Bid Set _ Illges Hall HVAC.pdf
PDF 4 MB Posted
- Attached to
- CSU-127-25 ILLGES HALL HVAC UPGRADES
- Solicitation number
- PE-53000-RFQ-2025-000000033
- Issued by
- Muscogee County, Columbus City, Georgia
About this file
This is a bid set of architectural and engineering drawings from NBP Engineers for HVAC upgrades at Illges Hall at Columbus State University in Columbus, Georgia (Project No. CSU-127-25). The project involves replacing and upgrading HVAC equipment including air handling units, terminal units, and associated ductwork and piping across three floors of Illges Hall. The bid set contains detailed mechanical and electrical drawings showing demolition plans, new work plans, flow diagrams, and installation details. The bid documents are dated December 3, 2024.
The drawings specify three new air handling units (AH-1, AH-2, AH-3) with cooling coils, filters, and variable frequency drives, along with multiple terminal units for zone control on each floor. The electrical scope includes power connections for new equipment, lighting upgrades in mechanical rooms, and integration with the building's fire alarm system. Detailed mechanical specifications show required flow rates, static pressures, and equipment sizing. The drawings include both demolition and new work plans for HVAC and electrical systems across the lower, middle and upper levels of the building, along with detailed sections of mechanical rooms 109, 225, and 324.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| DBB _ Ilges Hall HVAC.pdf | ||
| Bid Requirements.pdf | ||
| Pre_bid Sign_in Sheet.pdf | ||
| SPD_SPR010BiddersOfferorsConferenceAnnounceme.pdf | ||
| Pre_bid Agenda.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
TITLESHEET NO.
NBP ENGINEERS, INC.
MACON, GEORGIA316 CORPORATE PARKWAY
NBP
ENGINEERS
CONSULTANTS
478-745-1691 www.nbpengineers.com
M0.1
M1.1
M4.1
M5.1 DETAILS - HVAC
COLUMBUS STATE UNIVERSITY
ABBREVIATIONS, LEGENDS, & SCHEDULE - HVAC
M0.2 SCHEDULES - HVAC
M1.2
M2.1
M2.3
M3.1
FLOW DIAGRAM - HVAC
E2.1
E2.2
M5.2 DETAILS - HVAC
M3.2
COLUMBUS, GEORGIA
M1.3
LOWER LEVEL FLOOR PLAN - DEMOLITION - HVAC
MIDDLE LEVEL FLOOR PLAN - DEMOLITION - HVAC
UPPER LEVEL FLOOR PLAN - DEMOLITION - HVAC
LOWER LEVEL FLOOR PLAN - NEW WORK - HVAC
UPPER LEVEL FLOOR PLAN - NEW WORK - HVAC
M2.2 MIDDLE LEVEL FLOOR PLAN - NEW WORK - HVAC
E2.2
LOWER LEVEL FLOOR PLAN - NEW WORK - ELECTRICAL
MIDDLE LEVEL FLOOR PLAN - NEW WORK - ELECTRICAL
UPPER LEVEL FLOOR PLAN - NEW WORK - ELECTRICAL
LARGE SCALE - MECH. RM. 109 - DEMOLITION & NEW WORK - HVAC
LARGE SCALE - MECH. RM. 225 - DEMOLITION & NEW WORK - HVAC
LARGE SCALE - MECH. RM. 324 - DEMOLITION & NEW WORK - HVACM3.3
INDEX OF
DRAWINGS
PROJECT CONSULTANTS
12-03-2024 BID SET
PROJECT No: CSU-127-25
ILLGES HALL HVAC UPGRADES
SEAL
SCALE:
FILE PATH:
P:\22119\22119m01.dgn
DATE PLOTTED
DGN FILE
03-DEC-2024
SHEET NUMBER:
316 CORPORATE PARKWAY
NBP Engineers, Inc.
MACON, GEORGIA 31210
NBP
ENGINEERS
478-745-1691 www.nbpengineers.com
No. REVISIONS/SUBMISSIONS DATE
DRAWN:
CHECKED:
DESIGNED:
DATE:
PROJECT NUMBER:
P R
O J E
C T
T
IT
L E
SHEET TITLE:
CONSULTANTS
THIS DRAWING IS THE PROPERTY OF THE
ENGINEER AND MAY NOT BE REPRODUCED
OR USED IN WHOLE OR IN PART
WITHOUT HIS WRITTEN PERMISSION. IT IS
TO BE USED FOR THE PROJECT
SPECIFICALLY IDENTIFIED HEREIN AND TO
BE RETURNED UPON REQUEST.
P:\22119\22119m01.dgn
AS SHOWN
WSH
LTF
WSH
22119
C O
L U
M B
U S S
T A
T E U
N
IV
E R
S
IT
Y
COA Expiration: 6.30.2026
COA#PEF000774
NBP Engineers, Inc.
C o lu m b u s
G e o rg ia
12.03.2024
B
ID
S E
T
P R
O J E
C T N o
C
S U -1
-2
IL
L
G E S H
A L L H
V A
C U
P G
R A
D E S
A COMPRESSED AIR
AAV AUTOMATIC AIR VENT
AF AIR FOIL
-AFF ABOVE FINISHED FLOOR
AV ACID VENT
AVD AUTOMATIC VOLUME DAMPER
AW ACID WASTE
-AC ABOVE CEILING
AH- AIR HANDLING UNIT
BBD BOILER BLOW DOWN
BE BOTTOM ELEVATION
BOL BOTTOM OF LINE (UNINSULATED)
BOD BOTTOM OF DUCT
BP- BOOSTER PUMP
BTUH BRITISH THERMAL UNIT PER HOUR
-BF BELOW FLOOR
BFP BACK FLOW PREVENTOR
C CONDUIT
CC COOLING COIL
CHR CHILLED WATER RETURN
CHS CHILLED WATER SUPPLY
CR CONDENSER WATER RETURN
CS CONDENSER WATER SUPPLY
CW DOMESTIC COLD WATER
CAB CABINET FAN
CF CENTRIFICAL FAN
CFM CUBIC FEET PER MINUTE
CFP CHEMICAL FEED PUMP
CFT CHEMICAL FEED TANK
CH CABINET HEATER
CHR CHILLER
CL CENTER LINE
CO CLEANOUT
CP CHILLER PUMP
CPHB CHROME PLATED HOSE BIBB
CT COOLING TOWER
CU COPPER
CV- CONVECTOR
Cv VALVE COEFFICIENT
D DRAIN
DDC DIRECT DIGITAL CONTROL
DHW DOMESTIC HOT WATER
DN DOWN
DP DIFFERENTIAL PRESSURE
DS DOWN SPOUT
DSO DOWN SPOUT OVER FLOW
DX DIRECT EXCHANGE
EAD EXHAUST AIR DAMPER
EAT ENTERING AIR TEMPERATURE
EDB ENTERING DRY BULB
EWB ENTERING WET BULB
ESP END SUCTION PUMP
ESP EXTERNAL STATIC PRESSURE
ELL ELBOW
ET EXPANSION TANK
EQT EQUIPMENT TRAP SET
EWT ENTERING WATER TEMPERATURE
EX EXPANSION TANK LINE
EXT EXTERNAL
FOB FLAT ON BOTTOM
FOT FLAT ON TOP
F&BP FACE & BYPASS
FC FAN COIL UNIT
BPD BYPASS DAMPER
EAL EXHAUST AIR LOUVER
ECH ELECTRIC CABINET HEATER
ABBREVIATIONS
FD FLOOR DRAIN
FF FOULING FACTOR
FF- FLY FAN
FF FINISHED FLOOR
FF FINAL FILTER
FFM FIRE FLOW METER
FLEX FLEXIBLE
FM FIRE MAIN
FMS FLOW METER STATION
FOF FUEL OIL FLOW
FOR FUEL OIL RETURN
FOV FUEL OIL VENT
FOP FUEL OIL PUMP
FP FIRE PUMP
FP- FAN POWERED
FPM FEET PER MINUTE
FPS FEET PER SECOND
FRT FLOW RATE TRANSMITTER
FT FEET
G LOW PRESSURE GAS
GA GAUGE
GPM GALLONS PER MINUTE
GT GREASE TRAP
GTH GRAND TOTAL HEAT
H HEIGHT
HC HEATING COIL
HB HOSE BIBB
HBT HORIZONTAL BLOW THROUGH
HD HUB DRAIN
HDT HORIZONTAL DRAW THROUGH
HP HORSEPOWER/HIGH PRESSURE
HPA HIGH PRESSURE AIR
HPG HIGH PRESSURE GAS
HPS HIGH PRESSURE STEAM
HPWS HEAT PUMP WATER SUPPLY
HPWR HEAT PUMP WATER RETURN
HSC HORIZONTAL SPLIT CASE
HWG HOT WATER GENERATOR
HWR HEATING WATER RETURN
HWS HEATING WATER SUPPLY
ILC IN-LINE CENTRIFICAL
IT INTERVAL TIMER
IN INCHES
INV INVERT
JB JUNCTION BOX
L LENGTH
LR LONG RADIUS
LAT LEAVING AIR TEMPERATURE
LCP LOCAL CONTROL PANEL
LDB LEAVING DRY BULB
LN LIQUID NITROGEN
LWB LEAVING WET BULB
LWT LEAVING WATER TEMPERATURE
LPS LOW PRESSURE STEAM
MAV MANUAL AIR VENT
MVD MANUAL VOLUME DAMPER
MAX MAXIMUM
MBH ONE THOUSAND BTUH PER HOUR
MCC MOTOR CONTROL CENTER
MIN MINIMUM
MH MAN HOLE
MP SUMP (MUD) PUMP
MPS MEDIUM PRESSURE STEAM
MPR MEDIUM PRESSURE RETURN
MTS MEDIUM TEMPERATURE SUPPLY
MTR MEDIUM TEMPERATURE RETURN
MUA MAKE-UP AIR
MUW MAKE-UP WATER
MZ MULTIZONE
NC NORMALLY CLOSED
NIC NOT IN CONTRACT
NO NORMALLY OPEN
NTS NOT TO SCALE
OA OUTSIDE AIR
OAD OUTSIDE AIR DAMPER
ODT OUTDOOR TEMPERATURE
PC PUMP CONDENSATE
PD PRESSURE DROP
PRV PRESSURE REDUCING VALVE
PWF PROPELLER WALL FAN
R REFRIGERANT
RA RETURN AIR
RAD RETURN AIR DAMPER
RAS RELIEF AIR SUPPLY
RP RECIRCULATING PUMP
RHG REFRIGERANT HOT GAS
RL REFRIGERANT LIQUID
RS REFRIGERANT SUCTION
RD ROOF DRAIN
RV RELIEF VALVE
SR SHORT RADIUS
OAL OUTSIDE AIR LOUVER
SAN SANITARY SEWER
SC SILL COCK
SCD SMOKE DAMPER
SD STORM DRAIN
SD SMOKE DETECTOR
SF SQUARE FEET
SDO STORM DRAIN OVERFLOW
SHC SENSIBLE HEAT CAPACITY
SP STAND PIPE
SP SUMP PUMP
SPS STATIC PRESSURE SENSOR
STA STATION
TR TEMPERED WATER RETURN
UG UNDERGROUND
VAC VACUUM PIPING
VDT VERTICAL DRAW THROUGH
VTR VENT THROUGH ROOF
WB WET BULB
O2 OXYGEN
?F DEGREES FAHRENHEIT
?C DEGREES CENTIGRADE
WM WATER METER
WL WATER LINE
WH WATER HEATER
WG WATER GAUGE
W WIDTH
W WASTE
VT VERTICAL TURBINE
VFD VARIABLE FREQUENCY DRIVE
VB VACUUM BREAKER
VAV VARIABLE AIR VOLUME
V VENT
UC UNDERCUT (DOOR - 3/4")
V- VALVE
TOS TOP OF STRUCTURE
TB THRUST BLOCK
T TEMPERED WATER
STR STRAINER
SP STATIC PRESSURE
SP SPRINKLER PIPE
SG SPECIALTY GAS
EUH ELECTRIC UNIT HEATER
RECIRCULATING
DHR DOMESTIC HOT WATER
TRANSMITTER
DPT DIFFERENTIAL PRESSURE
PER MINUTE
SCIM STANDARD CUBIC INCHES
TEMPERATURE
SST SATURATED SUCTION
(UNINSULATED)
TE TOP ELEVATION
(TOWER) PUMP
TP CONDENSER WATER
FSD FIRE/SMOKE DAMPER
EA EXHAUST AIR
MA MIXED AIR
AE ADJUSTABLE AIR EXTRACTOR
RAO RETURN AIR OPENING
AD AREA DRAIN/ACCESS DOOR
COMBINATION STARTER
STARTER
PIPE SLEEVE
CONCENTRIC REDUCER
PIPE ANCHOR
HVAC LEGEND
GATE VALVE WITH
3/4" HOSE END
BALANCE VALVE
THREADED & FLANGED
GLOBE VALVE
CHECK VALVE
3-WAY MIXING VALVE
GATE VALVE
BUTTERFLY VALVE
SOLENOID VALVE
CONTROL VALVE
PLAN VIEW
2-WAY MOTORIZED VALVE
RELIEF VALVE
FLANGED UNION
BRANCH OUT TOP
STRAINER
BRANCH OUT BOTTOM
ELBOW DOWNELBOW UP
TEE OUT TOP
BLIND FLANGE
PIPE CAP
AUTOMATIC AIR VENTAAV
FLEX. PIPE CONN.
