Construction_Plans.pdf

PDF 291 KB Posted

Attached to
P2499012 - Honey Lake Mitigation Pump Replacement
Solicitation number
0000033414
Issued by
Lassen County, California

About this file

This is a construction plan document from the California Department of Fish and Wildlife for the Honey Lake Wildlife Area Mitigation Pump Repair project in Lassen County. The project involves replacement of irrigation pump components and miscellaneous improvements, including replacing the well pump motor and housing, discharge head and flange, pump head gasket, line shaft components, and various other underground pump components. The plans detail specific technical requirements for a 100 HP, 460V, 3-phase well pump that must operate at 1170 RPM with varying flow rates from 2050-4000 USGPM at different head pressures.

The plans include detailed technical drawings showing equipment pad layouts, pump components, electrical service configurations, and underground pump components. The project must conform to 19 different California building codes and standards, including the 2019 California Building Code, Electrical Code, and various NFPA standards. The contractor is responsible for verifying all dimensions and conditions, selecting and installing materials in compliance with codes, and maintaining high quality workmanship throughout construction. The location is specified as being near Highway 395 and Standish Buntingville Road in the Honey Lake Wildlife Area.

View the file

Other files

File Type Posted
BID_DOC.pdf PDF
Addendum_1.pdf PDF
Addendum_2.pdf PDF
CONTRACT_DOC.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

24"

CONCRETE

PAD

10'

10'

102"

EXISTING

CONDUIT

UNDER

SLAB

REMOVE AND REPLACE

100 HP WELL PUMP,

MOTOR AND CONTROLS

COMBINATION ELECTRICAL

SERVICE AND PUMP PANEL

CT SECTION

METERING

SECTION AND

MAIN

DISCONNECT

PUMP CONTROLS REPLACE WELL

PUMP MOTOR

AND HOUSING

REPLACE DISCHARGE HEAD

AND FLANGE

LIQUIDTIGHT

FLEXIBLE

METAL CONDUIT

REPLACE PUMP HEAD GASKET

4 IN. FILTER

AERIAL FEED PIPE

WITH THREADED

CAP

GROUND

CLAMP

ELECTRICAL

CONDUIT

MOTOR SUPPORT,

REINFORCED CONCRETE

REPLACE LINE SHAFT

DISCHARGE PIPE

WELL CASING

FILTER MATERIAL

INDUCTOR CASING

WELL SEAL

15"

ELECTRICAL CONTROL BOX

REPLACE TUBE TENSION NUT

REPLACE TUBE

& TENSION BEARING

REPLACE TOP COLUMN FLANGE

REPLACE LINE SHAFT BEARING

400A SERVICE

DISCONNECT

PUMP DISCONNECT

LMUD METER

CT CABINET

TO

PUMP

H O

A

PUMP CONTROL (HOA)

PUMP STATUS

PUMP HOURS

TO

SERVICE

POLE

EXISTING

REPLACE CONTROL

PANEL COMPONENTS

UTILITY

METER

480 VAC

3-PHASE FROM

UTILITY

400A 3P

SIZE CB PER

PUMP

REQUIREMENTS

OR PROVIDE AS

PART OF A

COMBINATION

SOFT STARTER

REDUCED

VOLTAGE SOFT

STARTER

WELL PUMP

100HP

INSTALL NEW

CONDUCTOR

IN EXISTING

CONDUIT-

3#1/0 AWG, 1#3(G)

CT

SECTION

METERING

SECTION

PUMP

CONTROL

SECTION

PUMP

DISCONNECT

EXISTING

CONTROLS

3P

HOA

HIGHW

AY 395

STANDISH BUNTINGVILLE ROAD

MAPES ROAD

LOCATION OF PUMP

CITY OF

SUSANVILLE

HONEY LAKE

P2499012

W04-2024-001

Sheet 01 of 01BRYTANNI K. PARRETT

C24-12

Drawing Number:California Department of Fish and WildlifeAPPROVED:

DESIGNED & DRAWN:

Facilities Engineering

The Natural Resources Agency

State of California

S. K. MURATA

REVISIONS:

DATENO. DESCRIPTION/SHEET NUMBERSAPPROVED

BY

CHIEF ENGINEER DATE

9/24/2024

HONEY LAKE WILDLIFE AREA

LASSEN COUNTY

NORTHERN REGION

MITIGATION PUMP REPAIR

PROJECT DESCRIPTION:

THE PROJECT CONSISTS OF REPLACEMENT OF IRRIGATION PUMP REPLACEMENTS

AND OTHER MISCELLANEOUS IMPROVEMENTS.

THE PROJECT SHALL CONFORM TO THE APPLICABLE STATE AND FEDERAL CODES

AS SHOWN BELOW: (REVISED AS NEEDED. MUST MATCH EXHIBIT T OF SPECIAL

PROVISIONS)

1. 2019 CALIFORNIA BUILDING STANDARDS ADMINISTRATIVE CODE (CAC) , ( CCR,

TITLE 24 ,PART 1)

2. 2019 CALIFORNIA BUILDING CODE (CBC), VOLUMES 1, AND 2, (CCR, TITLE 24,

PART 2, (2018 INTERNATIONAL BUILDING CODE WITH 2019 CALIFORNIA

AMENDMENTS).

