261030-26081- UNH ELEVATORS DIMOND CD.pdf

PDF 2 MB Posted

Attached to
UNH Dimond Library Elevator Upgrades
Solicitation number
2120271007
Issued by
New Hampshire

About this file

Contract Opportunity Summary

This is a construction specification and drawing set for the Dimond Library Elevator Modernization project at the University of New Hampshire in Durham, New Hampshire. The project encompasses the replacement and upgrade of elevator equipment and cabs, mechanical systems modifications including installation of a new roof-mounted exhaust fan with motorized damper control, electrical system upgrades to support a new 50-horsepower elevator motor and controller, and fire alarm system modifications. The scope of work includes selective demolition of existing elevator-related infrastructure, installation of new ductwork with fire dampers, replacement of electrical feeders and conduits from the main switchboard to the elevator disconnect and controller, and coordination of all mechanical, electrical, plumbing, and fire protection systems. The project must comply with the 2024 International Building Code, 2024 International Mechanical Code, 2023 National Electrical Code, 2024 International Fire Code, and all applicable New Hampshire state codes and amendments. The work is to be performed within an occupied building while minimizing disruption to building occupants.

The contract documents specify that all contractors, subcontractors, suppliers, and bidders are responsible for verifying their scope of work with the general contractor prior to submitting final bids and must field-measure existing conditions before work commences. Contractors are required to obtain all necessary permits and pay associated fees, provide comprehensive shop drawings for review and approval before ordering materials, maintain a weekly photographic log of construction progress, provide testing and balancing reports from certified professionals for all mechanical systems, and submit as-built drawings and comprehensive operation and maintenance manuals upon project completion. A one-year warranty from the date of beneficial use is required for all equipment and materials provided. The contract requires firestopping systems to be provided at all penetrations in fire-rated assemblies, compliance with manufacturer specifications and industry standards, and coordination with the existing campus Building Automation System for all control functions.

View the file

Other files

Show all 14

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

E

E EAST

EA EACH

EL ELEVATION

ELEC ELECTRICAL

ELEV ELEVATOR

EMER EMERGENCY

ENCL ENCLOSE

EP ELECTRICAL PANEL

EQ EQUAL

EQUIP EQUIPMENT

EXG EXISTING

EXH EXHAUST

EXP EXPOSED OR EXPANSION

EXPJT EXPANSION JOINT

EXT EXTERIOR

F

F FACE

FBO FURNISHED BY OTHERS

FD FLOOR DRAIN

FE FIRE EXTINGUISHER

FEC FIRE EXTINGUISHER

CABINET

FF FINISH FACE

FIN FINISHED

FIXT FIXTURE

FL FLOOR

FLEX FLEXIBLE

FLG FLASHING

FLUOR FLUORESCENT

FM FILLED METAL

FND FOUNDATION

FO FACE OF

FOC FACE OF CONCRETE

FOS FACE OF STUD

FPRF FIREPROOFING

FR FRAMING

FRT FIRE RATED PLYWOOD

FT FEET

FTG FOOTING

FURR FURRED

G

GA GAUGE

GALV GALVANIZED

GL GLASS

GLZ GLAZING

GR GRADE

GT GROUT

GYP GYPSUM

GWB GYPSUM WALL BOARD

H

H HIGH

HC HOLLOW CORE

HD HAND OR HEAD

HDBD HARDBOARD

HDR HEADER

HDW HARDWARE

HM HOLLOW METAL

HOR HORIZONTIAL

HP HIGH POINT

HR HOUR

HT HEIGHT

HVAC HEATING/VENTILATING/AIR

CONDITIONING

HWD HARDWOOD

I

ICF INSULATED CONCRETE

FORMS

ID INSIDE DIAMETER

ILO IN LIEU OF

IN INCHES

INCL INCLUDED

INS INSULATED

INT INTERIOR

IR IMPACT RESISTANT

J

JF JOINT FILLER

JMB JAMB

JST JOIST

JT JOINT

K

KIT KITCHEN

KO KNOCKOUT

L

L LENGTH

LAB LABORATORY

LAM LAMINATE

LAV LAVATORY

LBL LABEL

LG LONG

LH LEFT-HAND

LL LIVE LOAD

LO LOW

LOC LOCATION

LT LIGHT

S

S SOUTH OR SILL

SC SOLID CORE

SCH SCHEDULE

SECT SECTION

SH SHELF

SHT SHEET

SHTHG SHEATHING

SHWR SHOWER

SIM SIMILIAR

SL SLID

SLV SLEEVE

SNT SEALANT

SPC SPACER

SPEC SPECIFIED OR SPECIFICATION

SPK SPRINKLER

SQ SQUARE

SS STAINLESS STEEL

SSD SEE STRUCTURAL DRAWINGS

STA STATION

STC SOUND TRANSMISSION

COEFFICIENT

STD STANDARD

STL STEEL

STOR STORAGE

STR STRAIGHT

STRUC STRUCTURAL

SUSP SUSPENDED

SYM SYMMETRICAL

SYS SYSTEM

T

T TREAD

TB TOWEL BAR

T&B TOP AND BOTTOM

T&G TONGUE AND GROOVE

TEL TELEPHONE

TEMP TEMPORARY

TH THRESHOLD

THK THICKNESS

TLT TOILET

TO TOP OF

TOC TOP OF CONCRETE

TOL TOLERANCE

TOS TOP OF STEEL

TOP TOP OF PLATE

TOW TOP OF WALL

TP TOILET PAPER DISPENSER

TR TRANSOM

TS TOP OF SLAB

TYP TYPICAL

U

UC UNDERCOUNTER

UNO UNLESS NOTED OTHERWISE

US UNDERSIDE

V

VAL VALANCE

VARN VARNISH

VB VAPOR BARRIER

VCT VINYL COMPOSITION TILE

VERT VERTICAL

VEST VESTIBULE

VIF VERIFY IN FIELD

VNL VINYL

VNR VENEER

VP VISION PANEL

W

W WEST

W/ WITH

W/O WITHOUT

W/W WALL TO WALL

WB WOOD BASE

WC WATER CLOSET

WD WOOD

WL WALL

WM WIRE MESH

WP WATERPROOFING

WS WATERSTOP

WWF WELDED WIRE FABRIC

SYMBOLS

3D THREE DIMENSIONAL

& AND

@ AT

+/- PLUS OR MINUS

M

MAX MAXIMUM

MBR MASTER BEDROOM

MC MEDICINE CABINET

MECH MECHANICAL

MEMB MEMBRANE

MET METAL

MFR MANUFACTURER

MIN MINIMUM

MIR MIRROR

MISC MISCELLANEOUS

MO MASONRY OPENING

MR MOISTURE RESISTANT

MT METAL THRESHOLD

MTD MOUNTED

MTG MOUNTING

MTL MATERIAL OR METAL

MULL MULLION

N

N NORTH

NA NOT APPLICABLE

NAT NATURAL

NIC NOT IN CONTRACT

NO NUMBER

NOM NOMINAL

NR NOT REQUIRED

NRC NOISE REDUCTION

COEFFICIENT

NTS NOT TO SCALE

O

OA OVERALL

OC ON CENTER

OD OUTSIDE DIAMETER

OFF OFFICE

OH OVERHEAD

OPNG OPENING

OPP OPPOSITE

OPPH OPPOSITE HAND

OZ OUNCE

P

PAR PARALLEL

PBD PARTICLEBOARD

PCC PRE-CAST CONCRETE

PED PEDESTAL

PERIM PERIMETER

PL PROPERTY LINE

PLAM PLASTIC LAMINATE

PLAS PLASTER

PLUMB PLUMBING

PNL PANEL

PNT PAINT/PAINTED

PR PAIR

PRES PRESSURE

PT PRESSURE TREATED

PTN PARTITION

PVC POLYVINYL CHLORIDE

PVG PAVING

PVMT PAVEMENT

PWD PLYWOOD

R

R RISER

RAD RADIUS

RB RESILIENT BASE

RBR RUBBER

RBT RABBET

RCP REFLECTED CEILING PLAN

RD ROOF DRAIN

REBAR REINFORCING BARS

REC RECESSED

REF REFERENCE

REINF REINFORCED

REQD REQUIRED

RESIL RESILIENT

REV REVISION

RH RIGHT-HAND

RLG RAILING

RM ROOM

RO ROUGH OPEING

RVL REVEAL

RVS REVERSE SIDE

A

AB ANCHOR BOLT

ABV ABOVE

ABR AIR BARRIER

ACOUST ACOUSTICAL

ACT ACOUSTIC CEILING TILE

ADA AMERICAN DISABILITIES ACT

ADH ADHESIVE

ADJ ADJUSTABLE

AFF ABOVE FINISHED FLOOR

AGG AGGREGATE

AHR ANCHOR, ANCHORAGE

ALT ALTERNATE

ALUM ALUMINUM

ANOD ANODIZED

AP ACCESS PANEL

APPROX APPROXIMATE

ARCH ARCHITECTURAL

ASB ASBESTOS

ASPH ASPHALT

AUTO AUTOMATIC

A/V AUDIO VISUAL

B

BD BOARD

BEL BELOW

BET BETWEEN

BEY BEYOND

BIT BITUMINOUS

BKSPL BACKSPLASH

BLDG BUILDING

BLK BLOCK

BLKG BLOCKING

BM BEAM

BOT BOTTOM

BPL BEARING PLATE

BR BEDROOM

BRCG BRACING

BRG BEARING

BRK BRICK

BRZ BRONZE

BS BOTH SIDES

BSMT BASEMENT

BVL BEVELED

BW BOTH WAYS

BYND BEYOND

C

C CHANNEL

CAB CABINET

CAP CAPACITY

CEM CEMENT

CER CERAMIC

CI CAST IRON

CIP CAST IN PLACE

CIPC CAST IN PLACE CONCRETE

CG CORNER GUARD

CHNL CHANNEL

CJ CONTROL JOINT

CK CAULKING

CLG CEILING

CLO CLOSET

CLOS CLOSURE

CLR CLEAR

CMU CONCRETE MASONRY UNIT

CNTR COUNTER

COL COLUMN

COMPR COMPRESSIBLE

CONC CONCRETE

CONST CONSTRUCTION

CONT CONTINUOUS

CPT CARPET

CSK COUNTERSINK

CSMT CASEMENT

CT CERAMIC TILE

CTR CENTER

CTYD COURTYARD

D

DBL DOUBLE

DEMO DEMOLISH

DEPT DEPARTMENT

DET DETAIL

DF DRINKING FOUNTAIN

DIA DIAMETER

DIAG DIAGONAL

DIM DIMENSION

DISP DISPENSER

DN DOWN

DR DOOR

DS DOWNSPOUT

DWG DRAWING

A101

A101

SIM

Room name

1t

SHEET NO

INTERIOR

ELEVATION NO

SHEET NO

DETAIL NO

SHEET NO

FLOOR ELEVATION

MARKER

DOOR NUMBER

ROOM NUMBER

WINDOW TYPE

WALL TYPE

SECTION DETAIL NO

/1 A101 MATCHLINE REFERENCE

1 Ref

R ef

1 Ref

R ef

A101

SIM

KEYNOTE

EQUIPMENT / FURNITURE TAGA

LIGHT FIXTURE TAGLT-#

A LETTER: ROOF TYPE TAG

NUMBER: FLOOR/CEILING

ASSEMBLY TAG

1i

REVISION CLOUD

REVISION TAG

1. WORK INCLUDED IN THIS CONTRACT SHALL CONFORM TO THE STATE,

NATIONAL, AND OTHER CODES AND ORDINANCES THAT APPLY TO

THIS PROJECT.

