Clarendon EOC Specifications_VOL 2.pdf
PDF 4 MB Posted
- Solicitation number
- ITB 2024-006
- Issued by
- Chesterfield County, South Carolina
About this file
The document is a comprehensive architectural and engineering specification for the construction of a new Emergency Operations and 911 Communications Dispatch Center for Clarendon County, South Carolina. The project involves constructing a 10,112 gross square foot Type II-B building with multiple occupancy classifications including Business (B), Assembly (A-3), and Residential (R-3). The facility will be primarily constructed using concrete masonry and structural steel, with exterior cladding of brick veneer and aluminum metal panels, and featuring standing seam metal panels and modified bitumen roofing systems.
The specifications provide detailed technical requirements for various building systems, including plumbing, fire suppression, electrical, and HVAC components. The project involves comprehensive design and installation specifications for systems such as a clean agent fire suppression system, nitrogen generation system, water and waste piping, electrical infrastructure, and specialized equipment like water heaters, pumps, and communication systems. The documents indicate a thorough approach to building design that emphasizes safety, functionality, and compliance with local and national building codes, with specific attention to emergency management and communication infrastructure requirements.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
EMERGENCY MANAGEMENT & 911
COMMUNICATIONS DISPATCH CENTER
Clarendon County 1091 Capital Way, Manning, SC 29102
May 5, 2025
Volume 2 of 3
Caplea Coe Architects, Inc.
1643 Means Street
Charleston, SC 29412
(843) 577-6073
NON-STRUCTURAL METAL FRAMING 092216- 1
EMERGENCY MANAGEMENT AND 911 COMMUNICATIONS DISPATCH CENTER
SECTION 092216 - NON-STRUCTURAL METAL FRAMING
PART 1 - GENERAL
1.1 SUMMARY
A. Section Includes:
1. Framing systems.
2. Grid suspension systems.
B. Related Requirements:
1. Section 054000 "Cold-Formed Metal Framing" for exterior and interior load-bearing and exterior non-load-bearing wall studs; floor joists; and roof rafters and ceiling joists.
1.2 ACTION SUBMITTALS
A. Product Data: For each type of product.
1.3 INFORMATIONAL SUBMITTALS
A. Product Certificates: For each type of code-compliance certification for studs and tracks.
B. Evaluation Reports: For post-installed anchors and power-actuated fasteners, from ICC- ES or other qualified testing agency acceptable to authorities having jurisdiction.
1.4 QUALITY ASSURANCE
A. Code-Compliance Certification of Studs and Tracks: Provide documentation that framing members are certified according to the product-certification program of the Steel Stud Manufacturers Association.
1.5 DELIVERY, STORAGE, AND HANDLING
A. Notify manufacturer of damaged materials received prior to installation.
B. Deliver materials in manufacturer's original, unopened, undamaged containers with identification labels intact.
C. Protect cold-formed metal framing from corrosion, deformation, and other damage during delivery, storage, and handling as required by AISI S202, "Code of Standard Practice for Cold-Formed Steel Structural Framing."
NON-STRUCTURAL METAL FRAMING 092216- 2
PART 2 - PRODUCTS
2.1 PERFORMANCE REQUIREMENTS
A. Fire-Test-Response Characteristics: For fire-resistance-rated assemblies that incorporate non-load-bearing steel framing, provide materials and construction identical to those tested in assembly indicated, in accordance with ASTM E119 by an independent testing agency.
B. STC-Rated Assemblies: For STC-rated assemblies, provide materials and construction identical to those tested in assembly indicated on Drawings, in accordance with ASTM E90 and classified in accordance with ASTM E413 by an independent testing agency.
C. Horizontal Deflection: For non-composite wall assemblies, limited to 1/240 of the wall height based on horizontal loading of 5 lbf/sq. ft.
D. Design framing systems in accordance with AISI S220, "North American Specification for the Design of Cold-Formed Steel Framing - Nonstructural Members," unless otherwise indicated.
2.2 FRAMING SYSTEMS
A. Framing Members, General: Comply with AISI S220 for conditions indicated.
1. Steel Sheet Components: Comply with AISI S220 requirements for metal unless otherwise indicated
2. Protective Coating: Comply with AISI S220; ASTM A653/A653M, G40; or coating with equivalent corrosion resistance. Galvannealed products are unacceptable.
a. Coating demonstrates equivalent corrosion resistance with an evaluation report acceptable to authorities having jurisdiction.
B. Studs and Track: AISI S220.
1. Basis-of-Design Product: Subject to compliance with requirements, provide ClarkDietrich; ProSTUD Drywall Framing or comparable product by one of the following:
a. CEMCO; California Expanded Metal Products Co.
b. TELLING Industries.
2. Minimum Base-Steel Thickness: As required by performance requirements for horizontal deflection.
3. Depth: As indicated on Drawings.
NON-STRUCTURAL METAL FRAMING 092216- 3
C. Slip-Type Head Joints: Where indicated, provide the following:
1. Deflection Track: Steel sheet top track manufactured to prevent cracking of finishes applied to interior partition framing resulting from deflection of structure above; in thickness not less than indicated for studs and in width to accommodate depth of studs.
D. Firestop Tracks: Top track manufactured to allow partition heads to expand and contract with movement of structure while maintaining continuity of fire-resistance-rated assembly indicated; in thickness not less than indicated for studs and in width to accommodate depth of studs.
E. Flat Strap and Backing Plate: Steel sheet for blocking and bracing in length and width indicated.
1. Minimum Base-Steel Thickness: As indicated on Drawings.
F. Resilient Furring Channels: 1/2-inch- deep, steel sheet members designed to reduce sound transmission.
1. Configuration: Asymmetrical.
G. Cold-Rolled Channel Bridging: Steel, 0.0538-inch minimum base-steel thickness, with minimum 1/2-inch- wide flanges.
1. Depth: As indicated on Drawings.
2. Clip Angle: Not less than 1-1/2 by 1-1/2 inches, 0.068-inch- thick, galvanized steel.
H. Z-Shaped Furring: With slotted or nonslotted web, face flange of 1-1/4 inches, wall attachment flange of 3/4 inch, minimum uncoated-steel thickness of 0.0179 inch, and depth required to fit insulation thickness indicated.
