This solicitation is for the rehabilitation of Outlet Bridge and resurfacing of East Basin Drive located in the District of Columbia. The project consists of asphalt pavement milling, concrete removal and repair, PCC pavement, sidewalks, curbs, accessibility ramps, seawall repair, PCC overlay, cleaning and resealing joints, painting structural steel, repainting stone masonry, placing riprap and other miscellaneous work. Bids from certified Small Business Concerns only will be accepted, with bids expected to range from $1 million to $5 million. Bid documents will be issued on or about May 20, 2021, with the bid due date and location specified in Block 13a of the solicitation. The soliciting agency is the Department of Transportation Federal Highway Administration for this National Mall and Memorial Parks project. Annual Representations and Certifications must be completed online at SAM.gov, along with Vets-4212 at dol.gov/vets/vets4212.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
STRUCTURE SUMMARY STRUCTURE NO. 3400-031P
OUTLET BRIDGE INSPECTION DATE: 4/16/19
BRIDGE IDENTIFICATION AND DESCRIPTION
MAIN SPAN MATERIAL: ....... STEEL NO. OF MAIN SPANS:
MAIN SPAN TYPE: ............... STRINGER/MULTI-BEAM or GIRDER NO. OF APPR. SPANS:
# OF BEAMS, MAIN SPAN: .. N/A STRUCT. TOTAL LENGTH: .. 126.0 FT (38.4 M)
DECK TYPE: ......................... CONCRETE CAST-IN-PLACE MAX. SPAN LENGTH: .......... 42.0 FT (12.8 M)
WEARING SURFACE: .......... MODIFIED CONCRETE DECK WIDTH: ...................... 61.1 FT (18.6 M)
ABUT. FOUNDATIONS: ........ SPREAD FOOTING ON PILES CURB TO CURB WIDTH: ..... 40.0 FT (12.2 M)
PIER FOUNDATION(S): ........ SPREAD FOOTING ON PILES YEAR BUILT:
ABUTMENT / PIER MAT'L: ... CONCRETE YEAR RECONSTRUCTED: .. N/A
PROJ./PLAN REF. NO: ......... 32A1, 12(1) / NONE SKEW ANGLE: ..................... 0 °
NPS ROAD CLASS: .............. 1 - PRINCIPAL PARK ROAD FRACTURE CRITICAL: ........ NO
STRUCTURE HISTORY: ...... 1984-Redeck, paint, elastomeric brngs, conc patching. 1998-Membrane removed, wearing surf replaced, new appr slabs. 2007-Arch girder & substr repairs, ice fence, railings painted.
LOCATION
NATIONAL MALL AND MEMORIAL PARKS MILE POINT: ..................... 0.27 (KM PT 0.44)
STATE: ................................. DISTRICT OF COLUMBIA LOCATION: Adjacent to Structure No. 035T (Pedestrian Path over Washington Channel). FACILITY CARRIED: ............ EAST BASIN DRIVE
FEATURE INTERSECTED: .. WASHINGTON CHANNEL
STRUCTURE EVALUATION SUMMARY
This steel multi-beam bridge is in fair structural condition overall. The main problems include previously noted section loss on the steel beam bottom flanges and lower portions of the webs, and concrete deterioration with efflorescence and exposed rebar on the east fascia arch girder. The steel beams should be cleaned and spot painted to prevent further deterioration, and the exposed rebar on the east arch fascia girder should be cleaned and coated with an approved sealant.
Additional problems include moderate transverse cracking of the approach pavement and the bridge wearing surface, moderate delamination and spalling of the substructure concrete, and moderate cracking with efflorescence on the abutment backwalls.
It should be noted that the seawall adjacent to this structure and around the Tidal Basin continue to deteriorate, exhibiting extensive mortar loss throughout the masonry mortar joints, and numerous missing and displaced stones.
The seawall immediately to the southwest of structure is a safety hazard, the cap stone is undermined and could collapse under pedestrian load. The opening between the seawall and the west wingwalls has resulted in active erosion with significant soil loss from behind the seawall. Consideration should be given to a rehabilitating the seawall.
INSPECTION TEAM: Z. BAILEY, H. SALAD
CONDITION ASSESSMENT:
ZANE BAILEY, FIELD TEAM LEADER 703-404-6242
REPORT REVIEW:
MARCUS MILLER, P.E., BRIDGE INSPECTION ENGINEER 703-404-6252
REPORT APPROVAL: DATE: 8/30/19
JORGOMAI CEESAY, PH.D., P.E., BIP SUPERVISORY ENGINEER 703-404-6244
RECOMMENDATIONS AND ESTIMATED COSTS STRUCTURE NO. 3400-031P
A (Critical) - Structure is closed, in imminent danger of collapse, or presents a critical safety hazard.
B (Major) - Structure exhibits severe deterioration, presents a safety hazard, or is designated a high priority due to age and/or condition.
