Bid Plans Part 2 _ Maint Bldg Expansion - 909CM3028 .pdf
PDF 13 MB Posted
- Solicitation number
- 36C78624B0001
About this file
This federal contract opportunity solicitation requests bids to renovate and expand a maintenance building and repair asphalt roads at Fort Custer National Cemetery. The contractor will provide all management, supervision, labor, materials, parts, and equipment necessary to renovate and expand Maintenance Building 3001 and repair and repave asphalt roads at Fort Custer National Cemetery. The work includes general conditions, general construction, structures, alterations, roads, parking, walks, grading, drainage, mechanical, electrical, telecommunications and security work, utility systems, and the necessary removal of existing structures and construction of other items in accordance with the drawings and specifications. The solicitation was issued by the Department of Veterans Affairs National Cemetery Administration under number 36C78624B0001 for the project named Z2QA--909CM3028-29: Bldg Expansion and Road Repairs, Ft Custer.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C78624B0001.docx | DOCX document | |
| 8 - Cost Estimate Worksheet.xlsx | XLSX spreadsheet | |
| Bid Specs _ Roads Repair - 909CM3029.pdf | ||
| Bid Specs _ Maint Bldg Expansion - 909CM3028 .pdf | ||
| Bid Plans Part 1 _ Maint Bldg Expansion - 909CM3028 .pdf | ||
| Bid Plans _ Roads Repair - 909CM3029.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
F
S P
FACP
1. PROVIDE AND INSTALL A NEW FIRE ALARM SYSTEM
THROUGHOUT THE BUILDING PER NFPA 101, NFPA 72, THE VA
FIRE PROTECTION DESIGN MANUAL AND THE NCA DESIGN
GUIDE. REFER TO SPEC SECTION 28 46 00 FIRE DETECTION
AND ALARM.
2. FIRE ALARM SYSTEM SHALL FUNCTION AS A VOICE
EVACUATION SYSTEM PER THE VA DESIGN MANUAL.
3. SMOKE OR HEAT DETECTION SHALL BE PROVIDED
THROUGHOUT THE FACILITY.
4. PROVIDE FIRE SEAL FOR INSERTS, SLEEVES AND CONDUIT
PENETRATIONS THROUGH WALLS, CEILINGS AND FLOORS AS
PER SPECIFICATIONS
5. COORDINATE FIRE ALARM SYSTEM DEVICE LOCATIONS WITH
LIGHT FIXTURES, STRUCTURAL MEMBERS, SPRINKLER HEADS
AND PIPING, HVAC EQUIPMENT AND DUCTWORK.
6. THE CONTRACTOR SHALL FURNISH AND INSTALL COMPLETE
AND SATISFACTORILY OPERATING SYSTEMS AS INDICATED ON
THE CONTRACT DOCUMENTS AND AS EVIDENTLY INTENDED.
IT IS NOTED THAT THE DRAWINGS ARE DIAGRAMMATIC AND
INDICATE GENERAL ARRANGEMENTS OF SYSTEMS AND
WORK. INTERCONNECTIONS HAVE BEEN SHOWN, AND THE
CONTRACTOR SHALL FURNISH AND INSTALL CONDUIT AND
WIRING AS REQUIRED TO ACCOMPLISH THE FUNCTIONS
INDICATED. ADDITIONALLY, FIRE ALARM SYSTEMS HAVE BEEN
SHOWN AND THE CONTRACTOR SHALL FURNISH AND INSTALL
THE REQUIRED QUANTITIES AND TYPES OF CABLES,
CONDUCTORS, RACEWAYS, REMOTE POWER SUPPLIES AND
CONNECTIONS, SHIELDING REQUIREMENTS, ETC., AS
REQUIRED BY THE SYSTEM MANUFACTURER, THE
SPECIFICATIONS, AND ANY APPLICABLE CODES. ALL WIRING
SHOWN ON RISER DIAGRAMS SHALL ALSO BE FURNISHED AND
INSTALLED REGARDLESS OF WHETHER THESE ITEMS ARE
SHOWN ON THE FLOOR PLANS.
7. THE CONTRACTOR SHALL COORDINATE THE ELECTRICAL
WORK WITH THE WORK OF ALL OTHER TRADES AND EXISTING
CONDITIONS SO AS TO AVOID CONFLICTS. RESOLVE ALL
CONFLICTS THROUGH THE A/E PRIOR TO ROUGH-IN. FAILURE
TO PROVIDE SUCH COORDINATION PRIOR TO WORK BEING
INSTALLED SHALL NOT BE CAUSE FOR ADDITIONAL
COMPENSATION TO THE CONTRACTOR, AND MAY RESULT IN
REJECTION OF THE WORK.
8. ADDITIONAL DEVICES MAY BE REQUIRED. DO NOT USE THESE
DRAWINGS FOR DEVICE COUNTS.
9. ALL MATERIALS SHALL BE NEW, SHALL BE SUITABLE FOR THE
APPLICATION INTENDED, AND SHALL BEAR LABELS OR
MARKINGS INDICATING THIRD PARTY TESTING LABORATORY
LISTINGS ACCEPTABLE TO THE AUTHORITY HAVING
JURISDICTION.
10. VERIFY LOCATIONS OF WIRING DEVICES IN FINISHED SPACES,
MILLWORK, AND CASEWORK WITH ARCHITECTURAL
DRAWINGS, DETAILS, AND ELEVATIONS, AND WITH THE
OWNER'S EQUIPMENT AND FURNITURE LAYOUTS PRIOR TO
ROUGH-IN.
11. ALL FIRE ALARM CABLES SHOULD BE INSTALLED IN METAL
RACEWAYS AND BE PAINTED RED.
12. ALL RACEWAY AND WIRING SHALL BE CONCEALED IN
FINISHED SPACES AND MAY BE EXPOSED IN UNFINISHED
SPACES SUCH AS MECHANICAL AND ELECTRICAL ROOMS. ALL
RACEWAY AND WIRING SHALL BE ROUTED EITHER
PERPENDICULAR OR PARALLEL TO THE BUILDING'S
STRUCTURAL COMPONENTS.
13. PROVIDE PULL AND JUNCTION BOXES AS REQUIRED TO MEET
CODE AND INSTALLATION REQUIREMENTS. PULL AND
JUNCTION BOXES SHALL BE CONCEALED IN FINISHED SPACES
AND LOCATIONS SHALL BE COORDINATED WITH THE WORK OF
ALL OTHER TRADES SO AS TO AVOID CONFLICTS.
14. ALL CONDUCTORS SHALL BE IDENTIFIED AT EACH JUNCTION
BOX, OUTLET BOX, CABINET, PULL BOX, ETC., WITH VINYL
SELF-ADHESIVE TAGS INDICATING PANEL AND CIRCUIT
NUMBER, CONTROL WIRE IDENTIFICATION NUMBER, OR
OTHER APPROPRIATE INFORMATION. ALL PULL AND
JUNCTION BOXES SHALL BE LABELED AS TO FUNCTION.
15. ALL EQUIPMENT SHALL BE SECURELY FASTENED BY MEANS
OF ANCHORS, RODS, HANGERS, SUPPORTS, GUIDES, SWAY
BRACES, ETC., TO MAINTAIN ALIGNMENT AND PREVENT
EQUIPMENT MOVEMENT. ALL EQUIPMENT LOCATED IN
SEISMIC ZONES SHALL BE SECURED WITH MEANS APPROVED
FOR THE SEISMIC CLASSIFICATION ENCOUNTERED.
16. ALL PENETRATIONS OF FIRE OR SMOKE RATED
CONSTRUCTION SHALL BE SEALED WITH FIRESTOPPING
MATERIALS APPROVED AND LISTED FOR THE RATING OF THE
CONSTRUCTION TO BE PENETRATED. PROVIDE
DOCUMENTATION ON ALL SUCH PENETRATION SEALING
SYSTEMS FOR VERIFICATION OF PROPER INSTALLATION.
17. ALL PENETRATIONS OF ROOFS, EXTERIOR WALLS,
FOUNDATIONS, OR OTHER WATER OR MOISTURE PROOF
CONSTRUCTION SHALL BE SEALED WITH APPROPRIATE
SEALING FITTINGS OR SEALED CONSTRUCTION TO PREVENT
THE INTRODUCTION OF MOISTURE INTO THE BUILDING.
18. WHERE EMPTY RACEWAYS ARE INSTALLED, THEY SHALL BE
LABELED AT BOTH ENDS AND FITTED WITH NYLON
PULLSTRINGS FOR FUTURE USE.
19. ELECTRICAL WORK SHALL BE PERFORMED ON DE-ENERGIZED
SYSTEMS ONLY TO PREVENT PERSONNEL INJURY AND
POTENTIAL SYSTEM FAILURE. WHERE WORK ON EXISTING
SYSTEMS WILL REQUIRE INTERRUPTION OF ELECTRICAL
SERVICE, THEN TEMPORARY PROVISIONS ACCEPTABLE TO
THE OWNER FOR TEMPORARY POWER SHALL BE UTILIZED
UNTIL THE WORK IS COMPLETE.
20. THE FIRE ALARM SYSTEM SHALL COMPLY WITH ALL RELATED
NFPA, BUILDING CODES AND LOCAL FIRE DEPARTMENT
REGULATIONS.
21. WALL MOUNTED FIRE ALARM PULL STATIONS ARE TO BE
LOCATED 46" A.F.F. AND WITHIN 5' OF THE NEAREST
ADJACENT EXIT DOOR FROM THE FLOOR OR BUILDING.
22. WALL MOUNTED FIRE ALARM NOTIFICATION APPLIANCES,
EITHER VISUAL, OR COMBINATION AUDIO/VISUAL, SHALL BE
LOCATED SUCH THAT THE ENTIRE LENS OF THE VISUAL
PORTION IS BETWEEN 80" AND 96" A.F.F. AUDIO ONLY
APPLIANCES SHALL BE LOCATED, NOT LESS THAN 90" A.F.F.
TO TOP OF APPLIANCE, OR 6" BELOW CEILING.
FIRE ALARM GENERAL NOTES
1. THE SCOPE OF WORK FOR THIS PROJECT IS TO DEMOLISH ALL
EXISTING FIRE ALARM DEVICES AND SYSTEM COMPONENTS
INCLUDING THE EXISTING FIRE ALARM CONTROL PANEL. FIRE
ALARM DEVICES SHALL BE REPLACED WITH NEW.
2. THE EXISTING FIRE ALARM SYSTEM SHALL REMAIN IN SERVICE
UNTIL THE NEW DEVICES ARE INSTALLED, TESTED AND READY
TO BE PLACED IN SERVICE.
3. THESE DRAWINGS DEPICT THE GENERAL INTENT OF THE
SCOPE OF THE DEMOLITION WORK AND NOT ALL ITEMS ARE
NECESSARILY SHOWN. THE CONTRACTOR SHALL BE
REQUIRED TO VERIFY IN THE FIELD AND DETERMINE SCOPE
OF DEMOLITION PRIOR TO WORK.
4. PHASING OF DEMOLITION SHALL FOLLOW THAT OF THE
GENERAL CONTRACTOR. COORDINATE REMOVAL OF FIRE
ALARM COMPONENTS WITH OTHER ACTIVITIES AND
REQUIREMENTS OF THE VA.
