Delta College M-Wing 3D Printer Room IFB-10.28.2025.pdf
PDF 2 MB Posted
- Solicitation number
- 2024065
- Issued by
- Arenac County, Michigan
About this file
This document is a set of engineering and construction documents for Delta College's M-Wing and 3D Printer Room HVAC Renovation project, prepared by MacMillan Associates Consulting Engineers located in Bay City, Michigan. The project involves upgrading the HVAC system in the M-Wing, with bid documents issued on October 28, 2025. The scope includes mechanical demolition, installation of a new fan coil unit (FCU-M101), roof-mounted exhaust fan (EF-M101), modifications to existing ductwork, chilled water piping connections, and integration with the existing building management system. The work is specifically focused on Room M101 and surrounding areas, with detailed plans for airflow modifications, equipment placement, and system controls.
The project documents indicate that all new HVAC systems will be connected to the owner's existing Trane Building Management System, with all components, programs, controllers, and graphics to be furnished, installed, and programmed by Trane. The renovation will involve precise modifications to maintain proper ventilation and airflow, including installing a new 1200 CFM fan coil unit, connecting to existing chilled water piping, and ensuring proper exhaust and return air management. The electrical specifications outline requirements for power connections, grounding, equipment wiring, and installation standards, with specific attention to maintaining existing infrastructure while implementing the necessary upgrades.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Pricing Sheet.docx | DOCX document | |
| General .pdf | ||
| Insurance Requirements.pdf | ||
| Proposal form.doc | DOC document | |
| Addendum-Q_A (1).docx | DOCX document | |
| Certifications.docx | DOCX document | |
| Introduction Page.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DRAWING INDEX
COVER SHEET
M1.1 FIRST FLOOR MECHANICAL DEMOLITION PLAN
M2.1 FIRST FLOOR HVAC PLAN
M3.1 MECHANICAL SCHEDULES AND DETAILS
M4.1 MECHANICAL SPECIFICATIONS
E2.1 ELECTRICAL PLAN, SPECIFICATIONS AND PANEL SCHEDULE
LOCATION MAP
CODE INFORMATION
APPLICABLE CODES
- 2023 NATIONAL ELECTRICAL CODE
- 2021 MICHIGAN PLUMBING CODE
- 2021 MICHIGAN MECHANICAL CODE
- 2021 MICHIGAN ENERGY CODE
OCTOBER 28, 2025 (ISSUED FOR BIDS)
ENGINEER
MacMILLAN ASSOCIATES
714 E. MIDLAND ST.
BAY CITY MI, 48706
(989) 894-4300
Delta College
M-WING 3D PRINTER ROOM HVAC SYSTEM UPGRADE
KEY MAP - MAIN CAMPUS
NOT TO SCALE
DELTA ROAD
HOTCHKISS ROAD
MACKINAW DRIVE
M
AC
KI
N
AW
R
O
AD
SOUTH CAMPUS DRIVE
FO
U
R M
IL
E
R O
AD
NORTH CAMPUS DRIVE
HOTCHKISS DRIVE
DELTA DRIVE
WEST CAMPUS DRIVE
EAST CAMPUS DRIVE
SOUTH
PARKING LOT
EAST
PARKING LOT
EX CHALET BUILDING
EX TRANSMITTER BUILDING
TENNIS COURTS
WEST ANNEX
PARKING LOT
WEST
PARKING LOT
S-WING
(FINE ARTS)
A-WING
(LEARNING CENTER)
AREA OF WORK
SAN
SAN. MH
RIM 599.49
INV. 8" S. 584.19
INV. 8" W. 584.49
SA
N
POWER
HOUSE
W
W W
W
SA
N
N
1961 Delta Rd, University Center MI 48710
PARTIAL FIRST FLOOR - MECHANICAL DEMOLITION PLANN 1/8"=1'-0"
PARTIAL ENLARGED FIRST FLOOR - MECHANICAL DEMOLITION PLANN 1/4"=1'-0"
Since 1963
(989) 894-4300
714 East Midland Street Bay City, Michigan 48706 www.macmillanassociates.com
CONSULTING ENGINEERS
MacMILLAN ASSOCIATES
REV. DESCRIPTION BY DATE
0.5"0.0" 1.0" 2.0"1.5"2/ 3/
1:
A
M C
AL
EB
W
EN
D
LI
N G
(C W
EN
D
LI
N
G
M
AC
M
IL
LA
N
AS
SO
C
IA
TE
S.
C O
M
F:
\2
3- D
EL
TA
\2
4-
M
-W
IN
G A
N D
D
P R
IN
TE
R R
O O
M H
VA
C
S
TU
D Y\
-2
7- M
1.
- M
EC
H
AN
IC
AL
D
EM
O
LI
TI
O
N P
LA
N
PROJECT DESCRIPTION
SHEET DESCRIPTION
AL
L
RI
GH
TS
R
ES
ER
VE
D.
C
OP
YR
IG
HT
M ac M
IL
LA
N
AS
SO
CI
AT
ES
, I
NC
SHEET No.
JOB No.DRAWN BY
DESIGNED BY
APPROVED BY
ISSUED FOR BIDS 10.28.2025
DELTA COLLEGE
M-WING AND 3D PRINTER ROOM
HVAC RENOVATION
FIRST FLOOR - MECHANICAL
DEMOLITION PLAN
M1.1
2024-2307CHW
DSF
GRS
KEY PLANN
EX AHU-29
EX RF-29
KEYED NOTES
EXISTING DUCTWORK TO REMAIN (TYP.).
EXISTING DUCTWORK TO BE REMOVED (TYP.).
EXISTING GRILLE/DIFFUSER TO BE REMOVED.
EXISTING MECHANICAL EQUIPMENT IN
MECHANICAL ROOM TO REMAIN.
EXISTING GRILLE/DIFFUSER TO REMAIN.
EXISTING ROOF CURB, ON ROOF ABOVE, TO
BE REMOVED. RE-USE ROOF OPENING FOR
NEW EXHAUST FAN AND NEW DUCT ABOVE
CEILING. EXISTING EXHAUST DUCT DOWN
THROUGH ROOF WAS ABANDONED AND
REMAINED OPEN ABOVE CEILING.
EXISTING VAV BOX AND ASSOCIATED
THERMOSTAT TO REMAIN.
EXISTING CHILLED WATER PIPING TO REMAIN.
EXISTING FLOOR DRAIN TO REMAIN.
CAP EXISTING DUCTWORK AT LOCATION
WHERE BRANCH DUCT IS REMOVED.
EXISTING FIRE PROTECTION SPRINKLER HEAD
TO BE RE-WORKED TO ALLOW INSTALLATION
OF NEW FAN COIL UNIT. REVISE ASSOCIATED
PIPING AS NECESSARY TO INSTALL NEW UNIT.
EXISTING CEILING IS A LAY-IN CEILING. ALL
EXISTING CEILING TILES SHALL BE REMOVED
AND STORED TEMPORARILY WITH INTENT TO
BE RE-INSTALLED AFTER COMPLETION OF
NEW WORK. REMOVE AND RE-INSTALL
CEILING GRID AS NECESSARY TO INSTALL
NEW MECHANICAL. EXISTING CEILING GRID
MAIN RUNNERS SHALL REMAIN. AN
ALLOWANCE SHALL BE INCLUDED TO FURNISH
(6) NEW CEILING TILES, BASED ON POTENTIAL
DAMAGE.
GENERAL NOTES
1. THE INTENT OF THIS DRAWING IS TO
REMOVE ALL MATERIALS AND EQUIPMENT
WITH A DASHED AND DARKER LINE TYPE.
2. PATCH OPENINGS ON DUCTWORK MAINS
WHERE BRANCH DUCTS ARE REMOVED.
3. CONTRACTOR SHALL FIELD VERIFY ALL
MATERIALS AND EQUIPMENT BEFORE
STARTING WORK.
4. COORDINATE DEMOLITION WORK WITH
NEW WORK, ESPECIALLY IN REGARDS TO
NEW CONNECTIONS.
5. REMOVAL OF DUCTWORK AND PIPING
SHALL INCLUDE ALL FITTINGS,
INSULATION, SUPPORTS, ETC.
5 5
5 5
5 5 5
REFER TO ENLARGED
PLAN ON THIS SHEET
EX AHU-29
EX RF-29
T
6 6
AREA OF WORK
EX. 3"
http://www.macmillanassociates.com
PARTIAL FIRST FLOOR - HVAC PLANN 1/8"=1'-0"
PARTIAL ENLARGED FIRST FLOOR - HVAC PLANN 1/4"=1'-0"
Since 1963
(989) 894-4300
714 East Midland Street Bay City, Michigan 48706 www.macmillanassociates.com
CONSULTING ENGINEERS
MacMILLAN ASSOCIATES
REV. DESCRIPTION BY DATE
0.5"0.0" 1.0" 2.0"1.5"2/ 3/
1:
A
M C
AL
EB
W
EN
D
LI
N G
(C W
EN
D
LI
N
G
M
AC
M
IL
LA
N
AS
SO
C
IA
TE
S.
C O
M
F:
\2
3- D
EL
TA
\2
4-
M
-W
IN
G A
N D
D
P R
IN
TE
R R
O O
M H
VA
C
S
TU
D Y\
-2
7- M
2.
- H
VA
C P
LA
N
PROJECT DESCRIPTION
SHEET DESCRIPTION
AL
L
RI
GH
TS
R
ES
ER
VE
D.
C
OP
YR
IG
HT
M ac M
IL
LA
N
AS
SO
CI
AT
ES
, I
NC
SHEET No.
JOB No.DRAWN BY
DESIGNED BY
APPROVED BY
ISSUED FOR BIDS 10.28.2025
DELTA COLLEGE
M-WING AND 3D PRINTER ROOM
HVAC RENOVATION
FIRST FLOOR - HVAC PLAN
M2.1
2024-2307CHW
DSF
GRS
KEY PLANN
EX AHU-29
EX RF-29
EX AHU-29
EX RF-29
A-600
EF-M101
(ON ROOF ABV.)
12"x12" C-1200
B-600
KEYED NOTES
NEW ROOF MOUNTED EXHAUST FAN SHALL BE
INSTALLED AT LOCATION OF EXISTING CAPPED
ROOF CURB. INSTALL NEW ROOF CURB TO
PROVIDE A MINIMUM 18" HIGH TOTAL CURB
HEIGHT. COORDINATE NEW ROOF WORK WITH
ROOFING CONTRACTOR/MANUFACTURER THAT
HOLDS THE CURRENT WARRANTY. ROOFING
CONTRACTOR HOLDING WARRANTY SHALL
COMPLETE ALL ROOF WORK.
NEW THERMOSTAT/SENSOR WIRED TO NEW
FCU CONTROLLER. REFER TO CONTROLS
INFORMATION ON SCHEDULE SHEET.
EXISTING MECHANICAL EQUIPMENT TO REMAIN.
EXISTING DIFFUSER/GRILLE TO REMAIN.
CONNECT NEW DIFFUSER AND BRANCH DUCT
TO EXISTING SUPPLY AIR DUCTWORK,
DOWNSTREAM OF VAV BOX, ABOVE CEILING.
