Addendum 2 22223.pdf

PDF 1 MB Posted

Attached to
751/22233. GAG; Muskegon SGA - Office Renovation & Addition
Solicitation number
RFQ 171 240000000473 3
Issued by
Oakland County, Warren City, Michigan

About this file

This Addendum No. 2, dated June 24, 2024, issued by Kendra C. Thompson Architects for the State of Michigan, provides electrical clarifications and revisions to the Office Renovation & Addition project at the Muskegon State Game Area located at 7600 Messinger Road in Twin Lake, Michigan (State Project No. 751/22233.GAG, KTA No. 216015C). The addendum modifies electrical specifications and drawings across four sheets: E000 (Electrical Specifications & Details), ED100 (Electrical Demolition Floor Plan), E100 (Electrical Floor Plan), and E200 (Electrical Schedules & Details). Key revisions include updates to the electrical riser diagram to include the existing sub-panel, recalculation of service load, incorporation of a new electric utility meter on the floor plan, updates to panel schedules, and clarification that all existing branch circuits not shown for demolition shall be re-fed from Panel #A with field verification required by the contractor. The addendum acknowledges receipt requirement on the bid proposal form, with failure to do so resulting in potential bid disqualification.

The electrical work must comply with the latest enforceable edition of the National Electrical Code (NEC), local and state codes, ordinances, and OSHA requirements. The electrical contractor is responsible for obtaining all permits, paying associated fees, and arranging inspections, with all certificates of final inspection to be provided to the owner upon completion. The contractor must provide all operating and maintenance manuals, certificates of inspection, test reports, spare parts, and as-built record drawings prior to project closeout, with final payment contingent upon punch list completion and receipt of closeout documentation. Branch circuit wiring must be copper rated 75°C minimum size #12 AWG, installed in appropriate conduit, with color coding per 2023 NEC Section 210.5. All panelboards must be rated 120/240V single-phase with plug-in/bolt-on type circuit breakers rated a minimum of 10,000 AIC, and the electrical contractor must verify available fault current with the utility provider prior to equipment ordering. The project design complies with ASHRAE 90.1-2013 automatic lighting shutoff and energy requirements, and all new equipment identification shall be done with engraved two-ply Lamacoid plates with white lettering on a black background, with DYMO or tape markers not permitted.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

803 cherry street manistee, mi 49660 ■ t: 231.723.4195 ■ thompson.kendra@sbcglobal.net ■ www.kendrathompson-architects.com kendra c.

THOMPSON

architects, p.c.

ADDENDUM NO. 2

OFFICE RENOVATION & ADDITION FOR: PAGE: 1 of 5 Muskegon State Game Area DATE: 6/24/2024 7600 Messinger Road STATE No: 751/22233.GAG Twin Lake, MI KTA No: 216015C

The following items are changes, additions, deletions and/or clarifications of the drawings and specifications, and shall be included in the Bid Proposal. All of items will be a part of the Construction Documents. Acknowledge receipt of this Addendum in the appropriate space on the Bid Proposal form. Failure to do so may result in disqualification of the bid.

Item No. 1: Electrical Clarifications and Revisions: Refer to revised Sheets E000, ED100, E100 and E200.

E1 Reference Sheet E000 – Electrical Specifications & Details

1. Update Electrical Riser Diagram to include existing sub-panel.

2. Update Service Load Calculations.

E2 Reference Sheet ED100 – Electrical Demolition Floor Plan

1. Update Electrical Demolition Notes with Keynote #8.

2. Update existing panel tag.

E3 Reference Sheet E100 – Electrical Floor Plan

1. Add new electric utility meter to floor plan.

E4 Reference Sheet E200 – Electrical Schedules & Details

1. Update Panel #A schedule to include circuit breaker for sup-panel feed.

2. Update name of existing panel schedule.

3. Note: All existing branch circuits fed from Extist’g Main Service Panel that are not shown to be demolished shall be re-fed from Panel #A. Contractor to verify circuits in field.

END OF ADDENDUM NO. 2

Attachment:

Drawing Sheets E000, ED100, E100 and E200.

SINGLE PHASE MOTOR, AS SPECIFIED

1Ø ELECTRICAL PANELBOARD/LOAD CENTER

SINGLE PHASE FUSED OR NON-FUSED DISCONNECT

20 AMP DUPLEX RECEPTACLE

REFER TO SPECIFICATIONS FOR DETAILS

MOTOR TOGGLE SWITCH WITH THERMAL OVERLOAD

AND LOCKOUT

SQUARE D #CLASS 2510 FGJ5P (SINGLE POLE)

DEMO HATCH

ELECTRICAL SYMBOL LEGEND

DESCRIPTIONSYMBOL NOTES

S S3

MOUNT @ 44" A.F.F. TO BOTTOM OF BOX, UNLESS OTHERWISE NOTEDSINGLE POLE SWITCH

MOUNT @ 44" A.F.F. TO BOTTOM OF BOX, UNLESS OTHERWISE NOTEDSINGLE POLE 3-WAY SWITCH

2x4 LIGHT FIXTURE, TYPE X

SM

DEVICE ON REAR SIDE OF COVER

OTHER THAN POWER OR

LIGHTING CKT.'S LABEL

COVERS INDICATING SYSTEM

TYPE AND ZONES.

JUNCTION BOXES (EXPOSED

OR CONCEALED ABOVE

FOR J.B.'S CONTAINING

ACCESSIBLE CEILING)

PLATE. USE PERMANENT MARKER PEN,

BRADY MARKING SYSTEM OR OTHER

METHOD APPROVED BY THE ENGINEER

CKT.S

LP4-13,15,17

"P.A. ZONES 4,5,&6"

"DATA CIRCUITS A&B"

"EXIT SIGNS-EMI&2"

"EMERG. CKTS. BPEM-3,4"

"FIRE ALARM-ZONES 2&3"

LABEL EXAMPLES:

LABEL COVERS WITH CKT.'S

METHOD.

