Binder_BLDG 1 HVAC Drawings.pdf
PDF 8 MB Posted
- Attached to
- Building 1 HVAC Repair Federal contract opportunity
- Solicitation number
- W50S8Q-25-Q-A003
- Issued by
- Department of the Army National Guard
About this file
The document is a detailed technical drawing set for HVAC (Heating, Ventilation, and Air Conditioning) system components for Building 1, likely at the Blue Ash Air National Guard Base. The drawings include comprehensive schematics and specifications for single-package cooling units (Carrier model 50FP series), which feature constant/variable volume capabilities, product integrated controls, and compatibility with the Carrier Comfort Network. The units offer multiple configuration options including factory-installed electric heat, optional economizer controls, and advanced control functions such as occupancy scheduling, building pressurization control, and remote monitoring capabilities.
The technical drawings provide extensive details on unit dimensions, roof curb specifications, field wiring configurations, and installation requirements. Key technical features include semi-hermetic Carrier compressors, dual refrigeration circuits, high-efficiency indoor motors, Tuff-Skin anti-microbial insulation, sloped condensate pans, and circuit breaker protection. The documentation includes performance data tables, electrical specifications, mounting details, and accessory options such as filters, economizers, and control modules. These drawings appear to support the W50S8Q-25-Q-A003 solicitation for HVAC repair at the Blue Ash Air National Guard Base, with the total project value estimated between $100,000 and $250,000.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| RFI Answers_BLDG1 HVAC.pdf | ||
| Binder_Controller Photos.pdf | ||
| SiteVisit Sign in Sheet_BLDG 1 HVAC_7-24-25.pdf | ||
| RFI Answers_BLDG1 HVAC.pdf | ||
| Solicitation - W50S8Q25QA003.pdf | ||
| RFI Template.docx | DOCX document | |
| Springfield Base Facility Standards - FINAL - March 2025 Signed.pdf | ||
| Material Submittals BVGM252001.xlsx | XLSX spreadsheet | |
| SOW BVGM252001.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
50FP034, 038, 044, 048, 054, 064, 074
SINGLE-PACKAGE COOLING UNITS
CONSTANT/VARIABLE VOLUME
PRODUCT INTEGRATED CONTROLS
CARRIER COMFORT NETWORK COMPATIBLE
FACTORY-INSTALLED OPTIONAL
ELECTRIC HEAT
— PERFORMANCE DATA
— TYPICAL FIELD WIRING
— CERTIFIED DIMENSION PRINTS
— CERTIFIED ROOF CURB
DIMENSION PRINTS
50FP-1SB
R 1997 Carrier Corporation • Syracuse, New York 13221
Form 50FP-1SB Supersedes New Printed in U.S.A. 12-97 Catalog No. 515-069
Date: Supersedes:
50FP034, 038, 044, 048, 054, 064, 074
SINGLE-PACKAGE COOLING UNITS,
WITH PRODUCT INTEGRATED
CONTROLS
50FP Rev.:
JOB NAME: LOCATION:
BUYER: BUYER P.O. # CARRIER #
UNIT NUMBER: MODEL NUMBER:
PERFORMANCE DATA CERTIFIED BY: DATE:
DESCRIPTION
50FP units are completely packaged, prewired and precharged electric cooling/heating or cooling only units with PRODUCT INTEGRATED CONTROLS.
50FP units are built for bottom supply and return applications. Their waterproof construction makes them ideally suited for installation on the accessory roof curb which is NRCA approved.
Units are either CONSTANT VOLUME or VARIABLEAIR VOLUME depending on the factory-installed options selected.
PRODUCT INTEGRATED CONTROL FEATURES
STANDARD CONTROL FUNCTIONS
Unit compatible with CARRIER COMFORT NETWORK or stand alone operation.
Constant Volume or Variable Air Volume control.
Four to six stages of compressor unloading possible.
Supply fan control based on occupancy schedule using 365-day electronic timeclock with holiday scheduling.
Time schedule override through the space temperature sensor provided with the unit.
Compatible with 37H and 45 Series PIC terminals to form a Digital Air Volume system (DAV).
Building pressurization control in conjunction with modulating power exhaust option.
Supply duct static pressure controlled through inlet guide vanes or field or factory supplied inverter.
Head pressure control to −20° F. Head pressure controlled by saturated condensing temperature, low ambient control utilizes Motor-mastert II fan cycling.
Lead-lag compressor control to even out run time.
Self-diagnostic run test confirms control and component operation at unit commissioning. Self-diagnostic troubleshooting codes in-dicate the reason unit tripped to expedite unit repair. Codes ex-pand to English Text.
Control of a two-speed supply fan motor on CV applications. (Two-speed motor available on Special Order.)