5. WHERE EXISTING JUNCTION BOX MUST REMAIN IN EXISTING
WALLS OR CEILINGS, THEY SHALL BE FITTED WITH BLANK
COVER PLATES AS REQUIRED FOR THE LEVEL OF
RENOVATION IN THE AREA.
FIRE PROTECTION DEMOLITION NOTES
DEVICES
COMBINATION OF SPEAKER/STROBE CEILING MOUNTED
MANUAL PULL STATION
STROBE ONLY CEILING MOUNTED
SYMBOL DESCRIPTION
DETECTORS
HEAT DETECTOR - RATE OF RISE
SMOKE DETECTOR - PHOTOELECTRIC
FIRE ALARM CONTROL PANEL
PANELS
STROBE ONLY WALL MOUNTED
COMBINATION OF SPEAKER/STROBE WALL MOUNTED
C
H R
FIRE ALARM SYMBOLS
FIRE ALARM
CONTROL
PANEL
CORR M100
NOTIFICATION APPLIANCES
LEVEL 1 FIRE/SMOKE
INITIATING DEVICES LEVEL 1
FIRE/SMOKE/HEAT
C
FS
LEVEL 1
= 17 = 5
= 5= 9
NOTE: REPRESENTS NUMBER OF DEVICES
ON THIS LEVEL. CONTRACTOR SHALL
VERIFY ALL NECESSARY DEVICE COUNTS
P
= 3= 1
H = 3 R
DUCT SMOKE DETECTOR
AREA SMOKE DETECTOR
DOOR RELEASE SMOKE DETECTOR
S O
U N
D G
E N
E R
A L
B U
IL
D
IN
G
A
LA
R
M
X
X
N O
T
IF
Y N
E C
E S
S A
R Y
S T
A
X
INPUT
OUTPUT
N O
T
IF
Y F
IR
E
D E
P A
R M
E N
T
IN
IT
IA
T
E S
U P
E R
V
IS
O R
Y S
IG
N
A L
T O
A
4- H
O U
R M
A N
N E
D P
O
IN
T
O
R
IM
M E
D
IA
T E
R E
S P
O N
S E
X
C
LO
S E
A S
S O
C
IA
T E
S M
O K
E
B
R R
IE
R
D O
O R
S O
N T
H
LO
O
R
X
MANUAL PULL STATION X X X X
C
LO
S E
D A
M P
E R
S O
N F
P
R O
X
IM
A T
E T
O D
E T
E C
T O
R
X
X
S H
U T
D O
W N
A
IR
H A
N D
LE
R
V E
D B
Y T
H E
D E
T E
C T
O R
X1
1. DO NOT PROVIDE DUCT DETECTORS IN DEDICATED (100%) EXHAUST FANS, THEY SHOULD CONTINUE TO RUN.
O P
E N
L O
C K
E D
E G
R E
D
O
R S
O N
F
LO
O R
O F
F
IR
IG
IN
X
X
X
FIRE ALARM MATRIX
X X X XHEAT DETECTOR
Location
Issue Date
GORDON - The LA Group Joint Venture, LLC
The LA Group 40 Long Alley Saratoga Springs, NY 12866
(518) 587-8100
Integrity Federal Services, Inc.
148 S. Queen Street, Suite 201 Martinsburg, WV 25401
(304) 725-8456
Project Number
Drawing Number
Project Title
Checked Drawn
KALAMAZOO COUNTY, MICHIGAN
909CM3028
MARCH 24, 2023
Dwg. of
Office of Design and Construction
Service
U.S. Department of Veterans Affairs
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
Revisions: Date:
Drawing Title
Approved: Project Director
Phase
Building Number
BID DOCUMENTS FORT CUSTER NATIONAL CEMETERY
RENOVATE & EXPAND
MAINTENANCE BUILDING 3001Leo A Daly
(202) 861-4600
F ile
P at h:
P
:\0
\0
-1
-0
\4
-0 -P
R O
D U
C T
IO
N
-W O
R K
IN
G
\4 -1
-B
IM
-C A
D \R
E V
IT
\R
E S
O U
R C
E -F
IL
E
S \C
A D
-L
IN
K S
\B D
\9
C M
_G -T
T
LB
.D W
G
Above Group, Inc.
(321) 345-9026
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9
VA FORM 08 - 6231
321 4 5 6 7 8 9 10
FIRE ALARM GENERAL NOTES
F-001
DLO EAG 37
SCALE: 12" = 1'-0"
F2
FIRE ALARM RISER DIAGRAM
SCALE: 1/16" = 1'-0"
F7
FIRE ALARM INPUT/OUTPUT MATRIX
24 MAR 2023
C P
1 2 3 4 5 6
B
C
FD01
FD02
FD02
FD02
FD02
FD02
FD02
FD02
FD02
FD02
FD02
FD02
FD02
FD02
FD02
FD02
Location
Issue Date
GORDON - The LA Group Joint Venture, LLC
The LA Group 40 Long Alley Saratoga Springs, NY 12866
(518) 587-8100
Integrity Federal Services, Inc.
148 S. Queen Street, Suite 201 Martinsburg, WV 25401
(304) 725-8456
Project Number
Drawing Number
Project Title
Checked Drawn
KALAMAZOO COUNTY, MICHIGAN
909CM3028
MARCH 24, 2023
Dwg. of
Office of Design and Construction
Service
U.S. Department of Veterans Affairs
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
Revisions: Date:
Drawing Title
Approved: Project Director
Phase
Building Number
BID DOCUMENTS FORT CUSTER NATIONAL CEMETERY
RENOVATE & EXPAND
MAINTENANCE BUILDING 3001Leo A Daly
(202) 861-4600
F ile
P at h:
P
:\0
\0
-1
-0
\4
-0 -P
R O
D U
C T
IO
N
-W O
R K
IN
G
\4 -1
-B
IM
-C A
D \R
E V
IT
\R
E S
O U
R C
E -F
IL
E
S \C
A D
-L
IN
K S
\B D
\9
C M
_G -T
T
LB
.D W
G
Above Group, Inc.
(321) 345-9026
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9
VA FORM 08 - 6231
321 4 5 6 7 8 9 10
FIRE ALARM DEMOLITION PLAN
FA101
DLO EAG 38
SCALE: 1/8" = 1'-0"
F2
FIRE ALARM DEMOLITION PLAN - MAINTENANCE (3001)
KEYNOTE LEGEND
FD01 DEMOLISH EXISTING FIRE ALARM CONTROL PANEL AND ALL
ASSOCIATED COMPONENTS
FD02 DEMOLISH EXISTING FIRE ALARM DETECTION AND
NOTIFICATION DEVICES, WIRING, CONDUIT, JUNCTION BOXES
AND ASSOCIATED COMPONENTS
4'
SCALE : 1/8" = 1'-0"
0 8' 16'
P
FACP
F
F
S P
S P
S P
S P
S P
S P
S P
S P
S P
S P
S P
H R
S P
S P
H R
S P
S P
S P
S P
F
FACP
S P
C
C
C
C
C
F
S P
H R
C
C
S P
F
DEVICES
COMBINATION OF SPEAKER/STROBE CEILING MOUNTED
MANUAL PULL STATION
STROBE ONLY CEILING MOUNTED
SYMBOL DESCRIPTION
DETECTORS
HEAT DETECTOR - RATE OF RISE
SMOKE DETECTOR - PHOTOELECTRIC
FIRE ALARM CONTROL PANEL
PANELS
STROBE ONLY WALL MOUNTED
COMBINATION OF SPEAKER/STROBE WALL MOUNTED
C
H R
FIRE ALARM SYMBOLS
1 2 3 4 5 6
B
C
TRAINING
M107
FAC MAINT
M102
FOREMAN
M103
MEN'S
M105
WOMEN'S
M106
BREAK
M101
STOR
M104
PARTS
M108
MAINTENANCE
BAYS
M109
OFFICE
M110A
CORRIDOR
M100
STORAGE
M113
GROUNDS SUPPLY
M112
EQUIPMENT
STORAGE
M111
WORKSHOP
M110 CORRIDOR
M110B
VEST
M099
FA01
A
Location
Issue Date
GORDON - The LA Group Joint Venture, LLC
The LA Group 40 Long Alley Saratoga Springs, NY 12866
(518) 587-8100
Integrity Federal Services, Inc.
148 S. Queen Street, Suite 201 Martinsburg, WV 25401
(304) 725-8456
Project Number
Drawing Number
Project Title
Checked Drawn
KALAMAZOO COUNTY, MICHIGAN
909CM3028
MARCH 24, 2023
Dwg. of
Office of Design and Construction
Service
U.S. Department of Veterans Affairs
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
Revisions: Date:
Drawing Title
Approved: Project Director
Phase
Building Number
BID DOCUMENTS FORT CUSTER NATIONAL CEMETERY
RENOVATE & EXPAND
MAINTENANCE BUILDING 3001Leo A Daly
(202) 861-4600
F ile
P at h:
P
:\0
\0
-1
-0
\4
-0 -P
R O
D U
C T
IO
N
-W O
R K
IN
G
\4 -1
-B
IM
-C A
D \R
E V
IT
\R
E S
O U
R C
E -F
IL
E
S \C
A D
-L
IN
K S
\B D
\9
C M
_G -T
T
LB
.D W
G
Above Group, Inc.
(321) 345-9026
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9
VA FORM 08 - 6231
321 4 5 6 7 8 9 10
FIRE ALARM PLAN
FA102
DLO EAG 39
KEYNOTE LEGEND
FA01 PROVIDE AND INSTALL NEW FIRE ALARM CONTROL PANEL.
PANEL TO INCLUDE VOICE EVACUATION CAPABILITIES.
