Cath Lab - Electrical_IFC_5-20-2025.pdf
PDF 11 MB Posted
- Attached to
- Y1DA--Project 688-CSI-013 Cardiac Cath Lab Replacement Room 4A124 at the Washington DC VAMC
- Solicitation number
- 36C24525R0080
About this file
These are detailed electrical design drawings for a Cardiac Catheterization Lab Renovation project at the Washington DC Veterans Affairs Medical Center. The comprehensive set of electrical plans includes multiple sheets covering electrical lighting, power, communication, fire alarm, nurse call systems, demolition, phasing, and riser diagrams for the 4th floor cath lab renovation. Key design elements include proposed wiring and conduit routing across basement, first, second, third, penthouse, and roof levels, with specific attention to electrical panel schedules, lighting fixture specifications, and electrical demolition notes. The project is fully sprinklered and involves extensive electrical system modifications, with drawings prepared by A Design Group, LLC for the Office of Construction and Facilities Management, U.S. Department of Veterans Affairs, with an issued date of 05/20/2025.
The electrical design documents detail comprehensive technical specifications, including electrical symbols, equipment specifications, general and keyed notes for demolition and new work, and precise electrical system requirements. The plans cover multiple electrical systems including lighting (with photometric calculations), power distribution, communication infrastructure, fire alarm systems, and nurse call systems. Specific technical details are provided for electrical panels (UL-2-4A, EUL-2-3A-4A), voltage drop calculations, and detailed routing of electrical infrastructure across different building levels. The project number is 688-CSI-013, located at 50 Irving St NW, Washington, DC 20422, with the design team including Frank V. Sturgeon (AIA) and Ambrish Rastogi (PE) from A Design Group, LLC.
View the file
Other files
Show all 12
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
E001
ELECTRICAL COVER SHEET
NN
95 WASHINGTON STREET, MORRISTOWN, NJ 07960
t. 973.539.5353
f. 973.539.0916
THE WOOLWORTH BUILDING
233 BROADWAY SUITE 2150, NEW YORK, NY 10279
t. 212.982.7900
f. 212.982.8111 www.nkarchitects.com
NK ARCHITECTS
STAMP
SIGNATURE:
Drawing Title
Approved: Project Director
Project Title
Issued Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. of
CONSULTANTS ARCHITECT/ENGINEER OF RECORD
NO. 1
on e ei gh th in ch o ne fo ot th re e in ch es o ne fo ot 6"
6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot
6" 6" th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r i nc h on e fo ot
VA FORM 08-6231
A
1 2 3 4 5 6 7 8 9 10
B
C
D
E
F
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9 10
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
FULLY SPRINKLERED
688-CSI-013
05/20/2025
NO: REVISION DESCRIPTION: DATE:
ART - ARCHITECTURE - ENGINEERING
2787 HILL ROAD
VIENNA, VA 22181
FRANK V. STURGEON, AIA
AMBRISH RASTOGI, PE
703.938.5226
FRANK@ADG10.COM
A DESIGN GROUP, LLC
35% SUBMISSION 01-30-2024
50 Irving St NW, Washington, DC 20422
4TH FLOOR CATH LAB
RENOVATION
AR
65% SUBMISSION 04-05-2024
95% SUBMISSION 05-31-20243
100% SUBMISSION 03-21-20254
ISSUED FOR CONSTRUCTION 05-20-20255
05/20/2025
AutoCAD SHX Text
1. IT IS THE INTENT OF THESE DRAWINGS AND OTHER RELATED DOCUMENTS TO PRODUCE A COMPLETE AND FUNCTIONING IT IS THE INTENT OF THESE DRAWINGS AND OTHER RELATED DOCUMENTS TO PRODUCE A COMPLETE AND FUNCTIONING ELECTRICAL SYSTEM. THE ELECTRICAL CONTRACTOR SHALL PROVIDE ALL LABOR, MATERIALS, TESTS, AND OTHER SERVICES AS MAY BE NECESSARY TO ACHIEVE THIS PRODUCT. THE CONTRACTOR SHALL ACKNOWLEDGE ACCEPTANCE OF THE PLANS AS AN ADEQUATE DEFINITION OF THE SCOPE OF WORK AND EXTRA COST CLAIMS BASED ON DISCREPANCIES ON THE PLANS WILL NOT BE CONSIDERED. 2. ALL ELECTRICAL WORK SHALL BE IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE (NEC) AND ALL LOCAL CODES ALL ELECTRICAL WORK SHALL BE IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE (NEC) AND ALL LOCAL CODES HAVING JURISDICTION. ALL EQUIPMENT, DEVICES, AND MATERIAL SHALL BE LISTED WITH UNDERWRITERS LABORATORIES FOR ITS APPLICATION AS INSTALLED AND SHALL BEAR THE UL LABEL. 3. THE ELECTRICAL CONTRACTOR SHALL OBTAIN ALL PERMITS AND PAY SUCH FEES AS MAY BE NECESSARY FOR THE ELECTRICAL CONTRACTOR SHALL OBTAIN ALL PERMITS AND PAY SUCH FEES AS MAY BE NECESSARY FOR INSPECTIONS, TESTS, AND OTHER SERVICES WHICH ARE REQUIRED FOR THE COMPLETION OF HIS WORK. 4. THE CONTRACTOR SHALL VISIT THE SITE AND EXAMINE CONDITIONS OF THE PREMISES AND THE CHARACTER AND EXTENT THE CONTRACTOR SHALL VISIT THE SITE AND EXAMINE CONDITIONS OF THE PREMISES AND THE CHARACTER AND EXTENT OF WORK REQUIRED PRIOR TO SUBMISSION OF BIDS. ANY DIFFICULTIES IN COMPLYING WITH THE DRAWINGS AND SPECIFICATIONS SHALL BE BROUGHT TO THE ATTENTION OF ARCHITECT/ENGINEERS BEFORE BIDDING. 5. ELECTRICAL PLANS ARE DIAGRAMMATIC. DO NOT SCALE DRAWINGS. ELECTRICAL PLANS ARE DIAGRAMMATIC. DO NOT SCALE DRAWINGS. 6. CONSULT PLANS OF ALL OTHER TRADES FOR COORDINATION AND FOR RELATED AND ADJOINING WORK. CONSULT PLANS OF ALL OTHER TRADES FOR COORDINATION AND FOR RELATED AND ADJOINING WORK. 7. CONSULT ARCHITECTURAL AND STRUCTURAL PLANS AND DETAILS FOR CONSTRUCTION HEADROOM, ROOM FINISHES, CONSULT ARCHITECTURAL AND STRUCTURAL PLANS AND DETAILS FOR CONSTRUCTION HEADROOM, ROOM FINISHES, CEILINGS, ETC. 8. SEE ARCHITECTURAL REFLECTED CEILING PLAN FOR EXACT LOCATION OF LIGHT FIXTURES. SEE ARCHITECTURAL REFLECTED CEILING PLAN FOR EXACT LOCATION OF LIGHT FIXTURES. 9. CIRCUIT NUMBERS ARE FOR IDENTIFICATION PURPOSES ONLY. CONTRACTOR SHALL BE RESPONSIBLE FOR CIRCUIT NUMBERS ARE FOR IDENTIFICATION PURPOSES ONLY. CONTRACTOR SHALL BE RESPONSIBLE FOR CORRECTLY SPACING THE CIRCUITS IN THE PANEL AND BALANCE THE LOAD ON THE PHASES UNDER NORMAL OPERATING CONDITIONS. 10. SHOP DRAWINGS FOR ALL ELECTRICAL EQUIPMENT, FIXTURES, DEVICES AND MATERIALS SHALL BE SUBMITTED TO THE SHOP DRAWINGS FOR ALL ELECTRICAL EQUIPMENT, FIXTURES, DEVICES AND MATERIALS SHALL BE SUBMITTED TO THE ARCHITECT FOR APPROVAL BEFORE DELIVERY TO THE JOB SITE. EQUIPMENT, FIXTURES, DEVICES, AND MATERIAL DELIVERED TO THE JOB SITE OR INSTALLED PRIOR TO APPROVAL OF THE SHOP DRAWINGS, AND FOR WHICH THE SHOP DRAWINGS ARE SUBSEQUENTLY REJECTED, SHALL BE REPLACED WITH AN APPROVED ITEM AT NO ADDITIONAL COST TO THE VA. 11. CONTRACTOR SHALL VERIFY WIRE SIZES, C/B AND FUSE RATINGS FOR ALL HVAC EQUIPMENT, AND BRING TO THE CONTRACTOR SHALL VERIFY WIRE SIZES, C/B AND FUSE RATINGS FOR ALL HVAC EQUIPMENT, AND BRING TO THE ATTENTION OF THE ARCHITECT/ENGINEERS ANY DISCREPANCIES AFFECTING THE WORK PRIOR TO PROCEEDING. 