EXISTING THERMOSTAT/SENSOR TO REMAIN. IF
CONTROLS CONTRACTOR IS ABLE TO USE A
SINGLE NON-ADJUSTABLE SENSOR TO
CONTROL BOTH THE NEW FAN COIL UNIT AND
EXISTING VAV BOX, THEN A SINGLE SENSOR
CAN BE USED.
CONNECT NEW 1" CHWS & CHWR PIPING
SERVING NEW FCU, TO EXISTING CHWS & CHWR
PIPING. INSTALL ISOLATION VALVES IN NEW
PIPING AFTER CONNECTION.
NEW FAN COIL UNIT TO BE INSTALLED HIGH IN
SPACE ABOVE CEILING, TIGHT TO STEEL.
SUPPORT UNIT FROM STEEL JOISTS ABOVE.
REFER TO MANUFACTURER'S INSTALLATION
INSTRUCTIONS.
EXISTING VAV BOX SHALL BE RE-BALANCED TO
MATCH UPDATED AIRFLOW ON THE SINGLE
SUPPLY AIR DIFFUSER SERVED BY VAV BOX.
EXISTING ROOF PENETRATION AND ROOF CURB
SHALL BE UTILIZED TO ACCOMMODATE NEW
12"x12" EXHAUST DUCT AND NEW FAN.
NEW CONDENSATE DRAIN PIPING SHALL ROUTE
FROM NEW FAN COIL UNIT TO EXISTING
SERVICE SINK IN ADJACENT ROOM M102. SLOPE
PIPING FROM UNIT, TO LOCATION AT SERVICE
SINK WHERE PIPING SHALL AIR GAP DISCHARGE
INTO SINK. ROUTE PIPING DOWN TIGHT
AGAINST WALL TO SERVICE SINK.
UTILIZE A FLEXIBLE DUCT CONNECTION
BETWEEN SUPPLY AIR AND RETURN AIR DUCT
AND FAN COIL UNIT.
COORDINATE ROUTING OF NEW CHILLED
WATER PIPING WITH EXISTING DUCTWORK,
NEW DUCTWORK, AND NEW FAN COIL UNIT.
UTILIZE SPACE BETWEEN AND THROUGH STEEL
JOISTS, AS NECESSARY.
SEAL AROUND PIPE PENETRATIONS IN EXISTING
WALL.
CONTRACTOR SHALL HIRE THE SERVICES OF A
LICENSED FIRE PROTECTION CONTRACTOR TO
PROPERLY RELOCATE EXISTING SPRINKLER
HEADS AND ASSOCIATED PIPING, AS
NECESSARY TO AVOID CONFLICTS WITH NEW
FAN COIL UNIT, DUCTWORK, PIPING, ETC. FIELD
VERIFY THE EXACT QUANTITY OF SPRINKLER
HEADS AND PIPING THAT REQUIRE REWORK.
COORDINATE INSTALLATION OF RETURN GRILLE
WITH EXISTING LIGHT. INTENT IS FOR NEW
RETURN GRILLE TO BE LOCATED NEXT TO
EXISTING LIGHT. RETURN DUCT IS TO BE
INSTALLED HIGH IN SPACE ABOVE CEILING. 16"
NECK CONNECTING TO RETURN GRILLE SHALL
ROUTE FROM RETURN DUCT TO NEW RETURN
GRILLE. 16" DUCT MAY NEED TO OFFSET IF
NECESSARY.
GENERAL NOTES
1. ALL DIFFUSER AND GRILLE LOCATIONS SHALL BE
COORDINATED WITH EXISTING CEILING GRID.
2. ALL EXISTING CEILING TILES SHALL BE REMOVED
AND STORED TEMPORARILY WITH INTENT TO BE
RE-INSTALLED AFTER COMPLETION OF NEW
WORK. REMOVE AND RE-INSTALL CEILING GRID AS
NECESSARY TO INSTALL NEW MECHANICAL.
EXISTING CEILING GRID MAIN RUNNERS SHALL
REMAIN. AN ALLOWANCE SHALL BE INCLUDED TO
FURNISH (6) NEW CEILING TILES, BASED ON
POTENTIAL DAMAGE.
3. FURNISH AND INSTALL MANUAL BALANCING
DAMPERS ON ALL SUPPLY AIR, RETURN AIR, AND
EXHAUST BRANCH DUCTWORK, TO ALLOW
BALANCING OF EACH INDIVIDUAL AIR OUTLET.
4. FOR BRANCH DUCTS ROUTED TO DIFFUSERS OR
GRILLES THAT DO NOT SHOW SIZES ON
DRAWINGS, DUCT SIZE SHALL MATCH DIFFUSER
OR GRILLE NECK SIZE NOTED ON DIFFUSER AND
GRILLE SCHEDULE.
5. PROPERLY SLEEVE AND SEAL AROUND ALL
INDOOR AND OUTDOOR WALL/ROOF PIPE
PENETRATIONS.
6. ALL NEW CONTROLS FOR NEW FAN COIL UNIT,
NEW EXHAUST FAN, AND EXISTING VAV BOX SHALL
BE FURNISHED, INSTALLED, AND PROGRAMMED
BY TRANE. ALL CONTROLS SHALL BE INTEGRATED
INTO EXISTING BUILDING MANAGEMENT SYSTEM.
REFER TO SCHEDULE AND DETAIL SHEET FOR
CONTROLS SEQUENCE OF OPERATION AND
DIAGRAMS.
7. INTENT FOR EXISTING VAV BOX IS TO CHANGE
CONTROLS TO FIX DAMPER AND SUPPLY A
CONSTANT VOLUME AIRFLOW. SUPPLY AIR FROM
VAV BOX AND AHU-29 SHALL PROVIDE
VENTILATION AIR AND MAKE-UP AIR FOR NEW
EXHAUST FAN, AS WELL AS ANY HEATING NEEDS
THE SPACE MAY HAVE. THE VAV BOX HEATING
COIL CONTROL VALVE SHALL CONTINUE TO OPEN
AND CLOSE UPON A CALL FOR HEATING.
4 4
4 4
REFER TO ENLARGED
PLAN ON THIS SHEET
4 4 4
T
A-600
T
12"x8"
A-400
CHWR
12"x10" 12"x10"
16"x14"
B-600
B-1200
A-400
A-600
FCU-M101
CHWS
CHWR
CHWS
1"
1"
AREA OF WORK
60"x7"
60"x7"
(16Ø NECK)
EF-M101
MECHANICAL ROOM
ROOM M101 - AIRFLOW SCHEMATICN NO SCALE
FCU-M101
CEILING
1200 CFM 1200 CFM 600 CFM400 CFM
ROOM - M101
(200 CFM NEGATIVE)
FCU-M101
ROOM M101
AIRFLOW SUMMARY
SYSTEM AIRFLOW (CFM)
AHU/VAV SUPPLY 400
FAN COIL SUPPLY 1200
FAN COIL RETURN 1200
EXHAUST 600
AHU - 29 (EXISTING)
1" CD
60"x14"
EX. 3"
Since 1963
(989) 894-4300
714 East Midland Street Bay City, Michigan 48706 www.macmillanassociates.com
CONSULTING ENGINEERS
MacMILLAN ASSOCIATES
REV. DESCRIPTION BY DATE
0.5"0.0" 1.0" 2.0"1.5"2/ 3/
1:
A
M C
AL
EB
W
EN
D
LI
N G
(C W
EN
D
LI
N
G
M
AC
M
IL
LA
N
AS
SO
C
IA
TE
S.
C O
M
F:
\2
3- D
EL
TA
\2
4-
M
-W
IN
G A
N D
D
P R
IN
TE
R R
O O
M H
VA
C
S
TU
D Y\
-2
7- M
3.
- M
EC
H
AN
IC
AL
S C
H
ED
U
LE
S
AN
D D
ET
AI
LS
PROJECT DESCRIPTION
SHEET DESCRIPTION
AL
L
RI
GH
TS
R
ES
ER
VE
D.
C
OP
YR
IG
HT
M ac M
IL
LA
N
AS
SO
CI
AT
ES
, I
NC
SHEET No.
JOB No.DRAWN BY
DESIGNED BY
APPROVED BY
ISSUED FOR BIDS 10.28.2025
DELTA COLLEGE
M-WING AND 3D PRINTER ROOM
HVAC RENOVATION
MECHANICAL SCHEDULES
AND DETAILS
M3.1
2024-2307CHW
DSF
GRS
BRANCH DUCT CONNECTION TO DIFFUSER OR GRILLE DETAIL
NO SCALE
BRANCH DUCT
TRANSITION
DAMPER WITH POSITIVE
LOCKING WING NUT
FLEXIBLE INSULATED
DUCT SIMILAR TO FLEXMASTER
TYPE 3 OR APPROVED EQUAL
MAXIMUM 5'-0" LENGTH
DIFFUSER OR GRILLE W/ ROUND NECK
OR SQUARE TO ROUND NECK ADAPTER
LAY-IN CEILING
TAKE-OFF FITTING SIMILAR TO FLEXMASTER
MODEL #CB-D CONICAL BELL MOUTH
FITTING WITH DAMPER AND POSITIVE LOCKING
WING NUT
NO SCALE
DUCTWORK SQUARE VANE MITERED ELBOWS
W
W1NOTE
1 ALL VANE ELBOWS SHALL BE CONSTRUCTED AND INSTALLED AS DETAILED
BY SMACNA.
2 WHEN W1 DOES NOT EQUAL W2, VANE SHALL BE SINGLE THICKNESS VANE
TYPE REGARDLESS OF W DIMENSION.
3 ALL SINGLE THICKNESS VANES SHALL HAVE A 2” RADIUS, 1 1/2" MAXIMUM
SPACE BETWEEN VANES AND A 3/4" TRAILING EDGE.
4 WHEN W EQUALS W2 AND W1 IS GREATER THAN 20”, VANES SHALL BE
DOUBLE VANE TYPE.
5 NO MITERED ELBOW WITHOUT VANES SHALL BE INSTALLED.
NO SCALE
W
R
DUCTWORK RADIUS ELBOW
NOTE
1. THE INTERIOR SURFACE OF ALL RADIUS ELBOWS SHALL BE
MADE ROUND.
2. ALL STANDARD RADIUS ELBOWS CAN BE SUBSTITUTED WITH A SQUARE
VANE MITERED ELBOW.
3. NO MITERED ELBOWS WITHOUT VANES SHALL BE INSTALLED.
R=1.5W
DISCONNECT SWITCH
GASKET SEAL
ROOFING AND FLASHING
BY G.C.
ROOF CONSTRUCTION
STRUCTURAL STEEL SUPPORT
SEE STRUCTURAL DRAWINGS
EXHAUST DUCT
BACKDRAFT DAMPER
INSULATED ROOF CURB BY
M.C. (PREFABRICATED)-SEE DRAWINGS
VERIFY ROOF PITCH-THE MECHANICAL
TRADE SHALL FURNISH BLOCKING
AS NECESSARY TO LEVEL CURB
ROOF EXHAUST FAN DETAIL
NO SCALE
FOR CURB HEIGHT
AND EXHAUST FAN
EXHAUST FAN SCHEDULE
MARK SERVING AIRFLOW
(CFM)
EXTERNAL STATIC
PRESSURE
(IN. W.G.)
