C05__ATTACHMENT_2_MAJOR_FIRE_ALARM_SYSTEM_COMPONENTS.PDF

PDF 3 MB Posted

Attached to
NCAO Fire Alarm Maintenance Services Federal contract opportunity
Solicitation number
140R2022Q0003
Issued by
Department of the Interior Bureau of Reclamation

About this file

This solicitation is for fire alarm maintenance services at ten Bureau of Reclamation locations within the NCAO area. Services will include inspection, testing, repair, and documentation of fire alarm systems. The solicitation is issued by the Department of the Interior Bureau of Reclamation, with responses due by the date specified. Pricing and terms will be negotiated with the awardee, who will provide fire alarm maintenance for an initial period of one year with four optional one-year extensions.

View the file

Other files for this federal contract opportunity

Other files attached to NCAO Fire Alarm Maintenance Services, newest first.
File Type Posted
Sol_140R2022Q0003_Amd_0001.pdf PDF
C05__ATTACHMENT_3_INSPECTION-TESTING_LIST.PDF PDF
C05__ATTACHMENT_5_WAGE_DETERMINATION_2015-5627_REV_13_10-20-2021.pdf PDF
C05__ATTACHMENT_4_RSHS_APPENDIX_B_CONTRACTOR_SAFETY_PROGRAM.pdf PDF
C05__ATTACHMENT_1_FIRE_ALARM_REPORTING_DIAGRAM.PDF PDF
Sol_140R2022Q0003.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Intrusion Alarm Systems | Conettix D6600 Communications Receiver/Gateway

Conettix D6600 Communications Receiver/Gateway www.boschsecurity.com u 32 lines for public switched telephone network (PSTN) communications with Two Way audio, Caller ID, ANI and DNIS support u Award winning VOIP compensation feature reduces signal errors caused by digitally distorted Contact ID signals u Up to 3,200 network accounts for IPv6 and IPv4 network communications u Supports NIST-FIPS197 certified 128 to 256 bit AES encryption u Designed with electrically isolated, hot-swappable line cards and front panel access to CPU card

The Conettix D6600 Communications Receiver/ Gateway with Conettix IP hardware components works in the following configurations:

• Telephone line communications over the public switched telephone network (PSTN).

• Internet or intranet communications over a LAN or WAN using standard user datagram protocol and internet protocol (UDP/IP).

• Simultaneous PSTN and LAN or WAN communications.

The Conettix network environment reduces signal-reporting time, improves security, and provides instant notification when a site experiences communication problems. A D6600 with Conettix IP hardware is compatible with most manufacturer’s fire and security system control panels.

System overview

PSTN communications configuration This configuration uses existing telephone lines. A control panel's signal transmits over a PSTN analog telephone line to the D6600. The D6600 translates the signal to a common data format and sends the signal through Ethernet LAN, WAN, or RS-232 to a central station automation system.

Internet or intranet communications configuration This configuration requires Conettix IP hardware components, uses existing Internet or intranet structures, and avoids additional telephone service costs.

This configuration permits the Conettix D6200 Programming/Administration Software to connect to the D6600 remotely. A control panel's signal transmits over the LAN or WAN to the D6600. The D6600 translates the signal to a common data format and sends the signal through Ethernet LAN, WAN, or RS-232 to a central station automation system. The central automation system sends information to operator workstations.

Conettix D6200 programming/administration software Conettix D6200 Programming/Administration Software is a PC-based application that allows users to view, change, upload, and download D6600 programming parameters through a network connection or RS-232 serial port. Through the Conettix D6200 Programming/ Administration Software users can edit CPU and line card parameters; view the status of all accounts in the databases; add, edit, and delete accounts; and configure network operations.

Notice Conettix D6200 Programming/Administration Software is compatible with the following operating systems: Microsoft Windows XP, Windows 7, Windows 8.

1 2 3

4 5

4.2

5.1

5.2

5.36

4.3

4.1

1. Access Control

2. Commercial Monitoring

3. Residential Monitoring

4. PSTN

4.1 Private Branch Exchange (PBX)

4.2 Two-way Audio

4.3 Analog Telephone Lines

5. LAN/WAN

5.1 Firewall, Router, and Hub

5.2 LAN

5.3 Conettix D6680 Ethernet Network Adapter

6. Conettix D6600 Communications Receiver/Gateway

7. RS-232

8. Conettix D6200 Programming/Administration Software

9. Automation System

10. Central Station Operators

Functions

Communication formats

• Acron Superfast • ROBOFON

• Ademco Slow • Scantronics Scancom

• Ademco Express • SERIEE FSK/DTMF

• Ademco High Speed • Sescoa Super Speed

• Ademco Contact ID • SIA 8/20/300

• CFSK BELL/V.21 • SIA ADT

• FBI Superfast • SIA V.21

• Franklin/Sescoa • Silent Knight Fast

• ITI • Silent Knight FSK

• Radionics BFSK • Standard Pulse Formats

• Radionics Hex • Sur-Gard DTMF

• Radionics Modem II • Telim

• Radionics Modem IIe/IIIa2 • Veritech FSK

• RB2000 • VONK

PSTN communications

Function Benefit

Dialed number identification service (DNIS) adjusts line card settings according to the telephone number dialed by the control panel.

Handles more field dialers with fewer line cards and allows you to create virtual lines.

Caller identification (Caller ID) alarm processing stores corresponding handshake formats. The processing automatically recalls the format when the same caller identification is processed.

Shortens the amount of time that calls are connected to the receiver.

Decreases money spent on fixed hardware or monthly phone bills.

Uses the Conettix D6641 Telephone Line Card.

Digital signal processing technology in the cards allows the D6600 to recognize more communication formats and accurately decode information.

2 | Conettix D6600 Communications Receiver/Gateway

Additional PSTN communications advantages

• Automatic number identification (ANI) system identifies incoming telephone numbers.

• Each line card has four telephone lines.

• Receives signals on up to 32 telephone lines simultaneously.

• Independent, configurable communication format settings for each telephone line.

• Visual front panel light emitting diode (LED) indicators for on-line and line-fault status conditions.

Two-way audio

• Able to transfer calls to another line or extension.

• Activated by account numbers and by events.

LAN or WAN gateway communications

• Requires Conettix IP hardware components.

• Two-way communications with a control panel.

• Supervised network automation computer links.

• Supports up to 3200 network accounts.

• Ethernet configuration available.

• Supports 128-bit AES Rijndael encryption.

Supervision and programming with network communications The protected premises sends supervision messages to the D6600 at a programmed rate. Users can program the supervision rate to be 5 seconds to 1275 seconds. The D6600 acknowledges the supervision message, providing end-to-end security. If authentication and encryption algorithms detect potentially damaging activity, they alert the central station operator.

The data network's communication link is continuously supervised. Even when monitoring thousands of control panels, the system consumes only a small amount of bandwidth.

