Detroit_Facility_Survey_Final_Vol2_Part1_Att_J-9.pdf
PDF 3 MB Posted
- Solicitation number
- DOL13RA20003
About this file
RFP Attachment J-9 Facility Survey Vol II
View the file
Other files
Show all 19
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DetroitDetroit
Job Corps Center Detroit, MI
Facility Planning ReportFacility Planning Report Volume II
Supporting Data
Fi lFinal March 2012
Department of Labor/ Office of Job Corps
22Detroit Job Corps Center
DetroitDetroit
Job Corps Center Detroit, MI
Facility Planning ReportFacility Planning Report Volume II
Supporting Data
Fi lFinal March 2012
Dormitory Building 1A
33 Detroit Job Corps Center
CONTENTS
DETROIT JOB CORPS CENTER
FACILITY PLANNING REPORT
VOLUME I - Planning Strategy
• Existing Site Plan
• Center Statistics
INTRODUCTION
• Purpose
• Report Contents
EXECUTIVE SUMMARY
A. EXISTING CONDITIONS
• Background
• General Site Conditions
• General Building Conditions
• Preventive Maintenance
• Ownership
• Facility Assessment by Function
• Energy
• Environmental Issues
• Sustainability
• Accessibility Standards
• Health and Life Safety Issues
• Summary of Defi ciencies
B. RECOMMENDATIONS
• Status of the Previous (PY08) Plan
• Signifi cant Issues
• PY 11 Plan Overview
• Summary of Proposed Projects
• Regional Projects
• Proposed Site Plan
C. PLANNING ANALYSIS
• Purpose
• Planning Objectives and Assumptions
• Space Utilization Analysis
• Federal Real Property Asset Management
• Mission Dependency Site Plan
• Defi ciency Analysis
• Facility Condition Summary Report
• Building Condition by Function
• Building Condition Site Plan
VOLUME II - Supporting Data
• Vicinity Map
• Location Map
• Existing Site Plan
D. DESCRIPTIONS
• Building and Structures
• Space Utilization By Function
• NSF by Building
• Energy Management Report
• Environmental Management
Asbestos Report Radon Report
• Site Descriptions
• Building Descriptions
E. DEFICIENCIES
F. CORRESPONDENCE AND REPORTS
• Center Review Meeting Minutes
• Survey Brief
• RA and Student Facility Feedback Questionnaire
• Life Safety Defi ciencies Transmittal and List
• O & M Defi ciency List
• Active Warranty Report
• FRPC Performance Measures Matrix
44Detroit Job Corps Center
55 Detroit Job Corps Center
66Detroit Job Corps Center
77 Detroit Job Corps Center
D Descriptions
BUILDINGS AND STRUCTURES
00504 DETROIT 06-MAR-12
1Page: of 1
0001A - DORMITORY
0001B - ADMINISTRATION/DORMITORY
0001C - MEDICAL/DENTAL/STUDENT
LOUNGE
0001D -
CLASSROOM/ADMIN/CAFETERIA
0001E - BOILER
0002 - TRADE BUILDING
0003 - RECREATION
0005 - GUARDHOUSE
0011 - CARPENTRY SHED
0014 - STORAGE GARAGE
0015 - STORAGE GARAGE
Name GSF
64,290 24,520 8,060
64,830
10,550 5,690
16,600
Active Active Active
Active
Active Active Active Active Active Active Active
StatusType
Building Building Building
Building
Building Building Building Structure Structure Structure Structure
Use Group Built Flrs Const
Residential Residential Business
Business
Utility/Misc.
Business Assembly Business Storage Storage Storage
Fair Fair Fair
Fair
Fair Good Good Good Good Good Good
ConditionAsset Number
0050400030 0050400036 0050400035
0050400034
0050400037 0050400031 0050400032 0050408077 0050408069 0050408072 0050408073
7 194,540
4 610
11 195,150
Buildings
Structures
Total
GSF
GSF
GSF
Summary
March 06, 2012 Space Utilization By Function 00504 Detroit
Page: 1 of 2
HOUSING
EDUCATION
FOOD SERVICE
SUGGESTED
NSF/
ENROLLEE
SUGGESTED
TOTAL
NSF
ACTUAL
TOTAL
NSF
TYPE OF SPACE
SUB TOTAL
SUB TOTAL
SUB TOTAL
Resident Men Resident Women Total Residents
Residents 280 Non Residents 60
340Total Students
(280)
(340)
(340)
DIFFERENCE
28,000
15,650
6,120
62,795
26,283
8,734
Lounge Other Shower/Toilet Sleeping Storage
Academic (340) Non-Academic
24 -- ACT (Off-Ctr) 30 -- Cable T.V. Installer 50 -- Cert. Nursing Asst. (Off-Ctr) 30 -- Computer Service Tech.
24 -- Facilities Maint. and Const. + 60 -- Office Administration 30 -- Security Services 24 -- Weatherization
Vocational Theory (24)
Dining (2 Servings) Food Preparation Food Storage
8,080 5,130 5,410
41,875 2,300
4,773 7,936
1,530
1,159 1,944 1,779 1,729 4,249
1,184
4,687 3,011 1,036
2,800
3,360 20,160
1,680
3,400 3,400
1,200
1,800 2,700 1,050
2,720 2,040 1,360
5,280
2,050 21,715
1,373 4,536
-921
3,289
1,967 -324
Vocations
34,795
10,633
2,614
March 06, 2012 Space Utilization By Function 00504 Detroit
Page: 2 of 2
RECREATION
MEDICAL/DENTAL
ADMINISTRATION
STORAGE/SUPPORT
SUGGESTED
NSF/
ENROLLEE
SUGGESTED
TOTAL
NSF
ACTUAL
TOTAL
NSF
TYPE OF SPACE
SUB TOTAL
SUB TOTAL
SUB TOTAL
SUB TOTAL
TOTAL 236.29 80,340 134,930
(340)
(340)
(340)
(340)
DIFFERENCE
194,540
0.69
TOTAL GSF
NET TO GROSS RATIO
14,900
2,070
6,800
6,800
16,801
1,915
10,486
7,916
Aerobics/Exercise Computer Lab Gymnasium Men's Exercise Room Miscellaneous Recreation Multipurpose Room Pool Hall Recreation Office Recreation Storage T.V. Room Women's Exercise Room
Medical/Dental
Administration
Operations & Maintenance Warehouse
6.09
1,785
8,489
1,411 2,148
1,915
10,486
6,416 1,500
2,070
6,800
2,720 4,080
-155
3,686
3,696 -2,580
RESIDENT
NON-RESIDENT
(280)
(60) 15
50 14,000
1,901
-155
3,686
1,116
54,590
Net Square Footage By Building Date: 03/06/2012 Page: 1Center: DETROIT (00504) of 4
HOUSING
Sleeping
Lounge
Storage
Shower/Toilet
Other
Function Suggested NSF
36,485 5,390
7,410
1,800
4,060 1,350
2,730 2,400
0001A - DORMITORY
0001B - ADMINISTRATION/DORMITORY
0001B - ADMINISTRATION/DORMITORY
0001A - DORMITORY
0001A - DORMITORY
0001B - ADMINISTRATION/DORMITORY
0001A - DORMITORY
0001B - ADMINISTRATION/DORMITORY
0001B - ADMINISTRATION/DORMITORY
0001A - DORMITORY
Bldg Name Actual NSF Difference
41,875
8,080
2,300
5,410
5,130
Sub Total: 62,795
20,160
2,800
1,680
3,360
28,000
21,715
5,280
2,050
5,130
( 280
34,795
Page: 2Center: DETROIT (00504) of 4
EDUCATION
FOOD SERVICE
Academic
Vocational Theory (24)
Computer Service Tech.