C (Moderate) - Structure is deficient, functionally obsolete, or requires substantial repairs to prevent a serious deficiency or unsafe condition.
D (Minor) - Structure is generally in good condition. Preventative maintenance may be required.
E (Special) - Structure is under construction or reconstruction.
C226 PRIORITY OF IMPROVEMENT
ITEM
NO.
ROUTINE MAINTENANCE QTY. UNIT UNIT
COST
PRELIM.
COST
ESTIMATE
60.9, 223.4 PLACE EROSION CONTROL MEASURES AT JUNCTION OF WEST SIDE WINGWALLS
AND SEAWALL TO PREVENT ADDITIONAL EROSION.
30 CY
58.2 CLEAN AND RESEAL DECK EXPANSION JOINTS. 116 LF
60.8 CLEAN AND RESEAL VERTICAL JOINTS. 150 LF
58.3, 222.4 CLEAN AND SEAL CRACKS IN APPROACH PAVEMENT AND IN BRIDGE WEARING
SURFACE ALONG JOINTS.
500 LF
59.2, 60.4 CLEAN EXPOSED REBAR ON EAST ARCH GIRDER AND SUBSTRUCTURE
CONCRETE AND COAT WITH APPROVED SEALANT.
25 SF
58.8 REPAIR DISCONNECTED UTILITY CONDUITS AND BROKEN INSULATION COVERS
ON DECK UNDERSIDE. REPAIR LEAKING WATER LINE AT SOUTH ABUTMENT.
1 LS
222.5 REPAIR UNDERMINING OF WEST APPROACH SIDEWALK AT NORTH END. 4 CF
PRELIM. MAINTENANCE TOTAL :
ITEM
NO.
REHABILITATION/RECONSTRUCTION
(TYPICALLY NEEDED WITHIN 5 YEARS)
QTY. UNIT
UNIT
COST
PRELIM. COST
ESTIMATES
REHAB. RECONSTR.
59.2,7 CLEAN AND PAINT STRUCTURAL STEEL. 1 LS
PRELIM. REHABILITATION/RECONSTRUCTION TOTAL :
PRELIMINARY ESTIMATE TOTAL* :
(*Includes typical contract costs for mobilization, traffic control, and design/construction engineering; but does not include detour bridges, work beyond the bridge limits, or work not listed above. Estimates are approximate and are for preliminary planning purposes only; they should not be used as a complete or final engineers estimate.)
REMARKS: This structure was under rehabilitation at time of inspection under Project PRA-NACC-12(1).
Cost estimates assume that the recommended actions will be combined with similar work being performed on other structures.
FIELD INSPECTION REPORT STRUCTURE NO. 3400-031P
G = GOOD (CODES 7 - 9) F = FAIR (CODES 5 - 6) P = POOR (CODES 0 - 4)
CONDITION RATING CODE EQUIVALENTS FOR SUB-ELEMENTS
SERIOUS CONDITION - loss of section, deterioration, spalling, or scour have seriously affected primary structural components. Local failures are possible.
Fatigue cracks in steel or shear cracks in concrete may be present.
CRITICAL CONDITION - advanced deterioration of primary structural elements. Fatigue cracks in steel or shear cracks in concrete may be present or scour may have removed substructure support. Unless closely monitored it may be necessary to close the structure until corrective action can be taken.
“IMMINENT” FAILURE CONDITION - major deterioration or sec ion loss present in critical structural components or obvious vertical or horizontal movement affecting structure stability. Structure is closed to traffic but corrective action may return structure to light service.
FAILED CONDITION - out of service; beyond corrective action.
CONDITION RATING CODES FOR ITEMS 58 - 62, 222, 223
NOT APPLICABLE
EXCELLENT CONDITION
VERY GOOD CONDITION - no problems noted.
GOOD CONDITION - some minor problems.
SATISFACTORY CONDITION - structural elements show some minor deterioration.
FAIR CONDITION - all primary structural elements are sound but may have minor section loss, cracking, spalling, or scour.
POOR CONDITION - advanced section loss, deterioration, spalling, or scour.
N
58. DECK ITEM REFERENCE AND REMARKS
OTHER
ALIGNMENT
DEFLECTION AND/OR VIBRATION
FASCIA(E)
DIAPHRAGMS AND BRACING
TRUSSES
FLOOR BEAMS AND STRINGERS
ARCH(ES) OR SLAB(S)
GIRDERS OR BEAMS
BEARING DEVICES
59. SUPERSTRUCTURE
OTHER
DEFLECTION AND/OR VIBRATION
UTILITIES
DRAINS AND DRAINAGE
PARAPETS AND/OR RAILINGS
CURBS, SIDEWALKS, AND MEDIAN
RIDEABILITY
WEARING SURFACE
EXPANSION JOINTS
DECK SLAB
ABUTMENTS
60. SUBSTRUCTURE
1.
10.
2.
3.
4.
5.
6.
7.
8.
9.
10.
9.
8.
7.
6.
5.
4.
3.
2.