4'
SCALE : 1/8" = 1'-0"
0 8' 16'
N
SCALE: 1/8" = 1'-0"
F1
FIRE ALARM PLAN - MAINTENANCE (3001)
SS
DSDO
SS
DSS
S
DSD
OSS
D
A
WA
WA
V
T
T
SS
OSSR
IR
MG
F
S
MFO
SFO
RFO
VFO
FFO
G
SANITARY SEWER (BELOW FLOOR)
DESCRIPTIONSYMBOL
STORM DRAIN (BELOW FLOOR)
STORM DRAIN OVERFLOW (BELOW FLOOR)
SUBSOIL DRAIN (BELOW FLOOR)
SANITARY VENT
ACID WASTE (ABOVE FLOOR)
ACID VENT
DOMESTIC COLD WATER
DOMESTIC HOT WATER
DOMESTIC HOT WATER RECIRCULATING
ACID WASTE (BELOW FLOOR)
PIPING LINES
SANITARY SEWER (ABOVE FLOOR)
STORM DRAIN (ABOVE FLOOR)
STORM DRAIN OVERFLOW (ABOVE FLOOR)
SUBSOIL DRAIN (ABOVE FLOOR)
DRINKING WATER RECIRCULATING
NATURAL GAS
FIRE LINE
SPRINKLER MAIN
IRRIGATION WATER MAIN
TEMPERED WATER
TEMPERED WATER RECIRCULATING
DRINKING WATER SUPPLY
FUEL OIL SUPPLY
FUEL OIL RETURN
FUEL OIL VENT
FUEL OIL FILL
FUEL OIL GAGE
CONTINUATION - PIPE NOT SHOWN
CONNECT TO EXISTING
DESCRIPTIONSYMBOL
KEYNOTE
GENERIC ANNOTATIONS
EQUIP ID MECHANICAL EQUIPMENT TAG
V
FE
CO
FCO
GCO
WCO
(DRAINS)
RD-
HB-
WH-
FS
M
FHC
FVC
GATE VALVE
DESCRIPTIONSYMBOL
GLOBE VALVE
CHECK VALVE
BUTTERFLY VALVE
FLANGE
BLIND FLANGE
BALANCING VALVE
GAS COCK
PRESSURE REGULATING VALVE
SOLENOID VALVE
CAP
PIPE VALVES, FITTINGS, SENSORS AND GAGES
ECCENTRIC PLUG VALVE
BALL VALVE
STRAINER
UNION
PRESSURE GAGE
COCK (GAGE, AIRVENT, DRAIN)
PIPE ANCHOR
PIPE GUIDE
PIPE EXPANSION COMPENSATOR
VACUUM BREAKER
SAFETY RELIEF VALVE
CONTROL VALVE (2-WAY)
CONTROL VALVE (3-WAY)
THERMOMETER
SUPERVISED O S & Y VALVE
FLOW MEASURING ELEMENT
SIGHT GLASS (FLOW TYPE)
AIR ELIMINATOR
TEMPERATURE & PRESSURE RELIEF VALVE
STEAM TRAP
TEST PLUG
PIPE ELBOW UP
PIPE ELBOW DOWN
FLOOR CLEANOUT
WALL CLEANOUT
DRAINS - FLOOR - FD, TRENCH - TD, AREA -
ADROOF DRAIN OR OVERFLOW ROOF DRAIN
HOSE BIBB
GRADE CLEANOUT
PIPE TEE UP
PIPE TEE DOWN
CLEANOUT
WALL HYDRANT
FIRE DEPARTMENT CONNECTION
FIRE HOSE CABINET
FIRE VALVE CABINET
FLOW SWITCH
WATER METER
BACKFLOW PREVENTER
FLEXIBLE PIPE CONNECTION
NPC
WNPHW
SC
W
NON POTABLE COLD WATER
NON POTABLE HOT WATER
SOFT COLD WATER
SHW
ROR
SOFT HOT WATER
REVERSE OSMOSIS RETURN
ROS REVERSE OSMOSIS SUPPLY
PWS PURE WATER SUPPLY
PWR PURE WATER RETURN
PLUMBING GENERAL NOTES
1. THE CONTRACTOR SHALL FURNISH AND INSTALL COMPLETE AND SATISFACTORILY OPERATING SYSTEMS AS INDICATED IN THE CONTRACT DOCUMENTS. IT IS NOTED THAT THE DRAWINGS ARE DIAGRAMMATIC AND INDICATE GENERAL ARRANGEMENTS OF SYSTEMS AND WORK. THE CONTRACTOR SHALL OBTAIN EXACT LOCATION, MEASUREMENTS, LEVELS, ETC., AT THE SITE AND SHALL ADAPT THE
WORK TO THE ACTUAL CONDITIONS OF THE FIELD.
2. THE CONTRACTOR SHALL COORDINATE THE PLUMBING WITH THE WORK OF ALL OTHER TRADES, INCLUDING, BUT NOT LIMITED TO, ARCHITECTURAL, STRUCTURAL, LIGHTING, POWER, SYSTEMS, MECHANICAL, FIRE PROTECTION, AND OTHERS FOR EXISTING AND NEW WORK SO AS TO AVOID
CONFLICTS. RESOLVE ALL CONFLICTS THROUGH THE A/E PRIOR TO INSTALL. FAILURE TO PROVIDE SUCH
COORDINATION PRIOR TO WORK BEING INSTALLED SHALL NOT BE CAUSE FOR ADDITIONAL
COMPENSATION TO THE CONTRACTOR, AND MAY RESULT IN REJECTION OF WORK. IT IS THE
CONTRACTORS' RESPONSIBILITY TO COORDINATE SUBSTITUTIONS WITH OTHER TRADES.
3. THE SIZE AND LOCATION OF EQUIPMENT INSTALLED UNDER DIVISION 22-PLUMBING SHALL BE
COORDINATED WITH OTHER TRADES. CONNECTION TO EQUIPMENT SHALL BE VERIFIED WITH
MANUFACTURER'S CERTIFIED DRAWINGS. TRANSITIONS TO ALL EQUIPMENT SHALL BE VERIFIED AND
PROVIDED FOR EQUIPMENT FURNISHED.
4. ALL PIPING IS TO BE CONCEALED ABOVE CEILING (WHERE INSTALLED) OR IN NEW WALLS UNLESS SPECIFICALLY NOTED AS EXPOSED OR SURFACE MOUNTED. CONTRACTOR TO COORDINATE WITH THE GENERAL CONTRACTOR TO PAINT ALL EXPOSED PIPING TO MATCH CORRESPONDING EXPOSED AREAS.
5. ALL EQUIPMENT SHALL BE SECURELY FASTENED BY MEANS OF ANCHORS, RODS, HANGERS, SUPPORTS, GUIDES, SWAY BRACES, ETC., TO MAINTAIN ALIGNMENT AND PREVENT EQUIPMENT MOVEMENT.
6. ANY EQUIPMENT, PIPING, DUCTWORK, ETC., SHALL ONLY BE SUPPORTED FROM THE BUILDING STRUCTURE. NO EQUIPMENT SHALL BE SUPPORTS FROM OTHER PIPING, DUCTWORK, METAL ROOF
DECK, LATERAL BRACING, OR CONDUIT.
7. ALL PENETRATIONS OF FIRE OR SMOKE RATED CONSTRUCTION SHALL BE SEALED WITH FIRESTOPPING MATERIALS APPROVED AND LISTED FOR THE RATING OF THE CONSTRUCTION TO BE PENETRATED.
PROVIDE DOCUMENTATION ON ALL SUCH PENETRATION SEALING SYSTEMS FOR VERIFICATION OF
PROPER INSTALLATION.
8. ALL PENETRATIONS OF ROOFS, EXTERIOR WALLS, FOUDNATIONS, OR OTHER WATER OR MOISTURE
PROOF CONSTRUCTION SHALL BE SEALED WIT APPROPRIATE SEALING FITTINGS OR SEALED
CONSTRUCTION TO PREVENT THE INTRODUCTION OF MOISTURE INTO THE BUILDING.
9. ALL CONCRETE HOUSEKEEPING PADS FOR MECHANICAL AND PLUMBING EQUIPMENT SHALL BE SIZED
AND LOCATED BY THE MECHANICAL/PLUMBING CONTRACTOR. A MINIMUM THICKNESS OF ANY
HOUSEKEEPING PADS SHALL BE 4" AND EXTEND A MINIMUM OF 4" BEYOUND THE MECHANICAL OR PLUMBING EQUIPMENT. MECHANICAL/PLUMBING CONTRACTOR SHALL COORDINATE WITH THE GENERAL
CONTRACTOR FOR THE SIZE AND LOCATION OF HOUSEKEEPING PADS.
10. MAINTAIN CLEARANCE OF MINIMUM OF 6" BETWEEN DUCTWORK, PIPING, EQUIPMENT, ETC. AND ALL FIRE
RATED AND FIRE/SMOKE RATED PARTITIONS TO ALLOW FOR INSPECTION OF RATED WALLS.
11. ALL DASHED LINEWORK AROUND MECHANICAL AND PLUMBING EQUIPMENT INDICATES REQUIRED SERVICE CLEARANCES. ALL EQUIPMENT SHALL BE INSTALLED IN A MANNER TO MAINTAIN THE CODE AND/OR MANUFACTURER'S REQUIRED CLEARANCES. FOLLOW MANUFACTURER'S RECOMMENDATION ON
EQUIPMENT ACCESS AND MAINTENANCE WHEN NOT INDICATED ON PLANS.
12. DO NOT LOCATE VALVES, ANY EQUIPMENT WITH MOVING PARTS, OR ANY EQUIPMENT NEEDING ACCESS
OR REGULAR MAINTENANCE ABOVE INACCESSIBLE CEILINGS. WHERE LOCATIONS OF VALVES
CONTROLS OR EQUIPMENT IS UNAVOIDABLE, PROVIDE MIN. 24"X24" ACCESS PANELS.
13. COORDINATE PLUMBING, MECHANICAL, AND ELECTRICAL SUCH THAT PIPING, DUCTWORK, AND
EQUIPMENT ARE NOT LOCATED OVER ANY ELECTRICAL PANELS.
14. APPLICABLE PLUMBING CODES AND STANDARDS:
• VA PLUMBING DESIGN MANUAL, REV. JUNE 1, 2022
• INTERNATIONAL PLUMBING CODE, 2018 EDITION
• INTERNATIONAL BUILDING CODE, 2018 EDITION
Location
Issue Date
GORDON - The LA Group Joint Venture, LLC
The LA Group 40 Long Alley Saratoga Springs, NY 12866
(518) 587-8100
Integrity Federal Services, Inc.
148 S. Queen Street, Suite 201 Martinsburg, WV 25401
(304) 725-8456
Project Number
Drawing Number
Project Title
Checked Drawn
KALAMAZOO COUNTY, MICHIGAN
909CM3028
MARCH 24, 2023
Dwg. of
Office of Design and Construction
Service
U.S. Department of Veterans Affairs
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
Revisions: Date:
Drawing Title
Approved: Project Director
Phase
Building Number
BID DOCUMENTS FORT CUSTER NATIONAL CEMETERY
RENOVATE & EXPAND
MAINTENANCE BUILDING 3001Leo A Daly
(202) 861-4600
F ile
P at h:
P
:\0
\0
-1
-0
\4
-0 -P
R O
D U
C T
IO
N
-W O
R K
IN
G
\4 -1
-B
IM
-C A
D \R
E V
IT
\R
E S
O U
R C
E -F
IL
E
S \C
A D
-L
IN
K S
\B D
\9
C M
_G -T
T
LB
.D W
G
Above Group, Inc.
(321) 345-9026
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9
VA FORM 08 - 6231
321 4 5 6 7 8 9 10
PLUMBING NOTES, SYMBOLS &
ABBREVIATIONS
P-001
DES MLG 40
10.28.202203.24.2023
1 2 3 4 5 6
C
PP01
PP01
PP01
PP01
PP01
PP01
PP01
PP01
PP01
EXISTING SINK AND TRIM
TO REMAIN.
EXISTING WATER HEATER
ABOVE SINK TO REMAIN
PP03
PP04
PP01
PD01
Location
Issue Date
GORDON - The LA Group Joint Venture, LLC
The LA Group 40 Long Alley Saratoga Springs, NY 12866
(518) 587-8100
Integrity Federal Services, Inc.
148 S. Queen Street, Suite 201 Martinsburg, WV 25401
(304) 725-8456
Project Number
Drawing Number
Project Title
Checked Drawn
KALAMAZOO COUNTY, MICHIGAN
909CM3028
MARCH 24, 2023
Dwg. of
Office of Design and Construction
Service
U.S. Department of Veterans Affairs
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
Revisions: Date:
Drawing Title
Approved: Project Director
Phase
Building Number
BID DOCUMENTS FORT CUSTER NATIONAL CEMETERY
RENOVATE & EXPAND
MAINTENANCE BUILDING 3001Leo A Daly
(202) 861-4600
F ile
P at h:
P
:\0
\0
-1
-0
\4
-0 -P
R O
D U
C T
IO
N
-W O
R K
IN
G
\4 -1
-B
IM
-C A
D \R
E V
IT
\R
E S
O U
R C
E -F
IL
E
S \C
A D
-L
IN
K S
\B D
\9
C M
_G -T
T
LB
.D W
G
Above Group, Inc.
