C05__ATTACHMENT_3_INSPECTION-TESTING_LIST.PDF

PDF 277 KB Posted

Attached to
NCAO Fire Alarm Maintenance Services Federal contract opportunity
Solicitation number
140R2022Q0003
Issued by
Department of the Interior Bureau of Reclamation

About this file

This attachment provides the inspection and testing requirements for fire alarm systems at multiple Bureau of Reclamation locations within the Northern California Area Office. Systems covered include those at Shasta Powerplant, Shasta Dam, Shasta Maintenance Center, Upper Vista House, Keswick Powerplant, Keswick Office Building, Spring Creek Powerplant, J.F. Carr Powerplant, Lewiston Powerplant, Trinity Powerplant, and other sites. Inspection and testing requirements are specified for various system components including control equipment, batteries, notification appliances, initiating devices, and more. Required actions, reference standards, and frequencies are delineated for each location and component. This document supports solicitation number 140R2022Q0003, in which the Bureau of Reclamation is seeking fire alarm maintenance services at the ten locations listed to perform inspection, testing, repair, and documentation activities.

View the file

Other files for this federal contract opportunity

Other files attached to NCAO Fire Alarm Maintenance Services, newest first.
File Type Posted
Sol_140R2022Q0003_Amd_0001.pdf PDF
C05__ATTACHMENT_2_MAJOR_FIRE_ALARM_SYSTEM_COMPONENTS.PDF PDF
C05__ATTACHMENT_5_WAGE_DETERMINATION_2015-5627_REV_13_10-20-2021.pdf PDF
C05__ATTACHMENT_4_RSHS_APPENDIX_B_CONTRACTOR_SAFETY_PROGRAM.pdf PDF
Sol_140R2022Q0003.pdf PDF
C05__ATTACHMENT_1_FIRE_ALARM_REPORTING_DIAGRAM.PDF PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Location Component Quantity Maintenance Action Reference/Method Freqency Shasta Powerplant All Equipment Inspect NFPA 72, Table 14.3.1, line 1 Annually Shasta Powerplant Control Equipment 1 Inspect NFPA 72, Table 14.3.1, line 2 (1) (a, b, c, d) Annually Shasta Powerplant Control Equipment 1 Inspect NFPA 72, Table 14.3.1, line 2 (1) (e) Semiannually Shasta Powerplant Control Equipment and Transponder 1 Test NFPA 72, Table 14.4.3.2, line 2 (1) (2) (3) (4) (5) Annually Shasta Powerplant Alarm Control Unit Trouble Signals 1 Test NFPA 72, Table 14.4.3.2, line 3 (1) (2) (3) (4) Annually Shasta Powerplant Digital Alarm Communication Transmitter (DACT) 1 Inspect NFPA 72, Table 14.3.1, line 4 (1) Annually Shasta Powerplant Digital Alarm Communication Transmitter (DACT) 1 Test NFPA 72, Table 14.4.3.2, line 4 (1) (2) Annually Shasta Powerplant Batteries 10 Inspect NFPA 72, Table 14.3.1, line 9 Semiannually Shasta Powerplant Secondary (standby) Power Supply 1 Test NFPA 72, Table 14.4.3.2, line 8 Annually Shasta Powerplant 30‐sec Backup Battery Power Function Test 1 Test FIST 4‐1, Section 18.2, row 3 Monthly Shasta Powerplant Batteries, all types within fire det & alarm sys 10 Inspect FIST 4‐1, Section 18.2, row 5 Annually Shasta Powerplant 90‐min Battery Discharge Test 1 Test FIST 4‐1, Section 18.2, row 6 Annually Shasta Powerplant Remote Annunciator 1 Inspect NFPA 72, Table 14.3.1, line 11 Semiannually Shasta Powerplant Remote Annunciator 1 Test NFPA 72, Table 14.4.3.2, line 11 Annually Shasta Powerplant Conductors ‐ circuit integrity 1 Test NFPA 72, Table 14.4.3.2, line 15 Annually Shasta Powerplant Initiating Device ‐ Manual Pull Stations 24 Inspect NFPA 72, Table 14.3.1, line 17 (5) Semiannually