C04c Attachment 3 Drawings 1160423.pdf
PDF 3 MB Posted
- Attached to
- Lighting Renovation for USDA ARS in Ames, IA (Amended) Federal contract opportunity
- Solicitation number
- 1232SA26Q0962
About this file
This document is a complete set of construction documents for the USDA National Center for Animal Health Building 7 Lighting and Controls Upgrade project located at 1920 Dayton Avenue, Ames, Iowa. The project, identified by USDA Contract Number 12505B23F0175, involves upgrading the lighting systems and installing new lighting control infrastructure throughout the facility's three operational levels, with construction documents dated September 25, 2023.
The scope of work includes complete removal and replacement of all existing luminaires on a one-for-one basis while retaining existing electrical wiring, installation of new lighting control devices in locations of existing equipment, and establishment of a centralized lighting control system with networked architecture located on the third-floor mechanical mezzanine. Key technical requirements include compliance with 2021 International Building Code, 2021 International Energy Conservation Code, and 2023 National Electrical Code standards. The project specifies a phased implementation approach coordinated with on-site operations teams to maintain continuous facility operation, with particular emphasis on preserving through-slab penetrations to prevent air transmission between research areas and mechanical spaces. The lighting control system utilizes Paradigm/Unison equipment with BACnet/IP communication protocol to the Building Automation System, including programmable controls for research suite holding areas with capabilities for schedule modification, light level adjustment (measured in footcandles), and moonlight functionality accessible through pass-code-protected graphical user interfaces at each suite entry point. Emergency lighting, exit signage, and washdown-rated equipment are specified throughout, with local override switches providing manual control with 30-minute timeout to return to preprogrammed schedules for cleaning operations.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| C05b Attachment 9 Q and A.pdf | ||
| C05 SF30 1232SA26Q09620001.pdf | ||
| C05a Attachment 8 Specifications Addendum.pdf | ||
| C04 SF1442 RFQ 1232SA26Q0962.pdf | ||
| C04a Attachment 1 Statement of Work 1160423.pdf | ||
| C04f Attachment 6 ARS_372_REQUEST FOR PAYMENT TRANSMITTAL.pdf | ||
| C04b Attachment 2 Specifications 1160423.pdf | ||
| C04g Attachment 7 SF1413 Subcontractor Acknowlegement.pdf | ||
| C04e Attachment 5 ARS_371_CONSTRUCTION PROGRESS.pdf | ||
| C04d Attachment 4 Wage Determination.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
D
ORDER DATE:
TASK ORDER NO.:
A
U S
DESCRIPTIONBYDATENO.
BAILEY EDWARD
DESIGN
EPM:
AOE:
BED PROJECT NO.:
CHECKED BY:
PROJECT MANAGER:
REAL PROPERTY:
SAFETY & HEALTH:
USDA
COPYRIGHT BAILEY EDWARD 2025 - BED# 23116
DWG. NO.
SHEET OF
AMES, IA 50010
1920 DAYTON AVENUE
NATIONAL CENTER FOR ANIMAL
HEALTH- BUILDING 7
BUILDING 7 LIGHTING AND CONTROLS UPGRADE
Agricultural Research Service
KWL
CHK
23116 t 312.440.2300 f 312.440.2303 www.baileyedward.com
35 East Wacker Dr Suite 2800 Chicago, IL 60601-2308 ©2024 Bailey Edward Design Design Firm License No. 184-001962
TBD
KARLA TEBBEN
BEN A'HEARN
TBDREO
1 8/12/2025 BED 100% CONSTRUCTION DOCUMENTS
12505B23F0175
25 September, 2023 33
Pr in t D at e/ Ti m e:
/1
1/
:1
PM
P:
\P ro je ct F ile s\
-0
0-
U
SD
A
N C
AH
B
LD
G
L
IG
H
TI
N
G R
EN
O
VA
TI
O N
D
ES
IG
N
\0 2_
C
AD
\M
EP
COVER SHEET
USDA NCAH BUILDING 7 LIGHTING RENOVATION
CODE INFORMATION & STANDARDS
2021 INTERNATIONAL BUILDING CODE
2021 INTERNATIONAL ENERGY CONSERVATION CODE
2021 INTERNATIONAL EXISTING BUILDING CODE
2021 INTERNATIONAL MECHANICAL CODE
INDEX - GENERAL
GENERAL PROJECT NOTES
USDA CONTRACT NO.: 12505B23F0175
1. THE CONTRACTOR SHALL COORDINATE, SCHEDULE, TEST AND PROVIDE ANY EFFORT NECESSARY TO RESULT IN A COMPLETE
AND OPERATING SYSTEM.
2. DETAILS SHOWN ARE INDICATIVE OF THE CHARACTER, PROFILES, MATERIAL, AND SYSTEMS REQUIRED FOR THE WORK. THE CONTRACTOR SHALL PROVIDE ALL EQUIPMENT, LABOR, SUNDRIES, TESTING AND REPORTING TO PROVIDE A COMPLETE AND OPERATIONAL SYSTEM. THE CONTRACTOR SHALL INCLUDE THOSE CONDITIONS NOT COVERED BY SPECIFIC DETAILS.
3. WHERE THE DESIGN INTENT CANNOT BE DETERMINED FROM THE DRAWINGS OR SPECIFICATIONS, CONSULT THE
CONTRACTING OFFICER'S REPRESENTATIVE BEFORE PROCEEDING WITH THE WORK.
4. FIELD VERIFY ALL CONDITIONS & DIMENSIONS BEFORE PROCEEDING WITH THIS WORK. IF CONDITIONS VARY FROM INFORMATION WITHIN THE CONTRACT DOCUMENTS, CONSULT THE ARCHITECT OR ENGINEER BEFORE PROCEEDING WITH
THE WORK.
5. THE CONTRACTOR SHALL NOTIFY THE CONTRACTING OFFICER'S REPRESENTATIVE OF ANY AND ALL DISCREPANCIES BETWEEN THE CONTRACT DOCUMENTS AND EXISTING CONDITIONS PRIOR TO PROCEEDING WITH THE WORK. PROVIDE RFI'S
DURING COORDINATION DRAWING EFFORT TO AVOID FIELD REVISIONS.
6. PROVIDE A FULL AND COMPLETE, OPERATING LIGHTING AND LIGHTING CONTROL SYSTEM.
7. ALL PENETRATIONS OF ROOF AND FIRE RATED WALL OR SMOKE PARTITIONS SHALL BE PATCHED & REPAIRED AS REQUIRED TO MAINTAIN THE EXISTING FIRE RATING OR SMOKE INFILTRATION INTEGRITY OF THE FLOOR AND WALL. ALL SLEEVES, WIREWAYS, CABLE TRAYS, PIPES, DUCTWORK, ARE TO BE FIRE SEALED TIGHT TO THE WALL OR FLOOR PENETRATIONS TO
MAINTAIN THE REQUIRED CODE COMPLIANT FIRE RATING.
8. THE CONTRACTOR IS RESPONSIBLE FOR THE TIMELY REMOVAL OF ALL DEMOLITION DEBRIS AND PROTECTION OF EXISTING AREAS WHICH ARE NOT AFFECTED BY THE SCOPE OF WORK. THE CONTRACTOR SHALL IMMEDIATELY NOTIFY THE CONTRACTING OFFICER'S REPRESENTATIVE OF ANY INCIDENTAL DAMAGE ASSOCIATED WITH THEIR EFFORTS. ANY DAMAGE TO THE PREMISES SHALL BE BROUGHT BACK TO ORIGINAL CONDITION AT THE COST OF THE GENERAL CONTRACTOR OR SUBCONTRACTOR INFLICTING THE DAMAGE. RUBBISH SHALL BE REMOVED DAILY AT THE END OF EACH SHIFT.
9. CONTRACTOR RESPONSIBLE FOR PROTECTING EXISTING WALL, CEILING, AND FLOOR FINISHES DURING CONSTRUCTION.
REPAIR ANY DAMAGES RESULTING FROM THIS PROJECT AT NO ADDITIONAL COST TO THE OWNER.
10. ALL SUBSTITUTIONS TO BE REVIEWED AND APPROVED IN WRITING BY ARCHITECT/ENGINEER REFER TO SPECIFICATIONS FOR
SUBSTITUTION PROCEDURES.
11. PROVIDE TEMPORARY PROTECTION FROM DUST, NOISE, DAMAGE, ETC. GRINDING OR HOT WORK SHALL BE ACCOMPANIED WITH SOURCE CAPTURE DEVICES TO REMOVE PARTICULATE AND ODORS. THE CONTRACTOR SHALL OBTAIN DAILY PERMITS
FOR HOT WORK.
12. MAINTAIN EXISTING BUILDING EXITS. THE BUILDING IS TO REMAIN IN COMPLIANCE WITH ALL ASPECTS OF THE LIFE SAFETY CODE DURING THE COURSE OF CONSTRUCTION INCLUDING BUT NOT LIMITED TO EXISTING FIRE ALARM SYSTEM, SMOKE AND
FIRE DETECTION SYSTEM, SPRINKLER SYSTEM, ETC. AS APPLICABLE.
13. INDIVIDUAL DRAWINGS ARE PART OF A LARGER SET OF DRAWINGS WHICH, WHEN COMPLETE CONSIST OF ALL DRAWINGS LISTED BY THE INDEX OF DRAWINGS. THE WORK DESCRIBED BY THE DRAWINGS OF ANY ONE DISCIPLINE MAY BE AFFECTED BY THE WORK DESCRIBED ON DRAWINGS OF ANOTHER DISCIPLINE AND MAY REQUIRE REFERENCE TO DRAWINGS OF ANOTHER DISCIPLINE. PARTIAL SETS OF DRAWINGS ARE INCOMPLETE AND SHALL NOT BE DISTRIBUTED AND UTILIZED BY THE CONTRACTOR. IT IS THE CONTRACTOR'S RESPONSIBILITY TO REVIEW AND COORDINATE THE WORK OF ALL SUBCONTRACTORS, TRADES, AND SUPPLIERS WITH THE REQUIREMENTS OF THE CONTRACT DOCUMENTS BEFORE COMMENCING CONSTRUCTION, AND TO ASSURE THAT ALL PARTIES ARE AWARE OF ALL REQUIREMENTS, REGARDLESS OF
WHERE THE REQUIREMENTS OCCUR ON THE CONTRACT DOCUMENTS.
14. THE CONTRACTOR IS RESPONSIBLE FOR COORDINATING THE WORK OF ALL SUBCONTRACTORS, TRADES, AND SUPPLIERS, THE CONTRACTOR SHALL ENDEAVOR TO IDENTIFY AND NOTIFY THE ARCHITECT OF ANY CONFLICTS BETWEEN THE WORK OF DIFFERENT PARTIES AT THE EARLIEST POSSIBLE DATE SO AS TO ALLOW REASONABLE AND ADEQUATE TIME FOR THE CONFLICT TO BE RESOLVED WITHOUT DELAYING THE WORK. ALL DEVIATIONS FROM THAT WHICH IS REQUIRED BY THE
CONTRACT DOCUMENTS MUST BE APPROVED IN ADVANCE BY THE OWNER.
