Bid Plans - Muskegon SGA Office Renovation 751-22233-GAG 240520.pdf

PDF 8 MB Posted

Attached to
751/22233. GAG; Muskegon SGA - Office Renovation & Addition
Solicitation number
RFQ 171 240000000473 3
Issued by
Oakland County, Warren City, Michigan

About this file

This document is a comprehensive set of bid plans and specifications for the State of Michigan Department of Natural Resources Muskegon State Game Area office renovation and addition project located at 7600 Messinger Road, Twin Lake, Michigan (State File No. 751/22233.GAG). The project encompasses renovation of approximately 2,998 square feet of existing building space and construction of a 1,297 square foot addition, for a total completed building area of 4,101 square feet, with 679 square feet designated for renovation. The scope of work includes site preparation and demolition, structural modifications, installation of new mechanical and plumbing systems, electrical upgrades, interior finishes including gypsum board, acoustic ceiling tiles, vinyl tile flooring, and casework, roofing with architectural asphalt shingles, exterior metal siding, windows, doors, and associated site work. The building will accommodate office spaces, staff facilities, a managed hunt area, service areas, and barrier-free toilet rooms, designed to house personnel for the State Game Area operations.

The project is governed by the Michigan Building Code (2015 IBC as amended), Michigan Mechanical Code, Michigan Plumbing Code, and National Electrical Code, with construction type 5B non-protected, business classification, and occupancy capacity of 41 persons based on 100 square feet per person. The design incorporates ADA accessibility requirements throughout, including barrier-free fixtures, grab bars, accessible parking, and compliant door hardware. All work must comply with current editions of applicable codes and standards, including ANSI A117.1 for accessibility. The bid plans set (dated May 10, 2024) represents the bid and plan review set following multiple design revisions completed between September 2022 and April 2024. Contractors are required to obtain required permits and pay associated fees, provide insurance with the Owner and Design Professional named as co-insureds, and verify existing site conditions prior to bidding. All materials must be new and undamaged, with shop drawings submitted for Design Professional approval prior to procurement and installation.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

MUSKEGON

COUNTY

LAKE

COUNTY

MASON

COUNTY

OCEANA

COUNTY

MUSKEGON

COUNTY

NEWAYGO

COUNTY

KENT

COUNTY

OTTAWA

COUNTY

MUSKEGON STATE

BID & PLAN REVIEW SET

SCHEDULE OF DRAWINGS:

TWIN LAKE, MICHIGAN

MAY 10, 2024

kendra c.

architects, p.c.

THOMPSON

803 Cherry Street Manistee, MI 49660 tel: 231.723.4195 thompson.kendra@sbcglobal.net www.kendrathompson-architects.com

PROJECT FOR:

GAME AREA

T100

DRAWING TITLE

KCT PROJECT NO.DRAWN

KCT

REVIEWED

KCT

DATE

SCALE

AS NOTED

DRAWING NO.

SEAL

COVER SHEET

SHEET NO.

NO. REVISIONS / SUBMISSIONS DATE

PROJECT NAME

7600 MESSINGER ROAD

NO SCALE

STATE MAP

N NO SCALE

COUNTY MAP

MI State File No. 751/22233.GAG

N NO SCALE

LOCATION MAP

N

SITE

OFFICE RENOVATIONS/ADDITION

SEP. 2022

KT-216015C

T100 COVER SHEET

A100 ABBREVIATIONS & SYMBOLS

A101 GENERAL SPECIFICATIONS

A200 DEMOLITION PLAN & SITE PLAN

A201 FOUNDATION PLAN

A202 FLOOR PLAN

A203 ROOM FINISH & DOOR SCHEDULES

A204 REFLECTED CEILING PLAN

A205 ROOF PLAN

A300 BUILDING ELEVATIONS

A301 BUILDING ELEVATIONS

A400 BUILDING SECTIONS

A401 WALL SECTIONS

A402 WALL SECTIONS

A500 INTERIOR ELEVATIONS

PD100 PLUMBING DEMOLITION FLOOR PLAN

P100 PLUMBING FLOOR PLAN

P200 PLUMBING SCHEDULES & DETAILS

MD100 MECHANICAL DEMOLITION FLOOR PLAN

M100 MECHANICAL FLOOR PLAN

M200 MECHANICAL DETAILS

M201 MECHANICAL SPECIFICATIONS & DETAILS

E000 ELECTRICAL SPECIFICATIONS & DETAILS

ED100 ELECTRICAL DEMOLITION FLOOR PLAN

E100 ELECTRICAL FLOOR PLAN

E200 ELECTRICAL SCHEDULES & DETAILS

ADDITION PROJECT

STATE GAME

MI FILE NO. 751/22233.GAG

MUSKEGON

AREA

7600 MESSINGER RD. -TWIN LAKE, MICHIGAN

OFFICE RENOVATIONS/

C op yr ig ht

Ke nd ra C

. T ho m ps on A rc hi te ct s, P

.C

Manistee, MI 49660

Kendra C. Thompson

803 Cherry Street t: 231.723.4195

Architects, P.C.

ARCHITECT:

t: 231.933.0510

Nealis Engineering

Traverse City, MI 49696 1419 Industry Drive

MECH/ELECT. ENGINEER

2 SD REV. #1 10/3/2022

1 SCHEMATIC DESIGNS 9/30/2022

3 SD REV. #2 2/20/2023

4 OWNER REVIEW SET 4/10/2024

5 OWNER REVIEW SET #2 5/6/2024

6 BID & PLAN REVIEW SET 5/10/2024

T S A

E G

A N

I

HICFO M

T

NO.

KENDRA

CAYE

1301035207

ARCHITECT

L

I C E N

SED

T

ARC

H

IT

E

C

THOMPSON

STANDARD ABBREVIATIONS

SYMBOLS KEYHATCHING PATTERN KEY

BARRIER-FREE MIN. CLEARANCES

BARRIER-FREE MOUNTING HEIGHTS

'-0

" M

IN

M A X.

M

IN

M

IN

MIRROR

SIMILAR)

(LAV. IN COUNTER,

B.F. LAVATORY

'-0

" M A X.

'-0

" M

IN

'-0

" M A X.

TY

P.

'-4

'-3

M A X.

M

IN

(ON WALL

SIGNAGE

EQUIPMENT

MISC. DISPENSERS,

OF DOOR

MISC. CONTROLS

LATCH SIDE

M A X.

'-0

W/ COAT

HAT SHELF

BAR

7"-9"

'-1

B.F. WATER

"M

IN

-4

"M

A X

CLOSET

GRAB BARS

TOILET PAPER

DISPENSER

CONT. FLOW

'-2

'-3

'-5

39"-41"

60"

" 3

12" 36" 12"

18" MIN.

12" MIN.

" M

IN

C

LE

A R

" M

IN

C

LE

A R

36" MIN. CLEAR

" M

IN

C

LE

A R

EXTERIOR

SIDE

" M

IN

C

LE

A R

12" MIN.

60" DIA. 60" TEE

INTERIOR EXTERIOR

60"

BUILDING

N

DET. NO.

SHT. NO.

A000

0 DET. NO.

SHT. NO.

DET.

SHT.

A COL. NO. A2

A-18

A

EL. NO.

SHT. NO.

SECTION

WALL/DETAIL

NORTH

ARROW

SECTION

CENTERLINE

DETAIL

BUBBLE

COLUMN

ROOM

101A DOOR

NUMBER

ROOM NAME/

NUMBER

INTERIOR

ELEVATION

WINDOW

TYPE

WALL

TYPE

8'0" CEILING

HEIGHT AFF

A000

2-HOUR FIRE

SEPARATION WALL

BRICK CONC BLOCK RIGID INSUL BATT INSUL ACOUST TILE

CONCRETE ASPHALT METAL FINISH WOOD GYP BOARD

EARTH SAND GRAVEL LUMBER PLYWOOD

ANG./L

BD.

