C05a Attachment 8 Specifications Addendum.pdf

PDF 729 KB Posted

Attached to
Lighting Renovation for USDA ARS in Ames, IA (Amended) Federal contract opportunity
Solicitation number
1232SA26Q0962
Issued by
Department of Agriculture Agricultural Research Service

About this file

This is Addendum No. 1 to the USDA contract for the NCAH Building 7 Lighting Renovation project located at the National Center For Animal Health in Ames, Iowa (Project Number: 1232SA26Q0962/023116), issued by Bailey Edward on 8/17/2026. The addendum modifies the original Bidding Documents dated 8/12/2025 and must be acknowledged on the Bid Form to avoid bidder disqualification.

The addendum clarifies and modifies lighting control and fixture requirements. Lighting control commissioning will occur in five sequential phases, one per animal holding suite, due to sensitive research and containment protocols. The controls manufacturer must provide a minimum of seven site visits: one per suite (five total), one preconstruction visit, and one floating site visit as required. Verification of luminaire on/off state in individual animal holding rooms is required, coordinated with the design team through control system programming. All wall-mounted occupancy sensors must be wash-down rated with a minimum IP66 rating and NEMA4X compliance, with manufacturer specifications set to McMaster-Carr Model 7409N11. The construction documents are revised to delete three previously approved equal manufacturers (Current HLI Evolve LED EWLS, Cooper Lumark XTOR, and LSI WPSLS) as equals for Type F3 fixtures and add two new approved equals: Kenall MLHA12 and Kurtzon WL-A Profile Wrap. A mandatory site visit is required for all bidders.

View the file

Other files for this federal contract opportunity

Other files attached to Lighting Renovation for USDA ARS in Ames, IA (Amended), newest first.
File Type Posted
C05 SF30 1232SA26Q09620001.pdf PDF
C05b Attachment 9 Q and A.pdf PDF
C04d Attachment 4 Wage Determination.pdf PDF
C04b Attachment 2 Specifications 1160423.pdf PDF
C04c Attachment 3 Drawings 1160423.pdf PDF
C04g Attachment 7 SF1413 Subcontractor Acknowlegement.pdf PDF
C04e Attachment 5 ARS_371_CONSTRUCTION PROGRESS.pdf PDF
C04 SF1442 RFQ 1232SA26Q0962.pdf PDF
C04a Attachment 1 Statement of Work 1160423.pdf PDF
C04f Attachment 6 ARS_372_REQUEST FOR PAYMENT TRANSMITTAL.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ADDENDUM NO. 1

Agency Name: United States Department of Agriculture Project Name: NCAH Building 7 Lighting Renovation Project Location: National Center For Animal Health, Ames Iowa Project Number: 1232SA26Q0962/023116 To: USDA From: Bailey Edward Issue Date: 8/17/2026

This addendum forms a part of the Contract Documents and modifies the original Bidding Documents dated 8/12/2025 and any subsequent addenda. Acknowledge receipt of this Addendum in the space provided on the Bid Form. Failure to do so may subject the Bidder to disqualification.

This addendum consists of Addendum Items Sketches (1 pages).

Attachments:

1. Drawing E600

Clarification:

1. Specification Section 01 01 00 General Requirements, add the following to 1.1 Scope of Work, Section C part 8:

a. The lighting control commissioning will happen in phases. as construction will happen in each animal holding suite (total of 5) in sequential phases due to the sensitive nature of the research and containment protocols in building 7. The controls manufacturer shall include a minimum of 7 site visits to coordinate programming for the lighting control system (1 per suite, total of 5, (1)preconstruction and

(1) floating site visit as may be required.

2. Specification Section 01 01 00 General Requirements, add the following to 1.1 Scope of Work, Section C to create part 11 that reads as follows:

a. Verification of luminaire on/off state in the individual animal holding rooms is required. coordinate with design team regarding exact method via programming of the control system.

3. Specification Section 26 09 33 Lighting Controls add the following:

a. ALL WALL MOUNTED OCCUPANCY SENSORS SHALL BE WASH-DOWN RATED (IP66 MIN & NEMA4X).

