Building_Concept.pdf

PDF 161 KB Posted

Attached to
Hazardous Waste Storage Unit
Solicitation number
IFB-080-2821001-MG
Issued by
Orange County, San Francisco City, California

About this file

The file is a detailed architectural design drawing (ARC-DWG-A101) for a Hazardous Materials Storage Building Concept, prepared by Wood (formerly AMEC Foster Wheeler E&C Services) for Orange County Public Works. The document provides comprehensive technical specifications for a four-compartment prefabricated hazardous materials storage unit designed to store classified materials including flammables, combustibles, corrosives, and toxics. The building features a concrete slab foundation, 4-hour fire-rated perimeter wall construction, 1-hour roof construction, adjustable height ramps, fire-rated doors, and containment floors with sumps in each room.

The technical specifications include specific requirements for electrical systems, ventilation, fire suppression, and safety features. Key required items not included in the base design include hazard signage, DOT placards, electrical grounding systems, natural and mechanical ventilation with fire dampers, air conditioning units, temperature controllers, explosion-proof lighting, and a dry chemical fire suppression system. The storage unit is intended to be white in color, designed for relocation to another site, and must comply with California Building Codes and obtain all necessary state and local approvals and permits. The document is marked "For Bid" and was issued on February 13, 2023, indicating an active procurement process for this specialized hazardous materials storage infrastructure.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

A101

A101

A101

A101

A101

A101

A101

A P

P R

O X

'-6

T

O

0' -0

APPROX 35' TO 36'

EQ EQ EQ

EQ EQ EQ EQ

EQ EQ EQ EQ EQ EQ EQ EQ

ADJUSTABLE

HEIGHT RAMP, TYP

4-0 X 7-0 FIRE RATED

DOOR WITH FIRE EXIT

HARDWARE, TYP

4-HR FIRE RATED

PERIMETER WALL

CONSTRUCTION, TYP

3 TIERS OF ADJUSTABLE

HEIGHT, HEAVY DUTY

SHELVING, APPROX 8 FT

IN LENGTH, TYP

3 TIERS OF ADJUSTABLE

HEIGHT, HEAVY DUTY

SHELVING, APPROX 6 FT IN

LENGTH, TYP IN EACH ROOM

CONC SLAB FOUNDATION

(BY OTHERS)

CONTAINMENT FLOOR WITH

SUMP BELOW, TYP IN EACH

ROOM. SUMP CAPACITY

SHALL BE APPROX 228 GALS

FLAMMABLES COMBUSTIBLES CORROSIVES TOXICS

A101

A101

A101

A101

A101

A101

A101

S L O

P E

1-HR ROOF CONSTRUCTION

BASE

0"

ROOF

8'-6"

A101

A101

ADJUSTABLE

HEIGHT RAMP, TYP

4-HR FIRE RATED

PERIMETER WALL

CONSTRUCTION, TYP

CONC SLAB FOUNDATION

(BY OTHERS)

1-HR FIRE RATED ROOF

CONSTRUCTION, TYP

BASE

0"

ROOF

8'-6"

A101

ADJUSTABLE

HEIGHT RAMP, TYP

4-HR FIRE RATED

PERIMETER WALL

CONSTRUCTION, TYP

CONC SLAB FOUNDATION

(BY OTHERS)

1-HR FIRE RATED ROOF

CONSTRUCTION, TYP

4-0 X 7-0 FIRE RATED

DOOR WITH FIRE EXIT

HARDWARE, TYP

BASE

0"

ROOF

8'-6"

A101

REFER TO OTHER EXT ELEVS FOR TYP NOTES.

BASE

0"

ROOF

8'-6"

A101

A101

REFER TO OTHER EXT

ELEVS FOR TYP NOTES.