(321) 345-9026
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9
VA FORM 08 - 6231
321 4 5 6 7 8 9 10
PLUMBING DEMOLITION PLAN
PD101
DES MLG 41
4'
SCALE : 1/8" = 1'-0"
0 8' 16'
N
SCALE: 1/8" = 1'-0"
F2
PLUMBING DEMOLITION PLAN - MAINTENANCE (3001)
KEYNOTE LEGEND
PD01 DEMOLISH EXISTING WATER HEATER AND SUPPORT.
PP01 REMOVE EXISTING PLUMBING FIXTURE AND ALL ASSOCIATED
PIPING. CAP EXISTING PIPES BACK AT MAIN.
PP03 EXISTING SANITARY SEWER TO BE DEMOLISHED AS
REQUIRED TO FACILITATE NEW WORK. PIPE LEFT TO BE
ABANDONED SHALL BE FILLED WITH GROUT.
PP04 DEMOLISH FLOOR SLAB AS NECESSARY FOR NEW SANITARY
SEWER PIPING. REFER TO ARCHITECTURAL PLANS AND
PP100.
SCALE: 1/8" = 1'-0"
F8
PLUMBING DEMOLITION PLAN - RESTROOMS (1501)
C
EXISTING
2" SS
EXISTING
2" SS
(E) 4" SS
EXISTING 4" SS
EXISTING 4" SS
2" SS UP
TO P-401
2" SS UP
TO P-202
4" SS UP
TO P-102
4" SS UP TO P-101
2" SS UP
TO P-401
4" SS UP TO P-101
2" SS UP
TO P-604
(E) 4" SANITARY SEWER EXIT
PP02
2" SS
2" SS UP
TO P-512
PP02
EXISTING 4" VTR
EXISTING C.O.
A
PP05
Location
Issue Date
GORDON - The LA Group Joint Venture, LLC
The LA Group 40 Long Alley Saratoga Springs, NY 12866
(518) 587-8100
Integrity Federal Services, Inc.
148 S. Queen Street, Suite 201 Martinsburg, WV 25401
(304) 725-8456
Project Number
Drawing Number
Project Title
Checked Drawn
KALAMAZOO COUNTY, MICHIGAN
909CM3028
MARCH 24, 2023
Dwg. of
Office of Design and Construction
Service
U.S. Department of Veterans Affairs
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
Revisions: Date:
Drawing Title
Approved: Project Director
Phase
Building Number
BID DOCUMENTS FORT CUSTER NATIONAL CEMETERY
RENOVATE & EXPAND
MAINTENANCE BUILDING 3001Leo A Daly
(202) 861-4600
F ile
P at h:
P
:\0
\0
-1
-0
\4
-0 -P
R O
D U
C T
IO
N
-W O
R K
IN
G
\4 -1
-B
IM
-C A
D \R
E V
IT
\R
E S
O U
R C
E -F
IL
E
S \C
A D
-L
IN
K S
\B D
\9
C M
_G -T
T
LB
.D W
G
Above Group, Inc.
(321) 345-9026
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9
VA FORM 08 - 6231
321 4 5 6 7 8 9 10
PLUMBING PLAN - UNDERGROUND
PP100
DES MLG 42
4'
SCALE : 1/8" = 1'-0"
0 8' 16'
N
SCALE: 1/8" = 1'-0"
F2
PLUMBING PLAN - UNDERGROUND - MAINTENANCE (3001)
KEYNOTE LEGEND
PP02 PIPING LOCATIONS AND RUNS TO BE FIELD VERIFIED. ADJUST
ACCORDINGLY TO FIELD POSITION. SITE PHOTOS INDICATE
ADDITIONAL LINES NOT SHOWN ON EXISTING DRAWINGS.
REQUEST FURTHER INFORMATION FROM DESIGN ENGINEER
AS REQUIRED.
PP05 INSTALL DOUBLE CLEANOUT NEAR POINT OF EXITING
BUILDING IF THERE IS NOT ONE FOUND DURING SITE
ASSESSMENT.
C
P-202
P-202
P-202
P-101
P-102
P-101
P-401
P-401PARTS
M108
MAINTENANCE
BAYS
M109
WOMEN'S
M106
MEN'S
M105
FOREMAN
M103
FAC MAINT
M102
VEST
M099
BREAK
M101
STOR
M104
CORRIDOR
M100
TRAINING
M107
P-604
PP02
2" CW
CONNECT TO EXISTING
MINIMUM 2" CW
P-512
2" VTR
1 1/4" HWC
1" HW
3/4" CW
2" CW
1 1/4" HWC
3/4" HW
3/4" CW
2" V
1" CW
EXISTING SINK
EXISTING WATER
HEATER
P-1
ET-1
REFER TO DETAIL B1 FOR
WATER HEATER + PUMP
COORDINATION
A
P-802
P-803
FD-1
ENSURE NO PIPING
CROSSES ABOVE
ELECTRICAL EQPT
P-401
3/4" HW
1 1/4" HWC
1 1/4" HW
1 1/2" CW
CONNECT TO EXISTING 2" CW
ES
P-401
P-202
P-101
P-101
P-202
P-101
P-401
P-604
P-202
P-401
EWH
FD-1
P-1
P-512
1" CW
2" CW
3/4" CW
1 1/4" HWC
3/4" CW
1/2" CW
1 1/4" HW
1 1/4" HWC
2" CW
1" CW
1 1/4" HWC
3/4" HW
ES
P-401
P-202
P-101
P-101
P-202
P-101
P-401
P-512
P-604
P-202
P-401
4" SS
2" SS
4" SS
4" V
2" SS
1 1/2" SS
2" SS
2" V
4" SS
3" SS
VTR
VTR
PP06
Location
Issue Date
GORDON - The LA Group Joint Venture, LLC
The LA Group 40 Long Alley Saratoga Springs, NY 12866
(518) 587-8100
Integrity Federal Services, Inc.
148 S. Queen Street, Suite 201 Martinsburg, WV 25401
(304) 725-8456
Project Number
Drawing Number
Project Title
Checked Drawn
KALAMAZOO COUNTY, MICHIGAN
909CM3028
MARCH 24, 2023
Dwg. of
Office of Design and Construction
Service
U.S. Department of Veterans Affairs
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
Revisions: Date:
Drawing Title
Approved: Project Director
Phase
Building Number
BID DOCUMENTS FORT CUSTER NATIONAL CEMETERY
RENOVATE & EXPAND
MAINTENANCE BUILDING 3001Leo A Daly
(202) 861-4600
F ile
P at h:
P
:\0
\0
-1
-0
\4
-0 -P
R O
D U
C T
IO
N
-W O
R K
IN
G
\4 -1
-B
IM
-C A
D \R
E V
IT
\R
E S
O U
R C
E -F
IL
E
S \C
A D
-L
IN
K S
\B D
\9
C M
_G -T
T
LB
.D W
G
Above Group, Inc.
(321) 345-9026
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9
VA FORM 08 - 6231
321 4 5 6 7 8 9 10
PLUMBING PLAN
PP101
DES MLG 43
4'
SCALE : 1/8" = 1'-0"
0 8' 16'
N
SCALE: 1/8" = 1'-0"
F2
PLUMBING PLAN - MAINTENANCE (3001)
KEYNOTE LEGEND
PP02 PIPING LOCATIONS AND RUNS TO BE FIELD VERIFIED. ADJUST
ACCORDINGLY TO FIELD POSITION. SITE PHOTOS INDICATE
ADDITIONAL LINES NOT SHOWN ON EXISTING DRAWINGS.
REQUEST FURTHER INFORMATION FROM DESIGN ENGINEER
AS REQUIRED.
PP06 REPLACE DEMOED SHELF AND WATER HEATER WITH LIKE
RATING AND CAPACITY. COORDINATE SIMILAR LOAD WITH
ELECTRICAL.
DOMESTIC FIXTURE SCHEDULE
ID DESCRIPTION MANUFACTURER MODEL
MATERIAL
DESCRIPTION FINISH
TRIM FLOW FIXTURE FLUSH FIXTURE
WASTE
ROUGH-IN
PIPE SIZE
INDIRECT
WASTE
PIPE SIZE
VENT
PIPE
SIZE
COLD
WATER
ROUGH-IN
PIPE SIZE
HOT WATER
ROUGH-IN
PIPE SIZE SPECIFICATIONMANUFACTURER MODEL TYPE
MOTION SENSOR
CONTROL WATER FLOW
TIMER
DURATION
(SEC)
COLD
WATER
TEMP.
HOT
WATER
TEMP.
MAX. MIXED
WATER
TEMP.
VOL. PER
FLUSH
MIN. VOL.
PER FLUSH
P-101 WATER CLOSET - WALL
MOUNTED - ADA
AMERICAN
STANDARD
AFWALL MILLENNIUM
2257.101
WHITE VITREOUS
CHINA
WHITE SLOAN ROYAL 111
ESS
ELECTRONIC Yes 40 °F 40 °F 1.28 gal 1.28 gal 4” --- 2” 1” ELONGATED WALL HUNG WATER CLOSET, 1-1/2” TOP SPUD, WITH CHURCH 295SSCT ELONGATED OPEN FRONT
SEAT. HARD WIRED ELECTRONIC POWERED SENSOR ACTIVATED FLUSHOMETER.
P-102 WATER CLOSET - WALL HUNG AMERICAN
STANDARD
AFWALL MILLENNIUM
2257.101
WHITE VITREOUS
CHINA
WHITE SLOAN ROYAL 111
ESS
ELECTRONIC Yes 40 °F 40 °F 1.28 gal 1.28 gal 4” --- 2” 1” ELONGATED WALL HUNG WATER CLOSET, 1-1/2” TOP SPUD, WITH CHURCH 295SSCT ELONGATED OPEN FRONT
SEAT. HARD WIRED ELECTRONIC POWERED SENSOR ACTIVATED FLUSHOMETER.
P-202 URINAL - ADA AMERICAN
STANDARD
WASHBROOK .125
GPF 6590.001
WHITE VITREOUS
CHINA
WHITE SLOAN ROYAL 186
ESS
ELECTRONIC Yes 40 °F 40 °F 0.125 gal 0.125 gal 2” --- 1-1/2” 3/4” WALL HUNG URINAL WITH WASHOUT ACTION, TOP SPUD, SIZE 18” WITH INTEGRAL EXTENDED SHIELDS SUPPORTED BY THROUGH GOING BOLTS AND C.P. NUTS. HARD WIRED ELECTRONIC POWERED SENSOR
ACTIVATED FLUSHOMETER. INSTALL AT ADA COMPLIANT HEIGHT.
P-401 LAVATORY - COUNTER - ADA INTEGRAL BOWL N/A SOLID SURFACE SEE ARCH CHICAGO FAUCET
CO
E80-A11A-41A
BCP
ELECTRONIC Yes 0.50 GPM 12 40 °F 120 °F 105 °F 1-1/2” --- 1-1/2” 1/2” 1/2” COUNTERTOP LAVATORY,INTEGRAL BOWL, SINGLE FAUCET HOLE. DECK-MOUNTED FAUCET WITH SENSOR, HARD WIRED ELECTRONIC POWER WITH VANDAL RESISTANT SPRAY, EXTERNAL ASSE 1070 COMPLIANT THERMOSTATIC MIXING VALVE, GRID DRAIN, LOOSE KEY ANGLE STOPS AND SUPPLIES. MOUNT AT ADA COMPLIANT HEIGHT. INSULATE WATER AND WASTE TO MEET ADA REQUIREMENTS USING ADA INSULATION KIT.