SWITCH PLATE

STANDARD TOGGLE

REAR SIDE

LABEL CKT. NO. OF EACH

DUPLEX RECEPTACLE

ELECTRICAL IDENTIFICATION

N-2

FRONT

OF PLATE

FRONT

PLATE

N-5

OF PLATE

REAR SIDE

ELECTRICAL ABBREVIATIONS

1-21 PANEL 1, CIRCUIT 21

A AMPERES

AC ABOVE COUNTER

ACL ABOVE CEILING

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

BC BELOW COUNTER

BCL BELOW CEILING

C CONDUIT

C/B, CB CIRCUIT BREAKER

DF DEAD FRONT GFCI

DWG DRAWING

E EXISTING TO REMAIN

EC, E.C. ELECTRICAL CONTRACTOR

EF EXHAUST FAN

EGC EQUIPMENT GROUNDING

CONDUCTOR

EH ELECTRIC HEATER

EMT ELECTRICAL METALLIC TUBING

ERV ENERGY RECOVERY

VENTILATOR

EWC ELECTRIC WATER COOLER

EWH ELECTRIC WATER HEATER

G GROUND

GEC GROUNDING ELECTRODE

CONDUCTOR

GFI GROUND FAULT CIRCUIT

INTERRUPTER

GTD GENERATOR TRANSFER

DEVICE

HOR HORIZONTAL

KCMIL THOUSAND CIRCULAR MILS

kVA KILOVOLT-AMPERES

KW KILOWATTS

MC, M.C. MECHANICAL CONTRACTOR

MCB MAIN CIRCUIT BREAKER

MDP MAIN DISTRIBUTION PANEL

MLO MAIN LUG ONLY

NTS NOT TO SCALE

P PUMP

PS PRIMARY SWITCH

PT PRIMARY TRANSFORMER

PVC POLYVINYL CHLORIDE

RGS RIGID GALVANIZED STEEL

TR TAMPER RESISTANT

TVSS TRANSIENT VOLTAGE SURGE

SUPPRESSION

UGRD UNDERGROUND

UON UNLESS OTHERWISE NOTED

V VOLT

VIF VERIFY IN THE FIELD

W WIRE

WG WIRE GUARD

WP WEATHER PROOF

xR EXISTING (TO BE) RELOCATED

ELECTRICAL SPECIFICATIONSSECTION

260000

BASIC

ELECTRICAL

REQUIREMENTS

1. PRIOR TO SUBMITTING A PROPOSAL, BIDDER SHALL HAVE VISITED

THE CONSTRUCTION SITE. THEY SHALL BE FAMILIAR WITH THE

EXISTING CONDITIONS UNDER WHICH THEY WILL HAVE TO OPERATE

AND WHICH WILL IN ANY WAY AFFECT THE WORK UNDER THIS

CONTRACT. NO SUBSEQUENT ALLOWANCE WILL BE MADE IN THIS

CONNECTION ON BEHALF OF THE CONTRACTOR FOR ANY ERROR OR

NEGLIGENCE ON THEIR PART.

2. ELECTRICAL WORK SHALL COMPLY WITH THE LATEST ENFORCEABLE

EDITION OF THE N.E.C., LOCAL AND STATE CODES, ORDINANCES,

REGULATIONS, INCLUDING THE OCCUPATIONAL SAFETY AND HEALTH

ACT (OSHA), AND ADA GUIDELINES WITH THE LOCAL CODE

AUTHORITIES HAVING JURISDICTION.

3. ELECTRICAL CONTRACTOR SHALL OBTAIN ALL PERMITS, PAY ALL

FEES, AND ARRANGE FOR ALL INSPECTIONS FOR THEIR WORK. AT

THE COMPLETION OF ELECTRICAL WORK, THE ELECTRICAL

CONTRACTOR SHALL FURNISH THE OWNER WITH ALL CERTIFICATES

OF FINAL INSPECTION AND APPROVALS.

4. THE CONTRACTOR SHALL EMPLOY QUALIFIED AND EXPERIENCED

WORKMEN FOR THIS WORK.

5. ELECTRICAL CONTRACTOR SHALL GUARANTEE ALL WORK INSTALLED

UNDER THEIR CONTRACT TO BE FREE FROM DEFECTIVE

WORKMANSHIP AND MATERIALS FOR A PERIOD OF ONE YEAR AFTER

THE ACCEPTANCE OF THE BUILDING BY THE OWNER. SHOULD

DEFECTS OCCUR WITHIN THIS PERIOD, REPAIR AND/OR REPLACE

DEFECTIVE ITEMS AT NO EXPENSE TO THE OWNER.

6. THE ELECTRICAL CONTRACTOR SHALL PROVIDE ALL OPERATING AND

MAINTENANCE INSTRUCTION MANUALS, CERTIFICATES OF

INSPECTION, TEST REPORTS, SPARE PARTS, AND RECORD

DRAWINGS (AS-BUILTS) TO THE OWNER PRIOR TO CLOSEOUT. FINAL

PAYMENT WILL ONLY BE MADE AFTER THE FINAL PUNCH LIST

COMPLETION AND RECEIPT OF THE ABOVE CLOSEOUT

DOCUMENTATION.

7. ELECTRICAL CONTRACTOR SHALL COORDINATE LOCATIONS OF

THEIR EQUIPMENT AND WORK WITH OTHER BUILDING TRADES TO

AVOID ANY INTERFERENCES BETWEEN THEIR WORK AND THE WORK

OF OTHER BUILDING TRADES. IF ANY DISCREPANCIES OCCUR,

CONSULT WITH THE ENGINEER AND/OR OWNER BEFORE

CONTINUING.

8. THE CONTRACTOR SHALL BE HELD FULLY RESPONSIBLE FOR THE

PROPER RESTORATION OF ALL EXISTING SURFACES REQUIRING

PATCHING, PLASTERING, PAINTING AND/OR REPAIR DUE TO THE

INSTALLATION OF ELECTRICAL WORK UNDER THE TERMS OF THIS

SPECIFICATION. CLOSE ALL OPENINGS, REPAIR ALL SURFACES, ETC.

AS REQUIRED.