2. DO NOT SCALE DRAWINGS OR DIMENSIONS. FOR MISSING

DIMENSIONS OR DIMENSIONAL CONFLICTS, CONTACT THE ARCHITECT

IMMEDIATELY BEFORE CONTINUING WITH THE WORK.

3. BRING ANY DISCREPANCIES IN THESE PLANS TO THE ARCHITECT'S

ATTENTION IMMEDIATELY.

4. REFER TO MECHANICAL, ELECTRICAL, PLUMBING AND FIRE

PROTECTION DRAWINGS AND SPECIFICATIONS FOR LOCATIONS OF

ALL BLOCK OUTS, INSERTS, OPENINGS, CURBS, BASES, AND PADS

THAT ARE NOT DIMENSIONED OR SHOWN ON ARCHITECTURAL OR

STRUCTURAL DRAWINGS, TYP.

5. STRUCTURAL STEEL, MECHANICAL, ELECTRICAL, PLUMBING, AND FIRE

PROTECTION DRAWINGS AND SPECIFICATIONS SHALL BE PROVIDED

AND ARE THE RESPONSIBILITY OF THEIR RESPECTIVE

SUBCONTRACTORS AND THEIR DESIGN BUILD ENGINEER.

6. DIMENSIONS ARE FROM FACE OF FRAMING TO FACE OF FRAMING

UNLESS NOTED OTHERWISE. DIMENSIONS INDICATED AS "CLEAR"

SHALL MAINTAIN A CLEAR OPENING WIDTH FROM FACE OF FINISHES.

DIMENSIONS TO EXISTING CONSTRUCTION ARE TO FACE OF FINISH

UNLESS NOTED OTHERWISE.

7. WORK FROM GIVEN DIMENSIONS AND LARGE SCALE DETAILS ONLY.

DO NOT SCALE DRAWINGS.

8. ROOM NUMBERS ON PLANS ARE FOR REFERENCE ONLY AND MAY

NOT CORRESPOND TO ACTUAL ROOM NUMBERS AT THE SITE.

9. BEFORE PENETRATING JOISTS, BEAMS, OR OTHER STRUCTURAL

MEMBERS, OBTAIN APPROVAL FROM THE ARCHITECT.

10. THE LOCATION OF DOOR OPENINGS NOT DIMENSIONED SHALL BE 6"

FROM ADJACENT WALL (FACE OF FRAMING TO ROUGH OPENING).

11. PROVIDE BLOCKING BEHIND SURFACE APPLIED FIXTURES, TRIM, GRAB

BARS, SHELVING, CHAIR RAILS, PICTURE RAILS, WOOD TRIM AND

BASE, AND OTHER ACCESSORIES WHEN MOUNTED ON STUD WALLS.

12. WHERE WALLS OR INFILLS ABUT OR INTERSECT EXISTING WALLS,

TAPE AND FINISH JOINTS AT INTERSECTIONS SMOOTH AND

CONTINUOUS. USE METAL TRIM WHERE GYPSUM BOARD INTERSECTS

OTHER MATERIALS.

13. PERMITS ARE THE RESPONSIBILITY OF THE CONTRACTOR AND SHALL

BE COORDINATED WITH PHASING AND WITH THE LOCAL BUILDING

COMMISSIONER.

14. DURING THE ENTIRE CONTRACT PERIOD, MAINTAIN THE

CONSTRUCTION SITE IN A SECURE, NEAT CLEAN, AND SAFE MANNER.

15. DISPOSE OF AND/OR RECYCLE CONSTRUCTION DEBRIS FROM THE

PROJECT SITE AS REQUIRED BY THE CONTRACT AND AS INSTRUCTED

BY THE OWNER. OBTAIN DISPOSAL PERMITS AS REQUIRED.

16. PROVIDE AND COORDINATE TEMPORARY UTILITY CONNECTIONS WITH

THE OWNER.

17. WORK SHALL BE COMPLETED IN COMPLIANCE WITH INDUSTRY

STANDARDS AND PERFORMED IN A WORKMANLIKE PROFESSIONAL

MANNER.

CONTINUOUS

LUMBER

NON-CONTINUOUS

LUMBER

BATT INSULATION

RIGID INSULATION

CONCRETE

MASONRY UNITS

CONCRETE

EARTH

METAL

GYPSUM, PLASTER,

MORTAR, GROUT, ETC.

PLYWOOD

FINISHED WOOD

BRICK

COURSE GRAVEL

STONE

SPRAY FOAM CLOSED

CELL INSULATION

: EXISTING

: PROPOSED

: TO BE REMOVED

DIMENSION FROM FINISH

FACE TO FINISH FACE

DIMENSION FROM FACE OF

STUD TO FACE OF STUD

XX' - XX"

XX' - XX"

FIRE - 1Hr Sep.

FIRE - 2Hr Sep.

Scale:

Project Number:

Date:

Drawn By:

Checked By:

ARCHITECT:

PORTSMOUTH ARCHITECTS

4 MARKET STREET

PORTSMOUTH NH, 03801

PHONE: (603) 430-0274

NOT TO SCALE

Drawing Name:

Project Name:

© 2026 Portsmouth Architects

4 Market Street Portsmouth, New Hampshire

603.430.0274

/3

0/

:4 2:

A

M Z:

\A ct iv e

Pr oj ec t F ile s\

1- U

N H

E

LE

VA

TO

R S\

D w gs \4

-C D

\2

- U

N H

E

LE

VA

TO

R S

D

IM

O N

D C

D .rv t

T1

26081 10/30/2026

MM

MG

UNIVERSITY OF NEW HAMPSHIRE

18 LIBRARY WAY

DURHAM, NH 03824

U N

IV

ER

SI

TY

O F

N

EW

H

AM

PS

H

IR

E

L

IB

R

AR

Y

W

AY

D U

R H

AM

, N

H

D

IM

O N

D L

IB

R

AR

Y

ABBREVIATIONS,

LEGENDS, GENERAL

NOTES AND LIST OF

DRAWINGS

UNIVERSITY OF NEW

HAMPSHIRE

ABBREVIATIONS

ARCHITECTURAL SYMBOLS

GENERAL NOTESMATERIAL KEY

GRAPHIC KEY

DIMENSION KEY

SHEET LIST

Sheet Number Sheet Name

GENERAL INFORMATION

T1 ABBREVIATIONS, LEGENDS, GENERAL NOTES AND LIST OF

DRAWINGS

T2 GENERAL SPECIFICATIONS

ARCHITECTURAL DRAWINGS

A101 OVERALL FLOOR PLANS

MECHANICAL DRAWINGS

M000 MECHANICAL ABBREVIATIONS, NOTES, AND SYMBOLS

M201 MECHANICAL DUCTWORK FLOOR PLAN

M400 MECHANICAL SPECIFICATIONS

ELECTRICAL DRAWINGS

E000 ELECTRICAL ABBREVIATIONS, NOTES, AND SYMBOLS

E201 ELECTRICAL POWER PLAN

E300 ELECTRICAL SPECIFICATIONS

18 LIBRARY WAY

DURHAM, NH 03824

FIRE RATING KEY

MECHANICAL AND ELECTRICAL

ENGINEER

Consulting Engineering Services (CES), Inc.

811 Middle Street Middletown, CT 06457 Office: (860) 632-1682

DIMOND LIBRARY - ELEVATOR MODERNIZATION

No. Description Date

Mark Gianniny NH Arch Stamp

010000 – GENERAL CONDITIONS

A. IT IS THE RESPONSIBILITY OF EACH CONTRACTOR, SUB-CONTRACTOR, SUPPLIER AND

BIDDER TO VERIFY THEIR SCOPE OF WORK WITH THE GENERAL CONTRACTOR (GC)

PRIOR TO SUBMITTING A FINAL BID.

B. ALL WORK TO COMPLY WITH THE STATE BUILDING CODE, INTERNATIONAL BUILDING

CODE, AND ALL APPLICABLE LOCAL, STATE AND FEDERAL CODES AND REGULATIONS.

NOTHING IN THESE DRAWINGS OR SPECIFICATIONS IS TO BE CONSIDERED AS

REQUIRING OR PERMITTING WORK THAT IS CONTRADICTORY TO THE CODES AND

REGULATIONS IN FORCE ON THE DATE OF THE CONSTRUCTION CONTRACT. SHOULD

ANY CONDITION DEVELOP WHICH IS NOT COVERED BY THE CONTRACT DOCUMENTS,

WHEREIN THE FINISHED WORK WILL NOT COMPLY WITH APPLICABLE CODES, A

CHANGE ORDER DETAILING AND SPECIFYING THE WORK REQUIRED SHALL BE

SUBMITTED AND APPROVED BEFORE PROCEEDING WITH WORK.

C. PRIOR TO START OF CONSTRUCTION, GC SHALL COORDINATE SCHEDULING OF

MEETING WITH HIS PROJECT PERSONNEL, THE BUILDING OWNER, REP(S), AND

OTHERS, FOR REVIEW OF PROJECT SCOPE, PROCEDURES, DESIGN INTENT,

CONSTRUCTION QUALITY EXPECTED, & FINAL DISCUSSION OF

DRAWINGS/DETAILS/QUESTIONS.

D. DIMENSIONS ON DRAWINGS ARE FINISH FACE TO FINISH FACE OF PARTITIONS,

COLUMNS ETC. OR TO WHERE SHOWN, UNLESS OTHERWISE NOTED. DO NOT SCALE

DRAWINGS.

E. WRITTEN DIMENSIONS TAKE PRECEDENCE OVER GRAPHIC REPRESENTATION. DETAIL

DIMENSIONS TAKE PRECEDENCE OVER PLAN DIMENSIONS.

F. CONTRACTOR IS RESPONSIBLE FOR FIELD MEASURING OF EXISTING CONDITIONS

PRIOR TO START OF WORK AND DURING CONSTRUCTION, AS NECESSARY, TO ASSURE

CONSTRUCTION ADHERENCE TO DRAWINGS. BY ENTERING INTO A CONSTRUCTION

CONTRACT FOR THIS WORK THE CONTRACTOR SHALL INDICATE HIS FAMILIARITY WITH

THE SITE/FIELD CONDITIONS. ALL 'HOLD' DIMENSIONS SHALL BE MONITORED TO

ASSURE CORRECTNESS. ANY DIMENSIONAL MODIFICATIONS/CONFLICTS ARE TO BE

BROUGHT TO ATTENTION OF ARCHITECT FOR REVIEW/APPROVAL.

G. ALL VERTICAL DIMENSIONS SHALL BE TAKEN FROM 'BENCH MARK' OR OTHER SIMILAR

GUIDE ESTABLISHED PRIOR TO START OF CONSTRUCTION, HIGH POINTS, LOW POINTS,

IRREGULARITIES IN FLOOR SLAB, PARTICULARLY, WHICH COULD IN ANY WAY AFFECT

FABRICATION/INSTALLATION WORK OF OTHER TRADES OR VENDORS (EG. CABINET

CONTRACTORS) SHALL BE BROUGHT TO ATTENTION OF ARCHITECT.

H. CONTRACTOR SHALL BE RESPONSIBLE FOR THE REMOVAL OF ALL CONSTRUCTION

DEBRIS AND FOR THE RETURN OF ANY BUILDING STANDARD COMPONENTS IF

REQUESTED BY THE OWNER.

I. ALL EXISTING HOLES/CRACKS IN SLAB AND THOSE RESULTING FROM THE

CONSTRUCTION PROCESS SHALL BE FILLED/REPAIRED AND THE SURFACE PATCHED

SMOOTH AND LEVEL WITH ADJACENT FLOOR SURFACE, IN A MANNER ACCEPTABLE TO

THE OWNER.