Facilities Maint. and Const.
Security Services
Cable T.V. Installer
Weatherization
Non-Academic
Office Administration
Dining (2 Servings)
Food Preparation
Food Storage
Function Suggested NSF
1,141 1,342
1,459
1,159
1,944
1,729
1,530
4,249
3,192 1,727
1,779
4,687
3,011
1,036
0001D - CLASSROOM/ADMIN/CAFETERIA
0001D - CLASSROOM/ADMIN/CAFETERIA
0001D - CLASSROOM/ADMIN/CAFETERIA
0001D - CLASSROOM/ADMIN/CAFETERIA
0001D - CLASSROOM/ADMIN/CAFETERIA
0002 - TRADE BUILDING
0001D - CLASSROOM/ADMIN/CAFETERIA
0001D - CLASSROOM/ADMIN/CAFETERIA
0001D - CLASSROOM/ADMIN/CAFETERIA
0001D - CLASSROOM/ADMIN/CAFETERIA
0001D - CLASSROOM/ADMIN/CAFETERIA
0002 - TRADE BUILDING
0001D - CLASSROOM/ADMIN/CAFETERIA
0001D - CLASSROOM/ADMIN/CAFETERIA
0001D - CLASSROOM/ADMIN/CAFETERIA
0001D - CLASSROOM/ADMIN/CAFETERIA
0001D - CLASSROOM/ADMIN/CAFETERIA
0001D - CLASSROOM/ADMIN/CAFETERIA
0001D - CLASSROOM/ADMIN/CAFETERIA
0001D - CLASSROOM/ADMIN/CAFETERIA
0001D - CLASSROOM/ADMIN/CAFETERIA
0001D - CLASSROOM/ADMIN/CAFETERIA
Bldg Name Actual NSF Difference
4,773
1,184
1,159
1,944
1,729
1,530
4,249
7,936
1,779
4,687
3,011
1,036
Sub Total:
Sub Total:
26,283
8,734
3,400
1,800
1,050
1,200
3,400
2,700
2,720
2,040
1,360
15,650
6,120
1,373
3,289
4,536
-921
1,967
-324
10,633
2,614
Page: 3Center: DETROIT (00504) of 4
RECREATION
MEDICAL/DENTAL
ADMINISTRATION
Multipurpose Room
Gymnasium
Miscellaneous Recreation
Pool Hall
Aerobics/Exercise
T.V. Room
Men's Exercise Room
Women's Exercise Room
Computer Lab
Recreation Storage
Recreation Office
Medical/Dental
Administration
Function Suggested NSF
1,438
8,489
1,043
1,785
1,915
3,230 7,256
0001C - MEDICAL/DENTAL/STUDENT LOUNGE
0003 - RECREATION
0003 - RECREATION
0001C - MEDICAL/DENTAL/STUDENT LOUNGE
0003 - RECREATION
0003 - RECREATION
0003 - RECREATION
0001C - MEDICAL/DENTAL/STUDENT LOUNGE
0003 - RECREATION
0003 - RECREATION
0003 - RECREATION
0003 - RECREATION
0003 - RECREATION
0001C - MEDICAL/DENTAL/STUDENT LOUNGE
0001B - ADMINISTRATION/DORMITORY
0001D - CLASSROOM/ADMIN/CAFETERIA
Bldg Name Actual NSF Difference
2,148
8,489
1,411
1,785
1,915
10,486
Sub Total:
Sub Total:
Sub Total:
16,801
1,915
10,486
2,070
6,800
14,900
2,070
6,800
-155
3,686
1,901
-155
3,686
Page: 4Center: DETROIT (00504) of 4
STORAGE/SUPPORT
Warehouse
Operations & Maintenance
Function Suggested NSF
1,500
6,416
0001D - CLASSROOM/ADMIN/CAFETERIA
0001E - BOILER
Bldg Name Actual NSF Difference
1,500
6,416
Sub Total: 7,916
4,080
2,720
6,800
-2,580
3,696
( 340
1,116
Energy Management Report Center: DETROIT (00504)
Page: 1 Date: 03/06/2012 of 3
CENTER ENERGY DATA
Deferred (new center)
ENERGY CONSUMPTION ASSESSMENT
- 35% 160,716 97,665 119,104
ENERGY USE BY FUEL TYPE
Energy Audit :
Date of Audit :
Electric Company :
Percent Reduction since Baseline Year :
Natural Gas Company :
Property Status :
N/A
DTE Energy DTE Energy
Federally Owned (DOL)
1,520,877 5,189=
Total 31,265
MBtu
MBtu
Total $359,927 MBtu/ $11.512
BTU/GSF
BTU/GSF
BTU/GSF
Electricity
Natural Gas kWh
25,292 MCF = 26,076 MBtu
$186,263 $0.122= kWhElectricity
Natural Gas $173,664 = $6.866 MCF
ENERGY COST BY FUEL TYPE
COMMENTS
8/05/03 Data is estimated. New management at the center does not have access to energy bills yet.
2/01 Detroit does not convert their electric bills. FY 01, First Quarter report consistent with FY 00 4th Qtr.
WATER CONSUMPTION ASSESSMENT
FY 2007 Baseline:
Percent Reduction Since Baseline Year:
1,000 Gallons
1,000 Gallons
FY 2011 Energy Goal:
Further Reduction in Energy Usage is needed to meet Energy Reduction Goals.
FY 2011 Energy Consumption:
Note: The Federal Government has set a goal of 3% Energy Consumption Reduction per year in EO 13423.
15,578 14,332 9,185
41%
Water Goals are being met. Keep reducing Water Consumption.
Note: The Federal Government has set a goal of 2% Water Consumption Reduction per year in EO 13423.
FY 2011 Goal:
FY 2011 Water Consumption:
1,000 Gallons
FY 2003 Energy Baseline:
Page: 2 Date: 03/06/2012 of 3
Implementing some of the below recommendations can save you 10% to 25% off your annual energy bill without negatively impacting comfort or productivity.
