BOOK 2.pdf
PDF 2 MB Posted
- Attached to
- N059--512-22-714 EHRM NextGen Wi-Fi AP Completion Federal contract opportunity
- Solicitation number
- 36C24525B0004
About this file
This file contains technical specifications for door, glazing, finish and window-related requirements as part of Book 2 for EHRM Infrastructure Upgrades at Loch Raven VA Medical Center in Baltimore, MD.
The specifications detail requirements for hollow metal doors and frames, interior wood doors, integrated door assemblies, access doors/frames, aluminum entrances/storefronts, aluminum windows, glazing, acoustical ceilings, resilient flooring, wall/door protection, window shades, and related finishes and accessories. Key requirements include fire-rated door assemblies, blast-resistant glazing, accessibility compliance, sustainable materials, quality assurance testing, and coordination with security/access control systems. The specifications mandate specific performance criteria for items like sound transmission class ratings, thermal properties, and durability standards. Installation requirements, warranty terms, and finish schedules are provided. Products must meet applicable building codes and VA design standards, with detailed requirements for materials, fabrication, hardware integration and installation procedures.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C24525B0004 0001_1.docx | DOCX document | |
| Image 7.jpg | JPG image | |
| Image 6.jpg | JPG image | |
| Image 5.jpg | JPG image | |
| BOOK 4 Rev2.pdf | ||
| BOOK 1.pdf | ||
| BOOK 3.pdf | ||
| 03-01 Loch Raven NextGen WIFI - List of AP Locations .xlsx | XLSX spreadsheet | |
| 36C24525B0004_1.docx | DOCX document | |
| Image 9.jpg | JPG image | |
| Image 8.jpg | JPG image | |
| Image 4.jpg | JPG image | |
| 03-02 Loch Raven NextGen WIFI Bldg 1_4 AP Locations - Drawing.pdf |
Show all 13
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
BOOK TWO OF FOUR
Openings, Finishes, Specialties, Furnishings
SPECIFICATION
PROJECT TITLE: EHRM Infrastructure Upgrades Loch Raven
PROJECT NUMBER: 512-22-710
LOCATION: Loch Raven VA Medical Center
3901 Loch Raven Blvd.
Baltimore, MD 21218
PHASE: Issue for Bid
DATE: August 30, 2024
512-22-710 - EHRM Infrastructure Upgrades Date: 8/30/2024
Loch Raven VA Medical Center Issue for Bid
3901 Loch Raven Blvd. Baltimore MD 21218 01-01-21
08 11 13 - 1
SECTION 08 11 13
HOLLOW METAL DOORS AND FRAMES
PART 1 - GENERAL
1.1 SUMMARY
A. Section Includes:
1. Hollow metal doors and transom panels hung in hollow metal frames at interior and exterior locations.
2. Hollow metal door frames for wood doors at interior locations.
3. Glazed openings and louvers in hollow metal doors.
1.2 RELATED WORK
A. Section 05 50 00, METAL FABRICATIONS: Frames fabricated of structural steel.
B. Section 08 41 13, ALUMINUM-FRAMED ENTRANCES AND STOREFRONTS: Aluminum frames entrance work.
C. Section 08 71 00, DOOR HARDWARE: Door Hardware:
D. Section 08 80 00, GLAZING: Glazing.
E. Card Readers and Biometric Devices: Section 28 13 00, PHYSICAL ACCESS
CONTROL SYSTEM.
F. Intrusion Alarm: Section 28 16 00, INTRUSION DETECTION SYSTEM.
G. Security Monitors: Section 28 23 00, VIDEO SURVEILLANCE.
1.3 APPLICABLE PUBLICATIONS
A. Comply with references to extent specified in this section.
B. American National Standard Institute (ANSI):
A250.8-2014 ............Standard Steel Doors and Frames
C. ASTM International (ASTM):
A240/A240M-15b .........Chromium and Chromium-Nickel Stainless Steel
Plate, Sheet, and Strip for Pressure Vessels and for General Applications
A653/A653M-15 ..........Steel Sheet, Zinc-Coated (Galvanized) or
Zinc-Iron Alloy-Coated (Galvannealed) by the
Hot-Dip
A1008/A1008M-15 ........Steel, Sheet, Cold-Rolled, Carbon, Structural, High Strength Low Alloy and High Strength Low
Alloy with Improved Formability, Solution
Hardened, and Bake Hardenable
B209-14 ................Aluminum and Aluminum-Alloy Sheet and Plate
3901 Loch Raven Blvd. Baltimore MD 21218 01-01-21
08 11 13 - 2
B209M-14 ...............Aluminum and Aluminum-Alloy Sheet and Plate
(Metric)
B221-14 ................Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes
B221M-13 ...............Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes (Metric)
D3656/D3656M-13 ........Insect Screening and Louver Cloth Woven from
Vinyl Coated Glass Yarns
E90-09 .................Laboratory Measurement of Airborne Sound
Transmission Loss of Building Partitions and
Elements
D. Federal Specifications (Fed. Spec.):
L-S-125B ...............Screening, Insect, Nonmetallic
E. Master Painters Institute (MPI):
No. 18 .................Primer, Zinc Rich, Organic
F. National Association of Architectural Metal Manufacturers (NAAMM):
AMP 500-06 .............Metal Finishes Manual
G. National Fire Protection Association (NFPA):
80-16 ..................Fire Doors and Other Opening Protectives
H. UL LLC (UL):
10C-09 .................Positive Pressure Fire Tests of Door Assemblies
1784-15 ................Air Leakage Tests of Door Assemblies and Other
Opening Protectives
I. Department of Veterans Affairs
VA Physical Security and Resiliency Design Manual October 1, 2020
1.4 SUBMITTALS
A. Submittal Procedures: Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES.
B. Submittal Drawings:
1. Show size, configuration, and fabrication and installation details.
C. Manufacturer's Literature and Data:
1. Description of each product.
2. Include schedule showing each door and frame requirements fire label for openings.
3. Installation instructions.
D. Sustainable Construction Submittals:
3901 Loch Raven Blvd. Baltimore MD 21218 01-01-21
08 11 13 - 3
1. Recycled Content: Identify post-consumer and pre-consumer recycled content percentage by weight.
E. Test reports: Certify products comply with specifications.
1. Sound rated door.
F. Qualifications: Substantiate qualifications comply with specifications.
1. Manufacturer with project experience list .
G. Blast Design Calculations.
1. Submit calculations for review and approval prepared by qualified blast consultant, with a minimum of 5 years of experience in design of blast resistant window systems, verifying door assembly including anchors comply with specified blast resistance performance. The magnitudes of the design threats W1, W2 and GP1, GP2 are defined in the Physical Security and Resiliency Design Standards Data
Definitions which is a document separate from the referenced VA
Security and Resiliency Design Manual. The Physical Security and
Resiliency Design Standards Data Definitions are provided on a need-to-know basis by the structural blast specialist performing the blast design on VA projects. It is the responsibility of the delegated engineer responsible for the design of blast resistant doors to request and obtain the Physical Security and Resiliency
Design Data Standard Data Definitions from the VA Office of
Construction and Facilities Management (CFM). Any associated delays or increased costs due to failure to obtain this information will be borne by the contractor.
