Construction_Plans.pdf
PDF 291 KB Posted
- Solicitation number
- 0000033414
- Issued by
- Lassen County, California
About this file
This is a construction plan document from the California Department of Fish and Wildlife for the Honey Lake Wildlife Area Mitigation Pump Repair project in Lassen County. The project involves replacement of irrigation pump components and miscellaneous improvements, including replacing the well pump motor and housing, discharge head and flange, pump head gasket, line shaft components, and various other underground pump components. The plans detail specific technical requirements for a 100 HP, 460V, 3-phase well pump that must operate at 1170 RPM with varying flow rates from 2050-4000 USGPM at different head pressures.
The plans include detailed technical drawings showing equipment pad layouts, pump components, electrical service configurations, and underground pump components. The project must conform to 19 different California building codes and standards, including the 2019 California Building Code, Electrical Code, and various NFPA standards. The contractor is responsible for verifying all dimensions and conditions, selecting and installing materials in compliance with codes, and maintaining high quality workmanship throughout construction. The location is specified as being near Highway 395 and Standish Buntingville Road in the Honey Lake Wildlife Area.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| BID_DOC.pdf | ||
| Addendum_1.pdf | ||
| Addendum_2.pdf | ||
| CONTRACT_DOC.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
24"
CONCRETE
PAD
10'
10'
102"
EXISTING
CONDUIT
UNDER
SLAB
REMOVE AND REPLACE
100 HP WELL PUMP,
MOTOR AND CONTROLS
COMBINATION ELECTRICAL
SERVICE AND PUMP PANEL
CT SECTION
METERING
SECTION AND
MAIN
DISCONNECT
PUMP CONTROLS REPLACE WELL
PUMP MOTOR
AND HOUSING
REPLACE DISCHARGE HEAD
AND FLANGE
LIQUIDTIGHT
FLEXIBLE
METAL CONDUIT
REPLACE PUMP HEAD GASKET
4 IN. FILTER
AERIAL FEED PIPE
WITH THREADED
CAP
GROUND
CLAMP
ELECTRICAL
CONDUIT
MOTOR SUPPORT,
REINFORCED CONCRETE
REPLACE LINE SHAFT
DISCHARGE PIPE
WELL CASING
FILTER MATERIAL
INDUCTOR CASING
WELL SEAL
15"
ELECTRICAL CONTROL BOX
REPLACE TUBE TENSION NUT
REPLACE TUBE
& TENSION BEARING
REPLACE TOP COLUMN FLANGE
REPLACE LINE SHAFT BEARING
400A SERVICE
DISCONNECT
PUMP DISCONNECT
LMUD METER
CT CABINET
TO
PUMP
H O
A
PUMP CONTROL (HOA)
PUMP STATUS
PUMP HOURS
TO
SERVICE
POLE
EXISTING
REPLACE CONTROL
PANEL COMPONENTS
UTILITY
METER
480 VAC
3-PHASE FROM
UTILITY
400A 3P
SIZE CB PER
PUMP
REQUIREMENTS
OR PROVIDE AS
PART OF A
COMBINATION
SOFT STARTER
REDUCED
VOLTAGE SOFT
STARTER
WELL PUMP
100HP
INSTALL NEW
CONDUCTOR
IN EXISTING
CONDUIT-
3#1/0 AWG, 1#3(G)
CT
SECTION
METERING
SECTION
PUMP
CONTROL
SECTION
PUMP
DISCONNECT
EXISTING
CONTROLS
3P
HOA
HIGHW
AY 395
STANDISH BUNTINGVILLE ROAD
MAPES ROAD
LOCATION OF PUMP
CITY OF
SUSANVILLE
HONEY LAKE
P2499012
W04-2024-001
Sheet 01 of 01BRYTANNI K. PARRETT
C24-12
Drawing Number:California Department of Fish and WildlifeAPPROVED:
DESIGNED & DRAWN:
Facilities Engineering
The Natural Resources Agency
State of California
S. K. MURATA
REVISIONS:
DATENO. DESCRIPTION/SHEET NUMBERSAPPROVED
BY
CHIEF ENGINEER DATE
9/24/2024
HONEY LAKE WILDLIFE AREA
LASSEN COUNTY
NORTHERN REGION
MITIGATION PUMP REPAIR
PROJECT DESCRIPTION:
THE PROJECT CONSISTS OF REPLACEMENT OF IRRIGATION PUMP REPLACEMENTS
AND OTHER MISCELLANEOUS IMPROVEMENTS.
THE PROJECT SHALL CONFORM TO THE APPLICABLE STATE AND FEDERAL CODES
AS SHOWN BELOW: (REVISED AS NEEDED. MUST MATCH EXHIBIT T OF SPECIAL
PROVISIONS)
1. 2019 CALIFORNIA BUILDING STANDARDS ADMINISTRATIVE CODE (CAC) , ( CCR,
TITLE 24 ,PART 1)
2. 2019 CALIFORNIA BUILDING CODE (CBC), VOLUMES 1, AND 2, (CCR, TITLE 24,
PART 2, (2018 INTERNATIONAL BUILDING CODE WITH 2019 CALIFORNIA
AMENDMENTS).