15. THE CONTRACTOR SHALL COORDINATE LOCATIONS FOR STORAGE OF CONSTRUCTION MATERIALS, DUMPSTER ,TOOL STORAGE, AND LAY-DOWN SPACE WITH THE CONTRACTING OFFICER'S REPRESENTATIVE AND FIELD CONDITIONS.
16. THE CONTRACTOR SHALL MANAGE KICK-OFF AND PROGRESS MEETINGS EVERY OTHER WEEK, PROVIDE AGENDA RFI LOG, SUBMITTAL LOG, AND THREE WEEK LOOK AHEAD 24 HOURS IN ADVANCE OF THE MEETING. PROVIDE MINUTES FOR REVIEW
WITHIN 48 HOURS OF THE MEETING.
17. THE DRAWINGS REPRESENT DESIGN INTENT. THEY ARE SCALED GRAPHIC REPRESENTATIONS OF A LARGE BUILDING. THE DRAWINGS ARE DIAGRAMMATIC AND DO NOT SHOW ALL OFFSETS, FITTINGS, SUPPORTS, OR DEVICES TO RESULT IN A SUCCESSFUL INSTALLATION. THE CONTRACTOR SHALL COORDINATE WITH THE FIELD CONDITIONS, TRADES, AND EQUIPMENT
MANUFACTURES TO PROVIDE A FULL AND COMPLETE INSTALLATION.
18. SCHEDULE EFFORTS WITH COR. IDENTIFY LOCATIONS OWNER NEEDS TO REMOVE OR RELOCATE ITEMS TO FACILITATE
WORK.
19. PERFORMANCE OF ANY PATCHES SHALL ACCOMMODATE BIO-SAFTEY WASHDOWN REQUIREMENTS.
20. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ENSURING THAT DELIVERIES ARE MADE TO THE PROJECT SITE. DELIVERIES SHALL NOT BE MADE TO ANY OTHER BUILDING, USDA WAREHOUSE, OR OTHER LOCATION ON CAMPUS.
SCOPE OF WORK
1. THE PROJECT SHALL BE EXECUTED IN PHASES SO THAT RESEARCH CAN CONTINUE DURING CONSTRUCTION.
RESEARCH SUITES SHALL BE DECONTAMINATED BY THE USDA PRIOR TO COMMENCING WITH CONSTRUCTION IN THE
SUITE. THE CONTRACTOR SHALL DEVELOP AND SUBMIT A PHASING PLAN.
2. VISIT THE SITE TO WALK THROUGH THE SUITES, PLAN FOR COMPLETION OF CONSTRUCTION, PLAN FOR
STORAGE/STAGING, CHOOSE A DUMPSTER LOCATION AND BECOME FAMILIAR WITH THE SITE.
3. PROVIDE PRODUCT DATA SUBMITTALS, QUALIFICATIONS, CONTROL SHOP DRAWINGS, SCHEDULE, AND OTHER
DOCUMENTS REQUIRED BY THE SPECIFICATIONS.
4. PROVIDE EFFORTS TO REMOVE THE LIGHTS AND LIGHTING CONTROLS. DISPOSE OF ITEMS IN AN APPROPRIATE MANNER. RECYCLE METALLIC MATERIALS TO THE GREATEST EXTENT POSSIBLE. REFER TO SPECIFICATIONS FOR APPROPRIATE DISPOSAL. THE CONTRACTOR SHALL PROVIDE LOAD TICKETS/RECEIPT COPIES TO THE COR
5. PROVIDE AND INSTALL LIGHTS AND LIGHTING CONTROLS. REPAIR FINISHES DAMAGED OR EXPOSED DURING
CONSTRUCTION. FINISHES SHALL MATCH OR BLEND WITH THE PRE-ALTERATION FINISHES.
6. THE CONTRACTOR SHALL HIRE A VENDOR CERTIFIED TO INSTALL JOHNSON CONTROLS INCORPORATED METASYS BUILDING AUTOMATION SYSTEMS TO EXTEND THE BAS AS NECESSARY TO MONITOR THE LIGHTING CONTROLS. PROVIDE ENGINEERING, FIELD VERIFICATION, PROGRAMMING, AND GRAPHIC USER INTERFACE SO THAT ALARMS ARE TRANSMITTED FROM THE LIGHTING CONTROLS TO THE BUILDING AUTOMATION SYSTEM TO NOTIFY THE USDA
ENGINEERS OF A FAULT.
7. AT THE END OF EACH PHASE CONTRACTOR EFFORTS SHALL BE REVIEWED AND CORRECTIONS COMPLETED PRIOR TO
TURNOVER TO THE USDA.
8. PROVIDE EFFORTS TO COMMISSION THE LIGHTING UPGRADES AND THE LIGHTING CONTROLS UPGRADE. VERIFY
SEQUENCES OF OPERATIONS IS ACCOMMODATED BY CONTROLS AND PROGRAMMING.
9. SUBMIT TRAINING AGENDA FOR REVIEW. TRAINING SHALL BE RECORDED BY A PROFESSIONAL VIDEOGRAPHER.
10. PROVIDE CLOSEOUT DOCUMENTS INCLUDING WARRANTY, AS-BUILT DOCUMENTS, TESTING REPORTS, AND
COMMISSIONING REPORT.
SEQUENCE OF EFFORTS
1. SUBMIT NECESSARY FRONT END PAPERWORK, BONDS, INSURANCE.
2. OBTAIN ANY SECURITY CLEARANCES OR BACKGROUND CHECKS NECESSARY TO ACCESS FACILITY.
3. SUBMIT QUALIFICATION DATA FOR TECHNICAL TRADES. REFER TO PROJECT MANUAL.
4. VISIT THE SITE TO VERIFY EXISTING CONDITIONS AND PLAN FOR COMPLETION OF CONSTRUCTION.
5. DEVELOP AND SUBMIT COORDINATED SHOP DRAWINGS WITH SIGN OFF FROM THE TRADES. PROVIDE PRODUCT DATA.
DEVELOP STRATEGY FOR TEMPORARY LIGHTING. SUBMIT PLAN, NARRATIVE, ETC.
6. DEVELOP A SCHEDULE THAT OUTLINES KEY MILESTONES FOR EACH AREA OF THE BUILDING.
7. THE SCOPE OF WORK IN THE RESEARCH SUITES SHALL BE EXECUTED IN PHASES SO THAT RESEARCH IS ABLE TO CONTINUE. CONTRACTOR SHALL HAVE ACCESS TO A SINGLE SUITE AT ANY GIVEN TIME. THE CONTRACTOR SHALL GIVE NOTICE THAT THE PHASE IS COMPLETED AND SHALL OBTAIN NOTICE FROM THE USDA TO MOVE ON TO THE NEXT PHASE.
8. COORDINATE WITH THE USDA TO ENSURE THAT THE SPACES HAVE BEEN CLEARED AND DECONTAMINATED. VERIFY THAT SPACE PRESSURIZATION CONTROLS THROUGH THE BUILDING AUTOMATION SYSTEM HAVE BEEN ADJUSTED BY THE USDA
FOR THE ACTIVE CONSTRUCTION AREA. ENSURE THAT BUILDING PRESSURIZATION HAS
9. REMOVE LIGHTS AND CONTROLS FROM THE PHASE AREA.
10. PROVIDE AND INSTALL LIGHTS AND CONTROLS WITHIN THE PHASE AREA.
11. PROVIDE COMMISSIONING SERVICES WITHIN THE PHASED AREA. PROVIDE THE FINAL CX REPORT WITH CLOSEOUT.
12. COORDINATE WITH THE USDA TO ENSURE THAT BUILDING PRESSURIZATION HAS BEEN RETURNED TO NORMAL
OPERATION FOR EACH OF THE COMPLETED PHASES.
13. PERFORM TRAINING AFTER EACH PHASE HAS BEEN COMMISSIONED. THE FINAL TRAINING SESSION SHALL BE RECORDED
BY A PROFESSIONAL VIDEOGRAPHER.
14. PROVIDE CLOSEOUT DOCUMENTS.
15. PERFORM ANY WARRANTY WORK.
2023 NATIONAL ELECTRIC CODE
G000 COVER SHEET
G001 LOWER LEVEL GENERAL PLAN
PROJECT SUMMARY
UPGRADE THE LIGHTING AND THE LIGHTING CONTROLS SYSTEM. EXTEND THE BUILDING
AUTOMATION SYSTEM TO MONITOR THE LIGHTING CONTROLS.
AREA MAP
LOCATION MAP
NATIONAL CENTER FOR ANIMAL HEALTH
1920 DAYTON AVENUE, AMES, IA 50010
G002 FIRST FLOOR GENERAL PLAN
G003 PENTHOUSE GENERAL PLAN
INDEX - ELECTRICAL
USDA NATIONAL CENTER FOR
ANIMAL HEALTH (NCAH)
ELECTRICAL COVERSHEET
LEVEL 01 DEMOLITION PLAN - OVERALL - LIGHTING
LEVEL 01 DEMOLITION PLAN - AREA A - LIGHTING
LEVEL 01 DEMOLITION PLAN - AREA B - LIGHTING
LEVEL 01 DEMOLITION PLAN - AREA C - LIGHTING
LEVEL 02 DEMOLITION PLAN - OVERALL - LIGHTING
LEVEL 02 DEMOLITION PLAN - AREA A - LIGHTING
LEVEL 02 DEMOLITION PLAN - AREA B - LIGHTING
LEVEL 02 DEMOLITION PLAN - AREA C&D - LIGHTING
LEVEL 03 DEMOLITION PLAN - OVERALL - LIGHTING
LEVEL 03 DEMOLITION PLAN - AREA A - LIGHTING
LEVEL 03 DEMOLITION PLAN - AREA B - LIGHTING
LEVEL 03 DEMOLITION PLAN - AREA C - LIGHTING
LEVEL 01 PLAN - OVERALL - LIGHTING
LEVEL 01 PLAN - AREA A - LIGHTING
LEVEL 01 PLAN - AREA B - LIGHTING
LEVEL 01 PLAN - AREA C - LIGHTING
LEVEL 02 PLAN - OVERALL - LIGHTING
LEVEL 02 PLAN - AREA A - LIGHTING
LEVEL 02 PLAN - AREA B - LIGHTING
LEVEL 02 PLAN - AREA C&D - LIGHTING
LEVEL 03 PLAN - OVERALL - LIGHTING
LEVEL 03 PLAN - AREA A - LIGHTING
LEVEL 03 PLAN - AREA B - LIGHTING
LEVEL 03 PLAN - AREA C - LIGHTING
ELECTRICAL DETAILS
LIGHTING CONTROL SYSTEM DETAILS
LIGHTING CONTROL SYSTEM CONTACT SCHEDULES
ELECTRICAL SCHEDULES
E000 E101 E101A E101B E101C E102 E102A E102B E102C E103 E103A E103B E103C E201 E201A E201B E201C E202 E202A E202B E202C E203 E203A E203B E203C E400 E401 E402 E600
G000
TASK ORDER NO.:
A
U S
DESCRIPTIONBYDATENO.
BAILEY EDWARD
DESIGN
EPM:
AOE:
BED PROJECT NO.:
CHECKED BY:
PROJECT MANAGER:
REAL PROPERTY:
SAFETY & HEALTH:
USDA
COPYRIGHT BAILEY EDWARD 2025 - BED# 23116
DWG. NO.
