This file contains electrical construction drawings for data closet installations in the New Groves K-12 Multi-School project for the Savannah-Chatham County Public School System (SCCPSS). The drawings, prepared by LS3P Associates Ltd. and dated October 9, 2020, detail the layout and specifications for multiple enlarged data rooms distributed across the facility. The project specifications include the installation of telecommunications infrastructure components such as plywood backboards with fire-retardant paint, telecommunications grounding busbars (TMGB and TGB), 4-inch EMT conduit sleeves with bushings, 18-inch wide ladder racks/cable trays, and various electrical panel circuits for backup power generation. Multiple data rooms are documented including Data 1017, IDF 1311.1, IDF 2309.1, Data 2206, IDF 3309.1, Data 3221.1, Data 1518, Data 2512, Data 1726, Data 2716, and Data 3407, each with specific circuit designations from designated electrical load panels (ELS12 through ELS34).
The drawings specify detailed requirements for future UPS power provisions through 4#10 homerun cables with 3/4-inch conduit, telecommunications receptacles coordinated with rack installers, and telephone demarc provisions accommodating emergency 911 backup lines, fire alarm, intrusion detection alarm, and elevator systems. All conduit sleeves require bushing on both ends with proper sealing per contract specifications and bonding to the telecommunications grounding and bonding system. The electrical circuits are designated for generator backup power distribution across multiple panels, with specific circuit numbers identified for each data room location. The project is associated with RFP 22-28 for Data Cabling for New Groves K-12 School, designated as E-Rate eligible, indicating federal funding eligibility through the Education Rate Discount Program.
Text of this file
GENERATOR BACKUP CIRCUITS
IN THIS AREA SHALL BE FED
FROM PANEL: ELS12, UNO
DATA
NOTE 3
(TYP.)
NOTE 1 NOTE 6
/SEE 8 T-002
ELS12-10,12,14
ELS12-4,6,8
NOTE 2
NOTE 2
NOTE 2
ELS12-18,20
ELS12-16
NOTE 7
NOTE 9
(TYP.)
IDF
1311.1
31 31
33 33
41 39 37
/SEE 8 T-002
NOTE 6
NOTE 2 NOTE 2 NOTE 2
NOTE 3
(TYP.)
GENERATOR BACKUP CIRCUITS
IN THIS AREA SHALL BE FED
FROM PANEL: ELS13, UNO
ELS13-31,33,35
ELS13-37,39,41
NOTE 1
ELS13-43,45
NOTE 7
NOTE 9
(TYP.)
IDF
2309.1
3 7
5 5
9 11 13
/SEE 8 T-002
NOTE 6
NOTE 2 NOTE 2 NOTE 2
NOTE 3
(TYP.)
GENERATOR BACKUP CIRCUITS
IN THIS AREA SHALL BE FED
FROM PANEL: ELS23, UNO
ELS23-3,5,7
ELS23-9,11,13
NOTE 1
ELS23-27,29
NOTE 7
NOTE 8
NOTE 9
(TYP.)
NOTE 3
(TYP.)
NOTE 1 NOTE 6
/SEE 8 T-002
1 7
GENERATOR BACKUP CIRCUITS
IN THIS AREA SHALL BE FED
FROM PANEL: ELS22, UNO
ELS22-1,3
ELS22-5,7
ELS22-9,11,13
NOTE 2
NOTE 2
NOTE 2
ELS22-27,29
DATA
NOTE 7
NOTE 8
NOTE 9
(TYP.)
IDF
3309.1
2 2
4 4
8 10 12
/SEE 8 T-002
NOTE 6
NOTE 2 NOTE 2 NOTE 2
NOTE 3
(TYP.)
GENERATOR BACKUP CIRCUITS
IN THIS AREA SHALL BE FED
FROM PANEL: ELS33, UNO
ELS33-2,4,6
ELS33-8,10,12
NOTE 1
ELS33-14,16
NOTE 8
NOTE 9
(TYP)
DATA
3221.1
NOTE 3
(TYP.)
NOTE 1
NOTE 6
/SEE 8 T-002
35 29
GENERATOR BACKUP CIRCUITS
IN THIS AREA SHALL BE FED
FROM PANEL: ELS32, UNO
ELS32-31,33,35
NOTE 2
NOTE 2
NOTE 2
ELS32-36,38
ELS32-29
ELS32-30,32,34
NOTE 8
NOTE 9
(TYP.)
No. 32283
R T
PROFESSIONAL
OE
G
G I A
NE E
R
IG
N E
SIGE
R
ERE
D
O.
