276
(192)
(192)
(192)
(0)
DIFFERENCE
90,786
0.73
TOTAL GSF
NET TO GROSS RATIO
1,255
3,840
3,840
1,775
4,720
6,284
1,040
Medical Only
Administration
Operations & Maintenance Warehouse
Vacant
6.54
1,775
4,720
1,985 4,299
1,040
1,255
3,840
1,536 2,304
1,995
1,040
2,444
1,040
18,025
Net Square Footage By Building Date: 09/29/2015 Page: 1
Center: BLUE RIDGE (00302) of 4
HOUSING
Sleeping excl. SPD
Lounge
Storage
Shower/Toilet
Other
Function Suggested
NSF
11,470 1,400
1,920
1,401
0001 - MAIN (ALESHIRE)
0005 - TRANSITIONAL LIVING (WARREN HOUSE)
0005 - TRANSITIONAL LIVING (WARREN HOUSE)
0001 - MAIN (ALESHIRE)
0005 - TRANSITIONAL LIVING (WARREN HOUSE)
0001 - MAIN (ALESHIRE)
0001 - MAIN (ALESHIRE)
0005 - TRANSITIONAL LIVING (WARREN HOUSE)
0005 - TRANSITIONAL LIVING (WARREN HOUSE)
0001 - MAIN (ALESHIRE)
Bldg Name Actual NSF Difference
12,870
2,201
1,646
Sub Total: 18,367
11,520
1,600
1,920
1,280
17,280
1,350
-645
-265
( 160
1,087 rooms; beds rooms; beds
Page: 2
Center: BLUE RIDGE (00302) of 4
EDUCATION
FOOD SERVICE
Academic
Vocational Theory (80)
Medical Assistant
LPN
Non-Academic
Nursing Assistant
Medical Office Specialist
Dining (2 Servings)
Food Preparation
Food Storage
Function Suggested
NSF
1,280
1,739
1,080
1,223
1,080
1,627
1,754
0002 - ACADEMICS/REC (RUSSELL)
0002 - ACADEMICS/REC (RUSSELL)
0007 - NURSING/MEDICAL ASSISTANT
0001 - MAIN (ALESHIRE)
0007 - NURSING/MEDICAL ASSISTANT
0007 - NURSING/MEDICAL ASSISTANT
0002 - ACADEMICS/REC (RUSSELL)
0001 - MAIN (ALESHIRE)
0002 - ACADEMICS/REC (RUSSELL)
0001 - MAIN (ALESHIRE)
0008 - TEAP CLASSROOM
0001 - MAIN (ALESHIRE)
0001 - MAIN (ALESHIRE)
0002 - ACADEMICS/REC (RUSSELL)
0007 - NURSING/MEDICAL ASSISTANT
0001 - MAIN (ALESHIRE)
0001 - MAIN (ALESHIRE)
0001 - MAIN (ALESHIRE)
0001 - MAIN (ALESHIRE)
Bldg Name Actual NSF Difference
1,280
1,739
1,080
6,309
1,080
1,627
1,754
Sub Total:
Sub Total:
14,087
3,673
2,000
1,200
2,000
2,400
1,536
1,152
10,100
3,456
-1,028
4,309
-1,320
-157
3,987
Page: 3
Center: BLUE RIDGE (00302) of 4
RECREATION
MEDICAL/DENTAL
ADMINISTRATION
STORAGE/SUPPORT
Arts & Crafts
Gymnasium
Auditorium
Student Store
Miscellaneous Recreation
Activity Room
Recreation Storage
Recreation Office
Medical Only
Administration
Warehouse
Operations & Maintenance
Function Suggested
NSF
7,450
2,535
1,290
3,250
1,775
3,695
4,299
1,115
0003 - ARTS AND CRAFTS
0013 - GYMNASIUM
0001 - MAIN (ALESHIRE)
0002 - ACADEMICS/REC (RUSSELL)
0013 - GYMNASIUM
0001 - MAIN (ALESHIRE)
0002 - ACADEMICS/REC (RUSSELL)
0013 - GYMNASIUM
0002 - ACADEMICS/REC (RUSSELL)
0013 - GYMNASIUM
0011 - MEDICAL
0006 - ADMINISTRATION OFFICE
0003 - ARTS AND CRAFTS
0001 - MAIN (ALESHIRE)
0001 - MAIN (ALESHIRE)
0001 - MAIN (ALESHIRE)
0004A - MAINTENANCE STORAGE
0004 - MAINTENANCE SHOP
Bldg Name Actual NSF Difference
7,450
2,535
1,685
3,250
1,775
4,720
4,299
1,985
Sub Total:
Sub Total:
Sub Total:
Sub Total:
16,330
1,775
4,720
6,284
1,255
3,840
2,304
1,536
8,480
1,255
3,840
3,840
1,995
7,850
2,444
Page: 4
Center: BLUE RIDGE (00302) of 4
VACANT
Vacant
Function Suggested
NSF
1,0400003 - ARTS AND CRAFTS
Bldg Name Actual NSF Difference
1,040
Sub Total: 1,040
1,040
( 0
1,040
Environmental Management Report
Center: BLUE RIDGE (00302) Page: 1 Date: 09/29/2015 of 1
SOLID & HAZARDOUS WASTE MANAGEMENT (RCRA)
Commercial Waste Service
HAZARDOUS MATERIALS STORAGE (EPCRA)
Yes Building 9 oil-based paint (4 gals), organic solvent (2 gals) Yes
PETROLEUM UNDERGROUND STORAGE TANKS (RCRA)
N/A0
PETROLEUM ABOVEGROUND STORAGE TANKS (CWA)
ASBESTOS AND PCB MANAGEMENT (TSCA)
AIR POLLUTION CONTROL (CAA)
Natural gas fired boiler Minor Source - Permitted
Attainment
Solid Waste Disposal :
Hazardous Waste Generator :
Hazardous Waste ID :
Generator Classification :
Hazadous Materials Storage :
Hazardous Materials ID :
HazMat Storage Area :
HazMat Spill Response Plan :
Number of Regulated USTs :
Number of Un-regulated USTs :
Local Hazardous Use Permit :
LEPC Notification :
EPA Generator ID Number :
Hazardous Waste Disposal :
RCRA Compliance :
ID LocationFuel Type Capacity
Number of ASTs :
Asbestos Survey Date :
Asbestos Type :
Asbestos Coordinator :
Coordinator Training Date:
Custodial/Maintenance Training :
AHERA Regulated :
Management Plan Approval :
PCB Transformer Testing :
PCB Transformers :
PCB-Contaminated Transformers :
Transformers Labelled :
Regional Air Quality :
Permitted Air Pollution Source :
Source Description :
BFI Industries No N/A
N/A N/A N/A N/A
No No
Overfill Leak Corrosion
SPCC Plan Required : SPCC Plan Completed :
No N/A
02/14/1990 Friable/Non-Friable Hurley Davis 07/01/2003 No No N/A No No
ID Fuel Type Capacity Location Overfill
Prevention Secondary ContainmentTank Status
Tank Status Prevention/Detection
Asbestos-Containing Materials Inventory
Date: 09/29/2015Center : Blue Ridge (00302) Page: 1 of 1
Floor Finishes Air Conditioning Plumbing (Bldg)
Floor Finishes Air Conditioning
Floor Finishes Exterior Walls
Plumbing (Bldg) Water Plumbing Floor Finishes
Bldg System
Bldg System
Bldg System
Bldg System
9x9 Floor tiles Flexible duct connectors Pipe fitting insulation
9x9 Black floor tile Flexible duct connectors
Vinyl sheet flooring Asbestos cement siding
Aircell pipe insulator Asbestos tank insulation Vinyl sheet flooring
Category Description
Category Description
Category Description
Category Description
Sq. Ft.
