261030-26081- UNH ELEVATORS DIMOND CD.pdf
PDF 2 MB Posted
- Attached to
- UNH Dimond Library Elevator Upgrades
- Solicitation number
- 2120271007
- Issued by
- New Hampshire
About this file
Contract Opportunity Summary
This is a construction specification and drawing set for the Dimond Library Elevator Modernization project at the University of New Hampshire in Durham, New Hampshire. The project encompasses the replacement and upgrade of elevator equipment and cabs, mechanical systems modifications including installation of a new roof-mounted exhaust fan with motorized damper control, electrical system upgrades to support a new 50-horsepower elevator motor and controller, and fire alarm system modifications. The scope of work includes selective demolition of existing elevator-related infrastructure, installation of new ductwork with fire dampers, replacement of electrical feeders and conduits from the main switchboard to the elevator disconnect and controller, and coordination of all mechanical, electrical, plumbing, and fire protection systems. The project must comply with the 2024 International Building Code, 2024 International Mechanical Code, 2023 National Electrical Code, 2024 International Fire Code, and all applicable New Hampshire state codes and amendments. The work is to be performed within an occupied building while minimizing disruption to building occupants.
The contract documents specify that all contractors, subcontractors, suppliers, and bidders are responsible for verifying their scope of work with the general contractor prior to submitting final bids and must field-measure existing conditions before work commences. Contractors are required to obtain all necessary permits and pay associated fees, provide comprehensive shop drawings for review and approval before ordering materials, maintain a weekly photographic log of construction progress, provide testing and balancing reports from certified professionals for all mechanical systems, and submit as-built drawings and comprehensive operation and maintenance manuals upon project completion. A one-year warranty from the date of beneficial use is required for all equipment and materials provided. The contract requires firestopping systems to be provided at all penetrations in fire-rated assemblies, compliance with manufacturer specifications and industry standards, and coordination with the existing campus Building Automation System for all control functions.
View the file
Other files
Show all 14
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
E
E EAST
EA EACH
EL ELEVATION
ELEC ELECTRICAL
ELEV ELEVATOR
EMER EMERGENCY
ENCL ENCLOSE
EP ELECTRICAL PANEL
EQ EQUAL
EQUIP EQUIPMENT
EXG EXISTING
EXH EXHAUST
EXP EXPOSED OR EXPANSION
EXPJT EXPANSION JOINT
EXT EXTERIOR
F
F FACE
FBO FURNISHED BY OTHERS
FD FLOOR DRAIN
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER
CABINET
FF FINISH FACE
FIN FINISHED
FIXT FIXTURE
FL FLOOR
FLEX FLEXIBLE
FLG FLASHING
FLUOR FLUORESCENT
FM FILLED METAL
FND FOUNDATION
FO FACE OF
FOC FACE OF CONCRETE
FOS FACE OF STUD
FPRF FIREPROOFING
FR FRAMING
FRT FIRE RATED PLYWOOD
FT FEET
FTG FOOTING
FURR FURRED
G
GA GAUGE
GALV GALVANIZED
GL GLASS
GLZ GLAZING
GR GRADE
GT GROUT
GYP GYPSUM
GWB GYPSUM WALL BOARD
H
H HIGH
HC HOLLOW CORE
HD HAND OR HEAD
HDBD HARDBOARD
HDR HEADER
HDW HARDWARE
HM HOLLOW METAL
HOR HORIZONTIAL
HP HIGH POINT
HR HOUR
HT HEIGHT
HVAC HEATING/VENTILATING/AIR
CONDITIONING
HWD HARDWOOD
I
ICF INSULATED CONCRETE
FORMS
ID INSIDE DIAMETER
ILO IN LIEU OF
IN INCHES
INCL INCLUDED
INS INSULATED
INT INTERIOR
IR IMPACT RESISTANT
J
JF JOINT FILLER
JMB JAMB
JST JOIST
JT JOINT
K
KIT KITCHEN
KO KNOCKOUT
L
L LENGTH
LAB LABORATORY
LAM LAMINATE
LAV LAVATORY
LBL LABEL
LG LONG
LH LEFT-HAND
LL LIVE LOAD
LO LOW
LOC LOCATION
LT LIGHT
S
S SOUTH OR SILL
SC SOLID CORE
SCH SCHEDULE
SECT SECTION
SH SHELF
SHT SHEET
SHTHG SHEATHING
SHWR SHOWER
SIM SIMILIAR
SL SLID
SLV SLEEVE
SNT SEALANT
SPC SPACER
SPEC SPECIFIED OR SPECIFICATION
SPK SPRINKLER
SQ SQUARE
SS STAINLESS STEEL
SSD SEE STRUCTURAL DRAWINGS
STA STATION
STC SOUND TRANSMISSION
COEFFICIENT
STD STANDARD
STL STEEL
STOR STORAGE
STR STRAIGHT
STRUC STRUCTURAL
SUSP SUSPENDED
SYM SYMMETRICAL
SYS SYSTEM
T
T TREAD
TB TOWEL BAR
T&B TOP AND BOTTOM
T&G TONGUE AND GROOVE
TEL TELEPHONE
TEMP TEMPORARY
TH THRESHOLD
THK THICKNESS
TLT TOILET
TO TOP OF
TOC TOP OF CONCRETE
TOL TOLERANCE
TOS TOP OF STEEL
TOP TOP OF PLATE
TOW TOP OF WALL
TP TOILET PAPER DISPENSER
TR TRANSOM
TS TOP OF SLAB
TYP TYPICAL
U
UC UNDERCOUNTER
UNO UNLESS NOTED OTHERWISE
US UNDERSIDE
V
VAL VALANCE
VARN VARNISH
VB VAPOR BARRIER
VCT VINYL COMPOSITION TILE
VERT VERTICAL
VEST VESTIBULE
VIF VERIFY IN FIELD
VNL VINYL
VNR VENEER
VP VISION PANEL
W
W WEST
W/ WITH
W/O WITHOUT
W/W WALL TO WALL
WB WOOD BASE
WC WATER CLOSET
WD WOOD
WL WALL
WM WIRE MESH
WP WATERPROOFING
WS WATERSTOP
WWF WELDED WIRE FABRIC
SYMBOLS
3D THREE DIMENSIONAL
& AND
@ AT
+/- PLUS OR MINUS
M
MAX MAXIMUM
MBR MASTER BEDROOM
MC MEDICINE CABINET
MECH MECHANICAL
MEMB MEMBRANE
MET METAL
MFR MANUFACTURER
MIN MINIMUM
MIR MIRROR
MISC MISCELLANEOUS
MO MASONRY OPENING
MR MOISTURE RESISTANT
MT METAL THRESHOLD
MTD MOUNTED
MTG MOUNTING
MTL MATERIAL OR METAL
MULL MULLION
N
N NORTH
NA NOT APPLICABLE
NAT NATURAL
NIC NOT IN CONTRACT
NO NUMBER
NOM NOMINAL
NR NOT REQUIRED
NRC NOISE REDUCTION
COEFFICIENT
NTS NOT TO SCALE
O
OA OVERALL
OC ON CENTER
OD OUTSIDE DIAMETER
OFF OFFICE
OH OVERHEAD
OPNG OPENING
OPP OPPOSITE
OPPH OPPOSITE HAND
OZ OUNCE
P
PAR PARALLEL
PBD PARTICLEBOARD
PCC PRE-CAST CONCRETE
PED PEDESTAL
PERIM PERIMETER
PL PROPERTY LINE
PLAM PLASTIC LAMINATE
PLAS PLASTER
PLUMB PLUMBING
PNL PANEL
PNT PAINT/PAINTED
PR PAIR
PRES PRESSURE
PT PRESSURE TREATED
PTN PARTITION
PVC POLYVINYL CHLORIDE
PVG PAVING
PVMT PAVEMENT
PWD PLYWOOD
R
R RISER
RAD RADIUS
RB RESILIENT BASE
RBR RUBBER
RBT RABBET
RCP REFLECTED CEILING PLAN
RD ROOF DRAIN
REBAR REINFORCING BARS
REC RECESSED
REF REFERENCE
REINF REINFORCED
REQD REQUIRED
RESIL RESILIENT
REV REVISION
RH RIGHT-HAND
RLG RAILING
RM ROOM
RO ROUGH OPEING
RVL REVEAL
RVS REVERSE SIDE
A
AB ANCHOR BOLT
ABV ABOVE
ABR AIR BARRIER
ACOUST ACOUSTICAL
ACT ACOUSTIC CEILING TILE
ADA AMERICAN DISABILITIES ACT
ADH ADHESIVE
ADJ ADJUSTABLE
AFF ABOVE FINISHED FLOOR
AGG AGGREGATE
AHR ANCHOR, ANCHORAGE
ALT ALTERNATE
ALUM ALUMINUM
ANOD ANODIZED
AP ACCESS PANEL
APPROX APPROXIMATE
ARCH ARCHITECTURAL
ASB ASBESTOS
ASPH ASPHALT
AUTO AUTOMATIC
A/V AUDIO VISUAL
B
BD BOARD
BEL BELOW
BET BETWEEN
BEY BEYOND
BIT BITUMINOUS
BKSPL BACKSPLASH
BLDG BUILDING
BLK BLOCK
BLKG BLOCKING
BM BEAM
BOT BOTTOM
BPL BEARING PLATE
BR BEDROOM
BRCG BRACING
BRG BEARING
BRK BRICK
BRZ BRONZE
BS BOTH SIDES
BSMT BASEMENT
BVL BEVELED
BW BOTH WAYS
BYND BEYOND
C
C CHANNEL
CAB CABINET
CAP CAPACITY
CEM CEMENT
CER CERAMIC
CI CAST IRON
CIP CAST IN PLACE
CIPC CAST IN PLACE CONCRETE
CG CORNER GUARD
CHNL CHANNEL
CJ CONTROL JOINT
CK CAULKING
CLG CEILING
CLO CLOSET
CLOS CLOSURE
CLR CLEAR
CMU CONCRETE MASONRY UNIT
CNTR COUNTER
COL COLUMN
COMPR COMPRESSIBLE
CONC CONCRETE
CONST CONSTRUCTION
CONT CONTINUOUS
CPT CARPET
CSK COUNTERSINK
CSMT CASEMENT
CT CERAMIC TILE
CTR CENTER
CTYD COURTYARD
D
DBL DOUBLE
DEMO DEMOLISH
DEPT DEPARTMENT
DET DETAIL
DF DRINKING FOUNTAIN
DIA DIAMETER
DIAG DIAGONAL
DIM DIMENSION
DISP DISPENSER
DN DOWN
DR DOOR
DS DOWNSPOUT
DWG DRAWING
A101
A101
SIM
Room name
1t
SHEET NO
INTERIOR
ELEVATION NO
SHEET NO
DETAIL NO
SHEET NO
FLOOR ELEVATION
MARKER
DOOR NUMBER
ROOM NUMBER
WINDOW TYPE
WALL TYPE
SECTION DETAIL NO
/1 A101 MATCHLINE REFERENCE
1 Ref
R ef
1 Ref
R ef
A101
SIM
KEYNOTE
EQUIPMENT / FURNITURE TAGA
LIGHT FIXTURE TAGLT-#
A LETTER: ROOF TYPE TAG
NUMBER: FLOOR/CEILING
ASSEMBLY TAG
1i
REVISION CLOUD
REVISION TAG
1. WORK INCLUDED IN THIS CONTRACT SHALL CONFORM TO THE STATE,
NATIONAL, AND OTHER CODES AND ORDINANCES THAT APPLY TO
THIS PROJECT.