Y
W
E O
L
M
S
M
E
A
W
C K
CHECKED BY:
DRAWN BY:
DATE:
PROJECT:
REVISIONS:
MEMBERS OF THE AMERICAN INSTITUTE OF ARCHITECTS
A
2 3 4 5 6
B
C
D
E
COPYRIGHT 2019 ALL RIGHTS RESERVED
PRINTED OR ELECTRONIC DRAWINGS AND
DOCUMENTATION MAY NOT BE REPRODUCED
IN ANY FORM WITHOUT WRITTEN PERMISSION
FROM LS3P ASSOCIATES LTD.
WWW.LS3P.COM
SAVANNAH, GEORGIA 31401
TEL. 912.695.2111 FAX 912.298.0206
321 WEST CONGRESS STREET SUITE 301
/1
/2
:4 :4
A
M
B
IM
/S C
C P
S S
N e w
K -1
M u lt i- S c h o o l/ E
L E
C G ro v e s K
K v .r v t
5201-192070
10/09/2020
GJC/MRC
WOW
ENLARGED
DATA ROOMS
E-502
NEW K-12
MULTI-SCHOOL
625-0518
CONSTRUCTION SET
SAVANNAH-CHATHAM
COUNTY PUBLIC SCHOOL
SYSTEM
1/2" = 1'-0"
ENLARGED DATA 1017
E1
1/2" = 1'-0"
ENLARGED IDF 1311.1
A1
1/2" = 1'-0"
ENLARGED IDF 2309.1
A2
1/2" = 1'-0"
ENLARGED DATA 2206
E2
1/2" = 1'-0"
ENLARGED IDF 3309.1
A3
1/2" = 1'-0"
ENLARGED DATA 3221.1
E3
NOTES
1. PROVIDE 4#10 HOMERUN, 3/4" C. FOR FUTURE UPS POWER.
2. RECEPTACLE SHALL BE INSTALLED IN THE TELECOMMUNICATION RACK.
COORDINATE EXACT LOCATION WITH TELECOMMUNICATION RACK INSTALLER.
3. PLYWOOD BACKBOARD: PROVIDE 3/4" THICK, FIRE RETARDANT GRADE A/C
PLYWOOD BACKBOARD, COAT PLYWOOD WITH TWO COATS LIGHT GRAY FIRE
RETARDANT PAINT. FIRE RATING ON PLYWOOD SHALL NOT BE PAINTED OVER SO
AT LEAST ONE MARKING SHALL BE VISIBLE ON EACH PIECE OF PLYWOOD. PROVIDE
3/4" X 3/4" ALUMINUM ANGLE FRAME AFTER PAINTING. PROVIDE OUTLET BOX
EXTENSION RING AS REQUIRED FOR DEVICES INSTALLED IN WALLS RECEIVING
PLYWOOD FOR FLUSH MOUNTING WITH WOOD SURFACE.
4. TELEPHONE DEMARC: PROVIDE TELEPHONE CABLE AND 66-BLOCK FOR THE
FOLLOWING: EMERGENCY 911 BACKUP LINES (2), FIRE ALARM (1), INTRUSION
DETECTION ALARM (1), ELEVATOR (2).
5. PROVIDE 12" TELECOMMUNICATIONS MAIN GROUNDING BUSBAR (TMGB). TMGB
SHALL BE MADE OF 1/4" THICK ELECTROLYTIC, TIN-PLATED COPPER AND UL
LISTED.
6. PROVIDE 12" TELECOMMUNICATIONS GROUNDING BUSBAR (TGB). TGB SHALL BE
MADE OF 1/4" THICK ELECTROLYTIC, TIN-PLATED COPPER AND UL LISTED.
7. PROVIDE (2) 4" EMT CONDUIT SLEEVES UP THROUGH CEILING. BOTH ENDS OF
CONDUIT SLEEVES ARE TO BE BUSHED. ALL PENETRATIONS ARE TO BE SEALED IN
ACCORDANCE WITH CONTRACT SPECIFICATIONS. ALL CONDUIT SLEEVES ARE TO
BE BONDED TO THE TELECOMMUNICATIONS GROUNDING AND BONDING SYSTEM
PER TYPICAL TELECOM METALLIC CONDUIT BONDING DETAIL.
8. PROVIDE (2) 4" EMT CONDUIT SLEEVES UP THROUGH FLOOR. BOTH ENDS OF
CONDUIT SLEEVES ARE TO BE BUSHED. ALL PENETRATIONS ARE TO BE SEALED IN
ACCORDANCE WITH CONTRACT SPECIFICATIONS. ALL CONDUIT SLEEVES ARE TO
BE BONDED TO THE TELECOMMUNICATIONS GROUNDING AND BONDING SYSTEM
PER TYPICAL TELECOM METALLIC CONDUIT BONDING DETAIL.
