Bid Docs_MEP DRAWINGS.pdf

PDF 9 MB Posted

Attached to
Z2DA--FCA - Renovate Space for Domiciliary Providers, Building 2 PA:657-19-127JB
Solicitation number
36C25522R0033
Issued by

About this file

This solicitation is for renovation services for Building 2 at the Jefferson Barracks Division VA Medical Center in St. Louis, Missouri. The contractor will renovate areas on the second floor north and all of the first floor, phasing work to complete the second floor followed by the first floor. The project costs range from $2 million to $5 million, with an estimated 457-day completion period. The NAICS code is 236220 with a small business size standard of $39.5 million. The solicitation will be posted to SAM on December 20, 2021. The successful offeror must perform at least 15% of construction labor. The award will use best value tradeoff and discussions are not planned but reserved if needed. The opportunity is a total SDVOSB set-aside following 38 USC 8127(d) and PL 109-461. Firms must register in SAM and VetBiz. A site visit will be scheduled and documented in the solicitation. Responses are due as specified therein.

View the file

Other files

File Type Posted
657-19-127JB_spec section 27 51 16.pdf PDF
36C25522R0033 0007.docx DOCX document
657-19-127JB_Electrical plan changes.pdf PDF
657-19-127JB-2022.03.17_ADD-2.pdf PDF
36C25522R0033 0006.docx DOCX document
1801901 Asbestos Mold Survey - Jefferson Building 2 (final).pdf PDF
JB-2-Report.pdf PDF
36C25522R0033 0005.docx DOCX document
36C25522R0033 0004.docx DOCX document
36C25522R0033 0003.docx DOCX document
UpdatedSpecs_Vol1_revised 20211215.pdf PDF
UpdatedSpecs_Vol2.pdf PDF
36C25522R0033.docx DOCX document
PastPerformanceQuestionnaire36C25522R0033Project657-19-127JB.docx DOCX document
Bid Docs_Arch.pdf PDF
Show all 15

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SPRINKLER HEADS TO BE INSTALLED IN

CENTER OF 2x2 CEILING TILES.

12"12"

SCALE: NONE

2x2 CEILING TILE DETAIL

12"

12"

RETURN BEND DETAIL

FIRE MAIN

SEMI RECESSED SPRINKLER

CEILING

SPRINKLER PIPE

SCALE: NONE

FIRE PROTECTION SYSTEM RISER

TO SPRINKLER HEADS IN

NEW ADDITION AND FUTURE

ADDITION.

TYPICAL MECHANICAL JOINT

COUPLING. REFER TO

SPECIFICATIONS.

ALARM CHECK VALVE WITH

PRESSURE GAUGES AND

SYSTEM MAIN DRAIN. REFER

TO SPECIFICATIONS.

SYSTEM DRAIN THRU

EXTERIOR WALL. REFER

TO FIRE PROTECTION

PLANS.

BUTTERFLY VALVE

WITH TAMPER SWITCH.

REFER TO SITE

UTILITIES PLAN FOR

CONTINUATION.

PROVIDE SPARE HEAD

CABINET WITH HEADS.

F P

F P

F P

TS

F S

ABBREVIATIONSGENERAL NOTES - FIRE PROTECTION

A. ALL AREAS SHALL BE PROTECTED BY A 100% WET PIPE FIRE SUPPRESSION

SYSTEM INSTALLED IN STRICT ACCORDANCE WITH NFPA-13, THE STATE

BUILDING CODES AND THE PROJECT SPECIFICATIONS.

B. ALL AREAS ARE PRESENTLY PROTECTED BY A 100% WET PIPE FIRE

SUPPRESSION SYSTEM. CONTRACTOR SHALL MODIFY THE SYSTEM AS

REQUIRED TO MAINTAIN 100% PROTECTION, IN ACCORDANCE WITH NFPA

13, STATE BUILDING CODE AND SPECIFICATIONS.

C. THE SUCCESSFUL FIRE PROTECTION CONTRACTOR SHALL OBTAIN AND

UTILIZE THE ARCHITECTURAL REFLECTED CEILING PLAN FOR LAYING OUT

THE SPRINKLER HEADS. THE REFLECTED CEILING PLANS SHOWN ARE TO

COORDINATE CEILING TYPES AND LOCATIONS. REFER TO THE MECHANICAL

AND ELECTRICAL DRAWINGS FOR CEILING DEVICE LOCATIONS. REFER TO

THE SPECIFICATIONS FOR COORDINATION DRAWING REQUIREMENTS.