2. DO NOT SCALE DRAWINGS OR DIMENSIONS. FOR MISSING
DIMENSIONS OR DIMENSIONAL CONFLICTS, CONTACT THE ARCHITECT
IMMEDIATELY BEFORE CONTINUING WITH THE WORK.
3. BRING ANY DISCREPANCIES IN THESE PLANS TO THE ARCHITECT'S
ATTENTION IMMEDIATELY.
4. REFER TO MECHANICAL, ELECTRICAL, PLUMBING AND FIRE
PROTECTION DRAWINGS AND SPECIFICATIONS FOR LOCATIONS OF
ALL BLOCK OUTS, INSERTS, OPENINGS, CURBS, BASES, AND PADS
THAT ARE NOT DIMENSIONED OR SHOWN ON ARCHITECTURAL OR
STRUCTURAL DRAWINGS, TYP.
5. STRUCTURAL STEEL, MECHANICAL, ELECTRICAL, PLUMBING, AND FIRE
PROTECTION DRAWINGS AND SPECIFICATIONS SHALL BE PROVIDED
AND ARE THE RESPONSIBILITY OF THEIR RESPECTIVE
SUBCONTRACTORS AND THEIR DESIGN BUILD ENGINEER.
6. DIMENSIONS ARE FROM FACE OF FRAMING TO FACE OF FRAMING
UNLESS NOTED OTHERWISE. DIMENSIONS INDICATED AS "CLEAR"
SHALL MAINTAIN A CLEAR OPENING WIDTH FROM FACE OF FINISHES.
DIMENSIONS TO EXISTING CONSTRUCTION ARE TO FACE OF FINISH
UNLESS NOTED OTHERWISE.
7. WORK FROM GIVEN DIMENSIONS AND LARGE SCALE DETAILS ONLY.
DO NOT SCALE DRAWINGS.
8. ROOM NUMBERS ON PLANS ARE FOR REFERENCE ONLY AND MAY
NOT CORRESPOND TO ACTUAL ROOM NUMBERS AT THE SITE.
9. BEFORE PENETRATING JOISTS, BEAMS, OR OTHER STRUCTURAL
MEMBERS, OBTAIN APPROVAL FROM THE ARCHITECT.
10. THE LOCATION OF DOOR OPENINGS NOT DIMENSIONED SHALL BE 6"
FROM ADJACENT WALL (FACE OF FRAMING TO ROUGH OPENING).
11. PROVIDE BLOCKING BEHIND SURFACE APPLIED FIXTURES, TRIM, GRAB
BARS, SHELVING, CHAIR RAILS, PICTURE RAILS, WOOD TRIM AND
BASE, AND OTHER ACCESSORIES WHEN MOUNTED ON STUD WALLS.
12. WHERE WALLS OR INFILLS ABUT OR INTERSECT EXISTING WALLS,
TAPE AND FINISH JOINTS AT INTERSECTIONS SMOOTH AND
CONTINUOUS. USE METAL TRIM WHERE GYPSUM BOARD INTERSECTS
OTHER MATERIALS.
13. PERMITS ARE THE RESPONSIBILITY OF THE CONTRACTOR AND SHALL
BE COORDINATED WITH PHASING AND WITH THE LOCAL BUILDING
COMMISSIONER.
14. DURING THE ENTIRE CONTRACT PERIOD, MAINTAIN THE
CONSTRUCTION SITE IN A SECURE, NEAT CLEAN, AND SAFE MANNER.
15. DISPOSE OF AND/OR RECYCLE CONSTRUCTION DEBRIS FROM THE
PROJECT SITE AS REQUIRED BY THE CONTRACT AND AS INSTRUCTED
BY THE OWNER. OBTAIN DISPOSAL PERMITS AS REQUIRED.
16. PROVIDE AND COORDINATE TEMPORARY UTILITY CONNECTIONS WITH
THE OWNER.
17. WORK SHALL BE COMPLETED IN COMPLIANCE WITH INDUSTRY
STANDARDS AND PERFORMED IN A WORKMANLIKE PROFESSIONAL
MANNER.
CONTINUOUS
LUMBER
NON-CONTINUOUS
LUMBER
BATT INSULATION
RIGID INSULATION
CONCRETE
MASONRY UNITS
CONCRETE
EARTH
METAL
GYPSUM, PLASTER,
MORTAR, GROUT, ETC.
PLYWOOD
FINISHED WOOD
BRICK
COURSE GRAVEL
STONE
SPRAY FOAM CLOSED
CELL INSULATION
: EXISTING
: PROPOSED
: TO BE REMOVED
DIMENSION FROM FINISH
FACE TO FINISH FACE
DIMENSION FROM FACE OF
STUD TO FACE OF STUD
XX' - XX"
XX' - XX"
FIRE - 1Hr Sep.
FIRE - 2Hr Sep.
Scale:
Project Number:
Date:
Drawn By:
Checked By:
ARCHITECT:
PORTSMOUTH ARCHITECTS
4 MARKET STREET
PORTSMOUTH NH, 03801
PHONE: (603) 430-0274
NOT TO SCALE
Drawing Name:
Project Name:
© 2026 Portsmouth Architects
4 Market Street Portsmouth, New Hampshire
603.430.0274
/3
0/
:4 2:
A
M Z:
\A ct iv e
Pr oj ec t F ile s\
1- U
N H
E
LE
VA
TO
R S\
D w gs \4
-C D
\2
- U
N H
E
LE
VA
TO
R S
D
IM
O N
D C
D .rv t
T1
26081 10/30/2026
MM
MG
UNIVERSITY OF NEW HAMPSHIRE
18 LIBRARY WAY
DURHAM, NH 03824
U N
IV
ER
SI
TY
O F
N
EW
H
AM
PS
H
IR
E
L
IB
R
AR
Y
W
AY
D U
R H
AM
, N
H
D
IM
O N
D L
IB
R
AR
Y
ABBREVIATIONS,
LEGENDS, GENERAL
NOTES AND LIST OF
DRAWINGS
UNIVERSITY OF NEW
HAMPSHIRE
ABBREVIATIONS
ARCHITECTURAL SYMBOLS
GENERAL NOTESMATERIAL KEY
GRAPHIC KEY
DIMENSION KEY
SHEET LIST
Sheet Number Sheet Name
GENERAL INFORMATION
T1 ABBREVIATIONS, LEGENDS, GENERAL NOTES AND LIST OF
DRAWINGS
T2 GENERAL SPECIFICATIONS
ARCHITECTURAL DRAWINGS
A101 OVERALL FLOOR PLANS
MECHANICAL DRAWINGS
M000 MECHANICAL ABBREVIATIONS, NOTES, AND SYMBOLS
M201 MECHANICAL DUCTWORK FLOOR PLAN
M400 MECHANICAL SPECIFICATIONS
ELECTRICAL DRAWINGS
E000 ELECTRICAL ABBREVIATIONS, NOTES, AND SYMBOLS
E201 ELECTRICAL POWER PLAN
E300 ELECTRICAL SPECIFICATIONS
18 LIBRARY WAY
DURHAM, NH 03824
FIRE RATING KEY
MECHANICAL AND ELECTRICAL
ENGINEER
Consulting Engineering Services (CES), Inc.
811 Middle Street Middletown, CT 06457 Office: (860) 632-1682
DIMOND LIBRARY - ELEVATOR MODERNIZATION
No. Description Date
Mark Gianniny NH Arch Stamp
010000 – GENERAL CONDITIONS
A. IT IS THE RESPONSIBILITY OF EACH CONTRACTOR, SUB-CONTRACTOR, SUPPLIER AND
BIDDER TO VERIFY THEIR SCOPE OF WORK WITH THE GENERAL CONTRACTOR (GC)
PRIOR TO SUBMITTING A FINAL BID.
B. ALL WORK TO COMPLY WITH THE STATE BUILDING CODE, INTERNATIONAL BUILDING
CODE, AND ALL APPLICABLE LOCAL, STATE AND FEDERAL CODES AND REGULATIONS.
NOTHING IN THESE DRAWINGS OR SPECIFICATIONS IS TO BE CONSIDERED AS
REQUIRING OR PERMITTING WORK THAT IS CONTRADICTORY TO THE CODES AND
REGULATIONS IN FORCE ON THE DATE OF THE CONSTRUCTION CONTRACT. SHOULD
ANY CONDITION DEVELOP WHICH IS NOT COVERED BY THE CONTRACT DOCUMENTS,
WHEREIN THE FINISHED WORK WILL NOT COMPLY WITH APPLICABLE CODES, A
CHANGE ORDER DETAILING AND SPECIFYING THE WORK REQUIRED SHALL BE
SUBMITTED AND APPROVED BEFORE PROCEEDING WITH WORK.
C. PRIOR TO START OF CONSTRUCTION, GC SHALL COORDINATE SCHEDULING OF
MEETING WITH HIS PROJECT PERSONNEL, THE BUILDING OWNER, REP(S), AND
OTHERS, FOR REVIEW OF PROJECT SCOPE, PROCEDURES, DESIGN INTENT,
CONSTRUCTION QUALITY EXPECTED, & FINAL DISCUSSION OF
DRAWINGS/DETAILS/QUESTIONS.
D. DIMENSIONS ON DRAWINGS ARE FINISH FACE TO FINISH FACE OF PARTITIONS,
COLUMNS ETC. OR TO WHERE SHOWN, UNLESS OTHERWISE NOTED. DO NOT SCALE
DRAWINGS.
E. WRITTEN DIMENSIONS TAKE PRECEDENCE OVER GRAPHIC REPRESENTATION. DETAIL
DIMENSIONS TAKE PRECEDENCE OVER PLAN DIMENSIONS.
F. CONTRACTOR IS RESPONSIBLE FOR FIELD MEASURING OF EXISTING CONDITIONS
PRIOR TO START OF WORK AND DURING CONSTRUCTION, AS NECESSARY, TO ASSURE
CONSTRUCTION ADHERENCE TO DRAWINGS. BY ENTERING INTO A CONSTRUCTION
CONTRACT FOR THIS WORK THE CONTRACTOR SHALL INDICATE HIS FAMILIARITY WITH
THE SITE/FIELD CONDITIONS. ALL 'HOLD' DIMENSIONS SHALL BE MONITORED TO
ASSURE CORRECTNESS. ANY DIMENSIONAL MODIFICATIONS/CONFLICTS ARE TO BE
BROUGHT TO ATTENTION OF ARCHITECT FOR REVIEW/APPROVAL.
G. ALL VERTICAL DIMENSIONS SHALL BE TAKEN FROM 'BENCH MARK' OR OTHER SIMILAR
GUIDE ESTABLISHED PRIOR TO START OF CONSTRUCTION, HIGH POINTS, LOW POINTS,
IRREGULARITIES IN FLOOR SLAB, PARTICULARLY, WHICH COULD IN ANY WAY AFFECT
FABRICATION/INSTALLATION WORK OF OTHER TRADES OR VENDORS (EG. CABINET
CONTRACTORS) SHALL BE BROUGHT TO ATTENTION OF ARCHITECT.
H. CONTRACTOR SHALL BE RESPONSIBLE FOR THE REMOVAL OF ALL CONSTRUCTION
DEBRIS AND FOR THE RETURN OF ANY BUILDING STANDARD COMPONENTS IF
REQUESTED BY THE OWNER.
I. ALL EXISTING HOLES/CRACKS IN SLAB AND THOSE RESULTING FROM THE
CONSTRUCTION PROCESS SHALL BE FILLED/REPAIRED AND THE SURFACE PATCHED
SMOOTH AND LEVEL WITH ADJACENT FLOOR SURFACE, IN A MANNER ACCEPTABLE TO
THE OWNER.