Shasta Powerplant Initiating Device ‐ Manual Pull Stations 24 Test NFPA 72, Table 14.4.3.2, line 17 (5) Annually Shasta Powerplant Initiating Device ‐ Heat Detectors 3 Inspect NFPA 72, Table 14.3.1, line 17 (6) (9) Semiannually Shasta Powerplant Initiating Device ‐ Heat Detectors 3 Test NFPA 72, Table 14.4.3.2, line 17 (12) Annually Shasta Powerplant Initiating Device ‐ Smoke Detectors 67 Inspect NFPA 72, Table 14.3.1, line 17 (9) Semiannually Shasta Powerplant Initiating Device ‐ Smoke Detectors 67 Test NFPA 72, Table 14.4.3.2, line 17 (7)(a) Annually Shasta Powerplant Initiating Device ‐ Projected Beam Detectors 3 Inspect NFPA 72, Table 14.3.1, line 17 (10) Semiannually Shasta Powerplant Initiating Device ‐ Projected Beam Detectors 3 Test NFPA 72, Table 14.4.3.2, line 17 (7) (f) Annually Shasta Powerplant Initiating Device ‐ Duct Detectors 12 Inspect NFPA 72, Table 14.3.1, line 17 (2)(a) Semiannually Shasta Powerplant Initiating Device ‐ Duct Detectors 12 Inspect NFPA 72, Table 14.3.1, line 17 (2)(b) Annually Shasta Powerplant Initiating Device ‐ Duct Detectors 12 Test NFPA 72, Table 14.4.3.2, line 17 (7)(e) Annually Shasta Powerplant Notification Appliances (strobe & horn/strobe) 95 Inspect NFPA 72, Table 14.3.1, line 22 (1) (3) Semiannually Shasta Powerplant Alarm Notification Appliances (strobe & horn/strobe) 95 Test NFPA 72, Table 14.4.3.2, line 22 (1) (3) Annually Shasta Powerplant Supervising Station Alarm System ‐ Receiver 1 Inspect NFPA 72, Table 14.3.1, line 27 (2) Annually Shasta Powerplant Supervising Station Alarm System ‐ Receiver 1 Test NFPA 72, Table 14.4.3.2, line 27 (1) (2) Monthly Shasta Dam All Equipment Inspect NFPA 72, Table 14.3.1, line 1 Annually Shasta Dam Control Equipment 1 Inspect NFPA 72, Table 14.3.1, line 2 (1) (a, b, c, d) Annually Shasta Dam Control Equipment 1 Inspect NFPA 72, Table 14.3.1, line 2 (1) (e) Semiannually Shasta Dam Control Equipment and Transponder 1 Test NFPA 72, Table 14.4.3.2, line 2 (1) (2) (3) (4) (5) Annually Shasta Dam Alarm Control Unit Trouble Signals 1 Test NFPA 72, Table 14.4.3.2, line 3 (1) (2) (3) (4) Annually Shasta Dam Digital Alarm Communication Transmitter (DACT) 1 Inspect NFPA 72, Table 14.3.1, line 4 (1) Annually Shasta Dam Digital Alarm Communication Transmitter (DACT) 1 Test NFPA 72, Table 14.4.3.2, line 4 (1) (2) Annually Shasta Dam Batteries 2 Inspect NFPA 72, Table 14.3.1, line 9 Semiannually Shasta Dam Secondary (standby) Power Supply 1 Test NFPA 72, Table 14.4.3.2, line 8 Annually Shasta Dam Remote Annunciator 1 Inspect NFPA 72, Table 14.3.1, line 11 Semiannually Shasta Dam Remote Annunciator 1 Test NFPA 72, Table 14.4.3.2, line 11 Annually Shasta Dam Conductors ‐ circuit integrity 1 Test NFPA 72, Table 14.4.3.2, line 15 Annually Shasta Dam Initiating Device ‐ Manual Pull Stations 14 Inspect NFPA 72, Table 14.3.1, line 17 (5) Semiannually Shasta Dam Initiating Device ‐ Manual Pull Stations 14 Test NFPA 72, Table 14.4.3.2, line 17 (5) Annually Shasta Dam Initiating Device ‐ Smoke Detectors 27 Inspect NFPA 72, Table 14.3.1, line 17 (9) Semiannually Shasta Dam Initiating Device ‐ Smoke Detectors 27 Test NFPA 72, Table 14.4.3.2, line 17 (7)(a) Annually Shasta Dam Notification Appliances (strobe & horn/strobe) 22 Inspect NFPA 72, Table 14.3.1, line 22 (1) (3) Semiannually

Attachment 3: Inspection & Testing Requirements