TYPE MOTOR BHP HP FLA VOLTS/PH/HZ MANUFACTURER
MODEL NUMBER SONES WEIGHT
(LBS) DIMENSIONS NOTES
EF-M101 3-D PRINTER ROOM 600 0.62 DOWNBLAST DIRECT-DRIVE 0.11 1/4 3.8 120V /1PH /60HZ G-100-VG 5.7 54 24" DIA X 36"H 1,2,3,4,5
NOTES:
1. MOTOR TO BE EC MOTOR, DESIGNED FOR FAN APPLICATIONS (GREENHECK VARI-GREEN WITH DIAL ON MOTOR CONTROL).
2. NEMA-1 DISCONNECT SWITCH SHALL BE PROVIDED BY FAN MANUFACTURER. DISCONNECT SHALL BE MOUNTED AND WIRED BY MANUFACTURER.
3. PROVIDE BACKDRAFT DAMPER FOR INSTALLATION IN DUCTWORK, BELOW FAN.
4. FAN SHALL BE PLACED ON NEW ROOF CURB. ROOF CURB SHALL BE RE-WORKED/EXTENDED TO BE 18" TALL ABOVE FINISHED ROOF. PROVIDE PRE-MANUFACTURERED, PRE-INSULATED ROOF CURB.
5. FANS SHALL BE MANUFACTURERED BY GREENHECK OR EQUAL.
FAN COIL UNIT (FC-M101)
RUN CONDITIONS - AUTOMATIC OPERATION:
1. THE UNIT SHALL RUN ACCORDING TO A USER DEFINABLE TIME SCHEDULE IN THE
FOLLOWING MODES:
A. OCCUPIED MODE: THE UNIT SHALL MAINTAIN A 72°F (ADJ.) COOLING SETPOINT
B. UNOCCUPIED MODE (NIGHT SETBACK): THE UNIT SHALL MAINTAIN A
76°F (ADJ.) COOLING SETPOINT.
ALARMS SHALL BE PROVIDED AS FOLLOWS:
1. HIGH ZONE TEMP: IF THE ZONE TEMPERATURE IS GREATER THAN THE
COOLING SETPOINT BY A USER DEFINABLE AMOUNT (ADJ.).
FAN:
1. THE FAN SHALL RUN ANYTIME THE UNIT IS COMMANDED TO RUN, UNLESS
SHUTDOWN ON SAFETIES. THE FAN SPEEDS SHALL AUTOMATICALLY BE INDEXED
AS FOLLOWS:
A. LOW SPEED SHALL RUN ANYTIME THE ZONE TEMPERATURE IS BELOW OR 1
DEGREE ABOVE SETPOINT.
B. MEDIUM SPEED SHALL RUN ANYTIME THE ZONE TEMPERATURE IS ABOVE
SETPOINT BY 2 DEGREES OR MORE.
C. HIGH SPEED SHALL RUN ANYTIME THE ZONE TEMPERATURE IS ABOVE
SETPOINT BY 4 DEGREES (ADJ.).
COOLING COIL VALVE:
1. THE CONTROLLER SHALL MEASURE THE ZONE TEMPERATURE AND OPEN
THE COOLING COIL VALVE TO MAINTAIN ITS COOLING SETPOINT.
THE COOLING SHALL BE ENABLED WHENEVER:
1. THE ZONE TEMPERATURE IS ABOVE COOLING A SETPOINT AND THE FAN IS ON.
FAN STATUS:
1. THE CONTROLLER SHALL MONITOR THE FAN STATUS AND SPEED.
ALARMS SHALL BE PROVIDED AS FOLLOWS:
1. FAN FAILURE: COMMANDED ON, BUT THE STATUS IS OFF.
2. FAN IN HAND: COMMANDED OFF, BUT THE STATUS IS ON.
3. FAN RUNTIME EXCEEDED: FAN STATUS RUNTIME EXCEEDS A USER DEFINABLE
LIMIT (ADJ.).
BI - FAN STATUS
BO - FAN START/STOP
CT
M
EA
T
DARA
BI - FAN STATUS
BO - FAN LOW SPEED
BO - FAN MEDIUM SPEED
BO - FAN HIGH SPEED
CT
M
CHW
BO - COOLING VALVE
CHWR CHWS
S
DA
AI - ZONE TEMP
EXHAUST FAN (EF-M101)
RUN CONDITIONS - SCHEDULED:
1. THE FAN SHALL RUN ACCORDING TO A USER DEFINABLE SCHEDULE.
FAN:
1. THE FAN SHALL HAVE A USER DEFINABLE (ADJ.) MINIMUM RUNTIME.
FAN STATUS:
1. THE CONTROLLER SHALL MONITOR THE FAN STATUS.
ALARMS SHALL BE PROVIDED AS FOLLOWS:
1. FAN FAILURE: COMMANDED ON, BUT THE STATUS IS OFF.
2. FAN IN HAND: COMMANDED OFF, BUT THE STATUS IS ON.
3. FAN RUNTIME EXCEEDED: FAN STATUS RUNTIME EXCEEDS A USER
DEFINABLE LIMIT (ADJ.).
MECHANICAL CONTROLS - FAN COIL UNIT
MECHANICAL CONTROLS - EXHAUST FAN
GRILLE, REGISTER, AND DIFFUSER SCHEDULE
TYPE
MODEL NUMBERS DEFLECTION NECK SIZE REMARKS
REF SERVICE AND
TYPE
A SUPPLY AIR
DIFFUSER PRICE SCD OR EQUAL TITUS 4 WAY
0-125 CFM: 6" x 6" (6" DIA) 126-250 CFM: 9" x 9" (8" DIA)
251-350 CFM: 12" x 12" (10" DIA) 351-450 CFM: 12" x 12" (12" DIA) 451-600 CFM: 15" x 15" (14" DIA) 601-900 CFM: 18" x 18" (16" DIA)
ALL STEEL CONSTRUCTION, ADJUSTABLE
HORIZONTAL TO VERTICAL AIRFLOW PATTERN, 3
CONE, 24X24, BAKED ON ENAMEL FINISH WITH
COLOR SELECTED BY DELTA COLLEGE. FRAME AS
REQUIRED FOR CEILING TYPE WITH DIFFUSER
PANEL SHALL MATCH GRID SIZE WHERE INSTALLED
IN LAY IN CEILING. MAXIMUM NECK VELOCITY
SHALL BE 700 FPM AND MAXIMUM NC LEVEL SHALL
BE 25.
B DUCTED EXHAUST
AIR GRILLE PRICE 80 OR EQUAL TITUS EGGCRATE 24"L X 24"W (TYPICAL) UNLESS OTHERWISE
NOTED ON DRAWINGS
ALL ALUMINUM CONSTRUCTION, EXTRUDED
ALUMINUM BORDER AND FRAME, 1/2" X 1/2" X 1/2"
ALUMINUM GRID CORE. FIELD VERIFY DIMENSIONS.
C
DUCTED RETURN
AIR GRILLE WITH
FILTER
PRICE 80 FH OR EQUAL TITUS EGGCRATE 24"L X 24"W, 16" NECK SIZE
ALL ALUMINUM CONSTRUCTION, EXTRUDED
ALUMINUM BORDER AND FRAME, 1/2" X 1/2" X 1/2"
ALUMINUM GRID CORE. GRILLE SHALL BE
FURNISHED WITH FILTER FRAME WITH HINGED
ACCESS. FILTER FRAME SHALL HAVE 1" DEPTH TO
ACCEPT STANDARD 1" FILTER MEDIA. PROVIDE
FILTER FOR FILTER RACK (NOT SUPPLIED BY
MANUFACTURER). FIELD VERIFY DIMENSIONS.
FURNISH WITH STANDARD 24"L x 24"W x 1"H MERV 8
FILTER.
NO SCALE
WITH 2-WAY CONTROL VALVE
FAN COIL UNIT
AIR VENT (TYP)
BALL SHUT-OFF VALVE (TYP)
CHILLED WATER RETURN
CHILLED WATER SUPPLY
CONDENSATE DRAIN TO AIR GAP DISCHARGE
UNION (TYP)
1" CONDENSATE DRAIN PIPING
CEILING
P T
STRAINER W/DRAIN
VALVE (TYP)
FLOOR DRAIN OR SERVICE SINK
2-WAY PRESSURE INDEPENDENT CONTROL
WITH/INTEGRAL PRESET BALANCE VALVE
(CHILLED WATER)
P T
FAN COIL UNIT DETAIL
SA SUPPLY AIR
TWO WAY CONTROL VALVE
MANUAL DAMPER
VARIABLE AIR VOLUMEVAV
MISC. EQUIP. COND DRAIN PIPINGCD
`[B-250`]
`[A-250`]
RETURN OR EXHAUST AIR GRILLE -
SUPPLY AIR DIFFUSER -
MECHANICAL SYMBOL LIST
EX
CHWR
CHWS
EXISTING
CHILLED WATER RETURN PIPING
CHILLED WATER SUPPLY PIPING
TWO WAY CONTROL VALVE
STRAINER
FLOW ARROW
ISOLATION VALVE
UNION
CAP
REDUCER
BALL VALVE
T THERMOSTAT OR WALL SENSOR
FLOOR DRAIN
EXHAUST FAN WITH FAN ABOVE
ELBOW DROPPING DOWN
ELBOW RISING UP
AIR HANDLING UNITAHU
ABOVEABV
CUBIC FEET PER MINUTECFM
RF RETURN AIR FAN
FAN COIL UNITFCU
EXHAUST FANEF
COOLING TOWERCT
RA RETURN AIR
EXHAUST AIREA
(PNEUMATIC)
(FLOOR PLAN)
TYPE "A", 250 CFM
TYPE "B", 250 CFM
PRESSURE/TEMPERATURE PORT
EXTERNAL STATIC PRESSUREESP
FAN COIL UNIT SCHEDULE
TAG MANUFACTURER MODEL TYPE
COOLING CAPACITY FAN MOTOR
DIMENSIONS OPERATING
WEIGHT
ELECTRICAL DATA
AIRFLOW MBH COIL AIR TEMP CHILLED WATER
HP ESP
(IN H20) CFM VOLT PHASE MCA
MAX FUSE
SIZE
CFM TOTAL ENTERING
DB
LEAVING
DB
LEAVING
TEMP (°F) GPM FLUID PD (FT
H2O)
CONTROL
VALVE LxWxH LBS AMP
FCU- M101 TRANE FCDB120 HORIZONTAL
CABINET 1200 36 80 58.76 45 58.42 5.7 11.42 2-WAY 0.130/0.220 0.250" 1200 75"x26"x10" 218 120 1 6.07 15
NOTES:
1. FRONT AND BACK DUCT COLLAR INLET/OUTLET.
2. MANUFACTURER PROVIDED AND MOUNTED, NON-FUSED DISCONNECT SWITCH. ELECTRICAL TRADES SHALL FURNISH AND INSTALL SINGLE POINT POWER CONNECTION.
