Brooklyn Senior Center Renovations - Addendum 1 10.19.26.pdf
PDF 563 KB Posted
- Attached to
- Renovations at Brooklyn Senior Center
- Solicitation number
- 39457
- Issued by
- Tolland County, Connecticut
About this file
Brooklyn Senior Center Renovations - Addendum 1
This addendum document pertains to the Town of Brooklyn, Connecticut's Invitations for Bid (ITB) for renovations at the Brooklyn Senior Center. The project requires bidders to furnish all labor, materials, tools, services, and equipment necessary to complete renovations in accordance with contract documents and specifications dated October 16, 2026, as prepared by Silver Petrucelli + Associates. Sealed bids are due November 5, 2026, at 1:00 p.m. at the Brooklyn First Selectman's Office, located at 4 Wolf Den Road, Brooklyn, CT 06234. Bids received after the deadline will not be opened; all timely submissions will be opened and read aloud. Addendum 1 was issued on October 19, 2026. Inquiries regarding the project should be directed to Lisa Mileski, Administrative Assistant to the First Selectman, at 860-779-3411, ext. 116, or l.mileski@brooklynct.org.
The successful bidder must furnish and pay for 100% Performance and Payment Bonds and maintain minimum insurance coverage as required by the Connecticut Department of Housing. No pricing information, set-asides, or award timeline is specified in the available documentation. The contract documents and detailed specifications are dated October 16, 2026, and were prepared by Silver Petrucelli + Associates, located at 3190 Whitney Ave, Hamden, CT 06518.
View the file
Other files
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ADDENDUM #1
Senior Center Renovations – Brooklyn Addendum #1-1
RENOVATIONS
SENIOR CENTER
69 SOUTH MAIN STREET
BROOKLYN, CT 06234
S/P+A PROJECT #25.099
DATE: October 19, 2026
The following changes to the Drawings and Project Specifications shall become a part of the Drawings and Project Specifications; superseding previously issued Drawings and Project Specifications to the extent modified by Addendum #1.
General Information:
• The deadline for RFIs is Thursday, October 29, 2026, 4:00pm.
• See attached RFI log. (1)
New Drawings:
• DRAWING M110, MECH LOWER LEVEL DUCT PLAN has been added and is attached as part of this addendum.~ (Per Internal Review)
Changes to the Drawings:
• The following drawings ELECTRICAL drawings have been deleted in their entirety. New drawings have been added and are attached as part of this bid supplement~: (3) o E001 ELEC ABBREVIATIONS & LEGENDS (Per Internal Review) o E210 ELEC LOWER LEVEL LIGHTING PLAN (Per Internal Review) o E600 ELEC DETAILS PLAN (Per Internal Review)
The bid date remains unchanged by this addendum.
The addendum consists of two (2) pages of 8½” x 11” text four (4) 24” x 36” drawings~.
End of Addendum #1
BID RFI LOG
Project: Brooklyn Senior Center Renovations State Project/Bid #: RFI Deadline: 10/29/26, 4p
S/P+A Project #: 25.099 Bids Due: 11/05/26, 1p
RFI # QUESTION DATE RESPONSE ADDENDUM #
RECEIVED ISSUED
Could you point us in the right direction to where the drawings and bid docs are available for download for free? All I see is advanced reprographics to view them, but to d/l, its $109.
10/16/26
Drawings & bid documents are also available for download on the Town of Brooklyn's website, https://www.brooklynct.gov/bids.aspx & will be posted on CT Source.
002 Is a project schedule required with the bid? 10/19/26 No. 1
003 Would you like us to include a DAS prequalification certificate and bid statement with the bid? 10/19/26 No. 1
004 How many copies of the bid would you like us to submit? 10/19/26 Two (2) total, one (1) original & one (1) copy. 1 005 Does this project require a CHRO plan? 10/19/26 No. 1
Are we required to provide preventative maintenance once the job is done? If so, for how long? This would be separate from our 1 Year Workmanship Warranty.
10/19/26 No. 1
SILVER PETRUCELLI + ASSOCIATES
3190 Whitney Avenue | Hamden CT 06518 311 State Street | New London CT 06320
A B C D E
MECHANICAL
MECHANICAL
TOILET
ELECTRICAL
STAIRS
ST1.0
MECHANICAL
JANITOR
ELECTRICAL
STORAGE
CORRIDOR
GAME ROOM
CRAFT ROOM
GROUP EXERCISE ROOM
EXERCISE ROOM
STORAGE
CORRIDOR
STORAGE
019A
S1
125 CFM
S1
125 CFM
S1
135 CFM
S1
70 CFM
S1
70 CFM
S1
70CFM
ZD-5
ZD-2
S1
110 CFM
S1
110 CFM
R1
135 CFM
R1
210 CFM
R1
110 CFM
R1
110 CFM
CU-2
AHU-2
DH-1
ZD-1
ZD-3
ZD-4
VD
VD
VD
VD VD
VD
VD
20 cfm
20 cfm
EF-1
EF-2
1/2" UNDER CUT DOOR.
TYPICAL.
L-2
L-1
T
T
T
T
T
E1
20 CFM
E1
20 CFM
E1
20 CFM
E1
20 CFM
E1
20 CFM
E1
20 CFM
AHU-1
38"x18" 38"x18" 36"x18"
63"x23"
48"x20"
60"x18"
CU-1
8"x5"5"x5"
4"x4"4"x4"
VD VD VD
4"x4"
VD
VD
4"x4"
4"x4" ø5"
5"x5"
6"x6" 6"x6" ø6" ø6"
8"x8"
16"x10" ø6"
10"x8"
12"x8" ø6"
6"x6"
6"x6"
8"x6" ø8"
6"x6"6"x6" ø5"5"x5"
8"x7"
12"x10"
E1
50 CFM
E1
20 CFM E2
20 CFM
8"x6"
8"x6"
4"x4"
4"x4"
4"x4"
VD VD
VD
PROVIDE NEW 6"
CONCRETE PAD
MAINTAIN ALL SERVICE CLEARANCES
PER MANUFACTURER REQUIREMENTS
MD MD
MD
MOTORIZED
DAMPER SHALL BE
INTERLOCKED WITH
AHU-1
MOTORIZED DAMPER SHALL
ONLY OPEN IN ECONOMIZER
MODE.