D. INSTALL HEADS IN CENTER OF 2'X2' TILES. INSTALL HEADS ON 1/4 POINTS

OF THE 4' DIMENSION AND CENTER OF THE 2' DIMENSION IN 2'X4' TILES.

DO NOT MOUNT HEADS IN CENTER OF 2'X4' TILE IF IT IS SCORED TO LOOK

LIKE TWO 2'X2' TILES.

E. ALL SPRINKLER HEADS SHALL BE "SEMI-RECESSED", QUICK RESPONSE

SPRINKLER HEADS (UNLESS OTHERWISE NOTED ON THE PLANS.) HEADS

SHALL BE FED FROM A RETURN BEND ARRANGEMENT.

F. UTILIZE UPRIGHT AND/OR WALL-MOUNTED TYPE SPRINKLER HEADS IN

AREAS WITHOUT CEILINGS.

G. THE FIRE PROTECTION CONTRACTOR SHALL PERFORM HIS OWN FLOW TEST

PRIOR TO SUBMITTING SHOP DRAWINGS.

H. REFER TO A COMPLETE SET OF DOCUMENTS (ARCHITECTURAL,

STRUCTURAL, MECHANICAL AND ELECTRICAL PLANS AND SPECIFICAITONS)

FOR COORDINATION OF TRADES, ROOMS, STRUCTURE AND EQUIPMENT.

HVAC DUCTWORK MAINS SHALL BE INSTALLED PRIOR TO FIRE PROTECTION

PIPING. PROVIDE DRAIN VALVES IN THE FIRE PROTECTION SYSTEM WHERE

REQUIRED TO COMPLETELY DRAIN THE SYSTEM.

I. REFER TO THE SPECIFICATIONS FOR SPRINKLER HEAD TYPES.

J. PROVIDE ALL REQUIRED DRAIN PIPING TO TEST FLOW SWITCHES.

DISCHARGE DRAIN PIPING TO OUTDOORS OR A FLOOR DRAIN.

K. SIZE ALL FIRE PROTECTION PIPING IN ACCORDANCE WITH NFPA 13. PIPE

SIZING SHALL BE ACCOMPLISHED USING HYDRAULIC CALCULATIONS.

L. SUBMIT HYDRAULIC CALCULATIONS AND SYSTEMS DESIGN FOR REVIEW TO

THE M/E ENGINEER.

M. THE CONTRACTOR SHALL EXERCISE EXTREME CARE IN THE COURSE OF

THEIR WORK SO AS TO ENSURE THAT THEY DO NOT INTERRUPT ANY

EXISTING SERVICE. FOR SAFETY PURPOSES, PAY PARTICULAR ATTENTION

TO THIS PRECAUTION RELATIVE TO NATURAL GAS AND ELECTRICAL LINES.

VERIFY THE LOCATION, SIZE, TYPE, ETC., OF EACH UNDERGROUND OR

OVERHEAD UTILITY. ALL WORK SHALL BE PERFORMED IN ACCORD WITH

ALL FEDERAL, STATE AND/OR LOCAL RULES, REGULATIONS, STANDARD

AND SAFETY REQUIREMENTS.

N. WHERE WORK IS REQUIRED ABOVE EXISTING LAY-IN, PLASTER OR GYPSUM

BOARD CEILINGS, THE CONTRACTOR SHALL BE RESPONSIBLE FOR

REMOVAL AND REINSTALLATION (OR REPLACEMENT, IF DAMAGED) OF ALL

CEILING OR TILE AND GRID MEMBERS NECESSARY TO PERFORM HIS WORK.

NEW TILE AND GRID SHALL MATCH THE SURROUNDING AREAS. ALL

PATCHING WORK SHALL MATCH ADJACENT SURFACES.

O. ALL NEW WORK SHALL BE HUNG FROM STRUCTURE, NOT FROM THE WORK

OF OTHER TRADES, WHETHER EXISTING OR NEW.