12. ALL WORK SHALL BE DONE AT SUCH TIMES AND IN SUCH A MANNER AS WILL LEAST INTERFERE WITH THE MAINTENANCE ALL WORK SHALL BE DONE AT SUCH TIMES AND IN SUCH A MANNER AS WILL LEAST INTERFERE WITH THE MAINTENANCE AND OPERATION OF ALL RELATED OR AFFECTED SYSTEMS. ALL POWER OUTAGES, FIRE ALARM SHUT DOWNS, ETC SHALL BE COORDINATED WITH VA COR. PROVIDE 14 CALENDAR DAY ADVANCED NOTICE OF ALL SHUTDOWNS, VIA THE VA SHUTDOWN REQUESTED FORM, TO BE PROVIDED TO THE CONTRACTOR. 13. CONTRACTOR SHALL VERIFY THAT ALL DOOR SWINGS ARE CORRECT BEFORE INSTALLING LIGHT SWITCH OUTLETS. CONTRACTOR SHALL VERIFY THAT ALL DOOR SWINGS ARE CORRECT BEFORE INSTALLING LIGHT SWITCH OUTLETS. 14. CONTRACTOR SHALL BE RESPONSIBLE FOR PROPER SIZING OF ALL MOTOR OVERLOAD DEVICES (HEATERS) IN STARTERS CONTRACTOR SHALL BE RESPONSIBLE FOR PROPER SIZING OF ALL MOTOR OVERLOAD DEVICES (HEATERS) IN STARTERS BASED ON ACTUAL NAMEPLATE RATINGS ON THE EQUIPMENT BEING INSTALLED. 15. HORSEPOWER RATINGS INDICATED ON DRAWINGS MAY DIFFER FROM ACTUAL EQUIPMENT FURNISHED. IF FURNISHED HORSEPOWER RATINGS INDICATED ON DRAWINGS MAY DIFFER FROM ACTUAL EQUIPMENT FURNISHED. IF FURNISHED EQUIPMENT DIFFERS FROM RATINGS ON DRAWINGS, CONTRACTOR SHALL NOTIFY ARCHITECT/ENGINEER FOR APPROPRIATE ACTION TO BE TAKEN. 16. CONTRACTOR SHALL NOTE U.L. LABELS ON PACKAGED TYPE MECHANICAL EQUIPMENT. IF U.L. LABEL ON MECHANICAL CONTRACTOR SHALL NOTE U.L. LABELS ON PACKAGED TYPE MECHANICAL EQUIPMENT. IF U.L. LABEL ON MECHANICAL EQUIPMENT TO ACTUALLY BE INSTALLED CALLS FOR THE OVER CURRENT PROTECTIVE DEVICE TO BE FUSES, THE ELECTRICAL CONTRACTOR SHALL PROVIDE A FUSED DISCONNECT SWITCH WITH PROPER SIZE FUSES AT THE SWITCH LOCATION INDICATED ON DRAWINGS AT NO ADDITIONAL CHARGE TO THE VA. 17. THE ELECTRICAL CONTRACTOR SHALL VERIFY THE TYPE OF CEILING SYSTEM WITH THE GENERAL CONTRACTOR OR CEILING THE ELECTRICAL CONTRACTOR SHALL VERIFY THE TYPE OF CEILING SYSTEM WITH THE GENERAL CONTRACTOR OR CEILING CONTRACTOR TO INSURE THAT ALL RECESSED LIGHTING FIXTURES ARE COMPATIBLE WITH THE CEILING SYSTEM BEING INSTALLED. LIGHTING FIXTURES SHOULD NOT BE ORDERED UNTIL TYPE OF CEILING HAS BEEN VERIFIED. 18. LIGHTING FIXTURES INSTALLED IN SUSPENDED CEILINGS SHALL BE SUPPORTED DIRECTLY FROM THE BUILDING STRUCTURE. LIGHTING FIXTURES INSTALLED IN SUSPENDED CEILINGS SHALL BE SUPPORTED DIRECTLY FROM THE BUILDING STRUCTURE. AND SHALL COMPLY WITH NEC 410.30 AND 410.36. 19. THE CORRECT NUMBER OF WIRES MAY NOT BE INDICATED FOR ALL CIRCUITS, ONLY THOSE WHERE CLARIFICATION IS THE CORRECT NUMBER OF WIRES MAY NOT BE INDICATED FOR ALL CIRCUITS, ONLY THOSE WHERE CLARIFICATION IS NECESSARY. THE CONTRACTOR SHALL PROVIDE ALL WIRES NECESSARY FOR THE PROPER FUNCTION OF THE SYSTEM WHETHER INDICATED ON THE DRAWINGS OR NOT. 20. ALL EMPTY CONDUIT RUNS IN EXCESS OF 10 FT. SHALL BE PROVIDED WITH A PULL WIRE OF FISH TAPE/CORD. ALL EMPTY CONDUIT RUNS IN EXCESS OF 10 FT. SHALL BE PROVIDED WITH A PULL WIRE OF FISH TAPE/CORD. 21. ALL CONDUCTORS, RACEWAYS AND CABLES SHALL BE CONCEALED IN CEILING OR WALL UNLESS INDICATED OTHERWISE. ALL CONDUCTORS, RACEWAYS AND CABLES SHALL BE CONCEALED IN CEILING OR WALL UNLESS INDICATED OTHERWISE. 22. OPENINGS IN EXISTING BUILDING STRUCTURE FOR PASSAGE OF CONDUITS/CABLES SHALL NOT BE CUT UNTIL THE OPENINGS IN EXISTING BUILDING STRUCTURE FOR PASSAGE OF CONDUITS/CABLES SHALL NOT BE CUT UNTIL THE CONTRACTOR HAS ASKED FOR AND RECEIVED WRITTEN APPROVAL FROM THE ARCHITECT. 23. THE LIGHTING FIXTURES SHALL BE PROVIDED COMPLETE WITH ALL ACCESSORIES (INCLUDING LAMPS) BY THE ELECTRICAL THE LIGHTING FIXTURES SHALL BE PROVIDED COMPLETE WITH ALL ACCESSORIES (INCLUDING LAMPS) BY THE ELECTRICAL CONTRACTOR. 24. SYMBOLS SHOWN ON THIS SHEET ARE STANDARD SYMBOLS AND MAY NOT NECESSARILY ALL BE APPLICABLE TO THIS SYMBOLS SHOWN ON THIS SHEET ARE STANDARD SYMBOLS AND MAY NOT NECESSARILY ALL BE APPLICABLE TO THIS PROJECT. 25. THE CONTRACTOR SHALL GUARANTEE ALL HIS WORK AND MATERIALS FOR A PERIOD OF ONE YEAR AFTER ACCEPTANCE BY THE CONTRACTOR SHALL GUARANTEE ALL HIS WORK AND MATERIALS FOR A PERIOD OF ONE YEAR AFTER ACCEPTANCE BY VA COR. UNLESS SPECIFICALLY NOTED OTHERWISE. 26. ALL PENETRATIONS OF FLOOR AND WALLS SHALL BE FIRE STOPPED IN ACCORDANCE WITH IBC, NEC AND NFPA. ALL PENETRATIONS OF FLOOR AND WALLS SHALL BE FIRE STOPPED IN ACCORDANCE WITH IBC, NEC AND NFPA. 27. CONDUCTORS SHALL BE INSTALLED CONTINUOUS BETWEEN DEVICES, WITH SPLICES LOCATED ONLY IN JUNCTION BOXES OR CONDUCTORS SHALL BE INSTALLED CONTINUOUS BETWEEN DEVICES, WITH SPLICES LOCATED ONLY IN JUNCTION BOXES OR IN CABINETS. CONDUCTORS SHALL BE OF SUFFICIENT LENGTH TO REACH THE FARTHEST TERMINAL IN PANELS. A MINIMUM OF 6" LOOPS SHALL REMAIN WHERE CONNECTIONS OR TAPS ARE TO BE MADE IN BRANCH CIRCUIT WIRING. 28. PROVIDE AN UPDATED TYPEWRITTEN PANEL DIRECTORY IN EACH PANEL AFTER COMPLETION OF WORK IN EACH PANEL PROVIDE AN UPDATED TYPEWRITTEN PANEL DIRECTORY IN EACH PANEL AFTER COMPLETION OF WORK IN EACH PANEL WORKED IN. 29. CONTRACTOR SHALL PROVIDE AS BUILT DRAWINGS AND ALL MANUFACTURERS DATA AND WARRANTY LITERATURE AT THE CONTRACTOR SHALL PROVIDE AS BUILT DRAWINGS AND ALL MANUFACTURERS DATA AND WARRANTY LITERATURE AT THE COMPLETION OF THE CONTRACT. 30. IF CEILING SPACE IS USED AS PLENUM, APPROPRIATE WIRING SHALL BE USED. IF CEILING SPACE IS USED AS PLENUM, APPROPRIATE WIRING SHALL BE USED. 31. STARTERS SHALL BE PROVIDED AS PER MANUFACTURER'S RECOMMENDATION. COORDINATE EXACT LOCATIONS AND STARTERS SHALL BE PROVIDED AS PER MANUFACTURER'S RECOMMENDATION. COORDINATE EXACT LOCATIONS AND REQUIREMENTS. 32. PER NEC 210.4 (B), CIRCUIT BREAKERS FEEDING MULTIWIRE BRANCH CIRCUITS SHALL BE SIMULTANEOUSLY DISCONNECTED PER NEC 210.4 (B), CIRCUIT BREAKERS FEEDING MULTIWIRE BRANCH CIRCUITS SHALL BE SIMULTANEOUSLY DISCONNECTED WITH IDENTIFIED HANDLE TIE. TYPICAL. 33. (SHARED)" UNDER THIS CONTRACT IS DEFINED AS SPLIT CIRCUIT; CONTRACTOR SHALL SPLICE THE CIRCUIT AT THE SOURCE (SHARED)" UNDER THIS CONTRACT IS DEFINED AS SPLIT CIRCUIT; CONTRACTOR SHALL SPLICE THE CIRCUIT AT THE SOURCE PANELBOARD AND RUN SEPARATE WIRING TO THE LOADS INDICATED. 34. CARD READERS, KEYPADS, DOOR RELEASE PUSH BUTTON, CABLING SHALL BE PROVIDED AND INSTALLED BY THE CONTRACTOR CARD READERS, KEYPADS, DOOR RELEASE PUSH BUTTON, CABLING SHALL BE PROVIDED AND INSTALLED BY THE CONTRACTOR (JOHNSON CONTROLS). FINAL TERMINATIONS TO THE BUILDING SECURITY SYSTEM AND PROGRAMMING SHALL BE PERFORMED BY THE VA. PROVIDE MULTI-CONDUCTOR CABLE-UNSHIELDED PLENUM RATED COPPER CONDUCTORS FOR ALL SECURITY CONNECTION. COORDINATE WITH VA PRIOR TO ROUGH-IN.