1. Your staff and students are the key to savings. Educate the students and staff on the why of energy saving - costs and environmental impacts. Encouraging them to actively participate in energy reduction is also important. Post reminders at exit doors and bulletin boards about energy conservation. Simple tips include:
a. Turn it down (lights, heating & cooling),
b. Turn it off (lights, computers, other equipment),
c. Keep it tight (close doors and windows, use window blinds)
2. Operations and Maintenance: Educate the O&M staff on the why of energy saving -costs and environmental impacts. Simple tips include:
a. Make sure that the Operations and Maintenance staff is properly trained for the equipment they operate.
b. Tune and clean HVAC: Perform seasonal cleanups on air conditioners, boilers and furnaces, and regularly clean cooling coils and drain pans. Get rooftop or outdoor condenser coils cleaned and maintain an appropriate filter changing schedule.
c. Check (or ask your HVAC contractor to check) your outside air dampers or economizers to verify proper ventilation. Make sure economizer controls function properly. Make sure automatic dampers close during unoccupied periods.
d. Restore automatic control: When troubleshooting a system, take time to figure out and repair the automatic controls. Today's quick fix is tomorrow's bad idea.
e. Reasonable set points: Try 68°F in the heating season and 75°F in the cooling season.
f. Schedule HVAC equipment and lighting: (weekdays, weekends, holidays, off-season). Make sure equipment runs only when it is needed and the buildings are occupied. When buildings are vacant (i.e. dormitories during the day with students in class), make sure all the lights in the building are off.
g. Seasonal (resets, schedules, and shutoffs): As the seasons change, adjust set points and schedules to match the system's response to the weather.
h. Lighting: Invest in an inexpensive light level meter to measure the foot-candles in spaces to determine whether or not they are over lit and lamps can be safely removed. Where four-lamp fixtures are in use, two lamps can usually be removed from every fixture or every other fixture. After lamps are removed, disconnect ballasts. Contact the Energy team at PBDewberry for suggested light levels for individual space types. Cleaning fixtures regularly increases light levels.
i. Utilize power management features for all computers and monitors to shut them off when idle for more than 15 minutes.
Page: 3 Date: 03/06/2012 of 3
j. Have your vending machine suppliers turn off or remove light tubes from the advertising lighting in the machine. This will save about $50 per year per vending machine.
k. Save water with low flow sink aerators (0.5gpm) and low flow shower heads (1.5gpm - 2.0gpm). This will also reduce water heating energy consumption.
l. Set your water heater to 120°F. Verify by measuring at the tap. Never go below 115°F.
m. For water heaters installed in unconditioned spaces, add insulation blankets making sure that access covers, electric connection areas, and pressure relief valves are left uncovered.
n. Caulk and fill cracks around doors and windows to reduce costly air leaks.
o. When replacing broken glass, use high transmittance, low heat gain windows.
p. Make sure automatic door closers are functioning properly to avoid drafts.
3. Buy energy efficient, buy EnergyStar (www.energystar.gov).
a. Buy EnergyStar appliances and equipment.
b. Replace burned out lightbulbs with EnergyStar labeled compact fluorescent lightbulbs (CFLs).
c. Replace broken thermostats with EnergyStar labeled programmable products.
d. Replace broken exit signs with EnergyStar LED exit signs.
Environmental Management Report
Page: 1 Date: 03/06/2012 of 1
SOLID & HAZARDOUS WASTE MANAGEMENT (RCRA)
HAZARDOUS MATERIALS STORAGE (EPCRA)
Yes
Yes
PETROLEUM UNDERGROUND STORAGE TANKS (RCRA)
Compliance0
PETROLEUM ABOVEGROUND STORAGE TANKS (CWA)
ASBESTOS AND PCB MANAGEMENT (TSCA)
AIR POLLUTION CONTROL (CAA)
None
Attainment
Solid Waste Disposal :
Hazardous Waste Generator :
Hazardous Waste ID :
Generator Classification :
Hazadous Materials Storage :
Hazardous Materials ID :
HazMat Storage Area :
HazMat Spill Response Plan :
Number of Regulated USTs :
Number of Un-regulated USTs :
Local Hazardous Use Permit :
LEPC Notification :
EPA Generator ID Number :
Hazardous Waste Disposal :
RCRA Compliance
ID LocationFuel Type Capacity
Number of ASTs :
Asbestos Survey Date :
Asbestos Type :
Asbestos Coordinator :
Coordinator Training Date:
Custodial/Maintenance Training :
AHERA Regulated :
Management Plan Approval :
PCB Transformer Testing :
PCB Transformers :
PCB-Contaminated Transformers :
Transformers Labelled :
Regional Air Quality :
Permitted Air Pollution Source :
Source Description :
Yes
Yes Yes
Overfill Leak Corrosion
SPCC Plan Required : SPCC Plan Completed :
Yes Yes
07/01/2005 Friable/Non-Friable
Yes Yes
Yes Yes
ID Fuel Type Capacity Location Overfill
Prevention Secondary ContainmentTank Status
Tank Status Prevention/Detection
Asbestos-Containing Materials Inventory
Date: Mar. 06, 2012Center : Detroit (00504) Page: 1 of 1
Floor Finishes Plumbing Fixtures Floor Finishes Heating Heating Roof Repair/Replacement
Roof Repair/Replacement Heating
Heating Heating Roof Repair/Replacement Plumbing Fixtures
Roof Repair/Replacement Heating Heating Heating
Bldg System
Bldg System
Bldg System
Bldg System
Pebble pattern linoleum Black sink undercoating 9" x 9" mint green floor tile Insulation on Pipe Fittings Pipe Insulation Roof Flashing
Roof Flashing Insulation on Pipe Fittings
Pipe Insulation Insulation on Pipe Fittings Roof Flashing White Sink Undercoating
Roof Flashing Exhaust Duct Lining Insulation on Pipe Fittings Pipe Insulation
Category Description
Category Description
Category Description
Category Description
Sq. Ft.
Ea.
Sq. Ft.
Ea.
Lin. Ft.
Sq. Ft.
Sq. Ft.
Ea.
Lin. Ft.
Ea.
Sq. Ft.
Ea.
Sq. Ft.
Lin. Ft.
Ea.
Lin. Ft.
Location
Location
Location
Location
Unit
Unit
Unit
Unit
Quantity
Quantity
Quantity
Quantity
2nd Floor Hallway Laundry Room 2nd Flr Hallway Throughout Throughout Roof
Roof Throughout
Facility Maintenance Throughout Roof Kitchenette near 59A
Roof Throughout Throughout Throughout
Building :
Building :
Building :
Building :
0001A - DORMITORY
0001B - ADMINISTRATION/DORMITORY
0001D - CLASSROOM/ADMIN/CAFETERIA
0001E - BOILER
Radon
Page: 1 of 1
0001A - DORMITORY
0001B - ADMINISTRATION/DORMITORY
0001C - MEDICAL/DENTAL/STUDENT LOUNGE
0001D - CLASSROOM/ADMIN/CAFETERIA
0001E - BOILER
0002 - TRADE BUILDING
0003 - RECREATION
Bldg Name
02/10/2004
02/10/2004
02/10/2004
02/10/2004
02/10/2004
02/10/2004
02/10/2004
Test Date
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Radon Testing
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
Test Result
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Mitigation Mitigation Date
RADON EXPLANATORY NOTES
The US Environmental Protection Agency (EPA) has established a radon action level of 4.0 picoCuries per liter (pCi/L). Occupied buildings with radon concentrations less than 4.0 pCi/L do not require radon mitigation; un-occupied buildings, or those buildings which are occupied only infrequently for brief periods of time, also do not require radon mitigation. Occupied buildings with radon concentrations greater than
4.0 pCi/L require radon mitigation and verification of radon reductions as soon as possible, with priority given to dormitories and student recreation buildings. Occupied buildings with radon concentrations greater than 20.0 pCi/L should be considered significant radon exposure hazards, and priority for mitigation should be given to buildings with these highly elevated radon concentrations.