J. ALL NECESSARY WOOD BLOCKING/GROUNDS, ETC., ARE TO BE SUPPLIED AS
FIREPROOFED ELEMENTS. CONTRACTOR SHALL FULLY COORDINATE SETTING
PLACEMENT OF THESE ELEMENTS AS REQUIRED BY LOCAL CODE/BUILDING OR
SURROUNDING CONSTRUCTION CONDITIONS. GROUNDS/GROUNDS/BLOCKING MAY
NOT BE WHOLLY SHOWN ON DRAWINGS AND GOOD CONSTRUCTION PRACTICE SHALL
GOVERN SAID USE WHERE A QUESTION ARISES. DRYWALL CONTRACTOR TO PAY
PARTICULAR ATTENTION TO ALL LOCATIONS OF DRYWALL PARTITION CONSTRUCTION
THAT ABUT OR RECEIVE MILLWORK OR CABINETWORK CONSTRUCTION. INTERNAL
WOOD BLOCKING SHALL BE SUPPLIED FOR STURDY ANCHORAGE OF MILLWORK AND
AT INTERSECTIONS OF WOOD/GLASS BORROWED LIGHT PARTITIONS AND ADJACENT
DRYWALL CONSTRUCTION.
K. CONTRACTORS, AND VENDORS, ARE TO VERIFY ALL CLEARANCES (CORRIDORS,
STAIRS, ELEVATORS, ETC.) REQUIRED FOR DELIVERIES, PASSAGE OF ALL JOB
MATERIALS/EQUIPMENT.
L. ALL SUBSTITUTIONS, I.E., "EQUALS" MUST BE SUBMITTED TO THE OWNER & ARCHITECT
FOR WRITTEN APPROVAL PRIOR TO SUBSTITUTION BEING MADE.
M. PROVIDE RECORD AS-BUILT DRAWINGS THAT SHALL INCLUDE ALL CHANGES AND
DEVIATIONS FROM THE CONTRACT DOCUMENTS.
N. ALL MATERIALS, FINISHES, AND SYSTEMS INDICATED ON CONTRACT DOCUMENTS ARE
TO BE INSTALLED PER MANUFACTURER'S REQUIREMENTS AND RECOMMENDATIONS.
FOLLOW CONSTRUCTION INDUSTRY STANDARDS.
O. CONTRACTOR AND VENDORS SHALL DETERMINE AVAILABILITY OF FINISH MATERIALS.
ANY DELIVERY SCHEDULE THAT POTENTIALLY MAY CAUSE COORDINATION PROBLEMS
DURING THE FINAL STAGES OF CONSTRUCTION/INSTALLATION SHALL BE BROUGHT TO
THE ATTENTION OF GC, EARLY ON, FOR POSSIBLE REEVALUATION OF MATERIAL
DESIGNATION.
P. FINAL CLEAN - CLEAN ALL SURFACES, EQUIPMENT AND FURNISHINGS AFTER
COMPLETION OF CONSTRUCTION.
Q. PRIOR TO COMPLETION OF THE PROJECT SUBMIT OPERATION AND MAINTENANCE
(O&M) DATA FOR THE PROVIDED EQUIPMENT, PRODUCT, OR SYSTEM, DEFINING THE
IMPORTANCE OF SYSTEM INTERACTIONS, TROUBLESHOOTING, AND LONG-TERM
PREVENTIVE OPERATION AND MAINTENANCE AND WARRANTY INFORMATION.
COMPILE, PREPARE, AND AGGREGATE O&M DATA TO INCLUDE CLARIFYING AND
UPDATING THE ORIGINAL SEQUENCES OF OPERATION TO AS-BUILT CONDITIONS.
ORGANIZE AND PRESENT INFORMATION IN SUFFICIENT DETAIL TO CLEARLY EXPLAIN
O&M REQUIREMENTS AT THE SYSTEM, EQUIPMENT, COMPONENT, AND SUBASSEMBLY
LEVEL.
R. THE CONTRACTOR IS RESPONSIBLE FOR TAKING PHOTOS OF THE CONDITIONS OF
THE PROJECT SITE/SURROUNDING PROPERTIES, EXISTING CONDITIONS TO BE
REMOVED, AND EXISTING CONDITIONS TO REMAIN PRIOR TO THE COMMENCEMENT OF
WORK.
a. THE CONTRACTOR TO MAINTAIN A WEEKLY PHOTOGRAPHIC LOG OF THE
PROGRESS OF WORK UNTIL FINAL COMPLETION.
020000- SELECTIVE DEMO
A. OWNER WILL OCCUPY PORTIONS OF BUILDING IMMEDIATELY ADJACENT TO SELECTIVE
DEMOLITION AREA. CONDUCT SELECTIVE DEMOLITION SO BUILDING OCCUPANTS
OPERATIONS WILL NOT BY DISRUPTED.
B. NOTIFY OWNERS AND ARCHITECT OF DISCREPANCIES BETWEEN EXISTING
CONDITIONS AND DRAWINGS BEFORE PROCEEDING WITH SELECTIVE DEMOLITION.
C. IF MATERIALS ARE SUSPECTED OF CONTAINING HAZARDOUS MATERIALS ARE
UNCOVERED OR DISCOVERED, DO NOT DISTURB. IMMEDIATELY NOTIFY THE OWNER.
OWNER WILL REMOVE HAZARDOUS MATERIALS UNDER A SEPARATE CONTRACT.
D. LOCATE, IDENTIFY, DISCONNECT, AND SEAL OR CAP OFF UTILITY SERVICES AND
MECHANICAL/ELECTRICAL SYSTEMS SERVING AREAS TO BE SELECTIVELY
DEMOLISHED.
E. CONDUCT SELECTIVE DEMOLITION AND DEBRIS-REMOVAL OPERATIONS TO ENSURE
MINIMUM INTERFERENCE WITH FACILITY. DO NOT CLOSE OR OBSTRUCT STREETS,
WALKS, WALKWAYS, VEHICULAR ENTRANCES TO THE SITE OR ADJACENT OCCUPIED
OR USED FACILITIES WITHOUT PERMISSION FROM THE OWNER AND AUTHORITIES
HAVING JURISDICTION.
F. PROVIDE TEMPORARY BARRICADES & PROTECTION TO ENSURE SAFE PASSAGE OF
PEOPLE AROUND DEMOLITION AREA AND TO AND FROM OCCUPIED PORTIONS OF THE
BUILDING.
G. DEMOLITION SHALL BE LIMITED TO NON-STRUCTURAL BUILDING CONSTRUCTION, UNO.
IF STRUCTURAL ELEMENTS ARE DAMAGED OR AFFECTED BY DEMOLITION, PROVIDE
TEMPORARY SHORING AND BRACING AS REQUIRED TO PREVENT MOVEMENT,
SETTLEMENT OR COLLAPSE OF CONSTRUCTION BEING DEMOLISHED OR ADJACENT
FACILITIES TO REMAIN, CEASE OPERATIONS IMMEDIATELY AND NOTIFY THE OWNER &
ARCHITECT.
H. NEATLY CUT OPENINGS AND HOLES PLUMB, SQUARE AND TRUE TO DIMENSIONS
REQUIRED. USE HAND TOOLS OR SMALL POWER TOOLS DESIGNED FOR SAWING OR
GRINDING, NOT HAMMERING AND CHOPPING, TO MINIMIZE DISTURBANCE OF
ADJACENT SURFACES.
I. LOCATE SELECTIVE DEMOLITION EQUIPMENT AND REMOVE DEBRIS AND MATERIALS
SO AS NOT TO IMPOSE EXCESSIVE LOADS ON SUPPORTING WALLS, FLOORS OR
FRAMING.
J. PROTECT CONSTRUCTION INDICATED TO REMAIN AGAINST DAMAGE AND SOILING
DURING SELECTION DEMOLITION.
K. ERECT TEMPORARY DUST PARTITIONS, USE WATER MIST AND OTHER SUITABLE
METHODS TO LIMIT SPREAD OF DUST AND DIRT.
L. TRANSPORT AND DISPOSE OF DEMOLISHED ITEMS AND MATERIALS LEGALLY AND IN
EPA-APPROVED LANDFILL. DO NOT BURN DEMOLISHED MATERIALS.
M. CLEAN ADJACENT STRUCTURES AND IMPROVEMENTS OF DUST, DIRT AND DEBRIS
CAUSED BY SELECTIVE DEMOLITION OPERATIONS. RETURN ADJACENT AREAS TO
CONDITION EXISTING BEFORE SELECTIVE DEMOLITION.
042000 – UNIT MASONRY
A. ALL FACE BRICK IS NOTED ON THE DRAWINGS AND SHALL BE INSTALLED AS
RECOMMENDED BY THE BRICK INSTITUTE OF AMERICA FOR THE APPLICATIONS
SHOWN.
B. EXPOSED MASONRY WORK SHALL BE THOROUGHLY WASHED AND CLEANED WITH
CLEAR WATER AND FIBER BRUSH TO REMOVE MORTAR STAINS, DIRT, ETC.
C. PROVIDE METAL FLASHING AT OPENINGS AS REQUIRED.
D. PROVIDE STEEL ANGLE LINTELS AT NEW OR MODIFIED OPENINGS.
054000 - COLD-FORMED METAL FRAMING
A. STEEL STUDS AND RUNNERS ARE TO BE A MINIMUM OF 20-GA. STEEL AND SHALL
CONFORM TO ASTM C645. BRACE WALL FRAMING TO SUITABLE STRUCTURE.
061000 - ROUGH CARPENTRY
A. WOOD BLOCKING - MIN. 2" NOMINAL DIMENSIONAL LUMBER.
B. PLYWOOD BACKING PANELS - MIN. 3/4" FIRE RETARDANT TREATED.
C. ALL LUMBER MATERIAL EXPOSED TO THE WEATHER OR IN CONTACT WITH CONCRETE
OR MASONRY SHALL BE PRESSURE TREATED.
PROVIDE ALL ROUGH HARDWARE INCLUDING NAILS, SCREWS, FRAMING ANCHORS,
HANGERS, CLIPS AND OTHER RELATED ITEMS TO COMPLETE THE WORK.
078413 – PENETRATION FIRESTOPPING
A. FIRESTOPPING SYSTEMS FOR THROUGH-PENETRATIONS OF FIRE-RESISTANCE-RATED
WALLS, PARTITIONS, FLOORS, FLOOR-CEILING ASSEMBLIES, AND ROOF-CEILING
ASSEMBLIES.
B. PROVIDE TESTED AND LISTED PENETRATION FIRESTOP SYSTEMS COMPLYING WITH
ASTM E814 OR UL 1479.
C. PROVIDE SYSTEMS LISTED FOR THE ACTUAL TYPE, SIZE, AND CONFIGURATION OF
PENETRATING ITEMS AND THE CONSTRUCTION BEING PENETRATED.
D. FIRESTOP SYSTEM SUBMITTALS: IDENTIFY THE TESTED AND LISTED SYSTEM FOR
EACH PENETRATION CONDITION.
E. PROVIDE THIRD PARTY INSPECTIONS FOR ALL FIRE STOPPING ASSEMBLIES AND
LOCATIONS.