MOTORIZED DAMPER IN THE
RETURN DUCT SHALL ONLY
CLOSE IN ECONOMIZER
MODE.
CONTRACTOR SHALL
RECONECT HWS & HWR TO
NEW AHU. SEE DETAIL
CONTRACTOR SHALL CONNECT NEW
REFRIGERANT LINES TO NEW AHU
PROVIDE SLEEVE FOR ALL NEW
REFRIGERANT PIPING GOING
THROUGH CONCRETE WALL. PROVIDE
HYDRAULIC CEMENT TO PREVENT
LEAKAGE.
CONNECT NEW 1" HWS
AND HWR TO EXISTING
PROVIDE A APRILAIRE MODEL E130C
DEHUMIDIFIER. 120V1PH SECURE TO
WALL AS REQUIRED. WHEN
DEHUMIDIFIER IS ACTIVATED THE
SUPPLY FAN ON AHU-2 SHALL START.
H
WALL MOUNTED DEHUMIDIFIER
CONTOL MODEL 76
PROVIDE PLENUM TO
EXISTING LOUVER.
CONNECT NEW EXHAUST
DUCT TO PLENUM
PROVIDE PLENUM TO
EXISTING LOUVER.
CONNECT NEW EXHAUST
DUCT TO PLENUM
TOILET
STORAGE
VD
4"x4"
E1
50 CFM
FD/SD
FD/SD
12"x8"
8"x8"
7"x6"
12"x6"
MOTORIZED DAMPER
INTERLOCKED WITH
AHU-2
MD
VD
VD
H
L-3
EL. MACHINE ROOM
PROVIDE MINI
SPLIT STAND
QUICK SLING
AC-1
CU-3
CONDENSING UNIT
LOCATED ON
GRADE LEVEL FIRST
FLOOR
T
VD
4"x4"
6"ø
5"x5"
CONRACTOR SHALL CLEAN ALL EXISTING SUPPLY AND RETURN AIR DUCTS, GRILLS
AND DIFFUSERS LOCATED ON THE FIRST FLOOR. INSPECT ALL EXISTING DUCTWORK
FOR ANY DAMAGE, CORROSION, OR OBSTRUCTION. CLEAN INTERIOR SURFACE OF
DUCT USING APPROPRIATE TOOLS AMD METHODS (HEPA VACUUM, BRUSHES).
ENSURE ALL DUCT CONNECTIONS ARE SECURE AND SEALED PROPERLY AFTER
CLEANING. DISPOSE OF DEBRIS AND CONTAMINANTS IN ACCORDANCE WITH LOCAL
REGULATIONS.
FD/SD FD/SD
HVAC NOTES
1. PIPING AND DUCT WORK LAYOUTS AS INDICATED ON THE DRAWINGS ARE DIAGRAMMATIC; PROVIDE ADDITIONAL TRANSITIONS AND OFFSETS AS REQUIRED FOR COORDINATION WITH BUILDING CONSTRUCTION
AND THE WORK OF OTHER TRADES AT NO ADDITIONAL COST TO THE OWNER.
2. PROVIDE VOLUME DAMPERS, THROTTLING VALVES AND ISOLATION VALVES AS SPECIFIED AND/OR AS
INDICATED ON THE DRAWINGS.
3. PROVIDE FIRE DAMPERS AT DUCT PENETRATIONS OF FIRE RATED PARTITIONS.
4. PROVIDE SMOKE DETECTORS ON THE SUPPLY AND RETURN DUCTWORK OF ALL AIR HANDLING EQUIPMENT
2000 CFM AND OVER.
5. ALL MOTORS AND EQUIPMENT SHALL BE OF EFFICIENCIES THAT ARE ELIGIBLE FOR UTILITY COMPANY
ENERGY INCENTIVE PROGRAMS.
6. THE BUILDING MANAGEMENT AND CONTROL SYSTEM SHALL BE COMPLETE IN ALL REGARDS, TESTED AND CAPABLE OF ACHIEVING THE SEQUENCES OF OPERATION. ALL DEVICES SHALL BE UNDER SYSTEM CONTROL.
ALL ZONES SHALL BE THERMOSTATICALLY CONTROLLED WHETHER OR NOT A THERMOSTAT, SENSOR OR
CONTROLLER IS INDICATED.
7. MAINTAIN MANUFACTURER'S RECOMMENDED MINIMUM CLEARANCES FOR INSTALLATION OF EQUIPMENT.
8. INSULATED FLEXIBLE DUCT RUNS SHALL NOT BE LONGER THAN 5 FT AND SHALL TERMINATE AT A 90 DEGREE
ELBOW MATCHING THE NECK SIZE OF THE DIFFUSER IT SERVES.
9. PROVIDE VANDAL RESISTANT COVERS ON THERMOSTATS, AS NOTED.
10. ALL DUCTWORK DIMENSIONS, AS SHOWN ON THE DRAWINGS, ARE INTERNAL CLEAR DIMENSIONS AND DUCT
SIZE SHALL BE INCREASED TO COMPENSATE FOR DUCT LINING THICKNESS.
11. PROVIDE ALL 90 DEGREE SQUARE ELBOWS WITH DOUBLE WALL TURNING VANES UNLESS OTHERWISE INDICATED. UNVANED ELBOWS SHALL BE SMOOTH RADIUS CONSTRUCTION WITH A RADIUS EQUAL TO 1-1/2 TIMES THE WIDTH OF THE DUCT. PROVIDE ACCESS DOORS UPSTREAM OF ALL ELBOWS WITH TURNING
VANES.
12. COORDINATE DIFFUSER, REGISTER AND GRILLE LOCATIONS WITH ARCHITECTURAL REFLECTED CEILING
PLANS, LIGHTING AND OTHER CEILING ITEMS.