FT. or '

A.F.F.

ACC.

ACC. PNL.

AC

ADDN.

ADJ.

A/C A.C.U.

A.H.U.

ALT.

ANCH.

A.B.

ANOD.

PT

APPR.

ARCH.

ASPH.

AUTO.

AVE.

BF

B.P.

BM.

B/C

BRG.

B.M.

BT.

BTW.

BIT.

BLKG.

BOTT.

B.S.

BDRY.

BLDG.

BRKT.

BULL.

CAB.

C.U.H.

CAP.

CPT.

L.L.

CSM.

C.I.

C.I.P.

CAT. NO.

C.B.

CLG.

CLG. HGT.

CEM.

CTR.

CL

C/C

CER.

C.T.

C.BD.

CHAM.

CHG.

CHAN.

CHKD. PL.

CHD.

CIRCUM.

C.O.

CLR.

CLO.

CW

COL.

CONC.

C.M.U.

COND.

CONF.

CONN.

CONST.

C.J.

CONT.

CONTR.

C.P.

CONV.

C.G.

CORR.

CPR.

CNTR.

CTSK.

CRS.

COV.

C.C.T.

CU. FT.

CFM

CY

CULV.

DAMPRG.

D.L.

DWG.

DEPT.

DES.

DIAG.

DIA.

DIFF.

DIM.

DIR.

EA.

E.F.

E.W.

E.I.F.S.

ELAST.

ELEC.

E.P.

EWC

EL

ELEV.

EMERG.

ENCL.

ENGR.

E/E

ENTR.

EPDM

EQ.

EQUIP.

EQUIV.

EST.

EXC.

EXH.

E.F.

EXIST.

EXP.

E.J.

EXP'D.

EXT.

EXTR.

FAB.

F/F

F. FIN.

FIG.

FIN.

F.R.

FIN. FLR/F.F.

F.A.

F.E.

F.E.C.

FPRF'G.

FLASH.

FIXT.

FLR. FIN.

FLR.

F.D.

R.S.

FLUOR.

FLDG.

FTG.

FDN.

FR.

FR/COV.

FRMG.

FURN.

FURR.

GA.

GALV.

G

GSKT.

GEN.

GL.

GLZ.

G.B.

GR

GB

G.F.I.

GT

GYP. BD.

H.R.

HDRW.

HR.

HD

HDR

HTR.

HTG.

HVAC

HGT

HEX.

H.

H.P.

HWY.

HSTWY.

H.M.

HORIZ.

H.B.

HRWD.

HYD.

I.D.

IN. or "

INCL.

INFO.

I.D.

I.F.

INST'L.

INSUL.

INT.

INV.

J.C.

JT.

JST.

K.P.

KIT.

K.D.

LBL.

LAB.

LAM.

LGE.

LDRY.

LAV.

L.H.

LGTH.

LEV.

LT.

LPRF.

LTG.

LTWT.

LTL.

LIN. DIFF.

L.F.

L.L.H.

LG.

L.L.V.

L.P.

LVR

LBR.

LBS. OR #

MACH.

M.A.U.

M.B.

MACH. RM.

MAINT.

MAT'L.

M.H.

MAS.

M.O.

MAX.

MED.

MEMB.

MEZZ.

MET.

UR.

MIN.

MIR.

MISC.

M.I.

MOD.

M.S.&S.

MLDG.

MTD.

MULL.

NAT.

N.S.

NRC

NOM.

NOR.

N N.I.C.

N.T.S.

NO. or #

O.C.

OPG.

OPER.

OPP.

OPP. HD.

ORIG.

OZ.

O/O O.A.

O.D.

O.F.

OHD.

PTD

PR

P.T.D.

P.T.W.R.

PRTN.

PVMT.

PED.

PERF.

PERIM.

PERM.

PERP.

PH

PLAS.

PL. LAM.

PL

PLBG

PLWD

FIRE EXTINGUISHER

POL.

PVC

PORC.

PSI

PCF

P/C

PREFAB.

P.T.WD.

PRIV.

PROJ.

PROP.

P.L.

P.S.

QTY

Q.T.

QTR

QTR. RD.

RAD.

REC'G.

RECT.

REF.

REFL.

REFR.

REINF.

REM.

REQ'D.

RESIL.

REV.

R.

R.O.W.

R.D.

R.H.

RM.

RFG.

RTU

R.O.

SAN

RND.

S.D.

SCHED.

S.S.

SECT.

SERV.

SHTHG.

SHT.

SHT. MET.

SHWR

S&R

SIM.

S.D.

SK

SPEC.

CONVECTOR

SPKLR.

SQ.

S.F.

STAG.

ST. STL.

STD

STL

STL. PL.

STIFF.

STOR.

ST.

STRUCT.

S. STL.

SURF.

SUSP.

SW.

SYM.

SYS.

T.BD.

TECH.

TEL.

TV

TEMP.

T

THK

THRESH.

THRU

T/TOIL.

T.P.

T.P.H.

T&G T&B T/C T.O.F.

T.O.W.

T.B.

T.D.

TD&WR

TRAN.

T T.D.

TS

TYP.

UL

UNFIN.

U.H.

U.V.

USGS

U.N.O.

EXTERIOR

V. BARR.

V

VTR

VENT.

V.I.F.

VERT.

VEST.

VCT

W.CAB.

W.C.O.

W/W

W.

W.C.

W.H.

W.STPG.

WT.

W.

W.O.

W.M.