SHEET OF
AMES, IA 50010
1920 DAYTON AVENUE
NATIONAL CENTER FOR ANIMAL
HEALTH- BUILDING 7
BUILDING 7 LIGHTING AND CONTROLS UPGRADE
Agricultural Research Service
KWL
CHK
23116 t 312.440.2300 f 312.440.2303 www.baileyedward.com
35 East Wacker Dr Suite 2800 Chicago, IL 60601-2308 ©2024 Bailey Edward Design Design Firm License No. 184-001962
TBD
KARLA TEBBEN
BEN A'HEARN
TBDREO
1 8/12/2025 BED 100% CONSTRUCTION DOCUMENTS
12505B23F0175
25 September, 2023 33
Pr in t D at e/ Ti m e:
/1
1/
:1 ro je ct F ile s\
-0
0-
U
SD
A
N C
AH
B
LD
G
L
IG
H
TI
N
G R
EN
O
VA
TI
O N
D
ES
IG
N
\0 2_
C
AD
\M
EP
LOWER LEVEL GENERAL PLAN
SCALE: 1/16" = 1'-0"
0 8' 16' 32'
GENERAL PLAN - LOWER LEVEL
G001
AutoCAD SHX Text
OS
AutoCAD SHX Text
OS
AutoCAD SHX Text
OS
AutoCAD SHX Text
OS
AutoCAD SHX Text
OS
AutoCAD SHX Text
AutoCAD SHX Text
TYPICAL
AutoCAD SHX Text
AutoCAD SHX Text
TYPICAL
AutoCAD SHX Text
AutoCAD SHX Text
TYPICAL
AutoCAD SHX Text
AutoCAD SHX Text
TYPICAL
AutoCAD SHX Text
AutoCAD SHX Text
TYPICAL
AutoCAD SHX Text
AutoCAD SHX Text
TYPICAL
AutoCAD SHX Text
AutoCAD SHX Text
TYPICAL
AutoCAD SHX Text
AutoCAD SHX Text
TYPICAL
AutoCAD SHX Text
%%UPLAN NOTES
AutoCAD SHX Text
1. THE CONTRACTOR SHALL VISIT THE SITE TO BECOME THE CONTRACTOR SHALL VISIT THE SITE TO BECOME FAMILIAR WITH THE FACILITY, VERIFY THE EXISTING CONDITIONS, AND PLAN FOR COMPLETION ON THE PROJECT. 2. THE CONTRACTOR SHALL DEVELOP A SCHEDULE WITH THE CONTRACTOR SHALL DEVELOP A SCHEDULE WITH MILESTONE TO DEMONSTRATE COMPLETION OF IMPORTANT TASK AND PHASING. 3. THE PROJECT SHALL BE EXECUTED IN PHASES SO THAT A THE PROJECT SHALL BE EXECUTED IN PHASES SO THAT A PORTION OF THE RESEARCH SUITES ARE AVAILABLE FOR RESEARCHERS. COORDINATE SHUT DOWN OF RESEARCH SUITES WITH THE USDA. INCLUDE THE PHASING IN THE PROJECT SCHEDULE. 4. PROVIDE PRODUCT DATA, QUALIFICATIONS, SHOP DRAWINGS PROVIDE PRODUCT DATA, QUALIFICATIONS, SHOP DRAWINGS AND SUBMITTALS FOR REVIEW AND COMMENT. 5. EFFORTS SHALL BE PERFORMED IN A SAFE, NEAT AND EFFORTS SHALL BE PERFORMED IN A SAFE, NEAT AND ORDERLY FASHION BY SKILLED CRAFT WORKERS EXPERIENCED IN THE SPECIFIC TRADE. 6. THE USDA SHALL DECONTAMINATE RESEARCH PRIOR TO THE USDA SHALL DECONTAMINATE RESEARCH PRIOR TO CONTRACTOR ACCESS TO THE SPACE. THE CONTRACTOR SHALL COORDINATE ACCESS TO THE RESEARCH SPACES WITH THE USDA. 7. COORDINATE LOCATIONS FOR DUMPSTER, DELIVERY AND COORDINATE LOCATIONS FOR DUMPSTER, DELIVERY AND STORAGE OF EQUIPMENT WITH THE USDA. PROVIDE DUMPSTER SERVICE AND TEMPORARY FACILITY TO STORE PRODUCTS THAT HAVE BEEN DELIVERED AND ARE AWAITING INSTALLATION. 8. CLEAR THE WORK SITE AT THE END OF EACH SHIFT TO CLEAR THE WORK SITE AT THE END OF EACH SHIFT TO ENSURE THE FACILITY IS FREE OF CONSTRUCTION DEBRIS. 9. THE CONTRACTOR SHALL PATCH AND REPAIR FINISHES THE CONTRACTOR SHALL PATCH AND REPAIR FINISHES IMPACTED BY THE WORK EFFORTS. COORDINATE SEQUENCING OF WORK AMONGST THE TRADES. 10. SUBMIT CLOSEOUT DOCUMENTS INCLUDING TESTING SUBMIT CLOSEOUT DOCUMENTS INCLUDING TESTING REPORTS, AS-BUILT DRAWINGS, WARRANTY, OPERATIONS MANUAL AND LOAD TICKETS/RECEIPTS FROM RECYCLED MATERIALS. 11. PROVIDE TEMPORARY LIGHTING DURING CONSTRUCTION PROVIDE TEMPORARY LIGHTING DURING CONSTRUCTION EFFORTS TO ACCOMMODATE SHUT DOWNS OF CIRCUITS DURING LIGHTING UPGRADES.
AutoCAD SHX Text
%%UKEYNOTES
AutoCAD SHX Text
1. UPGRADE LIGHT FIXTURE. REPAIR FINISHES DISRUPTED UPGRADE LIGHT FIXTURE. REPAIR FINISHES DISRUPTED BY REMOVAL AND REPLACEMENT. 2. UPGRADE EMERGENCY LIGHT FIXTURE. REPAIR FINISHES UPGRADE EMERGENCY LIGHT FIXTURE. REPAIR FINISHES DISRUPTED BY REMOVAL AND REPLACEMENT. 3. UPGRADE THE OCCUPANCY SENSOR. REPAIR FINISHES UPGRADE THE OCCUPANCY SENSOR. REPAIR FINISHES DISRUPTED BY EFFORTS TO UPGRADE.
AutoCAD SHX Text
%%ULEGEND
AutoCAD SHX Text LIGHT FIXTURE NIGHT LIGHT FIXTURE BATTERY EMERGENCY FIXTURE EMERGENCY FIXTURE WITH REMOTE BATTERY EXIT SIGN OCCUPANCY SENSOR
AutoCAD SHX Text
OS
TASK ORDER NO.:
A
U S
DESCRIPTIONBYDATENO.
BAILEY EDWARD
DESIGN
EPM:
AOE:
BED PROJECT NO.:
CHECKED BY:
PROJECT MANAGER:
REAL PROPERTY:
SAFETY & HEALTH:
USDA
COPYRIGHT BAILEY EDWARD 2025 - BED# 23116
DWG. NO.
SHEET OF
AMES, IA 50010
1920 DAYTON AVENUE
NATIONAL CENTER FOR ANIMAL
HEALTH- BUILDING 7
BUILDING 7 LIGHTING AND CONTROLS UPGRADE
Agricultural Research Service
KWL
CHK
23116 t 312.440.2300 f 312.440.2303 www.baileyedward.com
35 East Wacker Dr Suite 2800 Chicago, IL 60601-2308 ©2024 Bailey Edward Design Design Firm License No. 184-001962
TBD
KARLA TEBBEN
BEN A'HEARN
TBDREO
1 8/12/2025 BED 100% CONSTRUCTION DOCUMENTS
12505B23F0175
25 September, 2023 33
Pr in t D at e/ Ti m e:
/1
1/
:1 ro je ct F ile s\
-0
0-
U
SD
A
N C
AH
B
LD
G
L
IG
H
TI
N
G R
EN
O
VA
TI
O N
D
ES
IG
N
\0 2_
C
AD
\M
EP
FIRST FLOOR GENERAL PLAN
SCALE: 1/16" = 1'-0"
0 8' 16' 32'
GENERAL PLAN - FIRST FLOOR
G002
AutoCAD SHX Text b
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text f
AutoCAD SHX Text d
AutoCAD SHX Text r
AutoCAD SHX Text p
AutoCAD SHX Text s
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text d
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text r
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text HL3-11k
AutoCAD SHX Text
AutoCAD SHX Text
TYPICAL
AutoCAD SHX Text
AutoCAD SHX Text
TYPICAL
AutoCAD SHX Text
AutoCAD SHX Text
TYPICAL
AutoCAD SHX Text
AutoCAD SHX Text
TYPICAL
AutoCAD SHX Text
AutoCAD SHX Text
TYPICAL
AutoCAD SHX Text P
AutoCAD SHX Text
OS
AutoCAD SHX Text
OS
AutoCAD SHX Text
OS
AutoCAD SHX Text
OS
AutoCAD SHX Text
OS
AutoCAD SHX Text
OS
AutoCAD SHX Text
OS
AutoCAD SHX Text
OS
AutoCAD SHX Text
OS
AutoCAD SHX Text
OS
AutoCAD SHX Text
OS
AutoCAD SHX Text
OS
AutoCAD SHX Text
OS
AutoCAD SHX Text
OS
AutoCAD SHX Text L
AutoCAD SHX Text
OS
AutoCAD SHX Text
OS
AutoCAD SHX Text
OS
AutoCAD SHX Text
OS
AutoCAD SHX Text
OS
AutoCAD SHX Text
OS
AutoCAD SHX Text
OS
AutoCAD SHX Text
OS
AutoCAD SHX Text
OS
AutoCAD SHX Text
OS
AutoCAD SHX Text
OS
AutoCAD SHX Text
OS
AutoCAD SHX Text
OS
AutoCAD SHX Text
OS
AutoCAD SHX Text
MH
AutoCAD SHX Text
MH
AutoCAD SHX Text
MH
AutoCAD SHX Text
AREA WITHIN BORDERS REPRESENT THE RESEARCH SUITES.