Radon mitigation techniques include: (1) adjustment of the building HVAC system to create a positive pressure within the building; (2) sealing of foundation wall cracks, penetrations, or other openings;
(3) sealing crawlspace openings and sump pits; (4) installing an active subslab depressurization (ASD) system.
504 D t it J b C C t504 Detroit Job Corps Center Site Description
Detroit JCC Areal Photo
Page: 1 Date: 03/06/2012 of 4
Paving Type for Roads & Parking Paving Type for Sidewalks
Asphalt Concrete
Comments:
Topography Buildings and Structures
Center is fully enclosed by fencing. In addition mechanical equipment areas and roof access ladders are fenced.
ROADS, PARKING & SIDEWALKS
Water Source Water Authority Service Meter On-Site Treatment Plant
1. Water System
Treatment Type Storage Type Storage Capacity(Gallons)
NoIndividualDetroit Water and Sewerage DepartmentPublic Water Authority
None 0None
Water is metered for Buildings 1A, 1B, 1C and 1D at Boiler Building 1E. Building 1A has a separate metered water service. The remainder of buildings are individually metered.
Comments:
Fire Hydrants On-Site Water Supply Storage Capacity
(Gallons) Pressure Source FD Response Time (Minutes)
Yes 0 5None Municipal
Sewage Treatment Flow
Center
Publicly Owned Treatment Works
Center
Gravity
Maintenance ResponsibilityOwnership
SITE FEATURES
UTILITIES
3. Sanitary Sewer System/ Sewage Treatment Plant
2. Fire Protection System
Buildings Structures7 4Flat
Surrounding
Outdoor Recreation
Urban
Basketball, Volleyball Smoke Stack
Entire Site Chain Link
Location Type
Maintenance Responsibility System Capacity Adequate System Condition
Center Center Yes Good
Separate Loop
No
Ownership Maintenance Responsibility System Capacity Adequate System Condition
Utility Utility Yes Unknown
System Capacity Adequate System Condition
Yes Unknown
Ownership
Roads & Parking Adequate Roads & Parking Condition Sidewalks Adequate Sidewalk Condition Yes Good Yes Good
Fencing
Other Features
Page: 2 Date: 03/06/2012 of 4
Comments: The center gas supplier is DTE Energy and the carrier is Constellation Energy. Gas is metered for Buildings 1A, 1B, 1C, and 1D at Boiler Building 1E. The remainder of the buildings are individually metered.
DTE Energy
Comments: The plant is located in and on Building 1E. A new boiler and a new chiller were installed during the 1999 renovation of the facility.
5. Fuel Distribution System
6. Central Plant
4. Storm Water System
Drain Type On-Site Storm Water Management
Underground N/A
Ownership Maintenance Responsibility System Capacity Adequate System Condition
Center Yes UnknownCenter
Gas Company Metering
Master
Ownership Maintenance Responsibility System Capacity Adequate System Condition
Utility Center Yes Good
Type Energy Source
Chilled Water
Steam
Electric
Natural Gas
Heat: 1A, 1B, 1C, 1D & 1E Cooling: 1A, 1B, 1C & 1D
Bldgs Served
Ownership Maintenance Responsibility Plant Capacity Adequate Plant Condition
Center Center Yes Poor
Page: 3 Date: 03/06/2012 of 4
Comments:
Electric Company PCB Trans.
Transformer Mounting Transformer Ownership
Systems Ownership Maintenance Responsibility
DTE Energy
Two sets of underground primary conductors, one from each of two adjacent overhead primary line sets (same poles), via associated fused cutouts and underground transition at poles, enter the electrical room in the lower level of Boiler Building 1E and terminate in substations #1 and #2, respectively. Each substation consists of a utility-owned C/T cabinet and primary metering section, 600A, 8.2 KV - rated load-break primary switch section (additionally one unused switch at substation 1), a 750 kVA dry-type 4800/480V delta/delta center-owned transformer section, and a 1200A secondary distribution section. The two substations are connected with a main-tie-main secondary configuration with automatic transfer, with tie breaker (1200A) located in substation #1, achieving improved reliability as well as power system availability during maintenance operations. The substations serve Buildings 1A, 1C, 1D, 1E, 2 and 5. Additionally, a feeder tap from one set of the primary conductors (load side substation #1 primary switch) serves another 2 MVA center-owned, pad-mounted primary transformer located in the fenced service yard behind Boiler Building 1E. This transformer supplies power to a 1,600A and a 1,200A switchboard which serve Buildings 1B, 1D (one MCC), 1E (one MCC), and chiller, respectively. The new Recreation Building 3 is separately served from another utility pole southwest of the center via a utility-owned, pad-mounted 480/277V transformer, a C/T cabinet and a meter. A 480V generator that once served selected building loads has been abandoned in place since the original conversion of the property to a JCC. The center owns and maintains the substations. There are two primary meters (in Building 1E electrical room) and two secondary meters (one for Building 3 and one for the site lighting) on center.
Pad Utility, Center
Center Center
No
4,800V, 3-Phase, 3W Delta
480&277/480V, 3-Ph; 120/208V, 3-PhUnderground
Overhead & UndergroundPrimary Service
Secondary Service
Distribution Characteristics
Number of Deficiencies = 17. Electrical (Service)
Transformer Maint Resp
Utility,Center
System Capacity Adequate System Condition
Yes Fair
Generator
Natural Gas
8. Electrical (Site Lighting)
Roadways Parking Walkways Building Outdoor Sports
Mounting
Control
Pole Pole Pole Building Pole
Photocell Photocell Photocell Photocell Photocell
System Ownership Maintenance Responsibility System Capacity Adequate System Condition
Center Center No Good
Comments: The site lighting system within the property is owned and maintained by the center. Site lighting is accomplished by cobra head and shoe type pole-mounted light fixtures and wall-mounted HID fluorescent flood lights. Poles with two cobra head pole-mounted light fixtures are utilized at the basketball court and parking areas. Perimeter lighting in the public space, utilizing colonial style and cobra-head pole-mounted fixtures, belongs to the city and is mostly not operational.
ATS MTS
No No
Metering Individual and Master
Page: 4 Date: 03/06/2012 of 4
ACCESSIBILITY
Yes
NoNoNoNo
Nationally Registered Site
Site Eligible for National Register
Located in Historic District
Archaeological Significance
Comments:
Telephone Company
On-site Line Owner
The center's main telephone/data communication equipment is located in the Building 1E data closet. Overhead and underground fiber optic cabling is utilized between the buildings for computer network, VoIP and security cameras. Long-distance telephone (VoIP), local and internet service to the center is provided by JCDC through AT&T. Three T1 lines connected to 2 Cisco 3800 routers are provided and managed by JCDC. The equipment manufactured by Cisco is connected to a UPS back-up system. Also Main Building is provided by redundant power service in case of a power outage. Cable TV service is provided in Buildings 1A, 1B, 1C, 1D and 3. The center security system consists of 47 CCTV cameras, monitored by color screen monitor in the security office of Building 1D. Magnetic door alarms for an unauthorized egress, provided in Dormitory Building 1A and dormitory floors of Building 1B, are not in use. A central fire alarm control/annunciator panel, in first-floor main lobby of Building 1D, monitors all fire alarm panels on the center. The system has a self-diagnostic feature and a status printer in the Safety and Security Manager's office. Last FA inspection was done by SimplexGrinnell ((248) 427-5050) 01/24/2011.