3. 2019 CALIFORNIA RESIDENTIAL CODE (CRC), (CCR, TITLE 24, PART 2.5), BASED
ON 2018 INTERNATIONAL RESIDENTIAL CODE.
4. 2019 CALIFORNIA ELECTRICAL CODE (CEC), (CCR, TITLE 24, PART 3), BASED ON
2017 NATIONAL ELECTRICAL CODE WITH 2019 CALIFORNIA AMENDMENTS).
5. 2019 CALIFORNIA MECHANICAL CODE (CMC), (CCR, TITLE 24, PART 4), BASED ON
2018 UNIFORM MECHANICAL CODE WITH 2019 CALIFORNIA AMENDMENTS).
6. 2019 CALIFORNIA PLUMBING CODE (CPC), (CCR, TITLE 24, PART 5,) BASED ON
2018 UNIFORM PLUMBING CODE WITH 2019 CALIFORNIA AMENDMENTS).
7. 2019 CALIFORNIA ENERGY CODE, (CCR, TITLE 24, PART 6).
8. 2019 CALIFORNIA HISTORICAL BUILDING CODE, (CCR, TITLE 24, PART 8).
9. 2019 CALIFORNIA FIRE CODE (CFC), (CCR, TITLE 24, PART 9), BASED ON 2018
INTERNATIONAL FIRE CODE WITH 2019 CALIFORNIA AMENDMENTS).
10. 2019 CALIFORNIA EXISTING BUILDING CODE, (CCR, TITLE 24, PART 10), BASED ON
2018 INTERNATIONAL EXISTING BUILDING CODE.
11. 2019 CALIFORNIA GREEN BUILDING STANDARDS CODE, (CCR, TITLE 24, PART 11).
12. TITLE 19 C.C.R., PUBLIC SAFETY, STATE FIRE MARSHAL REGULATIONS
NFPA 13 AUTOMATIC SPRINKLER SYSTEMS W/ CA AMENDMENTS 2016 EDITION
NFPA 14 STANDPIPE SYSTEMS W/CA AMENDMENTS 2013 EDITION
NFPA 17A WET CHEMICAL SYSTEMS 2016 EDITION
NFPA 20 STATIONARY PUMPS 2013 EDITION
NFPA 24 PRIVATE FIRE MAINS W/CA AMENDMENTS 2016 EDITION
NFPA 72 NATIONAL FIRE ALARM CODE W/CA AMENDMENTS 2016 EDITION
NFPA 2001 CLEAN AGENT FIRE EXTINGUISHING SYSTEMS W/CA 2015 EDITION
AMENDMENTS REFERENCE CODE SECTION FOR NFPA STANDARDS ARE IN
2019 CBC CHAPTER 35 OR 2019 CFC CHAPTER 80. SEE CHAPTER 35 FOR
STATE OF CALIFORNIA AMENDMENTS TO NFPA STANDARDS.
13. REFERENCE CODE SECTIONS FOR APPLICABLE STANDARDS
2019 CBC, CHAPTER 35
2019 CFC, CHAPTER 45
14. TITLE 8, CALIFORNIA CODE OF REGULATIONS, (CCR), CAL/OSHA REGULATIONS -
SAFETY ORDERS ISSUED BY DIVISION OF INDUSTRIAL SAFETY OF THE STATE OF
CALIFORNIA.
15. TITLE 19, CALIFORNIA CODE OF REGULATIONS, (CCR), PUBLIC SAFETY, SFM
REGULATIONS, LIST OF FEDERAL CODES & STANDARDS (IF APPLICABLE).
16. AMERICAN WITH DISABILITIES ACT (ADA), TITLEII OR TITLE III.
17. 2019 CALIFORNIA ACCESS COMPLIANCE ADVISORY REFERENCE MANUAL (AS
PREPARED BY THE DIVISION OF THE STATE ARCHITECT OFFICE, PUBLISHED ON
JULY 1, 2019, EFFECTIVE JANUARY 1, 2020.)
18. DOT STANDARD SPECIFICATIONS AND/OR PLANS; STATE OF CALIFORNIA, DOT,
2018.
19. UNDERWRITERS LABORATORIES, INC. (UL STANDARDS).
GENERAL NOTES:
1. CONTRACTOR SHALL READ AND BE FAMILIAR WITH ALL FACETS OF THE PLANS
AND SPECIFICATIONS.
2. THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND CONDITIONS IN THE
FIELD PRIOR TO BIDDING/COMMENCEMENT OF WORK.
