Building_Concept.pdf
PDF 161 KB Posted
- Attached to
- Hazardous Waste Storage Unit
- Solicitation number
- IFB-080-2821001-MG
- Issued by
- Orange County, San Francisco City, California
About this file
The file is a detailed architectural design drawing (ARC-DWG-A101) for a Hazardous Materials Storage Building Concept, prepared by Wood (formerly AMEC Foster Wheeler E&C Services) for Orange County Public Works. The document provides comprehensive technical specifications for a four-compartment prefabricated hazardous materials storage unit designed to store classified materials including flammables, combustibles, corrosives, and toxics. The building features a concrete slab foundation, 4-hour fire-rated perimeter wall construction, 1-hour roof construction, adjustable height ramps, fire-rated doors, and containment floors with sumps in each room.
The technical specifications include specific requirements for electrical systems, ventilation, fire suppression, and safety features. Key required items not included in the base design include hazard signage, DOT placards, electrical grounding systems, natural and mechanical ventilation with fire dampers, air conditioning units, temperature controllers, explosion-proof lighting, and a dry chemical fire suppression system. The storage unit is intended to be white in color, designed for relocation to another site, and must comply with California Building Codes and obtain all necessary state and local approvals and permits. The document is marked "For Bid" and was issued on February 13, 2023, indicating an active procurement process for this specialized hazardous materials storage infrastructure.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Hazardous_Waste_Storage_Unit.pdf | ||
| MODEL_CONTRACT_IFB-080-2821001-MG_Hazardous_Waste_Storage_Unit.pdf | ||
| Site_Concept.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
A101
A101
A101
A101
A101
A101
A101
A P
P R
O X
'-6
T
O
0' -0
APPROX 35' TO 36'
EQ EQ EQ
EQ EQ EQ EQ
EQ EQ EQ EQ EQ EQ EQ EQ
ADJUSTABLE
HEIGHT RAMP, TYP
4-0 X 7-0 FIRE RATED
DOOR WITH FIRE EXIT
HARDWARE, TYP
4-HR FIRE RATED
PERIMETER WALL
CONSTRUCTION, TYP
3 TIERS OF ADJUSTABLE
HEIGHT, HEAVY DUTY
SHELVING, APPROX 8 FT
IN LENGTH, TYP
3 TIERS OF ADJUSTABLE
HEIGHT, HEAVY DUTY
SHELVING, APPROX 6 FT IN
LENGTH, TYP IN EACH ROOM
CONC SLAB FOUNDATION
(BY OTHERS)
CONTAINMENT FLOOR WITH
SUMP BELOW, TYP IN EACH
ROOM. SUMP CAPACITY
SHALL BE APPROX 228 GALS
FLAMMABLES COMBUSTIBLES CORROSIVES TOXICS
A101
A101
A101
A101
A101
A101
A101
S L O
P E
1-HR ROOF CONSTRUCTION
BASE
0"
ROOF
8'-6"
A101
A101
ADJUSTABLE
HEIGHT RAMP, TYP
4-HR FIRE RATED
PERIMETER WALL
CONSTRUCTION, TYP
CONC SLAB FOUNDATION
(BY OTHERS)
1-HR FIRE RATED ROOF
CONSTRUCTION, TYP
BASE
0"
ROOF
8'-6"
A101
ADJUSTABLE
HEIGHT RAMP, TYP
4-HR FIRE RATED
PERIMETER WALL
CONSTRUCTION, TYP
CONC SLAB FOUNDATION
(BY OTHERS)
1-HR FIRE RATED ROOF
CONSTRUCTION, TYP
4-0 X 7-0 FIRE RATED
DOOR WITH FIRE EXIT
HARDWARE, TYP
BASE
0"
ROOF
8'-6"
A101
REFER TO OTHER EXT ELEVS FOR TYP NOTES.
BASE
0"
ROOF
8'-6"
A101
A101
REFER TO OTHER EXT
ELEVS FOR TYP NOTES.