AT&T
Maint. Responsibility
Center Center
Security Cameras, Color Monitor
N/AN/AN/A N/AN/A NoN/A
STORAGE TANKS
TypeStatus Location Owner Fuel Type Capacity (Gallons) Install Date
Earthquake Risk
Low Low LowMedium MediumIBC Low
LightningEarthquake Def. Authority Flooding Tornado Hurricane Forest
Fire
ID
Reg.
Accessible Parking: Accessible Slope:
Yes
Curb Cuts:
Yes
Ramps:
N/AYes
Site Accessible Route:
GENERAL SITE CONDITION
Rating X Good Fair Poor
HISTORIC PRESERVATION
9. Electrical (Communication/Alarm/Security)
NATURAL HAZARDS
The site condition is not impacting the functional use of the facilities.
The site condition IS impacting the functional use of the facilities.
The site condition IS SIGNIFICANTLY impacting the functional use of the facilities.
N/A
Purpose
Yes
Central
VOIP
System Capacity Adequate System Condition
GoodYes
Number of Deficiencies = 8
Fire Alarm Security
Building Descriptions and Utilities Detroit
BUILDING 1A DORMITORYBUILDING 1A - DORMITORY
Building Descriptions Date: Mar. 09, 2012Center : Detroit (00504) Page: 1 of 37
Building: 0001A - DORMITORY
BUILDING ENVELOPE
Foundation RoofBuilding
Concrete Loadbearing Masonry Steel
Brick Masonry Glass Block
Wall Roof Rigid Rigid
Metal Units - Metal Frame
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership#Floors
Residential 64,290 52,155 4 Owned 1935 Unevaluated
Comments: Elevator service is provided through the connection to Building 1B. Accessible sleeping rooms and corresponding toilet/shower rooms lack fire alarm horn/strobes.
REAL ESTATE
Access to Building
Ramps
Entrance
2nd Egress
Visual Alarm
Corridor/Aisle
Rooms
Stairs
Elevator
Restrooms
Drinking Fountain
Telephone
Yes
N/A
No
Yes
Yes
Yes
Yes
Yes
N/A
No
No
Yes
ACCESSIBILITY
Structural Systems1.
Exterior Walls2.
Insulation4.
Exterior Doors5.
Material
Asbestos: Yes
Drainage Year Life
Remaining Type Area Served
Single Ply Gutters and Downspouts 2000 9 Flat Entire Building
3. Roof
Entire Building
Area Served
Page: 2 of 37
Building: 0001A - DORMITORY
INTERIOR FINISH
Carpet Ceramic Tile Concrete Vinyl Tile
Brick CMU Clay tile Drywall Exposed Structure
Metal Unit - Metal Frame Wood Unit - Metal Frame
VERTICAL CIRCULATION
Concrete Stairs Metal Stairs
Double Hung - Aluminum Frame; Double Glazing; Fixed - Aluminum Frame; Double Glazing;
Fixed - Aluminum Frame; Single Glazing; Sliding - Aluminum Frame; Double Glazing;
Acoustical Tile Exposed Structure Gypsum Board Plaster
Number of Deficiencies = 1
Windows6.
Floors1. Asbestos: Yes
Interior Walls2.
3.
Interior Doors4. Number of Deficiencies = 1
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
The boiler is located in Building 1E (see there for details). The steam is provided to three air handlers (AHUs, one located on and serving the first floor, two on the fourth). These AHUs were manufactured to operate as multi-zone units, but have been modified to operate as single zone units.
Hot water baseboard convectors serve the perimeter of the building and are provided with hot water from a steam-to-water heat exchanger.
There are six packaged rooftop units (McQuay #LGA240SH1G, 420 MBH input, built 1998) each serve one of the three wings of the second or third floor. They are controlled by a single thermostat creating one, single zone.
Comments:
Comments:
Comments:
HVAC
Heat1. Asbestos: Yes Number of Deficiencies = 1
Gas-Fired Steam Boiler
Gas-Fired Steam Boiler
Gas-Fired Packaged
Single-Zone
AHU
Baseboard Convector
Single Duct
Two-Pipe
Two-Pipe
None
Pneumatic
Thermostatic Valves
Electric
Mechanical
Natural
Mechanical
None
None
Economizer
Dorm Rooms
Entire Building
Dorm Rooms
Ceilings
Page: 3 of 37
Building: 0001A - DORMITORY
Mechanical
Mechanical
Mechanical
Mechanical
Equipment Room
Toilet/Shower
Janitor's Closet
Laundry
Comments: The steam tunnel is provided with exhaust ventilation at several locations.
Ventilation Area Served
Air-Cooled Chiller
Packaged Direct
Expansion (Air Source)
Single-Zone
AHU
Single Duct
Two-Pipe
None
Pneumatic
Pneumatic
Mechanical
Mechanical
None
Economizer
Dorm Rooms
Dorm Rooms
Exhaust Ventilation
The air-cooled chiller is located on the roof of Building 1E (see there for details). The chilled water is provided to three air handlers (AHUs, one located on and serving the first floor, two on the fourth).
These AHUs were manufactured to operate as multi-zone units, but have been modified to operate as single zone units.
There are six packaged rooftop units (McQuay #LGA240SH1G, 20 ton, built 1998) each serving one of the three wings of the second or third floor. They are controlled by a single thermostat, creating one single zone. The units are equipped with power exhaust for use with the economized modes.
Comments:
Comments:
Ventilation2.
System Type
Number of Deficiencies = 3
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
3. Air Conditioning
Page: 4 of 37
Building: 0001A - DORMITORY
Piping is galvanized steel in the steam tunnels and risers; branch lines are copper. Hot water is stored in two 200-gallon storage tanks, which are supplied from a steam-to-water heat exchanger in the first floor mechanical equipment room. Builidng 1A has a metered domestic water service.
Comments:
Cast Iron/PVC None Cast Iron
Bathtub Electric Water Cooler Lavatory Mop Sink Service Sink Shower Sink Wall Hydrant Water Closet (Flush Valve) Water Closet (Tank)
Gas (Natural)
Comments:
Wet Wet ABC Type Fire Extinguisher
Comments: The stand pipe cabinets are in the corridors without a hose.