3. FAN COIL UNIT SHALL BE FURNISHED WITHOUT FILTER.
4. POLYMER DRAIN PAN.
5. HIGH SPEED ECM MOTORS.
6. SELECTION BASED ON TRANE. OR EQUAL MANUFACTURERS SHALL BE CONSIDERED IF ALL REQUIREMENTS ARE MATCHED OR EXCEEDED.
ENTERING
TEMP (°F)
(989) 894-4300
714 East Midland Street Bay City, Michigan 48706 www.macmillanassociates.com
CONSULTING ENGINEERS
MacMILLAN ASSOCIATES
REV. DESCRIPTION BY DATE
0.5"0.0" 1.0" 2.0"1.5"2/ 3/
1:
A
M C
AL
EB
W
EN
D
LI
N G
(C W
EN
D
LI
N
G
M
AC
M
IL
LA
N
AS
SO
C
IA
TE
S.
C O
M
F:
\2
3- D
EL
TA
\2
4-
M
-W
IN
G A
N D
D
P R
IN
TE
R R
O O
M H
VA
C
S
TU
D Y\
-2
7- M
4.
- M
EC
H
AN
IC
AL
S
PE
C
IF
IC
AT
IO
N
S
PROJECT DESCRIPTION
SHEET DESCRIPTION
AL
L
RI
GH
TS
R
ES
ER
VE
D.
C
OP
YR
IG
HT
M ac M
IL
LA
N
AS
SO
CI
AT
ES
, I
NC
SHEET No.
JOB No.DRAWN BY
DESIGNED BY
APPROVED BY
ISSUED FOR BIDS 10.28.2025
DELTA COLLEGE
M-WING AND 3D PRINTER ROOM
HVAC RENOVATION
MECHANICAL SPECIFICATIONS
M4.1
2024-2307CHW
DSF
GRS
MECHANICAL SPECIFICATIONS
REFERENCE
INSTRUCTIONS TO BIDDERS, CONDITIONS OF THE CONTRACT, DIVISION 1, AND THIS SECTION SHALL APPLY TO THIS
DIVISION.
CODES, PERMITS & INSPECTIONS
CONTRACTOR SHALL SECURE PERMITS, INSPECTIONS AND TESTS, PAY ALL FEES, DEPOSITS, AND COSTS FOR ALL MECHANICAL UTILITIES AND SERVICES INVOLVED AND PRESENT THE OWNER A CERTIFICATE OF INSPECTION AND APPROVAL FROM THE DEPARTMENT HAVING JURISDICTION OVER HIS WORK. SHOULD ANY CHANGE IN THE DRAWINGS AND SPECIFICATIONS BE REQUIRED TO COMPLY WITH ALL APPLICABLE CODES, RULES, REGULATIONS, ETC., CONTRACTOR SHALL NOTIFY THE ENGINEER BEFORE SUBMITTING BID. AFTER ENTERING INTO CONTRACT, ALL WORK NECESSARY TO MEET THE REQUIREMENTS SHALL BE COMPLETED WITHOUT ADDITION TO THE CONTRACT AMOUNT.
WHERE WORK INDICATED IS MORE THAN REQUIRED BY CODES, ETC., SUCH WORK SHALL BE AS INDICATED.
JOB OBSERVATION
NOT WITHSTANDING ANY REFERENCE TO ANY CODE, RULE OR REGULATION, ENGINEER SHALL HAVE NO RESPONSIBILITY FOR SAFETY ON THE JOB SITE, SHALL HAVE NO RIGHT TO CHANGE OR STOP THE WORK, SHALL NOT CONTROL THE MEANS OF THE WORK, AND SHALL NOT HAVE ANY DUTY TO PROVIDE SUPERVISION OF MEANS, METHODS, PROCESSES
OR PROCEDURES OF CONSTRUCTION.
FIRST-CLASS WORKABLE SYSTEMS
FIRST CLASS WORKABLE SYSTEMS SHALL BE PROVIDED BY THE CONTRACTOR. IF, IN THE OPINION OF THE CONTRACTOR, CHANGES IN THE DRAWINGS OR SPECIFICATIONS ARE REQUIRED TO PRODUCE FIRST-CLASS WORKABLE SYSTEMS, CONTRACTOR SHALL REQUEST AN INTERPRETATION FROM THE ENGINEER BEFORE PROCEEDING WITH THE WORK. IF THE CONTRACTOR FAILS TO MAKE SUCH A REQUEST, NO EXCUSE WILL THEREAFTER BE ENTERTAINED FOR FAILURE TO
PROVIDE FIRST-CLASS WORKABLE SYSTEMS.
DRAWINGS
DRAWINGS ARE INTENDED TO SHOW THE GENERAL ARRANGEMENT, DESIGN, AND EXTENT OF THE WORK AND ARE DIAGRAMMATIC. THEY ARE NOT INTENDED TO BE SCALED FOR ROUGH-IN MEASUREMENTS NOR TO SERVE AS SHOP DRAWINGS. THE ENGINEERS AND OWNER RESERVE THE RIGHT TO MAKE MINOR CHANGES IN THE LOCATION OF EQUIPMENT, DUCTWORK, PIPING, ETC. AT THE TIME OF ROUGH-IN WITHOUT ADDITIONAL COST TO THE OWNER.
CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS, LOCATIONS, ETC. FOR ACCURACY AND POSSIBILITY OF INTERFERENCES DUE TO FIELD CONDITIONS AND ACTUAL BUILDING STRUCTURE. FAILURE TO CHECK WILL BE NO
REASON FOR ADDITIONAL COMPENSATION.
SHOP DRAWINGS
SUBMIT ELECTRONIC SET OF COMPLETE SHOP DRAWINGS FOR ALL MECHANICAL EQUIPMENT AND MATERIALS TO THE ENGINEER FOR REVIEW BEFORE FABRICATION OF WORK OR ORDERING OF EQUIPMENT. DRAWINGS MUST BE REVIEWED BY THE ENGINEER BEFORE ORDERING EQUIPMENT. ALL SHOP DRAWINGS REJECTED SHALL BE CORRECTED AND
RESUBMITTED TO THE ENGINEER BEFORE ORDERING.
STANDARDS OF INDUSTRY
STANDARDS OF INDUSTRY SHALL BE FOLLOWED WHEN APPLICABLE.
GUARANTEE
CONTRACTOR SHALL GUARANTEE EQUIPMENT, MATERIALS AND WORKMANSHIP IN HIS CONTRACT AND SHALL MAKE GOOD AT HIS OWN EXPENSE ANY DEFECTS WHICH MAY DEVELOP WITHIN ONE YEAR AFTER START-UP OF EACH PIECE OF EQUIPMENT, OCCUPANCY BY OWNER, OR FINAL ACCEPTANCE OF THE JOB, WHICHEVER OCCURS FIRST.
CONTRACTORS RECORD/AS-BUILT DRAWINGS
CONTRACTOR SHALL MAINTAIN AND KEEP AN UP-TO-DATE SET OF "RECORD" DRAWINGS REFLECTING "AS-BUILT" CONDITIONS OF THEIR WORK. CONTRACTOR SHALL INDICATE EXACT DIMENSIONS AND ELEVATIONS FOR ALL UNDERGROUND WORK. UPON COMPLETION OF THIS PROJECT, THE CONTRACTOR SHALL DELIVER TO THE ENGINEER THE
"RECORD" DRAWINGS.
LOCAL CONDITIONS
BEFORE SUBMITTING BIDS AND/OR PROCEEDING WITH THE PROJECT, THE CONTRACTOR SHALL EXAMINE ALL DRAWINGS, SPECIFICATIONS AND ADDENDA ISSUED FOR THE PROJECT AND SHALL EXAMINE THE PROJECT SITE. THE CONTRACTOR SHALL THOROUGHLY INVESTIGATE THE PROJECT SITE AND BECOME FULLY INFORMED AS TO THE EXTENT OF HIS WORK AND COORDINATION OF THIS WORK WITH ALL OTHER TRADES AND INCLUDE ALL COST TO PERFORM AND COMPLETE
WORK FOR THIS PROJECT PER DRAWINGS AND SPECIFICATION AND ALL CODES.
OPERATION AND MAINTENANCE MANUALS
CONTRACTOR SHALL FURNISH TO THE ARCHITECT/ENGINEER TWO (2) COPIES OF AN APPROVED BOUND (3-RING BINDER) BOOK WITH TABS FOR SECTIONS COVERING EACH ITEM OF EQUIPMENT. THESE NOTEBOOKS SHALL INCLUDE SHOP DRAWINGS, MAINTENANCE MANUALS, OPERATING MANUALS AND PARTS LIST AS NECESSARY TO INSTRUCT THE OWNER ON PROPER OPERATION AND USE AS WELL AS MAINTENANCE FOR EACH PIECE OF EQUIPMENT FOR THIS PROJECT.
THESE BOOKS SHALL ALSO INCLUDE CONTRACTOR'S, SUBCONTRACTOR'S AND MANUFACTURER'S NAMES, TELEPHONE NUMBERS AND ADDRESSES. MANUALS SHALL ALSO INCLUDE SEQUENCE OF OPERATION, CONTROL EQUIPMENT LITERATURE, WIRING AND CONTROL DIAGRAMS, CERTIFICATES OF GUARANTEES, CERTIFICATES OF INSPECTION, MECHANICAL SYSTEM TEST AND BALANCING REPORTS. THE CONTRACTOR SHALL ACCUMULATE AND SUMMARIZE THE CONTROL AND MAINTENANCE SEQUENCE IN TYPEWRITTEN SHEET TO BE INCLUDED IN THE REPORT. THESE MANUALS SHOULD BE HARD BOUND IN BEST QUALITY BINDERS AND TURNED OVER TO THE ARCHITECT/ENGINEER FOR APPROVAL
AT COMPLETION OF PROJECT.
START-UP SERVICE
CONTRACTOR SHALL ARRANGE WITH EQUIPMENT MANUFACTURERS FOR PROVIDING COMPLETE START-UP SERVICE FOR ALL EQUIPMENT ON THIS PROJECT. ALL START-UP SERVICES SHALL BE PERFORMED IN THE PRESENCE OF THE OWNER AND/OR ENGINEER. A WRITTEN REPORT SHALL BE SUBMITTED TO THE ENGINEER STATING DATE OF START-UP, MANUFACTURER APPROVAL OF SYSTEM OPERATION AND INSTALLATION.
CUTTING AND PATCHING
CUTTING AND PATCHING SHALL BE BY TRADES REGULARLY ENGAGED IN THIS TYPE OF WORK, EXCEPT DRILLING OF HOLES SHALL BE DONE BY THE TRADES REQUIRING SAME. STRUCTURAL MEMBERS SHALL NOT BE CUT OR DRILLED.
SALVAGEABLE MATERIAL
SALVAGEABLE MATERIAL SHALL REMAIN THE PROPERTY OF THE OWNER AND SHALL BE STORED AT LOCATIONS AS DIRECTED BY THE OWNER, EXCEPT THE OWNER RESERVES THE RIGHT TO DESIGNATE CERTAIN ITEMS OF SALVAGEABLE
MATERIAL TO BE REMOVED FROM THE PROJECT SITE.
RIGGING AND HOISTING
PERFORM ALL REQUIRED RIGGING, HOISTING, TRANSPORTATION, MOVING, ETC. OF ALL EQUIPMENT, MATERIALS, ETC. TO BE FURNISHED AND/OR INSTALLED AS SHOWN ON DRAWINGS, WHETHER FURNISHED BY THIS CONTRACTOR OR BY THE
OWNER OR OTHER TRADES.