2.3 GRID SUSPENSION SYSTEMS
A. Grid Suspension Systems for Gypsum Board Ceilings: ASTM C645, direct-hung system composed of main beams and cross-furring members that interlock.
1. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
a. Armstrong World Industries, Inc.
b. USG Corporation.
2.4 AUXILIARY MATERIALS
A. General: Provide auxiliary materials that comply with referenced installation standards.
1. Fasteners for Steel Framing: Of type, material, size, corrosion resistance, holding power, and other properties required to fasten steel members to substrates.
NON-STRUCTURAL METAL FRAMING 092216- 4
B. Isolation Strip at Exterior Walls: Provide one of the following:
1. Asphalt-Saturated Organic Felt: ASTM D226/D226M, Type I (No. 15 asphalt felt), nonperforated.
PART 3 - EXECUTION
3.1 EXAMINATION
A. Examine areas and substrates, with Installer present, and including welded hollow- metal frames, cast-in anchors, and structural framing, for compliance with requirements and other conditions affecting performance of the Work.
B. Proceed with installation only after unsatisfactory conditions have been corrected.
3.2 PREPARATION
A. Suspended Assemblies: Coordinate installation of suspension systems with installation of overhead structure to ensure that inserts and other provisions for anchorages to building structure have been installed to receive hangers at spacing required to support the Work and that hangers will develop their full strength.
1. Furnish concrete inserts and other devices indicated to other trades for installation in advance of time needed for coordination and construction.
3.3 INSTALLATION, GENERAL
A. Installation Standard: ASTM C754.
1. Gypsum Board Assemblies: Also comply with requirements in ASTM C840 that apply to framing installation.
B. Install framing and accessories plumb, square, and true to line, with connections securely fastened.
C. Install supplementary framing, and blocking to support fixtures, equipment services, heavy trim, grab bars, toilet accessories, furnishings, or similar construction.
D. Install bracing at terminations in assemblies.
E. Do not bridge building control and expansion joints with non-load-bearing steel framing members. Frame both sides of joints independently.
NON-STRUCTURAL METAL FRAMING 092216- 5
3.4 INSTALLATION OF FRAMING SYSTEMS
A. Install framing system components according to spacings indicated, but not greater than spacings required by referenced installation standards for assembly types.
1. Single-Layer Application: As required by horizontal deflection performance requirements unless otherwise indicated.
2. Tile Backing Panels: As required by horizontal deflection performance requirements unless otherwise indicated.
3. Multilayer Application: 16 inches on center unless otherwise indicated.
B. Where studs are installed directly against exterior masonry walls or dissimilar metals at exterior walls, install isolation strip between studs and exterior wall.
C. Install studs so flanges within framing system point in same direction.
D. Install tracks at floors and overhead supports. Extend framing full height to structural supports or substrates above suspended ceilings except where partitions are indicated to terminate at suspended ceilings. Continue framing around ducts that penetrate partitions above ceiling.
1. Slip-Type Head Joints: Where framing extends to overhead structural supports, install to produce joints at tops of framing systems that prevent axial loading of finished assemblies.
2. Door Openings: Screw vertical studs at jambs to jamb anchor clips on door frames;
install track section (for cripple studs) at head and secure to jamb studs.
a. Install two studs at each jamb unless otherwise indicated.
b. Install cripple studs at head adjacent to each jamb stud, with a minimum 1/2-inch clearance from jamb stud to allow for installation of control joint in finished assembly.
c. Extend jamb studs through suspended ceilings and attach to underside of overhead structure.
3. Other Framed Openings: Frame openings other than door openings the same as required for door openings unless otherwise indicated. Install framing below sills of openings to match framing required above door heads.
4. Fire-Resistance-Rated Partitions: Install framing to comply with fire-resistance-rated assembly indicated and support closures and to make partitions continuous from floor to underside of solid structure.
a. Firestop Track: Where indicated, install to maintain continuity of fire-resistance-rated assembly indicated.
5. Sound-Rated Partitions: Install framing to comply with sound-rated assembly indicated.
E. Installation Tolerance: Install each framing member so fastening surfaces vary not more than 1/8 inch from the plane formed by faces of adjacent framing.
NON-STRUCTURAL METAL FRAMING 092216- 6
3.5 INSTALLATION OF GRID SUSPENSION SYSTEMS
A. Grid Suspension Systems: Attach perimeter wall track or angle where grid suspension systems meet vertical surfaces. Mechanically join main beam and cross-furring members to each other and butt-cut to fit into wall track.
3.6 FIELD QUALITY CONTROL
A. Installation Tolerances: Install suspension systems that are level to within 1/8 inch in 12 feet measured lengthwise on each member that will receive finishes and transversely between parallel members that will receive finishes.
END OF SECTION 092216
GYPSUM BOARD 092900- 1
SECTION 092900 - GYPSUM BOARD
1.1 SUMMARY
A. Section Includes:
1. Interior gypsum board.
2. Tile backing panels.
B. Related Requirements:
1. Section 072100 "Thermal Insulation" for glass fiber thermal insulation and glass fiber sound batt insulation.
2. Section 079219 "Acoustical Joint Sealants" for acoustical joint sealants installed in gypsum board assemblies.
3. Section 092216 "Non-Structural Metal Framing" for non-structural steel framing and suspension systems that support gypsum board panels.
B. Shop Drawings: Show locations and installation of control and expansion joints, including plans, elevations, sections, details of components, and attachments to other work.
1.3 DELIVERY, STORAGE AND HANDLING
A. Store materials inside under cover and keep them dry and protected against weather, condensation, direct sunlight, construction traffic, and other potential causes of damage.
Stack panels flat and supported on risers on a flat platform to prevent sagging.
1.4 FIELD CONDITIONS
A. Environmental Limitations: Comply with ASTM C840 requirements or gypsum board manufacturer's written instructions, whichever are more stringent.