1.
PAINT
11.
F F N N N G F F G
N G
F G F G G F
N
P
G
F
58.1 MINOR TRANSVERSE CRACKING WITH EFFLORESCENCE ON DECK
UNDERSIDE.
58.2 DECK EXPANSION JOINTS FILLED WITH DEBRIS THROUGHOUT;
COMPRESSION SEALS DEPRESSED UP TO 1-1/2". SEVERE
CRACKING OF COMPRESSION SEALS THROUGHOUT. NORTH
COMPRESSION SEAL AT WEST SIDEWALK TORN FOR 3' LENGTH.
COMPRESSION SEAL OVER SOUTH PIER HAS FAILED.
58.3 MINOR LONGITUDINAL, TRANSVERSE, AND RANDOM CRACKING OF
WEARING SURFACE THROUGHOUT; MODERATE NEAR JOINTS WITH
ASPHALT BREAKING UP (UP TO 3"W X 1"D). ASPHALT PATCHING IN
WEARING SURFACE IN SOUTHBOUND LANE OVER NORTH
ABUTMENT JOINT AND ALONG SOUTH PIER JOINT AT LOCATION OF
PREVIOUSLY MISSING JOINT HEADER.
58.5 MINOR CRACKING AND SPALLING OF CURBS AT ISOLATED
LOCATIONS.
MINOR TRANSVERSE AND DIAGONAL CRACKING OF WEST
SIDEWALK. MINOR SPALLING OF MORTAR MATERIAL WITH
ANCHORAGE PLATE EXPOSED IN WEST SIDEWALK IN NORTH SPAN
AT NORTH PIER JOINT AND IN EAST SIDEWALK IN SOUTH SPAN AT
SOUTH PIER JOINT.
MINOR MAP CRACKING OF CONCRETE MEDIAN; MINOR TO
MODERATE SPALLING AND DELAMINATION OF JOINT HEADER IN
CONCRETE MEDIAN ADJACENT TO DECK EXPANSION JOINTS WITH
ANCHORAGE BOLTS EXPOSED.
58.6 MINOR SURFACE RUST ON RAILINGS, PRIMARILY AT BASE PLATES.
MINOR TO MODERATE DETERIORATION OF PARAPET MASONRY
MORTAR JOINTS. MINOR DELAMINATION AND SPALLING OF EAST
PARAPET AT NORTH END. MINOR DELAMINATION OF PREVIOUS
CONCRETE PATCH REPAIR AT NORTH END OF EAST PARAPET;
SEVERAL LOOSE STONES IN THIS AREA. MINOR SPALL AT BASE OF
EAST PARAPET AT SOUTH END.
1. BREASTWALLS OR COLUMNS F
2. PILE BENTS N
3. CAPS AND/OR BEARING SEATS F
4. BACKWALLS AND/OR BULKHEADS F
5. FOUNDATIONS N
6. WINGWALLS F
7. WEEP HOLES N
8. EXPANSION JOINTS P
9. EROSION AND/OR SCOUR P
10. SETTLEMENT OR DEFLECTION F
11. SLOPE PROTECTION N
12. OTHER N
PIER(S)
F13. WALLS AND/OR COLUMNS
N14. PILE BENTS
F15. CAPS AND/OR BEARING SEATS
N16. FOUNDATIONS
G17. EROSION AND/OR SCOUR
G18. SETTLEMENT OR DEFLECTION
N19. OTHER
ITEM REFERENCE AND REMARKS
STREAM BED COMPOSITION : 9.
AVERAGE CLEAR OPENING 8.
NORMAL VELOCITY 7.
ADEQUACY OF OPENING 6.
OTHER 5.
WATERWAY OBSTRUCTIONS 4.
CHANNEL PROTECTION 3.
EROSION AND/OR SCOUR 2.
ALIGNMENT 1.
61. CHANNEL 7
G G N G
G(ICE FENCE)
MED
SUFF
18 FT.
SILT, SAND
222. APPROACHES 6
1. APPROACH SLABS
2. RELIEF JOINTS
3. APPROACH GUARDRAIL
4. SURFACING
5. EROSION
6. SETTLEMENT
7. SIGNS
8. ALIGNMENT
9. OTHER
N N N F F G N G N
223. RETAINING WALL 6
1. WALL
2. WEEP HOLES
3. FOUNDATION
4. EROSION AND/OR SCOUR
5. SETTLEMENT OR DEFLECTION
6. OTHER
F N N F G N
36. TRAFFIC AND SAFETY FEATURES
A. BRIDGE RAILINGS
B. TRANSITIONS
C. APPROACH GUARDRAILS
D. APPROACH GUARDRAIL ENDS
N N N
TRAFFIC SAFETY RATING CODES
0 - Does not meet standards or a safety feature is required and none is provided.
1 - Meets currently acceptable standards.
N - Not applicable or a safety feature is not required.