P-512 DOUBLE BOWL SINK - DROP IN ELKAY LRAD331965PD STAINLESS STEEL STAINLESS
STEEL
AMERICAN
STANDARD
2302E2805 MANUAL No 1.00 GPM 240 40 °F 120 °F 105 °F --- 2” --- 1/2” 1/2” TWO COMPARTMENT DROP IN 18 GAUGE SINK. GOOSENECK FAUCET WITH SINGLE LEVER SIDE VALVE, GRID STRAINER, P-TRAP, TAILPIECES, SUPPLIES AND LOOSE KEY STOPS. INSULATE WATER AND WASTE TO MEET ADA
REQUIREMENTS.
P-604 WATER COOLER - DUAL HEIGHT ELKAY LZSTL8WSLK GALVANIZED STEEL LIGHT GRAY
GRANITE
No 0.13 GPM 15 40 °F 40 °F 1-1/2” --- 1-1/2” 1/2” TWO LEVEL WALL HUNG WATER COOLER WITH BOTTLE FILLING STATION. THE UNIT SHALL BE COMPLETE WITH CABINET, MOUNTING FRAME, SELF CLOSING EASY TOUCH SIDE AND FRONT PUSHBAR CONTROLS, FLEXIGUARD SAFETY BUBBLER, REFRIGERATING SYSTEM, AIR COOLED, 120 VOLT, 60 CYCLE, SINGLE PHASE POWER
CONNECTION, FULLY AUTOMATIC, COMPLETE AND READY TO OPERATE.
P-802 HOSE BIBB CHICAGO FAUCET CHICAGO FAUCET
CO
952-CP MANUAL No 2.50 GPM 0 40 °F 40 °F 1/2” INTERIOR HOSE BIBB WITH VACUUM BREAKER, 3/4" HOSE THREAD OUTLET, LOCK SHIELD CAP, AND REMOVABLE
"TEE" HANDLE. PROVIDE SHUTOFF VALVE IN COLD WATER SUPPLY AHEAD OF HOSE BIBB.
P-803 HOSE BIBB WITH SPRAY CHICAGO FAUCET CHICAGO FAUCET
CO
809-777-21KC
P
MANUAL No 1.50 GPM 0 40 °F 40 °F 1/2” INTERIOR HOSE BIBB WITH VACUUM BREAKER, 1/2" TAPERED OUTLET, LOCK SHIELD CAP, AND REMOVABLE CROSS HANDLE. 53" WHITE VINYL HOSE, SPRAY NOZZLE FULL FLOW SELF CLOSING SPAY VALVE. PROVIDE
SHUTOFF VALVE IN COLD WATER SUPPLY AHEAD OF HOSE BIBB.
SCALE: NTS
D8
DIAGRAM - DOMESTIC RISER
SCALE: NTS
F8
DIAGRAM - SANITARY RISER
EXPANSION TANK SCHEDULE - PLUMBING
EQPM ID LOCATION SERVES
SIZE INCH
CAPACITY
GALLONS
TANK DATA
MANUFACTURER MODELDIA. HEIGHT
ACCEPTANCE
FACTOR
FILL TEMP.
(°F)
MAX. TEMP.
(°F)
ET-1 M108 BUILDING 8" 1'-1" 2.0 0.45 110 200 AMTROL ST-5
ET-2 RR CLOSET RR 8" 1'-1" 2.0 0.45 110 200 AMTROL ST-5
PLUMBING PUMP SCHEDULE
EQPM ID LOCATION SERVES TYPE FLOW (GPM)
TOTAL HEAD
FT WG
SUCTION DIA
(IN)
DISCHARGE
DIA (IN)
IMPELLER
DIA (IN) RPM
ELECTRICAL DATA
MANUFACTURER MODEL NOTESHP VOL PH HZ
P-1 M108 RECIRCULATION 3-SPEED 1 9.87 1/2" 1/2" 3" 1750 .114 120 1 60 GRUNDFOS UPS 32-40 F B 1
1. INCLUDE AQUA-STAT FOR PUMP CONTROL.
FLOOR DRAIN SCHEDULE
TAG DESCRIPTION MANUFACTURER MODEL QTY
MATERIAL DESCRIPTION PRIMER
CONNECTIO
N
WASTE VENT PRIMER
SPECIFICATIONDRAIN BODY STRAINER
PIPE
SIZE
PIPE
SIZE
PIPE
SIZE
FD-1 FLOOR DRAIN WATTS FD-100-A 1 EPOXY
COATED CAST
IRON
NICKEL
BRONZE
No 4” 2” --- EPOXY COATED CAST IRON FLOOR DRAIN WITH ANCHOR FLANGE, REVERSIBLE
CLAMPING COLLAR WITH PRIMARY & SECONDARY WEEPHOLES, ADJUSTABLE
ROUND HEEL PROOF NICKEL BRONZE STRAINER, AND NO HUB OUTLET.
SCALE: 1/8" = 1'-0"
F6
PLUMBING PLAN - RESTROOMS (1501)
ELECTRIC WATER HEATER SCHEDULE
EQPM ID LOCATION SERVES
HEATING
OUTPUT
(KW)
TANK
STORAGE
CAPACITY
RECOVERY
EXPANSION
TANK TYPE
ELECTRICAL DATA
MANUFACTU
RER MODEL
WATER FLOW
(GPM) EWT (°F) LWT (°F)
TEMPERATU
RE RISE (°F) VOL PH HZ
EWH-1 RR CLOSET RR HOT
WATER
2.5 17.0 3 50 140 90 DIAPHRAGM 120 1 60 LOCHINVAR JRCO20FS
1-1/2"
SINK
10 MICRON FILTER
1-1/2"
WASTE PIPING
WITHIN WALL.
2"
DRAIN BOX
1-1/2" COLD WATER
SINK TRAP
HOT WATER
WATER SUPPLY & DRAIN
HOSE WITHIN WALL. SEE
EQUIPMENT
INFORMATION FOR PIPE
SIZES.
COUNTER
FLOOR
ICE MAKER
FROM HW SOURCE
TO FINAL FIXTURE (OR
FIXTURE GROUP) ON
BRANCH
TO CIRCULATING PUMPBALL VALVE
CIRCULATION CONTROL VALVE CHECK VALVE
D
STRAINER
HWC
CW
HW CIRCULATING PUMP CHECK VALVE (TYP.)
SHUT-OFF VALVE (TYP.)
HW
THERMOMETER (TYP.)
TEMPERATURE AND
PRESSURE RELIEF
VALVE
TO SINK BELOW
DRAIN VALVE WITH
HOSE THREADS
UNION
(TYP.)
5 GALLON
DIAPHRAGM
TYPE
EXPANSION
TANK
A
GENERAL:
1. SYSTEM CONSISTS OF A CIRCULATING PUMP AND AQUASTAT.
PUMP UNIT CONTROL:
1. PUMP SHALL ONLY BE OPERABLE DURING OCCUPIED HOURS AS DETERMINED BY
THE BUILDING TIME CLOCK (ADJ).
2. DURING OCCUPIED HOURS THE PUMP SHALL BE CONTROLLED BY THE SYSTEM'S
AQUASTAT.
SEQUENCE OF OPERATION - DOMESTIC HOT WATER CIRCULATING PUMP
DOMESTIC
WATER
SUCTION
DOMESTIC WATER
DISCHARGE
M
IT
CW UNION (TYP.)
SHUT-OFF VALVE
(TYP.)
HW
THERMOMETER
TEMPERATURE AND
PRESSURE RELIEF
VALVE
TO FLOOR DRAIN
DRAIN VALVE
WITH HOSE
THREADS
? GALLON
DIAPHRAGM
TYPE
EXPANSION
TANK
EDITING NOTE:
DELETE EXPANSION TANK IF THERE
ARE NO CHECK VALVES, PRV'S OR
BACKFLOW PREVENTERS IN CW
UPSTREAM.
D
Location
Issue Date
GORDON - The LA Group Joint Venture, LLC
The LA Group 40 Long Alley Saratoga Springs, NY 12866
(518) 587-8100
Integrity Federal Services, Inc.
148 S. Queen Street, Suite 201 Martinsburg, WV 25401
(304) 725-8456
Project Number
Drawing Number
Project Title
Checked Drawn
KALAMAZOO COUNTY, MICHIGAN
909CM3028
MARCH 24, 2023
Dwg. of
Office of Design and Construction
Service
U.S. Department of Veterans Affairs
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
Revisions: Date:
Drawing Title
Approved: Project Director
Phase
Building Number
BID DOCUMENTS FORT CUSTER NATIONAL CEMETERY
RENOVATE & EXPAND
MAINTENANCE BUILDING 3001Leo A Daly
(202) 861-4600
F ile
P at h:
P
:\0
\0
-1
-0
\4
-0 -P
R O
D U
C T
IO
N
-W O
R K
IN
G
\4 -1
-B
IM
-C A
D \R
E V
IT
\R
E S
O U
R C
E -F
IL
E
S \C
A D
-L
IN
K S
\B D
\9
C M
_G -T
T
LB
.D W
G
Above Group, Inc.