B. Do not install paper-faced gypsum panels until installation areas are enclosed and conditioned.
GYPSUM BOARD 092900- 2
C. Do not install panels that are wet, moisture damaged, and mold damaged.
1. Indications that panels are wet or moisture damaged include, but are not limited to, discoloration, sagging, or irregular shape.
2. Indications that panels are mold damaged include, but are not limited to, fuzzy or splotchy surface contamination and discoloration.
2.1 SOURCE LIMITATIONS
A. Obtain each type of gypsum panel and joint finishing material from single source with resources to provide products of consistent quality in appearance and physical properties.
2.2 PERFORMANCE REQUIREMENTS
A. Fire-Resistance-Rated Assemblies: For fire-resistance-rated assemblies, provide materials and construction identical to those tested in assembly indicated in accordance with ASTM E119 by an independent testing agency.
B. STC-Rated Assemblies: For STC-rated assemblies, provide materials and construction identical to those tested in assembly indicated in accordance with ASTM E90 and classified in accordance with ASTM E413 by an independent testing agency.
2.3 GYPSUM BOARD, GENERAL
A. Size: Provide maximum lengths and widths available that will minimize joints in each area and that correspond with support system indicated.
2.4 INTERIOR GYPSUM BOARD
A. Gypsum Wallboard: ASTM C1396/C1396M.
1. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
a. American Gypsum.
b. Georgia-Pacific Gypsum LLC.
c. Gold Bond Building Products, LLC provided by National Gypsum Company.
d. USG Corporation.
2. Thickness: 5/8 inch.
3. Long Edges: Tapered.
GYPSUM BOARD 092900- 3
B. Gypsum Board, Type X: ASTM C1396/C1396M.
1. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
a. American Gypsum.
b. Georgia-Pacific Gypsum LLC.
c. Gold Bond Building Products, LLC provided by National Gypsum
Company.
d. USG Corporation.
2. Thickness: 5/8 inch.
3. Long Edges: Tapered.
C. Mold-Resistant Gypsum Board: ASTM C1396/C1396M. With moisture- and mold-resistant core and paper surfaces.
1. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
a. American Gypsum.
b. Georgia-Pacific Gypsum LLC.
c. Gold Bond Building Products, LLC provided by National Gypsum Company.
d. USG Corporation.
2. Core: As indicated on Drawings.
3. Long Edges: Tapered.
4. Mold Resistance: ASTM D3273, score of 10 as rated in accordance with
ASTM D3274.
2.5 TILE BACKING PANELS
A. Cementitious Backer Units: ANSI A118.9 and ASTM C1288 or ASTM C1325, with manufacturer's standard edges.
1. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
a. James Hardie Building Products, Inc.
b. PermaBASE Building Products, LLC provided by National Gypsum Company.
c. USG Corporation.
2. Thickness: As indicated on Drawings.
3. Mold Resistance: ASTM D3273, score of 10 as rated in accordance with
ASTM D3274.
GYPSUM BOARD 092900- 4
2.6 TRIM ACCESSORIES
A. Interior Trim: ASTM C1047.
1. Material: Paper-faced galvanized-steel sheet.
2. Shapes:
a. Cornerbead.
b. LC-Bead: J-shaped; exposed long flange receives joint compound.
c. L-Bead: L-shaped; exposed long flange receives joint compound.
2.7 JOINT TREATMENT MATERIALS
A. General: Comply with ASTM C475/C475M.
B. Joint Tape:
1. Interior Gypsum Board: Paper.
2. Tile Backing Panels: As recommended by panel manufacturer.
C. Joint Compound for Interior Gypsum Board: For each coat, use formulation that is compatible with other compounds applied on previous or for successive coats.
1. Prefilling: At open joints and damaged surface areas, use setting-type taping compound.
2. Embedding and First Coat: For embedding tape and first coat on joints, fasteners, and trim flanges, use drying-type, all-purpose compound.
a. Use setting-type compound for installing paper-faced metal trim accessories.
3. Fill Coat: For second coat, use drying-type, all-purpose compound.
4. Finish Coat: For third coat, use drying-type, all-purpose compound.
D. Joint Compound for Tile Backing Panels:
1. Cementitious Backer Units: As recommended by backer unit manufacturer.
2.8 AUXILIARY MATERIALS
A. Provide auxiliary materials that comply with referenced installation standards and manufacturer's written instructions.
B. Steel Drill Screws: ASTM C1002 unless otherwise indicated.
1. Use screws complying with ASTM C954 for fastening panels to steel members from 0.033 to 0.112 inch thick.
C. Acoustical Sealant: As specified in Section 079219 "Acoustical Joint Sealants."
D. Thermal Insulation: As specified in Section 072100 "Thermal Insulation" for glass fiber thermal insulation and glass fiber sound batt insulation.
GYPSUM BOARD 092900- 5
A. Examine areas and substrates including welded hollow-metal frames and support framing, with Installer present, for compliance with requirements and other conditions affecting performance of the Work.
B. Examine panels before installation. Reject panels that are wet, moisture damaged, and mold damaged.
C. Proceed with installation only after unsatisfactory conditions have been corrected.
3.2 INSTALLATION AND FINISHING OF PANELS, GENERAL
A. Comply with ASTM C840.
B. Install ceiling panels across framing to minimize the number of abutting end joints and to avoid abutting end joints in central area of each ceiling. Stagger abutting end joints of adjacent panels not less than one framing member.
C. Install panels with face side out. Butt panels together for a light contact at edges and ends with not more than 1/16 inch of open space between panels. Do not force into place.
D. Locate edge and end joints over supports, except in ceiling applications where intermediate supports or gypsum board back-blocking is provided behind end joints. Do not place tapered edges against cut edges or ends. Stagger vertical joints on opposite sides of partitions. Do not make joints other than control joints at corners of framed openings.
E. Form control and expansion joints with space between edges of adjoining gypsum panels.
F. Cover both faces of support framing with gypsum panels in concealed spaces (above ceilings, etc.), except in chases braced internally.
1. Unless concealed application is indicated or required for sound, fire, air, or smoke ratings, coverage may be accomplished with scraps of not less than 8 sq. ft. in area.