9. CUTTING AND/OR PATCHING THAT MAY BE REQUIRED FOR THE

INSTALLATION OF THE ELECTRICAL SYSTEM(S) SHALL BE DONE

AND/OR REPAIRED BY THE ELECTRICAL CONTRACTOR. NO CUTTING

OF THE BUILDING STRUCTURAL SYSTEM SHALL BE DONE WITHOUT

THE WRITTEN CONSENT OF AN ARCHITECT OR STRUCTURAL

ENGINEER.

10. CERTAIN REMODELING OF ELECTRICAL FACILITIES WILL BE

REQUIRED IN THE EXISTING BUILDING. EXISTING CONDUIT RUNS ARE

GENERALLY NOT SHOWN ALTHOUGH AN ATTEMPT HAS BEEN MADE

TO SHOW SOME EXISTING CONDITIONS FOR WHICH THE

INFORMATION HAS BEEN TAKEN FROM FIELD OBSERVATIONS OF

THIS PROJECT. THE DRAWINGS SHOWING LOCATIONS OF EXISTING

EQUIPMENT, OUTLETS, FIXTURES, ETC., IN EXISTING AREAS ARE

APPROXIMATE ONLY (FIELD VERIFY). VERIFY ALL EXISTING LOADS

AND WIRING - NOTIFY THE ARCHITECT/ENGINEER IF EXISTING

CONDITIONS ARE FOUND THAT VIOLATE INSTALLATION OR SAFETY

CODES.

11. EXISTING ELECTRICAL WIRING WHICH WILL NOT BE MADE OBSOLETE

AND WHICH WILL BE DISTURBED DUE TO CONSTRUCTION CHANGES

REQUIRED BY THIS CONTRACT SHALL BE RESTORED TO OPERATING

CONDITION AS REQUIRED AND/OR DIRECTED. WHERE REQUIRED,

SHOWN AND/OR DIRECTED, OUTLETS AND CONDUIT RUNS SHALL BE

RELOCATED. IN SOME CASES IT MAY BE NECESSARY TO EXTEND

CONDUITS AND PULL IN NEW WIRING, INSTALL JUNCTION BOXES AND

SPLICE IN NEW WIRING, OR REPLACE OLD WIRING WITH NEW.

12. OUTLETS FROM WHICH FIXTURES, SWITCHES, RECEPTACLES,

AND/OR OTHER ELECTRICAL DEVICES ARE MOVED AND WHICH ARE

NOT REPLACED OR REUSED SHALL BE REMOVED OR, IF IT IS NOT

POSSIBLE TO REMOVE, HAVE A BLANK COVER PLACED ON THE

OUTLET BOX. WHERE OUTLETS, BOXES, ETC. ARE COMPLETELY

REMOVED, THE CONTRACTOR SHALL CUT OFF AND CAP CONDUITS

AND REMOVE WIRING.

13. WHERE EXISTING CONDUIT IS TO BE ABANDONED, THE CONDUIT

SHALL BE REMOVED IF IT IS EXPOSED, IN A CRAWL SPACE OR IN AN

ACCESSIBLE CEILING. WHERE IT IS IMPOSSIBLE TO REMOVE THE

CONDUIT, IT SHALL BE CUT OFF AND CAPPED OR PLUGGED.

14. THE ELECTRICAL CONTRACTOR SHALL PERIODICALLY REMOVE FROM

THE SITE ALL DEBRIS AND RUBBISH ACCUMULATING AS A RESULT OF

THE ELECTRICAL INSTALLATION. UPON COMPLETION OF THE

PROJECT, THEY SHALL DISPOSE OF ALL DEBRIS AND RUBBISH AND

SHALL LEAVE ALL AREAS CLEAN. THE INTERIORS OF ALL CABINETS,

PULL BOXES, AND EQUIPMENT ENCLOSURES SHALL BE FREE OF ANY

DEBRIS.

15. BRANCH CIRCUITS SHALL BE REUSED WHERE PRACTICAL AND SHALL,

IN ADDITION, BE REMODELED AS REQUIRED.

16. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS AND

SHALL WORK WITH EXISTING SYSTEMS IN AN "AS FOUND"

CONDITION.

17. DRAWINGS ARE DIAGRAMMATIC ONLY AND SHOW OBSERVATIONS

FROM CASUAL FIELD INVESTIGATIONS AND EXISTING DRAWINGS.

FIELD VERIFY ALL EXISTING CONDITIONS, DIMENSIONS AND

MOUNTING LOCATIONS. NOTIFY ENGINEER IF ANY DISCREPANCIES

ARE FOUND THAT AFFECT THE WORK TO BE PERFORMED, PRIOR TO

PROCEEDING.

18. ELECTRICAL JOINTS WILL BE PERMITTED ONLY IN JUNCTION AND

OUTLET BOXES. ALL JOINTS SHALL BE FIRMLY BONDED TOGETHER

AND TAPED OR SHALL BE MADE WITH MECHANICAL CONNECTORS.

19. ELECTRICAL MATERIALS SHALL BE NEW, AND BEAR THE "UL" LABEL

OR LISTING.

20. WITHIN THIRTY (30) DAYS AFTER THE ELECTRICAL CONTRACTOR HAS

BEEN NOTIFIED TO PROCEED WITH THE WORK, HE SHALL SUBMIT TO

THE OWNER EIGHT (8) PRINTED AND BOUND COPIES -OR- ONE (1)

ELECTRONIC COPY IN PDF FORMAT OF EACH OF THE FOLLOWING

DRAWINGS AND DATA SHEETS FOR REVIEW. ALL EQUIPMENT FOR

WHICH SHOP DRAWINGS ARE BEING SUBMITTED SHALL NOT BE

ORDERED UNTIL APPROVED DRAWINGS HAVE BEEN RETURNED.

SUCH SUBMITTALS SHALL INCLUDE:

* WIRING DEVICES, POWER POLES, ETC.

* SAFETY SWITCHES, MOTOR TOGGLE SWITCHES, STARTER

DISCONNECTS, ETC.

* PANELBOARDS, CIRCUIT BREAKERS, FUSES, ETC.