081113 - HOLLOW METAL DOORS AND FRAMES
A. MANUFACTURERS
1. CECO DOOR; ASSA ABLOY
2. CURRIES COMPANY; ASSA ABLOY
3. DERONDE PRODUCTS
4. MESKER DOOR INC.
5. PHILIPP MANUFACTURING CO
6. REPUBLIC DOORS AND FRAMES
7. STEELCRAFT; AN ALLEGION BRAND
B. STANDARD STEEL DOORS AND FRAMES
1. CONSTRUCT HOLLOW-METAL DOORS AND FRAMES TO COMPLY WITH
STANDARDS INDICATED FOR MATERIALS, FABRICATION, HARDWARE LOCATIONS,
HARDWARE REINFORCEMENT, TOLERANCES, AND CLEARANCES, AND AS
SPECIFIED.
2. DOORS AND FRAMES: SDI A250.8, LEVEL 2; SDI A250.4, LEVEL B.
3. DOORS: TYPE - AS INDICATED IN THE DOOR AND FRAME SCHEDULE; THICKNESS:
1-3/4 INCHES
A. FACE: UNCOATED OR METALLIC-COATED STEEL SHEET, MINIMUM THICKNESS
OF 0.042 INCH.
B. EDGE CONSTRUCTION: MODEL 1, FULL FLUSH.
C. EDGE BEVEL: PROVIDE MANUFACTURER'S STANDARD BEVELED OR SQUARE
EDGES.
D. CORE: MANUFACTURER'S STANDARD KRAFT-PAPER HONEYCOMB,
POLYSTYRENE, POLYURETHANE, OR VERTICAL STEEL STIFFENER.
E. EXTERIOR DOORS - TOP EDGE CLOSURES: CLOSE TOP EDGES OF DOORS
WITH FLUSH CLOSURES OF SAME MATERIAL AS FACE SHEETS. SEAL JOINTS
AGAINST WATER PENETRATION. BOTTOM EDGES: PROVIDE WEEP-HOLE
OPENINGS IN BOTTOMS OF EXTERIOR DOORS TO PERMIT MOISTURE TO
ESCAPE.
4. FRAMES:
A. MATERIALS: UNCOATED OR METALLIC-COATED STEEL SHEET, MINIMUM
THICKNESS OF 0.053 INCH.
B. SIDELITE AND TRANSOM FRAMES: FABRICATED FROM SAME THICKNESS
MATERIAL AS ADJACENT DOOR FRAME.
C. CONSTRUCTION: WELDED.
5. EXPOSED FINISH: PRIME FACTORY.
6. FIRE LOUVER: METALLIC-COATED STEEL FUSIBLE LINK FIRE RATED LOUVER.
A. UL LISTED, FUSIBLE LINK ACTIVATES AT 135˚F
B. FREE FLOW AREA: 50% FREE MINIMUM.
087100 - DOOR HARDWARE
A. SEE DOOR SCHEDULE FOR HARDWARE SETS
B. COORDINATE LOCK CORES AND KEYING WITH THE OWNER AND ARCHITECT. KEYING
TO MATCH EXISTING MASTER KEY SYSTEM.
C. SUBMITTALS - PROVIDE MANUFACTURER'S PRODUCT DATA, DOOR SCHEDULE, AND
KEYING SCHEDULE.
D. STANDARD WARRANTY PERIOD: ONE YEAR FROM DATE OF SUBSTANTIAL
COMPLETION, UNLESS OTHERWISE INDICATED. SPECIAL WARRANTY PERIODS - SEVEN
YEARS FOR HEAVY DUTY CYLINDRICAL (BORED) LOCKS AND LATCHES, FIVE YEARS
FOR EXIT HARDWARE, TWENTY FIVE YEARS FOR MANUAL SURFACE DOOR CLOSER
BODIES, AND TWO YEARS FOR ELECTROMECHANICAL DOOR HARDWARE.
E. SUBSTITUTIONS: REQUESTS FOR SUBSTITUTION AND PRODUCT APPROVAL FOR
INCLUSIVE MECHANICAL AND ELECTROMECHANICAL DOOR HARDWARE IN
COMPLIANCE WITH THE SPECIFICATIONS MUST BE SUBMITTED IN WRITING. APPROVAL
OF REQUESTS IS AT THE DISCRETION OF THE ARCHITECT, OWNER, AND THEIR
DESIGNATED CONSULTANTS.
092900 - GYPSUM BOARD
A. FIRE-RESISTANCE-RATED ASSEMBLIES: FOR FIRE-RESISTANCE-RATED ASSEMBLIES,
PROVIDE MATERIALS AND CONSTRUCTION IDENTICAL TO THOSE TESTED IN ASSEMBLY
INDICATED ACCORDING TO ASTM E 119 BY AN INDEPENDENT TESTING AGENCY.
B. 5/8" TYPE X, TAPERED EDGES THROUGHOUT UNLESS NOTED OTHERWISE.
C. "WET" AREAS:
1. PROVIDE MOLD-RESISTANT GYPSUM BOARD WITH MOISTURE- AND MOLD-
RESISTANT CORE AND PAPER SURFACES.
D. ALL EXTERIOR CORNERS SHALL RECEIVE GALVANIZED OR ALUMINUM-COATED STEEL
SHEET OR ROLLED ZINC CORNER BEAD.
E. TREAT GYPSUM BOARD JOINTS, INTERIOR ANGLES, EDGE TRIM, CONTROL JOINTS,
PENETRATIONS, FASTENER HEADS, SURFACE DEFECTS, AND ELSEWHERE AS
REQUIRED TO PREPARE GYPSUM BOARD SURFACES FOR DECORATION. PROMPTLY
REMOVE RESIDUAL JOINT COMPOUND FROM ADJACENT SURFACES. PREFILL OPEN
JOINTS AND DAMAGED SURFACE AREAS. APPLY JOINT TAPE OVER GYPSUM BOARD
JOINTS, EXCEPT FOR TRIM PRODUCTS SPECIFICALLY INDICATED AS NOT INTENDED TO
RECEIVE TAPE.
F. GYPSUM BOARD FINISH LEVELS: FINISH PANELS TO LEVELS INDICATED BELOW AND
ACCORDING TO ASTM C 840:
1. LEVEL 1: CEILING PLENUM AREAS, CONCEALED AREAS, AND WHERE INDICATED.
2. LEVEL 2: PANELS THAT ARE SUBSTRATE FOR TILE.
3. LEVEL 4: AT PANEL SURFACES THAT WILL BE EXPOSED TO VIEW UNLESS
OTHERWISE INDICATED.
G. SOUND ATTENUATION BLANKETS (ASTM C665) SHALL BE INSTALLED WHERE
INDICATED. BLANKETS SHALL CONFORM WITH FIRE RESISTANCE RATING REQUIRED
FOR WALL TYPE AND SHALL BE MANUFACTURERS STANDARD MATERIAL UTILIZING
MINERAL FIBERS.
099123 - INTERIOR PAINTING
A. PAINT FOR WALL FINISHES SHALL BE PROVIDED AS A THREE (3) COAT EGGSHELL
LATEX ENAMEL PAINT INSTALLATION, ONE (1) PRIME AND TWO (2) FINISH COATS,
COLORS AS SPECIFIED.
B. PAINT FOR METAL ELEMENTS, DOOR AND FRAMES AND WINDOW FRAMES SHALL HAVE
A THREE COAT SEMI-GLOSS LATEX ENAMEL FINISH. ONE (1) PRIME AND TWO (2) FINISH
COATS, COLORS AS SPECIFIED.
C. PAINTING CONTRACTOR SHALL ASSURE THAT NO ELECTRIC RECEPTACLE OR
TELECOM. OUTLET COVERPLATES HAVE BEEN INSTALLED PRIOR TO CONTEMPLATION
OF APPLICATION TO ANY WALL FINISH MATERIALS. ANY SUCH COVERPLATED OR
SURFACE HARDWARE, ETC., IN PLACE, SHALL BE REMOVED PRIOR TO WALL FINISH
APPLICATION.
D. UPON COMPLETION OF FINISH PHASE OF JOB, PAINTING CONTRACTOR SHALL
REMOVE ALL PAINT, WALLCOVERING PASTE ETC. FROM WHERE IT HAS SPILLED,
SPLASHED OR SPATTERED.
14200 – HYDRAULIC ELEVATORS.
A. WORK TO REPLACE AND UPGRADE ELEVATOR EQUIPMENT AND ELEVATOR CABS BY
OTHERS. COORDINATE WITH OWNER’S ELEVATOR SCOPE OF WORK.
Scale:
Project Number:
Date:
Drawn By:
Checked By:
NOT TO SCALE
Drawing Name:
Project Name:
© 2026 Portsmouth Architects
4 Market Street Portsmouth, New Hampshire
603.430.0274
/3
0/
:4 2:
A
M Z:
\A ct iv e
Pr oj ec t F ile s\
1- U
N H
E
LE
VA
TO
R S\
D w gs \4
-C D
\2
- U
N H
E
LE
VA
TO
R S
D
IM
O N
D C
D .rv t
T2
26081 10/30/2026
MM
MG
U N
IV
ER
SI
TY
O F
N
EW
H
AM
PS
H
IR
E
L
IB
R
AR
Y
W
AY
D U
R H
AM
, N
H
D
IM
O N
D L
IB
R
AR
Y
GENERAL
SPECIFICATIONS
UNIVERSITY OF NEW
HAMPSHIRE
GENERAL SPECIFICATIONS
STATE BUILDING CODE:
2024 INTERNATIONAL BUILDING
CODE (2024 IBC) WITH NEW
HAMPSHIRE AMENDMENTS
LIFE SAFETY AND FIRE CODE:
2024 NATIONAL FIRE PROTECTION
AGENCY 101 (NFPA 101) AMENDED
BY SAF-FMO300
2024 FIRE CODE NFPA 1 AMENDED
BY SAF-FMO300
STATE ENERGY CODE:
2018 INTERNATIONAL ENERGY
CONSERVATION CODE
(2018 IECC) WITH NEW
HAMPSHIRE AMENDMENTS
STATE MECHANICAL CODE:
2024 INTERNATIONAL
MECHANICAL CODE (2021 IMC)
WITH NEW HAMPSHIRE
AMENDMENTS
STATE ELECTRICAL CODE:
2023 NATIONAL ELECTRICAL
CODE (NEC 2023 NFPA70) WITH
NEW HAMPSHIRE AMENDMENTS
STATE PLUMBING CODE:
2024 INTERNATIONAL PLUMBING
CODE (2024 IPC) WITH NEW
HAMPSHIRE AMENDMENTS
STATE ACCESSIBILITY CODE:
THE ARCHITECTURAL BARRIER
FREE DESIGN CODE FOR THE
STATE OF NEW HAMPSHIRE
A117.1, 2017
EXISTING BUILDING CODE:
2024 INTERNATIONAL EXISTING
BUILDING CODE (2024 IEBC) WITH
NEW HAMPSHIRE AMENDMENTS
APPLICABLE CODES:
No. Description Date
A101
SIM
1 1.7
7'
8"
A101
MECH. ROOM
105 ELEVATOR
HOISTWAY
105ESA
3' - 0" 5' - 0" 8' - 10"
6'
100 CRA
1 1.7
N N
J J
J
J
A101 ELEVATOR
HOISTWAY
EXISTING ACT
EBU
1 1.7
8'
1/
2"
LEVEL 5
116'-11"
LEVEL 4
105'-8 1/2"
LEVEL 3
93'-6"
LEVEL 2
82'-3 1/2"
LEVEL 1
71'-1"
TOP OF STEEL
129' - 6 1/2"
/2
/2
/2
/2
/2
EXISTING HOIST VENT,
COORDINATE FAN WITH
MECHANICAL DRAWINGS.
ELEVATOR
HOISTWAY
MECH. ROOM
TYPE A:
1-1/2 HR FIRE
RATED DOOR
WITH 18"X18"
LOUVER W/ F.D.