P. COORDINATE ALL WORK WITH PROJECT PHASING REQUIREMENTS.

Q. PATCH, REPAIR AND PAINT OR PROVIDE WALL COVERING FOR (TO OWNER'S

STANDARDS) EXISTING WALLS, CEILINGS, ETC., THAT ARE TO REMAIN IF

DAMAGED DURING CONSTRUCTION. REPAIRS SHALL MATCH ADJACENT

SURFACES TO THE SATISFACTION OF THE ARCHITECT AND OWNER.

R. OBSERVE ALL APPLICABLE CODES, RULES AND REGULATIONS THAT MAY

APPLY TO THE WORK UNDER THIS CONTRACT. (CITY, COUNTY, LOCAL,

FEDERAL, MUNICIPALITY, UTILITY COMPANY, STATE, ETC.)

S. CONTRACTOR SHALL BE AWARE OF UNSEEN PLUMBING, HVAC AND

ELECTRICAL WORK DURING DEMOLITION. IF ITEMS ARE UNCOVERED

DURING DEMOLITION THEN FIELD VERIFY THE USE OF THE ITEMS AND

PLAN AN ALTERNATE ROUTE TO RUN THESE ITEMS. THEN CONTACT THE

ENGINEERS TO REVIEW THE ROUTING.

T. ALL PENETRATIONS OF FIRE AND SMOKE RATED ASSEMBLIES SHALL BE

APPROPRIATELY FIRE STOPPED PER AN APPROVED U.L. LISTED STANDARD.

CONTRACTOR SHALL PAY PARTICULAR ATTENTION TO INSULATED PIPING

PENETRATIONS.

U. ALL WORK REQUIRING DOWNTIME OF ANY AREA IN THE BUILDING SHALL

BE SCHEDULED 2 WEEKS IN ADVANCE, AND SHALL COMPLY WITH INTERIM

LIFE SAFETY MEASURES.

V. WHERE CEILINGS ARE INDICATED ALL SPRINKLER PIPING MUST BE

INSTALLED ABOVE CEILINGS. SPRINKLER PIPING MUST BE COORDINATED

WITH OTHER TRADES. PIPING MUST BE OFFSET TO AVOID CONFLICTS

WITH DUCTWORK, CONDUIT, ALL EQUIPMENT, ETC.

W. LOCATIONS OF PIPING, DUCTS AND EQUIPMENT ARE APPROXIMATE AND

SUBJECT TO MINOR ADJUSTMENTS IN THE FIELD. DO NOT SCALE THE

DRAWINGS.

X. ALL OFFSETS IN DUCTS AND PIPING ARE NOT NECESSARILY SHOWN.

PROVIDE ADDITIONAL OFFSETS WHERE NECESSARY.

Y. COORDINATE ALL HVAC WORK WITH ELECTRICAL, PLUMBING AND OTHER

TRADES TO AVOID INTERFERENCE WITH PIPING, DUCTS, CONDUIT AND

OTHER EQUIPMENT.

Z. SEAL AIRTIGHT AROUND ALL DUCTS AND PIPING PENETRATIONS THROUGH

WALLS, FLOORS AND ROOF. PROVIDE FIRE STOPPING IN FIRE PARTITION.

AA. THE CONTRACTOR SHALL RELOCATE OR AVOID ANY EXISTING EQUIPMENT

APPURTENANCES, ETC., THAT CONFLICT WITH NEW WORK.

BB. VALVES, BALANCING DAMPERS OR ANY MECHANICAL/ELECTRICAL ITEM

REQUIRING ACCESS SHALL NOT BE LOCATED ABOVE A HARD CEILING. IF

THIS IS NOT POSSIBLE, THEN AN APPROPRIATELY SIZED ACCESS DOOR

SHALL BE PLACED UNDER THE ITEM TO ALLOW EASY MAINTENANCE AND

ADJUSTMENT. ADDITIONALLY ALL SUCH ITEMS SHALL NOT BE LOCATED AN

UNREASONABLE DISTANCE ABOVE THE CEILINGS. IN GENERAL ALL SUCH

ITEMS UNLESS INDICATED OTHERWISE SHALL BE MOUNTED SIX TO TWELVE

INCHES ABOVE THE CEILING. IF IN DOUBT, CONTACT ENGINEER PRIOR TO

INSTALLING.

