DIMOND LIBRARY ELEVATOR SPECIFICATIONS 10-02-2026.pdf
PDF 156 KB Posted
- Attached to
- UNH Dimond Library Elevator Upgrades
- Solicitation number
- 2120271007
- Issued by
- New Hampshire
About this file
This document is a hydraulic elevator specifications section for the University of New Hampshire (UNH) Dimond Library renovation project located at 18 Library Way. The project involves the complete renovation of one oil-hydraulic passenger elevator, including the replacement of the car enclosure, doors, door operator, car ceiling, handrails, floor designations, car sill, and associated machinery components, while retaining the existing elevator cylinder, car frame, car platform, guide rails, buffers, hoistway entrances, and landing doors. The elevator specifications call for a 3,500-pound capacity passenger elevator with a minimum speed of 150 feet per minute, five stops (floors 1-5), 42" x 84" single-speed center-opening doors, 40 HP submersible motor with 208-volt, 3-phase power supply, and comprehensive safety features including two-way leveling, infrared door protection, firefighter's service (Phase I and II), and independent service operation. Acceptable manufacturers include Canton Elevator, CEMCOLIFT Inc., ESCO Elevator Products, Elevator Equipment Company, Claddagh Controls, G.A.L. Manufacturing Corporation, and PTL Equipment Company, while acceptable installing firms are Stanley, Otis, Kone, and Pine State, all of which must demonstrate at least three similar installations within fifty miles completed within two years and five years of satisfactory maintenance service prior to bidding.
The contractor is required to provide a twelve-month warranty covering defective materials and workmanship from the date of final acceptance or state inspector certification, along with one year of maintenance service consisting of monthly inspections, lubrication, adjustment, and emergency call-back service responding within one hour during regular working hours and two hours outside regular hours. The specifications emphasize non-proprietary equipment that can be serviced by any recognized service company with readily accessible aftermarket parts, and require compliance with ASME/ANSI A17.1 safety standards, the National Electrical Code (ANSI/NFPA 70), and New Hampshire's Architectural Barrier-Free Design Code. The microprocessor-based controller must be field programmable with a 32-character alphanumeric display, real-time clock with battery backup, serial communication port, and comprehensive diagnostic capabilities. All work must be completed in accordance with approved shop drawings and applicable codes, with the contractor responsible for examining all site conditions and assuming all costs for incidental work necessary for proper elevator operation.
View the file
Other files
Show all 14
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
UNH DIMOND LIBRARY 18 LIBRARY WAY
HYDRAULIC ELEVATOR
14200- 1
SECTION 14200 – HYDRAULIC ELEVATOR
PART 1 – GENERAL
1.01 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this Section.
1.02 WORK INCLUDED
A. The work in this Section consists of all labor, materials, equipment, and services necessary to complete the work of this Section, and without limiting the generality thereof includes:
1. The renovation of one (1) oil-hydraulic elevator, including transportation, insurance, temporary protection, supervision and incidental items essential for proper installation and operation even though not specifically mentioned or indicated in the Specifications, but which are usually provided or are essential for proper operation.
2. Furnish and maintain hoistway equipment, operating personnel and rigging to perform the work of this Section.
3. In all cases where a device or part of the equipment is referred to herein in the singular, it is intended that such reference shall apply to as many devices as required to complete the installation.
1.03 RELATED WORK SPECIFIED ELSEWHERE
A. The following items of work are not included in this Section and are specified under the designed
Sections.
1. WORK BY THE ELEVATOR CONTRACTOR
a. UNH to provide a dry, safe location for storage of the elevator materials.
b. Provide two (2) hour fire-rated hoistway walls, machine room walls and ceilings, with required legal ventilation.
c. Provide barricades and protection of hoistways during the time the elevator equipment is being installed.
d. Cut walls, floors, and partitions, together with any repairs made necessary thereby.
Provide recesses in walls and floors to receive doors, sills, and signal equipment such as indicators, push buttons, hall lanterns, etc.
e. Protect all finished installed work until Substantial Completion of Project, including installation of protective coverings at hoistway entrances.
f. Provide machine room with ventilation, main line disconnect and 120 disconnect for car lights.
g. If required, grout the underside of thresholds at all elevator landing entrances.
2. MISCELLANEOUS METAL
a. Steel ladder for the elevator pit.
3. CEMENTITIOUS WATERPROOFING SECTION
NA.
4. MECHANICAL SECTION
a. Ductwork and related work.