Shasta Dam Alarm Notification Appliances (strobe & horn/strobe) 22 Test NFPA 72, Table 14.4.3.2, line 22 (1) (3) Annually Shasta Maintenance Center All Equipment Inspect NFPA 72, Table 14.3.1, line 1 Annually Shasta Maintenance Center Control Equipment 1 Inspect NFPA 72, Table 14.3.1, line 2 (1) (a, b, c, d) Annually Shasta Maintenance Center Control Equipment 1 Inspect NFPA 72, Table 14.3.1, line 2 (1) (e) Semiannually Shasta Maintenance Center Control Equipment and Transponder 1 Test NFPA 72, Table 14.4.3.2, line 2 (1) (2) (3) (4) (5) Annually Shasta Maintenance Center Alarm Control Unit Trouble Signals 1 Test NFPA 72, Table 14.4.3.2, line 3 (1) (2) (3) (4) Annually Shasta Maintenance Center Digital Alarm Communication Transmitter (DACT) 1 Inspect NFPA 72, Table 14.3.1, line 4 (1) Annually Shasta Maintenance Center Digital Alarm Communication Transmitter (DACT) 1 Test NFPA 72, Table 14.4.3.2, line 4 (1) (2) Annually Shasta Maintenance Center Batteries 2 Inspect NFPA 72, Table 14.3.1, line 9 Semiannually Shasta Maintenance Center Secondary (standby) Power Supply 1 Test NFPA 72, Table 14.4.3.2, line 8 Annually Shasta Maintenance Center Remote Annunciator 1 Inspect NFPA 72, Table 14.3.1, line 11 Semiannually Shasta Maintenance Center Remote Annunciator 1 Test NFPA 72, Table 14.4.3.2, line 11 Annually Shasta Maintenance Center Conductors ‐ circuit integrity 1 Test NFPA 72, Table 14.4.3.2, line 15 Annually Shasta Maintenance Center Initiating Device ‐ Manual Pull Stations 10 Inspect NFPA 72, Table 14.3.1, line 17 (5) Semiannually Shasta Maintenance Center Initiating Device ‐ Manual Pull Stations 10 Test NFPA 72, Table 14.4.3.2, line 17 (5) Annually Shasta Maintenance Center Initiating Device ‐ Heat Detectors 8 Inspect NFPA 72, Table 14.3.1, line 17 (6) Semiannually Shasta Maintenance Center Initiating Device ‐ Heat Detectors 8 Test NFPA 72, Table 14.4.3.2, line 17 (4)(a) Annually Shasta Maintenance Center Initiating Device ‐ Smoke Detectors 41 Inspect NFPA 72, Table 14.3.1, line 17 (9) Semiannually Shasta Maintenance Center Initiating Device ‐ Smoke Detectors 41 Test NFPA 72, Table 14.4.3.2, line 17 (7)(a) Annually Shasta Maintenance Center Initiating Device ‐ Projected Beam Detectors 2 Inspect NFPA 72, Table 14.3.1, line 17 (10) Semiannually Shasta Maintenance Center Initiating Device ‐ Projected Beam Detectors 2 Test NFPA 72, Table 14.4.3.2, line 17 (7) (f) Annually Shasta Maintenance Center Notification Appliances (strobe & horn/strobe) 32 Inspect NFPA 72, Table 14.3.1, line 22 (1) (3) Semiannually Shasta Maintenance Center Alarm Notification Appliances (strobe & horn/strobe) 32 Test NFPA 72, Table 14.4.3.2, line 22 (1) (3) Annually Upper Vista House All Equipment Inspect NFPA 72, Table 14.3.1, line 1 Annually Upper Vista House Control Equipment 1 Inspect NFPA 72, Table 14.3.1, line 2 (1) (a, b, c, d) Annually Upper Vista House Control Equipment 1 Inspect NFPA 72, Table 14.3.1, line 2 (1) (e) Semiannually Upper Vista House Control Equipment and Transponder 1 Test NFPA 72, Table 14.4.3.2, line 2 (1) (2) (3) (4) (5) Annually Upper Vista House Alarm Control Unit Trouble Signals 1 Test NFPA 72, Table 14.4.3.2, line 3 (1) (2) (3) (4) Annually Upper Vista House Digital Alarm Communication Transmitter (DACT) 1 Inspect NFPA 72, Table 14.3.1, line 4 (1) Annually Upper Vista House Digital Alarm Communication Transmitter (DACT) 1 Test NFPA 72, Table 14.4.3.2, line 4 (1) (2) Annually Upper Vista House Batteries 2 Inspect NFPA 72, Table 14.3.1, line 9 Semiannually Upper Vista House