* LIGHT FIXTURES & LIGHTING CONTROLS

21. BRANCH CIRCUIT WIRE SHALL BE COPPER, RATED 75°C, MINIMUM

SIZE #12 AWG, AND BE:

(A) TYPE "THHN", "THWN OR "THWN-2" AND INSTALLED IN CONDUIT

(EMT, FOR INDOOR USE; SCHEDULE 40 PVC OR SCHEDULE 80

PVC, WHERE SUBJECT TO DAMAGE, FOR INDOOR WET

LOCATIONS, AND SCHEDULE 40 PVC OR RMC FOR OUTDOOR

USE, MINIMUM SIZE 1/2", OR UNLESS OTHERWISE NOTED OR

REQUIRED BY CODE.

(B) INTERIOR MOTOR CONNECTIONS SHALL BE TYPE "MC" OR "AC"

CABLE OR LIQUID TITE FLEXIBLE CONDUIT (BOTH WITH A 6FT.

MAXIMUM LENGTH).

22. FEEDERS AND SECONDARY SERVICE CONDUCTORS SHALL BE

STRANDED COPPER WITH 600 VOLT INSULATION, RATED 90°C, TYPE

"THHN", "THWN" OR "THWN-2" AND BE INSTALLED IN EMT OR PVC

CONDUIT, MINIMUM SIZE 1/2" UNLESS OTHERWISE NOTED OR

REQUIRED BY CODE.

23. ALL WIRE AND CABLE SHALL BE NEW AND SHALL BE DELIVERED TO

PROJECT IN UNBROKEN AND UNDAMAGED CARTONS AND/OR REELS.

24. ALL NEW BRANCH WIRING SHALL BE COLOR CODED BY THE

FOLLOWING VOLTAGE SYSTEMS AND LABELED AT THEIR SOURCE

PER 2023 NEC SECTION #210.5:

120/240-1Ø-3W SYSTEM:

ØA - BLACK

ØB - RED

NEUTRAL - WHITE

E.G.C. - GREEN

25. MOTOR CONTROLLERS SHALL BE RATED AS FOLLOWS.

A. 120 VOLT, LESS THAN 1 HP:

PROVIDE MOTOR TOGGLE SWITCH WITH THERMAL OVERLOADS AND

PILOT LIGHT, SURFACE OR FLUSH MOUNTED AS NOTED BY SQUARE

D CLASS 2510 OR SIMILAR, BASED ON SQ-D #FGJ5P (SURFACE

MOUNT) OR #FF2P FL2 (FLUSH MOUNT).

B. 208V, 1PH; 208V, 3PH; 480V. 1PH; AND 480V, 3PH; 1/2 HP OR LARGER:

PROVIDE NEMA RATED COMBINATION MAGNETIC MOTOR STARTER

AND DISCONNECT IN APPROPRIATE ENCLOSURE WITH H.O.A.

SELECTOR SWITCH, RED PILOT LIGHT, 120 VOLT CONTROL

TRANSFORMER, 1-N.O. & 1- N.C. AUX. COIL COMBINATION MOTOR

STARTER DISCONNECT SHALL BE BASED ON SQ-D CLASS 8539 WITH

BREAKER SIZED FOR RESPECTIVE MOTOR LOAD OR TWO SPEED

STARTERS AS SHOWN ON PLANS. MOUNT WITHIN SIGHT AND WITHIN

50' OF MOTOR. SIZE HEATERS PER NEC AND MANUFACTURES'S

RECOMMENDATIONS.

26. PANELBOARDS SHALL BE RATED 120/240V, 1 PHASE, 3W, AS NOTED

WITH PLUG-IN/BOLT-ON TYPE BRANCH CIRCUIT BREAKERS RATED A

MINIMUM OF 10,000 A.I.C. E.C. TO VERIFY AVAILABLE FAULT CURRENT

WITH THE UTILITY PROVIDER PRIOR TO ORDERING EQUIPMENT.

PANELBOARDS SHALL BE TO EATON OR SQ. D NQ.

27. RECEPTACLES SHALL BE COMMERCIAL SPECIFICATION GRADE,

RATED 125 VOLT, 20 AMP, GROUNDED TYPE (NEMA 5-20R). EQUAL TO

LEVITON, HUBBELL, LEGRAND, OR P & S.

28. SWITCHES SHALL BE COMMERCIAL SPECIFICATION GRADE, RATED

20A, 120/277 VOLT, SINGLE, DOUBLE-POLE, THREE-WAY, ETC. AS

INDICATED. EQUAL TO LEVITON, HUBBELL, LEGRAND, OR P & S.

29. INTEGRAL EMERGENCY BATTERIES SHALL PROVIDE A MINIMUM OF 90

MINUTES OF RUN-TIME FOR FIXTURES AS SHOWN.

30. ALL LIGHT FIXTURES HAVE BEEN SELECTED BY THE OWNER, THE

ARCHITECT, AND THE ENGINEER FOR THE BASIS OF DESIGN AND

APPEARANCE.

31. PROJECT HAS BEEN DESIGNED TO COMPLY WITH AUTOMATIC

LIGHTING SHUTOFF AND ENERGY REQUIREMENTS OF ASHRAE

90.1-2013. AUTOMATIC LIGHTING CONTROLS SHALL BE PROVIDED AS

SHOWN PER THE FLOOR PLANS AND SPECIFICATIONS.

32. FUSES SHALL BE "UL" LISTED, DUAL-ELEMENT AS MANUFACTURED BY

BUSSMAN CO., OR APPROVED EQUAL (200,000 AIC).

33. FIRE CAULKING REQUIRED WHERE ANY PENETRATIONS ARE MADE

THROUGH FIRE RATED WALLS, BY. E.C

34. PROVIDE AN UPDATED, AND ACCURATE PANEL SCHEDULE FOR THE

EXISTING ELECTRICAL PANEL(S) THAT ARE AFFECTED BY THE WORK

IN THIS PROJECT. DOCUMENT ALL CHANGES ON FINAL AS-BUILT

DRAWINGS AS REQUIRED. VERIFY ALL EXISTING LOADS AND WIRING

- NOTIFY THE ARCHITECT/ENGINEER IF EXISTING CONDITIONS ARE

FOUND THAT VIOLATE INSTALLATION OR SAFETY CODES.