13. PROVIDE INSULATED FLEXIBLE CONNECTIONS IN ALL DUCTWORK SYSTEMS CONNECTED TO AIR HANDLING UNITS, FANS AND OTHER EQUIPMENT WHICH REQUIRE VIBRATION ISOLATION. FLEXIBLE CONNECTIONS SHALL
BE AT THE POINT OF CONNECTION TO THE EQUIPMENT UNLESS OTHERWISE INDICATED.
14. PROVIDE INSULATED FLEXIBLE CONNECTIONS IN ALL DUCTWORK PASSING THROUGH BUILDING SEISMIC
EXPANSION JOINTS.
15. ALL DUCTWORK SHALL BE COORDINATED WITH ALL TRADES INVOLVED. OFFSETS IN DUCTS, INCLUDING DIVIDED DUCTS AND TRANSITIONS AROUND OBSTRUCTIONS, SHALL BE PROVIDED AT NO ADDITIONAL COST
TO THE OWNER.
16. PROVIDE ACCESS DOORS IN DUCTWORK TO PROVIDE ACCESS FOR ALL SMOKE DETECTORS, FIRE DAMPERS, SMOKE DAMPERS, VOLUME DAMPERS, COILS AND OTHER ITEMS LOCATED IN DUCTWORK WHICH REQUIRE
SERVICE OR INSPECTION.
17. DUCTWORK SHALL BE PRESSURE TESTED AND SEALED FOR LEAKAGE IN ACCORDANCE WITH THE CODE.
18. THE SUPPLY AIR SYSTEM SHALL BE PURGED TO ENSURE ALL FOREIGN PARTICLES ARE REMOVED PRIOR TO
FINAL CONNECTION OF SUPPLY AIR DIFFUSERS.
19. ALL ELBOWS AND TEES FROM DOWNFLOW ROOF MOUNTED UNITS SHALL BE WRAPPED WITH A SOUND
LAGGING MATERIAL.
20. ALL SUPPLY, RETURN AND OUTSIDE AIR DUCTWORK AND PLENUMS SHALL BE PROVIDED WITH INSULATION.
PIPING NOTES
1. UNLESS OTHERWISE NOTED, ALL PIPING IS OVERHEAD, TIGHT TO UNDERSIDE OF STRUCTURE OR SLAB, WITH
SPACE FOR INSULATION.
2. INSTALL PIPING SO THAT ALL VALVES, STRAINERS, UNIONS, TRAPS, FLANGES AND OTHER APPURTENANCES
REQUIRING ACCESS ARE ACCESSIBLE.
3. UNIONS AND/OR FLANGES SHALL BE INSTALLED AT EACH PIECE OF EQUIPMENT, IN BYPASSES AND IN LONG
PIPING RUNS (100 FEET OR MORE) TO PERMIT DISASSEMBLY FOR ALTERATION AND REPAIRS.
4. ALL PIPING WORK SHALL BE COORDINATED WITH ALL TRADES INVOLVED. OFFSETS IN PIPING AROUND
OBSTRUCTIONS SHALL BE PROVIDED AT NO ADDITIONAL COST TO THE OWNER.
5. PROVIDE FLEXIBLE CONNECTIONS IN ALL PIPING SYSTEMS CONNECTED TO PUMPS AND OTHER EQUIPMENT WHICH REQUIRE VIBRATION ISOLATION, EXCEPT WATER COILS. FLEXIBLE CONNECTIONS SHALL BE PROVIDED
AS CLOSE TO THE EQUIPMENT AS POSSIBLE.
6. ALL PENETRATIONS THRU RATED WALLS, FLOORS & CEILINGS SHALL BE SEALED USING U.L. LISTED METHODS
APPROPRIATE FOR INDICATED ASSEMBLY RATING.
7. PROVIDE SWING JOINTS AT ALL BRANCH CONNECTIONS TO WATER SUPPLY AND RETURN. PROVIDE ISOLATION
VALVES AT ALL BRANCH CONNECTIONS.
8. PROVIDE AIR VENTS AT ALL HIGH POINTS.
9. INSTALL DRAIN VALVES WITH HOSE CONNECTION AT ALL LOW POINTS.
10. PROVIDE HOSE END CAPS WITH CHAIN ON ALL DRAIN VALVES.
11. ALL PIPING PASSING THROUGH BUILDING EXPANSION JOINTS SHALL BE PROVIDED WITH PIPING EXPANSION
LOOPS.
12. ALL PIPING, VALVES AND FITTINGS SHALL BE PROVIDED WITH INSULATION FOR SERVICES REQUIRING
INSULATION.
13. ALL EXISTING PIPING AND ASSOCIATED FITTINGS THAT ARE TO REMAIN TEMPORARILY AS PART OF THE CONSTRUCTION MANAGER'S STAGING PLAN AND THAT ARE AFFECTED BY ABATEMENT WORK SHALL BE
PROVIDED WITH NEW INSULATION. REFER TO ABATEMENT DRAWINGS AND PROJECT MANUAL.
RENOVATION NOTES
1. THIS PROJECT IS AN EXISTING FACILITY RENOVATION.
2. BEFORE SUBMITTING BIDS, THE CONTRACTOR SHALL VISIT THE SITE AND BECOME
THOROUGHLY FAMILIAR WITH THE EXISTING CONDITIONS UNDER WHICH THE PROJECT IS
TO BE COMPLETED.
3. THE CONTRACTOR SHALL BE HELD RESPONSIBLE FOR ANY ASSUMPTIONS, OMISSIONS OR
ERRORS MADE AS A RESULT ON OF THEIR FAILURE TO BECOME FULLY FAMILIAR WITH THE
EXISTING CONDITIONS.
4. IT IS NOT THE INTENT OF THESE DRAWINGS TO SHOW EVERY PIECE OF EQUIPMENT, PIPING
OR CONDUIT TO BE REMOVED. EQUIPMENT NOT BEING USED SHALL BE REMOVED
INCLUDING ALL ASSOCIATED HANGERS, SUPPORTS, PIPES, DUCTS, CONDUITS, WIRES AND
CONTROLS BACK TO THE POINT OF ORIGIN.
5. NO EQUIPMENT, PIPING OR CONDUIT SHALL BE ABANDONED IN PLACE UNLESS
SPECIFICALLY NOTED.