14200- 2
b. Venting of hoistway and machine room. Remove one concrete block. Install metal on each side of opening.
5. ELECTRICAL SECTION
a. Provide electrical power feeder to elevator controller, with main line fuses disconnect switch.
b. Provide separate fused electrical service for car lights, and in the machine room, as shown on the elevator Shop Drawing.
c. Provide fused electrical services, convenience outlets, and switched light fixtures in elevator pit and machine room.
d. Provide new GFCI outlet in pit for feed to new scavenger pump.
e. Smoke detectors in elevator lobbies, pit and machine room to initiate emergency recall operation.
f. Provide electrical service for the installation, testing and adjusting of the elevator equipment.
g. Pit and machine room lighting to be LED type; fixtures shall be equipped with protective guards.
1.04 SUBMITTALS
A. General: Submit samples for all materials exposed in the finished work and as requested by the Owner. Include detailed information regarding rough-in and other preparatory work by other trades related to the elevator improvements.
B. Product Data: Include capacities, sizes, performances, operations, safety features, finishes and similar information. Provide manufacturer’s written specifications, installation and maintenance requirements for each product or material to be utilized in the elevator installations.
C. Samples: Submit sample of finished materials and colors to Owner for approval, consisting of various exposed equipment and accessories, such as indicators, push buttons, etc., for selection and/or approval, as may be required.
D. Do not order materials or begin fabrications or installation of materials until approval has been obtained.
E. Maintenance Manuals: Include operation and maintenance instructions, part listing with sources indicated, recommended parts inventory listing, emergency instructions, and similar information.
Include diagnostic and repair information available to manufacturer's and installer's maintenance personnel.
F. Inspection and Acceptance Certificates and Operating Permits: As required by authorities having jurisdiction for normal, unrestricted elevator use.
1.05 REQUIREMENTS OF REGULATORY AGENCIES
A. Comply with all State and Local Authorities having jurisdiction and obtain all necessary permits, pay all fees, obtain all required inspections, and carry out all required tests which are required by such Authorities.
14200- 3
1.06 STANDARDS, CODES AND REGULATIONS
A. Furnish all elevator equipment in accordance with most-stringent applicable provisions of the following Codes and/or Authorities, including revisions and changes in effect on date of these specifications:
1. American National Standards Institute “Standard Safety Code for Elevators, Dumbwaiters, Escalators and Moving Walks”, ASME/ANSI A17.1 (the ANSI Code).
2. Inspector’s Manual, ASME/ANSI A17.2.
3. National Electrical Code, No. ANSI/NFPA 70.
4. Requirements of any other Codes, Ordinances and Laws applicable with the governing jurisdiction.
5. Architectural Barrier-Free Design Code for New Hampshire.
1.07 COORDINATION
A. Coordinate installation of sleeves, block outs, and items that are embedded in concrete or masonry for elevator equipment. Furnish templates and installation instructions and deliver to Project site in time for installation.
B. Coordinate locations and dimensions of other work relating to hydraulic elevators including pit ladders and sumps in pit; and electrical service, electrical outlets, lights, and switches in pit and machine room.
1.08 WARRANTY
A. Provide written warranty agreeing to replace, repair, or restore defective materials and workmanship of elevator work for a period of 12 months from date of final acceptance by Owner or certification of the elevators by State Inspectors, whichever is later. “Defective” is hereby defined to include, but not limited to operation or control system failures, performances below required minimum, excessive wear, unusual deterioration or aging of materials or finishes, unsafe conditions, the need for excessive maintenance, abnormal noise or vibrations, and similar unusual, unexpected and unsatisfactory conditions.
B. This warranty is not intended to supplant maintenance service and shall not be construed to require free service for periodic examination, lubrication, or adjustment due to normal use, beyond that included in the Specification; nor correction without charge, or breakage, maladjustment, or other trouble arising from abuse, misuses, or any other causes beyond the control of the Elevator Manufacturer and Elevator Installing Firm.
1.09 MAINTENANCE
A. The Elevator Installing Firm shall furnish maintenance and call back service for a period of one (1) year following the date of final acceptance by the Owner or certification for operation by State authorities, whichever is later. Maintenance services shall consist of at least monthly inspections, lubrication, and adjustment of equipment. Call back service will provide all intermediate service calls requested by the Owner. This shall consist of responding within one hour of notification provided such notification is during the normal working hours of the elevator trade and within two hours outside of regular working hours of the trade.