Front panel access The D6600 enclosure design provides convenient access to the CPU card or the hot-swappable telephone line cards. A hot-swappable card can be removed and replaced without affecting system performance.

Flash technology Using the Conettix D6200 Programming/ Administration Software, flash technology in the D6600 allows for software upgrades without additional hardware or firmware changes.

Certifications and approvals

Australia Austel Approved

USA ANSI National Institute of Standards and Technology's Advanced Encryption Standard Certification (Certificate Number 82)

NIST National Institute of Standards and Technology AES Certification

Region Certification

Europe CE EMC, LVD, R&TTE

USA UL

UL UL 1076 - Proprietary Burglar Alarm Units and Systems

UL UL 1610 - Central Station Burglar Alarm Units

UL UL 365 - Police Station Connected Bur-glar Alarm Units

UL UL 864 - Standard for Control Units and Accessories for Fire Alarm Systems

FM

CSFM California State Fire Marshal (see our website)

FCC ESVUSA-25328-AL-N

Canada ULC

ULC CAN/ULC S303 - Local Burglar Alarm Units and Systems

ULC CAN/ULC S304-06, Second Edition, dated July 2006 – For Signal Receiving Centre and

ULC CAN/ULC S559 - Fire Signal Receiving Centres and Systems

ULC ULC-ORD C1076 - Proprietary Burglar Alarm Units and Systems

IC 1249A-8925A

Hong Kong HKFSD

Brazil ANATEL 0841-03-2045

Installation/configuration notes

The D6600 and monitoring centers The D6600 has extended edges so that installers can mount it easily into a rack cabinet. Mount up to eight D6600 units into a standard 48.3 cm (19 in.) rack cabinet to conserve floor space. Each D6600 connects 32 telephone lines. Eight D6600 units can connect a total of 256 telephone lines, process 600,000 digital accounts, and process 28,800 supervised Internet or intranet accounts.

Notice Rack cabinets are sold separately by a variety of manufacturers.

Incorporating Conettix IP function into the D6600 With the correct Conettix IP hardware components, the D6600 can supervise the network communications link. The Conettix IP hardware components include:

• Conettix D6201 Series IP Security Keys

• Conettix D6672 COM 1 Expansion Kit

• Conettix D6680 Ethernet Network Adapter

3 | Conettix D6600 Communications Receiver/Gateway

Network communications and control panels For network communications, it is necessary to use one of following modules with the appropriate control panel: Conettix C900V2 Dialer Capture Ethernet Module or Conettix DX4020 Ethernet Network Interface Module. Review the control panel specifications for the recommended network interface or dialer capture modules.

Parts included

Quantity Component

1 Conettix D6600 Communications Receiver/Gateway

1 Conettix D6610 CPU Card

1 Conettix D6615 CPU Terminator Card

1 Conettix D6641 Telephone Line Card (Expanded Memory)

1 Conettix D6645 Telephone Line Terminator Card

1 Conettix D6200CD CD-ROM (Includes the Conettix D6200 Programming/Administration Software)

1 P6601 Battery Cable

1 P6602 Input and Output Cable

Technical specifications

Electrical

Power requirements

AC nominal operating range 120 V or 230 V

AC maximum operating range 100 VAC to 120 VAC, 220 VAC to 230 VAC, 50 Hz or 60 Hz,

2.5 A maximum

Standby power Uninterruptible power supply (UPS) containing a sealed lead-acid battery, 12 V, 7 Ah to 18 Ah

Current requirements

One line card installed Battery: 800 mA UPS AC Standby: 350 mA

For each additional line card or terminal card pair

Battery: 210 mA UPS AC Standby: 35 mA

One network communications card installed

Battery: 10 mA UPS AC Standby: 10 mA

Mechanical

Automation outputs

Automation outputs SIA mode 6500 mode

Enclosure

Rack Mount dimensions (4U) 18 cm x 48.3 cm x 49.5 cm (7.0 in. x 19.0 in. x 19.5 in.)

Standalone dimensions 18 cm x 45 cm x 49.5 cm (7.0 in. x 17.75 in. x 19.5 in.)

Weight 8.7 kg (19 lb)

Telephone

Telephone RJ11C modular jacks, with 26 AWG or larger wire diameter

Ringer equivalence number (REN)

REN 0.4 B

Industry Canada (IC) REN 0.2

Display

Screen dimensions 1.8 cm x 15.2 cm (0.7 in. x

6.0 in.) dot matrix LCD, 5 x 7 dots per character. Shows two separate lines, 40 characters per line.

Indicators LED display section indicates receiver status and power.

Inputs and outputs

For automation computer connection

One RS-232 interface port COM3

For external serial printer, PC, modem, or network connection

One RS-232 interface port COM4

For parallel printer connection One parallel printer port

Number of programmable inputs Two (wire harness included)

Number of programmable outputs Two (wire harness included)

Optional input

For optional network communications expansion

One RS-232 interface port COM1

Environmental

Temperature (operating) 0°C to 50°C (+32°F to +122°F)

Trademarks All hardware and software product names used in this document are likely to be registered trademarks and must be treated accordingly.

Ordering information

Conettix D6600 Communications Receiver/Gateway Supports communications through PSTN and/or LAN/ WAN. Supports 32 telephone lines, 3200 network accounts, two-way audio, caller ID, ANI, and DNIS.

Order number D6600

4 | Conettix D6600 Communications Receiver/Gateway

Accessories

3200 Account Conettix IP Security Key (LPT) Designed for parallel ports. Allows each Conettix Communications Receiver/Gateway to support a maximum of 3200 IP accounts.

Order number D6201

3200 Account Conettix IP Security Key (USB) Allows each Conettix Communications Receiver/ Gateway to support a maximum of 3200 IP accounts.

Designed for USB ports.

Order number D6201-USB

500 Account Conettix IP Security Key (USB) Allows each Conettix Communications Receiver/ Gateway to support 500 IP accounts. Designed for USB ports.

Order number D6201-500-USB

Conettix D6610 CPU Line Card CPU card for Conettix D6600 Communications Receiver/Gateway.

Order number D6610

Conettix D6615 CPU Terminator Card Provides a shielded interface between the Conettix D6610 CPU Line Card and external connections to automation database computers and printers.

Order number D6615

Conettix D6641 Telephone Line Card Answers and decodes signals from up to four telephone lines using advanced digital signal processing technology.

Order number D6641

Conettix D6645 Telephone Line Terminator Card Provides isolation and transient suppression to the Conettix D6641 Telephone Line Card.

Order number D6645

Conettix D6672 Com 1 Expansion Kit Creates a third serial port on the Conettix D6600 Communications Receiver/Gateway. Provides a DB9 male connector and transient protection.

Order number D6672

P6601 Battery Cable Connects a 12 VDC power source to the Conettix D6600 Communications Receiver/Gateway.