STORAGE FACILITY
FURNISH AND MAINTAIN A WEATHERPROOF STORAGE FACILITY ON THE SITE OF ADEQUATE SIZE TO STORE MISCELLANEOUS EQUIPMENT AND/OR MATERIALS TO PREVENT EXPOSURE TO THE WEATHER. LOCATION OF SHED SHALL BE DETERMINED BY THE OWNER AND ARCHITECT/ENGINEER. THE OWNER RESERVES THE RIGHT TO DENY STORAGE OF
MATERIALS OR EQUIPMENT IN ANY EXISTING OR NEW BUILDINGS.
PROTECTION FROM DAMAGE
THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL MATERIALS, EQUIPMENT, ETC. AND ALL WORK INSTALLED BY HIMSELF AND SHALL PROTECT IT FROM DAMAGE UNTIL FINAL ACCEPTANCE OF THIS PROJECT BY THE OWNER.
FURNISH ALL COVERINGS AND PROTECTION FROM DIRT, DUST, RAIN, STORM, HEAT, TRAFFIC, WEAR, ETC. AND ALL POSSIBLE INJURY INCLUDING THAT BY OTHER WORKMEN. ANY EQUIPMENT, WORKMANSHIP, MATERIALS, ETC. DAMAGED PRIOR TO FINAL ACCEPTANCE BY THE OWNER OF THIS PROJECT SHALL BE PROPERLY REPAIRED AT NO EXPENSE TO THE
OWNER.
PROTECT ALL PLUMBING FIXTURES AND OTHER EQUIPMENT FROM DAMAGE BY COVERING OR COATING. ANY DENTED, SCRATCHED, RUSTED OR MARRED SURFACE FINISHES WILL NOT BE ACCEPTED.
PROTECT ALL EQUIPMENT, MATERIALS, ETC. FROM FREEZING.
PLUMBING AND PIPING BASIC MATERIALS AND METHODS:
CONDENSATE DRAIN PIPING:
EQUIPMENT DRAINS, COOLING COIL DRAINS, OVERFLOWS AND PIPING FROM RELIEF VALVES 1" AND SMALLER SHALL BE
COPPER TUBING: ASTM B88, TYPE L, HARD DRAWN.
FITTINGS: ASME B16.18 CAST BRASS TEE TAP OR ASME B16.22 SOLDER WROUGHT COPPER.
JOINTS: SOLDER, LEAD FREE, 95-5 TIN-ANTIMONY, OR TIN AND SILVER, WITH MELTING RANGE 430 TO 535 DEGREES F.
EQUIPMENT DRAINS, COOLING COIL DRAINS, OVERFLOWS AND PIPING FROM RELIEF VALVES 1¼" THRU 2" SHALL BE ASTM
A53, SCHEDULE 40 BLACK STEEL WITH THREADED JOINTS OR SCHEDULE 40 PVC.
HEATING HOT WATER AND CHILLED WATER PIPING
PIPING 3" AND SMALLER: COPPER TUBING: ASTM B88, TYPE L, HARD DRAWN, SEAMLESS.
FITTINGS: ASME B16.18 CAST BRONZE TEE TAP OR ASME B16.22 SOLDER WROUGHT COPPER.
JOINTS: 95-5 TIN - ANTIMONY OR TIN AND SILVER WITH MELTING RANGE 430 TO 535 DEGREES F.
JOINTS: 2" THRU 6" MAY BE MECHANICAL PIPE COUPLINGS OF A BOLTED TYPE WITH A CENTRAL CAVITY DESIGN PRESSURE-RESPONSIVE GASKET ALONG WITH GROOVED END COPPER OR BRONZE FITTINGS AS AVAILABLE, AS
MANUFACTURED BY VICTAULIC OR GRUVLOK AS FOLLOWS:
COPPER TUBE: ASTM B88 (TYPE K OR L) - ROLL GROOVED ONLY.
MECHANICAL COUPLINGS: SHALL BE VICTAULIC STYLE 606 RIGID COUPLINGS FOR COPPER CONSISTING OF A DUCTILE IRON CAST HOUSING, A SYNTHETIC RUBBER GASKET OF A CENTRAL CAVITY PRESSURE-RESPONSIVE DESIGN, WITH
PLATED NUTS AND BOLTS TO SECURE UNIT TOGETHER.
COUPLING HOUSINGS: SHALL BE DUCTILE IRON CONFORMING TO ASTM A395 AND ASTM A536 (GRADE 65-45-12), WITH A COPPER COLORED ALKYD ENAMEL PAINT COATING, AS MANUFACTURED BY VICTAULIC COMPANY OF AMERICA.
GASKETS: SHALL BE MOLDED OF SYNTHETIC RUBBER IN A FLUSHSEAL® CONFIGURATION CONFORMING TO THE COPPER TUBE SIZE (CTS) OUTSIDE DIAMETER AND COUPLING HOUSING, OF ELASTOMERS HAVING PROPERTIES AS DESIGNATED IN
ASTM D-2000.
GASKET SUPPLIED FOR WATER SERVICES FROM -30 TO +230 DEGREES F GRADE "E" EPDM COMPOUND MOLDED OF
MATERIALS CONFORMING TO ASTM D-2000, DESIGNATION 2CA615A25B24F17Z.
FLANGE ADAPTERS: SIMILAR TO VICTAULIC STYLE 641 VIC-FLANGE ADAPTERS 2" - 6", DUCTILE IRON ASTM A-536 OR MALLEABLE IRON ASTM A-47, ENGAGING DIRECTLY INTO ROLL GROOVED COPPER TUBE AND FITTINGS AND BOLTING DIRECTLY TO ANSI CLASS 125 CAST IRON AND CLASS 150 STEEL FLANGED COMPONENTS; INSTALLER TO SUPPLY STANDARD FLANGE BOLTS. FLANGE CASTING SHALL BE AS IN 7.2.A ABOVE WITH A CORRESPONDING VIC-FLANGE
GASKET AS IN 7.3 ABOVE.
FITTINGS: FITTINGS SHALL BE FULL FLOW (SMOOTH TURN ELBOWS) COPPER FITTINGS WITH GROOVES DESIGNED TO
ACCEPT GROOVED END COUPLINGS.
VICTAULIC MECHANICAL PIPE COUPLINGS, FITTING, VALVES AND OTHER GROOVED COMPONENTS MAY BE USED AS AN OPTION TO WELDING, THREADING OR FLANGED METHODS. ALL GROOVED COMPONENTS SHALL BE OF ONE MANUFACTURER AND SHALL CONFORM TO LOCAL CODE APPROVAL AND/OR AS LISTED BY ANSI B31.1, B 31.9, ASME, UL/FM IAPMO OR BOC. GROOVED END PRODUCT MANUFACTURER TO BE ISO-9001 CERTIFIED.
ROLL OR CUT GROOVED ENDS AS APPROPRIATE TO PIPE MATERIAL, WALL THICKNESS, PRESSURES, SIZE AND METHOD OF JOINING. PIPE ENDS SHALL BE GROOVED IN ACCORDANCE WITH MANUFACTURERS CURRENT LISTED STANDARDS
CONFORMING TO ANSI/AWWA C-606.
MECHANICAL COUPLINGS SHALL BE SIMILAR TO VICTAULIC STYLE 07 (ZERO-FLEX) RIGID COUPLING OR STYLE HP-70 RIGID COUPLING FOR HIGH PRESSURE SERVICE. VICTAULIC STYLE 77 OR 75 COUPLING SHALL BE USED WHERE SYSTEM FLEXIBILITY IS DESIRED AT PUMPS AND OTHER MECHANICAL EQUIPMENT TO REDUCE NOISE AND VIBRATION. NOISE AND VIBRATION REDUCTION IS ACHIEVED BY INSTALLING (3) STYLE 77 OR 75 FLEXIBLE COUPLINGS NEAR THE VIBRATION SOURCE. COUPLINGS SHALL BE OF CAST DUCTILE IRON CONFORMING TO ASTM A536, GRADE 65-45-12 OR MALLEABLE
IRON CONFORMING TO ASTM A47, GRADE 32-510.
PIPE SUPPORTS AND ANCHORS:
CONFORM TO ASME B31.5, ASTM F708, MSS SP58, MSS SP69 AND MSS SP89.
HANGERS FOR PIPE SIZES 1/2 TO 1 1/2 INCH: MALLEABLE IRON, ADJUSTABLE SWIVEL, SPLIT RING.
HANGERS FOR PIPE SIZES 2 INCHES AND OVER: CARBON STEEL, ADJUSTABLE, CLEVIS.
MULTIPLE OR TRAPEZE HANGERS: STEEL CHANNELS WITH WELDED SPACERS AND HANGER RODS.
WALL SUPPORT FOR PIPE SIZES TO 3 INCHES: CAST IRON HOOK.
WALL SUPPORT FOR PIPE SIZES 4 INCHES AND OVER: WELDED STEEL BRACKET AND WROUGHT STEEL CLAMP. VERTICAL
SUPPORT: STEEL RISER CLAMP.
FLOOR SUPPORT: CAST IRON ADJUSTABLE PIPE SADDLE, LOCK NUT, NIPPLE, FLOOR FLANGE, AND CONCRETE PIER OR
STEEL SUPPORT.
COPPER PIPE SUPPORT: CARBON STEEL RING, ADJUSTABLE, COPPER PLATED.
HANGER RODS: MILD STEEL THREADED BOTH ENDS, THREADED ONE END, OR CONTINUOUS THREADED. INSERTS:
MALLEABLE IRON CASE OF STEEL SHELL AND EXPANDER PLUG FOR THREADED CONNECTION WITH LATERAL ADJUSTMENT, TOP SLOT FOR REINFORCING RODS, LUGS FOR ATTACHING TO FORMS; SIZE INSERTS TO SUIT THREADED
HANGER RODS.
REAM PIPE AND TUBE ENDS. REMOVE BURRS. BEVEL PLAIN END FERROUS PIPE. REMOVE SCALE AND DIRT ON INSIDE AND OUTSIDE BEFORE ASSEMBLY. PREPARE PIPING CONNECTIONS TO EQUIPMENT WITH FLANGES OR UNIONS.
TESTING, FLUSHING AND CLEANING OF PIPING SYSTEMS
HEATING AND AIR CONDITION PIPING: HYDROSTATICALLY TEST TO AT LEAST TWICE THE OPERATING PRESSURE BUT IN NO CASE LESS THAN 100 PSIG FOR FOUR (4) HOURS. THIS PRESSURE TO BE ON PIPING ONLY, NOT ON EQUIPMENT.
SUPPORT FOR PIPE WITH INSULATION
ALL PIPING SHALL BE SUPPORTED IN SUCH A MANNER THAT NEITHER THE INSULATION OR THE VAPOR/WEATHER BARRIER IS COMPROMISED BY THE HANGER OR THE EFFECTS OF THE HANGER. IN ALL CASES, HANGER SPACING SHALL
BE SUCH THAT BUTT JOINTS MAY BE MADE OUTSIDE THE HANGER.