AutoCAD SHX Text
RESEARCH VESTIBULE
AutoCAD SHX Text
RESEARCH VESTIBULE
AutoCAD SHX Text
RESEARCH VESTIBULE
AutoCAD SHX Text
RESEARCH VESTIBULE
AutoCAD SHX Text
RESEARCH VESTIBULE
AutoCAD SHX Text
ANIMAL HOLDING
AutoCAD SHX Text
ANIMAL HOLDING
AutoCAD SHX Text
ANIMAL HOLDING
AutoCAD SHX Text
ANIMAL HOLDING
AutoCAD SHX Text
ANIMAL HOLDING
AutoCAD SHX Text
ANIMAL HOLDING
AutoCAD SHX Text
ANIMAL HOLDING
AutoCAD SHX Text
ANIMAL HOLDING
AutoCAD SHX Text
ANIMAL HOLDING
AutoCAD SHX Text
ANIMAL HOLDING
AutoCAD SHX Text
ANIMAL HOLDING
AutoCAD SHX Text
ANIMAL HOLDING
AutoCAD SHX Text
ANIMAL HOLDING
AutoCAD SHX Text
ANIMAL HOLDING
AutoCAD SHX Text
ANIMAL HOLDING
AutoCAD SHX Text
ANIMAL HOLDING
AutoCAD SHX Text
ANIMAL HOLDING
AutoCAD SHX Text
%%UKEYNOTES
AutoCAD SHX Text
1. UPGRADE LIGHT FIXTURE. REPAIR FINISHES DISRUPTED UPGRADE LIGHT FIXTURE. REPAIR FINISHES DISRUPTED BY REMOVAL AND REPLACEMENT. 2. UPGRADE EMERGENCY LIGHT FIXTURE. REPAIR FINISHES UPGRADE EMERGENCY LIGHT FIXTURE. REPAIR FINISHES DISRUPTED BY REMOVAL AND REPLACEMENT. 3. UPGRADE THE OCCUPANCY SENSOR. REPAIR FINISHES UPGRADE THE OCCUPANCY SENSOR. REPAIR FINISHES DISRUPTED BY EFFORTS TO UPGRADE. 4. UPGRADE EXTERIOR LIGHTS, REPAIR FINISHES UPGRADE EXTERIOR LIGHTS, REPAIR FINISHES DISRUPTED BY EFFORTS TO UPGRADE. 5. UPGRADE CONTROLS FOR THE LIGHTING.UPGRADE CONTROLS FOR THE LIGHTING.
AutoCAD SHX Text
%%ULEGEND
AutoCAD SHX Text LIGHT FIXTURE NIGHT LIGHT FIXTURE BATTERY EMERGENCY FIXTURE EMERGENCY FIXTURE WITH REMOTE BATTERY EXIT SIGN OCCUPANCY SENSOR EXTERIOR LIGHT FIXTURE
OS
TASK ORDER NO.:
A
U S
DESCRIPTIONBYDATENO.
BAILEY EDWARD
DESIGN
EPM:
AOE:
BED PROJECT NO.:
CHECKED BY:
PROJECT MANAGER:
REAL PROPERTY:
SAFETY & HEALTH:
USDA
COPYRIGHT BAILEY EDWARD 2025 - BED# 23116
DWG. NO.
SHEET OF
AMES, IA 50010
1920 DAYTON AVENUE
NATIONAL CENTER FOR ANIMAL
HEALTH- BUILDING 7
BUILDING 7 LIGHTING AND CONTROLS UPGRADE
Agricultural Research Service
KWL
CHK
23116 t 312.440.2300 f 312.440.2303 www.baileyedward.com
35 East Wacker Dr Suite 2800 Chicago, IL 60601-2308 ©2024 Bailey Edward Design Design Firm License No. 184-001962
TBD
KARLA TEBBEN
BEN A'HEARN
TBDREO
1 8/12/2025 BED 100% CONSTRUCTION DOCUMENTS
12505B23F0175
25 September, 2023 33
Pr in t D at e/ Ti m e:
/1
1/
:2 ro je ct F ile s\
-0
0-
U
SD
A
N C
AH
B
LD
G
L
IG
H
TI
N
G R
EN
O
VA
TI
O N
D
ES
IG
N
\0 2_
C
AD
\M
EP
SCALE: 1/16" = 1'-0"
0 8' 16' 32'
LIGHTING - MEZZANINE
FIRST FLOOR GENERAL PLAN
G003
AutoCAD SHX Text
OS
AutoCAD SHX Text
OS
AutoCAD SHX Text
AutoCAD SHX Text P
AutoCAD SHX Text P
AutoCAD SHX Text P
AutoCAD SHX Text P
AutoCAD SHX Text P
AutoCAD SHX Text
LOCATION OF BUILDING AUTOMATION SYSTEM
AutoCAD SHX Text
AutoCAD SHX Text
TYPICAL
AutoCAD SHX Text
AutoCAD SHX Text
TYPICAL
AutoCAD SHX Text
AutoCAD SHX Text
TYPICAL
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
CNTL
AutoCAD SHX Text
CNTL
AutoCAD SHX Text
%%UKEYNOTES
AutoCAD SHX Text
1. UPGRADE LIGHT FIXTURE. REPAIR FINISHES DISRUPTED UPGRADE LIGHT FIXTURE. REPAIR FINISHES DISRUPTED BY REMOVAL AND REPLACEMENT. 2. UPGRADE EMERGENCY LIGHT FIXTURE. REPAIR FINISHES UPGRADE EMERGENCY LIGHT FIXTURE. REPAIR FINISHES DISRUPTED BY REMOVAL AND REPLACEMENT. 3. UPGRADE THE OCCUPANCY SENSOR. REPAIR FINISHES UPGRADE THE OCCUPANCY SENSOR. REPAIR FINISHES DISRUPTED BY EFFORTS TO UPGRADE. 4. THE LIGHTING CONTROL SYSTEM SHALL BE UPGRADED THE LIGHTING CONTROL SYSTEM SHALL BE UPGRADED AND TIED INTO THE BUILDING AUTOMATION SYSTEM, COORDINATE EFFORTS AMONGST THE CONTRACTORS AND USDA STAKEHOLDERS.
AutoCAD SHX Text
%%ULEGEND
AutoCAD SHX Text LIGHT FIXTURE NIGHT LIGHT FIXTURE BATTERY EMERGENCY FIXTURE EMERGENCY FIXTURE WITH REMOTE BATTERY EXIT SIGN OCCUPANCY SENSOR MAIN CONTROLLER FOR LIGHTING CONTROLS
AutoCAD SHX Text
OS
CNTL
1. THE COMPLETE INSTALLATION SHALL BE IN ACCORDANCE WITH THE ADA STANDARDS FOR
ACCESSIBLE DESIGN. REFER TO THE ADA GUIDELINES FOR ALL CONFIGURATION DETAILS ON
THIS PAGE FOR ADDITIONAL INFORMATION.
2. CIRCUIT NUMBERS ARE SHOWN FOR CIRCUIT IDENTIFICATION. CIRCUITING SHALL AGREE
WITH NUMBERING ON THE PANEL PROVIDED. COMMON NEUTRALS MAY NOT BE USED FOR
BRANCH CIRCUITS. BALANCE THE LOAD ON PANEL AS EVENLY AS POSSIBLE BETWEEN EACH
PHASE.
3. SURFACE MOUNT ALL LIGHTING CONTROL DEVICES AT +42" FROM FLOOR (CENTERLINE
DIMENSION), EXCEPT WHERE OTHERWISE NOTED.
4. ALL MATERIALS USED TO SEAL PENETRATIONS OF FIRE RATED WALLS AND FLOORS SHALL
BE TESTED AND CERTIFIED AS A SYSTEM PER ASTM E814 STANDARDS FOR FIRE TESTS OF
THROUGH-PENETRATION FIRESTOPS. REFER TO 26 05 03 FOR ADDITIONAL INFORMATION AND
REQUIREMENTS SPECIFIC TO FIRESTOPPING.
5. CONTRACTOR SHALL COORDINATE THE LOCATION OF ALL CEILING MOUNTED DEVICES AND
EQUIPMENT WITH LUMINAIRES, SPRINKLER, AND CEILING DIFFUSERS. OCCUPANCY/VACANCY
SENSORS SHALL BE LOCATED NO CLOSER THAN 3 FEET TO AN AIR SUPPLY DIFFUSER OR
RETURN GRILLE.
6. ELECTRICAL AND TECHNOLOGY EQUIPMENT SHALL BE MOUNTED TO AVOID IMPEDANCE OF,
OPERATION OF, AND/OR ACCESS TO ELECTRICAL AND MECHANICAL EQUIPMENT. ALL
MOUNTING OF ELECTRICAL AND TELECOMMUNICATIONS EQUIPMENT, ON EQUIPMENT
SUPPLIED BY ANOTHER CONTRACTOR, SHALL BE APPROVED IN ADVANCE BY THE OTHER
CONTRACTOR.
7. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL OPENINGS REQUIRED IN WALLS. ALL
OPENINGS SHALL BE REPAIRED TO MATCH EXISTING BY A QUALIFIED CONTRACTOR AT THE
EXPENSE OF THIS CONTRACTOR. ALL CONDUITS THROUGH WALLS SHALL BE GROUTED OR
SEALED INTO OPENINGS. CONTRACTOR WILL BE RESPONSIBLE FOR MEETING BIOSAFETY
REQUIREMENTS AS LAID OUT BY COR FOR ANY PATCHES.
8. EACH CONTRACTOR IS RESPONSIBLE FOR DAMAGE CAUSED BY THEIR ACTIONS TO THE
WALLS, FLOORS, CEILINGS, AND ROOFS. THE CONTRACTOR WHOSE WORK CAUSES DAMAGE
IS RESPONSIBLE FOR PATCHING TO MATCH ORIGINAL CONSTRUCTION, FIRE RATING, AND
FINISH. CONTRACTOR WILL BE RESPONSIBLE FOR MEETING BIOSAFETY REQUIREMENTS AS
LAID OUT BY COR FOR ANY PATCHES.
ELECTRICAL INSTALLATION NOTES:
1. EXISTING CONDITIONS ARE SHOWN BASED ON INFORMATION OBTAINED FROM FIELD
SURVEYS, EXISTING BUILDING DOCUMENTS. CONTRACTOR SHALL REVIEW EXISTING
CONDITIONS AND REPORT CONFLICTS.
2. NOT ALL EXISTING EQUIPMENT, LUMINAIRES, AND CONDUIT ARE SHOWN. CONTRACTOR
SHALL REVIEW EXISTING CONDITIONS AND REPORT CONFLICTS.
3. ELECTRICAL CONTRACTOR SHALL REVIEW EXISTING CONDITIONS TO VERIFY ACCESSIBILITY
TO THE AREAS OF THEIR WORK INCLUDING WALLS, FLOOR, CEILINGS, CEILING TILES/GRID,
AND ROOF. ELECTRICAL CONTRACTOR IS RESPONSIBLE TO PROVIDE CUTTING, REMOVAL,
PATCHING, AND REINSTALLATION OF AFFECTED AREAS ASSOCIATED WITH THEIR WORK BY
COORDINATING WITH THE GENERAL CONTRACTOR OR QUALIFIED CONTRACTOR.
4. WHERE EXISTING ELECTRICAL SYSTEMS ARE LOCATED IN AREAS THAT CONFLICT WITH NEW
EQUIPMENT, PIPING, OR DUCTWORK TO BE INSTALLED, EACH CONTRACTOR SHALL EITHER
ARRANGE NEW EQUIPMENT, CONDUIT, OR DUCTWORK IN SUCH A FASHION THAT IT DOES
NOT CONFLICT WITH EXISTING SYSTEMS, OR REWORK EXISTING ELECTRICAL SYSTEMS TO
ALLOW FOR INSTALLATION OF NEW EQUIPMENT, PIPING, OR DUCTWORK.
ELECTRICAL RENOVATION NOTES:
THESE NOTES APPLY TO ALL ELECTRICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED
TO, LIGHTING, POWER, FIRE ALARM, AND OTHER LOW VOLTAGE SYSTEMS.
ELECTRICAL PHASING NOTES:
THESE NOTES APPLY TO ALL ELECTRICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED
TO, LIGHTING, POWER, FIRE ALARM, AND OTHER LOW VOLTAGE SYSTEMS.