Secondary (standby) Power Supply 1 Test NFPA 72, Table 14.4.3.2, line 8 Annually Upper Vista House Remote Annunciator 1 Inspect NFPA 72, Table 14.3.1, line 11 Semiannually Upper Vista House Remote Annunciator 1 Test NFPA 72, Table 14.4.3.2, line 11 Annually Upper Vista House Conductors ‐ circuit integrity 1 Test NFPA 72, Table 14.4.3.2, line 15 Annually Upper Vista House Initiating Device ‐ Manual Pull Stations 8 Inspect NFPA 72, Table 14.3.1, line 17 (5) Semiannually Upper Vista House Initiating Device ‐ Manual Pull Stations 8 Test NFPA 72, Table 14.4.3.2, line 17 (5) Annually Upper Vista House Initiating Device ‐ Heat Detectors 2 Inspect NFPA 72, Table 14.3.1, line 17 (6) Semiannually Upper Vista House Initiating Device ‐ Heat Detectors 2 Test NFPA 72, Table 14.4.3.2, line 17 (4)(a) Annually Upper Vista House Initiating Device ‐ Smoke Detectors 51 Inspect NFPA 72, Table 14.3.1, line 17 (9) Semiannually Upper Vista House Initiating Device ‐ Smoke Detectors 51 Test NFPA 72, Table 14.4.3.2, line 17 (7)(a) Annually Upper Vista House Initiating Device ‐ Duct Detectors 6 Inspect NFPA 72, Table 14.3.1, line 17 (2)(a) Semiannually Upper Vista House Initiating Device ‐ Duct Detectors 6 Inspect NFPA 72, Table 14.3.1, line 17 (2)(b) Annually Upper Vista House Initiating Device ‐ Duct Detectors 6 Test NFPA 72, Table 14.4.3.2, line 17 (7)(e) Annually Upper Vista House Notification Appliances (strobe & horn/strobe) 28 Inspect NFPA 72, Table 14.3.1, line 22 (1) (3) Semiannually Upper Vista House Alarm Notification Appliances (strobe & horn/strobe) 28 Test NFPA 72, Table 14.4.3.2, line 22 (1) (3) Annually Keswick Powerplant All Equipment Inspect NFPA 72, Table 14.3.1, line 1 Annually

Keswick Powerplant Control Equipment 1 Inspect NFPA 72, Table 14.3.1, line 2 (1) (a, b, c, d) Annually Keswick Powerplant Control Equipment 1 Inspect NFPA 72, Table 14.3.1, line 2 (1) (e) Semiannually Keswick Powerplant Control Equipment and Transponder 1 Test NFPA 72, Table 14.4.3.2, line 2 (1) (2) (3) (4) (5) Annually Keswick Powerplant Alarm Control Unit Trouble Signals 1 Test NFPA 72, Table 14.4.3.2, line 3 (1) (2) (3) (4) Annually Keswick Powerplant Digital Alarm Communication Transmitter (DACT) 1 Inspect NFPA 72, Table 14.3.1, line 4 (1) Annually Keswick Powerplant Digital Alarm Communication Transmitter (DACT) 1 Test NFPA 72, Table 14.4.3.2, line 4 (1) (2) Annually Keswick Powerplant Batteries 8 Inspect NFPA 72, Table 14.3.1, line 9 Semiannually Keswick Powerplant Secondary (standby) Power Supply 1 Test NFPA 72, Table 14.4.3.2, line 8 Annually Keswick Powerplant 30‐sec Backup Battery Power Function Test 1 Test FIST 4‐1, Section 18.2, row 3 Monthly Keswick Powerplant Batteries, all types within fire det & alarm sys 8 Inspect FIST 4‐1, Section 18.2, row 5 Annually Keswick Powerplant 90‐min Battery Discharge Test 1 Test FIST 4‐1, Section 18.2, row 6 Annually Keswick Powerplant Remote Annunciator 1 Inspect NFPA 72, Table 14.3.1, line 11 Semiannually Keswick Powerplant Remote Annunciator 1 Test NFPA 72, Table 14.4.3.2, line 11 Annually Keswick Powerplant Conductors ‐ circuit integrity 1 Test NFPA 72, Table 14.4.3.2, line 15 Annually Keswick Powerplant Initiating Device ‐ Manual Pull Stations 17 Inspect NFPA 72, Table 14.3.1, line 17 (5) Semiannually Keswick Powerplant Initiating Device ‐ Manual Pull Stations 17 Test NFPA 72, Table 14.4.3.2, line 17 (5) Annually Keswick Powerplant Initiating Device ‐ Heat Detectors 