Order number P6601

P6602 Input and Output Cable Supports use of input and output lines for Conettix receivers.

Order number P6602

P6603 Acknowledgement Button Spare acknowledgement button for Conettix D6600 Communications Receiver/Gateway.

Order number P6603

Conettix ITS-D6686-UL Ethernet Network Adapter Order number ITS-D6686-UL

Conettix ITS-D6686-INTL Ethernet Network Adapter Provides a 10/100 Base T network interface connection for IP account monitoring and central station automation with Conettix D6600 Communications Receiver/Gateway. Supports IPv6/ IPv4 dual stack and up to 256-bit AES encryption.

Order number ITS-D6686-INTL

Software Options

Conettix D6200CD CD‑ROM Provides software for programming and operating Conettix receivers. Includes PDF documentation for hardware and software relating to the Conettix Communications Receiver/Gateway.

Order number D6200CD

5 | Conettix D6600 Communications Receiver/Gateway

6 | Conettix D6600 Communications Receiver/Gateway

Represented by:

Europe, Middle East, Africa: Germany: North America: Asia-Pacific:

Bosch Security Systems B.V.

P.O. Box 80002 5600 JB Eindhoven, The Netherlands Phone: + 31 40 2577 284 emea.securitysystems@bosch.com emea.boschsecurity.com

Bosch Sicherheitssysteme GmbH Robert-Bosch-Ring 5 85630 Grasbrunn Germany www.boschsecurity.com

Bosch Security Systems, Inc.

130 Perinton Parkway Fairport, New York, 14450, USA Phone: +1 800 289 0096 Fax: +1 585 223 9180 onlinehelp@us.bosch.com www.boschsecurity.us

Robert Bosch (SEA) Pte Ltd, Security Systems 11 Bishan Street 21 Singapore 573943 Phone: +65 6571 2808 Fax: +65 6571 2699 apr.securitysystems@bosch.com www.boschsecurity.asia

© Bosch Security Systems 2016 | Data subject to change without notice 2663469195 | en, V11, 21. Sep 2016

Intrusion Alarm Systems | B465 Universal Dual Path Communicator

B465 Universal Dual Path Communicator www.boschsecurity.com u Compatible with any control panel using Contact ID, SIA, Pulse 3/1 or Pulse 4/2 communication formats (auto detecting) u No control panel reprogramming required to install u Supports Ethernet directly and optional plug-in cellular communication technologies in single, or multi-path configurations u Supports four configurable inputs and three configurable outputs u Approved for Commercial Fire/Burglary applications as sole, primary, or secondary communication path

The B465 Conettix Universal Dual Path Communicator converts the Public Switch Telephone Network (PSTN) digital dialer, or dry contact outputs from an intrusion/ fire control panel to an IP signal for transmission over the Ethernet or cellular network. The B465 Conettix Universal Dual Path Communicator is UL 864 10th

Edition approved per NFPA 72 version 2013.

The module can use its built-in Ethernet connection, and/or an optional Conettix plug-in cellular module (B440/B441/B442/B443) to send reports to the central station receiver.

Automation programming for the supported control panel remains unchanged with the installation of the B465 module, thus simplifying the installation process This allows for a smooth transition from the PSTN realm into IP. All messages generated internally by the B465 are shown in Contact ID format at the central station.

The module can be powered from a 16.5 VAC transformer or 24 VDC power supply.

System overview

The B465 simulates dial tone and line voltages when the digital dialer has a report to send. The module simulates a PSTN connection to the central station.

The module decodes the control panel’s PSTN dialer report and sends the decoded reports by IP connection using Bosch’s Conetix Protocol to the Conettix D6600, D6100IPv6, or D6100i Communication Gateway/Receiver (referred to as the receiver). When the receiver acknowledges receipt of the message, it sends an acknowledgement report to the module which in turn sends an acknowledgement to the connected control panel. This process maintains true end-to-end security.

T M

P R

BAT

E T

H E

R N

E T

E X

T E

R N

A L

A N

N U

N C

X

MODULE 1

Y

MODULE

RELEASE

1 COM 2 PNL LINE 23 COM 4 PNL LINE 1C NO

RELAY 2

+ BAT -18VAC NO C NC

RELAY 1

TRBL

TX

RX

AC

PANEL

LINE 2

USB

ETHERNET

100BASE-T

LINK

COMMUNICATION MODULE 1

3 COM 41 COM 2

R Y G B

SDI2

Device Bus

18 VAC BATTERY

PANEL

LINE 1

BATTERY

AC

RX

TX

SYSTEM TROUBLE

INPUTS

2.2 k End of

Line Resistors

C NO

RELAY 3

12V

AUX COM

Callout ー Description

1 ー Intrusion/fire control panel

2 ー Control panel phone line connections

3 ー B465 Conettix Universal Dual Path Communicator

4 ー B44x plug-in cellular communicator

5 ー Ethernet connection (LAN/WAN)

6 ー Internet

7 ー Cellular communication to cellular carrier

8 ー Cellular carrier network

9 ー Conettix receiver/gateway

10 ー Conettix receiver/gateway

11 ー Monitoring center automation

Functions

PSTN inputs (2) When the control panel’s PSTN dialer sends a message, the module simulates a PSTN connection to the central station. The module connects to the host control panel through either one or both of the Phone Line inputs. Both Panel Line 1 and Panel Line 2 of the module run 28 VDC and support Contact ID (4 and 10 digit account codes), Pulse 3/1, Pulse 4/2, and SIA communication formats. The B465 is setup to auto detect the communication format which eliminates programming steps.

IP Communication options The module uses the on-board Ethernet connector, and/or optional B440 Conettix Plug-in Communicator, Cellular (3G), B441 Conettix Plug-in CDMA Cellular Communicator, B442 Conettix Plug-in GPRS Cellular Communicator, or B443 Conettix Plug-in HSPA+ Cellular Communicator to communicate with a Conettix D6600, Conettix D6100i or a Conettix D6100IPv6 Communications Receiver/Gateway. Using Conettix IP communication protocol offers a secure path that includes anti-replay/anti-substitution features and provides enhanced security with up to AES 256-bit encryption.

The module supports Domain Name System (DNS) for central station communication. DNS provides ease of use, eliminating the need to use static IP addresses as your reporting destination, and accommodates a simple solution for central station disaster recovery.

Direct wire inputs The B465 provides four on-board inputs. Each input functions independently and does not interfere with the operation of the others. The module monitors the input loops for normal, shorted, or open conditions between an input terminal and any of the input common terminals. Inputs are disabled by default so no EOL resistors are required until activated.

These four inputs on the B465 connect to dry contact outputs on the control panel and generate Contact ID reports instead of using a phone line connection/or in addition to using the control panel phone connection.