2. Fit gypsum panels around ducts, pipes, and conduits.
3. Where partitions intersect structural members projecting below underside of floor/roof slabs and decks, cut gypsum panels to fit profile formed by structural members; allow 1/4- to 3/8-inch- wide joints to install sealant.
G. Isolate perimeter of gypsum board applied to non-load-bearing partitions at structural abutments. Provide 1/4- to 1/2-inch- wide spaces at these locations and trim edges with edge trim where edges of panels are exposed. Seal joints between edges and abutting structural surfaces with acoustical sealant.
GYPSUM BOARD 092900- 6
H. Attachment to Steel Framing: Attach panels so leading edge or end of each panel is attached to open (unsupported) edges of stud flanges first.
I. STC-Rated Assemblies: Seal construction at perimeters, behind control joints, and at openings and penetrations with a continuous bead of acoustical sealant. Install acoustical sealant at both faces of partitions at perimeters and through penetrations.
Comply with ASTM C919 and with manufacturer's written instructions for locating edge trim and closing off sound-flanking paths around or through assemblies, including sealing partitions above acoustical ceilings.
J. Install sound attenuation blankets before installing gypsum panels unless blankets are readily installed after panels have been installed on one side.
3.3 INSTALLATION OF INTERIOR GYPSUM BOARD
A. Install interior gypsum board in the following locations:
1. Wallboard Type: As indicated on Drawings.
2. Type X: As indicated on Drawings.
3. Mold-Resistant Type: As indicated on Drawings.
B. Single-Layer Application:
1. On ceilings, apply gypsum panels before wall/partition board application to greatest extent possible and at right angles to framing unless otherwise indicated.
2. On partitions/walls, apply gypsum panels vertically (parallel to framing) unless otherwise indicated or required by fire-resistance-rated assembly, and minimize end joints.
a. Stagger abutting end joints not less than one framing member in alternate courses of panels.
b. At high walls, install panels horizontally unless otherwise indicated or required by fire-resistance-rated assembly.
3. On Z-shaped furring members, apply gypsum panels vertically (parallel to framing) with no end joints. Locate edge joints over furring members.
4. Fastening Methods: Apply gypsum panels to supports with steel drill screws.
3.4 INSTALLATION OF TILE BACKING PANELS
A. Cementitious Backer Units: ANSI A108.11, at locations indicated to receive tile.
B. Where tile backing panels abut other types of panels in same plane, shim surfaces to produce a uniform plane across panel surfaces.
GYPSUM BOARD 092900- 7
3.5 INSTALLATION OF TRIM ACCESSORIES
A. General: For trim with back flanges intended for fasteners, attach to framing with same fasteners used for panels. Otherwise, attach trim according to manufacturer's written instructions.
B. Control Joints: Install control joints in accordance with ASTM C840 and in specific locations approved by Architect for visual effect.
C. Interior Trim: Install in the following locations:
1. Cornerbead: Use at outside corners unless otherwise indicated.
2. LC-Bead: Use at exposed panel edges.
3. L-Bead: Use where indicated on Drawings.
3.6 FINISHING OF GYPSUM BOARD
A. General: Treat gypsum board joints, interior angles, edge trim, control joints, penetrations, fastener heads, surface defects, and elsewhere as required to prepare gypsum board surfaces for decoration. Promptly remove residual joint compound from adjacent surfaces.
B. Prefill open joints and damaged surface areas.
C. Apply joint tape over gypsum board joints, except for trim products specifically indicated as not intended to receive tape.
D. Gypsum Board Finish Levels: Finish panels to levels indicated below and in accordance with ASTM C840:
1. Level 1: Ceiling plenum areas, concealed areas, and where indicated.
2. Level 4: At panel surfaces that will be exposed to view unless otherwise indicated.
a. Primer and its application to surfaces are specified in Section 099123
"Interior Painting."
E. Cementitious Backer Units: Finish according to manufacturer's written instructions.
3.7 PROTECTION
A. Protect adjacent surfaces from drywall compound and promptly remove from floors and other non-drywall surfaces. Repair surfaces stained, marred, or otherwise damaged during drywall application.
B. Protect installed products from damage from weather, condensation, direct sunlight, construction, and other causes during remainder of the construction period.
GYPSUM BOARD 092900- 8
C. Remove and replace panels that are wet, moisture damaged, and mold damaged.
1. Indications that panels are wet or moisture damaged include, but are not limited to, discoloration, sagging, or irregular shape.
2. Indications that panels are mold damaged include, but are not limited to, fuzzy or splotchy surface contamination and discoloration.
END OF SECTION 092900
TILING 093000 - 1
SECTION 093000 - TILING
1.1 SUMMARY
A. Section Includes:
1. Porcelain floor tile and base.
2. Glazed wall tile.
3. Waterproof membranes.
4. Crack isolation membranes.
5. Setting material.
6. Grout materials.
7. Metal edge strips.
B. Related Requirements:
1. Section 092900 "Gypsum Board" for tile backing panels.
1.2 DEFINITIONS
A. General: Definitions in ANSI A108 series of tile installation standards and in ANSI A137.1 apply to Work of this Section unless otherwise specified.
B. Face Size: Actual tile size, excluding spacer lugs.
C. Large Format Tile: Tile with at least one edge 15 inches or longer.
D. Module Size: Actual tile size plus joint width indicated.
1.3 PREINSTALLATION MEETINGS
A. Preinstallation Conference: Conduct conference at Project site.
1. Review requirements in ANSI A108.01 for substrates and for preparation by other trades.
2. Review requirements for aesthetics and joint alignment.
1.4 ACTION SUBMITTALS
B. Shop Drawings: Show locations, plans, and elevations, of each type of tile and tile pattern. Show widths, details, and locations of movement joints in tile substrates and finished tile surfaces. Show thresholds.
TILING 093000 - 2
C. Samples for Initial Selection: For tile, grout, and accessories involving color selection or shade variation.
D. Samples for Verification:
1. Full-size units of each type and composition of tile and for each color and finish required.
2. Full-size units of each type of trim and accessory.
3. Metal thresholds in 6-inch lengths.
4. Metal cove 6-inch lengths.
1.5 INFORMATIONAL SUBMITTALS
A. Qualification Data: For Installer.
B. Master Grade Certificates: For each shipment, type, and composition of tile, signed by tile manufacturer and Installer.