6. PROPERLY DISPOSE OF ALL DEMOLISHED EQUIPMENT AND MATERIALS IN COMPLIANCE
WITH CODES AND REGULATIONS.
7. RELOCATE EXISTING EQUIPMENT, PIPING, WIRING AND RELATED SYSTEMS TO REMAIN AS
REQUIRED FOR CONSTRUCTION. EXTEND FEEDER/CONDUIT AND PROVIDE
RECONNECTIONS FOR SYSTEM TO BE FULLY OPERATIONAL. ALL RELOCATED EQUIPMENT
SHALL BE PROTECTED DURING CONSTRUCTION.
8. PROVIDE TEMPORARY CONNECTIONS AND SYSTEM MODIFICATIONS AS REQUIRED FOR
PHASED CONSTRUCTION.
9. INCLUDE ALL WORK REQUIRED TO ALLOW STAGED CONSTRUCTION . COORDINATE WITH
GENERAL CONTRACTOR/CONSTRUCTION MANAGER FOR SEQUENCE OF CONSTRUCTION
REQUIREMENTS.
10. GENERAL CONTRACTOR IS RESPONSIBLE FOR PATCHING, REPAIRING, CAPPING, ETC. PER
DEMOLITION AND CONSTRUCTION REQUIREMENTS.
DRAWING TITLE:REVISED BY:DATE:DESCRIPTION:REVISION:PROJECT TITLE: DATE:
SCALE:
DRAWN BY:
PROJECT NUMBER:
DRAWING NUMBER:
SILVER PETRUCELLI + ASSOCIATES
203 230 9007
3190 WHITNEY AVENUE HAMDEN CT 06518
silverpetrucelli.com
311 STATE STREET NEW LONDON CT 06320
PROJECT SUBMISSION:
STATE PROJECT NUMBER:
RENOVATIONS TO
BROOKLYN SENIOR CENTER
69 SOUTH MAIN STREET
BROOKLYN, CT
ISSUED FOR BID
25.099
10-16-2026
As indicated
/1
9/
:2 2:
P
M
M110
MECH LOWER LEVEL DUCT PLAN
R. LUCENTE
1/8" = 1'-0"1 LOWER LEVEL DUCT PLAN
1 ADDENDUM # 1 10-19-26 RL1 ADDENDUM # 1 10-19-26 RL
36" INDICATES MOUNTING HEIGHT TO CENTER OF DEVICE
A AMPERES
ACR AUTOMATICALLY CONTROLLED RECEPTACLE
AD DEVICE DEDICATED FOR AUTO DOOR OPENER
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
ATS AUTOMATIC TRANSFER SWITCH
AV DEVICE DEDICATED FOR AUDIOVISUAL EQUIPMENT (VERIFY MOUNTING HEIGHT AND
LOCATION IN FIELD WITH AUDIOVISUAL INSTALLER PRIOR TO ROUGH-IN)
BF BOTTLE FILLING STATION
C CONDUIT
CB CIRCUIT BREAKER
CKT CIRCUIT
CP CONDENSATE PUMP
EC ELECTRICAL CONTRACTOR
EM EMERGENCY SHUT-OFF SWITCH
EWC ELECTRIC WATER COOLER
FAA FIRE ALARM ANNUNCIATOR
FACP FIRE ALARM CONTROL PANEL
FAP FIRE ALARM COMMUNICATIONS PANEL
FB FLOOR BOX
FRZ RECEPTACLE DEDICATED FOR FREEZER
FV ELECTRONIC FLUSH VALVE
GFI GROUND FAULT CIRCUIT INTERRUPTER
HD HAND DRYER
HFW HOT FOOD WELL
HM HORIZONTALLY MOUNTED
HT HEAT TRACE
INV INVERTER
ISA INFRARED SENSOR ACTIVATION (LAVATORY FAUCET & WATER CLOSET FLUSH VALVE)
JB JUNCTION BOX
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MD MOTORIZED DAMPER
MDS MAIN DISTRIBUTION SECTION
MFD RECEPTACLE DEDICATED FOR MULTI-FUNCTION DEVICE
MLO MAIN LUG ONLY
MSD MAIN SERVICE DISCONNECT
MTD MOUNTED
MW RECEPTACLE DEDICATED FOR MICROWAVE
PIT DEVICE MOUNTED IN PIT (VERIFY EXACT LOCATION IN FIELD)
PNL PANELBOARD
REF RECEPTACLE DEDICATED FOR REFRIGERATOR
SM RECEPTACLE DEDICATED FOR SOUND MASKING EQUIPMENT
SF SENSOR FAUCET
ST SHUNT TRIP FOR ELEVATOR
TBB TELEPHONE BACKBOARD
TP TRAP PRIMER
TR TAMPER RESISTANT
UC UNDER COUNTERTOP MOUNTED DEVICE
U.O.N. UNLESS OTHERWISE NOTED
WG WIRE GUARD
WP WEATHERPROOF
ABBREVIATIONS (NOT ALL MAY BE USED)
ELECTRICAL POWER SYMBOLS
DUPLEX RECEPTACLE; MOUNT AT 18" AFF UNLESS OTHERWISE SPECIFIED
SINGLE RECEPTACLE; MOUNT AT 18" AFF UNLESS OTHERWISE SPECIFIED
LIGHTING AND CONTROL SYMBOLS
RECESSED LIGHT FIXTURE; LETTER INDICATES FIXTURE TYPE; E INDICATES EMERGENCY; N
INDICATES EMERGENCY/NIGHTLIGHT
SINGLE POLE SWITCH OR DISCONNECT; MOUNT AT 48" AFF, OR AT EQUIPMENTS
TYPICAL WALL MOUNTED LIGHT FIXTURE; LETTER INDICATES FIXTURE TYPE
TYPICAL RECESSED LIGHT FIXTURE; LETTER INDICATES FIXTURE TYPE
EMERGENCY LIGHT FIXTURE CONNECTED TO THE EMERGENCY DISTRIBUTION SYSTEM OR
INVERTER
NE
TYPICAL EXTERIOR WALL MOUNTED LIGHT FIXTURE; LETTER INDICATES FIXTURE TYPE
SINGLE FACE EXIT SIGN, SHADING INDICATES DIRECTION OF FIXTURE FACE, ARROWS INDICATES
DIRECTION OF CHEVRONS, PROVIDE UNSWITCHED POWER FROM AREA LIGHTING CIRCUIT
KEYED SINGLE POLE SWITCH; MOUNT AT 48" AFF
KEYED 3-WAY SWITCH; MOUNT AT 48" AFF
KEYED 4-WAY SWITCH; MOUNT AT 48" AFF
SINGLE POLE SWITCH WITH PILOT LIGHT; MOUNT AT 48" AFF
S K
S3K
S 4K
SP
MULTI-LOCATION DIMMING SWITCH; MOUNT AT 48" AFF, COMPATIBLE WITH LOAD CONTROLLED
DIMMING SWITCH; MOUNT AT 48" AFF, COMPATIBLE WITH LOAD CONTROLLED
DUAL TECHNOLOGY, OCCUPANCY SENSOR SWITCH; MOUNT AT 48" AFFSM
SD
S 3D
3-WAY SWITCH; MOUNT AT 48" AFF
4-WAY SWITCH; MOUNT AT 48" AFF
S 3
S 4
COMMUNICATIONS SYMBOLS
CEILING MOUNTED DATA JACK: #D DEPICTS # OF JACKS NEEDED, PROVIDE 1 OTHERWISE.