The available functions are:

• Panel System Trouble

• Panel AC Fail

• Panel Battery Trouble

• Fire Alarm

• Fire Trouble

• Burg Alarm

• Burg Trouble

• Fire Supervisory

Each input allows the use of dry contacts or powered outputs up to 30 VDC if needed. The inputs use 2.2K EOLs to monitor the dry contact outputs when connected to dry contacts. The inputs recognize the following thresholds when using dry contacts: 2.0 to

3.0 VDC = Normal, 3.7 to 5.0 VDC = Open, 0.0 to 1.3

VDC = Short.

Outputs Includes three programmable output relays rated at 30 VDC, 0.1 A. These outputs can be used to show the status of the B465 or they can be connected to the control panel zone inputs for reporting B465 system faults. The three outputs consist of RELAY 1, RELAY 2, and RELAY 3.

• RELAY 1 is active (energized) once the B465 is running. If the B465 detect a problem or loses power, RELAY 1 de-energizes, which can be used to indicate a system trouble on the local control panel's zone inputs, if required. Depending on the configuration required to create a system trouble on the control panel, the installer needs to use either the NO and COM or the NC and COM connections. Refer to the control panel manual for the required zone configuration to obtain the proper input response.

• RELAY 2 is a normally open (NO) relay with contacts that close when the desired function programmed is detected.

• RELAY 3 is a normally open (NO) relay with contacts that close when the desired function programmed is detected.

2 | B465 Universal Dual Path Communicator

Input power supply The B465 uses a 16.5 VAC transformer or 24 VDC voltage for its primary power source. The approved transformers are the D1640 plug-in transformer, D1640-CA plug-in transformer, or D1640-120WI transformer. The B465 can optionally be powered from 24 VDC power source applied to the AC terminals.

B465 modular connections The B465 module has three modular connections.

• Cellular plug-in connector. Connects to a cellular communication module.

• Tamper connector. Connects the ICP-EZTS Dual Tamper Switch for monitoring the enclosure cover.

• External Annunciator connector. Connects to the optional B46 module.

On-board LED Indicators The B465 has a total of ten on-board LEDs that indicate the module's status (SYSTEM TROUBLE, TX, RX, POWER, BATTERY, HEARTBEAT, Panel Line 1 (ACT),Panel Line 2 ( ACT), 100BASE-T and ETHERNET

LINK).

B46 External Annunciator (Optional) The B46 is an optional module that provides external module LED and sounder status when installed in a supported enclosure. The module has 3 LEDs (System Trouble, Power, and Battery) which illuminate through the B46 LED cover. The LED cover snaps into a knockout in the enclosure door.

The B46 is compatible with the B10, B10R, B11, B11R, and D8103 enclosures.

Certifications and approvals

Region

USA UL 365 - Police Station Connected Burglar Alarm Units and Systems

UL 609 - Local Burglar Alarm Units and Systems

UL 636 - Holdup Alarm Units and Systems

UL 864 - Control Units and Accessories for Fire Alarm Systems (Commercial Fire)

UL 985 - Household Fire Warning System Units

UL 1023 - Household Burglar Alarm System Units

UL 1076 - Proprietary Burglar Alarm Units and Systems

UL 1610 - Central Station Burglar Alarm Units

NIST FIPS 197 AES Certification (IP Communications)

CSFM approved

FCC Part 15 Class B

Canada CAN/ULC S303 - Local Burglar Alarm Units and Systems

CAN/ULC S304 - Signal Receiving Centre and Premise

CAN/ULC S545 - Residential Fire Warning System Control

ICES-003 - Information Technology Equipment (ITE)

ULC-ORD C1023 - Household Burglar Alarm System Units

ULC-ORD C1076 - Proprietary Burglar Alarm Units and System

Region Certification

USA UL 20150807-S1871

CSFM 7300-1615:0253

Parts included

Quantity Component

1 B465 Conettix Universal Dual Path Communicator

1 Hardware pack

1 Quick Start Guide (hardcopy)

1 Wiring label (hardcopy)

1 Literature (mini-CD)

Technical specifications

Properties

Dimensions 3.11 in x 5.03 in x 1.50 in (79 mm x 128 mm x 38 mm)

Environmental considerations

Relative humidity 5% to 93% at +32°C (+90°F)

Temperature (operating) 0°C to +49°C (+32°F to +120°F)

Operational use Indoor use only

Power requirements

Standby battery current Battery input: B465: Idle 150 mA;

Alarm 230 mA

24 VDC input current 24 VDC input: B465: Idle 120 mA;

Alarm 160 mA

Wiring

Terminal wire size 12 AWG to 22 AWG (2.0 mm to 0.65 mm)

Transformer secondary wiring length

15 m (50 ft) maximum unshielded wire

Control panel phone line wiring

100 Ω loop resistance, maximum unshielded wire

Input loop wiring 100 Ω loop resistance, maximum unshielded wire

Ethernet wiring 100 m (328 ft) maximum using Cat 5 wire or better

3 | B465 Universal Dual Path Communicator

Compatibility

Compatible PSTN input formats

Ademco Contact ID (SIA DC-05) +10 digit account codes Pulse 3/1, 3/1 Checksum (2300 Hz ACK Tone) Pulse 3/1, 3/1 Checksum (1400 Hz ACK Tone) Pulse 4/2 (2300 Hz ACK Tone) Pulse 4/2 (1400 Hz ACK Tone) SIA (SIA8, SIA20) – 110 and 300 baud

Receivers D6600 D6100i D6100IPv6

Cellular B440 Conettix Plug-in Communicator, Cellular (3G) B441 Conettix Plug-in CDMA Cellular Communicator B442 Conettix Plug-in GPRS Cellular Communicator B443 Conettix Plug-in HSPA+ Cellular Communicator

Modules B46 External Annunciator

Enclosures B10 Medium Control Panel Enclosure B10R Medium Control Panel Enclosure (Red) B11 Small Control Panel Enclosure B11R Small Control Panel Enclosure (Red) D8103 Universal Enclosure D8108A Attack Resistant Enclosure

Transformers D1640 transformer 120 VAC input,

16.5 VAC, 40 VA output plug-in

D1640-CA transformer 120 VAC input,

16.5 VAC, 40 VA output plug-in

D1640-120WI transformer 120 VAC input, 16.5 VAC, 40 VA output wired in

Ordering information

B465 Universal Dual Path Communicator Compatible with control panels using a standard digital dialer format. Provides end-to-end security.

Allows digital dialer control panels to work over an IP network (such as LAN, WAN, or the Internet).

Order number B465

Accessories

B46 External Annunciator An optional module that uses audio and LEDs to show System Trouble, Power, and Battery status through a knockout on select enclosure doors Order number B46

B10 Medium Control Panel Enclosure White, steel enclosure. Accepts an optional lock and tamper switch. Measures 35.6 cm x 31.8 cm x 7.6 cm (14 in x 12.5 in x 3 in).

Order number B10

B10R Medium Control Panel Enclosure (Red) Red, steel enclosure. Accepts an optional lock and tamper switch.