BASE
0"
ROOF
8'-6"
A101
COMBUSTIBLESFLAMMABLES CORROSIVES TOXICS
4-HR FIRE RATED
PERIMETER WALL
CONSTRUCTION, TYP
3 TIERS OF ADJUSTABLE
HEIGHT, HEAVY DUTY
SHELVING, REFER TO PLAN
CONC SLAB FOUNDATION
(BY OTHERS)
CONTAINMENT FLOOR WITH
SUMP BELOW, TYP IN EACH
ROOM. SUMP CAPACITY
SHALL BE APPROX 228 GALS
4-HR FIRE RATED PARTITION
1-HR ROOF CONSTRUCTION
NON-RATED PARTITION
4-0 X 7-0 FIRE RATED
DOOR WITH FIRE EXIT
HARDWARE, TYP
BASE
0"
ROOF
8'-6"
A101
A101
4-HR FIRE RATED
PERIMETER WALL
CONSTRUCTION, TYP
3 TIERS OF ADJUSTABLE
HEIGHT, HEAVY DUTY
SHELVING, REFER TO PLAN
CONC SLAB FOUNDATION
(BY OTHERS)
CONTAINMENT FLOOR WITH
SUMP BELOW, TYP IN EACH
ROOM. SUMP CAPACITY
SHALL BE APPROX 228 GALS
4-HR FIRE RATED PARTITION,
BEYOND. REFER TO PLAN.
1-HR ROOF CONSTRUCTION
4-0 X 7-0 FIRE RATED
DOOR WITH FIRE EXIT
HARDWARE, TYP
FLAMMABLES
ADJUSTABLE
HEIGHT RAMP, TYP
BASE
0"
ROOF
8'-6"
A101
4-HR FIRE RATED
PERIMETER WALL
CONSTRUCTION, TYP
3 TIERS OF ADJUSTABLE
HEIGHT, HEAVY DUTY
SHELVING, REFER TO PLAN
CONC SLAB FOUNDATION
(BY OTHERS)
CONTAINMENT FLOOR WITH
SUMP BELOW, TYP IN EACH
ROOM. SUMP CAPACITY
SHALL BE APPROX 228 GALS
4-HR FIRE RATED PARTITION
1-HR ROOF CONSTRUCTION
NON-RATED PARTITION
TOXICS CORROSIVES COMBUSTIBLES FLAMMABLES
REQUIRED ITEMS NOT SHOWN (BY VENDOR):
• HAZARD SIGNAGE AND DOT PLACARDS
• ELECTRICAL GROUND SYSTEM CONNECTION POINTS.
SITE GROUNDING SYSTEM BY OTHERS.
• NATURAL VENTILATION RAIN LOUVERS WITH FIRE
DAMPERS (3 REQUIRED) PER ROOMS BEING SERVED.
• MECHANICAL VENTS WITH FIRE DAMPERS (2
REQUIRED); EXPLOSION PROOF (CLASS 1 - DIV 1) PER
ROOMS BEING SERVED.
• MECHANICAL VENTS WITH FIRE DAMPERS (1
REQUIRED); CORROSION RESISTANT (GEN PURPOSE)
PER ROOM BEING SERVED.
• VENT SWITCHES (3 REQUIRED) WEATHERPROOF,
GENERAL PURPOSE
• AIR CONDITIONER UNITS (2 REQUIRED): 24K BTU, 240V
1PH, EXPLOSION PROOF CLASS 1 -DIV 2 AT INTERIOR.
• TEMPERATURE CONTROLLER (MIN 1 REQUIRED)
EXPLOSION PROOF CLASS 1 -DIV 2
• INTERIOR LIGHTING: LED FIXTURES (4 REQUIRED),
EXPLOSION PROOF (CLASS 1 DIV 2)
• LIGHT SWITCHES (4 REQUIRED) WEATHERPROOF,
GENERAL PURPOSE
• DRY CHEMICAL FIRE SUPPRESSION SYSTEM WITH
ANNUNCIATORS - DESIGN BY VENDOR
• GFCI DUPLEX RECEPTACLES (2 REQUIRED)
WEATHERPROOF, GENERAL PURPOSE.
GENERAL NOTES:
• ELECTRICAL EQUIPMENT AND FIXTURES SHALL BE
120V / 1PH UNLESS NOTED OTHERWISE.
• ELECTRICAL LOAD CENTER SHALL BE 120/240V / 1PH
(GENERAL PURPOSE). FLA = 32.5, MCB = 60 AMPS.
• ANCHORAGE DESIGN AND ANCHORAGE POINTS
FOR THE STORAGE UNIT TO FOUNDATION IS BY
VENDOR. FOUNDATION, UNLOADING, PLACEMENT
AND ACHORAGE OF UNIT IS BY OTHERS.