35. ALL NEW EQUIPMENT (PANELS, DISCONNECTS, COMBINATION

STARTER/DISCONNECTS, VARIABLE FREQUENCY DRIVES (VFD), ETC.)

IDENTIFICATION SHALL BE DONE WITH ENGRAVED 2-PLY LAMACOID

PLATES WITH 14" WHITE LETTERING ON A BLACK BACKGROUND.

"DYMO" OR TAPE MARKERS ARE NOT ALLOWED.

36. ALL CONDUIT AND JUNCTION BOXES SHALL BE APPROPRIATELY

MARKED WITH THE CIRCUITS THEY CONTAIN AND A DESIGNATION

THAT IT IS CONTAINING ELECTRICAL CONDUCTORS.

2x2 LIGHT FIXTURE, TYPE X

X EXIT SIGN, TYPE X

SEE LIGHTING FIXTURE SCHEDULE FOR TYPES

SEE LIGHTING FIXTURE SCHEDULE FOR TYPES

TV TELEVISION OUTLET

DEEP PLASTER RING ON THE CEILING, UON. ONE (1) FOR A DUPLEX

RECEPTACLE AND ONE (1) WITH A 1" CONDUIT STUBBED ABOVE THE

E.C. TO PROVIDE AND INSTALL TWO (2) 4" SQ. x 2-1/8" DEEP BOX WITH 2"

NEAREST ACCESSIBLE (LAY-IN) CEILING.

E.C. TO PROVIDE AND INSTALL 4" SQ. x 2-1/8" DEEP BOX WITH SINGLE GANG

PLASTER RING AT 18" AFF WITH ONE (1) 1" CONDUIT STUBBED ABOVE THE

LOW VOLTAGE OUTLET

NEAREST ACCESSIBLE (LAY-IN) CEILING, UNLESS OTHERWISE NOTED.

OCCUPANCY SENSOR RELAY SWITCHPACK

(GREENGATE #SP20-MV)

CONNECT TO OCC. SENSORS PER MANUFACTURERS INSTRUCTIONS

SD MOUNT @ 44" A.F.F. TO BOTTOM OF BOX, UNLESS OTHERWISE NOTED

ST MOUNT @ 44" A.F.F. TO BOTTOM OF BOX, UNLESS OTHERWISE NOTED

X

CONNECT TO POWER PACK PER MANUFACTURERS INSTRUCTIONS

ELECTRIC UTILITY METER

ELECTRICAL RISER DIAGRAM

NEW UTILITY METER.

COORDINATE WITH

CONSUMERS

ENERGY

EXT'G

PANEL #A

200A MCB

X

20 AMP DOUBLE DUPLEX (QUAD) RECEPTACLE

W P MOUNT @ 24" A.F.F. TO BOTTOM OF BOX, UNLESS OTHERWISE NOTEDWR GFCI DUPLEX OUTLET WITH LOCKABLE WEATHER

PROOF IN-USE COVER

X

SEE LIGHTING FIXTURE SCHEDULE FOR TYPES

WALL PACK LIGHT FIXTURE, TYPE X SEE LIGHTING FIXTURE SCHEDULE FOR TYPES

CEILING MOUNTED OCCUPANCY SENSOR

(GREENGATE #OAC-P-1500-R)

24HR PROGRAMMABLE TIMER SWITCH

(GREENGATE #TSW-MV-W)

0-10V DIMMER SWITCH

(LEGRAND #WS4FBL3P)

MOUNT @ 16" A.F.F. TO BOTTOM OF BOX, UNLESS OTHERWISE NOTED

MOUNT @ 16" A.F.F. TO BOTTOM OF BOX, UNLESS OTHERWISE NOTED

NEW INCOMING

SERVICE CONDUCTORS

BY CONSUMERS ENERGY

1#1/0 (CU) G.E.C.2 - 3/4" x 10' 0"

COPPER CLAD

GROUND RODS

1#6 (CU) G.E.C.

1#1/0 (CU) G.E.C.

BOND TO METALLIC WATER

PIPE (IF AVAILABLE).

BUILDING STEEL

CONNECTIONS

(IF AVAILABLE)

BUILDING CONCRETE FOOTING

IN FOOTING CONCRETE

20'-0" MIN. POURED

#4 BARE (CU)

1# 1/

(C

U ) B

AR

E

G .E

.C

G.E.C. NOTE:

EXOTHERMIC WELD OR

UL-LISTED IRREVERSIBLE

CLAMPS ON ALL G.E.C.

CONNECTIONS.

SVD

NEW

PANEL #B

200A MCB

WIREWAY WITH TERMINAL

BLOCKS AS REQ'D.

FLUSH-FLOOR BOX FB

BE LABELED AND HAVE PULL STRINGS INSTALLED IN THEM.

WIREMOLD #RFB4-CI-1-(2)RFB-GFI-(1)DTB-2-4TKO-FPBTCxx WITH ONE (1)

DUPLEX RECEPTACLE, AND ONE (1) 1"C STUBBED TO NEAREST

ACCESSIBLE CEILING, EITHER ABOVE OR BELOW. xx DENOTES STANDARD

FINISH AS SELECTED BY THE ARCHITECT. ALL CONDUIT STUBS ARE TO

COORDINATE REQUIREMENTS WITH THE SHOP DRAWINGS

MOUNT @ 44" A.F.F. TO BOTTOM OF BOX, UNLESS OTHERWISE NOTEDPASSIVE INFRARED VACANCY SENSOR 0-10V DIMMER

(GREENGATE #OSW-P-010-X) PROGRAM AS VACANCY SWITCH (MANUAL ON/AUTO OFF)

3#3/0 2"C

3#3/0 2"C

(2) // RUNS OF:

3#3/0, 2"C

1# 1/

(C

U) B

AR

E

G .E

.C

PC MOUNT IN EXTERIOR SOFFITPHOTOCELL (INTERMATIC #K4321C)

E X

X

EMERGENCY ONLY LIGHT FIXTURE, TYPE X SEE LIGHTING FIXTURE SCHEDULE FOR TYPES

STRIP LIGHT FIXTURE, TYPE X SEE LIGHTING FIXTURE SCHEDULE FOR TYPES

3#8, 1#10 E.G.C 3/4"C

E000

DRAWING TITLE

KCT PROJECT NO.DRAWN

BSR

REVIEWED

JAV

DATE

SCALE

AS NOTED

DRAWING NO.