PROVIDE ACCESSORIES FOR MOUNTING AND POWER AS NECESSARY.

i. BASIS OF DESIGN:

ii. MANUFACTURER: MCMASTER-CARR

iii. MODEL: 7409N11

Changes to Construction Documents:

1. Drawing Sheet E600 Drawing ELECTRICAL SCHEDULES:

a. DELETE ‘CURRENT HLI EVOLVE LED EWLS, COOPER LUMARK XTOR, & LSI WPSLS’ as equals from Type

F3.

b. ADD the following as APPROVED EQUAL MANUFACTURERS AND SERIES for Type F3:

i. KENALL ‘MLHA12’

ii. KURTZON ‘WL-A PROFILE WRAP’

End of Addendum 1

4. The site visit is mandatory.

A

B

C

D

BUILDING 7 LIGHTING AND CONTROLS UPGRADE

D A

U S

Agricultural Research Service

BEN A'HEARN

ORDER DATE:

TASK ORDER NO.:

DESCRIPTIONBYDATENO.

BAILEY EDWARD

DESIGN

EPM:

AOE:

BED PROJECT NO.:

CHECKED BY:

PROJECT MANAGER:

REAL PROPERTY:

SAFETY & HEALTH:

USDA

DWG. NO.

SHEET

AMES, IA 50010

1920 DAYTON AVENUE

NATIONAL CENTER FOR ANIMAL

HEALTH- BUILDING 7

t 312.440.2300 f 312.440.2303 www.baileyedward.com

35 East Wacker Dr

Suite 2800

Chicago, IL

60601-2308

©2024 Bailey Edward Design

Design Firm License No. 184-001962

TBD

KARLA TEBBEN

TBD

12505B23F0175

OF

E600

ELECTRICAL SCHEDULES

CW

KS

23005300.02 32

REFER TO SPECIFICATION SECTIONS LED LIGHTING 26 51 19 FOR ADDITIONAL INFORMATION AND REQUIREMENTS.

INTERIOR CORRELATED COLOR TEMPERATURE 4000/4100K, COLOR RENDERING INDEX (CRI) AT OR ABOVE 80, UNLESS NOTED OTHERWISE.

CATALOG NUMBER SHALL NOT BE CONSIDERED COMPLETE AND MATERIAL SHALL NOT BE ORDERED BY MANUFACTURER AND CATALOG NUMBER ONLY. THE COMPLETE DESCRIPTION AND THE SPECIFICATION SHALL BE COORDINATED WITH THE CATALOG NUMBER TO DETERMINE THE EXACT MATERIAL AND ACCESSORIES TO BE ORDERED. THE FIRST MANUFACTURER LISTED IS THE BASIS OF

DESIGN.

VERIFY AND COORDINATE ALL CEILING TYPES WITH LUMINAIRE MOUNTING AND TRIM REQUIREMENTS PRIOR TO THE RELEASE OF THE LUMINAIRE ORDER.

CONFIRM ALL COLORS AND FINISHES OF ALL LUMINAIRE COMPONENTS WITH ARCHITECT AND INTERIOR DESIGNER PRIOR TO THE RELEASE OF THE LUMINAIRE ORDER.

UNLESS INDICATED ON LIGHTING PLANS OR BELOW, REFER TO ARCHITECTURAL AND INTERIOR DESIGN ELEVATIONS, SECTIONS AND DETAILS FOR ALL SUSPENDED AND WALL MOUNTED LUMINAIRE

MOUNTING HEIGHTS.