1 Inspect NFPA 72, Table 14.3.1, line 17 (6) (9) Semiannually Keswick Powerplant Initiating Device ‐ Heat Detectors 1 Test NFPA 72, Table 14.4.3.2, line 17 (12) Annually Keswick Powerplant Initiating Device ‐ Smoke Detectors 60 Inspect NFPA 72, Table 14.3.1, line 17 (9) Semiannually Keswick Powerplant Initiating Device ‐ Smoke Detectors 60 Test NFPA 72, Table 14.4.3.2, line 17 (7)(a) Annually Keswick Powerplant Initiating Device ‐ Projected Beam Detectors 3 Inspect NFPA 72, Table 14.3.1, line 17 (10) Semiannually Keswick Powerplant Initiating Device ‐ Projected Beam Detectors 3 Test NFPA 72, Table 14.4.3.2, line 17 (7) (f) Annually Keswick Powerplant Initiating Device ‐ Duct Detectors 10 Inspect NFPA 72, Table 14.3.1, line 17 (2)(a) Semiannually Keswick Powerplant Initiating Device ‐ Duct Detectors 10 Inspect NFPA 72, Table 14.3.1, line 17 (2)(b) Annually Keswick Powerplant Initiating Device ‐ Duct Detectors 10 Test NFPA 72, Table 14.4.3.2, line 17 (7)(e) Annually Keswick Powerplant Notification Appliances (strobe & horn/strobe) 57 Inspect NFPA 72, Table 14.3.1, line 22 (1) (3) Semiannually Keswick Powerplant Alarm Notification Appliances (strobe & horn/strobe) 57 Test NFPA 72, Table 14.4.3.2, line 22 (1) (3) Annually Keswick Office Building All Equipment Inspect NFPA 72, Table 14.3.1, line 1 Annually Keswick Office Building Control Equipment 1 Inspect NFPA 72, Table 14.3.1, line 2 (1) (a, b, c, d) Annually Keswick Office Building Control Equipment 1 Inspect NFPA 72, Table 14.3.1, line 2 (1) (e) Semiannually Keswick Office Building Control Equipment and Transponder 1 Test NFPA 72, Table 14.4.3.2, line 2 (1) (2) (3) (4) (5) Annually Keswick Office Building Alarm Control Unit Trouble Signals 1 Test NFPA 72, Table 14.4.3.2, line 3 (1) (2) (3) (4) Annually Keswick Office Building Digital Alarm Communication Transmitter (DACT) 1 Inspect NFPA 72, Table 14.3.1, line 4 (1) Annually Keswick Office Building Digital Alarm Communication Transmitter (DACT) 1 Test NFPA 72, Table 14.4.3.2, line 4 (1) (2) Annually Keswick Office Building Batteries 1 Inspect NFPA 72, Table 14.3.1, line 9 Semiannually Keswick Office Building Secondary (standby) Power Supply 1 Test NFPA 72, Table 14.4.3.2, line 8 Annually Keswick Office Building Remote Annunciator 1 Inspect NFPA 72, Table 14.3.1, line 11 Semiannually Keswick Office Building Remote Annunciator 1 Test NFPA 72, Table 14.4.3.2, line 11 Annually Keswick Office Building Conductors ‐ circuit integrity 1 Test NFPA 72, Table 14.4.3.2, line 15 Annually Keswick Office Building Initiating Device ‐ Manual Pull Stations 8 Inspect NFPA 72, Table 14.3.1, line 17 (5) Semiannually Keswick Office Building Initiating Device ‐ Manual Pull Stations 8 Test NFPA 72, Table 14.4.3.2, line 17 (5) Annually Keswick Office Building Initiating Device ‐ Heat Detectors 2 Inspect NFPA 72, Table 14.3.1, line 17 (6) Semiannually Keswick Office Building Initiating Device ‐ Heat Detectors 2 Test NFPA 72, Table 14.4.3.2, line 17 (4)(a) Annually Keswick Office Building Initiating Device ‐ Smoke Detectors 51 Inspect NFPA 72, Table 14.3.1, line 17 (9) Semiannually Keswick Office Building Initiating Device ‐ Smoke Detectors 51 Test NFPA 72, Table 14.4.3.2, line 17 (7)(a) Annually Keswick Office Building Initiating Device ‐ Duct Detectors 6 Inspect NFPA 72, Table 14.3.1, line 17 (2)(a) Semiannually Keswick Office Building Initiating Device ‐ Duct Detectors 6 Inspect NFPA 72, Table 14.3.1, line 17 (2)(b) Annually