1.5 QUALITY ASSURANCE
A. Manufacturer Qualifications:
1. Regularly manufactures specified products.
2. Manufactured specified products with satisfactory service on five similar installations for minimum five years.
a. Project Experience List: Provide contact names and addresses for completed projects.
1.6 DELIVERY
A. Fasten temporary steel spreaders across the bottom of each door frame before shipment.
B. Deliver products in manufacturer's original sealed packaging.
C. Mark packaging, legibly. Indicate manufacturer's name or brand, type, production run number, and manufacture date.
3901 Loch Raven Blvd. Baltimore MD 21218 01-01-21
08 11 13 - 4
D. Before installation, return or dispose of products within distorted, damaged, or opened packaging.
1.7 STORAGE AND HANDLING
A. Store products indoors in dry, weathertight conditioned facility.
B. Protect products from damage during handling and construction operations.
1.8 WARRANTY
A. Construction Warranty: FAR clause 52.246-21, "Warranty of
Construction."
PART 2 - PRODUCTS
2.1 SYSTEM PERFORMANCE
A. Design hollow metal doors and frames complying with specified performance:
1. Fire Doors and Frames: UL 10C; NFPA 80 labeled.
a. Fire Ratings: See drawings.
2. Stair Doors: Temperature rise rated fire doors.
3. Smoke Control Doors and Frames: UL 1784; NFPA 80 labeled, maximum
0.15424 cubic meter/second/square meter (3.0 cubic feet/minute/square foot) at 24.9 Pa (0.10 inches water gauge) pressure differential.
4. Sound Rated Doors and Frames: Minimum 45 sound transmission class
(STC) when tested according to ASTM E90.
5. Thermal Transmittance: U-value .45maximum at exterior doors .
6. Blast Resistant Doors: Door, Frame and Anchorage:
a. Standoff Distance: 25 feet (Life Safety Protected
b. Design Threat W1 at the standoff distance not to exceed pressure and impulse associated with GP1 threat for Life Safety Protected buildings
c. Frame Rotation not to exceed L/20 (Life Safety Protectedwhile experiencing design level pressure and impulse.
d. Glazing: Glazing shall meet the blast requirements shown in
Specification 08 80 00.
e. Minimum gauge of metal used on blast resistant doors shall be 14 gauge.
3901 Loch Raven Blvd. Baltimore MD 21218 01-01-21
08 11 13 - 5
2.2 MATERIALS
A. Stainless Steel: ASTM A240/A240M; Type 304 .
B. Sheet Steel: ASTM A1008/A1008M, cold-rolled.
C. Galvanized Sheet Steel: ASTM A653.
D. Insect Screening: ASTM D3656/D3656M, 18 by 18 aluminum wire mesh.
E. Aluminum Sheet: ASTM B209M (ASTM B209).
F. Aluminum Extrusions: ASTM B221M (ASTM B221).
2.3 PRODUCTS - GENERAL
A. Basis of Design: Section 09 06 00, SCHEDULE FOR FINISHES.
B. Provide hollow metal doors and frames from one manufacturer.
C. Sustainable Construction Requirements:
1. Steel Recycled Content: 30 percent total recycled content, minimum.
2. Stainless Steel Recycled Content: 70 percent total recycled content, minimum.
3. Aluminum Recycled Content: 50 percent total recycled content, minimum.
2.4 HOLLOW METAL DOORS
A. Hollow Metal Doors: ANSI A250.8; 44 mm (1-3/4 inches) thick. See drawings for sizes and designs.
1. Interior Doors: Level 1 and Physical Performance Level C, standard duty; Model 2, seamless at adminstative and maintenance locations .
B. Door Faces:
1. Interior Doors: Sheet steel Z180 or ZF180 (G60 or A60) coating .
2. Exterior Doors: Galvanized sheet steel minimum Z120 or ZF120 (G40 or
A40) Z180 or ZF180 (G60 or A60)
C. Door Cores:
1. Interior Doors: Kraft paper honeycomb
3901 Loch Raven Blvd. Baltimore MD 21218 01-01-21
08 11 13 - 6
2. Exterior Doors: Polystyrene, or polyurethane .
3. Fire Doors: Manufacturer's standard complying with specified fire rating performance.
2.5 HOLLOW METAL FRAMES
A. Hollow Metal Frames: ANSI A250.8; face welded .
1. Interior Frames:
a. Level 1 Hollow Metal Doors: 1.0 mm (0.042 inch) thick.
b. Level 3 Hollow Metal Doors: 1.3 mm (0.053 inch) thick.
c. Level 1 Hollow Metal Doors: 1.0 mm (0.042 inch) thick.
d. Wood Doors: 1.3 mm (0.053 inch) thick.
2. Interior Borrowed Light Frames: 1.3 mm (0.051 inch) thick.
a. Exterior Frames:
1) Level 3Hollow Metal Doors: 1.3 mm (0.053 inch) thick.
2) Level 4 Hollow Metal Doors: 1.7 mm (0.067 inch) thick.
B. Frame Materials:
1. Interior Frames: Sheet steel
2. Exterior Frames: Galvanized sheet steel minimum (G60 or A60) coating .
2.6 LOUVERS
A. If louvers are provided in blast resistant doors both the louver and the door must meet the blast resistance requirements noted in this specification.
B. Louver Style: Sight-proof lightproof permitting free ventilation.
1. Provide insect screen and wire guards at exterior doors.
C. Louver Construction: Sheet metal matching door faces.
1. Interior Door Louvers: 0.8 mm (0.032 inch) thick.
2. Exterior Door Louvers: 1.3 mm (0.053 inch) inch thick.
3. both directions.
3901 Loch Raven Blvd. Baltimore MD 21218 01-01-21
08 11 13 - 7
2.7 FABRICATION
A. Hardware Preparation: ANSI A250.8; for hardware specified in Section
08 71 00, DOOR HARDWARE.
B. Hollow Metal Door Fabrication:
1. Close top edge of exterior doors flush and seal to prevent water intrusion.
2. Fill spaces between vertical steel stiffeners with insulation.
C. Fire Doors:
1. Close top and vertical edges flush.
2. Apply steel astragal to active leaf at pair and double egress doors.
a. Exception: Where vertical rod exit devices are specified for both leaves swinging in same direction.
3. Fire // Door Clearances: NFPA 80.
D. Sound Rated Doors:
1. Seals: Integral spring type automatic door bottom seal.
2. Fabricate vision panel cutouts and frames to receive double glazing as shown on drawings.
2.8 FINISHES
A. Steel ANSI A250.8; shop primed.
B. Stainless Steel: NAAMM AMP 500; No. 4 polished finish.
1. Blend welds to match adjacent finish.
C. Finish exposed surfaces after fabrication.
D. Aluminum Anodized Finish: NAAMM AMP 500.
1. Clear Anodized Finish: AA-C22A41; Class I Architectural, 0.018 mm
(0.7 mil) thick.
2. Color Anodized Finish: AA-C22A42 or AA-C22A44; Class I
Architectural, 0.018 mm (0.7 mil) thick.