BACKFLOW PREVENTER
THERMOMETER
TEE OUT BOTTOM
MANUAL AIR VENT
PIPE TEST PLUG
UNDERGROUND
BOTTOM OF LINE (BARE)
CHILLED WATER FLOWHEATING WATER FLOW
COLD WATER DOMESTIC
NATURAL GAS CONDENSER WATER FLOW
DRAIN
MANUAL AIR VENT
LONG RADIUS
FLOW METER
CHILLED WATER RETURNHEATING WATER RETURN
HOT WATER DOMESTIC
U.G.
B.O.L.
G
D
M.A.V.
L.R.
DUCT SIZE FIRST DIMENSION
IS SIDE SHOWN
24\12 DOOR GRILLE
C.F.M.
RELIEF AIR SUPPLY
MANUAL VOL. DAMPER
TOP ELEVATION
FLAT ON TOP
RETURN AIR
NOT TO SCALE
REFERS TO DETAIL OR
PLAN ON SHEET M-1.
THERMOSTAT
INTERVAL TIMER
AUTO VOL. DAMPER
BOTTOM ELEVATION
FLAT ON BOTTOM
OUTSIDE AIR
DOOR UNDERCUT (3/4 ")
T
I.T.
A.V.D.
B.E.
F.O.B.
O.A.
U.C.
R.A.S.
M.V.D.
T.E.
F.O.T.
R.A.
NTS
1\M-4
LINED DUCT OR PLENUM
DAMPER
FIRE DAMPER
ELBOW WITH
TURNING VANES
FLEX. DUCT CONN.
DAMPER
TURNING VANES
ELBOW WITHOUT
ADJUSTABLE AIR
EXTRACTOR
INSULATED FLEX. DUCT INSULATED FLEX. DUCT
FIRE DAMPERF.D.
c
DN DOWN
ECCENTRIC REDUCER
A.D. ACCESS DOOR
HWS
HWR
CHS
CHR
CONDENSER WATER RETURN
CS
CR
SPS STATIC PRESSURE SENSOR
EAL EXHAUST AIR LOUVEROAL OUTSIDE AIR LOUVER
RAO RETURN AIR OPENING
STATIC PRESSURE SENSOR
SMOKE DETECTOR
POINT OF CONNECTION
DUCT SPLIT
THREADED & FLANGED
THREADED & FLANGED
UNION
GAUGE TAPPING
GAUGE WITH TAPPING
THREADED & FLANGED
THREADED & FLANGED
PIPE SOCKET WELL
FLOW INDICATOR BALANCER
WINTER
DESIGN CONDITIONS
SUMMER
OUTSIDE
INSIDE
95 DB / 76 WB
74 / 55% RH
SINGLE LINE DUCT LEGEND
DUCT (SUPPLY, RETURN & EXHAUST)
SUPPLY DUCT UP
SUPPLY DUCT DOWN
RETURN OR EXHAUST DUCT UP
RETURN OR EXHAUST DUCT DOWN
DUCT RISE
DUCT DOWN
VOLUME DAMPER (MANUAL UNLESS INDICATED A.V.D.)
TRANSITION
DUCT TAKE-OFF (SEE SPEC. PERTAINING TO DEFLECTROLS)
TRANSITION (FLAT ON TOP)
TRANSITION (FLAT ON BOTTOM)
TRANSITION (TOP OR BOTTOM ONLY)
SUPPLY CEILING DIFFUSER
RETURN OR EXHAUST CEILING GRILLE
SIDEWALL SUPPLY
SIDEWALL RETURN
FLEXIBLE CONNECTION (DUCT)
RELIEF AIR SUPPLY TO TOILET
DUCT SPLIT WITH SPLITTER DAMPER
FLEX. DUCT WITH SCREW ON COLLAR, TAKE-OFF
DUCT WITH DUCT LINER
SQUARE ELBOW WITH TURNING VANES
RADIUS ELBOW (SEE SPECS. PERTAINING TO TURNING VANES)
AUTOMATIC VOLUME DAMPER
DN
R
12\10 SPLIT
OR
OR
SCD
FOB
T OR B
RAS
AVD
FD/SCD
FD
SMOKE CONTROL DAMPER
COMBINATION FIRE/SMOKE CONTROL DAMPER
FIRE DAMPER (FD)
FIRE DAMPER
M0.1
SCHEDULE - HVAC
LEGENDS, &
ABBREVIATIONS,
FILE PATH:
P:\22119\22119m02.dgn
DATE PLOTTED
DGN FILE
03-DEC-2024
SHEET NUMBER:
316 CORPORATE PARKWAY
NBP Engineers, Inc.
MACON, GEORGIA 31210
NBP
ENGINEERS
478-745-1691 www.nbpengineers.com
No. REVISIONS/SUBMISSIONS DATE
DRAWN:
CHECKED:
DESIGNED:
DATE:
PROJECT NUMBER:
P R
O J E
C T
T
IT
L E
SHEET TITLE:
CONSULTANTS
THIS DRAWING IS THE PROPERTY OF THE
ENGINEER AND MAY NOT BE REPRODUCED
OR USED IN WHOLE OR IN PART
WITHOUT HIS WRITTEN PERMISSION. IT IS
TO BE USED FOR THE PROJECT
SPECIFICALLY IDENTIFIED HEREIN AND TO
BE RETURNED UPON REQUEST.
P:\22119\22119m02.dgn
AS SHOWN
WSH
LTF
WSH
22119
C O
L U
M B
U S S
T A
T E U
N
IV
E R
S
IT
Y
COA Expiration: 6.30.2026
COA#PEF000774
NBP Engineers, Inc.
C o lu m b u s
G e o rg ia
12.03.2024
T
P R
O J E
C T N o
C
S U -1
-2
IL
L
G E S H
A L L H
V A
C U
P G
R A
D E S
M0.2
SCHEDULES - HVAC
TOTAL EXT. S.P.
IN H O2
FACE VEL.
F.P.M.
SENSIBLETOTAL
ENTERING AIR LEAVING AIR
MOTOR
HP
VALVE
CV
COOLING COIL
APPROX.
T.S.P.
IN H O2
MARK
AH-2
TYPE WHEEL
SIZE
AIR FLOW
AH-1
FAN
TYPE CFM CFM
MIN. OA
MBH MBH DB WB DB WB GPM EWT LWT
AIR HANDLING UNIT SCHEDULE
MIN.
REMARKS
AH-3
VAV 4800 1060 2.0 4.0 500PLENUM
PLENUMVAV
PLENUMVAV
54 53 45 55
6400 1455 2.0 4.0 500 54 53 45 55
7300 1740 2.0 4.0 500 54 53 45 55316
79.8
79.5
79.4
66.9
66.7
66.7
MARK
TERMINAL BOX SCHEDULE
RUNOUT
PIPE
SIZE
TITUS
MAX. CFM
COOLING
MAX. CFM
HEATING
MIN. CFM
HEATING
MBH
COIL
GPM
COIL
CV
VALVE
TU3-8
TU3-7
TU3-6
TU3-5
TU3-4
TU3-3
TU3-2
TU3-1
TU2-10
TU2-9
TU2-8
TU2-7
TU2-6
TU2-5
TU2-4
TU2-3
TU2-2
TU2-1
TU1-6
TU1-5
TU1-4
TU1-3
TU1-2
TU1-1
1,065
1,175
1,605
2,375
1,285
1,060
1,010
1,860
1,190
10.1
13.4
17.3
3.6
13.8
18.8
25.8
37.8
8.1
22.0
10.1
12.4
7.8
3.9
11.4
17.3
14.3
11.4
6.7
14.6
8.2
11.0
16.3
30.1
0.7
0.9
1.2
0.2
0.9
1.3
1.7
2.5
0.5
1.5
0.7
0.8
0.5
0.3
0.8
1.2
1.0
0.8
0.4
1.0
0.5
0.7
1.1
2.0
0.32
0.43
0.55
0.11
0.44
0.60
0.82
1.20
0.26
0.70
0.32
0.39
0.25
0.12
0.36
0.55
0.45
0.36
0.21
0.46
0.26
0.35
0.52
0.96
1/2
1/2
1/2
1/2
1/2
1/2
3/4
3/4
1/2
1/2
1/2
1/2
1/2
1/2
1/2
1/2
1/2
1/2
3/4
REMARKS
NOTES:
TWO FANS @ 5 HP EACH; TOTAL 10 HP.
TWO FANS @ 7.5 HP EACH; TOTAL 15 HP.
7.5
13.5
24.5
15.0
21 3 4 5 6
A
B
C
D
1 10
PATIENT ED.
1 1 1
SUPPLY
MECH. RM.
LOCKER RM.
STAIR #1
STAIR #2
NURSING STOR.
MEN
WOMEN
WAITING
OFFICE
OFFICE
OFFICE
OFFICE
1 17
STORAGE
1 18
RECORDS
1 19
STERILIZE
FACULTY DEV.
1 16
DENTAL CLINIC
1 12
DARK RM.
1 14
X-RAY
1 13
STORAGE
1 15
DEMONSTRATION
SEAL
SCALE:
FILE PATH:
P:\22119\22119m11.dgn
DATE PLOTTED
DGN FILE
03-DEC-2024
SHEET NUMBER:
316 CORPORATE PARKWAY
NBP Engineers, Inc.
MACON, GEORGIA 31210
NBP
ENGINEERS
478-745-1691 www.nbpengineers.com
No. REVISIONS/SUBMISSIONS DATE
DRAWN:
CHECKED:
DESIGNED:
DATE:
PROJECT NUMBER:
P R
O J E
C T
T
IT
L E
SHEET TITLE:
CONSULTANTS
THIS DRAWING IS THE PROPERTY OF THE
ENGINEER AND MAY NOT BE REPRODUCED
OR USED IN WHOLE OR IN PART
WITHOUT HIS WRITTEN PERMISSION. IT IS
TO BE USED FOR THE PROJECT
SPECIFICALLY IDENTIFIED HEREIN AND TO
BE RETURNED UPON REQUEST.
P:\22119\22119m11.dgn
AS SHOWN
WSH
LTF
WSH
22119
C O
L U
M B
U S S
T A
T E U
N
IV
E R
S
IT
Y
COA Expiration: 6.30.2026
COA#PEF000774
NBP Engineers, Inc.
C o lu m b u s
G e o rg ia
12.03.2024
T
P R
O J E
C T N o
C
S U -1
-2
IL
L
G E S H
A L L H
V A
C U
P G
R A
D E S
SCALE:
= 1'-0
8 0 4 8 16
M1.1
LINE LEGEND
EXISTING TO REMAIN
DEMOLITION
JUNCTION BOX AND CONDUIT FOR THERMOSTAT IN ACCORDANCE WITH DIV. 26 (TYPICAL).
BOX OR CONDUIT EXIST AT EXISTING THERMOSTAT LOCATION, PROVIDE NEW
OF NEW THERMOSTAT. DO NOT ABANDON THERMOSTAT IN PLACE. IF NO JUNCTION
REMOVE EXISTING THERMOSTAT. REUSE EXISTING WALL LOCATION FOR PLACEMENT
GENERAL NOTES:(THIS SHEET ONLY)
A
IF DAMAGED DURING CONSTRUCTION.
CEILING TILES, CEILING GRIDS, OR FIXTURES TO MATCH EXISTING
PERFORMED ABOVE FINISHED SPACES. REPAIR/REPLACE ANY
REMOVE EXISTING CEILING TILES WHERE SCOPE OF WORK ISB
SURVEY EXISTING CONDITIONS TO VERIFY ITEMS TO BE DEMOLISHED.
ALL CONDITIONS FOR DEMOLITION MAY NOT BE SHOWN.