AutoCAD SHX Text
1. LIGHT FIXTURES: LIGHT FIXTURES: A. LIGHT FIXTURES SHALL BE AS SPECIFIED. LIGHT FIXTURES SHALL BE AS SPECIFIED. 2. RACEWAY: RACEWAY: A. MINIMUM SIZE OF THE CONDUIT SHALL BE 3/4". MINIMUM SIZE OF THE CONDUIT SHALL BE 3/4". B. PROVIDE FLEXIBLE CONDUIT FOR MOTOR CONNECTIONS, AND FOR OTHER ELECTRICAL EQUIPMENT CONDITIONS, WHERE PROVIDE FLEXIBLE CONDUIT FOR MOTOR CONNECTIONS, AND FOR OTHER ELECTRICAL EQUIPMENT CONDITIONS, WHERE SUBJECT TO MOVEMENT AND VIBRATION. 18" MAXIMUM LENGTH. C. PROVIDE LIQUID TIGHT FLEXIBLE CONDUIT FOR CONNECTION OF MOTOR AND FOR OTHER ELECTRICAL EQUIPMENT PROVIDE LIQUID TIGHT FLEXIBLE CONDUIT FOR CONNECTION OF MOTOR AND FOR OTHER ELECTRICAL EQUIPMENT WHERE SUBJECT TO MOVEMENT AND VIBRATION, AND ALSO WHERE SUBJECT TO ONE OR MORE OF THE FOLLOWING CONDITIONS, UNLESS NOTED OTHERWISE: a. MOIST AND HUMID ATMOSPHERE WHERE CONDENSATE CAN BE EXPECTED TO ACCUMULATE. MOIST AND HUMID ATMOSPHERE WHERE CONDENSATE CAN BE EXPECTED TO ACCUMULATE. b. CORROSIVE ATMOSPHERE. CORROSIVE ATMOSPHERE. c. SUBJECT TO DRIPPING OIL, GREASE OR WATER. SUBJECT TO DRIPPING OIL, GREASE OR WATER. D. ALL CONDUITS SHALL BE GROUNDED PER NEC. CONDUITS ENTERING THE OUTLET BOXES, PANEL CABINETS ETC. MUST ALL CONDUITS SHALL BE GROUNDED PER NEC. CONDUITS ENTERING THE OUTLET BOXES, PANEL CABINETS ETC. MUST BE FITTED WITH A DOUBLE LOCKNUT AND BUSHING. E. PROVIDE RIGID STEEL, THREADED, THICK WALL CONDUIT, GALVANIZED OR EMT FOR ALL PANEL FEEDERS, AND ALL PROVIDE RIGID STEEL, THREADED, THICK WALL CONDUIT, GALVANIZED OR EMT FOR ALL PANEL FEEDERS, AND ALL EXPOSED WIRING IN UNFINISHED AREAS. F. ALL WIRE RACEWAYS IN OR PASSING THROUGH CONCRETE WALLS, SLABS, OR UNDERGROUND SHALL BE GALVANIZED ALL WIRE RACEWAYS IN OR PASSING THROUGH CONCRETE WALLS, SLABS, OR UNDERGROUND SHALL BE GALVANIZED RIGID STEEL THREADED CONDUIT. 3. WIRES AND CABLES: WIRES AND CABLES: A. ALL WIRE AND CABLE SHALL BE COPPER WITH THHN/THWN INSULATION AND ALL WIRE SIZES ARE BASED ON COPPER ALL WIRE AND CABLE SHALL BE COPPER WITH THHN/THWN INSULATION AND ALL WIRE SIZES ARE BASED ON COPPER CONDUCTORS WITH 75°C INSULATION UNLESS INDICATED OTHERWISE. ALL CONNECTORS, LUGS, ETC. SHALL BE LISTEDFOR 75°C.B. PROVIDE WIRING NOT SMALLER THAN #12 AWG FOR THE POWER DISTRIBUTION, AND NOT SMALLER THAN #14 AWG FOR PROVIDE WIRING NOT SMALLER THAN #12 AWG FOR THE POWER DISTRIBUTION, AND NOT SMALLER THAN #14 AWG FOR THE FIRE ALARM SYSTEM. C. ALL CIRCUITS 120/208 VOLT OVER 100 FEET AND ALL 277/480 VOLT CIRCUITS OVER 200 FEET FROM PANEL TO ALL CIRCUITS 120/208 VOLT OVER 100 FEET AND ALL 277/480 VOLT CIRCUITS OVER 200 FEET FROM PANEL TO FIRST OUTLET SHALL HAVE CONDUCTORS ONE SIZE LARGER THAN NORMALLY REQUIRED WHETHER INDICATED ON PANEL SCHEDULE OR NOT. D. CONDUCTORS INSTALLED UNDERGROUND OR IN THE WET LOCATIONS SHALL BE U.L. LISTED PER NEC, AND SHALL BE CONDUCTORS INSTALLED UNDERGROUND OR IN THE WET LOCATIONS SHALL BE U.L. LISTED PER NEC, AND SHALL BE SUITABLE FOR WET LOCATIONS. E. ALL BRANCH CIRCUIT WIRING SHALL BE PROVIDED WITH AN INSULATED GROUND CONDUCTOR FOR ANY DEVICE ALL BRANCH CIRCUIT WIRING SHALL BE PROVIDED WITH AN INSULATED GROUND CONDUCTOR FOR ANY DEVICE ACCESSIBLE BY A PATIENT AS PER NEC 517.13 (A) & (B). 4. ELECTRICAL BOXES AND FITTINGS: ELECTRICAL BOXES AND FITTINGS: A. ALL BOXES AND FITTINGS SHALL BE OF CODE-GAUGE STEEL. ALL BOXES AND FITTINGS SHALL BE OF CODE-GAUGE STEEL. B. JUNCTION AND PULL BOXES: PROVIDE GALVANIZED CODE-GAUGE SHEET STEEL JUNCTION AND PULL BOXES WITH JUNCTION AND PULL BOXES: PROVIDE GALVANIZED CODE-GAUGE SHEET STEEL JUNCTION AND PULL BOXES WITH SCREW-ON COVER OF TYPES, SHAPES AND SIZES TO SUIT EACH RESPECTIVE LOCATION AND INSTALLATION, WITH WELDED SEAMS AND EQUIPPED WITH STAINLESS STEEL NUTS, SCREWS, AND WASHERS. C. PROVIDE WEATHERPROOF OUTLETS FOR INTERIOR AND EXTERIOR LOCATIONS EXPOSED TO WEATHER OR MOISTURE. PROVIDE WEATHERPROOF OUTLETS FOR INTERIOR AND EXTERIOR LOCATIONS EXPOSED TO WEATHER OR MOISTURE. D. ALL PULL BOXES SHALL BE FABRICATED FROM #12 OR HEAVIER GAUGE GALVANIZED STEEL AS REQUIRED BY THE NEC, ALL PULL BOXES SHALL BE FABRICATED FROM #12 OR HEAVIER GAUGE GALVANIZED STEEL AS REQUIRED BY THE NEC, AND SHALL BE EQUIPPED WITH SCREW FASTENED COVER. 5. WIRING DEVICES: WIRING DEVICES: A. PROVIDE DUPLEX, HOSPITAL GRADE RECEPTACLES 2 POLE, 3 WIRE GROUNDING WITH GREEN HEXAGONAL EQUIPMENT PROVIDE DUPLEX, HOSPITAL GRADE RECEPTACLES 2 POLE, 3 WIRE GROUNDING WITH GREEN HEXAGONAL EQUIPMENT GROUND SCREWS, GROUND TERMINALS AND POLES INTERNALLY CONNECTED TO MOUNTING YOKE, 20 AMPERES, 125 VOLTS, WITH METAL PLASTER EARS, SIDE WIRING, NEMA CONFIGURATION 5-20R. ALL RECEPTACLES ON EMERGENCY POWER SHALL BE IN RED COLOR WITH MATCHING COVER PLATES. B. WEATHERPROOF RECEPTACLE, SHALL BE WEATHER RESISTANT PER NEC 406.9. WEATHERPROOF RECEPTACLE, SHALL BE WEATHER RESISTANT PER NEC 406.9. C. SWITCHES, 20 AMPS, 120/277 VOLTS, WITH MOUNTING YOKE INSULATED FROM MECHANISM, EQUIPPED WITH PLASTER SWITCHES, 20 AMPS, 120/277 VOLTS, WITH MOUNTING YOKE INSULATED FROM MECHANISM, EQUIPPED WITH PLASTER EARS, SWITCH HANDLE, AND SIDE WIRED SCREW TERMINALS. D. ALL SWITCHES AND RECEPTACLES SHALL BE OF WHITE COLOR WITH MATCHING COVER PLATES, OR AS SELECTED BY ALL SWITCHES AND RECEPTACLES SHALL BE OF WHITE COLOR WITH MATCHING COVER PLATES, OR AS SELECTED BY ARCHITECT. E. ALL DEVICES INSTALLED IN THE LOCATION EXPOSED TO AMBIENT CONDITIONS SHALL BE WEATHERPROOF AND SHALL ALL DEVICES INSTALLED IN THE LOCATION EXPOSED TO AMBIENT CONDITIONS SHALL BE WEATHERPROOF AND SHALL COMPLY WITH NEC 406.9. 6. PANELBOARDS: PANELBOARDS: A. PANELBOARD BUSBARS SHALL BE COPPER. PANELBOARD BUSBARS SHALL BE COPPER. B. PANELBOARD ENCLOSURES: PROVIDE GALVANIZED SHEET STEEL CABINET, CODE-GAUGE, GUTTERS. PROVIDE FRONTS PANELBOARD ENCLOSURES: PROVIDE GALVANIZED SHEET STEEL CABINET, CODE-GAUGE, GUTTERS. PROVIDE FRONTS WITH ADJUSTABLE TRIM CLAMPS, AND DOORS WITH CONCEALED PIANO DOOR HINGES AND DOOR SWINGS AS INDICATED. EQUIPMENT WITH INTERIOR CIRCUIT-DIRECTORY FRAME AND CARD WITH CLEAR PLASTIC COVERING. PROVIDE BAKED GRAY ENAMEL FINISH OVER A RUST INHIBITOR COATING. DESIGN ENCLOSURES FOR RECESSED/SURFACE MOUNTING AS INDICATED. PROVIDE ENCLOSURES WHICH ARE FABRICATED BY SAME MANUFACTURES AS PANELBOARDS WHICH MATE AND MATCH PROPERLY WITH PANELBOARD TO BE ENCLOSED. C. CABINETS FOR DISTRIBUTION PANELS SHALL HAVE 6 INCHES OF GUTTER SPACE ON ALL SIDES. PANELBOARDS AND CABINETS FOR DISTRIBUTION PANELS SHALL HAVE 6 INCHES OF GUTTER SPACE ON ALL SIDES. PANELBOARDS AND LIGHTING PANELS SHALL HAVE A MINIMUM OF 5" ON ALL SIDES. D. ALL PANELBOARDS SHALL BE EQUIPPED WITH COMMON KEYED LOCKS. PROVIDE MINIMUM OF ONE KEY PER PANEL ALL PANELBOARDS SHALL BE EQUIPPED WITH COMMON KEYED LOCKS. PROVIDE MINIMUM OF ONE KEY PER PANEL PLUS (6) SPARES. E. PANELBOARDS SHALL BE AS INDICATED ON THE DRAWINGS, WITH BOLT-ON MOLDED CASE CIRCUIT BREAKERS AND PANELBOARDS SHALL BE AS INDICATED ON THE DRAWINGS, WITH BOLT-ON MOLDED CASE CIRCUIT BREAKERS AND COPPER BUS BARS. CIRCUIT BREAKERS AND INTERIORS SHALL BE OF THE SAME MANUFACTURER AND UL LISTED. THE PANELBOARDS SHALL COMPLY WITH ALL APPLICABLE STANDARDS. F. ALL NEW ELECTRICAL EQUIPMENT AND PANELBOARDS PROVIDED UNDER THIS WORK SHALL BE FULLY RATED. SERIES ALL NEW ELECTRICAL EQUIPMENT AND PANELBOARDS PROVIDED UNDER THIS WORK SHALL BE FULLY RATED. SERIES RATED EQUIPMENT AND PANELBOARDS ARE NOT ACCEPTABLE. 1. DISCONNECT SWITCHES: DISCONNECT SWITCHES: A. DISCONNECT SWITCHES SHALL BE TYPE HD, HEAVY DUTY, FUSIBLE OR NON-FUSIBLE, AS NOTED, SINGLE THROW, DISCONNECT SWITCHES SHALL BE TYPE HD, HEAVY DUTY, FUSIBLE OR NON-FUSIBLE, AS NOTED, SINGLE THROW, 600-V AC, 1200 A AND SMALLER: UL 98 AND NEMA KS 1, HORSEPOWER RATED, WITH CLIPS OR BOLT PADS TO ACCOMMODATE INDICATED FUSES, LOCKABLE HANDLE WITH CAPABILITY TO ACCEPT TWO PADLOCKS, AND INTERLOCKED WITH COVER IN CLOSED POSITION. NEMA TYPE 1 OR 3R, AS REQUIRED.