ON ALL SIZE PIPING OF COLD SYSTEMS, THE PIPE HANGER SADDLES SHALL BE SEPARATED AWAY FROM THE PIPE BY UTILIZING INSERTS. THE VAPOR BARRIER SHALL BE CONTINUOUS, INCLUDING MATERIAL COVERED BY THE HANGER
SADDLE. UTILIZE A CLEVIS STYLE HANGER WITH PROTECTIVE SHIELD PER MSS SP-69.
ON WARM WATER PIPING SYSTEMS 3" IN DIAMETER OR LESS, INSULATED WITH FIBERGLAS INSULATION, MAY BE SUPPORTED BY PLACING SADDLES OF THE PROPER LENGTH AND SPACING, AS DESIGNATED IN OWENS-CORNING PUB.
1-IN-12534, UNDER THE INSULATION.
FOR HOT OR COLD PIPING SYSTEMS LARGER THAN 2½” IN DIAMETER, OWENS-CORNING CALCIUM SILICATE PIPE INSULATION SHALL BE USED FOR HIGH DENSITY INSERTS. PIPING SADDLES FOR PIPING LARGER THAN 3” SHALL NOT BE
IN CONTACT WITH THE PIPING. VAPOR BARRIER SHALL COVER INSERTS.
OWENS-CORNING CALCIUM SILICATE PIPE INSULATION MAY BE USED TO SUPPORT THE ENTIRE WEIGHT OF THE PIPING SYSTEM PROVIDED THE HANGER SADDLE IS DESIGNED SO THE MAXIMUM COMPRESSIVE LOAD DOES NOT EXCEED 100
PSI.
WHERE PIPE SHOES AND ROLLER SUPPORTS ARE REQUIRED, INSULATION SHALL BE INSERTED IN THE PIPE SHOE TO MINIMIZE PIPE HEAT LOSS. WHERE POSSIBLE, THE PIPE SHOE SHALL BE SIZED TO BE FLUSH WITH THE OUTER PIPE
INSULATION DIAMETER.
THERMAL EXPANSION AND CONTRACTION OF THE PIPING AND INSULATION SYSTEM CAN GENERALLY BE TAKEN CARE OF BY UTILIZING DOUBLE LAYERS OF INSULATION AND STAGGERING BOTH LONGITUDINAL AND CIRCUMFERENTIAL JOINTS.
WHERE LONG RUNS ARE ENCOUNTERED, EXPANSION JOINTS MAY BE REQUIRED WHERE SINGLE LAYERS OF THE
INSULATION ARE BEING USED.
ON VERTICAL RUNS, INSULATION SUPPORT RINGS SHALL BE USED.
VALVES
SWING CHECK VALVES:
UP TO AND INCLUDING 3 INCHES: BRONZE BODY, BRONZE TRIM, BRONZE ROTATING SWING DISC, WITH COMPOSITION
DISC, SOLDER OR THREADED ENDS.
OVER 3 INCHES: IRON BODY, BRONZE TRIM, BRONZE OR BRONZE FACED ROTATING SWING DISC, RENEWABLE DISC AND
SEAT, FLANGED ENDS OR GROOVED ENDS IF VICTAULIC GROOVED END FITTINGS ARE USED.
BALL VALVES:
UP TO AND INCLUDING 2 INCHES: BRONZE ONE PIECE BODY, STAINLESS STEEL BALL, TEFLON SEATS AND STUFFING BOX
RING, LEVER HANDLE WITH BALANCING STOPS, SOLDER OR THREADED ENDS.
OVER 2 INCHES: CAST STEEL BODY, CHROME PLATED STEEL BALL, TEFLON SEAT AND STUFFING BOX SEALS, LEVER HANDLE, OR GEAR DRIVE HANDWHEEL FOR SIZES 10 INCHES AND OVER, FLANGED. DUCTILE IRON BODY, CHROME PLATED CARBON STEEL BALL AND STEM, TFE SEATS, LEVER HANDLE OR GEAR OPERATOR, GROOVED ENDS. VICTAULIC
SERIES 726.
PLUG VALVES:
UP TO AND INCLUDING 3 INCHES: BRONZE BODY, BRONZE TAPERED PLUG, FULL PORT OPENING, NON-LUBRICATED, TEFLON PACKING, THREADED ENDS. OPERATOR: ONE PLUG VALVE WRENCH FOR EVERY TEN PLUG VALVES MINIMUM OF
ONE.
OVER 3 INCHES: CAST IRON BODY AND PLUG, FULL PORT OPENING, PRESSURE LUBRICATED, TEFLON PACKING, FLANGED ENDS OR GROOVED ENDS IF VICTAULIC GROOVED END FITTINGS ARE USED. DUCTILE IRON BODY AND PLUG, STANDARD PORT OPENING, NON-LUBRICATED ECCENTRIC-TYPE, WELDED-IN NICKEL SEAT, GROOVED ENDS. VICTAULIC SERIES 377.
OPERATOR: EACH PLUG VALVE SHALL HAVE A WRENCH HANDLE WITH SET SCREW.
UNIONS
UNIONS OR FLANGES SHALL BE USED AT EQUIPMENT CONNECTIONS. DIELECTRIC CONNECTIONS BETWEEN COPPER AND IRON OR STEEL PIPE SHALL BE MADE WITH DIELECTRIC NIPPLES SIMILAR TO VICTAULIC STYLE 47. A BRASS
ADAPTER DIELECTRIC UNION IS NOT ACCEPTABLE.
PLATES AND SLEEVES
PROVIDE AND INSTALL PIPE SLEEVES FOR ALL PIPING AND DUCTS PASSING THROUGH WALLS, FLOORS AND CEILINGS. SLEEVES THROUGH WALLS BELOW GRADE AND AT ALL FLOORS SHALL BE BLACK STEEL. SLEEVES THROUGH WALLS AND CEILINGS MAY BE 20 GAUGE GALVANIZED SHEET METAL. WHERE PIPES ARE INSULATED, SLEEVES SHALL BE LARGE ENOUGH TO PASS THE INSULATION. ALL PENETRATION VOIDS SHALL BE SEALED SMOKE TIGHT WITH NON-COMBUSTIBLE MATERIALS SIMILAR TO 3M OR HILTI FIRESTOP SYSTEMS TO MAINTAIN THE INTEGRITY OF THE FIRE RATED STRUCTURE. IN A NON-FIRE RATED ASSEMBLY, SEAL ALL VOIDS WITH
NON-HARDENING SEALANT.
HANGERS AND SADDLES
SHALL BE MODERN PIPE SUPPORTS CORP., GRINNELL/ANVIL, AUTO GRIP OR M-CO. FOR COPPER PIPE WITH STEEL HANGERS, CLEAN AND WRAP PIPE WITH TWO LAYERS OF PLASTIC INSULATING TAPE AT POINTS OF CONTACT. HANGERS FOR PIPING WITH VAPOR BARRIER SEALED INSULATION SHALL BE MULTIPURPOSE PIPE SADDLES FITTING OVER THE INSULATION. WIRE OR PERFORATED STRAP IRON WILL NOT BE PERMITTED FOR PIPE SUPPORTS. HANGERS SHALL BE CLEVIS OR SPLIT RING TYPE WITH VERTICAL ADJUSTMENT AND BEAM CLAMP SIMILAR TO GRINNELL/ANVIL FIG. 260, WITH MAXIMUM SPACING PER ASHRAE STANDARDS:
PIPE SIZE STEEL PIPE COPPER PIPE PVC PIPE ROD SIZE
1/2 TO 3/4 INCH 6 FEET 5 FEET 4 FEET 3/8"
1 INCH 7 FEET 5 FEET 4 FEET 3/8"
1 1/4 INCH 7 FEET 7 FEET 4 FEET 3/8"
1 1/2 INCH 7 FEET 7 FEET 4 FEET 1/2"
PIPE INSULATION ON INDOOR SYSTEMS
PIPE INSULATION SHALL BE AS MANUFACTURED BY ARMSTRONG, CERTAINTEED, KNAUF, MANSVILLE OR OWENS-CORNING. OWENS-CORNING NUMBERS ARE GIVEN TO ESTABLISH TYPES. ALL INSULATIONS, COVERINGS, VAPOR BARRIERS, ADHESIVES, ETC. SHALL BE CLASS A, MAXIMUM OF 25 FLAME SPREAD, 35 FUEL CONTRIBUTED AND 50 SMOKE DEVELOPED RATING. INSULATION SHALL HAVE VAPOR BARRIER AND BE UL RATED. INSULATION SHALL BE OWENS-CORNING FIBERGLAS ASJ-SSL II PIPE COVERING WITH FACTORY APPLIED DOUBLE PRESSURE SENSITIVE ADHESIVE SYSTEM TO PROVIDE POSITIVE CLOSURES AND VAPOR BARRIER INTEGRITY.
ALL LONGITUDINAL JOINTS SHALL BE SECURED WITH SELF SEALING LAPS. ALL TRANSVERSE JOINTS SHALL BE SECURED WITH SELF-SEALING BUTT STRIPS. BUTT STRIPS SHALL BE MINIMUM 3" WIDE. APPLY INSULATION TO PIPE WITH ALL JOINTS BUTTED TIGHTLY TOGETHER. FITTINGS, INCLUDING VALVES, FLANGES, UNIONS, ETC.
SHALL BE INSULATED WITH THE SAME THICKNESS AS THE REQUIRED PIPE INSULATION AND COVERED WITH ZESTON OR SPEEDLINE PVC FITTING COVER.
INSULATION THICKNESS SHALL BE AS FOLLOWS:
PIPING SYSTEM PIPE SIZE INSULATION THICKNESS INSULATION CONDUCTIVITY BTU IN H-FT2-F
CHILLED WATER UP THRU 3" 1" 0.28
4” AND LARGER 1½"
REFRIGERANT PIPING, CONDENSATE DRAIN PIPING AND/OR UNDERGROUND DOMESTIC WATER PIPING SHALL BE COVERED WITH ARMSTRONG TYPE AP ARMAFLEX INSULATION, 3/4" THICK, BLACK IN COLOR, CLOSED CELL WITH A FLAME SPREAD RATING OF 25 OR LESS AND A SMOKE DEVELOPED RATING OF 50 OR LESS. USE ARMSTRONG #520 ADHESIVE. ARMAFLEX INSULATION LOCATED OUTDOORS SHALL BE PAINTED WITH (2) COATS OF WHITE ARMSTRONG ARMAFLEX FINISH.
CLEAN ALL SURFACES BEFORE APPLYING COVERING. INSULATION SHALL BE CONTINUOUS THROUGH WALLS, FLOORS, CEILINGS, ETC. TERMINATE AND SEAL INSULATION AT BOTH ENDS OF UNINSULATED UNIONS AND FLANGES BY A NEAT 45 DEGREE BEVEL. INSTALL ALL INSULATION IN ACCORDANCE WITH MANUFACTURER'S
INSTALLATION INSTRUCTIONS.