C. Product Certificates: For each type of product, including product use classification.
D. Product Test Reports:
1. Tile-setting and -grouting products.
2. Certified porcelain tile.
3. Slip-resistance test reports from qualified independent testing agency.
1.6 MAINTENANCE MATERIAL SUBMITTALS
A. Extra Stock Material: Furnish extra materials, from the same production run, to Owner that match products installed and that are packaged with protective covering for storage and identified with labels describing contents.
1. Tile and Trim Units: Furnish quantity of full-size units equal to 3 percent of amount installed for each type, composition, color, pattern, and size indicated.
2. Grout: Furnish quantity of grout equal to 3 percent of amount installed for each type, composition, and color indicated.
1.7 QUALITY ASSURANCE
A. Installer Qualifications:
1. Installer is a Five-Star member of the National Tile Contractors Association or a Trowel of Excellence member of the Tile Contractors' Association of America.
2. Installer's supervisor for Project holds the International Masonry Institute's Supervisor Certification.
TILING 093000 - 3
B. Mockups: Build mockups to verify selections made under Sample submittals and to demonstrate aesthetic effects and set quality standards for materials and execution.
1. Build mockup of each type of floor tile installation.
2. Build mockup of each type of wall tile installation.
3. Subject to compliance with requirements, approved mockups may become part of the completed Work if undisturbed at time of Substantial Completion.
1.8 DELIVERY, STORAGE, AND HANDLING
A. Deliver and store packaged materials in original containers with seals unbroken and labels intact until time of use. Comply with requirements in ANSI A137.1 for labeling tile packages.
B. Store tile and cementitious materials on elevated platforms, under cover, and in a dry location.
C. Store aggregates where grading and other required characteristics can be maintained and contamination can be avoided.
D. Store liquid materials in unopened containers and protected from freezing.
1.9 FIELD CONDITIONS
A. Environmental Limitations: Do not install tile until construction in spaces is complete and ambient temperature and humidity conditions are maintained at the levels indicated in "Referenced Standards" Article in the Evaluations and manufacturer's written instructions.
2.1 SOURCE LIMITATIONS
A. Tile: Obtain tile of each type from single source or producer.
1. Obtain tile of each type and color or finish from same production run and of consistent quality in appearance and physical properties for each contiguous area.
B. Tiling System: Obtain system products from single manufacturer and each aggregate from single source or producer.
1. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
a. ARDEX Americas.
b. Custom Building Products.
c. Laticrete International, Inc.
d. MAPEI Corporation.
TILING 093000 - 4
2. Obtain setting and grouting materials, except for unmodified portland cement and aggregate, from single manufacturer.
3. Obtain waterproof membrane, crack isolation, and other required membranes from manufacturer of setting and grouting materials.
4. Obtain joint sealants from manufacturer of setting and grouting materials.
C. Accessory Products: Obtain each of the following products specified in this Section from a single manufacturer:
1. Backer units.
2.2 PRODUCTS, GENERAL
A. ANSI Ceramic Tile Standard: Provide tile that complies with ANSI A137.1 for types, compositions, and other characteristics indicated.
1. Provide tile complying with Standard Grade requirements.
B. ANSI Standards for Tile Installation Materials: Provide materials complying with ANSI A108.02, ANSI standards referenced in other Part 2 articles, ANSI standards referenced by TCNA installation methods specified in tile installation schedules, and other requirements specified.
C. Factory Blending: For tile exhibiting color variations within ranges, blend tile in factory and package so tile units taken from one package show same range in colors as those taken from other packages and match approved Samples.
D. Mounting: For factory-mounted tile, provide back- or edge-mounted tile assemblies as standard with manufacturer unless otherwise indicated.
1. Where tile is indicated for installation in wet areas, do not use back- or edge-mounted tile assemblies unless tile manufacturer specifies in writing that this type of mounting is suitable for installation indicated and has a record of successful in-service performance.
2.3 TILE PRODUCTS
A. Ceramic Tile Type: Unglazed porcelain floor tile
1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to the following:
a. American Olean; a brand of Dal-Tile Corporation.
b. Crossville, Inc.
c. Daltile; a brand of Dal-Tile Corporation.
2. Certification: Tile certified by the Porcelain Tile Certification Agency.
3. Face Size: 11-13/16 by 11-13/16 inches.
4. Face Size Variation: Rectified.
5. Thickness: 5/16 inch.
TILING 093000 - 5
6. Face: Plain with square or cushion edges.
7. Dynamic Coefficient of Friction: Not less than 0.42.
8. Tile Color, Glaze, and Pattern: As selected by Architect from manufacturer's full range.
9. Grout Color: As selected by Architect from manufacturer's full range.
10. Trim Units: Coordinated with sizes and coursing of adjoining flat tile where applicable and matching characteristics of adjoining flat tile. Provide shapes as follows, selected from manufacturer's standard shapes:
a. Base Cap: Surface bullnose, module size same as adjoining flat tile by 3 inches high.
B. Ceramic Tile Type: Glazed wall tile.
1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to the following:
a. American Olean; a division of Dal-Tile Corporation.
b. Daltile.
c. Crossville.
2. Module Size: 4-1/4 by 4-1/4 inches (108 by 108 mm).
3. Face Size Variation: Rectified.
4. Thickness: 5/16 inch (8 mm).
5. Face: Plain with modified square edges or cushion edges.
6. Finish: Mat, opaque glaze.
7. Tile Color and Pattern: As selected by Architect from manufacturer's full range.
8. Grout Color: As selected by Architect from manufacturer's full range.
9. Mounting: Factory, back mounted.
10. Trim Units: Coordinated with sizes and coursing of adjoining flat tile where applicable and matching characteristics of adjoining flat tile. Provide shapes as follows, selected from manufacturer's standard shapes:
a. Wainscot Cap for Thinset Mortar Installations: Surface bullnose, module size
4-1/4 by 4-1/4 inches (108 by 108 mm).