(321) 345-9026
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9
VA FORM 08 - 6231
321 4 5 6 7 8 9 10
PLUMBING DETAILS
PP501
DES MLG 44
SCALE:NONEB3
COUNTERTOP ICE MAKER DETAIL
SCALE:NONEB5
DOMESTIC HOT WATER CIRCULATING CONTROL
SCALE:NONE
B1
ELECTRIC DOMESTIC WATER HEATER W/PUMP
SCALE:NONE
C1
DOMESTIC HOT WATER CIRCULATING PUMP (DHWCP-1) CONTROLS DIAGRAM
SCALE:NONE
B7
ELECTRIC DOMESTIC WATER HEATER
V
H
S
P
FE
FCO
GCO
WCO
(DRAINS)
RD-
HB-
WH-
FS
M
FHC
FVC
CHWS
CHWR
HWS
HWR
CWS
CWR
CD
LPS
MPS
HPS
PC
RS
RL
LPC
MPC
HPC
RD
CF
GHS
GHR
HPWS
HPWR
HTWS
HTWR
HCS
HCR
T
GATE VALVE
DESCRIPTIONSYMBOL
GLOBE VALVE
CHECK VALVE
BUTTERFLY VALVE
FLANGE
BLIND FLANGE
BALANCING VALVE
GAS COCK
PRESSURE REGULATING VALVE
SOLENOID VALVE
CAP
PIPE VALVES, FITTINGS, SENSORS AND GAGES
ECCENTRIC PLUG VALVE
BALL VALVE
STRAINER
UNION
PRESSURE GAGE
COCK (GAGE, AIRVENT, DRAIN)
PIPE ANCHOR
PIPE GUIDE
PIPE EXPANSION COMPENSATOR
VACUUM BREAKER
SAFETY RELIEF VALVE
CONTROL VALVE (2-WAY)
CONTROL VALVE (3-WAY)
THERMOMETER
SUPERVISED O S & Y VALVE
THERMOSTAT
FLOW MEASURING ELEMENT
SIGHT GLASS (FLOW TYPE)
AIR ELIMINATOR
TEMPERATURE & PRESSURE RELIEF VALVE
STEAM TRAP
TEST PLUG
HUMIDISTAT
TEMPERATURE, HUMIDITY, OR CO2 SENSOR
PRESSURE SENSOR
PIPE ELBOW UP
PIPE ELBOW DOWN
FLOOR CLEANOUT
WALL CLEANOUT
CONTINUATION - PIPE NOT SHOWN
DRAINS - FLOOR - FD, TRENCH - TD, AREA -
ADROOF DRAIN OR OVERFLOW ROOF DRAIN
HOSE BIBB
GRADE CLEANOUT
PIPE TEE UP
PIPE TEE DOWN
WALL HYDRANT
FIRE DEPARTMENT CONNECTION
FIRE HOSE CABINET
FIRE VALVE CABINET
FLOW SWITCH
WATER METER
BACKFLOW PREVENTER
CONNECT TO EXISTING
CHILLED WATER SUPPLY (COOLING)
DESCRIPTIONSYMBOL
CHILLED WATER RETURN (COOLING)
HEATING WATER SUPPLY
HEATING WATER RETURN
MEDIUM PRESSURE STEAM (15-50 PSIG)
LOW PRESSURE CONDENSATE
MEDIUM PRESSURE CONDENSATE
HIGH PRESSURE CONDENSATE
PUMP CONDENSATE
REFRIGERANT SUCTION
HIGH PRESSURE STEAM (50-200 PSIG)
HVAC PIPING
CONDENSER WATER SUPPLY
CONDENSER WATER RETURN
CONDENSATE DRAIN
LOW PRESSURE STEAM (0-5 PSIG)
GLYCOL HEATING SUPPLY
HEAT PUMP WATER SUPPLY
HEAT PUMP WATER RETURN
HIGH TEMP WATER SUPPLY (HEATING)
HIGH TEMP WATER RETURN (HEATING)
HOT OR CHILLED WATER SUPPLY
GLYCOL HEATING RETURN
REFRIGERANT LIQUID
REFRIGERANT HOT GAS DISCHARGE
CHEMICAL FEED
HOT OR CHILLED WATER RETURN
ROUND FACE SUPPLY DIFFUSER
DESCRIPTIONSYMBOL
SQUARE FACE RETURN GRILLE
HVAC SYMBOLS
M
SQUARE FACE SUPPLY DIFFUSER
SQUARE FACE EXHAUST GRILLE
ROUND OR SPIRAL DUCTWORK
FLAT OVAL DUCT - FIRST NUMBER IS SIDE
SHOWNRECTANGULAR DUCTWORK
12 Ø
12/6 Ɵ
12x6
SUPPLY DUCT UP OR DOWN
RETURN / OUTSIDE AIR DUCT UP OR DOWN
EXHAUST DUCT UP OR DOWN
MANUAL VOLUME DAMPER
MOTORIZED DAMPER
ROUND DUCT TAP WITH MANUAL VOLUME
DAMPER
DESCRIPTIONSYMBOL
KEYNOTE
GENERIC ANNOTATIONS
EQUIP ID MECHANICAL EQUIPMENT TAG
#ØD1
ROUND NECK
DIFFUSER/GRILLE TAG
NECK DIAMETER, ID
AIRFLOW (CFM)
#x#G1
SQUARE NECK
DIFFUSER/GRILLE TAG
NECK SIZE, ID
AIRFLOW (CFM)
LINEAR SLOT DIFFUSER
FLEXIBLE PIPE CONNECTION
FLEXIBLE DUCT
FIRE DAMPER
SMOKE DAMPER
COMBINATION FIRE & SMOKE DAMPER
CONICAL TAKE-OFF
RECTANGULAR TAKE-OFF
MITERED ELBOW WITH TURNING VANES
RADIUSED ELBOW
EMERGENCY BOILER SHUTDOWN SWITCH
AIRFLOW MEASURING STATION
CO CLEANOUT
MECHANICAL DEMOLITION NOTES
1. ALL LINEWORK SHOWN BOLD, DASHED, OR HATCHED ON DEMOLITION DRAWINGS ARE TO BE REMOVED UNLESS
NOTED OTHERWISE.
2. ALL EXISTING MECHANICAL EQUIPMENT, DUCTWORK, PIPING, AND ACCESSORIES SHOWN HALFTONE ARE EXISTING
AND TO REMAIN.
3. NOT ALL EXISTING MECHANICAL EQUIPMENT, DUCTWORK, PIPING, AND ACCESSORIES ARE SHOWN FOR CLARITY.
THE SIZES AND LOCATIONS OF EXISTING EQUIPMENT, PIPING, AND DUCTWORK ARE SHOWN ACCORDING TO RECORD INFORMATION. CONTRACTOR SHALL MAKE APPROPRIATE PRE-BID SITE INSPECTIONS IN ORDER TO ASCERTAIN EXISTING CONDITIONS AND SHALL INCLUDE IN BID THE COST OF ALL WORK RESULTING FROM EXISTING
CONDITIONS. REFER ALL QUESTIONS TO THE A/E PRIOR TO BID FOR CLARIFICATION.
4. ALL UNDERGROUND UTILITIES ARE SHOWN IN APPROXIMATE LOCATIONS ONLY. CONTRACTOR SHALL DETERMINE
EXACT LOCATION OF ALL EXISTING UTILITIES PRIOR TO START OF WORK.
5. THE OWNER SHALL HAVE SALVAGE RIGHTS TO ANY ITEMS THAT ARE TO BE DEMOLISHED. EXISTING AHUs, FAN COIL UNITS, CHILLERS, PUMPS, EXHAUST FANS, AND VAV BOXES SHALL REMAIN PROPERTY OF THE OWNER AND SHALL ONLY BE DISPOSED IF DESIRED BY THE OWNER. ALL SHEET METAL AND PIPING WILL BE DISPOSED BY THE
GENERAL CONTRACTOR.
6. DEMOLITION WORK THAT WILL INTERRUPT HVAC OR PLUMBING CONTINUITY TO OTHER AREAS OF THE FACILITY THAT ARE TO REMAIN IN OPERATION, SHALL BE COORDINATED WITH THE OWNER TO ACCOMMODATE THE OWNER'S
NEEDS AS REQUIRED.
7. IF HAZARDOUS MATERIALS (I.E. ASBESTOS, PCB's, ETC.) ARE ENCOUNTERED AT ANY TIME DURING CONSTRUCTION
IN THE WORK AREA, STOP WORK IMMEDIATELY AND CONTACT THE ARCHITECT OR THE OWNER.
8. ANY BRANCH DUCTWORK OR PIPING SHOWN TO BE DEMOLISHED SHALL BE REMOVED BACK TO THE MAIN AND
CAPPED UNLESS OTHERWISE NOTED.
9. COORDINATE WITH MECHANICAL AND ELECTRICAL CONTRACTOR ALL THE EQUIPMENT TO BE REMOVED. REPORT ANY DISCREPANCIES BETWEEN PLANS AND ACTUAL FIELD CONDITIONS TO ARCHITECT PRIOR TO THE
COMMENCEMENT OF DEMOLITION WORK.
10. DEMOLISHED MATERIALS MUST BE PROPERLY CLEANED AND PLACED IN AN AIRTIGHT CONTAINER BEFORE
REMOVAL FROM THE AREA THROUGH ALL OCCUPIED SPACES.
11. OPENINGS IN WALLS, FLOORS, AND CEILINGS REMAINING FROM DUCT AND PIPE REMOVAL SHALL BE FILLED AND SEALED TO MATCH EXISTING WALL CONSTRUCTION AND MAINTAIN EXISTING WALL SMOKE AND FIRE RATING.
12. DEMOLITION SHALL BE PERFORMED IN SUCH A MANNER THAT WILL NOT DAMAGE ADJOINING SURFACES OR
EQUIPMENT INDICATED TO REMAIN.
13. CONTRACTOR SHALL GIVE THE OWNER NOTICE PRIOR TO ANY INTERRUPTION OF HVAC & PLUMBING SERVICES AS
SPECIFIED.
14. ANY AREAS DISRUPTED BY DEMOLITION THAT DOES NOT HAVE NEW WORK SHALL BE REPAIRED/PATCHED TO
MATCH EXISTING CONDITIONS AND FINISHES.
15. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING MATERIALS, EQUIPMENT, APPLIANCES AND DEVICES THAT ARE TO BE REUSED SHALL BE RECONDITIONED, TESTED AND PLACED IN GOOD AND PROPER WORKING CONDITION AND APPROVED. ANY DISCREPANCIES MUST BE BROUGHT TO THE ATTENTION OF THE ARCHITECT PRIOR TO BID.
16. RELOCATE EXISTING SYSTEMS (E.G. DUCT, PIPING, CONDUIT, CABLE TRAYS) OBSTRUCTING THE NEW
CONSTRUCTION.
MECHANICAL GENERAL NOTES
1. THE CONTRACTOR SHALL FURNISH AND INSTALL COMPLETE AND SATISFACTORILY OPERATING SYSTEMS AS INDICATED ON THE CONTRACT DOCUMENTS. IT IS NOTED THAT THE DRAWINGS ARE DIAGRAMMATIC AND INDICATE GENERAL ARRANGEMENTS OF SYSTEMS AND WORK. THE CONTRACTOR SHALL OBTAIN EXACT LOCATION, MEASUREMENTS LEVELS, ETC AT THE SITE AND SHALL ADAPT THE WORK TO THE ACTUAL CONDITIONS OF THE FIELD.
2. THE CONTRACTOR SHALL COORDINATE THE MECHANICAL WORK WITH THE WORK OF ALL OTHER TRADES INCLUDING, BUT NOT LIMITED TO, ARCHITECTURAL, STRUCTURAL, LIGHTING, POWER, SYSTEMS, PLUMBING, FIRE PROTECTION AND OTHERS FOR EXISTING AND NEW WORK SO AS TO AVOID CONFLICTS. RESOLVE ALL CONFLICTS THROUGH THE A/E PRIOR TO INSTALL. FAILURE TO PROVIDE SUCH COORDINATION PRIOR TO WORK BEING INSTALLED SHALL NOT BE CAUSE FOR ADDITIONAL COMPENSATION TO THE CONTRACTOR, AND MAY RESULT IN REJECTION OF THE WORK. IT IS
THE CONTRACTORS' RESPONSIBILITY TO COORDINATE SUBSTITUTIONS WITH OTHER TRADES.
3. THE SIZE AND LOCATION OF EQUIPMENT INSTALLED UNDER DIVISION 23 MECHANICAL SHALL BE COORDINATED WITH OTHER TRADES. CONNECTION TO EQUIPMENT SHALL BE VERIFIED WITH MANUFACTURER'S CERTIFIED DRAWINGS.
TRANSITIONS TO ALL EQUIPMENT SHALL BE VERIFIED AND PROVIDED FOR EQUIPMENT FURNISHED.
4. ALL PIPING AND DUCT IS TO BE CONCEALED ABOVE CEILING OR IN NEW WALLS UNLESS SPECIFICALLY NOTED AS EXPOSED OR SURFACE MOUNTED. CONTRACTOR TO COORDINATE WITH THE GENERAL CONTRACTOR TO PAINT ALL
EXPOSED PIPING TO MATCH CORRESPONDING EXPOSED AREAS.
