BigSmokyElectrical Foundations maps.pdf
PDF 4 MB Posted
- Solicitation number
- 1240LT24R0040
- Issued by
-
Department of Agriculture Forest Service
About this file
This document is a solicitation for the Big Smoky Hybrid Electrical System Upgrade and Building Foundation Improvements project.
The base bid includes the installation of a standalone generator system that backs up a DC solar array with battery storage and inversion to a 240/120 Vac distribution system. The work involves removing and salvaging an existing generator and solar array, site work for a new generator pad and generator, and providing and installing a Flexware system with batteries and other components for a fully operational system.
Option Item #1 is for installing permanent concrete foundations for two existing buildings, including raising, shifting, and resetting the buildings, hauling excavated material, and reconnecting utilities.
Option Item #2 is similar to the base bid, but involves removing and disposing an existing generator, rather than salvaging it, and using the salvaged solar modules from the existing array as part of the new pole-mounted array.
The solicitation is issued by the Department of Agriculture Forest Service for the Sawtooth National Forest in Fairfield, Idaho. No award date or pricing terms are provided.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Big Smoky Pre-bid Sign-in Sheet 05-23.pdf | ||
| 1240LT24R0040 AMD 1.pdf | ||
| 1240LT24R0040.pdf | ||
| SOW.docx | DOCX document | |
| Camas County Wage Determination.txt | TXT text file | |
| FirePrecautions Plan.docx | DOCX document | |
| ScheduleOfItems.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
VICINITY MAP
TRAVEL DIRECTIONS:
SHEET OF
United States Department of Agriculture Forest Service
1 5
FROM THE FAIRFIELD RANGER DISTRICT OFFICE, TRAVEL NORTH ON 1ST STREET 148 FT TO POPLAR AVE AND TURN LEFT ON TO POPLAR AVE AND HEAD WEST FOR 472 FT TO TURN RIGHT ONTO CENTER STREET/SOLDIER ROAD, CONTINUE 1.8 MILES AND TURN RIGHT (EAST) FOR 0.3 MILES AND TURN RIGHT (NORTH) TO REMAIN ON SOLDIER CREEK ROAD AND CONTINUE FOR 4.1 MILES. TURN LEFT (WEST) TO STAY ON SOLDIER CREEK ROAD AND FOLLOW FOR 3.6 MILES. TAKE A SLIGHT RIGHT ONTO COUCH SMT ROAD/NF-94 FOR 4.4 MILES AND TURN RIGHT TO KEEP ON SAME ROAD FOR 10 MILES.
TURN RIGHT AT THE EXTENDED 4 CORNER INTERSECTION TO HEAD NORTHEAST ON BIG SMOKY ROAD FOR 0.7 MILES AND TURN LEFT ONTO BIG SMOKY WORK CENTER ROAD FOR 0.1 MILE AND TURN LEFT
ONTO FOREST ROAD 70050 TO ARRIVE AT THE NORTH BIG SMOKY ADMINISTRATION SITE.
43° 37' 17.40" NORTH LATITUDE AND 114° 52' 03.80" WEST LONGITUDE, 5580 FEET ELEVATION.
FARIFIELD DISTRICT OFFICE
102 1ST STREET
FAIRFIELD, IDAHO 83327
RECOMMENDED BY:
APPROVED:
FOREST ENGINEER
DISTRICT RANGER DATE
DATE
DIRECTOR OF ENGINEERING OR ASSISTANT DATE
FOREST SUPERVISOR DATE
3/2 8/2
4 1 3:
B
KR
IC
HI
NS
C :\U
SE
RS
\B
KR
IC
HI
NS
\O
NE
DR
IV
E
- U
SD
A\
DO
CU
ME
NT
S\
RI
CH
IN
SF
IL
ES
\P
RO
JE
CT
S\
P
RO
JE
CT
S\
BI
GS
MO
KY
EL
EC
TR
IC
AL
&F
OU
ND
AT
IO
NI
MP
RO
VE
ME
NT
S2
4\E
LE
CT
RI
CA
L\
RE
VI
EW
SU
BM
IT
TA
L_
NO
RT
H\
BI
GS
MO
KY
NH
YB
CV
R.
DW
G;
IDAHO
CAMAS COUNTY
R-4 INTERMOUNTAIN REGION
SAWTOOTH NATIONAL FOREST
FAIRFIELD RANGER DISTRICT
INDEX OF SHEETS
SHEET SHEET TITLE DATE
COVERSHEET (G-1) 03/05/24
GENERAL LAYOUT, SIGNS, AND ARRAY
SUPPORT (E-1) 03/05/24
SITE PLAN AND GENERATOR BUILDING (E-2) 03/05/24
FLEXWARE SYSTEM (E-3) 03/05/24
GENERATOR PAD AND ARRAY MOUNTING
(D-1) 03/05/24
BIG SMOKY NORTH SITE HYBRID ELECTRIC
BIG SMOKY NORTH SITE
IDAHO
IDAHO
BASE BID
Shawn Robnett, PE
Mathew Filbert
Jake Strohmeyer
3/5/24
3/5/24
3/6/24
Scott Bingham, PE 3/28/24
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
PROJECT LOCATION
AutoCAD SHX Text
BONNERS FERRY
AutoCAD SHX Text
SANDPOINT
AutoCAD SHX Text
COEUR D'ALENE
AutoCAD SHX Text
MOSCOW
AutoCAD SHX Text
LEWISTON
AutoCAD SHX Text
GRANGEVILLE
AutoCAD SHX Text
WHITE BIRD
AutoCAD SHX Text
RIGGINS
AutoCAD SHX Text
NEW MEADOWS
AutoCAD SHX Text
COUNCIL
AutoCAD SHX Text
YELLOW PINE
AutoCAD SHX Text McCALL
AutoCAD SHX Text
CASCADE
AutoCAD SHX Text
NORTH FORK
AutoCAD SHX Text
SALMON
AutoCAD SHX Text
LEADORE
AutoCAD SHX Text
STANLEY
AutoCAD SHX Text
CLAYTON
AutoCAD SHX Text
CHALLIS
AutoCAD SHX Text
MACKAY
AutoCAD SHX Text
LOWMAN
AutoCAD SHX Text
WEISER
AutoCAD SHX Text
EMMETT
AutoCAD SHX Text
IDAHO CITY
AutoCAD SHX Text
KETCHUM
AutoCAD SHX Text
BOISE
AutoCAD SHX Text
FAIRFIELD
AutoCAD SHX Text
MOUNTAIN HOME
AutoCAD SHX Text
BUHL
AutoCAD SHX Text
TWIN FALLS
AutoCAD SHX Text
BURLEY
AutoCAD SHX Text
DUBOIS
AutoCAD SHX Text
ISLAND PARK
AutoCAD SHX Text
ST. ANTHONY
AutoCAD SHX Text
ASHTON
AutoCAD SHX Text
DRIGGS
AutoCAD SHX Text
IDAHO FALLS
AutoCAD SHX Text
POCATELLO
AutoCAD SHX Text
SODA SPRINGS
AutoCAD SHX Text
MALAD
AutoCAD SHX Text
MONTPELIER
GENERATOR NOTES
1. EXISTING GENERATOR SYSTEM (INCLUDES FLEXIBLE FUEL, EXHAUST, AND VENTILATION
SYSTEMS) SHALL BE REMOVED FROM BUILDING AND SHALL REMAIN THE PROPERTY OF THE
GOVERNMENT. THE CONTRACTOR SHALL BE RESPONSIBLE FOR LOADING IT IN A
GOVERNMENT VEHICLE OR PLACING IT AT A LOCATION NOTED BY THE GOVERNMENT ON THIS
SITE.
2. INSTALL PAD AND KOHLER GENERATOR, MODEL 15REOZK, 60 HZ, 1 PHASE, 120/240 V, 14.0 KW
PRIME (105°C RISE), DIESEL, AND WEATHER ENCLOSURE MOUNTED ON 168 GALLON SUBBASE
FUEL TANK. SUPPLY WITH MAIN BREAKER, PRIME POWER SWITCH, STARTING BATTERY AND
CHARGER, STANDARD CONTROL FEATURES, AND ALL APPURTENANCES READY FOR
OPERATION. 2-YEAR WARRANTY. SUBBASE FUEL TANK INCLUDES I-BEAMS FOR GROUND
CLEARANCE, 5 GALLON FUEL FILL SPILL CONTAINMENT, AND COMBUSTIBLE LIQUIDS DECAL.
3. ENSURE GROUND AND NEUTRAL ARE NOT BONDED AT THE GENERATOR. SYSTEM NEUTRAL
BOND TO OCCUR ELSEWHERE.
4. AUTOSTART CIRCUIT: CONNECT REMOTE CIRCUIT TO TERMINALS 3 AND 4.
5. PROVIDE FULL STARTUP SERVICE COORDINATING WITH FLEXWARE STARTUP SERVICE.
GENERAL LAYOUT ONE-LINE
SCHEMATIC
AC FEEDER
GENERATOR START
PV DC FEEDER
AC LOADS
DC POWER
GROUND, SEE
SPECIFICATIONS
NEW
GENERATOR
EXISTING
DTS
FLEXWARE
BATTERIES
NOTES:
GENERATOR IS CALLED OUT ON THIS SHEET. MOUNTING
PAD IS ON SHEET D-1. SITE PLAN, SHEET E-2.
PV ARRAY CALLED OUT ON SHEET E-3. MOUNTING IS ON
SHEET D-1. SITE PLAN, SHEET E-2.
INSTALL FEEDER FROM GENERATOR INTO FLEXWARE
SYSTEM. SEE SHEET E-3.
INSTALL GENERATOR START/RUN CIRCUIT IN SEPARATE
CONDUIT FROM GENERATOR POWER CIRCUIT TO
GENERATOR. SEE SHEET E-3, AND, FLEXWARE AND
GENERATOR DOCUMENTATION.
DC FEEDER CIRCUIT FROM ARRAY TO FLEXWARE
SYSTEM. SEE SHEETS E-2 AND E-3.
FLEXWARE SYSTEM WITH ALL EQUIPMENT AS SHOWN ON
SHEET E-3 . PROVIDES DC BATTERY CHARGING FROM
GENERATOR AND PV POWER SOURCES, DC INVERTER TO
120/240 VAC, AND GENERATOR CONTROL. FLOOR -PLAN,
SHEET E-2.