1. COORDINATE WITH OWNER AND BAILEY EDWARDS PRIOR TO ANY WORK ON PROJECT TO
DEVELOP A PHASING SCHEDULE DUE TO THE SENSITIVE NATURE OF THE RESEARCH IN THIS
FACILITY.
2. ELECTRICAL DRAWINGS DEPICT THE INTENT OF THE FINAL DESIGN. THE ELECTRICAL
DRAWINGS DO NOT DEPICT THE MEANS AND METHODS TO MEET THE REQUIREMENTS OF
THE PHASING CRITERIA.
3. REVIEW PROJECT PHASING PLANS TO COORDINATE DEMOLITION WORK, OUTAGES, ETC.
WITH AFFECTED ADJACENT AREAS.
4. PROVIDE TEMPORARY LIGHTING, POWER, FIRE ALARM, AND OTHER LOW VOLTAGE
SYSTEMS, ETC. AS NEEDED TO MAINTAIN SERVICE TO ALL AREAS DURING ALL PHASES OF
PROJECT.
PLAN OR DETAIL NUMBER
PLAN OR DETAIL NAME
PLAN OR DETAIL SCALE
DETAIL REFERRED TO BY SECTION CUT
SHEET DETAIL IS LOCATED ON
NAME
VIEW NAME
1/8" = 1'-0"
M101
SIMSIM
INDICATES SIMILAR DETAIL REFERENCED
IN MULTIPLE LOCATIONS
LEVEL NAME
10'-0" HEIGHT ABOVE
PROJECT 0'-0"
1 KEYNOTE: INDICATES NOTE USED TO
DESCRIBE ADDITIONAL INFORMATION
ABOUT WORK REQUIRED, SPECIFIC
TO THE SHEET AND/OR DETAIL
N O R
HT
INDICATES DIRECTION OF TRUE NORTH
VIEW KEY
LINE TYPE AND TAG KEY:
NEW WORK BY THIS CONTRACTOR (WIDE LINE)
NEW
EXISTING TO BE REMOVED (SHORT DASHED PATTERN)
NEW UNDERFLOOR OR UNDERGROUND (LONG DASHED PATTERN)
EXISTING TO REMAIN OR WORK BY OTHERS (NARROW LINE)
EXISTING
EXISTING TO BE REMOVED BY OTHERS (SHORT DASHED PATTERN)
EXISTING UNDERFLOOR OR UNDERGROUND (LONG DASHED PATTERN)
HALFTONING DOES NOT MODIFY SCOPE.
'TAG'-E TAGS WITH DASH 'E' INDICATES THE REFERENCED OBJECT IS EXISTING
TAG-1 UNDERLINED TAG INDICATES OBJECT IS IN-SCOPE. IF NEW, ADDITIONAL
INFORMATION IS AVAILABLE IN A SCHEDULE, MATERIAL LIST, OR SYMBOL LIST
INDICATES AN EXISTING SYSTEM'S POINT OF CONNECTION/REMOVAL
T101
TEMPERATURE CONTROLS CONTRACTORT.C.C.
SECURITY CONTRACTORS.C.
AUDIO/VISUAL CONTRACTORA.V.C.
NURSE CALL CONTRACTORN.C.C.
CIVIL CONTRACTORC.C.
ASBESTOS ABATEMENT CONTRACTOR
FIRE PROTECTION CONTRACTORF.P.C.
HEATING CONTRACTORH.C.
PLUMBING CONTRACTORP.C.
GENERAL CONTRACTORG.C.
MECHANICAL CONTRACTORM.C.
VENTILATION CONTRACTORV.C.
ELECTRICAL CONTRACTORE.C.
A.C.
CONTRACTOR ABBREVIATION KEY
ABBR: DESCRIPTION:
TECHNOLOGY CONTRACTORT.C.
CONSTRUCTION MANAGERC.M.
FOOD SERVICE CONTRACTORF.S.C.
CONTACT PERSONS:
PROJECT MANAGER
LIGHTING AND CONTROLS:
RYNE OBENAUF, BAILEY EDWARDS
CHRIS WOJTAL, IMEG
DESCRIPTION: PERSON:
BUILDING CODE: IBC 2021 EDITION
ELECTRICAL CODE: NEC 2023 EDITION
ENERGY CONSERVATION CODE: IECC 2021
HEALTH DEPARTMENT CODE: CURRENT EDITION
LOCAL BUILDING CODE: CURRENT EDITION
APPLICABLE CODES
CONTRACTOR SHALL COMPLY WITH APPLICABLE CODES AND LOCAL AMENDMENTS
INCLUDING, BUT NOT LIMITED TO, THE FOLLOWING:
SW-1P
26 09 34
SW-1P-EM
SW-2P
SW-3W
SW-1P-WP
SW-O
SW-O2
OC 26 09 34
SW-1P-K
SW-2P-K
SW-3W-K
SW-4W-K
ELECTRICAL SYMBOL LIST
SYMBOL: SPEC
TAG:
SPEC
SECTION:
DESCRIPTION:
SW-#B LIGHTING CONTROL STATION - DEFAULT
DIMMED CONTROL - # DEFINES MINIMUM
QUANTITY OF CONTROL SCENES, PLUS OFF,
REFER TO LIGHTING SEQUENCE OF
OPERATIONS WHEN NOT DEFINED.
SUBSCRIPTS:
BLANK = DIMMING CONTROL
S = SWITCHED CONTROL
W = WIRELESS WITH BATTERY
# = UNIQUE ID WHEN APPLICABLE
26 09 34#B
LCD SW-LCD LCD LIGHTING CONTROL - CUSTOM
PROGRAMMING
SUBSCRIPTS:
BLANK = DIMMING CONTROL
S = SWITCHED CONTROL
# = UNIQUE ID WHEN APPLICABLE
26 09 34
SW-D
SW-D3
SW-DML
SW-DO
SWITCH
SUBSCRIPTS:
BLANK = SINGLE POLE
2 = TWO POLE
3 = THREE WAY
4 = FOUR WAY
D = DIMMER - STAND ALONE
D3=DIMMER - THREE WAY WITH S3 TYPE
DML=DIMMER - MULTI-LOCATION FADE
CONTROL [NTS: RESIDENTIAL USE -
DIFFERS FROM #B PUSH BUTTON DIMMER]
DO=DIMMER - OCCUPANCY/VACANCY
SENSORS - DUAL TECHNOLOGY
ULTRASONIC/ACOUSTIC AND PIR
W = WEATHERPROOF
O = DUAL TECHNOLOGY OCCUPANCY SENSOR
WITH WALL SWITCH
O2=OCCUPANCY SENSOR AND DUAL SWITCH
K = SINGLE POLE - KEY LOCK
K2=TWO POLE - KEY LOCK
K3=THREE WAY - KEY LOCK
K4=FOUR WAY - KEY LOCK
E = SINGLE POLE - EMERGENCY
3E=THREE WAY - EMERGENCY
4E=FOUR WAY - EMERGENCY
P = SINGLE POLE - RED PILOT LIGHT
L = SINGLE POLE - LIGHTED HANDLE
M = THREE POSITION MOMENTARY
60= LOCAL TIMER - SPRING WOUND
T = LOCAL TIMER - USER ADJUSTABLE
X = SINGLE POLE - EXPLOSION PROOF
SW-4W
SW-3W-EM
SW-4W-EM
SW-1P-PL
SW-1P-LH
SW-1P-M
SW-1P-060
SW-1P-ADJ
SW-1P-EX
OCCUPANCY SENSOR - CEILING MOUNTED
SUBSCRIPTS:
BLANK = DUAL TECHNOLOGY
A = ULTRASONIC - TWO SIDED CORRIDOR
COVERAGE
P = PASSIVE INFRARED - 360° COVERAGE
P2=PASSIVE INFRARED - 100° COVERAGE
U = ULTRASONIC - 360° COVERAGE
HA=HIGHBAY - ISLE COVERAGE
HB=HIGH BAY
W = WIRELESS WITH BATTERY
SW-OC-D
SW-OC-A
SW-OC-P
SW-OC-P2
SW-OC-U
SW-OC-HA
SW-OC-HB
SW-OC-W
PC
SW-LS-PC 26 09 33 PHOTO CELL
LINEAR LUMINAIRES
TROFFER
WALL SCONCE LUMINAIRE
DOWNLIGHT LUMINAIRE
AIMABLE OR WALL WASH LUMINAIRE
INDUSTRIAL LUMINAIRE
SINGLE FACE EXIT SIGN
DOUBLE FACE EXIT SIGN
EMERGENCY UNIT
WALL BRACKET LUMINAIRE
ELECTRICAL SYMBOL LIST
SYMBOL: TAG: SPEC
SECTION:
DESCRIPTION:
WALL/CEILING EMERGENCY EXIT SIGN
REFER TO LUMINAIRE
SCHEDULE
LUMINAIRE
F1 = FIXTURE TAG
1 = CIRCUIT NUMBER
a = SWITCH DESIGNATION z1=ZONE DESIGNATION
"NL" INDICATES LUMINAIRE IS UNSWITCHED FOR NIGHT LIGHT.
"SE" INDICATES LUMINAIRE IS SWITCHED/CONTROLLED DURING NORMAL
OPERATION AND OPERATES FROM EMERGENCY CIRCUIT UPON LOSS OF POWER.
*IF LABEL IS ORIENTED HORIZONTALLY A SLASH WILL SEPARATE THIS
INFORMATION. EX: F1 / 1 / a / NL
LUMINAIRE CIRCUIT AND CONTROL KEY
THE DESIGN DOCUMENTS DESCRIBE THE OPERATIONAL PERFORMANCE REQUIREMENTS OF THE
LIGHTING CONTROL SYSTEM. THE PROJECT MAY REQUIRE ONE OR MORE LIGHTING CONTROL
STRATEGIES FOR THE PROJECT. REFER TO THE ELECTRICAL SYMBOL KEY, SPECIFICATION
SECTION 26 09 34 LIGHTING CONTROL SYSTEMS, AND THE DRAWINGS TO DETERMINE THE
DESIGN APPLICATION FOR EACH SPACE. THE POTENTIAL STRATEGICS ARE AS FOLLOWS:
1. STANDALONE LIGHTING CONTROL DEVICES: INDEPENDENT (STANDALONE) DEVICES
TRADITIONALLY OPERATING AT LINE OR LOW VOLTAGE, FIELD CONFIGURABLE WITH
OTHER STANDALONE DEVICES TO PROVIDE AN OVERALL LIGHTING CONTROL SYSTEM.
2. ROOM BASED LIGHTING CONTROLS: INTEGRATED SYSTEM COMPRISED OF SWITCH
STATIONS, SENSORS, ROOM CONTROLLERS, CONTROL PANELS, AND ACCESSORIES,
OPERATING AT LINE AND/OR LOW VOLTAGE, CONFIGURED AS AN INTEGRATED OVERALL
‘INTELLIGENT’ LIGHTING CONTROL SYSTEM. LIGHTING CONTROL ZONES AND POWER
CIRCUITS COMMONLY ALIGN.