C
TO NEW EQUIPMENT IN NEW WORK.
WHICH IS REQUIRED TO REPLACE FOR PROPER CONNECTIONS
ALL EXISTING DUCTWORK TO REMAIN EXCEPT FOR THAT
NOTES:(THIS SHEET ONLY)
3 REMOVE EXISTING PACKAGED AC UNIT AND ALL ASSOCIATED AIR DISTRIBUTION.
4 EXISTING TERMINAL UNIT TO REMAIN.
EXISTING MAIN SUPPLY DUCT.
NEW EQUIPMENT IN NEW WORK. REMOVE EXISTING RUNOUT BACK TO
EXISTING TERMINAL UNIT TO BE REMOVED AND REPLACED WITH
HAS BEEN INSTALLED.
PROVIDE NEW ACOUSTICAL TILE CEILING AFTER NEW DUCTWORK AND AIR DISTRIBUTION
AND INSTALLATION OF NEW DUCTWORK. TEMPORARILY SUPPORT EXISTING LIGHT FIXTURES.
REMOVE EXISTING CEILING TILE AND GRID TO ALLOW FOR REMOVAL OF EXISTING DUCTWORK
CONTRACTOR UNDER SEPARATE CONTRACT.
EXISTING MEDIUM PRESSURE DUCT WORK TO BE REMOVED BY ABATEMENT
LOWER LEVEL FLOOR PLAN - DEMOLITION - HVAC
DEMOLITION - HVAC
FLOOR PLAN -
LOWER LEVEL
T
AU-1-2
T
6/6 CR
95|95| 95| 95| 265|
310| 310|310|
310| 310| 315|
12/10 22/10 12/10
8/8 CR 6/6 CR
10/4
EF-3
EF-2
w/FD
12"x12" RAO
T
270|
250|
200|200|
100|
350|
80|
80|
18/9
T AU-1-4
w/FD
10"x10" RAO
20/7-UP
195|
195| 24/8
18/8
8/8
8/66/6
60|
WALL CAP
WALL CAP
T
T
AU-1-5
AU-1-1
195|
AU-1-6
10/6
430|
430|
150|
AU-1-3
265|
2"-UP
3"-UP
1 1/8
M3.1
H W
R
C H
R C
H S
H W
24/16 RAOw/FD24/16 RAOw/FD
B
C
D
STAIR #1
STAIR #2
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
LOUNGE
LOBBY
CLOSET
TOILET
OFFICE
OFFICE
OFFICE
OFFICE
TOILET
WOMENS
STORAGE
TOILET
SEMINAR
CLASSROOM217
CLASSROOM
SEMINAR
CONFERENCE
CORRIDOR
CORRIDOR
MECH. RM.
SEAL
SCALE:
FILE PATH:
P:\22119\22119m12.dgn
DATE PLOTTED
DGN FILE
03-DEC-2024
SHEET NUMBER:
316 CORPORATE PARKWAY
NBP Engineers, Inc.
MACON, GEORGIA 31210
NBP
ENGINEERS
478-745-1691 www.nbpengineers.com
No. REVISIONS/SUBMISSIONS DATE
DRAWN:
CHECKED:
DESIGNED:
DATE:
PROJECT NUMBER:
P R
O J E
C T
T
IT
L E
SHEET TITLE:
CONSULTANTS
THIS DRAWING IS THE PROPERTY OF THE
ENGINEER AND MAY NOT BE REPRODUCED
OR USED IN WHOLE OR IN PART
WITHOUT HIS WRITTEN PERMISSION. IT IS
TO BE USED FOR THE PROJECT
SPECIFICALLY IDENTIFIED HEREIN AND TO
BE RETURNED UPON REQUEST.
P:\22119\22119m12.dgn
AS SHOWN
WSH
LTF
WSH
22119
C O
L U
M B
U S S
T A
T E U
N
IV
E R
S
IT
Y
COA Expiration: 6.30.2026
COA#PEF000774
NBP Engineers, Inc.
C o lu m b u s
G e o rg ia
12.03.2024
T
P R
O J E
C T N o
C
S U -1
-2
IL
L
G E S H
A L L H
V A
C U
P G
R A
D E S
SCALE:
= 1'-0
8 0 4 8 16
M1.2
LINE LEGEND
EXISTING TO REMAIN
DEMOLITION
DEMOLITION - HVAC
FLOOR PLAN -
MIDDLE LEVEL
MIDDLE LEVEL FLOOR PLAN - DEMOLITION - HVAC
T
AU-2-8
T
AU-2-10
AU-2-3
T
AU-2-9
T AU-2-7
20/7-DN
18/10-UP
11/7
12/5 195|
40|
90|
18/18-UP
12/12-UP
140|
350|
345|210|
210|
210|
200|
20/8
18/8
/8
10/8
640|
645|
30/8
120|160| 110|110|
160|160| 140| 115|
135|
135|
10/7
RAO w/FD
20/15
8/6 8/8
/8
10/8 8/8 8/6
10/10
10/8
180|
13/8
8/8
14/8
265|
265| 265|
265|
270|
120|120|
8/5
13/5 13/8
M3.2
185|
285|
FILTER
8/8-UP
90|
90|
JUNCTION BOX AND CONDUIT FOR THERMOSTAT IN ACCORDANCE WITH DIV. 26 (TYPICAL).
BOX OR CONDUIT EXIST AT EXISTING THERMOSTAT LOCATION, PROVIDE NEW
OF NEW THERMOSTAT. DO NOT ABANDON THERMOSTAT IN PLACE. IF NO JUNCTION
REMOVE EXISTING THERMOSTAT. REUSE EXISTING WALL LOCATION FOR PLACEMENT
GENERAL NOTES:(THIS SHEET ONLY)
A
IF DAMAGED DURING CONSTRUCTION.
CEILING TILES, CEILING GRIDS, OR FIXTURES TO MATCH EXISTING
PERFORMED ABOVE FINISHED SPACES. REPAIR/REPLACE ANY
REMOVE EXISTING CEILING TILES WHERE SCOPE OF WORK ISB
SURVEY EXISTING CONDITIONS TO VERIFY ITEMS TO BE DEMOLISHED.
ALL CONDITIONS FOR DEMOLITION MAY NOT BE SHOWN.
C
TO NEW EQUIPMENT IN NEW WORK.
WHICH IS REQUIRED TO REPLACE FOR PROPER CONNECTIONS
ALL EXISTING DUCTWORK TO REMAIN EXCEPT FOR THAT
NOTES:(THIS SHEET ONLY)
3 REMOVE EXISTING PACKAGED AC UNIT AND ALL ASSOCIATED AIR DISTRIBUTION.
4 EXISTING TERMINAL UNIT TO REMAIN.
EXISTING MAIN SUPPLY DUCT.
NEW EQUIPMENT IN NEW WORK. REMOVE EXISTING RUNOUT BACK TO
EXISTING TERMINAL UNIT TO BE REMOVED AND REPLACED WITH
HAS BEEN INSTALLED.
PROVIDE NEW ACOUSTICAL TILE CEILING AFTER NEW DUCTWORK AND AIR DISTRIBUTION
AND INSTALLATION OF NEW DUCTWORK. TEMPORARILY SUPPORT EXISTING LIGHT FIXTURES.
REMOVE EXISTING CEILING TILE AND GRID TO ALLOW FOR REMOVAL OF EXISTING DUCTWORK
CONTRACTOR UNDER SEPARATE CONTRACT.
EXISTING MEDIUM PRESSURE DUCT WORK TO BE REMOVED BY ABATEMENT
25/8
/8
13/8
30/8RAO w/FD
20/15
T
AU-2-1
AU-2-2
AU-2-4
AU-2-5
AU-2-6
270| 150|
T
HWS
HWR
CHS
CHR
24/17 RAOw/FD w/FD
RAO
24/17 w/FD
RAO
24/17 w/FD
RAO
24/17
B
C
D
MECH. RM.
STAIR #1
STAIR #2
OFFICE
OFFICE
OFFICE
CLOSET
ELEVATOR325
OFFICE
TOILET
MULTIPURPOSE
JAN
STORAGE301
PROJ
STORAGE
CLOS
CLOS
TOILET
WOMEN
MEN
CORRIDOR
STUDY CARRELS
A/V CENTER309
SEAL
SCALE:
FILE PATH:
P:\22119\22119m13.dgn
DATE PLOTTED
DGN FILE
03-DEC-2024
SHEET NUMBER:
316 CORPORATE PARKWAY
NBP Engineers, Inc.
MACON, GEORGIA 31210
NBP
ENGINEERS
478-745-1691 www.nbpengineers.com
No. REVISIONS/SUBMISSIONS DATE
DRAWN:
CHECKED:
DESIGNED:
DATE:
PROJECT NUMBER:
P R
O J E
C T
T
IT
L E
SHEET TITLE:
CONSULTANTS
THIS DRAWING IS THE PROPERTY OF THE
ENGINEER AND MAY NOT BE REPRODUCED
OR USED IN WHOLE OR IN PART
WITHOUT HIS WRITTEN PERMISSION. IT IS
TO BE USED FOR THE PROJECT
SPECIFICALLY IDENTIFIED HEREIN AND TO
BE RETURNED UPON REQUEST.
P:\22119\22119m13.dgn
AS SHOWN
WSH
LTF
WSH
22119
C O
L U
M B
U S S
T A
T E U
N
IV
E R
S
IT
Y
COA Expiration: 6.30.2026
COA#PEF000774
NBP Engineers, Inc.
C o lu m b u s
G e o rg ia
12.03.2024
T
P R
O J E
C T N o
C
S U -1
-2
IL
L
G E S H
A L L H
V A
C U
P G
R A
D E S
SCALE:
= 1'-0
8 0 4 8 16
M1.3
LINE LEGEND
EXISTING TO REMAIN
DEMOLITION
UPPER LEVEL FLOOR PLAN - DEMOLITION - HVAC
DEMOLITION - HVAC
FLOOR PLAN -
UPPER LEVEL
T
T
T
T
T
8/924/9
|395
|395
|395
|395
AU-3-4
AU-3-6
EF-4
|460
|310 |225 |265
|265 |265
|270
14/1020/10
AU-3-8
AU-3-7
AU-3-2
TAU-3-3
7/8 1 1/8
22/8
10/8 15/8
25/10
|465
22/8
24/1 1
20/1 1
13/8 16/8
|145 w/FD
30/18 RAO
w/FD
30/18 RAO
10/8
|195 |195 |185
|40
R
16/1 1
320|
215|
320|
320|
320|
320|
320|
320|
325|
6/6
8/8
6/6
10/7 8/4
18-10-DN
14/14-UP
EF-5
w/FD
30/18 RAO
18/18
60|
135|
195|
12/5 8/5
14/
JUNCTION BOX AND CONDUIT FOR THERMOSTAT IN ACCORDANCE WITH DIV. 26 (TYPICAL).
BOX OR CONDUIT EXIST AT EXISTING THERMOSTAT LOCATION, PROVIDE NEW
OF NEW THERMOSTAT. DO NOT ABANDON THERMOSTAT IN PLACE. IF NO JUNCTION
REMOVE EXISTING THERMOSTAT. REUSE EXISTING WALL LOCATION FOR PLACEMENT
GENERAL NOTES:(THIS SHEET ONLY)
A
IF DAMAGED DURING CONSTRUCTION.
CEILING TILES, CEILING GRIDS, OR FIXTURES TO MATCH EXISTING
PERFORMED ABOVE FINISHED SPACES. REPAIR/REPLACE ANY
REMOVE EXISTING CEILING TILES WHERE SCOPE OF WORK ISB
SURVEY EXISTING CONDITIONS TO VERIFY ITEMS TO BE DEMOLISHED.
ALL CONDITIONS FOR DEMOLITION MAY NOT BE SHOWN.
C
TO NEW EQUIPMENT IN NEW WORK.
WHICH IS REQUIRED TO REPLACE FOR PROPER CONNECTIONS
ALL EXISTING DUCTWORK TO REMAIN EXCEPT FOR THAT
NOTES:(THIS SHEET ONLY)
3 REMOVE EXISTING PACKAGED AC UNIT AND ALL ASSOCIATED AIR DISTRIBUTION.
4 EXISTING TERMINAL UNIT TO REMAIN.
EXISTING MAIN SUPPLY DUCT.
NEW EQUIPMENT IN NEW WORK. REMOVE EXISTING RUNOUT BACK TO
EXISTING TERMINAL UNIT TO BE REMOVED AND REPLACED WITH
HAS BEEN INSTALLED.