W/ W/O

WD

YD

YR

ABOVE FINISHED FLOOR

ACCESS

ACCESS PANEL

ACOUSTIC TILE

ADDITION

ADJUSTIBLE

AIR CONDITIONING

AIR CONDITIONING UNIT

AIR HANDLING UNIT

ALTERNATE

ANCHOR

ANCHOR BOLT

AND

ANGLE

ANODIZED

APPROXIMATE

ARCHITECT/ARCHITECTURAL

ASPHALT

AT

AUTOMATIC

AVERAGE

BARRIER FREE

BASE PLATE

BEAM

BACK OF CURB

BEARING

BENCH MARK

BENT

BETWEEN

BITUMINOUS

BLOCKING

BOARD

BOTH SIDES

BOTTOM

BOUNDARY

BRACKET

BUILDING

BULLETIN

CABINET

CABINET UNIT HEATER

CAPACITY

CARPET

CASEMENT

CAST IRON

CAST IRON PIPE/CAST-IN-PLACE

CATALOG NUMBER

CATCH BASIN

CEILING

CEILING HEIGHT

CEMENT

CENTER

CENTERLINE

CENTER-TO-CENTER

CERAMIC

CERAMIC TILE

CHALKBOARD

CHAMFER

CHANGE

CHANNEL

CHECKERED PLATE

CHORD

CIRCUMFERENCE

CLEAN OUT

CLEAR

CLOSET/CLOSURE

COLD WATER

COLUMN

CONCRETE

CONCRETE MASONRY UNIT

CONDUIT

CONFERENCE

CONNECT

CONSTRUCTION

CONTROL JOINT

CONTINUE/CONTINUOUS

CONTRACTOR

CONTROL PANEL

CORRIDOR/CORRUGATED

CORNER GUARD

CARPET

COUNTER

CUBIC FEET

COUNTERSINK

COURSE

COVER

CLINICAL CURTAIN TRACK

CUBIC FEET PER MINUTE

CUBIC YARD

DIAMETER

CULVERT

DAMPROOFING

DEAD LOAD

DRAWING

DEPARTMENT

DESIGN

DIAGONAL

DIFFUSER

EACH WAY

DIMENSION

DIRECTORY

EACH

EACH FACE

ELEVATION

EXTERIOR INSULATION FINISH SYSTEM

ELASTOMERIC

ELECTRIC/ELECTRICAL

ELECTRICAL PANEL

ELECTRIC WATER COOLER

ELEVATOR

EMERGENCY

ENCLOSURE

ENGINEER

MAKE-UP AIR UNIT

END-TO-END

ENTRANCE/ENTRY

ETHYLENE PROPYLENE DENE MONOMER

EQUAL

EQUIPMENT

EQUIVALENT

ESTIMATE

EXCAVATED

EXHAUST

EXHAUST FAN

EXISTING

EXPANSION

EXPANSION JOINT

EXPOSED

EXTRUDED

FLOOR-TO-FLOOR

FABRICATED/FABRIC

FACTORY FINISH

FEET/FOOT

FIGURE

FINISH FLOOR

FINISH/FINISHED

FIRE ALARM

FIRE EXTINGUISHER CABINET

FIRE RETARDANT/FIRE TREATED

WALL CABINET

FIXTURE

FIREPROOFING

FLASHING

FLOOR

FLOOR DRAIN

FLUORESCENT

FLOOR FINISH

FOLDING

FRAME

FOOTING

FOUNDATION

FRAME AND COVER

FRAMING

GAUGE

FURNISH/FURNISHED

FURRING/FURRED

GAS

GALVANIZED

GLASS

GASKET

GENERAL

GRAB BAR

GLAZING

GRADE/GRILLE

GRADE BEAM

PERMANENT

GROUND FAULT INTERRUPTER

GROUT

GYPSUM BOARD

HANDRAIL

HARDWARE

HARDWOOD

HEAD

HEADER

HEATER

HEATING

HEATING, VENTILATING AND

HEIGHT

HEXAGON

HIGH

HIGH POINT

HIGHWAY

HOISTWAY

HOLLOW METAL

HORIZONTAL

HOSE BIBB

HOUR

HYDRANT/HYDRAULIC

IDENTIFICATION

INCH/INCHES

INCLUDE/INCLUDING

INFORMATION

INSIDE DIAMETER

INSIDE FACE

INSTALL/INSTALLATION

INSULATION

INTERIOR

INVERT

JANITOR CLOSET

JOINT

JOIST

KICK PLATE

KITCHEN

KNOCK DOWN

LABEL

LABORATORY

LAMINATE/LAMINATED

LARGE

LAUNDRY

LAVATORY

LEFT HAND

LENGTH

LEVEL

LIGHT

LIGHTPROOF

LIGHTING

LIGHTWEIGHT

LINTEL

LINEAR DIFFUSER

LINEAR FEET/FOOT

LIVE LOAD

LONG

LONG LEG HORIZONTAL

LONG LEG VERTICAL

LOUVER

LOW POINT

LUMBER

POUNDS

MACHINE

MARKER BOARD

MACHINE ROOM

MAINTENANCE

MANHOLE

MASONRY

MASONRY OPENING

MATERIAL

MAXIMUM

MEDIUM

MEMBRANE

METAL

MEZZANINE

MINIMUM

MIRROR

MISCELLANEOUS

MISCELLANEOUS IRON

MODEL

MOP STRIP AND SHELF

MOLDING

MOUNTED

MULLION

NATURAL

NEAR SIDE

NOICE REDUCTION COEFFICIENT

NOMINAL

NORMAL

NORTH

NOT-IN-CONTRACT

NOT-TO-SCALE

NUMBER

ON CENTER

OPENING

OPERATOR

OPPOSITE

OPPOSITE HAND

ORIGINAL

OUNCE

OUT-TO-OUT

OUTSIDE AIR

OUTSIDE DIAMETER

OUTSIDE FACE

OVERHEAD

PAINTED

PAIR

PAPER TOWEL DISPENSER

PAPER TOWEL WASTE RECEPTACLE

PARTITION

PAVEMENT

PEDESTAL

PERFORATED

PERIMETER

URINAL

PERPENDICULAR

PHYSICALLY HANDICAPPED

PLASTER

PLASTIC LAMINATE

PLATE

PLUMBING

PLYWOOD

POINT

POLISH/POLISHED

POLYVINYLCHLORIDE

PORCELAIN

POUNDS PER SQUARE INCH

POUNDS PER CUBIC FOOT

PRECAST

PREFABRICATED

PRESERVATIVE TREATED WOOD

PRIVACY

PROJECT/PROJECTOR

PROPERTY/PROPOSED

PROPERTY LINE

PURSE SHELF

QUANTITY

QUARRY TILE

QUARTER

QUARTER ROUND

RADIUS

RECEIVE/RECEIVING

RECEPTACLE

REFER/REFERENCE

REFLECTED/REFLECTIVE

REFRIGERATOR

REINFORCED/REINFORCING

REMOVE/REMOVABLE

REQURIED

RESILIENT

REVISED/REVISION

RISER

RIGHT-OF-WAY

ROOF DRAIN

ROOF HATCH

ROOF SUMP

ROOFING

ROOF TOP UNIT

ROOM

ROUGH OPENING

ROUND

SANITARY

SANITARY NAPKIN DISPOSAL

SCHEDULE

SECTION

SERVICE

SERVICE SINK

SHEATHING

SHEET

SHEET METAL

SHELF AND ROD

SHOWER

SIMILAR

SINK

SOAP DISPENSER

SOUND TRANSMISSION CLASS

SPECIFICATIONS

SPRINKLER

STAGGERED

SQUARE

SQUARE FEET/FOOT

STAINLESS STEEL

STANDARD

STEEL PLATE

STEEL

SWITCH

STIFFENER

STORAGE

STREET

STRUCTURAL

STRUCTURAL STEEL

SURFACE/SURFACING

SUSPEND/SUSPENSION

SYMBOL/SYMMETRICAL

SYSTEM

TECHNICAL

TACKBOARD

THICK/THICKNESS

TELEPHONE

TELEVISION

TEMPERATURE

THERMOSTAT

THRESHOLD

THROUGH

TOILET PAPER HOLDER

TOILET

TOILET PAPER DISENSER

TONGUE AND GROOVE

TOP OF CURB

TOP AND BOTTOM

TOWEL BAR

TOP OF FOOTING

TOP OF WALL

TOWEL DISPENSER

TRANSOM

TOWEL DISPENSER

TREAD

TRENCH DRAIN

TUBE SECTION

TYPICAL

DET.

UNDERWRITERS LABORATORY

UNFINISHED

UNIT HEATER

UNIT VENTILATOR

UNITED STATES GEOLOGICAL SURVEY

UNLESS NOTED OTHERWISE

VAPOR BARRIER

VENT

VENT THRU ROOF

VENTILATE/VENTILATION

VERIFY IN FIELD

VERTICAL/VERTICALLY

VESTIBULE

VINYL COMPOSITION TILE

WALL CLEAN OUT

WALL-TO-WALL

WEST

WATER CLOSET

WATER HEATER

WEATHERSTRIPPING

WEIGHT

WIDE/WIDTH

WINDOW OPENING

WIRE MESH

WITH

WITHOUT

WOOD

YARD

YEAR

ACT

ACOUSTIC/ACOUSTICAL

AMT

ALUMINUMALUM./AL

AMOUNT

AIR CONDITIONING

MECH. MECHANICAL

AND WASTE RECEPTACLE

DETAIL

WWR

STC

WELDED WIRE REINFORCING

FFE FURNITURE, FIXTURES & EQUIPMENT

FOR USE WHERE NOT OTHERWISE INDICATED ON DETAILED DRAWINGS - ALL WORK TO COMPLY W/CURRENT EDITION OF ANSI A117.1 & ADA REQUIREMENTS

DWG. DRAWING

H.D. HAND DRYER

S.C. SHARPS CONTAINER DISPOSAL

C.H. COAT (OR ROBE) HOOK

W.D. WASTE DISPOSAL

BUILDING DESIGN DATA

kendra c.

architects, p.c.