DATA JACK: #D/#V DEPICTS # OF JACKS NEEDED, PROVIDE 1 OTHERWISE.
FLOOR MOUNTED DATA JACK: #D DEPICTS # OF JACKS NEEDED, PROVIDE 1 OTHERWISE.
VOICE JACK: #V DEPICTS # OF JACKS NEEDED, PROVIDE 1 OTHERWISE.
CALL-FOR-AID SWITCH. MOUNT AT 36" AFF WITH PULL CORD HANGING DOWN TO 6" AFF
CALL-FOR-AID CORRIDOR LIGHT/BUZZER, MOUNT AT 7'-6" AFF
ELECTRICAL ALARM BELLB
E
E
DOUBLE FACED EXIT SIGN, SHADING INDICATES DIRECTION OF FIXTURE FACE, ARROWS INDICATES
DIRECTION OF CHEVRONS, PROVIDE UNSWITCHED POWER FROM AREA LIGHTING CIRCUIT
RECEPTACLE WITH METALLIC OUTDOOR RATED "IN-USE" COVER PLATE, PROVIDE FLUSH
MOUNTED BOX
WP
TYPICAL PENDANT/CHAIN HUNG LIGHT FIXTURE; LETTER INDICATES FIXTURE TYPE
TYPICAL SURFACE MOUNTED LIGHT FIXTURE; LETTER INDICATES FIXTURE TYPE
TYPICAL LINEAR RECESSED LIGHT FIXTURE; LETTER INDICATES FIXTURE TYPE
EMERGENCY/NIGHTLIGHT FIXTURE CONNECTED TO THE EMERGENCY DISTRIBUTION SYSTEM OR
INVERTER
E E
N N
CEILING MOUNTED DUAL TECHNOLOGY OCCUPANCY SENSOR (INFRARED/ULTRASONIC) WITH 360°
COVERAGE
CEILING MOUNTED HIGH BAY DUAL TECHNOLOGY OCCUPANCY SENSOR (15-45 FT HIGH MOUNTING
RANGE) WITH 360° COVERAGE
WALL OR CEILING MOUNTED DUAL TECHNOLOGY OCCUPANCY SENSOR (INFRARED/ULTRASONIC)
WITH 180° COVERAGE
OC
OC
HB
OC
QUAD RECEPTACLE; MOUNT AT 18" AFF UNLESS OTHERWISE SPECIFIED
SPECIAL RECEPTACLE CONFIGURATION - NEMA# AS INDICATED. COORDINATE EXACT NEMA#
WITH APPROVED EQUIPMENT BEING INSTALLED.
FLOOR MOUNTED RECEPTACLE; SEE FLOOR PLANS FOR DETAILS
CEILING MOUNTED DUPLEX RECEPTACLE; PROVIDE FLUSH MOUNTED BOX
PANELBOARD
DISCONNECT SWITCH - FUSED
DISCONNECT SWITCH - NON-FUSED
J
J
SXX
WALL MOUNTED JUNCTION BOX, ACCORDING TO NEC REQUIREMENTS
CEILING MOUNTED JUNCTION BOX, ACCORDING TO NEC REQUIREMENTS
AUTO DOOR OPEN - WALL MOUNTED ACTIVATION STATIONA
HEAT TRACE SYSTEM CONTROL PANELHT
SINGLE POLE DISCONNECT SWITCH. XX = EQUIPMENT TYPE
BRANCH CIRCUIT HOMERUN (PANEL/CIRCUIT DESIGNATION)CKT
BRANCH CIRCUIT WIRINGCKT
CONTROL CIRCUIT WIRINGCKT
FIRE ALARM SYMBOLS
SMOKE DETECTOR; "R" DENOTES ELEVATOR RECALL DEVICES
HEAT DETECTOR; 135° U.O.N.; ST DENOTES FOR ELEVATOR SHUNT TRIP
H
DUCT MOUNTED IONIZATION SMOKE DETECTORS
D
AR AREA OF RESCUE ASSISTANCE - LIGHTED SIGN
AREA OF RESCUE ASSISTANCE - CALL STATION
AOR
DRAWING TITLE:REVISED BY:DATE:DESCRIPTION:REVISION:PROJECT TITLE: DATE:
SCALE:
DRAWN BY:
PROJECT NUMBER:
DRAWING NUMBER:
SILVER PETRUCELLI + ASSOCIATES
203 230 9007
3190 WHITNEY AVENUE HAMDEN CT 06518
silverpetrucelli.com
311 STATE STREET NEW LONDON CT 06320
PROJECT SUBMISSION:
RENOVATIONS TO
BROOKLYN SENIOR CENTER
69 SOUTH MAIN STREET
BROOKLYN, CT
ISSUED FOR BID
25.099
10/16/2026
NONE
/1
9/
:5 1:
P
M
E001
ELEC ABBREVIATIONS AND
LEGENDS
D. Turner
ELECTRICAL DRAWING LIST
E001 ELEC ABBREVIATIONS AND LEGENDS
E002 ELEC GENERAL NOTES
E010 ELEC LOWER LEVEL LIGHTING DEMO PLAN
E020 ELEC LOWER LEVEL POWER DEMO PLAN
E110 ELEC LOWER LEVEL LIGHTING PLAN
E210 ELEC LOWER LEVEL POWER PLAN
E300 ELEC SITE LIGHTING PLAN - BID ALTERNATE
E500 ELEC SCHEDULES
E600 ELEC DETAILS
1 ADDENDUM #1 10-19-26 DT1 ADDENDUM #1 10-19-26 DT
E
E
E
E
S D
S D
CU-1
CU-2
EF-1
DH-1
EF-2
EWC/BF
OP-1
ATS
MSDB TR-1LS
METER
MSD
AC-1
CU-3
STORAGE
STORAGE
019A
STORAGE
018A
CORRIDOR
ELEVATOR
EL1.0
EL.