PROVIDE NEW ACOUSTICAL TILE CEILING AFTER NEW DUCTWORK AND AIR DISTRIBUTION
AND INSTALLATION OF NEW DUCTWORK. TEMPORARILY SUPPORT EXISTING LIGHT FIXTURES.
REMOVE EXISTING CEILING TILE AND GRID TO ALLOW FOR REMOVAL OF EXISTING DUCTWORK
CONTRACTOR UNDER SEPARATE CONTRACT.
EXISTING MEDIUM PRESSURE DUCT WORK TO BE REMOVED BY ABATEMENT
M3.3
|395
|395
|265
AU-3-5
B
C
D
1 10
PATIENT ED.
1 1 1
SUPPLY
MECH. RM.
LOCKER RM.
STAIR #1
STAIR #2
NURSING STOR.
MEN
WOMEN
WAITING
OFFICE
OFFICE
OFFICE
OFFICE
1 17
STORAGE
1 18
RECORDS
1 19
STERILIZE
FACULTY DEV.
1 16
DENTAL CLINIC
1 12
DARK RM.
1 14
X-RAY
1 13
STORAGE
1 15
DEMONSTRATION
SEAL
SCALE:
FILE PATH:
P:\22119\22119m21.dgn
DATE PLOTTED
DGN FILE
03-DEC-2024
SHEET NUMBER:
316 CORPORATE PARKWAY
NBP Engineers, Inc.
MACON, GEORGIA 31210
NBP
ENGINEERS
478-745-1691 www.nbpengineers.com
No. REVISIONS/SUBMISSIONS DATE
DRAWN:
CHECKED:
DESIGNED:
DATE:
PROJECT NUMBER:
P R
O J E
C T
T
IT
L E
SHEET TITLE:
CONSULTANTS
THIS DRAWING IS THE PROPERTY OF THE
ENGINEER AND MAY NOT BE REPRODUCED
OR USED IN WHOLE OR IN PART
WITHOUT HIS WRITTEN PERMISSION. IT IS
TO BE USED FOR THE PROJECT
SPECIFICALLY IDENTIFIED HEREIN AND TO
BE RETURNED UPON REQUEST.
P:\22119\22119m21.dgn
AS SHOWN
WSH
LTF
WSH
22119
C O
L U
M B
U S S
T A
T E U
N
IV
E R
S
IT
Y
COA Expiration: 6.30.2026
COA#PEF000774
NBP Engineers, Inc.
C o lu m b u s
G e o rg ia
12.03.2024
T
P R
O J E
C T N o
C
S U -1
-2
IL
L
G E S H
A L L H
V A
C U
P G
R A
D E S
6/6 CR
95|95| 95| 95| 265|
310| 310|310|
310| 310| 315|
12/10 22/10 12/10
8/8 CR 6/6 CR
10/4
EF-3
EF-2
w/FD
12"x12" RAO
270|
250|
200|200|
100|
350|
80|
80|
18/9 w/FD
10"x10" RAO
20/7-UP
195|
195|
18/8
8/8
8/66/6
60|
WALL CAP
WALL CAP
195|
10/6
430|
430|
150|
265|
2"-UP
1 1/8
H W
R
C H
R C
H S
H W
S
24/16 RAOw/FD24/16 RAOw/FD
SCALE:
= 1'-0
8 0 4 8 16
M2.1
GENERAL NOTES:(THIS SHEET ONLY)
A
IF DAMAGED DURING CONSTRUCTION.
CEILING TILES, CEILING GRIDS, OR FIXTURES TO MATCH EXISTING
PERFORMED ABOVE FINISHED SPACES. REPAIR/REPLACE ANY
REMOVE EXISTING CEILING TILES WHERE SCOPE OF WORK ISB
SURVEY EXISTING CONDITIONS TO VERIFY ITEMS TO BE DEMOLISHED.
ALL CONDITIONS FOR DEMOLITION MAY NOT BE SHOWN.
C
TO NEW EQUIPMENT IN NEW WORK.
WHICH IS REQUIRED TO REPLACE FOR PROPER CONNECTIONS
ALL EXISTING DUCTWORK TO REMAIN EXCEPT FOR THAT
NOTES:(THIS SHEET ONLY)
M3.1
LOWER LEVEL FLOOR PLAN - NEW WORK - HVAC
LINE LEGEND
POINT OF CONNECTION
EXISTING TO REMAIN
NEW WORK
NEW WORK - HVAC
FLOOR PLAN -
LOWER LEVEL
T
T
T
T
T
T
TU1-3
TU1-4
TU1-1
TU1-5
TU1-2
AU-1-6
NEW THERMOSTAT.1
24/12
TU1-1
TU1-2
FD
3"
HWS
HWR
ƒ"
B
C
D
STAIR #1
STAIR #2
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
LOUNGE
LOBBY
CLOSET
TOILET
OFFICE
OFFICE
OFFICE
OFFICE
TOILET
WOMENS
STORAGE
TOILET
SEMINAR
CLASSROOM217
CLASSROOM
SEMINAR
CONFERENCE
CORRIDOR
CORRIDOR
MECH. RM.
SEAL
SCALE:
FILE PATH:
P:\22119\22119m22.dgn
DATE PLOTTED
DGN FILE
03-DEC-2024
SHEET NUMBER:
316 CORPORATE PARKWAY
NBP Engineers, Inc.
MACON, GEORGIA 31210
NBP
ENGINEERS
478-745-1691 www.nbpengineers.com
No. REVISIONS/SUBMISSIONS DATE
DRAWN:
CHECKED:
DESIGNED:
DATE:
PROJECT NUMBER:
P R
O J E
C T
T
IT
L E
SHEET TITLE:
CONSULTANTS
THIS DRAWING IS THE PROPERTY OF THE
ENGINEER AND MAY NOT BE REPRODUCED
OR USED IN WHOLE OR IN PART
WITHOUT HIS WRITTEN PERMISSION. IT IS
TO BE USED FOR THE PROJECT
SPECIFICALLY IDENTIFIED HEREIN AND TO
BE RETURNED UPON REQUEST.
P:\22119\22119m22.dgn
AS SHOWN
WSH
LTF
WSH
22119
C O
L U
M B
U S S
T A
T E U
N
IV
E R
S
IT
Y
COA Expiration: 6.30.2026
COA#PEF000774
NBP Engineers, Inc.
C o lu m b u s
G e o rg ia
12.03.2024
T
P R
O J E
C T N o
C
S U -1
-2
IL
L
G E S H
A L L H
V A
C U
P G
R A
D E S
20/7-DN
18/10-UP
11/7
12/5 195|
40|
90|
12/12-UP
140|
350|
345|210|
210|
210|
200|
10/8
640|
645|
120|160| 110|110|
160|160| 140| 115|
135|
135|
10/7
RAO w/FD
20/15
8/6 8/8 10/8 8/8 8/6
10/10
10/8
180|
14/8
265|
265| 265|
265|
270|
120|120|
8/5
13/5
185|
285|
FILTER
8/8-UP
90|
90|
25/8
13/8
30/8RAO w/FD
20/15
270| 150|
24/17 RAOw/FD w/FD
RAO
24/17 w/FD
RAO
24/17 w/FD
RAO
24/17
SCALE:
= 1'-0
8 0 4 8 16
M2.2
M3.2
MIDDLE LEVEL FLOOR PLAN - NEW WORK - HVAC
NEW WORK - HVAC
FLOOR PLAN -
MIDDLE LEVEL
LINE LEGEND
POINT OF CONNECTION
EXISTING TO REMAIN
NEW WORK
GENERAL NOTES:(THIS SHEET ONLY)
A
IF DAMAGED DURING CONSTRUCTION.
CEILING TILES, CEILING GRIDS, OR FIXTURES TO MATCH EXISTING
PERFORMED ABOVE FINISHED SPACES. REPAIR/REPLACE ANY
REMOVE EXISTING CEILING TILES WHERE SCOPE OF WORK ISB
SURVEY EXISTING CONDITIONS TO VERIFY ITEMS TO BE DEMOLISHED.
ALL CONDITIONS FOR DEMOLITION MAY NOT BE SHOWN.
C
TO NEW EQUIPMENT IN NEW WORK.
WHICH IS REQUIRED TO REPLACE FOR PROPER CONNECTIONS
ALL EXISTING DUCTWORK TO REMAIN EXCEPT FOR THAT
NOTES:(THIS SHEET ONLY)
NEW THERMOSTAT.1
1 1
T
T
TU2-8
T
TU2-6
T
T
TU2-5
T
TU2-4
T TU2-3 T
T
TU2-1
T
TU2-10
TU2-1
TU2-2
TU2-9
TU2-9
TU2-8
TU2-7
TU2-10
TU2-3
34/12 20/12
TU2-2
TU2-4
TU2-7
18/12
TU2-6
TU2-5
w/FD
30/24 UP
HWS
HWR
H W
S H
W R ƒ"
1‚"
H W
S H
W R
1"ƒ"
2 •" FLOW INDICATOR VALVE; SET @ 0.5 GPM.
B
C
D
MECH. RM.
STAIR #1
STAIR #2
OFFICE
OFFICE
OFFICE
CLOSET
ELEVATOR325
OFFICE
TOILET
MULTIPURPOSE
JAN
STORAGE301
PROJ
STORAGE
CLOS
CLOS
TOILET
WOMEN
MEN
CORRIDOR
STUDY CARRELS
A/V CENTER309
SEAL
SCALE:
FILE PATH:
P:\22119\22119m23.dgn
DATE PLOTTED
DGN FILE
03-DEC-2024
SHEET NUMBER:
316 CORPORATE PARKWAY
NBP Engineers, Inc.
MACON, GEORGIA 31210
NBP
ENGINEERS
478-745-1691 www.nbpengineers.com
No. REVISIONS/SUBMISSIONS DATE
DRAWN:
CHECKED:
DESIGNED:
DATE:
PROJECT NUMBER:
P R
O J E
C T
T
IT
L E
SHEET TITLE:
CONSULTANTS
THIS DRAWING IS THE PROPERTY OF THE
ENGINEER AND MAY NOT BE REPRODUCED
OR USED IN WHOLE OR IN PART
WITHOUT HIS WRITTEN PERMISSION. IT IS
TO BE USED FOR THE PROJECT
SPECIFICALLY IDENTIFIED HEREIN AND TO
BE RETURNED UPON REQUEST.
P:\22119\22119m23.dgn
AS SHOWN
WSH
LTF
WSH
22119
C O
L U
M B
U S S
T A
T E U
N
IV
E R
S
IT
Y
COA Expiration: 6.30.2026
COA#PEF000774
NBP Engineers, Inc.
C o lu m b u s
G e o rg ia
12.03.2024
T
P R
O J E
C T N o
C
S U -1
-2
IL
L
G E S H
A L L H
V A
C U
P G
R A
D E S
8/924/9
|395
|395
|395
|395
EF-4
|460
|310 |225 |265
|265 |265
|270
14/10
7/8 1 1/8
22/8
10/8 15/8
25/10
|465
13/8 16/8
|145 w/FD
30/18 RAO
w/FD
30/18 RAO
10/8
|195 |195 |185
|40
R
16/1 1
320|
215|
320|
320|
320|
320|
320|
320|
325|
6/6
8/8
6/6
10/7 8/4
18-10-DN
14/14-UP
EF-5
w/FD
30/18 RAO
18/18
60|
135|
195|
12/5 8/5
|395
|395
|265
SCALE:
= 1'-0
8 0 4 8 16
M2.3
LINE LEGEND
POINT OF CONNECTION
EXISTING TO REMAIN
NEW WORK
GENERAL NOTES:(THIS SHEET ONLY)
A
IF DAMAGED DURING CONSTRUCTION.
CEILING TILES, CEILING GRIDS, OR FIXTURES TO MATCH EXISTING
PERFORMED ABOVE FINISHED SPACES. REPAIR/REPLACE ANY
REMOVE EXISTING CEILING TILES WHERE SCOPE OF WORK ISB
SURVEY EXISTING CONDITIONS TO VERIFY ITEMS TO BE DEMOLISHED.
ALL CONDITIONS FOR DEMOLITION MAY NOT BE SHOWN.
C
TO NEW EQUIPMENT IN NEW WORK.
WHICH IS REQUIRED TO REPLACE FOR PROPER CONNECTIONS
ALL EXISTING DUCTWORK TO REMAIN EXCEPT FOR THAT
NOTES:(THIS SHEET ONLY)
NEW THERMOSTAT.1
UPPER LEVEL FLOOR PLAN - NEW WORK - HVAC
NEW WORK - HVAC
FLOOR PLAN -
UPPER LEVEL
T
TU3-4
T
TU3-5
TU3-6 T
T
TU3-3
T TU3-8 T
TU3-7
TTU3-1
TTU3-2
TU3-1
52/14
40/14 28/14
22/14
18/12
TU3-3
TU3-2
TU3-8
TU3-7
TU3-6
TU3-5TU3-4
M3.3
HWR
HWS
H W
R H
W S
HWS
HWR
•" ƒ" 1"
2 •" FLOW INDICATOR VALVE; SET @ 0.5 GPM.