DOOR TYPES
Scale:
Project Number:
Date:
Drawn By:
Checked By:
Drawing Name:
Project Name:
© 2026 Portsmouth Architects
4 Market Street Portsmouth, New Hampshire
603.430.0274
As indicated
/3
0/
:4 2:
A
M Z:
\A ct iv e
Pr oj ec t F ile s\
1- U
N H
E
LE
VA
TO
R S\
D w gs \4
-C D
\2
- U
N H
E
LE
VA
TO
R S
D
IM
O N
D C
D .rv t
A101
26081 10/30/2026
MM
MG/RD
U N
IV
ER
SI
TY
O F
N
EW
H
AM
PS
H
IR
E
L
IB
R
AR
Y
W
AY
D U
R H
AM
, N
H
D
IM
O N
D L
IB
R
AR
Y
OVERALL FLOOR PLANS
UNIVERSITY OF NEW
HAMPSHIRE
PLAN
NORTH
1/4" = 1' - 0" 0 5' 10' 15'1'
GENERAL NOTES
GRAPHIC SCALE(S)
KEY PLAN
KEYNOTES#
© 2026 Portsmouth Architects
KEYPLAN DIMOND LIBRARY FIRST FLOOR
1/4" = 1'-0"1 NORTH ELEVATOR LEVEL 1 DIMOND LIBRARY
1/4" = 1'-0"2 NORTH ELEVATOR DIAMOND LIBRARY RCP
1/4" = 1'-0"3 NORTH ELEVATOR DIMOND LIBRARY SECTION
DOOR SCHEDULE
Mark Size Door Frame Fire
Rating Door
Hardware CommentsHeight Width Type Mark Material Finish Frame Material Frame Finish
105 7' - 0" 3' - 0" A HM PNT EXIST PNT 1.5 EXIST PNT TO MATCH EXISTING
1. REMOVE EXISTING DOOR AND HARDWARE. SALVAGE HARDWARE FOR
REUSE. PROVIDE HOLLOW METAL DOOR WITH METAL VENTILATION LOUVER
AND FIRE DAMPER. REINSTALL SALVAGED HARDWARE.
2. INFILL WALL AT REMOVED TRANSFER DUCT AND GRILL. MATCH EXISTING
GWB CONSTRUCTION AND FIRE RATED ASSEMBLY.
3. CLEAR OBSTRUCTIONS IN EXISTING FIRE DAMPER SCREEN.
1. WORK TO REPLACE AND UPGRADE ELEVATOR EQUIPMENT AND CABS BY
OTHERS. COORDINATE WITH OWNER’S ELEVATOR SCOPE OF WORK.
2. PROVIDE FIRESTOPPING AT PENETRATIONS IN FIRE RATED ASSEMBLIES.
3. EXISTING RATED ASSEMBLIES SHALL BE MAINTAINED. ANY MODIFICATIONS TO
ASSEMBLIES WILL NEED TO MAINTAIN FIRE-RESISTANCE RATING.
No. Description Date
TAG SYMBOLS
DIFFUSER
TAG
6"
A
NECK SIZE /
LINEAR LENGTH
AIRFLOW (CFM)
UNIT TYPE
EQUIPMENT TAG-#
T# TYPICAL OF #
EQUIPMENT ABBREVIATIONS
LOUVER
RETURN GRILLE
TRANSFER GRILLE
EF
RG
TG
DUCTWORK LEGEND
SYMBOL DESCRIPTION
RECTANGULAR DUCTWORK
ACOUSTICALLY LINED DUCTWORK
RECTANGULAR SUPPLY DUCTWORK TOWARDS (UP IN PLAN)
RECTANGULAR SUPPLY DUCTWORK AWAY (DOWN IN PLAN)
RECTANGULAR RETURN DUCTWORK TOWARDS (UP IN PLAN)
RECTANGULAR RETURN DUCTWORK AWAY (DOWN IN PLAN)
RECTANGULAR EXHAUST DUCTWORK TOWARDS (UP IN PLAN)
RECTANGULAR EXHAUST DUCTWORK AWAY (DOWN IN PLAN)
FLEXIBLE DUCT
12x6
ROUND DUCTWORK12"ø
OVAL DUCTWORK12/6
ROUND SUPPLY DUCTWORK TOWARDS (UP IN PLAN)
ROUND SUPPLY DUCTWORK AWAY (DOWN IN PLAN)
ROUND RETURN DUCTWORK TOWARDS (UP IN PLAN)
ROUND RETURN DUCTWORK AWAY (DOWN IN PLAN)
ROUND EXHAUST DUCTWORK TOWARDS (UP IN PLAN)
ROUND EXHAUST DUCTWORK AWAY (DOWN IN PLAN)
DUCTWORK SHOWN SINGLE LINE
CAPPED DUCT
OPEN ENDED DUCT WITH WIRE MESH SCREEN
DUCT TRANSITION
ACOUSTICALLY LINED DUCTWORK (SINGLE LINE)
12x6
AIR DEVICE LEGEND
SYMBOL DESCRIPTION
SUPPLY DIFFUSER
RETURN GRILLE OR REGISTER
EXHAUST GRILLE OR REGISTER
SIDEWALL SUPPLY GRILLE
SIDEWALL RETURN OR EXHAUST GRILLE OR REGISTER
DAMPER LEGEND
SYMBOL DESCRIPTION
BACKDRAFT DAMPER
FIRE DAMPER W/ACCESS DOOR
SMOKE DAMPER W/SMOKE DETECTOR AND ACCESS DOOR
COMBINATION FIRE/SMOKE DAMPER W/SMOKE DETECTOR
AND ACCESS DOOR
MOTORIZED CONTROL DAMPER W/ACCESS DOOR
MANUAL VOLUME DAMPER
BD
FD
MD
RADIATION DAMPERRD
AUTOMATIC VOLUME DAMPER (PRESSURE INDEPENDENT)AVD
SD
FSD
GENERAL ABBREVIATIONS
ACCESS DOOR
ADJUSTABLE
ABOVE FINISHED FLOOR
ALTERNATE
AUTHORITY HAVING JURISDICTION
ACCESS PANEL
CONVECTOR
AIR PRESSURE DROP
AVERAGE WATER TEMPERATURE
BUILDING AUTOMATION SYSTEM
BYPASS FEEDER
BREAK HORSEPOWER
BUILDING MANAGEMENT SYSTEM
BRITISH THERMAL UNIT
BTU / HOUR
BOTTOM OF DUCT
BOTTOM OF PIPE
CEILING RADIATION DAMPER
CAPACITY
COEFFICIENT OF PERFORMANCE
CHILLED WATER SUPPLY
CHILLED WATER RETURN
CUBIC FEET PER MINUTE
CUBIC FEET
DECIBELS
DRY BULB TEMPERATURE
DIRECT DIGITAL CONTROL
DIAMETER
DOWN
DIRECT EXPANSION
EXHAUST AIR
ENTERING AIR TEMPERATURE (DRY BULB)
ENTERING DRY BULB
ENERGY EFFICIENCY RATIO
ELECTRICAL
EXTERNAL STATIC PRESSURE
ENTERING WET BULB
ENTERING WATER TEMPERATURE
DEGREES FAHRENHEIT
FIRE DAMPER
FEET
FEET WATER GAUGE
FULL LOAD AMPS
FEET PER MINUTE
COMBINATION FIRE SMOKE DAMPER
GALLONS PER HOUR
GALLONS PER MINUTE
GRILLE, REGISTER, DIFFUSER
HEAD
HORSEPOWER
HEATING SEASON PERFORMANCE FACTOR
HERTZ
HEATING, VENTILATION AND AIR CONDITIONING
HOT WATER RETURN
HOT WATER SUPPLY
INCHES
INCHES WATER GAUGE
INTEGRATED PART LOAD VALUE
KILOWATTS
LOUVER
LEAVING AIR TEMPERATURE
LEAVING DRY BULB
LEAVING WET BULB
LEAVING WATER TEMPERATURE
MAXIMUM
MECHANICAL
THOUSANDS OF BTU / HOUR
MINIMUM CIRCUIT AMPACITY
MINIMUM
NOT IN CONTRACT
NOT TO SCALE
OUTSIDE AIR TEMPERATURE
OUTER DIAMETER
OPEN ENDED DUCT
PUMP
PHASE
PLUMBING
PRESSURE REDUCING VALVE
POUNDS PER SQUARE INCH GAUGE
QUANTITY
RETURN AIR
REVOLUTIONS PER MINUTE
REDUCED PRESSURE ZONE BACKFLOW PREVENTER
RADON VENT
SUPPLY AIR
SEASONAL ENERGY EFFICIENCY RATIO
SIGHT GLASS
STATIC PRESSURE
STATIC PRESSURE DROP
STAINLESS STEEL
SATURATED SUCTION PRESSURE
SQUARE FEET
TEMPERATURE
TOTAL STATIC PRESSURE
THERMOSTAT
TYPICAL
UNLESS OTHERWISE INDICATED
VARIABLE AIR VOLUME
VARIABLE FREQUENCY DRIVE
VENT THRU ROOF
WITH
WITHOUT
WET BULB
WATER COLUMN
WATER GAUGE
WIRE MESH SCREEN
WATER PRESSURE DROP
AD
ADJ
AFF
ALT
AHJ
AP
CNV
APD
AWT
BAS
BF
BHP
BMS
BTU
BTUH
BOD
BOP
CRD
CAP
COP
CHWS
CHWR
CFM
CUFT
dB
DB
DDC
DIA
DN
DX
EA
EAT
EDB
EER
ELEC
ESP
EWB
EWT
°F
FD
FT
FT WG
FLA
FPM
FSD
GPH
GPM
GRD
HD
HP
HSPF
HZ
HVAC
HWR
HWS
IN
IN WG
IPLV
KW
L
LAT
LDB
LWB
LWT
MAX
MECH
MBH
MCA
MIN
NIC
NTS
OAT
OD
OED
P
PH
PLBG
PRV
PSIG
QTY
RA
RPM
RPZ
RV
SA
SEER
SG
SP
SPD
SS
SST
SQFT / SF
TEMP
TSP
TSTAT
TYP
UOI
VAV
VFD
VTR
W W/O
WB
WC
WG
WMS
WPD
GENERAL NOTES
1. GENERAL NOTES, SYMBOLS, AND DETAILS ARE APPLICABLE TO DRAWINGS WITHIN DIVISION 23.
2. PROVIDE ALL MATERIALS AND EQUIPMENT AND PERFORM ALL LABOR REQUIRED TO INSTALL
COMPLETE AND OPERABLE MECHANICAL SYSTEMS AS INDICATED ON THE DRAWINGS, AS
SPECIFIED, AND AS REQUIRED BY CODES.
3. DRAWINGS ARE DIAGRAMMATIC AND ARE INTENDED TO INDICATE CAPACITY, SIZE,
APPROXIMATE LOCATION AND GENERAL ARRANGEMENT. COORDINATE LOCATIONS OF
SYSTEMS AND COMPONENTS.
4. COORDINATE ROOF AND WALL PENETRATIONS WITH WORK OF OTHER SECTIONS AND WITH
FLASHING REQUIREMENTS. COORDINATE SLAB PENETRATIONS WITH WORK OF OTHER
SECTIONS.
5. RUN DUCTS AND PIPING CONCEALED UNLESS SPECIFIED OTHERWISE NOTED.
6. INSTALL SENSORS (THERMOSTATS) AT LOCATIONS SHOWN ON PLANS OR AS DIRECTED BY
ARCHITECT. MOUNTING HEIGHT AFF SHALL COMPLY WITH ADA AND SHALL BE MOUNTED
LEVEL WITH ADJACENT SWITCHES (IE LIGHT SWITCHES).