Order number B10R

B11 Small Control Panel Enclosure White, steel enclosure. Accepts an optional lock and tamper switch. Measures 27.8 cm x 25.9 cm x 8.32 cm (10.9 in x 10.2 in x 3.3 in).

Order number B11

B11R Small Control Panel Enclosure (Red) Red, steel enclosure. Accepts an optional lock and tamper switch. Measures 27.8 cm x 25.9 cm x 8.32 cm (10.9 in x 10.2 in x 3.3 in).

Order number B11R

D8103 Enclosure Grey steel enclosure measuring 41 cm x 41 cm x 9 cm (16 in. x 16 in. x 3.5 in.).

Order number D8103

D8108A Attack Resistant Enclosure Grey steel enclosure measuring 41 cm x 41 cm x 9 cm (16 in. x 16 in. x 3.5 in.). UL Listed. Includes lock and key set. B520, B4512, and B5512 require the B12 mounting plate.

Order number D8108A

B12 Mounting Plate for D8103 Enclosure Required for mounting select control panels and other devices in D8103, D8108A, D8109, or BATB Battery Box enclosures.

Order number B12

D101 Lock and Key Set Short-body lock set with one key supplied. Uses the D102 (#1358) replacement key.

Order number D101

ICP‑EZTS Dual Tamper Switch Combination tamper switch with a wire loop for additional tamper outputs.

Order number ICP-EZTS

D1640 Transformer System transformer rated at 16.5 VAC, 40 VA.

Order number D1640

D1640-CA Transformer For use in Canada. System transformer rated at

16.5 VAC, 40 VA.

Order number D1640-CA

B440 Conettix Plug-in Cellular Communicator Dual technology 3G EVDO/CDMA cellular communicator for secure two-way IP communication on the Verizon Wireless network.

Order number B440

4 | B465 Universal Dual Path Communicator

B441 Conettix Plug-in Cellular Communicator Multi-function CDMA cellular communicator for secure two-way IP communication on the Verizon Wireless network.

Order number B441

B442 Conettix Plug-in GPRS Cellular Communicator Multi-function cellular communicator that provides IP communication over a (GPRS) cellular network.

Order number B442

B443 Conettix Plug-in HSPA+ Cellular Communicator Multi-function 3G/4G cellular communicator providing IP communication over a GPRS/EDGE/UMTS/HSPA+ cellular network.

Order number B443

5 | B465 Universal Dual Path Communicator

Represented by:

Americas: Europe, Middle East, Africa: Asia-Pacific: China: America Latina:

Bosch Security Systems, Inc.

130 Perinton Parkway Fairport, New York, 14450, USA Phone: +1 800 289 0096 Fax: +1 585 223 9180 security.sales@us.bosch.com www.boschsecurity.us

Bosch Security Systems B.V.

P.O. Box 80002 5617 BA Eindhoven, The Netherlands Phone: + 31 40 2577 284 Fax: +31 40 2577 330 emea.securitysystems@bosch.com www.boschsecurity.com

Robert Bosch (SEA) Pte Ltd, Security Systems 11 Bishan Street 21 Singapore 573943 Phone: +65 6571 2808 Fax: +65 6571 2699 apr.securitysystems@bosch.com www.boschsecurity.asia

Bosch (Shanghai) Security Systems Ltd.

203 Building, No. 333 Fuquan Road North IBP Changning District, Shanghai 200335 China Phone +86 21 22181111 Fax: +86 21 22182398 www.boschsecurity.com.cn

Robert Bosch Ltda Security Systems Division Via Anhanguera, Km 98

CEP 13065-900

Campinas, Sao Paulo, Brazil Phone: +55 19 2103 2860 Fax: +55 19 2103 2862 latam.boschsecurity@bosch.com www.boschsecurity.com

© Bosch Security Systems 2015 | Data subject to change without notice 18116851979 | en, V8, 05. Nov 2015

Desigo Panel (for mid-size buildings) 6815 s Industry, Inc.

Building Technologies Division s Data Sheet

Fire Safety Products

Desigo® Fire Safety System 252-Point and 504-Point Addressable (FIRE-Only) Control Panel Models FC2025 and FC2050

Product Overview Specifications The Desigo Fire Safety 252-point (Model FC2025) / 504-point (FC2050) addressable FACP is designed to meet the fire-protection needs of mid-size public and commercial buildings.

This advanced panel offers features typically required in mid-size buildings in a package that is easy to install.

Models FC2025 and FC2050 are networkable, allowing the systems to fulfill the growing fire-protection needs of the building. The programming software for the 252 / 504-point fire systems is held in flash electrically erasable programmable read-only memory (EEPROM).

The following Desigo Fire Safety system components are used in the 252-point / 504-point FACP:

ƒ Operating units Periphery boards ƒ Power supplies System enclosures

Other options are available to meet specific needs of the customer. Models FC2025 and FC2050 are FM (#3010);

CSFM (#7165-0067:0259) and FDNY (#6104) Approved.

Operating Interface Unit The Operating Interface Unit (Model FCM2018-U2 or Model FCM2019-U2) serves as the operating interface and central microprocessor for each panel-type.

Either operating interface unit provides multi-use capability for each end-user to efficiently ‘Acknowledge’ events; to quickly control the NACs of the FACP, and to permit a manual reset of the respective system.

Detailed information about the nature and location of the events can also be displayed, via a backlit, 2” ─x─ 4-3/4” (5.1 cm. ─x─ 12.1 cm.) LCD screen and the four-way navigation push button at the top of the FACP.

Periphery Boards The periphery boards (Models FCI2016-U1 and FCI2017- U1) serve as the main operating components for the 252 / 504-point FACP. Each module operates and monitors input-device identity; as well as controls the signaling-line circuits that communicate with smoke detectors and other field devices (i.e. − FDnet).

ARCHITECT AND ENGINEER SPECIFICATIONS

Desigo operating unit with LEDs in a Two-Height-Unit (2HU) enclosure

∂ Addressable fire alarm control panel (FACP) intended for mid-size building applications

∂ Comprised of the following system components:

ƒ Operating units ƒ Periphery boards ƒ Power supplies ƒ System enclosures

∂ System features:

ƒ Supports 252-to-504 addressable devices:

∂ Model FC2025: one (1) to four (4) ‘Class B’; one (1) to two (2) ‘Class A’ ∂ Model FC2050: one (1) to eight (8) ‘Class B’; one (1) to four (4) ‘Class A’ ƒ Includes one (1) ‘Class A’, or two (2) ‘Class B’ notification appliance circuits (NACs) ƒ Releasing module supports activation of releasing valves in pre-action / deluge systems / agent release ƒ Resettable and non-resettable 24VDC, [nominal] auxiliary power ƒ Desigo Fire Safety Management Station can monitor and control up to 32 Models FC2025 and FC2050 FACPs ƒ Digital alarm communication transmitter (DACT) ƒ Connectivity to a leased-line / city-tie module ƒ Fast and easy set-up with auto-configuration feature

∂ UL 864 9th Edition Listed, ULC Listed;

FM, CSFM & NYC Fire Department Approved

Building Technologies Division

–2–

Specifications ─ (continued) Power Supplies All functions are supported by the 170W (Model FP2016-U1) or 300W (Model FP2012-U1) power supplies, which therefore eliminate the need for external power supplies.