PIPE IDENTIFICATION
ALL PIPING SHALL BE IDENTIFIED PER ANSI/OSHA OR OWNER'S STANDARDS WITH COLOR PIPE BANDS, IDENTIFICATION LABELS AND FLOW ARROWS. PIPES SHALL BE BANDED AND LABELED ON 10'-0" CENTERS ON CONTINUOUS LINES, AT EQUIPMENT CONNECTIONS, AT BOTH SIDES OF A WALL THROUGH WHICH PIPE PASSES AT EVERY BRANCH CONNECTION, ON PIPING WITHIN SIGHT OF AN ACCESS DOOR OR PANEL. SHOW SLOPE DIRECTIONAL ARROWS AT EACH IDENTIFICATION POINT. LABELS, FLOW ARROWS AND STENCIL AND PAINT SHALL BE 1" HIGH ON PIPING UP TO 2 1/2" AND SHALL BE 2" HIGH ON PIPE SIZES OF 3" AND LARGER. BANDS SHALL BE 1 1/2" WIDE.
LABELS SHALL BE AS MANUFACTURED BY SETON OR W.H. BRADY COMPANY OR EQUAL. VERIFY TYPE, SIZE AND COLORS OF PIPE IDENTIFICATION WITH OWNER.
GENERAL PLUMBING AND PIPING NOTES
WHERE DISSIMILAR MATERIAL PIPING ARE JOINED, DIELECTRIC NIPPLES SHALL BE UTILIZED AND SHALL BE NON-CONDUCTING FOR CONNECTION OF DISSIMILAR MATERIALS. DIELECTRIC NIPPLES SHALL BE SIMILAR TO VICTAULIC STYLE 47. A BRASS ADAPTOR DIELECTRIC UNION IS NOT ACCEPTABLE.
PIPING SHALL BE COMPLETE FROM SERVICE CONNECTION TO ALL FIXTURES, EQUIPMENT, OUTLETS, ETC.
ALL BRACKETS, CLEATS, PLATES, ANCHORS, ETC. REQUIRED TO SUPPORT FIXTURES OR PIPING SHALL BE FURNISHED.
SHUT OFF VALVES SHALL BE INSTALLED AT ALL BRANCH LINES OFF MAIN PIPING, OR WHERE MAINS DIVIDE/SEPARATE TO SERVE DIFFERENT AREAS, TO ALLOW ISOLATION OF ALL BRANCH PIPING AND SYSTEMS THEY SERVE SUCH AS TOILET ROOMS, AREAS OR WINGS OF THE BUILDING, ETC.
DUCTWORK
DUCTS, CASINGS, HOUSINGS, ETC. SHALL BE FABRICATED FROM, PRIME QUALITY, HOT DIP GALVANIZED STEEL SHEET AS RECOMMENDED IN THE LATEST ISSUES OF ASHRAE GUIDE AND SMACNA DUCT MANUALS IN VARIABLE AIR VOLUME SYSTEMS, WHEN USED. SUPPLY AIR DUCTS LOCATED BETWEEN AIR HANDLING SYSTEM AND VAV BOXES; DUCT CONSTRUCTION AND INSTALLATION SHALL MEET SMACNA STANDARDS FOR 6" W.C. FOR ALL OTHER SUPPLY AIR DUCTWORK AND EXHAUST AIR, RETURN AIR, OUTSIDE AIR INTAKE AND RELIEF AIR DUCTS, DUCT CONSTRUCTION AND INSTALLATION SHALL MEET SMACNA STANDARDS FOR 2" W.C.
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
MINIMUM OF BENDS USING LONG RADIUS BENDS ONLY.
DUCTWORK, PIPING AND EQUIPMENT SUPPORT
ATTACHMENTS OF MECHANICAL EQUIPMENT TO STRUCTURAL MEMBERS ARE THE RESPONSIBILITY OF THE INSTALLING TRADE. STRUCTURAL MEMBERS SHALL NOT BE FIELD CUT, WELDED OR OTHERWISE MODIFIED WITHOUT APPROVAL OF THE ARCHITECT/ENGINEER. ATTACHMENT TO STEEL JOIST SHALL BE MADE AT PANEL POINTS.
WHEN ROUTING PIPING OR DUCTWORK PERPENDICULAR TO JOIST, A SUPPORT SHALL BE PROVIDED AT EVERY STEEL JOIST; WHEN PARALLEL TO JOIST, A SUPPORT SHALL BE PROVIDED AT NO MORE THAN 6' ON CENTERS OR TWO PANEL BAYS. STRUCTURAL MEMBERS SHALL NOT BE OVERLOADED AS A RESULT OF ATTACHMENTS.
ATTACHMENT/EQUIPMENT LOADING FOR ALL TRADES RESULTING IN TOTAL LOAD GREATER THAN AN EQUIVALENT UNIFORM 5 PSF FOR ANY MEMBER SHALL BE SUBMITTED TO THE ARCHITECT/ENGINEER FOR REVIEW. MECHANICAL TRADES MAY CONTACT THE PROJECT STRUCTURAL ENGINEER AS REQUIRED FOR PANEL POINT LOCATION ASSISTANCE AND WELDER CERTIFICATION REQUIREMENTS. ELECTRICAL TRADES ARE STILL RESPONSIBLE FOR DESIGN, LAYOUT, AND FABRICATION AND INSTALLATION OF ELECTRICAL SUPPORTS AND SUPPORT ATTACHMENT METHODS. MECHANICAL TRADES SHALL SUBMIT ATTACHMENT METHODS TO THE STRUCTURAL
ENGINEER FOR REVIEW.
DUCT SEALANT
ALL DUCTWORK INCLUDING SUPPLY AIR, OUTSIDE AIR, RETURN AIR, EXHAUST AIR AND RELIEF AIR DUCT SYSTEMS SHALL HAVE ALL JOINTS SEALED. DUCTWORK DESIGNED AT SMACNA 6" PRESSURE SHALL MEET SMACNA CLASS "A" SEAL REQUIREMENTS. DUCTWORK DESIGNED AT SMACNA 2" PRESSURE SHALL MEET SMACNA
CLASS "C" SEAL REQUIREMENTS.
DUCT HANGERS
HORIZONTAL STEEL DUCTWORK SHALL BE SUPPORTED BY MEANS OF TRAPEZE BARS AND ROUND STEEL ROD OF SIZES LISTED BELOW. ROUND STEEL RODS SHALL BE ELECTRO-GALVANIZED ALL-THREAD ROD. HANGERS SHALL BE PROVIDED AT BOTH SIDES OF FLAT SIDED DUCTWORK FOR THE FULL HEIGHT OF DUCT. ROUND DUCTWORK SHALL BE PROVIDED WITH A BAND OF THE SAME SIZE AS THE HANGER TO COMPLETELY ENCIRCLE THE DUCT. BAND SHALL BE SECURED TO THE HANGER BY MEANS OF A MINIMUM 3/16" BOLT. MINIMUM DUCT HANGER SIZES SHALL BE AS LISTED BELOW
MIN. UPPER MINIMUM
DUCT ATTACHMENT STEEL MAXIMUM NO. OF TRAPEZE
SIZE RATING ROD SPACING HANGERS SHELF ANGLE
UP TO 16" 750 LBS. 3/8" 10' 2 1 1/2" X 1 1/2" X 3/16"
19" TO 36" 1000 LBS. 3/8" 10' 2 1 1/2" X 1 1/2" X 3/16"
37" TO 120" 3000 LBS. 3/8" 8' 2 2" X 2" X 1/4"
TEMPERATURE CONTROL SYSTEM
ALL NEW HVAC SYSTEMS SHALL BE CONNECTED TO OWNER'S EXISTING TRANE BUILDING MANAGEMENT SYSTEM (BMS). ALL COMPONENTS, PROGRAMS, CONTROLLERS, GRAPHICS, ETC SHALL BE FURNISHED, INSTALLED, AND PROGRAMMED BY TRANE. REFER TO DRAWINGS FOR ADDITIONAL INFORMATION.
SCOPE OF WORK THE TEMPERATURE CONTROL MANUFACTURER SHALL FURNISH INSTALLATION DEVICES, ELECTRONIC DAMPER ACTUATORS, ELECTRONIC CONTROL VALVES, RELAYS, SWITCHES, CONTROLLERS AND ALL NECESSARY WIRING, CABLING, DEVICES, HARDWARE, ETC. FOR A COMPLETE TEMPERATURE CONTROL SYSTEM .
TESTING, ADJUSTING AND BALANCING
TESTING, ADJUSTING AND BALANCING SHALL BE PERFORMED BY AN INDEPENDENT CERTIFIED AGENCY IN ACCORDANCE WITH AABC, ADC, ASHRAE III, NEBB AND SMACNA STANDARDS. FURNISH REPORT OF AIR SYSTEMS BALANCE REPORTS TO THE ENGINEER INDICATING DESIGN AND ACTUAL QUANTITIES, NAMEPLATE DATA, ETC.
ADJUST AIR HANDLING, DISTRIBUTION SYSTEMS, AIR INLETS AND OUTLETS, ETC. TO PROVIDE SUPPLY, RETURN, EXHAUST, OUTSIDE AIR AND RELIEF AIR QUANTITIES TO WITHIN 10% OF REQUIRED OR DESIGNED AIR QUANTITIES. VERIFY THAT SYSTEMS ARE COMPLETE AND OPERABLE BEFORE COMMENCING WORK. VERIFY SYSTEMS ARE STARTED AND OPERATING AT A SAFE AND NORMAL OPERATION, TEMPERATURE CONTROL SYSTEMS ARE INSTALLED COMPLETE AND OPERABLE, PROPER THERMAL OVERLOAD PROTECTION IS IN PLACE FOR ELECTRICAL EQUIPMENT, FINAL FILTERS ARE CLEAN AND IN PLACE, DUCT SYSTEMS ARE CLEAN OF DEBRIS, FANS ARE ROTATING CORRECTLY, FIRE AND VOLUME DAMPERS ARE IN PLACE AND IN OPEN POSITIONS, ACCESS DOORS ARE CLOSED AND DUCT END CAPS ARE IN PLACE, AIR OUTLETS ARE INSTALLED AND CONNECTED, DUCT SYSTEM LEAKAGE IS MINIMIZED, ETC. MEASURE AND RECORD ALL AIR MOVING EQUIPMENT, AIR INLETS AND OUTLETS
STATIC PRESSURES, RPM'S, ETC.
PARTIAL FIRST FLOOR - ELECTRICAL PLANN 1/4"=1'-0"
(989) 894-4300
714 East Midland Street Bay City, Michigan 48706 www.macmillanassociates.com
CONSULTING ENGINEERS
MacMILLAN ASSOCIATES
REV. DESCRIPTION BY DATE
0.5"0.0" 1.0" 2.0"1.5"2/ 3/
1:
A
M R
AI
N
EY
M
C C
AR
TH
Y (R
M C
C
AR
TH
Y@
M
AC
M
IL
LA
N
AS
SO
C
IA
TE
S.
C O
M
F:
\2
3- D
EL
TA
\2
4-
M
-W
IN
G A
N D
D
P R
IN
TE
R R
O O
M H
VA
C
S
TU
D Y\
-2
7- E-
E2 .1
EL
EC
TR
IC
AL
P
LA
N
PROJECT DESCRIPTION
SHEET DESCRIPTION
AL
L
RI
GH
TS
R
ES
ER
VE
D.
C
OP
YR
IG
HT
M ac M
IL
LA
N
AS
SO
CI
AT
ES
, I
NC
SHEET No.