B. The Elevator Manufacturer and/or Elevator Installing Firm shall furnish all labor, material, and equipment required for replacing all parts which become defective within one year after date of
14200- 4
Substantial Completion of Project at no cost to the Owner, except defects due to misuse, accidents, or negligence on the part of the Owner will not be considered to be covered under the maintenance guarantee.
C. Include, but do not limit to, replacement of all seals, packing and reservoir oil as often as necessary during the maintenance period to maintain adequate factor of safety and performance. Only genuine standard parts produced by the manufacturer of the equipment concerned shall be used for replacement.
D. All work under the maintenance provision shall be performed by trained, licensed, competent personnel under the supervision and in the direct employ of the Elevator Manufacturer and/or Elevator Installing Firm.
E. The maintenance service shall be performed solely by the Elevator Installing Firm and shall not be assigned or transferred to any agent or subcontractor.
1.10 ADDITIONAL REQUIREMENTS
A. It is the responsibility of the Elevator Installing Firm to examine all conditions on the in the Specifications and the governing laws and building code, and to assume all costs in connection with this Contract, including cost of any incidental work and equipment which may not be called for on the Drawings and Specifications but which are necessary for construction and proper operation of elevators or required by the governing laws and building codes.
1.11 PROPRIETARY EQUIPMENT
A. The intent of these specifications that all elevator equipment installed, including but not limited to the elevator controller, be non-proprietary in nature. Non-Proprietary shall be defined as that which can be easily serviced by any and all recognized service companies and for which all repair and replacement parts are readily accessible on the aftermarket within one year of the initial installation.
PART 2 – PRODUCTS
2.01 MANUFACTURER
A. The elevator equipment shall be manufactured by Canton Elevator CEMCOLIFT, INC., Inc., ESCO Elevator Products, Elevator Equipment Company, Inc., Claddagh Controls, G.A.L. Manufacturing Corporation, PTL Equipment Co., Inc. or equal as approved by the Owner.
B. Elevator Installing Firms acceptable to the Owner: Stanley, Otis, Kone and Pine State.
1. The Elevator Installing Firm shall have been regularly engaged in the installation/modernization of elevators of the type specified herein and shall be able to demonstrate at least three installations/modernizations of the type specified made by him within fifty (50) miles of the site, which have provided satisfactory operation for a period of at least two years prior to the date of receipt of general bids for this project.
2. Also, the Elevator Installing Firm shall be able to demonstrate that they have provided satisfactory maintenance service for elevators of the type specified, that they have maintained a complete elevator maintenance organization comprised of regularly employed, competent, trained elevator mechanics, and that they have maintained an adequate stock of parts for
14200- 5 replacement and emergency purposes, all within 50 miles of the site for a period of at least five years prior to the date of receipt of general bids.
2.02 DESCRIPTION OF EQUIPMENT
A. Passenger Elevator --Dimond Library NHE 3905
1. Type: Passenger, holed hydraulic.
2. Capacity: 3500 pounds.
3. Speed: 150 feet per minute, minimum.
4. Entrances: Retain landing doors; retain frames.
5. Hoistway Access: Drop key, all levels.
6. Car Direction Lanterns with Audible Signals: surface mounted pushbutton hall stations with
#4 brushed stainless steel trim.
7. Position Indicators: Car and Corridor Push Buttons.
8. Registration Lights: Car and Corridor Pushbuttons.
9. Stops: 5 stops, 1,2,3,4, 5
10. Openings and Type: 42" x 84"; single-speed, center opening doors
11. Power Supply: 208 volt, 3 Phase.
12. Motor Horsepower: 40 HP Submersible Motor
13. Emergency Operation: Fireman’s Service – Phase I and II.
14. Car Ceiling: Replace
15. Car Enclosure: Replace – New Snap Cab
16. Handrails: Replace
17. Floor Designations: Replace.
18. Car Sill: Replace
19. Entrance Jambs and Headers: Retain:
a. Disabilities Act (ADA) of 1990, effective 1/26/92
b. Car Door Full Length Detection Device.
c. New Two-way audio plus 1 way video Communication, one touch auto dial, built-in by
Rath.
20. Door Operator: Replace.
21. Replace existing car hanger track, hanger rollers, Clutch, gibs and interlocks.
2.03 ELEVATOR MACHINERY
A. Type of Equipment:
1. The elevator is oil hydraulic type with direct acting plunger, pumping unit, storage tank and control valves. The power unit and associated control equipment are located in machine room.