MACHINE
ROOM
STORAGE
EXERCISE
ROOM
GROUP
EXERCISE
ROOM
CRAFT
ROOM
GAME
ROOM
CORRIDOR
ELECTRICAL
STAIRS
ST1.0
ELECTRICAL
TOILET
TOILET
CORRIDOR
MECHANICAL
MECHANICAL
STORAGE
MECHANICAL
JANITOR
STORAGE
AREA
WAY
CLT
017A
HPHWH-1
UH
GFI/48"
G F
I/4 8"
G F
I/4 8"
GFI/48"
GFI/48"
GFI/48"GFI/48"
G F
I/4 8"
G F
I/4 8"
G F
I/4 8"
48"
60"
AHU-2
AHU-1
E M
E M
G F
I/W P
SUB METERS
GFI/WP
TR-1LS /16
RP-1
M S
D B
TR-1LS /32
TR-1LS /31
TR-1LS /33
TR-1LS /35
TR-1LS /37
TR-1LS /39
TR-1LS /1
TR-1LS /9
T R
-1
LS
TR-1LS /34
TR-1LS /13
TR-1LS /17
TR-1LS /15
TR-1LS /19
TR-1LS /21
CT-1
M S
D B
/8 ,1
0, MSDB
/7,9,11
MSDB /33,35
MSDB /43,45
T R
-1
LS
/6 ,8 T
R -1
LS
/2
,4
M S
D B
/1 4, ,1
TR-1LS /3
MSDB /20
D H
TR-1LS /5
CP
TR-1LS
/26,28
AR
AOR
GENERAL POWER NOTES
POWER KEY NOTES
1. FURNISH AND INSTALL ALL ELECTRICAL EQUIPMENT, DEVICES,
AND WIRE AS INDICATED ON PLAN AND DIAGRAMS, SHOWN AS
DARK AND SOLID, UNLESS OTHERWISE NOTED BY KEY NOTE.
2. ALL NEW ELECTRICAL DEVICES MOUNTED ON EXISTING
CONCRETE WALLS (POURED OR BLOCK), MUST BE FED WITH
SURFACE MOUNTED "WIREMOLD" RACEWAY TYPE 500 OR 700
SERIES. PROVIDE ALL NECESSARY ACCESSORIES, CONNECTIONS
AND FITTINGS FOR A COMPLETE SYSTEM.
3. ALL ELECTRICAL EQUIPMENT, DEVICES, ETC. SHOWN AS LIGHT
(HALF-TONE) AND SOLID ARE EXISTING TO REMAIN, UNLESS
OTHERWISE NOTED BY KEY NOTE.
4. CONTRACTOR IS RESPONSIBLE FOR MAINTAINING THE
CONTINUITY OF ALL EXISTING BRANCH CIRCUITS AFFECTED BY
THIS RENOVATION AND PROVIDE ADDITIONAL WIRING AS NEEDED.
5. REFER TO DRAWINGS E001 & E002 FOR GENERAL NOTES,
ABBREVIATIONS & ELECTRICAL LEGEND.
6. REFER TO E600 SERIES DRAWINGS FOR DETAILS AND WIRING
DIAGRAMS.
7. REFER TO E500 SERIES DRAWINGS FOR SWITCHBOARD AND
PANELBOARD SCHEDULES.
ELECTRICAL MAIN SERVICE DISCONNECT SWITCH AND UTILITY
METER TO REMAIN.
ELECTRICAL PANEL TO REMAIN. REFER TO E500 SERIES PLANS
FOR PANEL SCHEDULE INFORMATION AND REQUIREMENTS.
AUTOMATIC TRANSFER SWITCH TO REMAIN.
SUB-METERS TO REMAIN.
TELEPHONE BACKBOARD TO REMAIN.
REFER EQUIPMENT SCHEDULE ON E500 PLAN FOR POWER
REQUIREMENTS.
EXISTING ELECTRICAL SERVING EQUIPMENT TO REMAIN.
INSTALL RELOCATED (HP) HEAT PUMP EMERGENCY SHUT-OFF
SWITCH AND EXTEND/MODIFY WIRING AS REQUIRED.
FURNISH AND INSTALL NEW (HWH-1) WATER HEATER
EMERGENCY SHUT-OFF SWITCH AND WIRE AS REQUIRED.
FURNISH AND INSTALL NEW DISCONNECT SWITCHES FOR
WATER HEATER AND RE-CIRCULATION PUMP. EXTEND MODIFY
EXISTING BRANCH CIRCUIT WIRING TO DISCONNECT SWITCHES
AND NEW EQUIPMENT AS REQUIRED.
FURNISH AND INSTALL AREA OF RESCUE ASSISTANCE SURFACE
MOUNTED CALL STATION AT THIS LOCATION WITH FIXED
COMMAND UNIT, SUB-COMMAND UNIT, AND STROBE/SIREN
LOCATED ON THE FIRST FLOOR. PROVIDE COMPLETE AOR
SYSTEM REQUIREMENTS AND WIRE AS INDICATED ON DRAWING
E600 DETAIL 10.