THOMPSON

803 Cherry Street Manistee, MI 49660 tel: 231.723.4195 thompson.kendra@sbcglobal.net www.kendrathompson-architects.com

A100

DRAWING TITLE

KCT PROJECT NO.DRAWN

KCT

REVIEWED

KCT

DATE

SCALE

AS NOTED

DRAWING NO.

SEAL

SHEET NO.

NO. REVISIONS / SUBMISSIONS DATE

PROJECT NAME

ABBREV. &

SYMBOLS

1 SCHEMATIC DESIGN 9/28/2022

SEP. 2022

KT-216015C

2 SD REV. #1 10/3/2022

1 SCHEMATIC DESIGNS 9/30/2022

3 SD REV. #2 2/20/2023

4 OWNER REVIEW SET 4/10/2024

5 OWNER REVIEW SET #2 5/6/2024

6 BID & PLAN REVIEW SET 5/10/2024

ADDITION PROJECT

STATE GAME

MI FILE NO. 751/22233.GAG

MUSKEGON

AREA

7600 MESSINGER RD. -TWIN LAKE, MICHIGAN

OFFICE RENOVATIONS/

C op yr ig ht

Ke nd ra C

. T ho m ps on A rc hi te ct s, P

.C

MICHIGAN MECHANICAL CODE, CURRENT EDITIONMECHANICAL CODE:

ELECTRICAL CODE: NATIONAL ELECTRIC CODE, CURRENT EDITION

BUILDING CODE:

PLUMBING CODE: MICHIGAN PLUMBING CODE, CURRENT EDITION

MICHIGAN BUILDING CODE (2015 IBC, AS AMENDED)

BUILDING DATA:

MECH/ELECT. CODE JURISDICTION: STATE OF MICHIGAN - LARA BCC

BUILDING CODE JURISDICTION: STATE OF MICHIGAN - LARA BCC

W/ 2019 MICHIGAN PART 8 RULES, OR APPROVED CURRENT EDITION

USE GROUP CLASSIFICATION:

CONSTRUCTION TYPE: 5B, NON-PROTECTED

B, BUSINESS

2,998 SF, GROSS INTERIOREXISTING

BUILDING AREA:

BUILDING OCCUPANCY:

BUILDING AREA = 4,101 SF, INTERIOR THEREFORE, 41 PERSONS (BASED ON 100 SF/PERSON)

FIRE-RESISTANCE RATINGS: UTILITY ROOM: 1-HOUR

1,297 SF, GROSS INTERIORADDITION

679 SF, GROSS INTERIORRENOVATED AREA

ROOF DESIGN LOADS:

ROOF DEAD LOADS:

ROOFING 2.5 PSF

STRUCTURE

DECKING 2.5 PSF

MISCELLANEOUS 5.0 PSF

7.0 PSF

GROUND SNOW LOAD:

EXPOSURE FACTOR: 1.0

60 PSF

IMPORTANCE FACTOR: 1.1

BASIC WIND SPEED: 120 MPH, EXPOSURE B

SEISMIC DESIGN CATEGORY: USE GROUP I

SITE CLASS D

APPLICABLE CODES:

( 194 SF, GROSS INTERIOR)AREA TO BE DEMOLISHED

4,101 SF, GROSS INTERIORTOTAL AREA COMPLETED BLDG.

Furnish and install exterior overhead insulated steel garage door as indicated on drawings. Door shall be Model #150 Thermaspan as manufactured by Wayne Dalton or approved equal. Doors shall be constructed of hot-dipped galvanized structural steel with embossed stucco texture finish with polyurethane core. Factory finish using two-coat plus primer polyester paint system, color selected by Design Professional from manufacturer's full range of colors. Inside and exterior skins shall have thermal break. Construction shall include 20 gauge steel brackets and plates with 18 gauge section end caps.

Glass shall be 1-inch Low-E insulating glass. Unit shall minimum overall R-value equal to 14.5 or higher.

Guides shall be manufacturer's standard roll-formed steel channel secured to wall in accordance with manufacturer's installation requirements. Door shall be balanced with manufacturer's 50,000 cycle torsion springs. Provide motor operator with photo-eye sensing edge for automatic reversing upon contact with an object, perimeter seals and weatherstripping and interior sealed slide locking mechanism. Provide 12 HP, 115V, 60 H, 1-phase electric operator and logic control board. Furnish one remote operator. Comply with wind loading as required by local codes. Installation shall be in accordance with manufacturer's instructions. Contractor to coordinate overhead track with installation of ceiling system. Submit product information to Design Professional for review prior to construction.

Furnish and install factory finished flush panel interior wood doors in size and profile as indicated on drawings. Acceptable manufacturer's are Eggers Industries, Graham Doors, Marshfield Doors or approved equal. Doors shall be 1-3/4 inch thick, solid lumber construction with mortised and tenoned construction. Doors shall wood veneered, maple species, rift cut with slip-matched grain with edges of same species. Construct and finish doors in accordance with AWI standards. Doors shall be factory machined for finish hardware. Factory finish doors in accordance with AWI Quality Standards Section 1500 for transparent catalyzed polyurethane, satin sheen. Install doors in accordance with manufacturer's instructions and AWI standards. Submit shop drawings and color finish samples to Design Professional for review prior to construction.

Anchors

All roof sheathing shall be 5/8-inch exterior grade, APA rated for 24-inch span. Install with H-clips and anchor per all APA recommendations. Exterior wall sheathing shall be 1/2-inch exterior grade, APA rated. Install and anchor per all APA recommendations. Install all necessary backer boards and blocking required for cabinets, casegoods, shelf supports, wall brackets, door hardware, toilet accessories, electrical, telephone and other miscellaneous equipment.

Roof & Wall Sheathing

DIVISION 5 - METALS

DIVISION 4 - MASONRY

DIVISION 3 - CONCRETE

Concrete

DIVISION 2 - SITE WORK

DIVISION 1 - GENERAL REQUIREMENTS

Do NOT scale drawings. Use dimensional figures only. Contractor shall verify all dimensions prior to construction and shall be responsible for same. Contractor to notify Design Professional immediately of any discrepancies, dimensional errors, etc. occurring on the drawings and specifications.

It shall be required that the Contractor submit material samples and shop drawings for the primary components of this project to the Design Professional. Additionally, reference shall be made to mechanical, plumbing and electrical specifications within the drawings. Where specific materials are specified, provide only that product unless approved prior to installation by the Design Professional.

Colors selected shall be from manufacturer's full range of colors.

Product Samples and Substitutions

Contractors are responsible for obtaining and paying for required permits and inspections as associated with their respective trade. General Contractor shall secure land use and other applicable site development permits as required.

Contractors shall provide Certificate of Insurance as outlined by State of Michigan DTMB Bid Manual contract requirements for general, auto, workman's compensation insurance and other as applicable.

The Owner and Design Professional shall be named as co-insured for the duration of the project.

Prime and Sub-Contractors required to be licensed by State of Michigan for their respective trade.

Earthwork

Drawings

Permit Fees

Insurance

Overhead Insulated Door

All Work shall be performed in strict conformance with State of Michigan Building Code (IBC 2015, as amended), American's with Disabilities Act (ADA, current edition), Michigan Mechanical Code, Michigan Plumbing Code, National Electrical Code and other state and local regulations as they may apply.

Governing Regulations

The scope of work includes, but not limited to, the furnishing materials and providing labor to complete all work required for the renovations and addition of an existing building located at 7600 Messinger Road, Twin Lake, Muskegon, Mason County, Michigan to accommodate facilities for State of Michigan Department of Natural Resources - Muskegon State Game Area.