Comments: This building is served from substation #1 located in the Boiler Building 1E electrical room by several laterals. Two laterals from a 125A CB and a 400A CB, through 50 kVA and 167 kVA, 480:120/240V, pad-mounted transformers serve an 800A, 240/120 distribution panel with an 800A MCB. Third lateral (from 150A CB) serves a 150A MLO emergency panel. The next laterals serve 200A MCB MCC-D and 200A, 240V roof-mounted switchboard, both serving HVAC loads. The 800A distribution panel serves a 112.5 kVA pad-mounted transformer, which converts the 240V primary to the 120/208V secondary and a 400A MLO distribution panel (400A CB). The 400A panel serves a 200A MLO (200A CB) and (3) 100A MLO (200A CB) laundry floor panels. Also, both distribution panels (800A & 400A) serve wing's secondary panels. The 50 kVA & 167 kVA transformers and 200A MCB MCC-D are located in the exterior first floor mech. room. Two distribution panels & 112.5 kVA transformer are located in the first floor interior mech.
room.
Galvanized Steel and Copper
Galvanized Steel and Copper
Steam Heat Exchanger
None Yes
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
High Intensity Discharge (HID)
Comments: The building-mounted exterior lights are controlled by photocell.
Main Distribution Panel 480V, 3-Phase, 3 Wire Panelboard Receptacles, GFCI, Switches
Sprinkler System Stand Pipe System Fire Suppression
PLUMBING
Water Distribution1.
Sanitary Distribution2.
Fixtures3. Number of Deficiencies = 2
Fuel Distribution4.
FIRE PROTECTION
ELECTRICAL SERVICES Number of Deficiencies = 3
Exterior Lighting1. Number of Deficiencies = 2
Gas is metered for Buildings 1A, 1B, 1C, and 1D at Building 1E.
LIGHTING
Page: 5 of 37
Building: 0001A - DORMITORY
FIRE ALARM
Comments: The building fire alarm control/annunciator panel is a Simplex model 4120 located in the first floor laundry room. It is monitored by the central fire alarm control/annunciator panel in Building 1D.
Audible Alarm Control/Annunciator Panel Duct Smoke Detector Flow/Tamper Switch Manual Pull Station Smoke Detector Visual Alarm
Comments: Recorded footcandle levels include natural light contribution. Some sleeping rooms have compact-fluorescent fixtures in addition to T8-fluorescent fixtures. Some janitor closets have incandescent lamps.
Comments: Emergency lights are selected T8-fluorescent fixtures with battery backup (integral emergency battery/ballast) utilized at the stairs. Some linear fluorescent light fixtures with battery backup (integral emergency battery/ballasts) are also provided.
T8 - Fluorescent
T8 - Fluorescent
Incand., T8&T12 - Fluorescent
Incand., T8 - Fluorescent, CF
Compact Fluorescent
T8 - Fluorescent
T8 - Fluorescent
Incand., T8 -Flourescent
T8 - Fluorescent
Incand., T12 - Fluorescent
T8 - Fluorescent
Incandescent
Sleeping Rooms
Offices
Storage Rooms
Toilets
Shower
Housing Lounge
Corridors & Stairs
Shaving, Make-Up, Grooming
Laundry Room
Equipment Rooms (Elec/Mech)
Lounges
Toilets
Area Recommended Level
Recorded Level Light Type
Battery Backup Battery Backup
Emergency Exit
Number of Deficiencies = 2
Interior Lighting2. Number of Deficiencies = 2
Emergency /Exit Lighting3. Number of Deficiencies = 3
Type Location None None
Comments: There is no need for carbon monoxide detectors, due to the fact that there are no gas operated HVAC units at the floors.
CARBON MONOXIDE DETECTION
Page: 6 of 37
Building: 0001A - DORMITORY
Comments: The building is connected to the center's LAN system for data communication. The closed circuit TV cameras are mounted on the building exterior, in front of the floor lounges and in some locations along the wing corridors. The surveillance cameras mounted along wing corridors are looking like smoke detectors, which interfere with the existing fire alarm system and give a false sense of protection. Some exit doors have audible alarm devices for unauthorized egress, which are currently not in use. Pay phones are provided for student use on the second floor. Cable TV is provided in the sleeping rooms and lounges.
Connected to Main System Closed Circuit TV None Local Cable Company
Telephone Security Public Address Television
GENERAL BUILDING CONDITION
Rating
Comments:
X Good Fair Poor
Room finishes (torn carpet, damaged ceilings, and damaged doors) are deteriorated particularly in bathrooms. Steam and condensate piping is deteriorated and leaking. HVAC pneumatic controls are not functional. Domestic water distribution system is failing. Most electrical panelboards are 70 years old and unreliable.
COMMUNICATION Number of Deficiencies = 1
The facility condition is not impacting the functional use of the facility.
The facility condition IS impacting the functional use of the facility.
The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.
Electric Water Gas Yes NoZone
BUILDING UTILITY METERING
Structure: Good Exterior: Good Interior: Fair Mechanical: Poor Electrical: Fair
This building has been recommended for demolition in the Long Range Development Plan after construction of new dormitoriy buildings. The demolition is included in Project 3169.
DEMOLITION RECOMMENDATION
BUILDING 1B ADMINISTRATION/DORMITORYBUILDING 1B - ADMINISTRATION/DORMITORY
Page: 7 of 37
Building: 0001B - ADMINISTRATION/DORMITORY
BUILDING ENVELOPE
Foundation RoofBuilding
Concrete Loadbearing Masonry Steel
Brick Masonry
Wall Roof Rigid Rigid
Metal Units - Metal Frame
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership#Floors
Residential 24,520 13,870 4 Owned 1935 Unevaluated
Comments: Accessible sleeping rooms and corresponding toilet/shower rooms lack fire alarm horn/strobes.
REAL ESTATE
Access to Building
Ramps
Entrance
2nd Egress
Visual Alarm
Corridor/Aisle
Rooms
Stairs
Elevator
Restrooms
Drinking Fountain
Telephone
Yes
N/A
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
N/A
ACCESSIBILITY
Structural Systems1.
Exterior Walls2.
Insulation4.
Exterior Doors5.
Material
Asbestos: Yes
Drainage Year Life
Remaining Type Area Served
Single Ply Interior Roof Drains 2000 9 Flat Entire Building
3. Roof
Page: 8 of 37
Building: 0001B - ADMINISTRATION/DORMITORY
INTERIOR FINISH
Carpet Ceramic Tile Concrete Vinyl Tile
Ceramic Tile Drywall Exposed Structure
Metal Unit - Metal Frame Wood Unit - Metal Frame
Mechanical
Mechanical
Toilet/Shower
Janitor's Closet
Ventilation Area Served
VERTICAL CIRCULATION
Concrete Stairs Elevator
Comments: There is one working elevator in the building. The other three elevators are not operable.
Fixed - Aluminum Frame; Double Glazing; Fixed - Aluminum Frame; Single Glazing;
Acoustical Tile Exposed Structure Gypsum Board Plaster
Exhaust Ventilation
Number of Deficiencies = 1
Windows6.
Floors1.
Interior Walls2.
3.
Interior Doors4.
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
The boiler is located in Building 1E (see there for details). The steam is provided to an air handler (AHU) that serves the entire building. The AHU was manufactured to operate as a multi-zone unit, but has been modified to operate as a single zone unit.