7. COORDINATE WORK OF THIS SECTION WITH THAT OF OTHER SECTIONS AND WITH ALL
TRADES INVOLVED. PROVIDE OFFSETS IN PIPING AND DUCTS (INCLUDING DIVIDED DUCTS)
AND TRANSITIONS AROUND OBSTRUCTIONS.
8. NOT ALL ACCESS DOORS HAVE BEEN SHOWN ON THE PLANS. PROVIDE ACCESS PANELS
THROUGH BUILDING ASSEMBLIES TO SERVICE AND MAINTAIN EQUIPMENT UNLESS SUCH
EQUIPMENT IS INSTALLED IN EXPOSED LOCATIONS OR ABOVE LAY-IN CEILINGS. COORDINATE
THE LOCATION OF ACCESS DOORS AND PANELS AND VERIFY THE QUANTITY, SIZE, AND
LOCATIONS AFTER THE SYSTEMS AND EQUIPMENT REQUIRING ACCESS HAVE BEEN
INSTALLED AND PRIOR TO THE CLOSURE OF THE AFFECTED CEILINGS AND BUILDING
ASSEMBLIES. SUBMIT ACCESS PANEL LOCATIONS FOR REVIEW.
9. AT SUBSTANTIAL COMPLETION, THE FOLLOWING ITEMS, NEW OR EXISTING, SHALL BE FULLY
AND REASONABLY ACCESSIBLE: HVAC CONTROL BOXES, JUNCTION BOXES, VALVES, DDC
CONTROL BOXES, ELECTRICAL PANELS, FILTERS, BELTS, WATER COILS, DISCONNECT
SWITCHES AND ELEMENTS OF EQUIPMENT REQUIRING MAINTENANCE. "FULLY AND
REASONABLY ACCESSIBLE" SHALL BE DEFINED AS NATIONAL ELECTRIC CODE REQUIRED
CLEARANCE FOR POWERED EQUIPMENT AND CAPABLE OF BEING ACCESSED OR SERVICED
WITHOUT REMOVING, MODIFYING OR DISTORTING OTHER COMPONENTS OF THE WORK.
PROVIDE MANUFACTURER'S RECOMMENDED CLEARANCE FOR ALL EQUIPMENT.
10. SUPPORT EQUIPMENT AND DUCTWORK FROM BUILDING STRUCTURE OR WITH STEEL
SUPPORTS AND PLATFORMS AS REQUIRED. PROVIDE VIBRATION ISOLATION FOR ROTATING
EQUIPMENT, DUCTWORK, AND PIPING IN ACCORDANCE WITH THE SPECIFICATIONS.
11. ROOF CURB AND RAIL HEIGHTS INDICATED ARE THE DIMENSIONS BETWEEN THE ROOF
SURFACE AND THE TOPS OF THE CURBS AND RAILS. WHERE THE ROOF IS PITCHED,
CONSTRUCT CURBS AND RAILS SUCH THAT THE BOTTOM PITCHES WITH THE ROOF AND THE
TOP IS LEVEL.
12. CONTROL WIRING METHODS SHALL COMPLY WITH NEC, AND DIVISION 26 SPECIFICATIONS.
13. VERIFY EQUIPMENT CONNECTIONS WITH MANUFACTURER'S DRAWINGS. VERIFY AND
PROVIDE FITTINGS TO TRANSITION TO FURNISHED EQUIPMENT. FIELD VERIFY AND
COORDINATE DIMENSIONS BEFORE FABRICATION.
14. PERFORM PRESSURE AND LEAKAGE TESTS BEFORE INSULATING DUCTWORK AND PIPING
15. MAINTAIN 6’-8” CLEARANCE TO THE UNDERSIDE OF PIPES, DUCTS, CONDUITS, SUSPENDED
EQUIPMENT, ETC., THROUGHOUT ROUTES IN MECHANICAL ROOMS. MAINTAIN 3’-0” WIDE
MEANS OF EGRESS IN MECHANICAL ROOMS.
16. MISCELLANEOUS STEEL REQUIRED TO ENSURE PROPER INSTALLATION AND, AS SHOWN IN
THE DETAILS FOR PIPING, DUCTWORK, AND EQUIPMENT, SHALL BE FURNISHED BY THE
MECHANICAL CONTRACTOR.
17. INSTALL UNITS WITH CLEARANCE FOR SERVICE AS REQUIRED BY THE MANUFACTURER.
AIR SYSTEM GENERAL NOTES
1. REFER TO SPECIFICATIONS FOR DUCTWORK CONSTRUCTION CLASSES, SEAL, AND
LEAKAGE CLASSES.
2. EXTERIOR LOUVERS ARE INDICATED FOR LOCATION ONLY. DETAILED DESCRIPTIONS ARE
PROVIDED IN ARCHITECTURAL DRAWINGS AND SPECIFICATIONS.
3. PROVIDE UL FIRE DAMPERS OR SMOKE/FIRE DAMPERS AND ASSOCIATED ACCESS PANELS
WHERE SHOWN ON DRAWINGS IN COMPLIANCE WITH NFPA 90A. FOR DUCTS THAT
PENETRATE FIRE-RATED WALLS, AND FLOORS.
4. REFER TO REFLECTED CEILING PLANS FOR LOCATIONS OF AIR TERMINAL DEVICES.
5. INTERNAL AIR FLOW DIMENSIONS ARE SHOWN FOR DUCTS. INCREASE SHEETMETAL SIZE
FOR LINER IF APPLICABLE.
6. DIFFUSER SIZES SHOWN ARE NECK SIZES; REGISTER AND GRILLE SIZE ARE NOMINAL.
ROUND RUN OUTS TO DIFFUSERS SHALL BE THE SAME NOMINAL SIZE AS THE SCHEDULED
NECK SIZE, UNLESS NOTED AS LARGER. DUCT TRANSITIONS SHALL BE PROVIDED AS
NECESSARY AT INLET TO DIFFUSER.
7. PROVIDE FLEXIBLE CONNECTIONS ON DUCTS CONNECTING TO FANS AND AIR HANDLING
UNITS.
8. THE INSIDE OF DUCTWORK VISIBLE THROUGH A GRILLE OR DIFFUSER SHALL BE PAINTED
FLAT BLACK.
9. OPEN ENDED DUCTS SHALL BE PROVIDED WITH A 1/4"x1/4" MESH ALUMINUM OR
GALVANIZED SCREEN (80% FREE AREA MINIMUM).
10. ELBOWS IN DUCT SYSTEMS SHALL BE FULL RADIUS (CENTERLINE RADIUS = 1.5 DUCT
WIDTH) WHERE SPACE PERMITS. WHERE LIMITED CLEARANCE OCCURS, PROVIDE SHORT
RADIUS ELBOW WITH FULL LENGTH SPLITTER VANES PER SMACNA OR MITERED ELBOW
WITH TURNING VANES PER SMACNA.
11. NOT ALL MANUAL DAMPERS ARE SHOWN ON THE DRAWINGS. PROVIDE MANUAL
ADJUSTABLE DAMPERS ON EACH LOW-PRESSURE SUPPLY, RETURN, AND EXHAUST DUCT
TAKE-OFF, AND AT TAKE-OFFS TO REGISTERS, GRILLES, DIFFUSERS, AND OED; AS
REQUIRED FOR PROPER BALANCE OF SYSTEM. PROVIDE CABLE-OPERATED DAMPERS
WHERE MANUAL DAMPER IS INACCESSIBLE. EACH DAMPER IN DUCTS 12" AND MORE SHALL
BE OPPOSED BLADE TYPE.
12. WHERE DUCTS PENETRATE WALLS WITH SOUND ISOLATION PERFORMANCE RATINGS,
PROVIDE DUCT SLEEVE SIZED TO PROVIDE 1/4" GAP BETWEEN THE SLEEVE AND DUCT. FILL
THE GAP WITH FIBEROUS MATERIAL AND SEAL AIRTIGHT WITH NON-HARDENING ACOUSTIC
SEALANT
13. HVAC EQUIPMENT AND DUCTS SHALL NOT BE USED FOR TEMPORARY HEATING, COOLING
OR VENTILATION.
14. PROVIDE FLEXIBLE CONNECTIONS AT ALL LOCATIONS WHERE DUCTS CROSS EXPANSION
OR SEISMIC JOINTS. COORDINATE WITH ARCHITECTURAL DRAWINGS.
DEMOLITION NOTES
DEMOLITION NOTES
1. SITE VISIT: THIS PROJECT INVOLVES CONSTRUCTION INSIDE AN EXISTING STRUCTURE.
BEFORE SUBMITTING BID, VISIT AND CAREFULLY EXAMINE SITE TO IDENTIFY EXISTING
CONDITIONS AND DIFFICULTIES THAT WILL AFFECT WORK OF THIS SECTION. NO EXTRA
PAYMENT WILL BE ALLOWED FOR ADDITIONAL WORK CAUSED BY UNFAMILIARITY WITH
SITE CONDITIONS THAT ARE VISIBLE OR READILY CONSTRUED BY EXPERIENCED
OBSERVER.
2. PREPARATORY WORK: BEFORE STARTING WORK IN A PARTICULAR AREA OF THE
PROJECT, VISIT SITE AND EXAMINE CONDITIONS UNDER WHICH WORK MUST BE
PERFORMED INCLUDING PREPARATORY WORK DONE UNDER OTHER SECTIONS OR
CONTRACTS BY OWNER. REPORT CONDITIONS THAT MIGHT AFFECT WORK ADVERSELY IN
WRITING TO ARCHITECT AND OWNER. DO NOT PROCEED WITH WORK UNTIL DEFECTS
HAVE BEEN CORRECTED AND CONDITIONS ARE SATISFACTORY. COMMENCEMENT OF
WORK SHALL BE CONSTRUED AS COMPLETE ACCEPTANCE OF EXISTING CONDITIONS AND
PREPARATORY WORK.
3. PHASING: DEMOLITION WORK SHALL COMPLY WITH THE PHASING REQUIREMENTS OF THE
PROJECT AND BE COORDINATED WITH THE OWNER, ARCHITECT, CM AND ENGINEER. NO
REMOVALS SHALL BE IMPLEMENTED WITHOUT A THOROUGH UNDERSTANDING OF THE
PHASING REQUIREMENTS.
4. ABANDONING OF DUCTWORK, PIPING OR EQUIPMENT IN PLACE WITHIN SCOPE AREA IS
PROHIBITED.
5. PROVIDE 2 WEEKS NOTICE TO OWNER FOR SHUT DOWN OF ANY SERVICES AND/OR
SYSTEMS.
6. COORDINATE EXISTING EQUIPMENT AND MATERIALS THAT SHALL REMAIN THE PROPERTY
OF THE OWNER. ITEMS OF VALUE WHICH ARE NOT DIRECTED TO BE RETURNED TO THE
OWNER, SHALL BECOME THE PROPERTY OF THE CONTRACTOR AND SHALL BE REMOVED
FROM SITE AND LEGALLY DISPOSED OF. STORAGE OR SALE OF ITEMS ON THE PROJECT
SITE IS PROHIBITED.
7. PROTECTION: ENSURE THE SAFE PASSAGE OF PERSONS IN AND AROUND THE BUILDING
DURING DEMOLITION. PREVENT INJURY TO PERSONS AND DAMAGE TO PROPERTY.