DIVISION 0 - CONDITIONS OF THE CONTRACT

Scope of the Work

GENERAL SPECIFICATIONS

Licensing

DIVISION 8 - DOORS AND WINDOWS

Interior Flush Wood Doors

All surfaces not having factory finish or as otherwise indicated on drawings shall receive finish paint or stain. Painting also includes all unfinished equipment or materials that do not already have a factory finish. Paint and stains shall meet federal regulations for low VOC. Work shall include all accessory materials including primers, cleaning agents, sealers and patching material as required for a complete job. Color Schedule to be provided by Design Professional prior to paint installation. Use the following schedule, or as otherwise recommended by manufacturer:

Exterior ferrous metals:

Exterior galvanized metals:

Interior concrete floor, opaque:

Interior ferrous metals:

Interior gypsum board/plaster:

Specific finishes as follows:

Concrete, concrete block

Gypsum board Interior ceilings, soffits, bulkheads Interior walls

Steel frames

Steel fabrications

Galvanized steel

Shop-primed metal items Exposed surfaces of lintels Mechanical equipment Electrical equipment

Acceptable manufacturers: Sherwin-Williams, Glidden Professional, Benjamin Moore & Co., Pratt & Lammbert Paints, Martin Seynour or approved equal.

DIVISION 10 - EQUIPMENT

Painting

Furnish and install glass, glazing compounds and accessories. Exterior glazing units shall be 1-inch insulating glass with low-E coating on #2 surface, 1/4-inch thick min. annealed float glass at outboard and inboard lite. Provide for gasket type glazing method. Interior glazing units shall consist of single safety glazing, 1/4-inch min. fully tempered float glass. Exterior glazing assemblies shall provide for dead loads and wind loads indicated on drawings, with deflection of glass being limited to 1/200 or glass flexure limitations. Float glass shall be annealed in compliance with ASTM C 1036, Type I, transparent flat, Class 1 clear, quality Q3. Fully tempered glass shall comply with ASTM C 1048.

Exterior sealed insulating units shall have aluminum edge spacers bent and soldered at corners, elastomer edge seal with silicone sealant, and purged interpane space with dry hermetic air developed to comply with ASTM E 2190. Glazing putty shall be polymer modified latex. Provide black butyl sealant of single component ASTM C 920, Grade NS, Class 12-1/2, uses M and A, Shore A hardness of 10 to 20, non-skinning. Acrylic sealant shall be black ASTM C 920, Type S, Grade NS, Class 12-1/2, Uses M and A. Silicone sealant shall be black capable of water immersion, Type S, Grade NS, Clas 25, uses M, A and G. Provide neoprene setting blocks and spacer shims, preformed butyl glazing tape and resilient polyvinyl chloride gaskets and splines as required for a complete assembly.

Installation method shall be as recommended by FRP door and frame storefront manufacturer system.

Glass and Glazing

DIVISION 9 - FINISHES

Gypsum Board

Install Dupont "TYVEK" polyethylene building wrap or equivalent at all exterior walls prior to installation of finish siding. All joints shall be lapped, fastened and sealed with tape.

Install formaldehyde-free closed cell foam insulation (2#) with R-value of 6.7 per inch minimum (BASF Earthform or approved equal), formaldehyde-free open cell foam insulation (1#) with R-value of 4.5 per inch minimum (BASF or approved equal), batt insulation with R-value of 3.0 per inch minimum (Johns-Manville or approved equal) and blown-in cellulose insulation with 100% recycled material content such as newspapers or equivalent (NuWool or approved equal) where indicated on drawings.

Seal all end joints between batts with tape. Provide sound attenuation blanket at all interior partition walls. Ceiling blanket insulation where ceiling is not in direct contact with the insulation shall meet limitations of flame spread rating not less than 25 and smoke developed rating less than 450. All insulation materials shall be installed by insulation contractor familiar with product and having minimum 3 years of relevant experience in systems. Installation shall be in strict accordance with manufacturer's recommendations. Submit product information to Design Professional for review prior to construction.

Furnish and install pre-finished metal siding "TruCedar CarbonTech 90" as manufactured by Quality Edge or approved equal. Siding material shall be factory finished in manufacturer's standard HD woodgrain super polyurethane. Color to be selected by Design Professional from manufacturer's full color range.

Siding material shall be roll formed galvanized steel. Vertical siding shall be 10-inch exposure in board-and-batten, single board style. Install using manufacturer's coordinating pre-finished starter strips, edge trims, outside and inside corner caps and other items as required for a complete installation. Accessories shall be made from same material as adjacent siding unless otherwise indicated. Install using fastening to wood using nails recommended by manufacturer of sufficient length to penetrate a minimum of 1-inch into substrate, installed at no more than 24-inches o.c. Where siding is in contact with dissimilar metals, protect against galvanic action as recommended by manufacturer.

Install joint sealant to provide a weathertight installation. All work shall be be completed in strict accordance with manufacturer's instructions. Submit shop drawings to Design Professional for review prior to construction.

Install sealant and backer rod where required to seal any joints, dissimilar material transitions and for watertightness. All sealants shall be low VOC products. General purpose exterior sealant shall be polyurethane ASTM C 920; Grade NS; Class 25; Use M, G, A; single or mulit-component. Exterior metal lap joint sealant shall be butyl or polyisobutylene; nondrying; nonskinning; noncuring. General purpose interior sealant shall be acrylic emulsion latex; ASTM C 834; Type OP; Grade NF; single component; paintable. Fixture to tile sealant shall be silicone ASTM C 920; Uses I, M and A; single component; mildew resistant. Butyl sealant for glazing shall be ASTM C 920; Grade NS; Class 12-1/2;

Uses NT, M, A, G, O; single component; solvent release; non-skinning; non-sagging. Colors to match adjacent surfaces. Install acoustic sealant at all interior partition sill plate, top plate and around wall penetrations. Firestopping material shall be installed of all joints and penetrations in fire-resistant and smoke-resistant assemblies, whether indicated on drawings or not. Firestopping material shall be system meeting ASTM E 814 that has F rating equal to rated assembly and minimum T rating equal to F rating that meets all requirements.

Sealants

Metal Siding: Vertical

Air Retardent

DIVISION 7 - THERMAL AND MOISTURE PROTECTION

Building Insulation: Closed Cell foam, Batt and Blown-In

Countertops: Plastic Laminate and Solid Surface Furnish and install countertops as indicated on drawings. Plastic laminate countertops shall be high-pressure plastic laminate (0.048 inch HPDL) selected from Formica, Wilsonart or approved equal with color selection from manufacturer's full color range. Plastic laminate countertops shall be 3/4-inch medium density fiberboard (MDF) substrate covered with HDPL, conventionally fabricated with HDPL edges. Provide backsplash of same construction where indicated on drawings. Toilet room vanity counter indicated on drawings as solid surface shall be as manufactured by Corian, Wilsonart or approved equal (color selection by Design Professional from manufacturer's full color range), bullnose edge with fabrication and installation in strict conformance with manufacturer's recommendations.

Submit product information to Design Professional for review prior to construction.

Hollow Metal Door Frames Furnish and install hollow metal frames as indicated on drawings and door schedule. Acceptable manufacturer's are Assa Abloy Ceco, Curries or Fleming; Republic Doors and Frames, Steelcraft or approved equal. Included are fire-rated and non-fire-rated steel frames for wood doors. All frames shall be factory primed with rust inhibiting primer complying with ANSI A250.10 and ready for field finishing. Steel frames for wood doors shall comply with requirements specified in ANSI A250.8 Level 3, 14 ga frames. All frames shall be equipped with resilient rubber silencers, 3 on strike side of single door. Frames shall be provided with mortar guard boxes for hardware cut-outs and grouted with Portland cement ground with max 4-inch slump. Installation of doors and frames shall be in conformance with NAAMM HMMA 840 standards. Doors and frames indicated to be fire-rated shall bear the certification plate of UL or other approved testing agency for rating specified. Coordinate preparation for door hardware in accordance with BHMA A 156.115 with reinforcement welded in place. Submit shop drawings to Design Professional for review prior to construction.