H W
S H
W R
1"
4 5
SCALE:
FILE PATH:
P:\22119\22119m31.dgn
DATE PLOTTED
DGN FILE
03-DEC-2024
SHEET NUMBER:
316 CORPORATE PARKWAY
NBP Engineers, Inc.
MACON, GEORGIA 31210
NBP
ENGINEERS
478-745-1691 www.nbpengineers.com
No. REVISIONS/SUBMISSIONS DATE
DRAWN:
CHECKED:
DESIGNED:
DATE:
PROJECT NUMBER:
P R
O J E
C T
T
IT
L E
SHEET TITLE:
CONSULTANTS
THIS DRAWING IS THE PROPERTY OF THE
ENGINEER AND MAY NOT BE REPRODUCED
OR USED IN WHOLE OR IN PART
WITHOUT HIS WRITTEN PERMISSION. IT IS
TO BE USED FOR THE PROJECT
SPECIFICALLY IDENTIFIED HEREIN AND TO
BE RETURNED UPON REQUEST.
P:\22119\22119m31.dgn
AS SHOWN
WSH
LTF
WSH
22119
C O
L U
M B
U S S
T A
T E U
N
IV
E R
S
IT
Y
COA Expiration: 6.30.2026
COA#PEF000774
NBP Engineers, Inc.
C o lu m b u s
G e o rg ia
12.03.2024
T
P R
O J E
C T N o
C
S U -1
-2
IL
L
G E S H
A L L H
V A
C U
P G
R A
D E S
4 5
60/20 RA
P-2 BLR
ET
FD
FD FD
LOUVER
24"x24" OA
LOUVER
INTAKE
44"x24"
GAS PIPING
EXISTING
EXISTING 8"{ VENT
WH
FACP
BA E
M/C
ELEVATOR
MSM
CHS
CHR
HWRH
W
S
EXISTING
ACP TO REMAIN
H W
R
C H
R C H S
H W
S
H W
R
M3.1
LINE LEGEND
EXISTING TO REMAIN
DEMOLITION
SCALE:
= 1'-0
4 0 2 4 8
SCALE:
= 1'-0
4 0 2 4 8
NEW WORK
POINT OF CONNECTION
LARGE SCALE - MECH. RM. 109 - DEMOLITION - HVAC LARGE SCALE - MECH. RM. 109 - NEW WORK - HVAC
NEW WORK - HVAC
DEMOLITION &
MECH. RM. 109 -
LARGE SCALE -
60/20 RA
AU-1
P-2 BLR
ET
P-3
EF-1
FD
FD
FD
FD
LOUVER
24"x24" OA
LOUVER
INTAKE
44"x24"
GAS PIPING
EXISTING
EXISTING 8"{ VENT
15/8
20/9
WH
M3.1
SCALE:
= 1'-0
4 0 2 4 8
SECTION @ AU-1 - DEMOLITION - HVAC
18/8
8/12
18/18
FD
12/24
60/20 RA
8/24 8/18 8/15 9/20
FILTER
AU-1
CLG
2•"
1"
MVD
2•" HWR
2•" HWS
4" CHR
4" CHR
SCALE:
= 1'-0
4 0 2 4 8
SECTION @ AU-1 - NEW WORK - HVAC
NOTES:(THIS SHEET ONLY)
REMOVE EXISTING AU-1.
PATCH UNUSED OPENINGS TO MATCH EXISTING.
REMOVE EXISTING CONCRETE PAD.
EXISTING 16"{ FLUE CAPPED & ABANDONED IN PLACE.4
(TYP)
24/12
FAN
COIL
COOLING
FILTER
PLENUM
MIXING AIR
AH-1
TU1-5
TU1-4
TU1-6
FD
18/8
22/14
14"{
TU1-3
M3.1 60/20
AH-1
12/24
NEW CONCRETE PAD
14/22
14"{
FACP
BA E
M/C
ELEVATOR
MSM
CHS
CHR
HWRH
W
S
CORRESPONDING CONCRETE PAD
ABANDONED PUMP &
REMOVE EXISTING
LOUVER TO REMAIN
EXHAUST FAN; EXISTING
REMOVE EXISTING
ABANDONED ACP'S
REMOVE EXISTING
EXISTING
ACP TO REMAIN
REMOVE ALL EXISTING ABANDONED CONCRETE PAD IN MECHANICAL ROOM.
6 7
EXISTING HW PUMP TO REMAIN.
7 EXISTING BOILER TO REMAIN.
8 REMOVE EXISTING ABANDONED PIPING IN MECHANICAL ROOM.
H W
R
C H
R C H S
H W
S
H W
R
EXISTING HW PUMP
STARTER SERVING
WITH DISCONNECT &
& STARTERS ALONG
ABANDONED DISCONNECTS
REMOVE EXISTING
SF-1ACP
VFD-AH-1
STARTER P-2
NEW COMBO
NEW 24"x24" OUTSIDE AIR INTAKE LOUVER IN EXISTING OPENING.9
AFMS
24/24
12/12
MAX OA AVD
MIN OA AVD
FILE PATH:
P:\22119\22119m32.dgn
DATE PLOTTED
DGN FILE
03-DEC-2024
SHEET NUMBER:
316 CORPORATE PARKWAY
NBP Engineers, Inc.
MACON, GEORGIA 31210
NBP
ENGINEERS
478-745-1691 www.nbpengineers.com
No. REVISIONS/SUBMISSIONS DATE
DRAWN:
CHECKED:
DESIGNED:
DATE:
PROJECT NUMBER:
P R
O J E
C T
T
IT
L E
SHEET TITLE:
CONSULTANTS
THIS DRAWING IS THE PROPERTY OF THE
ENGINEER AND MAY NOT BE REPRODUCED
OR USED IN WHOLE OR IN PART
WITHOUT HIS WRITTEN PERMISSION. IT IS
TO BE USED FOR THE PROJECT
SPECIFICALLY IDENTIFIED HEREIN AND TO
BE RETURNED UPON REQUEST.
P:\22119\22119m32.dgn
AS SHOWN
WSH
LTF
WSH
22119
C O
L U
M B
U S S
T A
T E U
N
IV
E R
S
IT
Y
COA Expiration: 6.30.2026
COA#PEF000774
NBP Engineers, Inc.
C o lu m b u s
G e o rg ia
12.03.2024
T
P R
O J E
C T N o
C
S U -1
-2
IL
L
G E S H
A L L H
V A
C U
P G
R A
D E S
78/20 RA
C
H W
R
H W
S
C H
R
C H S
M3.2
SCALE:
= 1'-0
4 0 2 4 8
SCALE:
= 1'-0
4 0 2 4 8
NEW WORK
POINT OF CONNECTION
LARGE SCALE - MECH. RM. 225 - DEMOLITION - HVAC LARGE SCALE - MECH. RM. 225 - NEW WORK - HVAC
78/20 RA
/8
18/18
18/820/825/8
18/8
8/8
13/8
10/10
AU-2
FILTER
18/8
78/20 RA
4/8
8/30
EXISTING MVD IN VERTICL (TYP)
10/10
CEILING CEILING
SCALE:
= 1'-0
4 0 2 4 8
SECTION - MECH. RM. 225 - DEMOLITION - HVAC
8/25 8/18
8/13 8/19
8/16
1 •"-DN
2•"-DN
C H
R
C H S
H W
R
H W
S
AU-2
CEILINGCEILING
SCALE:
= 1'-0
4 0 2 4 8
SECTION - MECH. RM. 225 - NEW WORK - HVAC
(TYP)
PATCH OPENINGS IN WALL NOT USED TO MATCH EXISTING.
REMOVE EXISTING AU-2.
EXISTING 78/20 WALL OPENING TO REMAIN.
FILTER
RA AVD
CONCRETE PAD
AH-2
20/14
34/12
36/14
12/34
20/54
RA AVD
PLENUM
MIXING
F
IL
T E
R
C O
IL
C O
O L
IN
G
F A
N
AH-2
CONCRETE PAD
C
LINE LEGEND
EXISTING TO REMAIN
DEMOLITION
NEW WORK - HVAC
DEMOLITION &
MECH. RM. 225 -
LARGE SCALE -
NOTES:(THIS SHEET ONLY)
REMOVE EXISTING ACP
4 REMOVE EXISTING HW & CHW PIPING TO 0'-12" ABOVE FINISHED FLOOR.
REMOVE EXISTING STARTER
REMOVE EXISTING 18/18 OA DUCT
EXISTING FLOOR DRAIN
5 REMOVE EXISTING FIBERGLASS INSULATION FROM WALLS OF MECHANICAL ROOM.
AFMS
COOLING COIL
FAN
1•"
1‚"HWR/S
2•" CHR/S
30/24
2•"
H W
S
H W
R
HWR
HWS
CHR
CHS
3"
30"x18" MAX AVD
30"x6" MIN AVD
H W
R
H W
S
C H
R
C H S
PLENUM
MIXING
CONNECT NEW 1•" HWR/S PIPING TO EXISTING 2" HWR/S PIPING AT FLOOR.6
7 3" CHR/S DOWN; CONNECT TO EXISTING CHR/S PIPING AT FLOOR.
FILE PATH:
P:\22119\22119m33.dgn
DATE PLOTTED
DGN FILE
03-DEC-2024
SHEET NUMBER:
316 CORPORATE PARKWAY
NBP Engineers, Inc.
MACON, GEORGIA 31210
NBP
ENGINEERS
478-745-1691 www.nbpengineers.com
No. REVISIONS/SUBMISSIONS DATE
DRAWN:
CHECKED:
DESIGNED:
DATE:
PROJECT NUMBER:
P R
O J E
C T
T
IT
L E
SHEET TITLE:
CONSULTANTS
THIS DRAWING IS THE PROPERTY OF THE
ENGINEER AND MAY NOT BE REPRODUCED
OR USED IN WHOLE OR IN PART
WITHOUT HIS WRITTEN PERMISSION. IT IS
TO BE USED FOR THE PROJECT
SPECIFICALLY IDENTIFIED HEREIN AND TO
BE RETURNED UPON REQUEST.
P:\22119\22119m33.dgn
AS SHOWN
WSH
LTF
WSH
22119
C O
L U
M B
U S S
T A
T E U
N
IV
E R
S
IT
Y
COA Expiration: 6.30.2026
COA#PEF000774
NBP Engineers, Inc.
C o lu m b u s
G e o rg ia
12.03.2024
T
P R
O J E
C T N o
C
S U -1
-2
IL
L
G E S H
A L L H
V A
C U
P G
R A
D E S
ABOVE CEILING
78/20 RA
TO REMAIN
78/20 RA
EXISTING
ELECTRICAL PANEL
EXISTING
M3.3
SCALE:
= 1'-0
4 0 2 4 8
SCALE:
= 1'-0
4 0 2 4 8
LINE LEGEND
EXISTING TO REMAIN
DEMOLITION
NEW WORK
POINT OF CONNECTION
LARGE SCALE - MECH. RM. 324 - DEMOLITION - HVAC LARGE SCALE - MECH. RM. 324 - NEW WORK - HVAC
NEW WORK - HVAC
DEMOLITION &
MECH. RM. 324 -
LARGE SCALE -
8/8
22/8
16/8
25/10
20/10
18/18
30/20 OA
ABOVE CEILING
78/20 RA
AU-3
FILTER
8/16
24/18
CEILING CEILING
BOTTOM OF JOIST
MVD
SCALE:
= 1'-0
4 0 2 4 8
SECTION - MECH. RM. 324 - DEMOLITION - HVAC
M3.3
VERTICAL (TYP)
EXISTING MVD IN
20/30 OA
18/18
CEILINGCEILING
SCALE:
= 1'-0
4 0 2 4 8
SECTION - MECH. RM. 324 - NEW WORK - HVAC
NOTES:(THIS SHEET ONLY)
EXISTING OPENING IN FLOOR TO REMAIN.
3 EXISTING WALL OPENING AND FIRE DAMPER TO REMAIN.
4 REMOVE EXISTING AIR HANDLER.
5 PATCH WALL OPENING NOT REUSED TO MATCH EXISTING.
5 (TYP)
6 REMOVE EXISTING CONCRETE PAD.
METAL CURB CAP.