Keswick Office Building Initiating Device ‐ Duct Detectors 6 Test NFPA 72, Table 14.4.3.2, line 17 (7)(e) Annually Keswick Office Building Notification Appliances (strobe & horn/strobe) 28 Inspect NFPA 72, Table 14.3.1, line 22 (1) (3) Semiannually Keswick Office Building Alarm Notification Appliances (strobe & horn/strobe) 28 Test NFPA 72, Table 14.4.3.2, line 22 (1) (3) Annually Spring Creek Powerplant All Equipment Inspect NFPA 72, Table 14.3.1, line 1 Annually Spring Creek Powerplant Control Equipment 1 Inspect NFPA 72, Table 14.3.1, line 2 (1) (a, b, c, d) Annually Spring Creek Powerplant Control Equipment 1 Inspect NFPA 72, Table 14.3.1, line 2 (1) (e) Semiannually Spring Creek Powerplant Control Equipment and Transponder 1 Test NFPA 72, Table 14.4.3.2, line 2 (1) (2) (3) (4) (5) Annually Spring Creek Powerplant Alarm Control Unit Trouble Signals 1 Test NFPA 72, Table 14.4.3.2, line 3 (1) (2) (3) (4) Annually Spring Creek Powerplant Digital Alarm Communication Transmitter (DACT) 1 Inspect NFPA 72, Table 14.3.1, line 4 (1) Annually Spring Creek Powerplant Digital Alarm Communication Transmitter (DACT) 1 Test NFPA 72, Table 14.4.3.2, line 4 (1) (2) Annually Spring Creek Powerplant Batteries 2 Inspect NFPA 72, Table 14.3.1, line 9 Semiannually Spring Creek Powerplant Secondary (standby) Power Supply 1 Test NFPA 72, Table 14.4.3.2, line 8 Annually Spring Creek Powerplant 30‐sec Backup Battery Power Function Test 1 Test FIST 4‐1, Section 18.2, row 3 Monthly Spring Creek Powerplant Batteries, all types within fire det & alarm sys 2 Inspect FIST 4‐1, Section 18.2, row 5 Annually Spring Creek Powerplant 90‐min Battery Discharge Test 1 Test FIST 4‐1, Section 18.2, row 6 Annually Spring Creek Powerplant Remote Annunciator 1 Inspect NFPA 72, Table 14.3.1, line 11 Semiannually Spring Creek Powerplant Remote Annunciator 1 Test NFPA 72, Table 14.4.3.2, line 11 Annually Spring Creek Powerplant Conductors ‐ circuit integrity 1 Test NFPA 72, Table 14.4.3.2, line 15 Annually Spring Creek Powerplant Initiating Device ‐ Manual Pull Stations 5 Inspect NFPA 72, Table 14.3.1, line 17 (5) Semiannually Spring Creek Powerplant Initiating Device ‐ Manual Pull Stations 5 Test NFPA 72, Table 14.4.3.2, line 17 (5) Annually Spring Creek Powerplant Initiating Device ‐ Smoke Detectors 21 Inspect NFPA 72, Table 14.3.1, line 17 (9) Semiannually Spring Creek Powerplant Initiating Device ‐ Smoke Detectors 21 Test NFPA 72, Table 14.4.3.2, line 17 (7)(a) Annually Spring Creek Powerplant Initiating Device ‐ Projected Beam Detectors 2 Inspect NFPA 72, Table 14.3.1, line 17 (10) Semiannually Spring Creek Powerplant Initiating Device ‐ Projected Beam Detectors 2 Test NFPA 72, Table 14.4.3.2, line 17 (7) (f) Annually Spring Creek Powerplant Notification Appliances (strobe & horn/strobe) 24 Inspect NFPA 72, Table 14.3.1, line 22 (1) (3) Semiannually Spring Creek Powerplant Alarm Notification Appliances (strobe & horn/strobe) 24 Test NFPA 72, Table 14.4.3.2, line 22 (1) (3) Annually J.F. Carr Powerplant All Equipment Inspect NFPA 72, Table 14.3.1, line 1 Annually J.F. Carr Powerplant Control Equipment 1 Inspect NFPA 72, Table 14.3.1, line 2 (1) (a, b, c, d) Annually J.F. Carr Powerplant Control Equipment 1 Inspect NFPA 72, Table 14.3.1, line 2 (1) (e) Semiannually J.F. Carr Powerplant Control Equipment and Transponder 1 Test NFPA 72, Table 14.4.3.2, line 2 (1) (2) (3) (4) (5) Annually J.F. Carr Powerplant