Summary of Brooklyn Senior Center Renovations Bid Documents
This document set comprises architectural and structural bid drawings for renovation work at the Brooklyn Senior Center located at 69 South Main Street, Brooklyn, Connecticut, issued for bid on October 16, 2026, by the Town of Brooklyn with design prepared by Silver Petrucelli + Associates. The project encompasses comprehensive renovations to both the lower level and first floor of the existing senior center facility, including structural repairs, MEP system upgrades, interior partition modifications, flooring and finish replacements, roof restoration, and accessibility improvements. The scope includes demolition of existing conditions, installation of new concrete foundations and slabs, structural steel connections, new elevator installation, stair replacement (with alternate concrete stair option), wall and partition construction using metal studs and masonry infill, new roofing with asphalt shingles and EPDM membrane, interior finishes including VCT and resilient flooring, painting, toilet room renovations, and complete signage package. Sealed bids are due November 5, 2026, at 1:00 p.m. at the Brooklyn First Selectman's Office; a pre-bid addendum was issued October 19, 2026. The successful bidder must provide 100% Performance and Payment Bonds and maintain minimum insurance coverage as required by the Connecticut Department of Housing.
The contract documents, dated October 16, 2026, specify detailed construction requirements including concrete specifications with 4500 PSI strength for foundations and 3500 PSI for slabs, reinforcing steel per ASTM standards, welded wire fabric reinforcement, structural steel ASTM A36 and A992 materials, and post-installed anchor requirements with certification and testing protocols. Construction must comply with the 2021 International Building Code as adopted by Connecticut, including wind load criteria based on 125 mph ultimate wind speed for Risk Category II occupancy, seismic design provisions, and fire-resistance ratings ranging from 1 to 2 hours for various building elements. The project involves coordination among multiple trades including mechanical, electrical, plumbing, and fire protection systems, with the contractor responsible for field verification of all existing conditions, temporary shoring design and installation, and protection of materials during construction. Pricing information, specific bid amount, and funding sources are not disclosed in the architectural and structural drawing set provided.
View the file
Other files
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ARCHITECT
SILVER PETRUCELLI & ASSOC.
3190 WHITNEY AVENUE, HAMDEN CT 06518
311 STATE STREET NEW LONDON, CT 06320
PHONE 203 230 9007 silverpetrucelli.com
M/E/P/FP
SILVER PETRUCELLI & ASSOC.
3190 WHITNEY AVENUE, HAMDEN CT 06518
311 STATE STREET NEW LONDON, CT 06320
PHONE 203 230 9007 silverpetrucelli.com
STRUCTURAL
MICHAEL HORTON ASSOCIATES INC
780 EAST MAIN STREET
BRANFORD, CT 06405
PHONE 203 481 8600 mha-eng.com
ELEVATOR
STERLING ELEVATOR CONSULTANTS, LLC
195 WEST MAIN STREET, SUITE 1, AVON, CT 06001
PHONE 800 209 9909 sterlingec.com
SILVER
203 230 9007
3190 WHITNEY AVENUE HAMDEN
silverpetrucelli.com
CT 06320
ASSOCIATESPETRUCELLI +
CT 06518
311 STATE STREET NEW LONDON
10/16/2026ISSUED FOR BID
PROJECT TITLE:
RENOVATIONS TO
BROOKLYN SENIOR CENTER
69 SOUTH MAIN STREET
BROOKLYN, CT
BRICK
CONCRETE
CONCRETE MASONRY UNIT (CMU)
RIGID BOARD INSULATION
INSULATION (BATT)
EARTH
GYPSUM BOARD
PLYWOOD
WOOD FRAMING (THROUGH MEMBER)
WOOD FRAMING (INTERRUPTED MEMBER)
ACOUSTICAL TILE OR PANEL
WOOD TRIM/FINISH
DRAWING NUMBER
CX
DETAIL NUMBER
CONSTRUCTION NOTE
ROOM NUMBER
WINDOW TYPE
DX DEMOLITION NOTE
DOOR NUMBER
EXISTING DOOR
NEW DOOR
DOUBLE LEAF DOOR
DOOR W/ 180 HOLD OPEN
UNEQUAL LEAF DOOR
TWO-WAY DOOR
EXISTING DOOR TO BE REMOVED
ROOM NAMEROOM NAME
ACT-1
ROOM IDENTIFICATION
CEILING PLAN
ROOM IDENTIFICATION
ROOM NAME
MATERIAL - HEIGHT
CB1
18"
PREMANUFACTURED
CASEWORK SYMBOL
CABINET TYPE
NOMINAL HEIGHT/WIDTH
SPECIAL DEPTH &/OR EQUIP.
POCKET DOOR
BI- FOLDING DOOR
SLIDING DOOR
DOUBLE ACTING DOOR
CPT-1
ROOM NAME
FINISH FLOOR PLAN
ROOM IDENTIFICATION
ROOM NAME
MATERIAL - RM NUMBER
SQ FTSQ FT
ROOM NAME
ROOM NUMBER
ABBREVIATIONS (NOT ALL ARE USED) GRAPHIC SYMBOLS MATERIAL CONVENTIONS
DOOR INDICATIONS
METAL FRAMING
XXX
X
AXXX
TX TOILET ACCESSORY SYMBOL
W
XX
STOREFRONT TYPE
SF
XX
CURTAIN WALL TYPE
CW
XX
1. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS & DIMENSIONS PRIOR TO FABRICATION, FURNISHING & INSTALLATION OF ANY MATERIALS, EQUIPMENT AND WORK.
2. ALL MATERIALS & EQUIPMENT SHOWN ARE NEW TO BE PROVIDED BY CONTRACTOR(S) UNLESS OTHERWISE NOTED.
3. ALL EXISTING UTILITIES & EQUIPMENT LOCATIONS ARE APPROXIMATE - CONTRACTOR(S) SHALL FIELD VERIFY AND/OR COORDINATE EXACT LOCATIONS.
4. CONTRACTOR ASSUMES ALL RESPONSIBILITY DURING CONSTRUCTION TO PROTECT MATERIALS AND EQUIPMENT. ANY & ALL DAMAGED ITEMS & EQUIPMENT DURING CONSTRUCTION SHALL BE REPLACED AT NO ADDITIONAL COST TO
THE OWNER.
5. ALL RATED DOORS & DOORS FRONTING A CORRIDOR SHALL HAVE POSITIVE LATCHING LOCKSETS UNLESS OTHERWISE INDICATED ON THE DOOR SCHEDULE.
6. ALL DOORS EXITING 50 PERSONS OR MORE SHALL HAVE PANIC EXIT DEVICES.
7. ALL HANDICAP ACCESSIBLE DOOR HARDWARE SHALL BE PROVIDED TO COMPLY WITH ADA, ANSI AND ALL OTHER APPLICABLE CODES.
8. ALL NEW AND EXISTING EXPOSED/VISIBLE GUARDRAILS, HANDRAILS, DOOR FRAMES, GLAZING FRAMES, DECKING, BEAMS, COLUMNS, JOISTS AND OTHER STRUCTURAL COMPONENTS SHALL BE PAINTED UNLESS OTHERWISE NOTED.
9. IF A NOTE IS FOUND ON ARCHITECTURAL DRAWINGS READING - "SEE STRUCTURAL DRAWINGS" - AND SIZE AND DETAILING OF MEMBER(S) IS NOT FOUND, THE CONTRACTOR SHALL CONTACT THE ARCHITECT TO REQUEST MISSING INFORMATION. THESE ITEMS SHALL BE PART OF THE BASE BID AND STEEL SUBCONTRACTOR SHALL REVIEW STRUCTURAL AS WELL AS ARCHITECTURAL DRAWINGS PRIOR TO BIDDING.
10. ALL CONTRACTORS SHALL REVIEW DRAWINGS AND PROJECT MANUAL. IF THERE IS A DISCREPANCY BETWEEN THE TWO OR ANY OTHER PARTS OF THE DOCUMENTS, THE HIGHER VALUE (IN DOLLARS) SHALL PREVAIL AS THE SCOPE OF WORK THAT WILL BE PRICED UNLESS OTHERWISE DIRECTED IN WRITING BY THE ARCHITECT DURING THE BIDDING PERIOD.
11. PATCH ALL EXISTING WALLS AND OTHER SURFACES AFFECTED BY DEMOLITION & REMOVALS WITH MATERIALS TO MATCH EXISTING.
12. SAW CUT AND REMOVE PORTIONS OF CONCRETE SLAB AS REQUIRED TO ACCOMMODATE NEW PLUMBING, ELECTRICAL, MECHANICAL AND OTHER TRADES WORK. COORDINATE LOCATION, WIDTH, AND DEPTH OF TRENCHING
WITH M/E/P DRAWINGS FOR SCOPE OF NEW WORK REQUIRED.
13. WALL OPENINGS RESULTING FROM REMOVAL OF DUCTS, PIPES, CONDUITS, ETC. SHALL BE INFILLED WITH MATERIALS TO MATCH THE WALL. SEE M/E/P DEMOLITION DRAWINGS FOR REMOVALS.
14. WHERE NEW DUCTS, PIPES, AND CONDUITS PASS THROUGH NEW AND EXISTING WALLS, PROVIDE OPENING AND HEADER, AS REQUIRED AND SEAL THE PERIMETER OF THE PENETRATION FOR SOUND TRANSMISSION RESISTANCES AN FIRE RATING WHERE INDICATED ON CODE PLANS AND OTHER DRAWINGS. COORDINATE WITH M/E/P/FP DRAWINGS FOR ALL OPENINGS REQUIRED.