J. ALL NECESSARY WOOD BLOCKING/GROUNDS, ETC., ARE TO BE SUPPLIED AS

FIREPROOFED ELEMENTS. CONTRACTOR SHALL FULLY COORDINATE SETTING

PLACEMENT OF THESE ELEMENTS AS REQUIRED BY LOCAL CODE/BUILDING OR

SURROUNDING CONSTRUCTION CONDITIONS. GROUNDS/GROUNDS/BLOCKING MAY

NOT BE WHOLLY SHOWN ON DRAWINGS AND GOOD CONSTRUCTION PRACTICE SHALL

GOVERN SAID USE WHERE A QUESTION ARISES. DRYWALL CONTRACTOR TO PAY

PARTICULAR ATTENTION TO ALL LOCATIONS OF DRYWALL PARTITION CONSTRUCTION

THAT ABUT OR RECEIVE MILLWORK OR CABINETWORK CONSTRUCTION. INTERNAL

WOOD BLOCKING SHALL BE SUPPLIED FOR STURDY ANCHORAGE OF MILLWORK AND

AT INTERSECTIONS OF WOOD/GLASS BORROWED LIGHT PARTITIONS AND ADJACENT

DRYWALL CONSTRUCTION.

K. CONTRACTORS, AND VENDORS, ARE TO VERIFY ALL CLEARANCES (CORRIDORS,

STAIRS, ELEVATORS, ETC.) REQUIRED FOR DELIVERIES, PASSAGE OF ALL JOB

MATERIALS/EQUIPMENT.

L. ALL SUBSTITUTIONS, I.E., "EQUALS" MUST BE SUBMITTED TO THE OWNER & ARCHITECT

FOR WRITTEN APPROVAL PRIOR TO SUBSTITUTION BEING MADE.

M. PROVIDE RECORD AS-BUILT DRAWINGS THAT SHALL INCLUDE ALL CHANGES AND

DEVIATIONS FROM THE CONTRACT DOCUMENTS.

N. ALL MATERIALS, FINISHES, AND SYSTEMS INDICATED ON CONTRACT DOCUMENTS ARE

TO BE INSTALLED PER MANUFACTURER'S REQUIREMENTS AND RECOMMENDATIONS.

FOLLOW CONSTRUCTION INDUSTRY STANDARDS.

O. CONTRACTOR AND VENDORS SHALL DETERMINE AVAILABILITY OF FINISH MATERIALS.

ANY DELIVERY SCHEDULE THAT POTENTIALLY MAY CAUSE COORDINATION PROBLEMS

DURING THE FINAL STAGES OF CONSTRUCTION/INSTALLATION SHALL BE BROUGHT TO

THE ATTENTION OF GC, EARLY ON, FOR POSSIBLE REEVALUATION OF MATERIAL

DESIGNATION.

P. FINAL CLEAN - CLEAN ALL SURFACES, EQUIPMENT AND FURNISHINGS AFTER

COMPLETION OF CONSTRUCTION.

Q. PRIOR TO COMPLETION OF THE PROJECT SUBMIT OPERATION AND MAINTENANCE

(O&M) DATA FOR THE PROVIDED EQUIPMENT, PRODUCT, OR SYSTEM, DEFINING THE

IMPORTANCE OF SYSTEM INTERACTIONS, TROUBLESHOOTING, AND LONG-TERM

PREVENTIVE OPERATION AND MAINTENANCE AND WARRANTY INFORMATION.

COMPILE, PREPARE, AND AGGREGATE O&M DATA TO INCLUDE CLARIFYING AND

UPDATING THE ORIGINAL SEQUENCES OF OPERATION TO AS-BUILT CONDITIONS.

ORGANIZE AND PRESENT INFORMATION IN SUFFICIENT DETAIL TO CLEARLY EXPLAIN

O&M REQUIREMENTS AT THE SYSTEM, EQUIPMENT, COMPONENT, AND SUBASSEMBLY

LEVEL.

R. THE CONTRACTOR IS RESPONSIBLE FOR TAKING PHOTOS OF THE CONDITIONS OF

THE PROJECT SITE/SURROUNDING PROPERTIES, EXISTING CONDITIONS TO BE

REMOVED, AND EXISTING CONDITIONS TO REMAIN PRIOR TO THE COMMENCEMENT OF

WORK.

a. THE CONTRACTOR TO MAINTAIN A WEEKLY PHOTOGRAPHIC LOG OF THE

PROGRESS OF WORK UNTIL FINAL COMPLETION.

020000- SELECTIVE DEMO

A. OWNER WILL OCCUPY PORTIONS OF BUILDING IMMEDIATELY ADJACENT TO SELECTIVE

DEMOLITION AREA. CONDUCT SELECTIVE DEMOLITION SO BUILDING OCCUPANTS

OPERATIONS WILL NOT BY DISRUPTED.

B. NOTIFY OWNERS AND ARCHITECT OF DISCREPANCIES BETWEEN EXISTING

CONDITIONS AND DRAWINGS BEFORE PROCEEDING WITH SELECTIVE DEMOLITION.

C. IF MATERIALS ARE SUSPECTED OF CONTAINING HAZARDOUS MATERIALS ARE

UNCOVERED OR DISCOVERED, DO NOT DISTURB. IMMEDIATELY NOTIFY THE OWNER.

OWNER WILL REMOVE HAZARDOUS MATERIALS UNDER A SEPARATE CONTRACT.

D. LOCATE, IDENTIFY, DISCONNECT, AND SEAL OR CAP OFF UTILITY SERVICES AND

MECHANICAL/ELECTRICAL SYSTEMS SERVING AREAS TO BE SELECTIVELY

DEMOLISHED.

E. CONDUCT SELECTIVE DEMOLITION AND DEBRIS-REMOVAL OPERATIONS TO ENSURE

MINIMUM INTERFERENCE WITH FACILITY. DO NOT CLOSE OR OBSTRUCT STREETS,

WALKS, WALKWAYS, VEHICULAR ENTRANCES TO THE SITE OR ADJACENT OCCUPIED

OR USED FACILITIES WITHOUT PERMISSION FROM THE OWNER AND AUTHORITIES

HAVING JURISDICTION.

F. PROVIDE TEMPORARY BARRICADES & PROTECTION TO ENSURE SAFE PASSAGE OF

PEOPLE AROUND DEMOLITION AREA AND TO AND FROM OCCUPIED PORTIONS OF THE

BUILDING.

G. DEMOLITION SHALL BE LIMITED TO NON-STRUCTURAL BUILDING CONSTRUCTION, UNO.

IF STRUCTURAL ELEMENTS ARE DAMAGED OR AFFECTED BY DEMOLITION, PROVIDE

TEMPORARY SHORING AND BRACING AS REQUIRED TO PREVENT MOVEMENT,

SETTLEMENT OR COLLAPSE OF CONSTRUCTION BEING DEMOLISHED OR ADJACENT

FACILITIES TO REMAIN, CEASE OPERATIONS IMMEDIATELY AND NOTIFY THE OWNER &

ARCHITECT.

H. NEATLY CUT OPENINGS AND HOLES PLUMB, SQUARE AND TRUE TO DIMENSIONS

REQUIRED. USE HAND TOOLS OR SMALL POWER TOOLS DESIGNED FOR SAWING OR

GRINDING, NOT HAMMERING AND CHOPPING, TO MINIMIZE DISTURBANCE OF

ADJACENT SURFACES.

I. LOCATE SELECTIVE DEMOLITION EQUIPMENT AND REMOVE DEBRIS AND MATERIALS

SO AS NOT TO IMPOSE EXCESSIVE LOADS ON SUPPORTING WALLS, FLOORS OR

FRAMING.

J. PROTECT CONSTRUCTION INDICATED TO REMAIN AGAINST DAMAGE AND SOILING

DURING SELECTION DEMOLITION.

K. ERECT TEMPORARY DUST PARTITIONS, USE WATER MIST AND OTHER SUITABLE

METHODS TO LIMIT SPREAD OF DUST AND DIRT.

L. TRANSPORT AND DISPOSE OF DEMOLISHED ITEMS AND MATERIALS LEGALLY AND IN

EPA-APPROVED LANDFILL. DO NOT BURN DEMOLISHED MATERIALS.

M. CLEAN ADJACENT STRUCTURES AND IMPROVEMENTS OF DUST, DIRT AND DEBRIS

CAUSED BY SELECTIVE DEMOLITION OPERATIONS. RETURN ADJACENT AREAS TO

CONDITION EXISTING BEFORE SELECTIVE DEMOLITION.

042000 – UNIT MASONRY

A. ALL FACE BRICK IS NOTED ON THE DRAWINGS AND SHALL BE INSTALLED AS

RECOMMENDED BY THE BRICK INSTITUTE OF AMERICA FOR THE APPLICATIONS

SHOWN.

B. EXPOSED MASONRY WORK SHALL BE THOROUGHLY WASHED AND CLEANED WITH

CLEAR WATER AND FIBER BRUSH TO REMOVE MORTAR STAINS, DIRT, ETC.

C. PROVIDE METAL FLASHING AT OPENINGS AS REQUIRED.

D. PROVIDE STEEL ANGLE LINTELS AT NEW OR MODIFIED OPENINGS.

054000 - COLD-FORMED METAL FRAMING

A. STEEL STUDS AND RUNNERS ARE TO BE A MINIMUM OF 20-GA. STEEL AND SHALL

CONFORM TO ASTM C645. BRACE WALL FRAMING TO SUITABLE STRUCTURE.

061000 - ROUGH CARPENTRY

A. WOOD BLOCKING - MIN. 2" NOMINAL DIMENSIONAL LUMBER.

B. PLYWOOD BACKING PANELS - MIN. 3/4" FIRE RETARDANT TREATED.

C. ALL LUMBER MATERIAL EXPOSED TO THE WEATHER OR IN CONTACT WITH CONCRETE

OR MASONRY SHALL BE PRESSURE TREATED.

PROVIDE ALL ROUGH HARDWARE INCLUDING NAILS, SCREWS, FRAMING ANCHORS,

HANGERS, CLIPS AND OTHER RELATED ITEMS TO COMPLETE THE WORK.

078413 – PENETRATION FIRESTOPPING

A. FIRESTOPPING SYSTEMS FOR THROUGH-PENETRATIONS OF FIRE-RESISTANCE-RATED

WALLS, PARTITIONS, FLOORS, FLOOR-CEILING ASSEMBLIES, AND ROOF-CEILING

ASSEMBLIES.

B. PROVIDE TESTED AND LISTED PENETRATION FIRESTOP SYSTEMS COMPLYING WITH

ASTM E814 OR UL 1479.

C. PROVIDE SYSTEMS LISTED FOR THE ACTUAL TYPE, SIZE, AND CONFIGURATION OF

PENETRATING ITEMS AND THE CONSTRUCTION BEING PENETRATED.

D. FIRESTOP SYSTEM SUBMITTALS: IDENTIFY THE TESTED AND LISTED SYSTEM FOR

EACH PENETRATION CONDITION.

E. PROVIDE THIRD PARTY INSPECTIONS FOR ALL FIRE STOPPING ASSEMBLIES AND

LOCATIONS.

