SIERRA NEVADA
Job Corps Center
Reno, NV
Facility Planning Report Volume II
Supporting Data
Final December 2014
Department of Labor/ Office of Job Corps
SIERRA NEVADA
Job Corps Center
Reno, NV
Facility Planning Report Volume II
Supporting Data
Final December 2014
Support Services Building 29
VOLUME I - PLANNING STRATEGY
Acronyms and Abbreviations Defi nition of Terms Executive Summary Exsting Site Plan Center Statistics Facility Survey Assement Results and Recommentdations
1.0 INTRODUCTIONS
• Objective and Scope
• Report Contents
2.0 EXISTING CONDITIONS
• Background
• Ownership
• General Site Conditions
• General Building Conditions
• Preventive Maintenance
• Facility Assessment by Function
• Environmental Management
• Resource Use/Conservation
• Sustainability
• Accessibility Standards
• Completed and Current Projects
• Health and Life Safety Issues
• Defi ciency Summary
3.0 PLANNING ANALYSIS
• Space Utilization Analysis
• Federal Real Property Assest Management
• Defi ciency Analysis
• Facility Condition Summary
• Building Condition by Function
• Planning Analysis Results and Conculsions
3.0 RECOMMENDATIONS
• Status of Previous Plan
• Proposed Plan
• Funded Not Corrected (FNC) Defi ciencies
• Summary of Proposed Plan
• Proposed Site Plan - Near Term
• Proposed Site Plan - Long Term
• Implementation Plan
• Summary List of National Projects
• Project Data Sheets
VOLUME II - SUPPORTING DATA
Acronyms and Abbreviations Defi nition of Terms Executive Summary
1.0 SITE LAYOUT AND PLANS
• Location Map
• Exisiting Site Plan
2.0 DESCRIPTIONS
• Buildings and Structures
• Space Utilization By Function
• NSF by Building
• Environmental Management Report
• Asbestos Report
• Radon Report
• Site Descriptions
• Building Descriptions
3.0 DEFICIENCIES
APPENDICES - CORRESPONDENCE AND REPORTS
Appendix A.
• Center Review Meeting Minutes
• Survey Brief
• Student Questionnaire
Appendix B.
• Life Safety Defi ciencies and List
Appendix C.
• O&M Defi ciencies List
Appendix D.
• Active Warranty List
Appendix E.
• FRPC Performance Measures Matrix
Acronyms and Abbreviations
ACRONYMS AND ABBREVIATIONS
A Amperage ABAAS Architectural Barriers Act Accessibility Standard ACM Asbestos-Containing Materials AFUE Annual Fuel Utilization Efficiency AHU Air Handling Unit ANSI American National Standards Institute ARRA American Recovery and Reinvestment Act of 2009 BTU British Thermal Units\ CAA Clean Air Act CCF Hundred Cubic Feet CCTV Closed Circuit Television CDC Child Development Center CDC Centers for Disease Control and Prevention CDP Career Development Period CDSS Career Development Service System CFL Compact Fluorescent Light Bulbs CFM Cubic Feet per Minute CIS Center Information System CMA Certified Medical Assistant CMMS Computerized Maintenance Management System CMU Concrete Masonry Unit CAN Certified Nursing Assistant CO Carbon Monoxide CO Contracting Officer COR Contracting Officer’s Representative CPP Career Preparation Period CRA Construction, Rehabilitation, and Acquisition CTP Career Transition Period CTS Career Transition Services
CTST Career Technical Skills Training (formerly Vocational Skills Training [VST])
CW Cold Water CWA Clean Water Act DDC Direct Digital Controls DFAM Division of Facilities and Asset Management DOL Department of Labor EISA Energy Independence and Security Act of 2007 EMT Emergency Medical Technician
EMT Electrical Metal Tubing (Conduit) EO Executive Order EPA U.S. Environmental Protection Agency EPCRA Emergency Planning and Community Right-to-Know Act (1986) EPMD Ethylene Propylene Diene Terpolymer ESC Engineering Support Contractor ESCIS Engineering Support Contractor Information System ESL English as a Second Language oF Degrees Fahrenheit FACP Fire Alarm Control/Annunciator Panel fc Foot Candle FNC Funded Not Corrected FOP Financial Operating Plan FRPC Federal Real Property Council FY Fiscal Year GAO General Accounting Office GED General Educational Development GFCI Ground Fault Circuit Interrupter gph Gallons per Hour GSA General Services Administration GSF Gross Square Feet HID High Intensity Discharge HP Horsepower HSD High School Diploma HTW Hazard and Toxic Waste HVAC Heating, Ventilating, and Air Conditioning HW Hot Water IBC International Building Code IMC International Mechanical Code ION Inventory of Needs IPC International Plumbing code KBTU Thousand British Thermal Unit/Gross Square Foot/Year kV Kilovolt kVA Kilovolt-Amps kw Kilowatt JCC Job Corps Center JCDC Job Corps Data Center JCH Job Corps Handbook kWh Kilowatt Hours LAN Local Area Network LED Light Emitting Diode LF Linear Feet MBH Thousand BTUs per Hour MBTU Thousand British Thermal Unit MWH Megawatt Hour MC Mission Critical MCF Million Cubic Feet MDNC Mission Dependent, Not Critical MDP Main Distribution Panel MLO Main Lug Only m/s Meters/Second MTS Manual Transfer Switch NEC National Electric Code NEMA National Electrical Manufacturers Association NEPA National Environmental Protection Act NFPA National Fire Protection Association NMD Not Mission Dependent NSF Net Square Feet OA Outreach and Admissions OBS On Board Strength OCM Office of Contract Management OIG Office of Inspector General O&M Operations and Maintenance OSHA Occupational Safety and Health Administration PA Public Address pCi Picocurie PV Photovoltaic PVC Polyvinyl Chloride RCRA Resource Conservation and Recovery Act RTU Rooftop Unit SGA Student Government Association SHPO State Historic Preservation Office SF Square Feet SPCC Spill Prevention, Control and Countermeasure SST Social Skills Training T5 Fluorescent Lighting Designation (High Efficiency)
T8 Fluorescent Lighting Designation T12 Fluorescent Lighting Designation (Low Efficiency TSCA Toxic Substances Control Act of 1976 TV Television TVSS Transient Voltage Surge Suppression UEV Unevaluated UFAS Uniform Federal Accessibility Standards UL Underwriters Laboratories USDA U. S. Department of Agriculture V Volt VCR Video Cassette Recorder VST Vocational Skills Training W Watt WAN Wide Area Network WBL Work-Based Learning WIA Workforce Investment Act WIB Workforce Investment Board
Defi nition of Terms
DEFINITION OF TERMS
Accessibility: The degree to which a product, device, service, or environment is available to as many people as possible. Accessibility can be viewed as the "ability to access" and benefit from some system or entity. The Federal Government is required to comply with published law (Architectural Barriers Act (ABA) of 1968 , American Disabilities Act of 1990), regulations and related standards. Accessibility laws and standards have evolved over the past 12 years. DOL now follows ABA Accessibility Standards for Federal Facilities (ABAAS) adopted by the General Services Administration.
