Direct Bury Pipe - Salient Characteristics.pdf

PDF 690 KB Posted

Attached to
Y1LC--Replace Steam Line Buildings 115, 118, and 400 [552-24-512]
Solicitation number
36C25025B0032_A00005
Issued by

About this file

These are technical engineering drawings for the Dayton VA Medical Center steam and condensate piping system, prepared by Rovanco Piping Systems. The documents detail a direct bury pipe system using an INSUL-800 pre-insulated pipe configuration with specific technical specifications for steam and condensate lines. Key technical details include:

Steam line specifications: 10" steam carrier pipe using XS A106B seamless steel pipe, mineral wool insulation with a K-value of no greater than 0.29 at 200°F, and a 10 GA welded steel conduit. The system uses high-density polyethylene (HDPE) outer jacket with 175 mil minimum thickness. The piping is designed to be fully spooled in 40' straight lengths, with match-marked spools and specific installation requirements. The drawings include detailed cross-sections, elbow details, field joint configurations, and a pipe layout showing connections between multiple vaults and building walls, with total pipe runs ranging from 172' to 190' across different segments.

View the file

Other files

File Type Posted
B-118 HV1.00.pdf PDF
024100 demolition.pdf PDF
B118 outside power and water.jpg JPG image
B-115 M-01.pdf PDF
B-118 HV200.pdf PDF
Building 118 Basement Photos.docx DOCX document
Electrical Distribution Plan B115 B118 B400.docx DOCX document
312011 earthwork.docx DOCX document
B-400 M-02.pdf PDF
015719 Temp Environ Cont.docx DOCX document
Building 400 Basement Photos.docx DOCX document
36C25025B0032 A00005.pdf PDF
Contractor Areas.jpg JPG image
Pre-Bid RFIs Answers.xlsx XLSX spreadsheet
Building 115 Basement Photos.docx DOCX document
Show all 15

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DESIGN CRITERIA

SERVICE PSIG TEMP.

DESIGN

TEMP.

AMBIENT

LENGTH/100'TEMP.

STEAM 140 360°F 50°F 310°F 2.526"

COND - 212°F 50°F 162°F 1.340"

OPERATING SERVICE CRITERIA

SERVICE PSIG TEMP.

DESIGN

TEMP.

AMBIENT

LENGTH/100'TEMP.

STEAM N.A. N.A. N.A. N.A. N.A.

COND N.A. N.A. N.A. N.A. N.A.

ENGINEERED PIPING SYSTEM BY

ROVANCOâ PIPING SYSTEMS

20535 SE FRONTAGE RD. - JOLIET, ILLINOIS 60431

PH. (815) 741-6700 - FAX: (815) 741-4229

WEB: WWW.ROVANCO.COM

CUSTOMER

OWNER

ENGINEER

TITLE

BYREV

FOR

DESCRIPTIONDATE

SHT NO

APPROVED BY:

CK

DATE: DRAWING NO.:

DRAWN BY:

CHECKED BY:P.O. NUMBER

JOB NO.:

SCALE

OF

THIS DRAWING IS PROPERTY OF ROVANCO PIPING SYSTEMS, INC. IT IS STRICTLY FORBIDDEN TO SHARE WITH ANY THIRD PARTY, WITHOUT WRITTEN CONSENT

BUCKEYE INDUSTRIAL PIPING

N.A.

DAYTON VA MEDICAL CENTER

STEAM & CONDENSATE

CROSS SECTIONS & NOTES

DAYTON VA PROJECT

1 5

10601

NONEZA124112

09/04/2024 ZA

69759 ZA

SUBMITTAL DRAWING BASED ON

REV DATE SPECIFICATION

THIS DRAWING HAS BEEN REVIEWED FOR DESIGN

CONFORMANCE TO APPLICABLE STANDARDS AND

SPECIFICATIONS AND DETAILS REVIEWED FOR ACCURACY.

ENGINEER / OWNER DESIGN APPROVAL

DRAWING APPROVAL

BY: DATE:

ENGINEER

WRITTEN APPROVAL MUST BE RECEIVED BY ROVANCO BEFORE

PROJECT IS RELEASED FOR FABRICATION AFTER APPROVAL

DRAWINGS WILL BE ISSUED AND PROJECT SCHEDULED FOR

PRODUCTION.

CONTRACTOR FIELD DIMENSION APPROVAL

THIS DRAWING HAS BEEN REVIEWED FOR CONFORMANCE TO

SITE CONDITIONS. THE DIMENSIONS AND DETAILS SHOWN HAVE

BEEN VERIFIED AND CERTIFIED FOR FABRICATION.

BY: DATE:

CERTIFICATION OF FIELD DIMENSIONS

CONTRACTOR

SERVICE CARRIER OD CARRIER TYPE CARRIER INSULATION CONDUIT OD CONDUIT

INSULATION

OUTER

JACKET OD

10" STM. 10.750" XS A106B SMLS

STEEL 2" MIN. WOOL 18" 1.9" PIR300 22.33"

N.T.S.

TRENCH CROSS SECTION

CARRIER PIPE

CARRIER INSULATION

CONDUIT

CONDUIT INSULATION

OUTER JACKET

SERVICE CARRIER OD CARRIER TYPE CARRIER

INSULATION

HDPE OUTER

JACKET OD

2" COND. 2.375" XS A53B ERW STEEL 2.6" PIR300 8.06"

N.T.S.

BEDDING AS REQUIRED

BY SPECIFICATIONS

TRENCH CROSS SECTION

CARRIER PIPE

CARRIER INSULATION

OUTER JACKET

BEDDING AS REQUIRED

BY SPECIFICATIONS

GENERAL NOTES

1. ALL BELOW GROUND STEAM LINES ARE AN INSUL-800 SYSTEM AS

MANUFACTURED BY ROVANCO PIPING SYSTEMS INC., JOLIET, ILLINOIS.

1.1. 10" STEAM CARRIER PIPE SHALL BE XS A106B SMLS STEEL PIPE WITH

BEVELED CUT ENDS FOR BUTT/ WELD.

1.2. CARRIER PIPE INSULATION SHALL BE MINERAL WOOL CONFORMING TO ASTM

C-547 WITH A K-VALUE OF NO GREATER THAN .29 AT 200°F. SECTIONAL

INSULATION IS BANDED ON PIPE WITH STAINLESS STEEL BANDING ON 18"

CENTERS.

1.3. THE CONDUIT SHALL BE 10 GA. WELDED STEEL CONFORMING TO ASTM A-139.

1.4. THE CONDUIT INSULATION SHALL BE HI-TEMP POLYISOCYANURATE FOAM

INSULATION WITH AN INITIAL K FACTOR OF .14 @ 50°F, DENSITY OF 2 PCF,

CLOSED CELL CONTENT OF 90%, COMPREHENSIVE STRENGTH OF 30 PSI,

RATED FOR 300°F. CONFORMING TO ASTM STANDARD D1621, 1622, 2126, 2842,

2856, AND C518-91.

1.5. THE OUTER JACKET IS A HIGH DENSITY POLYETHYLENE WITH A MINIMUM

THICKNESS OF 175 MILS CONFORMING TO ASTM D3350.

1.6. THIS SYSTEM IS TO BE FULLY SPOOLED OUT WITH MATCH MARKED SPOOLS

AND TO BE SUPPLIED IN {40'} STRAIGHT LENGTHS OF PIPE.

1.7. ALL CONDUIT UNITS WILL BE SHIPPED WITH SHIPPING BARS IN PLACE,

ATTACHING THE CARRIER PIPES TO THE CONDUIT. THESE SHIPPING BARS

MUST BE REMOVED IN THE FIELD PRIOR TO CLOSING OF THE FIELD JOINT.

DETAILED INSTALLATION INSTRUCTIONS WILL BE PROVIDED WITH SHIPMENT.

2. ALL DIMENSIONS AND DESIGN PARAMETERS SHOWN ON THIS DRAWING MUST BE

VERIFIED BY THE INSTALLING CONTRACTOR. CORRECTED FIELD DIMENSIONS AND

/ OR DESIGN PARAMETERS MUST BE SHOWN ON THIS DRAWING. WE REQUIRE 1

COPY OF THIS DRAWING MARKED "APPROVED AND RELEASED FOR FABRICATION"

PRIOR TO RELEASING THIS PROJECT FOR FABRICATION. PLEASE SIGN APPROVAL

BLOCK PROVIDED.

3. ALL DIMENSIONS ARE CENTER LINE OF CARRIER PIPE TO CENTER LINE OF

CARRIER PIPE OR FROM CENTER LINE OF CARRIER PIPE TO END OF CARRIER PIPE.

GENERAL NOTES

1. ALL BELOW GROUND CONDENSATE LINES ARE AN INSUL-8 JACKETED FOAM

SYSTEM AS MANUFACTURED BY ROVANCO PIPING SYSTEMS INC., JOLIET, IL.

1.1. 2" COND. CARRIER PIPE SHALL BE XS A53B ERW STEEL PIPE WITH BEVELED

ENDS FOR BUTT WELD.

1.2. CARRIER PIPE INSULATION SHALL BE HI-TEMP POLYISOCYANURATE FOAM

INSULATION WITH AN INITIAL K FACTOR OF .14 @ 50°F, DENSITY OF 2 PCF,

CLOSED CELL CONTENT OF 90%, COMPREHENSIVE STRENGTH OF 30 PSI,

RATED FOR 300°F. CONFORMING TO ASTM STANDARD D1621, 1622, 2126, 2842,

2856, AND C518-91.

1.3. THE OUTER JACKET SHALL BE HIGH DENSITY POLYETHYLENE WITH A

MINIMUM THICKNESS OF 175 MILS CONFORMING TO ASTM D3350.

2. THIS SYSTEM IS TO BE FULLY SPOOLED OUT WITH MATCH MARKED SPOOLS AND

TO BE SUPPLIED IN {40'} STRAIGHT LENGTHS OF PIPE.

3. ALL DIMENSIONS AND DESIGN PARAMETERS SHOWN ON THIS DRAWING MUST BE

VERIFIED BY THE INSTALLING CONTRACTOR. CORRECTED FIELD DIMENSIONS AND

/ OR DESIGN PARAMETERS MUST BE SHOWN ON THIS DRAWING. WE REQUIRE 1

COPY OF THIS DRAWING MARKED "APPROVED AND RELEASED FOR FABRICATION"

PRIOR TO RELEASING THIS PROJECT FOR FABRICATION. PLEASE SIGN APPROVAL

BLOCK PROVIDED.

4. ALL DIMENSIONS ARE CENTER LINE OF CARRIER PIPE TO CENTER LINE OF

CARRIER PIPE OR FROM CENTER LINE OF CARRIER PIPE TO END OF CARRIER PIPE.

VHADAYGILLAS

Text Box For Direct Bury Pipe

DESIGN

TEMP.

AMBIENT

LENGTH/100'TEMP.

STEAM 140 360°F 50°F 310°F 2.526"

COND - 212°F 50°F 162°F 1.340"

OPERATING SERVICE CRITERIA

SERVICE PSIG TEMP.

DESIGN

TEMP.

AMBIENT

LENGTH/100'TEMP.

STEAM N.A. N.A. N.A. N.A. N.A.

COND N.A. N.A. N.A. N.A. N.A.

ENGINEERED PIPING SYSTEM BY

ROVANCOâ PIPING SYSTEMS

20535 SE FRONTAGE RD. - JOLIET, ILLINOIS 60431

PH. (815) 741-6700 - FAX: (815) 741-4229

WEB: WWW.ROVANCO.COM

CUSTOMER

OWNER

ENGINEER

TITLE

BYREV

FOR

DESCRIPTIONDATE

SHT NO

APPROVED BY:

CK

DATE: DRAWING NO.:

DRAWN BY:

CHECKED BY:P.O. NUMBER

JOB NO.:

SCALE

OF

THIS DRAWING IS PROPERTY OF ROVANCO PIPING SYSTEMS, INC. IT IS STRICTLY FORBIDDEN TO SHARE WITH ANY THIRD PARTY, WITHOUT WRITTEN CONSENT

BUCKEYE INDUSTRIAL PIPING

N.A.

DAYTON VA MEDICAL CENTER

STEAM - INSUL 800

DETAILS

DAYTON VA PROJECT

2 5

10601

NONEZA124112

09/04/2024 ZA

69759 ZA

X

10 Ga. RHINOCOAT STEEL

CONDUIT RING

2"

5'-0"

6"

END SEAL

10 GA. BARE

STEEL CONDUIT

CARRIER

INSULATION

CARRIER PIPE

NOTCH ANCHOR PLATE

AT 12 O'CLOCK POSITION

TO INDICATE TOP

1/2 " THICK

STEEL PLATE

2"

CROSS SECTION X-X

ROUND ANCHOR 1/2" THICK

4'-0"

X FACTORY APPLIED

FOAM INSULATION

FACTORY APPLIED

HIGH TEMP INSULATION

6" WIDE SHRINK

MATERIAL

HDPE JACKET

3"

1 INSUL-800 GORED ELBOW DETAIL

N.T.S.

FACTORY APPLIED

POLYETHYLENE

SHRINK MATERIAL

CARRIER PIPE

FITTING OR BEND

AS REQUIRED

HDPE OUTER

JACKET

FACTORY APPLIED

FOAM INSULATION

FACTORY APPLIED

CARRIER PIPE

INSULATION

10 Ga. BARE STEEL

INNER CONDUIT CASING

FACTORY WELDED

HDPE JOINTS

2 INSUL-800 ODD DEGREE ELBOW DETAIL

N.T.S.

HDPE OUTER

JACKET

FACTORY WELDED

HDPE JOINTS

FITTING OR BEND

AS REQUIRED

10 Ga. BARE STEEL

INNER CONDUIT CASING CARRIER

PIPE

FACTORY APPLIED

POLYETHYLENE

SHRINK MATERIAL

FACTORY APPLIED

FOAM INSULATION

FACTORY APPLIED

CARRIER PIPE

INSULATION

5 INSUL-800 FIELD JOINT DETAIL

N.T.S.

INSUL-800 CONDUIT END SEAL DETAIL

ALL OF OUR DIMENSIONS ARE TAKEN FROM

END OF CARRIER PIPE AT WALL PENETRATIONS.

N.T.S.

3" 6"

18" LONG 10 GA

FUSION BONDED EPOXY

COATED CONDUIT

3/4" DRAIN (AS REQ'D)

CARRIER PIPE

1/2" THK. STEEL PLATE

3/4" VENT (AS REQ'D)

10 Ga. STEEL

INNER CONDUIT

WALL SEAL AND APPURTENANCES

AS REQUIRED BY SPECIFICATIONS

(NOT BY ROVANCO)

CARRIER

INSULATION

HEAT SHRINK

SLEEVE

HDPE JACKET

HIGH TEMP

INSULATION

CONTINUOUSLY WELDED

CONTINUOUSLY WELDED

40'-0"

5"

6"

CARRIER PIPE

FACTORY APPLIED

CARRIER PIPE

INSULATION

HDPE OUTER

JACKET

FACTORY APPLIED

FOAM INSULATION

10 Ga. BARE STEEL

INNER CONDUIT CASING

3 INSUL-800 STRAIGHT PIPE DETAIL

N.T.S.

AutoCAD SHX Text N.T.S.

AutoCAD SHX Text

INSUL-800 ANCHOR DETAIL WITH END SEAL

AutoCAD SHX Text

HDPE OUTER JACKET

AutoCAD SHX Text

POLYETHYLENE WRAP AROUND SHRINK MATERIAL

AutoCAD SHX Text

FACTORY APPLIED FOAM INSULATION

AutoCAD SHX Text 10 Ga. BARE STEEL INNER CONDUIT CASING

AutoCAD SHX Text

FIELD APPLIED INSULATION

AutoCAD SHX Text

BANDING AND CLIPS

AutoCAD SHX Text

FIELD APPLIED FOAM INSULATION

AutoCAD SHX Text

FACTORY APPLIED INSULATION

AutoCAD SHX Text FIELD APPLIED 10 Ga. STEEL CONNECTOR BAND

AutoCAD SHX Text

HDPE SPLIT MOLD

AutoCAD SHX Text

ROCKSHIELD HDPE SLEEVE

DESIGN

TEMP.

AMBIENT

LENGTH/100'TEMP.

STEAM 140 360°F 50°F 310°F 2.526"

COND - 212°F 50°F 162°F 1.340"

OPERATING SERVICE CRITERIA

SERVICE PSIG TEMP.

DESIGN

TEMP.

AMBIENT

LENGTH/100'TEMP.

STEAM N.A. N.A. N.A. N.A. N.A.

COND N.A. N.A. N.A. N.A. N.A.

ENGINEERED PIPING SYSTEM BY

ROVANCOâ PIPING SYSTEMS

20535 SE FRONTAGE RD. - JOLIET, ILLINOIS 60431

PH. (815) 741-6700 - FAX: (815) 741-4229

WEB: WWW.ROVANCO.COM

CUSTOMER

OWNER

ENGINEER

TITLE

BYREV

FOR

DESCRIPTIONDATE

SHT NO

APPROVED BY:

CK

DATE: DRAWING NO.:

DRAWN BY:

CHECKED BY:P.O. NUMBER

JOB NO.:

SCALE

OF

THIS DRAWING IS PROPERTY OF ROVANCO PIPING SYSTEMS, INC. IT IS STRICTLY FORBIDDEN TO SHARE WITH ANY THIRD PARTY, WITHOUT WRITTEN CONSENT

BUCKEYE INDUSTRIAL PIPING

N.A.

DAYTON VA MEDICAL CENTER

CONDENSATE - FOAM PRODUCTS

DETAILS

DAYTON VA PROJECT

3 5

10601

NONEZA124112

09/04/2024 ZA

69759 ZA

1 PRE-FAB GORED ELBOW DETAIL

N.T.S.

HDPE JACKET

FOAM INSULATION

CARRIER FITTING

(OR AS REQ'D) CARRIER PIPE

2 PRE-FAB ODD DEGREE ELBOW DETAIL

N.T.S.

HDPE JACKET

FOAM INSULATION

CARRIER PIPE

6 PRE-FAB STEEL ANCHOR DETAIL

N.T.S.

1/2" CARBON STEEL

ANCHOR PLATE

2" 3"

3"

4"1"

HDPE JACKET

CARRIER PIPE

FACTORY APPLIED

FOAM INSULATION

FACTORY APPLIED WRAP

AROUND SHRINK MATERIAL

CONTINUOUSLY WELDED

10 GA STEEL RING

4 SHRINK END SEAL DETAIL

N.T.S.

WALL SEAL APPURTENANCES AND

PACKING MATERIAL AS REQUIRED

PER CONTRACT SPECIFICATIONS

(NOT BY ROVANCO)

HDPE JACKET

FOAM INSULATION

CARRIER PIPE

SHRINK

END SEAL

2" 6"

5 TYPICAL PREINSULATED PIPE DETAIL

N.T.S.

SECTION A-A

A

A

N.T.S.

40'

HDPE JACKET

CARRIER PIPE

FOAM INSULATION

ROCKSHIELD HDPE SLEEVE

3 FIELD JOINT DETAIL

N.T.S.

HDPE JACKET

POLYETHYLENE

WRAP AROUND

SHRINK MATERIAL

STEEL CARRIER PIPE

HDPE SPLIT MOLD

FIELD WELD

FIELD APPLIED

FOAM INSULATION

FACTORY APPLIED

FOAM INSULATION

5"

DESIGN

TEMP.