EXISTING GROUNDING ELECTRODE SYSTEM. SEE NOTE
12.
CONDUIT SLEEVED BATTERY CONNECTION, SEE SHEET
E-3.
BATTERY BANK AND MOUNTING RACK. SEE SHEET E-2
AND E-3.
120/240 VAC FEEDER. SEE SHEET E-3.
EXISTING DOUBLE THROW DISCONNECT (DTS), TO
REMAIN WITH OVERRIDE TO A PORTABLE GENERATOR.
SEE PHOTOS SHEET E-2.
EXISTING DISTRIBUTION PANELBOARD. INSTALL WITH
NEUTRAL TO GROUND BONDING FOR THE ENTIRE
SYSTEM. REWORK OR REPLACE THE GEC TO THE
EXISTING GROUNDING ELECTRODE SYSTEM.
EXISTING
PANELBOARD
REQUIRED SIGNS (MOUNTING LOCATION), 0.5-INCH MINIMUM
HIGH TEXT
"STRUCTURE SERVED WITH STAND ALONE PHOTOVOLTAIC SYSTEM.
PV DISCONNECT LOCATED ON ARRAY POLE JUST TO THE NORTH OF
THIS BUILDINGS." (MOUNT ON SHED DOOR.)
"MAXIMUM DC VOLTAGE = 117 VDC
MAXIMUM ARRAY CURRENT = 28.8 ADC
MAXIMUM RATED CURRENT OUTPUT OF EACH CHARGE CONTROLLER =
80 AMPS"
(MOUNT ON SHED DOOR AND AT FLEXWARE SYSTEM)
"WARNING: ELECTRICAL SHOCK HAZARD - TERMINALS ON THE LINE
AND LOAD SIDES MAY BE ENERGIZED IN THE OPEN POSITION" (MOUNT
ON FLEXWARE SYSTEM DISCONNECT COVER)
"PV SYSTEM MAIN DISCONNECTS - 1 OF 2 (ARRAY)" (MOUNT ON COVER
BY DISCONNECT MEANS ON FLEXWARE SYSTEM)
"PV SYSTEM MAIN DISCONNECT - 2 OF 2 (BATTERY)" (MOUNT ON
COVER BY DISCONNECT MEANS ON FLEXWARE SYSTEM)
"DANGER - GENERATOR STARTS AUTOMATICALLY AND WITHOUT
WARNING. TURN GENERATOR OFF AT GENERATOR CONTROL BEFORE
WORKING ON IT." (MOUNT ON GENERATOR AND FLEXWARE SYSTEM)
"WARNING - DC ARC FLASH HAZARD APPROPRIATE PPE REQUIRED
NOMINAL VOLTAGE: 48 VOLTS DC. 6,000 AMPERES ARE AVAILABLE AT
THE BATTERY TERMINALS. 11,700 AMPERES ARE AVAILABLE AT THE
BATTERY BANK. 10,050 AMPERES ARE AVAILABLE AT THE FLEXWARE
EQUIPMENT. CALCULATED 11/21/2023. (MOUNT ABOVE BATTERY BANK)
MULTIPLE POWER SOURCE WARNING SIGNS, SEE SECTION 260553 -
IDENTIFICATION FOR ELECTRICAL SYSTEMS (MOUNT ON FLEXWARE
SYSTEM, GENERATOR START RELAY ENCLOSURE, AND BATTERY
BANK)
WORKING CLEARANCE SIGNS, SEE SECTION 260553 - IDENTIFICATION
FOR ELECTRICAL SYSTEMS (MOUNT AT FLEXWARE SYSTEM, BATTERY
BANK, AND EXITING DISTRIBUTION PANELBOARD)
"HAZARD: THIS BUILDING IS NOT A STORAGE AREA." (ONE SIGN
MOUNT ON CENTER OF REAR WALL ABOVE BATTERY STORAGE)
"DC CIRCUIT" (MOUNT ON ARRAY CONDUIT (INSIDE AND EXTERIOR TO
BUILDING) AND BATTERY SLEEVE, EVERY 10-FT AND EVERY CONDUIT
BODY AND JUNCTION BOX)
"WARNING - PV POWER SOURCE" (MOUNT ON VISIBLE PORTION OF
ARRAY CONDUIT AT BUILDING EXTERIOR AND INTERIOR)
"PV SYSTEM DISCONNECT - NOT RAPID SHUTDOWN RATED." (MOUNT
ON POLE DISCONNECT COVER)
"WARNING: ELECTRICAL SHOCK HAZARD - TERMINALS ON THE LINE
AND LOAD SIDES MAY BE ENERGIZED IN THE OPEN POSITION" (MOUNT
ON POLE DISCONNECT COVER)
"POWER IS LIMITED AT THIS SITE. ELECTRIC PLUG LOADS SHALL BE
LIMITED TO SMALL LOADS SUCH AS A LAPTOP, UNPLUGGED WHEN NOT
IN USE. LIGHTING SHALL BE TURNED OFF WHEN NOT IN USE." (8
TOTALS, AT ELECTRICALLY POWERED BUILDING WITH ONE SPARE FOR
FUTURE WAREHOUSE, MOUNT AT MAIN ENTRY JUST ABOVE LIGHT
SWITCH)
PROJECT DESCRIPTION
PROJECT INCLUDES A NEW HYBRID POWER SOURCE (GENERATOR AND SOLAR)
AND DISCONNECTING AND REMOVING THE EXISTING GENERATOR FROM THE
GENERATOR BUILDING.
PV ARRAY
PV ARRAY
DRAWN
DESIGNER
STAMPS, LOGOS, AND SEALS
PROJECT NAME
DRAWING TITLE
CHECKED
ARCHIVE NO.DATE
PROJECT NO.
DRAWING SHEET NO.
DATENO.
REVISION / ISSUE
OFSHEET
United States Department of Agriculture Forest Service
3/5 /24
:5
0 S
AB
RO
W
N X:
\S
AW
TO
OT
H\
BI
GS
MO
KY
NO
RT
HH
YB
RI
D.
\D
W G\
BI
GS
MO
KY
NH
YB
.D W
G;
REGION 4
INTERMOUNTAIN REGION
BIG SMOKY
NORTH SITE
HYBRID
ELECTRIC
SAWTOOTH NATIONAL
FOREST
FARIFIELD DISTRICT
GENERAL LAYOUT,
SIGNS, AND ARRAY
SUPPORT
03/05/2024
S.BROWN
S.BROWN
R.ANDERSON
E-1 2 5
Approved: x
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text S
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text V
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text P
AutoCAD SHX Text A
AutoCAD SHX Text R
AutoCAD SHX Text T
AutoCAD SHX Text M
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text T
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text A
AutoCAD SHX Text G
AutoCAD SHX Text R
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text U
AutoCAD SHX Text L
AutoCAD SHX Text T
AutoCAD SHX Text U
AutoCAD SHX Text R
E
30' 0 60' 120'
BLOWUP APPROXIMATE
4' M
IN
E
E
E
~52'
10'
BATTER
IES
PNL A
SHED FLOOR PLAN
16'8'4'2'02'
EXISTING ARRAY TO SALVAGE
AND REUSE
FLEXWARE
SMALL (24" WIDE x 9" DEEP
MAX) CABINET ALLOWED FOR
GENERATOR MAINTENANCE
PRODUCTS
PROVIDE SURFACE MOUNTED
BLOCKING SECURELY
MOUNTED TO WALL FRAMING
TO MOUNT FLEXWARE TO.
EXISTING PANELBOARD
AND DOUBLE THROW
DISCONNECT (DTS)
GENERATOR SHED EXISTING DTS AND
PANELBOARD
GENERATOR SHED INTERIOR
GENERAL PHOTO OF PROPOSED ARRAY
LOCATION
GENERATOR PAD LOCATION AND
GENERATOR SHED
REMOVE AND SALVAGE ARRAY FOR REUSE.
REMOVE SUPPORTS AND WOOD BLOCKING (TO
REMAIN THE PROPERTY OF THE GOVERNMENT)
AND REPAIR SIDING DAMAGE CAUSED BY REMOVAL
INCLUDING SILICONE CAULKING BLOCKING
FASTENER HOLES. REPAIR PAINT AS NEEDED TO
MATCH EXISTING. SEE SITE PLAN FOR LOCATION.
GENERATOR SHED
LOOKING EAST
GENERATOR AND PAD TO BE LOCATED ON NORTH
SIDE OF SHED, REQUIRING BUILDING UP SURFACE
SO TOP OF PAD IS 9-INCHES MINIMUM ABOVE
EXISTING GRADE. EDGE OF GENERATOR SHALL
BE 4-FT MINIMUM FROM SHED WALL.
GENERATOR SYSTEM
TO BE REMOVED AND
SALVAGED
VENT SYSTEM TO BE
REMOVED AND SALVAGED
EXHAUST SYSTEM TO BE
REMOVED AND SALVAGED
DTS TO REMAIN
GOVERNMENT TO REMOVE
SHELVING BEFORE START
OF CONTRACT
WALL PENETRATIONS TO
BE REPAIRED BY OTHERS
ROOF PENETRATION REPAIR BY
OTHERS (NOT INCLUDING
EXCESSIVE DAMAGE)
DO NOT REMOVE 2x4 WALL CROSS BRACING, IT MAY BE USED TO SUPPLEMENT BLOCKING
FOR FLEXWARE MOUNTING
CUT ELECTRICAL STUBUPS OFF
FLUSH WITH CONCRETE AND
REMOVE UNUSED CONDUCTORS
PROPANE LINE TO BE REMOVED
AND CAPPED WHERE IT ENTERS
THE BUILDING AFTER VALVE AT
FLOOR BEHIND GENERATOR.
PANELBOARD
DTS
CORD TO REMAIN FOR
PORTABLE GENERATOR
CONNECTION
JUNCTION/PULL BOX
GFI
S
NEW GFCI DUPLEX RECEPTACLE, 15
AMP, 120 VAC; AND SINGLE POLE
SWITCH. MAY BE IN SAME DEVICE BOX.
NEW LUMINAIRE, RAB
VAN1LED12NW
PNL A NOTE:
ADD A SQUARE D QO115 BREAKER AND SZ 0.5EMT,
2#14&1#14 GND CIRCUIT FOR NEW LIGHTING AND
RECEPTACLE CIRCUIT.
