The document is a comprehensive Facilities Design and Specification Manual for Cherokee County Property Management, covering multiple technical specification sections for building construction and infrastructure systems. The manual provides detailed technical guidelines for various building components including door hardware, hollow metal and wood doors, fire alarm systems, fire suppression, HVAC specifications, and access control systems. The specification manual establishes precise requirements for manufacturers, materials, installation methods, product performance, testing, and quality assurance across multiple building system disciplines.
The manual represents a standardized approach to facility construction and renovation for Cherokee County, specifying preferred manufacturers, technical performance standards, and installation protocols for critical building systems. Key manufacturers include Carrier, Trane, Schlage, Von Duprin, and Honeywell, with specific requirements for product lines and technical capabilities. The document emphasizes compatibility with existing county infrastructure, particularly in areas like HVAC controls (Carrier i-Vu Open system) and access control (Honeywell Commercial Security systems), indicating a strategic approach to maintaining consistency across county facilities. The specifications also include detailed requirements for environmental considerations, energy efficiency, maintenance, and long-term performance of building systems.
View the file
Other files
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CCPM REV. 8/8/2024
Cherokee County Property Management
Facilities Design and Specification Manual
These guidelines are unique to Cherokee County and should be reviewed and understood by all design professionals responsible for the project to help ensure best-in-class execution.
Cherokee County Property Management Facilities Design and Specification Manual
Table of Contents Table of Contents
Door Hardware Specification
THE PROCESS
PART 1 GENERAL
1.1 RELATED DOCUMENTS
1.2 SUMMARY
1.3 REFRENCES
1.4 SYSTEM DESCRIPTION
1.5 SUBMITTALS
1.6 QUALITY ASSURANCE
1.7 PRODUCT HANDLING
1.6 WARRANTY
1.9 MAINTENANCE
PART 2 – PRODUCTS
2.1 HINGES:
2.2 CONTINUOUS HINGES:
2.3 CYLINDERS:
2.4 LOCKSETS, LATCHSETS, DEADBOLTS:
2.5 EXTRA HEAVY-DUTY CYLINDRICAL LOCKS AND LATCHES:
2.6 EXIT DEVICES:
2.7 ELECTRIC STRIKES:
2.8 CLOSERS AND DOOR CONTROL DEVICES:
2.9 OVERHEAD DOOR HOLDERS:
2.10 FLOOR STOPS AND WALL BUMPERS:
2.11 DOOR BOLTS/COORDINATORS:
2.12 PUSH PLATES:
2.14 DOOR PUSH SETS:
2.15 PROTECTIVE PLATES:
2.16 THRESHOLDS:
2.17 DOOR SEALS/GASKETING:
2.18 SILENCERS:
2.19 SECURITY EQUIPMENT:
PART 3 - MATERIALS AND FABRICATION
3.1 MANUFACTURER'S NAME PLATE:
3.2 BASE METALS:
3.3 FASTENERS:
3.4 HARDWARE FINISHES
PART 4 - EXECUTION
4.1 INSTALLATION
4.2 ADJUSTING, CLEANING, AND DEMONSTRATING
PART 5 – HARDWARE SCHEDULE
5.1 WRITTEN HARDWARE SCHEDULE
END OF SECTION
Hollow Metal Door and Frame Specification Guide
PART 1 – GENERAL
1.01 SUMMARY
1.02 REFERENCES
1.03 SUBMITTALS
1.04 QUALITY ASSURANCE
1.05 DELIVERY, STORAGE, AND HANDLING
1.06 WARRANTY
PART 2 - PRODUCTS
2.01 MANUFACTURERS
2.02 MATERIALS
2.03 DOORS
2.04 FRAMES
2.05 FABRICATION
PART 3 - EXECUTION
3.01 INSTALLATION
3.02 ADJUSTING AND CLEANING
END OF SECTION
FLUSH WOOD DOORS SECTION 08-1400
PART 1 – GENERAL
1.01 SUMMARY
1.02 REFERENCES
1.03 SUBMITTALS
1.04 QUALITY ASSURANCE
1.05 DELIVERY, STORAGE, AND HANDLING
1.06 WARRANTY
PART 2 - PRODUCTS
2.01 MANUFACTURERS
2.02 FIRE RATED DOORS
2.03 DOORS
2.04 FACTORY FINISHING
2.05 LIGHT FRAMES
2.06 LOUVERS
2.07 FABRICATION
PART 3 - EXECUTION
3.01 EXAMINATION
3.02 INSTALLATION
3.03 ADJUSTING AND PROTECTING
END OF SECTION
Impact Resistance Doors (FRP) 08-1105
PART 1 - GENERAL
1.1 SUMMARY
1.2 REFERENCES
1.3 SUBMITTALS
1.4 QUALITY ASSURANCE
1.5 WARRANTY
PART 2 – PRODUCTS
2.1 MANUFACTURERS:
2.2 MATERIALS AND ACCESSORIES
2.3 FABRICATION
2.4 FIBERGLASS REINFORCED POLYESTER FRP FLUSH DOORS
2.5 ALUMINUM FRAMING SYSTEMS
2.6 GLAZING
2.7 DOOR HARDWARE
2.8 ALUMINUM FINISHES
PART 3 - EXECUTION
3.1 ACCEPTABLE INSTALLERS
3.2 INSTALLATION
3.3 CLEANING
END OF SECTION
Fire Alarm Specification Guide
PART 1 GENERAL
1.1. DESCRIPTION
1.2. SCOPE
1.3. SUBMITTALS
1.4. GUARANTEE:
1.5. POST CONTRACT MAINTENANCE:
1.6. POST CONTRACT EXPANSIONS:
1.7. APPLICABLE PUBLICATIONS:
1.8. APPROVALS:
PART 2 PRODUCTS
2.1. EQUIPMENT AND MATERIAL, GENERAL:
2.2. CONDUIT AND WIRE:
2.3. MAIN FIRE ALARM CONTROL PANEL OR NETWORK NODE
2.4. ANNUNCIATOR:
2.5. SYSTEM COMPONENTS - ADDRESSABLE DEVICES
2.6. BATTERIES AND EXTERNAL CHARGER:
PART 3 EXECUTION
3.1. INSTALLATION:
3.2. TYPICAL OPERATION:
3.3. TEST:
3.4. FINAL INSPECTION:
3.5. INSTRUCTION:
END OF SECTION
Fire Suppression 13900
PART 1 GENERAL
1.1 SUMMARY
1.2 SYSTEM DESCRIPTION
1.3 SUBMITTALS
1.4 CHARTS AND TAGS
1.5 CLOSEOUT SUBMITTALS
1.6 QUALITY ASSURANCE
PART 2 PRODUCTS
2.1 EQUIPMENT AND MATERIAL
2.2 PIPE AND TUBE
2.3 GATE VALVES
2.4 BUTTERFLY VALVES
2.5 CHECK VALVES
2.6 DRAIN VALVES
2.7 SPRINKLERS
2.8 SPRINKLER PIPING SPECIALTIES
2.9 STANDPIPE EQUIPMENT
2.10 FIRE DEPARTMENT CONNECTION
2.11 FIRE PUMP
2.12 PRESSURE BOOSTER (JOCKEY) PUMP
2.13 ELECTRICAL CHARACTERISTICS AND COMPONENTS
PART 3 EXECUTION
3.1 INSTALLATION
3.2 HYDRAULIC PLACARD / DATA PLATE
15000 HVAC Specifications
SECTION 15010 – MECHANICAL GENERAL
PART 1 GENERAL
1.1 GENERAL REQUIREMENTS
1.2 EQUIPMENT IDENTIFICATION
1.3 PIPE IDENTIFICATION
1.4 EQUIPMENT & MATERIAL PROTECTION
END OF SECTION 15010