Annual Operating Cost: This FRPC performance measure reflects the cost to operate each used asset and consists of lease costs as well as costs related to recurring maintenance, utilities, janitorial, and roads and grounds expenses (Source: FRPC 2012).
Building: In accordance with the FRPC 2012 Guidance for Real Property Inventory Reporting, a building includes an enclosure for human occupancy that serves a variety of functions (food service, education, recreation, medical/dental, storage, administration) and is likely to have full utility services (heating, cooling, etc.). A building typically is over 400 square feet.
Building Condition Rating by Function: Each building is assigned a building condition based on the physical condition of the building and the impact on the functional use of the facility. Three ratings are possible:
Good: The facility condition is not impacting the facility function. A facility can have deficiencies and still be considered good.
Fair: The facility condition is impacting the facility function and deficiencies are limited to less than 30% of the replacement value. Correction of the deficiencies would allow the facility to return to a good status.
Poor: The facility condition is significantly impacting the facility function and/or deficiencies are more than 30% of the replacement value. Generally a poor rating indicates a “gut renovation or total replacement/demolition would be required.
Building/Structure Ratings: Each building is rated according to three ratings (good, fair, and poor) based on evaluations of the structure, exterior, interior, mechanical, and electrical elements. Three ratings are possible:
Good: The facility condition is not impacting the facility function. A facility can have deficiencies and still be considered good.
Fair: The facility condition is impacting the facility function and deficiencies are limited to less than 30% of the replacement value. Correction of the deficiencies would allow the facility to return to a good status.
Poor: The facility condition is significantly impacting the facility function and/or deficiencies are more than 30% of the replacement value. Generally a poor rating indicates a “gut renovation or total replacement/demolition would be required
Construction Type: The International Building Code (IBC) construction classifications include the following:
Type I and II. Those types of construction in which building elements are of noncombustible materials, except as permitted in Section 603 and elsewhere in the code.
Type II and III. Any type of construction where the exterior walls are of noncombustible material and the interior building elements are of any material permitted by the code.
Type IV. This type (heavy timber, HT) is where the exterior walls are of noncombustible material and the interior building elements are of solid or laminated wood without concealed spaces.
Type V. That type of construction where structural elements, exterior walls, and interior walls are of any materials permitted by the code.
Contract Strength: The authorized number of students at a Center in accordance with the contract between the Region and Center Operator.
Deficiency: A deficiency at a Center represents the spectrum of conditions related to the Center’s mission and/or its physical, functional, or operational features do not meet related goals, standards, codes, or other measures of acceptability. Each deficiency at a JCC or CCC initially is categorized as one of the following three deficiencies: Program, Site, or Building:
Program: Program deficiencies address issues such as square footage shortages or the omission of amenities required or standard for the proper operation of a particular Job Corps function.
Site: Site deficiencies indicate adverse site and infrastructure conditions which negatively impact operations and environment (e.g., site lighting, sidewalks, roads, etc.)
Building: Building deficiencies indicate adverse conditions at the building level.
This element includes the substructure, shell, interior, services (plumbing, HVAC, fire protection, and electrical), and equipment and furnishings.
Deficiency Classifications (I to IV): Deficiency classifications are defined as follows:
Class IA - Deficiencies which address imminent life safety and health hazards.
Class II - Deficiencies which address code violations, however, do not represent imminent life safety and health hazards.
A - Deficiencies which violate code (Federal, State or Local) and may result in an interruption of center operations if not corrected.
B - Deficiencies which violate code (Federal, State or Local) and have no immediate impact on center operations if not corrected.
C- Deficiencies which are not in compliance for accessibility in accordance with the Architectural Barriers Act (ABA), Americans with Disabilities Act (ADA), Uniform Federal Accessibility Standards (UFAS), or other applicable standards.
Class III - Deficiencies which address facility repair, replacement or maintenance.
A - Deficiencies which if not corrected may result in an interruption of center operations.
B - Deficiencies which if not corrected will have minimal impact on center operations or can be mitigated through temporary measures until the deficiency is corrected.
Class IV – Deficiencies which address programmatic needs.
A - Deficiencies which if corrected produce substantial improvements in the quality of the learning and living environment.
B - Deficiencies which if corrected are desirable enhancements.
Deficiency Funding Status: The status of the deficiency included the following categories:
Funded deficiencies report indicates the funding year for funded Regional projects, which have dollar amounts shown, or deficiencies assigned to funded National and Regional projects without dollar amounts. Major Regional projects are equivalent to National projects but assigned to the Federal agency (e.g., U.S.
Department of Agriculture) that acts as the Center operator. All operations and maintenance (O&M) deficiencies are treated as funded through the Center Operators O&M contract within the Region.
Proposed deficiencies have been assigned to a proposed future National project.
Unfunded deficiencies are Regional projects unless or until they are assigned to a National project.
Deficiency Status: The deficiency status is tracked and updated during the three-year facility survey cycle, or as such deficiencies are corrected and reported. The status includes:
Uncorrected: Once a deficiency is identified, documented, reported, and assigned for correction, the deficiency remains uncorrected until such time that the deficiency is corrected, reported, and verified.
Corrected: A corrected deficiency is one that has been assigned, funded, corrected, reported, and verified. Typically, the ESC verifies completion of the deficiency through the facility survey or site visit. The Center also may report completion and provide verifiable evidence of the correction, subject to review by the ESC.
Funded Not Corrected: A deficiency that has been approved and authorized as a regional project through the CRA budget, emergency or supplemental funding, or the Life Safety Memo. Note: the funding may not have reached the Center yet as the first steps are a FOP allocation by the National Office and a contract modification by the Region.
No Longer Needed: A no longer needed deficiency is one that has been approved and funded as a Regional project, but due to subsequent circumstances, has been reported by the Center as no longer being required to be accomplished. This type of deficiency is verified and confirmed by the ESC and removed from the Funded Not Corrected deficiency category. The Center should take action with its Region to return the funds.
Facility Condition Index: This performance measure reflects the condition of each asset by comparing the current repair needs to the replacement value of the asset. The index is expressed as a percentage, with 100% being a facility with no repair needs.
Gross Square Foot: The sum of all areas on all floors of a building included within the outside faces of its exterior walls, including all vertical penetration areas, for circulation and shaft areas that connect one floor to another. Gross Area is computed by physically measuring or scaling measurements from the outside faces of exterior walls, disregarding cornices, pilasters, buttresses, etc., that extend beyond the wall faces. Exclude areas having less than a 3-foot clear ceiling height unless the criteria of a separate structure are met. Measured in terms of Gross Square Feet (GSF): GSF = Net Usable Area + Structural Space (Source: http://nces.ed.gov/pubs2006/ficm/).