3. Clear Anodized Finish: AA-C22A31; Class II Architectural, 0.01 mm
(0.4 mil) thick.
4. Color Anodized Finish: AA-C22A32 or AA-C22A34; Class II
Architectural, 0.01 mm (0.4 mil) thick.
2.9 ACCESSORIES
A. Primers: ANSI A250.8.
B. Barrier Coating: ASTM D1187/D1187M.
3901 Loch Raven Blvd. Baltimore MD 21218 01-01-21
08 11 13 - 8
C. Welding Materials: AWS D1.1/D1.1M, type to suit application.
D. Clips Connecting Members and Sleeves: Match door faces.
E. Fasteners: stainless steel
1. Metal Framing: Steel drill screws.
2. Masonry and Concrete: Expansion bolts and power actuated drive pins .
F. Anchors: stainless steel .
G. Galvanizing Repair Paint: MPI No. 18.
H. Insulation: Unfaced mineral wool.
PART 3 - EXECUTION
3.1 PREPARATION
A. Examine and verify substrate suitability for product installation.
B. Protect existing construction and completed work from damage.
C. Apply barrier coating to metal surfaces in contact with cementitious materials to minimum 0.7 mm (30 mils) dry film thickness.
3.2 INSTALLATION - GENERAL
A. Install products according to manufacturer's instructions and approved submittal drawings .
1. When manufacturer's instructions deviate from specifications, submit proposed resolution for Contracting Officer's Representative consideration.
2. Install fire doors and frames according to NFPA 80.
3.3 FRAME INSTALLATION
A. Apply barrier coating to concealed surfaces of frames built into masonry.
B. Plumb, align, and brace frames until permanent anchors are set.
1. Use triangular bracing near each corner on both sides of frames with temporary wood spreaders at midpoint.
2. Use wood spreaders at bottom of frame when shipping spreader is removed.
3. Where construction permits concealment, leave shipping spreaders in place after installation, otherwise remove spreaders when frames are set and anchored.
4. Remove wood spreaders and braces when walls are built and jamb anchors are secured.
C. Floor Anchors:
1. Anchor frame jambs to floor with two expansion bolts.
3901 Loch Raven Blvd. Baltimore MD 21218 01-01-21
08 11 13 - 9
a. Lead Lined Frames: Use 9 mm (3/8 inch) diameter bolts.
b. Other Frames: Use 6 mm (1/4 inch) diameter bolts.
2. Power actuated drive pins are acceptable to secure frame anchors to concrete floors.
D. Jamb Anchors:
1. Masonry Walls:
a. Embed anchors in mortar.
b. Fill space between frame and masonry with grout or mortar as walls are built.
2. Metal Framed Walls: Secure anchors to sides of studs with two fasteners through anchor tabs.
3. Prepared Masonry and Concrete Openings:
a. Direct Securement: 6 mm (1/4 inch) diameter expansion bolts through spacers.
b. Subframe or Rough Buck Securement:
1) 6 mm (1/4 inch) diameter expansion bolts on 600 mm (24 inch) centers.
2) Power activated drive pins on 600 mm (24 inches) centers.
c. Secure two-piece frames to subframe or rough buck with machine screws on both faces.
E. Frames for Sound Rated Doors: Fill frames with insulation.
F. Touch up damaged factory finishes.
1. Repair galvanized surfaces with galvanized repair paint.
2. Repair painted surfaces with touch up primer.
3.4 DOOR INSTALLATION
A. Install doors plumb and level.
B. Adjust doors for smooth operation.
C. Touch up damaged factory finishes.
1. Repair galvanized surfaces with galvanized repair paint.
2. Repair painted surfaces with touch up primer.
3.5 CLEANING
A. Clean exposed door and frame surfaces. Remove contaminants and stains.
3.6 PROTECTION
A. Protect doors and frames from traffic and construction operations.
B. Remove protective materials immediately before acceptance.
C. Repair damage.
- - - E N D - - -
3901 Loch Raven Blvd. Baltimore MD 21218 95% Construction Documents 3900 Loch Raven Blvd, Baltimore MD 21218 01-01-21
08 14 00 - 1
SECTION 08 14 00
INTERIOR WOOD DOORS
PART 1 - GENERAL
1.1 SUMMARY
A. Section Includes:
1. Interior flush wood doors transparent finish.
2. Interior stile and rail wood doors transparent finish.
1.2 RELATED WORK
A. Section 01 81 13, SUSTAINABLE CONSTRUCTION REQUIREMENTS: Paints and
Coatings and Composite Wood and Agrifiber VOC Limits.
B. Section 08 11 13, HOLLOW METAL DOORS AND FRAMES: Installation of Doors.
C. Section 08 71 00, DOOR HARDWARE: Installation of Door Hardware.
D. Section 09 06 00, SCHEDULE FOR FINISHES: Door Finish.
1.3 APPLICABLE PUBLICATIONS
A. Comply with references to extent specified in this section.
B. American National Standards Institute/Window and Door Manufacturers
Association (ANSI/WDMA):
1. I.S. 1A-13 - Architectural Wood Flush Doors.
2. I.S. 6A-13 - Interior Architectural Stile and Rails Doors.
C. ASTM International (ASTM):
1. E90-09(2016) - Laboratory Measurements of Airborne Sound
Transmission Loss of Building Partitions and Elements.
D. National Fire Protection Association (NFPA):
1. 80-16 - Fire Doors and Other Opening Protectives.
2. 252-12 - Fire Tests of Door Assemblies.
E. UL LLC (UL):
1. 10C-09 - Positive Pressure Fire Tests of Door Assemblies.
F. Window and Door Manufacturers Association (WDMA):
1. TM 7-14 - Cycle-Slam Test.
2. TM 8-14 - Hinge Loading Test.
3. TM 10-14 - Screw Holding Capacity.
1.4 SUBMITTALS
A. Submittal Procedures: Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES.
B. Submittal Drawings:
1. Show size, configuration, and fabrication and installation details.
3901 Loch Raven Blvd. Baltimore MD 21218 95% Construction Documents 3900 Loch Raven Blvd, Baltimore MD 21218 01-01-21
08 14 00 - 2
2. Include details of glazing
3. Indicate project specific requirements not included in
Manufacturer's Literature and Data submittal.
C. Manufacturer's Literature and Data:
1. Description of each product.
2. Fire rated doors showing conformance with NFPA 80 .
D. Samples:
1. Corner section of flush veneered door 300 mm (12 inches) square, showing details of construction, labeled to show grade and type number and conformance to specified standard.
2. Veneer sample 200 mm by 275 mm (8 inch by 11 inch) showing specified wood species sanded to receive a transparent finish. Factory finish veneer sample where the prefinished option is accepted.
E. Sustainable Construction Submittals:
1. Low Pollutant-Emitting Materials:
Show volatile organic compound types and quantities.