TAGGED NOTE DESIGNATOR

GENERAL SYMBOLS

X REVISION TRIANGLE

ROOM NAME

RM # ROOM TAG

AFF ABOVE FINISHED FLOOR

ADJ ADJUSTABLE

AHJ AUTHORITY HAVING JURISDICTION

ANSI AMERICAN NATIONAL STANDARD INSTITUTE

POINT OF CONNECTION / CONNECT TO EXISTING

POINT OF DEMOLITION

MECHANICAL PIPING LEGEND

ABBREVIATIONS (CONTINUED)

PIPE ELBOW TURNING DOWN

PIPE ELBOW TURNING UP

PIPE TEE; CONNECTION ON BOTTOM

PIPE TEE; CONNECTION ON TOP

EXISTING PIPING - (XXX) DENOTES SYSTEM

ABANDONED IN PLACE PIPING - (XXX) DENOTES SYSTEM

PIPING TO BE DEMOLISHED - (XXX) DENOTES SYSTEMD(XXX)

E(XXX)

A(XXX)

TS

FS

PS

CHECK VALVE

FLEXIBLE PIPE CONNECTION

FLOW SWITCH

PRESSURE SWTICH

TAMPER SWITCH

DOUBLE CHECK VALVE ASSEMBLY

PIPING UNION

PETE'S PLUG; TEMPERATURE/PRESSURE PORT

MANUAL ISOLATION VALVE

OS&Y (GATE) VALVE

STRAINER

PRESSURE REDUCING VALVE (STEAM, GAS, WATER, ETC.)

FIRE PROTECTION PIPINGFP

PIPE CAP

EQUIPMENT TAG

INSTANCE

TAG XXX-#

XXXX

CLG CEILING

CLR CLEAR

FLAT ON TOPFOT

FIRE PROTECTION CONTRACTORFPC

FEET OR FOOTFT

FUTUREFUT

GAGE/GAUGEGA

GALLON (-S)GAL

GENERAL CONTRACTORGC

HORIZONTALHORIZ

IRON PIPE SIZEIPS

INTER (-IOR, -ERVAL)INT

POUNDSLBS

LINEAR FEET/FOOTLF

MAXIMUMMAX

MANUFACTURERMFG

MIN (-IMUM, -UTE)MIN

MISCELLANEOUSMISC

MOUNTINGMTG

INCH (-ES)IN

ID I (-DENTIFICATION, -NSIDE DIAMETER, -NSIDE DIMENSION)

FLOORFL

FULL LOAD AMPSFLA

FLAT ON BOTTOMFOB

NOISE CRITERIA OR NORMALLY CLOSEDNC

NOT APPLICABLEN/A

NOT IN CONTRACTNIC

NORMALLY OPEN OR NUMBERNO

NOT TO SCALENTS

OUTSIDE DI (-AMETER, -MENSION)OD

CONTRACTOR FURNISHED, CONTRACTOR INSTALLEDCFCI

OWNER FURNISHED, CONTRACTOR INSTALLEDOFCI

OWNER FURNISHED, OWNER INSTALLEDOFOI

ON CENTEROC

PLUMBING CONTRACTORPC

PLUMBINGPLBG

PRESSURE REDUCING VALVE (STEAM, WATER, GAS)PRV

POUNDS PER SQUARE INCHPSI

POUNDS PER SQUARE FOOTPSF

PPSI GAUGEPSIG

TO BE DETERMINEDTBD

SQUARE FEET OR FOOTSQ FT

TOP ELEVATIONTE

TYPICALTYP

UNLESS NOTED OTHERWISEUNO

WEIGHTWT

WITHW/

WITHOUTW/O

PERCENT%

℄ CENTERLINE

DN DOWN

ENGR ENGINEER

EXT EXTERIOR

ETR EXISTING TO REMAIN

EQ EQUAL

FVC FIRE VALVE CABINET

SEMI-RECESSED SPRINKLER HEAD WITH REMOVABLE

ESCUTCHEON PLATE

UPRIGHT TYPE SPRINKLER HEAD

SIDEWALL TYPE SPRINKLER HEAD

E IN

I

SEIBERT

KENNETH L.