Mission Dependency: The value an asset brings to the performance of the mission as determined by the governing agency. Specific elements of this category include (FRPC 2012):
Mission Critical - – Without constructed asset or parcel of land, mission is compromised.
Mission Dependent, Not critical (MDNC) - Does not fit into Mission Critical or Not Mission Dependent categories.
Not Mission Dependent (NMD) – Mission unaffected
Ownership (Owned vs Leased): If the property is owned, the Federal Government has fee simple interest for the real property asset. If the property is leased, the rights to use the asset are assigned to the Federal Government by a private entity or a non-Federal Government entity for a defined period of time in return for rental payments (FRPC 2012).
National Project: Generally large and complex projects that require professionally prepared drawings and specifications that are time phased (design and construction) and contracted by the DOL National Office.
Net Square Foot: The sum of all areas on all floors of a building assigned to, or available for assignment to, an occupant or specific use. This value is computed by physically measuring or scaling measurements from the inside faces of surfaces that form the boundaries of the designated areas. Exclude areas having less than a 3-foot clear ceiling height unless the criteria of a separate structure are met. Included should be major space use categories for assignable space (e.g., dormitories, education, recreation, etc.) that are used to accomplish the institution’s mission. Net Square foot: NASF = Sum of Areas Designated by the Major Space Use Categories (Source: http://nces.ed.gov/pubs2006/ficm/).
On Board Strength (OBS): The actual number of students on Center on a day to day basis.
Preventive Maintenance: The care and servicing by personnel for the purpose of maintaining equipment and facilities in satisfactory operating condition by providing for systematic inspection, detection, and correction of incipient failures either before they occur or before they develop into major defects (Source: Dictionary of Military and Associated Terms, US DOD 2005).
Property Type: Indicates the asset as one of the following categories of real property:
land, building, structure.
Property Use: Since the elements defined by the FRPC do not match the space use codes employed in ESCIS, a mapping procedure will be created to align the definitions.
In the report, the Federal Real Property Council (FRPC) classifications will be printed for display. The information is available through the property registration field of Engineering Support Contractor Information System (ESCIS), and the current ESCIS designations will be correlated to the FRPC designations as follows:
ESCIS FRPC
Dormitory Dormitories/Barracks Food Service Other Institutional Uses Education School Recreation Other Institutional Uses Medical/Dental Other Institutional Uses Storage Warehouse Administration Office Structure * Storage, Service, Utility
Systems, or Other Land Institutional
* Each structure will be entered manually from the ESCIS database into one of four FRPC categories listed opposite the term “structure”.
Replacement Value: The cost of replacing the existing constructed asset at today’s building standards. It is the amount required to construct an asset of similar size and in the same location at today’s construction standards. The replacement value reported must be greater than zero (FRPC 2012).
Regional Office Project: Generally smaller projects where the funds will be transferred to the region for center execution.
Structure: In accordance with the FRPC 2012 Guidance for Real Property Inventory Reporting, a structure serves to provide storage, service, utility systems and is not likely to have full utilities (heating, cooling, etc.). A structure typically is less than 400 square feet.
Sustainability: Formally known as the World Commission on Environment and Development, the Brundtland Commission's mission in the 1980s was to unite countries to pursue sustainable development. The Commission defined sustainability as the “development which meets the needs of current generations without compromising the ability of future generations to meet their own needs".
Sustainability also is defined as the creation or enhancement of environmental, economic, and social-cultural balance, as realized through business activities, individual actions, and community engagement. Sustainability addresses approaches, methods and practices that optimize the use of energy, water, and materials while reducing greenhouse gas emissions.”
Utilization: This performance measure assesses the degree to which each asset is utilized and is expressed as a percentage. It is calculated on a square footage basis, comparing the square footage used to the “design square footage” based on contract strength (Source: FRPC 2012).
Executive Summary
The facility survey for Sierra Nevada Job Corps Center was completed during April 9-18, 2014. The information presented in Volume II, Supporting Data, represents the current status of the campus.
The information includes the following:
Existing site layout Overall status of existing building and structures Space utilization by building and function compared to recommended standards Status of environmental elements of the Center’s operations Details on the site and buildings and structures based on architectural, electrical, and mechanical survey and supporting documentation Presentation of the status of historical deficiencies and compilation of deficiencies documented through this survey Supporting documentation, as presented in the appendices of the center review meeting; survey brief and student questionnaire; life safety IA/IIA transmittal;
active warranties; and Federal Real Property Council (FRPC) Measures Matrix
Section 1.0 of this volume addresses site layout and plans while Section 2.0 presents details on the buildings and structures. Section 3.0 presents historic deficiencies and their status as well as new ones identified in this survey. The appendices provide additional information as noted below:
Appendix A. Survey Brief Questionnaire Appendix B. Life Safety Deficiencies and List Appendix C. O&M Deficiencies List Appendix D. Active Warranty Report Appendix E. FRPC Performance Measures Matrix
EXECUTIVE SUMMARY
1.0 - Site Layout and Plans
SIERRA NEVADA
JOB CORPS CENTER
RENO, NEVADA
SIERRA
NEVADA JCC
10 MI5 0
2.0 - Descriptions
2.0 DESCRIPTIONS
In this section, the following information on the Center and its buildings and structures is presented in tabular format:
Building and Structures – This table indicates the building type, asset number, name, use group, gross square footage (GSF), construction year, number of floors, number of sleeping room and number of beds, construction type (noted as numerical values instead of code-specified Roman numerals), status (active or closed), and overall condition. The possible International Building Code (IBC) construction classifications include the following:
Type I and II. Those types of construction in which building elements are of noncombustible materials, except as permitted in Section 603 and elsewhere in the code.
Type III. This type of construction is where the exterior walls are of noncombustible material and the interior building elements are of any material permitted by the code.
Type IV. This type (heavy timber, HT) is where the exterior walls are of noncombustible material and the interior building elements are of solid or laminated wood without concealed spaces. Fire-retardant-treated wood framing complying with IBC section 2303.2 shall be permitted within exterior wall construction with a 2-hour rating or less.
Type V. That type of construction where structural elements, exterior walls, and interior walls are of any materials permitted by the code.
The overall building/structure condition is rated in one of three categories: good, fair, or poor.
Space Utilization by Function - This table compares the DOL recommended net square footage per enrollee and for the total function (e.g., housing, education, food service, recreation, medical/dental, administration, storage/support) to the actual values.
Net Square Footage by Building - This table compares the DOL recommended net square footage for the buildings with the function (e.g., housing, education, food service, recreation, medical/dental, storage/support) to the actual values and presents a percentage difference in the two values. In some instances, a recommended value is not available for sub-elements of a function; therefore, the recommended value is shown as “0”.