58.8 SEVERAL UTILITY CONDUITS MOUNTED ON UNDERSIDE OF
SUPERSTRUCTURE. CONDUITS DISCONNECTED AND INSULATION
COVERS BROKEN OR MISSING WITH WIRES EXPOSED AT SEVERAL
LOCATIONS. SEVERE DETERIORATION OF UTILITY CABLE TRAY ON
UNDERSIDE OF STRUCTURE IN BAY #10 AT ISOLATED LOCATIONS.
UTILITY HANGERS BROKEN AT ISOLATED LOCATIONS. LEAKING
WATER LINE AT SOUTH ABUTMENT.
59.1, 60.3 MODERATE DELAMINATION AND SPALLING OF BEAM #2 BEARING
SEAT AT SOUTH ABUTMENT.
59.2,7,8 MINOR SPOT RUSTING AND DETERIORATION OF PAINT ALONG
BOTTOM FLANGES AND WEBS THROUGHOUT STEEL BEAMS.
PREVIOUS NEGLIGIBLE SECTION LOSS NOTED ALONG BOTTOM
FLANGE AND BOTTOM OF WEB, MOST BEAMS; NO NEW SECTION
LOSS NOTED.
MODERATE RUSTING OF BOTTOM FLANGE AND LOWER PORTION
OF WEB OF BEAM #6 AT NORTH PIER, CENTER SPAN.
SEVERE EFFLORESCENCE FROM FASCIA ARCH GIRDER RING
STONES. MINOR RANDOM CRACKING WITH EFFLORESCENCE,
DELAMINATION, AND SPALLING OF EAST FASCIA ARCH GIRDER
INTERIOR SIDE AND UNDERSIDE WITH EXPOSED REBAR, ALL
SPANS. MINOR SPALLING WITH EXPOSED REBAR ON INSIDE FACE
OF EAST FASCIA ARCH GIRDER, CENTER SPAN AT MIDSPAN. SPALL
(20"W X UP TO 7"H X 5"D) ON SOUTH END OF WEST ARCH GIRDER AT
NORTH PIER. CORNER SPALL (8"W X 6"H X 4"D) ON WEST ARCH
GIRDER AT NORTH ABUTMENT.
MEDIUM-SIZED TREES GROWING AGAINST EAST ARCH FASCIA
GIRDER; SOUTH SPAN TREES HAVE BEEN CUT, BUT STARTING TO
REGROW.
60.1,13 ABUTMENT BREASTWALLS AND PIERS REHABILITATED IN 2007
(PARTIAL DEPTH CONCRETE REPAIRS); MINOR MAP CRACKING
WITH EFFLORESCENCE AT ISOLATED LOCATIONS. MINOR VERTICAL
AND MAP CRACKING OF COLUMNS AT ABUTMENTS AND PIERS.
MINOR HORIZONTAL CRACKING OF NORTH ABUTMENT
BREASTWALL, WEST HALF, WITH MOISTURE STAINS. MINOR TO
MODERATE SPALLING OF SOUTH ABUTMENT BREASTWALL COLUMN
BELOW BEAM #4. ACCUMULATION OF DEBRIS ALONG EAST SIDE OF
SOUTH ABUTMENT.
MINOR CRACKING OF MASONRY FASCIA STONES AND MORTAR AT
ENDS OF PIERS NOTED IN UNDERWATER INSPECTION PERFORMED
ON 8/2/13.
60.4 MODERATE HORIZONTAL AND VERTICAL CRACKING WITH
EFFLORESCENCE ON ABUTMENT BACKWALLS; MINOR TO
MODERATE SPALLING WITH EXPOSED REBAR ON NORTH
ABUTMENT BACKWALL IN BAYS #1, #3, AND #11. ISOLATED AREAS
OF HEAVY LEAKAGE ON BACKWALLS. MINOR TO MODERATE
SPALLING OF SOUTH ABUTMENT BACKWALL, EAST SIDE.
ADDITIONAL ITEM REFERENCE AND REMARKS
60.6,10, 223.5
SOUTHWEST AND NORTHWEST WINGWALLS REMAIN ROTATED AND DISPLACED FROM ABUTMENTS DUE TO SETTLEMENT (UP TO 5" OPENING ON TOP); WINGWALLS APPEAR TO HAVE STABILIZED, HOWEVER. MINOR
EFFLORESCENCE FROM WINGWALL MORTAR JOINTS THROUGHOUT.
60.8 JOINT FILLER MISSING AT TOP OF VERTICAL JOINTS. BACKFILL IS FALLING THROUGH SOUTHEAST VERTICAL
JOINT.
60.9, 223.4 SEAWALL HAS SEPARATED 6" FROM SOUTHWEST WINGWALL AND 9" FROM NORTHWEST WINGWALL; LARGE VOIDS ADJACENT TO WINGWALLS (9'-8"L X 4'-2"W X 3'D AT SOUTHWEST AND 5'L X 3'W X 5'D AT NORTHWEST) DUE TO EROSION OF FILL MATERIAL. CRACK ASSOCIATED WITH VOID AT SOUTHWEST SEAWALL INDICATES
DIFFERENTIAL MOVEMENT UP TO 1-1/4" VERTICALLY AND OUTWARD 1-1/2".