LOOKING SOUTH TOWARD SHED
PAD AREA
DRAWN
DESIGNER
STAMPS, LOGOS, AND SEALS
PROJECT NAME
DRAWING TITLE
CHECKED
ARCHIVE NO.DATE
PROJECT NO.
DRAWING SHEET NO.
DATENO.
REVISION / ISSUE
OFSHEET
United States Department of Agriculture Forest Service
3/5 /24
:5
0 S
AB
RO
W
N X:
\S
AW
TO
OT
H\
BI
GS
MO
KY
NO
RT
HH
YB
RI
D.
\D
W G\
BI
GS
MO
KY
NH
YB
.D W
G;
REGION 4
INTERMOUNTAIN REGION
BIG SMOKY
NORTH SITE
HYBRID
ELECTRIC
SAWTOOTH NATIONAL
FOREST
FAIRFIELD DISTRICT
SITE PLAN AND
GENERATOR BUILDING
03/05/2024
S.BROWN
S.BROWN
R.ANDERSON
E-2 3 5
Approved: x
SHED (GENERATOR
BUILDING)
SITE PLAN
N
N
BI
G
S M
O
KY
R O
AD
BIG SM
OKY W
ORK CENTER RD
FR 70
GENERATOR PAD AND
GENERATOR, WITH AC
FEEDER AND START
CIRCUIT NOT SHOWN
NEW HANDHOLE
NEW EAST PV ARRAY
PV DC FEEDER
EXISTING ARRAY
LOCATION, SEE PHOTO
NEW
WEST PV
ARRAY
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text S
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text V
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text P
AutoCAD SHX Text A
AutoCAD SHX Text R
AutoCAD SHX Text T
AutoCAD SHX Text M
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text T
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text A
AutoCAD SHX Text G
AutoCAD SHX Text R
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text U
AutoCAD SHX Text L
AutoCAD SHX Text T
AutoCAD SHX Text U
AutoCAD SHX Text R
AC
IN
L
EG
AC
IN
L
EG
AC
O
U T
LE
G
AC
O
U T
LE
G
AC
G
R O
U N
D
AC
N
EU
TR
AL
PV
A
R R
AY
R
TS
D C
G R
O U
N D
FLEXWARE SYSTEM AND BALANCE OF
SYSTEM COMPONENTS ONE-LINE
SCHEMATIC
OUTBACK POWER INTEGRATED BATTERY
RACK IBR-3-48-175 (DESIGNED AND COMES
WITH DISCONNECTS AND CONNECTIONS FOR
12 BATTERIES IN 3 GROUPS OPERATING AT
48VDC, THE TOP ROW SHALL BE UNUSED FOR
ADDITIONAL FUTURE BATTERIES, LABEL TOP
ROW BREAKER "UNUSED-KEEP OFF")
8 BATTERIES NORTHSTAR NSB190FT BLUE+
12VDC NOMINAL (180 AHR @ 8 HR RATE, 6000
AIC, CHARGE 14.1V, FLOAT 13.6/13.7V,
CONDITIONING CHARGE 14.4V @ 25°C, TEMP
COMPENSATION -2mV/°C).
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
B+ B- PV- PV+OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
BY
PA
SS
O U
TP
U
T
IN
PU
T
MASTER INVERTER
SLAVE INVERTER
MATE
IN
VE
R
TE
R O
N /O
FF
AU
X
XC
T
B+ B- PV- PV+
CHARGE
CONTROLLER 1
(WEST ARRAY)
CHARGE
CONTROLLER 2
(EAST ARRAY)
M
AS
TE
R
IN
VE
R
TE
R
SL
AV
E
IN
VE
R
TE
R
DC NEG
DC POS
C H
AR
G
E C
O N
TR
O
LL
ER
FN
D
C
OFF
ON
G
FP
D
SZ 0.75C,2#8&1#8GND.
COMBINER
ARRAY EXTERNAL
DISCONNECT
ARRAY: 4 MODULES TOTAL, 2 PARALLEL STRING OF 2 MODULES IN
SERIES, ARRAY TOTAL = 1520 WATTS (4000 WATTS IS PRACTICAL LIMIT).
MODULES SHALL MEET THE FOLLOWING REQUIREMENTS: BUY AMERICAN
ACT COMPLIANT, Vmp > 29 VDC, Voc < 46.5 VDC, RATED OUTPUT AT STC
>= 380 WATTS, POWER TOLERANCE >= 0%, MINIMUM LOAD CERTIFIED
5400 PA FRONT AND 2400 PA BACK, MINIMUM 25 YEAR LINEAR
WARRANTY TO 82.5% AND 12 YEARS ON WORKMANSHIP, RATED FOR 20
AMP FUSE MINIMUM.
COMBINER: OUTBACK FLEXWARE COMBINER FWPV-8 WITH 2 DIN-15-DC
BREAKERS EACH, OR, MIDNITE SOLAR MNPV3 WITH 2 MNEPV15.
ARRAY EXTERIOR DISCONNECT - SQUARE D HEAVY DUTY SAFETY
SWITCH H222NRB WITH 30 AMP FUSES, USE SOLID NEUTRAL AS GROUND
AND BOND TO ENCLOSURE OR INSTALL WITH GROUND KIT.
GROUND MODULES AND MOUNTING SYSTEM WITH GROUNDING LUGS
PER MANUFACTURERS REQUIREMENTS USING 8 AWG BARE SOLID
GROUND TO A SYSTEM GROUNDING BAR ON THE EXTERIOR OF THE
COMBINER BOX.
CONNECTIONS TO COMBINER BOXES SHALL USE 10 AWG, SUNLIGHT
RESISTANT USE-2 OR PV WITH PROPER LOCKING CONNECTORS FOR
CONNECTIONS TO SOLAR MODULES.
SZ 0.75C,2#8&1#8GND.
FLEXWARE SYSTEM, OUTBACK
POWER FP2-VFXR3648A-01
(INVERTERS, CHARGE CONTROLLER,
HUB, MATE, AND BREAKERS.
FACTORY WIRING NOT SHOWN, SOME
ASSEMBLY REQUIRED).
SYSTEM REQUIRES SETUP AND
PROGRAMMING:
SETUP FOR THE BATTERIES CALLED
FOR OR APPROVED INCLUDING
TEMPERATURE COMPENSATION.
AUTOMATIC GENERATOR START,
12HR START - VOLTAGE @42VDC, 2HR
START - VOLTAGE @ 48.8VDC, AND
30MIN START - VOLTAGE @ 50VDC;
QUIET TIME FROM 11:00 PM UNTIL 5:30
AM.
OUTPUT VOLTAGE SET AT 120/240
VAC AT NO LOAD.
KEEP BREAKER OFF FOR CHARGE
CONTROLLER 2 (NOT USED AT THIS
TIME, BUT SHALL BE INSTALLED AND
WIRED AS SHOWN).
SEE FLEXWARE EQUIPMENT
MANUALS FOR OTHER SETTINGS.
SZ 2C,2#3/0&1#6GND.
NEW GENERATOR
SZ 1C,3#6&1#8GND.
EXISTING
DISTRIBUTION
PANELBOARD
SZ 1C,3#6&1#8GND.
NEUTRAL
BONDING
OCCURS
HERE ALONG
WITH
CONNECTION
TO GEC AND
SYSTEM
C BA
GENERATOR AUTO START CONTACT
RELAY, SQUARE D CLASS 8501
KUD12V51 WITH SOCKET AND METAL
NEMA 12, SCREW COVER ENCLOSURE
SZ 0.5C,2#12
GENERATOR 2-WIRE AUTOSTART CIRCUIT
HH
SZ 1.5C,4#8&1#8GND.
8"x12" MINIMUM
HANDHOLE, SEE SPECS
N.I.C. - NOTES FOR FUTURE EXPANSION:
TWO DUPLICATE ARRAYS TO THE EXISTING ARRAY(S) RATED 2000 WATTS
OR LESS, PER CHARGE CONTROLLER, MAY BE INSTALLED. THAT WOULD
BE 4 MOUNTING POLES FOR THE ENTIRE SYSTEM. ADDING SECOND
ARRAY TO INCLUDE PULLING ADDITIONAL 2#8 IN CONDUIT FROM
FLEXWARE TO HANDHOLE, AND WIRING TO FUTURE CHARGE
CONTROLLER, THE SAME AS ORIGINAL. ADD THIRD AND FORTH ARRAYS
BY ADDING A TAPS FROM THE FIRST AND SECOND ARRAY FEEDERS AT
THE HANDHOLE RESPECTIVELY TO THE NEW ARRAYS.
ADDITIONAL BATTERY BANKS MAY BE ADDED FOR STORAGE. BATTERIES
MUST BE SAME MAKE, MODEL, AND USAGE AGE AS THE EXISTING BANKS.
PARALLEL CONNECT TO EXISTING BANK, NO INCREASE IN CONDUCTOR
SIZE REQUIRED.
TWO REQUIRED
PREAPPROVED MODULE MANUFACTURERS
MANUFACTURER WEBSITE PART # SIZE (INCHES) SPECIAL CONSIDERATIONS
HELIENE www.heliene.com 108HC M10 SL 380 67.8" x 44.65" TOP-OF-MOUNT SIZE COORDINATION REQ'D MISSION SOLAR ENERGY www.missionsolar.com MSE PERC66 390 73.1" x 41.5" TOP-OF-MOUNT SIZE COORDINATION REQ'D SILFAB SOLAR www.silfabsolar.com SIL-380 BK 70.7" x 39" SOLARIA www.solaria.com - Maximum Voc exceeded for site SUNSPARK TECH. INC. sunsparkusa.com SST 7F 54M(H)-400 67.8" x 44.65" TOP-OF-MOUNT SIZE COORDINATION REQ'D
DRAWN
DESIGNER
STAMPS, LOGOS, AND SEALS
PROJECT NAME
DRAWING TITLE
CHECKED
ARCHIVE NO.DATE
PROJECT NO.
DRAWING SHEET NO.
DATENO.
REVISION / ISSUE
OFSHEET
United States Department of Agriculture Forest Service
3/5 /24
:2
5 S
AB
RO
W
N X:
\S
AW
TO
OT
H\
BI
GS
MO
KY
NO
RT
HH
YB
RI
D.