FURNISH AND INSTALL AREA OF RESCUE ASSISTANCE
ILLUMINATED SIGNAGE AND WIRE TO LINE SIDE OF LOCAL LIGHT
CIRCUIT. REFER TO DRAWING E600 DETAIL 10 FOR
REQUIREMENTS.
DRAWING TITLE:REVISED BY:DATE:DESCRIPTION:REVISION:PROJECT TITLE: DATE:
SCALE:
DRAWN BY:
PROJECT NUMBER:
DRAWING NUMBER:
SILVER PETRUCELLI + ASSOCIATES
203 230 9007
3190 WHITNEY AVENUE HAMDEN CT 06518
silverpetrucelli.com
311 STATE STREET NEW LONDON CT 06320
PROJECT SUBMISSION:
RENOVATIONS TO
BROOKLYN SENIOR CENTER
69 SOUTH MAIN STREET
BROOKLYN, CT
ISSUED FOR BID
25.099
10/16/2026
As indicated
/1
9/
:5 1:
P
M
E210
ELEC LOWER LEVEL POWER PLAN
D. Turner
1/8" = 1'-0"1 ELEC LOWER LEVEL POWER PLAN
TBB
1 ADDENDUM #1 10-19-26 DT1 ADDENDUM #1 10-19-26 DT
11 12
PROVIDE PENDANT WHERE HUNG CEILING
OR STRUCTURE EXCEEDS 102" A.F.F.
EXIT SIGN
EMERGENCY POWER OFF (E.P.O.)
SWITCHES
NOTES:
1. ALL MOUNTING HEIGHTS SHALL BE
MEASURED FROM FINISHED FLOOR TO
CENTERLINE OF DEVICE (EXCEPT FOR
DEVICES SHOWN OTHERWISE).
2. DEVICES SHALL BE INSTALLED ON A
COMMON VERTICAL CENTERLINE
WHEREVER POSSIBLE.
3. ALL DEVICES SHALL BE INSTALLED AT
THE MOUNTING HEIGHTS INDICATED
ON THIS DETAIL, UNLESS OTHERWISE
NOTED. REFER TO ARCHITECTURAL
INTERIOR ELEVATIONS FOR MOUNTING
HEIGHTS OF RECEPTACLES LOCATED
ABOVE COUNTERS.
COUNTER HEIGHT OUTLETS
(MTD. 6" ABOVE COUNTER - REFER
TO ARCHITECTURAL ELEVATIONS)
RECEPTACLE
TEL/DATA OUTLET
CONDUITCONDUIT
NOTES:
1. PROVIDE UL LISTED FIRE/SMOKE PENETRATION ASSEMBLY IN
ACCORDANCE W/ UL1479, ASTM E814 REQUIREMENTS FOR WALL
TYPE, RATING, PIPE SIZE INSTALLED.
2. FIRESTOPPING SHALL HAVE A RATING EQUAL TO OR GREATER THAN
THE WALL BEING PENETRATED - SEE SPECIFICATIONS. REFER TO
ARCHITECTURAL DRAWINGS FOR WALL RATINGS AND LOCATIONS.
SCHEDULE 40 GALVANIZED
PIPE SLEEVE
FIRE OR SMOKE RATED
DRYWALL PARTITION
FIRESTOP SEALANT
UL LISTED FIRE SEALANT
REFER TO SPEC. SECTION
GROUT SLEEVE IN
MASONRY WALL
SCHEDULE 40 GALVANIZED
PIPE SLEEVE
UL LISTED FIRE SEALANT
REFER TO SPEC. SECTION
FIRE OR SMOKE RATED
CONCRETE/MASONRY WALL
ANCHOR AND WATER
STOP PLATE
STANDARD WEIGHT
STEEL PIPE
ANCHOR AND WATER
STOP PLATE
CONDUIT
BUILDING WALL
STANDARD WEIGHT
STEEL PIPE
PRESSURE PLATES,
BOLTS AND NUTS
LINK SEAL RUBBER
SEALING ELEMENT
WALL THICKNESS
(2) #12 GA. WIRES ATTACHED TO FIXTURE AND
STRUCTURE, AT OPPOSITE CORNERS. INSTALL
AN ADDITIONAL (2) #12 GA. WIRES ATTACHED
TO FIXTURE AND STRUCTURE AT OPPOSITE
CORNERS FOR EMERGENCY LIGHT FIXTURES.
LIGHTING FIXTURE PER
DRAWINGS AND SCHEDULE
CEILING GRID AS CALLED
FOR ON ARCH. DRAWINGS
KEY NOTES:
ATTACH WIRE TO FIXTURE (3 TIGHT TURNS MIN. IN 1 1/2" MAX.).
ATTACH HANGER WIRES TO STRUCTURE AS PER STRUCTURAL & ARCHITECTURAL DETAILS.
CEILING SYSTEM SPLAY/HANGER WIRES AS OCCURS, SEE PLANS.
EMERGENCY NOTES:
1. PROVIDE THE EDWARDS #6538-G5 CALL FOR
ASSISTANCE KIT.
2. TRANSFORMER SHALL BE INSTALLED ABOVE
ACCESSIBLE CEILING.
3. PROVIDE ALL WIRING FOR A COMPLETE
INSTALLATION.
120VAC - (2)#12 & (1)#12 GND. IN 3/4"C. TO
PANEL & CIRCUIT BREAKER AS INDICATED
ON DRAWINGS.
(2)#12 & (1)#12 GND. 3/4"C.
PULL CORD STATION WITH RESET SWITCH
HORN & STROBE WITH CLEAR LENS
TRANSFORMER 24VDC OUTPUT
ACCESSIBLE CEILING
NOTES:
1. REFER TO SPECIFICATIONS FOR ELEVATOR RECALL
WIRING REQUIREMENTS.