SECTION 15015 – AIR FILTRATION AND AIR QUALITY
PART 1 GENERAL
1.1 GENERAL
PART 2 PRODUCTS
2.1 BASIS OF DESIGN
2.2 FILTERS
2.3 FILTER CABINETS
2.4 IONIZATION AIR PURIFICATION SYSTEM
SECTION 15020 – HVAC INSULATION
PART 1 GENERAL
1.1 GENERAL
PART 2 PRODUCTS
2.1 BASIS OF DESIGN
2.2 DUCT INSULATION
2.3 PIPE INSULATION
SECTION 15650 DDC Controls
Part 1 i-Vu Open Requirements
1.1 Summary
1.2 New or Existing Buildings not currently connected to the network:
1.3 Roof Top Units, heat pumps, or split systems
1.4 Dedicated Outside Air Systems
1.5 Fan Coil Units with chilled water and/or hot water or electric heat
1.6 Exhaust Fan Control
1.7 Modular Central Station VAV Air Handling Units
1.8 VAV System Terminal Boxes
1.9 Modular Central Station Constant Volume Air Handling Units
1.10 Chillers
1.11 Boilers
1.12 Support Equipment for Chilled Water or Hot Water Systems
End of Section
SECTION 15750 – Major HVAC Equipment
PART 1 GENERAL
1.1 GENERAL
1.2 BASIS OF DESIGN
SECTION 28 10 00 ACCESS CONTROL
PART 1 - GENERAL
1.1 SECTION INCLUDES
1.2 RELATED SECTIONS
1.3 REFERENCES
1.4 SECURITY MANAGEMENT SYSTEM DESCRIPTION
1.5 SUBMITTALS
1.6 QUALITY ASSURANCE
1.7 DELIVERY, STORAGE, AND HANDLING
1.8 WARRANTY
PART 2 - PRODUCTS
2.1 MANUFACTURERS
2.2 ACCESS AND SECURITY MANAGEMENT SYSTEM (PRO4200)
2.3 INTEGRATED SECURITY MANAGEMENT SYSTEM (ISMS)
2.4 ACCESS CONTROL READERS (Data security with Omni Class cards.)
2.5 ACCESS CONTROL CREDENTIALS
2.6 ACCESS CONTROL CABLES
PART 3 - EXECUTION
3.1 EXAMINATION
3.2 PREPARATION
3.3 INSTALLATION
3.4 FIELD TESTING AND CERTIFICATION
3.5 PROTECTION
END OF SECTION
CCPM REV. 8/8/2024
Cherokee County Property Management Door Hardware Specification
80 - 7100
Cherokee County Hardware Guide Spec Process
THE PROCESS
1. Latest revision of the Cherokee County Property Mgmt. Door and Hardware Guide Spec is provided to the Architect firm by Cherokee County Project Manager.
2. Architect is to complete the door and hardware schedule using the CCPM Door and Hardware Guide
Specification as a guideline and submit it to CCPM for approval.
Contact person to assist with the schedule is:
ALLEGION
Krystina B. Regan Allegion Specification Consultant 678-906-2106 Mobile- 678-353-4854 Krystina.Regan@Allegion.com
3. When the Architect completes the door and hardware schedule it is then sent to CCPM for approval. Once approved, the architect includes the door and hardware schedule in the bid set documents.
(Note: This is prior to the RFP process so that all door and hardware information needed for the GC to properly estimate the project will be in the original bid set documents.)
4. General Contractor will submit his proposed door/hardware information that meet the door/hardware specification to the architect and owner for review and acceptance.
5. Once approved, CCPM will order the permanent cores to match the door/hardware schedule and forward the invoice for the cores to the CC Project Manager to be paid out of the project budget. This process should ensure the permanent cores are available at final punch.
It is necessary for this process to take place to avoid the confusion about the hardware that is used and potential change orders being needed.
CC = Cherokee County Board of Commissioners
CCPM = Cherokee County Property Management
PART 1 GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this Section.
1.2 SUMMARY
A. This Section includes items known commercially as finish or door hardware that are required for swing, sliding, and folding doors, except special types of unique hardware specified in the same sections as the doors and door frames on which they are installed.
B. This Section includes the following:
Hinges Continuous Hinges Pivots
Spring Hinges Key Control System Lock cylinders and keys
Lock and latch Bolts Exit devices
Push/Pull Units Closers Overhead holders
Misc. door control devices Door trim unit Protection plates
Weather stripping Sound stripping Automatic drop seals
C. Related Sections: The following Sections contain requirements that relate to this Section:
1. Section 01 2000: Price and Payment Procedures
2. Section 08 1113: Hollow Metal Doors and Frames
3. Section 08 1400: Flush Wood Doors
4. Section 08 1150: Impact Resistance Doors (FRP)
5. Section 08 3323: Coiling Doors
6. Section 08 4113: Aluminum-Framed Entrances and Storefronts
D. Products furnished but not installed under this Section to include:
1. Cylinders for locks on entrance doors.
2. Owner will purchase final cores and keys with project funds.
3. Final replacement cores and keys to be installed by Owner.
1.3 REFRENCES
Standards of the following as referenced:
1. American National Standards Institute (ANSI)
2. Door and Hardware Institute (DHI)
3. Factory Mutual (FM)
4. National Fire Protection Association (NFPA)
5. Underwriters' Laboratories, Inc. (UL)
a. UL 10C - Fire Tests Door Assemblies
6. Warnock Hersey
B. Regulatory standards of the following as referenced:
1. Department of Justice, Office of the Attorney General, Americans with Disabilities Act, Public Law 101-336 (ADA).
2. CABO/ANSI A117.1: Providing Accessibility and Usability for Physically Handicapped People, 1992 edition.
1.4 SYSTEM DESCRIPTION
A. Refer to applicable “Headings” for system description for electric and electro-pneumatic hardware products.
1.5 SUBMITTALS
A. Submittals for all doors, store front, all hardware and / or any other section 8 door products to be reviewed and approved by CCPM. See page 11, Cherokee County Hardware Guide Spec Process.