081113 - HOLLOW METAL DOORS AND FRAMES

A. MANUFACTURERS

1. CECO DOOR; ASSA ABLOY

2. CURRIES COMPANY; ASSA ABLOY

3. DERONDE PRODUCTS

4. MESKER DOOR INC.

5. PHILIPP MANUFACTURING CO

6. REPUBLIC DOORS AND FRAMES

7. STEELCRAFT; AN ALLEGION BRAND

B. STANDARD STEEL DOORS AND FRAMES

1. CONSTRUCT HOLLOW-METAL DOORS AND FRAMES TO COMPLY WITH

STANDARDS INDICATED FOR MATERIALS, FABRICATION, HARDWARE LOCATIONS,

HARDWARE REINFORCEMENT, TOLERANCES, AND CLEARANCES, AND AS

SPECIFIED.

2. DOORS AND FRAMES: SDI A250.8, LEVEL 2; SDI A250.4, LEVEL B.

3. DOORS: TYPE - AS INDICATED IN THE DOOR AND FRAME SCHEDULE; THICKNESS:

1-3/4 INCHES

A. FACE: UNCOATED OR METALLIC-COATED STEEL SHEET, MINIMUM THICKNESS

OF 0.042 INCH.

B. EDGE CONSTRUCTION: MODEL 1, FULL FLUSH.

C. EDGE BEVEL: PROVIDE MANUFACTURER'S STANDARD BEVELED OR SQUARE

EDGES.

D. CORE: MANUFACTURER'S STANDARD KRAFT-PAPER HONEYCOMB,

POLYSTYRENE, POLYURETHANE, OR VERTICAL STEEL STIFFENER.

E. EXTERIOR DOORS - TOP EDGE CLOSURES: CLOSE TOP EDGES OF DOORS

WITH FLUSH CLOSURES OF SAME MATERIAL AS FACE SHEETS. SEAL JOINTS

AGAINST WATER PENETRATION. BOTTOM EDGES: PROVIDE WEEP-HOLE

OPENINGS IN BOTTOMS OF EXTERIOR DOORS TO PERMIT MOISTURE TO

ESCAPE.

4. FRAMES:

A. MATERIALS: UNCOATED OR METALLIC-COATED STEEL SHEET, MINIMUM

THICKNESS OF 0.053 INCH.

B. SIDELITE AND TRANSOM FRAMES: FABRICATED FROM SAME THICKNESS

MATERIAL AS ADJACENT DOOR FRAME.

C. CONSTRUCTION: WELDED.

5. EXPOSED FINISH: PRIME FACTORY.

6. FIRE LOUVER: METALLIC-COATED STEEL FUSIBLE LINK FIRE RATED LOUVER.

A. UL LISTED, FUSIBLE LINK ACTIVATES AT 135˚F

B. FREE FLOW AREA: 50% FREE MINIMUM.

087100 - DOOR HARDWARE

A. SEE DOOR SCHEDULE FOR HARDWARE SETS

B. COORDINATE LOCK CORES AND KEYING WITH THE OWNER AND ARCHITECT. KEYING

TO MATCH EXISTING MASTER KEY SYSTEM.

C. SUBMITTALS - PROVIDE MANUFACTURER'S PRODUCT DATA, DOOR SCHEDULE, AND

KEYING SCHEDULE.

D. STANDARD WARRANTY PERIOD: ONE YEAR FROM DATE OF SUBSTANTIAL

COMPLETION, UNLESS OTHERWISE INDICATED. SPECIAL WARRANTY PERIODS - SEVEN

YEARS FOR HEAVY DUTY CYLINDRICAL (BORED) LOCKS AND LATCHES, FIVE YEARS

FOR EXIT HARDWARE, TWENTY FIVE YEARS FOR MANUAL SURFACE DOOR CLOSER

BODIES, AND TWO YEARS FOR ELECTROMECHANICAL DOOR HARDWARE.

E. SUBSTITUTIONS: REQUESTS FOR SUBSTITUTION AND PRODUCT APPROVAL FOR

INCLUSIVE MECHANICAL AND ELECTROMECHANICAL DOOR HARDWARE IN

COMPLIANCE WITH THE SPECIFICATIONS MUST BE SUBMITTED IN WRITING. APPROVAL

OF REQUESTS IS AT THE DISCRETION OF THE ARCHITECT, OWNER, AND THEIR

DESIGNATED CONSULTANTS.

092900 - GYPSUM BOARD

A. FIRE-RESISTANCE-RATED ASSEMBLIES: FOR FIRE-RESISTANCE-RATED ASSEMBLIES,

PROVIDE MATERIALS AND CONSTRUCTION IDENTICAL TO THOSE TESTED IN ASSEMBLY

INDICATED ACCORDING TO ASTM E 119 BY AN INDEPENDENT TESTING AGENCY.

B. 5/8" TYPE X, TAPERED EDGES THROUGHOUT UNLESS NOTED OTHERWISE.

C. "WET" AREAS:

1. PROVIDE MOLD-RESISTANT GYPSUM BOARD WITH MOISTURE- AND MOLD-

RESISTANT CORE AND PAPER SURFACES.

D. ALL EXTERIOR CORNERS SHALL RECEIVE GALVANIZED OR ALUMINUM-COATED STEEL

SHEET OR ROLLED ZINC CORNER BEAD.

E. TREAT GYPSUM BOARD JOINTS, INTERIOR ANGLES, EDGE TRIM, CONTROL JOINTS,

PENETRATIONS, FASTENER HEADS, SURFACE DEFECTS, AND ELSEWHERE AS

REQUIRED TO PREPARE GYPSUM BOARD SURFACES FOR DECORATION. PROMPTLY

REMOVE RESIDUAL JOINT COMPOUND FROM ADJACENT SURFACES. PREFILL OPEN

JOINTS AND DAMAGED SURFACE AREAS. APPLY JOINT TAPE OVER GYPSUM BOARD

JOINTS, EXCEPT FOR TRIM PRODUCTS SPECIFICALLY INDICATED AS NOT INTENDED TO

RECEIVE TAPE.

F. GYPSUM BOARD FINISH LEVELS: FINISH PANELS TO LEVELS INDICATED BELOW AND

ACCORDING TO ASTM C 840:

1. LEVEL 1: CEILING PLENUM AREAS, CONCEALED AREAS, AND WHERE INDICATED.

2. LEVEL 2: PANELS THAT ARE SUBSTRATE FOR TILE.

3. LEVEL 4: AT PANEL SURFACES THAT WILL BE EXPOSED TO VIEW UNLESS

OTHERWISE INDICATED.

G. SOUND ATTENUATION BLANKETS (ASTM C665) SHALL BE INSTALLED WHERE

INDICATED. BLANKETS SHALL CONFORM WITH FIRE RESISTANCE RATING REQUIRED

FOR WALL TYPE AND SHALL BE MANUFACTURERS STANDARD MATERIAL UTILIZING

MINERAL FIBERS.

099123 - INTERIOR PAINTING

A. PAINT FOR WALL FINISHES SHALL BE PROVIDED AS A THREE (3) COAT EGGSHELL

LATEX ENAMEL PAINT INSTALLATION, ONE (1) PRIME AND TWO (2) FINISH COATS,

COLORS AS SPECIFIED.

B. PAINT FOR METAL ELEMENTS, DOOR AND FRAMES AND WINDOW FRAMES SHALL HAVE

A THREE COAT SEMI-GLOSS LATEX ENAMEL FINISH. ONE (1) PRIME AND TWO (2) FINISH

COATS, COLORS AS SPECIFIED.

C. PAINTING CONTRACTOR SHALL ASSURE THAT NO ELECTRIC RECEPTACLE OR

TELECOM. OUTLET COVERPLATES HAVE BEEN INSTALLED PRIOR TO CONTEMPLATION

OF APPLICATION TO ANY WALL FINISH MATERIALS. ANY SUCH COVERPLATED OR

SURFACE HARDWARE, ETC., IN PLACE, SHALL BE REMOVED PRIOR TO WALL FINISH

APPLICATION.

D. UPON COMPLETION OF FINISH PHASE OF JOB, PAINTING CONTRACTOR SHALL

REMOVE ALL PAINT, WALLCOVERING PASTE ETC. FROM WHERE IT HAS SPILLED,

SPLASHED OR SPATTERED.

14200 – HYDRAULIC ELEVATORS.

A. WORK TO REPLACE AND UPGRADE ELEVATOR EQUIPMENT AND ELEVATOR CABS BY

OTHERS. COORDINATE WITH OWNER’S ELEVATOR SCOPE OF WORK.

Scale:

Project Number:

Date:

Drawn By:

Checked By:

NOT TO SCALE

Drawing Name:

Project Name:

© 2026 Portsmouth Architects

4 Market Street Portsmouth, New Hampshire

603.430.0274

/3

0/

:4 2:

A

M Z:

\A ct iv e

Pr oj ec t F ile s\

1- U

N H

E

LE

VA

TO

R S\

D w gs \4

-C D

\2

- U

N H

E

LE

VA

TO

R S

D

IM

O N

D C

D .rv t

T2

26081 10/30/2026

MM

MG

U N

IV

ER

SI

TY

O F

N

EW

H

AM

PS

H

IR

E

L

IB

R

AR

Y

W

AY

D U

R H

AM

, N

H

D

IM

O N

D L

IB

R

AR

Y

GENERAL

SPECIFICATIONS

UNIVERSITY OF NEW

HAMPSHIRE

GENERAL SPECIFICATIONS

STATE BUILDING CODE:

2024 INTERNATIONAL BUILDING

CODE (2024 IBC) WITH NEW

HAMPSHIRE AMENDMENTS

LIFE SAFETY AND FIRE CODE:

2024 NATIONAL FIRE PROTECTION

AGENCY 101 (NFPA 101) AMENDED

BY SAF-FMO300

2024 FIRE CODE NFPA 1 AMENDED

BY SAF-FMO300

STATE ENERGY CODE:

2018 INTERNATIONAL ENERGY

CONSERVATION CODE

(2018 IECC) WITH NEW

HAMPSHIRE AMENDMENTS

STATE MECHANICAL CODE:

2024 INTERNATIONAL

MECHANICAL CODE (2021 IMC)

WITH NEW HAMPSHIRE

AMENDMENTS

STATE ELECTRICAL CODE:

2023 NATIONAL ELECTRICAL

CODE (NEC 2023 NFPA70) WITH

NEW HAMPSHIRE AMENDMENTS

STATE PLUMBING CODE:

2024 INTERNATIONAL PLUMBING

CODE (2024 IPC) WITH NEW

HAMPSHIRE AMENDMENTS

STATE ACCESSIBILITY CODE:

THE ARCHITECTURAL BARRIER

FREE DESIGN CODE FOR THE

STATE OF NEW HAMPSHIRE

A117.1, 2017

EXISTING BUILDING CODE:

2024 INTERNATIONAL EXISTING

BUILDING CODE (2024 IEBC) WITH

NEW HAMPSHIRE AMENDMENTS

APPLICABLE CODES:

No. Description Date

A101

SIM

1 1.7

7'

8"

A101

MECH. ROOM

105 ELEVATOR

HOISTWAY

105ESA

3' - 0" 5' - 0" 8' - 10"

6'

100 CRA

1 1.7

N N

J J

J

J

A101 ELEVATOR

HOISTWAY

EXISTING ACT

EBU

1 1.7

8'

1/

2"

LEVEL 5

116'-11"

LEVEL 4

105'-8 1/2"

LEVEL 3

93'-6"

LEVEL 2

82'-3 1/2"

LEVEL 1

71'-1"

TOP OF STEEL

129' - 6 1/2"

/2

/2

/2

/2

/2

EXISTING HOIST VENT,

COORDINATE FAN WITH

MECHANICAL DRAWINGS.

ELEVATOR

HOISTWAY

MECH. ROOM

TYPE A:

1-1/2 HR FIRE

RATED DOOR

WITH 18"X18"

LOUVER W/ F.D.