3. 2019 CALIFORNIA RESIDENTIAL CODE (CRC), (CCR, TITLE 24, PART 2.5), BASED

ON 2018 INTERNATIONAL RESIDENTIAL CODE.

4. 2019 CALIFORNIA ELECTRICAL CODE (CEC), (CCR, TITLE 24, PART 3), BASED ON

2017 NATIONAL ELECTRICAL CODE WITH 2019 CALIFORNIA AMENDMENTS).

5. 2019 CALIFORNIA MECHANICAL CODE (CMC), (CCR, TITLE 24, PART 4), BASED ON

2018 UNIFORM MECHANICAL CODE WITH 2019 CALIFORNIA AMENDMENTS).

6. 2019 CALIFORNIA PLUMBING CODE (CPC), (CCR, TITLE 24, PART 5,) BASED ON

2018 UNIFORM PLUMBING CODE WITH 2019 CALIFORNIA AMENDMENTS).

7. 2019 CALIFORNIA ENERGY CODE, (CCR, TITLE 24, PART 6).

8. 2019 CALIFORNIA HISTORICAL BUILDING CODE, (CCR, TITLE 24, PART 8).

9. 2019 CALIFORNIA FIRE CODE (CFC), (CCR, TITLE 24, PART 9), BASED ON 2018

INTERNATIONAL FIRE CODE WITH 2019 CALIFORNIA AMENDMENTS).

10. 2019 CALIFORNIA EXISTING BUILDING CODE, (CCR, TITLE 24, PART 10), BASED ON

2018 INTERNATIONAL EXISTING BUILDING CODE.

11. 2019 CALIFORNIA GREEN BUILDING STANDARDS CODE, (CCR, TITLE 24, PART 11).

12. TITLE 19 C.C.R., PUBLIC SAFETY, STATE FIRE MARSHAL REGULATIONS

NFPA 13 AUTOMATIC SPRINKLER SYSTEMS W/ CA AMENDMENTS 2016 EDITION

NFPA 14 STANDPIPE SYSTEMS W/CA AMENDMENTS 2013 EDITION

NFPA 17A WET CHEMICAL SYSTEMS 2016 EDITION

NFPA 20 STATIONARY PUMPS 2013 EDITION

NFPA 24 PRIVATE FIRE MAINS W/CA AMENDMENTS 2016 EDITION

NFPA 72 NATIONAL FIRE ALARM CODE W/CA AMENDMENTS 2016 EDITION

NFPA 2001 CLEAN AGENT FIRE EXTINGUISHING SYSTEMS W/CA 2015 EDITION

AMENDMENTS REFERENCE CODE SECTION FOR NFPA STANDARDS ARE IN

2019 CBC CHAPTER 35 OR 2019 CFC CHAPTER 80. SEE CHAPTER 35 FOR

STATE OF CALIFORNIA AMENDMENTS TO NFPA STANDARDS.

13. REFERENCE CODE SECTIONS FOR APPLICABLE STANDARDS

2019 CBC, CHAPTER 35

2019 CFC, CHAPTER 45

14. TITLE 8, CALIFORNIA CODE OF REGULATIONS, (CCR), CAL/OSHA REGULATIONS -

SAFETY ORDERS ISSUED BY DIVISION OF INDUSTRIAL SAFETY OF THE STATE OF

CALIFORNIA.

15. TITLE 19, CALIFORNIA CODE OF REGULATIONS, (CCR), PUBLIC SAFETY, SFM

REGULATIONS, LIST OF FEDERAL CODES & STANDARDS (IF APPLICABLE).

16. AMERICAN WITH DISABILITIES ACT (ADA), TITLEII OR TITLE III.

17. 2019 CALIFORNIA ACCESS COMPLIANCE ADVISORY REFERENCE MANUAL (AS

PREPARED BY THE DIVISION OF THE STATE ARCHITECT OFFICE, PUBLISHED ON

JULY 1, 2019, EFFECTIVE JANUARY 1, 2020.)

18. DOT STANDARD SPECIFICATIONS AND/OR PLANS; STATE OF CALIFORNIA, DOT,

2018.

19. UNDERWRITERS LABORATORIES, INC. (UL STANDARDS).

GENERAL NOTES:

1. CONTRACTOR SHALL READ AND BE FAMILIAR WITH ALL FACETS OF THE PLANS

AND SPECIFICATIONS.

2. THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND CONDITIONS IN THE

FIELD PRIOR TO BIDDING/COMMENCEMENT OF WORK.

3. THESE PLANS ARE FOR GENERAL CONSTRUCTION PURPOSES ONLY. THEY ARE

NOT FULLY SPECIFIED.

4. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO SELECT, VERIFY, RESOLVE,

AND INSTALL ALL MATERIALS AND EQUIPMENT WITH COMPLIANCE TO CODES

AND /OR ORDINANCES.