EETT

SS

TATA

FF MOO

P O

F R

SO

S

I

U

R

R E

E

S

NAL

SIO ENG

NUMBER

PE-2009005131

10411 Meeting Street, Prospect, Kentucky 40059 502 326.3085 f 502 326.2691 www.cmta.com th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing # of

657-19-127JBFCA - RENOVATE SPACE FOR

DOMICILIARY PROVIDERS, BUILDING 2

5/1/2020

VA Health Care System Approval:

BID DOCUMENTS

Revision: Date:

ARCHITECT/ENGINEER:

A/E: PROJECT LEAD

Architect, Structural Engineer

Consultant:

CMTA CONSULTING ENGINEERS

10411 MEETING STREET

PROSPECT, KY 40059

502.326.3085

JEFFERSON BARRACKS

1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125

/1

/2

:1

:1

A

M

02-FP-001

FIRE SUPPRESSION LEGEND

ISRBSB

MOST RECENT FLOW TEST DATE SHOWN BELOW.

INFORMATION IS OUTDATED AND LIMITED. SHOWN

FOR REFERENCE ONLY. CONTRACTOR TO PREFORM

NEW FLOW TEST AND SEND TO ENGINEER.

STATIC: 100 PSI

RESIDUAL: 85PSI

RECOVERY TIME: 1 SECOND

DATE: 6/16/2018

NEW FIRE SERVICE INTO BUILDING TO

SPRINKLER FIRST AND SECOND FLOOR

ONLY. THIRD FLOOR AND BASEMENT TO

BE SPRINKLERED IN FUTURE.

SPRINKLER

RISER

REFER TO SITE PLAN

FOR CONTINUATION.

E IN

I

SEIBERT

KENNETH L.

EETT

SS

TATA

FF MOO

P O

F R

SO

S

I

U

R

R E

E

S

NAL

SIO ENG

NUMBER

PE-2009005131

10411 Meeting Street, Prospect, Kentucky 40059 502 326.3085 f 502 326.2691 www.cmta.com th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing # of

657-19-127JBFCA - RENOVATE SPACE FOR

DOMICILIARY PROVIDERS, BUILDING 2

5/1/2020

VA Health Care System Approval:

BID DOCUMENTS

Revision: Date:

ARCHITECT/ENGINEER:

A/E: PROJECT LEAD

Architect, Structural Engineer

Consultant:

CMTA CONSULTING ENGINEERS

10411 MEETING STREET

PROSPECT, KY 40059

502.326.3085

JEFFERSON BARRACKS

1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125

/1

/2

:1

:1

A

M

02-FP-101

FIRE PROTECTION PLAN - FLOOR 00

ISRBSB

SCALE: 1/4" = 1'-0"02-FP-101

1 FIRE PROTECTION PLAN - FLOOR 00N

HATCHED AREA INDICATES AREA TO BE PROVIDED WITH A FULLY AUTOMATIC

WET SPRINKLER SYSTEM. ALL SPRINKLER RELATED WORK SHALL BE DONE IN

ACCORDANCE WITH NFPA 13 AND ALL STATE AND LOCAL CODES.

OFFICE

OFFICE

CORRIDOR

OFFICE

OFFICE

OFFICE

OFFICE

STORAGE/COPY

OFFICE

CORRIDOR

OFFICE

OFFICE

OFFICE

OFFICE

STAIR 1

VESTIBULE

ELEV LOBBY

ELEV LOBBY

ELEV

GROUP

COMPUTER

MECH

OIT

ELEC

MEN

WOMEN

OFFICE

MULTI-PURPOSE

STORAGE

STAIR 3

S103

STAIR 2

S133

CORRIDOR

INSTITUTIONAL SPRINKLERS ON FIRST FLOOR.

SPRINKLER

RISER, WITH

CONTROL

VALVE

LIGHT HAZARD

ORDINARY HAZARD,

GROUP 1

ORDINARY HAZARD,

GROUP 2

E IN

I

SEIBERT

KENNETH L.