Additionally, Models FP2016-U1 and FP2012-U1 provide primary, 24VDC nominal power for normal operation to Models FC2025 and FC2050.

Both power supplies are filtered and regulated.

Model FP2016-U1 is rated at 6.5 Amps, while the rating of Model FP2012-U1 is 11.5A.

The 170-Watt power supply incorporates a 4.0A, non-resettable slow-blow fuse on the primary input, and includes a built-in AC-line filter for surge and noise suppression. Model FP2016-U1 mounts in the panel’s enclosure, and there are no serviceable Desigo Fire Safety parts to be maintained.

The 300-Watt power supply incorporates two (2) 6.3A replaceable, non-resettable slow-blow fuses on the primary input and includes a built-in AC line filter for surge and noise suppression. Model FP2012-U1 mounts in the panel’s enclosure, and there are no serviceable Desigo Fire Safety parts to be maintained.

System Enclosures The Desigo fire-alarm enclosures and their accessories provide a complete set of hardware for mounting all Desigo main-system and remote terminal cards, as well as Desigo modules that are housed in each enclosure.

The hardware allows this Desigo system to be configured for a variety of applications, as well as for future system upgrades. Included in the enclosure series are back box and door sets; removable mounting plates and clear lenses; and blank plates for use with the enclosure doors.

All enclosures come with ground straps for the inner and outer doors, shield termination lugs, grounding lugs, and tie wrap lances for securing wire. All Desigo two height-unit (2HU) enclosures can also mount system back-up batteries up to 33AH in capacity.

Models FC2025 and FC2050 utilize a two-height-unit enclosure. The following components comprise a complete two-height-unit enclosure:

ƒ One (1) back box, (Model FHB2002-U1 / R1) ƒ One (1) or two (2) inner doors, (Models FHD2004-U1 or FHD2005-U1) ƒ One (1) outer door, (Model FHD2002-U2 / R2, or FHD2003-U2 / R2) ƒ One (1) or two (2) clear windows, (Model FHD2006-U1)

Note: One (1) window is installed for Model FHD2002-U2 / R2 outer door, and two (2) windows are required for Model FHD2003-U2 / R2.

The approximate size for each two-height-unit enclosure is: 27.5" (70cm.) high; 21.5" (54.6cm.) wide, and 5.75" (14.6cm.) deep. The weight, without connected components, is approximately 6.3 Lbs. (2858 g).

Additionally, the two-height-unit enclosure supports the following components:

ƒ Enclosure trim kit (for flush-mounting) ƒ Battery bracket (to comply with seismic certification) ƒ DIN rail kit (provides connection between internal-system wiring and field wiring)

Optional Accessories Digital Alarm Communication Transmitter (DACT) The DACT is used to provide communication between Models FC2025 and FC2050 and with either a central or remote monitoring station.

The Model FCA2015-U1 module mounts directly on the back enclosure and connects to the periphery boards.

The DACT enables remote transmission of alarms and events via a public telephone line.

Releasing Module The releasing module (Model XCI2001-U1) supports activation of releasing valves in pre-action / deluge systems (including double-interlock pre-action systems, or Sinorix® Engineered Fire Suppression systems).

Activation can be event-controlled or performed by addressable manual pull stations.

When installed on Models FC2025 / FC2050, the releasing module contains an integral manual-disconnect switch for releasing circuits. This essential feature protects the releasing circuits from accidental discharge during maintenance.

Battery Disconnect Module The Battery Disconnect Module (Model FCA2032-U1) is specifically designed to disconnect the backup battery on the Desigo Fire Safety 252 / 504-point addressable FACP when its voltage drops below 19VDC. The cut-off function of Model FCA2032-U1 prevents the battery from operating beyond its normal power level for basic system operation.

The battery-disconnect module remains disconnected until AC power is restored to a Desigo 252 / 504 FACP.

Migration Hardware Kit Model FHA2056-series kits are specifically designed for the seamless transition of an existing Siemens FS-250 (FireSeeker) control panel into a fully operational 252 or 504-point addressable Desigo Fire Safety fire-alarm FACP, [FC2025 or FC2050, respectively].

Each shipment of the Model FHA2056-series kits contains the following pieces of equipment:

• One (1) outer door

• One (1) inner door

• One (1) hinge-assembly bracket

• One (1) back plate

• One (1) inner-door bracket

Note: The five (5) items that comprise one (1) Model FHA2056-series hardware-migration kit cannot be ordered individually.

–3–

Specifications ─ (continued) Network Module The SafeDLINK network module (Model FN2001-U1) is used to network up to 16 FACPs or fire terminals, via the FCnet system bus. Model FN2001-U1 is plugged into the Operating Unit (Models FCM2018-U2 / R2 and FCM2019-U2 / R2).

Model FN2001-U1, which connects to system input / output bus, has ground-fault monitoring, as well as an integrated degrade-mode feature. Redundant networking is accomplished with one (1) network module per panel [Simple-Loop Trouble]. There is electrical isolation between the system bus and the FACP.

Remote Display Terminals The Remote Display Terminals (Models FT2014-U2 / R2 and FT2015-U2 / R2) are remote annunciators that show the existing status of Models FC2025 / FC2050.

Light-emitting diodes (LEDs) will illuminate for any given Alarm, Supervisory and Trouble Desigo-system event.

A LCD screen will give details of the event in alphanumeric form. The display screen can be scrolled, via the four-way navigation button, to reveal additional events.

Model FT2014 is a display-only, remote annunciator that has one (1) button used to silence the local sounder.

Model FT2015 has three (3) control buttons for ‘acknowledging’ events, ‘silencing’ audible circuits and ‘resetting’ the system. Additionally, there are three (3) user-programmable buttons available. Model FT2015 has a key switch that enables the control buttons to operate.

The remote display terminals are remotely connected to Models FC2025 and FC2050, via the RS─485 interface.

Models FC2025 and FC2050 require the Model FCA2016- U1 RS─485 interface module to provide communication to the remote display terminals. Model FCA2016-U1 supports Style 4 or Style 6 wiring. Up to eight (8) modules can be supported on a RS─485 bus.

The remote display terminals require 24VDC [nominal] power, and the necessary power can be provided from the Desigo FACP or from another UL Listed, 24VDC power source.

Note: A Model FHD2012-U1 inner door can be optionally purchased in UL markets. The inner door mounts with the optional Model FT201x-series Remote Display terminals.