60.15 MODERATE SPALL (12"L X 10"H X 6"D) ON BEAM #5 BEARING SEAT AT SOUTH PIER, WEST SIDE. MINOR SPALL ON
BEAM #2 BEARING SEAT AT NORTH PIER, WEST SIDE.
60.19 MODERATE DETERIORATION AND ADHESION FAILURE OF SEALANT MATERIAL BETWEEN ICEBREAKERS AND
FASCIAE NOTED IN 2007 INSPECTION; UNABLE TO VERIFY DUE TO HIGH WATER.
61.2 MODERATE TO SEVERE EROSION (30'L X 15'W X 2'D) BEHIND SEAWALL ADJACENT TO SOUTHWEST WINGWALL.
EROSION AND SINKHOLE (20'L X 10'W X AVERAGE OF 1'D) IN NORTHWEST EMBANKMENT. WATER UP TO 29" DEEP
IN 18" DIAMETER HOLE ADJACENT TO NORTHWEST WINGWALL.
61.2 SEE BRIDGE FILE FOR SCOUR EVALUATION.
61.5 ICE FENCE RECONSTRUCTED IN 2007. PREVIOUSLY NOTED LOOSE BOLTS ON TIMBER ICE FENCE (THIRD
CONNECTION) IN SPAN #1 HAVE BEEN REPLACED/TIGHTENED.
222.4 MINOR TO MODERATE TRANSVERSE CRACKING AND BREAKING UP (UP TO 3"W) OF APPROACH PAVEMENT OVER
ABUTMENTS AND OVER FREE END OF APPROACH SLABS.
222.5 UNDERMINING OF WEST SIDEWALK AT NORTH END OF PARAPET (12'L X UP TO 10"H X UP TO 6' BACK UNDER IN
AREAS).
223.1 SEVERE DETERIORATION OF SEAWALL MASONRY MORTAR JOINTS; NUMEROUS STONES MISSING.
STRUCTURE LOAD RATING STRUCTURE NO. 3400-031P
TRUCK TYPE
INVENTORY RATING (NORMAL TRAFFIC) OPERATING RATING (MAXIMUM LOAD)
TONS METRIC TONS TONS METRIC TONS
H 42 38 70 64
HS 56 51 93 84
TYPE 3 24 22 41 37
TYPE 3S2 38 34 65 59
TYPE 3-3 47 43 78 71
DESIGN LOADING: HS20 (MS18)
X CAPACITY MEETS OR EXCEEDS DESIGN LOAD
CAPACITY IS LESS THAN DESIGN LOAD
X ORIGINAL LOAD RATING CALCULATION APPLICABLE
ORIGINAL LOAD RATING CALCULATION REVISED
DATE OF LOAD RATING CALCULATION: 7/15
LOAD RATING CONTROLLED BY: GIRDER #3 MOMENT
REMARKS: SEE BRIDGE FILE FOR LOAD RATING CALCULATIONS.
STRUCTURE INVENTORY AND APPRAISAL STRUCTURE NO. 3400-031P
STRUCTURE IDENTIFICATION
(201) PARK: NATIONAL MALL AND MEMORIAL PARKS (1) STATE: ....................................... 113 - DISTRICT OF COLUMBIA
(202) STRUCTURE NAME: .......... OUTLET BRIDGE (2) STATE HWY. AGENCY DIST:
(203) STRUCTURE KIND: ............1 - BRIDGE (3) COUNTY CODE: ........................ 001 - DISTRICT OF COLUMBI
(204) STRUCTURE NUMBER: ..... 3400-031P (4) CITY/PLACE CODE:
(205) NPS REGION: .................... 2 - NATIONAL CAPITAL (5) INVENTORY ROUTE:
(206) ROUTE CODE NUMBER: ... 12 (6) FEATURES INTERSECTED:....... WASHINGTON CHANNEL
(207) ROAD SECTION NO: ..........031P (7) FACILITY CARRIED: .................. EAST BASIN DRIVE
(208) NPS ROAD CLASS: ............ 1 - PRINCIPAL PARK ROAD (8) STATE STRUCTURE NO: .......... 3400031P0000000
(209) WITHIN NPS BNDRY?: .......YES (9) LOCATION: ................................ Adjacent to Structure No.
(210) OPERATING UNIT: ............. PARK (10) INV. RTE. - MIN. VERT. CLR: .. 99.99 FT (99.99 M)
(211) PROJECT NO(S): ................32A1, 12(1) (11) MILE POINT: .............................0.27 (KM PT 0.44)
(212) DRAWING NUMBERS: ....... NONE (27) YEAR BUILT:
(21) MAINTAINED BY: ................. 66 - NATIONAL PARK SERVICE (106) YEAR RECONSTRUCTED: .... N/A
(22) OWNER: ............................... 66 - NATIONAL PARK SERVICE (20) TOLL: ........................................3 - FREE ROAD
(37) HISTORICAL DESIGNATION: .. 5 - NOT ELIGIBLE
STRUCTURE DESCRIPTION, FOUNDATION, AND DECK TYPE
(43A) MAIN STR. MATERIAL: ..