DMX - DIGITAL MULTIPLEX EM - EMERGENCY BATTERY ML - MULTI-LEVEL SWITCHING O - OTHER (SEE DESCRIPTION)

DALI - DIGITAL ADDRESSABLE ELV - ELECTRONIC LOW VOLTAGE LINE - LINE VOLTAGE DIMMING REM - REMOTE

0-10V - 0-10V DIMMING EB - ELECTRONIC HL - HIGH/LOW (100%/50%) STEP DIM MV - MULTI-VOLTAGE ELECTRONIC

(TYPE) DRIVER:

PL - POLE O - OTHER (SEE DESCRIPTION) DLED - DYNAMIC TUNABLE LED WLED - WARM DIM LED

P - PERIMETER WL - WALL OLED - ORGANIC LED RLED - RETROFIT LED

FR - FLANGED RECESSED UC - UNDER CABINET TLED - TUBULAR LED LAMP RGBA - COLOR CHANGING + AMBER

CV - COVE SU - SURFACE LED - LIGHT EMITTING DIODE RGBW - COLOR CHANGING + WHITE

CL - CEILING SURFACE SP - SUSPENDED (TYPE) LED RGB - COLOR CHANGING LED

(MTG) MOUNTING: RE - RECESSED (WATT) PER: FIX - FIXTURE, FT - FOOT, LAMP

CFSA - COLOR-FINISH SELECTION BY ARCHITECT [DESIGN SPECIFIC BLANKS]

PAF - PAINT AFTER FABRICATION WW - WALL WASH K - KSH12 .125" ACRYLIC O - OTHER (SEE DESCRIPTION)

FINISH: VWD - VERY WIDE G - TEMPERED GLASS SS - SEMI-SPECULAR CLEAR

RS - REGRESSED STEEL V - ANSI/IES TYPE 5 DISTRIBUTION WD - WIDE F - FROSTED ACRYLIC R - HIGH IMPACT DR ACRYLIC

RA - REGRESSED ALUMINUM IV - ANSI/IES TYPE 4 DISTRIBUTION MD - MEDIUM C - CLEAR ALZAK P - POLYCARBONATE

FS - FLAT STEEL III - ANSI/IES TYPE 3 DISTRIBUTION SP - SPOT B - BAFFLE/LOUVER N - NONE

FA - FLAT ALUMINUM II - ANSI/IES TYPE 2 DISTRIBUTION NSP - VERY NARROW SPOT A - .125" ACRYLIC M - MATTE DIFFUSE CLEAR

(DESC) DOOR: DISTRIBUTION: BEAMWIDTH: (L/L) LENS/LOUVER: K19 - KSH19 .156" ACRYLIC

LED LUMINAIRE SCHEDULE

ITEM DESCRIPTION L/L MTG

DIMENSIONS WATT LED DRIVER

MANUFACTURER AND MODELL W H DIA.

ANSI

WATTS PER TYPE QTY

DELIVERED

LUMENS

(MIN) VOLTS TYPE

EM1 NEMA 4X RATED, WALL MOUNTED HIGH

OUTPUT EMERGENCY WALL PACK.

O WL <varies

<varies

<varies

22 W FIX LED 1 2200 277 V EB ACUITY LITHONIA

EXTL-SP2200L-UVOLT-LTP-SDRT-E

HO

ENGINEER APPROVED EQUAL

EX1 SINGLE FACED EXIT SIGN, CAST ALUMINUM

HOUSING, RED LETTERS, UNIVERSAL

ARROWS/MOUNTING. VERIFY RECESSED

END, BACK OR CEILING MOUNTING AND

ARROWS WITH PLANS. NEMA 4X RATED.

O CL

WL

SP

1'-0" 1 1/2" 10" 3 W FIX LED 1 3 WATT

LED.

277 V MV

EM

ACUITY LITHONIA

LV-S-1-R-120/277-UM-4X

ENGINEER APPROVED EQUALS

EX2 DOUBLE FACED EXIT SIGN, CAST ALUMINUM

HOUSING, RED LETTERS, UNIVERSAL

ARROWS/MOUNTING. VERIFY RECESSED

END, BACK OR CEILING MOUNTING AND

ARROWS WITH PLANS. NEMA 4X RATED.

O CL

WL

SP

1'-0" 1 1/2" 10" 3 W FIX LED 1 3 WATT

LED.