SEAL

SHEET NO.

NO. REVISIONS / SUBMISSIONS DATE

PROJECT NAME

ELECTRICAL

SPECIFICATIONS &

KT-216015C

1 BID & PLAN REVIEW SET 5/10/2024

ADDITION PROJECT

STATE GAME

MI FILE NO. 751/22233.GAG

MUSKEGON

AREA

7600 MESSINGER RD. -TWIN LAKE, MICHIGAN

OFFICE RENOVATIONS/

C op yr ig ht

Ke nd ra C

. T ho m ps on A rc hi te ct s, P

.C kendra c.

architects, p.c.

THOMPSON

803 Cherry Street Manistee, MI 49660 tel: 231.723.4195 thompson.kendra@sbcglobal.net www.kendrathompson-architects.com

DETAILS

APRIL 2024

2 ADDENDUM #2 6/24/2024

AutoCAD SHX Text

SP

AutoCAD SHX Text M

AutoCAD SHX Text

%%UEXT'G

AutoCAD SHX Text

%%USERVICE

AutoCAD SHX Text

OS

AutoCAD SHX Text M

AutoCAD SHX Text

EXT'G ELECT. METER

AutoCAD SHX Text

%%UPANEL

AutoCAD SHX Text

%%UEXT'G

AutoCAD SHX Text

%%USUB-

AutoCAD SHX Text

%%UPANEL

AutoCAD SHX Text

%%UMAIN

S

S 3 S 3

S3S3

S 3

S3S

SS

S

S

SS

S

TV

PC

SM

xR xR

2 3

1 2

1 2

1 2 3

ELECTRICAL DEMOLITION NOTES

FOR THE ELECTRICAL EQUIPMENT TO BE DISCONNECTED

AND REMOVED, THE OWNER SHALL BE GIVEN THE

OPPORTUNITY OF HAVING ANY OF IT TURNED OVER TO THEM.

DISCONNECT AND REMOVE ELECTRICAL DEVICE(S)

WHICH WILL INTERFERE WITH THE DEMOLITION AND

REMOVAL OF WALLS, FLOORING, AND/OR CEILING AS

DESCRIBED IN THE ARCHITECTURAL DEMOLITION

PLANS. REMOVE EXISTING CIRCUITRY (WIRING) AND

CONDUIT BACK TO PANEL AND DISCARD.

DISCONNECT AND REMOVE ALL EXISTING LIGHTS AND

CONTROLS IN THIS AREA, U.O.N. REMOVE EXISTING

CIRCUITRY (WIRING) AND CONDUIT BACK TO PANEL AND

DISCARD, UNLESS IT IS SHOWN TO BE REUSED. INSTALL

NEW LIGHTS AND CONTROLS AS SHOWN ON NEW

PROPOSED FLOOR PLANS. REUSE EXISTING CIRCUIT, IF

SHOWN, OR CIRCUIT TO PANEL WITH NEW CIRCUIT AS

SHOWN ON NEW PROPOSED FLOOR PLANS. PROVIDE

BLANK COVER PLATES FOR EMPTY GANG BOXES.

DISCONNECT AND REMOVE ALL EXISTING RECEPTACLES

AND POWER DEVICES IN THIS AREA, U.O.N. REMOVE

EXISTING CIRCUITRY (WIRING) AND CONDUIT BACK TO

PANEL AND DISCARD, UNLESS IT CAN BE REUSED.

INSTALL NEW RECEPTACLES AND POWER DEVICES AS

SHOWN ON NEW PROPOSED FLOOR PLANS. PROVIDE

BLANK COVER PLATES FOR EMPTY GANG BOXES.

DISCONNECT, REMOVE ALL EXISTING DATA,

TELEPHONE/PAGING, TELEVISION, CLOCK, AND ACCESS

CONTROLS WIRING AND EQUIPMENT, U.O.N. PROVIDE

BLANK COVER PLATES FOR EMPTY GANG BOXES.

PROVIDE NEW BOXES AND CONDUIT AS SHOWN ON NEW

PROPOSED FLOOR PLANS. NEW WIRING AND

TERMINATIONS BY OWNER'S CONTRACTOR.

DISCONNECT AND REMOVE EXISTING ELECTRICAL

CONNECTIONS AND DISCONNECTS TO EXISTING

MECHANICAL AND/OR PLUMBING EQUIPMENT THAT IS

TO BE REMOVED, U.O.N. REMOVE EXISTING CIRCUITRY

(WIRING) AND CONDUIT BACK TO PANEL AND DISCARD.

PROVIDE BLANK COVER PLATES FOR EMPTY GANG

BOXES. COORDINATE ALL DISCONNECTIONS WITH THE

MECHANICAL CONTRACTOR.

DISCONNECT, REMOVE AND RELOCATE ALL SPEAKERS

AND FIRE ALARM SYSTEMS DEVICES, AS SHOWN.

EXTEND/RECONFIGURE EXISITNG CIRCUITRY (WIRING) &

CONDUITS AS REQUIRED AND RECONNECT TO

RELOCATED DEVICES. PROVIDE BLANK COVER PLATE

FOR EMPTY GANG BOXES.

DISCONNECT AND REMOVE EXISTING METER SOCKET,

AND INSTALL NEW METER SOCKET AS SHOWN ON THE

PROPOSED NEW FLOOR PLANS.

DISCONNECT, REMOVE AND RELOCATE THE EXISTING

TELEPHONE UTILITY BOX, AS SHOWN. COORDINATE

WITH THE EXISTING UTILITY PROVIDER ON RELOCATING

INCOMING SERVICE. RECONFIGURE EXISTING CABLING

AND PROVIDE NEW RACEWAYS AS REQUIRED.