Environmental Management Report – This table summarizes regulatory related solid and hazardous waste information in accordance with the Resource Conservation and Recovery Act (RCRA) and the presence or absence of hazardous material storage facilities in accordance with Emergency Planning and Community Right-to-Know Act of
1986 (EPCRA). An inventory of petroleum storage tanks is noted as well as asbestos and polychlorinated biphenyls (PCBs) in accordance with the Clean Water Act (CWA) and Toxic Substance Control Act (TSCA), respectively. In addition, this report statuses air quality as required under the Clean Air Act (CAA).Any radon testing of buildings also is documented.
Site Descriptions – Tabular information is documented for the site. Among the data presented are the topography; total number of buildings and structures; roads, parking and sidewalks; fencing; site utilities; storage tanks; accessibility; historic preservation;
natural hazards; and sustainability. The overall condition of the site is rated in one of three categories: good, fair, or poor.
Building Descriptions – Tabular information, as well as photographs and floor plan drawings, are provided for each building or structure, as appropriate, in the following categories: real estate; accessibility; building envelope; interior finishes; vertical circulation; heating, ventilation and air conditioning (HVAC); plumbing; fire protection;
electrical services; fire alarms; carbon monoxide detection; communication; and building metering. The overall condition of the building and its five key subsystems (structure, exterior, interior, mechanical, and electrical) are rated in one of three categories: good, fair, or poor. If applicable, recommendations for renovation or demolition are provided.
BUILDINGS AND STRUCTURES
00907 SIERRA NEVADA 12/04/2014
1Page: of Date:
0001 - ADMINISTRATION
0002 - EDUCATION 1 (ED-1)
0003 - EDUCATION 2 (ED-2)
0004 - HEALTH SERVICES/WELLNESS
0005 - STUDENT SERVICES & SECURITY
0006 - VOCATION (A)
0007 - VOCATION (B)
0008 - VOCATION (C)
0010 - CULINARY ARTS/HOSPITALITY
0011 - DONNER HALL DORMITORY
0015 - WASHOE HALL - CO-ED DORM
0016 - SECURITY VOCATION
0018 - LASSEN HALL/ FEMALE
DORMITORY
0019 - COMSTOCK HALL-MEN'S DORM
0020 - FREMONT HALL-MEN'S DORM
0021 - CARSON HALL-MEN'S DORM
0022 - CAFETERIA
0023 - CENTER DUTY OFFICER
0025 - RECREATION
0026 - GYMNASIUM
0029 - SUPPORT SERVICES BUILDING
0030B- VOCATIONAL STORAGE
0031 - THEATRE
0019A - GAZEBO (35Ft x 20Ft) 0022A - GAZEBO (10Ft x 10Ft) 0022B - GAZEBO (10Ft x 10Ft) 0022C - GAZEBO (24Ft x 10Ft) 0026A - IRRIGATION SHED (10Ft x 6Ft) 0026B - RECREATION STORAGE #1 (8Ft x 6Ft)
0026C - RECREATION STORAGE #2
(10Ft x 8Ft) 0027 - VACUUM MAINTENANCE (16Ft x 16Ft) 0027A - SECURITY STORAGE (14Ft x 8Ft) 0028B - GAZEBO (20Ft x 10Ft) 0030C- PLASTERING STORAGE (14Ft x 14Ft) 0030D- CTST STORAGE (82Ft x 19Ft) 0030E - WELDING STORAGE (8Ft x 8Ft) 0030F - CEMENT STORAGE (10Ft x 8Ft) 0039 - VALVE HOUSE (14Ft x 11Ft) 0040A - GAZEBO (10Ft x 10Ft) 0040B - GAZEBO (24Ft x 8Ft) 0040C - GAZEBO (16Ft x 8Ft) 0042 - TRELLIS (15Ft x 10Ft) 0043 - RESIDENTIAL STORAGE (7Ft x 7Ft)
Name GSF
8,623 20,942 11,035 5,770
16,472 8,171 8,564
19,327 11,000 21,920 21,920 1,710
16,920
16,920 16,920 16,920 20,130
3,560 15,150 10,600 15,600 2,190 5,090
1,558
Active Active Active Active Active Active Active Active Active Active Active Active Active
Active Active Active
Demolition Approved
Active Active Active Active Active Active Active Active Active Active Active Active
Active
Active
Active Active Active
Active Active Active Active Active Active Active Active Active
StatusType
Building Building Building Building Building Building Building Building Building Building Building Building Building
Building Building Building Building
Building Building Building Building Building Building Structure Structure Structure Structure Structure Structure
Structure
Structure
Structure Structure Structure
Structure Structure Structure Structure Structure Structure Structure Structure Structure
Use Group Built Flrs Const
Business Business Business Business Business Business Business Business Business Residential Residential Business Residential
Residential Residential Residential Assembly
Business Assembly Assembly Factory/Ind.
Business Assembly Assembly Assembly Assembly Assembly Utility/Misc.
Storage
Storage
Storage
Business Assembly Storage
Storage Storage Business Utility/Misc.