EETT

SS

TATA

FF MOO

P O

F R

SO

S

I

U

R

R E

E

S

NAL

SIO ENG

NUMBER

PE-2009005131

10411 Meeting Street, Prospect, Kentucky 40059 502 326.3085 f 502 326.2691 www.cmta.com th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing # of

657-19-127JBFCA - RENOVATE SPACE FOR

DOMICILIARY PROVIDERS, BUILDING 2

5/1/2020

VA Health Care System Approval:

BID DOCUMENTS

Revision: Date:

ARCHITECT/ENGINEER:

A/E: PROJECT LEAD

Architect, Structural Engineer

Consultant:

CMTA CONSULTING ENGINEERS

10411 MEETING STREET

PROSPECT, KY 40059

502.326.3085

JEFFERSON BARRACKS

1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125

/1

/2

:1

:2

A

M

02-FP-111

FIRE PROTECTION PLAN - FLOOR 01

ISRBSB

SCALE: 1/4" = 1'-0"02-FP-111

1 FIRE PROTECTION PLAN - FLOOR 01N

HATCHED AREA INDICATES AREA TO BE PROVIDED WITH A FULLY AUTOMATIC

WET SPRINKLER SYSTEM. ALL SPRINKLER RELATED WORK SHALL BE DONE IN

ACCORDANCE WITH NFPA 13 AND ALL STATE AND LOCAL CODES.

OFFICE

OFFICE

OFFICE

MECH

CONFERENCE

KITCHENETTE

HAC

OIT

ELEC

ELEV

STORAGE

218A

STAIR 1

S200

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

WOMEN

MEN

SPRINKLER

RISER, WITH

CONTROL

VALVE

LIGHT HAZARD

ORDINARY HAZARD,

GROUP 1

COPY ROOM

E IN

I

SEIBERT

KENNETH L.

EETT

SS

TATA

FF MOO

P O

F R

SO

S

I

U

R

R E

E

S

NAL

SIO ENG

NUMBER

PE-2009005131

10411 Meeting Street, Prospect, Kentucky 40059 502 326.3085 f 502 326.2691 www.cmta.com th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing # of

657-19-127JBFCA - RENOVATE SPACE FOR

DOMICILIARY PROVIDERS, BUILDING 2

5/1/2020

VA Health Care System Approval:

BID DOCUMENTS

Revision: Date:

ARCHITECT/ENGINEER:

A/E: PROJECT LEAD

Architect, Structural Engineer

Consultant:

CMTA CONSULTING ENGINEERS

10411 MEETING STREET

PROSPECT, KY 40059

502.326.3085

JEFFERSON BARRACKS

1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125

/1

/2

:1

:2

A

M

02-FP-121

FIRE PROTECTION PLAN - FLOOR 02

ISRBSB

SCALE: 1/4" = 1'-0"02-FP-121

1 FIRE PROTECTION PLAN - FLOOR 02N

OFFICES

EXCLUDED FROM

SPRINKLER WORK.

P6

P7

P6

P8 P8

E (S

A N

E (S

A N

E(SAN)E(SAN)

E(CW)

E(SAN)

E(CW)

E(SAN)

E(CW)

E(SAN)

E(CW)

E (S

A N

E(S

AN

E (S

A N

E(CW)

6"ø

1 1/2"ø 1 1/2"ø

6"ø

1 1/2"ø

6"ø

E IN

I

SEIBERT

KENNETH L.

EETT

SS

TATA

FF MOO

P O

F R

SO

S

I

U

R

R E

E

S

NAL

SIO ENG

NUMBER

PE-2009005131

10411 Meeting Street, Prospect, Kentucky 40059 502 326.3085 f 502 326.2691 www.cmta.com th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing # of

657-19-127JBFCA - RENOVATE SPACE FOR

DOMICILIARY PROVIDERS, BUILDING 2

5/1/2020

VA Health Care System Approval:

BID DOCUMENTS

Revision: Date:

ARCHITECT/ENGINEER:

A/E: PROJECT LEAD

Architect, Structural Engineer

Consultant:

CMTA CONSULTING ENGINEERS

10411 MEETING STREET

PROSPECT, KY 40059

502.326.3085

JEFFERSON BARRACKS

1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125

/1

/2

:1

:2

A

M

02-PD-101

PLUMBING DEMOLITION PLAN - FLOOR

AuthorChecker

SCALE: 1/4" = 1'-0"02-PD-101

1 PLUMBING DEMOLITION PLAN - FLOOR 00

TAGGED NOTES

P6 DEMOLISH HOT WATER HEATER AND ALL HOT WATER PIPING

IN BASEMENT, FIRST FLOOR, AND SECOND FLOOR.

P7 DEMOLISH FIXTURE AND PIPING. CAP PIPING AT MAINS.

P8 DEMOLISH PIPING. CAP AT MAINS.