REMOVE EXISTING OA INTAKE HOOD ON ROOF. PROVIDE INSULATED
FAN
FILTER
MIXING PLENUM
52/14
RA DAMPER
TO REMAIN
78/20 RA
EXISTING
M
IX
IN
G
P L
E N
U M
F
IL
T E
R
C O
IL
C O
O L
IN
G
F A
N
48/24
AH-3
RA DAMPER
AH-3
CONCRETE PAD
REMOVE EXISTING ACP
ELECTRICAL PANEL
EXISTING
AU-3
REMOVE EXISTING STARTER
PATCH FLOOR TO MATCH EXISTING
& CORRESPONDING CONCRETE CURB;
REMOVE EXISTING CHW & HW PIPING
REMOVE EXISTING FIBERGLASS INSULATION FROM WALLS OF MECHANICAL ROOM.7
30/24 DN
2•"
AFMS
36"x18" MAX OA AVD
36"x6" MIN OA AVD
1‚" HWR/S DN
2•" CHR/S DN
MAV
MAV1‚"
CHR
CHS
H W
R
H W
S
HOOD ON ROOF
90"x24" OA INTAKE
FILE PATH:
P:\22119\22119m41.dgn
DATE PLOTTED
DGN FILE
03-DEC-2024
SHEET NUMBER:
316 CORPORATE PARKWAY
NBP Engineers, Inc.
MACON, GEORGIA 31210
NBP
ENGINEERS
478-745-1691 www.nbpengineers.com
No. REVISIONS/SUBMISSIONS DATE
DRAWN:
CHECKED:
DESIGNED:
DATE:
PROJECT NUMBER:
P R
O J E
C T
T
IT
L E
SHEET TITLE:
CONSULTANTS
THIS DRAWING IS THE PROPERTY OF THE
ENGINEER AND MAY NOT BE REPRODUCED
OR USED IN WHOLE OR IN PART
WITHOUT HIS WRITTEN PERMISSION. IT IS
TO BE USED FOR THE PROJECT
SPECIFICALLY IDENTIFIED HEREIN AND TO
BE RETURNED UPON REQUEST.
P:\22119\22119m41.dgn
AS SHOWN
WSH
LTF
WSH
22119
C O
L U
M B
U S S
T A
T E U
N
IV
E R
S
IT
Y
COA Expiration: 6.30.2026
COA#PEF000774
NBP Engineers, Inc.
C o lu m b u s
G e o rg ia
12.03.2024
T
P R
O J E
C T N o
C
S U -1
-2
IL
L
G E S H
A L L H
V A
C U
P G
R A
D E S
M4.1
HVAC
FLOW DIAGRAM -
FLOW DIAGRAM AH-1
S.A.
TT
FAR
DP
1 WALL
EXTERIOR
SAF
VFD
VFD R FAR
VLV
TTLL
TT
OA
OA
AFMS
RA
SPS
AI
FIL
T
TUC
H W
R
H W
S
ZONE
COND.
T-X
T
TUC
H W
R
H W
S
ZONE
COND.
T-X
TU-X
SAT
TU-X
TU-X
SAT
TU-X
SPS
H
Y
S T
M
G R
A P
IC
D
IS
P L
A Y
S T
A R
T
S T
O P
E N
A B
L E
D
IS
A B
L E
O P
E N
C L
O S
E
S T
A R
T
S T
O
K E
U P
S E
T P
O
IN
T
J
U S
T
D
C
N T
R O
L
D
IF
F E
R E
N T
IA
L
P
R E S
S U
R E
P R
E S
S U
R E
S
W
IT
C H
A U
X
IL
IA
Y
N T
A C
T
A L
A
N T
A C
T
T E
M P
E R
A T
U R
E
R E
L A
T
IV
U
M
ID
IT
Y
P R
E S
S U
R E
H
IG
H
L
W
IM
IT
R
N
T A
L
IZ
A T
IO
N
P R
O P
O R
T
IO
N A
L
P R
O P
IN
T E
G R
A L
T
IM
E
S
C H
E D
U L
E
S
S
O P
T
IM
A R
T
S T
O P
D A
Y
N
IG
T B
A C
K
D E
M A
IT
C Y
C L
E
R E S
T
IM
IZ
A T
IO
N
E C
O N
O M
IZ
E R
F A
IL
U
D E (S
T E S
A
N D
N O
T E S
OUTPUTS INPUTS SOFTWARE
DDC PANELS
INPUT/OUTPUT
SUMMARIES
DIGITAL ANALOG ANALOG ALARM DDC ENERGY MGMT.DIGITAL
C U
R R
E
L A
Y
D R
IV
E
S
T A
T U
S
S P
E E
D
IN
D
IC
A T
IO
N
S P
E
N T
R O
L
E
W
IT
C H
C O
IR
F
O W
PRIMARY AIR FLOW
AIR TERMINAL UNITS (TU/FP)
HC VALVE
C
O
C
NOTES:
1. FAILURE MODES:
2. WHERE FAILURE MODE IS INDICATED, THE INDICATED POSITION SHALL OCCUR ON INTERRUPTION OF
ELECTRIC POWER TO THE DDC PANEL.
L - LAST COMMAND
L
C A
L C
U L
A T
IN
T
C
O - OPEN OR ON
C - CLOSE OR OFF
PERCENTAGE DESIGN FLOW-HEATING
PERCENTAGE DESIGN FLOW-COOLING
TAG
OA 1
OA 2
AFMS 1
FAR
TT 1
TT 2
TT 3
SPS H
SPS 1
TUC-XX
TUC-XX
TUC-XX
ZONE-SPACE TEMP.
SAT
LL
HT
CC-L.A.T.
L.L.-TEMP.
RA 1
T-XX
F.A. RELAY
P O
S
IT
IO
N
IN
D
IC
A T
IO
N
O P
E N
C L
O S
S
IT
IO
N
CC CONTROL VALVE
TT 4
ACP
C
VLV 1
HIGH LIMIT SPS
L
BUILDING PRESSUREDP 1
NOT TO SCALE
FAR
TT
HT
CHS
CHR
AI
MCP
D0 A0 D1
FAN ARRAY
AHU AHU
CC
AHU
AHU VAV SYSTEM
S T
A T
U S
T R
E
G
LOGS
VFD 1
AHU
RA DAMPER
RA TEMP.
RA-RH
RA AVD
RA-PATH
MIN. OA DAMPER
MAX. OA DAMPER
MIN. OA AFMS
MAX. OA AVD
OA
O A
MIN. OA AVD
OA
SA FAN ARRAY-VFD
SA-TEMP.
SA-SPS
SA DAMPER ACTUATOR
SA TEMP. TO ZONE
MA TEMP.
SD
SD
FILE PATH:
P:\22119\22119m51.dgn
DATE PLOTTED
DGN FILE
03-DEC-2024
SHEET NUMBER:
316 CORPORATE PARKWAY
NBP Engineers, Inc.
MACON, GEORGIA 31210
NBP
ENGINEERS
478-745-1691 www.nbpengineers.com
No. REVISIONS/SUBMISSIONS DATE
DRAWN:
CHECKED:
DESIGNED:
DATE:
PROJECT NUMBER:
P R
O J E
C T
T
IT
L E
SHEET TITLE:
CONSULTANTS
THIS DRAWING IS THE PROPERTY OF THE
ENGINEER AND MAY NOT BE REPRODUCED
OR USED IN WHOLE OR IN PART
WITHOUT HIS WRITTEN PERMISSION. IT IS
TO BE USED FOR THE PROJECT
SPECIFICALLY IDENTIFIED HEREIN AND TO
BE RETURNED UPON REQUEST.
P:\22119\22119m51.dgn
AS SHOWN
WSH
LTF
WSH
22119
C O
L U
M B
U S S
T A
T E U
N
IV
E R
S
IT
Y
COA Expiration: 6.30.2026
COA#PEF000774
NBP Engineers, Inc.
C o lu m b u s
G e o rg ia
12.03.2024
T
P R
O J E
C T N o
C
S U -1
-2
IL
L
G E S H
A L L H
V A
C U
P G
R A
D E S
M5.1
DETAILS - HVAC
WALL
AS SYSTEM PIPE.
MANUAL AIR VENT
TERMINATE DRAIN WITH HOSE END
CONNECTION 18" ABOVE FLOOR.
WHERE AIR VENTS OCCUR ABOVE ACCESSIBLE
CEILING. LOCATE VALVE AND TERMINATE DRAIN
HERE, UNLESS NOTED OTHERWISE AND POSITION
VALVE FOR VERTICAL DOWN DISCHARGE.
•" PIPE SAME MATERIAL
2•"
VERTICAL
PIPE
SUPPORT
WELDED PIPETHREADED / BRAISED
PIPING
BALL VALVE (EXPOSED) OR
GATE VALVE (CONCEALED)
ARRANGEMENT FOR LOCATIONS
WITH LIMITED CLEARANCE
6"MAX.
TYPICAL DRAIN VALVE CONNECTION
ELEVATION
THREADED PIPING
ELEVATION
WELDED PIPING
TYPICAL WATER PIPING
REDUCER, IF REQUIRED
ƒ" GATE VALVE
ADAPTER TO ƒ" HOSE THREAD
PROVIDE HOSE CAP NUT
NOTES:
DRAIN ALL LOW POINTS AS INDICATED ABOVE.1.
2.WHERE SCALE POCKETS ARE SHOWN ON PIPE RISER DIAGRAMS
AND/OR PLANS LOCATE DRAIN AT BOTTOM OF SCALE POCKET.
HANGER ROD - SEE SPECIFICATIONS
SECTION OF RIGID INSULATION
SPECIFIED INSULATION
PIPE
• ROUND BEARING PLATE
PLATE WASHER
CUT ROD ABOVE ANGLE LEG
1" MIN.
TRAPEZE HANGER
LONG LEG VERTICAL
SEE SPECIFICATIONS
DOUBLE HEX NUTS
TRAPEZE PIPE HANGER
A
B
DRAIN
PAN
1"
UNIT TYPE
WHERE X = STATIC PRESSURE IN PAN IN INCHES - H2O
A B
ADAPTER
DRAW THRU 2" PLUS X X
AIR HANDLING UNIT DRAIN TRAP
CLEAN OUT
SEDIMENT BUCKET
LOOSE CAP
GRATE
REMOVABLE
FITTING
LOOSE
THIS SIDE
FLOOR DRAIN (REFER TO DIVISION 220000)
FLOOR
PER FOOT SLOPE
MINIMUM 1/8 INCH
SLOPE TO DRAIN AT
1" (MIN)
DRAIN PIPE AS SPECIFIED
2" MAX.
REQUIRED BY CONDITIONS
DRAIN TERMINATION AS
BLOW THRU 1" MIN. 1.5"X
TYPICAL PIPING AT TU HEATING COILS - 3 WAY
NOT TO SCALE
UNLESS OTHERWISE NOTED
6" THICK CONCRETE
(INERTIA PAD IDENTICAL)
HOUSEKEEPING PAD DETAIL
3"
8" MIN.
3"X3"X3/8" BY 3" LONG ANGLE IRON(FACTORY PROVIDED
MOUNTING CLIPS DESIGNED FOR SEISMIC RESTRAINT ARE
ACCEPTABLE). SECURE TO UNIT FRAME WITH TWO •"
BOLTS EACH. SECURE TO STRUCTURE WITH TWO EACH •"
BOLTS EXTENDED THRU PAD AND ATTACHED WITH ICBO
RATED FEMALE STUD WEDGE ANCHORS. PROVIDE TWO
RESTRAINTS PER SIDE.
"L" BENT, #3(MIN.) REBAR DOWELED
FLOOR
SLAB, FLOOR, OR SUPPORTING STRUCTURE.
ROUGH UP WHERE CONCRETE DOES NOT HAVE
BROOM FINISH OR ROUGHER.
10" MINIMUM ALL SIDES
EQUIPMENT
SAME SIZE AS THE NIPPLE ON THE DRAIN PAN
DRAIN LINE SHALL BE AT LEAST THE
ALL SIDES
ƒ" CHAMFER
INTO FLOOR AT 18"O.C. EACH WAY
#3 REBAR(MIN.) AT 12" O.C.
EACH WAY MID-DEPTH OF PAD
COIL
(PROVIDE IF RUNOUT PIPING
IS A HIGH POINT)
MANUAL AIR VENT
GAUGE COCK
BALANCE VALVE
HWR
HWS
3-WAY CONTROL VALVE
N.O.
