This is an architectural construction document for Data Closets CTAE Media prepared by LS3P Associates Ltd. for the Savannah-Chatham County Public School System's new K-12 multi-school facility. The document provides enlarged plan details (Drawing E-500) specifying telecommunications and data infrastructure requirements for two data closets (DATA 113.1 and DATA 213.1). Key specifications include provisions for UPS power homerun cables, plywood backboards with fire-retardant coatings, telecommunications main and secondary grounding busbars (TMGB and TGB), 4-inch EMT conduit sleeves with bushing and bonding requirements, 18-inch wide ladder rack/cable tray systems, telephone demarcation points serving emergency 911 backup lines, fire alarm systems, intrusion detection, and elevator communications, along with fire alarm control panel labeling and breaker lock requirements. The construction drawings are dated October 9, 2020, with revision date of February 18, 2021, and reference the associated RFP 22-28 for Data Cabling for New Groves K-12 School (ERATE eligible) project.

The document serves as detailed technical specifications to support the competitive bid process for data cabling infrastructure installation. All telecommunications grounding, bonding, conduit routing, and cable management systems must comply with contract specifications and industry standards. The specifications coordinate with electrical site plans and require sealed penetrations at ceiling and floor locations. The architectural plans establish the technical baseline requirements that bidders must address in their proposals for the ERATE-eligible data cabling project for the Savannah-Chatham County Public School System.

Text of this file

DATA

113.1

NOTE 3

(TYP.)

NOTE 1

NOTE 7

NOTE 2 NOTE 2 NOTE 2

NOTE 5

SEE 7/T-002

NOTE 9

(TYP.)

FACP

NOTE 4

ELM1-2

NOTE 10

151311

81012

ELM1-11,13,15

ELM1-4,6,8

ELM1-16,18

ELM1-10,12,14

ELM1-17

DATA

213.1

NOTE 3

(TYP.)

NOTE 1

NOTE 2 NOTE 2 NOTE 2

NOTE 6

SEE 8/T-002

NOTE 9

(TYP.)

NOTE 8

AUX

ELM2-25

NOTE 10

171921

ELM2-13,15,17

ELM2-9,11

ELM2-7

ELM2-1,3,5

ELM2-19,21,23

CHECKED BY:

DRAWN BY:

DATE:

PROJECT:

REVISIONS:

MEMBERS OF THE AMERICAN INSTITUTE OF ARCHITECTS

A

2 3 4 5 6

B

C

D

E

COPYRIGHT 2019 ALL RIGHTS RESERVED

PRINTED OR ELECTRONIC DRAWINGS AND

DOCUMENTATION MAY NOT BE REPRODUCED

IN ANY FORM WITHOUT WRITTEN PERMISSION

FROM LS3P ASSOCIATES LTD.

WWW.LS3P.COM

SAVANNAH, GEORGIA 31401

TEL. 912.695.2111 FAX 912.298.0206

321 WEST CONGRESS STREET SUITE 301

/1

/2

:5 :5

P

M

B

IM

/S C

C P

S S

N e w

K -1

M u lt i- S c h o o l/ E

L E

C G ro v e s K

C

T A

E v .r v t

5201-192070

10/09/2020

PAA

WOW

ENLARGED

PLANS

E-500

NEW K-12

MULTI-SCHOOL

625-0518

CONSTRUCTION SET

SAVANNAH-CHATHAM

COUNTY PUBLIC SCHOOL

SYSTEM

SCALE: 1/2" = 1'-0"E-500

1 ENLARGED DATA 113.1

NOTES

1. PROVIDE 4#10 HOMERUN, 3/4" C. FOR FUTURE UPS POWER.

2. RECEPTACLE SHALL BE INSTALLED IN THE TELECOMMUNICATION RACK.

COORDINATE EXACT LOCATION WITH TELECOMMUNICATION RACK INSTALLER.