JOB No.DRAWN BY
DESIGNED BY
APPROVED BY
ISSUED FOR BIDS 10.28.2025
DELTA COLLEGE
M-WING AND 3D PRINTER ROOM
HVAC RENOVATION
PARTIAL FIRST FLOOR -
ELECTRICAL PLAN, SPECIFICATIONS,
AND PANEL SCHEDULE
E2.1
2024-2307RLM
JWF
JWF
KEY PLANN
EX AHU-29
EX RF-29
FCU-M101
EF-M101
(ON ROOF)
EX PANEL
LP-H8
LP-H8-32
LP-H8-22
S
KEYED NOTES
PROVIDE A POWER CONNECTION TO THE
MECHANICAL UNIT WITH SELF EQUIPPED
DISCONNECT.
REMOVE AND REINSTALL LIGHT FIXTURE TO
ACCOMMODATE INSTALL OF NEW DUCTWORK.
ELECTRICAL SPECIFICATIONS
BASIC ELECTRICAL REQUIREMENTS
A. FURNISH ALL EQUIPMENT, MATERIALS, ARTICLES, ITEMS, OPERATIONS
OR METHODS LISTED, MENTIONED OR SCHEDULED ON DRAWINGS,
THESE SPECIFICATIONS, MANUFACTURER'S INSTALLATION
INSTRUCTIONS AND INCLUDE ALL LABOR, MATERIALS, EQUIPMENT AND
INCIDENTALS NECESSARY FOR COMPLETE INSTALLATION AND
OPERATION.
B. LAYOUT OF THE WORK
EXAMINE THE SITE AND ALL THE DRAWINGS BEFORE PROCEEDING WITH
THE LAYOUT AND INSTALLATION OF THIS WORK. CONFER AND
COOPERATE WITH THE OTHER TRADES ON THE JOB SO ALL PARTS WILL
BE INSTALLED IN PROPER RELATIONSHIP. PRECISE LOCATIONS OF
PARTS TO COORDINATE WITH OTHER WORK IS THE RESPONSIBILITY OF
THE CONTRACTOR.
C. INTERFERENCES
THE CONTRACTOR SHALL CONFER WITH OTHER TRADES REGARDING
LOCATION OF EQUIPMENT, FIXTURES, CONDUIT, SWITCHES, OUTLETS,
ETC., IN ORDER THAT THERE MAY BE NO INTERFERENCE IN THE
INSTALLATION OF THE WORK OF ANY TRADES OR DELAY IN THE
PROGRESS OF ANY WORK.
D. MATERIALS AND WORKMANSHIP
ALL MATERIALS AND EQUIPMENT FURNISHED FOR INSTALLATION ON
THIS PROJECT SHALL BE NEW AND IN STRICT ACCORDANCE WITH THIS
SPECIFICATION. ALL PACKAGED MATERIALS SHALL BE DELIVERED IN
THE ORIGINAL CONTAINERS WHICH SHOW THE MANUFACTURER'S NAME
AND THE IDENTIFYING DESIGNATIONS AS TO SIZE, QUALITY, ETC.
MATERIALS DELIVERED TO THE JOB IN UNMARKED OR MUTILATED
PACKAGES WILL BE ORDERED TO BE REMOVED FROM THE SITE AT
ONCE. MATERIALS OR EQUIPMENT JUDGED AS "DAMAGED" BY THE
ARCHITECT OR ENGINEER SHALL BE REMOVED FROM THE JOB. ALL
ELECTRICAL EQUIPMENT SHALL BEAR THE UNDERWRITER'S LABEL.
E. GUARANTEES
ALL EQUIPMENT AND WORK PERFORMED SHALL BE GUARANTEED FOR
ONE YEAR FROM TIME OF SUBSTANTIAL COMPLETION OF PROJECT,
UNLESS DIRECTED OTHERWISE IN DIVISION 1.
F. SUBMITTALS
SUBMIT ELECTRONIC FILES.
PROPOSED PRODUCTS LIST: INCLUDE PRODUCTS SPECIFIED IN THE
FOLLOWING SECTIONS
G. REGULATORY REQUIREMENTS
CONFORM TO APPLICABLE BUILDING CODE.
CONFORM TO REQUIREMENTS OF NFPA 70, 2023 NATIONAL ELECTRIC
CODE, 2021 MICHIGAN BUILDING CODE, 2023 STATE OF MICHIGAN
ELECTRICAL CODE, 2009 ANSI 117.1, 2021 MICHIGAN ENERGY CODE, AND
LOCAL CODES.
EQUIPMENT: U.L. TESTED AND APPROVED FOR ITS PURPOSE.
THE ELECTRICAL CONTRACTOR SHALL OBTAIN AND PAY FOR ALL
PERMITS AND INSPECTION FEES. COPIES OF THE CERTIFICATE OF
INSPECTION ARE TO BE PROVIDED TO THE OWNER AFTER FINAL
INSPECTION AND APPROVAL FROM AUTHORITIES HAVING JURISDICTION.
H. PROJECT/SITE CONDITIONS
ALL BIDDERS SHALL PERSONALLY INSPECT THE SITE AND ACQUAINT
THEMSELVES WITH ALL EXISTING CONDITIONS INVOLVED IN EXECUTION
OF THIS CONTRACT, AND MAKE ALL NECESSARY MEASUREMENTS. NO
"EXTRA" WILL BE CONSIDERED FOR ADDITIONAL WORK REQUIRED
BECAUSE OF BIDDER'S FAILURE TO DO SO.
I. TEMPORARY SERVICES
THE CONTRACTOR SHALL PROVIDE AND MAINTAIN WIRING FOR ALL
INTERIOR CONSTRUCTION LIGHTING AND POWER TO MEET OSHA
STANDARDS. CONTRACTOR SHALL PROVIDE AND MAINTAIN ALL
REQUIRED LAMPS AND GUARDS. CONTRACTOR'S POWER TOOLS,
CORDS, ETC. SHALL BE IN STRICT ACCORDANCE WITH NATIONAL
ELECTRICAL CODE 2023, ARTICLE 590.
J. OPERATION AND MAINTENANCE MANUALS
TWO (2) BOUND SETS OF OPERATING AND MAINTENANCE MANUALS ARE
TO BE SUBMITTED TO THE ARCHITECT/ENGINEER FOR APPROVAL.
MANUALS ARE TO INCLUDE ELECTRICAL DISTRIBUTION PARTS LISTS
AND ALL OTHER PARTS LISTS AND MAINTENANCE PROCEDURES AS
WELL AS OPERATING INSTRUCTIONS ON ALL EQUIPMENT SUPPLIED.
CONDUIT
A. METAL CONDUIT.
B. LIQUIDTIGHT FLEXIBLE RIGID STEEL CONDUIT.
C. ELECTRICAL METALLIC TUBING.
D. NONMETAL CONDUIT. SCH 40 OR HDPE.
E. 3/4" MINIMUM SIZE.
F. UNDERGROUND INSTALLATIONS:
1. USE SCHEDULE 40 PVC NON-METALLIC CONDUIT OR SEAMLESS
HDPE DIRECT BURIAL CONDUIT.
G. EXTERIOR LOCATIONS: USE GALVANIZED RIGID STEEL CONDUIT FOR
ALL OUTSIDE INSTALLATION. USE APPLICABLE FITTINGS.
H. DRY INTERIOR LOCATIONS:
1. USE EMT TYPE CONDUIT, SET SCREW COUPLINGS AND
CONNECTORS.
2. USE RIGID STEEL FOR DRY INTERIOR WITH APPLICABLE FITTINGS AS
NOTED OR SHOWN ON THE DRAWINGS.
I. ONE 1" MINIMUM SIZE FOR DATA.
INSTALLATION
A. INSTALL NONMETALLIC CONDUIT IN ACCORDANCE WITH
MANUFACTURER'S INSTRUCTIONS.
B. ARRANGE SUPPORTS TO PREVENT MISALIGNMENT DURING WIRING
INSTALLATION.
C. SUPPORT CONDUIT USING COATED STEEL OR MALLEABLE IRON
STRAPS, LAY-IN ADJUSTABLE HANGERS, CLEVIS HANGERS, AND SPLIT
HANGERS.
D. GROUP RELATED CONDUITS; SUPPORT USING CONDUIT RACK.
CONSTRUCT RACK USING STEEL CHANNEL; PROVIDE SPACE ON EACH
FOR 25 PERCENT ADDITIONAL CONDUITS.
E. FASTEN CONDUIT SUPPORTS TO BUILDING STRUCTURE AND SURFACES.
F. DO NOT SUPPORT CONDUIT WITH WIRE OR PERFORATED PIPE STRAPS.
REMOVE WIRE USED FOR TEMPORARY SUPPORTS.
G. DO NOT ATTACH CONDUIT TO CEILING SUPPORT WIRES.
H. ARRANGE CONDUIT TO MAINTAIN HEADROOM AND PRESENT NEAT
APPEARANCE.
I. ROUTE CONDUIT PARALLEL AND PERPENDICULAR TO WALLS OR
BUILDING CENTERLINES.
J. ROUTE CONDUIT INSTALLED ABOVE ACCESSIBLE CEILINGS PARALLEL
AND PERPENDICULAR TO WALLS.
K. MAINTAIN ADEQUATE CLEARANCE BETWEEN CONDUIT AND PIPING.
INTERFACE WITH OTHER PRODUCTS
A. USE FIRESTOP CAULK WHERE CONDUIT PASSES THROUGH FIRE RATED
FLOORS AND WALLS. REFER TO ARCHITECTURAL PLANS FOR
LOCATIONS.
BUILDING WIRE AND CABLE
A. BUILDING WIRE AND CABLE.
B. METAL CLAD CABLE (MC).
C. DESCRIPTION: SINGLE CONDUCTOR INSULATED WIRE.
D. CONDUCTOR: COPPER.
E. INSULATION VOLTAGE RATING: 600 VOLTS.
F. INSULATION: TYPE THHN/THWN 75ºC.
INSTALLATION
A. USE CONDUCTOR SIZE NOT SMALLER THAN 12 AWG FOR POWER AND
LIGHTING CIRCUITS.
B. USE 10 AWG CONDUCTORS FOR 20 AMPERE, 120 VOLT BRANCH
CIRCUITS LONGER THAN 100 FEET.
C. NEATLY TRAIN AND LACE WIRING INSIDE BOXES, EQUIPMENT, AND
PANELBOARDS.
D. ALL POWER WIRING SHALL BE INSTALLED IN CONDUIT.
FIELD QUALITY CONTROL
A. VERIFY CONTINUITY OF EACH BRANCH CIRCUIT CONDUCTOR.
BOXES
A. BRANCH DEVICE BOXES. SHEET METAL BOXES: AS THE GENERAL
PROJECT REQUIREMENT FOR BRANCH POWER AND LOW VOLTAGE
SYSTEMS. USE 4" SQUARE STEEL BOX, WITH SINGLE GANG DEVICE.
NON-METALLIC BOX IS NOT ACCEPTABLE IN FIRE RATED WALLS AND OR
GENERAL PROJECT INSTALLATION.
B. PULL AND JUNCTION BOXES.
This is the start of the file's text. The full file is on GovTribe.