3. NETWORK BASED LIGHTING CONTROLS: INTEGRATED SYSTEM COMPRISED OF SWITCH
STATIONS, SENSORS, ROOM CONTROLS, CONTROL PANELS, DIMMER RACKS, AND
ACCESSORIES, OPERATING AT LINE AND/OR LOW VOLTAGE, CONFIGURED AS AN
INTEGRATED OVERALL 'INTELLIGENT' LIGHTING CONTROL SYSTEM FOR ADVANCED
ARCHITECTURALLY BASED LIGHTING CONTROL SYSTEMS. LIGHTING CONTROL ZONES
COMMONLY ASSOCIATED WITH ONE OR MORE BRANCH POWER CIRCUITS WITHIN THE
SAME CONTROL ZONE.
LIGHTING CONTROL SYSTEM DESIGNATION: THE FOLLOWING KEY MAY BE USED AS AN EXAMPLE
TO DETERMINE THE DESIGNATED LIGHTING CONTROL SYSTEM FOR EACH SPACE. REFER TO
ELECTRICAL COVERSHEET FOR ELECTRICAL SYMBOLS LIST AND DEVICE SPECIFICATION
TAG. REFER TO THE SPECIFICATIONS FOR ADDITIONAL INFORMATION.
1. STANDALONE LIGHTING CONTROL DEVICES: CONTROL STATION COMMONLY
DEFINED BY AN ALPHA CHARACTER WITH SUBSCRIPTS.
A. EXAMPLE SYMBOL “S”, SPECIFICATION TAG "SW-1P", DESCRIPTION "SWITCH-
SINGLE POLE SWITCH".
B. EXAMPLE CONTROL DESIGNATION: a, b, c (WHEN REQUIRED TO CLARIFY DESIGN
INTENT).
C. SINGLE POLE LIGHT SWITCH "SA" CONTROLS LUMINAIRES WITH THE SUBSCRIPT
“a” WITHIN THE SAME SPACE.
D. REFER TO THE LIGHT CONTROL SEQUENCE OF OPERATION TAG {L#-##} FOR A
COMPLETE DESCRIPTION OF THE LIGHTING CONTROL REQUIREMENTS.
2. ROOM BASED LIGHTING CONTROLS: CONTROL STATION COMMONLY DEFINED BY A
RECTANGLE SYMBOL.
A. EXAMPLE CONTROL STATION: SYMBOL “#B”, TAGGED "SW-#B", DESCRIPTION
"LIGHTING CONTROL STATION".
B. EXAMPLE PANEL/RACK/CABINET: TAGGED "LCPR#", DESCRIPTION "ROOM BASED
LIGHTING CONTROL PANEL/RACK/CABINET.
C. EXAMPLE CONTROL DESIGNATIONS: a, b, c D. LIGHTING CONTROL STATION “#B” a,b CONTROLS LUMINAIRES WITH THE
SUBSCRIPT “a” AND “b” WITHIN THE SAME SPACE
E. REFER TO THE LIGHT CONTROL SEQUENCE OF OPERATION TAG {L#-##} FOR A
COMPLETE DESCRIPTION OF THE LIGHTING CONTROL AND PRE-PROGRAMMED
SCENE SELECTION REQUIREMENTS.
3. NETWORK BASED LIGHTING CONTROLS: CONTROL STATION COMMONLY DEFINED BY A
RECTANGLE SYMBOL.
A. EXAMPLE SYMBOL “#B”, TAGGED "SW-#B", DESCRIPTION "LIGHTING CONTROL
STATION".
B. EXAMPLE PANEL/RACK/CABINET: TAGGED "LCPN", DESCRIPTION "NETWORK
BASED LIGHTING CONTROL PANEL/RACK/CABINET.
C. EXAMPLE CONTROL DESIGNATIONS: z1, z2, z3 D. LIGHTING CONTROL STATION “#B” z1 CONTROLS LUMINAIRES WITH THE
SUBSCRIPT “z1”. LUMINAIRES WITH A z1 DESIGNATION MAY OR MAY NOT BE
SERVED BY THE SAME BRANCH LIGHTING CIRCUIT.
E. REFER TO THE LIGHT CONTROL SEQUENCE OF OPERATION TAG {L#-##} FOR A
COMPLETE DESCRIPTION OF THE LIGHTING CONTROL AND PRE-PROGRAMMED
SCENE SELECTION REQUIREMENTS.
BOTH LUMINAIRES ARE CONTROLLED BY THE SAME CONTROL STATION, SAME
LIGHTING CONTROL ZONE Z1, BUT POWERED BY DIFFERENT BRANCH LIGHTING
CIRCUITS.
LIGHTING SYSTEM DESCRIPTION KEY:
LIGHTING CONTROL NOTES:
{L#-##} INDICATES THE LIGHTING SEQUENCE OF OPERATION FOR THE SPACE. REFER TO THE
LIGHTING SEQUENCE OF OPERATION MATRIX ON SHEET E600.
{#B} LIGHTING CONTROL STATION. THE “#” INDICATES THE MINIMUM QUANTITY OF INDIVIDUAL
BUTTONS WHEN DEFINED. LIGHTING CONTROL STATION SHALL BE CAPABLE OF ON/OFF
CONTROL FOR CLEANING AS INDICATED ON DRAWINGS AND DESCRIBED IN THE LIGHTING
SEQUENCE OF OPERATION MATRIX. REFER TO DRAWINGS AND LUMINAIRE SUBSCRIPTS TO
DETERMINE IF A ROOM BASED CONTROLLER (a,b,c SUBSCRIPTS) OR NETWORK CONTROL SYSTEM (z1, z2, z3) IS REQUIRED.
{ z##} INDICATES THE LIGHTING ZONES FOR THE SPACE. PROVIDE SEPARATE CONTROL OF EACH
CONTROLLED ZONE. LUMINAIRES ASSOCIATED WITH THE SAME ZONE SHALL OPERATE
TOGETHER WITHIN THE SAME PROGRAMMED SCENE.
LIGHTING CONTROL SUBSCRIPTS:
1. LOWER CASE ALPHA SUBSCRIPTS “a, b, c” INDICATE LINE VOLTAGE OR ROOM BASED
LIGHTING CONTROL SYSTEMS. REFER TO DRAWINGS TO DETERMINE IF LINE VOLTAGE
CONTROL (S, S3, S4, ETC) OR {#B} ROOM BASED CONTROLLER SYSTEM (#B) IS
REQUIRED.
2. LOWER CASE ALPHA NUMERIC SUBSCRIPTS “z1, z2, z3” INDICATE NETWORK BASED
LIGHTING CONTROL SYSTEM.
EMERGENCY LIGHTING OVERRIDE CONTROL (UL924 AND UL1008): LIGHTING CONTROL
EQUIPMENT COUPLED WITH REMOTE EMERGENCY POWER SOURCES (EXTERNAL TO THE
LUMINAIRE) REQUIRE ALCR (UL924) OR BCELTS (UL1008) DEVICES FOR EMERGENCY (LIFE
SAFETY) COMPLIANCE. AN EMERGENCY LIGHTING CONTROL BYPASS IS REQUIRED FOR EVERY
INDIVIDUAL LIGHTING CONTROL ZONE-CIRCUIT BUT NOT SHOWN ON THE PLANS. REFER TO THIS
SPECIFICATION FOR ALCR AND BCELTS DESCRIPTIONS. REFER TO THE SEQUENCE OF
OPERATION LIGHTING CONTROL DESCRIPTIONS ON THE PLANS FOR ADDITIONAL
REQUIREMENTS.
REFER TO SHEET E600 FOR LUMINAIRE SCHEDULE
REFER TO SHEET E401 FOR LIGHTING CONTROL ONE-LINE DIAGRAM
LUMINAIRE
aF# a
CONTROL
LUMINAIRE
a,bF# a
CONTROLLUMINAIRE
F# b #B
LUMINAIRE
z1F# z1
CONTROLLUMINAIRE
F# z1
#B
LIGHTING CONTROL NOTES:
ELECTRICAL SHEET INDEX
E000 ELECTRICAL COVERSHEET
E101 LEVEL 01 DEMOLITION PLAN - OVERALL - LIGHTING
E101A LEVEL 01 DEMOLITION PLAN - AREA A - LIGHTING
E101B LEVEL 01 DEMOLITION PLAN - AREA B - LIGHTING
E101C LEVEL 01 DEMOLITION PLAN - AREA C - LIGHTING
E102 LEVEL 02 DEMOLITION PLAN - OVERALL - LIGHTING
E102A LEVEL 02 DEMOLITION PLAN - AREA A - LIGHTING
E102B LEVEL 02 DEMOLITION PLAN - AREA B - LIGHTING
E102C LEVEL 02 DEMOLITION PLAN - AREA C&D - LIGHTING
E103 LEVEL 03 DEMOLITION PLAN - OVERALL - LIGHTING
E103A LEVEL 03 DEMOLITION PLAN - AREA A - LIGHTING
E103B LEVEL 03 DEMOLITION PLAN - AREA B - LIGHTING
E103C LEVEL 03 DEMOLITION PLAN - AREA C - LIGHTING
E201 LEVEL 01 PLAN - OVERALL - LIGHTING
E201A LEVEL 01 PLAN - AREA A - LIGHTING
E201B LEVEL 01 PLAN - AREA B - LIGHTING
E201C LEVEL 01 PLAN - AREA C - LIGHTING
E202 LEVEL 02 PLAN - OVERALL - LIGHTING
E202A LEVEL 02 PLAN - AREA A - LIGHTING
E202B LEVEL 02 PLAN - AREA B - LIGHTING
E202C LEVEL 02 PLAN - AREA C&D - LIGHTING
E203 LEVEL 03 PLAN - OVERALL - LIGHTING
E203A LEVEL 03 PLAN - AREA A - LIGHTING
E203B LEVEL 03 PLAN - AREA B - LIGHTING
E203C LEVEL 03 PLAN - AREA C - LIGHTING
E400 ELECTRICAL DETAILS
E401 LIGHTING CONTROL SYSTEM DETAILS
E402 LIGHTING CONTROL SYSTEM CONTACT SCHEDULES
E600 ELECTRICAL SCHEDULES
GRAND TOTAL: 29
A
B
C
D
BUILDING 7 LIGHTING AND CONTROLS UPGRADE
D A
U S
Agricultural Research Service
BEN A'HEARN
ORDER DATE:
TASK ORDER NO.:
DESCRIPTIONBYDATENO.
BAILEY EDWARD
DESIGN
EPM:
AOE:
BED PROJECT NO.:
CHECKED BY:
PROJECT MANAGER:
REAL PROPERTY:
SAFETY & HEALTH:
USDA
DWG. NO.
SHEET
AMES, IA 50010
1920 DAYTON AVENUE
NATIONAL CENTER FOR ANIMAL
HEALTH- BUILDING 7
t 312.440.2300 f 312.440.2303 www.baileyedward.com
35 East Wacker Dr
Suite 2800
Chicago, IL
60601-2308
©2024 Bailey Edward Design
Design Firm License No. 184-001962
TBD
KARLA TEBBEN
TBD
12505B23F0175
OF
E000
ELECTRICAL COVERSHEET
CW
KS
23005300.02 5
1 08/12/2025 BED 100% CONSTRUCTION DOCUMENTS
OC
OC
D
OC
D
OC
D
OC
D
A R
E A
C
A R
E A
B
AREA A
AREA B
A R
E A
B
A R
E A
D
A
B
C
D
BUILDING 7 LIGHTING AND CONTROLS UPGRADE
D A
U S
Agricultural Research Service
BEN A'HEARN
ORDER DATE:
TASK ORDER NO.:
DESCRIPTIONBYDATENO.