Alarm Control Unit Trouble Signals 1 Test NFPA 72, Table 14.4.3.2, line 3 (1) (2) (3) (4) Annually J.F. Carr Powerplant Digital Alarm Communication Transmitter (DACT) 1 Inspect NFPA 72, Table 14.3.1, line 4 (1) Annually J.F. Carr Powerplant Digital Alarm Communication Transmitter (DACT) 1 Test NFPA 72, Table 14.4.3.2, line 4 (1) (2) Annually J.F. Carr Powerplant Batteries 2 Inspect NFPA 72, Table 14.3.1, line 9 Semiannually J.F. Carr Powerplant Secondary (standby) Power Supply 1 Test NFPA 72, Table 14.4.3.2, line 8 Annually J.F. Carr Powerplant 30‐sec Backup Battery Power Function Test 1 Test FIST 4‐1, Section 18.2, row 3 Monthly J.F. Carr Powerplant Batteries, all types within fire det & alarm sys 2 Inspect FIST 4‐1, Section 18.2, row 5 Annually J.F. Carr Powerplant 90‐min Battery Discharge Test 1 Test FIST 4‐1, Section 18.2, row 6 Annually J.F. Carr Powerplant Remote Annunciator 1 Inspect NFPA 72, Table 14.3.1, line 11 Semiannually J.F. Carr Powerplant Remote Annunciator 1 Test NFPA 72, Table 14.4.3.2, line 11 Annually J.F. Carr Powerplant Conductors ‐ circuit integrity 1 Test NFPA 72, Table 14.4.3.2, line 15 Annually J.F. Carr Powerplant Initiating Device ‐ Manual Pull Stations 4 Inspect NFPA 72, Table 14.3.1, line 17 (5) Semiannually J.F. Carr Powerplant Initiating Device ‐ Manual Pull Stations 4 Test NFPA 72, Table 14.4.3.2, line 17 (5) Annually J.F. Carr Powerplant Initiating Device ‐ Smoke Detectors 28 Inspect NFPA 72, Table 14.3.1, line 17 (9) Semiannually J.F. Carr Powerplant Initiating Device ‐ Smoke Detectors 28 Test NFPA 72, Table 14.4.3.2, line 17 (7)(a) Annually J.F. Carr Powerplant Initiating Device ‐ Projected Beam Detectors 2 Inspect NFPA 72, Table 14.3.1, line 17 (10) Semiannually J.F. Carr Powerplant Initiating Device ‐ Projected Beam Detectors 2 Test NFPA 72, Table 14.4.3.2, line 17 (7) (f) Annually

J.F. Carr Powerplant Notification Appliances (strobe & horn/strobe) 29 Inspect NFPA 72, Table 14.3.1, line 22 (1) (3) Semiannually J.F. Carr Powerplant Alarm Notification Appliances (strobe & horn/strobe) 29 Test NFPA 72, Table 14.4.3.2, line 22 (1) (3) Annually Lewiston Powerplant All Equipment Inspect NFPA 72, Table 14.3.1, line 1 Annually Lewiston Powerplant Control Equipment 1 Inspect NFPA 72, Table 14.3.1, line 2 (1) (a, b, c, d) Annually Lewiston Powerplant Control Equipment 1 Inspect NFPA 72, Table 14.3.1, line 2 (1) (e) Semiannually Lewiston Powerplant Control Equipment and Transponder 1 Test NFPA 72, Table 14.4.3.2, line 2 (1) (2) (3) (4) (5) Annually Lewiston Powerplant Alarm Control Unit Trouble Signals 1 Test NFPA 72, Table 14.4.3.2, line 3 (1) (2) (3) (4) Annually Lewiston Powerplant Digital Alarm Communication Transmitter (DACT) 1 Inspect NFPA 72, Table 14.3.1, line 4 (1) Annually Lewiston Powerplant Digital Alarm Communication Transmitter (DACT) 1 Test NFPA 72, Table 14.4.3.2, line 4 (1) (2) Annually Lewiston Powerplant Batteries 2 Inspect NFPA 72, Table 14.3.1, line 9 Semiannually Lewiston Powerplant Secondary (standby) Power Supply 1 Test NFPA 72, Table 14.4.3.2, line 8 Annually Lewiston Powerplant 30‐sec Backup Battery Power Function Test 1 Test FIST 4‐1, Section 18.2, row 3 Monthly Lewiston Powerplant Batteries, all types within fire det & alarm sys 2 Inspect FIST 4‐1, Section 18.2, row 5 Annually Lewiston Powerplant 90‐min Battery Discharge Test 1 Test FIST 4‐1, Section 18.2, row 6 Annually Lewiston Powerplant Remote Annunciator 1 Inspect NFPA 