B. Product data including manufacturers' technical product data for each item of door hardware, installation instructions, maintenance of operating parts and finish, and other information necessary to show compliance with requirements. For items other than those scheduled in the “Headings” of Section 3, provide catalog information for the specified items and for those submitted.
C. Final hardware schedule coordinated with doors, frames, and related work to ensure proper size, thickness, hand, function, and finish of door hardware.
1. Final Hardware Schedule Content: Based on hardware indicated, organize schedule into vertical format “hardware sets" indicating complete designations of every item required for each door or opening. Use specification Heading numbers with any variations suffixed a, b, etc. Include the following information:
D. Contract closeout submittals:
1. Operation and maintenance data: Complete information for installed door hardware.
2. Warranty: Completed and executed warranty forms.
1.6 QUALITY ASSURANCE
A. Single Source Responsibility: Obtain each type of hardware (latch and locksets, hinges, closers, etc.) from a single manufacturer.
B. Supplier Qualifications: A recognized architectural door hardware supplier, with warehousing facilities in the Project's vicinity, that has a record of successful in-service performance for supplying door hardware similar in quantity, type, and quality to that indicated for this Project and that employs an experienced Architectural Hardware Consultant (AHC) who is available for consultation to Owner, Architect, and Contractor, at reasonable times during the course of the Work.
C. Coordination Meetings:
1. Contractor shall set up and attend the following:
a. Lock distributor to meet with the Owner to finalize lock functions and keying requirements and to obtain final instructions in writing.
b. Lock distributor and lock, closer and exit device manufacturer to meet with the installer prior to beginning of installation of door hardware. Instruct installer on proper installation of specified products.
2. General Contractor shall set up and attend the following:
a. Meet with the Owner, General Contractor, Supplier, electrical and security contractors to coordinate all electrical hardware items. Supplier to provide riser diagrams, elevation drawings, wiring diagrams and operational descriptions as required by the General and sub-contractors.
D. Fire-Rated Openings: Provide door hardware for fire-rated openings that complies with NFPA Standard No. 80 requirements of authorities having jurisdiction. Provide only items of door hardware that are listed and tested by UL or Warnock Hersey for given type/size opening and degree of label. Provide proper latching hardware, door closers, approved-bearing hinges and seals whether listed in the Hardware Schedule or not. All hardware shall comply with State and local codes and UL 10C.
1. Where emergency exit devices are required on fire-rated doors, (with supplementary marking on doors’ UL labels indicating “Fire Door to be equipped with Fire Exit Hardware”) provide UL label on exit devices indicating “Fire Exit Hardware”.
E. All hardware is to comply with Federal and State Handicap laws. Provide tactile warning at the back of all outside levers to electrical, mechanical, machine rooms and doors that lead to hazardous areas.
1.7 PRODUCT HANDLING
A. Tag each item or package separately with identification related to final hardware schedule, and include basic installation instructions with each item or package.
B. Packaging of door hardware is responsibility of supplier. As material is received by hardware supplier from various manufacturers, sort and repackage in containers clearly marked with appropriate hardware set number to match set numbers of approved hardware schedule. Two or more identical sets may be packed in same container.
C. Inventory door hardware jointly with representatives of hardware supplier and hardware installer until each is satisfied that count is correct.
D. Deliver individually packaged door hardware items promptly to place of installation (shop or Project site).
E. Provide secure lock-up for door hardware delivered to the Project, but not yet installed.
Control handling and installation of hardware items that are not immediately replaceable so that completion of the Work will not be delayed by hardware losses both before and after installation.
1.6 WARRANTY
A. Special warranties:
1. Door Closers: Ten-year period
2. Exit Devices: Three-year period
3. Automatic Door Operators: Two-year period
4. Locks and Cylinders: Three-year period
1.9 MAINTENANCE
A. Maintenance Tools and Instructions: Furnish a complete set of specialized tools and maintenance instructions as needed for Owner's continued adjustment, maintenance, and removal and replacement of door hardware.
B. Parts kits: Furnish manufacturers' standard parts kits for locksets, exit devices, and door closers.
PART 2 – PRODUCTS
2.1 HINGES:
1. Acceptable manufacturers:
a. Ives
b. Bommer
c. McKinney*
2. Characteristics:
a. Templates: Provide only template-produced units.
b. Screws: Provide Phillips flat-head screws complying with the following requirements:
1) For metal doors and frames install machine screws into drilled and tapped holes.
2) For wood doors and frames install threaded-to-the-head wood screws.
3) For fire-rated wood doors install #12 x 1-1/4 inch, threaded-to-the-head steel wood screws.
4) Finish screw heads to match surface of hinges or pivots.
c. Hinge pins: Except as otherwise indicated, provide hinge pins as follows:
1) Out-Swing Exterior Doors: Non-removable pins.
2) Out-Swing Corridor Doors with Locks: Non-removable pins.
3) Interior Doors: Non-rising pins.
4) Tips: Flat button and matching plug. Finished to match leafs.
d. Size: Size hinges in accordance with specified manufacturer’s published recommendations.
e. Quantity: Furnish one pair of hinges for all doors up to 5’-0" high. Furnish one hinge for each additional 2-1/2 feet or fraction thereof.
2.2 CONTINUOUS HINGES:
Cherokee County does not like continuous hinges and will only except them as a modification on remodel or retro fit situations.
1. Acceptable manufacturers:
a. Ives
b. Select Products
c. Markar
d. Pemko*
2. Characteristics:
a. Continuous gear hinges to be manufactured of extruded 6063-T6 aluminum alloy with anodized finish, or factory painted finish as scheduled.
b. All hinges are to be manufactured to template. Uncut hinges shall be non-handed and shall be a pinless assembly of three interlocking extrusions applied to the full height of the door and frame without mortising.
c. Vertical door loads shall be carried on chemically lubricated polyacetal thrust bearings. The door and frame leaves shall be continually geared together for the entire hinge length and secured with a full cover channel. Hinge to operate to a full 180o.
d. Hinges to be milled, anodized and assembled in matching pairs. Fasteners supplied shall be 410 stainless steel, plated and hardened.
e. Provide UL listed continuous hinges at fire doors. Continuous hinges at fire doors (suffix -FR) shall meet the required ratings without the use of auxiliary fused pins or studs.