Having a Model FHD2012-U1 inner door installed can assist in preventing unauthorized access to the RDT.

S-series License Key The S1 license key (Model FCA2033-A1) allows for virtual monitoring and control between a Desigo 252 / 504-point addressable fire-only panel and a personal computer.

The S2 license key (Model FCA2034-A1) is a BACnet output, and is used for monitoring-only purposes by a 3rd-party system for life-safety objects.

The S3 license key (Model FCA2035-A1) is a combination license key that allows for virtual monitoring and control, as well as for distribution of BACnet (monitoring-only) communications. A four-digit personal identification number (PIN) must be used in order to prevent unauthorized access.

Tabular Annunciators The Desigo tabular annunciators allow system events sent from Desigo addressable panels to be displayed remotely in real-time. The Model FT2008 series of tabular annunciators has 16 zones, and the Model FT2009 series uses 96 LEDs for 32 zones. Up to two (2) light-emitting diodes (LEDs) can be used per zone.

Tabular annunciators provide outputs for system and zone status, and are orderable in either black or red.

LED Annunciator Driver The Model FT2007-U1 LED Annunciator Driver provides custom graphic annunciators on addressable Desigo FACPs. This optional system module provides 96 highly programmable outputs to drive LED indicators.

There are 16 inputs to accommodate user-system commands: Silence, Unsilence, Reset, Acknowledge and Lamp Test. Model FT2007-U1 is supervised via a RS−485 interface. A maximum eight (8) modules are allowed on each RS−485 communication bus.

NAC Expansion Module The NAC expansion module (Model FCI2011-U1) provides either of the following additional NACs to a Desigo Fire Safety 252 / 504-point FACP:

ƒ one (1) `Class A’, or ƒ two (2) `Class B’ NACs

Each NAC is rated at 3 Amps. Each NAC expansion module is monitored for open-line and short-circuit conditions.

Related Documentation Product Data Sheet Number

Desigo operating units 6801 Desigo periphery boards 6802 Desigo fire terminals 6803 Desigo DACT 6804 SafeDLINK / FCnet module 6805 Power supplies 6806 Desigo enclosures 6807 NAC expansion module 6808 Desigo releasing module 6809 Leased-Line / city-tie module 6810 Remote periphery module 6811 Desigo Remote display terminals 6812 Single / multi-mode fiber modules 6814 LED / Blank option modules 6816 Battery disconnect module 6819 `S’-series license key 6820 Marine-specific equipment 6822 LED annunciator driver 6824 16-and-32-zone tabular annunciators 6825

Hardware Migration Kit 6826

Fire Safety 8 Fernwood Road Florham Park, NJ 07932 Tel: (973) 593-2600

FAX: (908) 547-6877

URL: www.USA.Siemens.com/ Desigo-Fire-Safety

(SII-FS)

Printed in U.S.A.

Fire Safety 1577 North Service Road East Oakville, Ontario L6H 0H6 / Canada Tel: [905] 465-8000 URL: www.Siemens.CA

January 2018 Supersedes sheet dated 4/2016

(Rev. 6)

Details for Ordering

Model Part

Number Description

FCI2016-U1 S54400-A55-A1

Desigo Periphery Board {for 252-point system}

FCI2017-U1 S54400-A56-A1

Desigo Periphery Board {for 504-point system}

FCM2018-U2 S54400-C40-A1 Desigo Operating Interface Unit

FCM2019-U2 S54400-C41-A1 Operating Interface Unit w/ LEDs

FHB2001-U1 S54400-B47-A1 1HU Back Box, Black

FHB2001-R1 S54400-B47-A2 1HU Back Box, Red

FHB2002-U1 S54400-B48-A1 2HU Back Box, Black

FHB2002-R1 S54400-B48-A2 2HU Back Box, Red

FHD2001-U2 S54400-B49-A1 1HU Outer Door, Black

FHD2001-R2 S54400-B49-A2 1HU Outer Door, Red

FHD2002-U2 S54400-B50-A1 2HU Outer Door w/ 1 Window, Black

FHD2002-R2 S54400-B50-A2 2HU Outer Door w/ 1 Window, Red

FHD2003-U2 S54400-B51-A1 2HU Outer Door w/ 2 Windows, Black

FHD2003-R2 S54400-B51-A2 2HU Outer door w/ 2 windows, Red

FHD2004-U1 S54400-B52-A1 Inner Door, Black

FHD2005-U1 S54400-B53-A1 Inner Door, Black (full plate)

FHD2006-U1 S54400-C46-A1 Clear-Lens Window

FP2011-U1 500-450222 170-Watt Power Supply

FP2012-U1 S54400-Z60-A1 300-Watt Power Supply

Optional Accessories

Model Part

Number Description

FCA2015-U1 S54400-A63-A1 Digital Alarm Comm. Transmitter [DACT]

FCA2016-U1 S54400-A39-A1 RS─485 Interface Module FCA2018-U1 S54400-A65-A1 Remote Peripheral Module FCA2032-U1 S54400-B145-A1 Battery Disconnect Module

FCA2033-U1 S54400-P154-A1 S1 License Key FCA2034-U1 S54400-P155-A1 S2 License Key: BACnet monitoring FCA2035-U1 S54400-P156-A1 S3 License Key: Rem. View w/ BACnet FCI2011-U1 S54400-A54-A1 NAC Expansion Module FCI2020-U1 S54400-A57-A1 Leased-Line / City-Tie Module FCM2022-U2 S54400-C44-A1 Blank Option Module

FCM2023-U2 S54400-C45-A1 LED Option Module:

[RED / GREEN bi-color LED; one (1) YELLOW LED]

FCM2034-U2 S54400-C137-A1 LED Option Module:

[RED / YELLOW bi-color LED; one (1) YELLOW LED]

FHA2056-U1 S54400-B18-A1

Desigo Fire Safety Hardware Migration Kit, Black

FHA2056-R1 S54400-B19-A1

Desigo Fire Safety Hardware Migration Kit, Red

FHD2012-U1 S54400-C145-A1 Inner Door, Black (optional)

FN2001-U1 S54400-A60-A1 SafeDLINK / FCnet Network Module

FN2006-U1 S54400-A61-A1 Single-Mode Fiber-Optic Module

FN2007-U1 S54400-A62-A1 Multi-Mode Fiber-Optic Module FT2007-U1 S54400-A142-A1 LED Annunciator Driver FT2008-U1 S54400-A143-A1 16-Zone Tabular Annunciator, Black

FT2008-R1 S54400-A144-A1 16-Zone Tabular Annunciator, Red FT2009-U1 S54400-A145-A1 32-Zone Tabular Annunciator, Black FT2009-R1 S54400-A146-A1 32-Zone Tabular Annunciator, Red FT2014-U2 S54400-F67-A1 Remote Display Terminal, Black FT2014-R2 S54400-B75-A1 Remote Display Terminal, Red FT2015-U2 S54400-F68-A1 Display Terminal with key, Black FT2015-R2 S54400-B15-A1 Display Terminal with key, Red FTI2001-U1 S54400-A58-A1 Fire Terminal Board XCI2001-U1 S54400-A69-A1 Releasing Module

Electronics Packages

Model Part

Number Description

FC2025-US

S54400-C4-A1

252-Point Fire System with 170 Watt Power Supply and standard operator interfaces

Includes:

FP2016-U1 (1 Qty.)