2.4 TILE BACKING PANELS
A. Cementitious Backer Units: See Section 092900 “Gypsum Board.”
2.5 WATERPROOF MEMBRANES
A. General: Manufacturer's standard product that complies with ANSI A118.10 and is recommended by manufacturer for application indicated. Include reinforcement and accessories recommended by manufacturer.
TILING 093000 - 6
B. Polyethylene Sheet: Polyethylene sheet faced on both sides with fleece webbing
1. Basis-of-Design Product: Subject to compliance with requirements, provide Schluter Systems L.P.; Kerdi Membrane, or comparable product, approved by the Architect, by one of the following:
a. ARDEX Americas.
b. Laticrete International, Inc.
c. MAPEI Corporation.
2. Nominal Thickness: 0.008 inch.
2.6 CRACK ISOLATION MEMBRANE AND UNCOUPLING MEMBRANE
A. Corrugated Polyethylene: Corrugated polyethylene with dovetail-shaped corrugations and with anchoring webbing on the underside; 3/16-inch (4-mm) nominal thickness.
1. Manufacturers: Subject to compliance with requirements, provide products by the following:
a. Schluter Systems L.P.
2. Basis-of-Design Product: Subject to compliance with requirements, provide Schluter Systems L.P.; Ditra, or comparable product, approved by the Architect, by one of the following:
a. ARDEX Americas.
b. Laticrete International, Inc.
c. MAPEI Corporation.
2.7 SETTING MATERIALS
A. Standard Dry-Set Mortar (Unmodified Thinset): ANSI A118.1.
1. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
a. ARDEX Americas.
b. Custom Building Products.
c. Laticrete International, Inc.
d. MAPEI Corporation.
2. For wall applications, provide mortar that complies with requirements for nonsagging mortar in addition to other requirements in ANSI A118.1.
2.8 GROUT MATERIALS
A. Water-Cleanable Epoxy Grout: ANSI A118.3 , with a VOC content of 65 g/L or less.
1. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
a. ARDEX Americas.
b. Custom Building Products.
c. Laticrete International, Inc.
TILING 093000 - 7
2. Provide product capable of withstanding continuous and intermittent exposure to temperatures of up to 140 and 212 degrees F, respectively, and certified by manufacturer for intended use.
2.9 MISCELLANEOUS MATERIALS
A. Trowelable Underlayments and Patching Compounds: Latex-modified, portland cement-based formulation provided or approved by manufacturer of tile-setting and adhesive materials for installations indicated.
B. Metal Cove: Designed specifically for flooring applications; stainless steel, ASTM A276/A276M or ASTM A666, 300 Series.
1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to the following:
a. Schluter – Dilex – EHK, including all accessories for a complete job.
C. Tile Cleaner: A neutral cleaner capable of removing soil and residue without harming tile and grout surfaces, specifically approved for materials and installations indicated by tile and grout manufacturers.
D. Grout Sealer: Manufacturer's standard product for sealing grout joints and that does not change color or appearance of grout.
1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:
a. Bonsal American, an Oldcastle company.
b. Bostik, Inc.
c. LATICRETE SUPERCAP, LLC.
2.10 MIXING MORTARS AND GROUT
A. Mix mortars and grouts to comply with referenced standards and mortar and grout manufacturers' written instructions.
B. Add materials, water, and additives in accurate proportions.
C. Obtain and use type of mixing equipment, mixer speeds, mixing containers, mixing time, and other procedures to produce mortars and grouts of uniform quality with optimum performance characteristics for installations indicated.
TILING 093000 - 8
A. Examine substrates, areas, and conditions where tile will be installed, with Installer present, for compliance with requirements for installation tolerances and other conditions affecting performance of the Work.
1. Verify that substrates for setting tile are firm; dry; clean; free of coatings that are incompatible with tile-setting materials, including curing compounds and other substances that contain soap, wax, oil, or silicone; and comply with flatness tolerances required by ANSI A108.01 for installations indicated.
2. Verify that concrete substrates for tile floors installed with thinset mortar comply with surface finish requirements in ANSI A108.01 for installations indicated.
a. Verify that surfaces that received a steel trowel finish have been mechanically scarified.
b. Verify that protrusions, bumps, and ridges have been removed by sanding or grinding.
3. Verify that installation of grounds, anchors, recessed frames, electrical and mechanical units of work, and similar items located in or behind tile has been completed.
4. Verify that joints and cracks in tile substrates are coordinated with tile joint locations; if not coordinated, adjust joint locations in consultation with Architect.
A. Fill cracks, holes, and depressions in concrete substrates for tile floors installed with thinset mortar with trowelable leveling and patching compound specifically recommended by tile-setting material manufacturer.
B. Blending: For tile exhibiting color variations, verify that tile has been factory blended and packaged so tile units taken from one package show same range of colors as those taken from other packages and match approved Samples. If not factory blended, either return to manufacturer or blend tiles at Project site before installing.
3.3 INSTALLATION OF CERAMIC TILE SYSTEM
A. Install tile backing panels and treat joints in accordance with ANSI A108.11 and manufacturer's written instructions for type of application indicated.
B. Install waterproof membrane to comply with ANSI A108.13 and manufacturer's written instructions to produce waterproof membrane of uniform thickness that is bonded securely to substrate.
1. Allow waterproof membrane to cure and verify by testing that it is watertight before installing tile or setting materials over it.
TILING 093000 - 9
C. Install crack isolation membrane to comply with ANSI A108.17 and manufacturer's written instructions to produce membrane of uniform thickness that is bonded securely to substrate.
1. Allow crack isolation membrane to cure before installing tile or setting materials over it.
D. Mix mortars and grouts to comply with "Referenced Standards" Article in the Evaluations and mortar and grout manufacturers' written instructions.
1. Add materials, water, and additives in accurate proportions.
2. Obtain and use type of mixing equipment, mixer speeds, mixing containers, mixing time, and other procedures to produce mortars and grouts of uniform quality with optimum performance characteristics for installations indicated.