3. PLYWOOD BACKBOARD: PROVIDE 3*4" THICK, FIRE RETARDANT GRADE A/C

PLYWOOD BACKBOARD, COAT PLYWOOD WITH TWO COATES LIGHT GRAY FIRE

RETARDANT PAINT. FIRE RATING ON PLYWOOD SHALL NOT BE PAINTED OVER SO

AT LEAST ONE MARKING SHALL BE VISIBLE ON EACH PIECE OF PLYWOOD. PROVIDE

3/4" X 3/4" ALUMINUM ANGLE FRAME AFTER PAINTING. PROVIDE OUTLET BOX

EXTENSION RING AS REQUIRED FOR DEVICES INSTALLED IN WALL RECEIVING

PLYWOOD FOR FLUSH MOUNTING WITH WOOD SURFACE.

4. TELEPHONE DEMARC: PROVIDE TELEPHONE CABLE AND 66-BLOCK FOR

FOLLOWING: EMERGENCY 911 BACKUP LINES (2), FIRE ALARM (1), INTRUSION

DETECTION ALARM (1), ELEVATOR (2). COORDINATE WITH ELECTRIC SITE PLAN FOR

ADDITIONAL CONDUIT ROUTING INFORMATION.

5. PROVIDE 12" TELECOMMUNICATIONS MAIN GROUNDING BUSBAR (TMGB). TMGB

SHALL BE MADE OF 1/4" THICK ELECTROLYTIC, TIN-PLATED COPPER AND UL

LISTED.

6. PROVIDE 12" TELECOMMUNICATIONS GROUNDING BUSBAR (TGB). TGB SHALL BE

MADE OF 1/4" THICK ELECTROLYTIC, TIN-PLATED COPPER AND UL LISTED.

7. PROVIDE (2) 4" EMT CONDUIT SLEEVES UP THROUGH CEILING. BOTH ENDS OF

CONDUIT SLEEVES ARE TO BE BUSHED. ALL PENETRATIONS ARE TO BE SEALED IN

ACCORDANCE WITH CONTRACT SPECIFICATIONS. ALL CONDUIT SLEEVES ARE TO

BE BONDED TO THE TELECOMMUNICATIONS GROUNDING AND BONDING SYSTEM

PER TYPICAL TELECOM METALLIC CONDUIT BONDING DETAIL.

8. (2) 4" EMT CONDUIT SLEEVES UP THROUGH FLOOR. BOTH ENDS OF CONDUIT

SLEEVES ARE TO BE BUSHED. ALL PENETRATIONS ARE TO BE SEALED IN

ACCORDANCE WITH CONTRACT SPECIFICATIONS. ALL CONDUIT SLEEVES ARE TO

BE BONDED TO THE TELECOMMUNICATIONS GROUNDING AND BONDING SYSTEM

PER TYPICAL TELECOM METALLIC CONDUIT BONDING DETAIL.

9. PROVIDE 18" WIDE LADDER RACK/CABLE TRAY. CABLE TRAY SHALL BE SECURED

TO WALL OR SECURELY SUSPENDED FROM CEILING STRUCTURE. PROVIDE

LENGTH AND QUANTITY PER PLANS.

10. LABEL BREAKER WITH RED NAMEPLATE “FIRE ALARM CONTROL PANEL”. LABEL

FIRE ALARM CONTROL PANEL WITH CIRCUIT NUMBER SERVING IT. PROVIDE

BREAKER LOCK FOR CIRCUIT BREAKER.

SCALE: 1/2" = 1'-0"E-500

2 ENLARGED DATA 213.1

No. 32283

R T

PROFESSIONAL

OE

G

G I A

NE E

R

IG

N E

SIGE

R

ERE

D

O.

Y

W

E O

L

M

S

M

E

A

W

C K

No. Description Date

Other files

File Type Posted
Award Information —
RFP 22-28 Sample Contract —
Data Security CTAE Media —
Data Closet Main Bldg —
BACKBONE CABLING —
RFP 22-28 Solicitation Documen —
Electrical CTAE Media —
RFP 22-28 Addendum 1 —
Technology Design Plan —
HORIZONTAL CABLING —