AutoCAD SHX Text
(E) DENOTES EXISTING TO REMAIN. (R) DENOTES EXISTING TO BE REMOVED WITH ALL CIRCUITRY THERETO. (RE) DENOTES EXISTING TO BE RELOCATED. (ER) DENOTES NEW LOCATION OF EXISTING ITEM.(*) (N) DENOTES NEW TO MATCH EXISTING. (*) EXTEND AND RECONNECT TO EXISTING BRANCH CIRCUIT WIRING AS REQUIRED.
AutoCAD SHX Text
%%UDEMO/NEW WORK LEGEND
AutoCAD SHX Text
%%UELECTRICAL SYMBOLS
AutoCAD SHX Text
%%UEQUIPMENT SPECIFICATIONS
AutoCAD SHX Text
A AFF AIC ATS AV CB CKT COR CU DN EC FAAP FACP FSS GFI GND HP HWRC IBC IG IT
AutoCAD SHX Text
%%UELECTRICAL ABBREVIATIONS
AutoCAD SHX Text AMP ABOVE FINISHED FLOOR AMPS INTERRUPTING CAPACITY AUTOMATIC TRANSFER SWITCH AUDIO VIDEO CIRCUIT BREAKER CIRCUIT CONTRACTING OFFICER REPRESENTATIVE COPPER DOWN EMPTY CONDUIT FIRE ALARM ANNUNCIATOR PANEL FIRE ALARM CONTROL PANEL FUSED SAFETY SWITCH GROUND FAULT INTERRUPTER GROUND HORSE POWER HOT WATER RECIRCULATING PUMP INTERNATIONAL BUILDING CODE ISOLATED GROUND INFORMATION TECHNOLOGY
AutoCAD SHX Text %%uELECTRICAL NOTES
AutoCAD SHX Text NOTE: THESE ABBREVIATIONS ARE STANDARD AND ALL MAY NOT BE APPLICABLE TO THIS PROJECT.
AutoCAD SHX Text FLUORESCENT OR LED LIGHTING FIXTURE. SEE LIGHTING FIXTURE SCHEDULE. LIGHTING FIXTURE ON EMERGENCY CIRCUIT OR WITH EMERGENCY BATTERY BACK-UP. CEILING MOUNTED RECESS/SURFACE DOWN LIGHT FIXTURE. WALL MOUNTED LIGHTING FIXTURE. EXIT SIGN. CONNECT TO UNSWITCHED HOT-LEG OF CIRCUIT INDICATED. BRANCH CIRCUIT WIRING CONCEALED IN WALLS OR CEILING. NUMBER OF HASHES INDICATES NUMBER OF WIRES AND SHOWN ONLY WHERE REQUIRED FOR CLARITY. 2 #12AWG + 1 #12 GROUND IN 3/4"C. BRANCH CIRCUIT WIRING RUN UNDER GROUND OR UNDER SLAB. 2 #12AWG + 1 #12 GROUND IN 3/4"C. HOME RUN TO PANELBOARD. NUMBER OF ARROWS INDICATE NUMBER OF CIRCUITS IN HOME RUN. 2 #12AWG + 1 12 GROUND IN 3/4"C. FLUSH MOUNTED SWITCH, +48" AFF. 3 WAY OR 4 WAY FLUSH MOUNTED SWITCH, +48" AFF. MOTOR RATED SWITCH WITH THERMAL OVERLOAD PROTECTION. FLUSH MOUNTED SWITCH WITH VACANCY SENSOR (DUAL TECHNOLOGY), +48" AFF. FLUSH MOUNTED SWITCH WITH OCCUPANCY SENSOR (DUAL TECHNOLOGY), +48" AFF. FLUSH MOUNTED SWITCH WITH PILOT LIGHT, +48" AFF. LOW VOLTAGE SWITCH. LOWER-CASE LETTER INDICATES WHICH FIXTURES ARE CONTROLLED BY WHICH LIGHT FIXTURE. LOW VOLTAGE DIMMER SWITCH. LOWER-CASE LETTER INDICATES WHICH FIXTURES ARE CONTROLLED BY WHICH SWITCH. "#" INDICATES THE QUANTITY OF LIGHTING ZONES. COORDINATE WITH MANUFACTURER FOR 3-WAY SWITCH/DIMMER SWITCH CAT. NO., AND INSTALLATION AS REQUIRED. COORDINATE COMPATIBLE DIMMING BALLAST/DRIVER WITH DIMMING CONTROL AS REQUIRED. DUAL TECHNOLOGY WALL SWITCH SENSOR/DIMMING 0-10V. CEILING MOUNTED OCCUPANCY SENSOR. LOW VOLTAGE POWER PACK UNIT FOR CONNECTING CEILING MOUNTED SENSORS. JUNCTION BOX, SIZE AS REQUIRED. DUPLEX RECEPTACLE, NEMA 5-20R, +18" AFF, U.O.N. (A) DENOTES 3" ABOVE COUNTER TOP/BACK SPLASH. (WP) DENOTES WEATHERPROOF WHILE IN USE WITH GROUND FAULT INTERRUPTER (GFI). DUPLEX RECEPTACLE WITH GROUND FAULT INTERRUPTER (GFI), NEMA 5-20R, +18" AFF, U.O.N. DUPLEX RECEPTACLE WITH GROUND FAULT INTERRUPTER (GFI), NEMA 5-20R, +18" AFF, U.O.N. (A) DENOTES 3" ABOVE COUNTER TOP/BACK SPLASH. DUPLEX RECEPTACLE ON EMERGENCY POWER, NEMA 5-20R, +18" AFF, U.O.N. DOUBLE DUPLEX (QUAD) RECEPTACLE, NEMA 5-20R, +18" AFF. DOUBLE DUPLEX (QUAD) RECEPTACLE ON EMERGENCY POWER, NEMA 5-20R, +18" AFF. DUPLEX RECEPTACLE WITH USB, NEMA 5-20R, +46" AFF. SINGLE RECEPTACLE, NEMA CONFIGURATION AS NOTED, +18" AFF. WALL MOUNTED COMMUNICATIONS OUTLET, (TELE/DATA) COMBO +18" AFF, UON. CONTRACTOR TO PROVIDE AND INSTALL BACK BOX, 1" CONDUIT STUB-UP 6" INTO CEILING SPACE, (2) DATA AND (2) PHONE FACE PLATE AND (4) CAT 6A PLENUM CABLES FROM THE DEVICE TO THE TELECOM CLOSET. FINAL CONNECTIONS TO TELE COMMUNICATION HEAD-ENDS SHALL BE PERFORMED BY THE IT/TELE COMMUNICATION CONTRACTOR. PROVIDE ADDITIONAL PATCH PANEL IN IT ROOM AS REQUIRED TO ACCOMMODATE NEW DEVICES AND CABLING. WALL MOUNTED TELEPHONE OUTLET, 54" AFF, UON. CONTRACTOR TO PROVIDE AND INSTALL BACK BOX, 1" CONDUIT STUB-UP 6" INTO CEILING SPACE. COORDINATE WITH VA FOR NUMBER OF CABLES REQUIRED FROM THE DEVICE TO TELECOM CLOSET. FINAL CONNECTIONS TO TELE COMMUNICATION HEAD-ENDS SHALL BE PERFORMED BY THE IT/ TELE COMMUNICATION CONTRACTOR. PROVIDE ADDITIONAL PATCH PANEL IN IT ROOM AS REQUIRED TO ACCOMMODATE NEW DEVICES AND CABLING. 120/208 VOLT ELECTRICAL PANELBOARD, SURFACE/RECESSED MOUNTED, +6'-0" TO TOP. DRY TYPE TRANSFORMER, KVA AS NOTED, 480 VOLT DELTA PRIMARY, TO 208Y/120 VOLT SECONDARY, 3 . U.O.N.277/480 VOLT PANELBOARD, SURFACE/RECESSED MOUNTED +6'-0" TO TOP. MOTOR CONNECTION. NON-FUSED DISCONNECT SWITCH. 600V, OR 240V, #/# INDICATE AMPS/POLE. FUSE DISCONNECT SWITCH 600V, OR 240V, #/# INDICATE AMPS/POLE FUSING TO MATCH CIRCUIT BREAKER, U.O.N. VARIABLE FREQUENCY DRIVE WITH DISCONNECTING MEANS. PROVIDED BY MECHANICAL CONTRACTOR, CONNECTION BY THE ELECTRICAL CONTRACTOR. MOTOR STARTER. ENCLOSED CIRCUIT BREAKER. FIRE ALARM MANUAL PULL STATION, 48" AFF. WALL MOUNTED FIRE ALARM AUDIO/VISUAL INDICATING DEVICE, 80" AFF. CANDELA RATING AS NOTED. WALL MOUNTED FIRE ALARM VISUAL ONLY INDICATING DEVICE, 80" AFF. CANDELA RATING AS NOTED. CEILING MOUNTED FIRE ALARM AUDIO/VISUAL INDICATING DEVICE, 80" AFF. CANDELA RATING AS NOTED. CEILING MOUNTED FIRE ALARM VISUAL ONLY INDICATING DEVICE, 80" AFF. CANDELA RATING AS NOTED. SMOKE DETECTOR. (D) DENOTES DUCT SMOKE. GROUND PER NEC ARTICLE 250. CABLE TELEVISION CONNECTION - PROVIDE 4" SQUARE BOX WITH 1" EMPTY CONDUIT FROM CABLE TV JUNCTION BOX TO CABLE TV RACK LOCATION. PROVIDE COAX CABLE TO TELECOMM ROOM. COORDINATE EXACT ROUTING AND TERMINATIONS OF THE CONDUIT RUN WITH THE VA. REFER TO ARCHITECTURE DRAWING FOR ELEVATION AND MOUNTING HEIGHT. KEY PAD - PROVIDE 4" SQUARE BOX AND STUB OUT 3/4" EC 6" INTO CEILING SPACE. PROVIDE MATCHING OUTLET FOR DOOR PUSH EXIT BUTTON AS REQUIRED. DOOR PUSH EXIT BUTTON - 4" SQUARE BOX AND STUB OUT 3/4" EC 6" INTO CEILING SPACE. PROVIDE MULTI-SERVICE CAST IRON FLUSH FLOOR BOX EQUIVALENT TO LEGRAND CAT. # RFB4-CI-1-NA RAKM11 (INCLUDED FLANGED COVER ASSEMBLIES PER COR SELECTION) WITH (2) CILT-2RT TELE/ DATA BRACKETS. PROVIDE (2) DUPLEX RECEPTACLES FOR COMPUTERS, RUN 1.25" EMPTY CONDUIT FROM FLOOR BOX TELE/ DATA BRACKET AND STUB ELECTRICAL CONDUIT 6" INTO CEILING SPACE AS REQUIRED. SEE ARCHITECTURAL FLOOR PLANS FOR ROUTING OF POWER/TELEPHONE AND A/V CONDUITS. COORDINATE LOCATION SYSTEMS BELOW, AND GPR SLAB PRIOR TO ROUGH-IN. COORDINATE FINAL SPECIFICATION AND LOCATION WITH ARCHITECT/COR/AV/IT CONSULTANTS. CARD READER - 4" SQUARE BOX AND STUB OUT 3/4" EC 6" INTO CEILING SPACE. SECURITY CAMERA - 4" SQUARE BOX ABOVE CEILING. WIREMESH CABLE TRAY 4"(H) x 6"(W) FOR TELEPHONES, DATA AND COMMUNICATION CABLING. WALL MOUNTED PUSH BUTTON, 2-1/4" RED MUSHROOM HEAD, PUSH-PULL ACTION, LABELED "EMERGENCY POWER OFF", WITH CLEAR ACRYLIC COVER TO PREVENT ACCIDENTAL OPERATION. PROVIDE CONTACTS AS REQUIRED. REFER TO PHILIPS WIRING SCHEMATICS FOR ADDITIONAL WIRING AND CONNECTION REQUIREMENTS, PRIOR TO ROUGH-IN.