Ea.
Lin. Ft.
Sq. Ft.
Ea.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Location
Location
Location
Location
Unit
Unit
Unit
Unit
Quantity
Quantity
Quantity
Quantity
Throughout basement Air condition units Copy room
First floor First floor AHU
First floor Ben. aluminum siding
Hot water risers Hot water tank First floor porch
Building :
Building :
Building :
Building :
0001 - MAIN (ALESHIRE)
0002 - ACADEMICS/REC (RUSSELL)
0003 - ARTS AND CRAFTS
0005 - TRANSITIONAL LIVING (WARREN HOUSE)
Radon
Page: 1 of 1
0001 - MAIN (ALESHIRE)
0002 - ACADEMICS/REC (RUSSELL)
0003 - ARTS AND CRAFTS
0004 - MAINTENANCE SHOP
0004A - MAINTENANCE STORAGE
0005 - TRANSITIONAL LIVING (WARREN HOUSE)
0006 - ADMINISTRATION OFFICE
0007 - NURSING/MEDICAL ASSISTANT
0008 - TEAP CLASSROOM
0011 - MEDICAL
0013 - GYMNASIUM
Bldg Name
06/12/1990
06/12/1990
06/12/1990
06/12/1990
06/12/1990
Test Date
Yes
Yes
Yes
No
N/A
Yes
Yes
No
N/A
No
No
Radon Testing
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
Test Result
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Mitigation Mitigation Date
RADON EXPLANATORY NOTES
The US Environmental Protection Agency (EPA) has established a radon action level of 4.0 picoCuries per liter (pCi/L). Occupied buildings with radon concentrations less than 4.0 pCi/L do not require radon mitigation; un-occupied buildings, or those buildings which are occupied only infrequently for brief periods of time, also do not require radon mitigation. Occupied buildings with radon concentrations greater than
4.0 pCi/L require radon mitigation and verification of radon reductions as soon as possible, with priority given to dormitories and student recreation buildings. Occupied buildings with radon concentrations greater than 20.0 pCi/L should be considered significant radon exposure hazards, and priority for mitigation should be given to buildings with these highly elevated radon concentrations.
Radon mitigation techniques include: (1) adjustment of the building HVAC system to create a positive pressure within the building; (2) sealing of foundation wall cracks, penetrations, or other openings;
(3) sealing crawlspace openings and sump pits; (4) installing an active subslab depressurization (ASD) system.
Site Description
Main entrance to the Center and Building 1.
Page: 1 Date: 09/29/2015 of 5
Comments:
Paving Type for Roads & Parking
Parking lot in the west quadrant of the site is deteriorating
Paving Type for Sidewalks
Asphalt Concrete
Comments:
Topography Buildings and Structures
Center is not fully enclosed by fencing. There is a chain link fence along the northeast side of campus.
ROADS, PARKING & SIDEWALKS
Water Source Water Authority Service Meter On-Site Treatment Plant
1. Water System
Treatment Type Storage Type Storage Capacity(Gallons)
NoIndividualTown of MarionPublic Water Authority
None 0None
There are six water meters for 13 buildings.Comments:
Comments:
Fire Hydrants On-Site Water Supply Storage Capacity
(Gallons) Pressure Source FD Response Time
(Minutes)
Yes 0 3None Municipal
Fire Department is a next door neighbor to the Center
Sewage Treatment Flow
Utility
Publicly Owned Treatment Works
Utility
Gravity
Maintenance ResponsibilityOwnership
Number of Deficiencies = 3
Number of Deficiencies = 7
SITE FEATURES
UTILITIES
3. Sanitary Sewer System/ Sewage Treatment Plant
2. Fire Protection System
Buildings Structures11 2Sloping
Surrounding
Outdoor Recreation
Light Commercial, Residential
Playfield
East property line Chain Link
Location Type
Maintenance Responsibility System Capacity Adequate System Condition
Center Utility Yes Good
Separate Loop
No
Ownership Maintenance Responsibility System Capacity Adequate System Condition
Center Center Yes Good
System Capacity Adequate System Condition
Yes Good
Ownership
Roads & Parking Adequate Roads & Parking Condition Sidewalks Adequate Sidewalk Condition Yes Fair Yes Good
Number of Deficiencies = 1
Fencing
Other Features
Page: 2 Date: 09/29/2015 of 5
Atmos
Comments:
Electric Company PCB Trans.
Transformer Mounting Transformer Ownership
Systems Ownership Maintenance Responsibility
Appalachian Power
Primary overhead electrical power service enters the center from the west at two locations from utility-owned primary power overhead distribution lines along College Street. This service feeds pole-mounted step-down transformers with corresponding exterior building-mounted secondary utility meters for each individual building.
120/240V, 1-phase, 3 wire secondary service is utilized and additionally 120/208V, 3-phase, 4 wire is utilized for the HVAC equipment in Building 1.