Assembly Assembly Assembly Assembly Storage
Good Good Good Good Good Good Good Good Fair
Good Good Good Good
Good Good Good Fair
Good Good Good Good Good Fair
Good Good Good Good Good Good
Good
Good
Good Good Good
Good Good Good Good Good Good Good Good Good
ConditionAsset Number
0090708025 0090708026 0090708027 0090708007 0090708028 0090708029 0090708030 0090708031 0090700006 0090700007 0090700008 0090700035 0090700009
0090700010 0090700011 0090700012 0090700013
0090700014 0090708032 0090700015 0090708005 0090700037 0090700019 0090708019 0090700065 0090700068 0090708012 0090700056 0090708047
0090708048
0090700041
0090708049 0090708013 0090700043
0090700044 0090708045 0090708046 0090700033 0090708014 0090708015 0090708016 0090708021 0090708022
BUILDINGS AND STRUCTURES
00907 SIERRA NEVADA 12/04/2014
2Page: of Date:
23 295,454
20 4,576
43 300,030
Buildings
Structures
Total
GSF
GSF
GSF
Summary
12/04/2014
Space Utilization By Function 00907 Sierra Nevada Page: 1 of Date:
HOUSING
EDUCATION
FOOD SERVICE
SUGGESTED
NSF/
ENROLLEE
SUGGESTED
TOTAL
NSF
ACTUAL
TOTAL
NSF
TYPE OF SPACE
SUB TOTAL
SUB TOTAL
SUB TOTAL
Resident Men Resident Women Total Residents
Residents 545 Non Residents 25
570Total Students
(545)
(570)
(570)
DIFFERENCE
58,860
44,400
10,260
79,945
70,349
13,571
Lounge Other Shower/Toilet Sleeping excl. SPD( rooms; beds) Storage
Academic (570) Non-Academic
30 -- ACT (Off-Ctr) 40 -- Auto Repair Tech/Helper + 90 -- Business Office Technologies 40 -- Carpentry + 20 -- Cement Masonry + 40 -- Culinary Arts + 24 -- Electrical + 24 -- Facilities Maint. and Const. + 90 -- Health Occupations + 30 -- Hotel Management 24 -- Maintenance Engineer + 20 -- Painting + 20 -- Plastering + 24 -- Plumbing + 20 -- Security Officer 24 -- Welding +
Vocational Theory (390)
Dining (2 Servings) Food Preparation Food Storage
4,590 6,150
11,253 54,177
3,775
8,918 12,640
2,480 4,100 2,907 3,260 5,725 2,546 3,054 3,835 1,798 2,539 2,184 3,260 2,574
4,421
3,245
5,051 4,728 3,792
5,450 4,360 6,540
39,240 3,270
5,700 5,700
3,000 3,600 3,000 1,500 2,400 1,200 1,800 3,600 1,200 1,200 1,500 1,500 1,200
1,800
3,900
4,560 3,420 2,280
-860 1,790 4,713
14,937
3,218 6,940
-520 -93
1,760 3,325 1,346 1,254
1,339
1,760 1,374
2,621
-655
1,308 1,512
Vocations
21,085
25,949
3,311
Page: 2 of Date:
RECREATION
MEDICAL/DENTAL
ADMINISTRATION
STORAGE/SUPPORT
VACANT
SUGGESTED
NSF/
ENROLLEE
SUGGESTED
TOTAL
NSF
ACTUAL
TOTAL
NSF
TYPE OF SPACE
SUB TOTAL
SUB TOTAL
SUB TOTAL
SUB TOTAL
SUB TOTAL
TOTAL 293.14 167,090 216,967
(570)
(570)
(570)
(570)
(0)
DIFFERENCE
27,625
3,145
11,400
23,289
4,150
8,405
14,098
3,160
Aerobics/Exercise Arts & Crafts Computer Lab Concession Stand/Restroom Gymnasium Lounges Miscellaneous Recreation Multipurpose Room Recreation Office Recreation Storage Theater Weight Room
Medical/Dental
Administration
Operations & Maintenance Warehouse
Under Renovation - Education Under Renovation - Housing Under Renovation - Recreation Vacant
5.52
7,277
1,267 3,022
5,567
4,150
8,405
4,545 9,553
1,493
3,145
4,560 6,840
7,277
1,267 3,022
5,567
1,005
-2,995
-15 2,713
1,493
RESIDENT
NON-RESIDENT
(545)
(25) 15
50 27,250
-4,336
1,005
-2,995
2,698
3,160
49,877
Page: 3 of Date:
SUGGESTED
NSF/
ENROLLEE
SUGGESTED
TOTAL
NSF
ACTUAL
TOTAL
NSF
TYPE OF SPACE DIFFERENCE
295,454
0.73
TOTAL GSF
NET TO GROSS RATIO
Net Square Footage By Building Date: 12/04/2014 Page: 1
Center: SIERRA NEVADA (00907) of 5
HOUSING
Sleeping excl. SPD
Lounge
Storage
Shower/Toilet
Other
Function Suggested
NSF
7,806 7,799
11,092 10,875
8,896 7,709
1,162
1,388
3,129 1,463
1,427 3,032 1,472
1,215
1,214 1,227
0021 - CARSON HALL-MEN'S DORM
0020 - FREMONT HALL-MEN'S DORM
0015 - WASHOE HALL - CO-ED DORM
0011 - DONNER HALL DORMITORY
0019 - COMSTOCK HALL-MEN'S DORM
0018 - LASSEN HALL/ FEMALE DORMITORY
0011 - DONNER HALL DORMITORY
0015 - WASHOE HALL - CO-ED DORM
0018 - LASSEN HALL/ FEMALE DORMITORY
0019 - COMSTOCK HALL-MEN'S DORM
0021 - CARSON HALL-MEN'S DORM
0020 - FREMONT HALL-MEN'S DORM
0015 - WASHOE HALL - CO-ED DORM
0020 - FREMONT HALL-MEN'S DORM
0018 - LASSEN HALL/ FEMALE DORMITORY
0021 - CARSON HALL-MEN'S DORM
0019 - COMSTOCK HALL-MEN'S DORM
0011 - DONNER HALL DORMITORY
0023 - CENTER DUTY OFFICER
0015 - WASHOE HALL - CO-ED DORM
0021 - CARSON HALL-MEN'S DORM
0019 - COMSTOCK HALL-MEN'S DORM
0018 - LASSEN HALL/ FEMALE DORMITORY
0011 - DONNER HALL DORMITORY
0020 - FREMONT HALL-MEN'S DORM
0018 - LASSEN HALL/ FEMALE DORMITORY
0015 - WASHOE HALL - CO-ED DORM
0021 - CARSON HALL-MEN'S DORM
0019 - COMSTOCK HALL-MEN'S DORM
0011 - DONNER HALL DORMITORY
0020 - FREMONT HALL-MEN'S DORM
Bldg Name Actual NSF Difference
54,177
4,590
3,775
11,253
6,150
Sub Total: 79,945
39,240
5,450
3,270
6,540
4,360
58,860
14,937
-860
4,713
1,790
( 545
21,085 rooms; beds rooms; beds rooms; beds rooms; beds rooms; beds rooms; beds
Page: 2
Center: SIERRA NEVADA (00907) of 5
EDUCATION
Academic
Vocational Theory (390)
Carpentry
Cement Masonry
Electrical
Plumbing
Health Occupations
Culinary Arts
Welding
Painting
Plastering
Hotel Management
Facilities Maint. and Const.