Comments:
HVAC
Heat1. Asbestos: Yes Number of Deficiencies = 1
Gas-Fired Steam Boiler
Gas-Fired Steam Boiler
Single-Zone
AHU
Baseboard Convector
Two-Pipe
Two-Pipe
Pneumatic
Thermostatic Valves
Mechanical
Natural
None
None
Entire Building
Entire Building
Ventilation2. Number of Deficiencies = 2
Page: 9 of 37
Building: 0001B - ADMINISTRATION/DORMITORY
The water heater (Laars, +/- 1500 MBH) and storage tank (PVI #P225AT, 225 gallon) are located in the second floor mechanical equipment room of Building 1D. During the heating season, domestic hot water is supplied by a steam heat exchanger in Building 1E. Water is metered for Buildings 1B at Boiler Building 1E. Piping is galvanized steel in the steam tunnels and risers; branch lines are copper.
Comments:
Cast Iron None Cast Iron
Drinking Fountain Electric Water Cooler Lavatory Service Sink Shower Sink Wall Hydrant Water Closet (Flush Valve)
None
Wet Wet ABC Type Fire Extinguisher
Comments: The stand pipe cabinets are in the corridors without a hose.
Galvanized Steel and Copper
Galvanized Steel and Copper
Gas-Fired None Yes
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Air-Cooled Chiller
Single-Zone
AHU
Two-Pipe Pneumatic Mechanical None Entire Building
Sprinkler System Stand Pipe System Fire Suppression
PLUMBING
The air-cooled chiller is located on the roof of Building 1E (see there for details). The chilled water is provided to three air handlers (AHUs, one located on and serving the first floor, two on the fourth).
These AHUs were manufactured to operate as multi-zone units, but have been modified to operate as single zone units.
Comments:
System Type
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Water Distribution1.
Sanitary Distribution2.
Fixtures3.
Fuel Distribution4.
FIRE PROTECTION
Page: 10 of 37
Building: 0001B - ADMINISTRATION/DORMITORY
Comments: This building is served from a 1,600A switchboard (400A disconnect switch) located behind Boiler Building 1E. Service enters to a 600A, 480V MLO switchboard. This switchboard serves three buildings air handling units and a 225 kVA pad-mounted transformer (300A CB) providing 120/208V system for smaller loads in the building. A 600A MCB, 120/208V distribution panel served from the transformer, provides for four 100A MLO floor panels (100A CB) and a 100A MLO penthouse panel (60A CB).
FIRE ALARM
Comments: The building fire alarm control/annunciator panel is a Simplex model 4120 located in the first floor waiting area. It is monitored by the central fire alarm control/annunciator panel in Building 1D.
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
Audible Alarm Control/Annunciator Panel Duct Smoke Detector Flow Switch Manual Pull Station Smoke Detector Tamper Switch Visual Alarm
Comments: Recorded footcandle levels include natural light contribution. CFL task lighting is provided where study desks were once located in sleeping rooms.
Comments: Emergency lights are selected T8-fluorescent fixtures with battery backup (integral emergency battery/ballasts). Wall-mounted emergency battery-backup lights are used in some areas.
High Intensity Discharge (HID)
Comments: The building-mounted exterior lights are controlled by photocell.
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
Incand., T8&T12 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent, CF
T8 - Fluorescent, CF
Compact Fluorescent
Compact Fluorescent
T8 - Fluorescent
Sleeping Rooms
Offices
Conference Rooms
Corridors & Stairs
Equipment Rooms (Elec/Mech)
Housing Lounge
Laundry Room
Shaving, Make-Up, Grooming
Storage Rooms
Shower
Toilets
Study Room
Area Recommended Level
Recorded Level Light Type
Selected Lighting w/ Battery Battery Backup
Switchboard 480V, 3-Phase, 3 Wire Panelboard Receptacles, GFCI, Switches
Emergency Exit
Number of Deficiencies = 1
ELECTRICAL SERVICES Number of Deficiencies = 1
Exterior Lighting1.
Interior Lighting2.
Emergency /Exit Lighting3. Number of Deficiencies = 1
Page: 11 of 37
Building: 0001B - ADMINISTRATION/DORMITORY
Comments: The building is connected to the center's LAN system for data communication. The closed circuit TV cameras are provided at the exterior and along the corridors. Some exit doors have audible alarm devices for unauthorized egress. Cable TV is provided in sleeping rooms and lounges.
Connected to Main System None None Local Cable Company
Telephone Security Public Address Television
GENERAL BUILDING CONDITION
Rating
Comments:
X Good Fair Poor
Room finishes (torn carpet, damaged ceilings, and damaged doors) are deteriorated particularly in bathrooms. Steam and condensate piping is deteriorated and leaking. HVAC pneumatic controls are not functional. Most electrical panelboards are 70 years old and unreliable.
COMMUNICATION Number of Deficiencies = 1
The facility condition is not impacting the functional use of the facility.
The facility condition IS impacting the functional use of the facility.
The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.
Electric Water Gas No NoZone
BUILDING UTILITY METERING
Structure: Good Exterior: Good Interior: Fair Mechanical: Poor Electrical: Fair
This building has been recommended for demolition in the Long Range Development Plan after construction of new dormitory buildings. The demolition is included in Project 3169.
DEMOLITION RECOMMENDATION
Type Location None None
Comments: There is no need for carbon monoxide detectors, due to the fact that there are no gas operated HVAC units at the floors.
CARBON MONOXIDE DETECTION
BUILDING 1C MEDICAL/DENTAL/STUDENT LOUNGEBUILDING 1C - MEDICAL/DENTAL/STUDENT LOUNGE
Page: 12 of 37
Building: 0001C - MEDICAL/DENTAL/STUDENT LOUNGE
BUILDING ENVELOPE
Foundation RoofBuilding
Concrete Concrete Steel
Brick Masonry
Wall Roof Rigid Rigid
Metal Units - Metal Frame
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership#Floors
Business 8,060 4,181 2 Owned 1935 Unevaluated
Comments: The second floor is accessible by the elevator in Building 1B.
REAL ESTATE
Access to Building
Ramps
Entrance
2nd Egress
Visual Alarm
Corridor/Aisle
Rooms
Stairs
Elevator
Restrooms
Drinking Fountain
Telephone
Yes
N/A
Yes
Yes
Yes
Yes
Yes
Yes
N/A
Yes
No
Yes
ACCESSIBILITY
Structural Systems1.
Exterior Walls2.
Insulation4.
Exterior Doors5.
Material Drainage Year Life
Remaining Type Area Served
Single Ply Interior Roof Drains 2001 10 Flat Entire Building
3. Roof
Page: 13 of 37
Building: 0001C - MEDICAL/DENTAL/STUDENT LOUNGE
INTERIOR FINISH
Carpet Ceramic Tile Concrete Vinyl Tile
Ceramic Tile Drywall Exposed Structure
Metal Unit - Metal Frame Wood Unit - Metal Frame
Mechanical
Mechanical
Toilet/Shower
Janitor's Closet
Ventilation Area Served
VERTICAL CIRCULATION
Concrete Stairs
Comments: The second floor is accessible through the elevator in Building 1B.