AutoCAD SHX Text 15cd
AutoCAD SHX Text V
AutoCAD SHX Text
SD
AutoCAD SHX Text F
AutoCAD SHX Text
AV
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text O
AutoCAD SHX Text S
AutoCAD SHX Text 3, AutoCAD SHX Text S
AutoCAD SHX Text
AutoCAD SHX Text m
AutoCAD SHX Text S
AutoCAD SHX Text J
AutoCAD SHX Text S
AutoCAD SHX Text P
AutoCAD SHX Text T
AutoCAD SHX Text NOTE: THESE SYMBOLS ARE STANDARD AND ALL MAY NOT BE APPLICABLE TO THIS JOB. ALL MOUNTING HEIGHTS ARE STANDARD UNLESS NOTED OTHERWISE ON THE DRAWINGS.
AutoCAD SHX Text
1. CONTRACTOR SHALL REMOVE ALL EXISTING WORK THAT WILL NOT BE REUSED DURING NEW CONSTRUCTION. LEAVING THE CONTRACTOR SHALL REMOVE ALL EXISTING WORK THAT WILL NOT BE REUSED DURING NEW CONSTRUCTION. LEAVING THE BUILDING FREE AND CLEAN OF OLD SYSTEMS. 2. THE CONTRACTOR SHALL COORDINATE ALL WORK WITH OTHER TRADES. THE CONTRACTOR SHALL COORDINATE ALL WORK WITH OTHER TRADES. 3. CONTRACTOR SHALL BE RESPONSIBLE FOR MAINTAINING FIRE RATING, AND WATERPROOFING INTEGRITY IN ALL CASES. CONTRACTOR SHALL BE RESPONSIBLE FOR MAINTAINING FIRE RATING, AND WATERPROOFING INTEGRITY IN ALL CASES. 4. ALL REMOVED ITEMS SHALL BECOME THE PROPERTY OF THE CONTRACTOR FOR DISPOSAL UNLESS OTHERWISE DIRECTED. ALL REMOVED ITEMS SHALL BECOME THE PROPERTY OF THE CONTRACTOR FOR DISPOSAL UNLESS OTHERWISE DIRECTED. CONTRACTOR SHALL COORDINATE FOR ITEMS THAT SHALL BE RETURNED TO COR. OTHER ITEMS THAT ARE NOT REQUIRED TO BE TURNED IN SHALL BECOME THE PROPERTY OF THE CONTRACTOR FOR DISPOSAL. 5. DEMOLITION SHALL BE WELL COORDINATED TO MINIMIZE DOWN TIME OF SYSTEMS THAT WILL REMAIN IN OPERATION. DEMOLITION SHALL BE WELL COORDINATED TO MINIMIZE DOWN TIME OF SYSTEMS THAT WILL REMAIN IN OPERATION. 6. PROVIDE CAP OFF CONNECTIONS FOR ALL REMOVED OR CUT OFF WORK THAT WILL NOT BE RECONNECTED DURING THE PROVIDE CAP OFF CONNECTIONS FOR ALL REMOVED OR CUT OFF WORK THAT WILL NOT BE RECONNECTED DURING THE NEW WORK PHASE. 7. REMOVE ALL EXPOSED, ELECTRICAL SERVICES THAT ARE NOT GOING TO BE REUSED IN NEW WORK BACK TO SOURCE. REMOVE ALL EXPOSED, ELECTRICAL SERVICES THAT ARE NOT GOING TO BE REUSED IN NEW WORK BACK TO SOURCE. 8. WHEN DEMOLITION WORK IS AFFECTING EXISTING UTILITIES SERVING BASE BUILDING, CONTRACTOR SHALL RELOCATE, WHEN DEMOLITION WORK IS AFFECTING EXISTING UTILITIES SERVING BASE BUILDING, CONTRACTOR SHALL RELOCATE, REROUTE, OFFSET IN CEILING SPACE, OR UNDER FLOOR SLAB, (SAW CUT SLAB WHEN REQUIRED) AND RELOCATE ALL SERVICES IN ACCORDANCE WITH ALL APPLICABLE CODES, REGULATIONS AND GOOD PRACTICE OF TRADES. COORDINATE WITH BUILDING OWNER REPRESENTATIVE, AND MAKE PROVISIONS FOR TEMPORARY SERVICES AS REQUIRED. CONTRACTOR SHALL COORDINATE AND GIVE ADEQUATE NOTICE TO COR PRIOR TO WORK IN ANY BASE BUILDING UTILITIES. 9. ALL ELECTRICAL DEVICES IN WALLS TO BE DEMOLISHED SHALL BE REMOVED UNLESS OTHERWISE NOTED. MAINTAIN CIRCUIT ALL ELECTRICAL DEVICES IN WALLS TO BE DEMOLISHED SHALL BE REMOVED UNLESS OTHERWISE NOTED. MAINTAIN CIRCUIT CONTINUITY FOR DEVICES THAT REMAIN. 10. SUPPORT ALL CEILING MOUNTED DEVICES INDEPENDENT OF CEILING GRIDS & TILES, WHICH WILL BE REMOVED & SUPPORT ALL CEILING MOUNTED DEVICES INDEPENDENT OF CEILING GRIDS & TILES, WHICH WILL BE REMOVED & REINSTALLED WHEN NEW WALLS ARE CONSTRUCTED.