Non-Academic
Function Suggested
NSF
2,293
1,650
1,677 1,097
1,986
2,907
3,260
2,546
2,574
3,835
5,725
4,421
2,184
3,260
1,798
2,537
8,361 2,449
1,107
0002 - EDUCATION 1 (ED-1)
0002 - EDUCATION 1 (ED-1)
0002 - EDUCATION 1 (ED-1)
0002 - EDUCATION 1 (ED-1)
0002 - EDUCATION 1 (ED-1)
0002 - EDUCATION 1 (ED-1)
0002 - EDUCATION 1 (ED-1)
0002 - EDUCATION 1 (ED-1)
0008 - VOCATION (C)
0007 - VOCATION (B)
0006 - VOCATION (A)
0008 - VOCATION (C)
0006 - VOCATION (A)
0008 - VOCATION (C)
0007 - VOCATION (B)
0003 - EDUCATION 2 (ED-2)
0010 - CULINARY ARTS/HOSPITALITY
0007 - VOCATION (B)
0008 - VOCATION (C)
0006 - VOCATION (A)
0010 - CULINARY ARTS/HOSPITALITY
0008 - VOCATION (C)
0030B- VOCATIONAL STORAGE
0005 - STUDENT SERVICES & SECURITY
0002 - EDUCATION 1 (ED-1)
0002 - EDUCATION 1 (ED-1)
0002 - EDUCATION 1 (ED-1)
Bldg Name Actual NSF Difference
8,918
3,245
2,907
3,260
2,546
2,574
3,835
5,725
4,421
2,184
3,260
1,798
3,054
12,640
5,700
3,900
3,000
1,500
1,200
1,200
3,600
2,400
1,800
1,500
1,500
1,200
1,800
5,700
3,218
-655
-93
1,760
1,346
1,374
3,325
2,621
1,760
1,254
6,940
( 570 )
Page: 3
Center: SIERRA NEVADA (00907) of 5
EDUCATION
FOOD SERVICE
Maintenance Engineer
Security Officer
Business Office Technologies
Auto Repair Tech/Helper
Dining (2 Servings)
Food Preparation
Food Storage
Function Suggested
NSF
2,539
4,100
2,480
5,051
4,728
3,792
0008 - VOCATION (C)
0016 - SECURITY VOCATION
0003 - EDUCATION 2 (ED-2)
0008 - VOCATION (C)
0022 - CAFETERIA
0022 - CAFETERIA
0022 - CAFETERIA
Bldg Name Actual NSF Difference
2,539
4,100
2,480
5,051
4,728
3,792
Sub Total:
Sub Total:
70,349
13,571
1,200
3,600
3,000
4,560
3,420
2,280
44,400
10,260
1,339
-520
1,308
1,512
( 570
25,949
3,311
Page: 4
Center: SIERRA NEVADA (00907) of 5
RECREATION
MEDICAL/DENTAL
Multipurpose Room
Arts & Crafts
Gymnasium
Weight Room
Theater
Lounges
Miscellaneous Recreation
Aerobics/Exercise
Concession Stand/Restroom
Computer Lab
Recreation Storage
Recreation Office
Medical/Dental
Function Suggested
NSF
3,022
7,277
1,381 4,186
1,267
4,150
0025 - RECREATION
0025 - RECREATION
0026 - GYMNASIUM
0025 - RECREATION
0025 - RECREATION
0031 - THEATRE
0025 - RECREATION
0025 - RECREATION
0025 - RECREATION
0025 - RECREATION
0026 - GYMNASIUM
0025 - RECREATION
0026 - GYMNASIUM
0025 - RECREATION
0026 - GYMNASIUM
0025 - RECREATION
0004 - HEALTH SERVICES/WELLNESS
Bldg Name Actual NSF Difference
3,022
7,277
5,567
1,267
4,150
Sub Total:
Sub Total:
23,289
4,150
3,145
27,625
3,145
1,005
-4,336
1,005
Page: 5
Center: SIERRA NEVADA (00907) of 5
ADMINISTRATION
STORAGE/SUPPORT
VACANT
Administration
Warehouse
Operations & Maintenance
Vacant
Under Renovation - Housing
Under Renovation - Education
Under Renovation - Recreation
Function Suggested
NSF
1,390
5,386 1,348
9,553
4,545
1,493
0005 - STUDENT SERVICES & SECURITY
0016 - SECURITY VOCATION
0001 - ADMINISTRATION
0023 - CENTER DUTY OFFICER
0029 - SUPPORT SERVICES BUILDING
0029 - SUPPORT SERVICES BUILDING
0005 - STUDENT SERVICES & SECURITY
0016 - SECURITY VOCATION
0023 - CENTER DUTY OFFICER
0021 - CARSON HALL-MEN'S DORM
0030B- VOCATIONAL STORAGE
0026 - GYMNASIUM
Bldg Name Actual NSF Difference
8,405
9,553
4,545
1,493
Sub Total:
Sub Total:
Sub Total:
8,405
14,098
3,160
11,400
6,840
4,560
11,400
11,400
-2,995
2,713
-15
1,493
-2,995
2,698
3,160
Environmental Management Report Center: SIERRA NEVADA (00907)
Page: 1 Date: 12/04/2014 of 2
SOLID & HAZARDOUS WASTE MANAGEMENT (RCRA)
Commercial Waste Service
HAZARDOUS MATERIALS STORAGE (EPCRA)
Yes Buildings 22, 30, 33, 34, 35, 35a, 36, 38
Propane gas (15 gal.), gasoline (10 gal.), kerosene (3 gal.), organic solvent (24 gal.), oil-based paint ( 20 gal.)
Yes
PETROLEUM UNDERGROUND STORAGE TANKS (RCRA)
Compliance0
PETROLEUM ABOVEGROUND STORAGE TANKS (CWA)
ASBESTOS AND PCB MANAGEMENT (TSCA)
Solid Waste Disposal :
Hazardous Waste Generator :
Hazardous Waste ID :
Generator Classification :
Hazadous Materials Storage :
Hazardous Materials ID :
HazMat Storage Area :
HazMat Spill Response Plan :
Number of Regulated USTs :
Number of Un-regulated USTs :
Local Hazardous Use Permit :
LEPC Notification :
EPA Generator ID Number :
Hazardous Waste Disposal :
RCRA Compliance
Building 10
Building 11
Building 15
Building 22
Building 26
Building 31
2,000
2,000
2,000
5,000
2,000
1,200
Petroleum - Heating Oil
Petroleum - Heating Oil
Petroleum - Heating Oil
Petroleum - Heating Oil
Petroleum - Heating Oil
Petroleum - Heating Oil
ID LocationFuel Type Capacity
Number of ASTs :
Asbestos Survey Date :
Asbestos Type :
Asbestos Coordinator :
Coordinator Training Date:
Custodial/Maintenance Training :
AHERA Regulated :
Management Plan Approval :
PCB Transformer Testing :
PCB Transformers :
PCB-Contaminated Transformers :
Transformers Labelled :
Reno Disposal, Inc.