72, Table 14.3.1, line 11 Semiannually Lewiston Powerplant Remote Annunciator 1 Test NFPA 72, Table 14.4.3.2, line 11 Annually Lewiston Powerplant Conductors ‐ circuit integrity 1 Test NFPA 72, Table 14.4.3.2, line 15 Annually Lewiston Powerplant Initiating Device ‐ Manual Pull Stations 2 Inspect NFPA 72, Table 14.3.1, line 17 (5) Semiannually Lewiston Powerplant Initiating Device ‐ Manual Pull Stations 2 Test NFPA 72, Table 14.4.3.2, line 17 (5) Annually Lewiston Powerplant Initiating Device ‐ Smoke Detectors 5 Inspect NFPA 72, Table 14.3.1, line 17 (9) Semiannually Lewiston Powerplant Initiating Device ‐ Smoke Detectors 5 Test NFPA 72, Table 14.4.3.2, line 17 (7)(a) Annually Lewiston Powerplant Notification Appliances (strobe & horn/strobe) 3 Inspect NFPA 72, Table 14.3.1, line 22 (1) (3) Semiannually Lewiston Powerplant Alarm Notification Appliances (strobe & horn/strobe) 3 Test NFPA 72, Table 14.4.3.2, line 22 (1) (3) Annually Trinity Powerplant All Equipment Inspect NFPA 72, Table 14.3.1, line 1 Annually Trinity Powerplant Control Equipment 1 Inspect NFPA 72, Table 14.3.1, line 2 (1) (a, b, c, d) Annually Trinity Powerplant Control Equipment 1 Inspect NFPA 72, Table 14.3.1, line 2 (1) (e) Semiannually Trinity Powerplant Control Equipment and Transponder 1 Test NFPA 72, Table 14.4.3.2, line 2 (1) (2) (3) (4) (5) Annually Trinity Powerplant Alarm Control Unit Trouble Signals 1 Test NFPA 72, Table 14.4.3.2, line 3 (1) (2) (3) (4) Annually Trinity Powerplant Digital Alarm Communication Transmitter (DACT) 1 Inspect NFPA 72, Table 14.3.1, line 4 (1) Annually Trinity Powerplant Digital Alarm Communication Transmitter (DACT) 1 Test NFPA 72, Table 14.4.3.2, line 4 (1) (2) Annually Trinity Powerplant Batteries 2 Inspect NFPA 72, Table 14.3.1, line 9 Semiannually Trinity Powerplant Secondary (standby) Power Supply 1 Test NFPA 72, Table 14.4.3.2, line 8 Annually Trinity Powerplant 30‐sec Backup Battery Power Function Test 1 Test FIST 4‐1, Section 18.2, row 3 Monthly Trinity Powerplant Batteries, all types within fire det & alarm sys 2 Inspect FIST 4‐1, Section 18.2, row 5 Annually Trinity Powerplant 90‐min Battery Discharge Test 1 Test FIST 4‐1, Section 18.2, row 6 Annually Trinity Powerplant Remote Annunciator 1 Inspect NFPA 72, Table 14.3.1, line 11 Semiannually Trinity Powerplant Remote Annunciator 1 Test NFPA 72, Table 14.4.3.2, line 11 Annually Trinity Powerplant Conductors ‐ circuit integrity 1 Test NFPA 72, Table 14.4.3.2, line 15 Annually Trinity Powerplant Initiating Device ‐ Manual Pull Stations 4 Inspect NFPA 72, Table 14.3.1, line 17 (5) Semiannually Trinity Powerplant Initiating Device ‐ Manual Pull Stations 4 Test NFPA 72, Table 14.4.3.2, line 17 (5) Annually Trinity Powerplant Initiating Device ‐ Smoke Detectors 24 Inspect NFPA 72, Table 14.3.1, line 17 (9) Semiannually Trinity Powerplant Initiating Device ‐ Smoke Detectors 24 Test NFPA 72, Table 14.4.3.2, line 17 (7)(a) Annually Trinity Powerplant Initiating Device ‐ Projected Beam Detectors 2 Inspect NFPA 72, Table 14.3.1, line 17 (10) Semiannually Trinity Powerplant Initiating Device ‐ Projected Beam Detectors 2 Test NFPA 72, Table 14.4.3.2, line 17 (7) (f) Annually Trinity Powerplant Notification Appliances (strobe & horn/strobe) 27 Inspect NFPA 72, Table 14.3.1, line 22 (1) (3) Semiannually Trinity Powerplant Alarm Notification Appliances (strobe & horn/strobe) 27 Test NFPA 72, Table 14.4.3.2, line 22 (1) (3) Annually