2.3 CYLINDERS:
a. Schlage* Everest D (FSIC)
2. Characteristics:
a. Equip locksets and mortice cylinders to accept Full Size Interchangeable Core (FSIC) cylinders featuring patented, restricted keys (Schlage Everest D) and auxiliary locking pin. Patented key and cylinder design shall be valid.
b. Construction FSIC cores to be provide by contractor.
c. Provide 10 construction master keys and 2 construction control keys. Provide copies of each to the owner. Coordinate with GC and owner.
d. Owner will purchase final cores and keys with project funds or coordinate with GC for payment of finial cores.
e. Keying to include an import file for Site Master.
f. Final cores and keys will be installed by the owner.
2.4 LOCKSETS, LATCHSETS, DEADBOLTS:
a. Schlage* (Owners standard)
2. Mortise Locksets and Latchsets: as scheduled.
a. Chassis: Cold-rolled steel, handing field-changeable without disassembly.
b. Latchbolts: 3/4-inch throw stainless steel anti-friction type.
c. Lever Trim: Through-bolted, accessible design, cast or solid rod lever as scheduled.
Spindles: Independent break-away.
d. Thumbturns: Accessible design not requiring pinching or twisting motions to operate.
e. Deadbolts: Schlage Stainless steel 1-inch throw.
f. Electric operation: Manufacturer-installed continuous duty solenoid.
g. Strikes: 16 gage curved stainless steel, bronze or brass with 1" deep box construction, lips of sufficient length to clear trim and protect clothing.
h. Scheduled Lock Series and Design: Schlage L series, 07A design.
i. Certifications:
1) ANSI A156.13, 1994, Grade 1 Operational, Grade 1 Security.
2) ANSI/ASTM F476-84 Grade 30 UL Listed.
2.5 EXTRA HEAVY-DUTY CYLINDRICAL LOCKS AND LATCHES:
a. Schlage ND Series* (Owners standard)
2. Characteristics:
a. Chassis: Cylindrical design, corrosion-resistant plated cold-rolled steel.
b. Locking Spindle: Stainless steel, interlocking design.
c. Latch Retractors: Forged steel. Balance of inner parts: Corrosion-resistant plated steel, or stainless steel.
d. Lever Trim: ATHENS (ATH) design, with removable FSIC core (J or JD), independent operation, spring-cage supported, minimum 2" clearance from lever mid-point to door face.
e. All lock functions: 7-year warranty,
f. Vandalguard function outside lever is disengaged when in the locked mode on all exterior doors.
g. Rosettes: Minimum 3-7/16" diameter for coverage of ANSI/DHI A115.18, 1994 door preparation, through-bolt lugs on both spring cages to fully engage this pattern.
h. Springs: Full compression type.
i. Electric operation: Manufacturer-installed continuous duty solenoid.
j. Strikes: 16 gage curved steel, bronze or brass with 1" deep box construction, lips of sufficient length to clear trim and protect clothing.
k. Certifications:
1) ANSI A156.2, 1994, Series 4000, Grade 1. Tested to exceed 3,000,000 cycles.
2) UL listed for A label single doors up to 4 ft x 8 ft.
2.6 EXIT DEVICES:
3. Acceptable manufacturers:
a. Von Duprin* (Owners standard)
4. Characteristics:
a. Exit devices shall be "UL" listed for life safety. All exit devices for fire rated openings shall have “UL" labels for “Fire Exit Hardware."
b. All exit devices mounted on labeled wood doors shall be mounted on the door per the door manufacturer’s requirements.
c. All trim to be thru-bolted to the lock stile case, and SNB at the hinge side. Lever design to match locksets (07A).
d. Attach all exit devices with sex nuts and bolts.
e. All exit devices shall be made of brass, bronze, stainless steel, or aluminum material, powder coated, anodized, or plated to the standard architectural finishes to match the balance of the door hardware.
f. Provide glass bead conversion kits to shim exit devices on doors with raised glass beads.
g. All exit devices shall be one manufacturer. No deviation will be considered.
h. All series exit devices shall incorporate a fluid damper, which decelerates the touchpad on its return stroke and eliminates noise associated with exit device operation. All exit devices shall be non-handed. Touchpad shall extend a minimum of 1/2 of the door width and shall extend to the height of the cross-rail housing for a “no pinch” operation. Plastic touchpads are not acceptable. All latchbolts to be the deadlocking type. Latchbolts shall have a self-lubricating coating to reduce wear. Plated or plastic coated latchbolts are not acceptable.
Plastic linkage and “dogging” components are not acceptable.
i. Lever trim shall be solid case material with a break-away feature to limit damage to the unit from vandalism.
j. Surface vertical rod devices shall be UL labeled for fire door applications without the use of bottom rod assemblies. Where bottom rods are required for security applications, the devices shall be UL labeled for fire doors applications with rod and latch guards by the device manufacturer.
k. Exit devices to include impact resistant, flush mounted end cap design to avoid damage due to carts and other heavy objects passing through an opening. End cap shall be of heavy-duty metal alloy construction and provide horizontal adjustment to provide alignment with device cover plate. When exit device end cap is installed, no raised edges will protrude.
2.7 ELECTRIC STRIKES:
a. Owner Standards
1. Von Duprin 6400 Series for Cylindrical and Mortis locks
2. Trine 6400F for rim exit devices.
3. Hess 9400 for rim exit devices.
2. Characteristics:
a. Heavy duty, stainless steel construction.
b. Adjustable strike box to compensate for any misalignment of door or frame.
c. Two-piece plug connectors for ease of installation and for removal during strike servicing.
2.8 CLOSERS AND DOOR CONTROL DEVICES:
a. LCN Closers* (4000 Series 4040XP)
2. Characteristics:
a. Attach all closers with thru-bolts (no exceptions).
b. Door closers shall have fully hydraulic, full rack and pinion action with a high strength cast iron cylinder.
c. All closers shall utilize a stable fluid withstanding temperature range of 120oF to - 30oF without seasonal adjustment of closer speed to properly close the door.