\D
W G\
BI
GS
MO
KY
NH
YB
.D W
G;
REGION 4
INTERMOUNTAIN REGION
BIG SMOKY
NORTH SITE
HYBRID
ELECTRIC
SAWTOOTH NATIONAL
FOREST
FARIFIELD DISTRICT
FLEXWARE SYSTEM
03/05/2024
S.BROWN
S.BROWN
R.ANDERSON
E-3 4 5
Approved: x
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text S
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text V
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text P
AutoCAD SHX Text A
AutoCAD SHX Text R
AutoCAD SHX Text T
AutoCAD SHX Text M
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text T
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text A
AutoCAD SHX Text G
AutoCAD SHX Text R
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text U
AutoCAD SHX Text L
AutoCAD SHX Text T
AutoCAD SHX Text U
AutoCAD SHX Text R
HORIZONTAL
HYBRID SOLAR ARRAY AND SUPPORT
43°
15" MIN
4 SOLAR MODULES
TOP-OF-POLE MOUNT,
PREFORMED LINE PRODUCTS
(404-461-5200, plp.com) POWERFAB
#TPM4-H-RENOGY-RNG320P-HWV
GRADE LEVEL
CONCRETE
4" GRAVEL IN
BOTTOM OF HOLE
FOR DRAINAGE
16.5-FOOT 6"Ø
GALVANIZED STEEL
SCHED 40 PIPE
CONCRETE NOTES
1- SEE SITE PLAN, SHEET E-2, FOR POLE LOCATIONS.
2- ENSURE ELECTRICAL CONDUIT IS INSTALLED WITHIN CONCRETE BASE.
3- COMPACT SUBGRADE TO REQUIRED ELEVATION BEFORE PLACING THE
POLE AND CONCRETE.
4- CONCRETE REQUIREMENTS:
3750 PSI CONCRETE @ 28 DAYS MINIMUM
CLASS A CONCRETE:
6.5 BAGS/CY MINIMUM
MAXIMUM WATER/CEMENT RATIO - 5.5 GAL/BAG
COARSE AGGREGATE SIZE RANGE 1-1/2" TO #4 STANDARD OR 1" TO
#4 ALTERNATIVE
SLUMP RANGE: 1" TO 3" FOR STANDARD COARSE AGGREGATE AND
2" TO 4" FOR ALTERNATIVE AGGREGATE
REQUIRED ENTRAINED AIR: 4% TO 6%
7- POUR CONCRETE AT TEMPERATURE ABOVE 35° FAHRENHEIT KEEP
CONCRETE TEMPERATURE OVER 50° FOR 5 DAYS.
8- BACKFILL AREA AROUND FOOTING WITH ROCK FREE EXCAVATED
MATERIAL (2-INCH MINUS) AND COMPACT TO AT LEAST 95% MAXIMUM
DENSITY.
9- INSTALL WITH ARRAY, MOUNTING DEVICES AND ALL OTHER NEEDED
EQUIPMENT AS CALLED FOR.
" M
IN
CONDUIT AS CALLED FOR
DISCONNECT
COMBINER BOX
12" #3 REBAR WELDED
TO PIPE TO PREVENT
TURNING, GALVANIZE
PAINT
PLAN VIEW
A
GENERATOR PAD NOTES
SL
O
PE
GENERATOR PAD DETAIL
NOT TO SCALE
LOCATION AND ELEVATION OF GENERATOR SLAB WILL BE STAKED BY THE CONTRACTOR AND
APPROVED BY THE CONTRACTING OFFICER PRIOR TO CONSTRUCTION.
MECHANICALLY COMPACT SUB-GRADE PRIOR TO FORMING AND CONSTRUCTING CAST-IN-PLACE
CONCRETE PADS PER SPECIFICATIONS, OR SETTING PRECAST PADS.
FINAL GRADE AROUND SLAB SHALL DRAIN AWAY FROM PADS A MINIMUM OF 2% (3H:1V MAXIMUM) FOR A MINIMUM OF 5 FEET IN ALL DIRECTIONS EXCEPT THE SHED SIDE WHICH SHALL SLOPE EAST
AND WEST FROM CENTERLINE BETWEEN THEM.
CONTRACTOR SHALL VERIFY THE DIMENSIONS OF THE GENERATOR AND FUEL TANK TO BE
SUPPLIED PRIOR TO BEGINNING CONSTRUCTION. COORDINATE THE LOCATION OF ANCHOR
BOLTS, ELECTRICAL FEEDER, AND AUTOSTART CIRCUIT. LOCATIONS SHOWN ARE NOT
ACCURATE. PAD SIZE IS BASED ON CALLED FOR GENERATOR AND SHALL BE ADJUSTED LARGER
FOR LARGER GENERATOR SUBSTITUTIONS.
6" MIN. COMPACTED CRUSHED
AGGREGATE BASE, 3/4" MINUS, PLACED
ON COMPACTED NATIVE SOIL
A
SECTION A-A
NOT TO SCALE
6"
#4 REBAR
CONCRETE SLAB
NOTE-1.
NOTE-2.
NOTE-3.
NOTE-4.
1C AND 0.5C ELECTRICAL
POWER AND GENERATOR
START CIRCUIT STUB-UPS,
SEE NOTES
WEDGE ANCHOR, SIMPSON STRONG BOLT
#STB50512 (1/2" x 5-1/2") EMBED 3-7/8" DEEP
(TYPICAL OF 4 FOR GENERATOR MOUNTING),
SEE NOTES
#4 REBAR, 12" O.C.
BOTH DIRECTIONS
LIGHTLY COMPACTED NATIVE
FILL OR AGGREGATE
FINAL GRADE, SEE NOTE 3
FINAL GRADE BUILDING
SIDE, SEE NOTE 3
12'-6"
7' -0
TWO REQUIRED, NOT TO SCALE
2"
DRAWN
DESIGNER
STAMPS, LOGOS, AND SEALS
PROJECT NAME
DRAWING TITLE
CHECKED
ARCHIVE NO.DATE
PROJECT NO.
DRAWING SHEET NO.
DATENO.
REVISION / ISSUE
OFSHEET
United States Department of Agriculture Forest Service
3/5 /24
:4
1 S
AB
RO
W
N X:
\S
AW
TO
OT
H\
BI
GS
MO
KY
NO
RT
HH
YB
RI
D.
\D
W G\
PO
LE
MO
UN
TI
NG
.D W
G;
REGION 4
INTERMOUNTAIN REGION
BIG SMOKY
NORTH SITE
HYBRID
ELECTRIC
SAWTOOTH NATIONAL
FOREST
FAIRFIELD DISTRICT
GENERATOR PAD AND
ARRAY MOUNTING
03/05/2024
S.BROWN
S.BROWN
R.ANDERSON
D-1 5 5
Approved:
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text S
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text V
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text P
AutoCAD SHX Text A
AutoCAD SHX Text R
AutoCAD SHX Text T
AutoCAD SHX Text M
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text T
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text A
AutoCAD SHX Text G
AutoCAD SHX Text R
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text U
AutoCAD SHX Text L
AutoCAD SHX Text T
AutoCAD SHX Text U
AutoCAD SHX Text R
PROJECT LOCATION
SHEET OF
United States Department of Agriculture Forest Service
INDEX OF SHEETS
SHEET SHEET TITLE DATE
01 COVER SHEET 3/28/2024
RECOMMENDED BY:
STAFF ENGINEER
FOREST ENGINEER
DATE
(R04) INTERMOUNTAIN REGION
SAWTOOTH NATIONAL FOREST
CAMAS COUNTY
IDAHO
BIG SMOKY WORK CENTER BUILDING
FOUNDATION CONSTRUCTION
Braidy K. Richins, PE 3/28/2024
DATE
BUILDING SITE PLAN
Shawn Robnett, PE 3/28/2024
FOUNDATION PLANS & DETAILS
3/28/2024
3/28/2024
BIG SMOKY WORK CENTER
OPTION ITEM #1
DRAWN
DESIGNER
STAMPS, LOGOS, AND SEALS
PROJECT NAME
DRAWING TITLE
CHECKED
ARCHIVE NO.DATE
PROJECT NO.
DRAWING SHEET NO.
DATENO.
REVISION / ISSUE
OFSHEET
United States Department of Agriculture Forest Service
C:
\U
SE
RS
\B
KR
IC
HI
NS
\O
NE
DR
IV
E
- U
SD
A\
DO
CU
ME
NT
S\
RI
CH
IN
SF
IL
ES
\P
RO
JE
CT
S\
P
RO
JE
CT
S\
BI
GS
MO
KY
EL
EC
TR
IC
AL
&F
OU
ND
AT
IO
NI
MP
RO
VE
ME
NT
S2
4\F
OU
ND
AT
IO
NS
\B
IG
SM
OK
YF
OU
ND
AT
IO
N_
BA
SE
.D W
G
(R04)
INTERMOUNTAIN REGION
BIG SMOKY
FOUNDATION
CONSTRUCTION
SAWTOOTH
NATIONAL FOREST
FAIRFIELD RANGER DISTRICT
BUILDING
SITE PLAN
03/28/2024
S.ROBNETT
B.RICHINS
S.ROBNETT
2 3
BIG SMOKY WORK CENTER - SITE PLAN
NOT TO SCALE
NORTH BUILDING
NOT TO SCALE
SOUTH BUILDING
NOT TO SCALE
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text S
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text V
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text P
AutoCAD SHX Text A
AutoCAD SHX Text R
AutoCAD SHX Text T
AutoCAD SHX Text M
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text T
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text A
AutoCAD SHX Text G
AutoCAD SHX Text R
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text U
AutoCAD SHX Text L
AutoCAD SHX Text T
AutoCAD SHX Text U
AutoCAD SHX Text R
AutoCAD SHX Text E
N
18'-0"
32'-0"
EQ
EQ
5'-0" 5'-0" 5'-0" 5'-0"
15" WIDE, 8" DEEP FOOTING WITH TWO #4
CONTINUOUS REBAR. FOOTING SHALL
BE SET ON PREPARED SUBGRADE.
CONCRETE PAD WITH STEEL PIER (TYP)
(2) 8"x16" FOUNDATION VENTS, ONE AT EACH END AS SHOWN
2'-6"
2'-6"
ENDS:
INSTALL (5) "SIMPSON" MASA
ANCHORS @ EVEN SPACING.
SIDES:
INSTALL (7) "SIMPSON" MASA
ANCHORS @ EVEN SPACING.