F. Test Reports: Indicate products comply with specifications.
1. Screw Holding Capacity Test.
2. Cycle-Slam Test.
3. Hinge-Loading Test.
G. Operation and Maintenance Data:
1. Care instructions for each exposed finish product.
1.5 QUALITY ASSURANCE
A. Manufacturer Qualifications:
1. Regularly and presently manufactures specified products.
2. Manufactures specified products with satisfactory service on five similar installations for minimum five years.
1.6 DELIVERY
A. Deliver products in manufacturer's original sealed packaging.
1. Minimum 0.15 mm (6 mil) polyethylene bags or cardboard packaging to remain unbroken during delivery and storage.
B. Mark packaging, legibly. Indicate manufacturer's name or brand, type, and manufacture date.
1. Identify door opening corresponding to Door Schedule.
3901 Loch Raven Blvd. Baltimore MD 21218 95% Construction Documents 3900 Loch Raven Blvd, Baltimore MD 21218 01-01-21
08 14 00 - 3
C. Before installation, return or dispose of products within distorted, damaged, or opened packaging. Retain packaging for door protection after installation.
1.7 STORAGE AND HANDLING
A. Store products indoors in dry, weathertight conditioned facility.
1. Store doors according to ANSI/WDMA I.S. 1A.
B. Protect products from damage during handling and construction operations.
1.8 FIELD CONDITIONS
A. Environment:
1. Product Temperature: Minimum 21 degrees C (70 degrees F) for minimum
48 hours before installation.
2. Work Area Ambient Temperature Range: 21 to 27 degrees C (70 to
80 degrees F) continuously, beginning 48 hours before installation.
3. Install products when building is permanently enclosed and when wet construction is completed, dried, and cured.
Comply with door manufacturer's instructions for relative humidity.
1.9 WARRANTY
A. Construction Warranty: FAR clause 52.246-21, "Warranty of
Construction."
B. Manufacturer's Warranty: Warrant interior factory finished flush stile and rail wood doors against material and manufacturing defects.
1. Warranty Period: Lifetime of original installation.
PART 2 - PRODUCTS
2.1 PRODUCTS - GENERAL
A. Basis of Design: Section 09 06 00, SCHEDULE FOR FINISHES.
B. Provide each product from one manufacturer.
C. Sustainable Construction Requirements:
1. Low Pollutant-Emitting Materials: Comply with VOC limits specified in Section 01 81 13, SUSTAINABLE CONSTRUCTION REQUIREMENTS for the following products:
2. Paints and coatings.
3. Composite wood and agrifiber.
3901 Loch Raven Blvd. Baltimore MD 21218 95% Construction Documents 3900 Loch Raven Blvd, Baltimore MD 21218 01-01-21
08 14 00 - 4
2.2 FLUSH WOOD DOORS
A. General:
1. ANSI/WDMA I.S. 1A, Extra Heavy Duty.
2. Adhesive: Type II.
3. Core: Structural composite lumber, except when mineral core is required for fire rating.
4. Thickness: 44 mm (1-3/4 inches) unless otherwise shown or specified.
B. Faces:
1. ANSI/WDMA I.S. 1A.
2. One species throughout project unless scheduled or otherwise shown.
3. Transparent Finished Faces: // Premium Grade. rotary cut, white maple white birch coordinate final selection with existing doors and COR
AA Grade face veneer.
4. Match face veneers for doors for uniform effect of color and grain at joints.
5. Door Edges: Same species as door face veneer, except maple is acceptable for stile face veneer on birch doors.
6. In existing buildings, where doors are required to have transparent finish, use wood species, grade, and assembly of face veneers to match adjacent existing doors.
7. Painted Finishes: Custom Grade, mill option close grained hardwood, premium or medium density overlay.
8. Factory sand doors for finishing.
C. Wood For Stops, Louvers, Muntins and Moldings For Flush Doors Required to Have Transparent Finish:
1. Solid wood of same species as face veneer, except maple is acceptable on birch doors.
2. Glazing:
a. On non-fire-rated doors, use applied wood stops nailed tightly on room side and attached on opposite side with flathead, countersunk wood screws, spaced approximately 125 mm (5 inches) on center.
3. Wood Louvers:
3901 Loch Raven Blvd. Baltimore MD 21218 95% Construction Documents 3900 Loch Raven Blvd, Baltimore MD 21218 01-01-21
08 14 00 - 5
a. Door manufacturer's standard product, fabricated of solid wood sections.
1) Wood Slats: minimum 5 mm (3/16 inch) thick.
2) Stiles routed out to receive slats.
3) Secure louvers in prepared cutouts with wood stops.
D. Stiles and Rails:
1. Composite material having screw withdrawal force greater than minimum performance level value when tested according to WDMA TM 10.
2. Provide adequate blocking for bottom of doors having mechanically operated door bottom seal meeting or exceeding performance duty level per WDMA TM 10 for horizontal door edge screw holding.
3. Rabbeted transom meeting rail edges match face veneers of doors.
E. Fire-Rated Wood Doors:
1. Fire Resistance Rating:
a. B Label: 1-1/2 hours.
b. C Label: 3/4 hour.
2. Provide 20-minute smoke-rated doors in smoke-rated barriers.
3. Labels:
a. Comply with NFPA 252, UL 10C, and labeled by qualified testing and inspection agency showing fire resistance rating.
1) Metal labels with raised or incised markings.
4. Performance Criteria for Stiles of Doors Utilizing Standard Mortise
Leaf Hinges:
a. Hinge Loading: WDMA TM 8. Average of 10 test samples for Extra
Heavy Duty doors.
b. Direct Screw Withdrawal: WDMA TM 10 for Extra Heavy Duty doors.
Average of 10 test samples using a steel, fully threaded #12 wood screw.
c. Cycle-Slam: 1,000,000 cycles with no loose hinge screws or other visible signs of failure when tested according to WDMA TM 7.
5. Hardware Reinforcement:
a. Provide fire rated doors with hardware reinforcement blocking.
b. Size of lock blocks as required to secure hardware specified.
c. Top, Bottom and Intermediate Rail Blocks: Minimum 125 mm
(5 inches) by full core width.
d. Reinforcement blocking in compliance with labeling requirements.
Mineral material similar to core is not acceptable.
3901 Loch Raven Blvd. Baltimore MD 21218 95% Construction Documents 3900 Loch Raven Blvd, Baltimore MD 21218 01-01-21
08 14 00 - 6
6. Other Core Components: Manufacturer's standard as allowed by labeling requirements.
7. Glazed Vision Panel Frame: Steel approved for use in labeled doors.
8. Astragal: Steel type for pairs of doors.
F. Sound Rated Doors:
1. Fabricated as specified for flush wood doors with additional construction requirements to comply with specified sound transmission class (STC).
2. STC Rating of door assembly in place when tested according to
ASTM E90 by independent acoustical testing laboratory minimum 35
a. Accessories:
1) Frame Gaskets and Automatic Door Bottom Seal: As specified in
Section 08 71 00, DOOR HARDWARE.
2.3 STILE AND RAIL WOOD DOORS
A. Doors: ANSI/WDMA I.S. 6A; Grade size and design shown on drawings.
B. Species: Ponderosa pine.
C. Door Panels:
1. Grain of face of panels parallel with longest dimensions of panel.
2. Flat panels: Veneered composite core, minimum 16 mm (5/8 inch) thick.
3. Raised panels: Unless otherwise shown, thickness of raised panels minimum the following:
a. For 35 mm (1-3/8 inch) and 44 mm (1-3/4 inch) thick doors: 28 mm
(1-1/8 inch) thick.