BAILEY EDWARD
DESIGN
EPM:
AOE:
BED PROJECT NO.:
CHECKED BY:
PROJECT MANAGER:
REAL PROPERTY:
SAFETY & HEALTH:
USDA
DWG. NO.
SHEET
AMES, IA 50010
1920 DAYTON AVENUE
NATIONAL CENTER FOR ANIMAL
HEALTH- BUILDING 7
t 312.440.2300 f 312.440.2303 www.baileyedward.com
35 East Wacker Dr
Suite 2800
Chicago, IL
60601-2308
©2024 Bailey Edward Design
Design Firm License No. 184-001962
TBD
KARLA TEBBEN
TBD
12505B23F0175
OF
E101
LEVEL 01 DEMOLITION PLAN - OVERALL -
LIGHTING
CW
KS
23005300.02 6
N O R
HT
1/16" = 1'-0"1
LEVEL 01 DEMOLITION PLAN - OVERALL - LIGHTING
OC
D
A
B
C
D
BUILDING 7 LIGHTING AND CONTROLS UPGRADE
D A
U S
Agricultural Research Service
BEN A'HEARN
ORDER DATE:
TASK ORDER NO.:
DESCRIPTIONBYDATENO.
BAILEY EDWARD
DESIGN
EPM:
AOE:
BED PROJECT NO.:
CHECKED BY:
PROJECT MANAGER:
REAL PROPERTY:
SAFETY & HEALTH:
USDA
DWG. NO.
SHEET
AMES, IA 50010
1920 DAYTON AVENUE
NATIONAL CENTER FOR ANIMAL
HEALTH- BUILDING 7
t 312.440.2300 f 312.440.2303 www.baileyedward.com
35 East Wacker Dr
Suite 2800
Chicago, IL
60601-2308
©2024 Bailey Edward Design
Design Firm License No. 184-001962
TBD
KARLA TEBBEN
TBD
12505B23F0175
OF
E101A
LEVEL 01 DEMOLITION PLAN - AREA A -
LIGHTING
CW
KS
23005300.02 7
N O R
HT
1/8" = 1'-0"1
LEVEL 01 DEMOLITION PLAN - AREA A - LIGHTING
DEMOLITION PLANS - GENERAL NOTES
1. REMOVE ALL EXISTING LUMINAIRES AND REPLACE WITH NEW
LUMINAIRES IN A "ONE FOR ONE" SCENARIO. ALL ELECTRICAL
WIRING SHALL REMAIN AND BE REUSED WITH NEW LUMINAIRES.
CAP AND MAINTAIN FOR SAFETY BETWEEN DEMOLITION AND NEW
WORK PHASES.
2. ENSURE THAT ALL THROUGH-SLAB PENETRATIONS REMAIN INTACT
TO ENSURE NO TRANSMISSION OF AIR BETWEEN RESEARCH AREAS
AND MECHANICAL SPACES. IF PENETRATIONS ARE MODIFIED
CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING THAT THE
PENETRATION HAS BEEN RESEALED.
3. REMOVE EXISTING LIGHTING CONTROL EQUIPMENT IN EACH SPACE.
THIS PERTAINS TO ALL SWITCHES, OCCUPANCY SENSORS AND
OTHER EQUIPMENT. THESE SHALL BE REPLACED IN-KIND.
4. FACILITY OWNER RETAINS FIRST RIGHT TO RETAIN ANY EXISTING,
FUNCTIONAL LUMINAIRES. IF THE OWNER REFUSES THESE
LUMINAIRES AND MATERIAL THEY SHALL BE DISPOSED OF IN
ACCORDANCE WITH GUIDELINES IN SPECIFICATION SECTION 26 05
00.
5. COORDINATE WITH ON-SITE OWNERS TEAM FOR PHASING OF
DEMOLITION AND NEW WORK.
OC
D
OC
D
A
B
C
D
BUILDING 7 LIGHTING AND CONTROLS UPGRADE
D A
U S
Agricultural Research Service
BEN A'HEARN
ORDER DATE:
TASK ORDER NO.:
DESCRIPTIONBYDATENO.
BAILEY EDWARD
DESIGN
EPM:
AOE:
BED PROJECT NO.:
CHECKED BY:
PROJECT MANAGER:
REAL PROPERTY:
SAFETY & HEALTH:
USDA
DWG. NO.
SHEET
AMES, IA 50010
1920 DAYTON AVENUE
NATIONAL CENTER FOR ANIMAL
HEALTH- BUILDING 7
t 312.440.2300 f 312.440.2303 www.baileyedward.com
35 East Wacker Dr
Suite 2800
Chicago, IL
60601-2308
©2024 Bailey Edward Design
Design Firm License No. 184-001962
TBD
KARLA TEBBEN
TBD
12505B23F0175
OF
E101B
LEVEL 01 DEMOLITION PLAN - AREA B -
LIGHTING
CW
KS
23005300.02 8
N O R
HT
1/8" = 1'-0"1
LEVEL 01 DEMOLITION PLAN - AREA B - LIGHTING
DEMOLITION PLANS - GENERAL NOTES
1. REMOVE ALL EXISTING LUMINAIRES AND REPLACE WITH NEW
LUMINAIRES IN A "ONE FOR ONE" SCENARIO. ALL ELECTRICAL
WIRING SHALL REMAIN AND BE REUSED WITH NEW LUMINAIRES.
CAP AND MAINTAIN FOR SAFETY BETWEEN DEMOLITION AND NEW
WORK PHASES.
2. ENSURE THAT ALL THROUGH-SLAB PENETRATIONS REMAIN INTACT
TO ENSURE NO TRANSMISSION OF AIR BETWEEN RESEARCH AREAS
AND MECHANICAL SPACES. IF PENETRATIONS ARE MODIFIED
CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING THAT THE
PENETRATION HAS BEEN RESEALED.
3. REMOVE EXISTING LIGHTING CONTROL EQUIPMENT IN EACH SPACE.
THIS PERTAINS TO ALL SWITCHES, OCCUPANCY SENSORS AND
OTHER EQUIPMENT. THESE SHALL BE REPLACED IN-KIND.
4. FACILITY OWNER RETAINS FIRST RIGHT TO RETAIN ANY EXISTING,
FUNCTIONAL LUMINAIRES. IF THE OWNER REFUSES THESE
LUMINAIRES AND MATERIAL THEY SHALL BE DISPOSED OF IN
ACCORDANCE WITH GUIDELINES IN SPECIFICATION SECTION 26 05
00.
5. COORDINATE WITH ON-SITE OWNERS TEAM FOR PHASING OF
DEMOLITION AND NEW WORK.
A R
E A
C
A R
E A
B
AREA A
A
B
C
D
BUILDING 7 LIGHTING AND CONTROLS UPGRADE
D A
U S
Agricultural Research Service
BEN A'HEARN
ORDER DATE:
TASK ORDER NO.:
DESCRIPTIONBYDATENO.
BAILEY EDWARD
DESIGN
EPM:
AOE:
BED PROJECT NO.:
CHECKED BY:
PROJECT MANAGER:
REAL PROPERTY:
SAFETY & HEALTH:
USDA
DWG. NO.
SHEET
AMES, IA 50010
1920 DAYTON AVENUE
NATIONAL CENTER FOR ANIMAL
HEALTH- BUILDING 7
t 312.440.2300 f 312.440.2303 www.baileyedward.com
35 East Wacker Dr
Suite 2800
Chicago, IL
60601-2308
©2024 Bailey Edward Design
Design Firm License No. 184-001962
TBD
KARLA TEBBEN
TBD
12505B23F0175
OF
E101C
LEVEL 01 DEMOLITION PLAN - AREA C -
LIGHTING
CW
KS
23005300.02 9
N O R
HT
1/8" = 1'-0"1
LEVEL 01 DEMOLITION PLAN - AREA C - LIGHTING
DEMOLITION PLANS - GENERAL NOTES
1. REMOVE ALL EXISTING LUMINAIRES AND REPLACE WITH NEW
LUMINAIRES IN A "ONE FOR ONE" SCENARIO. ALL ELECTRICAL
WIRING SHALL REMAIN AND BE REUSED WITH NEW LUMINAIRES.
CAP AND MAINTAIN FOR SAFETY BETWEEN DEMOLITION AND NEW
WORK PHASES.
2. ENSURE THAT ALL THROUGH-SLAB PENETRATIONS REMAIN INTACT
TO ENSURE NO TRANSMISSION OF AIR BETWEEN RESEARCH AREAS
AND MECHANICAL SPACES. IF PENETRATIONS ARE MODIFIED
CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING THAT THE
PENETRATION HAS BEEN RESEALED.
3. REMOVE EXISTING LIGHTING CONTROL EQUIPMENT IN EACH SPACE.
THIS PERTAINS TO ALL SWITCHES, OCCUPANCY SENSORS AND
OTHER EQUIPMENT. THESE SHALL BE REPLACED IN-KIND.
4. FACILITY OWNER RETAINS FIRST RIGHT TO RETAIN ANY EXISTING,
FUNCTIONAL LUMINAIRES. IF THE OWNER REFUSES THESE
LUMINAIRES AND MATERIAL THEY SHALL BE DISPOSED OF IN
ACCORDANCE WITH GUIDELINES IN SPECIFICATION SECTION 26 05
00.
5. COORDINATE WITH ON-SITE OWNERS TEAM FOR PHASING OF
OC
D
OC
D
OC
D
OC
D
OC
D
OC
D
OC
D
OC
D
OC
D
OC
D
OC
D
OC
D
OC
D
OC
D
OC
D
OC
D
OC
D
OC
D
OC
D
OC
D
OC
D
OC
D
OC
D
OC
D
OC
D
P C
A R
E A
C
A R
E A
B
AREA A
AREA B
A R
E A
B
A R
E A
D
A
B
C
D
BUILDING 7 LIGHTING AND CONTROLS UPGRADE
D A
U S
Agricultural Research Service
BEN A'HEARN
ORDER DATE:
TASK ORDER NO.:
DESCRIPTIONBYDATENO.
BAILEY EDWARD
DESIGN
EPM:
AOE:
BED PROJECT NO.:
CHECKED BY:
PROJECT MANAGER:
REAL PROPERTY:
SAFETY & HEALTH:
USDA
DWG. NO.
SHEET
AMES, IA 50010
1920 DAYTON AVENUE
NATIONAL CENTER FOR ANIMAL
HEALTH- BUILDING 7
t 312.440.2300 f 312.440.2303 www.baileyedward.com
35 East Wacker Dr
Suite 2800
Chicago, IL
60601-2308
©2024 Bailey Edward Design
Design Firm License No. 184-001962
TBD
KARLA TEBBEN
TBD
12505B23F0175
OF
E102
LEVEL 02 DEMOLITION PLAN - OVERALL -
LIGHTING
CW
KS
23005300.02 10
N O R
HT
1/16" = 1'-0"1
LEVEL 02 DEMOLITION PLAN - OVERALL - LIGHTING
OC
D
OC
D
OC
D
OC
D
OC
D
OC
D
OC
D
OC
D
OC
D
OC
D
OC
D
OC
D
OC
D
OC
D
OC
D
P C
A
B
C
D
BUILDING 7 LIGHTING AND CONTROLS UPGRADE
D A
U S
Agricultural Research Service
BEN A'HEARN
ORDER DATE:
TASK ORDER NO.:
DESCRIPTIONBYDATENO.