GENERAL FOUNDATION NOTES:
1. VERIFY EXISTING BUILDING DIMENSIONS PRIOR TO CASTING NEW FOUNDATIONS. ADJUST FOUNDATION LAYOUT TO MATCH AS NECESSARY TO ENSURE OUTSIDE
FOUNDATION WALL FACE AND OUTSIDE/END PRIMARY SUPPORT TIMBER FACE MATCH.
2. CONTRACTOR HAS OPTION TO INSTALL CONTINUOUS CONCRETE PAD FOR CENTER STEEL PIER SUPPORTS. COORDINATE WITH CONTRACTING OFFICER.
3. EXISTING BUILDINGS ARE COMPRISED OF THREE PRIMARY SUPPORT TIMBERS THAT RUN THE LENGTH OF EACH BUILDING; ONE ON EACH SIDE AND ONE EVENLY SPACED BETWEEN RUNNING DOWN THE MIDDLE. CONTRACTOR SHALL FIELD INSTALL TIMBER SUPPORTS ON EACH SIDE TO FILL THE RESPECTIVE GAPS BETWEEN
THESE THREE EXISTING PRIMARY TIMBER SUPPORTS.
4. THE UTILITIES TO EACH BUILDING CONSIST OF THE FOLLOWING:
· NORTH BUILDING - ELECTRICITY, GAS, AND COMMUNICATIONS (RADIO AND SATELLITE DISH)
· SOUTH BUILDING - ELECTRICITY, GAS, WATER, AND SEWER.
18'-0"
28'-0"
EQ
EQ
5'-0" 5'-0" 5'-0" 5'-0"4'-0" 4'-0"
15" WIDE, 8" DEEP FOOTING WITH TWO #4
CONTINUOUS REBAR. FOOTING SHALL
BE SET ON PREPARED SUBGRADE.
CONCRETE PAD WITH STEEL PIER (TYP)
(2) 8"x16" FOUNDATION VENTS, ONE AT EACH END AS SHOWN
2'-6"
2'-6"
ENDS:
INSTALL (5) "SIMPSON" MASA
ANCHORS @ EVEN SPACING.
SIDES:
INSTALL (7) "SIMPSON" MASA
ANCHORS @ EVEN SPACING.
6'-0" 6'-0"
2'-8"
1'-3"
8"
2'-6"
6"
8" WIDE x 2'-6" TALL
CONCRETE
FOUNDATION WALL
WITH #4 VERTICAL
BARS AT 18" O.C.
(ALTERNATE BENDS
IN FOOTING)
CONTINUOUS CONCRETE FOOTING
WITH (2) #4 CONTINUOUS REBAR
FINISHED GRADE
#4, CONT.
"SIMPSON" MASA ANCHOR. SEE
FOUNDATION PLAN FOR SPACING
EXISTING BUILDING TIMBER
VAPOR
RETARDER
EXISTING FLOOR JOIST
16" SQUARE
STEEL ADJUSTABLE
PIER. ANCHOR INTO
CONCRETE PAD WITH
(2) 12d POWER NAILS
16"x16"x4"(MIN)
CONCRETE PAD PER
SPACING ON FOUNDATION
PLAN
EXISTING BUILDING TIMBER
VAPOR RETARDER OVER
ENTIRE CRAWLSPACE.
4" (MIN)
FASTEN TO EXISTING
BUILDING SUPPORT
TIMBER WITH (1) 12d
RING SHANK NAIL
EXISTING FLOOR JOIST
DRAWN
DESIGNER
STAMPS, LOGOS, AND SEALS
PROJECT NAME
DRAWING TITLE
CHECKED
ARCHIVE NO.DATE
PROJECT NO.
DRAWING SHEET NO.
DATENO.
REVISION / ISSUE
OFSHEET
United States Department of Agriculture Forest Service
C:
\U
SE
RS
\B
KR
IC
HI
NS
\O
NE
DR
IV
E
- U
SD
A\
DO
CU
ME
NT
S\
RI
CH
IN
SF
IL
ES
\P
RO
JE
CT
S\
P
RO
JE
CT
S\
BI
GS
MO
KY
EL
EC
TR
IC
AL
&F
OU
ND
AT
IO
NI
MP
RO
VE
ME
NT
S2
4\F
OU
ND
AT
IO
NS
\B
IG
SM
OK
YF
OU
ND
AT
IO
N_
BA
SE
.D W
G
(R04)
INTERMOUNTAIN REGION
BIG SMOKY
FOUNDATION
CONSTRUCTION
SAWTOOTH
NATIONAL FOREST
FAIRFIELD RANGER DISTRICT
FOUNDATION
PLANS & DETAILS
03/28/2024
S.ROBNETT
B.RICHINS
S.ROBNETT
3 3
FOUNDATION PLAN #1 (NORTH BUILDING)
EXTERIOR FOUNDATION & ANCHOR DETAIL
FOUNDATION PLAN #2 (SOUTH BUILDING)
FLOOR MIDSPAN SUPPORT
NOT TO SCALE NOT TO SCALE
NOT TO SCALENOT TO SCALE
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text S
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text V
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text P
AutoCAD SHX Text A
AutoCAD SHX Text R
AutoCAD SHX Text T
AutoCAD SHX Text M
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text T
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text A
AutoCAD SHX Text G
AutoCAD SHX Text R
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text U
AutoCAD SHX Text L
AutoCAD SHX Text T
AutoCAD SHX Text U
AutoCAD SHX Text R
VICINITY MAP
TRAVEL DIRECTIONS:
SHEET OF
United States Department of Agriculture Forest Service
1 5
FROM THE FAIRFIELD RANGER DISTRICT OFFICE, TRAVEL NORTH ON 1ST STREET 148 FT TO POPLAR AVE AND TURN LEFT ON TO POPLAR AVE AND HEAD WEST FOR 472 FT TO TURN RIGHT ONTO CENTER STREET/SOLDIER ROAD, CONTINUE 1.8 MILES AND TURN RIGHT (EAST) FOR 0.3 MILES AND TURN RIGHT (NORTH) TO REMAIN ON SOLDIER CREEK ROAD AND CONTINUE FOR 4.1 MILES. TURN LEFT (WEST) TO STAY ON SOLDIER CREEK ROAD AND FOLLOW FOR 3.6 MILES. TAKE A SLIGHT RIGHT ONTO COUCH SMT ROAD/NF-94 FOR 4.4 MILES AND TURN RIGHT TO KEEP ON SAME ROAD FOR 10 MILES.
TURN RIGHT AT THE EXTENDED 4 CORNER INTERSECTION TO HEAD NORTHEAST ON BIG SMOKY ROAD FOR 0.7 MILES AND TURN LEFT ONTO BIG SMOKY WORK CENTER ROAD FOR 0.5 MILES AND TURN LEFT
ONTO FOREST ROAD 70086 TO ARRIVE AT THE SOUTH BIG SMOKY ADMINISTRATION SITE.
43° 37' 05.80" NORTH LATITUDE AND 114° 52' 04.50" WEST LONGITUDE, ELEVATION 5590 FEET.
FARIFIELD DISTRICT OFFICE
102 1ST STREET
FAIRFIELD, IDAHO 83327
RECOMMENDED BY:
APPROVED:
FOREST ENGINEER
DISTRICT RANGER DATE
DATE
DIRECTOR OF ENGINEERING OR ASSISTANT DATE
FOREST SUPERVISOR DATE
3/2 8/2
4 1 1:
B
KR
IC
HI
NS
C :\U
SE
RS
\B
KR
IC
HI
NS
\O
NE
DR
IV
E
- U
SD
A\
DO
CU
ME
NT
S\
RI
CH
IN
SF
IL
ES
\P
RO
JE
CT
S\
P
RO
JE
CT
S\
BI
GS
MO
KY
EL
EC
TR
IC
AL
&F
OU
ND
AT
IO
NI
MP
RO
VE
ME
NT
S2
4\E
LE
CT
RI
CA
L\
RE
VI
EW
SU
BM
IT
TA
L_
SO
UT
H\
BI
GS
MO
KY
SH
YB
CV
R.
DW
G;
IDAHO
CAMAS COUNTY
R-4 INTERMOUNTAIN REGION
SAWTOOTH NATIONAL FOREST
FAIRFIELD RANGER DISTRICT
BIG SMOKY SOUTH SITE HYBRID ELECTRIC
BIG SMOKY SOUTH SITE
IDAHO
IDAHO
INDEX OF SHEETS
SHEET SHEET TITLE DATE
COVERSHEET (G-1) 03/04/24
GENERAL LAYOUT, SIGNS, AND ARRAY
SUPPORT (E-1) 03/04/24
SITE PLAN AND GENERATOR BUILDING (E-2) 03/04/24
FLEXWARE SYSTEM (E-3) 3/5/2024
GENERATOR PAD AND ARRAY MOUNTING
(D-1) 3/4/2024
OPTION ITEM #2
Shawn Robnett, PE
Mathew Filbert
Jake Strohmeyer
3/5/24
3/5/24
3/6/24
Scott Bingham, PE 3/28/24
AutoCAD SHX Text
PROJECT LOCATION
AutoCAD SHX Text
BONNERS FERRY
AutoCAD SHX Text
SANDPOINT
AutoCAD SHX Text
COEUR D'ALENE
AutoCAD SHX Text
MOSCOW
AutoCAD SHX Text
LEWISTON
AutoCAD SHX Text
GRANGEVILLE
AutoCAD SHX Text
WHITE BIRD
AutoCAD SHX Text
RIGGINS
AutoCAD SHX Text
NEW MEADOWS
AutoCAD SHX Text
COUNCIL
AutoCAD SHX Text
YELLOW PINE
AutoCAD SHX Text McCALL
AutoCAD SHX Text
CASCADE
AutoCAD SHX Text
NORTH FORK
AutoCAD SHX Text
SALMON
AutoCAD SHX Text
LEADORE
AutoCAD SHX Text
STANLEY
AutoCAD SHX Text
CLAYTON
AutoCAD SHX Text
CHALLIS
AutoCAD SHX Text
MACKAY
AutoCAD SHX Text
LOWMAN
AutoCAD SHX Text
WEISER
AutoCAD SHX Text
EMMETT
AutoCAD SHX Text
IDAHO CITY
AutoCAD SHX Text
KETCHUM
AutoCAD SHX Text
BOISE
AutoCAD SHX Text
FAIRFIELD
AutoCAD SHX Text
MOUNTAIN HOME
AutoCAD SHX Text
BUHL
AutoCAD SHX Text
TWIN FALLS
AutoCAD SHX Text
BURLEY
AutoCAD SHX Text
DUBOIS
AutoCAD SHX Text
ISLAND PARK
AutoCAD SHX Text
ST. ANTHONY
AutoCAD SHX Text
ASHTON
AutoCAD SHX Text
DRIGGS
AutoCAD SHX Text
IDAHO FALLS
AutoCAD SHX Text
POCATELLO
AutoCAD SHX Text
SODA SPRINGS
AutoCAD SHX Text
MALAD
AutoCAD SHX Text
MONTPELIER
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
GENERATOR NOTES
1. EXISTING GENERATOR SYSTEM (INCLUDES FLEXIBLE FUEL, EXHAUST, AND VENTILATION
SYSTEMS) SHALL BE REMOVED FROM BUILDING AND SHALL REMAIN THE PROPERTY OF THE
GOVERNMENT. THE CONTRACTOR SHALL BE RESPONSIBLE FOR LOADING IT IN A
GOVERNMENT VEHICLE OR PLACING IT AT A LOCATION NOTED BY THE GOVERNMENT ON THIS
SITE.