Closers for fire-rated doors shall be provided with temperature stabilizing fluid that complies with standards UBC 7-2 (1997) and UL 10C.
d. Spring power shall be continuously adjustable over the full range of closer sizes, and allow for reduced opening force for the physically handicapped. Spring power adjustment (LCN Fast ™ Power Adjust) allows for quick and accurate power adjustment and visually shows closer power size settings by way of dial adjustment gauge located on closer spring tube. Hydraulic regulation shall be by tamper-proof, non-critical valves. Closers shall have separate adjustment for latch speed, general speed and back check.
e. All closers shall have solid forged steel main arms (and forearms for parallel arm closers) and where specified shall have a cast-in solid stop on the closer shoe (“SCUSH”). All parallel arm mounted closers shall have “EDA” type arms or, where door travel on out-swing doors must be limited, use “SCUSH” or
“SHCUSH” type closers arms. Auxiliary stops are not required when “SCUSH” type closers are used.
1. 4040XP-3077SCNS Spring Cush-n-Stop Arm (SCUSH)
2. 4040XP-3049SCNS Spring Hold Open Cush-n-Stop Arm (SHCUSH)
f. All surface closers shall be certified to exceed ten million (10,000,000) full load cycles by a recognized independent testing laboratory. All closers (overhead, surface and concealed) shall be of one manufacturer and carry manufacturer's ten-year warranty (electric closers to have two-year warranty).
g. Access-Free Manual Closers: Where manual closers are indicated for doors required to be accessible to the physically handicapped provide adjustable units complying with ADA and ANSI A-117.1 provisions for door opening force.
h. Closers to be installed to allow door swing as shown on plans. Doors swinging into exit corridors shall provide for corridor clear width as required by code. Where possible, mount closers inside rooms.
i. Powder coating finish to be certified to exceed 100 hours salt spray testing by ETL, an independent testing laboratory used by BHMA for ANSI certification.
j. Magnetic Door Holders to be heavy duty wall or floor mounted with metal housing and complete mounting hardware. Provide 24V holding coils unless otherwise scheduled.
2.9 OVERHEAD DOOR HOLDERS:
a. Glynn Johnson*
b. Rixson Fire mark
c. Rockwood
2. Characteristics:
a. Provide (heavy duty and/or medium duty and/or light duty) door holders (concealed and/or surface mounted) of brass, bronze or stainless steel.
b. Concealed holders to be installed with the jamb bracket mortised flush with the bottom of the jamb. The arm and channel to be mortised into the door.
c. Surface holders to be installed with the jamb bracket mounted on the stop.
2.10 FLOOR STOPS AND WALL BUMPERS:
a. Rockwood Manufacturing*
b. Ives
2. Characteristics: Refer to Hardware Headings.
2.11 DOOR BOLTS/COORDINATORS:
a. Rockwood Manufacturing*
b. Ives
2. Characteristics:
a. Flush bolts to be forged brass 6-3/4" x 1", with 1/2" diameter bolts. Plunger to be supplied with milled surface one side that fits into a matching guide.
b. Automatic flush bolts to be UL listed as top and bottom bolts on a pair of classified fire doors. Bolt construction to be of rugged steel and brass components.
c. Self-latching flush bolts to be UL listed as top and bottom bolts on a pair of classified fire doors. Bolt construction to be of rugged steel and brass components.
d. Automatic flush bolts and self-latching flush bolts shall be UL listed for fire door application without bottom bolts (LBB).
e. Furnish dust proof bottom strikes.
f. Coordinator to be soffit mounted non-handed fully automatic UL listed coordinating device for sequential closing of paired doors with or without astragals.
g. Provide filler pieced to close the header. Provide brackets as required for mounting of soffit applied hardware.
2.12 PUSH PLATES:
a. Rockwood Manufacturing*
c. Trimco
2. Characteristics:
a. Exposed Fasteners: Provide manufacturers standard exposed fasteners.
b. Material to be wrought/extruded/forged, brass/ bronze /aluminum/stainless steel, per the Hardware Headings.
c. Provide plates sized as shown in Hardware Headings.
2.13 DOOR PULL PLATES:
1. Acceptable manufacturers:
a. Rockwood Manufacturing*
b. Ives
c. Trimco
2. Characteristics:
a. Provide concealed thru-bolted trim on back to back mounted pulls, but not for single units.
b. Material to be extruded forged/ cast, brass/ bronze/ aluminum/ stainless steel.
c. Provide units sized as shown in Hardware Headings.
2.14 DOOR PUSH SETS:
a. Rockwood Manufacturing*
a. Provide mounting systems as shown in hardware sets.
b. Material to be (description - i.e. solid rod, tubular, cast etc.).
c. Brass/bronze aluminum/stainless steel.
d. Provide Push/Pull sets sized as shown in Hardware Headings.
2.15 PROTECTIVE PLATES:
a. Rockwood Manufacturing*
a. Provide manufacturers standard exposed fasteners for door trim units consisting of either machine screws or self-tapping screws.
b. Materials:
1) Metal Plates: Stainless Steel, .050 inch (U.S. 18 gage).
c. Fabricate protection plates not more than 2 inches less than door width on push side and not more than 1 inch less than door width on pull side.
d. Heights:
1) Kick plates to be 8 inches in height.
2) Mop plates to be 4 inches in height.
3) Armor plates to be 36 inches in height. Armor plates on fire doors to comply with NFPA 80.
2.16 THRESHOLDS:
a. National Guard Products, Inc.
b. Pemko*
c. Reese Industries
d. Zero Weather-stripping Co., Inc.
2. Types: Indicated in Hardware Headings.
2.17 DOOR SEALS/GASKETING:
a. National Guard Products, Inc.
b. Pemko*
c. Reese Industries
d. Zero Weather-stripping Co., Inc.
2. Types: Indicated in Hardware Headings.
2.18 SILENCERS:
a. Hager
b. Ives*
c. Rockwood Manufacturing
2. Three for each single door; two for each pair of doors.
2.19 SECURITY EQUIPMENT:
a. Schlage Electronics: Schlage AD200-70-MTK-ATH-PD
b. Provide Software SMS Premier “SPRE-SFT-1”
c. Provide one hand held programmer “HHD Kit”.
a. Provide items as found in Hardware Headings.
PART 3 - MATERIALS AND FABRICATION
3.1 MANUFACTURER'S NAME PLATE:
A. Do not use manufacturers' products that have manufacturer's name or trade name displayed in a visible location (omit removable nameplates) except in conjunction with required fire-rated labels and as otherwise acceptable to Architect.
1. Manufacturer's identification will be permitted on rim of lock cylinders only.
3.2 BASE METALS:
A. Produce hardware units of basic metal and forming method indicated, using manufacturer's standard metal alloy, composition, temper, and hardness, but in no case of lesser (commercially recognized) quality than specified for applicable hardware units by applicable ANSI/BHMA A156 series standards for each type of hardware item and with ANSI/BHMA A156.18 for finish designations indicated. Do not furnish "optional" materials or forming methods for those indicated, except as otherwise specified.