Acrylic latex, 3 coat One coat latex primer Semi-gloss: Two coats acrylic latex enamel Acrylic latex, 3 coat One coat galvanize primer Semi-gloss: Two coats acrylic latex enamel Epoxy enamel, 3 coat One coat primer, manufacturer recommended Two coat epoxy floor finish Acrylic latex, 3 coat One coat latex primer Semi-gloss: Two coats acrylic latex enamel Acrylic latex, 3 coats One coat latex primer sealer Two coat acrylic latex enamel

Finish all surfaces exposed to view Interior: acrylic latex, semi-gloss

Finish all surfaces exposed to view Acrylic latex, flat Acrylic latex, eggshell

Finish all surfaces exposed to view Acrylic latex, semi-gloss

Finish all surfaces exposed to view Interior & exterior, acrylic latex, semi-gloss

Finish all surfaces exposed to view Exterior, acrylic latex, semi-gloss

Finish all surfaces exposed to view Interior & exterior, acrylic latex, semi-gloss

Furnish and install accessories as outlined below. Accessory equipment and installation mounting shall be in compliance with ANSI/ICC 117.1 Standards for Accessibility. Installation shall be coordinated with placement of internal wall reinforcement for anchoring. Accessories semi- or recessed in walls shall be installed with acoustic sealant surround at perimeter. Products shall be as manufactured by Bobrick, Bradley Corp., American Specialties or approved equal. Accessories shall be manufacturer's standard stainless steel (ASTM A 666, Type 304), No. 4 brushed finish. Accessories shall be complete with necessary anchoring devices and miscellaneous components. Provide two keys for each accessory, master key all lockable accessories. Mirrors shall be float glass, ASTM C 1036 Type I, Class 1, Quality Q2, with coating in accordance with GSA CID-A-A-3002. Submit product information to Architect for review/approval prior to construction. Products shall be as follows:

BF Toilet Room #106 & Staff Bath #114:

1 ea. Grab Bar (@ water closet) 1 ea. Grab Bar (@ water closet) 1 ea. Grab Bar (@ water closet) 1 ea. Toilet Tissue Dispenser 1 ea. Paper Towel Dispenser 1 ea. Soap Dispenser 1 ea. Mirror, 24"X36"

Toilet and Bath Accessories

Furnish and install architectural casework as indicated conceptually on drawings and field verified for final dimensions. Casework shall be specially fabricated cabinet units consisting of high-pressure plastic laminate (0.048 HDPL) over 3/4-inch medium-denisty fiberboard (MDF) ANSI A208.2 with adhesive specified by AWI standards. Plastic laminate at exposed surfaces shall be Formica, Wilsonart or approved equal with color as selected from manufacturer's full color range. Cabinet liners that are closed to view by doors may be "melamine" type panels. All other exposed surfaces, including tops and bottoms of wall hung cabinets, shall be HPDL. Drawer bottom, panels and similar shall be constructed of hardwood meeting AHA A135.4, pressed wood fiber with resin binder, Class 1, tempered, 1/4-inch, smooth two sides. Provide European style door/drawer hardware with full extension and self-closing mechanism. Casework shelving shall include adjustable shelf supports using multiple pin supports and coordinating rest supports with 1-inch spacing adjustment. All cabinets shall be equipped with brushed aluminum C-pulls and individual keyed locks rated for heavy-duty use.

Cabinet supplier shall coordinate all work and requirements with General Contractor. Submit shop drawings to Design Professional for review prior to construction.

Architectural Casework

Finish Carpentry, miscellaneous components Furnish and install miscellaneous finish carpentry items as indicated on drawings. Shelf standards shall be 12 ga. anochrome finish #87 ANO and shelf brackets shall be 12 ga. heavy duty anachrome finish #187LL by Knape and Vogt. All shelving shown on drawings shall be shop fabricated plastic laminate face with laminate backing sheets on unexposed surfaces on medium density fiberboard (MDF) ANSI A208.2 with adhesive as specified by AWI standards. Plastic laminate shall be Formica, Wilsonart or approved equal. Color as selected from full color range. Submit shop drawings to Design Professional for review prior to construction.

Furnish and install miscellaneous sheet metal flashing and trim as indicated on drawings or as otherwise required for a complete job. Sheet metal flashing and trim shall be prefinished fluoropolymercoating (AAMA 2604) ASTM B209 aluminum. Minimum material thickness shall be 0.040 thick for components up to 6-inch face; 0.050 thick for 6-inch to 8-inch face and 0.064-inch thick for 8-inch to 10-inch face. Pieces shall be formed in longest possible lengths and completed in accordance with SMACNA guidelines. Coordinate all materials with other metal components, installing dissimilar material protection as required between components. Color shall be as selected by Design Professional from manufacturer's standard colors. Submit product information for review by Design Professional prior to construction.

Sheet Metal Flashing and Trim

Door Hardware

Furnish and install vinyl tile flooring and resilient wall base where indicated on Room Finish Schedule and drawings. Luxury vinyl tile (LVT) shall be solid vinyl with color extending throughout thickness complying with ASTM F 1700, wear layer thickness of 0.020-inch thickness with nominal 1/8-inch total thickness.

Products shall be 6" x 36" embossed wood grain equal to Shaw Contract Group "Uncommon Ground" or approved equal. Provide anodized extruded aluminum "L" or "T" component, satin chrome finish, as manufactured by Schluter Systems at all open edges of vinyl flooring, door thresholds, transitions between floor finish and/or materials. Transitions between differing height floor materials shall be install with floor leveling material placed to provide a continuous smooth transition. Resilient base shall be ASTM F 1861, Type TS rubber. Provide resilient base of 4-inch by 0.125-inch thick, satin finish with premolded external corners and end stops as manufactured by Johnsonite, Roppe or approved equal.

Colors to be selected from manufacturer's standard colors. Install in accordance with manufacture's instructions. Submit product information for Design Professional review prior to construction.

Vinyl Tile Flooring (LVT) and Wall Base

Model # (Bobrick Corporation) 36 inches 42 inches 18 inches B-2890 B-262 B-2112 B-290

Foundations have been designed for a soil bearing capacity of 2,500 psi. Soils shall be tested during the excavation at the design depth of footings. If adequate soil bearing capacity is not available, the Design Professional shall be notified immediately. Footings shall bear on firm, virgin soil or approved engineered fill. All materials excavated shall be distributed and finish graded on the site, excluding any undesirable materials which shall be legally disposed of off-site. All flatwork shall bear on minimum 6 inches MDOT Class IIA or better compacted sand with max. 95% density per ASTM D-1557.

Coordinate location of underground sleeves for site electrical prior to final construction. Finish landscaping shall be by Owner. Contractor responsible for removal of existing materials, vegetation and associated elements as required to accommodate new work. Finish landscaping shall be by Owner.

Concrete slabs shall be formed concrete of dimensions and reinforcement as indicated on drawings.

Welded wire reinforcement shall be 6x6 / #1.4x1.4 WWF ASTM A 185, flat sheets only. Concrete foundations and footings shall be as indicated on drawings. All concrete shall be 3500 psi at 28 days per ACI613-54. Place construction joints and control joints at intervals per current ACI standards.

Steel trowel all interior surfaces. Exterior concrete shall be air-entrained. Broom finish all exterior concrete slabs. All reinforcing bars shall be Grade 60, ASTM A 615 deformed bars, minimum 3 inches concrete cover. Reinforcing shall follow ACI 315 and ACI 318 requirements for placement. Use only non-chloride admixtures, if needed. Install rigid insulation where indicated on drawings. Insulation shall be 2" (R-10) extruded polystyrene for below slab use. Coordinate all buried work with associated trade contractors prior to construction.