ED100

DRAWING TITLE

KCT PROJECT NO.DRAWN

BSR

REVIEWED

JAV

DATE

SCALE

AS NOTED

DRAWING NO.

SEAL

SHEET NO.

NO. REVISIONS / SUBMISSIONS DATE

PROJECT NAME

KT-216015C

1 BID & PLAN REVIEW SET 5/10/2024

ADDITION PROJECT

STATE GAME

MI FILE NO. 751/22233.GAG

MUSKEGON

AREA

7600 MESSINGER RD. -TWIN LAKE, MICHIGAN

OFFICE RENOVATIONS/

C op yr ig ht

Ke nd ra C

. T ho m ps on A rc hi te ct s, P

.C

SCALE: 1/4" = 1'-0"

ELECTRICAL DEMOLITION FLOOR PLAN

N kendra c.

architects, p.c.

THOMPSON

803 Cherry Street Manistee, MI 49660 tel: 231.723.4195 thompson.kendra@sbcglobal.net www.kendrathompson-architects.com

ELECTRICAL

DEMOLITION

FLOOR PLAN

APRIL 2024

2 ADDENDUM #2 6/24/2024

AutoCAD SHX Text 0S

AutoCAD SHX Text

REF.

AutoCAD SHX Text

AC

AutoCAD SHX Text

AC

AutoCAD SHX Text M/W

AutoCAD SHX Text xFURN

AutoCAD SHX Text xEWH

AutoCAD SHX Text

ELECT

AutoCAD SHX Text

METER

AutoCAD SHX Text

EXT'G

AutoCAD SHX Text

RUN DOWN

AutoCAD SHX Text

WALL

AutoCAD SHX Text

CAT6

AutoCAD SHX Text

MAIN

AutoCAD SHX Text

SERVICE

AutoCAD SHX Text

EXT'G

AutoCAD SHX Text

HEAT TAPE

AutoCAD SHX Text

ON ROOF

AutoCAD SHX Text

OUTSIDE

AutoCAD SHX Text S

AutoCAD SHX Text

TV BOX

AutoCAD SHX Text

CABLE

AutoCAD SHX Text S

AutoCAD SHX Text

U/G TO EXTERIOR BUILDING FOR SECURITY SYSTEM

AutoCAD SHX Text

EXT'G SUB-PANEL

AutoCAD SHX Text

EXT'G METER SOCKET

AutoCAD SHX Text

EXT'G PANEL #A

AutoCAD SHX Text

PHONE UTILITY BOX

PANEL

EXISTING

EXISTING

ENTRY AREA

COVERED

STAFF

AREA

OFFICE #3

OFFICE #1

OFFICE #2

STORAGE /

FUTURE OFFICE

STAFF

ENTRY

WORK

AREA

BF STAFF

BATH

SUPPLIES /

EQUIPMENT

STAFF

LOCKERS

COMMONS

ROOM

MANAGED HUNT

AREA

SERVICE

AREA

BF

TLT. RM.

UTILITY

AC

AC

FBFB

FB

B

A-1

A-1

A-1

ST

A-5

A-5

A-5

A-5

A-13

A-15

A-15

A-13

A-13

A-11 A-11

A-9

A-9

A-9

A-9

A-9

TV

C

D

D

D

A2

A2 A2

A2 A2

A1

A1

A1

A1 A1 A1

A1A1

A1 A1

C

CCCC

D

A2 A2

A2 A2

A2

A2

A2

A2

A2

A2

A2

A2

A2

C

F

A-1

A-3

A-3

A-3

A-3

A-3

AC AC

S3

S3

AC

EF-1

EF-2

SS

A-7

A-7

A-7

A-7

A-7

A-17

AC

A-17

A-17

A-19

A-19

A-19

A-19

A-21

AC

A-23

AC

A-29

A-27

A-27

A-27

A-27

A-27

A-27

A-27

A-27

A-29

SS

A2

S V D

S V D

S V D

S V D

S S

SM O/H DOOR

A-25

S

EF-2

HP-2

AH-1

AH-2

EWH-1

B-10,12

EXREX

EX

EXR

EXR

EEM

E EM

E EM

MOUNT ABOVE

VANITY MIRROR

A-19

NOTE:

COORDINATE LIGHT FIXTURE

LOCATIONS IN UTILITY #107

WITH DUCTWORK.

A-17

AC

NOTE:

SERVICE AREA WALL DOES

NOT EXTEND TO CEILING.

SEE ARCHITECTURAL

DRAWINGS FOR DETAILS.

EXR

E EMR

E

EMR

E EMR

E

EMRxR

HP-1

B-2,4 B-6,8

B-14,16

B-6,8

36" AFF

IT RACK

A-12

36" AFF

A-12

36" AFF

A-10

A-12

36" AFF

NOTE:

COORDINATE POWER AND

CONTROL REQUIREMENTS

WITH THE OVERHEAD

DOOR SHOP DRAWINGS.

A-15

72" AFF

W P

W P

WP

A-14

A-14

A-14

A-12

36" AFF

S D

S3

NEW

PANEL #B

PC

A-27A-27

A-27

S

A-27 A-27

A-29

A-29

A-29

A-29

A-27

SD

WPWP

WP

xR

CONNECT TO LOCAL

LIGHTING CIRCUIT.

VIF.

RECONNECT TO

EXISTING LIGHTING

CIRCUIT.

VIF.

A-29

A-29 A-29

A-29

NOTE:

PROVIDE LABEL ON FACE PLATE:

EXTERIOR CANOPY LIGHTS

OVERRIDE SWITCH

NEW ELEC.

UTILITY

METER

GENERAL ELECTRICAL NOTES:

9. ANY NEW CONDUIT PENETRATIONS THROUGH WALLS SHALL BE APPROPRIATELY

FIRE-STOPPED, SMOKE-STOPPED OR CAULKED WHEN PENETRATION SIZE

EXCEEDS CONDUIT SIZE, AS REQUIRED.