3.3 FASTENERS:
B. Provide hardware manufactured to conform to published templates, generally prepared for machine screw installation.
1. Do not provide hardware that has been prepared for self-tapping sheet metal screws, except as specifically indicated.
2. Furnish screws for installation with each hardware item. Provide Phillips flat-head screws except as otherwise indicated. Finish exposed (exposed under any condition) screws to match hardware finish or, if exposed in surfaces of other work, to match finish of this other work as closely as possible including “prepared for paint" surfaces to receive painted finish.
3. Provide concealed fasteners for hardware units that are exposed when door is closed except to the extent no standard units of type specified are available with concealed fasteners. Use thru-bolts for installation of all exit devices, closers, and overhead stops. Coordinate with wood doors and metal doors and frames where thru-bolts are used, as a means of reinforcing the work, provide sleeves for each thru-bolt.
3.4 HARDWARE FINISHES
A. The designations used to indicate hardware finishes are those listed in ANSI/BHMA A156.18, "Materials and Finishes," including coordination with the traditional U.S. finishes shown by certain manufacturers for their products.
1. Hinges (Exterior): 630 (US32D) Satin Stainless Steel
2. Hinges (Interior wood doors): 652 (US26D) Satin Chrome Plated Steel
3. Continuous Hinges: 628 (US28) Clear Anodized Aluminum
4. Flush Bolts: 626 (US26D) Satin Chrome Plated Brass/Bronze
5. Locks: 626 (US26D) Satin Chrome Plated Brass/Bronze
6. Exit Devices: 628 (US28) chassis, 689 (powder coated) covers, and 630 (US32D) touchpads
7. Door Closers: 689 Powder Coat Aluminum
8. Push Plates: 630 (US32D) Satin Stainless Steel
9. Pull Plates: 630 (US32D) Satin Stainless Steel
10. Protective Plates: 630 (US32D) Satin Stainless Steel
11. Door Stops: 626 (US26D) Satin Chrome Plated Brass/Bronze
12. Overhead Holders: 630 Satin Stainless Steel and 689 Powder Coated Steel (as scheduled) B. Thresholds/Weatherstripping: 627/628 (US27/US28) Aluminum C. Match items to the manufacturer’s standard color and texture finish for the latch and lock sets (or push-pull units if no latch or lock sets).
D. Provide finishes that match those established by ANSI or, if none established, match the
Architect’s sample.
E. Provide quality of finish, including thickness of plating or coating (if any), composition, hardness, and other qualities complying with manufacturer’s standards, but in no case less than specified by referenced standards for the applicable units of hardware.
F. Provide protective lacquer coating on all exposed hardware finishes of brass, bronze, and aluminum, except as otherwise indicated. The suffix "-NL" is used with standard finish designations to indicate "no lacquer."
PART 4 - EXECUTION
4.1 INSTALLATION
A. Mount hardware units at heights indicated in following applicable publications, except as specifically indicated or required to comply with governing regulations and except as otherwise directed by Architect.
1. "Recommended Locations for Builders Hardware for Standard Steel Doors and Frames" by the Door and Hardware Institute.
2. "Recommended Locations for Builders Hardware for Custom Steel Doors and Frames" by the Door and Hardware Institute.
3. NWWDA Industry Standard I.S.1.7, "Hardware Locations for Wood Flush Doors."
B. Install each hardware item in compliance with the manufacturer's instructions and recommendations. Where cutting and fitting is required to install hardware onto or into surfaces that are later to be painted or finished in another way, coordinate removal, storage, and reinstallation or application of surface protection with finishing work specified in the Division 9 Sections. Do not install surface-mounted items until finishes have been completed on the substrates involved.
C. Set units level, plumb, and true to line and location. Adjust and reinforce the attachment substrate as necessary for proper installation and operation.
D. Drill and countersink units that are not factory prepared for anchorage fasteners. Space fasteners and anchors in accordance with industry standards.
E. Set thresholds for exterior doors in full bed of butyl-rubber or polyisobutylene mastic sealant complying with requirements specified in Division 7 Section “Joint Sealers”.
F. Weather-stripping and Seals: Comply with manufacturer's instructions and recommendations to the extent installation requirements are not otherwise indicated.
4.2 ADJUSTING, CLEANING, AND DEMONSTRATING
A. Adjust and check each operating item of hardware and each door to ensure proper operation or function of every unit. Replace units that cannot be adjusted to operate freely and smoothly or as intended for the application made.
1. Where door hardware is installed more than one month prior to acceptance or occupancy of a space or area, return to the installation during the week prior to acceptance or occupancy and make final check and adjustment of all hardware items in such space or area. Clean operating items as necessary to restore proper function and finish of hardware and doors. Adjust door control devices to function properly with final operation of heating and ventilating equipment.
B. Clean adjacent surfaces soiled by hardware installation.
C. Door Hardware Supplier's Field Service:
1. Inspect door hardware items for correct installation and adjustment after complete installation of door hardware.
2. Instruct Owner's personnel in the proper adjustment and maintenance of door hardware and hardware finishes.
3. File written report of this inspection to Architect.
D. Door Hardware Manufacturer’s Field Service:
1. Prior to project completion, representatives of the lock, exit device and overhead closer manufacturers shall inspect and certify that all units are installed in accordance with the manufacturer’s instructions, and are regulated properly and functioning correctly.
2. A written report of the inspection results and recommendations shall be provided to the Architect and shall include the appropriate certificates.
PART 5 – HARDWARE SCHEDULE
5.1 WRITTEN HARDWARE SCHEDULE
A. Door hardware schedule to be written by a certified:
1. Architectural Hardware Consultant (AHC)
2. Architectural Openings Consultant (AOC)
END OF SECTION
Hollow Metal Door and Frame Specification Guide
08-1113
SECTION 08 1113 – Hollow Metal Door and Frame
PART 1 – GENERAL
1.01 SUMMARY
A. SECTION INCLUDES
1. Work under this section comprises of furnishing hollow metal doors and frames, including transom frames, sidelight and window frames with provision for glazed, paneled or louvered openings, fire labeled and non-labeled, as scheduled.
B. RELATED DOCUMENTS
1. Related documents, drawings and general provisions of contract, including General and Supplementary Conditions and Division 1 specification sections apply to this section.