2. The pump shall deliver the oil directly to the cylinder at the necessary pressure and in sufficient quantity to lift the fully loaded elevator at the specified speed. The tank shall act as a storage tank only and the oil shall be pumped into the cylinder on the up trip and shall be returned into the tank on the down trip.
B. Elevator Cylinder and Piston: Retain:
1. Retain existing jack assembly.
Overhead runby shall be checked and findings submitted to the Owner in writing.
C. Power Unit:
14200- 6
1. The new power unit shall be compactly and neatly designed with all components combined in a self-contained unit and with all adjustment features accessible for adjustment. The power unit shall include a constant displacement rotary screw type pump, motor designed for oil hydraulic elevator service, oil reservoir with an oil-level (glass gauge) indicator, control valve, tank strainer in suction line, and a blow-out proof muffler to reduce pulsations that may occur in the system. The power unit shall be tested and adjusted at the factory by operating a test elevator loaded to conform to the elevators specified here-in.
2. Control Valve Assembly: Shall be of compact design, equipped with filters to protect the valves and suitable for operation under the required pressures. It shall contain a metered bypass valve, a check valve, a relief valve, a manual lowering valve, metered lowering and leveling valves and pilot valves. An isolated seal and coupling device, designed to reduce the transmission of vibrations and noise to the elevator car, shall be provided. The speed of the elevator shall not vary more than 10% of the contract speed, in either direction, regardless of the load. Operation of the manual lowering valve shall permit the car to be lowered at slow speed, in the event of a power failure.
3. Storage Tank: The new oil reservoir shall be constructed of welded steel sheets, and shall be provided with a cover, a protected vent opening, a filtering screen mounted over the suction inlet and a drain connection and an initial supply of oil, sufficient for proper operation of the elevators, shall be provided. The tank shall have a capacity equal to the volume of oil required to lift the elevator to the top terminal landing plus a reserve of not less than ten (10) gallons.
a. The tank shall be provided with a sight gauge to meter the hydraulic fluid level. The permissible minimum hydraulic fluid level shall be clearly indicated.
b. Data plates shall be affixed to the tank indicating the characteristics of the hydraulic fluid, the installation date, the name of the contractor, the manufacturer’s name, piston diameter, and manufacturer's designed head pressure.
4. Muffler: A blow-out muffler, designed to minimize the transmission of fluid pulsations, shall be furnished and installed in the pipe-line between the pumping unit and the cylinder heads of each unit.
5. Sound Isolation Couplings: A minimum of two shall be installed in the machine room oil line between the pump and jack.
6. Rubber Isolation: A rubber isolation mat shall be installed underneath the tank reservoirs.
D. Piping:
1. The new oil line shall be furnished and installed between the pumping unit and the cylinder head complete with necessary fittings. Gate valves, one in the machine room and one in the pit, shall be provided in the line to facilitate maintaining and adjusting the elevator.
2. All hydraulic piping related to the elevator machinery shall be installed so that rigid contact between the piping and other building systems is avoided. Piping supports shall include
14200- 7
Neoprene Isolators (1/4 inch static deflection) and Neoprene Filler Sleeves shall be used where piping penetrates walls.
E. Controller:
1. The new controller shall utilize a non-proprietary microprocessor based logic system that can be easily serviced by any and all recognized service companies with parts easily accessible on the aftermarket and shall comply with ANSI/ASME 17.1 safety code for elevators. The system shall provide comprehensive means to access the computer memory for elevator diagnostic purposes, and shall have permanent indicators to indicate important elevator statuses as an integral part of the controller. Systems that require hookup of external devices for troubleshooting shall have the device provided to the Owner as part of the installation.
2. Failure of any single magnetically operated switch, contactor, or relay to release in the intended manner or the occurrence of a single accidental ground or short circuit shall not permit the car to start or run if any hoistway door or gate interlock is unlocked or if any hoistway door or car door or gate contact is not in the made position. Furthermore, while on car top inspection or hoistway access operation, failure of any single magnetically operated switch, contactor or relay to release in the intended manner or the occurrence of a single accidental ground shall not permit the car to move even with the hoistway door locks and the car door contacts in the closed or made position.
3. Dedicated permanent status indicators shall be provided on the controller to indicate the following: When the safety circuit is open, when the door locks are open, when the elevator is operating at high speed, when the elevator is on independent service, when the elevator is on fireman’s service, when the elevator out of service timer has elapsed or when the motor limit timer or valve limit timer has elapsed. In addition, provide means of displaying other special or error conditions that are protected by the microprocessor.
