1. FIGURES

Figure 1. General site Orientation

Location of new generator Existing

Transformer

2.

Figure 2. Fuel Tank Environmental Requirements

Figure 3. Concrete pad detail (typical)

Figure 4. Bollard placement detail (typical)

Note 1. INSTALL 12"Ø THREADED ROD, ASTM F593, W/4"

MIN EMBED INTO SLAB USING HILTI HIT-RE 500-SD

EPOXY ANCHORING SYSTEM, INSTALL ANCHOR AT EACH

MOUNTING HOLE PROVIDED IN EQUIPMENT.

Figure 5. Location of new Automatic Transfer Switch

Approximate location of new

Automatic

Transfer Switch

Main Disconnect

a. Drawings:

Figure 6. Building footprint with approximate locations of new equipment.

Location of new

ATS

New Generator MAINTAIN 5-FOOT MINIMUM

CLEAR SPACE BETWEEN

GENERATOR FUEL TANK AND

BUILDING IN ACCORDANCE

WITH NFPA 30 T22.4.1.1(B).

Possible path for new conduit