15. REFERENCE CT IBC 703.5, THE CODE SHEET G001, AND THE SIGNAGE SHEET A900 FOR FIRE RATED WALL TYPE STENCILING.
DRAWING NUMBER
DRAWING NUMBER
REVISION CLOUD & MARK
WALL / PARTITION TYPE
BUILDING SECTION
SECTION/DETAIL
x x
COLUMNS (EXISTING)
DETAIL CALL OUT
"XX" DRAWING NUMBER
"#" INTERIOR ELEVATION
LABEL
ELEVATION
ELEVATION MARKER
DATUM POINT
DRAWING NUMBER
WALL SECTION
X
AXXX
X
AXXX
X
AXXX
X
AXXX
AXXX#
X
X
AXXX
"XX" DRAWING NUMBER
"#" EXTERIOR ELEVATION
AXXX
NORTH ARROW
XX
EXISTING-TO-REMAIN WINDOW,
STOREFRONT, OR CURTAIN WALL
ETR
A.B. ANCHOR BOLT
ABV. ABOVE
A/C AIR CONDITIONING
A.C.P. ASBESTOS CEMENT PIPE
ACT ACOUSTICAL CEILING TILE
AD. AREA DRAIN
ADJ. ADJUSTABLE
AFF ABOVE FINISH FLOOR
AHU AIR HANDLING UNIT
ALT ALTERNATE
ALUM. ALUMINUM
ANOD ANODIZED
APPROX. APPROXIMATE
ARCH. ARCHITECT(URAL)
ASPH. ASPHALT
AVG. AVERAGE
BC BRICK COURSE
B/C BOTTOM OF CURB
BD. BOARD
B.E.J BRICK (BLOCK) EXPANSION JOINT
B.F. BOTTOM OF FOOTING
BIT. BITUMINOUS
BLDG. BUILDING
BLK. BLOCK
BLKG. BLOCKING
BM BEAM
B.M. BENCH MARK
B.O. BOTTOM OF
BRG. BEARING
BRK. BRICK
B.S. BOTH SIDES
BSMT. BASEMENT
B.U.R. BUILT UP ROOFING
B/W BOTTOM OF WALL
B.W.R. BOTH WAYS WALL
CAB CABINET
C.B. CATCH BASIN
C. BD. CHALK BOARD
C.B.R. CATCH BASIN TO BE REMOVED
C.C. CURB CUT
CEM CEMENT
CER CERAMIC
C.F.M.F. COLD FORMED METAL FRAMING
CG CORNER GUARD
C.H. CABINET HEATER
CHKBD CHALKBOARD
C.I. CAST IRON
C.I.P. CAST IN-PLACE CONCRETE
C.J. CONTROL/CONSTRUCTION JOINT
CLG. CEILING
CLG. HT. CEILING HEIGHT
CLOS. CLOSET
CLR CLEAR
CLRM CLASSROOM
CMU CONCRETE MASONRY UNIT
CNTR COUNTER
C.O. CLEAN OUT
COL COLUMN
CONC. CONCRETE
CONF. CONFERENCE
CONN CONNECTION
CONSTR. CONSTRUCTION
CONT. CONTINUOUS, CONTINUE
CONTR. CONTRACTOR
CORR. CORRIDOR
CP CONTROL PANEL
CPT CARPET
C.R. CEILING REGISTER
CT CERAMIC TILE
CT CONNECTICUT
CTR CENTER
C.U.H. CABINET UNIT HEATER
C.Y. CUBIC YARD
DBL DOUBLE
DEPT CEPARTMENT
DET. DETAIL
DF DRINKING FOUNTAIN
DIA. DIAMETER
DIFF DIFFUSER
DIM. DIMENSION(S)
DISP DISPENSER
DIV DIVISION
D.L. DEAD LOAD
DN DOWN
D.O. DOOR OPENING
DP DAMP PROOFING
DR. DOOR
DS DOWNSPOUT
D.S.P. DRY STAND PIPE
DTL. DETAIL
DWG, DWGS DRAWING(S)
DWL DOWEL
E EAST
EA. EACH
ECTR. EXISTING CEILING-TO-REMAIN
ED. EDUCATION
E.F. EACH FACE
EIFS EXTERIOR INSULATION & FINISH SYSTEM
E.J. EXPANSION JOINT
E.J.C. EXPENSION JOINT COVER
EL. ELEVATION
ELEC. ELECTRICAL
ELEV. ELEVATION
EMER. EMERGENCY
ENCL. ENCLOSURE
ENGR ENGINEER
ENL. ENLARGED
ENT. ENTRANCE
EP. EPOXY PAINT
EQ. / = EQUAL(S)
EQUIP EQUIPMENT
ES. EXPOSED STRUCTURE
E.T.R. EXISTING-TO-REMAIN
E.W. EACH WAY
E.W.C. ELECTRIC WATER COOLER
E.W./E.F. EACH WAY/EACH FACE
EXAM. EXAMINATION
EXH EXHAUST
EXIST. EXISTING
EXP. EXPANSION
EXPO EXPOSED
EXT. EXTERIOR
F.A. FIRE ALARM
F.A.P. FIRE ALARM PANEL
F.B. FOOTING BREAK
PART PARTITION
P.C.B. PAINTED CONCRETE BLOCK
P.G.B. PAINTED GYPSUM BOARD
PL. OR PLAM PLASTIC LAMINATE
PLUMB. PLUMBING
PLYWD. PLYWOOD
PREFAB PREFABRICATED
PREP. PREPARATION
PROJ PROJECTION
PROP PROPERTY
P.T., PR. TR. PRESSURE TREATED
PTD PAINTED
P.V.C. POLYVINYL CHLORIDE
QT QUARRY TILE
R. RISER
R OR RAD. RADIUS
RB RESILIENT BASE
RCP REFLECTED CEILING PLAN
R.D. ROOF DRAIN
RECPT RECEPTACLE
REF REFERENCE
REFG REFRIGERATOR
REINF. REINFORCEMENT
REQ'D REQUIRED
RES RESILIENT
RET RETAINING
REV REVISION
R.H. ROOF HATCH
RI RHODE ISLAND
R.L. ROOF LEADER
RM. ROOM
R.O. ROUGH OPENING
R.O.W. RIGHT OF WAY
R.T. RUBBER TILE
RV ROOF VENT
R.W.L. RAIN WATER LEADER
S SOUTH
S. STORM
SAN. SANITARY
SB SMART BOARD
SC SEALED CONCRETE
S.C. SOLID CORE
SCHED. SCHEDULE
S.D. SOAP DISPENSER
SECT. SECTION
SF SQUARE FEET
S.FPRG. SPRAYED-ON FIREPROOFING
S.G.F.T. STRUCTURAL GLAZED FACING TILE
SHR SHOWER
SIM. SIMILAR
SK SKETCH
S.N.D. SANITARY NAPKIN DISPENSER
S.N.R. SANITARY NAPKIN RECEPTACLE
S.O.G. SLAB-ON-GRADE
SPEC. SPECIFICATIONS
SPKLR SPRINKLER
S.P.R. SINGLE PLY ROOF
SQ. SQUARE
SQ. FT. SQUARE FEET
SS SOLID SURFACE
SSTL STAINLESS STEEL
STA STATION
STD STANDARD
STIFF STIFFENERS
STL. STEEL
STRUCT. STRUCTURAL
SUSP. SUSPENDED, SUSPENSION
S.W. SHEAR WALL
S.W.F. SHEAR WALL FOOTING
SYM SYMMETRICAL
SYS.,SYST. SYSTEM
T. TELEPHONE
TB TACKBOARD
T&B TOP & BOTTOM
TBD TO BE DETERMINED
TECH. TECHNOLOGY
TEMP TEMPERED
TERR TERRAZZO
TEL TELEPHONE
THK THICK
THRES THRESHOLD
T.O. TOP OF
T.O.F. TOP OF FOUNDATION
T.O.S. TOP OF STEEL
T.P. TOILET PARTITION
T.P.D. TOILET PAPER DISPENSER
T/S TOP OF SLAB
T.T.F. TRIM TO FIT
T/W TOP OF WALL
TYP. TYPICAL
UL UNDERWRITERS LABORATORIES
UNO UNLESS NOTED OTHERWISE
UON UNLESS OTHERWISE NOTED
V.B. VINYL BASE
VCT VINYL COMPOSITE TILE
VERT. VERTICAL
VIF VERIFY IN FIELD
VT VERMONT
W WEST
W. WATER
W/ WITH
MA MASSACHUSETTS
WB WHITE BOARD
WC WALL COVERING
WCJ WALL CONTROL JOINT
WD. WOOD
WF. WIDE FLANGE
WIN. WINDOW
W/O WITHOUT
WOM WALK-OFF-MAT
WP WATERPROOFING
WS WOOD STAIN
W.W.F WELDED WIRE FABRIC
W.W.M. WELDED WIRE MESH
& AND
∠ ∡ ANGLE
@ AT
℄ CENTERLINE
= EQUAL(S)
⌀ DIAMETER
F.BRK FACE BRICK
FD FLOOR DRAIN
FDN. FOUNDATION
F.E. FIRE EXTINGUISHER
F.E.C. FIRE EXTINGUISHER & CABINET
F.F. FINISHED FLOOR
F.H. FIRE HYDRANT
F.H.P. FULL HEIGHT PARTITION
FFE, FF&E FURNITURE, FIXTURES, AND EQUIPMENT
FIN. FINISH, FINISHED
FIXT. FIXTURE
FL. FLOOR
FLASH FLASHING
FLEX FLEXIBLE
F.O.F. FACE OF FINISH
F.O.G. FACE OF GYPSUM BOARD
F.O.M. FACE OF MASONRY
F.O.S. FACE OF STUD
F.O.T. FACE OF TILE
F.P. FIRE PROOF / FIRE PROTECTION
FPFG FIREPROOFING
F.R. FIRE RATED
FRP FIBERGLASS REINFORCED PANEL
F.S. FAR SIDE
FT. FOOT OR FEET
F.T. FIRE TREATED
FTG FOOTING
F.T.R. FINNED TUBE RADIATION
FUR FURRING
G GAS
GA. GAGE, GUAGE
GALV. GALVANIZED
G.B. GRAB BAR
G.C. GENERAL CONTRACTOR
GEN. GENERAL
GFB GROUND FACE BLOCK
GL GLASS
GND GROUND
GRD GRADE
GYP. GYPSUM
GWB GYPSUM WALL BOARD
GYP. BD. GYPSUM BOARD
H.B. HOSE BIBB
H.C. HANDICAP(PED)
H.C. HOLLOW CORE
HD. HEADED
HDWR. HARDWARE
HGT. HEIGHT
HM HOLLOW METAL
HORIZ. HORIZONTAL, HORIZONTALLY
H.P. HIGH POINT
HR. HOUR
HTG HEATING
H.U. HEATING UNIT
HVAC HEATING / VENTILATION / AIR CONDITIONING
HWD HARDWOOD
HYD. HYDRANT
ID INTERIOR DESIGN
I.D. INSIDE DIAMETER
IN. INCH
INCL. INCLUDE OR INCLUDING
INSUL. INSULATION, INSULATED
INT. INTERIOR
INV. INVERT
JAN. JANITOR
JNT/JT JOINT
JST JOIST
K.D. KOCK DOWN
KIT KITCHEN
K.P. KICK PLATE
LAM. LAMINATE(D)
LAV LAVATORY
LBS POUNDS
LCKR LOCKER
L.F. LINEAR FOOT
LG. LONG
L.L. LIVE LOAD
LOC. LOCATION
L.P. LOW POINT
LTG. LIGHTING
LVL. LEVEL
LVT LUXURY VINYL TILE
M MINUTE
MAS. MASONRY
MATL MATERIAL
MAX. MAXIMUM
M.C. MASONRY COURSE
MECH. MECHANICAL
M.H. MANHOLE
MIN. MINIMUM
MIR MIRROR
MISC. MISCELLANEOUS
M.O. MASONRY OPENING
MTD. MOUNTED
MTL. METAL
MULL MULLION
N NORTH
N.A. NOT APPLICABLE
NH NEW HAMPSHIRE
N.I.C. NOT IN CONTRACT
NJ NEW JERSEY
NO. NUMBER
NOM. NOMINAL
N.P.S. NOMINAL PIPE SIZE
N.R.C. NOISE REDUCTION COEFFICIENT
N.S. NEAR SIDE
N.T.S. NOT TO SCALE
NY NEW YORK
NYC NEW YORK CITY
O/A OUTSIDE AIR
O.C. ON CENTER
O.C.C. OCCUPANT
O.D. OUTSIDE DIAMETER
OFF OFFICE
O.H. OPPOSITE HAND
OPNG. OPENING
OPP OPPOSITE
O.W.S.J. OPEN WEB STEEL JOIST
OZ OUNCE
PA PENNSYLVANIA
GENERAL NOTES
NEW WALL
EXISTING WALL TO BE REMOVED
TYPICAL WINDOW
EXISTING WALL
WINDOW WALL
RECESSED ITEM
WALL INDICATIONS DRAWINGS LIST
RESERVED ACCESSIBLITY SYMBOL
(OLD TERM "HANDICAPPED")
1"
SIGNAGE SYMBOL
EX EQUIPMENT SYMBOL
SX
DRAWING TITLE:REVISED BY:DATE:DESCRIPTION:REVISION:PROJECT TITLE: DATE:
SCALE:
DRAWN BY:
PROJECT NUMBER:
DRAWING NUMBER:
SILVER PETRUCELLI + ASSOCIATES
203 230 9007