Building Purge Mode flushes building interior with outdoor air to remove contaminants before occupancy.
Adaptive Optimal Start minimizes the amount of time and energy required before entering the occupied mode.
Unoccupied Mode Free Cooling — units with optimal economizer will utilize free cooling whenever possible to maintain the unoc-cupied setpoint.
Input/Output of data and monitoring of alarms can be done remotely using Building Supervisor, or at the unit using the ac-cessory HSIO module.
Delayed Mechanical Cooling — units with optional economizer will utilize cooling to cool the space 3 degrees below the occupied setpoint to delay the need for mechanical cooling.
ADDITIONAL CONTROL FUNCTIONS
AVAILABLE THROUGH FACTORY-INSTALLED ‘‘OPTION MODULE’’
Provides a discrete output with occupancy control for use as speci-fied by the customer.
Controls a field installed humidifier using a 4 to 20 mA or2-stage output. Requires accessory humidity sensor.
Smoke Control functions (Building Pressurization and Smoke Purge) are provided through software. Terminals are provided to interface with field supplied smoke/fire panel.
Provides a 4 to 20 mAoutput to direct or reverse proportional hot water control valve for field supplied hydronic heating coil. Re-quires a field supplied freezestat to protect coil.
Factory installed suction and discharge pressure transducers and suction temperature thermistors allow remote monitoring of these parameters and superheat to provide enhanced remote diagnostics.
Differential enthalpy control can be provided using field installed accessory humidity sensors.
Economizer control field configurable to:
— Maintain a minimum economizer setpoint position, OR
— Maintain the minimum economizer position based on input from an IAQ sensor (field supplied 0 - 10volt), OR
— Maintain a constant CFM of outdoor air intake (Requires ac-cessory Outdoor Air CFM package), OR
— Look at all three above and maintain minimum economizer position based on the dominant parameter.
UNIT FEATURES
Large hinged access doors.
Standard one-year product warranty.
Standard unit as factory-assembled is listed by ETL and/or ETL, Canada.
Units are rated in accordance with ARI Standard 360.
115-volt and 24-volt control circuit.
Semi-hermetic Carrier compressors.
Dual refrigeration circuits.
Crankcase heaters.
Compressor protection includes high and low pressure cutouts.
Manual adjustable outside air intake for up to 25% outside air.
Single low rpm supply fan with 2-in. deflection springs under fan sled.
High efficiency indoor motors (supply and exhaust).
Tuff-Skin Rx anti-microbial insulation.
Sloped condensate pan.
Cabinet made of prepainted galvanized steel.
Evaporator-fan motors are protected by circuit breakers.
Condenser-fan motors are internally protected.
Single-point electric service entry.
Circuit breaker protection for all power components.
Lifting lugs.
Two-inch disposable-type return air filters.
Five-year non prorated warranty on heater element is standard when heater is factory installed.
PERFORMANCE DATA
Unit Operating Weight lbs. Curb Weight lbs.
Indoor Entering Air dB F wB F CFM External Static Pressure in. wg
COOLING
Gross Total Capacity Btuh @ Condenser Air Temp F Gross Sensible Capacity Btuh Compressor Power Input kW Indoor Fan Motor Size HP Exhaust Fan Motor Size HP Return Fan Motor Size HP
HEATING
Heating Capacity Total Btuh Heating Capacity Total kW Stage 1 kW Stage 2 kW
ELECTRICAL DATA
Power Supply to Unit Volts Phase Hertz
Minimum Circuit Amps Maximum Fuse Amps
OPTIONS AND ACCESSORIES
FACTORY-INSTALLED OPTIONS
M Control option module M Two-inch pleated filters (30%) M Bag filters with prefilters (90%) M Inlet guide vanes or variable frequency drives M Alternate motor and drive M Premium efficiency motor and drive (208/230, 460 v) M Alternate premium-efficiency motor and drive
(208/230, 460 v) M Economizer with low leak dampers and spring return motor M Copper condenser coil M Hot gas bypass M Barometric relief* M Modulating power exhaust* M Electric heat kW M Non-fused factory mounted disconnect
*Unit mounted on vertical supply/return applications.
FIELD-INSTALLED ACCESSORIES
M Roof curb with full perimeter support (30, 35, 40, 45 ton) M Roof curb with condenser end support (50, 60, 70 ton) M Roof curb to enclose the condenser section (50, 60, 70 ton) M Outdoor air CFM package M Condenser coil guard M Local interface device M Space thermostat M Differential enthalpy control sensor M Modulating power exhaust package M Optional 5-year extended heat exchanger warranty M Optional 4-year extended compressor warranty M HSIO keypad and display module (required for initial start-up)x
M
M
M
TYPICAL FIELD WIRING
FIELD POWER WIRING CONNECTIONS
DISCONNECT PER NEC
EQUIP GND
FIELD CONTROL WIRING
TYPICAL SPACE TEMPERATURE SENSOR WIRING
LEGEND
CCN — Carrier Comfort Network COM — Communications GND — Ground SW — Switch T — Terminal TB — Terminal Block TH — Thermostat, Heating
Field Wiring *Constant Volume Applications Only.