4. All available options or parameters shall be field programmable, without need for knowledge of any programming languages. Programmable options and parameters shall be stored in a nonvolatile memory. As a minimum there shall be a 32 character alphanumeric display to be used for programming and diagnostics. Programmable parameters and options shall include and not be limited to the following:
a. Number of stops/opening served
b. Simplex Selective Collective/Double Hall Button
c. Fire Floors (Main, Alternates)
d. Single Automatic Pushbutton
e. Floor Encoding (Absolute PI)
f. Digital PI’s/single wire PI’s
g. Programmable door times
h. Programmable Motor Limit Timer
i. Nudging
j. External Car Shutdown Input (e.g. Rescuvator)
k. External Low Oil Sensor Input
l. External Viscosity Control Input
m. Parking Floors
5. The elevator shall have its own computer and dispatching algorithm.
6. On power up the controller shall move the car to the closest floor to identify the position of the elevator.
7. The controller shall have a real-time clock/calendar with battery backup.
8. The controller shall have a serial port for communication with any data or computer terminal such as CRT terminal, modem, etc.
9. Overload relays shall be of the manual reset type of suitable size for the motor furnished.
14200- 8
10. A main line switch shall be provided on the controllers to avoid the possibility of pump churning.
F. Reduced Voltage Starting: Solid-state closed transition starter will be required.
G. Stop Switch in Pit: A stop switch shall be provided in the elevator pit and shall comply with the specified code. The pit switch, when in the off position, shall eliminate, along with other operations, car leveling.
H. Car Stall Protective Circuit: In the event the car should stall while ascending as the result of a relay or control failure, valve failure, low oil in the system, etc., a special circuit shall be provided which shall automatically return the car to the bottom landing and perform a normal door operation, after which the elevator shall be completely shut down except for the door operation. Service will be restored by recycling the main line disconnect switch.
I. Motor Limit Timer: A motor limit timer function shall be provided which, in the event of the pump motor being energized longer than a predetermined time, shall cause the car to descent to the lowest landing, open the doors automatically and then reclose them. The car calls shall then be canceled and the car taken out of service automatically. Operation may be restored by cycling of the power disconnect switch.
J. Valve Limit Timer: A valve limit timer shall be provided which shall automatically cut off current to the valve solenoids if they have been energized longer than a predetermined time. The car calls shall then be canceled and the car taken out of service automatically. Operation may be restored by the cycling of the power disconnect switch.
K. Wiring: The Elevator Installing Firm shall furnish and install complete, all necessary insulated wiring to connect all parts of the equipment. All wire and traveling cables shall have a flame retarding and moisture resisting outer covering and shall be run in metal conduit, metallic tubing, wire ducts or raceways. Traveling cables shall be flexible and suitable suspended so that there is no strain on individual conductors. All electrical material and work shall, at minimum, comply with the latest enforcing electrical codes. Shielded telecommunication and 24V low voltage power wiring to be installed within traveling cable of Elevator No. 1. Wiring to be 1 pair of #18 AWG conductors for 24V power, and 24 Ga. Shielded CAT-6 twisted pair cable for data. A pair of #18 AWG to be included between Hand Reader junction box in Elevator #1 cab to control panel for connection to key switch.
L. Guide Rails:
1. Guide rails shall be retained.
2. Guide rails shall be free of any signs of rust or abrasion, and shall be filed to remove all rough edges prior to final inspection. All guide rail joints shall be filed to assure perfectly matching surfaces.
3. Unused sections of the rails shall be painted a flat black...
M. Guide Shoes: New guide shoes shall be mounted on the top and bottom of the car frame and shall be held in contact with the guide rails. Guides shall run on lubricated rails.
N. Buffers: Shall be retained. The buffers and pit channels shall be cleaned and painted with a flat black paint.
14200- 9
2.04 OPERATION AND CONTROL
Simplex Selective Collective Automatic Push Button Operation:
1. If the hoistway door interlock and the car door contact circuits have been activated, the car door contact circuits have been activated, the car shall start automatically upon activation of one or more pushbuttons within the car or in the hallway. The car shall stop at any floor reached for which a car call or a hall call in the direction of travel has been registered. The car shall not respond to hall calls registered in the opposite direction of travel unless it is the last call reached in the direction ahead of the car. The car shall make stops in the natural order in which calls are reached, irrespective of the sequence of which the calls have been registered, if the call is registered sufficiently in advance of the arrival of the car at that particular floor to permit a stop to be made.