E. Install tile in accordance with TCNA's "Handbook for Ceramic, Glass, and Stone Tile Installation" for TCNA installation methods specified in tile installation schedules. Comply with parts of ANSI A108 series that are referenced in TCNA installation methods and specified in tile installation schedules, and apply to types of setting and grouting materials used.
1. For the following installations, follow procedures in ANSI A108 series of tile installation standards for providing 95 percent mortar coverage:
a. Tile floors in wet areas.
b. Tile floors consisting of tiles 8 by 8 inches or larger.
2. Extend tile work into recesses and under or behind equipment and fixtures to form complete covering without interruptions unless otherwise indicated. Terminate work neatly at obstructions, edges, and corners without disrupting pattern or joint alignments.
3. Accurately form intersections and returns. Perform cutting and drilling of tile without marring visible surfaces. Carefully grind cut edges of tile abutting trim, finish, or built-in items for straight aligned joints. Fit tile closely to electrical outlets, piping, fixtures, and other penetrations so plates, collars, or covers overlap tile.
4. Provide manufacturer's standard trim shapes where necessary to eliminate exposed tile edges.
5. Jointing Pattern: Lay tile in grid pattern unless otherwise indicated. Lay out tile work and center tile fields in both directions in each space or on each wall area. Lay out tile work to minimize use of pieces that are less than half of a tile. Provide uniform joint widths unless otherwise indicated.
a. Where adjoining tiles on floor, base, walls, or trim are specified or indicated to be same size, align joints.
b. Where tiles are specified or indicated to be whole integer multiples of adjoining tiles on floor, base, walls, or trim, align joints unless otherwise indicated.
F. Metal Flooring Transitions: Install at locations indicated.
G. Grout Sealer: Apply grout sealer to grout joints in accordance with manufacturer's written instructions. As soon as sealer has penetrated grout joints, remove excess sealer and sealer from tile faces by wiping with soft cloth.
TILING 093000 - 10
3.4 ADJUSTING AND CLEANING
A. Remove and replace tile that is damaged or that does not match adjoining tile. Provide new matching units, installed as specified and in a manner to eliminate evidence of replacement.
B. Cleaning: On completion of placement and grouting, clean all ceramic tile surfaces so they are free of foreign matter.
1. Remove grout residue from tile as soon as possible.
2. Clean grout smears and haze from tile in accordance with tile and grout manufacturer's written instructions. Use only cleaners recommended by tile and grout manufacturers and only after determining that cleaners are safe to use by testing on samples of tile and other surfaces to be cleaned. Protect metal surfaces and plumbing fixtures from effects of cleaning. Flush surfaces with clean water before and after cleaning.
3.5 PROTECTION
A. Protect installed tile work with kraft paper or other heavy covering during construction period to prevent staining, damage, and wear. If recommended by tile manufacturer, apply coat of neutral protective cleaner to completed tile walls and floors.
B. Prohibit foot and wheel traffic from tiled floors for at least seven days after grouting is completed.
C. Before final inspection, remove protective coverings and rinse neutral protective cleaner from tile surfaces.
3.6 INTERIOR CERAMIC TILE NSTALLATION SCHEDULE
A. Interior Floor Installations, Concrete Subfloor:
1. Ceramic Tile Installation: TCNA F122; thinset mortar over waterproof membrane.
a. Ceramic Tile Type: Porcelain.
b. Thinset Mortar: Unmodified dry-set mortar.
c. Grout: Water-cleanable epoxy grout.
B. Interior Wall Installations, Metal Studs:
1. Ceramic Tile Installation: TCNA W244C; thinset mortar over waterproof membrane on cementitious backer units.
a. Ceramic Tile Type: Porcelain.
b. Thinset Mortar: Unmodified dry-set mortar.
c. Grout: Water-cleanable epoxy grout.
END OF SECTION 093000
ACOUSTICAL PANEL CEILINGS 095113- 1
SECTION 095113 - ACOUSTICAL PANEL CEILINGS
PART 1 - GENERAL
1.1 SUMMARY
A. Section Includes:
1. Acoustical panels.
2. Metal suspension system.
3. Metal edge moldings and trim.
1.2 PREINSTALLATION MEETINGS
A. Preinstallation Conference: Conduct conference at Project site.
1.3 ACTION SUBMITTALS
A. Product Data:
1. Acoustical panels.
2. Metal suspension system.
3. Metal edge moldings and trim.
B. Samples for Verification: For each component indicated and for each exposed finish required, prepared on Samples of sizes indicated below:
1. Acoustical Panels: Set of 6-inch- square Samples of each type, color, pattern, and texture.
2. Exposed Suspension-System Members, Moldings, and Trim: Set of 6-inch- long Samples of each type, finish, and color.
3. Clips: Full-size seismic clips.
C. Delegated Design Submittals: For seismic restraints for ceiling systems.
1. Include design calculations for seismic restraints including analysis data signed and sealed by the qualified professional engineer responsible for their preparation.
1.4 INFORMATIONAL SUBMITTALS
A. Coordination Drawings: Reflected ceiling plans, drawn to scale, on which the following items are shown and coordinated with each other, using input from installers of the items involved:
1. Ceiling suspension-system members.
ACOUSTICAL PANEL CEILINGS 095113- 2
2. Structural members to which suspension systems will be attached.
3. Method of attaching hangers to building structure.
a. Furnish layouts for cast-in-place anchors, clips, and other ceiling attachment devices whose installation is specified in other Sections.
4. Carrying channels or other supplemental support for hanger-wire attachment where conditions do not permit installation of hanger wires at required spacing.
5. Size and location of initial access modules for acoustical panels.
6. Items penetrating finished ceiling and ceiling-mounted items including the following:
a. Lighting fixtures.
b. Diffusers.
c. Grilles.
d. Speakers.
e. Sprinklers.
f. Access panels.
g. Perimeter moldings.
7. Minimum Drawing Scale: 1/4 inch = 1 foot.
B. Qualification Data: For testing agency.
C. Product Test Reports: For each acoustical panel ceiling, for tests performed by a qualified testing agency.
D. Evaluation Reports: For each acoustical panel ceiling suspension system and anchor and fastener type, from ICC-ES.
E. Field quality-control reports.
1.5 CLOSEOUT SUBMITTALS
A. Maintenance Data: For finishes to include in maintenance manuals.
1.6 MAINTENANCE MATERIAL SUBMITTALS
A. Furnish extra materials , from the same product run, that match products installed and that are packaged with protective covering for storage and identified with labels describing contents.