277 V MV

EM

ACUITY LITHONIA

LV-S-2-R-120/277-UM-4X

ENGINEER APPROVED EQUALS

F1 SURFACE MOUNTED SEALED CLEANROOM

TROFFER, ISO 3/CLASS 1 CLEANROOM

RATED, INSET ALUMINUM DOOR FRAME,

DOUBLE GASKETING MINIMUM,

POLYCARBONATE LENS, NEMA 4X WASH

DOWN RATED

P CL 4'-0" 2'-0" 4" 75 W FIX LED 1 9000 277 V 0-10V

1%

NEW STAR

SCS22-HA/IA-CL9000-40-1C-B-UN-D

M1

KURTZON KL-S-LED

KENALL RSEGI22

F2 LED LENSED AND GASKETED VAPOR-TIGHT

STRIP LUMINAIRE. FIBERGLASS HOUSING

WITH NEMA 4X POURED-IN-PLACE GASKET.

STAINLESS STEEL LATCHES. ACRYLIC

IMPACT RESISTANT FROSTED LENS.

R SU

WL

4'-0" 7" 4 1/2" 38 W FIX LED 1 6000 277 V MV ACUITY LITHONIA

FEM-L48-6000LM-IMAFL-WD-277-G

Z10-40K-80CRI-STSL

CURRENT HLI COLUMBIA LXEM

COOPER FAIL-SAFE VT3

F3 WALL MOUNTED STAIRWELL LUMINAIRE.

INTEGRAL OCCUPANCY SENSOR STEP

DIMMING. COLD ROLLED 18 GA. STEEL

HOUSING. POLYCARBONATE OPAL LENS.

LIFETIME WARRANTY AGAINST VANDALISM.

10 YEAR WARRANTY ON LED AND

COMPONENTS.

P SU

WL

4'-0" 3 1/2" 9 1/2" 50 W FIX LED 1 5966 277 V 0-10V

STEP

LUMINAIRE LED

TSL9-46IN-50W-40K-277-OP-FINISH

-FAM7

KURTZON WL-A PROFILE WRAP

KENALL MLHA12

F4 LED LENSED STRIP LIGHT, DIE-FORMED

COLD-ROLLED STEEL HOUSING, ROUND,

FULLY FROSTED ACRYLIC LENS. PAF.

PROVIDE CHAIN HANGING KIT AS REQUIRED

IN MECHANICAL SPACES.

O SP

CL

8'-0" 3" 4" 64 W FT LED 1 10000 277 V 0-10V

10%

ACUITY LITHONIA

CLX-L96-10000LM-SEF-RDL-MVOLT

-GZ10-40K-80CRI-WH

COOPER METALUX SNLED

CURRENT HLI COLUMBIA MPS

F5 6" SQUARE SHOWER DOWNLIGHT, MATTE

CLEAR SELF TRIMMING REFLECTOR. TRIM

FINISH SELECTION BY ARCHITECT. IP65

RATED.

PROVIDE FABRICATED TRIM RING TO ENSURE

SEAL BETWEEN CEILING AND LUMINAIRE

TRIM AND WIPE DOWN COMPATIBILITY.

O RE 1'-2" 1'-2" 4 1/2" 22 W FIX LED 1 2000 277 V 0-10V ACUITY GOTHAM

EVO6SQSH-40/20-DFFAML-SMO-M

VOLT-EZ1

CURRENT HLI PRESCOLITE

LTR-6SQD(SH)

COOPER LDSQ SERIES

F7 SURFACE WALL MOUNTED STEP LIGHT TO

SIMULATE MOONLIGHT. RECTANGULAR

FORM FACTOR WITH 1/8IN LENS WITH

ANTI-PIXELATION FILM INSIDE. DIMMABLE TO

1% VIA 0-10V. CAST ALUMINUM FACEPLATE

WITH ANTI-MICROBIAL WHITE FINISH. 4000K

LED. IP66 RATED MINIMUM. PROVIDE

NEMA-RATED SURFACE MOUNT JUNCTION

BOX. LUMINAIRES ARE TO BE MOUNTED AT

12" BELOW THE FINISHED CEILING IN EACH

SPACE.