2 Firefighters Service: The elevator shall be equipped with Phase I, Emergency Recall Operation and Phase II, Emergency In-Car Operation. The Firefighters Service shall comply with A17.1 and the Local Fire Fighters Code. .
a. The alternate level to be located at floor 2.
b. The designated level shall be floor # 1
3. Independent Service: The elevator shall be provided with a key switch to remove it from “Automatic” operation. The elevator shall operate in response to car calls only “in an independent mode of operation”. The cylinder will be an ASSA cylinder furnished by the Owner.
A. Signals: Replace:
1. Control of the elevator shall be automatic in operation by means of push buttons in the elevator marked for each of the landing levels served and button boxes at each of the landing levels served. Car or hall calls shall be registered by the momentary pressing of landing or car buttons and shall be maintained until the car answers the call. Each landing station shall contain push buttons which shall “light up” when pressed to indicate that a call has been registered to bring the car to that particular landing. A time delay, non-interference feature shall be incorporated in the control mechanism to allow ample time for opening and closing of the car and hoistway doors before it is again placed in motion.
2. The new car operating panel shall contain a keyed stop switch to interrupt the power supply to the valves and pump motor, independently of the regular operating devices. The opening of the stop switch shall not cancel the registered calls or the leveling operation while the elevator is in the landing zone and, after the stop switch is closed the car shall continue to answer its various calls. The car operating panels shall also contain a key operated light and fan switch.
3. Hall or car call registration and lamp acknowledgment shall be by means of a single wire per call besides the power busses. Systems that register the call with one wire and light the call acknowledgment lamp with a separate wire are not acceptable.
4. Elevator Car and Hall Stations:
a. All the signal systems described herein will be manufactured by PTL Equipment Company, Inc.
b. All faceplates shall be flush mounted stainless steel with #4 satin finish and shall be .135 thick.
c. All engraved numbers and letters on the faceplate for floor buttons shall be 5/8” high.
14200- 10
d. All other buttons and switches shall be identified with engraved lettering approximately 5/16” high.
e. All symbols shall comply with the latest ANSI Handicap Code.
f. Buttons shall be of the mushroom type bottoming out on the plate. Buttons shall be stainless steel with a maximum protrusion from the cover surface of 3/16”.
g. All floor buttons and switch assemblies requiring visual acknowledging light shall be
1/4-inch diameter clear Lexan Jewel replaceable insert type.
h. Hall push buttons shall have direction arrows and Lexan inserts.
i. Contact switch assembly shall be the Square D Class 9001 Type K contact.
j. Provide one (1) control key and three (3) change keys for construction phase of project.
Control key and change keys to be turned over to UNH lockshop at completion of project.
The new floor push button stations must be provided with the appropriate size boxes to ensure that the face plate can be installed tight to the finished wall surface.
5. Operating Procedures:
The operation of the elevator shall be from a single riser of pushbutton boxes at each landing, with “UP” and “DOWN” pushbuttons at all intermediate landings, and a single pushbutton at each terminal landing.
Car and Hall Buttons: When a call is registered by pressing a button, it shall illuminate to indicate that a call has been registered. The button shall remain lit until the elevator answers the call.
Car and hall push button stations shall be equipped with position indicators.
Alarm Bell: An alarm bell shall be provided in the hoistway, connected to the alarm bell button in the car operating station.
B. Two-Way Leveling: The car shall be equipped with a two-way leveling to automatically bring the car sill level with the landing sill, with a maximum one-quarter (1/4) inch tolerance above or below the floor, regardless of load. The two-way leveling system feature shall be automatic and independent of the operating device.
C. Automatic Terminal Stops: Normal and Final Switches shall be provided at the terminal floors to bring the car to a stop independent of their regular operating device.
2.05 CAR
A. Car Frame:
1. The car frame shall be retained.
B. Car Platform: to be retained.
C. Car Enclosure: The car enclosure shall be replaced.
The car enclosure shall be constructed of the following construction and design. The car enclosure shall be UL certified, in compliance with A17.1 Section 204.
14200- 11
1. Provide car enclosures of the snap type of design. Materials and finishes as hereafter indicated.
2. The car canopy shall be of best-grade cold-rolled furniture steel not less than No.14 US Standard Gauge. The canopy shall be of one-piece construction and reinforced to form a working platform to withstand a minimum weight of two workmen. The interior side of the canopy shall be finished with white baked enamel. The canopy will be equipped with recessed lighting fixtures. Drop ceiling will not be installed..