Pole Utility
Utility Utility
No
12.47/7.2 kV, 3-Phase, 4 Wire
120/208V, 3-Ph., 4 Wire &120/240V, 1-Ph., 3 WireOverhead
OverheadPrimary Service
Secondary Service
Distribution Characteristics
5. Fuel Distribution System
4. Storm Water System Number of Deficiencies = 8
Drain Type On-Site Storm Water Management
Surface Run-off N/A
Ownership Maintenance Responsibility System Capacity Adequate System Condition
Center Yes GoodCenter
Comments: There are gutters and downspouts on most buildings. The extent of underground piping is unknown. The soil is eroding below the covered deck/walkway along the south side of Building 2. The two storm drain pipes along the hill are eroding the hill at the outfall.
Gas Company Metering
Individual
Ownership Maintenance Responsibility System Capacity Adequate System Condition
Center Center Yes Good
7. Electrical (Service)
Transformer Maint Resp
Utility
System Capacity Adequate System Condition
Yes Good
Generator
None
8. Electrical (Site Lighting)
Roadways Parking Walkways Building Outdoor Sports
Mounting
Control
Pole Pole Pole Building None
Photocell Photocell Photocell Photocell, Time Clock None
System Ownership Maintenance Responsibility System Capacity Adequate System Condition
Utility, Center, City Utility, Center, City Yes Good
Comments: Perimeter site lighting is owned and maintained by the city.
ATS MTS
No No
6. Central Plant: None
Metering Individual
Page: 3 Date: 09/29/2015 of 5
Comments:
Telephone Company
On-site Line Owner
Building 1 is utilized as the main service entrance and demarcation point for the main and off-center telephone system, and is where the main communication data closets are located. The off-center location has dedicated phone service from the main campus; a separate data service entry point/demarcation and data cabinet are located at the off-center location. The internet and long distance communication system is implemented and managed by the JCDC. VoIP system is not utilized anywhere on the center. The local calls are managed by CenturyLink (formerly Embarq). The data communication system hardware is manufactured by Cisco. Each main campus building has Cisco switches and CAT 5e network to connect nodes with the computers. Routers and switches in the main data closet, and at the off-site location, are UPS-protected. The center maintains 5 trunk lines and 15 dedicated phone lines. Cable TV service is provided by Adelphia Communications in the dormitories and recreation facilities. The main campus fire alarm is centrally monitored in Building 1. There is a separate fire and ADT security system in the off-center facility. The telephone system has limited public address capabilities.
CenturyLinks
Maint. Responsibility
Utility, Center Utility, Center
Security Panel; Magnetic Door Sensors
There are no storage tanks on site.
STORAGE TANKS
Comments:
TypeStatus Location Owner Fuel Type
Capacity (Gallons) Install DateID Reg.
9. Electrical (Communication/Alarm/Security)
Purpose
No
Stand-Alone
VOIP
System Capacity Adequate System Condition
GoodYes
Number of Deficiencies = 9
Fire Alarm Security
Page: 4 Date: 09/29/2015 of 5
ACCESSIBILITY
Yes
The abrupt change of grade behind Building 1 makes this site inherently difficult for accessibility. It is possible to access the buildings in the lower part by using the sidewalk that surrounds the center.
Comments:
Comments:
UnknownYesYes
Main (Aleshire) Building1 is a candidate for the National Register of Historic Places. Any modifications or additions to the building must be submitted for review by the State Historic Preservation Office (SHPO) during the planning stage of the work. The site is located within a Historic District.
No
Nationally Registered Site
Site Eligible for National Register
Located in Historic District
Archaeological Significance
Earthquake Risk
Medium Low LowLow LowIBC Low
LightningEarthquake Def. Authority Flooding Tornado Hurricane Forest
Fire
Number of Deficiencies = 6
Accessible Parking: Accessible Slope:
No
Curb Cuts:
No
Ramps:
NoNo
Site Accessible Route:
GENERAL SITE CONDITION
Rating X Good Fair Poor
HISTORIC PRESERVATION
NATURAL HAZARDS
The site condition is not impacting the functional use of the facilities.
The site condition IS impacting the functional use of the facilities.
The site condition IS SIGNIFICANTLY impacting the functional use of the facilities.
Active Energy Use Reduction Program
Active Water Use Reduction Program
Approximate or Measured Waste Recycled
Use of School Dude or CMMS for Preventative Maintenance
Green Purchasing Policy Practiced
Site Stormwater Absorption Measures in Place
Center has Onsite Renewable Energy (PV or Wind)
Center has a Chartered Green Committee & Roster
Center Uses Green Cleaning Practices
SUSTAINABILITY
NO
Yes
NO
NO
NO
Yes
NO
NO
4 %
Page: 5 Date: 09/29/2015 of 5
SATELLITE SITE DESCRIPTION
Location:
Description:
Ownership Maintenance Responsibility
Nursing/Medical Assistant Building 7 is located approximately 1/4 mile northeast of Building 1. Students walk along a back street and cross two lightly traveled neighborhood feeder streets to get to Building 7
This is a single story masonry building that was formerly a restaurant and donated to the center for their use.
Center Center
Rating The site condition is not impacting the functional use of the facilities.
The site condition IS impacting the functional use of the facilities.
The site condition IS SIGNIFICANTLY impacting the functional use of the facilities.
Good Fair Poor
X
SATELLITE SITE CONDITION
Building Descriptions and Structures
BUILDING 1 - MAIN (ALESHIRE)
Building Descriptions
Page: 1 of 55
Building: 0001 - MAIN (ALESHIRE)
BUILDING ENVELOPE
Foundation RoofBuilding
Concrete Wood Wood
The exterior walls are loadbearing masonry. There are steel beams above the cafeteria and auditorium.
Brick Masonry Concrete Wood Siding
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership #Floors
A-3,A-2,R-2,B,S-1 52,100 37,202 4 Owned 1904 Candidate
Comments: This building is largely not accessible. Any renovations to the building will need to address this condition.
REAL ESTATE
Access to Building
Ramps
Entrance
2nd Egress
Visual Alarm
Corridor/Aisle
Rooms
Stairs
Elevator
Restrooms
Drinking Fountain
Telephone
No
No
No
No
Yes
Yes
Yes
No
No
No
No
No
ACCESSIBILITY
Structural Systems1.