4. Where armor plate is required for paneled doors, provide panels with plywood fillers, glued in place, and finished.
D. Stops and Molds:
1. Solid sticking both sides, same material as stiles and rails, coped joints.
2. Glazed Vision Panel Frame: Applied wood stops nailed on interior side of door.
E. Louvers: Size as shown.
2.4 FABRICATION
A. Factory machine interior wood doors to receive hardware, bevels, undercuts, cutouts, accessories and fitting for frame.
1. Factory fit fire rated doors according to NFPA 80.
3901 Loch Raven Blvd. Baltimore MD 21218 95% Construction Documents 3900 Loch Raven Blvd, Baltimore MD 21218 01-01-21
08 14 00 - 7
B. Rout doors for hardware using templates and location heights specified in Section 08 71 00, DOOR HARDWARE.
C. Factory fit doors to frame, bevel lock edge of doors 3 mm (1/8 inch) for each 50 mm (2 inches) of door thickness
D. Clearances between Doors and Frames and Floors:
1. Fire Rated Doors: Comply with NFPA 80.
a. Doors with Automatic Bottom Seal: Maximum clearance 10 mm
(3/8 inch) at threshold.
b. Other Door Bottoms: Maximum 3 mm (1/8 inch) clearance at the jambs, heads, and meeting stiles, and a 19 mm (3/4 inch) clearance at bottom, except as otherwise specified.
2. Door Jambs, Heads, and Meeting Stiles: Maximum 3 mm (1/8 inch).
E. Provide cutouts for glazed and louver openings.
F. Finish surfaces, including both faces, top and bottom and edges of the doors smooth to touch.
G. Identify each door on top edge.
1. Mark with stamp, brand or other indelible mark, giving manufacturer’s name, door’s trade name, construction of door, date of manufacture and quality.
2. Mark door or provide separate certification including name of inspection organization.
3. Identify door manufacturing standard, including glue type.
4. Identify veneer and quality certification.
5. Identification of preservative treatment for stile and rail doors.
2.5 FINISHES
A. Factory Transparent Finish:
1. Factory finish flush wood doors.
a. ANSI/WDMA I.S. 1A Section F-3 Finish System Descriptions for
System 5, Conversion Varnish or System 7, Catalyzed Vinyl.
b. Use stain when required to produce finish specified in Section
09 06 00, SCHEDULE FOR FINISHES.
PART 3 - EXECUTION
3.1 PREPARATION
A. Examine and verify substrate suitability for product installation.
1. Verify door frames are properly anchored.
2. Verify door frames are plumb, square, in plane, and within tolerances for door installation.
3901 Loch Raven Blvd. Baltimore MD 21218 95% Construction Documents 3900 Loch Raven Blvd, Baltimore MD 21218 01-01-21
08 14 00 - 8
B. Protect existing construction and completed work from damage.
C. Install astragal on active leaf of pair of smoke doors and one leaf of double egress smoke doors.
3.2 INSTALLATION
A. Install products according to manufacturer's instructions and approved submittal drawings .
1. Install fire rated doors according to NFPA 80.
2. When manufacturer's instructions deviate from specifications, submit proposed resolution for Contracting Officer's Representative consideration.
3.3 PROTECTION
A. After installation, place shipping container over door and tape in place.
1. Do not apply tape to door faces and edges.
B. Provide protective covering over exposed hardware in addition to covering door.
C. Maintain covering in good condition until removal is directed by
Contracting Officer's Representative.
- - E N D - -
3901 Loch Raven Blvd. Baltimore MD 21218 01-01-21
08 17 10 - 1
SECTION 08 17 10
INTEGRATED DOOR ASSEMBLIES
PART 1 - GENERAL
1.1 SUMMARY
A. Section Includes:
1. Integrated door assemblies including metal door frame, door, and hardware, unless specified in another Section, installed at cross-corridor locations.
B. Smoke and draft control seals, unless specified in another Section.
1.2 RELATED WORK
A. Section 01 81 13, SUSTAINABLE CONSTRUCTION REQUIREMENTS: Non-Flooring
Adhesives and Sealants and Paints and Coatings VOC Limits.
B. Section 08 71 00, DOOR HARDWARE: Lock Cylinders.
C. Section 09 06 00, SCHEDULE FOR FINISHES: Door and Frame Color:.
D. DIVISION 26, ELECTRICAL: Electrical Power.
1.3 APPLICABLE PUBLICATIONS
A. Comply with references to extent specified in this section.
B. Builders Hardware Manufacturers Association (BHMA):
A156.3-14 ..............Exit Devices.
A156.26-06 .............Continuous Hinges.
A156.32-14 .............Integrated Door Opening Assemblies.
C. ASTM International (ASTM):
A1011/A1011M-18a .......Steel, Sheet and Strip, Hot-Rolled, Carbon, Structural, High-Strength Low-Alloy, High-Strength Low-Alloy with Improved
Formability, and Ultra-High Strength.
E2180-18 ...............Determining the Activity of Incorporated
Antimicrobial Agents in Polymeric or
Hydrophobic Materials.
D. Door and Hardware Institute (DHI):
1. Recommended Locations for Architectural Hardware for Standard Doors
& Frames (2004).
2. Recommended Locations for Builders' Hardware Custom Steel Doors &
Frames (1996).
E. National Fire Protection Association (NFPA):
105-16 .................Smoke Door Assemblies and Other Opening
Protectives.
3901 Loch Raven Blvd. Baltimore MD 21218 01-01-21
08 17 10 - 2
252-12 .................Fire Tests of Door Assemblies.
F. Steel Door Institute (SDI):
A250.3-11 ..............Test Procedure and Acceptance Criteria for
Factory Applied Finish Coatings for Steel Doors and Frames.
A250.8-14 ..............Specifications for Standard Steel Doors and
Frames.
A250.10-11 .............Test Procedure and Acceptance Criteria for
Prime Painted Steel Surfaces for Steel Doors and Frames.
G. UL LLC (UL):
10C-09 .................Positive Pressure Fire Tests of Door
Assemblies.
1784-15 ................Air Leakage Tests of Door Assemblies and Other
Opening Protectives.
1.4 PREINSTALLATION MEETINGS
A. Conduct preinstallation meeting at project site minimum 30 days before beginning Work of this section.
1. Required Participants:
a. Contracting Officer's Representative.
b. Architect/Engineer.
c. Contractor.
d. Installer.
e. Other installers responsible for adjacent and intersecting work, including electrical.
2. Meeting Agenda: Distribute agenda to participants minimum 3 days before meeting.
a. Installation schedule.
b. Installation sequence.
c. Preparatory work.
d. Protection before, during, and after installation.
e. Installation.
f. Transitions and connections to other work.
g. Other items affecting successful completion.