CCN COMMUNICATIONS BUS WIRING TO OPTIONAL SPACE SENSOR RJ11 CONNECTOR
50F P 034,038
(PA
C
UNIT SIZE
WEIGHT
Lb Kg
50FP034 5400 2455
50FP038 5525 2511
NOTES:
1. Dimensions in [ ] are in millimeters.
2. Center of Gravity includes economizer. Unit weight does not include economizer.
3. Unit clearances:
Top — Do not restrict condenser fans Control Box End — 68-09 Sides — 68-09 Economizer End — 68-09 (except power exhaust units 108-09) For smaller service and operating clearances, contact Carrier Application Engineering Department.
4. Downshot ducts designed to be attached to accessory roof curb.
If unit is mounted on dunnage, it is recommended the ducts be supported by cross braces as done on the accessory roof curb.
5. When the unit is slab mounted, plug the factory drilled auxil-iary condensate drain holes.
6. Economizer side hoods are folded inside unit for shipping.
CERTIFIED DIMENSION PRINT
CUT ALONG DOTTED LINE CUT ALONG DOTTED LINE
044, (PA
C
UNIT SIZE
WEIGHT
Lb Kg
50FP044 6050 2750
50FP048 6090 2768
NOTES:
1. Dimensions in [ ] are in millimeters.
2. Center of Gravity includes economizer. Unit weight does not include economizer.
3. Unit clearances:
Top — Do not restrict condenser fans Control Box End — 68-09 Sides — 68-09 Economizer End — 68-09 (except power exhaust units 108-09) For smaller service and operating clearances, contact Carrier Application Engineer-ing Department.
4. Downshot ducts designed to be attached to accessory roof curb. If unit is mounted on dunnage, it is recommended the ducts be supported by cross braces as done on the accessory roof curb.
5. When the unit is slab mounted, plug the factory drilled auxiliary condensate drain holes.
6. Economizer side hoods are folded inside unit for ship-ping.
CERTIFIED DIMENSION PRINT
054-074
(PA
C
UNIT SIZE
WEIGHT A B C D E F
Lb Kg mm ft-in. mm ft-in. mm ft-in. mm ft-in. mm ft-in. mm ft-in.
50FP054 7700 3500 2864 9-43⁄4 5347 17-61⁄2 5537 18-2 1163 3-913⁄16 10092 33-15⁄16 10476 34-47⁄16
50FP064 8000 3636 2864 9-43⁄4 5347 17-61⁄2 5537 18-2 1163 3-913⁄16 10092 33-15⁄16 10476 34-47⁄16
50FP074 8430 3832 3727 12-23⁄4 4483 14-81⁄2 5969 21-3 1163 3-913⁄16 11001 36-11⁄8 11385 37-41⁄4
NOTES:
1. Dimensions in [ ] are in millimeters.
2. Center of Gravity includes economizer. Unit weight does not include economizer.
3. Unit clearances:
Top — Do not restrict condenser fans Control Box End — 68-09 Sides — 68-09 Economizer End — 68-09 (except power exhaust units 108-09).
For smaller service and operating clearances, contact Carrier Application Engineering Department.
4. Downshot ducts designed to be attached to accessory roof curb. If unit is mounted on dunnage, it is recommended the ducts be supported by cross braces as done on the accessory roof curb.
5. When the unit is slab mounted, plug the factory drilled auxiliary condensate drain holes.
6. Economizer side hoods are folded inside unit for shipping.
CERTIFIED DIMENSION PRINT
R O O F C U R B
50F P 034, (PA
C
CERTIFIED ROOF CURB DIMENSION PRINT
O F C U R B
50F P 044, (PA
C
CERTIFIED ROOF CURB DIMENSION PRINT
O F C U R B
50F P 054-074
(PA
C
A C C E S S O R Y R O O F C U R B
50F P 054, CERTIFIED ROOF CURB DIMENSION PRINT
A C C E S S O R Y R O O F C U R B
50F P
| Existing RTU Drawings.pdf |
| Bldg 1 Roof Plan.pdf |
| Bldg 1 Roof Framing.pdf |
| Bldg 1 Mechanical Schedule.pdf |
| Bldg 1 HVAC Floor Plan.pdf |
File details come from the government source that posted it. Updated .