3. The entrance columns shall be square. A new header shall be provided above the return panels from top of car entrance to ceiling. Entrance columns, return panels and header shall be stainless steel, type not less than 14 gauge, with a No.4 satin finish.
4. Finish flooring: The new flooring to be a high quality rubber tile, Norament 926 Arago, color Calm. Sample shall be submitted to UNH with the submittals.
5. The walls of the cab shall be constructed of 16 US Gauge commercial quality cold rolled steel adequately reinforced. Panels shall be formed to provide light-proof joints and securely fastened to the platform with bolts, a minimum 1’0” on center. Finish shall be plastic laminate mounted on ¾” plywood. Colors to be selected by Owner.
6. The finish panels shall be as indicated for each elevator type.
7. The elevator shall be provided with an emergency exit cover located in the canopy. The emergency exit cover shall be kept in the closed position when not in use by a manually operated self-locking latch equipped with a manual reset switch that will remove power from the motor and valves when the cover is in the open position. Opening the cover from the car top shall be achieved without the use of keys or tools. The locking devices shall be accessible only from the car top. The covers shall be hinged and equipped with a handle, mounted on the top of the cover.
8. Necessary cutouts shall be provided in the car for operating fixtures, signal fixtures, etc., as specified elsewhere.
9. Ventilation shall consist of a two-speed fan exhaust fan located in the car ceiling.
10. Provide an emergency light mounted above the car operating panels as required by code.
11. Provide stainless steel handrails for each elevator. The handrails shall be located on the rear and side walls. See individual elevator criteria for additional railing requirements.
12. Stainless steel pad buttons and removable protective pads shall be provided for the elevator cab.
13. All interior and exterior steel surfaces shall be bonderized or given an approved rust preventative process before the finish is applied.
14. Finish: All furniture steel work on car shall be thoroughly cleaned, followed by a baked-on primer coat and sprayed-on two-coat baked enamel finish. All exposed surfaces of the furniture steel work shall receive applications of mineral filler with each coat application, baked and sanded and rubbed smooth between coats. Colors of all finishes shall closely match special color chips furnished by the Owner.
15. Particular care must be taken in boxing and crating cabs to avoid damage in transit, as cabs and accessories must be in perfect condition at the time of final inspection after installation.
16. The car operating panel shall be replaced.
17. The Elevator Installing Firm shall furnish and install a suitable communications cabinet in the car and shall furnish and install the necessary communication wires from the cabinet to a junction box, furnished and installed on the machine room controller. The communication system shall be of the vandal-resistant, hands-free phone equipped with push button automatic dial system in coordination with a two way audio plus a one way video Emergency communication by Rath. Provide a continuous EMT conduit sized for 2ea.Cat6 cables, from the Telecom closet to the elevator machine room.
18. Provide an emergency light mounted above the car operating panel as required by code.
14200- 12
19. Stainless steel pad buttons and removable protective pads shall be provided for the elevator cab.
2.06 DOORS AND ENTRANCES
A. Car doors shall be as follows:
1. Opening Size: As noted. 42” x 84”opening.
2. Opening Type: As noted. Single speed, Center Opening.
3. The new car doors shall be horizontal sliding type construction not less than one (1) inch thick. The car door leaves shall be hung on two-point suspension sheave-type hangers similar to those specified for hoistway doors. Doors shall be especially design and reinforced for power operation. Face doors with Type #4 stainless steel.
B. Hollow Steel Elevator Hoistway Entrances: To be retained.
1. Landing Doors: To be retained
2. Sills: To be retained. Sills to be wire brushed and vacuumed clean.
3. Fascia Plates and Toe Guards: To be retained. Elevator Contractor to insure all fascia plates are in place and securely fastened.
4. Hanger Supports, Hangers and Dust Covers: To be retained.
5. Struts and Closer Angles: To be retained.
6. Sight Guards: To be retained.
7. The existing landing door frames shall be wrapped in stainless steel with a Satin finish. The doors and frames thoroughly cleaned before elevator is returned to service.
C. Door Operator: Replace
1. Doors on the car and at each hoistway landing shall be operated quietly and smoothly by an electric operator, which shall open and close the car doors and hoistway doors simultaneously.
2. The car doors shall be provided with a non-contact detector system, which shall cause the doors to reopen upon the detection of a person or object in the entrance of the elevator. The detector shall extend the full length of and not project beyond the leading edge of the car doors. The car door protection device shall be of the infrared type ray screen. The infrared ray screen, when interrupted, shall hold the doors in the open position, permitting the doors to close shortly after the closing and the infrared ray screen is interrupted. The doors shall automatically reverse and return to the full open position, reclosing after a predetermined time interval. Pressing of car operating floor button, or “Door Close” button, shall cancel the door timing interval and cause the doors to close.