Furnish and install all necessary anchors as required including anchor bolts for sill plates, column base supports, column/beam connectors, masonry ties and as otherwise required by structural system supplier. Install in a manner as specified in current ACI and AISC standards. Bolts shall be high-strength ASTM A325 bearing type with ASTM F436 washers.

All wood members shall be minimum 1050 psi bending stress materials, dressed lumber of S4S grade, (No. 2 Douglas Fir, Hem Fir or better) with maximum 19% moisture content at time of dressing. All lumber in contact with concrete, masonry or earth shall be treated for contact of such. All exterior wood shall be treated for exterior use. Install sill sealer equal to 1/2" compressible fiberglass blanket.

Provide continuous wood blocking between studs to accommodate installation of casework, toilet accessories, wall monitor equipment, and other elements requiring intermediate support for anchorage.

DIVISION 6 - WOOD AND PLASTICS

Wood Framing

Architectural Grade Asphalt Roof Shingles Install lifetime warranty Class A architectural grade asphalt roof shingles "Landmark" as manufactured by Certainteed or approved equal. Shingles shall be rated to withstand 110 mph winds. Use standard 6" stepped off diagonal method of installation. Provide 30# roofing felt conforming to ASTM D 226 asphalt impregnated building paper. Install aluminum (minimum .019) drip edge. Ridge vents shall be Certainteed Shinglevent or equivalent. All plumbing, mechanical and other penetrations shall be properly flashed in accordance with acceptable standard practice for shingle roof systems, paint to match roof color. Design intent is to match existing asphalt shingles scheduled to remain.

Furnish and install fiberglass reinforced polyester (FRP) flush panel doors and frames in size and profile as indicated on drawings. Acceptable manufacturer is Special-Lite, Inc. Model #SL-17 or approved equal. Doors shall be 1-3/4 inch thick, constructed with aluminum extrusions made using 6063-T6 alloy, minimum of 2-5/16 inch depth. Internal door construction shall include full-width tie rods through splines top and bottom and reinforced for hardware as required. Extruded stiles and rails shall be furnished with integral reglets to accept face sheets locked into place to permit flush appearance.

Doors shall complete pile brush weatherseals and bottom weather bar with nylon brush weatherstripping interlocked with bottom rail. Face sheet shall be FRP 0.120-inch thickness with pebbled finish and color throughout. Color shall be as selected by Design Professional from manufacturer's full color range. Door core shall be poured-in-place polyurethane foam of minimum 5 pound per cubic foot density (R-value of 9 minimum). Framing system shall be manufacturer's standard for FRP door leaf constructed using aluminum tubular framing system, 1/8-inch min. wall thickness.

Doors and frames shall be provided with manufacturer's SL-120 continuous aluminum hinge, sweep SL-301 and integral wool pile weatherstrip. Doors shall be factory machined for additional finish hardware. Install doors and frames in accordance with manufacturer's instructions and AWI standards.

Submit shop drawings and color finish samples to Design Professional for review prior to construction.

FRP Flush Doors and Aluminum Frames

Furnish and install gypsum board standard paper-faced gypsum panels per ASTM C 1396, sizes to minimize joints, square cut ends. Use 1/2-inch thickness for standard walls, 5/8-inch Type X for fire-rated assemblies, and 5/8-inch thickness for ceilings, unless indicated otherwise. Backing board for wet areas (surfaces behind shower unit) shall be 5/8-inch thick mold resistant, glass-mat faced board per ASTM C 1178 such as "DensShield" as manufactured by Georgia-Pacific Gypsum or approved equal. Finishing accessories, tape, screws and joint material shall be as recommended by board manufacturer. Installation of framing shall be in accordance with manufacturer's requirements for gypsum board substrate. Board installation shall be with screws and in compliance with ASTM C 840 and manufacturer's instructions. Place control joints consistent with lines of building spaces and not more than 30 feet apart on walls and ceilings over 50 feet long. Use corner beads at external corners and edge trim at dissimilar materials. Tape and finish walls and ceilings to be painted to Level 4; backing board to Level 2; wall areas above finished ceilings to Level 1. Maximum variation in finished surface: 1/8-inch in 10 feet. Walls indicated to meet fire resistant ratings shall be constructed in strict compliance with UL Laboratories, USG or other approved agency for ratings indicated. Provide fire and smoke barrier sealants for a complete assembly.

Furnish and install suspended metal grid ceiling system and acoustic ceiling panels as indicated on drawings. Metal suspension system shall be manufactured by same as acoustic panel units, equal to "Prelude XL" 15/16-inch tee system by Armstrong World Industries. Suspension system shall comply with ASTM C635 die-cut, interlocking components complete with stabilizer bars, clips, edge trim and all accessories to provide a complete installation. Provide minimum 4-inch high perimeter finish edge at ceiling cloud area where metal suspension system does not abut adjacent walls. Installation shall be in accordance with ASTM C 636, ASTM E 580 and manufacturer's instructions. Hold-down clips shall be installed on acoustic panels within 20 feet of an exterior door. Submit product information to Design Professional for review prior to construction. Acoustic tile panels shall be as follows:

ACT-1: "Cortega" as manufactured by Armstrong World Industries Size: 24 inch by 24 inch by 5/8-inch thickness Edge: Tegular reveal edge Surface Color: White Surface Pattern: Non-directional fissured

Acoustic Ceilings and Metal Suspension System

Signage

Furnish and install wall protection corner guards at all outside corners of interior walls at areas of new and renovated areas. Corner guards shall be surface-mounted opaque plastic-cover style with snap-on resilient plastic cover installed over retainer. Provide Model SSM-20N as manufactured by Acrovyn or approved equal. Fabrication shall accommodate 80-degree and 135-degree arrangements. Color and texture shall be as selected by Design Professional from manufacturer's full color range.

Wall Protection Corner Guards

Furnish and install fire extinguishers and cabinets as indicated on drawings. Cabinets shall be Model AL-1840 as manufactured by Guardian Fire Equipment or approved equal. Cabinets shall be semi-recessed steel cabinet with glass door designed to accommodate specific fire extinguisher, continuous steel piano hinge, pin and handle hardware with clear anodized aluminum finish. Fire extinguisher for cabinet shall be multi-purpose dry-chemical type 4-A:80-B:C UL-rated 10 gallon nominal capacity. Fire extinguisher to be provided by same manufacturer as cabinet. Cabinet and extinguisher installation shall meet requirements of NFPA 10, Americans with Disabilities Act (ADA) and other applicable regulations.

Submit shop drawings to Design Professional for review prior to construction.

Fire Extinguishers and Cabinet

All wood roof trusses, pre-engineered wood framing members and multi-ply laminate beams shall be designed by a registered engineer in the State of Michigan working with the truss manufacturer.

Design values shall be as indicated in the drawings. All roof trusses shall have a minimum of 2-inch by 6-inch chord members. All members shall be designed per current Truss Plate Institute "Design Specifications for Wood Trusses". Local and state regulations shall prevail if they exceed requirements of Truss Plate Institutes standards. Manufacturer shall provide all required bridging, cross bracing, clips and other components, including hurricane anchors/tie-downs for areas subject to wind uplift as required. Manufacturer shall be held responsible for the design and manufacture of members meeting the specifications and design intent set forth herein. Laminated beams shall meet AITC 115 Standards for Fabricated Structural Timber. Pre-engineered wood framing system and beams shall be as manufactured by TrusJoist Company or approved equal. Framing system manufacturer shall provide detailed framing diagrams and details specific for the scope of work for Design Professional review.

Pre-Engineered Trusses, Beams

Refer to Sheet A100 for Building Information & Data and Bid Manual for further General Requirements.