3190 WHITNEY AVENUE HAMDEN CT 06518
silverpetrucelli.com
311 STATE STREET NEW LONDON CT 06320
PROJECT SUBMISSION:
STATE PROJECT NUMBER:
RENOVATIONS TO
BROOKLYN SENIOR CENTER
69 SOUTH MAIN STREET
BROOKLYN, CT
ISSUED FOR BID
2025.4
10/16/2026
12" = 1'-0"
/1
5/
1:
:4
A M
G001
GENERAL INFORMATION AND
DRAWING LIST
J. TEBO
ARCHITECTURAL DRAWINGS
A010 DEMOLITION PLANS
A110 FLOOR PLANS
A113 ROOF PLAN
A250 LOWER LEVEL REFLECTED CEILING PLAN
A300 EXTERIOR ELEVATIONS
A400 AREAWAY SECTION AND ENLARGED PLAN
A440 VERTICAL CIRCULATION
A450 ENLARGED BATHROOM PLANS AND ELEVATIONS
A800 DOOR AND FINISH SCHEDULES
A810 WINDOW AND DOOR DETAILS
A850 ELEVATOR DETAILS
A900 SIGNAGE
STRUCTURAL DRAWINGS
MECHANICAL DRAWINGS
M010 MECH LOWER LEVEL DEMO PLAN
M110 MECH LOWER LEVEL DUCT PLAN
M300 MECH ENLARGED PLANS
M500 MECH SCHEDULES
M501 MECH SCHEDULES
M600 MECH DETAILS
M601 MECH DETAILS
PLUMBING DRAWINGS
P001 GENERAL NOTES, ABBREVIATIONS, AND LEGENDS
P010 LOWER LEVEL DEMO PLAN
P110 LOWER LEVEL FLOOR PLAN
P500 SCHEDULES
P600 DETAILS
ELECTRICAL DRAWINGS
E001 ELEC ABBREVIATIONS AND LEGENDS
E002 ELEC GENERAL NOTES
E010 ELEC LOWER LEVEL LIGHTING DEMO PLAN
E020 ELEC LOWER LEVEL POWER DEMO PLAN
E110 ELEC LOWER LEVEL LIGHTING PLAN
E210 ELEC LOWER LEVEL POWER PLAN
E300 ELEC SITE LIGHTING PLAN - BID ALTERNATE
E500 ELEC SCHEDULES
E600 ELEC DETAILS
GENERAL DRAWINGS
G000 COVER SHEET
G001 GENERAL INFORMATION AND DRAWING LIST
G002 BUILDING CODE PLANS & INFORMATION
G003 WALL / PARTITION TYPES
S100 FOUNDATION PLAN
S101 SECTIONS AND TYPICAL DETAILS
S102 EXISTING ROOF PLAN - REPAIRS AND GENERAL NOTES
DN
DN
DN
UP
X
X
IIIB
IIIB
B (BUSINESS)
7. CODES TO WHICH THIS PROJECT WAS DESIGNED
5. ENTIRE BUILDING SPRINKLERED
6. THRESHOLD BUILDING CONDITIONS
CODE INFORMATION
2. CONSTRUCTION TYPE (Chapter 6)
1. GROUP CLASSIFICATION (Chapter 3)
3. FIRE-RESISTANCE RATED REQUIREMENTS FOR BUILDING ELEMENTS
4. OCCUPANCY LOAD
NoYes
No
DATE OF ORIGINAL CONSTRUCTION
Minimum Type Required
Actual Type Provided (existing)
DATE OF RENOVATIONS
(Primary)
(Proposed new)
DATE OF PROPOSED RENOVATIONS
Hr(s)
Structural frame: including columns, girders, trusses
2 Bearing walls:
Exterior (Table 602)
Interior
3 Nonbearing walls & partitions
Exterior (Table 602)
4 Nonbearing walls & partitions
Interior
5 Floor Construction (including supporting beams & joists)
6 Roof Construction (including supporting beams & joists)
(Table 601, See Code Plans for specific designations)
Hr(s)
Hr(s)
Hr(s)
Hr(s)
Hr(s)
Hr(s)
Total Exit Capacity for Ground Floor Level
Design Total for Ground Floor Level
Yes
IIIB
2021 IPC/2022 CT
Current
2010 ADA
2021 NFPA 1 & 101 / 2022 CT
ADA Standards for Accessible Design
Section 504
State Fire Prevention / Life Safety Code
State Energy Conservation Code w/ CT Amend.
State Plumbing Code w/ CT Amendments
State Mechanical Code w/ CT Amendments
State Electrical Code w/ CT Amendments
Accessible and Usable Bldgs w/ CT Amendments
2021 IMC / 2022 CT
2021 IECC / 2022 CT
2020 NFPA 70 / 2022 CT
2017 ICC A117.1 / 2022 CT
2021 IEBC/2022 CT State Existing Building Code w/ CT Amendments
2021 IFC/2022 CT State Fire Safety Code
State Building Code w/ CT Amendments 2021 IBC/2022 CT
If any proposed building or addition that exceeds one or more of the following threshold limits mark YES and then refer to CT IBC107.7: (1) four stories, (2) 60 feet high, (3) a clear span of 150 feet wide, or (4) occupancy by 1,000 or more people
CHANGE OF USE
NO
OCCUPANCY PLAN - FIRST FLOOR
B
EXISTING NON-CONFORMING
A-3 (ASSEMBLY)
B A-3
OCCUPANCY PLAN - LOWER LEVEL
(60.66')
60.66'
MAX. ALLOWABLE EGRESS OCC. OF DOOR
ACTUAL EGRESS OCC. OF DOOR
CODE LEGEND
TD 145'
DIRECTION OF TRAVEL W/ ACCUMULATED OCC. LOAD
EXIT CAPACITY
ROOM NUMBER
MAXIMUM TRAVEL DISTANCE FROM FURTHEST POINT
ROOM OCCUPANCY LOAD
DENOTES ACCESSIBLE THRESHOLD 1/2" MAX STEP
W/BEVELED THRESHOLD OR 1/2" STEP W/OUT BEVELED
THRESHOLD
2 HOUR RATED FIRE AND SMOKE BARRIER
1 HOUR RATED FIRE AND SMOKE BARRIER
- DIMENSION OF OPEN PERIMETER ALONG ENTIRE
LONGITUDINAL FACE
COMMON PATH OF TRAVEL
AREA IN SF
OCC. LOAD FACTOR
C216
- DIMENSION OF NON-OPEN PERIMETER ALONG ENTIRE
LONGITUDINAL FACE
198'
INDICATES LOSS OF EXIT AS PER IBC 1005.5 CT
AMENDMENTS
LOT LINE
SMOKE BARRIER
300SF
420SF
GAME ROOM
STORAGE
KITCHEN
CORRIDOR
RECREATION ROOM
CLO
110A
OFFICE
DIRECTORS OFFICE
CLO
112A
ELEV LOBBY
ELEVATOR
EL1.1
WOMEN
MEN
STAIR
ST1.1
LOBBY
420SF
2618SF
355SF
STO
103A
30SF
177SF
164SF
UP
DN
UP
RAMP UP
EXERCISE ROOM
GROUP EXERCISE ROOM
GAME ROOM
CRAFT ROOM
STORAGE
STORAGE
019A
STORAGE
018A
MECHANICAL
JANITOR
ELECTRICAL
MECHANICAL
MECHANICAL
ELECTRICAL
STAIRS
ST1.0
STORAGE
STORAGE
C O
R R
ID
O
R
CORRIDOR
TOILET
EL. MACHINE ROOM
ELEVATOR
EL1.0
CORRIDOR
CLT
017A
TOILET
STORAGE
321SF
321SF
357SF
357SF
747SF
602SF
138SF
120SF
122SF
75SF
91SF
321SF
96SF
AREA WAY
58SF
34SF
34SF
45SF
1 1 1 1
AOR
AOR
DRAWING TITLE:REVISED BY:DATE:DESCRIPTION:REVISION:PROJECT TITLE: DATE:
SCALE:
DRAWN BY:
PROJECT NUMBER:
DRAWING NUMBER:
SILVER PETRUCELLI + ASSOCIATES
203 230 9007
3190 WHITNEY AVENUE HAMDEN CT 06518
silverpetrucelli.com
311 STATE STREET NEW LONDON CT 06320
PROJECT SUBMISSION:
STATE PROJECT NUMBER:
RENOVATIONS TO
BROOKLYN SENIOR CENTER
69 SOUTH MAIN STREET
BROOKLYN, CT
ISSUED FOR BID
2025.4
10/16/2026
As indicated
/1
4/
:1 6:
P
M
G002
BUILDING CODE PLANS &
INFORMATION
J. TEBO
1/8" = 1'-0" REFERENCE DWG: 2 / A3001 FIRST FLOOR CODE PLAN
1/8" = 1'-0" REFERENCE DWG: 1 / A3002 LOWER LEVEL CODE PLAN
TOP BOTTOM
VERTICAL SECTION
HORIZONTAL SECTION
1/
8"
1HR SHAFT WALL
1. 2 1/2" METAL "C-H" STUDS @ 16" O.C.
2. 5/8" GYPSUM WALL BOARD, PAINTED
3. 1" GYPSUM WALL BOARD
UL #U415
STC RATING - N/A
1 2
TOP BOTTOM
VERTICAL SECTION
HORIZONTAL SECTION
7/
8"
3 5/8" METAL STUD WALL
W/ SOUND BATT
1. 3 5/8" METAL STUDS @ 16" O.C.
2. 5/8" GYPSUM WALL BOARD, PAINTED
3. 3" SOUND ATTENUATION BATT
4. --
5. PUTTY PAD AROUND WALL PENETRATIONS
UL #U404 OR SIMILAR
STC RATING - 44
1B
1 2 3
TOP
VERTICAL SECTION
HORIZONTAL SECTION
1/
4"
3 5/8" METAL
STUD WALL
1. 3 5/8" METAL STUDS @ 16" O.C.
2. 5/8" GYPSUM WALL BOARD, PAINTED
UL # - N/A
STC RATING - 27
1C
1 2
TOP BOTTOM
VERTICAL SECTION
HORIZONTAL SECTION M
A
T C
H E
X
IS
T
IN
G
METAL
STUD WALL
W/ SOUND BATT
1. 2 1/2" METAL STUDS @ 16" O.C.
2. 5/8" GYPSUM WALL BOARD, PAINTED
3. 3" SOUND ATTENUATION BATT
UL N/A
STC RATING - N/A
1 2
TOP BOTTOM
VERTICAL SECTION
HORIZONTAL SECTION
7/
8"
3 5/8" METAL STUD WALL
W/ SOUND BATT
1. 3 5/8" METAL STUDS @ 16" O.C.
2. 5/8" GYPSUM WALL BOARD, PAINTED
3. 3" SOUND ATTENUATION BATT
4. --
5. PUTTY PAD AROUND WALL PENETRATIONS
STC RATING - 44
1A
1 2 3
UL # - N/A
BOTTOM
DRAWING TITLE:REVISED BY:DATE:DESCRIPTION:REVISION:PROJECT TITLE: DATE:
SCALE:
DRAWN BY:
PROJECT NUMBER:
DRAWING NUMBER:
SILVER PETRUCELLI + ASSOCIATES
203 230 9007
3190 WHITNEY AVENUE HAMDEN CT 06518
silverpetrucelli.com
311 STATE STREET NEW LONDON CT 06320
PROJECT SUBMISSION:
STATE PROJECT NUMBER:
RENOVATIONS TO
BROOKLYN SENIOR CENTER
69 SOUTH MAIN STREET
BROOKLYN, CT
ISSUED FOR BID
2025.4
10/16/2026
1" = 1'-0"
/1
4/
:1 6:
P
M
G003
WALL / PARTITION TYPES
J. TEBO
1" = 1'-0"1 PARTITION TYPES
UP
FOUNDATION NOTES:
1. TOP OF CONCRETE SLAB ELEVATION= MATCH EXISTING SLAB. V.I.F.
2. FLOOR CONSTRUCTION: 5" NORMAL WEIGHT CONCRETE SLAB REINF. WITH 6X6-W2.9XW2.9 W.W.F. (CHAIRED).
REFER TO GENERAL NOTES FOR SUBGRADE REQUIREMENTS.