GATE (BALL) VALVE
•" GATE VALVE W/
HOSE ADAPTER
TEST
PLUG
UNIONS (3)
UNION
W\HOSE ADAPTOR
•" GATE VALVE
(REFER TO DRAWING FOR PIPING ARRANGEMENT)
VALVE COEFFICIENTS
Cv
BALANCE VALVE
RETURN
SUPPLY
2 WAY CONTROL VALVE
AIR FLOW
COILS
TEST PLUG (TYPICAL)
AIR VENT - EXTEND THRU
UNIT CASING (PROVIDE WHERE
COIL IS NOT SELF VENTING)
SYSTEM
AH-1
BUTTERFLY VALVE
(PROVIDE CONNECTIONS FOR NUMBER OF STACKED COILS PROVIDED WITH UNIT)
AIR HANDLING UNIT COOLING COIL PIPING ISOMETRIC
AH-2 24
RUNOUT SIZE
2•"
PIPE
PIPE RISER CLAMP
3" X 3" X 1" RIBBED RUBBER
PIPE SLEEVE THRU FLOOR
& CORK ISOLATOR WITH 3"X3"
16 GAUGE PLATE ON TOP
(ENCASE PIPE & CLAMP IN INSULATION ON CHILLED WATER)
NOT TO SCALE
PIPE RISER CLAMP
NOT TO SCALE
NOT TO SCALE
NOT TO SCALE
NOT TO SCALE
NOT TO SCALE
NOT TO SCALE
AH-3 28 2•"
2•"
FILE PATH:
P:\22119\22119m52.dgn
DATE PLOTTED
DGN FILE
03-DEC-2024
SHEET NUMBER:
316 CORPORATE PARKWAY
NBP Engineers, Inc.
MACON, GEORGIA 31210
NBP
ENGINEERS
478-745-1691 www.nbpengineers.com
No. REVISIONS/SUBMISSIONS DATE
DRAWN:
CHECKED:
DESIGNED:
DATE:
PROJECT NUMBER:
P R
O J E
C T
T
IT
L E
SHEET TITLE:
CONSULTANTS
THIS DRAWING IS THE PROPERTY OF THE
ENGINEER AND MAY NOT BE REPRODUCED
OR USED IN WHOLE OR IN PART
WITHOUT HIS WRITTEN PERMISSION. IT IS
TO BE USED FOR THE PROJECT
SPECIFICALLY IDENTIFIED HEREIN AND TO
BE RETURNED UPON REQUEST.
P:\22119\22119m52.dgn
AS SHOWN
WSH
LTF
WSH
22119
C O
L U
M B
U S S
T A
T E U
N
IV
E R
S
IT
Y
COA Expiration: 6.30.2026
COA#PEF000774
NBP Engineers, Inc.
C o lu m b u s
G e o rg ia
12.03.2024
T
P R
O J E
C T N o
C
S U -1
-2
IL
L
G E S H
A L L H
V A
C U
P G
R A
D E S
M5.2
DETAILS - HVAC
WALL
3"MIN
DUCT
HORIZONTAL FIRE DAMPER
6"MAX
3"MIN
6"MAX
FLOOR
6"MAX
6"MAX
3"MIN.
3"MIN.
RIVET 8"
MAX. O.C.
DUCT
VERTICAL FIRE DAMPER
FIRE DAMPER DETAIL
S T
Y L
E
"A
S T
Y L
E
"B
S T
Y L
E
"C
STYLE "A"
STYLE "C"
STYLE "B"
DUCT TO SLEEVE JOINT.
'S' SLIP FOR LOW PRES-
SURE DUCT. FLANGE WITH
GASKET ON MEDIUM PRES-
SURE DUCT.
TRANSITION DUCT WHEN
SMALLER THAN DAMPER
FIRE DAMPER SAME
SIZE AS DUCT UNLESS
OTHERWISE NOTED
ALL FIRE DAMPERS ON THE PROJECT SHALL BE STYLE 'A' TYPE FIRE DAMPERS UNLESS OTHERWISE NOTED.
DAMPERS LOCATED IN MEDIUM OR HIGH PRESSURE DUCTWORK SHALL BE STYLE 'C' FIRE DAMPERS. WHERE
DAMPERS ARE INSTALLED IN DRYWALL PARTITION, STUD FRAMING SHALL BE PROVIDED ON ALL FOUR SIDES
ON DAMPER.
‚" MIN. CLEARANCE SHALL
COMPLY WITH UL LISTING
FOR DAMPER FURNISHED.
GALVANIZED SLEEVE OF
GAGE SPECIFIED FOR
JOINT TYPE,‚" LARGER
THAN DAMPER (DUCT) SIZE
DUCT TO SLEEVE JOINT.
'S' SLIP FOR LOW PRES-
SURE DUCT. FLANGE WITH
GASKET ON MEDIUM PRES-
SURE DUCT.
FIRE DAMPER SAME SIZE AS
DUCT UNLESS OTHERWISE NOTED
RIVET 8"
MAX. O.C.
SMALLER THAN DAMPER
TRANSITION DUCT WHEN
COPE AT CORNERS
GALVANIZED ANGLE FRAME
1•" X 1•" X 14 GAUGE
FOR DAMPER FURNISHED.
COMPLY WITH UL LISTING
‚" MIN. CLEARANCE SHALL
GALVANIZED SLEEVE OF
GAGE SPECIFIED FOR
JOINT TYPE,‚" LARGER
THAN DAMPER (DUCT) SIZE
LOUVER
WALL MOUNTED LOUVER WITH PLENUM
COUNTER
FLASHING
20 GAUGE SLEEVE
16"MIN.
REFER TO ARCHITECTURAL
FOR STRUCTURE MATERIALS
SUB FRAME
IN BLOCK WALLS,
USE LINTELBLOCK
ON HEAD AND SILL
PROVIDE MINIMUM 16 INCH
PLENUM BEHIND LOUVER
CEILING
DIFFUSER
SCREWS, MINIMUM 2 PER SIDE
45 DEGREE SIDE TAKE-OFF WITH GASKETED
TYPICAL TRANSITION TO
SINGLE DIFFUSER
FLANGE AND FIELD SUPPLIED GASKET
OR EQUIVALENT
45 MAXIMUM
CEILING
DIFFUSER
.75 RADIUS
ADJUSTABLE
ELBOW
SEAL ELBOW JOINTS WITH DUCT
ELBOW SHALL BE DIRECTLY ON TOP OF DIFFUSER
SEALER AFTER ELBOW IS SET (TYPICAL)
WITH OFFSET
WITHOUT OFFSET
.75 RADIUS
ADJUSTABLE ELBOW
45 MAX OFFSET
EXTEND FLEXIBLE DUCT
FROM DIFFUSER ELBOW
TO TAKEOFF FITTING DO
NOT EXCEED FIVE FEET(5)
LENGTH OF FLEXIBLE DUCT
.75 RADIUS
ADJUSTABLE ELBOW
45 MAX OFFSET
EXTEND OPERATOR THRU
DUCT INSULATION (NOT SHOWN)
BRANCH DUCT
SAME SIZE AS
DIFFUSER THROAT
EXTEND FLEXIBLE DUCT
FROM DIFFUSER ELBOW
NOT TO SCALE
FOR RUNOUT SIZE, UNLESS OTHERWISE NOTED
REFER TO GRILLE SCHEDULE
DIFFUSER RUNOUT DUCT TAKEOFF
BALANCING DAMPER WITH LOCKING QUADRANT.
OMIT DAMPER IF DAMPER SPECIFIED AT NECK
OF DIFFUSER IN GRILLE SCHEDULE OR
TAKE-OFF IS ABOVE INACCESSIBLE CEILING
WITH NO STRAIGHT DUCT BETWEEN ELBOW AND DIFFUSER
BRANCH DUCT
SAME SIZE AS
DIFFUSER THROAT
TO TAKEOFF FITTING
DO NOT EXCEED FIVE FEET(5)
LENGTH OF FLEXIBLE DUCT
NOT TO SCALE
NOT TO SCALE
B
C
D
1 10
PATIENT ED.
1 1 1
SUPPLY
MECH. RM.
LOCKER RM.
STAIR #1
STAIR #2
NURSING STOR.
MEN
WOMEN
WAITING
OFFICE
OFFICE
OFFICE
OFFICE
1 17
STORAGE
1 18
RECORDS
1 19
STERILIZE
FACULTY DEV.
1 16
DENTAL CLINIC
1 12
DARK RM.
1 14
X-RAY
1 13
STORAGE
1 15
DEMONSTRATION
SEAL
SCALE:
FILE PATH:
P:\22119\22119e21.dgn
DATE PLOTTED
DGN FILE
03-DEC-2024
SHEET NUMBER:
316 CORPORATE PARKWAY
NBP Engineers, Inc.
MACON, GEORGIA 31210
NBP
ENGINEERS
478-745-1691 www.nbpengineers.com
No. REVISIONS/SUBMISSIONS DATE
DRAWN:
CHECKED:
DESIGNED:
DATE:
PROJECT NUMBER:
P R
O J E
C T
T
IT
L E
SHEET TITLE:
CONSULTANTS
THIS DRAWING IS THE PROPERTY OF THE
ENGINEER AND MAY NOT BE REPRODUCED
OR USED IN WHOLE OR IN PART
WITHOUT HIS WRITTEN PERMISSION. IT IS
TO BE USED FOR THE PROJECT
SPECIFICALLY IDENTIFIED HEREIN AND TO
BE RETURNED UPON REQUEST.
P:\22119\22119e21.dgn
AS SHOWN
KMS
BCO
KMS
22119
C O
L U
M B
U S S
T A
T E U
N
IV
E R
S
IT
Y
COA Expiration: 6.30.2026
COA#PEF000774
NBP Engineers, Inc.
C o lu m b u s
G e o rg ia
12.03.2024
T
P R
O J E
C T N o
C
S U -1
-2
IL
L
G E S H
A L L H
V A
C U
P G
R A
D E S
TU1-1
TU1-2
AH-1
TU1-5
TU1-4
TU1-6
TU1-3
SF-1ACP
VFD-AH-1
STARTER P-2
NEW COMBO
SCALE:
= 1'-0
8 0 4 8 16
E2.1
LINE LEGEND
POINT OF CONNECTION
EXISTING TO REMAIN
NEW WORK
LOWER LEVEL FLOOR PLAN - NEW WORK - ELECTRICAL
ELECTRICAL
NEW WORK -
FLOOR PLAN -
LOWER LEVEL
MSM
WH
ET
FACP
BA E
M/C
ELEVATOR
P-2
ACP
BLR
RECEPTACLES
CIRCUITS
DUPLEX - NORMAL
GFI DUPLEX - NORMAL
ELECTRICAL LEGEND
WP WEATHER PROOF OUTLET
RACEWAY EXPOSED
FLEXIBLE RACEWAY
CONDUIT UP
CONDUIT DOWN
HOMERUN- ONE ARROW PER CIRCUIT
ONE CROSSMARK PER WIRE
(3 WIRE UNLESS SHOWN)
RACEWAY CONCEALED IN CEILING OR WALL
RACEWAY IN GROUND, SLAB, OR UNDER FLOOR
CAP
CONNECTION TO EQUIPMENT
GENERAL EQUIPMENT
BACKBOARD
F
PANELBOARD-250 VAC OR LESS
SURFACE MOUNTED
PANELBOARD-250 VAC OR LESS
RECESSED
M MANUAL STARTER AND MOTOR RATED SWITCH
EMERGENCY PUSHBUTTON
EXHAUST FAN
MOTOR
JJ J
COMMUNICATIONS
ENCLOSED CIRCUIT BREAKER
JUNCTION BOX - WALL/CEILING/FLOOR
DISCONNECT SWITCH: "F" IF FUSED
FRAME AMPS/POLES/NEMA TYPE
FUSE PER MANUFACTURERS RECOMMENDATIONS
SURGE SUPPRESSOR
COMBINATION STARTER AND DISCONNECT
# DATA OUTLET, QUANTITY OF JACKS AS NOTED
FIRE ALARM EQUIPMENT
R FIRE ALARM RELAY
J
GENERAL NOTES:(THIS SHEET ONLY)
A
NOTES:(THIS SHEET ONLY)
TERMINAL UNITS TO THIS BREAKER.
NEW BREAKERS. ADD NEW 20/1P BREAKER AND CIRCUIT ALL THE NEW
A NEW PANEL IS LOCATED ADJACENT TO ORIGINAL PANEL A WITH SPACE FOR 2
AND SWITCHES. CHAIN HANG NEW LIGHTS. BASIS OF DESIGN IS THE COLUMBIA CLS.