5. CONSTRUCTION SHALL BE OF THE HIGHEST QUALITY OF WORKMANSHIP. ALL

CONNECTIONS SHALL BE MADE SECURE ACCORDING TO ACCEPTED

CONSTRUCTION PRACTICES OR AS SPECIFIED HEREIN OR PER CURRENT

BUILDING CODES.

6. CONTRACTOR IS RESPONSIBLE FOR ANY CONSTRUCTION WHICH IS IN

DEVIATION FROM THESE PLANS.

C65221

N

VICINITY MAP

SCALE: NTS

COMBINATION ELECTRICAL SERVICE AND PUMP CONTROL PANEL

SCALE: NTS

PUMP

SCALE: NTS

PLAN VIEW EQUIPMENT PAD

SCALE: NTS

UNDERGROUND PUMP COMPONENTS

SCALE: NTS

59" MIN.

WELL SEAL

CONDUCTOR COATING

BORE HOLE, 1120 mm. DIA.

CONDUCTOR CASING, 915 mm DIA.

FILTER MATERIAL

BORE HOLE,

865 mm DIA.

BLANK WELL

CASING AND

WELL SCREEN,

510 mm DIA.CAP

50'

329'

552'

REPLACE HEADSHAFT

REPLACE LINE SHAFT COUPLING

INSTALL

OIL TUBE

REPLACE COLUMN PIPE COUPLING

REPLACE RUBBER CENTERING SPIDERS

REPLACE COLUMN PIPE

REPLACE BOWLSHAFT

REPLACE BOWL ADAPTER TUBE

REPLACE BOWL ADAPTER TUBE BEARING

REPLACE

DISCHARGE CASE

REPLACE

TOP THROTTLE

BEARING

REPLACE

IMPELLER

REPLACE SUCTION CASE WEAR RING

REPLACE IMPELLER COLLET

REPLACE SUCTION CASEREPLACE

SAND COLLAR

REPLACE

SUCTION BEARING

REPLACE SUCTION SCREEN

ELECTRICAL SCOPE NOTES:

1. FROM PUMP CONTROL SECTION OF CABINET, REMOVE AND REPLACE ALL PUMP CONTROLS.

2. EXISTING EQUIPMENT TO BE REPLACED INCLUDES:

A. HAND-OFF-AUTO CONTROL SWITCH (AUTO IS DISABLED, PUMP IS OPERATED MANUALLY)

B. CIRCUIT BREAKER DISCONNECT

C. RUNNING TIME METER

D. PUMP STATUS LIGHT

E. MOTOR STARTER CONTACTOR AND OVERLOADS

3. REPLACE EXISTING STANDARD MOTOR STARTER WITH REDUCED VOLTAGE SOFT STARTER. INCLUDE EXTERNAL BYPASS OPTION WITH OVERLOAD PROTECTION. CONTROL PANEL EQUIPMENT SIZING TO BE

DETERMINED BY CONTRACTOR BASED ON PUMP EQUIPMENT SELECTED.

4. IN EXISTING CONDUIT, REPLACE THE CONDUCTORS AS SHOWN IN SINGLE-LINE DIAGRAM.

ELECTRICAL SINGLE LINE DIAGRAM

SCALE: NTS

EQUIPMENT SCHEDULE

EQUIPMENT SPEED

(RPM) POWER VOLTS PHASE USGPM

TOTAL

DYNAMIC

HEAD (ft.)

WELL PUMP 1170 100 HP 460 3 2050 100

3000 85 4000 50

AutoCAD SHX Text L

AutoCAD SHX Text A

AutoCAD SHX Text L

AutoCAD SHX Text I

AutoCAD SHX Text E

AutoCAD SHX Text G

AutoCAD SHX Text R

AutoCAD SHX Text S

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text D

AutoCAD SHX Text P

AutoCAD SHX Text R

AutoCAD SHX Text F

AutoCAD SHX Text O

AutoCAD SHX Text E

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text I

AutoCAD SHX Text O

AutoCAD SHX Text N

AutoCAD SHX Text A

AutoCAD SHX Text E

AutoCAD SHX Text I

AutoCAD SHX Text N

AutoCAD SHX Text N

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text G

AutoCAD SHX Text C

AutoCAD SHX Text O

AutoCAD SHX Text O

AutoCAD SHX Text E

AutoCAD SHX Text A

AutoCAD SHX Text T

AutoCAD SHX Text S

AutoCAD SHX Text T

AutoCAD SHX Text F

AutoCAD SHX Text A

AutoCAD SHX Text F

AutoCAD SHX Text L

AutoCAD SHX Text I

AutoCAD SHX Text I

AutoCAD SHX Text R

AutoCAD SHX Text N

AutoCAD SHX Text C

AutoCAD SHX Text I

AutoCAD SHX Text I

AutoCAD SHX Text V

Sheets and Views
HoneyLakePump bs working-36 x 24 Sheet

File details come from the government source that posted it. Updated .