(43B) MAIN STR. TYPE:
(45) NO. OF MAIN SPANS:
(48) MAX. SPAN LENGTH:
(49) STRUCTURE LENGTH:
(216A) ABUTMENT #1 FDN:
(216B) ABUTMENT #2 FDN:
(217A) PREDOM. PIER FDN.: ..
(217B) SECOND. PIER FDN: ...
(107) DECK TYPE:
3 - STEEL
02 - STRINGER/MULTI-BEAM or GIRDER
42.0 FT (12.8 M)
126.0 FT (38.4 M)
3 - SPREAD FOOTING ON PILES
3 - SPREAD FOOTING ON PILES
3 - SPREAD FOOTING ON PILES
3 - SPREAD FOOTING ON PILES
1 - CONCRETE CAST-IN-PLACE
(44A) APPR. STR. MATERIAL: ........ 0 - OTHER
(44B) APPR. STR. TYPE: ................ 00 - OTHER
(46) NO. OF APPROACH SPANS: .. 0
(108) WEAR SURFACE/PROTECT SYSTEM:
A) TYPE WEARING SURFACE: .. 3 - MODIFIED CONCRETE
B) TYPE MEMBRANE: ................. 0 - NONE
C) TYPE PROTECTION: .............. 0 - NONE
(218) IS SALT USED?: ..................... YES
LOAD RATING AND POSTING
(31) DESIGN LOAD: ................. 5 - HS20 (MS18) (41) LOAD RESTRICTION: ......... A - OPEN, NO RESTRICTION
(66) INVENTORY RATING: ...... 56.0 TONS (50.8 METRIC TONS) (70) BRIDGE POSTING: .............. 5 - NO POSTING REQUIRED
(64) OPERATING RATING: ...... 93.0 TONS (84.4 METRIC TONS)
INSPECTION DATES
(90) INSPECTION DATE: 4/19 (91) FREQ. OF INSP: 24 MONTHS (92 / 93) CRITICAL FEATURE INSPECTION (CFI):
(219) ADD. STUDIES NEEDED: N - 0 - NONE (A) FRACTURE CRITICAL: ... NO
INSP. EVERY: MONTHS - LAST INSP. : (220) SPECIAL STUDY TYPE: 0 - NONE
(B) UNDERWATER: .............. YES
(221) SPECIAL STUDY DATE: INSP. EVERY: 60 MONTHS - LAST INSP. : 7/18
(C) SPECIAL INSPECTION: .. NO
INSP. EVERY: MONTHS - LAST INSP. :
STRUCTURE INVENTORY AND APPRAISAL STRUCTURE NO. 3400-031P
GEOMETRY, TRAFFIC, AND NAVIGATIONAL DATA
(16) LATITUDE: ............................. 38°52'55.70"
(17) LONGITUDE: ......................... 77°02'01.10"
(19) DETOUR LENGTH: ............... 1 MI (2 KM)
(28A) LANES ON STRUCT:
(28B) LANES UNDER STRUCT: ... 00
(42A) SERVICE ON: ..................... 5 - HIGHWAY-PEDESTRIAN
(42B) SERVICE UNDER: .............. 5 - WATERWAY
(29) AVG. DAILY TRAFFIC:
(30) YEAR OF ADT:
(114) FUTURE ADT:
(115) YEAR OF FUTURE ADT:
(101) PARALLEL STRUCTURE: ... N - NONE
(38) NAVIGATION CONTROL?: ... 0
(39) VERTICAL CLEARANCE: ...... 0.0 FT (0.0 M)
(40) HORIZ. CLEARANCE: ........... 0.0 FT (0.0 M)
(111) ABUT. OR PIER PROT:
LATERAL UNDERCLEARANCE:
(55) RIGHT: ....................... 0.0 FT (0.0 M)
(56) LEFT: ......................... 0.0 FT (0.0 M)
(51) CURB TO CURB WIDTH:
(52) DECK WIDTH:
(32) APPR. ROADWAY WIDTH:
(213) APPR. PAVEMENT WIDTH:
LEFT SHOULDER:
RIGHT SHOULDER:
(33) BRIDGE MEDIAN:
(34) SKEW ANGLE:
(35) DECK FLARE?:
(47) TOTAL HORIZ. CLEARANCE:
(50) SIDEWALKS:
LEFT :
RIGHT :
(214) BRIDGE RAIL TYPE:
RAIL CONFIGURATION:
MATERIAL:
DESIGN TYPE:
(215) BRIDGE RAIL HEIGHT:
(53) MIN. VRT. CLEAR. OVER DECK:
(54) MIN. VRT. UNDERCLEARANCE:
40.0 FT (12.2 M)
61.1 FT (18.6 M)
42.0 FT (12.8 M)
42.0 FT (12.8 M)
0.0 FT (0.0 M)
0.0 FT (0.0 M)
2 - CLOSED MEDIAN (no barrie
0 °
NO
40.0 FT (12.2 M)
2.0 FT (0.6 M)
14.1 FT (4.3 M)
2 - MOUNTED ON PARAPET
9 - OTHER
1 - CONTINUOUS RAIL
3.67 FT (1.12 M)
99.99 FT (99.99 M)
0.00 FT (0.00 M)
CONDITION AND APPRAISAL DATA, PROPOSED IMPROVEMENTS, AND COST
(58) DECK:
(59) SUPERSTRUCTURE:
(60) SUBSTRUCTURE:
(61) CHANNEL:
(62) CULVERT: ...........................N
(222) APPROACHES:
(223) RETAINING WALL:
(36) TRAFFIC SAFETY FEAT: ... 1NNN
(75A) TYPE OF WORK:
(75B) WORK DONE BY:
(76) IMPROVEMENT LENGTH: ..