5. ALL EQUIPMENT SHALL BE SECURELY FASTENED BY MEANS OF ANCHORS, RODS, HANGERS, SUPPORTS, GUIDES, SWAY
BRACES, ETC., TO MAINTAIN ALIGNMENT AND PREVENT EQUIPMENT MOVEMENT.
6. ANY EQUIPMENT, PIPING, DUCTWORK, ETC. SHALL ONLY BE SUPPORTED FROM THE BUILDING STRUCTURE. NO EQUIPMENT SHALL BE SUPPORTED FROM OTHER PIPING, DUCTWORK, METAL ROOF DECK, LATERAL BRACING, OR
CONDUIT.
7. ALL PENETRATIONS OF ROOFS, EXTERIOR WALLS, FOUNDATIONS, OR OTHER WATER OR MOISTURE PROOF CONSTRUCTION SHALL BE SEALED WITH APPROPRIATE SEALING FITTINGS OR SEALED CONSTRUCTION TO PREVENT
THE INTRODUCTION OF MOISTURE INTO THE BUILDING.
8. ALL CONCRETE HOUSEKEEPING PADS FOR MECHANICAL AND PLUMBING EQUIPMENT SHALL BE SIZED AND LOCATED BY THE MECHANICAL CONTRACTOR. A MINIMUM THICKNESS OF ANY HOUSEKEEPING PADS SHALL BE 4" AND EXTEND A MINIMUM OF 4" BEYOND THE MECHANICAL OR PLUMBING EQUIPMENT. MECHANICAL CONTRACTOR SHALL COORDINATE
WITH THE GENERAL CONTRACTOR FOR THE SIZE AND LOCATION OF HOUSEKEEPING PADS.
9. ALL DUCTWORK AND PIPING IS SHOWN SCHEMATICALLY. PROVIDE ALL TRANSITIONS, ELBOWS, FITTINGS, ETC., TO ALLOW SMOOTH FLOWS. ALL SPLIT DUCT FITTINGS SHALL TRANSITION TO FULL SIZE OF THE SUM OF BOTH BRANCHES
UPSTREAM OF SPLIT.
10. MAINTAIN CLEARANCE OF A MINIMUM OF 6" BETWEEN DUCTWORK, PIPING, EQUIPMENT, ETC.
11. ALL DASHED LINEWORK AROUND MECHANICAL AND PLUMBING EQUIPMENT INDICATES REQUIRED SERVICE
CLEARANCES. ALL EQUIPMENT SHALL BE INSTALLED IN A MANNER TO MAINTAIN THE CODE OR MANUFACTURER'S REQUIRED CLEARANCES. FOLLOW MANUFACTURER'S RECOMMENDATIONS ON EQUIPMENT ACCESS AND MAINTENANCE
WHEN NOT INDICATED ON PLANS.
12. THE CONTRACTOR IS SOLELY RESPONSIBLE FOR COORDINATING WORK WITH THE TEST AND BALANCE FIRM. PRIOR TO TESTING AND BALANCING, THE CONTRACTOR SHALL START-UP, PRE-BALANCE, AND REPLACE ALL AIR FILTERS FOR EVERY AHU BEING TESTED. ALL DISCREPANCIES, DRIVE CHANGES, ETC. REPORTED BY ARCHITECT OR TEST AND BALANCE FIRM SHALL BE CORRECTED BY CONTRACTOR WITHIN SPECIFIED NUMBER OF CALENDAR DAYS AT NO ADDITIONAL COST. TESTING AND BALANCING SHALL BE COMPLETED PRIOR TO SUBSTANTIAL COMPLETION.
13. DO NOT LOCATE VALVES, DAMPERS, ACTUATORS, CONTROL COMPONENTS, ANY EQUIPMENT WITH MOVING PARTS OR ANY EQUIPMENT NEEDING ACCESS OR REGULAR MAINTENANCE ABOVE INACCESSIBLE CEILINGS. WHERE LOCATIONS OF VALVES CONTROLS OR EQUIPMENT IS UNAVOIDABLE, PROVIDE MIN. 24"X24" ACCESS PANELS.
14. COORDINATE MECHANICAL AND ELECTRICAL SUCH THAT PIPING, DUCTWORK AND EQUIPMENT ARE NOT LOCATED OVER ANY ELECTRICAL PANELS. DO NOT INSTALL EXTERNAL PIPING AND DUCTWORK THROUGH ELEVATOR EQUIPMENT
ROOMS.
15. THERMOSTATS AND TEMPERATURE SENSORS SHALL BE MOUNTED 46" ABOVE FINISHED FLOOR. COORDINATE THEIR LOCATIONS WITH FURNITURE/EQUIPMENT LAYOUTS, WINDOWS, ELECTRICAL SWITCHES, AND DOOR SWING AREAS.
16. APPLICABLE HVAC CODES AND STANDARDS:
- VA HVAC DESIGN MANUAL, REV. MARCH 1, 2022
- VA PLUMBING DESIGN MANUAL, REV. JUNE 1, 2022
- ASHRAE HANDBOOKS AND STANDARDS, LATEST EDITIONS
- SMACNA HVAC DUCT CONSTRUCTION STANDARDS - METAL AND FLEXIBLE - LATEST EDITION
- AHRI STANDARD 340/360, LATEST EDITION
DUCTWORK:
1. OFFSETS IN DUCTS AND PIPING (INCLUDING DIVIDING DUCTS) AND TRANSITIONS AROUND OBSTRUCTIONS SHALL BE
PROVIDED AT NO ADDITIONAL COST.
2. ALL SUPPLY AIR INLET DUCTWORK TO VAV BOXES SHALL BE (1) SIZE GREATER AND AN EVEN DIAMETER THAN VAV BOX
INLET SIZE UNLESS OTHERWISE NOTED.
3. ALL SUPPLY, RETURN, AND EXHAUST BRANCH DUCTWORK TO DIFFUSERS, REGISTERS, AND GRILLES SHALL BE THE
SAME SIZE AS THE NECK SIZE UNLESS OTHERWISE NOTED.
4. FLEXIBLE DUCTWORK SHALL BE FULLY EXTENDED NOT TO EXCEED 5'-0" IN LENGTH.
5. DO NOT PROVIDE MANUAL VOLUME DAMPERS IN MEDIUM PRESSURE DUCT (UPSTREAM OF ATUs) EXCEPT WHERE
SPECIFICALLY SHOWN.
6. ALL VOLUME DAMPERS INSTALLED ABOVE GYPSUM BOARD CEILING SHALL HAVE A REMOTELY OPERATED DAMPER OR
DAMPER IN DUCT SHALL BE ACCESSIBLE THROUGH ACCESS DOOR. THE DAMPER LOCATION TO BE ACCURATELY
LOCATED AND LABELED ON THE AS-BUILT DRAWINGS AT THE COMPLETION OF THE PROJECT.
7. ALL EQUIPMENT, DUCTWORK, ETC., SHALL BE SUPPORTED AS DETAILED AND/OR SPECIFIED. PROVIDE ADDITIONAL SUPPORTS AS REQUIRED TO PROVIDE A VIBRATION-FREE, RIGID INSTALLATION. SUPPORT ALL OBJECTS FROM
STRUCTURE.
8. ALL DUCTWORK SHALL BE CONSTRUCTED AND INSTALLED IN ACCORDANCE WITH NFPA 90A AND 90B. DUCT SIZES SHOWN ARE MINIMUM INSIDE DIMENSIONS. BEFORE FABRICATION, VERIFY AND COORDINATE ALL DIMENSIONS IN FIELD.
DUCT SIZES AND ALL OPENINGS THROUGH BUILDING CONSTRUCTION SHALL SUIT EQUIPMENT FURNISHED.
9. ACCESS PANELS IN DUCTWORK AND CEILINGS SHALL BE PROVIDED WHERE REQUIRED FOR OPERATION, BALANCING, AND MAINTENANCE OF ALL MECHANICAL EQUIPMENT.
10. PROVIDE FLEXIBLE DUCT CONNECTIONS ON ALL DUCTS CONNECTING TO EACH FAN AND FAN COIL UNIT.
11. DIFFUSER NECKS SHALL MATCH SIZES OF FLEX DUCTS TO BE CONNECTED. FLEXIBLE DUCTWORK SHALL BE FULLY
EXTENDED NOT TO EXCEED 5'-0" IN LENGTH.
12. COORDINATE DIFFUSER, GRILLE, AND REGISTER LOCATIONS WITH ARCHITECTURAL REFLECTED CEILING PLANS AND
EQUIPMENT OF ALL TRADES.
13. ALL VISIBLE SURFACES BEHIND THE GRILLES, REGISTERS AND DIFFUSERS SHALL BE PAINTED FLAT BLACK.
14. PROVIDE FIRE DAMPERS AT EACH FIRE RATED WALL, FLOOR, AND CEILING PENETRATION OF ALL AIR SUPPLY, RETURN, EXHAUST AND VENTILATION DUCTS. IF NOT SHOWN ON THE DOCUMENTS THIS MUST BE BROUGHT TO THE ATTENTION
OF THE ENGINEER PRIOR TO BID.
15. PROVIDE A REMOVABLE 3/4" X 3/4" MINIMUM MESH SCREEN AT ALL INTAKE LOUVERS, NO INSECT SCREENS.
16. ALL TRANSFER DUCTS ARE ACOUSTICALLY LINED TURNED-UP ELBOWS ABOVE THE CEILING, SEE DETAILS FOR
FURTHER CLARIFICATION.
PIPING:
1. ALL REFRIGERANT PIPING QUANTITY AND SIZES SHALL BE PROVIDED PER MANUFACTURER'S RECOMMENDATIONS.
2. CONDENSATE DRAINS FROM ALL MECHANICAL EQUIPMENT SHALL BE COORDINATED FOR PROPER DRAINAGE TO SUIT
EQUIPMENT FURNISHED. FOLLOW MANUFACTURER'S RECOMMENDATIONS. ALL CONDENSATE DRAIN LINES SHALL BE INSULATED AND INSTALLED WITH A 'P' TRAP AT THE UNIT WITH A MINIMUM DEPTH OF 2" OR PER MANUFACTURER'S INSTRUCTIONS, WHICHEVER IS GREATER. ALL 90° ELBOWS SHALL BE INSTALLED WITH A CLEANOUT.
3. UNLESS OTHERWISE NOTED, ALL EQUIPMENT AND VALVE DRAINS SHALL BE INDEPENDENTLY PIPED FULL SIZE TO THE
NEAREST INDIRECT CONNECTION.
CONTROLS:
1. CONTROL DEVICE MOTORS (DAMPERS, ETC.) SHALL BE 24VAC TYPE WITH ALL ELECTRICAL POWER REQUIREMENTS
CLEARLY NOTED ON THE CONSTRUCTION DRAWINGS.
Location
Issue Date
GORDON - The LA Group Joint Venture, LLC
The LA Group 40 Long Alley Saratoga Springs, NY 12866
(518) 587-8100
Integrity Federal Services, Inc.