BAILEY EDWARD
DESIGN
EPM:
AOE:
BED PROJECT NO.:
CHECKED BY:
PROJECT MANAGER:
REAL PROPERTY:
SAFETY & HEALTH:
USDA
DWG. NO.
SHEET
AMES, IA 50010
1920 DAYTON AVENUE
NATIONAL CENTER FOR ANIMAL
HEALTH- BUILDING 7
t 312.440.2300 f 312.440.2303 www.baileyedward.com
35 East Wacker Dr
Suite 2800
Chicago, IL
60601-2308
©2024 Bailey Edward Design
Design Firm License No. 184-001962
TBD
KARLA TEBBEN
TBD
12505B23F0175
OF
E102A
LEVEL 02 DEMOLITION PLAN - AREA A -
LIGHTING
CW
KS
23005300.02 11
N O R
HT
1/8" = 1'-0"1
LEVEL 02 DEMOLITION PLAN - AREA A - LIGHTING
DEMOLITION PLANS - GENERAL NOTES
1. REMOVE ALL EXISTING LUMINAIRES AND REPLACE WITH NEW
LUMINAIRES IN A "ONE FOR ONE" SCENARIO. ALL ELECTRICAL
WIRING SHALL REMAIN AND BE REUSED WITH NEW LUMINAIRES.
CAP AND MAINTAIN FOR SAFETY BETWEEN DEMOLITION AND NEW
WORK PHASES.
2. ENSURE THAT ALL THROUGH-SLAB PENETRATIONS REMAIN INTACT
TO ENSURE NO TRANSMISSION OF AIR BETWEEN RESEARCH AREAS
AND MECHANICAL SPACES. IF PENETRATIONS ARE MODIFIED
CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING THAT THE
PENETRATION HAS BEEN RESEALED.
3. REMOVE EXISTING LIGHTING CONTROL EQUIPMENT IN EACH SPACE.
THIS PERTAINS TO ALL SWITCHES, OCCUPANCY SENSORS AND
OTHER EQUIPMENT. THESE SHALL BE REPLACED IN-KIND.
4. FACILITY OWNER RETAINS FIRST RIGHT TO RETAIN ANY EXISTING,
FUNCTIONAL LUMINAIRES. IF THE OWNER REFUSES THESE
LUMINAIRES AND MATERIAL THEY SHALL BE DISPOSED OF IN
ACCORDANCE WITH GUIDELINES IN SPECIFICATION SECTION 26 05
00.
5. COORDINATE WITH ON-SITE OWNERS TEAM FOR PHASING OF
DEMOLITION AND NEW WORK.
AREA B
OC
D
OC
D
OC
D
OC
D
OC
D
OC
D
OC
D
OC
D
OC
D
A
B
C
D
BUILDING 7 LIGHTING AND CONTROLS UPGRADE
D A
U S
Agricultural Research Service
BEN A'HEARN
ORDER DATE:
TASK ORDER NO.:
DESCRIPTIONBYDATENO.
BAILEY EDWARD
DESIGN
EPM:
AOE:
BED PROJECT NO.:
CHECKED BY:
PROJECT MANAGER:
REAL PROPERTY:
SAFETY & HEALTH:
USDA
DWG. NO.
SHEET
AMES, IA 50010
1920 DAYTON AVENUE
NATIONAL CENTER FOR ANIMAL
HEALTH- BUILDING 7
t 312.440.2300 f 312.440.2303 www.baileyedward.com
35 East Wacker Dr
Suite 2800
Chicago, IL
60601-2308
©2024 Bailey Edward Design
Design Firm License No. 184-001962
TBD
KARLA TEBBEN
TBD
12505B23F0175
OF
E102B
LEVEL 02 DEMOLITION PLAN - AREA B -
LIGHTING
CW
KS
23005300.02 12
N O R
HT
1/8" = 1'-0"1
LEVEL 02 DEMOLITION PLAN - AREA B - LIGHTING
DEMOLITION PLANS - GENERAL NOTES
1. REMOVE ALL EXISTING LUMINAIRES AND REPLACE WITH NEW
LUMINAIRES IN A "ONE FOR ONE" SCENARIO. ALL ELECTRICAL
WIRING SHALL REMAIN AND BE REUSED WITH NEW LUMINAIRES.
CAP AND MAINTAIN FOR SAFETY BETWEEN DEMOLITION AND NEW
WORK PHASES.
2. ENSURE THAT ALL THROUGH-SLAB PENETRATIONS REMAIN INTACT
TO ENSURE NO TRANSMISSION OF AIR BETWEEN RESEARCH AREAS
AND MECHANICAL SPACES. IF PENETRATIONS ARE MODIFIED
CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING THAT THE
PENETRATION HAS BEEN RESEALED.
3. REMOVE EXISTING LIGHTING CONTROL EQUIPMENT IN EACH SPACE.
THIS PERTAINS TO ALL SWITCHES, OCCUPANCY SENSORS AND
OTHER EQUIPMENT. THESE SHALL BE REPLACED IN-KIND.
4. FACILITY OWNER RETAINS FIRST RIGHT TO RETAIN ANY EXISTING,
FUNCTIONAL LUMINAIRES. IF THE OWNER REFUSES THESE
LUMINAIRES AND MATERIAL THEY SHALL BE DISPOSED OF IN
ACCORDANCE WITH GUIDELINES IN SPECIFICATION SECTION 26 05
00.
5. COORDINATE WITH ON-SITE OWNERS TEAM FOR PHASING OF
DEMOLITION AND NEW WORK.
A R
E A
C
A R
E A
B
C
D
BUILDING 7 LIGHTING AND CONTROLS UPGRADE
D A
U S
Agricultural Research Service
BEN A'HEARN
ORDER DATE:
TASK ORDER NO.:
DESCRIPTIONBYDATENO.
BAILEY EDWARD
DESIGN
EPM:
AOE:
BED PROJECT NO.:
CHECKED BY:
PROJECT MANAGER:
REAL PROPERTY:
SAFETY & HEALTH:
USDA
DWG. NO.
SHEET
AMES, IA 50010
1920 DAYTON AVENUE
NATIONAL CENTER FOR ANIMAL
HEALTH- BUILDING 7
t 312.440.2300 f 312.440.2303 www.baileyedward.com
35 East Wacker Dr
Suite 2800
Chicago, IL
60601-2308
©2024 Bailey Edward Design
Design Firm License No. 184-001962
TBD
KARLA TEBBEN
TBD
12505B23F0175
OF
E102C
LEVEL 02 DEMOLITION PLAN - AREA C&D -
LIGHTING
CW
KS
23005300.02 13
N O R
HT
1/8" = 1'-0"1
LEVEL 02 DEMOLITION PLAN - AREA C - LIGHTING
N O R
HT
1/8" = 1'-0"2
LEVEL 02 DEMOLITION PLAN - AREA D - LIGHTING
DEMOLITION PLANS - GENERAL NOTES
1. REMOVE ALL EXISTING LUMINAIRES AND REPLACE WITH NEW
LUMINAIRES IN A "ONE FOR ONE" SCENARIO. ALL ELECTRICAL
WIRING SHALL REMAIN AND BE REUSED WITH NEW LUMINAIRES.
CAP AND MAINTAIN FOR SAFETY BETWEEN DEMOLITION AND NEW
WORK PHASES.
2. ENSURE THAT ALL THROUGH-SLAB PENETRATIONS REMAIN INTACT
TO ENSURE NO TRANSMISSION OF AIR BETWEEN RESEARCH AREAS
AND MECHANICAL SPACES. IF PENETRATIONS ARE MODIFIED
CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING THAT THE
PENETRATION HAS BEEN RESEALED.
3. REMOVE EXISTING LIGHTING CONTROL EQUIPMENT IN EACH SPACE.
THIS PERTAINS TO ALL SWITCHES, OCCUPANCY SENSORS AND
OTHER EQUIPMENT. THESE SHALL BE REPLACED IN-KIND.
4. FACILITY OWNER RETAINS FIRST RIGHT TO RETAIN ANY EXISTING,
FUNCTIONAL LUMINAIRES. IF THE OWNER REFUSES THESE
LUMINAIRES AND MATERIAL THEY SHALL BE DISPOSED OF IN
ACCORDANCE WITH GUIDELINES IN SPECIFICATION SECTION 26 05
00.
5. COORDINATE WITH ON-SITE OWNERS TEAM FOR PHASING OF
DEMOLITION AND NEW WORK.
A R
E A
C
A R
E A
B
A R
E A
OC
D
A R
E A
C
A R
E A
B
AREA A
AREA B
A R
E A
B
A R
E A
D
A
B
C
D
BUILDING 7 LIGHTING AND CONTROLS UPGRADE
D A
U S
Agricultural Research Service
BEN A'HEARN
ORDER DATE:
TASK ORDER NO.:
DESCRIPTIONBYDATENO.
BAILEY EDWARD
DESIGN
EPM:
AOE:
BED PROJECT NO.:
CHECKED BY:
PROJECT MANAGER:
REAL PROPERTY:
SAFETY & HEALTH:
USDA
DWG. NO.
SHEET
AMES, IA 50010
1920 DAYTON AVENUE
NATIONAL CENTER FOR ANIMAL
HEALTH- BUILDING 7
t 312.440.2300 f 312.440.2303 www.baileyedward.com
35 East Wacker Dr
Suite 2800
Chicago, IL
60601-2308
©2024 Bailey Edward Design
Design Firm License No. 184-001962
TBD
KARLA TEBBEN
TBD
12505B23F0175
OF
E103
LEVEL 03 DEMOLITION PLAN - OVERALL -
LIGHTING
CW
KS
23005300.02 14
N O R
HT
1/16" = 1'-0"1
LEVEL 03 DEMOLITION PLAN - OVERALL - LIGHTING
A
B
C
D
BUILDING 7 LIGHTING AND CONTROLS UPGRADE
D A
U S
Agricultural Research Service
BEN A'HEARN
ORDER DATE:
TASK ORDER NO.:
DESCRIPTIONBYDATENO.
BAILEY EDWARD
DESIGN
EPM:
AOE:
BED PROJECT NO.:
CHECKED BY:
PROJECT MANAGER:
REAL PROPERTY:
SAFETY & HEALTH:
USDA
DWG. NO.
SHEET
AMES, IA 50010
1920 DAYTON AVENUE
NATIONAL CENTER FOR ANIMAL
HEALTH- BUILDING 7
t 312.440.2300 f 312.440.2303 www.baileyedward.com
35 East Wacker Dr
Suite 2800
Chicago, IL
60601-2308
©2024 Bailey Edward Design
Design Firm License No. 184-001962
TBD
KARLA TEBBEN
TBD
12505B23F0175
OF
E103A
LEVEL 03 DEMOLITION PLAN - AREA A -
LIGHTING
CW
KS
23005300.02 15
N O R
HT
1/8" = 1'-0"1
LEVEL 03 DEMOLITION PLAN - AREA A - LIGHTING
DEMOLITION PLANS - GENERAL NOTES
1.…