Exterior Walls2. Number of Deficiencies = 2
Material
Asphalt shingles cover hipped ends of each wing
The main roof over the dorm rooms and corridors is rolled roofing which terminate into hipped roof structures at the ends of each wing. Gutters are residential quality and failing in places.
Metal roofing covers the main back storage wing of the building (old gym).
Drainage Year Life
Type Area Served
Asphalt Shingles
Rolled Asphalt
Metal
Gutters and Downspouts
Gutters and Downspouts
Gutters and Downspouts
Hip
Gable
Gambrel
Dorm Rooms
Dorm Rooms
Storage
Number of Deficiencies = 1
Comments:
Comments:
Comments:
3. Roof
Entire Building
Area Served
Comments:
Page: 2 of 55
Building: 0001 - MAIN (ALESHIRE)
Wall Roof None Batt/in the attic
Comments: Windows fit poorly in places and have infiltration problems. The northwest facing end windows on both wings of the end dorm rooms (on the exterior fire escape walls) have automatic metal fire shutter systems installed (8 total). These are left permanently down in these eight rooms.
INTERIOR FINISH
Carpet Ceramic Tile Concrete Vinyl Tile Wood
Drywall With Wall Paper Plaster Plastic Laminate Wainscot Tile Wood Paneling
Comments: There is a long vertical crack on the west wall on the third floor (top dorm level) of the north cental main stairwell.
Metal Unit - Metal Frame Wood Unit - Metal Frame
Wood Unit - Wood Frame
VERTICAL CIRCULATION
Concrete Stairs With Brick Veneer Dumbwaiter Metal Stairs Wood Stairs Comments: There are two main interior stairs in the front/main wing. There are two fire escapes on the end of each wing and one on the east side of the building seving the the dormitory rooms. There is a dumbwaiter to bring food from the storage area in the basement to the cafeteria kitchen on the first floor. There is a wood stair from the third floor to the cupola.
Metal Units - Metal Frame Storefront - Storefront Frame Wood Unit - Wood Frame
Awning Units - Metal Frame; Single Glazing; Double Hung - Aluminum Frame; Double Glazing;
Double Hung - Wood Frame; Double Glazing; Fixed - Metal Frame; Single Glazing;
Acoustical Tile Exposed Structure Gypsum Board Plaster
Number of Deficiencies = 1
Insulation4.
Exterior Doors5.
Windows6. Number of Deficiencies = 2
Floors1. Asbestos: Yes
Interior Walls2.
3.
Interior Doors4. Number of Deficiencies = 1
Ceilings
Page: 3 of 55
Building: 0001 - MAIN (ALESHIRE)
Mechanical
Mechanical
Mechanical
Toilet/Shower
Dorm rooms
Kitchen
Comments: Two air to air heat exhangers located in the attic provide tempered outside air to fan coils on the second and third floors. The units are Renew Air model HE2XINL/H.
Ventilation Area ServedExhaust Ventilation
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Heat is provided by two Ruud model UGRA-12ERAJS 120 MBH gas furnaces.
The second and third floors are heated with a two pipe hydronic system. The gas-fired hot water boiler is Hurst model # S45-X-50-60W and heats the building, except areas heated by gas fired furnaces and electric baseboard heaters. Energy from air exhausted from bathrooms is transferred to pre-heat outdoor air supplied to fan coils.
The classrooms and offices on the ground floor and first floor are heated and cooled by nine Carrier model 42 DDA fan coil units.
Heat is provided by two Ruud model UGRA-12ERAJS 120 MBH gas furnaces.
The electric baseboard heaters provide heating for the library area located in the attic and CPP II in the basement.
Comments:
Comments:
Comments:
Comments:
Comments:
HVAC
Heat1. Number of Deficiencies = 1
Gas-Fired Furnace
Gas-Fired Hot Water Boiler
Gas-Fired Hot Water Boiler
Gas-Fired Furnace
Electric Resistance
Single Duct
Fan Coil
Fan Coil
Single Duct
Baseboard
None
Two-Pipe
Four-Pipe
None
None
Electric
Electric
Electric
Electric
Electric
Mechanical
Mechanical
Mechanical
Mechanical
Natural
None
Heat Recovery
None
None
None
Dining Hall
Dorm Rooms
Classrooms and Offices
Auditorium
Common Area
Ventilation2. Number of Deficiencies = 1
Page: 4 of 55
Building: 0001 - MAIN (ALESHIRE)
Chiller
Split Direct Expansion (Air
Source)
Packaged Direct
Expansion (Air Source)
Chiller
Packaged Direct
Expansion (Air Source)
Split Direct Expansion (Air
Source)
Split Direct Expansion (Air
Source)
Fan Coil
Single Duct
Window Unit
Single Duct
Portable Unit
Window Unit
Single Duct
Two-Pipe
Refrigerant
None
Four-Pipe
None
None
Refrigerant
Electric
Electric
Electric
Electric
Electric
Electric
Electric
Mechanical
Mechanical
Mechanical
Mechanical
Natural
Mechanical
Mechanical
None
None
None
None
None
None
None
Dorm Rooms
Dining Hall
Kitchen
Classrooms and Offices
Electronic Equipment
Room
Offices
Auditorium
The dormitory second and third floors are cooled with a two pipe hydronic system. Two air cooled water chillers located outside the building provide cooling. One chiller is a 40 ton Dunham-Bush model ACDR035A and the other chiller is a 60 ton Carrier.
The condensing unit is a Rudd RAWD 100 CAZ.
The classrooms and offices on the ground floor and first floor are heated and cooled by nine Carrier model 42 DDA fan coil units.
Two window units serve the library on the fourth floor of the building.
Condensing unit is a Ruud model RAWD-100CAZ.
Comments:
Comments:
Comments:
Comments:
Comments:
System Type
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation Area
Served
3. Number of Deficiencies = 1Air Conditioning
Page: 5 of 55
Building: 0001 - MAIN (ALESHIRE)
Domestic hot water is provided to most of the building by three 75-gallon State model SBF7300N water heaters and a 1000 gallon storage tank. A Rheem model GPV 75 serves the kitchen.
Comments:
Cast Iron Outdoor None
Electric Water Cooler Hose Bibb Lavatory Mop Sink Multi-Compartment Sink Shower Sink Urinal Water Closet (Flush Valve)
Gas (Natural)
Wet Dry ABC Type Fire Extinguisher, K Type Fire Extinguisher, Wet
Chemical
Copper Copper Gas-Fired None Yes
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Sprinkler System Stand Pipe System Fire Suppression
PLUMBING
Water Distribution1.