9. PROVIDE 18" WIDE LADDER RACK/CABLE TRAY AT 8'-0" AFF. CABLE TRAY SHALL BE
SECURED TO WALL OR SECURELY SUSPENDED FROM CEILING STRUCTURE.
PROVIDE LENGTH AND QUANTITY PER PLANS.
No. Description Date
J
DATA
NOTE 3
(TYP.)
NOTE 2 NOTE 2
NOTE 1
GENERATOR BACKUP CIRCUITS
IN THIS AREA SHALL BE FED
FROM PANEL: ELS15, UNO
ELS15-9,11
ELS15-13,15
NOTE 6
/SEE 8 T-002
NOTE 7
ELS15-3,5,7
NOTE 9
(TYP.)
DATA
NOTE 3
(TYP.)
NOTE 2 NOTE 2
NOTE 1
14 12
GENERATOR BACKUP CIRCUITS
IN THIS AREA SHALL BE FED
FROM PANEL: ELS25, UNO
ELS25-12,14
ELS25-2,4
NOTE 6
/SEE 8 T-002
ELS25-6,8,10
NOTE 8
NOTE 9
(TYP.)
DATA
NOTE 3
(TYP.)
NOTE 6
/SEE 8 T-002
NOTE 2 NOTE 2 NOTE 2
NOTE 1
7 9 11
ELS17-1,3,5
ELS17-7,9,11
ELS17-13,15
GENERATOR BACKUP CIRCUITS
IN THIS AREA SHALL BE FED
FROM PANEL: ELS17, UNO
NOTE 9
(TYP.)
NOTE 7
DATA
NOTE 3
(TYP.)
/SEE 8 T-002
NOTE 2 NOTE 2 NOTE 2
7 9 11
ELS27-1,3,5
ELS27-7,9,11
ELS27-23,25
NOTE 9
(TYP.)
NOTE 1
NOTE 8
NOTE 6
9 11
/SEE 8 T-002
NOTE 6
NOTE 3
(TYP.)
NOTE 1
NOTE 2 NOTE 2
GENERATOR BACKUP CIRCUITS
IN THIS AREA SHALL BE FED
FROM PANEL: ELS34, UNO
ELS34-7,9,11 ELS34-13,15
ELS34-17,19
STOR
NOTE 8
NOTE 9
(TYP.)
GENERATOR BACKUP CIRCUITS
IN THIS AREA SHALL BE FED
FROM PANEL: ELS29, UNO
NOTE 1
NOTE 6
NOTE 3
(TYP.)
/SEE 8 T-002
ELS29-1,3,5
ELS29-7,9
NOTE 2
NOTE 8
NOTE 9
(TYP.)
DATA
1914.1
ELS19-2,4,6
ELS19-8,10
GENERATOR BACKUP CIRCUITS
IN THIS AREA SHALL BE FED
FROM PANEL: ELS19, UNO
NOTE 6
/SEE 8 T-002
NOTE 1
NOTE 3
(TYP.)
NOTE 9
(TYP.)
NOTE 2
NOTE 3
(TYP.)
NOTE 5
NOTE 2
NOTE 1
ELS28-1,3
ELS28-5,7,9
ELS28-11,13
NOTE 2 2
ELS28-2,4
NOTE 2 6
ELS28-6,8
NOTE 2 10
ELS28-10,12
NOTE 2 14
ELS28-14,16
NOTE 4
/SEE 7 T-002
F A
C P
DACS
ELS28-18
ELS28-20
22 24 26
ELS28-22,24,26
STOR
NOTE 5
/SEE 7 T-002
NOTE 9
(TYP.)
INTERCOM SYSTEM
HEADEND EQUIP.
NOTE 2
NOTE 2
22 22
GENERATOR BACKUP CIRCUITS
IN THIS AREA SHALL BE FED
FROM PANEL: ELS16, UNO
ELS16-16,18
ELS16-20,22
NOTE 3
(TYP)
NOTE 1
ELS16-24,26
/SEE 8 T-002
TABLE/ CHAIR STOR
NOTE 6
NOTE 9
(TYP.)
No. 32283
R T
PROFESSIONAL
OE
G
G I A
NE E
R
IG
N E
SIGE
R
ERE
D
O.
Y
W
E O
L
M
S
M
E
A
W
C K
CHECKED BY:
DRAWN BY:
DATE:
PROJECT:
REVISIONS:
MEMBERS OF THE AMERICAN INSTITUTE OF ARCHITECTS
A
2 3 4 5 6
B
C
D
E
COPYRIGHT 2019 ALL RIGHTS RESERVED
PRINTED OR ELECTRONIC DRAWINGS AND
DOCUMENTATION MAY NOT BE REPRODUCED
IN ANY FORM WITHOUT WRITTEN PERMISSION
FROM LS3P ASSOCIATES LTD.