3. A door restrictor shall be installed on the car doors to prevent the opening of the doors from within the elevator unless the elevator is in the landing zone.
4. Each hoistway door shall be equipped with a new positive electromechanical interlock and auxiliary door closing device (sill mounted type) so that the elevator can be operated only after the interlock circuit is established. The interlock operations shall comply with the specified codes.
5. An electric contact for the car door shall be provided which shall prevent the elevator movement away from the landing unless the door is in the closed position as defined in the specified codes.
6. The door shall open automatically only after the elevator comes to a complete level stop, and close automatically either after the expiration of a time interval or the moment a car button call is registered. Only the door shall open for the landing being served. A “Door Open”
14200- 13 button, in the car station, shall cause the doors to stop and reopen upon activation of that button. The activation of a landing or car station button, at the landing where the elevator is located shall cause the doors to stop and reopen.
7. Door protection timers shall be provided for both the open and close directions which will help protect the door motor and which will help prevent the car from getting stuck at a landing. The door open protection timer shall cease attempting to open the door after a predetermined time in the event that the doors are prevented from reaching the open position.
The door close protection timer will reopen the doors for a short time in the event that the door closing attempt fails to make up the door locks after a predetermined time.
8. A minimum of three different door standing open times shall be provided. A car call time value shall predominate when a car call only is canceled. A hall call time value shall predominate whenever a hall call is canceled. In the event of a door reopen from the safety edge, photo eye, or door open button, a separate short door time value shall predominate.
The timing value for these timers must be field adjusted.
D. Headers, Door Hangers and Tracks: To be Retained.
PART 3 – EXECUTION
3.00 INSTALLATION
A. The Elevator Installing Firm shall be responsible for making field measurements of the machine rooms, hoistway, and openings for entrances before submitting drawings. After approval of shop drawings, the Elevator Installing Firm shall be responsible for the installation of equipment without field changes.
B. Elevator Improvements shall be complete in all respects and in a first-class manner, in accordance with the approved shop drawings, and the requirements of the laws, rules, regulations, codes, and industry standards specified herein.
C. Elevator work shall be complete in all respects, with all components properly adjusted, and with all operating mechanisms and controls in proper working order.
D. All Bidders shall visit the building/site prior to bidding, to examine existing conditions.
E. General: Shall be in accordance with manufacturer’s instructions and shall comply with applicable codes.
F. Welded Construction: Provide welded connections for installing elevator work where bolted connections are not required for subsequent removal or for normal operation, adjustment, inspection, maintenance, and replacement of worn parts. Comply with AWS standards for workmanship and for qualifications of welding operators.
G. Sound Isolation: Mount rotating and vibrating equipment on vibration-isolating mounts designed to effectively prevent transmission of vibrations to structure and thereby eliminate sources of structure-borne noise from elevator system.
H. Install piping above the floor.
I. Lubricate operating parts of systems as recommended by manufacturer.
14200- 14
J. Leveling Tolerance: 1/4 inch (6mm), up or down, regardless of load and direction of travel.
3.01 WIRING
A. Furnish and install as work of this Section all wiring necessary to connect operating buttons, switches and signals in the hoistway and all electrical equipment on the car to the elevator control panel. The wiring shall be installed in a neat and orderly manner, and shall be installed in conduit, electrical metallic tubing or metal wireways, excluding traveling cables, except that flexible conduit may be used for short runs.
B. Traveling cables shall be of the best grade for service and shall be so installed to provide a proper size loop to the car. The traveling cables shall have a fire resistant outer braid. Protection against wear shall be provided on any structural surface where the traveling cables come in contact during the movement of the elevator.
C. Three complete sets of wiring diagrams containing any field corrections, if necessary, shall be provided to the Owner upon completion of the installation of elevator equipment.
3.02 DEMONSTRATION
A. Instruct Owner’s personnel in proper use, operations, and daily maintenance of elevators. Review emergency provisions, including emergency access and procedures to be followed at time of operational failure and other building emergencies. Train Owner's personnel in procedures to follow in identifying sources of operational failures or malfunctions. Confer with Owner on requirements for a complete elevator maintenance program.
B. Make a final check of each elevator operation with Owner’s personnel present and before date of
Substantial Completion. Determine that operation systems and devices are functioning properly.
END OF SECTION 14200