Manufactured Stone Veneer and Precast Stone Components Furnish and install stone veneer at exterior column bases. Veneer material shall be premanufactured concrete stone as manufactured by Boral Products or approved equal. Stone selection shall be similar to 25% Southern Ledgestone, Chardonnay, 25% Southern Ledgestone, Bucks County, 25% Dressed Field Stone, Chardonnay and 25% Dressed Fieldstone, Bucks County. Final selection by Design Professional. Furnish and install limestone column pier cap as outlined on drawings. Veneer stone shall be installed using mortar consisting of Portland cement meeting ASTM C150, Type I or Type N masonry cement meeting ASTM C91, masonry sand, ASTM C207 lime and iron oxide pigments as required. Install clear non-glare masonry sealer at all finished surfaces. Installation shall be with metal lath on backer board in accordance with manufacturer's installation instructions.

Finish Wood, interior All miscellaneous finish wood, including but not limited to column surrounds, window casings and sills, Service Area casework veneer paneling and other miscellaneous finish trim, shall be No. 1 Cedar. Sizes shall be as indicated on drawings to comply with design intent. Finish wood to be field stained.

Submit shop drawing information to Design Professional for review prior to construction.

All rubber flashing shall be 40 mil, EPDM rubber glued to substrate as manufactured by Grace Construction Products (Ice and Water Shield) or approved equal. Roof ice and water shield shall be installed minimally at entire roof perimeter, extending minimum 36-inches up from interior face of exterior walls, at roof transitions extending minimum 36-inches up, at roof valleys extending each direction minimum 36-inches, entire areas of 4:12 or less roof slopes and at other similar locations requiring enhanced flashing. Install flashing minimum 18 inches up at all vertical wall/roof junctions.

Provide flashing at all plumbing, mechanical or other miscellaneous penetrations. All doors and windows shall be flashed and wrapped all sides using door/window manufacturer's recommended installation methods.

Membrane Flashing

Install vapor retardant polyethylene sheet not less than 6 mils thick on the interior face of exterior walls and ceilings prior to installation of finish material. Install 10 mil thickness vapor retardant polyethylene sheet under all concrete slabs. All wall seams shall be taped so as to provide a complete continuous membrane. Installation under concrete slabs shall have seams lapped 3-inches to provide a complete membrane. Do NOT install vapor barrier where specialized wall/roof sheathing with integral air barrier or insulation manufacturer does not recommend.

Vapor Retardent

Windows units shall be of sizes and configurations as indicated on drawings. Units shall be aluminum clad, wood frame units "Architectural" series window units as manufactured by Pella Corporation.

Provide low-E, insulating glass, with argon (Advanced Comfort). Furnish screens for all operable units.

All units shall be manufacturer's standard pine, factory stained and finished. Units shall meet requirements of Michigan Energy Code. Provide tempered glass where required by code such as units exceeding 9 sq.ft. or within 18 inches of floor or adjacent to an operable door shall be tempered. All units shall be factory assembled. Provide complete with manufacturer's warranty. Submit shop drawings and color finish samples for Design professional review prior to construction.

Aluminum-Clad Window Units

All concrete masonry units (CMU) shall be modular sizes hollow load bearing block (ASTM C90 Grade N), compressive strength of min. 1500 psi. Mortar shall comply with ASTM C270, Type "S" for work above grade and Type "M" for work below grade. Install ladder type horizontal reinforcing at 16" o.c.

All work shall be in strict accordance with current National Concrete Masonry Association standards.

Concrete Masonry Units (CMU)

Refer to Door Schedule and Door Hardware Sets for hardware selections.

Hardware supplier must be establish firm with min. 3-yrs experience, located within 100 miles of project, factory-authorized dealer and AHC certified. All hardware and mounting shall be in strict compliance with applicable codes, including current edition of Michigan Building Code and Americans With Disabilities Act (ADA). Use templates provided by manufacturer. Hardware sets indicated are to indicate general scope of hardware intent. Submit shop drawings for Design Professional review prior to proceeding with Work. All lock functions to be verified with Owner prior to ordering.

HINGES: Furnish as identified in sets. Acceptable manufacturers: Ives, McKinney, Stanley

LOCKSETS: Furnish Schlage lock sets, RHO Design as identified in hardware sets.

Acceptable equivalents: Sargent, Yale. Provide strikes w/extended lips where required to protect trim from marring. Strike lips shall not project more than 1/8-inch beyond frame trim; 7/8-inch at pairs. Provide wrought box strikes on all locks and latches.

BUMPERS: Furnish Ives WS406/407CVX. Bumpers shall be BHMA L02101, wrought, forged or cast, approx. 2-1/2-inch diameter. Provide convex rubber center with concealed fasteners.

KICKPLATES: Furnish 0.050 stainless steel with countersunk screws. Acceptable equivalents: Any BHMA manufacturer.

WEATHERSTRIP, SWEEPS,

THRESHOLDS & SEALS:Furnish Zero International as identified in hardware sets. Acceptable equivalents: Pemko. Coordinate requirements with door supplier for smoke and intumescent seals.

KEYING: Furnish manufacturer's standard embossed keys of nickel silver. Furnish (6) master keys per master group and (4) change keys per cylinder or keyed alike group. New masterkey to Owner existing keyway.

FINISHES: Generally, dull chrome, US26D (BHMA 626 or 652 depending on product and base material required).

CLOSERS: Furnish LCN 4000 Series. No substitutions. Provide brackets and spacers as required to anchor tightly to frame. Include fifth hole spacers, blade stop spacers and cushion shoe supports.

Furnish and install room identification signage at BF Toilet Room #106 and Staff Bath #114. Interior room identification signage shall comply with ANSI/ICC A117.1 Standards for Accessibility and Americans with Disabilities Act requirements, including tactile signage with letters raised minimum 1/32-inch and Grade II braille, including universal men/women and barrier-free symbols. Signage shall be manufacturer's standard polymer type installed with double-sided adhesive tape, 8"x10" (approximate) in size and include room names "UNISEX TOILET ROOM" and "STAFF TOILET ROOM".

Color as selected by Design Professional from manufacturer's full range of colors. Room identification signage shall be located on wall at latch side of door with centerline of sign at 60-inches above finished floor.

kendra c.

architects, p.c.

THOMPSON

803 Cherry Street Manistee, MI 49660 tel: 231.723.4195 thompson.kendra@sbcglobal.net www.kendrathompson-architects.com

A101

DRAWING TITLE

KCT PROJECT NO.DRAWN

KCT

REVIEWED

KCT

DATE

SCALE

AS NOTED

DRAWING NO.

SEAL

SHEET NO.

NO. REVISIONS / SUBMISSIONS DATE

PROJECT NAME

GENERAL

SPECS

1 SCHEMATIC DESIGN 9/28/2022

SEP. 2022

KT-216015C

2 SD REV. #1 10/3/2022

1 SCHEMATIC DESIGNS 9/30/2022

3 SD REV. #2 2/20/2023

4 OWNER REVIEW SET 4/10/2024

5 OWNER REVIEW SET #2 5/6/2024

6 BID & PLAN REVIEW SET 5/10/2024

ADDITION PROJECT

STATE GAME

MI FILE NO. 751/22233.GAG

MUSKEGON

AREA

7600 MESSINGER RD. -TWIN LAKE, MICHIGAN

OFFICE RENOVATIONS/

C op yr ig ht

Ke nd ra C

. T ho m ps on A rc hi te ct s, P

.C

REMOVE EXIST.

WALL & WINDOW

AS REQ'D. FOR

NEW DOOR OPENING

(V.I.F.)

REMOVE EXIST.

WALLS & COUNTERS

REMOVE EXIST.

BATHROOM & WALLS -

CAP PLUMBING BELOW

FLOOR

REMOVE EXIST.

WALL & DOOR AS

REQ'D. FOR NEW

WORK (V.I.F.)

REMOVE EXIST.

DOOR & FRAME