WWW.LS3P.COM
SAVANNAH, GEORGIA 31401
TEL. 912.695.2111 FAX 912.298.0206
321 WEST CONGRESS STREET SUITE 301
/1
/2
:4 :1
A
M
B
IM
/S C
C P
S S
N e w
K -1
M u lt i- S c h o o l/ E
L E
C G ro v e s K
K v .r v t
5201-192070
10/09/2020
GJC/MRC
WOW
ENLARGED
DATA ROOMS
E-503
NEW K-12
MULTI-SCHOOL
625-0518
CONSTRUCTION SET
SAVANNAH-CHATHAM
COUNTY PUBLIC SCHOOL
SYSTEM
1/2" = 1'-0"
ENLARGED DATA 1518
B1 1/2" = 1'-0"
ENLARGED DATA 2512
B2
1/2" = 1'-0"
ENLARGED DATA 1726
1/2" = 1'-0"
ENLARGED DATA 2716
1/2" = 1'-0"
ENLARGED DATA 3407
1. PROVIDE 4#10 HOMERUN, 3/4" C. FOR FUTURE UPS POWER.
2. RECEPTACLE SHALL BE INSTALLED IN THE TELECOMMUNICATION RACK.
COORDINATION EXACT LOCATION WITH TELECOMMUNICATION RACK INSTALLER.
3. PLYWOOD BACKBOARD: PROVIDE 3/4" THICK, FIRE RETARDANT GRADE A/C
PLYWOOD BACKBOARD, COAT PLYWOOD WITH TWO COATS LIGHT GRAY FIRE
RETARDANT PAINT. FIRE RATING ON PLYWOOD SHALL NOT BE PAINTED OVER SO
AT LEAST ONE MARKING SHALL BE VISIBLE ON EACH PIECE OF PLYWOOD. PROVIDE
3/4" X 3/4" ALUMINUM ANGLE FRAME AFTER PAINTING. PROVIDE OUTLET BOX
EXTENSION RING AS REQUIRED FOR DEVICES INSTALLED IN WALLS RECEIVING
PLYWOOD FOR FLUSH MOUNTING WITH WOOD SURFACE.
4. TELEPHONE DEMARC: PROVIDE TELEPHONE CABLE AND 66-BLOCK FOR THE
FOLLOWING: EMERGENCY 911 BACKUP LINES (2), FIRE ALARM (1), INTRUSION
DETECTION ALARM (1), ELEVATOR (2).
5. PROVIDE 12" TELECOMMUNICATIONS MAIN GROUNDING BUSBAR (TMGB). TMGB
SHALL BE MADE OF 1/4" THICK ELECTROLYTIC, TIN-PLATED COPPER AND UL
LISTED.
6. PROVIDE 12" TELECOMMUNICATIONS GROUNDING BUSBAR (TGB). TGB SHALL BE
MADE OF 1/4" THICK ELECTROLYTIC, TIN-PLATED COPPER AND UL LISTED.
7. PROVIDE (2) 4" EMT CONDUIT SLEEVES UP THROUGH CEILING. BOTH ENDS OF
CONDUIT SLEEVES ARE TO BE BUSHED. ALL PENETRATIONS ARE TO BE SEALED IN
ACCORDANCE WITH CONTRACT SPECIFICATIONS. ALL CONDUIT SLEEVES ARE TO
BE BONDED TO THE TELECOMMUNICATIONS GROUNDING AND BONDING SYSTEM
PER TYPICAL TELECOM METALLIC CONDUIT BONDING DETAIL.
8. PROVIDE (2) 4" EMT CONDUIT SLEEVES UP THROUGH FLOOR. BOTH ENDS OF
CONDUIT SLEEVES ARE TO BE BUSHED. ALL PENETRATIONS ARE TO BE SEALED IN
ACCORDANCE WITH CONTRACT SPECIFICATIONS. ALL CONDUIT SLEEVES ARE TO
BE BONDED TO THE TELECOMMUNICATIONS GROUNDING AND BONDING SYSTEM
PER TYPICAL TELECOM METALLIC CONDUIT BONDING DETAIL.
9. PROVIDE 18" WIDE LADDER RACK/CABLE TRAY. CABLE TRAY SHALL BE SECURED
TO WALL OR SECURELY SUSPENDED FROM CEILING STRUCTURE. PROVIDE
LENGTH AND QUANTITY PER PLANS.
NOTES
1/2" = 1'-0"
ENLARGED DATA 2908
1/2" = 1'-0"
ENLARGED DATA 1914.1
1/2" = 1'-0"
ENLARGED DATA 2835
1/4" = 1'-0"
ENLARGED DATA ROOM AREA 1834
No. Description Date
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
File details come from the government source that posted it. Updated .