PROVIDE ADEQUATE SHORING AND BRACING TO PREVENT COLLAPSE. IMMEDIATELY
REPAIR DAMAGED PROPERTY TO THE CONDITION BEFORE BEING DAMAGED. TAKE
EFFECTIVE MEASURES TO PREVENT WINDBLOWN DUST.
8. UTILITIES: MAINTAIN ALL UTILITIES EXCEPT THOSE REQUIRING REMOVAL OR RELOCATION.
KEEP UTILITIES IN SERVICE AND PROTECT FROM DAMAGE. DO NOT INTERRUPT UTILITIES
SERVING OCCUPIED AREAS WITHOUT FIRST OBTAINING PERMISSION FROM THE OWNER IN
WRITING. PROVIDE TEMPORARY SERVICES AS REQUIRED.
9. INFORMATION CONTAINED ON THESE DRAWINGS WAS OBTAINED FROM ARCHIVED
DRAWINGS AND SITE VISITS. DRAWINGS ARE DIAGRAMMATIC ONLY AND REFLECT OVERALL
SYSTEM REMOVAL. NOT EVERY ITEM OR COMPONENT OF A SYSTEM IS SHOWN. PROVIDE
COMPLETE REMOVAL OF ASSOCIATED ANCILLARY PIPES, HANGERS, VALVES AND
ACCESSORIES SERVING SYSTEM SHOWN.
10. DEMOLITION WORK SHALL COMPLY WITH OSHA, EPA AND APPLICABLE STATE AND LOCAL
CODES. COMPLY WITH HAULING AND DISPOSAL REGULATIONS.
11. REFER TO SPECIFICATIONS FOR ADDITIONAL DEMOLITION REQUIREMENTS AND
PROCEDURES.
FIRESTOPPING GENERAL NOTES
1. PROVIDE FIRE STOPPING AND SMOKE BARRIER SEALING OF PENETRATIONS THROUGH FIRE
OR SMOKE WALLS, BARRIERS AND PARTITIONS AS REQUIRED TO MAINTAIN RATING. REFER
TO ARCHITECTURAL FLOOR PLANS AND CODE SHEETS FOR WALL RATINGS. REFER TO
SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
CONTROLS LEGEND COMPLETE
DIGITAL INPUT
DIGITAL OUTPUT
ANALOG INPUT
ANALOG OUTPUT
DO
DI
AO
AI
T
PLAN
SYMBOL DESCRIPTION
DIAGRAM
SYMBOL
BAS TEMPERATURE SENSORTE
ACTUATOR LEGEND
SYMBOL DESCRIPTION
DAMPER WITH TWO POSITION ACTUATOR
POSITION SWITCHZS
CURRENT TRANSMITTERIT
Scale:
Project Number:
Date:
Drawn By:
Checked By:
CONSTRUCTION SET
Drawing Name:
Project Name:
© 2026 Portsmouth Architects
4 Market Street
Portsmouth, New Hampshire
603.430.0274
NTS
/2 /2
:2
:3
A M
C U s e rs \n h ill
\D o c u m e n ts
\R
-2
.0
-M
E P
C e n tr a l- U
N H
E le v a to r
M a c h in e R o o m
D
IM
O N
D n h ill R
Z E
J .r v t
M000
261202.00
10/30/2026
NGH
PTC
U N
H E
L E
V A
T O
R R
E N
O V
A T
IO
N
D
IM
O N
D L
IB
R
A R
Y
M A
IN
S
T R
E
T
D U
R H
A M
N
H
U N
IV
E
R S
IT
Y
O F
N E
W H
A M
P S
H
IR
E
MECHANICAL
ABBREVIATIONS, NOTES
AND SYMBOLS
UNH ELEVATOR
RENOVATION DIMOND
LIBRARY
261202.00
No. Description Date
1 1.7
DEMOLISH EXISTING 31x12
TRANSFER DUCT, GRILLES, AND
FIRE DAMPER.
EXISTING FIRE DAMPER TO REMAIN. CLEAR
OBSTRUCTIONS IN EXISTING FIRE DAMPER.
REPLACE EXISTING BIRD SCREEN.
EF-1
DEMOLISH EXISTING HOISTWAY
GOOSENECK, ASSOCIATED DAMPERS
AND CONTROLS. EXISTING ROOF CURB
TO REMAIN.
T
FD
FD
NEW ROOF MOUNTED EXHAUST FAN
MOUNTED ON EXISTING CURB. PROVIDE
CURB ADAPTER AS REQUIRED.
18x18 DOOR TRANSFER
GRILLE WITH INTEGRAL FIRE
DAMPER BY ARCHITECT
MECH. ROOM
ELEVATOR
HOISTWAY
105ESA
SEQUENCE OF OPERATION
GENERAL
1. PROVIDE BAS CONTROLS THOUGH THE CAMPUS BAS.
2. WHERE ADJUSTABLE TEMPERATURE SETPOINTS ARE INDICATED, THE
TEMPERATURE RANGE SHALL BE CAPABLE OF SETPOINTS BETWEEN
50°F AND 100 °F.
3. ALL ALARMS SHALL HAVE A 5 MIN. (ADJ.) DELAY BEFORE ACTIVATING
AT THE BAS.
SAFETIES AND ALARMS
1. IF THE FAN IS COMMANDED ON AND IT DOES NOT ACTIVATE, AN
ALARM SHALL BE GENERATED THROUGH THE BAS.
2. IF THE DAMPER IS COMMANDED OPEN AND IT DOES NOT PROVE
OPEN:
A. AN ALARM SHALL BE GENERATED THROUGH THE BAS.
B. THE FAN SHALL NOT ACTIVATE.
3. IF THE DAMPER IS COMMANDED CLOSED AND IT DOES NOT PROVE
CLOSED, AN ALARM SHALL BE GENERATED THROUGH THE BAS.
4. IF THE SPACE TEMPERATURE SENSOR FAILS OR LOSES
COMMUNICATION FOR 5 MIN (ADJ.)
OPERATION
1. IF THE SPACE TEMPERATURE RISES ABOVE SETPOINT 85°F (ADJ.):
A. THE BAS SHALL FULLY OPEN THE DAMPER.
B. ONCE THE DAMPER IS PROVEN OPEN, THE BAS SHALL ACTIVATE
THE FAN.
1. IF THE SPACE TEMPERATURE DROPS BELOW THE SETPONT 80°F
(ADJ.):
A. THE BAS SHALL DEACTIVATE THE FAN.
B. THE BAS SHALL FULLY CLOSE THE DAMPER.
FIRE ALARM SHUTDOWN
1. UPON THE BUILDING FIRE ALARM SYSTEM BEING ACTIVATED, THE
FAN SHALL SHUT OFF AND THE DAMPER SHALL CLOSE.
2. NOTE: FIRE ALARM SHUTDOWN SHALL BE A HARDWIRED LIFE-SAFETY
FUNCTION PROVIDED BY OTHERS AND NOT THROUGH THE BAS.
BAS
TEMPERATURE
SENSOR
EXH
EXH
TYPICAL FOR: EF-1
TE
DO
AI
DO
ZS
DI
DOIT
ESP
(IN WG)
FAN SCHEDULE
GENERAL
TAG MANUFACTURER MODEL LOCATION SERVICE
WEIGHT
(LBS)
PHYSICAL
CFM
ELECTRICAL REMARKS
TYPE
1. EC MOTOR, DIRECT DRIVE, DOWNBLAST ROOF FAN
MOP RATINGSRPM VOLTAGE FEATURESBHP PHASE INSTALL
REMARKS - TYPE REMARKS - RATINGS REMARKS - FEATURES REMARKS - INSTALL
1. AMCA CERTIFIED 1. FAN MOUNTED VARI-GREEN DIAL FOR BALANCING
2. ROOF CURB WITH INTEGRAL MOTORIZED DAMPER
1. SEE DETAIL
PERFORMANCE
EF-1 GREENHECK G-100HP-VG ROOF
MECHANICAL
ROOM
59 550 1.0 1,922 0.22 15 115 1 1 1 1,2 1
DRIVE
DIRECT
ACOUSTICAL DATA
INLET SONES
11.8
MCA
8.2
ELEVATOR
MACHINE ROOM ELEVATOR
EXISTING COUNTER FLASHING
EXISTING ROOF
ROOFING
EXISTING ROOF CURB AND
FLASHING
CURB ADAPTER
SECURE ADAPTER CURB TO EXISTING
ROOF CURB PER MANUFACTURERS
INSTRUCTIONS
SECURE FAN TO ADAPTER CURB PER
MANUFACTURERS INSTRUCTIONS
MOTORIZED DAMPER
Scale:
Project Number:
Date:
Drawn By:
Checked By:
CONSTRUCTION SET
Drawing Name:
Project Name:
© 2026 Portsmouth Architects
4 Market Street
Portsmouth, New Hampshire
603.430.0274
As indicated
/2 /2
:2
:3
A M
C U s e rs \n h ill
\D o c u m e n ts
\R
-2
.0
-M
E P
C e n tr a l- U
N H
E le v a to r
M a c h in e R o o m
D
IM
O N
D n h ill R
Z E
J .r v t
M101
261202.00
10/30/2026
NGH
PTC
U N
H E
L E
V A
T O
R R
E N
O V
A T
IO
N
D
IM
O N
D L
IB
R
A R
Y
M A
IN
S
T R
E
R H
A M
N
H
U N
IV
E
R S
IT
Y
O F
N E
W H
A M
P S
H
IR
E
MECHANICAL
DUCTWORK FLOOR PLAN
UNH ELEVATOR
RENOVATION DIMOND
LIBRARY
261202.00
1/4" = 1'-0"
MECHANICAL DUCTWORK - ELEVATOR
NTS
FANS - EXHAUST
1" = 20'-0"
MECHANICAL KEY PLAN - DIMOND LIBRARY - FIRST FLOOR
NTS
ROOF MOUNTED FAN DETAIL
23 00 00 - GENERAL
A. THESE SPECIFICATIONS ARE APPLICABLE TO ALL MECHANICAL DRAWINGS UNLESS NOTED
OTHERWISE. REVIEW THE ARCHITECTURAL, STRUCTURAL, ELECTRICAL, PLUMBING DRAWINGS
FOR NOTES, DIMENSIONS, ETC., AND COORDINATE WITH OTHER TRADES INVOLVED.
B. DESCRIPTION
1. THIS PROJECT COMPRISES ALTERATIONS AND RENOVATIONS TO THE EXISTING BUILDING.
THE EXISTING BUILDING IS CURRENTLY OCCUPIED AND THE PROJECT SHALL PROCEED IN A
MANNER THAT MINIMIZES ANY INCONVENIENCE TO THE BUILDING OCCUPANTS.
2. SCOPE OF WORK CONSISTS OF INSTALLATION OF MATERIALS TO BE FURNISHED UNDER THE
CONTRACT DOCUMENTS AND WITHOUT LIMITING GENERALITY THEREOF CONSISTS OF
FURNISHING LABOR, MATERIALS, EQUIPMENT, HOISTING, TRANSPORTATION, RIGGING,
STAGING, APPURTENANCES, AND SERVICES NECESSARY AND/OR INCIDENTAL TO PROPERLY
COMPLETE ALL WORK AS SHOWN ON THE DRAWINGS AND DESCRIBED HEREIN.
C. DEFINITIONS: THE FOLLOWING DEFINITIONS APPLY TO THIS CONTRACT
1. FURNISH: THE TERM "FURNISH" MEANS TO "SUPPLY AND DELIVER TO THE PROJECT SITE,
READY FOR UNLOADING, UNPACKING, ASSEMBLY, INSTALLATION, AND SIMILAR OPERATIONS"
2. INSTALL: THE TERM "INSTALL" IS USED TO DESCRIBE OPERATIONS AT PROJECT SITE
INCLUDING THE ACTUAL "UNLOADING, UNPACKING, ASSEMBLY, ERECTION, PLACING,
ANCHORING, APPLYING, WORKING TO DIMENSION, FINISHING, CURING, PROTECTING,
CLEANING, AND SIMILAR OPERATIONS."