A B C D E
NEW FOUNDATION WALLS
AT BASE OF STAIR.
REFER TO SECTION. DRILL AND EPOXY
ABUTTING REINFORCING INTO EXISTING
CONCRETE CONSTRUCTION
S100
INFILL OPENINGS PER ARCHITECTURAL
DRAWINGS. REFER TO TYPICAL CONCRETE WALL
INFILL DETAIL. HOLD TOP OF INFILL DOWN AS
REQUIRED FOR PLACEMENT AND VIBRATION.
INFILL GAP WITH DRYPACK AFTER CONCRETE
PLACEMENT.
EXISTING CONCRETE COLUMN
SPALLING TO BE REMOVED AND
REPAIRED BY AN APPROVED
REPAIR PROCEDURE
TOPPING SLAB ON EXISTING SLAB ON
GRADE TO BE FLUSH TO EXISTING DOOR,
REFER TO ARCH'L DRAWINGS. SLOPE TOP
OF TOPPING AWAY FROM DOOR.
CONSTRUCTION SIMILAR TO CONCRETE
PAD ON EXISTING SLAB ON GRADE DETAIL
COORDINATE UTILITY EXIT LOCATIONS WITH M/E/P
DRAWINGS. REFER TO TYPICAL DETAIL OF PIPE
PENETRATIONS BELOW WALL FOOTING DETAIL FOR
REQUIREMENTS WHERE UTILITIES PASS BELOW
WALL FOOTINGS. WHERE UTILITIES PASS
THROUGH WALL, WALL MUST BE SCANNED PRIOR
TO DRILLING AND OPENINGS MUST BE LOCATED
BETWEEN EXISTING REINFORCING. OPENING MUST
NOT BE LOCATED BELOW COLUMNS OR BEAMS
ABOVE.
S101
S101
S101
SIM.
PROVIDE NEW LINTEL ABOVE NEW
OPENINGS IN MASONRY WALLS.
REFER TO EXISTING MASONRY
LINTEL SCHEDULE. COORD. WITH
ARCH'L DRAWINGS.
EXISTING CONCRETE COLUMN
SPALLING TO BE REMOVED AND
REPAIRED BY AN APPROVED
REPAIR PROCEDURE
REMOVE AND REPLACE EXISTING WALL TO INSTALL NEW
ELEVATOR CAB AND TO REMOVE EXISTING WATER
DAMAGED CONSTRUCTION. REFER TO TYPICAL CONCRETE
AND MASONRY WALL INFILL DETAILS. SHORE EXISTING
FLOOR CONSTRUCTION PRIOR TO DEMOLITION, UNTIL NEW
WALL CONSTRUCTION IS COMPLETED AND HAS REACHED
DESIGN STRENGTH
STAIR REPLACEMENT IS AN
ALTERNATE. COORDINATE WITH
ARCH'L DRAWINGS
3/4" CRUSHED
STONE FILL
#5@16"O.C.
VERT. REINF.
ALTERNATE LEGS
#4@12" O.C.
#4 NOSING
(TYPICAL)
M
IN
.6"
8" 8" 8"
2' - 0"
1'
#4@12"O.C.
HORIZ. REINF.
#4@12"O.C.
DOWELS.
EXISTING FOUNDATION TO REMAIN
V.I.F.
6X6-W2.9XW2.9 WWF.
COMPACTED
STONE FILL
4" M
IN
4" MIN.
REMOVE EXISTING SLAB ON GRADE AS
REQUIRED TO INSTALL NEW FOUNDATION.
SLOPE TOP OF SLAB TO DRAIN AS REQUIRED.
#4X2'-0" AT 18" O.C. DRILL AND EPOXY (4" EMBED)
MATCH BOTTOM OF FOUNDATION
WITH BOTTOM OF EXISTING FOUNDATION.
V.I.F.
#4@12"O.C.
DOWELS
CUT DOWN TOP OF EXISTING
FOUNDATION WALL
M
IN
5"
M
IN
8"
6X6-W2.9XW2.9 WWF.
ARCH'L DRAWINGS
5' - 0" COORD. WITH
t/
CLASS "B" LAP
ADD #4@12"O.C. WHERE
NO REINFORCING IS
INDICATED (TYPICAL)
DOWELS MAY BE USED AS AN
ALTERNATE AT CONSTRUCTION
JOINTS AND ELSEWHERE
1 1/2" KEY
PROPOSED JOINT LOCATION
SUBMIT ON SHOP DRAWINGS
FOR REVIEW
KEY
1 1/2"
ADD (2)-#4X2'-6"
EACH FACE AT
TWICE THE SPACING
OF HORIZ. WALL REINF.
HORIZ. REINF. IS
CONT. THRU JOINT
"t
INTERSECTION CONSTRUCTION JOINTCORNER
STANDARD
90° HOOK
ADD #4@12"O.C.
WHERE NO REINF.
IS INDICATED
2'-0" AT ADDED REINF.
CLASS "B" LAP
CONTROL JOINT
3/4" CHAMFER AT
EXPOSED FACES
CUT EVERY OTHER BAR
AT JOINT
FOR REINFORCING
REFER TO DETAILS
NOTE: CONTROL JOINT SPACING IN FOUNDATION WALLS SHALL NOT
EXCEED 30 FEET. 50% OF HORIZONTAL REINFORCEMENT SHALL
EXTENT THROUGH JOINT AND HAVE A CLASS " B" SPLICE (PER ACI
318-05)
2"
45.00°
6"
OPENING
(2)-#5X5'-0" LG.
1. COORDINATE WITH MECHANICAL DRAWING FOR QUANTITY, SIZE AND LOCATION.
2. PROVIDE PADS AT GENERATORS, REFRIGERATOR AND FREEZER UNITS. COORDINATE WITH ELECTRICAL
& KITCHEN DRAWINGS FOR SIZE AND LOCATION.
(4
S
ID
ES
2'
M
IN
8" 8"
#4@12"O.C. TOP &
BOTTOM, EACH WAY
2" M
IN
M
IN
.FINISH GRADE FINISH GRADE
(2)-#5 CONT. (TYP.)
1'
M
IN
1'-0" MIN. COMPACTED STONE
FILL
TYP.
CLASS "B" SPLICE
DETAILED
FOOTING REINF.
TOP REINFORCING
WHERE DETAILED
WALL REINFORCING,
REFER TO SECTIONS
(TYPICAL)
MIN.
H
H
TY
P
2'
M A
X
TYP.
4' - 0" MIN.
CLASS "B" SPLICE
CLASS "B" SPLICE
TYP.
CLASS "B" SPLICE
TYP.
CLASS "B" SPLICE
EXCAVATION SLOPE
BASED ON SITE SOILS
NOTE:
CONTRACTOR SHALL SUBMIT A PLAN INDICATING THE PROPOSED LOCATION OF
CONTROL AND CONSTRUCTION JOINTS PRIOR TO PLACING CONCRETE FOR SLAB.
REFER TO GENERAL NOTES FOR SUBGRADE PREPARATION. REMOVE ALL FILL MATERIALS BELOW SLAB ON GRADE
TYPICAL THICKENED EDGE
THICKENED SLAB
AT EDGE
SUPPORTED W.W.F.
ON CHAIRS
SLAB ON GRADE
2T
T
10" 1"
SAWCUT SLAB JOINT
t/ t
2"
SAWCUT JOINT
VAPOR RETARDER
REFER TO PLAN NOTE
FOR SLAB CONSTRUCTION
SUPPORTED W.W.F. ON
CHAIRS
REFER TO GENERAL NOTES FOR
SUBGRADE REQUIREMENTS
2"
SLAB ON BASE
REFER TO PLAN
VAPOR RETARDER
1/4"X4 1/2"X4 1/2"
TAPERED PLATE
DOWELS AT 18" O.C. MAX.
S
EE
P
LA
N V
A R
IE
S
CONSTRUCTION JOINT
LAP SCHEDULE
SIZE
4500 PSI
TOP
19"24"
OTHERS
#3
25"32"#4
31"40"#5
37"48"#6
54"70"#7
62"80"#8
70"91"#9
DRAWING TITLE:REVISED BY:DATE:DESCRIPTION:REVISION:PROJECT TITLE: DATE:
SCALE:
DRAWN BY:
PROJECT NUMBER:
DRAWING NUMBER:
SILVER PETRUCELLI + ASSOCIATES
203 230 9007
3190 WHITNEY AVENUE HAMDEN CT 06518
silverpetrucelli.com
311 STATE STREET NEW LONDON CT 06320
PROJECT SUBMISSION:
MEP & DOOR REPLACEMENTS
BROOKLYN COMMUNITY CENTER
31 TIFFANY STREET
BROOKLYN, CT
ISSUED FOR BID
25-135
10/16/2026
As indicated
/1
/2
:0
:3
A
M
S100
FOUNDATION PLAN
A. Close
3/4" = 1'-0"3 TYPICAL WALL REINFORCING DETAIL
3/4" = 1'-0"7 TYPICAL SLAB ON GRADE DETAIL
3/4" = 1'-0"4 TYPICAL AT REENTRANT SLAB CORNERS
3/4" = 1'-0"5 TYPICAL CONCRETE EQUIPMENT PAD ON GRADE
1/2" = 1'-0"6 TYPICAL STEPPED FOOTING DETAIL
1/8" = 1'-0" REFERENCE DWG: 1 / S1011 BASEMENT/FOUNDATION
3/4" = 1'-0" REFERENCE DWG: 1 / S1002 STAIR SECTION
FIRST FLOOR LEVEL
0"
BASEMENT/FOUNDATION
-12' - 0"
SLAB ON GRADE
REINFORCED WITH
6X6-W2.9XW2.9 W.W.F.
#4 CONT. NOSING
BAR TYP.
RAILING REQUIRED BY ARCHITECTURAL
DRAWINGS. REFER TO ARCHITECTURAL
DRAWINGS FOR REQUIREMENTS
#4 AT 18" O.C. TYP.
#4 AT 12" O.C. CONT. HORIZ.
REINFORCING, TYP.
DRILL AND EPOXY REINFORCING
ABUTTING EXISTING CONSTRUCTION
INTO EXISTING FOUNDATION (4"
EMBED)
(3)-#5 CONT. IN FOOTING
FINISH GRADE
REFER TO SITE DRAWINGS
#5 AT 16" O.C. VERTICAL REINF.
CENTERED TYPICAL
ALTERNATE DOWEL LEGS
1'
8" 8" 8"
2' - 0"
BASEMENT/FOUNDATION
-12' - 0"
8" 8" 8"
2' - 0"
1'
SITE CONCRETE
REFER TO ARCHITECTURAL
DRAWINGS
(2)-#5 CONT. IN WALL
FOOTING
#4 AT 12" O.C. CONT.