1. Acoustical Ceiling Units: Full-size panels equal to 2 percent of quantity installed.
2. Suspension-System Components: Quantity of each exposed component equal to
2 percent of quantity installed.
ACOUSTICAL PANEL CEILINGS 095113- 3
1.7 DELIVERY, STORAGE, AND HANDLING
A. Deliver acoustical panels, suspension-system components, and accessories to Project site and store them in a fully enclosed, conditioned space where they will be protected against damage from moisture, humidity, temperature extremes, direct sunlight, surface contamination, and other causes.
B. Before installing acoustical panels, permit them to reach room temperature and a stabilized moisture content.
1.8 FIELD CONDITIONS
A. Environmental Limitations: Do not install acoustical panel ceilings until spaces are enclosed and weathertight, wet-work in spaces is complete and dry, work above ceilings is complete, and ambient temperature and humidity conditions are maintained at the levels indicated for Project when occupied for its intended use.
PART 2 - PRODUCTS
2.1 SOURCE LIMITATIONS
A. Source Limitations for Ceiling System: Obtain each type of acoustical ceiling panel and its supporting suspension system from single source from single manufacturer.
2.2 PERFORMANCE REQUIREMENTS
A. Delegated Design: Engage a qualified professional engineer, as defined in Section 014000 "Quality Requirements," to design seismic restraints for ceiling systems.
B. Seismic Performance: Suspended ceilings to withstand the effects of earthquake motions determined in accordance with ASCE/SEI 7.
C. Surface-Burning Characteristics: Comply with ASTM E84; testing by a qualified testing agency. Identify products with appropriate markings of applicable testing agency.
1. Flame-Spread Index: Class A in accordance with ASTM E1264.
2. Smoke-Developed Index: 50 or less.
2.3 ACOUSTICAL PANELS AND SUSPENSION SYSTEMS (ACT-1)
A. Basis-of-Design Product: Subject to compliance with requirements, provide one of the following products, or comparable product, approved by the Architect:
1. Armstrong; Ultima #1941 with Prelude XL HD grid #7301 and #7803, 7/8” molding per ICC Evaluation Report with BERC clips
2. USG; Mars #87200 with Donn DX 26 HD Grid and 7/8” USG M7 molding per ICC Evaluation Report #ESR-1222
B. Classification: Provide panels as follows:
ACOUSTICAL PANEL CEILINGS 095113- 4
1. Type and Form, Type IV Form 2: Mineral base with membrane-faced overlay;
Form 2, water felted; with vinyl overlay on face.
2. Pattern: C (perforated, small holes) and E (lightly textured).
C. Color: White.
D. Light Reflectance (LR): Not less than 0.85.
E. Ceiling Attenuation Class (CAC): Not less than 35.
F. Noise Reduction Coefficient (NRC): Not less than 0.80.
G. Articulation Class (AC): Not less than 170.
H. Edge/Joint Detail: Beveled tegular.
I. Thickness: 7/8 inch.
J. Modular Size: 24 by 24 inches.
2.4 ACOUSTICAL PANELS AND SUSPENSION SYSTEMS (ACT-2)
A. Basis-of-Design Product: Subject to compliance with requirements, provide one of the following products, or comparable product, approved by the Architect:
1. Armstrong; Dune #1772 square edge with Prelude XL 15/16” grid, 7/8” molding per ICC Evaluation Report with BERC clips
2. USG; Olympia Micro #4211 square edge with USG Donn DXW 7/8” USG M7 molding per ICC Evaluation Report #ESR-1222.
B. Classification: Provide panels as follows:
1. Composition: Mineral Fiber
2. Pattern: Fine Texture
C. Color: White.
D. Light Reflectance (LR): Not less than 0.81.
E. Ceiling Attenuation Class (CAC): Not less than 35.
F. Noise Reduction Coefficient (NRC): Not less than 0.50.
G. Articulation Class (AC): Not less than 170.
H. Edge/Joint Detail: Square Lay-in
I. Thickness: 5/8 inch.
J. Modular Size: 24 by 24 inches.
ACOUSTICAL PANEL CEILINGS 095113- 5
2.4 ACOUSTICAL PANELS AND SUSPENSION SYSTEMS (ACT-3 in kitchen)
A. Basis-of-Design Product: Subject to compliance with requirements, provide one of the following products, or comparable product approved by the Architect:
1. Armstrong; Ceramaguard #607 with Prelude 7301G90 Grid and Gordon Grid Co.
pattern CG-WA-20 2-inch wall angle molding.
2. USG; Radar Ceramic Panels; Donn DX 26 HD Grid and 7/8” USG M7 molding per ICC Evaluation Report #ESR-1222
B. Acoustical Panel Standard: Provide manufacturer's standard panels in accordance with ASTM E1264 and designated by type, form, pattern, acoustical rating, and light reflectance unless otherwise indicated.
C. Classification: Provide fire-resistance-rated panels as follows:
1. Type, Type XX: High-density, ceramic- and mineral-base panels with scrubbable finish, resistant to heat, moisture, and corrosive fumes.
2. Pattern: C (perforated, small holes) and E (lightly textured).
D. Color: White.
E. Light Reflectance (LR): Not applicable.
F. Ceiling Attenuation Class (CAC): Not less than 38.
G. Noise Reduction Coefficient (NRC): Not less than 0.55.
H. Articulation Class (AC): Not applicable.
I. Edge/Joint Detail: Square.
J. Thickness: 5/8 inch, per manufacturer.
K. Modular Size: 24 inches by 24 inches.
2.5 METAL SUSPENSION SYSTEM
A. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
1. Armstrong Ceiling & Wall Solutions.
2. USG Corporation.
B. Metal Suspension-System Standard: Provide manufacturer's standard, direct-hung, metal suspension system and accessories in accordance with ASTM…