3. Document and distribute meeting minutes to participants to record decisions affecting installation.
3901 Loch Raven Blvd. Baltimore MD 21218 01-01-21
08 17 10 - 3
1.5 SUBMITTALS
A. Submittal Procedures: Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES.
B. Submittal Drawings:
1. Show size, configuration, and fabrication and installation details.
2. For each opening, list finish hardware items included in assembly, finish, degree of opening, and electrical rough-in requirements according to Door Schedule.
3. Submit templates to door and frame manufacturers to ensure proper size and location of hardware.
C. Manufacturer's Literature and Data:
1. Description of each product.
2. Installation instructions.
D. Sustainable Construction Submittals:
1. Recycled Content: Identify post-consumer and pre-consumer recycled content percentage by weight.
2. Low Pollutant-Emitting Materials:
a. Show volatile organic compound types and quantities.
E. Certificates: Indicate integrated door assemblies comply with specifications.
1. Show fire rated integrated door assembly is UL Listed for specified application.
F. Qualifications: Substantiate qualifications comply with specifications.
1. Installer.
G. Operation and Maintenance Data:
1. Care instructions for each exposed finish product.
2. Maintenance and adjustment instructions for integrated door assemblies.
1.6 QUALITY ASSURANCE
A. Installer Qualifications:
1. Regularly installs specified products.
2. Installed specified products with satisfactory service on five similar installations for minimum five years.
a. Provide contact names and addresses for completed projects when requested by Contracting Officer's Representative.
1.7 DELIVERY
A. Deliver products in manufacturer's original sealed packaging.
3901 Loch Raven Blvd. Baltimore MD 21218 01-01-21
08 17 10 - 4
B. Mark packaging, legibly. Indicate manufacturer's name.
C. Before installation, return or dispose of products within distorted, damaged, or opened packaging.
1.8 STORAGE AND HANDLING
A. Store products indoors in dry, weathertight facility.
B. Protect products from damage during handling and construction operations.
1.9 FIELD CONDITIONS
A. Field Measurements: Verify field conditions affecting integrated door assembly fabrication and installation. Show field measurements on
Submittal Drawings.
1. Coordinate field measurement and fabrication schedule to avoid delay.
2. Coordinate electrical work for electrified hardware installation.
1.10 WARRANTY
A. Construction Warranty: FAR clause 52.246-21, "Warranty of
Construction."
B. Manufacturer's Warranty: Warrant door closers and hinges against material and manufacturing defects.
1. Warranty Periods:
a. Door Closers: 10 years.
b. Steel Pinned Continuous Hinges: 10 years.
PART 2 - PRODUCTS
2.1 SYSTEM PERFORMANCE
A. Design integrated door assemblies complying with specified performance:
1. BHMA A156.32: Grade 1: 1,000,000 cycles.
B. Fire Rated Doors:
1. Fire Resistance Rating: As shown in Door Schedule.
2. Label: Comply with NFPA 252, UL 10C, and labeled by qualified testing and inspection agency showing fire resistance rating.
C. Smoke Rated Doors:
1. Smoke Resistance Rating: As shown in Door Schedule.
2. Label: Comply with NFPA 105, UL 1784, and labeled by qualified testing and inspection agency showing smoke resistance rating.
2.2 PRODUCTS - GENERAL
A. Basis of Design: Section 09 06 00, SCHEDULE FOR FINISHES.
3901 Loch Raven Blvd. Baltimore MD 21218 01-01-21
08 17 10 - 5
B. Provide each integrated door assembly from one manufacturer.
C. Sustainable Construction Requirements:
1. Steel Recycled Content: 30 percent total recycled content, minimum.
2. Low Pollutant-Emitting Materials: Comply with VOC limits specified in Section 01 81 13, SUSTAINABLE CONSTRUCTION REQUIREMENTS for the following products:
a. Non-flooring adhesives and sealants.
b. Paints and coatings.
2.3 INTEGRATED DOOR ASSEMBLY
A. Metal Doors: SDI A250.8; Level 2 and Physical Performance Level B, heavy duty; Model 2 seamless.
1. Face: ASTM A1011/A1011M; cold rolled steel, 1.0 mm (0.04 inches) thick, minimum.
2. Core: Kraft paper honeycomb or polystyrene.
3. Thickness: 44 mm (1-3/4 inch).
4. Reinforce door for hardware installation.
B. Metal Frames: SDI A250.8 Level 2.
1. Metal: ASTM A1011/A1011M; cold rolled steel, 1.3 mm (0.05 inches) thick, minimum.
2. Construction: Continuously welded.
3. Reinforce frame for hardware.
a. Continuous Hinges: 2.3 mm (0.09 inches) thick.
b. Other Hardware: Comply with SDI A250.8.
4. Frame Anchors: Provide adjustable type anchors coordinated with wall construction, minimum 4 per jamb.
C. Integrated Hardware:
1. Exit Device: BHMA A156.3; Grade 1, passage function, inset in door face, clean and unobtrusive in design.
a. Push Bar End Caps: Metal, plated satin nickel (BHMA 619) finish.
b. Exit Device Trim: Lever matching door hardware specified in
Section 08 71 00, DOOR HARDWARE.
2. Continuous Hinges: BHMA A156.26.
a. Plastic Laminate Clad Doors: Wrap-around style hinge guards and provide stainless steel wrap-around edge guards at strike edge of door.
3. Other Hardware: As scheduled in this section.
3901 Loch Raven Blvd. Baltimore MD 21218 01-01-21
08 17 10 - 6
2.4 FINISHES
A. Hardware Finish Symbols:
TABLE I – Hardware Finish Symbols
US BHMA 156.18 Description
USP 600 Primed for field painting
US15 619 Dull Nickel Plated
US26D 626/652 Satin Chrome Plated
US28 628 Satin Aluminum
US32 629 Bright Stainless
US32D 630 Satin Stainless
N/A 689 Aluminum Painted
B. Finish Requirements:
1. Door Faces: Factory Pre-Finished, SDI A250.3
2. Frames: Factory Pre-Finished, SDI A250.3 .
3. Door Hardware:
a. Continuous Hinges: BHMA 630.
b. Push Bar: BHMA 630 clad with BHMA 619 end caps.
c. Exit Device Trim: BHMA 630.
d. Push/Pull Trim: BHMA 626.
e. Door Closers: BHMA 689.
f. Miscellaneous: To match other finishes.
4. Anti-Microbial Coating: ASTM E2180; ionic silver coating.
5. Apply coating to hand-operated hardware including levers, pulls, push bars, push plates, and paddles.
PART 3 - EXECUTION
3.1 PREPARATION
A. Examine and verify substrate suitability for product installation.
B. Protect existing construction and completed work from damage.
3.2 INSTALLATION - INTEGRATED DOOR ASSEMBLIES
A. Install products according to manufacturer's instructions // and approved submittal drawings //.
B. Install door hardware at locations indicated in DHI Recommended
Locations for Architectural Hardware for Standard Steel Doors & Frames and DHI Recommended Locations for Builders' Hardware Custom Steel Doors
& Frames, unless otherwise indicated, or to comply with requirements of governing regulations, or if otherwise directed by Contracting
Officer's Representative.