Fixed - Aluminum Frame; Double Glazing; Fixed - Aluminum Frame; Single Glazing;
Acoustical Tile Exposed Structure Gypsum Board
Exhaust Ventilation
Windows6.
Floors1.
Interior Walls2.
3.
Interior Doors4.
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
The boiler is located in Building 1E (see there for details). The steam is provided to a packaged rooptop AHU (Mammoth #DHEBFP330S546AA60MV6). There are six zones.
Hot water baseboard convectors serve the perimeter spaces and are provided with hot water from a steam to hot water heat exchanger.
Comments:
Comments:
HVAC
Heat1.
Gas-Fired Steam Boiler
Gas-Fired Steam Boiler
Multi- Zone/Single
AHU
Baseboard Convector
Two-Pipe
Two-Pipe
Pneumatic
Pneumatic
Mechanical
Natural
None
None
Entire Building
Entire Building
Ventilation2. Number of Deficiencies = 1
Page: 14 of 37
Building: 0001C - MEDICAL/DENTAL/STUDENT LOUNGE
Water is metered for Building 1C at Building 1E. Piping is galvanized steel in the steam tunnels and risers; branch lines are copper. Domestic hot water is provided from the central plant steam heat exchanger located in Building 1E.
Comments:
Cast Iron None Cast Iron
Electric Water Cooler Lab Sink Emergency Eyewash Lavatory Mop Sink Shower Sink Urinal Wall Hydrant Water Closet (Flush Valve)
None
Wet Wet ABC Type Fire Extinguisher
Comments: The stand pipe cabinets are in the corridors without a hose.
Galvanized Steel and Copper
Galvanized Steel and Copper
Steam Heat Exchanger
None No
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Air-Cooled Chiller
Multi- Zone/Single
AHU
Two-Pipe Electric Mechanical Economizer Entire Building
Sprinkler System Stand Pipe System Fire Suppression
PLUMBING
The air-cooled chiller is located on the roof of Building 1E (see there for details). The chilled water is provided to a packaged rooptop AHU (Mammoth #DHEBFP330S546AA60MV6, 25-30 ton). There are six zones.
Comments:
System Type
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Water Distribution1.
Sanitary Distribution2.
Fixtures3. Number of Deficiencies = 1
Fuel Distribution4.
3. Number of Deficiencies = 1Air Conditioning
Page: 15 of 37
Building: 0001C - MEDICAL/DENTAL/STUDENT LOUNGE
Comments: This building is served from substation #2 (400A CB) located in the Boiler Building 1E electrical room.
Service enters to a 400A, 480V main distribution panel with a 400A main circuit breaker (MCB). This panel serves 8 HVAC units ((8) 30A CB) and a 150 kVA pad-mounted transformer (200A CB). The 150 kVA transformer serves a 400A MCB, 120/208V distribution panel providing for smaller loads in the building.
All building distribution equipment, including 150 kVA step-down transformer and 480V and 208V distribution panels, is located in the second floor main mechanical room.
FIRE ALARM
Comments: The building fire alarm devices are connected to the central fire alarm control/annunciator panel located in the main lobby of Building 1D.
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
Audible Alarm Manual Pull Station Smoke Detector Visual Alarm
Comments: Recorded footcandle levels include natural light contribution. Dental chairs additionally have task lights.
Lab areas are well illuminated with T8-Fluorescent fixtures. The medical/dental waiting room has T8-fluorescent fixtures, 50 footcandles. The TV room and barber shop have T8-fluorescent fixtures, 50 and 40 footcandles respectively. Occupancy sensors are utilized everywhere throughout the building.
Comments: Emergency lights are mostly selected T8-fluorescent fixtures with battery backup (integral emergency battery/ballast). Wall-mounted emergency battery-backup lights are used in some areas.
High Intensity Discharge (HID)
Comments: The building-mounted exterior lights are controlled by photocell.
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
Compact Fluorescent
Compact Fluorescent
Compact Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
Medical/Dental
Offices
Storage Rooms
Wards (Patient)
Toilets
Shower
Reception
Recreation
Equipment Rooms (Elec/Mech)
Corridors & Stairs
Area Recommended Level
Recorded Level Light Type
Selected Lighting w/ Battery Battery Backup
Main Distribution Panel 480V, 3-Phase, 3 Wire Panelboard Receptacles, GFCI, Switches
Emergency Exit
ELECTRICAL SERVICES Number of Deficiencies = 2
Exterior Lighting1.
Interior Lighting2. Number of Deficiencies = 1
Emergency /Exit Lighting3. Number of Deficiencies = 1
Page: 16 of 37
Building: 0001C - MEDICAL/DENTAL/STUDENT LOUNGE
Comments: The building is connected to the center's LAN system for data communication. The closed circuit TV cameras are mounted on the building exterior walls and along the corridors. The phone for student use is at the desk.
Connected to Main System Closed Circuit TV None Local Cable Company
Telephone Security Public Address Television
GENERAL BUILDING CONDITION
Rating
Comments:
X Good Fair Poor
Steam and condensate piping is deteriorated and leaking. HVAC system is in poor condition and no longer functions adequately. Electrical distribution equipment is old and unreliable.
COMMUNICATION
The facility condition is not impacting the functional use of the facility.
The facility condition IS impacting the functional use of the facility.
The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.
Electric Water Gas No NoZone
BUILDING UTILITY METERING
Structure: Good Exterior: Good Interior: Good Mechanical: Poor Electrical: Fair
This building has been recommended for renovation in the Long Range Development Plan.
RENOVATION RECOMMENDATION
BUILDING 1D CLASSROOM/ADMIN/CAFETERIABUILDING 1D - CLASSROOM/ADMIN/CAFETERIA
Page: 17 of 37
Building: 0001D - CLASSROOM/ADMIN/CAFETERIA
BUILDING ENVELOPE
Foundation RoofBuilding
Concrete Concrete Steel
Brick Masonry
Wall Roof Rigid Rigid
Metal Overhead - Steel Frame Metal Unit - Metal Frame
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership#Floors
Business 64,830 39,144 2 Owned 1935 Unevaluated
Comments: The second floor is accessible by the elevator in Building 1B.
REAL ESTATE
Access to Building
Ramps
Entrance
2nd Egress
Visual Alarm
Corridor/Aisle
Rooms
Stairs
Elevator
Restrooms
Drinking Fountain
Telephone
Yes
N/A
Yes
Yes
Yes
Yes
Yes
Yes
N/A
Yes
Yes
N/A
ACCESSIBILITY
Structural Systems1.
Exterior Walls2.
Insulation4.
Exterior Doors5.
Material
Asbestos: Yes
Drainage Year Life
Remaining Type Area Served
Single Ply Interior Roof Drains 2001 10 Flat Entire Building
3. Roof
Page: 18 of 37
Building: 0001D - CLASSROOM/ADMIN/CAFETERIA
INTERIOR FINISH
Carpet Ceramic Tile Concrete Vinyl Tile
Ceramic Tile Drywall Exposed Structure
Metal Unit - Metal Frame Wood Unit - Metal Frame
VERTICAL…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .