B-118 HV200.pdf

PDF 657 KB Posted

Attached to
Y1LC--Replace Steam Line Buildings 115, 118, and 400 [552-24-512]
Solicitation number
36C25025B0032_A00005
Issued by

About this file

This document is an HVAC details drawing for the Dayton VA Renovation of Building 118 (Chapel Building), specifically a detailed mechanical engineering schematic (drawing HV2.00) showing various technical diagrams and connection details. The drawing includes multiple technical illustrations covering components such as floor-mounted expansion tanks, heat exchangers, steam traps, water treatment closed systems, ductwork transitions, piping connections, and valve configurations. The technical drawings provide precise mechanical engineering specifications for renovation work, with detailed symbols and notations for HVAC system components, including water coils, steam lines, and equipment interconnections. The document is dated 12/30/10 with a revision date of 08/20/12, and includes contact information for engineering firms involved in the project, including locations in Cincinnati, OH, Dayton, OH, Fort Thomas, KY, and Columbus, OH.

View the file

Other files

File Type Posted
Direct Bury Pipe - Salient Characteristics.pdf PDF
B-118 HV1.00.pdf PDF
024100 demolition.pdf PDF
B118 outside power and water.jpg JPG image
B-115 M-01.pdf PDF
Building 118 Basement Photos.docx DOCX document
Electrical Distribution Plan B115 B118 B400.docx DOCX document
312011 earthwork.docx DOCX document
B-400 M-02.pdf PDF
015719 Temp Environ Cont.docx DOCX document
Building 400 Basement Photos.docx DOCX document
36C25025B0032 A00005.pdf PDF
Contractor Areas.jpg JPG image
Pre-Bid RFIs Answers.xlsx XLSX spreadsheet
Building 115 Basement Photos.docx DOCX document
Show all 15

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DAYTON VA

RENOVATION

BUILDING 118

CHAPEL BUILDING

thinkchamplin.com

424 East Fourth Street Cincinnati, OH 45202

T 513.241.4474 F 513.241.0081

12/30/10 1 ISSUED FOR BID

WWW.KLHENGRS.COM

MECHANICAL/ELECTRICAL ENGINEERS

937-220-9702 FAX

104 BROWN STREET

DAYTON, OHIO 45402

1538 ALEXANDRIA PIKE, STE. 11

859-442-8050

859-442-8058 FAX

800-354-9783

FT. THOMAS, KENTUCKY 41075

937-220-9700

TWO MIRANOVA PLACE, SUITE 280

614-228-2183 FAX

COLUMBUS, OH 43215

614-228-2180

08/20/12 2 AS BUILTS

AutoCAD SHX Text

%%UDUCTWORK SYMBOLS

AutoCAD SHX Text

DN

AutoCAD SHX Text

DN

AutoCAD SHX Text

UP

AutoCAD SHX Text

UP

AutoCAD SHX Text

SUPPLY DUCT (UP & DOWN)

AutoCAD SHX Text

EXHAUST DUCT (UP & DOWN)

AutoCAD SHX Text

DN

AutoCAD SHX Text

UP

AutoCAD SHX Text

RETURN DUCT (UP & DOWN)

AutoCAD SHX Text

SECTION.)

AutoCAD SHX Text 10x8

AutoCAD SHX Text

VANED ELBOW (PROVIDE ALL SQUARE OR

AutoCAD SHX Text

RECTANGULAR ELBOWS WITH VANES EVEN IF

AutoCAD SHX Text

SYMBOL IS MISSING)

AutoCAD SHX Text

STANDARD RADIUS ELBOW (LONG RADIUS)

AutoCAD SHX Text NEW DUCT (INSIDE DIMENSIONS: WIDTH x DEPTH)

AutoCAD SHX Text

LOUVER (LOUVER SPECIFIED IN ARCHITECTURAL

AutoCAD SHX Text

VD

AutoCAD SHX Text

MANUAL VOLUME DAMPER

AutoCAD SHX Text

DUCT MOUNTED COIL (HOT WATER OR STEAM COIL)

AutoCAD SHX Text

SUPPLY

AutoCAD SHX Text

RETURN

AutoCAD SHX Text 45%%d

AutoCAD SHX Text RETURN, NO SPLITTER (45%%d TAP)

AutoCAD SHX Text

STANDARD BRANCH SUPPLY OR

AutoCAD SHX Text 45%%d

AutoCAD SHX Text

AUTOMATIC CONTROL DAMPER TWO POSITION

AutoCAD SHX Text

%%UPIPING SYMBOLS

AutoCAD SHX Text

HOT WATER HEATING SUPPLY

AutoCAD SHX Text

LOW PRESSURE STEAM CONDENSATE RETURN

AutoCAD SHX Text

LOW PRESSURE STEAM (15 PSIG AND BELOW)

AutoCAD SHX Text

MEDIUM PRESSURE STEAM (16 PSIG THRU 59 PSIG)

AutoCAD SHX Text

REFRIGERANT SUCTION

AutoCAD SHX Text

REFRIGERANT HOT GAS

AutoCAD SHX Text

REFRIGERANT LIQUID

AutoCAD SHX Text

DRAIN LINE

AutoCAD SHX Text

HOT WATER HEATING RETURN

AutoCAD SHX Text

MPS

AutoCAD SHX Text

MPS

AutoCAD SHX Text

MPS

AutoCAD SHX Text

LPS

AutoCAD SHX Text

LPS

AutoCAD SHX Text

LPS

AutoCAD SHX Text

LPR

AutoCAD SHX Text

LPR

AutoCAD SHX Text

LPR

AutoCAD SHX Text

HWS

AutoCAD SHX Text

HWS

AutoCAD SHX Text

HWS

AutoCAD SHX Text

HWR

AutoCAD SHX Text

HWR

AutoCAD SHX Text

HWR

AutoCAD SHX Text

RL

AutoCAD SHX Text

RL

AutoCAD SHX Text

RL

AutoCAD SHX Text

RS

AutoCAD SHX Text

RS

AutoCAD SHX Text

RS

AutoCAD SHX Text

RHG

AutoCAD SHX Text

RHG

AutoCAD SHX Text

RHS

AutoCAD SHX Text D

AutoCAD SHX Text D

AutoCAD SHX Text D

AutoCAD SHX Text

%%UGENERAL SYMBOLS

AutoCAD SHX Text

LIMIT OF DEMOLITION

AutoCAD SHX Text

REDUCER OR INCREASER

AutoCAD SHX Text

DIRECTION OF FLOW

AutoCAD SHX Text

SIDE CONNECTION

AutoCAD SHX Text

ECCENTRIC REDUCER

AutoCAD SHX Text BOTTOM CONNECTION, 45%%d OR 90%%d

AutoCAD SHX Text TOP CONNECTION, 45%%d OR 90%%d

AutoCAD SHX Text

UNION

AutoCAD SHX Text

RISE OR DROP IN PIPE

AutoCAD SHX Text

CAPPED OUTLET

AutoCAD SHX Text

AND EXISTING WORK

AutoCAD SHX Text

POINT OF CONNECTION BETWEEN NEW

AutoCAD SHX Text

FLOAT & THERMOSTATIC TRAP SET INCLUDING

AutoCAD SHX Text

PIPING ACCESSORIES

AutoCAD SHX Text

PIPING ACCESSORIES

AutoCAD SHX Text

INVERTED BUCKET TRAP SET INCLUDING

AutoCAD SHX Text

PIPE UP

AutoCAD SHX Text

PIPE DOWN

AutoCAD SHX Text

%%UVALVE SYMBOLS

AutoCAD SHX Text

BALL VALVE

AutoCAD SHX Text

CHECK VALVE

AutoCAD SHX Text

MODULATING CONTROL VALVE

AutoCAD SHX Text

THREE-WAY MODULATING CONTROL VALVE

AutoCAD SHX Text

GATE VALVE

AutoCAD SHX Text

WYE STRAINER (WITH BALL VALVE & HOSE CONNECTION)

AutoCAD SHX Text

FLEXIBLE CONNECTION

AutoCAD SHX Text

WATER BALANCE DEVICE

AutoCAD SHX Text

PRESSURE REDUCING VALVE (PRV)

AutoCAD SHX Text

%%UCONTROLS SYMBOLS

AutoCAD SHX Text T

AutoCAD SHX Text

ROOM THERMOSTAT

AutoCAD SHX Text

TT

AutoCAD SHX Text

TEMPERATURE TRANSMITTER

AutoCAD SHX Text

PT

AutoCAD SHX Text

PRESSURE TRANSMITTER

AutoCAD SHX Text

HVAC

AutoCAD SHX Text

HVAC CONTROL PANEL

AutoCAD SHX Text

EXISTING WORK TO REMAIN (LIGHT DASH)

AutoCAD SHX Text

EXISTING WORK TO BE REMOVED (HEAVY DASH)

AutoCAD SHX Text

NEW WORK (HEAVY SOLID)

AutoCAD SHX Text

PRESSURE REGULATING VALVE

AutoCAD SHX Text

AutoCAD SHX Text

PIPING CONNECTIONS

AutoCAD SHX Text

NTS

AutoCAD SHX Text

FLOOR MOUNTED EXPANSION TANK -

AutoCAD SHX Text

NOTE:

AutoCAD SHX Text

1. EXPANSION TANK EXPANSION TANK MIN TANK VOLUME OF 56 GAL [210 L] AND MIN BLADDER VOLUME OF 23 GAL [87 L]. 2. FOR HOT WATER FOR HOT WATER SYSTEMS 2" [50mm] AND SMALLER USE IN-LINE AIR PURGER IN LIEU OF AIR SEPARATOR. 3. SET PRESSURE SET PRESSURE REDUCING VALVE SO PRESSURE AT HIGHEST POINT IN SYSTEM HAS A MINIMUM OF 4 PSIG [28kPa].

AutoCAD SHX Text D

AutoCAD SHX Text FLOOR MOUNTING BASE RING WITH DRAIN ACCESS OPENING SHOWN. ANGLE IRON LEGS MAY BE USED AS AN OPTION.

AutoCAD SHX Text 6" [150mm] HOUSEKEEPING PAD

AutoCAD SHX Text

COLD WATER FILL LINE. SEE EXPANSION TANK SCHEDULE FOR SIZE

AutoCAD SHX Text

DRAIN

AutoCAD SHX Text

FROM SYSTEM

AutoCAD SHX Text

RUN DRAIN LINE TO NEAREST FD UNLESS INDICATED OTHERWISE

AutoCAD SHX Text

DRAIN

AutoCAD SHX Text

TO PUMP SUCTION

AutoCAD SHX Text

AIR SEPARATOR SEE NOTE 2

AutoCAD SHX Text

HANGER RODS (TYP)

AutoCAD SHX Text

CONNECTOR PIPE.

AutoCAD SHX Text

BLADDER EXPANSION TANK

AutoCAD SHX Text

REDUCED PRESSURE BACKFLOW PREVENTER

AutoCAD SHX Text

NC

AutoCAD SHX Text

BUTTERFLY OR BALL ISOLATION VALVE

AutoCAD SHX Text D

AutoCAD SHX Text

RUN DRAIN LINE TO NEAREST FD

AutoCAD SHX Text

AIR CHARGING SHRAEDER VALVE

AutoCAD SHX Text

MV

AutoCAD SHX Text

AUTO. AIR VENT TO DRAIN

AutoCAD SHX Text

PI

AutoCAD SHX Text

HEAT EXCHANGER - STEAM TO HOT WATER

AutoCAD SHX Text

AutoCAD SHX Text

NTS

AutoCAD SHX Text

NOTE:

AutoCAD SHX Text

1. PROVIDE SADDLE SUPPORTS AND LEGS OR HANGERS FOR HEAT EXCHANGER. MOUNTING HEIGHT PROVIDE SADDLE SUPPORTS AND LEGS OR HANGERS FOR HEAT EXCHANGER. MOUNTING HEIGHT SHALL BE ADJUSTED TO FACILITATE GRAVITY RETURN OF STEAM CONDENSATE. UTILIZE EXISTING FRAME FOR SUPPORT. 2. PIPING AND APPURTENANCES ARE SHOWN FOR GENERAL SCHEMATIC ARRANGEMENT.PIPING AND APPURTENANCES ARE SHOWN FOR GENERAL SCHEMATIC ARRANGEMENT.

AutoCAD SHX Text

TEST PLUG (TYP.)

AutoCAD SHX Text

THERMOMETER (TYP.)

AutoCAD SHX Text

LPS STEAM SUPPLY

AutoCAD SHX Text

HEAT EXCHANGER (TYP.)

AutoCAD SHX Text D

AutoCAD SHX Text

12"MIN.

AutoCAD SHX Text [305mm]

AutoCAD SHX Text

(TYP.)

AutoCAD SHX Text

6"MIN.

AutoCAD SHX Text [152mm]

AutoCAD SHX Text

(TYP.)

AutoCAD SHX Text

RUN DRAIN LINE FROM RELIEF VALVE TO NEAREST FLOOR DRAIN. (TYP.)

AutoCAD SHX Text

HWR FROM PUMP

AutoCAD SHX Text

HWS

AutoCAD SHX Text

LPR BACK TO PLANT

AutoCAD SHX Text 1/2" [15mm] CHECK VALVE VACUUM BREAKER (TYP.)

AutoCAD SHX Text

SCALE POCKET

AutoCAD SHX Text

(TYP.)

AutoCAD SHX Text

DDC TEMPERATURE SENSORS

AutoCAD SHX Text

25 PSIG RELIEF VALVE SETTING

AutoCAD SHX Text

TT

AutoCAD SHX Text

AutoCAD SHX Text

TT

AutoCAD SHX Text

AutoCAD SHX Text

PI

AutoCAD SHX Text

CONTROL VALVE

AutoCAD SHX Text

AutoCAD SHX Text

NTS

AutoCAD SHX Text

STEAM PRESSURE REDUCING STATION

AutoCAD SHX Text V

AutoCAD SHX Text

NOTE: 1. 2. 3. 4. 5. 6. 7.

AutoCAD SHX Text

VENT TO ATMOSPHERE

AutoCAD SHX Text BUILDING STEAM ENTRANCE AT 100 PSIG. STEAM TO EQUIPMENT AT 12 PSIG. SEE PLANS FOR PIPE SIZES D1 AND D2. MINIMUM REDUCING VALVE CAPACITY OF 235 LBS/HR WITH MAX FLOW WIDE OPEN OF 420 LBS/HR. INSTALL VALVE AS RECOMMENDED BY MANUFACTURER. MAKE BYPASS VALVE DISCHARGE PIPE THE SAME SIZE AS D2. PROVIDE NECESSARY UNIONS FOR THE REMOVAL OF VALVE WITH SCREWED CONNECTIONS. SAFETY VALVE SHALL BE SIZED SO AS TO RELIEVE AT PRESSURE OF 5 TO 10 PSIG ABOVE DELIVERED PRESSURE OF PRV AND SHALL HAVE A CAPACITY EQUAL TO MAXIMUM CAPACITY OF PRV. VENT PIPE SIZE SHALL BE NO LESS THAN ONE PIPE SIZE LARGER THAN SAFETY VALVE DISCHARGE.

AutoCAD SHX Text

SIPHON (TYP.)

AutoCAD SHX Text

PILOT CONTROL LINE

AutoCAD SHX Text

REDUCER (TYP.) IF REQUIRED.

AutoCAD SHX Text

NOTE 1

AutoCAD SHX Text D1

AutoCAD SHX Text N.C.

AutoCAD SHX Text D2

AutoCAD SHX Text

4 D2 MIN.

AutoCAD SHX Text

20 D2 MIN.

AutoCAD SHX Text

10 D1 MIN.

AutoCAD SHX Text

NOTE 2

AutoCAD SHX Text

NOTE 7

AutoCAD SHX Text

INVERTED BUCKET TRAP ASSEMBLY TYP.

AutoCAD SHX Text

PSV

AutoCAD SHX Text

THERMOSTATIC AIR VENT

AutoCAD SHX Text

PIPING CONNECTIONS

AutoCAD SHX Text

AutoCAD SHX Text

NTS

AutoCAD SHX Text

COIL

AutoCAD SHX Text

TEST PLUG (TYP.)

AutoCAD SHX Text

REDUCER, IF REQUIRED

AutoCAD SHX Text

WATER RETURN

AutoCAD SHX Text

MANUAL AIR VENT

AutoCAD SHX Text

UNION CONNECTIONS (TYP.)

AutoCAD SHX Text

WATER SUPPLY

AutoCAD SHX Text

TERMINAL UNIT WATER COILS -

AutoCAD SHX Text

SHUT OFF VALVE

AutoCAD SHX Text

DRAIN WITH HOSE CONNECTION

AutoCAD SHX Text

MV

AutoCAD SHX Text

MODULATION CONTROL VALVE

AutoCAD SHX Text

AutoCAD SHX Text

NTS

AutoCAD SHX Text PIPE HANGERS - PROVIDE DOUBLE DEFLECTION NEOPRENE (TYPE HN) FOR FIRST TWO ON EACH SIDE OF PUMP (SEE NOTE NO. 1)

AutoCAD SHX Text

PRESSURE GAGE

AutoCAD SHX Text 1/2" [15mm]

AutoCAD SHX Text

STRAINER

AutoCAD SHX Text

FLEXIBLE CONNECTION

AutoCAD SHX Text

BALL VALVE TYP.

AutoCAD SHX Text NOTES: 1. SUPPORT PUMP FROM PIPING ONLY. DO NOT SUPPORT PUMP FROM SUPPORT PUMP FROM PIPING ONLY. DO NOT SUPPORT PUMP FROM MOTOR.

AutoCAD SHX Text

IN-LINE PUMPS - CONNECTIONS

AutoCAD SHX Text

BALANCING DEVICE

AutoCAD SHX Text

ASSEMBLY

AutoCAD SHX Text

AutoCAD SHX Text

NTS

AutoCAD SHX Text

INVERTED BUCKET STEAM TRAP

AutoCAD SHX Text

NOTE: 1. 2.

AutoCAD SHX Text ALL DRIP POINTS ON STEAM MAINS SHALL BE PROVIDED WITH A 12" MINIMUM HIGH DRIP LEG FROM BOTTOM OF STEAM MAIN TO TRAP INLET. DRIP LEG SHALL HAVE 6" SCALE POCKET BELOW TRAP INLET. PROVIDE BYPASS PIPING.

AutoCAD SHX Text

SEE DRAWINGS FOR PIPE SIZES

AutoCAD SHX Text

TO RETURN MAIN

AutoCAD SHX Text

SCHEDULE 80 STEEL PIPE

AutoCAD SHX Text

PIPE SIZE SHALL BE SAME SIZE AS TRAP

AutoCAD SHX Text

INVERTED BUCKET TRAP. SEE PLANS AND DETAILS

AutoCAD SHX Text

DIELECTRIC FITTING WHERE RETURN IS COPPER PIPE

AutoCAD SHX Text

FLOW

AutoCAD SHX Text

SCHEDULE 80 STEEL PIPE

AutoCAD SHX Text BYPASS-INSTALL IN HORIZONTAL PLANE LEVEL WITH TRAP OR IN VERTICAL PLANE & BELOW TRAP

AutoCAD SHX Text

12" MIN.

AutoCAD SHX Text

6" MIN.

AutoCAD SHX Text

DRIP LEG. MAKE THE SAME SIZE AS THE SUPPLY MAIN. SEE NOTE 1

AutoCAD SHX Text [300mm]

AutoCAD SHX Text [150mm]

AutoCAD SHX Text

1" GATE VALVE

AutoCAD SHX Text

ASSEMBLY

AutoCAD SHX Text

AutoCAD SHX Text

NTS

AutoCAD SHX Text

FLOAT AND THERMOSTATIC STEAM TRAP

AutoCAD SHX Text

NOTE: 1.

AutoCAD SHX Text ALL DRIP POINTS ON STEAM MAINS SHALL BE PROVIDED WITH A 12" MINIMUM HIGH DRIP LEG FROM BOTTOM OF STEAM MAIN TO TRAP INLET. DRIP LEG SHALL HAVE 6" SCALE POCKET BELOW TRAP INLET.

AutoCAD SHX Text

TO RETURN MAIN

AutoCAD SHX Text

PIPE SIZE SHALL BE SAME SIZE AS TRAP

AutoCAD SHX Text

1" FLOAT AND THERMOSTATIC TRAP, 470 LBS/HR MIN CAPACITY

AutoCAD SHX Text

DIELECTRIC FITTING WHERE RETURN IS COPPER PIPE

AutoCAD SHX Text

FLOW

AutoCAD SHX Text

SCHEDULE 80 STEEL PIPE

AutoCAD SHX Text BYPASS-INSTALL IN HORIZONTAL PLANE LEVEL WITH TRAP OR IN VERTICAL PLANE & BELOW TRAP PROVIDE BYPASS PIPING FOR ALL TRAPS 1" AND LARGER.

AutoCAD SHX Text

12" MIN.

AutoCAD SHX Text

6" MIN.

AutoCAD SHX Text DRIP LEG OR EQUIPMENT CONNECTION. MAKE THE SAME SIZE AS THE SUPPLY MAIN OR EQUIPMENT CONNECTION. SEE NOTE 1

AutoCAD SHX Text [300mm]

AutoCAD SHX Text [150mm]

AutoCAD SHX Text

SCHEDULE 80 STEEL PIPE

AutoCAD SHX Text

SEE DRAWINGS FOR PIPE SIZES

AutoCAD SHX Text

1" GATE VALVE

AutoCAD SHX Text

AutoCAD SHX Text

NTS

AutoCAD SHX Text

END OF STEAM LINE DRIP TRAP

AutoCAD SHX Text

CONDENSATE

AutoCAD SHX Text

TO DRAIN

AutoCAD SHX Text

MV

AutoCAD SHX Text

MANUAL AIR VENT

AutoCAD SHX Text

TO BUILDING LOAD

AutoCAD SHX Text

3/4" INVERTED BUCKET TRAP ASSEMBLY, MIN 1000 LBS/HR CAPACITY

AutoCAD SHX Text

WELDED TEE

AutoCAD SHX Text

STEAM PIPE

AutoCAD SHX Text

12"[300 MM]

AutoCAD SHX Text

6"[150 MM]

AutoCAD SHX Text

SCHEDULE 80 STEEL PIPE

AutoCAD SHX Text

1" GATE VALVE

AutoCAD SHX Text

WATER TREATMENT - CLOSED SYSTEMS

AutoCAD SHX Text

AutoCAD SHX Text

NTS

AutoCAD SHX Text NOTE: TOP OF CHEMICAL POT FEEDER TANK SHALL NOT BE MORE THAN 4'-0" [1200mm] ABOVE FINISHED FLOOR.

AutoCAD SHX Text 1" [25mm]

AutoCAD SHX Text

CHEMICAL POT FEEDER- MINIMUM CAPACITY 5 GALLONS [19L]

AutoCAD SHX Text 1" [25mm]

AutoCAD SHX Text

FUNNEL

AutoCAD SHX Text 3/4" [20mm]

AutoCAD SHX Text

TO DRAIN

AutoCAD SHX Text

FROM PUMP DISCHARGE

AutoCAD SHX Text

TO PUMP SUCTION

AutoCAD SHX Text

AUTOMATIC FLOW CONTROL AND BALANCE DEVICE

AutoCAD SHX Text

AutoCAD SHX Text

NTS

AutoCAD SHX Text

(WITH EQUIPMENT MOUNTED IN DUCT)

AutoCAD SHX Text

DUCTWORK TRANSITIONS

AutoCAD SHX Text

NOTE: UNLESS OTHERWISE INDICATED ON PLANS, MAXIMUM ANGLES SHOWN SHALL APPLY.

AutoCAD SHX Text 30°

AutoCAD SHX Text

MAX.

AutoCAD SHX Text 30°

AutoCAD SHX Text

MAX.

AutoCAD SHX Text

EQUIPMENT

AutoCAD SHX Text

AIR FLOW

AutoCAD SHX Text

AIR FLOW

AutoCAD SHX Text

TYPICAL DUCTWORK TRANSITION PLAN OR SIDE VIEW

AutoCAD SHX Text

TYPICAL DUCTWORK TRANSITION WITH EQUIPMENT MOUNTED IN DUCT PLAN OR SIDE VIEW

AutoCAD SHX Text 15°

AutoCAD SHX Text

MAX.

AutoCAD SHX Text 15°

AutoCAD SHX Text

MAX.

AutoCAD SHX Text 15°

AutoCAD SHX Text 15°

AutoCAD SHX Text

MAX.

AutoCAD SHX Text

MAX.

AutoCAD SHX Text

AutoCAD SHX Text

NTS

AutoCAD SHX Text

SUPPLY DUCTWORK TAKE-OFFS

AutoCAD SHX Text

DESIGNER'S NOTES:

AutoCAD SHX Text

1. THE SUPPLY REGISTER TAKE-OFF MAY BE USED FOR UP UP TO 25% OF THE MAIN THE SUPPLY REGISTER TAKE-OFF MAY BE USED FOR UP UP TO 25% OF THE MAIN DUCT CFM. THE BRANCH DUCT TAKE-OFF MAY BE USED FOR UP TO 15% OF THE MAIN DUCT CFM ANYTIME AND UP TO 40% WHEN THE MAIN DUCT VELOCITY IS 1000 FPM [5.1 M/S] OR LESS. THE AIR SPLIT DUCT TAKE-OFF SHALL BE USED IN ALL OTHER CASES AND MAY BE USED AT ANYTIME. 2. SHOW ALL VOLUME DAMPERS ON FLOOR PLANS.SHOW ALL VOLUME DAMPERS ON FLOOR PLANS.

AutoCAD SHX Text

AIR SPLIT DUCT TAKE-OFF PLAN VIEW

AutoCAD SHX Text

BRANCH DUCT TAKE-OFF PLAN VIEW

AutoCAD SHX Text

SUPPLY REGISTER TAKE-OFF PLAN VIEW

AutoCAD SHX Text

AIR FLOW

AutoCAD SHX Text

AIR FLOW

AutoCAD SHX Text

AIR FLOW

AutoCAD SHX Text

SUPPLY REGISTER OR BRANCH DUCT

AutoCAD SHX Text

TURNING VANES

AutoCAD SHX Text

MAIN SUPPLY DUCT

AutoCAD SHX Text

SEE FLOOR PLAN FOR SPLIT DIMENSION

AutoCAD SHX Text

PROVIDE VOLUME DAMPER

AutoCAD SHX Text

PROVIDE VOLUME DAMPER

AutoCAD SHX Text

ADJUSTABLE METAL ROD OR LINKAGE

AutoCAD SHX Text

TOP REGISTER

AutoCAD SHX Text

MAIN SUPPLY DUCT

AutoCAD SHX Text VOLUME EXTRACTOR; ADJUSTABLE FROM FULLY CLOSED POSITION TO CFM NOTED ON FLOOR PLANS

AutoCAD SHX Text

AIR FLOW

AutoCAD SHX Text

AIR FLOW

AutoCAD SHX Text 1/4 W OR 4" [100mm] MIN.