Yes Lead/acid batteries (2/month), waste oil (15 gals/month)
Conditionally Exempt Small Quantity Generator
NVD 982443293
Municipal Hazardous Waste Disposal Service
University of Nevada-Reno HAZ-MAT Office
Yes Yes
Overfill Leak Corrosion
SPCC Plan Required : SPCC Plan Completed :
No N/A
02/10/1991 Friable/Non-Friable Randy Klatt 03/01/1999 Yes No N/A Yes Yes
No
No
No
Yes
No
No
No
No
No
Yes
No
No
No
No
No
Yes
No
No
ID Fuel Type Capacity Location Overfill
Prevention Secondary ContainmentTank Status
Active
Abandoned
Abandoned
Active
Abandoned
Abandoned
Tank Status Prevention/Detection
Environmental Management Report
Page: 2 Date: 12/04/2014 of 2
AIR POLLUTION CONTROL (CAA)
N/A None
Non-AttainmentRegional Air Quality :
Permitted Air Pollution Source :
Source Description :
CO, PM-10
Asbestos-Containing Materials Inventory
Date: 12/04/2014Center : Sierra Nevada (00907) Page: 1 of 3
Heating Heating Heating Heating Heating Heating Heating
Floor Finishes Water Plumbing Floor Finishes Floor Finishes
Floor Finishes Floor Finishes
Floor Finishes Floor Finishes Heating Heating Floor Finishes
Water Plumbing Water Plumbing
Bldg System
Bldg System
Bldg System
Bldg System
Bldg System
Pipe fitting insulation Pipe insulation Boiler insulation Pipe fitting insulation Pipe insulation Pipe fitting insulation Pipe insulation, pre-cast
9x9 floor tile, green Pipe fitting insulation 9x9 floor tile (covered) 9x9 floor tile, blue
9x9 floor tile, tan Mastic beneath 9x9 tile
Mastic beneath 9x9 tile 9x9 floor tile, tan Pipe fitting insulation Pipe fitting insulation 9x9 floor tile (covered)
Pipe fitting insulation Pipe fitting insuation
Category Description
Category Description
Category Description
Category Description
Category Description
Ea.
Lin. Ft.
Sq. Ft.
Ea.
Lin. Ft.
Ea.
Lin. Ft.
Sq. Ft.
Ea.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Ea.
Ea.
Sq. Ft.
Ea.
Ea.
Location
Location
Location
Location
Location
Unit
Unit
Unit
Unit
Unit
Quantity
Quantity
Quantity
Quantity
Quantity
Classrooms Classrooms Boiler room Interior hallway Boiler room Boiler room Interior hallway
2nd flr, storage Laundry room 2nd flr, dorm area Basement hallway
Throughout Throughout
Throughout Hallway 2nd flr, storage Room 217 Throughout
Laundry room Storage closet
18000 18000
Building :
Building :
Building :
Building :
Building :
0010 - CULINARY ARTS/HOSPITALITY
0011 - DONNER HALL DORMITORY
0015 - WASHOE HALL - CO-ED DORM
0018 - LASSEN HALL/ FEMALE DORMITORY
0019 - COMSTOCK HALL-MEN'S DORM
Page: 2 of 3
Floor Finishes Floor Finishes
Heating Heating Heating Roof Repair/Replacement
Roof Repair/Replacement Heating
Heating Heating Heating Heating Heating Heating Heating Heating Plumbing (Bldg) Exterior Walls
Bldg System
Bldg System
Bldg System
Bldg System
9x9 floor tile, brown Mastic beneath 9x9 tile
Boiler exhaust insulation Pipe fitting insulation Boiler insulation Asbestos cement board
Built-up roofing Pipe insulation, pre-cast
Pipe fitting insulation Boiler insulation Pipe insulation, pre-cast Pipe insulation, air-cell Pipe insulation Pipe fitting insulation Pipe insulation, air-cell Boiler exhaust insulation Pipe Fitting Insulation Asbestos cement board
Category Description
Category Description
Category Description
Category Description
Sq. Ft.
Sq. Ft.
Sq. Ft.
Ea.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Lin. Ft.
Ea.
Sq. Ft.
Lin. Ft.
Lin. Ft.
Lin. Ft.
Ea.
Lin. Ft.
Sq. Ft.
Ea.
Sq. Ft.
Location
Location
Location
Location
Unit
Unit
Unit
Unit
Quantity
Quantity
Quantity
Quantity
Rooms 221 thru 228 Rooms 221 thru 228
Boiler room Boiler room Boiler room Loading dock
Throughout Tunnel pipe chase
Boiler room Boiler room Boiler room Gymnasium Locker rooms Locker rooms Boiler room Boiler room Court Area Above windows
Building :
Building :
Building :
Building :
0020 - FREMONT HALL-MEN'S DORM
0022 - CAFETERIA
0023 - CENTER DUTY OFFICER
0026 - GYMNASIUM
Page: 3 of 3
Heating Heating Heating Heating Roof Repair/Replacement Heating Heating Heating Heating Heating
Bldg System Pipe fitting insulation Pipe insulation, air-cell Boiler insulation Pipe fitting insulation Roof flashing Pipe insulation, air-cell Pipe insulation, air-cell Pipe insulation, air-cell Pipe fitting insulation Pipe insulation, pre-cast
Category Description Ea.
Lin. Ft.
Sq. Ft.
Ea.
Lin. Ft.
Lin. Ft.
Lin. Ft.
Lin. Ft.
Ea.
Lin. Ft.
Location Unit Quantity Projection room Projection room Boiler room Boiler room Throughout Boiler room Stage area Bathrooms Bathrooms Boiler room
Building : 0031 - THEATRE
Radon
Page: 1 of 2
0001 - ADMINISTRATION
0002 - EDUCATION 1 (ED-1)
0003 - EDUCATION 2 (ED-2)
0004 - HEALTH SERVICES/WELLNESS
0005 - STUDENT SERVICES & SECURITY
0006 - VOCATION (A)
0007 - VOCATION (B)
0008 - VOCATION (C)
0010 - CULINARY ARTS/HOSPITALITY
0011 - DONNER HALL DORMITORY
0015 - WASHOE HALL - CO-ED DORM
0016 - SECURITY VOCATION
0018 - LASSEN HALL/ FEMALE DORMITORY
0019 - COMSTOCK HALL-MEN'S DORM
0020 - FREMONT HALL-MEN'S DORM
0021 - CARSON HALL-MEN'S DORM
0022 - CAFETERIA
0023 - CENTER DUTY OFFICER
0025 - RECREATION
0026 - GYMNASIUM
0029 - SUPPORT SERVICES BUILDING
0030B- VOCATIONAL STORAGE
0031 - THEATRE
Bldg Name
06/11/1990
08/11/1992
06/11/1990
06/11/1990
06/11/1990
06/11/1990
08/11/1992
06/11/1990
06/11/1990
06/11/1990
08/11/1992
06/11/1990
08/11/1992
Test Date
No
No
No
No
No
No
No
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
Yes
No
Yes
Yes
Radon Testing
< 4 pCi
> 20 pCi
< 4 pCi
< 4 pCi
< 4 pCi
4 - 20 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
Test Result
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
No
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Mitigation Mitigation Date
Radon
Page: 2 of 2
RADON EXPLANATORY NOTES
The US Environmental Protection Agency (EPA) has established a radon action level of 4.0 picoCuries per liter (pCi/L). Occupied buildings with radon concentrations less than 4.0 pCi/L do not require radon mitigation; un-occupied buildings, or those buildings which are occupied only infrequently for brief periods of time, also do not require radon mitigation. Occupied buildings with radon concentrations greater than
4.0 pCi/L require radon mitigation and verification of radon reductions as soon as possible, with priority given to dormitories and student recreation buildings. Occupied buildings with radon concentrations greater than 20.0 pCi/L should be considered significant radon exposure hazards, and priority for mitigation should be given to buildings with these highly elevated radon concentrations.