AutoCAD SHX Text
%%UELECTRICAL DEMOLITION NOTES
AutoCAD SHX Text
1. MODIFY FIRE ALARM SYSTEM ON DESIGN-BUILD BASIS. PROVIDE ADDITIONAL DEVICES, IF REQUIRED, BY THE VA COR EITHER MODIFY FIRE ALARM SYSTEM ON DESIGN-BUILD BASIS. PROVIDE ADDITIONAL DEVICES, IF REQUIRED, BY THE VA COR EITHER DURING SHOP DRAWINGS REVIEW PHASE, OR DURING CONSTRUCTION PHASE WITHOUT ANY ADDITIONAL COST TO THE VA. 2. ALL DEVICES AND EQUIPMENT FOR THIS SYSTEM SHALL BE LISTED BY THE UNDERWRITER'S LABORATORIES, INC. (U.L.), ALL DEVICES AND EQUIPMENT FOR THIS SYSTEM SHALL BE LISTED BY THE UNDERWRITER'S LABORATORIES, INC. (U.L.), BEAR THE U.L. LABEL AND SHALL CONFORM TO THE APPLICABLE SECTIONS OF NATIONAL FIRE PROTECTION ASSOCIATION (NFPA) 72 AND 90A. 3. THE INSTALLATION SHALL BE IN ACCORDANCE WITH ALL REQUIREMENTS OF NFPA 72, NFPA 90A, THE NATIONAL ELECTRICAL THE INSTALLATION SHALL BE IN ACCORDANCE WITH ALL REQUIREMENTS OF NFPA 72, NFPA 90A, THE NATIONAL ELECTRICAL CODE (NEC), ALL STATE AND LOCAL CODES AND ADA REQUIREMENTS. 4. UPON COMPLETION, THE SYSTEM SHALL BE THOROUGHLY TESTED BY THE CONTRACTOR TO ASSURE PROPER INTERFACING UPON COMPLETION, THE SYSTEM SHALL BE THOROUGHLY TESTED BY THE CONTRACTOR TO ASSURE PROPER INTERFACING OF ALL COMPONENTS. VA SAFETY OFFICER MUST BE WITNESS TO ALL TESTING. VERIFY IN WRITING THAT 100% OF THE PROJECT'S DEVICES WERE TESTED. 5. ALL WIRING FOR THE FIRE DETECTION AND ALARM SYSTEM SHALL BE RUN IN CONDUIT BY THE CONTRACTOR. ALL FIRE ALL WIRING FOR THE FIRE DETECTION AND ALARM SYSTEM SHALL BE RUN IN CONDUIT BY THE CONTRACTOR. ALL FIRE ALARM JUNCTION BOX COVERS SHALL BE PAINTED RED BY THE CONTRACTOR OR STENCILED FOR DISTINCT IDENTIFICATION. ALL CONDUIT, DEVICE MOUNTING BOXES, JUNCTION BOXES, AND PANELS SHALL BE SECURELY FASTENED BY THE CONTRACTOR WITH APPROPRIATE FITTINGS TO INSURE A POSITIVE GROUND THROUGHOUT THE ENTIRE SYSTEM. 6. ALL CONNECTIONS TO PANELS, DEVICES, AND DETECTORS SHALL BE MADE WITH CRIMP TYPE SPADE TERMINAL ALL CONNECTIONS TO PANELS, DEVICES, AND DETECTORS SHALL BE MADE WITH CRIMP TYPE SPADE TERMINAL CONNECTORS. SPLICES IN STATION CIRCUITS SHALL BE MADE ONLY IN JUNCTION BOXES AND SHALL BE CRIMP CONNECTED. 7. ALL WIRING SHALL BE CHECKED AND TESTED BY THE CONTRACTOR TO INSURE THE SYSTEM IS FREE FROM GROUNDS, ALL WIRING SHALL BE CHECKED AND TESTED BY THE CONTRACTOR TO INSURE THE SYSTEM IS FREE FROM GROUNDS, OPENS, AND SHORTS. 8. THE INSTALLATION AND FINAL CONNECTIONS BY THE CONTRACTOR OF ALL COMPONENTS AND DEVICES SHALL BE THE INSTALLATION AND FINAL CONNECTIONS BY THE CONTRACTOR OF ALL COMPONENTS AND DEVICES SHALL BE PERFORMED UNDER THE DIRECT SUPERVISION OF THE SYSTEM MANUFACTURER'S TECHNICAL STAFF. 9. CONTRACTOR SHALL MODIFY EXISTING SYSTEM AS REQUIRED, PROVIDE ALL NECESSARY SUB-PANELS, AUXILIARY PANEL TO CONTRACTOR SHALL MODIFY EXISTING SYSTEM AS REQUIRED, PROVIDE ALL NECESSARY SUB-PANELS, AUXILIARY PANEL TO CONVERT 110 VOLT TO 24 VOLT SYSTEM, POWER SUPPLIES, SUPPLIES, BATTERIES, ETC. IN ORDER TO ACCEPT NEW DEVICES AND OPERATE THE SYSTEM AS ONE INTEGRAL SYSTEM COMPLYING WITH ALL APPLICABLE REQUIREMENTS. ALL NEW DEVICES SHALL MATCH EXISTING. 10. CONTRACTOR SHALL VERIFY TYPE OF EXISTING FIRE ALARM SYSTEM BEFORE SUBMITTING THE BID. ALL MODIFICATIONS TO CONTRACTOR SHALL VERIFY TYPE OF EXISTING FIRE ALARM SYSTEM BEFORE SUBMITTING THE BID. ALL MODIFICATIONS TO EXISTING SYSTEM IN ORDER TO ACCEPT NEW DEVICES. SHALL BE INCLUDED IN THE BID. THE EXISTING FIRE ALARM SYSTEM IS MANUFACTURED BY SIEMENS. 11. WHERE INDICATED, PROVIDE DUCT-MOUNTED SMOKE DETECTORS WHICH SHALL BE INSTALLED BY MECHANICAL WHERE INDICATED, PROVIDE DUCT-MOUNTED SMOKE DETECTORS WHICH SHALL BE INSTALLED BY MECHANICAL CONTRACTOR.
AutoCAD SHX Text
%%UFIRE ALARM NOTES
AutoCAD SHX Text
VFD
AutoCAD SHX Text
1. ALL RECEPTACLES (DUPLEX OR OTHERWISE) AND TELECOMUNICATION OUTLETS SHALL BE CAST-TYPE, FLUSH MOUNTED WITH ALL RECEPTACLES (DUPLEX OR OTHERWISE) AND TELECOMUNICATION OUTLETS SHALL BE CAST-TYPE, FLUSH MOUNTED WITH GASKETED COVERPLATES. SURFACE MOUNTED PORTION OF RECEPTACLE/OUTLET BOXES ARE TO BE SEALED AND CAULKED VAPOR TIGHT. ALL CONDUITS AND WIRING SERVING RECEPTACLE/OUTLET BOXES SHALL BE SEALED AND CAULKED VAPOR TIGHT COMING INTO BOX, INSIDE BOX, AND AT FINISHED CEILING PENETRATION. SEAL AT INSIDE SUPPORT PENETRATIONS. 2. ALL PENETRATIONS IN WALL, CEILING, AND FLOOR MUST BE SEALED/CAULKED VAPOR TIGHT. THIS INCLUDES, BUT ARE NOT ALL PENETRATIONS IN WALL, CEILING, AND FLOOR MUST BE SEALED/CAULKED VAPOR TIGHT. THIS INCLUDES, BUT ARE NOT LIMITED TO THOSE PENETRATIONS MADE BY CONDUITS, JUNCTION BOXES, AND EQUIPMENT/CONDUIT/CAST BOX SUPPORTS. 3. PROVIDE VAPOR TIGHT SEALANT AROUND THE SURFACE MOUNTED PORTIONS OF ALL LIGHTING FIXTURES, LIGHT SWITCHES, PROVIDE VAPOR TIGHT SEALANT AROUND THE SURFACE MOUNTED PORTIONS OF ALL LIGHTING FIXTURES, LIGHT SWITCHES, RECEPTACLES, TELECOMMUNICATION OUTLETS, WIREMOLD, SECURITY EQUIPMENT, ALARM DEVICES, AND FIRE ALARM EQUIPMENT. 4. ALL JUNCTION BOXES SHALL BE CAST TYPE WITH WEATHERPROOF, GASKETED COVERS. ALL CONDUITS AND WIRING SERVING ALL JUNCTION BOXES SHALL BE CAST TYPE WITH WEATHERPROOF, GASKETED COVERS. ALL CONDUITS AND WIRING SERVING JUNCTION BOXES SHALL BE SEALED AND CAULKED VAPOR TIGHT COMING INTO BOX, INSIDE BOX, AND AT FINISHED CEILING PENETRATION. SEAL AT INSIDE SUPPORT PENETRATIONS. 5. DO NOT EXPOSE CONDUITS IF POSSIBLE UNLESS NOTED OTHERWISE. ALL EXPOSED CONDUITS SHALL BE RGS CONDUIT WITH DO NOT EXPOSE CONDUITS IF POSSIBLE UNLESS NOTED OTHERWISE. ALL EXPOSED CONDUITS SHALL BE RGS CONDUIT WITH THREADED FITTINGS. ALL ALARM, SECURITY, TELECOMMUNICATIONS, FIRE ALARM, AND ELECTRICAL WIRING MUST BE IN RGS CONDUIT. SEAL AT CONDUIT SUPPORTS. 6. ALL CONDUITS AND WIRING SERVING LIGHTING FIXTURES SHALL BE SEALED AND CAULKED VAPOR TIGHT COMING INTO FIXTURE ALL CONDUITS AND WIRING SERVING LIGHTING FIXTURES SHALL BE SEALED AND CAULKED VAPOR TIGHT COMING INTO FIXTURE AND AT FINISHED CEILING PENETRATION. SEAL AT INSIDE SUPPORT PENETRATIONS. 7. ALL WORK DONE BY ELECTRICAL CONTRACTOR MUST NOT ADVERSELY IMPACT THE VAPOR TIGHT ENVIRONMENT OF THE PROJECT ALL WORK DONE BY ELECTRICAL CONTRACTOR MUST NOT ADVERSELY IMPACT THE VAPOR TIGHT ENVIRONMENT OF THE PROJECT AREA. ENSURE THAT ALL DEVICES TO WHICH ELECTRICAL POWER IS FED ARE PROPERLY SEALED INSIDE AND WHERE ATTACHED TO WALL. 8. ALL RECEPTACLES AND SWITCH COVER PLATES SHALL BE LABELED WITH PANEL AND CIRCUIT IDENTIFICATIONS. ALL RECEPTACLES AND SWITCH COVER PLATES SHALL BE LABELED WITH PANEL AND CIRCUIT IDENTIFICATIONS. 9. ALL DATA AND PHONE JACKS MUST HAVE IDENTIFICATION LABELING ON THE COVER.ALL DATA AND PHONE JACKS MUST HAVE IDENTIFICATION LABELING ON THE COVER.