• FORKLIFT POCKETS, LIFTING LUGS, OR OTHER UNIT
PLACEMENT AIDS SHALL BE INTEGRAL WITH
STORAGE UNIT DESIGN.
• STORAGE UNIT SHALL BE DESIGNED TO BE
RELOCATED TO ANOTHER SITE BY OWNER AT A
LATER DATE.
• FIRE RATED WALL AND ROOF CONSTRUCTION
SHALL COMPLY WITH CALIFORNIA BUILDING CODES
FOR FIRE RESISTANCE RATINGS NOTED. VENDOR
SHALL PROVIDE CERTIFIED TESTING RESULTS FOR
EACH ASSEMBLY.
• CALIFORNIA STATE AND LOCAL APPROVALS AND
PERMITS ARE REQUIRED. ALL NECESSARY
EFFORTS TO OBTAIN SAID APPROVALS AND
RELATED PERMITS SHALL BE INCLUDED AND
OBTAINED BY THE VENDOR.
• UNIT COLOR SELECTION: WHITE
TENTHS 0 INCHES 1 3 4 5 6 7 8 9 102 EIGHTHS 0 MM 10 20 30 40 50 60 70 80 90 100
F
E
D
C
B
A
8 7 6 5 4 3 2 1
REV DDMMMYY REVISION / ISSUE DESCRIPTION DRN CHK APP APP APP APP
REF NUMBER TITLE
REFERENCES
PROJECT PHASE
UNLESS OTHERWISE AGREED IN A WRITTEN CONTRACT BETWEEN WOOD AND ITS CLIENT, THIS
DOCUMENT: (I) CONTAINS INFORMATION, DATA AND DESIGN THAT IS CONFIDENTIAL AND MAY NOT
BE COPIED OR DISCLOSED; AND (II) MAY BE USED BY THE CLIENT ONLY IN THE CONTEXT AND FOR
THE EXPRESS PURPOSE FOR WHICH IT WAS INTENDED. ANY USE OF, OR RELIANCE ON, THIS
DOCUMENT BY ANY THIRD PARTY IS AT THAT PARTY'S SOLE RISK.
STAMP/SEAL
CLIENT PROJECT MGR. DEPARTMENT MGR. PROJECT MGRS.
PROJECT NO. ACTIVITY NO.
SCALE PACKAGE CODE
BY MMDDDYY
DSN
DRN
CHK
APP
SUBJECT
CLIENT DWG. NO.
DRAWING NO.
AREA
30 PATEWOOD DRIVE, SUITE 200 - GREENVILLE, SC 29615 (864) 458-3600
NOT FOR
CONSTRUCTION
FOR BID
WORK SAFELY
COPYRIGHT © 2021
WOOD, DOING BUSINESS AS AMEC FOSTER WHEELER E&C SERVICES
F
E
D
C
B
A
REV DDMMMYY REVISION / ISSUE DESCRIPTION DRN CHK APP APP APP APP
As indicated
A
ISSUED FOR BIDS
Project Number ------
ORANGE COUNTY PUBLIC WORKS
REQUEST FOR PROPOSAL
HAZMAT STORAGE BUILDING CONCEPT
ARC-DWG-A101
SCALE = 1/4" = 1'-0"A101
BASE PLAN1
SCALE = 1/4" = 1'-0"A101
ROOF PLAN2
SCALE =A101
3D VIEW - NW3
SCALE = 1/4" = 1'-0"A101
EXT ELEV - EAST5
SCALE = 1/4" = 1'-0"A101
EXT ELEV - NORTH6
SCALE = 1/4" = 1'-0"A101
EXT ELEV - SOUTH8
SCALE = 1/4" = 1'-0"A101
EXT ELEV - WEST9
SCALE = 1/4" = 1'-0"A101
BLDG SECT - LOOKING NORTH10
SCALE = 1/4" = 1'-0"A101
BLDG SECT - LOOKING EAST4
SCALE = 1/4" = 1'-0"A101
BLDG SECT - LOOKING SOUTH7
A 13FEB23 ISSUED FOR BIDS MPK --- --- --- --- ---
| Sheets |
| A101 - HAZMAT STORAGE BUILDING CONCEPT |