C. RELATED SECTIONS
1. 08 01 00 – Operations and Maintenance
2. 06 10 00 – Rough Carpentry
3. 06 20 00 – Finish Carpentry
4. 08 71 00 – Door Hardware
1.02 REFERENCES
A. STANDARDS
1. NFPA 80 – Fire Doors and Windows
2. ANSI/SDI-100 – Recommended Specifications for Standard Steel Doors and Frames
3. ASTM-F 476 – Standard Test Methods for Security of Swinging Doors Assemblies
4. HMMA 862 – Guide Specifications for Commercial Security Hollow Metal Doors and Frames
5. SDI-105 – Recommended Erection Instructions for Steel Frames
6. SDI-107 – Hardware on Steel Doors (reinforcement application)
7. ANSI-A250.4 – Steel Doors and Frames Physical Endurance
8. UL10C - Standard for Positive Pressure Fire Tests of Door Assemblies
B. CODES
1. NFPA-101 – Life Safety Code
2. IBC 2003 – International Building Code
3. ANSI-A117.1 – Accessible and Usable Building and Facilities 4. ADA – Americans with Disabilities
Act
1.03 SUBMITTALS
A. GENERAL REQUIREMENTS
1. Submit copies of the hollow metal door and frame shop drawings in accordance with Division 1, General Requirements.
B. PRODUCT DATA
1. Submit shop drawings showing fabrication and installation of standard steel doors and frames.
Include details of each frame type, elevations of door and frame types, conditions at openings, details of construction, location and installation requirements of door and frame hardware reinforcements, and details of joints and connections. Show anchorage and accessory items.
C. SHOP DRAWINGS
1. Provide a schedule of doors and frames using same reference numbers for details and door openings as those on the contract documents. Shop drawings should include the following information:
a. Material thickness and/or gauge.
b. Door core material.
c. Mortises and reinforcements.
d. Anchorage types.
e. Locations of exposed fasteners.
f. Glazed, louvered and paneled openings.
g. Mounting locations of standard hardware.
1.04 QUALITY ASSURANCE
A. SUBSTITUTIONS
1. All substitution requests must be submitted within the procedures and time frame as outlined in Division 1, General Requirements. Approval of products is at the discretion of the architect and his consultant.
B. MANUFACTURER QUALIFICATIONS
1. Manufacturer shall be a member in good standing of the Steel Door Institute (SDI).
C. FIRE RATED DOOR ASSEMBLIES
1. All labeled fire door assemblies to be of a type that have been classified and listed in accordance with the latest edition of NFPA80 and test in compliance with NFPA-252, and UL10C. A physical label is to be affixed to the fire door at an authorized facility; embossed labels are acceptable on standard 3-sided door frames.
2. For openings required to be fire rated exceeding limitations of labeled assemblies, submit manufacturer’s certification that each door and frame assembly has been constructed to conform to design, materials and construction equivalent to requirements for labeled construction.
3. Project requires door assemblies and components that are compliant with positive pressure and label requirements. Specifications must be cross-referenced and coordinated with hardware and other door manufacturers to ensure that total opening engineering is compatible with UL10C Standard for Positive Pressure Fire Tests of Door Assemblies.
a. Certification(s) of compliance shall be made available upon request by the Authority Having Jurisdiction.
1.05 DELIVERY, STORAGE, AND HANDLING
A. The supplier shall deliver all materials to the project site; direct factory shipments are not allowed unless agreed upon beforehand. Supplier shall coordinate delivery times and schedules with the contractor.
B. Deliver doors cardboard wrapped or crated to provide protection during transit and jobsite storage.
Provide additional protection to prevent damage to any factory-finished doors. Mark all doors and frames with opening numbers as shown on the contract documents and shop drawings.
C. Inspect doors and frames upon delivery for damage. Minor damages may be repaired provided refinished items are equal in all respects to new work and acceptable to the architect. Otherwise, remove and replace damaged goods as directed.
D. Store doors and frames at the building site in a dry and secure place.
1. Place units on minimum 4” high wood blocking.
2. Avoid use of non-vented plastic or canvas shelters that could create a humidity chamber.
3. If cardboard wrapper on door becomes wet, remove carton immediately.
4. Provide 1/4” spaces between stacked doors to promote air circulation.
1.06 WARRANTY
A. All doors and frames shall be warranted in writing by the manufacturer against defects in materials and workmanship for a period of one (1) year commencing on the date of final completion and acceptance.
PART 2 - PRODUCTS
2.01 MANUFACTURERS
A. Subject to compliance with requirements, provide standard hollow metal doors and frames by one of the following:
1. Steelcraft
2. Ceco Corporation
3. Curries Company
2.02 MATERIALS
A. All doors and frames shall be manufactured of commercial quality cold rolled steel per ASTM-A366 and A568 general requirements; galvanized to A60 or G60 or galvanealed to A40 minimum coating weight standard per ASTM-A924. Internal reinforcing may be manufactured of hot rolled pickled and oiled steel per ASTM-A569.
B. Supports and anchors shall be fabricated of not less than 18-gauge sheet steel, galvanized where galvanized frames are used.
C. Where items are to be built into exterior walls, inserts, bolts and fasteners shall be hot dipped galvanized in compliance with ASTM-A153, Class C or D as applicable.
D. Rust inhibitive enamel or paint primer shall be used, baked on, and suitable as a base for specified finish paints complying with ANSI A224.1, “Test Procedure and Acceptance Criteria for Prime Painted Steel Surfaces on Steel Doors and Frames.”
E. Provide all hollow metal doors and frames receiving electrified hardware with molex wiring harness and concealed plug connectors on one end to accommodate up to twelve wires. Coordinate molex connectors on end of the wiring harness to plug directly into the electrified hardware and the electric hinge.
2.03 DOORS
A. Provide 1 3/4” thick doors of materials and ANSI/SDI-100 grades and models specified below, or as indicated on drawings or schedules:
1. Interior Doors: Level 2, Model 2 – Seamless
a. Interior doors shall be minimum 18-gauge steel with both lock and hinge rail edge of door intermittently welded, filled and ground smooth the full height of door.
1) Steelcraft L
2) Ceco: Regent-18-SEM
3) Curries: 707N-18
2. Exterior Doors: Level 3, Model 2 – Seamless
a. Exterior doors shall be minimum 18-gauge galvanized or galvanealed steel with both lock and hinge rail edge of door intermittently welded, filled and ground smooth the full height of door. Exterior doors shall be insulated with a solid slab of expanded polystyrene or polyurethane foam permanently bonded to the inside of each face skin. The top of all doors shall be closed flush by the addition of a 16-gauge screwed-in top cap and sealed to prevent water infiltration. The bottom channel shall include weep-holes.