N

DEMOLITION NOTE: ALL DOMESTIC HOT WATER

PIPING SHALL BE DEMOLISHED. NEW WORK

INCLUDES POINT OF USE WATER HEATERS.

P7

P7

P8

P8

P8

P8

P8

P8

P8

P8

E IN

I

SEIBERT

KENNETH L.

EETT

SS

TATA

FF MOO

P O

F R

SO

S

I

U

R

R E

E

S

NAL

SIO ENG

NUMBER

PE-2009005131

10411 Meeting Street, Prospect, Kentucky 40059 502 326.3085 f 502 326.2691 www.cmta.com th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing # of

657-19-127JBFCA - RENOVATE SPACE FOR

DOMICILIARY PROVIDERS, BUILDING 2

5/1/2020

VA Health Care System Approval:

BID DOCUMENTS

Revision: Date:

ARCHITECT/ENGINEER:

A/E: PROJECT LEAD

Architect, Structural Engineer

Consultant:

CMTA CONSULTING ENGINEERS

10411 MEETING STREET

PROSPECT, KY 40059

502.326.3085

JEFFERSON BARRACKS

1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125

/1

/2

:1

:2

A

M

02-PD-111

PLUMBING DEMOLITION PLAN - FLOOR

AuthorChecker

SCALE: 1/4" = 1'-0"02-PD-111

1 PLUMBING DEMOLITION PLAN - FLOOR 01

TAGGED NOTES

P7 DEMOLISH FIXTURE AND PIPING. CAP PIPING AT MAINS.

P8 DEMOLISH PIPING. CAP AT MAINS.

N

P8

P1

P7

P7

P7

P7

P7

P7

P7

P7 P7 P8

P8

E IN

I

SEIBERT

KENNETH L.

EETT

SS

TATA

FF MOO

P O

F R

SO

S

I

U

R

R E

E

S

NAL

SIO ENG

NUMBER

PE-2009005131

10411 Meeting Street, Prospect, Kentucky 40059 502 326.3085 f 502 326.2691 www.cmta.com th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing # of

657-19-127JBFCA - RENOVATE SPACE FOR

DOMICILIARY PROVIDERS, BUILDING 2

5/1/2020

VA Health Care System Approval:

BID DOCUMENTS

Revision: Date:

ARCHITECT/ENGINEER:

A/E: PROJECT LEAD

Architect, Structural Engineer

Consultant:

CMTA CONSULTING ENGINEERS

10411 MEETING STREET

PROSPECT, KY 40059

502.326.3085

JEFFERSON BARRACKS

1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125

/1

/2

:1

:2

A

M

02-PD-121

PLUMBING DEMOLITION PLAN - FLOOR

AuthorChecker

SCALE: 1/4" = 1'-0"02-PD-121

1 PLUMBING DEMOLITION PLAN - FLOOR 02

TAGGED NOTES

P1 EXISTING FIXTURE TO REMAIN.

P7 DEMOLISH FIXTURE AND PIPING. CAP PIPING AT MAINS.

P8 DEMOLISH PIPING. CAP AT MAINS.

G

CA

FP

ORL

RL

GW

FM

SAN

SS

VT

E(NAME)

ABAN(NAME)