AutoCAD SHX Text

AIR FLOW

AutoCAD SHX Text

MAIN SUPPLY DUCT

AutoCAD SHX Text W

AutoCAD SHX Text

AIR FLOW

AutoCAD SHX Text

WATER COILS - PIPING CONNECTIONS

AutoCAD SHX Text

AutoCAD SHX Text

NTS

AutoCAD SHX Text

%%USINGLE COIL

AutoCAD SHX Text

WATER COIL

AutoCAD SHX Text

AIR VENT WHEN COIL IS NOT SELF-VENTING

AutoCAD SHX Text

DRAIN WHEN COIL IS NOT SELF-DRAINING

AutoCAD SHX Text

TEST PLUG (TYP.)

AutoCAD SHX Text

PIPE HANGER SHALL SUPPORT PIPING INDEPENDENT OF COIL

AutoCAD SHX Text

REDUCER, IF REQUIRED

AutoCAD SHX Text

DRAIN

AutoCAD SHX Text

NOTE: 1. 2. 3.

AutoCAD SHX Text WHEN COIL IS INCLUDED IN CASING MOUNTED ON VIBRATION ISOLATORS THE FIRST 2 HANGERS FOR EACH PIPE SHALL BE SPRING & NEOPRENE TYPE. TYPE "H" FOR 4" [100mm] PIPE & SMALLER. TYPE "H-P" FOR 5" [125mm] PIPE & LARGER.PIPING SHALL BE INSTALLED IN SUCH MANNER THAT IT WILL NOT BLOCK THE SWING OR USE OF ACCESS DOORS OR PANELS; NEITHER SHALL IT BLOCK THE SERVICING OF FILTERS, VALES, OR EQUIPMENT. THE FLOW ELEMENT MAY BE INSTALLED IN THE SUPPLY PIPING IF THE REQUIRED MINIMUM UPSTREAM AND DOWNSTREAM DIMENSIONS CANNOT BE OBTAINED IN THE RETURN PIPING.

AutoCAD SHX Text

FE

AutoCAD SHX Text

MV

AutoCAD SHX Text

MV

AutoCAD SHX Text

MV

AutoCAD SHX Text

TI

AutoCAD SHX Text

TEMPERATURE INDICATION TO ECC

AutoCAD SHX Text

SAFETY RELIEF VALVE (PSV)

AutoCAD SHX Text

BALANCING DEVICE (TYP)

AutoCAD SHX Text

ITEM

AutoCAD SHX Text

NO.

AutoCAD SHX Text

DATE

AutoCAD SHX Text

ISSUANCES

AutoCAD SHX Text

PROJECT NO.

AutoCAD SHX Text

SHEET NO.

AutoCAD SHX Text

DRAWING TITLE

AutoCAD SHX Text

DRAWN BY

AutoCAD SHX Text

CHECKED BY

AutoCAD SHX Text

COMPUTER FILE

AutoCAD SHX Text Veterans Affairs

AutoCAD SHX Text Department of

AutoCAD SHX Text Office of Facilities

AutoCAD SHX Text K

AutoCAD SHX Text H

AutoCAD SHX Text L

AutoCAD SHX Text

ENGINEERS, PSC

AutoCAD SHX Text

KOHRS LONNEMANN HEIL

AutoCAD SHX Text 10276.00

AutoCAD SHX Text

NOT TO SCALE

AutoCAD SHX Text

H.V.A.C. - DETAILS

AutoCAD SHX Text

HV2.00

AutoCAD SHX Text

AutoCAD SHX Text

DLE

AutoCAD SHX Text

RAL

AutoCAD SHX Text

H.V.A.C. DETAILS

AutoCAD SHX Text

HV2.00

AutoCAD SHX Text

AND LEGEND

Sheets and Views
KLH-8825-36X24

File details come from the government source that posted it. Updated .