3. PROVIDE: THE TERM "PROVIDE" MEANS "TO FURNISH AND INSTALL, COMPLETE AND READY
FOR THE INTENDED USE."
4. REMOVE: THE TERM "REMOVE" MEANS TO DISCONNECT FROM ITS PRESENT POSITION,
REMOVE FROM THE PREMISES AND TO DISPOSE OF IN A LEGAL MANNER."
5. SUBSTITUTIONS: "SUBSTITUTIONS" ARE REQUESTS FOR CHANGES IN PRODUCTS, MATERIALS
AND/OR METHODS OF CONSTRUCTION AS PROPOSED BY THE CONTRACTOR AFTER AWARD
OF THE CONTRACT."
D. DRAWINGS
1. DRAWINGS ARE DIAGRAMMATIC. THE FINAL PLACEMENT OF EQUIPMENT OR DEVICES IN THE
FIELD MAY NOT DIRECTLY CORRESPOND TO THAT WHICH IS SHOWN ON THE DRAWINGS.
THOUGH SOME OFFSETS & TRANSITIONS MAY BE SHOWN IN PIPING & SHEET METAL TO HELP
INDICATE THE PHYSICAL RELATIONSHIP BETWEEN THEM, IT IS NOT THE INTENT OF THE
DRAWINGS TO SHOW ALL PIPING & SHEET METAL OFFSETS & TRANSITIONS REQUIRED. THE
CONTRACTOR SHALL FULLY COORDINATE THE WORK AND PROVIDE ALL MATERIALS,
EQUIPMENT AND LABOR NECESSARY TO COMPLETE THE WORK OUTLINED ON THESE
CONTRACT DOCUMENTS. IF A CONFLICT IN POSITIONING OCCURS THE CONTRACTOR IS TO
NOTIFY THE ENGINEER IMMEDIATELY TO ASCERTAIN WHAT THE INTENT WAS BY THE DESIGN
PROFESSIONAL.
E. CODES AND STANDARDS: WORK SHALL CONFORM TO THE CURRENT EDITIONS OF THE
FOLLOWING:
1. SHEET METAL SMACNA STANDARDS
2. INTERNATIONAL MECHANICAL CODE
3. INTERNATIONAL ENERGY CONSERVATION CODE
4. INTERNATIONAL EXISTING BUILDING CODE
5. ALL OTHER APPLICABLE STATE AND LOCAL CODES AND ORDINANCES, OWNER STANDARDS
AND BASE BUILDING SPECIFICATIONS AND STANDARDS.
F. PERMITS AND FEES:
1. THE CONTRACTOR SHALL GIVE ALL NECESSARY NOTICES, OBTAIN ALL PERMITS; AND PAY
ALL GOVERNMENT AND STATE SALES TAXES AND FEES WHERE APPLICABLE, AND OTHER
COSTS, INCLUDING UTILITY CONNECTIONS OR EXTENSIONS IN CONNECTION WITH THE
WORK, FILE ALL NECESSARY DRAWINGS, PREPARE ALL DOCUMENTS AND OBTAIN ALL
NECESSARY APPROVALS OF ALL GOVERNMENTAL AND STATE DEPARTMENTS HAVING
JURISDICTION, OBTAIN ALL REQUIRED CERTIFICATES OF INSPECTION FOR HIS WORK, AND
DELIVER A COPY TO THE OWNER AND ENGINEER BEFORE REQUEST FOR ACCEPTANCE AND
FINAL PAYMENT FOR THE WORK.
G. EXISTING SYSTEMS AND EQUIPMENT
1. EXISTING TO BE REUSED/RELOCATED EQUIPMENT: REPORT ANY EXISTING EQUIPMENT
DEFICIENCIES TO THE OWNER AND THE ARCHITECT AND/OR ENGINEER.
2. CONNECT WORK TO VARIOUS EXISTING SYSTEMS AS INDICATED ON THE DRAWINGS. WORK
SHALL BE COMPATIBLE WITH THE EXISTING SYSTEM CONDITIONS. ALL WORK SHALL BE
COORDINATED WITH ALL TRADES INVOLVED AS WELL AS WITH EXISTING SYSTEMS, THE
STRUCTURE, AND OTHER OBSTRUCTIONS.
H. SURVEY AND MEASUREMENTS
1. THIS PROJECT INVOLVES CONSTRUCTION INSIDE AN EXISTING STRUCTURE. CONTRACTORS,
BY SUBMITTING A BID, SHALL BE COMPLETELY FAMILIAR WITH THE EXISTING CONDITION OF
THE BUILDING AS IT INFLUENCES THE WORK DESCRIBED. NO COMPENSATION WILL BE
GRANTED FOR ADDITIONAL WORK CAUSED BY UNFAMILIARITY WITH SITE CONDITIONS THAT
ARE VISIBLE OR READILY IDENTIFIED BY EXPERIENCED OBSERVERS.
2. DO NOT SCALE DRAWINGS. SCALE INDICATED ON DRAWINGS IS FOR ESTABLISHING
REFERENCE POINTS ONLY. ACTUAL FIELD CONDITIONS SHALL GOVERN ALL DIMENSIONS.
3. PRIOR TO ORDERING ANY MATERIALS AND EQUIPMENT, THOROUGHLY REVIEW THE SITE
CONDITIONS TO DETERMINE IF ADEQUATE CLEARANCES AND ACCESS IS ALLOWED TO
INSTALL THE COMPONENTS. ORDER EQUIPMENT BROKEN DOWN AS NECESSARY TO ALLOW
FOR PROPER RIGGING THROUGH THE PROJECT AREA. PROVIDE ALL NECESSARY
ALTERATIONS TO THE STRUCTURE OF THE BUILDING AS NECESSARY TO RIG THE EQUIPMENT
IN PLACE.
4. CONTRACTORS SHALL VERIFY, LAYOUT AND BE RESPONSIBLE FOR ALL MEASUREMENTS OF
ALL EXISTING CONDITIONS BEFORE COMMENCING WORK AND SHALL NOTIFY ARCHITECT
AND/OR ENGINEER IF A CONDITION EXISTS THAT PREVENTS THE CONTRACTOR FROM
ACCOMPLISHING THE INTENT OF THE DRAWINGS.
I. SUBMITTALS AND SHOP DRAWINGS
1. SUBMIT FOR REVIEW, ELECTRONIC SHOP DRAWINGS IN SEARCHABLE PDF FORMAT FOR THE
FOLLOWING.
a. SUBMITTAL DATA FOR ALL MATERIAL AND EQUIPMENT. CLEARLY IDENTIFY DEVIATIONS
OF THE SUBMITTED PRODUCTS FROM THE DESIGN.
b. DUCTWORK AND PIPING SHOP DRAWINGS: DRAWN TO ACCURATE SCALE OF 1/4”=1'0”.
HIGHLIGHT, ENCIRCLE, OR OTHERWISE INDICATE DEVIATIONS FROM THE CONTRACT
DOCUMENTS. DO NOT REPRODUCE CONTRACT DOCUMENTS OR COPY STANDARD
INFORMATION AS THE BASIS OF SHOP DRAWINGS. STANDARD INFORMATION PREPARED
WITHOUT SPECIFIC REFERENCE TO THE PROJECT IS NOT CONSIDERED SHOP
DRAWINGS.
c. CONTROLS SHOP DRAWINGS: INCLUDE EQUIPMENT AND SYSTEM CONTROL
SCHEMATICS, SEQUENCES OF OPERATIONS, LOGIC DIAGRAMS AND SYSTEM
COMPONENTS INCLUDING DETAILS OF TIE-IN TO EXISTING BUILDING CONTROL
MANAGEMENT SYSTEM.
2. DO NOT USE SHOP DRAWINGS WITHOUT AN APPROPRIATE FINAL STAMP INDICATING ACTION
TAKEN IN CONNECTION WITH CONSTRUCTION.
3. DO NOT ORDER ANY MATERIALS OR EQUIPMENT PRIOR TO RECEIVING FINAL APPROVED
SUBMITTALS.
4. SCHEDULE AT LEAST TEN WORKING DAYS EXCLUSIVE OF TRANSMITTAL TIME, FOR
SUBMITTAL REVIEW.
J. AS-BUILT DRAWINGS
A. MAINTAIN ONE SET OF PRINTS ON THE SITE AND NOTE ALL CHANGES OR DEVIATIONS FROM
THE ORIGINAL DESIGN THEREON. AT THE COMPLETION OF THE PROJECT, INCORPORATE ALL
CHANGES INTO RECORD AS-BUILT DRAWINGS IN ELECTRONIC FORMAT AND SUBMIT FOR
APPROVAL.
23 31 00 - HVAC DUCTS
A. GENERAL REQUIREMENTS
1. FOR GALVANIZED DUCTWORK, SEAL AIR DUCT JOINTS AND JOINTS BETWEEN FITTINGS AND
DUCTS WITH HARDCAST SEALANT OR APPROVED EQUAL IN ACCORDANCE WITH
MANUFACTURER'S INSTRUCTIONS.
2. DUCTWORK SHALL BE FREE FROM VIBRATION UNDER ALL CONDITIONS OF OPERATION.
3. DIFFUSER & REGISTER LOCATIONS SHALL BE COORDINATED WITH ARCHITECTURAL
REFLECTED CEILING PLANS.
4. DIFFUSER SIZES SHOWN ARE NECK SIZES; REGISTER AND GRILLE SIZES ARE NOMINAL.
5. ALL DUCTS PENETRATING RATED FIRE WALLS SHALL BE PROVIDED WITH FIRE DAMPERS AND
ACCESS DOORS.
6. DUCTWORK SHALL NOT RUN ALONG FULL HEIGHT PARTITIONS.
7. PATCH AND SEAL ALL EXISTING OPENINGS IN DUCTWORK NOT UTILIZED FOR NEW LAYOUT.
8. THE INSIDE OF ALL UNLINED DUCTWORK VISIBLE THROUGH A GRILLE OR DIFFUSER SHALL BE
PAINTED FLAT BLACK.
9. WHEN SECTION OF DUCTWORK IS NOT LABELED FOR SIZE, THE LARGER SIZE INDICATED ON
THE CONNECTED DUCT SHALL PREVAIL. SIZE OF DUCT RUN-OUTS TO DIFFUSER SHALL
EQUAL DIFFUSER NECK SIZE.
10. DUCT BRANCH CONNECTIONS AND TAKE OFFS SHALL BE MADE WITH 45° CONNECTION,
BELLMOUTH OR CONICAL ONLY. SPIN IN COLLARS AND STRAIGHT TAPS SHALL NOT BE USED.
11. ELBOWS AND BENDS FOR RECTANGULAR DUCTS SHALL HAVE CENTER LINE RADIUS OF 1.5
TIMES DUCT WIDTH WHEREVER POSSIBLE. WHERE CENTERLINE RADIUS IS LESS THAN 1.5
TIMES DUCT WITH, ELBOWS SHALL BE RADIUS THROAT WITH RADIUS HEEL AND FULL-
LENGTH SPLITTER VANES.
12. NO PIPE, CONDUIT, HANGER, ARCHITECTURAL ELEMENT NOR STRUCTURAL MEMBER SHALL
PASS THROUGH DUCT WITHOUT…