HORIZ. REINFORCING
#5 AT 16" O.C. VERTICAL
REINFORCING CENTERED
ALTERNATE DOWEL LEGS
#4 AT 18" O.C.
REFER TO ARCHITECTURAL DRAWINGS
FOR STAIR GROOVE
REQUIREMENTS
COORDINATE STEP
GEOMETRY WITH
ARCHITECTURAL DRAWINGS
M
IN
5"
#4 NOSING
BAR (TYP.)
(TYP)
"Ld"
1/2" DEEP SAWCUT TO MAKE EDGES OF
REMOVAL PERPENDICULAR TO EXPOSED
FACE
RUBBED FINISH SMOOTH AND EVEN WITH
ADJACENT CONCRETE.
IF EXISTING REINFORCEMENT IS
DAMAGED BEYOND THE
REQUIREMENTS NOTED IN THE
CONCRETE REPAIR NOTES,
REFER TO REPAIR DETAIL ON
THIS SHEET
.REMOVE CONCRETE TO 3/4" MIN. BEHIND
REINFORCING BARS.
REMOVE ALL DETERIORATED CONCRETE
AND REPLACE WITH NEW CONCRETE WITH
1/2" MAX AGGREGATE SIZE OR APPROVED
REPAIR PRODUCT.
APPLY BONDING AGENT TO
EXISTING CONCRETE PRIOR TO
INSTALLING REPAIR MATERIAL
MIN.
1' - 0"
MIN.
1' - 0"
2'
M A
X.
2"
EXISTING FOUNDATION WALL
AND FOOTING. VERIFY IN FIELD
2" DRYPACK
PIPE PENETRATION
NOTE:
DO NOT LOCATE PENETRATIONS THROUGH COLUMN FOOTINGS.
COORDINATE WITH SITE MECHANICAL, PLUMBING, AND ELECTRICAL
DRAWINGS FOR LOCATIONS AND ELEVATIONS.
UNDERPINNING AT PIPE PENETRATIONS.
UNDERPINNING MUST BE PERFORMED
IN SEGMENTS NOT TO EXCEED 4' IN LENGTH.
UNDERPINNING TO MATCH WIDTH
OF EXISTING FOOTING.
PIPE SLEEVE
DIAMETER 2" LARGER
THAN PENETRATING
PIPE
WITH NEW CONCRETE (3000 PSI)
INFILL EXISTING WALL OPENING
3"
#4 AT 12" O.C. EACH WAY,
EACH FACE
DRILL AND SET #4X1'-0"
DOWELS AT 12" O.C.
INTO EXISTING CONCRETE
WALL WITH INJECTION ADHESIVE
3"
BENTONITE WATERSTOP
BOTH SIDES AND BOTTOM WALL
TYP.
6" EMBED
EXISTING CONCRETE
WALL
3"
DRILL AND SET #5X2'-0"
DOWELS INTO EXISTING
WALL WITH HILTI HIT-HY270
3"
BENTONITE WATERSTOP
BOTH SIDES AND BOTTOM WALL
WHERE BELOW GRADE
EXISTING MASONRY
WALL
SOLID GROUT ALL CORES
BELOW GRADE
#5 IN TOP COURSE, BOTTOM COURSE
AND 48" O.C. MAX.
EACH FACE IN SOLID GROUTED COURSE
#5 VERTICAL AT ENDS AND AT 32" O.C.
IN SOLID GROUTED CORE. DOWEL INTO
EX. WALL, SIMILAR TO HORIZONTAL
REINFORCING
TYP.
6" TOOTH IN NEW
MASONRY WHERE
REQUIRED BY ARCH'L
DRAWINGS
WITH NEW MASONRY
INFILL EXISTING WALL OPENING
EXISTING MASONRY LINTEL SCHEDULE
MARK CMU OPENING WIDTH LINTEL
(3)-L7X4X3/8 L.L.V.
(MIN. 8" BEARING)
UP TO 9'-6"EXISTING
12" BLOCK
NOTE:
1. PROVIDE LINTELS WHERE NEEDED. NOT SHOWN ON THE DRAWINGS
2. ALL EXTERIOR STEEL SHALL BE HOT DIPPED GALVANIZED
3. COORDINATE ALL OPENINGS WITH ARCHT & MECH DRAWINGS.
4. GROUT CORES SOLID BELOW LINTEL BEARING FULL HEIGHT TO UNDERSIDE OF LINTEL.
5. LINTELS FOR EXISTING 8" AND 12" CMU WERE DESIGNED BASED ON A BEARING WALL SUPPORTING 15'
OF ROOF, WITH 8' OF CMU ABOVE LINTEL. CONTRACTOR TO CONTACT STRUCTURAL ENGINEER, MICHAEL
HORTON ASSOCIATES, INC. FOR ALL FIELD CONDITIONS WITH BEARING WALLS SUPPORTING MORE THAN
15' OF ROOF ABOVE AND ALL OPENINGS LARGER THAN THOSE IN THE LINTEL SCHEDULE.
L5X3 1/2X5/16 (4" MIN. BEARING)UP TO 6'-0"
EXISTING
INTERIOR
4" MASONRY
L7X4X3/8 (4" MIN. BEARING) 6'-0" TO 10'-0"
UP TO 9'-6" EXISTING
8" BLOCK
(2)-L7X4X3/8 L.L.V.
(MIN. 8" BEARING)
EXISTING
INTERIOR
4" MASONRY
SAWCUT & REMOVE EXISTING
SLAB TO PLACE NEW UTILITIES.
REPLACE WITH NEW CONCRETE
SLAB ON GRADE.
EXISTING
SLAB ON
GRADE
6X6-W2.9XW2.9 WWF.
NEW UTILITY, REFER TO
MECHANICAL, ELECTRICAL &
PLUMBING DRAWINGS
COMPACTED
STONE FILL
OTH
IC
KN
ES
S M
A
TC
H E
X.
S
LA
B
M
IN
4"
4" MIN
6" M
IN
VAPOR RETARDER
FOUNDATIONS
1. BACKFILLING SHALL BE ACCOMPLISHED TO EQUAL HEIGHTS ON BOTH SIDES OF FOUNDATION WALLS TO PREVENT MOVEMENTS DUE TO UNBALANCED EARTH PRESSURE. WHERE EARTH IS ON ONE SIDE ONLY, BACKFILLING AND COMPACTION SHALL NOT START UNTIL FLOOR SLAB OR ADEQUATE BRACING IS PROVIDED FOR WALL SUPPORT (EXCEPT AT RETAINING
WALLS).
2. ALL FOOTINGS ARE TO REST ON UNDISTURBED NATURAL SOIL, AS DEFINED IN THE SPECIFICATIONS, OR CONTROLLED COMPACTED FILL, REGARDLESS OF ELEVATIONS SHOWN ON DRAWINGS. FOOTING BOTTOM ELEVATIONS SHALL NOT BE
HIGHER THAN INDICATED ON THE FOUNDATION PLAN, NOR LESS THAN 3'-6" BELOW FINISH GRADES.
3. IF FILL MATERIALS ARE ENCOUNTERED AT FOOTING BEARING ELEVATIONS, ALL FILL MATERIAL SHALL BE EXCAVATED AND DISPOSED OF LEGALLY OFF-SITE. THE OVER EXCAVATION SHALL BE BACKFILLED WITH CONTROLLED COMPACTED FILL TO THE
BOTTOM OF FOOTING ELEVATION AS REQUIRED.
4. ALL CONTROLLED COMPACTED BACKFILL UNDER FOOTINGS AND WITHIN THE FOOTPRINT OF THE STRUCTURE SHALL BE
COMPACTED TO 95% OF THE MODIFIED OPTIMUM DENSITY.
5. BOTTOM OF ALL EXTERIOR FOOTINGS SHALL BE AT LEAST 3'-6" BELOW FINISHED GRADE. PRIOR TO PROCEEDING WITH
FOOTING EXCAVATION, THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE COORDINATION OF FINISH GRADES AND BOTTOM
OF EXTERIOR FOOTING ELEVATIONS TO MAINTAIN THE 3'-6" FROST PROTECTION.
6. ALL SOIL SURROUNDING AND UNDER ALL FOOTINGS SHALL BE PROTECTED FROM FREEZING AND FROST ACTION DURING THE
COURSE OF CONSTRUCTION.
7. FOOTING BOTTOMS SHALL STEP AT THE RATE OF 1 UNIT VERTICAL TO 2 UNITS HORIZONTAL WITH A MAXIMUM VERTICAL STEP
OF 2'-0".
8. WHERE SUBSURFACE PIPING PASSES THROUGH FOUNDATION WALLS, THE TOP OF THE FOOTINGS SHALL BE AT LEAST 8" BELOW THE INVERT ELEVATION OF THE PIPING AND CONDUITS. COORDINATE ALL INVERTS WITH MECHANICAL, PLUMBING, ELECTRICAL, AND SITE UTILITY DRAWINGS.
9. WHERE FOOTINGS ARE IN CLOSE PROXIMITY OF SUBSURFACE PIPING OR CONDUIT, BOTTOM OF FOOTINGS SHALL BE AT LEAST
8" BELOW INVERT ELEVATION OF PIPING OR CONDUITS.
10. KEEP FOUNDATION EXCAVATIONS FREE OF WATER AT ALL TIMES.
11. PLACEMENT OF ALL COMPACTED FILL MATERIALS MUST BE UNDER SUPERVISION OF AN APPROVED TESTING LABORATORY
(SEE SPECIFICATIONS). CONCRETE FOUNDATIONS SHALL NOT BE PLACED UNTIL SUBGRADE HAS BEEN CHECKED IN PLACE
AND APPROVED BY TESTING LABORATORY.
12. EXISTING ON-SITE EXCAVATED MATERIALS SHALL NOT BE ACCEPTABLE BACKFILL MATERIAL BELOW BUILDING FOUNDATIONS, SLABS ON GRADE, OR FOR BACKFILLING OF FOUNDATION WALLS, OR WITHIN 2 FEET OF PAVEMENT GRADES UNLESS
APPROVED BY THE GEOTECHNICAL ENGINEER OF RECORD.
13. FOUNDATION DESIGN SITE PREPARATION: THE FOUNDATION DESIGN AS INDICATED ON THE STRUCTURAL DRAWINGS HAS BEEN BASED ON THE FOLLOWING SITE PREPARATION. THE SITE HAS BEEN PREPARED BY THE EXCAVATION AND REMOVAL FROM THE SITE OF ALL EXISTING FILL AND CONTAMINATED SOILS. THE FOUNDATION DESIGN IS BASED ON THE CONTROLLED
BACKFILLING OF THE SITE EXCAVATION WITH CONTROLLED FILL COMPACTED TO AT LEAST 95% OF THE MODIFIED OPTIMUM
DENSITY IN ACCORDANCE WITH ASTM D1557.
SLAB ON GRADE
1. ALL INTERIOR SLABS ON GRADE SHALL BEAR ON A 15 MIL, CLASS A, VAPOR RETARDER OVER A MINIMUM OF 4 INCHES OF 3/4" COMPACTED PROCESSED AGGREGATE FILL, OVER A MINIMUM OF 6 INCHES OF COMPACTED GRAVEL FILL.
a. ALL JOINTS OF THE VAPOR RETARDER SHALL BE SEALED WITH TAPE. TURN THE VAPOR BARRIER UP AT ALL
TERMINATIONS AGAINST FOUNDATION WALLS AND SEAL JOINT BY CONTINUOUSLY TAPING.