P SU

WL

6" 3 1/2" 6 1/2" 1 W FIX LED 1 9.1 277 V 0-10V

1%

KIRLIN LIGHTING

MTT-03NLT-LO-RCT-40K-D1-BG-I66

ENGINEER APPROVED EQUAL

NOTES:

1. {L##} DENOTES THE LIGHTING SEQUENCE OF OPERATIONS FOR THIS SPACE.

2. [#B] PUSH BUTTON REFERS TO SCENE QUANTITY. CONTROL STATION SHALL BE CAPABLE OF [RAISE/LOWER AND] SWITCHING ON/OFF FOR MULTIPLE SCENES AS INDICATED ON SHEETS AND THE LIGHTING SEQUENCE OF OPERATIONS {L##}.

COORDINATE QUANTITIES OF BUTTONS FOR CONTROL STATIONS WITH LIGHTING CONTROL MANUFACTURER.

3. [Z#] DENOTES LIGHTING CONTROL ZONE. PROVIDE SEPARATE CONTROL OF EACH CONTROLLED ZONE. LUMINAIRES ASSOCIATED WITH THE SAME ZONE SHALL OPERATE TOGETHER WITHIN THE SAME PROGRAMMED SCENE.

4. a = SWITCH DESIGNATION FOR LIGHTING CONTROL

5. VERIFY AND COORDINATE ALL TIME CLOCK SETTINGS WITH OWNER PRIOR TO FINAL PROGRAMMING.

6. VERIFY AND COORDINATE ALL PUSH BUTTON WALL DEVICES AND QUANTITIES OF INDIVIDUAL BUTTONS WITH SCENES AND

ZONES PER LOCATION.

7. VERIFY AND COORDINATE ALL PUSH BUTTON QUANTITIES AND SCENE NAMES WITH OWNER PRIOR TO SUBMITTING

ENGRAVING TEMPLATE TO MANUFACTURER.

LIGHTING SEQUENCE OF OPERATION

PLAN ID LIGHTING SWITCHED

{LD1} SEE 'LIGHTING CONTROL SYSTEM' NOTES ON SHEETS E202A & E202B FOR DETAILED SYSTEM FUNCTIONALITY AND PROGRAMMING REQUIREMENTS. CUSTOM GRAPHIC USER INTERFACE PROGRAMMING REQUIRED.

Sequence: Switched dimmable lights are controlled via programmed schedules in this space.

ON: The lights turn on at predetermined times via preprogrammed schedule or local override switch station.

ADJUST: The light levels are preset with programming.

OFF: The lights turn off at predetermined times via preprogrammed schedule or local override switch station.

NOTE: Programmed Preset control schedules are engaged and actuated from remote graphic user interfaces at each of the entry vestibules to the holding suites.

{LD2} Sequence: Switched multi-level lights are controlled in this space.

ON: The lights in the space will automatically turn on to 100% when the space becomes occupied.

ADJUST: The lights are controlled using sensors for light level reduction of at least 50%.

OFF: After the space has been vacant for 30 minutes, the lights will reduce to a minimum of 50% reduction.

{LS1} Sequence: Switched lights are controlled in this space.

ON: The normal lights turn on by the central schedule. Night lights will remain on at all times. Local over-ride switches shall provide 60 minutes of lights on.

OFF: The normal lights turn off by the central time clock sweep.

{LS2} Sequence: Switched lights are controlled in this space.

ON: The lights are turn on by occupancy sensor.

OFF: After the space has been vacant for 15 minutes, the lights will automatically turn off.

{LS3} Sequence: Switched lights are controlled in this space.

ON: The lights turned on using switches.

OFF: After the space has been vacant for 15 minutes, the lights will automatically turn off.

{LS4} Sequence: Switched lights are controlled in this space.

ON: The lights turn on using switches.

OFF: The lights turn off using switches.

1 08/12/2025 BED 100% CONSTRUCTION DOCUMENTS

2 814/26 BED ADDENDUM 01

E600 - ELECTRICAL SCHEDULES_20260814
26 0817 Bid Addendum rev

File details come from the government source that posted it. Updated .