REPLACE THE EXISTING. REMOVE ALL EXISTING LIGHTS, MAINTAIN CIRCUITING
PROVIDE FOUR NEW 1x4 LED STRIP FIXTURES FOR THE MECHANICAL ROOM TO
EXISTING POWER PANELS ARE WESTINGHOUSE TYPE INSTALLED IN 1970.
NEW TU. MAKE ALL FINAL CONNECTIONS.
ROUTED NEATLY TIGHT TO STRUCTURE FOLLOW BUILDING LINES TO EACH
MAINTENANCE WITHOUT TURNING ALL OF THEM OFF. USE 3#12 AWG MC CABLE
WIRE THE TERMINAL UNITS IN SUCH A WAY THAT ONE CAN BE TURNED OFF FOR
RECEPTACLE AT ACP SHALL BE 5-20R TYPE.
LIGHTS AND INTEGRAL SERVICE RECEPTACLE. ROUTE TO EACH WITH 3#12 IN •"EMT.
POWER THE NEW ACP RECEPTACLE. USE THIS SAME CIRCUIT TO POWER THE AHU
PROVIDE A NEW 20/1P BREAKER IN THE EXISTING PANEL NOTED IN NOTE 2 TO
SHUTDOWN AND THE GENERAL BUILDING ALL ALARM SHALL SOUND.
THE EXISTING SIMPLEX SLC CIRCUIT. UPON DETECTION OF SMOKE THE AHU SHALL
ADD NEW DUCT DETECTOR IN THE SUPPLY SIDE OF THE NEW AHU. CONNECT TO
ON 48" CENTERS.
ASSUME 75' OF CAT CABLE IS REQUIRED. SUPPORT IN J HOOKS ABOVE CEILING
CABLE ON THE JACK AND BACK IN THE EXISTING DATA CLOSET. FOR PRICING
PROVIDE A NEW RJ45 DATA JACK AT THE ACP. TERMINATE CAT 6 PLENUM RATED
LOCATE @ACP 5
WITH 4#12 AWG IN ƒ" EMT.
DISCONNECT TO POWER THE NEW VFD. MAKE CONNECTION FROM VFD TO NEW AHU
AHU-1 IS FED FROM THIS WIREWAY. REMOVE EXISTING STARTER AND USE THE EXISTING
DUCT MOUNTED SMOKE DETECTOR
SMOKE DETECTOR: CEILING / WALL
HEAT DETECTOR: CEILING / WALL
B
C
D
STAIR #1
STAIR #2
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
LOUNGE
LOBBY
CLOSET
TOILET
OFFICE
OFFICE
OFFICE
OFFICE
TOILET
WOMENS
STORAGE
TOILET
SEMINAR
CLASSROOM217
CLASSROOM
SEMINAR
CONFERENCE
CORRIDOR
CORRIDOR
MECH. RM.
SEAL
SCALE:
FILE PATH:
P:\22119\22119e22.dgn
DATE PLOTTED
DGN FILE
03-DEC-2024
SHEET NUMBER:
316 CORPORATE PARKWAY
NBP Engineers, Inc.
MACON, GEORGIA 31210
NBP
ENGINEERS
478-745-1691 www.nbpengineers.com
No. REVISIONS/SUBMISSIONS DATE
DRAWN:
CHECKED:
DESIGNED:
DATE:
PROJECT NUMBER:
P R
O J E
C T
T
IT
L E
SHEET TITLE:
CONSULTANTS
THIS DRAWING IS THE PROPERTY OF THE
ENGINEER AND MAY NOT BE REPRODUCED
OR USED IN WHOLE OR IN PART
WITHOUT HIS WRITTEN PERMISSION. IT IS
TO BE USED FOR THE PROJECT
SPECIFICALLY IDENTIFIED HEREIN AND TO
BE RETURNED UPON REQUEST.
P:\22119\22119e22.dgn
AS SHOWN
KMS
BCO
KMS
22119
C O
L U
M B
U S S
T A
T E U
N
IV
E R
S
IT
Y
COA Expiration: 6.30.2026
COA#PEF000774
NBP Engineers, Inc.
C o lu m b u s
G e o rg ia
12.03.2024
T
P R
O J E
C T N o
C
S U -1
-2
IL
L
G E S H
A L L H
V A
C U
P G
R A
D E S
AH-2
TU2-1
TU2-2
TU2-9
TU2-8
TU2-10
TU2-3
TU2-4
TU2-7
TU2-6
TU2-5
SCALE:
= 1'-0
8 0 4 8 16
E2.2
LINE LEGEND
POINT OF CONNECTION
EXISTING TO REMAIN
NEW WORK
MIDDLE LEVEL FLOOR PLAN - NEW WORK - ELECTRICAL
ELECTRICAL
NEW WORK -
FLOOR PLAN -
MIDDLE LEVEL
C
GENERAL NOTES:(THIS SHEET ONLY)
A
NOTES:(THIS SHEET ONLY)
TERMINAL UNITS TO THIS BREAKER.
NEW BREAKERS. ADD NEW 20/1P BREAKER AND CIRCUIT ALL THE NEW
A NEW PANEL IS LOCATED ADJACENT TO ORIGINAL PANEL A WITH SPACE FOR 2
AND SWITCHES. CHAIN HANG NEW LIGHTS. BASIS OF DESIGN IS THE COLUMBIA CLS.
REPLACE THE EXISTING. REMOVE ALL EXISTING LIGHTS, MAINTAIN CIRCUITING
PROVIDE FOUR NEW 1x4 LED STRIP FIXTURES FOR THE MECHANICAL ROOM TO
RECEPTACLES
CIRCUITS
RACEWAY EXPOSED
FLEXIBLE RACEWAY
CONDUIT UP
CONDUIT DOWN
HOMERUN- ONE ARROW PER CIRCUIT
ONE CROSSMARK PER WIRE
(3 WIRE UNLESS SHOWN)
RACEWAY CONCEALED IN CEILING OR WALL
RACEWAY IN GROUND, SLAB, OR UNDER FLOOR
CAP
CONNECTION TO EQUIPMENT
GENERAL EQUIPMENT
BACKBOARD
F
PANELBOARD-250 VAC OR LESS
SURFACE MOUNTED
PANELBOARD-250 VAC OR LESS
RECESSED
JJ J
COMMUNICATIONS
ENCLOSED CIRCUIT BREAKER
JUNCTION BOX - WALL/CEILING/FLOOR
DISCONNECT SWITCH: "F" IF FUSED
FRAME AMPS/POLES/NEMA TYPE
FUSE PER MANUFACTURERS RECOMMENDATIONS
SURGE SUPPRESSOR
COMBINATION STARTER AND DISCONNECT
# DATA OUTLET, QUANTITY OF JACKS AS NOTED
DUCT MOUNTED SMOKE DETECTOR
SMOKE DETECTOR: CEILING / WALL
HEAT DETECTOR: CEILING / WALL
FIRE ALARM EQUIPMENT
R FIRE ALARM RELAY
J
1 2
RECEPTACLE AT ACP SHALL BE 5-20R TYPE.
LIGHTS AND INTEGRAL SERVICE RECEPTACLE. ROUTE TO EACH WITH 3#12 IN •"EMT.
POWER THE NEW ACP RECEPTACLE. USE THIS SAME CIRCUIT TO POWER THE AHU
PROVIDE A NEW 20/1P BREAKER IN THE EXISTING PANEL NOTED IN NOTE 2 TO
SHUTDOWN AND THE GENERAL BUILDING ALL ALARM SHALL SOUND.
THE EXISTING SIMPLEX SLC CIRCUIT. UPON DETECTION OF SMOKE THE AHU SHALL
ADD NEW DUCT DETECTOR IN THE SUPPLY SIDE OF THE NEW AHU. CONNECT TO
ON 48" CENTERS.
ASSUME 75' OF CAT CABLE IS REQUIRED. SUPPORT IN J HOOKS ABOVE CEILING
CABLE ON THE JACK AND BACK IN THE EXISTING DATA CLOSET. FOR PRICING
PROVIDE A NEW RJ45 DATA JACK AT THE ACP. TERMINATE CAT 6 PLENUM RATED
TO VFD TO AHU.
OLD STARTER WITH A NEW VFD. MAKE ALL FINAL CONNECTIONS FROM BREAKER
IT WITH A NEW 20/3P. REUSE THE EXISTING CONDUCTORS AND CONDUIT. REPLACE
AHU-2 IS FED FROM THIS EXISTING PANEL. REMOVE EXISTING BREAKER, REPLACE EXISTING POWER PANELS ARE WESTINGHOUSE TYPE INSTALLED IN 1970.
LOCATE AT ACP5
NEW TU. MAKE ALL FINAL CONNECTIONS.
ROUTED NEATLY TIGHT TO STRUCTURE FOLLOW BUILDING LINES TO EACH
MAINTENANCE WITHOUT TURNING ALL OF THEM OFF. USE 3#12 AWG MC CABLE
WIRE THE TERMINAL UNITS IN SUCH A WAY THAT ONE CAN BE TURNED OFF FOR
B
C
D
MECH. RM.
STAIR #1
STAIR #2
OFFICE
OFFICE
OFFICE
CLOSET
ELEVATOR325
OFFICE
TOILET
MULTIPURPOSE
JAN
STORAGE301
PROJ
STORAGE
CLOS
CLOS
TOILET
WOMEN
MEN
CORRIDOR
STUDY CARRELS
A/V CENTER309
SEAL
SCALE:
FILE PATH:
P:\22119\22119e23.dgn
DATE PLOTTED
DGN FILE
03-DEC-2024
SHEET NUMBER:
316 CORPORATE PARKWAY
NBP Engineers, Inc.
MACON, GEORGIA 31210
NBP
ENGINEERS
478-745-1691 www.nbpengineers.com
No. REVISIONS/SUBMISSIONS DATE
DRAWN:
CHECKED:
DESIGNED:
DATE:
PROJECT NUMBER:
P R
O J E
C T
T
IT
L E
SHEET TITLE:
CONSULTANTS
THIS DRAWING IS THE PROPERTY OF THE
ENGINEER AND MAY NOT BE REPRODUCED
OR USED IN WHOLE OR IN PART
WITHOUT HIS WRITTEN PERMISSION. IT IS
TO BE USED FOR THE PROJECT
SPECIFICALLY IDENTIFIED HEREIN AND TO
BE RETURNED UPON REQUEST.
P:\22119\22119e23.dgn
AS SHOWN
KMS
BCO
KMS
22119
C O
L U
M B
U S S
T A
T E U
N
IV
E R
S
IT
Y
COA Expiration: 6.30.2026
COA#PEF000774
NBP Engineers, Inc.
C o lu m b u s
G e o rg ia
12.03.2024
T
P R
O J E
C T N o
C
S U -1
-2
IL
L
G E S H
A L L H
V A
C U
P G
R A
D E S
TU3-1
TU3-3
TU3-2
TU3-8
TU3-7
TU3-6
TU3-5TU3-4
AH-3
SCALE:
= 1'-0
8 0 4 8 16
E2.3
LINE LEGEND
POINT OF CONNECTION
EXISTING TO REMAIN
NEW WORK
ELECTRICAL
NEW WORK -
FLOOR PLAN -
UPPER LEVEL
UPPER LEVEL FLOOR PLAN - NEW WORK - ELECTRICAL
GENERAL NOTES:(THIS SHEET ONLY)
A
NOTES:(THIS SHEET ONLY)
AND SWITCHES. CHAIN HANG NEW LIGHTS. BASIS OF DESIGN IS THE COLUMBIA CLS.
REPLACE THE EXISTING. REMOVE ALL EXISTING LIGHTS, MAINTAIN CIRCUITING
PROVIDE FOUR NEW 1x4 LED STRIP FIXTURES FOR THE MECHANICAL ROOM TO
RECEPTACLES
CIRCUITS
RACEWAY EXPOSED
FLEXIBLE RACEWAY
CONDUIT UP
CONDUIT DOWN
HOMERUN- ONE ARROW PER CIRCUIT
ONE CROSSMARK PER WIRE
(3 WIRE UNLESS SHOWN)
RACEWAY CONCEALED IN CEILING OR WALL
RACEWAY IN GROUND, SLAB, OR UNDER FLOOR
CAP
CONNECTION TO EQUIPMENT
GENERAL EQUIPMENT
BACKBOARD
F
PANELBOARD-250 VAC OR LESS
SURFACE MOUNTED
PANELBOARD-250 VAC OR LESS
RECESSED
JJ J
COMMUNICATIONS
ENCLOSED CIRCUIT BREAKER
JUNCTION BOX - WALL/CEILING/FLOOR
DISCONNECT…