1. IF FILL MATERIALS ARE ENCOUNTERED SLAB SUBGRADE ELEVATIONS, ALL FILL MATERIAL SHALL BE EXCAVATED AND DISPOSED OF LEGALLY OFF-SITE. THE OVER EXCAVATION SHALL BE BACKFILLED WITH CONTROLLED COMPACTED FILL TO THE
BOTTOM OF THE SLAB SUBGRADE AS REQUIRED. ALL CONTROLLED COMPACTED BACKFILL UNDER SLABS WITHIN THE FOOTPRINT OF THE STRUCTURE SHALL BE COMPACTED TO 95% OF THE MODIFIED OPTIMUM DENSITY.
3. EXISTING ON-SITE EXCAVATED MATERIALS SHALL NOT BE ACCEPTABLE BACKFILL MATERIAL BELOW BUILDING SLABS ON
GRADE UNLESS APPROVED BY THE GEOTECHNICAL ENGINEER OF RECORD.
4. CONTRACTOR SHALL CONSOLIDATE ALL SLAB CONCRETE USING VIBRATIONAL METHODS IN CONFORMANCE WITH ACI 309, AGUIDE FOR CONSOLIDATION OF CONCRETE.
CONCRETE
MATERIALS:
CONCRETE SHALL MEET THE REQUIREMENTS OF THE EXPOSURE CATEGORY LISTED BELOW PER ACI 318 CHAPTER 19, AND SHALL HAVE THE MAXIMUM WATER TO CEMENT RATIO, TARGET AIR CONTENT AND DEVELOP STRENGTH IN 28 DAYS
AS FOLLOWS:
LOCATION EXPOSURE STRENGTH MAXIMUM WATER TARGET AIR
CATEGORY (PSI) TO CEMENT RATIO CONTENT
FOUNDATIONS F2 4500 0.45 6%
SLABS ON GRADE F0 3500 N/A N/A
EXTERIOR CONCRETE
MATS AND SLABS ON
GRADE F2 4500 0.45 6%
* INCLUDES ANY EXTERIOR CONCRETE PADS, SLABS, ETC. NOTED ON THE STRUCTURAL DRAWINGS. REFER
TO SITE CONCRETE SPECIFICATIONS FOR ALL OTHER EXTERIOR CONCRETE REQUIREMENTS.
1. ALL DETAILING, FABRICATION AND ERECTION OF REINFORCING BARS MUST FOLLOW ACI 318-19.
2. CONTRACTOR IS RESPONSIBLE FOR FOLLOWING ACI GUIDELINES FOR HOT AND COLD WEATHER CONCRETE
AND SHALL SUBMIT PROCEDURES FOR RECORD PRIOR TO COMMENCING WORK.
3. REINFORCING STEEL SHALL BE ASTM A615, GRADE 60.
4. NO TACK WELDING OF REINFORCING WILL BE PERMITTED
5. UNLESS NOTED OTHERWISE, ALL LAP SPLICES SHALL BE CLASS B, IN ACCORDANCE WITH ACI 318-19.
6. WELDED WIRE FABRIC SHALL CONFORM TO ASTM A-185
7. WIRE MESH REINFORCEMENT MUST LAP ONE MESH SIZE AT SIDES AND ENDS AND BE WIRED TOGETHER.
8. WELDED WIRE FABRIC SIDE LAPS SHALL BE STAGGERED TO AVOID FOUR MESH THICKNESS AT COINCIDING
END LAP AND SIDE LAP LOCATION.
9. NO CALCIUM CHLORIDE OR ADMIXTURES CONTAINING MORE THAN 0.1% CHLORIDE BY WEIGHT OF
ADMIXTURES SHALL BE USED IN THE CONCRETE.
10. BOTTOM OF ALL EXTERIOR FOOTINGS SHALL BE AT LEAST 3'-6" BELOW FINISHED GRADE. PRIOR TO
PROCEEDING WITH FOOTING FORMWORK, THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE
COORDINATION OF BOTTOM OF EXTERIOR FOOTING ELEVATIONS WITH THE FINISH GRADES AND MAINTAINING THE 3'-6" FROST PROTECTION. WHERE SUBSURFACE PIPING PASSES THROUGH FOUNDATION WALLS, THE TOP OF FOOTINGS SHALL BE AT LEAST 8" BELOW THE INVERT ELEVATION OF THE PIPING AND CONDUITS.
COORDINATE ALL INVERTS WITH MECHANICAL, PLUMBING, FIRE PROTECTION, ELECTRICAL, SITE AND SITE
UTILITY DRAWINGS. PIPING OR CONDUITS SHALL NOT PASS THROUGH COLUMNS OR PIERS.
11. ALL HORIZONTAL STEEL SHOWN IN SECTIONS AND DETAILS SHALL BE CONTINUOUS, UNLESS OTHERWISE
NOTED. ALL LAPS SHALL BE CLASS AB@ SPLICES IN ACCORDANCE WITH ACI 318. PROVIDE 90 DEGREE HOOKS ORIENTED VERTICALLY IN WALL AT LOCATIONS WHERE HORIZONTAL REINFORCING IS INTERRUPTED BY
TOP OR BOTTOM OF WALL STEPS OR AT WALL ENDS THAT DO NOT OCCUR AT WALL CORNERS.
12. AT INTERSECTIONS OF REINFORCED CONCRETE WALLS, PROVIDE CORNER DOWELS OF SAME SIZE AND AT
THE SAME SPACING AS THE SMALLER HORIZONTAL REINFORCING. DOWELS SHALL HAVE A CLASS B LAP
WITH HORIZONTAL REINFORCING IN EACH DIRECTION.
13. PROVIDE DRILLED AND EPOXIED DOWELS OF SAME SIZE TO MATCH NEW REINFORCING WHERE NEW
CONSTRUCTION ABUTS EXISTING CONCRETE CONSTRUCTION. LENGTH SHALL BE THE REQUIRED
EMBEDMENT DEPTH PER THE ANCHOR BOLT/EPOXY MANUFACTURER PLUS A CLASS B LAP SPLICE FOR THE
SIZE OF BAR.
14. ALL KEYS IN CONCRETE WALLS SHALL BE 2 X 4 UNLESS NOTED OTHERWISE.
15. SEE ARCHITECTURAL, MECHANICAL, PLUMBING, ELECTRICAL, SITE UTILITY AND EQUIPMENT DRAWINGS FOR
CONCRETE PADS, SLEEVES, OPENINGS, RECESSES, AND BUILT-IN WORK IN CONCRETE ELEMENTS.
16. THE CONTRACTOR SHALL FURNISH, LOCATE AND INSTALL ALL ACCESSORIES FOR PROPER ANCHORAGE OF WOOD AND METAL FRAMING, WOOD BLOCKING, BRICK WORK AND MASONRY UNITS. THEY SHALL BE
SOLELY RESPONSIBLE FOR FURNISHING, LOCATING AND ENSURING PROPER QUANTITY OF ALL FASTENING
DEVICES.
17. PROVIDE CLEARANCE FROM EDGE OF REINFORCING TO EDGE OF CONCRETE AS FOLLOWS:
FOOTINGS (AGAINST EARTH) 3"
BEAMS (LONGITUDINAL REINFORCING) 2"
COLUMNS AND PIERS (VERTICAL REINFORCING) 2"
WALLS, EXTERIOR FACE (#5 AND SMALLER) 1 1/2"
WALLS, EXTERIOR FACE (#6 AND LARGER) 2"
SLABS (INTERIOR) 3/4"
SLABS (EXTERIOR) 1 1/2"
SLABS ON GRADE (W.W.F.) 1/3 X THK. FROM TOP SURFACE
18. JOINTS NOT INDICATED ON THE DRAWINGS SHALL BE MADE SO AS TO LEAST IMPAIR THE STRENGTH OF
THE STRUCTURE. THERE SHALL BE NO HORIZONTAL JOINTS IN BEAMS OR SUSPENDED SLABS.
19. REINFORCING STEEL SHOP DRAWINGS SHALL INDICATE THE SEQUENCE IN WHICH LAYERS OF CROSSING REINFORCING SHOULD BE PLACED, IN ORDER TO PRODUCE THE CORRECT OUTERMOST LAYER AS INDICATED
ON THE DRAWINGS.
20. ALL REINFORCING, THREADED RODS OR BOLTS INDICATED TO BE DRILLED AND EPOXIED SHALL UTILIZE HILTI
HIT-HY200 ADHESIVE OR APPROVED EQUAL.
1. COORDINATE WITH MECHANICAL, ELECTRICAL AND PLUMBING DRAWINGS FOR QUANTITY, SIZE AND LOCATION.
2. CONCRTRE STREGTH EQUALS 3,500 PSI AT 28 DAYS.
EXISTING CONCRETE
SLAB ON GRADE
D R
A W
IN
G
S
R
EF
ER
T
O M
EC
H
'L
1" C
LE
A
R
6X6-W2.9XW2.9 W.W.F
5/8"Ø AB'S @18" O.C.
DRILL AND EPOXY
MECHANICAL UNIT
REFER TO MECHANICAL
DRAWINGS
NUT (TYPICAL)
3" E
M B
ED
INTENTIONALLY ROUGHEN
SURFACE
DRAWING TITLE:REVISED BY:DATE:DESCRIPTION:REVISION:PROJECT TITLE: DATE:
SCALE:
DRAWN BY:
PROJECT NUMBER:
DRAWING NUMBER:
SILVER PETRUCELLI + ASSOCIATES
203 230 9007
3190 WHITNEY AVENUE HAMDEN CT 06518
silverpetrucelli.com
311 STATE STREET NEW LONDON CT 06320
PROJECT SUBMISSION:
MEP & DOOR REPLACEMENTS
BROOKLYN COMMUNITY CENTER
31 TIFFANY STREET
BROOKLYN, CT
ISSUED FOR BID
25-135
10/16/2026
As indicated
/1
/2
:0
:3
A
M
S101
SECTIONS, TYPICAL DETAILS, AND
GENERAL NOTES
A. Close
3/4" = 1'-0" REFERENCE DWG: 1 / S1001 SECTION: STAIR REPLACEMENT ALTERNATE
3/4" = 1'-0" REFERENCE DWG: 1 / S1002 SECTION: STAIR REPLACEMENT ALTERNATE
3/4" = 1'-0"3 TYPICAL SPALL REPAIR
3/4" = 1'-0"5 TYPICAL DETAIL OF PIPE PENETRATIONS BELOW EXISTING WALL FOOTING
3/4" = 1'-0"4 TYPICAL FOUNDATION WALL INFILL
3/4" = 1'-0"6 TYPICAL MASONRY WALL INFILL
3/4" = 1'-0"7 TYPICAL DETAIL FOR NEW UTILITIES BELOW EX. SLAB ON GRADE.
3/4" = 1'-0"8 TYPICAL CONCRETE EQUIPMENT ON EXISTING SLAB ON GRADE DETAIL
ROOF CONSTRUCTION NOTES:
1. CONTRACTOR TO FIELD VERIFY ALL EXISTING FRAMING SIZES, SPACING AND LOCATIONS
PRIOR TO SUBMITTING SHOP DRAWINGS
A B C D E
EX. WOOD TRUSS AT
24' O.C. V.I.F.
EX. WOOD TRUSS AT
24' O.C. V.I.F.
EX
. W
O O
D T
R U
S S
A T
' O
.C . V
.I.
F.
EX
. W
O O
D T
R U
S S
A T
' O
.C . V
.I.
F.
EX. WOOD TRUSS AT
24' O.C. V.I.F.