DOOR TYPES

Scale:

Project Number:

Date:

Drawn By:

Checked By:

Drawing Name:

Project Name:

© 2026 Portsmouth Architects

4 Market Street Portsmouth, New Hampshire

603.430.0274

As indicated

/3

0/

:4 2:

A

M Z:

\A ct iv e

Pr oj ec t F ile s\

1- U

N H

E

LE

VA

TO

R S\

D w gs \4

-C D

\2

- U

N H

E

LE

VA

TO

R S

D

IM

O N

D C

D .rv t

A101

26081 10/30/2026

MM

MG/RD

U N

IV

ER

SI

TY

O F

N

EW

H

AM

PS

H

IR

E

L

IB

R

AR

Y

W

AY

D U

R H

AM

, N

H

D

IM

O N

D L

IB

R

AR

Y

OVERALL FLOOR PLANS

UNIVERSITY OF NEW

HAMPSHIRE

PLAN

NORTH

1/4" = 1' - 0" 0 5' 10' 15'1'

GENERAL NOTES

GRAPHIC SCALE(S)

KEY PLAN

KEYNOTES#

© 2026 Portsmouth Architects

KEYPLAN DIMOND LIBRARY FIRST FLOOR

1/4" = 1'-0"1 NORTH ELEVATOR LEVEL 1 DIMOND LIBRARY

1/4" = 1'-0"2 NORTH ELEVATOR DIAMOND LIBRARY RCP

1/4" = 1'-0"3 NORTH ELEVATOR DIMOND LIBRARY SECTION

DOOR SCHEDULE

Mark Size Door Frame Fire

Rating Door

Hardware CommentsHeight Width Type Mark Material Finish Frame Material Frame Finish

105 7' - 0" 3' - 0" A HM PNT EXIST PNT 1.5 EXIST PNT TO MATCH EXISTING

1. REMOVE EXISTING DOOR AND HARDWARE. SALVAGE HARDWARE FOR

REUSE. PROVIDE HOLLOW METAL DOOR WITH METAL VENTILATION LOUVER

AND FIRE DAMPER. REINSTALL SALVAGED HARDWARE.

2. INFILL WALL AT REMOVED TRANSFER DUCT AND GRILL. MATCH EXISTING

GWB CONSTRUCTION AND FIRE RATED ASSEMBLY.

3. CLEAR OBSTRUCTIONS IN EXISTING FIRE DAMPER SCREEN.

1. WORK TO REPLACE AND UPGRADE ELEVATOR EQUIPMENT AND CABS BY

OTHERS. COORDINATE WITH OWNER’S ELEVATOR SCOPE OF WORK.

2. PROVIDE FIRESTOPPING AT PENETRATIONS IN FIRE RATED ASSEMBLIES.

3. EXISTING RATED ASSEMBLIES SHALL BE MAINTAINED. ANY MODIFICATIONS TO

ASSEMBLIES WILL NEED TO MAINTAIN FIRE-RESISTANCE RATING.

No. Description Date

TAG SYMBOLS

DIFFUSER

TAG

6"

A

NECK SIZE /

LINEAR LENGTH

AIRFLOW (CFM)

UNIT TYPE

EQUIPMENT TAG-#

T# TYPICAL OF #

EQUIPMENT ABBREVIATIONS

LOUVER

RETURN GRILLE

TRANSFER GRILLE

EF

RG

TG

DUCTWORK LEGEND

SYMBOL DESCRIPTION

RECTANGULAR DUCTWORK

ACOUSTICALLY LINED DUCTWORK

RECTANGULAR SUPPLY DUCTWORK TOWARDS (UP IN PLAN)

RECTANGULAR SUPPLY DUCTWORK AWAY (DOWN IN PLAN)

RECTANGULAR RETURN DUCTWORK TOWARDS (UP IN PLAN)

RECTANGULAR RETURN DUCTWORK AWAY (DOWN IN PLAN)

RECTANGULAR EXHAUST DUCTWORK TOWARDS (UP IN PLAN)

RECTANGULAR EXHAUST DUCTWORK AWAY (DOWN IN PLAN)

FLEXIBLE DUCT

12x6

ROUND DUCTWORK12"ø

OVAL DUCTWORK12/6

ROUND SUPPLY DUCTWORK TOWARDS (UP IN PLAN)

ROUND SUPPLY DUCTWORK AWAY (DOWN IN PLAN)

ROUND RETURN DUCTWORK TOWARDS (UP IN PLAN)

ROUND RETURN DUCTWORK AWAY (DOWN IN PLAN)

ROUND EXHAUST DUCTWORK TOWARDS (UP IN PLAN)

ROUND EXHAUST DUCTWORK AWAY (DOWN IN PLAN)

DUCTWORK SHOWN SINGLE LINE

CAPPED DUCT

OPEN ENDED DUCT WITH WIRE MESH SCREEN

DUCT TRANSITION

ACOUSTICALLY LINED DUCTWORK (SINGLE LINE)

12x6

AIR DEVICE LEGEND

SYMBOL DESCRIPTION

SUPPLY DIFFUSER

RETURN GRILLE OR REGISTER

EXHAUST GRILLE OR REGISTER

SIDEWALL SUPPLY GRILLE

SIDEWALL RETURN OR EXHAUST GRILLE OR REGISTER

DAMPER LEGEND

SYMBOL DESCRIPTION

BACKDRAFT DAMPER

FIRE DAMPER W/ACCESS DOOR

SMOKE DAMPER W/SMOKE DETECTOR AND ACCESS DOOR

COMBINATION FIRE/SMOKE DAMPER W/SMOKE DETECTOR

AND ACCESS DOOR

MOTORIZED CONTROL DAMPER W/ACCESS DOOR

MANUAL VOLUME DAMPER

BD

FD

MD

RADIATION DAMPERRD

AUTOMATIC VOLUME DAMPER (PRESSURE INDEPENDENT)AVD

SD

FSD

GENERAL ABBREVIATIONS

ACCESS DOOR

ADJUSTABLE

ABOVE FINISHED FLOOR

ALTERNATE

AUTHORITY HAVING JURISDICTION

ACCESS PANEL

CONVECTOR

AIR PRESSURE DROP

AVERAGE WATER TEMPERATURE

BUILDING AUTOMATION SYSTEM

BYPASS FEEDER

BREAK HORSEPOWER

BUILDING MANAGEMENT SYSTEM

BRITISH THERMAL UNIT

BTU / HOUR

BOTTOM OF DUCT

BOTTOM OF PIPE

CEILING RADIATION DAMPER

CAPACITY

COEFFICIENT OF PERFORMANCE

CHILLED WATER SUPPLY

CHILLED WATER RETURN

CUBIC FEET PER MINUTE

CUBIC FEET

DECIBELS

DRY BULB TEMPERATURE

DIRECT DIGITAL CONTROL

DIAMETER

DOWN

DIRECT EXPANSION

EXHAUST AIR

ENTERING AIR TEMPERATURE (DRY BULB)

ENTERING DRY BULB

ENERGY EFFICIENCY RATIO

ELECTRICAL

EXTERNAL STATIC PRESSURE

ENTERING WET BULB

ENTERING WATER TEMPERATURE

DEGREES FAHRENHEIT

FIRE DAMPER

FEET

FEET WATER GAUGE

FULL LOAD AMPS

FEET PER MINUTE

COMBINATION FIRE SMOKE DAMPER

GALLONS PER HOUR

GALLONS PER MINUTE

GRILLE, REGISTER, DIFFUSER

HEAD

HORSEPOWER

HEATING SEASON PERFORMANCE FACTOR

HERTZ

HEATING, VENTILATION AND AIR CONDITIONING

HOT WATER RETURN

HOT WATER SUPPLY

INCHES

INCHES WATER GAUGE

INTEGRATED PART LOAD VALUE

KILOWATTS

LOUVER

LEAVING AIR TEMPERATURE

LEAVING DRY BULB

LEAVING WET BULB

LEAVING WATER TEMPERATURE

MAXIMUM

MECHANICAL

THOUSANDS OF BTU / HOUR

MINIMUM CIRCUIT AMPACITY

MINIMUM

NOT IN CONTRACT

NOT TO SCALE

OUTSIDE AIR TEMPERATURE

OUTER DIAMETER

OPEN ENDED DUCT

PUMP

PHASE

PLUMBING

PRESSURE REDUCING VALVE

POUNDS PER SQUARE INCH GAUGE

QUANTITY

RETURN AIR

REVOLUTIONS PER MINUTE

REDUCED PRESSURE ZONE BACKFLOW PREVENTER

RADON VENT

SUPPLY AIR

SEASONAL ENERGY EFFICIENCY RATIO

SIGHT GLASS

STATIC PRESSURE

STATIC PRESSURE DROP

STAINLESS STEEL

SATURATED SUCTION PRESSURE

SQUARE FEET

TEMPERATURE

TOTAL STATIC PRESSURE

THERMOSTAT

TYPICAL

UNLESS OTHERWISE INDICATED

VARIABLE AIR VOLUME

VARIABLE FREQUENCY DRIVE

VENT THRU ROOF

WITH

WITHOUT

WET BULB

WATER COLUMN

WATER GAUGE

WIRE MESH SCREEN

WATER PRESSURE DROP

AD

ADJ

AFF

ALT

AHJ

AP

CNV

APD

AWT

BAS

BF

BHP

BMS

BTU

BTUH

BOD

BOP

CRD

CAP

COP

CHWS

CHWR

CFM

CUFT

dB

DB

DDC

DIA

DN

DX

EA

EAT

EDB

EER

ELEC

ESP

EWB

EWT

°F

FD

FT

FT WG

FLA

FPM

FSD

GPH

GPM

GRD

HD

HP

HSPF

HZ

HVAC

HWR

HWS

IN

IN WG

IPLV

KW

L

LAT

LDB

LWB

LWT

MAX

MECH

MBH

MCA

MIN

NIC

NTS

OAT

OD

OED

P

PH

PLBG

PRV

PSIG

QTY

RA

RPM

RPZ

RV

SA

SEER

SG

SP

SPD

SS

SST

SQFT / SF

TEMP

TSP

TSTAT

TYP

UOI

VAV

VFD

VTR

W W/O

WB

WC

WG

WMS

WPD

GENERAL NOTES

1. GENERAL NOTES, SYMBOLS, AND DETAILS ARE APPLICABLE TO DRAWINGS WITHIN DIVISION 23.

2. PROVIDE ALL MATERIALS AND EQUIPMENT AND PERFORM ALL LABOR REQUIRED TO INSTALL

COMPLETE AND OPERABLE MECHANICAL SYSTEMS AS INDICATED ON THE DRAWINGS, AS

SPECIFIED, AND AS REQUIRED BY CODES.

3. DRAWINGS ARE DIAGRAMMATIC AND ARE INTENDED TO INDICATE CAPACITY, SIZE,

APPROXIMATE LOCATION AND GENERAL ARRANGEMENT. COORDINATE LOCATIONS OF

SYSTEMS AND COMPONENTS.

4. COORDINATE ROOF AND WALL PENETRATIONS WITH WORK OF OTHER SECTIONS AND WITH

FLASHING REQUIREMENTS. COORDINATE SLAB PENETRATIONS WITH WORK OF OTHER

SECTIONS.

5. RUN DUCTS AND PIPING CONCEALED UNLESS SPECIFIED OTHERWISE NOTED.

6. INSTALL SENSORS (THERMOSTATS) AT LOCATIONS SHOWN ON PLANS OR AS DIRECTED BY

ARCHITECT. MOUNTING HEIGHT AFF SHALL COMPLY WITH ADA AND SHALL BE MOUNTED

LEVEL WITH ADJACENT SWITCHES (IE LIGHT SWITCHES).