Sanitary Distribution2.
Fixtures3. Number of Deficiencies = 1
Fuel Distribution4.
Number of Deficiencies = 5FIRE PROTECTION
Location UL300 Compliance Status Kitchen Compliant
UL300 COMMERCIAL KITCHEN HOOD FIRE SUPPRESSION
Page: 6 of 55
Building: 0001 - MAIN (ALESHIRE)
Comments: Electrical services to the building are provided from a pole-mounted utility-owned transformer located at the south side of the building via overhead cables and terminated in the CT cabinets. This building has multiple electrical services. There are three 600A services, which are located near each other in the ground floor electrical room and are suitably identified. One 3-phase service is used for HVAC equipment only. Each service entrance has a 600A main distribution panelboard (MDP) with 600A main circuit breaker. The MDP-1 is 120/208V, 3-phase, 4 wire system used for HVAC equipment only for this building. MDP-2 and MDP-3 are 120/240V, 1-phase, 3 wire system used for the building's loads. MDP-1 also provides power to Building 2. Both buildings are metered together in Building 1. The utility meter is located on the south exterior wall of the building.
FIRE ALARM
Comments: The central fire alarm control/annunciator panel is a Silent Knight by Honeywell model SK-5208 and the fire door panel is a Silent Knight model 5495 which are located in the security office.
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
Audible Alarm Central Fire Alarm Panel Duct Smoke Detector Flow Switch Magnetic Door Holder Manual Pull Station Smoke Detector Tamper Switch Visual Alarm
Comments: Recorded footcandle levels include natural light contribution.
Comments: The emergency lighting panel is located in the boiler room.
High Intensity Discharge (HID) Comments: Building-mounted lighting is controlled by an astronomical time clock located in the electrical room.
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
High Intensity Discharge (HID)
Offices
Corridors & Stairs
Equipment Rooms (Elec/Mech)
Toilets
Dishwashing
Food Preparation
Storage Rooms
Sleeping Rooms
Recreation
Storage/Warehouse-Active
Area Recommended Recorded Light Type
Battery Backup Battery Backup
Main Distribution Panel 120/240V, 1-Ph, 3 W, 208/120V, Panelboard Receptacles, GFCI, Switches
Emergency Exit
Number of Deficiencies = 4
ELECTRICAL SERVICES Number of Deficiencies = 1
Exterior Lighting1.
Interior Lighting2.
Emergency /Exit Lighting3.
LIGHTING
Page: 7 of 55
Building: 0001 - MAIN (ALESHIRE)
Comments: Public address system operates through the telephone system.
Connected to Main System CCTV Connected to Main System Local Cable Company
Telephone Security Public Address Television
GENERAL BUILDING CONDITION
Rating X Good
Fair Poor
COMMUNICATION
The facility condition is not impacting the functional use of the facility.
The facility condition IS impacting the functional use of the facility.
The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.
Electric Water Gas Yes YesYes
BUILDING UTILITY METERING
Structure: Good Exterior: Good Interior: Good Mechanical: Good Electrical: Good
Type Location Battery Operated
Battery Operated
Battery Operated
Stairways
Mechanical Room
Corridor
CO detectors are wall-mounted in the stairways at each floor.
CARBON MONOXIDE DETECTION
Detection Required No
Number of Deficiencies = 0
IMPAIRMENT
Potentailly Impaired
DOL Responded
DOL Determination
Potentail Impaired Comments DOL Determination Discussion/Comments
BUILDING 2 - ACADEMICS/REC (RUSSELL)
Page: 8 of 55
Building: 0002 - ACADEMICS/REC (RUSSELL)
BUILDING ENVELOPE
Foundation RoofBuilding
Concrete Structural Steel Steel
Brick Masonry Metal Siding
Wall Roof Rigid Batt
Metal Unit - Metal Frame Wood Unit - Metal Frame
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership #Floors
A-3,B 8,100 6,723 2 Owned 1976 Not Evaluated
REAL ESTATE
Access to Building
Ramps
Entrance
2nd Egress
Visual Alarm
Corridor/Aisle
Rooms
Stairs
Elevator
Restrooms
Drinking Fountain
Telephone
Yes
Yes
Yes
No
Yes
Yes
Yes
No
No
No
No
N/A
ACCESSIBILITY
Structural Systems1.
Exterior Walls2.
Insulation4. Number of Deficiencies = 1
Exterior Doors5.
Material Drainage Year Life
Type Area Served
Metal Gutters and Downspouts 2010 35 Gable Entire Building
3. Roof
Entire Building
Page: 9 of 55
Building: 0002 - ACADEMICS/REC (RUSSELL)
INTERIOR FINISH
Concrete Vinyl Tile
CMU Drywall Exposed Structure Wood Paneling
Comments: Monitor z-cracking over doors to Reading and Driver's Ed. doors in main lower corridor.
Wood Unit - Metal Frame
Mechanical Restroom
Ventilation Area Served
VERTICAL CIRCULATION
Concrete Stairs Ramp Comments: Exterior wood stairs provide access between levels; interior stairs are concrete between levels.
Double Hung - Aluminum Frame; Double Glazing;
Acoustical Tile Exposed Structure
Exhaust Ventilation
Number of Deficiencies = 1
Windows6.
Floors1. Asbestos: Yes
Interior Walls2.
3.
Interior Doors4.
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
The building is heated and cooled by three Carrier model 48TCED12A2A packaged units. Two are mounted on the roof and serve the first floor recreation area and one is mounted on grade and serves the ground floor education spaces.
Comments:
HVAC
Heat1.
Gas-Fired Packaged
Single Duct None Electronic Mechanical None Entire Building
Ventilation2.
Page: 10 of 55
Building: 0002 - ACADEMICS/REC (RUSSELL)
Domestic hot water is provided by a Bosch model AQ125FXNG gas-fired tankless water heater.Comments:
Cast Iron None None
Drinking Fountain Electric Water Cooler Hose Bibb Lavatory Sink Urinal Water Closet (Flush Valve)
Gas (Natural)
None None ABC Type Fire Extinguisher
Copper Copper Gas-Fired None No
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Packaged Direct
Expansion (Air Source)
Single Duct None Electric Mechanical None Entire Building
Sprinkler System Stand Pipe System Fire Suppression
PLUMBING
The building is heated and cooled by three Carrier model 48TCED12A2A packaged units. Two are mounted on the roof and serve the first floor recreation area and one is mounted on grade and serves the ground floor education spaces.