EX. W8
EX
. W
EX
. W
EX. W8
S102
S102
S102
S102
S102
S102
S102
S102
PROVIDE CONNECTION
OF WF FRAMING TO
EXISTING COLUMN
SIMILAR TO 3/S102
PROVIDE CONNECTION
OF WF FRAMING TO
EXISTING COLUMN
SIMILAR TO 3/S102
PROVIDE CONNECTION
OF WF FRAMING TO
EXISTING COLUMN
SIMILAR TO 3/S102
PROVIDE CONNECTION
OF WF FRAMING TO
EXISTING COLUMN
SIMILAR TO 3/S102
A
EXISTING TIE. V.I.F.
ALL TRUSSES HAVE A TIE TO THE
WALL PLATE. IF EXISTING TRUSSES DO
NOT HAVE A TIE, PROVIDE A SIMPSON
H3 FROM TRUSS TO WALL PLATE
EXISTING WOOD PLATE
EXISTING THREADED ROD CONNECTOR. MULTIPLE
LOCATIONS WERE OBSERVED WHERE CONNECTOR
DID NOT HAVE A NUT. AT THESE LOCATIONS
PROVIDE A WASHER AND NUT. IF EXISTING
ROD WILL NOT ACCEPT A NUT PROVIDE A NEW
5/8"Ø HAS THREADED ROD 6" FROM THE EXISTING
THREADED ROD. CONNECT TO EXISTING
WALL WITH HILTI HIT-HY 270 EPOXY. PROVIDE
2X2X1/4 PLATE WASHER BETWEEN
NUT AND WOOD PLATE.
EXISTING WOOD TRUSS
B
EXISTING CONCRETE COLUMN
V.I.F.
EXISTING WOOD PLATE
TO REMAIN.
MAG-DRILL EXISTING FLANGE. INSTALL NEW
1/2"Ø A307N BOLT AT 24" O.C. THROUGH
EXISTING PLATES AND BEAM FLANGE.
PROVIDE 2X2X1/4 PLATE WASHER BETWEEN
NUT AND WOOD PLATE. STANDARD
WASHER IS ACCEPTABLE AGAINST STEEL.
EXISTING WOOD TRUSS
PROVIDE NEW SIMPSON H2.5A
FROM EACH TRUSS TO SUPPORTING PLATE
EXISTING STEEL BEAM
V.I.F.
NEW L6X4X3/8X0'-7" LLH
INSTALL (2)-5/8"Ø HAS THREADED RODS INTO EX.
CONCRETE
COLUMN WITH HILTI HIT-HY 200 (6" EMBED)
ANCHORS TO BE 4" APART.
MAG-DRILL EXISTING BEAM WEB AND INSTALL
(2)-3/4" A325N BOLTS.
PROVIDE NUT ABOVE AND BELOW ANGLE.1 1/2"
PROVIDE NEW SIMPSON H2A
FROM EACH TRUSS TO SUPPORTING TRUSS
ROOF EAVE
16' - 8"
EXISTING CONCRETE COLUMN
V.I.F.
EXISTING WOOD PLATE
TO REMAIN.
MAG-DRILL EXISTING FLANGE. INSTALL NEW
1/2"Ø A307N BOLT AT 24" O.C. THROUGH
EXISTING PLATES AND BEAM FLANGE.
PROVIDE 2X2X1/4 PLATE WASHER BETWEEN
NUT AND WOOD PLATE. STANDARD
WASHER IS ACCEPTABLE AGAINST STEEL.
EXISTING WOOD TRUSS
PROVIDE NEW SIMPSON H2.5A
FROM EACH TRUSS TO SUPPORTING PLATE
EXISTING STEEL BEAM
V.I.F.
NEW L6X4X3/8X0'-7" LLH
INSTALL (2)-5/8"Ø HAS THREADED RODS INTO EX. CONCRETE
COLUMN WITH HILTI HIT-HY 200 (6" EMBED) ANCHORS TO BE 4" APART.
MAG-DRILL EXISTING BEAM WEB AND INSTALL (2)-3/4" A325N BOLTS.
PROVIDE NUT ABOVE AND BELOW ANGLE.
1 1/2"
GENERAL
1. GOVERNING CODE: 2022 STATE OF CONNECTICUT BUILDING CODE, (2021 INTERNATIONAL BUILDING CODE).
1. DESIGN LOADS: TOWN OF BROOKLYN
3. CONSTRUCTION LIVE LOADS: 20 PSF
a. ROOF LOAD:
ROOF SNOW LOAD CRITERIA:
Pg = 35 PSF
Ce = 0.9 Is = 1.0
Ct= 1.1
Pf = 24.23 PSF
WITH INCREASES FOR SNOW DRIFTING, UNBALANCES AND SLIDING PER SECTION 1608 (2021 IBC).
MINIMUM ROOF LIVE LOAD = 30 PSF
ROOF DEAD LOAD = 15 PSF
b. WIND LOAD CRITERIA: SECTION 1609 (2021 IBC)
ULTIMATE WIND SPEED VU = 125 MPH
NOMINAL DESIGN WIND VASD = 97 MPH
RISK CATEGORY II, Iw = 1.0
EXPOSURE CLASSIFICATION "B".
MINIMUM WIND LOAD ON PRIMARY STRUCTURE = 16 PSF
WIND LOADS ON SECONDARY ELEMENTS SHALL CONFORM WITH ASCE 7-16.
COMPONENT AND CLADDING DESIGN WIND PRESSURES:
ROOF ZONE 1: POSITIVE: 22.59 PSF
NEGATIVE: -40.57 PSF
ROOF ZONE 2e,2r: POSITIVE: 22.59 PSF
NEGATIVE: -55.97 PSF
ROOF ZONE 3e,3r: POSITIVE: 16.00 PSF
NEGATIVE: -37.00 PSF
WALL ZONE 4: POSITIVE: 30.3 PSF
NEGATIVE: -32.9 PSF
WALL ZONE 5: POSITIVE: 30.3 PSF
NEGATIVE: -40.6 PSF
ROOF OVERHANG ZONE 2: -67.01 PSF
ROOF OVERHANG ZONE 3: -79.85 PSF
DESIGN WIND PRESSURE IS COMPUTED BASED ON ULTIMATE WIND SPEED USING 10 SQUARE FOOT OF AREA.
c. SEISMIC LOAD CRITERIA: AS PER SECTION 1613 (2021 IBC) WITH:
RISK CATEGORY = II
SEISMIC IMPORTANCE FACTOR, Ie = 1.0
Ss = 0.184g, S1 = 0.054g
SOIL SITE CLASS = D, DEFAULT
SPECTRAL RESPONSE COEFFICIENTS, Sds = 0.197G, Sd1 = 0.087g
SEISMIC DESIGN CATEGORY, B
PROVIDED FOR SECONDARY COMPONENTS ONLY, BUILDING FRAME NOT IMPACTED BY SCOPE OF WORK.
d. ASSUMED BEARING PRESSURE ON UNDISTURBED SOIL: 3000 PSF
4. SHOULD ANY OF THE DETAILED INSTRUCTIONS SHOWN ON THE PLANS CONFLICT WITH THE GENERAL STRUCTURAL NOTES, THE SPECIFICATIONS, OR WITH EACH OTHER, THE STRICTEST PROVISION SHALL GOVERN.
5. THE STRUCTURE IS DESIGNED TO BE SELF-SUPPORTING AND STABLE AFTER THE BUILDING IS FULLY COMPLETED. IT IS THE
CONTRACTOR'S SOLE RESPONSIBILITY TO DETERMINE ERECTION PROCEDURE AND SEQUENCE AND TO ENSURE THE SAFETY OF THE BUILDING AND ITS COMPONENT PARTS DURING ERECTION. THIS INCLUDES THE ADDITION OF WHATEVER SHORING, SHEETING, TEMPORARY BRACING, GUYS OR TIEDOWNS WHICH MIGHT BE NECESSARY. SUCH MATERIAL SHALL REMAIN THE
CONTRACTOR'S PROPERTY AFTER COMPLETION OF THE PROJECT.
a. THE CONTRACTOR SHALL PROVIDE SHORING CALCULATIONS AND SHORING DRAWINGS, INDICATING THE WORK TO
BE PROVIDED, SIGNED AND SEALED BY A PROFESSIONAL ENGINEER LICENSED IN THE STATE OF CONNECTICUT.
6. IT IS THE CONTRACTOR'S SOLE RESPONSIBILITY TO FOLLOW ALL APPLICABLE SAFETY CODES AND REGULATIONS DURING ALL
PHASES OF CONSTRUCTION.
7. SHOP DRAWINGS ARE TO BE CHECKED BY THE CONTRACTOR AND SUBCONTRACTOR AND BEAR CHECKER'S INITIALS BEFORE
BEING SUBMITTED TO THE ARCHITECT FOR APPROVAL.
8. THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS, ELEVATIONS, ANGLES AND EXISTING CONDITIONS BEFORE PROCEEDING
WITH ANY WORK.
9. ALL SECTIONS AND DETAILS SHALL BE CONSIDERED TYPICAL AND APPLY FOR THE SAME AND SIMILAR SITUATIONS
THROUGHOUT THE BUILDING, UNLESS OTHERWISE SPECIFICALLY NOTED.
10. CONTRACTOR SHALL REVIEW ALL ARCHITECTURAL AND STRUCTURAL DRAWINGS PRIOR TO SUBMITTING THEIR BID FOR REFERENCE TO ALL NOTES ON ARCHITECTURAL DRAWINGS REFERRING TO “SEE STRUCTURAL DRAWINGS”. IF THE SIZE OF ELEMENTS AND DETAILING OF MEMBERS IS NOT INDICATED, THE CONTRACTOR SHALL CONTACT THE ARCHITECT TO REQUEST
THE MISSING INFORMATION IN PREPARATION OF THEIR BID. THESE REFERENCED ITEMS SHALL BE PART OF THE BASE BID.
11. IN CASES OF DISCREPANCIES BETWEEN CONTRACT DOCUMENTS AND SUBMITTED SHOP DRAWINGS, THE CONTRACT
DOCUMENTS SHALL GOVERN INSTALLATION OF MATERIALS.
12. WOOD BLOCKING THAT IS NOT PART OF THE PRIMARY STRUCTURAL FRAME IS NOT OWNED BY MHAI. THE GENERAL CONTRACTOR OR CONSTRUCTION MANAGER IS RESPONSIBLE FOR COORDINATING THE PARTIES THAT OWN THE BLOCKING, INCLUDING THE CONNECTION OF THE BLOCKING TO ANY SUPPORTING MATERIAL. THIS INCLUDES BUT IS NOT LIMITED TO:
BLOCKING BELOW MECHANICAL EQUIPMENT, BLOCKING FOR ROOFING ATTACHMENT, AND BLOCKING FOR WINDOW SYSTEM
CONNECTIONS
CONTRACTOR’S DELEGATED DESIGN
1. CONTRACTOR SHALL RETAIN THE SERVICES OF A PROFESSIONAL ENGINEER REGISTERED IN THE STATE OF CONNECTICUT TO
PERFORM THE DESIGN OF THE FOLLOWING:
1. TEMPORARY SHORING OF EXISTING STRUCTURAL MEMBERS.
2. ALL NON-STRUCTURAL EQUIPMENT ATTACHMENT TO SUPPORTING STRUCTURE, THIS INCLUDES BUT IS NOT
LIMITED TO MECHANICAL CURB ATTACHMENTS, HANGING CONNECTIONS OF MEP ITEMS, ETC.