7. COORDINATE WORK OF THIS SECTION WITH THAT OF OTHER SECTIONS AND WITH ALL

TRADES INVOLVED. PROVIDE OFFSETS IN PIPING AND DUCTS (INCLUDING DIVIDED DUCTS)

AND TRANSITIONS AROUND OBSTRUCTIONS.

8. NOT ALL ACCESS DOORS HAVE BEEN SHOWN ON THE PLANS. PROVIDE ACCESS PANELS

THROUGH BUILDING ASSEMBLIES TO SERVICE AND MAINTAIN EQUIPMENT UNLESS SUCH

EQUIPMENT IS INSTALLED IN EXPOSED LOCATIONS OR ABOVE LAY-IN CEILINGS. COORDINATE

THE LOCATION OF ACCESS DOORS AND PANELS AND VERIFY THE QUANTITY, SIZE, AND

LOCATIONS AFTER THE SYSTEMS AND EQUIPMENT REQUIRING ACCESS HAVE BEEN

INSTALLED AND PRIOR TO THE CLOSURE OF THE AFFECTED CEILINGS AND BUILDING

ASSEMBLIES. SUBMIT ACCESS PANEL LOCATIONS FOR REVIEW.

9. AT SUBSTANTIAL COMPLETION, THE FOLLOWING ITEMS, NEW OR EXISTING, SHALL BE FULLY

AND REASONABLY ACCESSIBLE: HVAC CONTROL BOXES, JUNCTION BOXES, VALVES, DDC

CONTROL BOXES, ELECTRICAL PANELS, FILTERS, BELTS, WATER COILS, DISCONNECT

SWITCHES AND ELEMENTS OF EQUIPMENT REQUIRING MAINTENANCE. "FULLY AND

REASONABLY ACCESSIBLE" SHALL BE DEFINED AS NATIONAL ELECTRIC CODE REQUIRED

CLEARANCE FOR POWERED EQUIPMENT AND CAPABLE OF BEING ACCESSED OR SERVICED

WITHOUT REMOVING, MODIFYING OR DISTORTING OTHER COMPONENTS OF THE WORK.

PROVIDE MANUFACTURER'S RECOMMENDED CLEARANCE FOR ALL EQUIPMENT.

10. SUPPORT EQUIPMENT AND DUCTWORK FROM BUILDING STRUCTURE OR WITH STEEL

SUPPORTS AND PLATFORMS AS REQUIRED. PROVIDE VIBRATION ISOLATION FOR ROTATING

EQUIPMENT, DUCTWORK, AND PIPING IN ACCORDANCE WITH THE SPECIFICATIONS.

11. ROOF CURB AND RAIL HEIGHTS INDICATED ARE THE DIMENSIONS BETWEEN THE ROOF

SURFACE AND THE TOPS OF THE CURBS AND RAILS. WHERE THE ROOF IS PITCHED,

CONSTRUCT CURBS AND RAILS SUCH THAT THE BOTTOM PITCHES WITH THE ROOF AND THE

TOP IS LEVEL.

12. CONTROL WIRING METHODS SHALL COMPLY WITH NEC, AND DIVISION 26 SPECIFICATIONS.

13. VERIFY EQUIPMENT CONNECTIONS WITH MANUFACTURER'S DRAWINGS. VERIFY AND

PROVIDE FITTINGS TO TRANSITION TO FURNISHED EQUIPMENT. FIELD VERIFY AND

COORDINATE DIMENSIONS BEFORE FABRICATION.

14. PERFORM PRESSURE AND LEAKAGE TESTS BEFORE INSULATING DUCTWORK AND PIPING

15. MAINTAIN 6’-8” CLEARANCE TO THE UNDERSIDE OF PIPES, DUCTS, CONDUITS, SUSPENDED

EQUIPMENT, ETC., THROUGHOUT ROUTES IN MECHANICAL ROOMS. MAINTAIN 3’-0” WIDE

MEANS OF EGRESS IN MECHANICAL ROOMS.

16. MISCELLANEOUS STEEL REQUIRED TO ENSURE PROPER INSTALLATION AND, AS SHOWN IN

THE DETAILS FOR PIPING, DUCTWORK, AND EQUIPMENT, SHALL BE FURNISHED BY THE

MECHANICAL CONTRACTOR.

17. INSTALL UNITS WITH CLEARANCE FOR SERVICE AS REQUIRED BY THE MANUFACTURER.

AIR SYSTEM GENERAL NOTES

1. REFER TO SPECIFICATIONS FOR DUCTWORK CONSTRUCTION CLASSES, SEAL, AND

LEAKAGE CLASSES.

2. EXTERIOR LOUVERS ARE INDICATED FOR LOCATION ONLY. DETAILED DESCRIPTIONS ARE

PROVIDED IN ARCHITECTURAL DRAWINGS AND SPECIFICATIONS.

3. PROVIDE UL FIRE DAMPERS OR SMOKE/FIRE DAMPERS AND ASSOCIATED ACCESS PANELS

WHERE SHOWN ON DRAWINGS IN COMPLIANCE WITH NFPA 90A. FOR DUCTS THAT

PENETRATE FIRE-RATED WALLS, AND FLOORS.

4. REFER TO REFLECTED CEILING PLANS FOR LOCATIONS OF AIR TERMINAL DEVICES.

5. INTERNAL AIR FLOW DIMENSIONS ARE SHOWN FOR DUCTS. INCREASE SHEETMETAL SIZE

FOR LINER IF APPLICABLE.

6. DIFFUSER SIZES SHOWN ARE NECK SIZES; REGISTER AND GRILLE SIZE ARE NOMINAL.

ROUND RUN OUTS TO DIFFUSERS SHALL BE THE SAME NOMINAL SIZE AS THE SCHEDULED

NECK SIZE, UNLESS NOTED AS LARGER. DUCT TRANSITIONS SHALL BE PROVIDED AS

NECESSARY AT INLET TO DIFFUSER.

7. PROVIDE FLEXIBLE CONNECTIONS ON DUCTS CONNECTING TO FANS AND AIR HANDLING

UNITS.

8. THE INSIDE OF DUCTWORK VISIBLE THROUGH A GRILLE OR DIFFUSER SHALL BE PAINTED

FLAT BLACK.

9. OPEN ENDED DUCTS SHALL BE PROVIDED WITH A 1/4"x1/4" MESH ALUMINUM OR

GALVANIZED SCREEN (80% FREE AREA MINIMUM).

10. ELBOWS IN DUCT SYSTEMS SHALL BE FULL RADIUS (CENTERLINE RADIUS = 1.5 DUCT

WIDTH) WHERE SPACE PERMITS. WHERE LIMITED CLEARANCE OCCURS, PROVIDE SHORT

RADIUS ELBOW WITH FULL LENGTH SPLITTER VANES PER SMACNA OR MITERED ELBOW

WITH TURNING VANES PER SMACNA.

11. NOT ALL MANUAL DAMPERS ARE SHOWN ON THE DRAWINGS. PROVIDE MANUAL

ADJUSTABLE DAMPERS ON EACH LOW-PRESSURE SUPPLY, RETURN, AND EXHAUST DUCT

TAKE-OFF, AND AT TAKE-OFFS TO REGISTERS, GRILLES, DIFFUSERS, AND OED; AS

REQUIRED FOR PROPER BALANCE OF SYSTEM. PROVIDE CABLE-OPERATED DAMPERS

WHERE MANUAL DAMPER IS INACCESSIBLE. EACH DAMPER IN DUCTS 12" AND MORE SHALL

BE OPPOSED BLADE TYPE.

12. WHERE DUCTS PENETRATE WALLS WITH SOUND ISOLATION PERFORMANCE RATINGS,

PROVIDE DUCT SLEEVE SIZED TO PROVIDE 1/4" GAP BETWEEN THE SLEEVE AND DUCT. FILL

THE GAP WITH FIBEROUS MATERIAL AND SEAL AIRTIGHT WITH NON-HARDENING ACOUSTIC

SEALANT

13. HVAC EQUIPMENT AND DUCTS SHALL NOT BE USED FOR TEMPORARY HEATING, COOLING

OR VENTILATION.

14. PROVIDE FLEXIBLE CONNECTIONS AT ALL LOCATIONS WHERE DUCTS CROSS EXPANSION

OR SEISMIC JOINTS. COORDINATE WITH ARCHITECTURAL DRAWINGS.

DEMOLITION NOTES

DEMOLITION NOTES

1. SITE VISIT: THIS PROJECT INVOLVES CONSTRUCTION INSIDE AN EXISTING STRUCTURE.

BEFORE SUBMITTING BID, VISIT AND CAREFULLY EXAMINE SITE TO IDENTIFY EXISTING

CONDITIONS AND DIFFICULTIES THAT WILL AFFECT WORK OF THIS SECTION. NO EXTRA

PAYMENT WILL BE ALLOWED FOR ADDITIONAL WORK CAUSED BY UNFAMILIARITY WITH

SITE CONDITIONS THAT ARE VISIBLE OR READILY CONSTRUED BY EXPERIENCED

OBSERVER.

2. PREPARATORY WORK: BEFORE STARTING WORK IN A PARTICULAR AREA OF THE

PROJECT, VISIT SITE AND EXAMINE CONDITIONS UNDER WHICH WORK MUST BE

PERFORMED INCLUDING PREPARATORY WORK DONE UNDER OTHER SECTIONS OR

CONTRACTS BY OWNER. REPORT CONDITIONS THAT MIGHT AFFECT WORK ADVERSELY IN

WRITING TO ARCHITECT AND OWNER. DO NOT PROCEED WITH WORK UNTIL DEFECTS

HAVE BEEN CORRECTED AND CONDITIONS ARE SATISFACTORY. COMMENCEMENT OF

WORK SHALL BE CONSTRUED AS COMPLETE ACCEPTANCE OF EXISTING CONDITIONS AND

PREPARATORY WORK.

3. PHASING: DEMOLITION WORK SHALL COMPLY WITH THE PHASING REQUIREMENTS OF THE

PROJECT AND BE COORDINATED WITH THE OWNER, ARCHITECT, CM AND ENGINEER. NO

REMOVALS SHALL BE IMPLEMENTED WITHOUT A THOROUGH UNDERSTANDING OF THE

PHASING REQUIREMENTS.

4. ABANDONING OF DUCTWORK, PIPING OR EQUIPMENT IN PLACE WITHIN SCOPE AREA IS

PROHIBITED.

5. PROVIDE 2 WEEKS NOTICE TO OWNER FOR SHUT DOWN OF ANY SERVICES AND/OR

SYSTEMS.

6. COORDINATE EXISTING EQUIPMENT AND MATERIALS THAT SHALL REMAIN THE PROPERTY

OF THE OWNER. ITEMS OF VALUE WHICH ARE NOT DIRECTED TO BE RETURNED TO THE

OWNER, SHALL BECOME THE PROPERTY OF THE CONTRACTOR AND SHALL BE REMOVED

FROM SITE AND LEGALLY DISPOSED OF. STORAGE OR SALE OF ITEMS ON THE PROJECT

SITE IS PROHIBITED.

7. PROTECTION: ENSURE THE SAFE PASSAGE OF PERSONS IN AND AROUND THE BUILDING

DURING DEMOLITION. PREVENT INJURY TO PERSONS AND DAMAGE TO PROPERTY.