2. INSTALL PAD AND KOHLER GENERATOR, MODEL 15REOZK, 60 HZ, 1 PHASE, 120/240 V, 14.0 KW
PRIME (105°C RISE), DIESEL, AND WEATHER ENCLOSURE MOUNTED ON 168 GALLON SUBBASE
FUEL TANK. SUPPLY WITH MAIN BREAKER, PRIME POWER SWITCH, STARTING BATTERY AND
CHARGER, STANDARD CONTROL FEATURES, AND ALL APPURTENANCES READY FOR
OPERATION. 2-YEAR WARRANTY. SUBBASE FUEL TANK INCLUDES I-BEAMS FOR GROUND
CLEARANCE, 5 GALLON FUEL FILL SPILL CONTAINMENT, AND COMBUSTIBLE LIQUIDS DECAL.
3. ENSURE GROUND AND NEUTRAL ARE NOT BONDED AT THE GENERATOR. SYSTEM NEUTRAL
BOND TO OCCUR ELSEWHERE (PER NOTE 11).
4. AUTOSTART CIRCUIT: CONNECT REMOTE CIRCUIT TO TERMINALS 3 AND 4.
5. PROVIDE FULL STARTUP SERVICE COORDINATING WITH FLEXWARE STARTUP SERVICE.
GENERAL LAYOUT ONE-LINE
SCHEMATIC
AC FEEDER
GENERATOR START
PV DC FEEDER
AC LOADS
DC POWER
GROUND, SEE
SPECIFICATIONS
NEW
GENERATOR
FLEXWARE
BATTERIES
NOTES:
GENERATOR IS CALLED OUT ON THIS SHEET. MOUNTING
PAD IS ON SHEET D-1. SITE PLAN, SHEET E-2.
PV ARRAY CALLED OUT ON SHEET E-3. MOUNTING IS ON
SHEET D-1. SITE PLAN, SHEET E-2.
INSTALL FEEDER FROM GENERATOR INTO FLEXWARE
SYSTEM. SEE SHEET E-3.
INSTALL GENERATOR START/RUN CIRCUIT IN SEPARATE
CONDUIT FROM GENERATOR POWER CIRCUIT TO
GENERATOR. SEE SHEET E-3, AND, FLEXWARE AND
GENERATOR DOCUMENTATION.
DC FEEDER CIRCUIT FROM ARRAY TO FLEXWARE
SYSTEM. SEE SHEETS E-2 AND E-3.
FLEXWARE SYSTEM WITH ALL EQUIPMENT AS SHOWN ON
SHEET E-3 . PROVIDES DC BATTERY CHARGING FROM
GENERATOR AND PV POWER SOURCES, DC INVERTER TO
120/240 VAC, AND GENERATOR CONTROL. FLOOR -PLAN,
SHEET E-2.
EXISTING GROUNDING ELECTRODE SYSTEM. SEE NOTE
11.
CONDUIT SLEEVED BATTERY CONNECTION, SEE SHEET
E-3.
BATTERY BANK AND MOUNTING RACK. SEE SHEET E-2
AND E-3.
120/240 VAC FEEDER. SEE SHEET E-3.
EXISTING DISTRIBUTION PANELBOARD. INSTALL WITH
NEUTRAL TO GROUND BONDING FOR THE ENTIRE
SYSTEM. REWORK OR REPLACE THE GEC TO THE
EXISTING GROUNDING ELECTRODE SYSTEM.
EXISTING
PANELBOARD
REQUIRED SIGNS (MOUNTING LOCATION), 0.5-INCH MINIMUM
HIGH TEXT
"STRUCTURE SERVED WITH STAND ALONE PHOTOVOLTAIC SYSTEM.
PV DISCONNECT LOCATED ON ARRAY POLE JUST TO THE NORTH OF
THIS BUILDINGS." (MOUNT ON SHED DOOR.)
"MAXIMUM DC VOLTAGE = 117 VDC
MAXIMUM ARRAY CURRENT = 28.8 ADC
MAXIMUM RATED CURRENT OUTPUT OF EACH CHARGE CONTROLLER =
80 AMPS"
(MOUNT ON SHED DOOR AND AT FLEXWARE SYSTEM)
"WARNING: ELECTRICAL SHOCK HAZARD - TERMINALS ON THE LINE
AND LOAD SIDES MAY BE ENERGIZED IN THE OPEN POSITION" (MOUNT
ON FLEXWARE SYSTEM DISCONNECT COVER)
"PV SYSTEM MAIN DISCONNECTS - 1 OF 2 (ARRAY)" (MOUNT ON COVER
BY DISCONNECT MEANS ON FLEXWARE SYSTEM)
"PV SYSTEM MAIN DISCONNECT - 2 OF 2 (BATTERY)" (MOUNT ON
COVER BY DISCONNECT MEANS ON FLEXWARE SYSTEM)
"DANGER - GENERATOR STARTS AUTOMATICALLY AND WITHOUT
WARNING. TURN GENERATOR OFF AT GENERATOR CONTROL BEFORE
WORKING ON IT." (MOUNT ON GENERATOR AND FLEXWARE SYSTEM)
"WARNING - DC ARC FLASH HAZARD APPROPRIATE PPE REQUIRED
NOMINAL VOLTAGE: 48 VOLTS DC. 6,000 AMPERES ARE AVAILABLE AT
THE BATTERY TERMINALS. 11,700 AMPERES ARE AVAILABLE AT THE
BATTERY BANK. 10,050 AMPERES ARE AVAILABLE AT THE FLEXWARE
EQUIPMENT. CALCULATED 11/21/2023. (MOUNT ABOVE BATTERY BANK)
MULTIPLE POWER SOURCE WARNING SIGNS, SEE SECTION 260553 -
IDENTIFICATION FOR ELECTRICAL SYSTEMS (MOUNT ON FLEXWARE
SYSTEM, GENERATOR START RELAY ENCLOSURE, AND BATTERY
BANK)
WORKING CLEARANCE SIGNS, SEE SECTION 260553 - IDENTIFICATION
FOR ELECTRICAL SYSTEMS (MOUNT AT FLEXWARE SYSTEM, BATTERY
BANK, AND EXITING DISTRIBUTION PANELBOARD)
"HAZARD: THIS BUILDING IS NOT A STORAGE AREA." (ONE SIGN
MOUNT ON CENTER OF REAR WALL ABOVE BATTERY STORAGE <IS
THIS IRONY?>)
"DC CIRCUIT" (MOUNT ON ARRAY CONDUIT (INSIDE AND EXTERIOR TO
BUILDING) AND BATTERY SLEEVE, EVERY 10-FT AND EVERY CONDUIT
BODY AND JUNCTION BOX)
"WARNING - PV POWER SOURCE" (MOUNT ON VISIBLE PORTION OF
ARRAY CONDUIT AT BUILDING EXTERIOR AND INTERIOR)
"PV SYSTEM DISCONNECT - NOT RAPID SHUTDOWN RATED." (MOUNT
ON POLE DISCONNECT COVER)
"WARNING: ELECTRICAL SHOCK HAZARD - TERMINALS ON THE LINE
AND LOAD SIDES MAY BE ENERGIZED IN THE OPEN POSITION" (MOUNT
ON POLE DISCONNECT COVER)
"POWER IS LIMITED AT THIS SITE. ELECTRIC PLUG LOADS SHALL BE
LIMITED TO SMALL LOADS SUCH AS A LAPTOP, UNPLUGGED WHEN NOT
IN USE. LIGHTING SHALL BE TURNED OFF WHEN NOT IN USE." (8
TOTALS, AT ELECTRICALLY POWERED BUILDING WITH ONE SPARE FOR
FUTURE WAREHOUSE, MOUNT AT MAIN ENTRY JUST ABOVE LIGHT
SWITCH)
PROJECT DESCRIPTION
PROJECT INCLUDES A NEW HYBRID POWER SOURCE (GENERATOR AND SOLAR)
AND DISCONNECTING AND DISPOSING THE EXISTING GENERATOR.
PV ARRAY
DRAWN
DESIGNER
STAMPS, LOGOS, AND SEALS
PROJECT NAME
DRAWING TITLE
CHECKED
ARCHIVE NO.DATE
PROJECT NO.
DRAWING SHEET NO.
DATENO.
REVISION / ISSUE
OFSHEET
United States Department of Agriculture Forest Service
3/4 /24
:2
7 S
AB
RO
W
N X:
\S
AW
TO
OT
H\
BI
GS
MO
KY
SO
UT
HH
YB
RI
D.
\D
W G\
BI
GS
MO
KY
SH
YB
.D W
G;
REGION 4
INTERMOUNTAIN REGION
BIG SMOKY
SOUTH SITE
HYBRID
ELECTRIC
SAWTOOTH NATIONAL
FOREST
FARIFIELD DISTRICT
GENERAL LAYOUT,
SIGNS, AND ARRAY
SUPPORT
03/04/2024
S.BROWN
S.BROWN
R.ANDERSON
E-1 2 5
Approved: x
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text S
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text V
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text P
AutoCAD SHX Text A
AutoCAD SHX Text R
AutoCAD SHX Text T
AutoCAD SHX Text M
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text T
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text A
AutoCAD SHX Text G
AutoCAD SHX Text R
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text U
AutoCAD SHX Text L
AutoCAD SHX Text T
AutoCAD SHX Text U
AutoCAD SHX Text R
30' 0 60' 120'
BLOWUP APPROXIMATE
4' M
IN
E
E
E
10'
X X
X X
~33'
~52.5'
BATTERIES
PNL A
SHED FLOOR PLAN
16'8'4'2'02'
FLEXWARE
PROVIDE SURFACE MOUNTED
BLOCKING SECURELY
MOUNTED TO WALL FRAMING
TO MOUNT FLEXWARE TO.