BASE

0"

ROOF

8'-6"

A101

COMBUSTIBLESFLAMMABLES CORROSIVES TOXICS

4-HR FIRE RATED

PERIMETER WALL

CONSTRUCTION, TYP

3 TIERS OF ADJUSTABLE

HEIGHT, HEAVY DUTY

SHELVING, REFER TO PLAN

CONC SLAB FOUNDATION

(BY OTHERS)

CONTAINMENT FLOOR WITH

SUMP BELOW, TYP IN EACH

ROOM. SUMP CAPACITY

SHALL BE APPROX 228 GALS

4-HR FIRE RATED PARTITION

1-HR ROOF CONSTRUCTION

NON-RATED PARTITION

4-0 X 7-0 FIRE RATED

DOOR WITH FIRE EXIT

HARDWARE, TYP

BASE

0"

ROOF

8'-6"

A101

A101

4-HR FIRE RATED

PERIMETER WALL

CONSTRUCTION, TYP

3 TIERS OF ADJUSTABLE

HEIGHT, HEAVY DUTY

SHELVING, REFER TO PLAN

CONC SLAB FOUNDATION

(BY OTHERS)

CONTAINMENT FLOOR WITH

SUMP BELOW, TYP IN EACH

ROOM. SUMP CAPACITY

SHALL BE APPROX 228 GALS

4-HR FIRE RATED PARTITION,

BEYOND. REFER TO PLAN.

1-HR ROOF CONSTRUCTION

4-0 X 7-0 FIRE RATED

DOOR WITH FIRE EXIT

HARDWARE, TYP

FLAMMABLES

ADJUSTABLE

HEIGHT RAMP, TYP

BASE

0"

ROOF

8'-6"

A101

4-HR FIRE RATED

PERIMETER WALL

CONSTRUCTION, TYP

3 TIERS OF ADJUSTABLE

HEIGHT, HEAVY DUTY

SHELVING, REFER TO PLAN

CONC SLAB FOUNDATION

(BY OTHERS)

CONTAINMENT FLOOR WITH

SUMP BELOW, TYP IN EACH

ROOM. SUMP CAPACITY

SHALL BE APPROX 228 GALS

4-HR FIRE RATED PARTITION

1-HR ROOF CONSTRUCTION

NON-RATED PARTITION

TOXICS CORROSIVES COMBUSTIBLES FLAMMABLES

REQUIRED ITEMS NOT SHOWN (BY VENDOR):

• HAZARD SIGNAGE AND DOT PLACARDS

• ELECTRICAL GROUND SYSTEM CONNECTION POINTS.

SITE GROUNDING SYSTEM BY OTHERS.

• NATURAL VENTILATION RAIN LOUVERS WITH FIRE

DAMPERS (3 REQUIRED) PER ROOMS BEING SERVED.

• MECHANICAL VENTS WITH FIRE DAMPERS (2

REQUIRED); EXPLOSION PROOF (CLASS 1 - DIV 1) PER

ROOMS BEING SERVED.

• MECHANICAL VENTS WITH FIRE DAMPERS (1

REQUIRED); CORROSION RESISTANT (GEN PURPOSE)

PER ROOM BEING SERVED.

• VENT SWITCHES (3 REQUIRED) WEATHERPROOF,

GENERAL PURPOSE

• AIR CONDITIONER UNITS (2 REQUIRED): 24K BTU, 240V

1PH, EXPLOSION PROOF CLASS 1 -DIV 2 AT INTERIOR.

• TEMPERATURE CONTROLLER (MIN 1 REQUIRED)

EXPLOSION PROOF CLASS 1 -DIV 2

• INTERIOR LIGHTING: LED FIXTURES (4 REQUIRED),

EXPLOSION PROOF (CLASS 1 DIV 2)

• LIGHT SWITCHES (4 REQUIRED) WEATHERPROOF,

GENERAL PURPOSE

• DRY CHEMICAL FIRE SUPPRESSION SYSTEM WITH

ANNUNCIATORS - DESIGN BY VENDOR

• GFCI DUPLEX RECEPTACLES (2 REQUIRED)

WEATHERPROOF, GENERAL PURPOSE.

GENERAL NOTES:

• ELECTRICAL EQUIPMENT AND FIXTURES SHALL BE

120V / 1PH UNLESS NOTED OTHERWISE.

• ELECTRICAL LOAD CENTER SHALL BE 120/240V / 1PH

(GENERAL PURPOSE). FLA = 32.5, MCB = 60 AMPS.

• ANCHORAGE DESIGN AND ANCHORAGE POINTS

FOR THE STORAGE UNIT TO FOUNDATION IS BY

VENDOR. FOUNDATION, UNLOADING, PLACEMENT

AND ACHORAGE OF UNIT IS BY OTHERS.