3. THESE PLANS ARE FOR GENERAL CONSTRUCTION PURPOSES ONLY. THEY ARE
NOT FULLY SPECIFIED.
4. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO SELECT, VERIFY, RESOLVE,
AND INSTALL ALL MATERIALS AND EQUIPMENT WITH COMPLIANCE TO CODES
AND /OR ORDINANCES.
5. CONSTRUCTION SHALL BE OF THE HIGHEST QUALITY OF WORKMANSHIP. ALL
CONNECTIONS SHALL BE MADE SECURE ACCORDING TO ACCEPTED
CONSTRUCTION PRACTICES OR AS SPECIFIED HEREIN OR PER CURRENT
BUILDING CODES.
6. CONTRACTOR IS RESPONSIBLE FOR ANY CONSTRUCTION WHICH IS IN
DEVIATION FROM THESE PLANS.
C65221
N
VICINITY MAP
SCALE: NTS
COMBINATION ELECTRICAL SERVICE AND PUMP CONTROL PANEL
SCALE: NTS
PUMP
SCALE: NTS
PLAN VIEW EQUIPMENT PAD
SCALE: NTS
UNDERGROUND PUMP COMPONENTS
SCALE: NTS
59" MIN.
WELL SEAL
CONDUCTOR COATING
BORE HOLE, 1120 mm. DIA.
CONDUCTOR CASING, 915 mm DIA.
FILTER MATERIAL
BORE HOLE,
865 mm DIA.
BLANK WELL
CASING AND
WELL SCREEN,
510 mm DIA.CAP
50'
329'
552'
REPLACE HEADSHAFT
REPLACE LINE SHAFT COUPLING
INSTALL
OIL TUBE
REPLACE COLUMN PIPE COUPLING
REPLACE RUBBER CENTERING SPIDERS
REPLACE COLUMN PIPE
REPLACE BOWLSHAFT
REPLACE BOWL ADAPTER TUBE
REPLACE BOWL ADAPTER TUBE BEARING
REPLACE
DISCHARGE CASE
REPLACE
TOP THROTTLE
BEARING
REPLACE
IMPELLER
REPLACE SUCTION CASE WEAR RING
REPLACE IMPELLER COLLET
REPLACE SUCTION CASEREPLACE
SAND COLLAR
REPLACE
SUCTION BEARING
REPLACE SUCTION SCREEN
ELECTRICAL SCOPE NOTES:
1. FROM PUMP CONTROL SECTION OF CABINET, REMOVE AND REPLACE ALL PUMP CONTROLS.
2. EXISTING EQUIPMENT TO BE REPLACED INCLUDES:
A. HAND-OFF-AUTO CONTROL SWITCH (AUTO IS DISABLED, PUMP IS OPERATED MANUALLY)
B. CIRCUIT BREAKER DISCONNECT
C. RUNNING TIME METER
D. PUMP STATUS LIGHT
E. MOTOR STARTER CONTACTOR AND OVERLOADS
3. REPLACE EXISTING STANDARD MOTOR STARTER WITH REDUCED VOLTAGE SOFT STARTER. INCLUDE EXTERNAL BYPASS OPTION WITH OVERLOAD PROTECTION. CONTROL PANEL EQUIPMENT SIZING TO BE
DETERMINED BY CONTRACTOR BASED ON PUMP EQUIPMENT SELECTED.
4. IN EXISTING CONDUIT, REPLACE THE CONDUCTORS AS SHOWN IN SINGLE-LINE DIAGRAM.
ELECTRICAL SINGLE LINE DIAGRAM
SCALE: NTS
EQUIPMENT SCHEDULE
EQUIPMENT SPEED
(RPM) POWER VOLTS PHASE USGPM
TOTAL
DYNAMIC
HEAD (ft.)
WELL PUMP 1170 100 HP 460 3 2050 100
3000 85 4000 50
AutoCAD SHX Text L
AutoCAD SHX Text A
AutoCAD SHX Text L
AutoCAD SHX Text I
AutoCAD SHX Text E
AutoCAD SHX Text G
AutoCAD SHX Text R
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text D
AutoCAD SHX Text P
AutoCAD SHX Text R
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text I
AutoCAD SHX Text O
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text E
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text G
AutoCAD SHX Text C
AutoCAD SHX Text O
AutoCAD SHX Text O
AutoCAD SHX Text E
AutoCAD SHX Text A
AutoCAD SHX Text T
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text F
AutoCAD SHX Text A
AutoCAD SHX Text F
AutoCAD SHX Text L
AutoCAD SHX Text I
AutoCAD SHX Text I
AutoCAD SHX Text R
AutoCAD SHX Text N
AutoCAD SHX Text C
AutoCAD SHX Text I
AutoCAD SHX Text I
AutoCAD SHX Text V
| Sheets and Views |
| HoneyLakePump bs working-36 x 24 Sheet |
File details come from the government source that posted it. Updated .