EXISTING PANELBOARD
GENERATOR SHED INTERIORGENERAL PHOTO OF PROPOSED ARRAY
LOCATION (LOOKING WEST)
GENERATOR PAD LOCATION AND
GENERATOR SHED
GENERATOR SHED
LOOKING SOUTHWEST
GENERATOR AND PAD TO BE LOCATED ON NORTH
SIDE OF SHED, REQUIRING SOME EARTHWORK TO
MAKE PAD LEVEL. EDGE OF GENERATOR SHALL
BE 4-FT MINIMUM FROM SHED WALL.
GENERATOR SYSTEM
TO BE REMOVED AND
SALVAGED
EXHAUST SYSTEM TO BE
REMOVED AND SALVAGED
ELECTRICAL
TO BE
REMOVED
GFI
SNEW GFCI DUPLEX RECEPTACLE, 15
AMP, 120 VAC; AND SINGLE POLE
SWITCH. MAY BE IN SAME DEVICE BOX.
NEW LUMINAIRE, RAB
VAN1LED12NW
PNL A NOTES:
REMOVE FEEDER, INSTALL NEW FEEDER FROM FLEXWARE. TERMINATE IN
EXISTING LINE LUGS INSTEAD OF BACK FED MAIN. NEUTRAL BONDING EXISTS
IN PANELBOARD CURRENTLY AND SHALL REMAIN.
REMOVE BREAKER USED AS BACK FED MAIN, ADD A SQUARE D QO115
BREAKER AND SZ 0.5EMT, 2#14&1#14 GND CIRCUIT FOR NEW LIGHTING AND
RECEPTACLE CIRCUIT, INSTALL BREAKER GOOF PLATE.
ADD A SUPPLEMENTAL GROUND ROD PER SPECIFICATION SECTION 260526,
USE A #8 GND.
BATTERY BANK MAY NEED TO BE
ROTATED 90° CLOCKWISE TO
ALLOW ACCESS TO DISCONNECTS
DRAWN
DESIGNER
STAMPS, LOGOS, AND SEALS
PROJECT NAME
DRAWING TITLE
CHECKED
ARCHIVE NO.DATE
PROJECT NO.
DRAWING SHEET NO.
DATENO.
REVISION / ISSUE
OFSHEET
United States Department of Agriculture Forest Service
3/4 /24
:2
7 S
AB
RO
W
N X:
\S
AW
TO
OT
H\
BI
GS
MO
KY
SO
UT
HH
YB
RI
D.
\D
W G\
BI
GS
MO
KY
SH
YB
.D W
G;
REGION 4
INTERMOUNTAIN REGION
BIG SMOKY
SOUTH SITE
HYBRID
ELECTRIC
SAWTOOTH NATIONAL
FOREST
FAIRFIELD DISTRICT
SITE PLAN AND
GENERATOR BUILDING
03/04/2024
S.BROWN
S.BROWN
R.ANDERSON
E-2 3 5
Approved: x
GENERATOR SHED
SITE PLAN N
N
BI
G
S M
O
KY
R O
AD
FR 70086
GENERATOR PAD AND
GENERATOR, WITH AC
FEEDER AND START
CIRCUIT NOT SHOWN
NEW HANDHOLE
PV ARRAY
PV DC FEEDER
FUTURE
PV ARRAY
GENERATOR SHED
EXHAUST SYSTEM TO BE
REMOVED AND DISPOSED,
GOVERNMENT TO REPAIR
SIDING
EXISTING SQUARE
D, QO PANEL A
EXTEND GEC TO A NEW
SUPPLEMENTAL GROUND ROD
NOTE SLOPING GRADE AT
PROPOSED GENERATOR
PAD LOCATION
PV ARRAY
APPROXIMATE
LOCATION
EXISTING FENCE
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text S
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text V
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text P
AutoCAD SHX Text A
AutoCAD SHX Text R
AutoCAD SHX Text T
AutoCAD SHX Text M
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text T
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text A
AutoCAD SHX Text G
AutoCAD SHX Text R
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text U
AutoCAD SHX Text L
AutoCAD SHX Text T
AutoCAD SHX Text U
AutoCAD SHX Text R
AC
IN
L
EG
AC
IN
L
EG
AC
O
U T
LE
G
AC
O
U T
LE
G
AC
G
R O
U N
D
AC
N
EU
TR
AL
PV
A
R R
AY
R
TS
D C
G R
O U
N D
FLEXWARE SYSTEM AND BALANCE OF
SYSTEM COMPONENTS ONE-LINE
SCHEMATIC
OUTBACK POWER INTEGRATED BATTERY
RACK IBR-3-48-175 (DESIGNED AND COMES
WITH DISCONNECTS AND CONNECTIONS FOR
12 BATTERIES IN 3 GROUPS OPERATING AT
48VDC, THE TOP ROW SHALL BE UNUSED FOR
FUTURE POSSIBLE, LABEL TOP ROW
BREAKER "UNUSED-KEEP OFF")
8 BATTERIES NORTHSTAR NSB190FT BLUE+
12VDC NOMINAL (180 AHR @ 8 HR RATE, 6000
AIC, CHARGE 14.1V, FLOAT 13.6/13.7V,
CONDITIONING CHARGE 14.4V @ 25°C, TEMP
COMPENSATION -2mV/°C).
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
B+ B- PV- PV+OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
BY
PA
SS
O U
TP
U
T
IN
PU
T
MASTER INVERTER
SLAVE INVERTER
MATE
IN
VE
R
TE
R O
N /O
FF
AU
X
XC
T
B+ B- PV- PV+
CHARGE
CONTROLLER
CHARGE
CONTROLLER
(for future array)
M
AS
TE
R
IN
VE
R
TE
R
SL
AV
E
IN
VE
R
TE
R
DC NEG
DC POS
C H
AR
G
E C
O N
TR
O
LL
ER
FN
D
C
OFF
ON
G
FP
D
SZ 0.75C,2#8&1#8GND.
COMBINER
ARRAY EXTERNAL
DISCONNECT
ARRAY: 4 MODULES TOTAL, 2 PARALLEL STRING OF 2 MODULES IN
SERIES, ARRAY TOTAL = 1280 WATTS, PROVIDED BY GOVERNMENT FROM
FROM NORTH SITE BUNKHOUSE. EXISTING SOLAR MODULES, RENOGY
RNG-320P: Voc = 46.92 VDC, Ioc = 9.70 A, Vmpp = 38.16 VDC, Imp = 8.38 A.
COMBINER: OUTBACK FLEXWARE COMBINER FWPV-8 WITH 2 DIN-15-DC
BREAKERS EACH, OR, MIDNITE SOLAR MNPV3 WITH 2 MNEPV15.
ARRAY EXTERIOR DISCONNECT - SQUARE D HEAVY DUTY SAFETY
SWITCH H222NRB WITH 30 AMP FUSES, USE SOLID NEUTRAL AS GROUND
AND BOND TO ENCLOSURE OR INSTALL WITH GROUND KIT.
GROUND MODULES AND MOUNTING SYSTEM WITH GROUNDING LUGS
PER MANUFACTURERS REQUIREMENTS USING 8 AWG BARE SOLID
GROUND TO A SYSTEM GROUNDING BAR ON THE EXTERIOR OF THE
COMBINER BOX.
CONNECTIONS TO COMBINER BOXES SHALL USE 10 AWG, SUNLIGHT
RESISTANT USE-2 OR PV WITH PROPER LOCKING CONNECTORS FOR
CONNECTIONS TO SOLAR MODULES, OR APPROVED FLEXIBLE CONDUIT
OR CABLE BASED ON MODULE MANUFACTURERS ALLOWED CONNECTION
METHODS.
SZ 0.75C,2#8&1#8GND.
FLEXWARE SYSTEM, OUTBACK
POWER FP2-VFXR3648A-01
(INVERTERS, CHARGE CONTROLLER,
HUB, MATE, AND BREAKERS.
FACTORY WIRING NOT SHOWN, SOME
ASSEMBLY REQUIRED).
SYSTEM REQUIRES SETUP AND
PROGRAMMING:
SETUP FOR THE BATTERIES CALLED
FOR OR APPROVED INCLUDING
TEMPERATURE COMPENSATION.
AUTOMATIC GENERATOR START,
12HR START - VOLTAGE @42VDC, 2HR
START - VOLTAGE @ 48.8VDC, AND
30MIN START - VOLTAGE @ 50VDC;
QUIET TIME FROM 11:00 PM UNTIL 5:30
AM.
OUTPUT VOLTAGE SET AT 120/240
VAC AT NO LOAD.
KEEP BREAKER OFF FOR CHARGE
CONTROLLER 2 (NOT USED AT THIS
TIME, BUT SHALL BE INSTALLED AND
WIRED AS SHOWN).
SEE FLEXWARE EQUIPMENT
MANUALS FOR OTHER SETTINGS.
SZ 2C,2#3/0&1#6GND.
NEW GENERATOR
SZ 1C,3#6&1#8GND.
EXISTING
DISTRIBUTION
PANELBOARD A
SZ 1C,3#6&1#8GND.
NEUTRAL
BONDING
OCCURS
HERE ALONG
WITH
CONNECTION
TO GEC AND
SYSTEM
C BA
GENERATOR AUTO START CONTACT
RELAY, SQUARE D CLASS 8501
KUD12V51 WITH SOCKET AND METAL
NEMA 12, SCREW COVER ENCLOSURE
SZ 0.5C,2#12
GENERATOR 2-WIRE AUTOSTART CIRCUIT
HH
SZ 1.5C,2#8&1#8GND.