DUAL CONTACT FIXED HEAT DETECTOR (RATED FOR 190°)S
R
H R
S R
S R
S R
LOWER LEVEL
MAIN LEVEL
DEVICES MOUNTED
AT TOP OF SHAFT
H R
S R
TO CIRCUIT BREAKER,
REFER TO FLOOR PLAN
& PANEL SCHEDULE
FUSIBLE SHUNT TRIP
DISCONNECT SWITCH
SERVING ELEVATOR
CONTROLLER
ELEVATOR MACHINE ROOM ELEVATOR SHAFT ELEVATOR LOBBY
TO ELEVATOR CONTROLLER.
COORDINATE LOCATION
WITH ELEVATOR INSTALLER.
ELEVATOR PIT
ROOF
FINISHED GRADE
24"
3/4" DIAMETER 10'-0"
LONG ROUND ROD -
LOCATE ADJACENT
TO FOUNDATION
#8 BARE COPPER GROUND WELDED TO
INTERNAL LUG IN POLE - SIZE IN
ACCORDANCE WITH NFPA 70- PROVIDE
ADDITIONAL CONDUIT SWEEP
ANCHOR BOLTS FURNISHED
BY THE POLE MANUFACTURER
1" PVC SWEEPS
CLASS "PCC03340"
CONCRETE
8 #5 VERTICAL
BARS WITH #3 AT
12" O.C. - CIRCULAR TIES
LIGHT POLE
1" PVC STUBBED
UP 1" ABOVE
FOUNDATION
6' -6
CONFIRM EXACT BOLT CIRCLE
DIAMETER FOR POLES WITH
APPROVED SHOP DRAWINGS.
NEW ANCHOR BOLTS WILL NEED
TO BE PROVIDED FOR EACH POLE.
ADJUST DIAMETER OF POLE
FOUNDATION FOR POLES
PER REQUIREMENTS OF
APPROVED POLE SHOP
DRAWINGS. MINIMUM OF 12"
NOTE
VERIFY ANCHOR BOLT SIZE, BOLT CIRCLE
DIAMETER AND BOLT PROJECTION HEIGHT
WITH LIGHTING STANDARD MANUFACTURER
PRIOR TO BASE CONSTRUCTION.
1" CHAMFER
MAGNETIC MARKING
TAPE FOR CAUTION
ELECTRICAL CONDUIT
AS SPECIFIED ON PLANS
6"
36" COMPACTIVE
NATIVE
MATERIAL
36"
FINISHED GRADE
12" MASON SAND
12" MAX.
MAGNETIC MARKING
TAPE FOR CAUTION
6"
36"
SAWCUT IF
REQUIRED
NEW BITUMINOUS OR
CONCRETE PAVEMENT
EXISTING BITUMINOUS OR
CONCRETE PAVEMENT
6"
18" (MAX)
12" MASON SAND
12" MAX.
ELECTRICAL CONDUIT AS
SPECIFIED ON PLANS
NOTES:
1. REFER TO PLANS AND SPECIFICATIONS FOR QUANTITIES AND LOCATIONS OF DEVICES.
2. MANUFACTURED BY TALK-A-PHONE OR EQUAL.
3. WHEN ACTIVATED, SYSTEM SHALL REPORT TO THE LOCAL COMMAND UNIT, IF NOT
ANSWERED IT WILL ROLL OVER TO THE MAIN OFFICE, AND THEN IF NOT ANSWERED ON
TO OFF SITE SUPERVISED 24/7 FACILITY.
4. AREA OF RESCUE COMMAND UNIT SHALL BE LOCATED AT MAIN ENTRY ON GRADE LEVEL
FLOOR OR AS DETERMINED BY AHJ.
120V AC
DEDICATED PHONE LINE
AOR-5-10-PSU
POWER SUPPLY
AOR-5-DKL
SURFACE
COMMAND UNIT
(FIRST FLOOR
ENTRY 101)
STROBE/SIREN
AOR-SCU-1
SUB-COMMAND
UNIT
(FIRST FLOOR
OFFICE 111)
AREA OF RESCUE ILLUMINATED SIGNS SHALL
MEET CT BUILDING CODES FOR SYMBOL AND
LETTER HEIGHT REQUIREMENTS.
AOR
AOR-CSE-SM
EMERGENCY
CALL STATION
(LOWER LEVEL
CORRIDOR 001)
AREA OF
RESCUE
ASSISTANCE
120V AC
ETP-SIGN/LDR
LIGHTED SIGN
DRAWING TITLE:REVISED BY:DATE:DESCRIPTION:REVISION:PROJECT TITLE: DATE:
SCALE:
DRAWN BY:
PROJECT NUMBER:
DRAWING NUMBER:
SILVER PETRUCELLI + ASSOCIATES
203 230 9007
3190 WHITNEY AVENUE HAMDEN CT 06518
silverpetrucelli.com
311 STATE STREET NEW LONDON CT 06320
PROJECT SUBMISSION:
RENOVATIONS TO
BROOKLYN SENIOR CENTER
69 SOUTH MAIN STREET
BROOKLYN, CT
ISSUED FOR BID
25.099
10/16/2026
NOT TO SCALE
/1
9/
:5 1:
P
M
E600
ELEC DETAILS
D. Turner
NOT TO SCALE5 TYPICAL DEVICE MOUNTING HEIGHT DETAIL
NOT TO SCALE2 WALL PENETRATION WITH FIRE-SMOKE SEAL DETAIL
NOT TO SCALE3 WATER-TIGHT WALL SLEEVE DETAIL
NOT TO SCALE1 RECESSED LAY-IN FIXTURE MOUNTING DETAIL
NOT TO SCALE4 CALL FOR ASSISTANCE
NOT TO SCALE6 ELEVATOR SERVICE SHUNT-TRIP CONTROL DIAGRAM
NOT TO SCALE7 POLE FOUNDATION DETAIL - BID ALTERNATE
NOT TO SCALE8 CONDUIT TRENCH DETAIL - BID ALTERNATE
NOT TO SCALE9 CONDUIT TRENCH DETAIL BELOW ROADWAY - BID ALTERNATE
1 ADDENDUM #1 10-19-26 DT1 ADDENDUM #1 10-19-26 DT
NOT TO SCALE10 AREA OF RESCUE WIRING DIAGRAM