148 S. Queen Street, Suite 201 Martinsburg, WV 25401
(304) 725-8456
Project Number
Drawing Number
Project Title
Checked Drawn
KALAMAZOO COUNTY, MICHIGAN
909CM3028
MARCH 24, 2023
Dwg. of
Office of Design and Construction
Service
U.S. Department of Veterans Affairs
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
Revisions: Date:
Drawing Title
Approved: Project Director
Phase
Building Number
BID DOCUMENTS FORT CUSTER NATIONAL CEMETERY
RENOVATE & EXPAND
MAINTENANCE BUILDING 3001Leo A Daly
(202) 861-4600
F ile
P at h:
P
:\0
\0
-1
-0
\4
-0 -P
R O
D U
C T
IO
N
-W O
R K
IN
G
\4 -1
-B
IM
-C A
D \R
E V
IT
\R
E S
O U
R C
E -F
IL
E
S \C
A D
-L
IN
K S
\B D
\9
C M
_G -T
T
LB
.D W
G
Above Group, Inc.
(321) 345-9026
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9
VA FORM 08 - 6231
321 4 5 6 7 8 9 10
MECHANICAL NOTES, SYMBOLS &
ABBREVIATIONS
M-001
DES MLG 45
C
(E) UNIT
HEATER
(E) UNIT
HEATER
(E) UNIT
HEATER
(E) UNIT
HEATER
(E) UNIT
HEATER
(E)
DUCTLESS
SPLIT
(E)
DUCTLESS
SPLIT
(E)
CONDENSING
UNIT
(E)
CONDENSING
UNIT
(E) UNIT
HEATER
(E) UNIT
HEATER
(E) UNIT
HEATER
(E) UNIT
HEATER
(ETR)
EXHAUST
FAN
(ETR)
EXHAUST
FAN
(ETR)
EXHAUST
FAN
(ETR)
EXHAUST
FAN
(ETR)
EXHAUST
FAN
(E) UNIT
HEATER
MD01
(ETR)
EXHAUST
FAN
MD02
MD02
MD02
MD02
MD02
Location
Issue Date
GORDON - The LA Group Joint Venture, LLC
The LA Group 40 Long Alley Saratoga Springs, NY 12866
(518) 587-8100
Integrity Federal Services, Inc.
148 S. Queen Street, Suite 201 Martinsburg, WV 25401
(304) 725-8456
Project Number
Drawing Number
Project Title
Checked Drawn
KALAMAZOO COUNTY, MICHIGAN
909CM3028
MARCH 24, 2023
Dwg. of
Office of Design and Construction
Service
U.S. Department of Veterans Affairs
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
Revisions: Date:
Drawing Title
Approved: Project Director
Phase
Building Number
BID DOCUMENTS FORT CUSTER NATIONAL CEMETERY
RENOVATE & EXPAND
MAINTENANCE BUILDING 3001Leo A Daly
(202) 861-4600
F ile
P at h:
P
:\0
\0
-1
-0
\4
-0 -P
R O
D U
C T
IO
N
-W O
R K
IN
G
\4 -1
-B
IM
-C A
D \R
E V
IT
\R
E S
O U
R C
E -F
IL
E
S \C
A D
-L
IN
K S
\B D
\9
C M
_G -T
T
LB
.D W
G
Above Group, Inc.
(321) 345-9026
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9
VA FORM 08 - 6231
321 4 5 6 7 8 9 10
MECHANICAL DEMOLITION PLAN
MD101
DES MLG 46
SCALE: 1/8" = 1'-0"
F2
MECHANICAL DEMOLITION PLAN - MAINTENANCE (3001)
KEYNOTE LEGEND
MD01 ALL MECHANICAL ITEMS SHOWN IN HATCHED AREA ON
DEMOLITION PLANS SHALL BE DEMOLISHED AND REMOVED IN
THEIR ENTIRETY UNLESS OTHERWISE NOTED. SEE DRAWINGS
OF OTHER TRADES FOR EXTENT OF DEMOLITION WORK.
MECHANICAL ITEMS SHALL INCLUDE DUCTWORK SYSTEMS, AIR
CONDITIONING UNITS, EXHAUST FANS, INSULATION,
SUPPORTS, HOUSEKEEPING PADS, AND ASSOCIATED
CONTROLS WIRING AND DEVICES, ETC.. REFER ALL QUESTIONS
OF APPLICABILITY TO THE A/E PRIOR TO BID FOR
CLARIFICATION; OTHERWISE, FIELD DECISIONS BY THE A/E
SHALL BE BINDING.
MD02 EXISTING-TO-REMAIN (ETR) EQUIPMENT TO REMAIN. REPAIR
AND CLEAN AS NECESSARY TO BRING TO A LIKE NEW
CONDITION.
4'
SCALE : 1/8" = 1'-0"
0 8' 16'
MD03
HP-2
HP-3
HP-1
ECU-1
EFC-1
MD03
CU-1
CU-2
CU-3
MD03
EF-1D
Location
Issue Date
GORDON - The LA Group Joint Venture, LLC
The LA Group 40 Long Alley Saratoga Springs, NY 12866
(518) 587-8100
Integrity Federal Services, Inc.
148 S. Queen Street, Suite 201 Martinsburg, WV 25401
(304) 725-8456
Project Number
Drawing Number
Project Title
Checked Drawn
KALAMAZOO COUNTY, MICHIGAN
909CM3028
MARCH 24, 2023
Dwg. of
Office of Design and Construction
Service
U.S. Department of Veterans Affairs
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
Revisions: Date:
Drawing Title
Approved: Project Director
Phase
Building Number
BID DOCUMENTS FORT CUSTER NATIONAL CEMETERY
RENOVATE & EXPAND
MAINTENANCE BUILDING 3001Leo A Daly
(202) 861-4600
F ile
P at h:
P
:\0
\0
-1
-0
\4
-0 -P
R O
D U
C T
IO
N
-W O
R K
IN
G
\4 -1
-B
IM
-C A
D \R
E V
IT
\R
E S
O U
R C
E -F
IL
E
S \C
A D
-L
IN
K S
\B D
\9
C M
_G -T
T
LB
.D W
G
Above Group, Inc.
(321) 345-9026
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9
VA FORM 08 - 6231
321 4 5 6 7 8 9 10
MECHANICAL DEMOLITION PLANS -
FCA ITEMS
MD121
DES MLG 47
SCALE: 1/8" = 1'-0"
C5
MECHANICAL DEMOLITION PLAN - ADMINISTRATION (1001)
KEYNOTE LEGEND
MD03 EXISTING EQUIPMENT TO BE DEMOLISHED.
SCALE: 1/8" = 1'-0"
F5
MECHANICAL DEMOLITION PLAN - RESTROOMS (1501)
M M
B
C
ERV-1
AHU-1
AHU-2
EUH-1
EUH-2
EUH-3
EUH-4
EUH-5
HP-1 HP-2
WU-1
EQUIPMENT
STORAGE
M111
WORKSHOP
M110
GROUNDS SUPPLY
M112
STORAGE
M113
OFFICE
M110A
CORRIDOR
M110B
MAINTENANCE
BAYS
M109
PARTS
M108
TRAINING
M107
MEN'S
M105
FOREMAN
M103
FAC MAINT
M102
VEST
M099
BREAK
M101
STOR
M104WOMEN'S
M106
30"x30" EXHAUST LOUVER.
COORDINATE LOCATION AND
FINISH PER ARCHITECT'S DRAWINGS.
24"x24" EXHAUST LOUVER.
COORDINATE LOCATION AND
FINISH PER ARCHITECT'S DRAWINGS.
T
AHU-2
T
AHU-1
DH-1
DH-2
12x12 OA
12x12 EA x1
E
A
8x8 EA x1
O
A x1
R
A
12x12 RA
18x12 SA 12x12 SA x1
S
A
8x8R1
10ØD1
10ØD1
10ØD1
8x8R1
8ØD1
8ØD1
8ØD1
8ØD1
8ØD1
14x14R1
8ØD1
10ØD1
8x8G1
10x10G1
8x8G1
10ØD1
8x8R1
2'-0"
MM02
MM02
8ØD1
EUH-6
A
MOUNT AT 7'
12x12 OA
12x12 EA 12x12 EA
12x12 SA
Location
Issue Date
GORDON - The LA Group Joint Venture, LLC
The LA Group 40 Long Alley Saratoga Springs, NY 12866
(518) 587-8100
Integrity Federal Services, Inc.
148 S. Queen Street, Suite 201 Martinsburg, WV 25401
(304) 725-8456
Project Number
Drawing Number
Project Title
Checked Drawn
KALAMAZOO COUNTY, MICHIGAN
909CM3028
MARCH 24, 2023
Dwg. of
Office of Design and Construction
Service
U.S. Department of Veterans Affairs
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
Revisions: Date:
Drawing Title
Approved: Project Director
Phase
Building Number
BID DOCUMENTS FORT CUSTER NATIONAL CEMETERY
RENOVATE & EXPAND
MAINTENANCE BUILDING 3001Leo A Daly
(202) 861-4600
F ile
P at h:
P
:\0
\0
-1
-0
\4
-0 -P
R O
D U
C T
IO
N
-W O
R K
IN
G
\4 -1
-B
IM
-C A
D \R
E V
IT
\R
E S
O U
R C
E -F
IL
E
S \C
A D
-L
IN
K S
\B D
\9
C M
_G -T
T
LB
.D W
G
Above Group, Inc.
(321) 345-9026
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9
VA FORM 08 - 6231
321 4 5 6 7 8 9 10
HVAC PLAN
MH101
DES MLG 48
SCALE: 1/8" = 1'-0"
F2
HVAC PLAN - MAINTENANCE (3001)
4'
SCALE : 1/8" = 1'-0"
0 8' 16'
N
SPLIT SYSTEM OUTDOOR HEAT PUMP UNIT SCHEDULE - MAINTENANCE BLDG
EQPM ID LOCATION SERVES
REFRIGERA
NT TYPE
COOLING HEATING
CAPACITY
(MBH)
COMPRESSOR ELECTRICAL DATA
MANUFACTURE
R MODEL NOTESCAP. MBH
AMB. TEMP
(°F) NO. TYPE RLA EA FLA VOL PH HZ
COND. FAN
MCANO. HP
HP-1 EXTERIOR AHU-1 R-410A 34.4 95 32 1 SCROLL 4 0.6 208 3 60 1 1/4 5.4 CARRIER 25HCE436AP06
HP-2 EXTERIOR AHU-2 R-410A 34.4 95 32 1 SCROLL 4 0.6 208 3 60 1 1/4 5.4 CARRIER 25HCE436AP06
ELECTRIC UNIT HEATER SCHEDULE
EQPM ID LOCATION TYPE FLOW (CFM)
HEATING DATA ELECTRICAL DATA
MANUFACTURER MODEL NOTESEAT (°F) KW VOLTAGE PHASE Hz
EUH-1 M109 INDUSTRIAL
HUNG
500 60 10.0 480 3 60 BERKO HUH-1048M 1, 2
EUH-2 M109 INDUSTRIAL
HUNG
500 60 10.0 480 3 60 BERKO HUH-1048M 1, 2
EUH-3 M110 INDUSTRIAL
HUNG
500 60 10.0 480 3 60 BERKO HUH-1048M 1, 2
EUH-4 M110 INDUSTRIAL
HUNG
500 60 10.0 480 3 60 BERKO HUH-1048M 1, 2
EUH-5 M113 INDUSTRIAL
HUNG
500 60 10.0 480 3 60 BERKO HUH-1048M 1, 2
EUH-6 VESTIBULE WALL
MOUNTED
300 60 4.0 208 3…