PROVIDE ADEQUATE SHORING AND BRACING TO PREVENT COLLAPSE. IMMEDIATELY

REPAIR DAMAGED PROPERTY TO THE CONDITION BEFORE BEING DAMAGED. TAKE

EFFECTIVE MEASURES TO PREVENT WINDBLOWN DUST.

8. UTILITIES: MAINTAIN ALL UTILITIES EXCEPT THOSE REQUIRING REMOVAL OR RELOCATION.

KEEP UTILITIES IN SERVICE AND PROTECT FROM DAMAGE. DO NOT INTERRUPT UTILITIES

SERVING OCCUPIED AREAS WITHOUT FIRST OBTAINING PERMISSION FROM THE OWNER IN

WRITING. PROVIDE TEMPORARY SERVICES AS REQUIRED.

9. INFORMATION CONTAINED ON THESE DRAWINGS WAS OBTAINED FROM ARCHIVED

DRAWINGS AND SITE VISITS. DRAWINGS ARE DIAGRAMMATIC ONLY AND REFLECT OVERALL

SYSTEM REMOVAL. NOT EVERY ITEM OR COMPONENT OF A SYSTEM IS SHOWN. PROVIDE

COMPLETE REMOVAL OF ASSOCIATED ANCILLARY PIPES, HANGERS, VALVES AND

ACCESSORIES SERVING SYSTEM SHOWN.

10. DEMOLITION WORK SHALL COMPLY WITH OSHA, EPA AND APPLICABLE STATE AND LOCAL

CODES. COMPLY WITH HAULING AND DISPOSAL REGULATIONS.

11. REFER TO SPECIFICATIONS FOR ADDITIONAL DEMOLITION REQUIREMENTS AND

PROCEDURES.

FIRESTOPPING GENERAL NOTES

1. PROVIDE FIRE STOPPING AND SMOKE BARRIER SEALING OF PENETRATIONS THROUGH FIRE

OR SMOKE WALLS, BARRIERS AND PARTITIONS AS REQUIRED TO MAINTAIN RATING. REFER

TO ARCHITECTURAL FLOOR PLANS AND CODE SHEETS FOR WALL RATINGS. REFER TO

SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.

CONTROLS LEGEND COMPLETE

DIGITAL INPUT

DIGITAL OUTPUT

ANALOG INPUT

ANALOG OUTPUT

DO

DI

AO

AI

T

PLAN

SYMBOL DESCRIPTION

DIAGRAM

SYMBOL

BAS TEMPERATURE SENSORTE

ACTUATOR LEGEND

SYMBOL DESCRIPTION

DAMPER WITH TWO POSITION ACTUATOR

POSITION SWITCHZS

CURRENT TRANSMITTERIT

Scale:

Project Number:

Date:

Drawn By:

Checked By:

CONSTRUCTION SET

Drawing Name:

Project Name:

© 2026 Portsmouth Architects

4 Market Street

Portsmouth, New Hampshire

603.430.0274

NTS

/2 /2

:2

:3

A M

C U s e rs \n h ill

\D o c u m e n ts

\R

-2

.0

-M

E P

C e n tr a l- U

N H

E le v a to r

M a c h in e R o o m

D

IM

O N

D n h ill R

Z E

J .r v t

M000

261202.00

10/30/2026

NGH

PTC

U N

H E

L E

V A

T O

R R

E N

O V

A T

IO

N

D

IM

O N

D L

IB

R

A R

Y

M A

IN

S

T R

E

T

D U

R H

A M

N

H

U N

IV

E

R S

IT

Y

O F

N E

W H

A M

P S

H

IR

E

MECHANICAL

ABBREVIATIONS, NOTES

AND SYMBOLS

UNH ELEVATOR

RENOVATION DIMOND

LIBRARY

261202.00

No. Description Date

1 1.7

DEMOLISH EXISTING 31x12

TRANSFER DUCT, GRILLES, AND

FIRE DAMPER.

EXISTING FIRE DAMPER TO REMAIN. CLEAR

OBSTRUCTIONS IN EXISTING FIRE DAMPER.

REPLACE EXISTING BIRD SCREEN.

EF-1

DEMOLISH EXISTING HOISTWAY

GOOSENECK, ASSOCIATED DAMPERS

AND CONTROLS. EXISTING ROOF CURB

TO REMAIN.

T

FD

FD

NEW ROOF MOUNTED EXHAUST FAN

MOUNTED ON EXISTING CURB. PROVIDE

CURB ADAPTER AS REQUIRED.

18x18 DOOR TRANSFER

GRILLE WITH INTEGRAL FIRE

DAMPER BY ARCHITECT

MECH. ROOM

ELEVATOR

HOISTWAY

105ESA

SEQUENCE OF OPERATION

GENERAL

1. PROVIDE BAS CONTROLS THOUGH THE CAMPUS BAS.

2. WHERE ADJUSTABLE TEMPERATURE SETPOINTS ARE INDICATED, THE

TEMPERATURE RANGE SHALL BE CAPABLE OF SETPOINTS BETWEEN

50°F AND 100 °F.

3. ALL ALARMS SHALL HAVE A 5 MIN. (ADJ.) DELAY BEFORE ACTIVATING

AT THE BAS.

SAFETIES AND ALARMS

1. IF THE FAN IS COMMANDED ON AND IT DOES NOT ACTIVATE, AN

ALARM SHALL BE GENERATED THROUGH THE BAS.

2. IF THE DAMPER IS COMMANDED OPEN AND IT DOES NOT PROVE

OPEN:

A. AN ALARM SHALL BE GENERATED THROUGH THE BAS.

B. THE FAN SHALL NOT ACTIVATE.

3. IF THE DAMPER IS COMMANDED CLOSED AND IT DOES NOT PROVE

CLOSED, AN ALARM SHALL BE GENERATED THROUGH THE BAS.

4. IF THE SPACE TEMPERATURE SENSOR FAILS OR LOSES

COMMUNICATION FOR 5 MIN (ADJ.)

OPERATION

1. IF THE SPACE TEMPERATURE RISES ABOVE SETPOINT 85°F (ADJ.):

A. THE BAS SHALL FULLY OPEN THE DAMPER.

B. ONCE THE DAMPER IS PROVEN OPEN, THE BAS SHALL ACTIVATE

THE FAN.

1. IF THE SPACE TEMPERATURE DROPS BELOW THE SETPONT 80°F

(ADJ.):

A. THE BAS SHALL DEACTIVATE THE FAN.

B. THE BAS SHALL FULLY CLOSE THE DAMPER.

FIRE ALARM SHUTDOWN

1. UPON THE BUILDING FIRE ALARM SYSTEM BEING ACTIVATED, THE

FAN SHALL SHUT OFF AND THE DAMPER SHALL CLOSE.

2. NOTE: FIRE ALARM SHUTDOWN SHALL BE A HARDWIRED LIFE-SAFETY

FUNCTION PROVIDED BY OTHERS AND NOT THROUGH THE BAS.

BAS

TEMPERATURE

SENSOR

EXH

EXH

TYPICAL FOR: EF-1

TE

DO

AI

DO

ZS

DI

DOIT

ESP

(IN WG)

FAN SCHEDULE

GENERAL

TAG MANUFACTURER MODEL LOCATION SERVICE

WEIGHT

(LBS)

PHYSICAL

CFM

ELECTRICAL REMARKS

TYPE

1. EC MOTOR, DIRECT DRIVE, DOWNBLAST ROOF FAN

MOP RATINGSRPM VOLTAGE FEATURESBHP PHASE INSTALL

REMARKS - TYPE REMARKS - RATINGS REMARKS - FEATURES REMARKS - INSTALL

1. AMCA CERTIFIED 1. FAN MOUNTED VARI-GREEN DIAL FOR BALANCING

2. ROOF CURB WITH INTEGRAL MOTORIZED DAMPER

1. SEE DETAIL

PERFORMANCE

EF-1 GREENHECK G-100HP-VG ROOF

MECHANICAL

ROOM

59 550 1.0 1,922 0.22 15 115 1 1 1 1,2 1

DRIVE

DIRECT

ACOUSTICAL DATA

INLET SONES

11.8

MCA

8.2

ELEVATOR

MACHINE ROOM ELEVATOR

EXISTING COUNTER FLASHING

EXISTING ROOF

ROOFING

EXISTING ROOF CURB AND

FLASHING

CURB ADAPTER

SECURE ADAPTER CURB TO EXISTING

ROOF CURB PER MANUFACTURERS

INSTRUCTIONS

SECURE FAN TO ADAPTER CURB PER

MANUFACTURERS INSTRUCTIONS

MOTORIZED DAMPER

Scale:

Project Number:

Date:

Drawn By:

Checked By:

CONSTRUCTION SET

Drawing Name:

Project Name:

© 2026 Portsmouth Architects

4 Market Street

Portsmouth, New Hampshire

603.430.0274

As indicated

/2 /2

:2

:3

A M

C U s e rs \n h ill

\D o c u m e n ts

\R

-2

.0

-M

E P

C e n tr a l- U

N H

E le v a to r

M a c h in e R o o m

D

IM

O N

D n h ill R

Z E

J .r v t

M101

261202.00

10/30/2026

NGH

PTC

U N

H E

L E

V A

T O

R R

E N

O V

A T

IO

N

D

IM

O N

D L

IB

R

A R

Y

M A

IN

S

T R

E

R H

A M

N

H

U N

IV

E

R S

IT

Y

O F

N E

W H

A M

P S

H

IR

E

MECHANICAL

DUCTWORK FLOOR PLAN

UNH ELEVATOR

RENOVATION DIMOND

LIBRARY

261202.00

1/4" = 1'-0"

MECHANICAL DUCTWORK - ELEVATOR

NTS

FANS - EXHAUST

1" = 20'-0"

MECHANICAL KEY PLAN - DIMOND LIBRARY - FIRST FLOOR

NTS

ROOF MOUNTED FAN DETAIL

23 00 00 - GENERAL

A. THESE SPECIFICATIONS ARE APPLICABLE TO ALL MECHANICAL DRAWINGS UNLESS NOTED

OTHERWISE. REVIEW THE ARCHITECTURAL, STRUCTURAL, ELECTRICAL, PLUMBING DRAWINGS

FOR NOTES, DIMENSIONS, ETC., AND COORDINATE WITH OTHER TRADES INVOLVED.

B. DESCRIPTION

1. THIS PROJECT COMPRISES ALTERATIONS AND RENOVATIONS TO THE EXISTING BUILDING.

THE EXISTING BUILDING IS CURRENTLY OCCUPIED AND THE PROJECT SHALL PROCEED IN A

MANNER THAT MINIMIZES ANY INCONVENIENCE TO THE BUILDING OCCUPANTS.

2. SCOPE OF WORK CONSISTS OF INSTALLATION OF MATERIALS TO BE FURNISHED UNDER THE

CONTRACT DOCUMENTS AND WITHOUT LIMITING GENERALITY THEREOF CONSISTS OF

FURNISHING LABOR, MATERIALS, EQUIPMENT, HOISTING, TRANSPORTATION, RIGGING,

STAGING, APPURTENANCES, AND SERVICES NECESSARY AND/OR INCIDENTAL TO PROPERLY

COMPLETE ALL WORK AS SHOWN ON THE DRAWINGS AND DESCRIBED HEREIN.

C. DEFINITIONS: THE FOLLOWING DEFINITIONS APPLY TO THIS CONTRACT

1. FURNISH: THE TERM "FURNISH" MEANS TO "SUPPLY AND DELIVER TO THE PROJECT SITE,

READY FOR UNLOADING, UNPACKING, ASSEMBLY, INSTALLATION, AND SIMILAR OPERATIONS"

2. INSTALL: THE TERM "INSTALL" IS USED TO DESCRIBE OPERATIONS AT PROJECT SITE

INCLUDING THE ACTUAL "UNLOADING, UNPACKING, ASSEMBLY, ERECTION, PLACING,

ANCHORING, APPLYING, WORKING TO DIMENSION, FINISHING, CURING, PROTECTING,

CLEANING, AND SIMILAR OPERATIONS."