3901 Loch Raven Blvd. Baltimore MD 21218 01-01-21
08 17 10 - 7
C. Install door hardware in compliance with manufacturers' instructions, and templates. Comply with specified degree of opening for doors with automatic operators and overhead door closers. Securely fasten hardware. Confirm operating parts move freely and smoothly without binding, sticking, and excessive clearance.
D. Coordinate installation and interface wiring with fire alarm and smoke detection systems. Provide auxiliary contacts, relays, and interface for fire alarm and security systems.
E. Remove or protect door hardware, before painting and finishing performed after integrated door assembly installation.
F. Adjust and check door assembly and each operating hardware item to ensure correct operation and function. Replace products which cannot be adjusted to operate as intended.
G. Final Adjustment: Perform final hardware check and adjustment maximum one month before building acceptance or partial building occupancy.
3.3 CLEANING
A. Clean exposed surfaces, including hardware. Do not use cleaners that will harm finishes.
3.4 PROTECTION
A. Protect integrated door assemblies from construction operations.
3.5 SCHEDULES
A. The following is a general listing of the Integrated Door Assembly requirements and is not intended for use as a final door submittal.
Provide hardware items required by established standards and practices, and to meet IBC and NFPA 101 whether specified or not in the following listed groups.
1. 26.
HW-SH-4
Each [AC, EL, REX, DPS]Integrated Door to Have:
RATED
1 Steel Frame -
1 Integrated Door w/Elec. Exit Device Q2131 x TYPE 8 ELECTRIC DEVICE
(E01, E05/E06-VERIFY)x F13 LEVER
1 Continuous Transfer Hinge A51031B x 4-THRUWIRE TRANSFER x
IN-HINGE ACCESS PANEL
1 Power Supply REGULATED, FILTERED, 24VDC, AMPERAGE AS REQUIRED
1 Closer C02021 (PT4D, PT4F, PT4H)
3901 Loch Raven Blvd. Baltimore MD 21218 01-01-21
08 17 10 - 8
Each [AC, EL, REX, DPS]Integrated Door to Have:
RATED
1 Armor Plate J101 x 1.275 mm (0.050 inch)
THICKNESS
1 Floor Stop L02121 x 3 FASTENERS
1 Set Self-Adhesive Seals R0E154
1 Alarm Contact -
B. 120VAC power, conduit, and wiring by Division 26.
1. Card reader by Division 28.
2. Lock cylinder by Section 08 71 00, DOOR HARDWARE.
3901 Loch Raven Blvd. Baltimore MD 21218 04-01-22
08 31 13 - 1
SECTION 08 31 13
ACCESS DOORS AND FRAMES
PART 1 - GENERAL
1.1 SUMMARY
A. Section Includes:
1. Access doors and panels installed in walls and ceilings.
1.2 RELATED WORK
A. Section 08 71 00, DOOR HARDWARE: Lock Cylinders.
B. Section 09 91 00, PAINTING: Field Painting.
C. Section 09 06 00, SCHEDULE FOR FINISHES: Finish Color.
D. Section 21 13 13, WET-PIPE SPRINKLER SYSTEMS: Access Doors for Control or Drain Valves.
E. Section 21 12 16, DRY-PIPE SPRINKLER SYSTEMS: Access Doors for Control or Drain Valves.
F. Section 22 40 00, PLUMBING FIXTURES: Access Doors for Plumbing Valves.
G. Section 23 31 00, HVAC DUCTS AND CASINGS: Locations of Access Doors for
Ductwork Cleanouts.
1.3 APPLICABLE PUBLICATIONS
A. Comply with references to extent specified in this section.
B. American Welding Society (AWS):
D1.3/D1.3M-2018 ........Structural Welding Code - Sheet Steel
(6th Edition.
C. ASTM International (ASTM):
A653/A653M-20 ..........Steel Sheet, Zinc-Coated (Galvanized) or
Zinc-Iron Alloy-Coated (Galvannealed) by the
Hot-Sip Process.
A1008/A1008M-18 ........Steel, Sheet, Cold-Rolled, Carbon, Structural, High-Strength Low-Alloy, High-Strength
Low-Alloy with Improved Formability, Solution
Hardened, and Bake Hardenable.
A666-15 ................Annealed or Cold-Worked Austenitic Stainless
Steel sheet, Strip, Plate, and Flat Bar.
E119-20 ................Fire Test of Building Construction and
Materials.
D. National Fire Protection Association (NFPA):
80-2019 Edition ........Fire Doors and Other Opening Protectives.
252-2017 Edition .......Fire Tests of Door Assemblies.
E. National Association of Architectural Metal Manufacturers (NAAMM):
3901 Loch Raven Blvd. Baltimore MD 21218 04-01-22
08 31 13 - 2
AMP 500-06 .............Metal Finishes Manual.
F. UL LLC (UL):
Listed .................Online Certifications Directory.
10B-08 (Edition 10) ....Standard for Fire Tests of Door Assemblies.
263-11 (Edition 14) ....Fire Tests of Building Construction and
Materials.
1.4 SUBMITTALS
A. Submittal Procedures: Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES.
B. Submittal Drawings:
1. Show size, configuration, and fabrication and installation details.
C. Manufacturer's Literature and Data:
1. Description of each product.
2. Installation instructions.
D. Sustainable Construction Submittals:
1. Recycled Content: Identify post-consumer and pre-consumer recycled content percentage by weight.
1.5 DELIVERY
A. Deliver products in manufacturer's original sealed packaging.
B. Mark packaging, legibly. Indicate manufacturer's name or brand, type, production run number, and manufacture date.
C. Before installation, return or dispose of products within distorted, damaged, or opened packaging.
1.6 STORAGE AND HANDLING
A. Store products indoors in dry, weathertight facility.
B. Protect products from damage during handling and construction operations.
1.7 FIELD CONDITIONS
A. Field Measurements: Verify field conditions affecting access door fabrication and installation. Show field measurements on Submittal
Drawings.
1. Coordinate field measurement and fabrication schedule to avoid delay.
1.8 WARRANTY
A. Construction Warranty: FAR clause 52.246-21, "Warranty of
Construction."
3901 Loch Raven Blvd. Baltimore MD 21218 04-01-22
08 31 13 - 3
PART 2 - PRODUCTS
2.1 MATERIALS
A. Steel Sheet: ASTM A1008/A1008M.
B. Galvanized Steel: ASTM A653/A653M.
C. Stainless Steel: ASTM A666; Type 302 or Type 304.
2.2 PRODUCTS - GENERAL
A. Basis of Design: Section 09 06 00, SCHEDULE FOR FINISHES.
B. Provide each product from one manufacturer.
C. Sustainable Construction Requirements:
1. Steel Access Doors Recycled Content: 30 percent total recycled content, minimum.
2. Stainless Steel Access Doors Recycled Content: 70 percent total recycled content, minimum.
2.3 ACCESS DOORS, FIRE-RATED
A. Door Construction:
1. Ceiling Access Door Construction: ASTM E119 or UL 263.
2. Wall Access Doors: NFPA 252 or UL 10B.
B. Label: Class B opening according to UL 10B or test by another nationally recognized laboratory. 1-1/2 hour fire-rated,with maximum temperature rise of 120 degrees C (216 degrees F).