AutoCAD SHX Text
%%UNEW WORK GENERAL NOTES
AutoCAD SHX Text os
AutoCAD SHX Text A
AutoCAD SHX Text A
AutoCAD SHX Text 15cd
AutoCAD SHX Text V
AutoCAD SHX Text
AV
AutoCAD SHX Text 15cd
AutoCAD SHX Text 15cd
AutoCAD SHX Text D
AutoCAD SHX Text a
AutoCAD SHX Text D
AutoCAD SHX Text L
AutoCAD SHX Text
PP
AutoCAD SHX Text S
AutoCAD SHX Text V
AutoCAD SHX Text
KVA KW NEC NEMA NFPA NFSS OCP P RCP SWBD TR TRB UL UON V VA VFD W WP XFMR
AutoCAD SHX Text KILOVOLT AMPS KILOWATTS NATIONAL ELECTRICAL CODE NATIONAL ELECTRICAL MANUFACTURERS ASSOC NATIONAL FIRE PROTECTION ASSOCIATION NON FUSED SAFETY SWITCH OVER CURRENT PROTECTION POLE REFLECTED CEILING PLAN SWITCHBOARD TAMPER RESISTANT TERMINAL REHEAT BOX UNDERWRITERS LABORATORY UNLESS OTHERWISE NOTED VOLTS VOLT AMPS VARIABLE FREQUENCY DRIVE WATTS WEATHERPROOF TRANSFORMER
AutoCAD SHX Text
TV
AutoCAD SHX Text
KP
AutoCAD SHX Text S
AutoCAD SHX Text a
AutoCAD SHX Text L
AutoCAD SHX Text
DP
AutoCAD SHX Text
CR
AutoCAD SHX Text
CA
AutoCAD SHX Text
EPO
AutoCAD SHX Text D
95 WASHINGTON STREET, MORRISTOWN, NJ 07960
t. 973.539.5353
f. 973.539.0916
THE WOOLWORTH BUILDING
233 BROADWAY SUITE 2150, NEW YORK, NY 10279
t. 212.982.7900
f. 212.982.8111 www.nkarchitects.com
NK ARCHITECTS
STAMP
SIGNATURE:
Drawing Title
Approved: Project Director
Project Title
Issued Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. of
CONSULTANTS ARCHITECT/ENGINEER OF RECORD
NO. 1
on e ei gh th in ch o ne fo ot th re e in ch es o ne fo ot 6"
6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot
6" 6" th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r i nc h on e fo ot
VA FORM 08-6231
A
1 2 3 4 5 6 7 8 9 10
B
C
D
E
F
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9 10
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
FULLY SPRINKLERED
688-CSI-013
05/20/2025
NO: REVISION DESCRIPTION: DATE:
ART - ARCHITECTURE - ENGINEERING
2787 HILL ROAD
VIENNA, VA 22181
FRANK V. STURGEON, AIA
AMBRISH RASTOGI, PE
703.938.5226
FRANK@ADG10.COM
A DESIGN GROUP, LLC
35% SUBMISSION 01-30-2024
50 Irving St NW, Washington, DC 20422
4TH FLOOR CATH LAB
RENOVATION
AR
65% SUBMISSION 04-05-2024
95% SUBMISSION 05-31-20243
100% SUBMISSION 03-21-20254
ISSUED FOR CONSTRUCTION 05-20-20255
05/20/2025
EC101
PROPOSED WIRING AND CONDUITS
ROUTING PLANS
NN
1/8" = 1'-0"
PARTIAL BASEMENT PLAN1
NOT TO SCALE
KEY PLAN - BASEMENT LEVEL
1/8" = 1'-0"
PARTIAL 1ST FLOOR2
1/8" = 1'-0"
PARTIAL 2ND FLOOR3
1/8" = 1'-0"
PARTIAL 3RD FLOOR4
NOT TO SCALE
KEY PLAN - 1ST FLOOR
NOT TO SCALE
KEY PLAN - 2ND FLOOR
NOT TO SCALE
KEY PLAN - 3RD FLOOR
AutoCAD SHX Text
PHONE
AutoCAD SHX Text
EXAM RM
AutoCAD SHX Text 1E392A
AutoCAD SHX Text
CORRIDOR
AutoCAD SHX Text
WAITING AREA
AutoCAD SHX Text 1E392
AutoCAD SHX Text
EXAM RM
AutoCAD SHX Text 1E392B
AutoCAD SHX Text
EXAM RM
AutoCAD SHX Text 1E392D
AutoCAD SHX Text
EXAM RM
AutoCAD SHX Text 1E392C
AutoCAD SHX Text
EXAM RM
AutoCAD SHX Text 1E392E
AutoCAD SHX Text
EXAM RM
AutoCAD SHX Text 1E392F
AutoCAD SHX Text
WAITING AREA
AutoCAD SHX Text
EXAM RM
AutoCAD SHX Text 1E392H
AutoCAD SHX Text
EXAM RM
AutoCAD SHX Text 1E392I
AutoCAD SHX Text
WAITING AREA
AutoCAD SHX Text
EXAM RM
AutoCAD SHX Text 1E392G
AutoCAD SHX Text
EXAM RM
AutoCAD SHX Text 1E392J
AutoCAD SHX Text
EXAM RM
AutoCAD SHX Text
WAITING AREA
AutoCAD SHX Text 1E239
AutoCAD SHX Text Y
AutoCAD SHX Text
BB
AutoCAD SHX Text
CC
AutoCAD SHX Text
AutoCAD SHX Text
AA
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
PROVIDE CONDUITS SECURING AND SUPPORTS (TYPICAL)
AutoCAD SHX Text
CONDUIT RUN ON 1ST FLOOR ROOF.
AutoCAD SHX Text CONDUIT RUN ON BUILDING EXTERIOR WALL FROM 1ST FLOOR. PROVIDE PROVIDE CONDUITS SECURING AND SUPPORTS (TYPICAL)
AutoCAD SHX Text
MECH
AutoCAD SHX Text 2E136
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text Y
AutoCAD SHX Text X
AutoCAD SHX Text
CONDUIT RUN ON BUILDING EXTERIOR FROM 2ND FLOOR ROOF.
AutoCAD SHX Text CONDUIT RUN ON BUILDING EXTERIOR WALL FROM 1ST FLOOR. PROVIDE CONDUITS PROVIDE CONDUITS SECURING AND SUPPORTS (TYPICAL)
AutoCAD SHX Text
CONDUIT RUN ON 2ND FLOOR ROOF.
AutoCAD SHX Text
ROOF
AutoCAD SHX Text
AutoCAD SHX Text 18W
AutoCAD SHX Text
AutoCAD SHX Text
AA
AutoCAD SHX Text
CONFERENCE RM
AutoCAD SHX Text 3E112A
AutoCAD SHX Text Y
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text X
AutoCAD SHX Text
XS
AutoCAD SHX Text
XN
AutoCAD SHX Text
WA
AutoCAD SHX Text R
AutoCAD SHX Text
SA
AutoCAD SHX Text
UA
AutoCAD SHX Text
CONDUIT RUN ON BUILDING EXTERIOR FROM 2ND FLOOR ROOF.
AutoCAD SHX Text CONDUIT RUN ON 3RD FLOOR ROOF BUILDING EXTERIOR. PROVIDE CONDUITS SECURING AND SUPPORTS (TYPICAL)
AutoCAD SHX Text
CONDUIT RUN ON BUILDING EXTERIOR FROM 3RD FLOOR ROOF.
AutoCAD SHX Text
UP
AutoCAD SHX Text
RAMP DN
AutoCAD SHX Text
TO SUB-BASEMENT
AutoCAD SHX Text
DN
AutoCAD SHX Text
CORRIDOR
AutoCAD SHX Text
STORAGE
AutoCAD SHX Text
GE261
AutoCAD SHX Text
TRANSFORMER RM
AutoCAD SHX Text
GE263
AutoCAD SHX Text
STAIR
AutoCAD SHX Text
(E) SWITCHBOARD "E4" 2000A, 480Y/277V, 3-PHASE, 4 WIRE
AutoCAD SHX Text
UA
AutoCAD SHX Text
WA
AutoCAD SHX Text X
AutoCAD SHX Text
AA
AutoCAD SHX Text Y
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
PROVIDE CONDUITS SECURING AND SUPPORTS (TYPICAL)
AutoCAD SHX Text WIRING AND CONDUITS WILL EXIT ELECTRICAL ROOM ABOVE ROLL-UP DOOR, RUN PARALLEL WITH EXISTING CONDUIT SERVING "OR". SEE POWER SEE POWER DIAGRAM ON DRAWING ER101 FOR CONNECTIONS
AutoCAD SHX Text
(E) PANEL "EMB"
AutoCAD SHX Text
(E) PANEL "EMA"
AutoCAD SHX Text
(E) SWITCHBOARD "E1" 2000A, 480Y/277V, 3-PHASE, 4 WIRE
AutoCAD SHX Text 4 #600 kCMIL + 1 #2 GROUND IN 4" CONDUIT
AutoCAD SHX Text
2 #8 AWG + 1 #10 GROUND IN 1" CONDUIT
AutoCAD SHX Text
2 #8 AWG + 1 #10 GROUND IN 1" CONDUIT
AutoCAD SHX Text
BLDG. 6
AutoCAD SHX Text
BLDG. 1
AutoCAD SHX Text
BLDG. 4
AutoCAD SHX Text
ENGINEERED
AutoCAD SHX Text
PRE-
AutoCAD SHX Text N
AutoCAD SHX Text N
AutoCAD SHX Text
BLDG. 6
AutoCAD SHX Text
BLDG. 1
AutoCAD SHX Text
BLDG. 4
AutoCAD SHX Text
BLDG 6
AutoCAD SHX Text
BLDG 1
AutoCAD SHX Text
BLDG 4
AutoCAD SHX Text N
AutoCAD SHX Text
BLDG. 1
AutoCAD SHX Text
BLDG. 6
AutoCAD SHX Text N
AutoCAD SHX Text
ROOF
AutoCAD SHX Text
ROOF
AutoCAD SHX Text
AREA OF WORK
AutoCAD SHX Text
AREA OF WORK
AutoCAD SHX Text
AREA OF WORK
AutoCAD SHX Text
AREA OF WORK
NOTES: a. PROVIDE ROOF TOP CONDUIT BLOCK AND SUPPORT, 3 FEET AT THE PROVIDE ROOF TOP CONDUIT BLOCK AND SUPPORT, 3 FEET AT THE CONDUIT TERMINATION POINT, AND 10 FEET MAXIMUM BETWEEN THE CONDUIT SUPPORT. (TYPICAL) b. PROVIDE GALVANIZE RIGID STEEL (GRS) CONDUIT AS SHOWN ON PROVIDE GALVANIZE RIGID STEEL (GRS) CONDUIT AS SHOWN ON THIS DRAWING UNLESS OTHERWISE INDICATED (TYPICAL).
13.5A14A15A1617E 11.5A12.5A
AHU
MECHANICAL EQUIPMENT ROOM-3
AHU
COOLING
TOWER
ELEVATOR ROOM
EXTERIOR
STAIR #6
ROOF
EXTERIOR
EXTERIOR
EXTERIOR
EXTERIOR
95 WASHINGTON STREET, MORRISTOWN, NJ 07960
t. 973.539.5353
f. 973.539.0916
THE WOOLWORTH BUILDING
233 BROADWAY SUITE 2150, NEW YORK, NY 10279
t. 212.982.7900
f. 212.982.8111 www.nkarchitects.com
NK ARCHITECTS
STAMP
SIGNATURE:
Drawing Title
Approved: Project Director
Project Title
Issued Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. of
CONSULTANTS ARCHITECT/ENGINEER OF RECORD
NO. 1
on e ei gh th in ch o ne fo ot th re e in ch es o ne fo ot 6"
6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot
6" 6" th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r i nc h on e fo ot
VA FORM 08-6231
A
1 2 3 4 5 6 7 8 9 10
B
C
D
E
F
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9 10
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
FULLY SPRINKLERED
688-CSI-013
05/20/2025
NO: REVISION DESCRIPTION: DATE:
ART - ARCHITECTURE - ENGINEERING
2787 HILL ROAD
VIENNA, VA 22181
FRANK V. STURGEON, AIA
AMBRISH RASTOGI, PE
703.938.5226
FRANK@ADG10.COM
A DESIGN GROUP, LLC
35% SUBMISSION 01-30-2024
50 Irving St NW, Washington, DC 20422
4TH FLOOR CATH LAB
RENOVATION
AR
65% SUBMISSION 04-05-2024
95% SUBMISSION 05-31-20243
100% SUBMISSION 03-21-20254
ISSUED FOR CONSTRUCTION 05-20-20255
05/20/2025
EC102
PROPOSED WIRING AND CONDUITS
ROUTING - PENTHOUSE PLAN
NN
ROOF
AHU
MECHANICAL EQUIPMENT ROOM-3
AHU
COOLING
TOWER
ELEVATOR ROOM
EXTERIOR
STAIR #6
ROOF
EXTERIOR
EXTERIOR
EXTERIOR
EXTERIOR
NOT TO SCALE
KEY PLAN - PENTHOUSE FLOOR
1/8" = 1'-0"
PARTIAL PENTHOUSE PLAN1
AutoCAD SHX Text V
AutoCAD SHX Text U
AutoCAD SHX Text
SC
AutoCAD SHX Text R
AutoCAD SHX Text L
AutoCAD SHX Text N
AutoCAD SHX Text Q
AutoCAD SHX Text W
AutoCAD SHX Text
CONDUIT RUN ON BUILDING EXTERIOR FROM 3RD FLOOR ROOF.