Radon mitigation techniques include: (1) adjustment of the building HVAC system to create a positive pressure within the building; (2) sealing of foundation wall cracks, penetrations, or other openings;
(3) sealing crawlspace openings and sump pits; (4) installing an active subslab depressurization (ASD) system.
Site Description
Mountains in the background
Page: 1 Date: 12/04/2014 of 4
Comments:
Paving Type for Roads & Parking
Generally, the roads and sidewalks are in good condition. There are areas where minor repairs are needed; the parking area between Buildings 1 and 15 is partially deteriorated.
Paving Type for Sidewalks
Asphalt Concrete
Comments:
Topography Buildings and Structures
Center is not fully enclosed by fencing. There is a chain link fence and masonry wall at the perimeter to enclose most of the center property.
ROADS, PARKING & SIDEWALKS
Water Source Water Authority Service Meter On-Site Treatment Plant
1. Water System
Treatment Type Storage Type Storage Capacity(Gallons)
NoMasterTruckee Meadows Water AuthorityPublic Water Authority
None 0None
There are numerous water meters spread throughout the campus. Meters serve multiple buildings and irrigation lines.
Comments:
Comments:
Fire Hydrants On-Site Water Supply Storage Capacity
(Gallons) Pressure Source FD Response Time (Minutes)
Yes 0 5None Municipal
A fire station is less than one mile away with about 3 to 5 minutes response time.
SITE FEATURES
UTILITIES
2. Fire Protection System
Buildings Structures23 20Flat with gentle slopes
Surrounding
Outdoor Recreation
Airport, Housing, School
Basketball, Soccer Fields, Soft/Baseball None
Most of the site
Part of the perimeter
Chain Link
CMU
Location Type
Maintenance Responsibility System Capacity Adequate System Condition
Center Center Yes Good
Separate Loop
No
Ownership Maintenance Responsibility System Capacity Adequate System Condition
Center Center Yes Good
Ownership
Roads & Parking Adequate Roads & Parking Condition Sidewalks Adequate Sidewalk Condition Yes Good Yes Good
Fencing
Other Features
Page: 2 Date: 12/04/2014 of 4
Sewage Treatment Flow
Center
Publicly Owned Treatment Works
Center
Gravity
Maintenance ResponsibilityOwnership
Comments: Natural gas is metered for each building. Fuel oil is provided by Reno Fuel Co. and fuel oil tanks are dedicated to individual buildings.
Sierra Pacific Power Co.
Comments:
Electric Company PCB Trans.
Transformer Mounting Transformer Ownership
Systems Ownership Maintenance Responsibility
Nevada Energy
Electrical service is brought to the center from three locations from power poles along Mt. Bismark Street and Echo Avenue. The primary metering is located at the utility pole on Echo Avenue and secondary meters are installed in the majority of buildings on center. Most existing building services are overhead with pole-mounted and/or platform-mounted transformers while new buildings have underground services via pad-mounted transformers. Vocational Buildings 6, 7 and 8 secondary services are 480/277V, 3-phase, 4 wire with step-down transformers providing 120/208V, 3-phase, 4 wire system. Dormitory, Buildings 11, 15, 18, 19, 20 and 21 are each provided with a 1.5 kW generator to back-up the emergency lighting system in the buildings. The Cafeteria Building 22 has a 230 kVA diesel generator with automatic transfer switch (ATS) located outside in the back of the building.
Pole,Pad and Platform Center
Center Center
No
4.16/2.4 kV, 3-Ph, 4 W
480/277V and 120/208V, 3-Ph, 4 WOverhead & Underground
Overhead & UndergroundPrimary Service
Secondary Service
Distribution Characteristics
3. Sanitary Sewer System/ Sewage Treatment Plant
5. Fuel Distribution System
Number of Deficiencies = 4
System Capacity Adequate System Condition
Yes Good
4. Storm Water System Number of Deficiencies = 1
Drain Type On-Site Storm Water Management
Underground N/A
Ownership Maintenance Responsibility System Capacity Adequate System Condition
Center Yes GoodCenter
Gas Company Metering
Individual
Ownership Maintenance Responsibility System Capacity Adequate System Condition
Center Center Yes Good
7. Electrical (Service)
Transformer Maint Resp
Utility
System Capacity Adequate System Condition
Yes Good
Generator
Diesel
ATS MTS
Yes Yes
6. Central Plant: None
Metering Master-Smart Meter
Page: 3 Date: 12/04/2014 of 4
Comments:
Telephone Company
On-site Line Owner
Telephone/data service is brought to the center by AT&T via five T1 lines and terminates in the computer room in Security Vocation Building 16. From this location, digital voice over IP (VoIP) and data/communication networks are distributed throughout the center. The networks are provided and maintained by Job Corps Data Center. The fire alarm systems in buildings throughout the center are stand alone; however they are monitored via telephone line by the center's fire alarm system contractor. There is no electronic security system on site but some buildings on the center, especially the dormitories, are provided with door alarms and motion sensors to protect the buildings from unauthorized ingress/egress. Cable television is provided in all dormitories.
AT&T
Maint. Responsibility
Center Center
Door Alarms, Motion Sensors, Keypads
01/01/1987
01/01/1986
01/01/1986
01/01/1986
01/01/1987
01/01/1986
Center
Center
Center
Center
Center
Center
Active
Abandoned
Abandoned
Active
Abandoned
Abandoned
Underground, Non-regulated
Underground, Non-regulated
Underground, Non-regulated
Underground, Non-regulated
Underground, Non-regulated
Underground, Non-regulated
Building 10
Building 11
Building 15
Building 22
Building 26
Building 31
No
No
No
Yes
No
No
Petroleum - Heating Oil
Petroleum - Heating Oil
Petroleum - Heating Oil
Petroleum - Heating Oil
Petroleum - Heating Oil
Petroleum - Heating Oil
STORAGE TANKS
TypeStatus Location Owner Fuel Type Capacity (Gallons) Install DateID
Reg.
9. Electrical (Communication/Alarm/Security)
Heating
Heating
Heating
Heating
Heating
Heating
Purpose
Yes
Stand-Alone
VOIP
System Capacity Adequate System Condition
GoodYes
8. Electrical (Site Lighting)
Roadways Parking Walkways Building Outdoor Sports
Mounting
Control
Pole Pole Bollard Building Sport Light
Photocell Photocell, Time Clock, Switch
Time Clock, Photocell Photocell Switch
System Ownership Maintenance Responsibility System Capacity Adequate System Condition
Utility, Center Center Yes Good
Comments: The site lighting system is a combination of building-mounted fixtures, pole-mounted fixtures at parking areas, post-mounted fixtures along walkways and sport lights at the ball field.