3. PROVIDE: THE TERM "PROVIDE" MEANS "TO FURNISH AND INSTALL, COMPLETE AND READY

FOR THE INTENDED USE."

4. REMOVE: THE TERM "REMOVE" MEANS TO DISCONNECT FROM ITS PRESENT POSITION,

REMOVE FROM THE PREMISES AND TO DISPOSE OF IN A LEGAL MANNER."

5. SUBSTITUTIONS: "SUBSTITUTIONS" ARE REQUESTS FOR CHANGES IN PRODUCTS, MATERIALS

AND/OR METHODS OF CONSTRUCTION AS PROPOSED BY THE CONTRACTOR AFTER AWARD

OF THE CONTRACT."

D. DRAWINGS

1. DRAWINGS ARE DIAGRAMMATIC. THE FINAL PLACEMENT OF EQUIPMENT OR DEVICES IN THE

FIELD MAY NOT DIRECTLY CORRESPOND TO THAT WHICH IS SHOWN ON THE DRAWINGS.

THOUGH SOME OFFSETS & TRANSITIONS MAY BE SHOWN IN PIPING & SHEET METAL TO HELP

INDICATE THE PHYSICAL RELATIONSHIP BETWEEN THEM, IT IS NOT THE INTENT OF THE

DRAWINGS TO SHOW ALL PIPING & SHEET METAL OFFSETS & TRANSITIONS REQUIRED. THE

CONTRACTOR SHALL FULLY COORDINATE THE WORK AND PROVIDE ALL MATERIALS,

EQUIPMENT AND LABOR NECESSARY TO COMPLETE THE WORK OUTLINED ON THESE

CONTRACT DOCUMENTS. IF A CONFLICT IN POSITIONING OCCURS THE CONTRACTOR IS TO

NOTIFY THE ENGINEER IMMEDIATELY TO ASCERTAIN WHAT THE INTENT WAS BY THE DESIGN

PROFESSIONAL.

E. CODES AND STANDARDS: WORK SHALL CONFORM TO THE CURRENT EDITIONS OF THE

FOLLOWING:

1. SHEET METAL SMACNA STANDARDS

2. INTERNATIONAL MECHANICAL CODE

3. INTERNATIONAL ENERGY CONSERVATION CODE

4. INTERNATIONAL EXISTING BUILDING CODE

5. ALL OTHER APPLICABLE STATE AND LOCAL CODES AND ORDINANCES, OWNER STANDARDS

AND BASE BUILDING SPECIFICATIONS AND STANDARDS.

F. PERMITS AND FEES:

1. THE CONTRACTOR SHALL GIVE ALL NECESSARY NOTICES, OBTAIN ALL PERMITS; AND PAY

ALL GOVERNMENT AND STATE SALES TAXES AND FEES WHERE APPLICABLE, AND OTHER

COSTS, INCLUDING UTILITY CONNECTIONS OR EXTENSIONS IN CONNECTION WITH THE

WORK, FILE ALL NECESSARY DRAWINGS, PREPARE ALL DOCUMENTS AND OBTAIN ALL

NECESSARY APPROVALS OF ALL GOVERNMENTAL AND STATE DEPARTMENTS HAVING

JURISDICTION, OBTAIN ALL REQUIRED CERTIFICATES OF INSPECTION FOR HIS WORK, AND

DELIVER A COPY TO THE OWNER AND ENGINEER BEFORE REQUEST FOR ACCEPTANCE AND

FINAL PAYMENT FOR THE WORK.

G. EXISTING SYSTEMS AND EQUIPMENT

1. EXISTING TO BE REUSED/RELOCATED EQUIPMENT: REPORT ANY EXISTING EQUIPMENT

DEFICIENCIES TO THE OWNER AND THE ARCHITECT AND/OR ENGINEER.

2. CONNECT WORK TO VARIOUS EXISTING SYSTEMS AS INDICATED ON THE DRAWINGS. WORK

SHALL BE COMPATIBLE WITH THE EXISTING SYSTEM CONDITIONS. ALL WORK SHALL BE

COORDINATED WITH ALL TRADES INVOLVED AS WELL AS WITH EXISTING SYSTEMS, THE

STRUCTURE, AND OTHER OBSTRUCTIONS.

H. SURVEY AND MEASUREMENTS

1. THIS PROJECT INVOLVES CONSTRUCTION INSIDE AN EXISTING STRUCTURE. CONTRACTORS,

BY SUBMITTING A BID, SHALL BE COMPLETELY FAMILIAR WITH THE EXISTING CONDITION OF

THE BUILDING AS IT INFLUENCES THE WORK DESCRIBED. NO COMPENSATION WILL BE

GRANTED FOR ADDITIONAL WORK CAUSED BY UNFAMILIARITY WITH SITE CONDITIONS THAT

ARE VISIBLE OR READILY IDENTIFIED BY EXPERIENCED OBSERVERS.

2. DO NOT SCALE DRAWINGS. SCALE INDICATED ON DRAWINGS IS FOR ESTABLISHING

REFERENCE POINTS ONLY. ACTUAL FIELD CONDITIONS SHALL GOVERN ALL DIMENSIONS.

3. PRIOR TO ORDERING ANY MATERIALS AND EQUIPMENT, THOROUGHLY REVIEW THE SITE

CONDITIONS TO DETERMINE IF ADEQUATE CLEARANCES AND ACCESS IS ALLOWED TO

INSTALL THE COMPONENTS. ORDER EQUIPMENT BROKEN DOWN AS NECESSARY TO ALLOW

FOR PROPER RIGGING THROUGH THE PROJECT AREA. PROVIDE ALL NECESSARY

ALTERATIONS TO THE STRUCTURE OF THE BUILDING AS NECESSARY TO RIG THE EQUIPMENT

IN PLACE.

4. CONTRACTORS SHALL VERIFY, LAYOUT AND BE RESPONSIBLE FOR ALL MEASUREMENTS OF

ALL EXISTING CONDITIONS BEFORE COMMENCING WORK AND SHALL NOTIFY ARCHITECT

AND/OR ENGINEER IF A CONDITION EXISTS THAT PREVENTS THE CONTRACTOR FROM

ACCOMPLISHING THE INTENT OF THE DRAWINGS.

I. SUBMITTALS AND SHOP DRAWINGS

1. SUBMIT FOR REVIEW, ELECTRONIC SHOP DRAWINGS IN SEARCHABLE PDF FORMAT FOR THE

FOLLOWING.

a. SUBMITTAL DATA FOR ALL MATERIAL AND EQUIPMENT. CLEARLY IDENTIFY DEVIATIONS

OF THE SUBMITTED PRODUCTS FROM THE DESIGN.

b. DUCTWORK AND PIPING SHOP DRAWINGS: DRAWN TO ACCURATE SCALE OF 1/4”=1'0”.

HIGHLIGHT, ENCIRCLE, OR OTHERWISE INDICATE DEVIATIONS FROM THE CONTRACT

DOCUMENTS. DO NOT REPRODUCE CONTRACT DOCUMENTS OR COPY STANDARD

INFORMATION AS THE BASIS OF SHOP DRAWINGS. STANDARD INFORMATION PREPARED

WITHOUT SPECIFIC REFERENCE TO THE PROJECT IS NOT CONSIDERED SHOP

DRAWINGS.

c. CONTROLS SHOP DRAWINGS: INCLUDE EQUIPMENT AND SYSTEM CONTROL

SCHEMATICS, SEQUENCES OF OPERATIONS, LOGIC DIAGRAMS AND SYSTEM

COMPONENTS INCLUDING DETAILS OF TIE-IN TO EXISTING BUILDING CONTROL

MANAGEMENT SYSTEM.

2. DO NOT USE SHOP DRAWINGS WITHOUT AN APPROPRIATE FINAL STAMP INDICATING ACTION

TAKEN IN CONNECTION WITH CONSTRUCTION.

3. DO NOT ORDER ANY MATERIALS OR EQUIPMENT PRIOR TO RECEIVING FINAL APPROVED

SUBMITTALS.

4. SCHEDULE AT LEAST TEN WORKING DAYS EXCLUSIVE OF TRANSMITTAL TIME, FOR

SUBMITTAL REVIEW.

J. AS-BUILT DRAWINGS

A. MAINTAIN ONE SET OF PRINTS ON THE SITE AND NOTE ALL CHANGES OR DEVIATIONS FROM

THE ORIGINAL DESIGN THEREON. AT THE COMPLETION OF THE PROJECT, INCORPORATE ALL

CHANGES INTO RECORD AS-BUILT DRAWINGS IN ELECTRONIC FORMAT AND SUBMIT FOR

APPROVAL.

23 31 00 - HVAC DUCTS

A. GENERAL REQUIREMENTS

1. FOR GALVANIZED DUCTWORK, SEAL AIR DUCT JOINTS AND JOINTS BETWEEN FITTINGS AND

DUCTS WITH HARDCAST SEALANT OR APPROVED EQUAL IN ACCORDANCE WITH

MANUFACTURER'S INSTRUCTIONS.

2. DUCTWORK SHALL BE FREE FROM VIBRATION UNDER ALL CONDITIONS OF OPERATION.

3. DIFFUSER & REGISTER LOCATIONS SHALL BE COORDINATED WITH ARCHITECTURAL

REFLECTED CEILING PLANS.

4. DIFFUSER SIZES SHOWN ARE NECK SIZES; REGISTER AND GRILLE SIZES ARE NOMINAL.

5. ALL DUCTS PENETRATING RATED FIRE WALLS SHALL BE PROVIDED WITH FIRE DAMPERS AND

ACCESS DOORS.

6. DUCTWORK SHALL NOT RUN ALONG FULL HEIGHT PARTITIONS.

7. PATCH AND SEAL ALL EXISTING OPENINGS IN DUCTWORK NOT UTILIZED FOR NEW LAYOUT.

8. THE INSIDE OF ALL UNLINED DUCTWORK VISIBLE THROUGH A GRILLE OR DIFFUSER SHALL BE

PAINTED FLAT BLACK.

9. WHEN SECTION OF DUCTWORK IS NOT LABELED FOR SIZE, THE LARGER SIZE INDICATED ON

THE CONNECTED DUCT SHALL PREVAIL. SIZE OF DUCT RUN-OUTS TO DIFFUSER SHALL

EQUAL DIFFUSER NECK SIZE.

10. DUCT BRANCH CONNECTIONS AND TAKE OFFS SHALL BE MADE WITH 45° CONNECTION,

BELLMOUTH OR CONICAL ONLY. SPIN IN COLLARS AND STRAIGHT TAPS SHALL NOT BE USED.

11. ELBOWS AND BENDS FOR RECTANGULAR DUCTS SHALL HAVE CENTER LINE RADIUS OF 1.5

TIMES DUCT WIDTH WHEREVER POSSIBLE. WHERE CENTERLINE RADIUS IS LESS THAN 1.5

TIMES DUCT WITH, ELBOWS SHALL BE RADIUS THROAT WITH RADIUS HEEL AND FULL-

LENGTH SPLITTER VANES.

12. NO PIPE, CONDUIT, HANGER, ARCHITECTURAL ELEMENT NOR STRUCTURAL MEMBER SHALL

PASS THROUGH DUCT WITHOUT…