1) Steelcraft L-16
2) Ceco: Legion-16-SEM
3) Curries: 707N-16
B. All doors shall be reinforced for hardware as shown below where necessary to preclude the use of thrubolts.
1. Exit Devices: 14-gauge
2. Door Closers: 12-gauge
C. All doors shall be beveled 1/8” in 2” and shall have top and bottom channels of not less than 16-gauge, flush or inverted, welded to the face sheets. Doors shall have a full height 14-gauge hinge rail reinforcement channel, or individual 10-gauge hinge reinforcements.
D. All doors to conform to ANSI-A250.4 Level “A” criteria and shall be tested to 1,000,000 operating cycles and 23 twist tests. Certification of Level “A” doors is to be submitted with approval drawings by supplier upon request. Do no bid or supply any type or gauge of door not having been tested and passed these criteria.
2.04 FRAMES
A. Provide hollow metal frames for doors, transoms, sidelights, borrowed lights, and other openings, of types and styles as shown on the drawings and schedules. Conceal fastenings unless otherwise indicated.
1. Interior Frames: Level 2, 16-gauge, knockdown non-welded.
2. Exterior Frames: Level 2, 16-gauge, galvanized or galvanealed
3. Security Grade Frames: 14-gauge
a. Ceco: SF Series
b. Curries: M Series
c. Fleming: F Series
B. All frames over 36” in width shall be 14 gauge.
C. Fabricate frames with mitered and faces only welded corners, re-prime at the welded areas. All welds to be flush with neatly mitered or butted material cuts.
D. All frames shall have minimum 7-gauge hinge reinforcements, 14-gauge lock strike reinforcing, and 12gauge closer reinforcing. All frames shall have minimum 7-gauge hinge reinforcements with an additional high frequency 12-gauge hinge reinforcement welded to the top hinge, 14-gauge lock strike reinforcing, and 12-gauge closer reinforcing.
E. Provide temporary shipping bars to be removed before setting frames.
F. Except on weather-stripped frames, drill stops to receive three (3) silencers on strike jambs of single frames and two (2) silencers on heads of double frames.
G. Provide minimum 0.0179” thick steel plaster guards or mortar boxes at back of hardware cutouts where mortar or other materials might obstruct hardware operation and to close off interior of openings.
2.05 FABRICATION
A. Fabricate steel door and frame units to be rigid, neat in appearance, and free from defects, warp, or buckle. Where practical, fit and assemble units in manufacturer's plant. Clearly identify work that cannot be permanently factory assembled before shipment, to assure proper assembly at Project site. Comply with ANSI/SDI 100 requirements.
1. Clearances shall be no more than 1/8” at jambs and heads except between non-fire rated pairs of doors which may be no more than 1/4.” Not more than 3/4” at the bottom of the doors.
B. Fabricate exposed faces of doors and panels, including stiles and rails of non-flush units, from only cold rolled steel sheet.
C. Tolerances shall comply with SDI-117 "Manufacturing Tolerances Standard Steel Doors and Frames."
D. Fabricate concealed stiffeners, reinforcement, edge channels, louvers, and moldings from either cold- or hot-rolled steel sheet.
E. Unless otherwise indicated, provide exposed fasteners with countersunk flat or oval heads for exposed screws and bolts.
F. At exterior locations and elsewhere as shown or scheduled, assemblies fabricated as thermal-insulating door and frame assemblies and tested according to ASTM C 236 or ASTM C 976 on fully operable door assemblies.
1. Unless otherwise indicated, provide thermal-rated assemblies with a minimum U-value rating of
0.41 Btu/sq. ft. x h x deg F.
G. Where shown or scheduled, provide door and frame assemblies fabricated as sound-reducing type, tested according to ASTM E 1408, and classified according to ASTM E 413.
1. Unless otherwise indicated, provide acoustical assemblies with STC sound ratings of 33 or better.
H. Prepare doors and frames to receive mortised and concealed hardware according to final door hardware schedule and templates provided by hardware supplier. Comply with applicable requirements of SDI-107 and ANSI-A115 Series specifications for door and frame preparation for hardware.
I. Reinforce doors and frames to receive surface-applied hardware. Drilling and tapping for surface-applied hardware may be done at Project site. Provide internal reinforcements for all doors to receive door closers and exit devices.
J. Locate hardware as indicated on Shop Drawings or, if not indicated, according to the Door and Hardware Institute's (DHI) "Recommended Locations for Architectural Hardware for Standard Steel Doors and
Frames."
K. Provide glazing stops with minimum 0.0359-inch- thick steel or 0.040-inch- thick aluminum.
L. Provide non-removable stops on outside of exterior doors and on secure side of interior doors for glass, louvers, and other panels in doors.
M. Provide screw-applied, removable, glazing beads on inside of glass and other panels in doors
PART 3 - EXECUTION
3.01 INSTALLATION
A. Install steel doors, frames, and accessories according to shop drawings, manufacturer's data, and as specified.
B. Comply with provisions of SDI-105, “Recommended Erection Instructions for Steel Door Frames,” unless otherwise indicated. Set frames accurately in position, plumbed, aligned, and braced securely until permanent anchors are set. After wall construction is completed, remove temporary braces and spreaders, leaving surfaces smooth and undamaged.
1. Except for frames located in existing concrete, masonry, or gypsum board assembly construction, place frames before constructing enclosing walls and ceilings.
2. In masonry construction, install at least 3 wall anchors per jamb adjacent to hinge location on hinge jamb and at corresponding heights on strike jamb. Acceptable anchors include masonry wire anchors and masonry T-shaped anchors.
3. At existing concrete or masonry construction, install at least 3 completed opening anchors per jamb adjacent to hinge location on hinge jamb and at corresponding heights on strike jamb. Set frames and secure to adjacent construction with bolts and masonry anchorage devices.
4. In metal-stud partitions, install at least 3 wall anchors per jamb at hinge and strike levels. In steel stud partitions, attach wall anchors to studs with screws.
5. Install fire-rated frames according to NFPA 80.
C. Fit hollow-metal doors accurately in frames, within clearances specified in ANSI/SDI 100. Install fire rated doors with clearances specified in NFPA 80.
3.02 ADJUSTING AND CLEANING
A. Immediately after erection, sand smooth any rusted or damaged areas of prime coat and apply touchup of compatible air-drying primer
B. Immediately before final inspection, remove protective wrappings from doors and frames.
END OF SECTION
Flush Wood Door and Frame
Specification Guide
08-1400
FLUSH WOOD DOORS SECTION 08-1400
PART 1 – GENERAL
1.01 SUMMARY
A. SECTION INCLUDES:
Work under this section comprises of furnishing solid core doors (wood veneer faces…