2. ALL CALCULATIONS SHALL BE SIGNED AND SEALED BY THE ENGINEER AND SUBMITTED FOR REVIEW.
WOOD FRAMING
1. CONNECTIONS AND FASTENINGS: ALL MEMBERS SHALL BE FASTENED AT THEIR JUNCTIONS WITH APPROVED CONNECTORS, SPIKES, NAILS, STRAPS, OR OTHER DEVICES. ALL CONNECTORS AND FASTENERS FOR USE WITH PRESSURE TREATED WOOD SHALL BE HOT DIPPED, GALVANIZED OR STAINLESS STEEL. ALL BOLTS IN CONTACT WITH PRESSURE TREATED LUMBER SHALL
BE HOT DIPPED, GALVANIZED OR STAINLESS STEEL.
2. PROVIDE A MINIMUM 0.131 x 3” COMMON WIRE NAIL FOR ALL FRAMING. NAILING SHALL BE IN ACCORDANCE WITH THE "FASTENING SCHEDULE", IN CHAPTER 23 OF THE 2021 IBC CODE PER THE STATE OF CONNECTICUT BUILDING CODE.
3. ALL PREFABRICATED STEEL CONNECTORS INDICATED ON THE DRAWINGS SHALL BE AS MANUFACTURED BY SIMPSON
STRONG-TIE OR APPROVED EQUAL. ALL SUBSTITUTIONS SHALL BE SUBMITTED FOR APPROVAL PRIOR TO PLACEMENT ON THE PROJECT. CONTRACTOR SHALL ANTICIPATE THE LEAD TIMES REQUIRED FOR OBTAINING THE CONNECTORS INDICATED ON THE
DRAWINGS AND ALLOW SUFFICIENT TIME TO ORDER AND OBTAIN IN ORDER AS TO NOT DELAY THE WORK.
POST-INSTALLED ANCHORS
1. EXCEPT WHERE INDICATED ON THE DRAWINGS, POST-INSTALLED ANCHORS SHALL CONSIST OF THE FOLLOWING ANCHOR
TYPES OR APPROVED EQUAL AND INSTALLED IN ACCORDANCE WITH THEIR RESPECTIVE ICC-ES REPORT AND MANFACTURER’S
PUBLISHED INSTALLATION INSTRUCTIONS:
*SAFE SET CONSISTS OF HOLLOW DRILL BIT WITH HILTI VC SYSTEM
2) EXCEPT WHERE INDICATED ON THE DRAWINGS, POST-INSTALLED REINFORCING BARS SHALL CONSIST OF THE FOLLOWING ADHESIVE ANCHOR TYPES OR APPROVED EQUAL WITH APPROVAL FOR DEVELOPMENT OF BAR USING ACI PROVISIONS FOR
EMBEDMENT DEPTHS GREATER THAN 20 BAR DIAMETERS AND INSTALLED IN ACCORDANCE WITH THEIR RESPECTIVE ICC-ES
REPORT AND MANFACTURER’S PUBLISHED INSTALLATION INSTRUCTIONS
*SAFE SET CONSISTS OF HOLLOW DRILL BIT WITH HILTI VC SYSTEM
3) FOR ANCHORAGE TO HOLLOW / MULTI-WYTHE MASONRY THE CONTRACTOR SHALL PERFORM A PULL TEST ON 5% OF ALL ANCHORS TO VALIDATE THAT THE ANCHORS ACHIEVE THE MINIMUM TENSION CAPACITY SPECIFIED IN ESR-4144. AN ADDITIONAL 20% OF ALL ANCHORS SHALL BE TESTED USING A CALIBRATED TORQUE WRENCH TO A MINIMUM 60 FT-LBS TORQUE. TESTING SHALL BE PERFORMED AT RANDOM AND VARIED LOCATIONS THROUGHOUT THE PROJECT WHERE ANCHORS
ARE INSTALLED
4) ALL ANCHORS INTO CONCRETE SHALL BE INSTALLED AFTER THE CONCRETE HAS ACHIEVED IT'S 28-DAY DESIGN STRENGTH, BUT NOT LESS THAN 21 DAYS AFTER CONCRETE PLACEMENT.
5) ALL ADHESIVE ANCHORS INSTALLED IN THE HORIZONTAL, UPWARD INCLINED, AND OVERHEAD ORIENTATIONS SHALL BE CONTINUOUSLY INSPECTED DURING INSTALLATION PER ACI. OVERHEAD ADHESIVE ANCHORS SHALL BE INSTALLED USING THE
HILTI PROFI PISTON PLUG SYSTEM.
6) ANCHOR CAPACITY USED IN DESIGN SHALL BE BASED ON THE TECHNICAL DATA PUBLISHED BY HILTI OR SUCH OTHER METHOD AS APPROVED BY THE STRUCTURAL ENGINEER OF RECORD. SUBSTITUTION REQUESTS FOR ALTERNATE PRODUCTS MUST BE APPROVED IN WRITING BY THE STRUCTURAL ENGINEER OF RECORD PRIOR TO USE. CONTRACTOR SHALL PROVIDE CALCULATIONS DEMONSTRATING THAT THE SUBSTITUTED PRODUCT IS CAPABLE OF ACHIEVING THE PERFORMANCE VALUES OF THE SPECIFIED PRODUCT IN BOTH DRY AND WATER SATURATED CONCRETE, INCLUDING AN ICC-ES REPORT SHOWING COMPLIANCE WITH THE RELEVANT BUILDING CODE, SEISMIC USE, LOAD RESISTANCE, INSTALLATION CATEGORY, IN-SERVICE
TEMPERATURE, INSTALLATION TEMPERATURE, ETC.
7) USE OF DIAMOND CORE BIT WITH ROUGHENING TOOL REQUIRES APPROVAL FROM ENGINEER OF RECORD PRIOR TO DRILLING.
UNLESS OTHERWISE SHOWN IN THE DRAWINGS. ALL HOLES SHALL BE DRILLED PERPENDICULAR TO THE CONCRETE SURFACE.
8) FOR PROJECTS MEETING IBC 2012 OR LATER, ACI/CRSI ADHESIVE ANCHOR INSTALLER CERTIFICATION IS REQUIRED FOR ALL INSTALLERS OF ADHESIVE ANCHORS IN HORIZTONAL OR UPWARDLY INCLINED ORIENTATION. THE HILTI ADHESIVE ANCHOR
INSTALLER CERTIFICATION PROGRAM (HAAICP) IS AN APPROVED EQUIVALENT.
9) CONTRACTOR SHALL ARRANGE AN ANCHOR MANUFACTURER’S REPRESENTATIVE TO PROVIDE ON-SITE ANCHOR INSTALLATION
TRAINING FOR ALL OF THEIR ANCHORING PRODUCTS SPECIFIED. CONTRACTOR SHALL SUBMIT DOCUMENTED CONFIRMATION THAT ALL OF THE CONTRACTOR’S PERSONNEL INSTALLING ANCHORS HAVE RECEIVED THE REQUIRED TRAINING PRIOR TO THE
COMMENCEMENT OF WORK.
10) ANCHOR CAPACITY IS DEPENDANT UPON SPACING BETWEEN ADJACENT ANCHORS AND PROXIMITY OF ANCHORS TO EDGE OF CONCRETE. INSTALL ANCHORS IN ACCORDANCE WITH SPACING AND EDGE CLEARANCES INDICATED ON THE DRAWINGS.
11) CONTINOUS OR PERIODIC SPECIAL INSPECTION FOR POST INSTALLED ANCHORS SHALL BE PERFORMED IN ACCORDANCE WITH
SECTION 4.3/4.4 OF THE ICC-ES REPORT FOR THE INDIVIDUAL ANCHOR. SPECIAL INSPECTOR SHALL BE NOTIFIED PRIOR TO
COMMENCEMENT OF WORK TO COORDINATE INSPECTION EFFORTS.
12) THE DESIGN OF STRAIGHT POST-INSTALLED REINFORCING BARS SHALL BE PERFORMED PER THE DEVELOPMENT AND SPLICE REQUIREMENTS OF THE ACI 318 BUILDING CODE REQUIREMENTS. THE POST-INSTALLED REINFORCING BAR SYSTEM IS AN ALTERNATIVE TO CAST-IN-PLACE REINFORCING BARS GOVERNED BY ACI 318 AND IBC CHAPTER 19. SUBSTITUTION REQUESTS
FOR ALTERNATE PRODUCTS MUST BE APPROVED IN WRITING BY THE STRUCTURAL ENGINEER OF RECORD PRIOR TO USE. THE
ADHESIVE SYSTEM SHALL BE QUALIFIED FOR DEVELOPMENT LENGTH APPLIATION.
13) EXISTING REINFORCING BARS IN THE CONCRETE STRUCTURE MAY CONFLICT WITH SPECIFIC ANCHOR LOCATIONS. UNLESS
NOTED ON THE DRAWINGS THAT THE BARS CAN BE CUT, THE CONTRACTOR SHALL REVIEW THE EXISTING STRUCTURAL
DRAWINGS AND SHALL UNDERTAKE TO LOCATE THE POSITION OF THE REINFORCING BARS AT THE LOCATIONS OF THE
CONCRETE ANCHORS, BY HILTI PS 1000 OR OTHER GPR, X-RAY, CHIPPING OR OTHER MEANS.
STRUCTURAL STEEL
MATERIALS:
STRUCTURAL STEEL ASTM A 36
ALL W SHAPES ASTM A 992, GR.50
STRUCTURAL STEEL TUBING ASTM A500, GRADE C
STRUCTURAL STEEL PIPE ASTM A53, GRADE B
BOLTS ASTM A325
ANCHOR BOLTS ASTM F1554, GRADE 36
WELDING ELECTRODE ASTM E 70
WELDABLE REBAR ASTM A706, GRADE 60
1. DESIGN, FABRICATION, AND ERECTION OF STRUCTURAL STEEL SHALL CONFORM TO AMERICAN INSTITUTE OF STEEL
CONSTRUCTION SPECIFICATION, AISC 360-10. ALL REACTIONS SHOWN ON PLAN HAVE BEEN DEVELOPED USING ALLOWABLE
STRESS DESIGN.
2. WELDING SHALL CONFORM TO THE CODE FOR "ARC AND GAS WELDING IN BUILDING CONSTRUCTION" OF THE AMERICAN
WELDING SOCIETY. ALL WELDING SHALL BE DONE BY A CERTIFIED WELDER.
3. FOR MISCELLANEOUS STEEL NOT SPECIFICALLY DETAILED ON STRUCTURAL DRAWINGS, REFER TO ARCHITECTURAL
DRAWINGS.
4. CONNECTIONS:
MINIMUM CONNECTION ANGLE THICKNESS SHALL BE 5/16". MINIMUM SHEAR PLATE IS 3/8”.
CONNECTIONS SHALL BE MADE USING 3/4" DIAMETER ASTM A325 BOLTS (SNUG TIGHT OR SLIP CRITICAL) OR WELDS, UNLESS NOTED OTHERWISE. IF TENSION CONTROL BOLTS ARE USED, CONNECTIONS SHALL BE DESIGNED
FOR SLIP CRITICAL BOLT ALLOWABLE LOAD VALUES USING CLASS A FAYING SURFACE.
USE LARGER OF 1/4" FILLET WELDS OR MINIMUM SIZE PER AISC REQUIREMENTS WHERE NO WELD SIZE IS SHOWN
ON DRAWINGS.
WELDS IN EXCESS OF 24" IN LENGTH SHALL BE 3" STITCH WELDS AT 8" ON CENTERS, UNLESS SPECIFICALLY
SHOWN ON DRAWINGS TO BE CONTINUOUS.
5. NO WELDING OR FINAL BOLTING…