• FORKLIFT POCKETS, LIFTING LUGS, OR OTHER UNIT

PLACEMENT AIDS SHALL BE INTEGRAL WITH

STORAGE UNIT DESIGN.

• STORAGE UNIT SHALL BE DESIGNED TO BE

RELOCATED TO ANOTHER SITE BY OWNER AT A

LATER DATE.

• FIRE RATED WALL AND ROOF CONSTRUCTION

SHALL COMPLY WITH CALIFORNIA BUILDING CODES

FOR FIRE RESISTANCE RATINGS NOTED. VENDOR

SHALL PROVIDE CERTIFIED TESTING RESULTS FOR

EACH ASSEMBLY.

• CALIFORNIA STATE AND LOCAL APPROVALS AND

PERMITS ARE REQUIRED. ALL NECESSARY

EFFORTS TO OBTAIN SAID APPROVALS AND

RELATED PERMITS SHALL BE INCLUDED AND

OBTAINED BY THE VENDOR.

• UNIT COLOR SELECTION: WHITE

TENTHS 0 INCHES 1 3 4 5 6 7 8 9 102 EIGHTHS 0 MM 10 20 30 40 50 60 70 80 90 100

F

E

D

C

B

A

8 7 6 5 4 3 2 1

REV DDMMMYY REVISION / ISSUE DESCRIPTION DRN CHK APP APP APP APP

REF NUMBER TITLE

REFERENCES

PROJECT PHASE

UNLESS OTHERWISE AGREED IN A WRITTEN CONTRACT BETWEEN WOOD AND ITS CLIENT, THIS

DOCUMENT: (I) CONTAINS INFORMATION, DATA AND DESIGN THAT IS CONFIDENTIAL AND MAY NOT

BE COPIED OR DISCLOSED; AND (II) MAY BE USED BY THE CLIENT ONLY IN THE CONTEXT AND FOR

THE EXPRESS PURPOSE FOR WHICH IT WAS INTENDED. ANY USE OF, OR RELIANCE ON, THIS

DOCUMENT BY ANY THIRD PARTY IS AT THAT PARTY'S SOLE RISK.

STAMP/SEAL

CLIENT PROJECT MGR. DEPARTMENT MGR. PROJECT MGRS.

PROJECT NO. ACTIVITY NO.

SCALE PACKAGE CODE

BY MMDDDYY

DSN

DRN

CHK

APP

SUBJECT

CLIENT DWG. NO.

DRAWING NO.

AREA

30 PATEWOOD DRIVE, SUITE 200 - GREENVILLE, SC 29615 (864) 458-3600

NOT FOR

CONSTRUCTION

FOR BID

WORK SAFELY

COPYRIGHT © 2021

WOOD, DOING BUSINESS AS AMEC FOSTER WHEELER E&C SERVICES

F

E

D

C

B

A

REV DDMMMYY REVISION / ISSUE DESCRIPTION DRN CHK APP APP APP APP

As indicated

A

ISSUED FOR BIDS

Project Number ------

ORANGE COUNTY PUBLIC WORKS

REQUEST FOR PROPOSAL

HAZMAT STORAGE BUILDING CONCEPT

ARC-DWG-A101

SCALE = 1/4" = 1'-0"A101

BASE PLAN1

SCALE = 1/4" = 1'-0"A101

ROOF PLAN2

SCALE =A101

3D VIEW - NW3

SCALE = 1/4" = 1'-0"A101

EXT ELEV - EAST5

SCALE = 1/4" = 1'-0"A101

EXT ELEV - NORTH6

SCALE = 1/4" = 1'-0"A101

EXT ELEV - SOUTH8

SCALE = 1/4" = 1'-0"A101

EXT ELEV - WEST9

SCALE = 1/4" = 1'-0"A101

BLDG SECT - LOOKING NORTH10

SCALE = 1/4" = 1'-0"A101

BLDG SECT - LOOKING EAST4

SCALE = 1/4" = 1'-0"A101

BLDG SECT - LOOKING SOUTH7

A 13FEB23 ISSUED FOR BIDS MPK --- --- --- --- ---

Sheets
A101 - HAZMAT STORAGE BUILDING CONCEPT