AMBIENT

LENGTH/100'TEMP.

STEAM 140 360°F 50°F 310°F 2.526"

COND - 212°F 50°F 162°F 1.340"

OPERATING SERVICE CRITERIA

SERVICE PSIG TEMP.

DESIGN

TEMP.

AMBIENT

LENGTH/100'TEMP.

STEAM N.A. N.A. N.A. N.A. N.A.

COND N.A. N.A. N.A. N.A. N.A.

BUNKHOUSE

BLDG. WALL

87'-6"10'87'-6"

185'

10'

VAULT 1

10" STEAM

5'5'

LEGEND

END SEAL

ANCHOR (POUR IN CONCRETE)

81'10'81'

VAULT 1

10" STEAM

2" COND.

5' 5'

10'

VAULT 2

172'

1'-6"

ENGINEERED PIPING SYSTEM BY

ROVANCOâ PIPING SYSTEMS

20535 SE FRONTAGE RD. - JOLIET, ILLINOIS 60431

PH. (815) 741-6700 - FAX: (815) 741-4229

WEB: WWW.ROVANCO.COM

CUSTOMER

OWNER

ENGINEER

TITLE

BYREV

FOR

DESCRIPTIONDATE

SHT NO

APPROVED BY:

CK

DATE: DRAWING NO.:

DRAWN BY:

CHECKED BY:P.O. NUMBER

JOB NO.:

SCALE

OF

THIS DRAWING IS PROPERTY OF ROVANCO PIPING SYSTEMS, INC. IT IS STRICTLY FORBIDDEN TO SHARE WITH ANY THIRD PARTY, WITHOUT WRITTEN CONSENT

BUCKEYE INDUSTRIAL PIPING

N.A.

DAYTON VA MEDICAL CENTER

CONDENSATE - FOAM PRODUCTS

PIPE LAYOUT

DAYTON VA PROJECT

4 5

10601

NONEZA124112

09/04/2024 ZA

69759 ZA

SEE SHEET 5

FOR CONTINUATION

DESIGN

TEMP.

AMBIENT

LENGTH/100'TEMP.

STEAM 140 360°F 50°F 310°F 2.526"

COND - 212°F 50°F 162°F 1.340"

OPERATING SERVICE CRITERIA

SERVICE PSIG TEMP.

DESIGN

TEMP.

AMBIENT

LENGTH/100'TEMP.

STEAM N.A. N.A. N.A. N.A. N.A.

COND N.A. N.A. N.A. N.A. N.A.

15'

90'

10'

90'

30'

32°

38°

10" S

TEAM

2" C

ONDENSATE

5'

5'

10'

VAULT 2

190'

1'-6"

LEGEND

END SEAL

ANCHOR (POUR IN CONCRETE)

ENGINEERED PIPING SYSTEM BY

ROVANCOâ PIPING SYSTEMS

20535 SE FRONTAGE RD. - JOLIET, ILLINOIS 60431

PH. (815) 741-6700 - FAX: (815) 741-4229

WEB: WWW.ROVANCO.COM

CUSTOMER

OWNER

ENGINEER

TITLE

BYREV

FOR

DESCRIPTIONDATE

SHT NO

APPROVED BY:

CK

DATE: DRAWING NO.:

DRAWN BY:

CHECKED BY:P.O. NUMBER

JOB NO.:

SCALE

OF

THIS DRAWING IS PROPERTY OF ROVANCO PIPING SYSTEMS, INC. IT IS STRICTLY FORBIDDEN TO SHARE WITH ANY THIRD PARTY, WITHOUT WRITTEN CONSENT

BUCKEYE INDUSTRIAL PIPING

N.A.

DAYTON VA MEDICAL CENTER

CONDENSATE - FOAM PRODUCTS

PIPE LAYOUT

DAYTON VA PROJECT

5 5

10601

NONEZA124112

09/04/2024 ZA

69759 ZA

SEE SHEET 4

FOR CONTINUATION

Sheets and Views
10601-1
10601-2
10601-3
10601-4
10601-5