FCI2016-U1 (1 Qty.)

FCM2018-U2 (1 Qty.)

FC2050-US

S54400-C5-A1

504-Point Fire System with 170 Watt Power Supply and standard operator interfaces

Includes:

FP2016-U1 (1 Qty.)

FCI2017-U1 (1 Qty.)

FCM2018-U2 (1 Qty.)

FC2025-UE

S54400-C6-A1

252-Point Fire System with 170 Watt Power Supply and standard operator interfaces

(with 24-zone LEDs)

Includes:

FP2016-U1 (1 Qty.)

FCI2016-U1 (1 Qty.)

FCM2019-U2 (1 Qty.)

FC2050-UE

S54400-C7-A1

504-Point Fire System with 170 Watt Power Supply and standard operator interfaces

(with 24-zone LEDs)

Includes:

FP2016-U1 (1 Qty.)

FCI2017-U1 (1 Qty.)

FCM2019-U2 (1 Qty.)

FT2050-US

S54400-C8-A1

Network Terminal w/ standard operator interface

Includes:

FTI2001-U1 (1 Qty.)

FCM2018-U2 (1 Qty.)

FT2050-UE

S54400-C9-A1

Network Terminal w/ standard operator interface (with 24-zone LEDs)

Includes:

FTI2001-U1 (1 Qty.)

FCM2019-U2 (1 Qty.)

FC2025-UT

S54400-C10-A1

252-Point Fire System with 300 Watt Power Supply and standard operator interfaces

Includes:

FP2012-U1 (1 Qty.)

FCI2016-U1 (1 Qty.)

FCM2018-U2 (1 Qty.)

FC2050-UT

S54400-C11-A1

504-Point Fire System with 300 Watt Power Supply and standard operator interfaces

Includes:

FP2012-U1 (1 Qty.)

FCI2017-U1 (1 Qty.)

FCM2018-U2 (1 Qty.)

FC2025-UF

S54400-C12-A1

252-Point Fire System with 300 Watt Power Supply and standard operator interfaces

(with 24-zone LEDs)

Includes:

FP2012-U1 (1 Qty.)

FCI2016-U1 (1 Qty.)

FCM2019-U2 (1 Qty.)

FC2050-UF

S54400-C13-A1

504-Point Fire System with 300 Watt Power Supply and standard operator interfaces

(with 24-zone LEDs)

Includes:

FP2012-U1 (1 Qty.)

FCI2017-U1 (1 Qty.)

FCM2019-U2 (1 Qty.)

Temperature and Humidity Range Desigo Fire Safety 252 / 504-point addressable systems are UL 864 9th Edition Listed for indoor dry locations within a temperature range of 120 +/- 3°F (49 +/- 2°C) to 32 +/- 3°F (0 +/- 2°C) and a relative humidity of 93 +/- 2% at a temperature of 90 +/- 3°F (32 +/- 2°C).

Notice: This marketing data sheet is not intended to be used for system design or installation purposes.

For the most up-to-date information, refer to each product’s installation instructions.

Distributed Power Supply − NAC Extender (Model PAD-4 series) 3363 s Data Sheet

Fire Safety Products

FACP Accessories PAD-4 Distributed Power Supply Unit [for UL markets] Notification Appliance Circuit Extender Models PAD-4-ENCL, PAD-4-MB (with FP2011-U1, FP2012-U1 power supplies)

Product Overview Used with Siemens − Fire Safety fire alarm control panels (FACPs), the Distributed Power Supply PAD-4 Unit is a NAC expander with a built-in, auxiliary-power output. Each PAD-4 unit distributes additional power in buildings for audible and visual indicators that conform to the Americans with Disabilities Act (ADA). PAD-4 also has the following features:

NACs Signal-input circuits Battery-charging circuit Trouble relays for remote monitoring Diagnostic light-emitting diodes (LEDs) Alternating Current (AC) power connection

The Siemens NACs, which connect with alarm signaling devices, have been designed to provide the highest level of reliability and performance.

Signal coding on the circuits is accomplished through integrated circuits (rather than relays), which eliminates mechanical wear on the output circuits.

The PAD-4 unit provides constant 24VDC output voltage to each NAC − independent of voltage fluctuations on the primary or secondary power source. As a result, a larger voltage drop and a greater wire length for each NAC are supported by each PAD-4.

Specifications This version of the Siemens Distributed Power Supply Unit can be configured in the following manner that makes the outputs easily programmable:

‘STEADY’ outputs Synchronized strobe outputs

American National Standards Institute (ANSI) Temporal 3 ANSI Temporal 4 [for carbon monoxide (CO) alarm signal]

There are also two (2) inputs used to control the activation of the four (4) outputs. Programming can be set so one (1) input will silence the audible signal on Siemens Models ‘AS’-series, ‘NS’-series, or ‘ZH’-series horn and horn-strobes while the strobes remain active.

ARCHITECT AND ENGINEER SPECIFICATIONS

• Multi-module mounting in System 3™ enclosures Multiple modules share battery set

• ADA Compliant

• UL 864 9th Edition Listed, UL 1481 Listed;

FM (#3010), CSFM (#7315-0067:0268) Approved

`Class A’ Adapter Card

[Model PAD-4-CLSA]

Main Board [Model PAD-4-MB]

Unit Enclosure [Model PAD-4-ENCL]

• Four (4) ‘Class B’, power-limited notification appliance circuits (NACs)

• `Class A’, field-selectable wiring Each unit can support an optional module (Model PAD-4-CLSA) that converts two (2) built-in ‘Class A’ NACs into four (4) ‘Class A’ NACs

• Up to 3 Amps of auxiliary-power output

• Optional built-in strobe synchronization Supports coded audible signals, including Temporal 3, Temporal 4 patterns

• Battery supervision and control

• ‘Form C’ general Trouble / AC Fail monitoring contact

• Power supplies support NAC power Up to 6A used with Model FP2011-U1 Up to 9A used with Model FP2012-U1

• 24VDC output voltage

• Ground-fault detection

• Advanced microprocessor control

• Uses Flash memory-based system firmware Optional system-diagnostic and firmware-upgrade tool

Specifications ─ (continued)

Operation of each PAD-4 unit is controlled by firmware stored in Flash memory on the main board, as well as the storage of a 10-event log, which can be viewed via Model PAD-4-FDT.