C. Door Panel: Minimum 0.9 mm (0.0359 inch) thick stainless steel sheet, with mineral-fiber insulation core, insulated sandwich type construction.
D. Frame: Minimum 1.5 mm (0.0598 inch) thick steel sheet, depth and configuration to suit material and construction type where installed.
1. Frame Flange: Provide at units installed in concrete, masonry, or gypsum board.
2. Exposed Joints in Flange: Weld and grind smooth.
E. Provide automatic closing device.
F. Hinge: Continuous stainless steel hinge with stainless steel pin.
G. Lock: Self-latching, mortise type with provision for fitting flush a standard screw-in type lock cylinder.
1. Lock cylinder specified in Section 08 71 00, DOOR HARDWARE.
2. Latch release device operable from inside of door.
H. Anchors for Fire-Rated Access Doors: Comply with requirements of applicable fire test.
3901 Loch Raven Blvd. Baltimore MD 21218 04-01-22
08 31 13 - 4
2.4 ACCESS DOORS, FLUSH PANEL, NON-RATED
A. Door Panel:
1. 1.9 mm (0.07 inch) thick steel sheet.
2. Reinforce to maintain flat surface.
B. Frame:
1. 1.5 mm (0.06 inch) thick stainless steel sheet, depth and configuration to suit material and construction type where installed.
2. Frame Flange: Provide at units installed in concrete, masonry, and gypsum board.
3. Exposed Joints in Flange: Weld and grind smooth.
C. Hinge:
1. Concealed spring hinge, 175 degrees of opening.
2. Removable hinge pin to allow removal of door panel from frame.
D. Lock:
1. Flush, screwdriver-operated cam lock.
2. Tamper proof screws (spanner head locks) for access panels in
Behavioral Health Areas.
2.5 ACCESS DOOR, RECESSED PANEL, NON-RATED
A. Door Panel:
1. 1.2 mm (0.05 inch) thick stainless steel sheet to form a 25 mm
(1 inch) deep recessed pan to accommodate installation of acoustical units and other materials where shown in walls and ceiling.
2. Reinforce to prevent sagging.
B. Frame:
1. 1.5 mm (0.06 inch) thick steel sheet of depth and configuration to suit installation in suspension system of ceiling or wall framing.
2. Extend sides of frame to protect edge of acoustical units when door panel is in open position.
3. Provide shims, bushings, clips and other devices necessary for installation.
C. Hinge: Continuous stainless steel hinge with stainless steel pin, or concealed hinge.
D. Lock:
1. Flush screwdriver-operated cam lock.
2. Plastic sleeve or stainless steel grommet to protect hole made in acoustical unit for screwdriver access to lock.
3901 Loch Raven Blvd. Baltimore MD 21218 04-01-22
08 31 13 - 5
3. Tamper proof screws (spanner head locks) for access panels in
Behavioral Health Areas.
2.6 FABRICATION - GENERAL
A. Size: Minimum 600 mm (24 inches) square door unless otherwise shown or required to suit opening in suspension system of ceiling.
B. Component Fabrication: Straight, square, flat and in same plane where required.
1. Exposed Edges: Slightly rounded, without burrs, snags and sharp edges.
2. Exposed Welds: Continuous, ground smooth.
3. Welding: AWS D1.3/D1.3M.
C. Locks and Non-Continuous Hinges: Provide in numbers required to maintain alignment of door panel with frame. For fire-rated doors, provide hinges and locks as required by fire test.
D. Anchoring: Make provisions in frame for anchoring to adjacent construction. Provide anchors in size, number and location on four sides to secure access door to substrate. Provide anchors as required by fire test.
2.7 FINISHES
A. Steel Paint Finish:
1. Powder-Coat Finish: Manufacturer's standard two-coat finish system consisting of the following:
a. One coat primer.
b. One coat thermosetting topcoat.
c. Dry-film Thickness: 0.05 mm (2 mils) minimum.
d. Color: Refer to Section 09 06 00, SCHEDULE FOR FINISHES.
B. Stainless Steel Exposed Surfaces: NAAMM AMP 500; No.06 Metal Finishes.
2.8 ACCESSORIES
A. Fasteners: Type and size recommended by access door manufacturer, to suit application.
1. Stainless Steel Access Doors: Stainless steel fasteners.
2. Other Access Doors: Stainless steel fasteners.
PART 3 - EXECUTION
3.1 PREPARATION
A. Examine and verify substrate suitability for product installation.
1. Verify access door locations and sizes provide required maintenance access to installed building services components.
B. Protect existing construction and completed work from damage.
3901 Loch Raven Blvd. Baltimore MD 21218 04-01-22
08 31 13 - 6
3.2 INSTALLATION - GENERAL
A. Install products according to manufacturer's instructions and approved submittal drawings .
1. When manufacturer's instructions deviate from specifications, submit proposed resolution for Contracting Officer's Representative consideration.
B. Install access doors and panels permitting access to service valves, traps, dampers, cleanouts, and other mechanical, electrical and conveyor control items concealed in walls and partitions, and concealed above gypsum board and plaster ceilings.
C. Install fire rated access door according to NFPA 80.
D. Install fire-rated doors in fire-rated partitions and ceilings.
E. Install flush access panels in partitions and in gypsum board and plaster ceilings.
3.3 ACCESS DOOR AND FRAME INSTALLATION
A. Wall Installations: Install access doors in openings with sides vertical.
B. Ceiling Installations: Install access doors parallel to ceiling suspension grid or room partitions.
C. Frames without Flanges: Install frame flush with surrounding finish surfaces.
D. Frames with Flanges: Overlap opening, with face uniformly spaced from finish surface.
E. Recessed Panel Access Doors: Install with face of surrounding materials flush with door panel installed finish.
F. Secure frames to adjacent construction with fasteners.
G. Install type, size and quantity of anchoring device suitable for material surrounding opening to maintain alignment, and resist displacement, during normal use of access door.
H. Field Painting Primed Access Doors: Comply with the requirements of
Section 09 91 00, PAINTING.
3.4 ADJUSTMENT
A. Adjust hardware so door panel opens freely.
B. Adjust door when closed so door panel is centered in frame.
3901 Loch Raven Blvd. Baltimore MD 21218 01-01-21
08 41 13 - 1
SECTION 08 41 13
ALUMINUM-FRAMED ENTRANCES AND STOREFRONTS
PART 1 - GENERAL
SUMMARY
Section Includes:
1. Aluminum-framed entrances and storefronts .
RELATED REQUIREMENTS
Door Finish and Color: Section 09 06 00, SCHEDULE FOR FINISHES.
Glass and Glazing: Section 08 80 00, GLAZING.
Hardware: Section 08 71 00, DOOR HARDWARE.
APPLICABLE PUBLICATIONS
Comply with references to extent specified in this section.
American Architectural Manufacturers Associations (AAMA):
2603-15.................Performance Requirements and Test Procedures for Pigmented Organic Coatings on Aluminum
Extrusions and Panels
2604-13.................Performance Requirements and Test Procedures or
High Performance Organic Coatings on
Architectural Extrusions and Panels
2605-13.................Performance Requirements and Test Procedures for Superior Performing Organic…