AND PULL TAPE FOR
FUTURE EXPANSION
8"x12" MINIMUM
HANDHOLE, SEE SPECS
N.I.C. - NOTES FOR FUTURE EXPANSION:
TWO DUPLICATE ARRAYS TO THE EXISTING ARRAY(S) RATED 2000 WATTS
OR LESS, PER CHARGE CONTROLLER, MAY BE INSTALLED. THAT WOULD
BE 4 MOUNTING POLES FOR THE ENTIRE SYSTEM. ADDING SECOND
ARRAY TO INCLUDE PULLING ADDITIONAL 2#8 IN CONDUIT FROM
FLEXWARE TO HANDHOLE, AND WIRING TO FUTURE CHARGE
CONTROLLER, THE SAME AS ORIGINAL. ADD THIRD AND FORTH ARRAYS
BY ADDING A TAPS FROM THE FIRST AND SECOND ARRAY FEEDERS AT
THE HANDHOLE RESPECTIVELY TO THE NEW ARRAYS.
ADDITIONAL BATTERY BANKS MAY BE ADDED FOR STORAGE. BATTERIES
MUST BE SAME MAKE, MODEL, AND USAGE AGE AS THE EXISTING BANKS.
PARALLEL CONNECT TO EXISTING BANK, NO INCREASE IN CONDUCTOR
SIZE REQUIRED.
DRAWN
DESIGNER
STAMPS, LOGOS, AND SEALS
PROJECT NAME
DRAWING TITLE
CHECKED
ARCHIVE NO.DATE
PROJECT NO.
DRAWING SHEET NO.
DATENO.
REVISION / ISSUE
OFSHEET
United States Department of Agriculture Forest Service
3/4 /24
:2
7 S
AB
RO
W
N X:
\S
AW
TO
OT
H\
BI
GS
MO
KY
SO
UT
HH
YB
RI
D.
\D
W G\
BI
GS
MO
KY
SH
YB
.D W
G;
REGION 4
INTERMOUNTAIN REGION
BIG SMOKY
SOUTH SITE
HYBRID
ELECTRIC
SAWTOOTH NATIONAL
FOREST
FARIFIELD DISTRICT
FLEXWARE SYSTEM
03/05/2024
S.BROWN
S.BROWN
R.ANDERSON
E-3 4 5
Approved: x
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text S
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text V
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text P
AutoCAD SHX Text A
AutoCAD SHX Text R
AutoCAD SHX Text T
AutoCAD SHX Text M
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text T
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text A
AutoCAD SHX Text G
AutoCAD SHX Text R
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text U
AutoCAD SHX Text L
AutoCAD SHX Text T
AutoCAD SHX Text U
AutoCAD SHX Text R
HORIZONTAL
HYBRID SOLAR ARRAY AND SUPPORT
43°
15" MIN
4 SOLAR MODULES
TOP-OF-POLE MOUNT,
PREFORMED LINE PRODUCTS
(404-461-5200, plp.com) POWERFAB #TPM4-H-(module mfg and part#)-HWV
GRADE LEVEL
CONCRETE
4" GRAVEL IN
BOTTOM OF HOLE
FOR DRAINAGE
16.5-FOOT 6"Ø
GALVANIZED STEEL
SCHED 40 PIPE
CONCRETE NOTES
1- SEE SITE PLAN, SHEET E-2, FOR POLE LOCATIONS.
2- ENSURE ELECTRICAL CONDUIT IS INSTALLED WITHIN CONCRETE BASE.
3- COMPACT SUBGRADE TO REQUIRED ELEVATION BEFORE PLACING THE
POLE AND CONCRETE.
4- CONCRETE REQUIREMENTS:
3750 PSI CONCRETE @ 28 DAYS MINIMUM
CLASS A CONCRETE:
6.5 BAGS/CY MINIMUM
MAXIMUM WATER/CEMENT RATIO - 5.5 GAL/BAG
COARSE AGGREGATE SIZE RANGE 1-1/2" TO #4 STANDARD OR 1" TO
#4 ALTERNATIVE
SLUMP RANGE: 1" TO 3" FOR STANDARD COARSE AGGREGATE AND
2" TO 4" FOR ALTERNATIVE AGGREGATE
REQUIRED ENTRAINED AIR: 4% TO 6%
7- POUR CONCRETE AT TEMPERATURE ABOVE 35° FAHRENHEIT KEEP
CONCRETE TEMPERATURE OVER 50° FOR 5 DAYS.
8- BACKFILL AREA AROUND FOOTING WITH ROCK FREE EXCAVATED
MATERIAL (2-INCH MINUS) AND COMPACT TO AT LEAST 95% MAXIMUM
DENSITY.
9- INSTALL WITH ARRAY, MOUNTING DEVICES AND ALL OTHER NEEDED
EQUIPMENT AS CALLED FOR.
" M
IN
CONDUIT AS CALLED FOR
DISCONNECT
COMBINER BOX
12" #3 REBAR WELDED
TO PIPE TO PREVENT
TURNING, GALVANIZE
PAINT
PLAN VIEW
A
GENERATOR PAD NOTES
SL
O
PE
GENERATOR PAD DETAIL
LOCATION AND ELEVATION OF GENERATOR SLAB WILL BE STAKED BY THE CONTRACTOR AND
APPROVED BY THE CONTRACTING OFFICER PRIOR TO CONSTRUCTION.
MECHANICALLY COMPACT SUB-GRADE PRIOR TO FORMING AND CONSTRUCTING CAST-IN-PLACE
CONCRETE PADS PER SPECIFICATIONS, OR SETTING PRECAST PADS.
FINAL GRADE AROUND SLAB SHALL DRAIN AWAY FROM PADS A MINIMUM OF 2% (3H:1V MAXIMUM) FOR A MINIMUM OF 5 FEET IN ALL DIRECTIONS EXCEPT THE UPHILL SIDE WHICH SHALL SLOPE INTO A 4 TO 6-INCH DEEP DRAINAGE DITCH, CENTERLINE ABOUT 24 TO 36-INCHES FROM EDGE OF
PAD, GRADED TO BLEND INTO THE NATURAL SLOPE AND TO DRAIN TO NATURAL GRADE.
CONTRACTOR SHALL VERIFY THE DIMENSIONS OF THE GENERATOR AND FUEL TANK TO BE
SUPPLIED PRIOR TO BEGINNING CONSTRUCTION. COORDINATE THE LOCATION OF ANCHOR
BOLTS, ELECTRICAL FEEDER, AND AUTOSTART CIRCUIT. LOCATIONS SHOWN ARE NOT
ACCURATE. PAD SIZE IS BASED ON CALLED FOR GENERATOR AND SHALL BE ADJUSTED LARGER
FOR LARGER GENERATOR SUBSTITUTIONS.
A
SECTION A-A
6"
#4 REBAR
CONCRETE SLAB
NOTE-1.
NOTE-2.
NOTE-3.
NOTE-4.
1C AND 0.5C ELECTRICAL
POWER AND GENERATOR
START CIRCUIT STUB-UPS,
SEE NOTES
WEDGE ANCHOR, SIMPSON STRONG BOLT
#STB50512 (1/2" x 5-1/2") EMBED 3-7/8" DEEP
(TYPICAL OF 4 FOR GENERATOR MOUNTING),
SEE NOTES
#4 REBAR, 12" O.C.
BOTH DIRECTIONS
LIGHTLY COMPACTED NATIVE
FILL OR AGGREGATE
12'-6"
7' -0
POSSIBLY "I" VERIFY
WITH MANUFACTURER
NOT TO SCALE
6" MIN. COMPACTED CRUSHED
AGGREGATE BASE, 3/4" MINUS, PLACED
ON COMPACTED NATIVE SOIL
NOT TO SCALE
FINAL GRADE, SEE NOTE 3
FINAL GRADE UPHILL
SIDE, SEE NOTE 3
ONE REQUIRED, NOT TO SCALE
2"
DRAWN
DESIGNER
STAMPS, LOGOS, AND SEALS
PROJECT NAME
DRAWING TITLE
CHECKED
ARCHIVE NO.DATE
PROJECT NO.
DRAWING SHEET NO.
DATENO.
REVISION / ISSUE
OFSHEET
United States Department of Agriculture Forest Service
3/4 /24
:2
6 S
AB
RO
W
N X:
\S
AW
TO
OT
H\
BI
GS
MO
KY
SO
UT
HH
YB
RI
D.
\D
W G\
PO
LE
MO
UN
TI
NG
.D W
G;
REGION 4
INTERMOUNTAIN REGION
BIG SMOKY
SOUTH SITE
HYBRID
ELECTRIC
SAWTOOTH NATIONAL
FOREST
FAIRFIELD DISTRICT
GENERATOR PAD AND
ARRAY MOUNTING
03/04/2024
S.BROWN
S.BROWN
R.ANDERSON
D-1 5 5
Approved:
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text S
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text V
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text P
AutoCAD SHX Text A
AutoCAD SHX Text R
AutoCAD SHX Text T
AutoCAD SHX Text M
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text T
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text A
AutoCAD SHX Text G
AutoCAD SHX Text R
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text U
AutoCAD SHX Text L
AutoCAD SHX Text T
AutoCAD SHX Text U
AutoCAD SHX Text R
| Sheets and Views |
| BigSmokyNHybCvr-PLOT 11x17 |
| BigSmokyNHybDwgFinal.03.05.24.pdf |
| Sheets and Views |
| BigSmokyNHybCvr-PLOT 11x17 |
| BigSmokyNHyb-General Layout |
| BigSmokyNHyb-Site and floor plans |
| BigSmokyNHyb-Flexware |
| PoleMounting-Mounting |
| BigSmokyFoundationConstructionDrawing_Final.pdf |
| Sheets and Views |
| 0_CoverSheet-17x11 EXPANDED |
| BigSmokyFoundation_BASE-FoundationSitePlan |
| BigSmokyFoundation_BASE-FoundationPlans&Details |
| BigSmokySouthCover.pdf |
| Sheets and Views |
| BigSmokySHybCvr-PLOT 11x17 |
| BigSmokySHybDwgFinal.03.05.24.pdf |
| Sheets and Views |
| BigSmokySHybCvr-PLOT 11x17 |
| BigSmokySHyb-General Layout |
| BigSmokySHyb-Site and floor plans |
| BigSmokySHyb-Flexware |
| PoleMounting-Mounting |
| PoleMounting-Propane tank |
| BigSmokyNorthCover.pdf |
| Sheets and Views |
| BigSmokyNHybCvr-PLOT 11x17 |
| BigSmokySouthCover.pdf |
| Sheets and Views |
| BigSmokySHybCvr-PLOT 11x17 |
File details come from the government source that posted it. Updated .