Comments:
System Type
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation Area
Served
Water Distribution1.
Sanitary Distribution2.
Fixtures3.
Fuel Distribution4.
Number of Deficiencies = 2FIRE PROTECTION
3. Air Conditioning
Page: 11 of 55
Building: 0002 - ACADEMICS/REC (RUSSELL)
Comments: The service entrance has a 400A wall-mounted enclosed main circuit breaker. Service for this building is provided from a 400A circuit breaker in the MDP-1 panel located in the Building 1 main electrical room. This building is metered from the meter located in Building 1.
FIRE ALARM
Comments: The fire alarm control/annunciator panel is a Silent Knight SK 5700. The monitoring signal is transferred to the central control/annunciator panel, a Fire-Lite Sensiscan 2000, located in the security room, Building 1.
Comments: The public address system operates throughout the telephone system. Speakers in some areas are utilized for public address. The phone system provides access for announcements.
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
Audible Alarm Control/Annunciator Panel Manual Pull Station Smoke Detector Visual Alarm
Connected to Main System None Connected to Main System TV with VCR
Telephone Security Public Address Television
Comments: Recorded footcandle levels include natural light contribution.
Fluorescent High Intensity Discharge (HID) Comments: Building-mounted lighting is controlled by a toggle switch located in the recreational office.
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
Offices
Corridors & Stairs
Toilets
Storage Rooms
Classrooms
Recreation
Area Recommended Recorded Light Type
Battery Backup Battery Backup
Main Circuit Breaker 120/208V, 1-Phase, 3 Wire Panelboard Receptacles, GFCI, Switches
Emergency Exit
Number of Deficiencies = 2
ELECTRICAL SERVICES
Exterior Lighting1.
Interior Lighting2.
Emergency /Exit Lighting3. Number of Deficiencies = 1
COMMUNICATION
Type Location N/A N/A
There are no sleeping rooms in this building.
CARBON MONOXIDE DETECTION
LIGHTING
Detection Required No
Number of Deficiencies = 0
Page: 12 of 55
Building: 0002 - ACADEMICS/REC (RUSSELL)
GENERAL BUILDING CONDITION
Rating X Good
Fair Poor
The facility condition is not impacting the functional use of the facility.
The facility condition IS impacting the functional use of the facility.
The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.
Electric Water Gas Yes YesZone
BUILDING UTILITY METERING
Structure: Good Exterior: Good Interior: Good Mechanical: Good Electrical: Good
IMPAIRMENT
Potentailly Impaired
DOL Responded
BUILDING 3 - ARTS AND CRAFTS
Page: 13 of 55
Building: 0003 - ARTS AND CRAFTS
BUILDING ENVELOPE
Foundation RoofBuilding
Concrete Wood Wood
CMU Masonry Metal Siding
Wall Roof Batt Batt
Metal Unit - Metal Frame Wood Unit - Metal Frame
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership #Floors
A-3,B 2,476 2,100 2 Owned 1912 Not Evaluated
REAL ESTATE
Access to Building
Ramps
Entrance
2nd Egress
Visual Alarm
Corridor/Aisle
Rooms
Stairs
Elevator
Restrooms
Drinking Fountain
Telephone
No
No
No
No
Yes
No
No
No
N/A
N/A
N/A
N/A
ACCESSIBILITY
Structural Systems1.
Exterior Walls2. Asbestos: Yes Number of Deficiencies = 1
Insulation4.
Exterior Doors5.
Material Drainage Year Life
Type Area Served
Metal Gutters and Downspouts 2008 33 Gable Entire Building
3. Roof
Page: 14 of 55
Building: 0003 - ARTS AND CRAFTS
INTERIOR FINISH
Concrete Vinyl Tile
CMU Drywall Plaster
Comments: The basement walls have been lined with black plastic.
Wood Unit - Wood Frame
Mechanical Kiln Area
Comments: A kitchen hood is used to exhaust two kilns. Captive-Aire model #4824, not in use.
Ventilation Area Served
VERTICAL CIRCULATION
Ramp Wood Stairs Comments: The vertical circulation between the ground and first floors is by exterior wood stairs.
Double Hung - Aluminum Frame; Double Glazing; Double Hung - Wood Frame; Single Glazing;
Acoustical Tile Exposed Structure Gypsum Board
Exhaust Ventilation
Windows6.
Floors1. Asbestos: Yes
Interior Walls2.
3.
Interior Doors4.
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
HVAC
Heat1.
Electric Resistance
Electric Resistance
Baseboard Convector
Unit Heater
None
None
Electric
Electric
Natural
Natural
None
None
Classrooms
Classrooms
Page: 15 of 55
Building: 0003 - ARTS AND CRAFTS
Hot water is provided by a 10 gallon electric water heater that is located under the sink in the arts and crafts area.
Comments:
PVC None None
Sink
None
None None ABC Type Fire Extinguisher, Wet Chemical
Copper Copper None None No
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Packaged Direct
Expansion (Air Source)
Window Unit Refrigerant Electric Mechanical None Classrooms
Sprinkler System Stand Pipe System Fire Suppression
PLUMBING
System Type
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation Area
Served
Water Distribution1.
Sanitary Distribution2.
Fixtures3.
Fuel Distribution4.
FIRE PROTECTION
3. Air Conditioning
Location UL300 Compliance Status N/A
UL300 COMMERCIAL KITCHEN HOOD FIRE SUPPRESSION
Page: 16 of 55
Building: 0003 - ARTS AND CRAFTS
Comments: Electrical service to the building is provided from a pole-mounted utility-owned transformer located at the south side of the building via overhead cables and terminated in the 400A main panelboard with a 300A main circuit breaker. The utility meter is located on the south exterior wall of the building.
FIRE ALARM
Comments: Fire alarm devices are connected to the Building 2 fire alarm system panel. The monitoring signal is transferred to the central control/annunciator panel, a Fire-Lite Sensiscan 2000, located in the security room, Building 1.
Comments: A public Address system operates throughout the telephone system.The phone system provides access for announcements.