10.E.C. SHALL COORDINATE PROPER PLACEMENT AND ORIENTATION OF OCCUPANCY

SENSORS MOUNTED IN THE CEILING WITH THE MANUFACTURERS REPRESENTATIVE.

11.

COORDINATE CONDUIT SLEEVES WITHIN THE WALLS FOR DATA, TELEPHONE/

PAGING, TELEVISION, SECURITY, AND CLOCK SYSTEMS WITH THE OWNER.

12.

15.CIRCUITS SHOWN ON PLANS WITH AN * AFTER IT, INDICATE THE CIRCUIT

CIRCUIT AND USE IT IF DIFFERENT THAN CIRCUIT INDICATED.

NUMBER FROM OLD DRAWINGS OR A TAKEOFF. E.C. IS TO VERIFY ACTUAL

OVERLOAD EXISTING CIRCUITS, PANELS OR TOTAL SERVICE.

E.C. SHALL FIELD VERIFY THAT ALL ADDITIONS AND CHANGES SHALL NOT

PROVIDE KEVLAR PULL STRINGS IN ALL SPARE CONDUITS.7.

8.

LOW VOLTAGE CONTRACTORS.

E.C. SHALL COORDINATE FEEDER ROUTING WITH PLUMBING, MECHANICAL AND

DEVICE (i.e., HAVING A DIRECT (HOT) CONNECTION TO THE BATTERY).

CONNECT ALL EXIT SIGNS AHEAD OF THE LOCAL AREA LIGHTING'S CONTROL

CLOCK OUTLETS, ETC. WITH ARCHITECT/ENGINEER. FAILURE TO DO SO

E.C. SHALL VERIFY ALL ROUGH-IN ELEVATIONS, LOCATIONS AND/OR

HEIGHTS OF ALL LIGHT FIXTURES, RECEPTACLE OUTLETS, T.V., COMPUTER,

WILL REQUIRE E.C. TO RELOCATE RESPECTIVE ITEMS AT THE E.C.'S EXPENSE.

4.

3.

2.

CAUTION !!!!!!!!1.

5. COORDINATE LOCATIONS AND MOUNTING HEIGHTS OF LIGHT FIXTURES WITH

THE INTERIOR ELEVATIONS AND REFLECTED CEILING PLANS.

ALL PENDANT MOUNTED FIXTURES SHALL BE SECURELY HUNG FROM6.

BUILDING STRUCTURE.

FEEDS TO NEW POWER, LIGHTING, AND LOW VOLTAGE DEVICES SHALL BE

ATTEMPTED IN EVERY WAY TO BE INSTALLED FLUSH-MOUNT (RECESSED BEHIND

COMMUNICATION OUTLET LOCATIONS SHALL BE COORDINATED WITH OWNER

AND OWNER FURNITURE PLAN.

THERE SHALL BE NO EXPOSED CONDUITS, EXCEPT IN ELECTRICAL ROOMS.

THE WALL/CEILING SURFACE).

NORMAL POWER, BY HAVING A DIRECT (HOT) CONNECTION TO THE

TO AN INTEGRAL EMERGENCY BATTERY AND SHALL OPERATE AT A LOSS OF

THE LIGHTS THAT ARE SHADED REPRESENT LIGHTS THAT HAVE A CONNECTION

EMERGENCY BATTERY.

E100

DRAWING TITLE

KCT PROJECT NO.DRAWN

BSR

REVIEWED

JAV

DATE

SCALE

AS NOTED

DRAWING NO.

SEAL

SHEET NO.

NO. REVISIONS / SUBMISSIONS DATE

PROJECT NAME

KT-216015C

1 BID & PLAN REVIEW SET 5/10/2024

ADDITION PROJECT

STATE GAME

MI FILE NO. 751/22233.GAG

MUSKEGON

AREA

7600 MESSINGER RD. -TWIN LAKE, MICHIGAN

OFFICE RENOVATIONS/

C op yr ig ht

Ke nd ra C

. T ho m ps on A rc hi te ct s, P

.C

SCALE: 1/4" = 1'-0"

ELECTRICAL FLOOR PLAN

N kendra c.

architects, p.c.

THOMPSON

803 Cherry Street Manistee, MI 49660 tel: 231.723.4195 thompson.kendra@sbcglobal.net www.kendrathompson-architects.com

ELECTRICAL

FLOOR PLAN

APRIL 2024

2 ADDENDUM #2 6/24/2024

AutoCAD SHX Text

OS

AutoCAD SHX Text

OS

AutoCAD SHX Text

OS

AutoCAD SHX Text

SP

AutoCAD SHX Text

EXT'G PANEL #A

AutoCAD SHX Text

OS

AutoCAD SHX Text

SP

AutoCAD SHX Text

OS

AutoCAD SHX Text

OS

AutoCAD SHX Text

PHONE UTILITY BOX

EXT'G SUB-PANEL

E200

DRAWING TITLE

KCT PROJECT NO.DRAWN

BSR

REVIEWED

JAV

DATE

SCALE

AS NOTED

DRAWING NO.

SEAL

SHEET NO.

NO. REVISIONS / SUBMISSIONS DATE

PROJECT NAME

ELECTRICAL

SCHEDULES &

KT-216015C

1 BID & PLAN REVIEW SET 5/10/2024

ADDITION PROJECT

STATE GAME

MI FILE NO. 751/22233.GAG

MUSKEGON

AREA

7600 MESSINGER RD. -TWIN LAKE, MICHIGAN

OFFICE RENOVATIONS/

C op yr ig ht

Ke nd ra C

. T ho m ps on A rc hi te ct s, P

.C kendra c.

architects, p.c.

THOMPSON

803 Cherry Street Manistee, MI 49660 tel: 231.723.4195 thompson.kendra@sbcglobal.net www.kendrathompson-architects.com

DETAILS

APRIL 2024

LIGHT FIXTURE SCHEDULE PANEL SCHEDULES

EXISTING PANEL SCHEDULES

2 ADDENDUM #2 6/24/2024

Sheets and Views
Ebase-MGSA-E000
Ebase-MGSA-ED100
Ebase-MGSA-E100
Ebase-MGSA-E200