(67) STRUCTURAL EVALUATION:
(68) DECK GEOMETRY:
(69) UNDERCLEARANCES:
(71) WATERWAY ADEQUACY:
(72) APPROACH ALIGNMENT:
(113) SCOUR CRITICAL:
(225) PURPOSE OF IMPROVEMENT:
(226) PRIORITY OF IMPROVEMENT:
(227) MAINTENANCE COST:
(228) REHAB./RECONSTR. COST: ...
(229) CONSTRUCTION COST:
N
5 - Stable; scour within limits of
2 - REHAB/RECONSTRUCTION
C - MODERATE
ADDITIONAL INFORMATION
(230) STRUCTURE HISTORY:
1984-Redeck, paint, elastomeric brngs, conc patching. 1998-Membrane removed, wearing surf replaced, new appr slabs. 2007-Arch girder & substr repairs, ice fence, railings painted.
(231) ADDITIONAL CONSIDERATIONS:
KEY FROM NPS NEEDED TO OPEN FENCE GATE FOR BOAT ACCESS. BOAT ACCESS LIMITED TO OUTGOING TIDE (HIGH TO LOW)
DUE TO TIDE GATES AT ADJACENT STRUCTURE #3400-035T.
(330) ADDITIONAL CONFIG. INFO.:
APPENDIX STRUCTURE NO. 3400-031P
PHOTOGRAPHS STRUCTURE NO. 3400-031P
PHOTO #1 - LOOKING NORTH TOWARD MAINE AVENUE
PHOTO #2 - GENERAL TOPSIDE VIEW LOOKING NORTH
PHOTO #3 - TYPICAL TRANSVERSE CRACKING OF WEARING SURFACE
ALONG NORTHBOUND LANE NEAR NORTH END
PHOTO #4 - TYPICAL ASPHALT PATCH AT APPROACH PAVEMENT,
SOUTH APPROACH SHOWN
PHOTO #5 - MAP CRACKING OF WEARING
SURFACE AT SOUTH END
PHOTO #6 - TYPICAL DEBRIS ACCUMULATION
IN EXPANSION JOINTS OVER PIERS, SOUTH
PIER SHOWN
PHOTO #7 - TYPICAL JOINT OVER ABUTMENT,
NORTH END SHOWN
PHOTO #8 - SPALLING OF JOINT HEADER IN
CONCRETE MEDIAN ADJACENT TO DECK
EXPANSION JOINTS WITH ANCHORAGE BOLTS
EXPOSED; SOUTH PIER SHOWN
PHOTO #9 - TYPICAL DETERIORATION OF PARAPET MASONRY MORTAR
JOINTS; NORTHEAST CORNER SHOWN
PHOTO #10 - DELAMINATION ON EAST PARAPET NEAR NORTH END
PHOTO #11 - MISSING TOP RAIL RETURN AT
NORTHWEST CORNER OF STRUCTURE
PHOTO #12 - TYPICAL GAP BETWEEN BRIDGE
PARAPET AND APPROACH PARAPET;
NORTHWEST CORNER SHOWN
PHOTO #13 - TYPICAL JOINT FILLER MATERIAL
MISSING AT VERTICAL JOINTS, SOUTHEAST
VERTICAL JOINT SHOWN
PHOTO #14 - SPALL WITH DELAMINATION OF
EAST PARAPET
PHOTO #15 - DIFFERENTIAL SETTLEMENT OF APPROACH AT WEST
SIDEWALK NEAR SOUTH END
PHOTO #16 - UNDERMINING OF WEST SIDEWALK AT NORTH END OF
PARAPET
PHOTO #17 - 15" DEEP SINK HOLE AT SOUTHEAST CORNER
PHOTO #18 - GENERAL UNDERSIDE VIEW OF CENTER SPAN LOOKING
TOWARD BASIN; NOTE CRACKING OF UNDERSIDE OF ARCH
PHOTO #19 - TYPICAL TRANSVERSE CRACKING WITH
EFFLORESCENCE ON DECK UNDERSIDE, BAY #3, SOUTH SPAN SHOWN
PHOTO #20 - VIEW OF NEW UTILITY CONDUIT AND HANGERS RUNNING
THROUGH IN SPANS, SPAN #3 SHOWN