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
Audible Alarm Manual Pull Station Smoke Detector Visual Alarm
Connected to Main System None Connected to Main System TV with VCR
Telephone Security Public Address Television
Comments: Recorded footcandle levels include natural light contribution.
High Intensity Discharge (HID) Comments: The building-mounted exterior light fixtures are controlled by an individual photocell.
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
Offices
Storage Rooms
Recreation
Vacant
N/A
Area Recommended Recorded Light Type
Battery Backup Battery Backup
Main Panelboard 120/208V, 3-Phase, 4 Wire Panelboard Receptacles, GFCI, Switches
Emergency Exit
Number of Deficiencies = 2
ELECTRICAL SERVICES Number of Deficiencies = 1
Exterior Lighting1.
Interior Lighting2. Number of Deficiencies = 1
Emergency /Exit Lighting3.
COMMUNICATION
Type Location N/A N/A
There is no plausible means by which harmful levels of CO could enter the building. There are no sleeping rooms in this building.
CARBON MONOXIDE DETECTION
LIGHTING
Detection Required
Page: 17 of 55
Building: 0003 - ARTS AND CRAFTS
GENERAL BUILDING CONDITION
Rating
Comments:
X Good Fair Poor
Foundation walls leak at the ground floor; interior finishes are deteriorated on both floors.
The facility condition is not impacting the functional use of the facility.
The facility condition IS impacting the functional use of the facility.
The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.
Electric Water Gas No N/AYes
BUILDING UTILITY METERING
Structure: Good Exterior: Fair Interior: Fair Mechanical: Good Electrical: Good
IMPAIRMENT
Potentailly Impaired
DOL Responded
BUILDING 4 - MAINTENANCE SHOP
Page: 18 of 55
Building: 0004 - MAINTENANCE SHOP
BUILDING ENVELOPE
Foundation RoofBuilding
Concrete Wood Wood
Brick Masonry Vinyl Siding
Comments: Z cracking at lower north wall was 1/8 IN wide at the time of the PY 15 Survey.
Wall Roof Batt Batt
Metal Overhead - Metal Frame Wood Unit - Wood Frame
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership #Floors
B,S-1 1,630 1,115 3 Owned 1912 Not Evaluated
REAL ESTATE
Access to Building
Ramps
Entrance
2nd Egress
Visual Alarm
Corridor/Aisle
Rooms
Stairs
Elevator
Restrooms
Drinking Fountain
Telephone
No
No
No
N/A
Yes
N/A
No
No
N/A
No
No
N/A
ACCESSIBILITY
Structural Systems1.
Exterior Walls2. Number of Deficiencies = 1
Insulation4.
Exterior Doors5. Number of Deficiencies = 1
Material
The estimated roof life is based on visual observation during the March 2015 Facilitiy Survey.
Drainage Year Life
Type Area Served
Asphalt Shingles Gutters and Downspouts 1990 2 Shed Entire Building
Comments:
3. Roof
Page: 19 of 55
Building: 0004 - MAINTENANCE SHOP
INTERIOR FINISH
Carpet Ceramic Tile Concrete Vinyl Tile Wood
Brick Drywall Wood Wainscot
Metal Unit - Metal Frame Wood Unit - Wood Frame
Mechanical Restroom
Ventilation Area Served
VERTICAL CIRCULATION
Metal Stairs Wood Stairs Comments: Interior wood stairs provide access between floors. Metal stairs are the fire escape from the third floor.
Double Hung - Vinyl Frame; Double Glazing;
Exposed Structure Gypsum Board Plaster
Exhaust Ventilation
Windows6.
Floors1.
Interior Walls2.
3.
Interior Doors4.
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
The furnace is a Carrier WeatherMaker (model number not available).Comments:
HVAC
Heat1.
Gas-Fired Furnace
Electric Resistance
Single Duct
Baseboard
None
None
Electric
Electric
Mechanical
Natural
None
None
Offices
Offices
Page: 20 of 55
Building: 0004 - MAINTENANCE SHOP
Domestic hot water is provided by a State model PV52ZORT8F 52-gallon water heater.Comments:
PVC None None
Electric Water Cooler Fixed Emergency Eyewash Hose Bibb Lavatory Mop Sink Sink Water Closet (Tank)
Gas (Natural)
None None ABC Type Fire Extinguisher
Copper Copper Electric None No
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Packaged Direct
Expansion (Air Source)
Window Unit None Electric Mechanical None Offices
Sprinkler System Stand Pipe System Fire Suppression
PLUMBING
System Type
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation Area
Served
Water Distribution1.
Sanitary Distribution2.
Fixtures3.
Fuel Distribution4.
FIRE PROTECTION
Page: 21 of 55
Building: 0004 - MAINTENANCE SHOP
Comments: Electrical service to the building is provided from a pole-mounted utility-owned transformer located at the west side of the building via overhead cables and terminated in the 200A main panelboard with a 200A main circuit breaker. The utility meter is located on the west exterior wall of the building.
FIRE ALARM
Comments: Fire alarm devices are connected to the Building 3 and then to Building 2 fire alarm system panel. The monitoring signal is transferred to the central control/annunciator panel, Fire-Lite Sensiscan 2000, located in the security room, Building 1.
Comments: A public address system operates through the telephone system.
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
Audible Alarm Heat Detector Manual Pull Station Smoke Detector Visual Alarm
Connected to Main System None None None
Telephone Security Public Address Television
Comments: Recorded footcandle levels include natural light contribution.
None
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
Offices
Equipment Rooms (Elec/Mech)
Toilets
Storage Rooms
Maintenance Shop
Area Recommended Recorded Light Type
Battery Backup Battery Backup
Main Panelboard 120/240V, 1-Phase, 3 Wire Panelboard Receptacles, GFCI, Switches
Emergency Exit
ELECTRICAL SERVICES Number of Deficiencies = 1
Exterior Lighting1.
Interior Lighting2.
Emergency /Exit Lighting3.
COMMUNICATION
Type Location N/A N/A
There are no plausible means by which harmful levels of CO could enter the building. There are no sleeping rooms in this building.
CARBON MONOXIDE DETECTION
LIGHTING
Detection Required Yes
Page: 22 of 55
Building: 0004 - MAINTENANCE SHOP
GENERAL BUILDING CONDITION
Rating X Good
Fair Poor
The facility condition is not impacting the functional use of the facility.