AutoCAD SHX Text
CONDUIT WILL PENETRATE METAL SCREEN WALL ON ROOF
AutoCAD SHX Text
CONDUIT RUN AT 4TH FLOOR ROOF AREA.
AutoCAD SHX Text CONDUIT SHALL PENETRATE WALL INTO MECHANICAL ROOM IN PENTHOUSE WHERE PANELS "ELH-CATH-EQ", "CATH-A", "CATH-B" AND TRANSFORMER ARE LOCATED
AutoCAD SHX Text
PROPOSED (N) PANEL "ELH-CATH-EQ"
AutoCAD SHX Text T
AutoCAD SHX Text
UNISTRUT CHANNEL MOUNTED EXISTING CONCRETE PAD
AutoCAD SHX Text
EXISTING CONCRETE PAD
AutoCAD SHX Text
ROOF HATCH
AutoCAD SHX Text PROPOSED CONDUITS TURN/RUN DOWN ON WALL CORE DRILL FLOOR SLAB INTO CATH LAB SPACE BELOW FOR CONNECTION TO PANELS "CATH-IPS1", "CATH-IPS2", "CATH-IPS3" AND "EUL-CATH-CR". COORDINATE WITH COR AND BUILDING ENGINEER, PERFORM X-RAY AND SCAN.
AutoCAD SHX Text N
AutoCAD SHX Text
AREA OF WORK
NOTES: a. PROVIDE ROOF TOP CONDUIT BLOCK AND SUPPORT, 3 FEET AT THE PROVIDE ROOF TOP CONDUIT BLOCK AND SUPPORT, 3 FEET AT THE CONDUIT TERMINATION POINT, AND 10 FEET MAXIMUM BETWEEN THE CONDUIT SUPPORT. (TYPICAL) b. PROVIDE GALVANIZE RIGID STEEL (GRS) CONDUIT AS SHOWN ON PROVIDE GALVANIZE RIGID STEEL (GRS) CONDUIT AS SHOWN ON THIS DRAWING UNLESS OTHERWISE INDICATED (TYPICAL).
15A 14A 13A
N
Q
R
NOT TO SCALE
ROOF
AHU
MECHANICAL EQUIPMENT ROOM-3
AHU
COOLING
TOWER
ELEVATOR ROOM
EXTERIOR
STAIR #6
ROOF
EXTERIOR
EXTERIOR
EXTERIOR
EXTERIOR
NOT TO SCALE
KEY PLAN-MECHANICAL ROOM AND LOWER ROOF
GENERAL NOTES - DEMOLITION PLAN
KEYED NOTES - DEMOLITION PLAN
M
M
1/4" = 1'-0"
PARTIAL EQUIPMENT - DEMOLITION
1/4" = 1'-0"
PARTIAL FLOOR PLAN - DEMOLITION3
CLEAN UTILITY
4A120
CORRIDOR
4A117
HAC
4A126
BREAK RM
MISCELLANEOUS
4A129B
FOYER
4A129D
PULM
PHYSIOLOGY
LAB WAITING
4A129
STRESS LAB
4A128
CATH LAB
CONTROL
CORRIDOR
4A119A
CATH LAB
OPERATING
ROOM
4A124
LAB
4A129A
NOT TO SCALE
ELECTRICAL RISER DIAGRAM - DEMOLITION5
MECHANICAL EQUIPMENT ROOM-3
AHU
COOLING
TOWER
ELEVATOR ROOM
STAIR #6
ROOF
XTERIOR
1/8" = 1'-0"
PARTIAL PENTHOUSE MECHANICAL ROOM - DEMOLITION1
1/8" = 1'-0"
PARTIAL ROOF PLAN - DEMOLITION2
NN 61
95 WASHINGTON STREET, MORRISTOWN, NJ 07960
t. 973.539.5353
f. 973.539.0916
THE WOOLWORTH BUILDING
233 BROADWAY SUITE 2150, NEW YORK, NY 10279
t. 212.982.7900
f. 212.982.8111 www.nkarchitects.com
NK ARCHITECTS
STAMP
SIGNATURE:
Drawing Title
Approved: Project Director
Project Title
Issued Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. of
CONSULTANTS ARCHITECT/ENGINEER OF RECORD
NO. 1
on e ei gh th in ch o ne fo ot th re e in ch es o ne fo ot 6"
6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot
6" 6" th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r i nc h on e fo ot
VA FORM 08-6231
A
1 2 3 4 5 6 7 8 9 10
B
C
D
E
F
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9 10
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
FULLY SPRINKLERED
688-CSI-013
05/20/2025
NO: REVISION DESCRIPTION: DATE:
ART - ARCHITECTURE - ENGINEERING
2787 HILL ROAD
VIENNA, VA 22181
FRANK V. STURGEON, AIA
AMBRISH RASTOGI, PE
703.938.5226
FRANK@ADG10.COM
A DESIGN GROUP, LLC
35% SUBMISSION 01-30-2024
50 Irving St NW, Washington, DC 20422
4TH FLOOR CATH LAB
RENOVATION
AR
NOT TO SCALE
KEY PLAN - 4TH FLOOR
KEY PLAN - UPPER ROOF
FEC
FEC
FE
C
FEC
65% SUBMISSION 04-05-2024
95% SUBMISSION 05-31-20243
100% SUBMISSION 03-21-20254
ISSUED FOR CONSTRUCTION 05-20-20255
05/20/2025
ED101
ELECTRICAL DEMOLITION PLAN
AutoCAD SHX Text N
AutoCAD SHX Text
AREA/SCOPE OF WORK
AutoCAD SHX Text N
AutoCAD SHX Text
AREA/SCOPE OF WORK
AutoCAD SHX Text
LOWER ROOF
AutoCAD SHX Text
LOWER ROOF
AutoCAD SHX Text
LOWER ROOF
AutoCAD SHX Text
LOWER ROOF
AutoCAD SHX Text
LOWER ROOF
AutoCAD SHX Text
LOWER ROOF
AutoCAD SHX Text
LOWER ROOF
AutoCAD SHX Text
LOWER ROOF
AutoCAD SHX Text
UPPER ROOF
AutoCAD SHX Text
MECHANICAL EQUIPMENT ROOM-3
AutoCAD SHX Text DISCONNECT AND REMOVE ALL (NOT SHOWN) EMERGENCY LIGHTING FIXTURES AND EXIT SIGNS IN THE AREA OF WORK REMOVE CIRCUITRY FROM DEVICE LOCATION BACK TO THE NEXT ACTIVE OUTLET OR BACK TO THE PANELBOARD IF CIRCUIT IS NO LONGER ACTIVE. AT THE PANELBOARD, TURN CIRCUIT BREAKER(S) TO THE OFF POSITION AND LABEL AS "SPARE". RESTORE CONNECTION TO EXISTING DEVICES FOR OPERATION AS BEFORE IF INTERRUPTED BY DEMOLITION. DISCONNECT AND REMOVE ALL (NOT SHOWN) FIRE ALARM DEVICES IN THE AREA OF WORK UNLESS OTHERWISE NOTED. SAFELY TERMINATE THE FIRE ALARM CIRCUITRY ABOVE THE CEILING FOR REUSE. COORDINATE REMOVAL OF FIRE ALARM DEVICES AND CABLING WITH COR AND BUILDING ENGINEERS BEFORE PROCEEDING WITH DEMOLITION. DISCONNECT AND REMOVE ALL (NOT SHOWN) RECEPTACLES, WIRE TROUGHS AND PULL BOXES IN THE AREA OF WORK UNLESS OTHERWISE NOTED. REMOVE CIRCUITRY FROM DEVICE LOCATION BACK TO THE NEXT ACTIVE OUTLET OR BACK TO THE PANELBOARD IF CIRCUIT IS NO LONGER ACTIVE. AT THE PANELBOARD, TURN CIRCUIT BREAKER(S) TO THE OFF POSITION AND LABEL AS "SPARE". RESTORE TURN CIRCUIT BREAKER(S) TO THE OFF POSITION AND LABEL AS "SPARE". RESTORE CONNECTION TO EXISTING DEVICES FOR OPERATION AS BEFORE IF INTERRUPTED BY DEMOLITION. DISCONNECT AND REMOVE ALL (NOT SHOWN) TELEPHONE/DATA OUTLETS, WIFI ROUTER, SPEAKERS AND SECURITY DEVICES IN THE AREA OF WORK UNLESS OTHERWISE NOTED. COORDINATE WITH COR, IT MANAGER BEFORE REMOVAL OF TELEPHONE/DATA CABLING AND SECURITY NETWORKING PRIOR TO DISCONNECT OR DEMO ANY SECURITY DEVICES AND WIRING. DISCONNECT AND REMOVE ALL (NOT SHOWN) LIGHT FIXTURES IN THE AREA OF WORK UNLESS OTHERWISE NOTED. REMOVE CIRCUITRY FROM DEVICE LOCATION BACK TO THE NEXT ACTIVE OUTLET OR BACK TO THE PANELBOARD IF CIRCUIT IS NO LONGER ACTIVE. AT THE PANELBOARD, TURN CIRCUIT BREAKER(S) TO THE OFF POSITION AND LABEL AS "SPARE". RESTORE CONNECTION TO EXISTING DEVICES FOR OPERATION AS BEFORE IF INTERRUPTED BY DEMOLITION. DISCONNECT AND REMOVE EXISTING EXHAUST FAN (EF) WITH ASSOCIATED WIRING, CONDUIT AND CONTROL BACK TO THE NEXT ACTIVE OUTLET OR BACK TO THE PANELBOARD.
This is the start of the file's text. The full file is on GovTribe.