PHOTO #21 - TYPICAL RUSTING AND PAINT FAILURE OF GIRDERS
ALONG CENTERLINE OF STRUCTURE, SOUTH SPAN SHOWN
PHOTO #22 - DETERIORATION AND SPALLING OF CONCRETE AND
STAY-IN-PLACE FORM AT WEST SIDE IN CENTER SPAN
PHOTO #23 - TYPICAL EFFLORESCENCE FROM FASCIA ARCH GIRDER
RING STONES; EAST FASCIA GIRDER IN SOUTH SPAN SHOWN
PHOTO #24 - TYPICAL DELAMINATION, RANDOM CRACKING WITH
EFFLORESCENCE OF FACIA ARCH INTERIOR, EAST ARCH, SOUTH SPAN
SHOWN
PHOTO #25 - GENERAL VIEW OF NORTH ABUTMENT
PHOTO #26 - SPALLING WITH EXPOSED REBAR ON NORTH ABUTMENT
BACKWALL EAST SIDE OF BAY #1
PHOTO #27 - TYPICAL DELAMINATION AND CRACKING WITH
EFFLORESCENCE OF ARCH UNDERSIDE, EAST ARCH IN NORTH SPAN
SHOWN
PHOTO #28 - LEAKING SEWER LINE AT EAST SIDE OF NORTH SPAN
PHOTO #29 - SPALLING AND DELAMINATION OF EAST FACE OF WEST
COLUMN IN NORTH PIER
PHOTO #30 - GENERAL VIEW OF NORTH FACE OF NORTH PIER
PHOTO #31 - VERTICAL CRACK WITH EFFLORESCENCE ON NORTH
FACE OF NORTH PIER AT EAST END
PHOTO #32 - GENERAL VIEW OF SOUTH ABUTMENT
PHOTO #33 - SPALLING OF COLUMNS AT SOUTH ABUTMENT
PHOTO #34 - TYPICAL DETERIORATION OF BEARING SEAT AREA OVER
ABUTMENTS, BEARING #4 AT SOUTH ABUTMENT SHOWN
PHOTO #35 - SPALL AND DETERIORATION OF CONCRETE COLUMN AT
EAST END OF SOUTH ABUTMENT
PHOTO #36 - CLOSE UP OF DETERIORATION OF BEARING SEAT AREA
AT EAST END OF SOUTH ABUTMENT
PHOTO #37 - ACCUMULATION OF DEBRIS ALONG EAST SIDE OF SOUTH
ABUTMENT
PHOTO #38 - CRACKING AND STAINING ON SOUTH PIER COLUMNS,
SOUTH FACE NEAR WEST END
PHOTO #39 - CRACKING WITH
EFFLORESCENCE AND DETERIORATION OF
COLUMNS ON SOUTH PIER, BENTS #4 - #7,
SOUTH SIDE SHOWN
PHOTO #40 - SPALLING AND DELAMINATION
WITH EFFLORESCENCE UNDERNEATH BEAM
IN SOUTH PIER BENT #4
PHOTO #41 - CLOSE-UP OF SOUTH PIER, BENT #4
PHOTO #42 - VERTICAL CRACKING THROUGH MASONRY STONES OF
SOUTH PIER, SOUTHEAST FACE SHOWN
PHOTO #43 - EROSION BEHIND SOUTHWEST SEAWALL ADJACENT TO
WINGWALL; NOTE SEPARATION OF SEAWALL FROM WINGWALL
PHOTO #44 - EROSION OF EMBANKMENT BEHIND SEAWALL AT
NORTHWEST SIDE OF STRUCTURE
PHOTO #45 - CLOSE-UP VIEW OF EROSION OF EMBANKMENT BEHIND
SEAWALL AT NORTHWEST END
PHOTO #46 - EROSION AND SINKHOLE IN NORTHWEST EMBANKMENT
AT SEAWALL; NOTE SEPARATION OF SEAWALL FROM WINGWALL
PHOTO #47 - LOSS OF MASONRY STONE FOR SOUTHWEST SEAWALL
PHOTO #48 - GENERAL VIEW OF ICE FENCE, CENTER SPAN
PHOTO #49 - LOOKING WEST INTO TIDAL BASIN THROUGH
STRUCTURE, CENTER SPAN
PHOTO #50 - LOOKING EAST AT STRUCTURE NO. 3400-035T THROUGH
STRUCTURE, CENTER SPAN