The facility condition IS impacting the functional use of the facility.
The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.
Electric Water Gas Yes YesYes
BUILDING UTILITY METERING
Structure: Good Exterior: Good Interior: Good Mechanical: Good Electrical: Good
IMPAIRMENT
Potentailly Impaired
DOL Responded
BUILDING 4A - MAINTENANCE STORAGE
Page: 23 of 55
Building: 0004A - MAINTENANCE STORAGE
BUILDING ENVELOPE
Foundation RoofBuilding
Concrete Wood Wood
Vinyl Siding
Wall Roof None None
Metal Rollup - Metal Frame Wood Unit - Wood Frame
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership #Floors
S-1 770 700 2 Owned 1994 Not Evaluated
REAL ESTATE
Access to Building
Ramps
Entrance
2nd Egress
Visual Alarm
Corridor/Aisle
Rooms
Stairs
Elevator
Restrooms
Drinking Fountain
Telephone
No
No
No
N/A
Yes
N/A
No
No
N/A
N/A
N/A
N/A
ACCESSIBILITY
Structural Systems1.
Exterior Walls2.
Insulation4.
Exterior Doors5.
Material Drainage Year Life
Type Area Served
Metal Gutters and Downspouts 1994 19 Gable Entire Building
3. Roof
Page: 24 of 55
Building: 0004A - MAINTENANCE STORAGE
INTERIOR FINISH
Ceramic Tile Concrete
Drywall Exposed Structure
None
Natural Entire Building
Ventilation Area Served
VERTICAL CIRCULATION
Wood Ladder Wood Stairs Comments: There is a wood ladder that provides access to the loft storage area.
None
None None None None Natural None Entire Building
Acoustical Tile Gypsum Board
Exhaust Ventilation
Windows6.
Floors1.
Interior Walls2.
3.
Interior Doors4.
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
HVAC
Heat1.
None None None None Natural None Entire Building
Ventilation2.
System Type
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation Area
Served
Page: 25 of 55
Building: 0004A - MAINTENANCE STORAGE
None None None
None
None
None None ABC Type Fire Extinguisher
Comments: Electrical service to the building is provided from a pole-mounted utility-owned transformer located at the west side of the building via overhead cables and terminated in the 200A main circuit breaker located on the west exterior wall. The utility meter is located on the west exterior wall of the building.
None None None None No
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
Comments: Recorded footcandle levels include natural light contribution.
None
T8 - Fluorescent60Storage/Warehouse-Active 30
Area Recommended Recorded Light Type
Battery Backup None
Main Circuit Breaker 120/240V, 1-Phase, 3 Wire Branch Panel Only Receptacles, Switches
Sprinkler System Stand Pipe System Fire Suppression
Emergency Exit
PLUMBING
Water Distribution1.
Sanitary Distribution2.
Fixtures3.
Fuel Distribution4.
Number of Deficiencies = 1FIRE PROTECTION
ELECTRICAL SERVICES
Exterior Lighting1.
Interior Lighting2.
Emergency /Exit Lighting3.
Page: 26 of 55
Building: 0004A - MAINTENANCE STORAGE
FIRE ALARM
Comments: The fire alarm control/annunciator panel is a Fire Lite Alarms MP-12/24. The monitoring signal is transferred to the central control/annunciator panel, a Silent Knight SK 5208, located in the security room, Building 1.
Audible Alarm Control/Annunciator Panel Heat Detector Manual Pull Station Smoke Detector Visual Alarm
None None None None
Telephone Security Public Address Television
Number of Deficiencies = 1
GENERAL BUILDING CONDITION
Rating X Good
Fair Poor
COMMUNICATION
The facility condition is not impacting the functional use of the facility.
The facility condition IS impacting the functional use of the facility.
The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.
Electric Water Gas N/A N/AYes
BUILDING UTILITY METERING
Structure: Good Exterior: Good Interior: Good Mechanical: Good Electrical: Good
Type Location
CARBON MONOXIDE DETECTION
Detection Required No
Number of Deficiencies = 0
IMPAIRMENT
Potentailly Impaired
DOL Responded
BUILDING 5 - TRANSITIONAL LIVING (WARREN HOUSE)
Page: 27 of 55
Building: 0005 - TRANSITIONAL LIVING (WARREN HOUSE)
BUILDING ENVELOPE
Foundation RoofBuilding
Masonry Wood Wood
Brick Masonry Concrete Vinyl Siding
Wall Roof Batt Batt
Wood Unit - Wood Frame
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership #Floors
R-2 4,130 2,541 2 Owned 1923 Not Evaluated
REAL ESTATE
Access to Building
Ramps
Entrance
2nd Egress
Visual Alarm
Corridor/Aisle
Rooms
Stairs
Elevator
Restrooms
Drinking Fountain
Telephone
No
No
No
No
Yes
No
No
Yes
N/A
No
N/A
N/A
ACCESSIBILITY
Structural Systems1.
Exterior Walls2. Number of Deficiencies = 1
Insulation4.
Exterior Doors5.
Material Drainage Year Life
Type Area Served
Metal Gutters and Downspouts 2008 33 Gable Entire Building
3. Roof
Page: 28 of 55
Building: 0005 - TRANSITIONAL LIVING (WARREN HOUSE)
INTERIOR FINISH
Carpet Ceramic Tile Concrete
Brick CMU Ceramic Tile Drywall
Wood Unit - Wood Frame
Mechanical Toilet/Shower
Ventilation Area Served
VERTICAL CIRCULATION
Metal Stairs Wood Stairs Comments: Interior wood stairs provide circulation between floors. Metal stairs are fire escapes.
Double Hung - Aluminum Frame; Double Glazing;
Exposed Structure Gypsum Board
Exhaust Ventilation
Windows6.
Floors1. Asbestos: Yes
Interior Walls2.
3.
Interior Doors4.
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Heat is provided by an H.B. Smith hot water boiler model number GB100-W-A10COND . There are 9 circulating pumps for the building.
Comments:
HVAC
Heat1. Number of Deficiencies = 1
Gas-Fired Hot Water Boiler
Radiator Two-Pipe Electric Mechanical None Entire Building
Page: 29 of 55
Building: 0005 - TRANSITIONAL LIVING (WARREN HOUSE)
Domestic hot water is provided by a Ruud gas-fired hot water heater, model GBV 75-75E, rated at 75 gallons storage…