O

A

V

FD-#

RD-#

P-#

TS

FS

PS

BALANCING VALVE

BALL VALVE

CHECK VALVE

FLOW SWITCH

PRESSURE SWTICH

TAMPER SWITCH

THERMOMETER

DOUBLE CHECK VALVE ASSEMBLY

PIPING UNION

COMPRESSED AIR

FIRE PROTECTION LINE

SANITARY WASTE PIPING TO GREASE TRAP

OVERFLOW ROOF LEADER PIPING

ROOF LEADER PIPING

FORCED MAIN

GAS LINE

PETE'S PLUG

POINT OF CONNECTION

LIMIT OF DEMOLITION

OS&Y (GATE) VALVE

PIPE ELBOW TURNING UP/TURNING DOWN

PIPE TEE TURNING UP/TURNING DOWN

MEDICAL AIR

ABOVE FINISHED FLOOR

ABOVE FINISHED ROOFAFR

AFF

A, AIR

CARBON DIOXIDECO2

DOMESTIC COLD WATERCW

EVACUATION (WASTE ANESTHETIC GAS DISPOSAL)EV

FIRE HOSE VALVE WITH CABINETFHV

FREEZE PROOF WALL HYDRANTFPWH

HOSE BIBBHB

DOMESTIC HOT WATERHW

INSIDE DIMENSIONID

IN ACCORDANCE WITHIAW

INVERT ELEVATIONIE

LINE PRESSURE ALARM (MEDICAL GAS AREA ALARM)LPA

MANHOLEMH

MULTI-SINGLE ALARM (MEDICAL GAS MASTER ALARM)MSA

NOT TO SCALENTS

NOT IN CONTRACTNIC

NORMALLY OPENNO

NORMALLY CLOSEDNC

OXYGENO, OX

OUTSIDE DIMENSIONOD

OPEN RECEPTACLEOR

TOP ELEVATIONTE

TYPICALTYP

UNLESS OTHERWISE NOTEDUON

SANITARY WASTE PIPING

STORM SEWER PIPING

VENT PIPING

EXISTING PIPING (THIN LINE)

ABANDONED EXISTING PIPING (THIN LINE)

DOMESTIC COLD WATER PIPING

DOMESTIC HOT WATER SUPPLY

DOMESTIC RECIRCULATING HOT WATER

CLEANOUT IN CEILING SPACE

FLOOR CLEANOUT

EXTERIOR CLEANOUT

SYMBOLS & ABBREVIATIONS

CAST IRONC.I.

DOWNDN

OVERFLOW ROOF LEADERORL

PRESSURE REDUCING VALVE (STEAM, WATER, OR GAS)PRV

POUNDS PER SQUARE INCHPSI

DOMESTIC RECIRCULATING HOT WATERRHW

ROOF LEADERRL

SOFT DOMESTIC COLD WATERSCW

SANITARY RISERSR

THRUST BLOCKTB

TRAP PRIMERTP

VACUUMV, VAC

VENT THRU ROOFVTR

OWNER FURNISHED, CONTRACTOR INSTALLEDOFCI

OWNER FURNISHED, OWNER INSTALLEDOFOI

CONTRACTOR FURNISHED, CONTRACTOR INSTALLEDCFCI

CO

CO

ECO

OXYGEN PIPING

MEDICAL AIR

VACUUM PIPING

FLOOR DRAIN DESIGNATOR

ROOF DRAIN DESIGNATOR

PLUMBING FIXTURE DESIGNATOR

XXX

X

EQUIPMENT TAG DESIGNATOR

PRESSURE REDUCING VALVE (STEAM, GAS, WATER, ETC.)

STRAINER

X TAGGED NOTE DESIGNATOR

X REVISION DESIGNATOR

SAFETY RELIEF VALVE

SAFETY RELIEF VALVE

LIMITED AREA SPRINKLER HEAD

VACUUM BREAKERV

X S

TEMPERATURE SENSOR

HOSE BIB

MOP SINK DETAIL

PROVIDE CHECK

VALVES

BALL

3/4" HW AND CW

NOT TO SCALE

VALVES

WATER HAMMER

ARRESTOR (TYPICAL)

FAUCET WITH INTEGRAL

VACUUM BREAKER

MOP

BASIN

E IN

I

SEIBERT

KENNETH L.

EETT

SS

TATA

FF MOO

P O

F R

SO

S

I

U

R

R E

E

S

NAL

SIO ENG

NUMBER

PE-2009005131

10411 Meeting Street, Prospect, Kentucky 40059 502 326.3085 f 502 326.2691 www.cmta.com th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing # of

657-19-127JBFCA - RENOVATE SPACE FOR

DOMICILIARY PROVIDERS, BUILDING 2

5/1/2020

VA Health Care System Approval:

BID DOCUMENTS

Revision: Date:

ARCHITECT/ENGINEER:

A/E: PROJECT LEAD

Architect, Structural Engineer

Consultant:

CMTA CONSULTING ENGINEERS

10411 MEETING STREET

PROSPECT, KY 40059

502.326.3085

JEFFERSON BARRACKS

1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125

/1

/2

:1

:2

A

M

02-PL-001

PLUMBING LEGEND

ISRBSB

HAZARDOUS MATERIAL NOTE:

A. THE CONTRACTOR IT IS HEREBY ADVISED THAT IS POSSIBLE THAT

ASBESTOS AND/OR OTHER HAZARDOUS MATERIALS ARE OR WERE

PRESENT IN THIS BUILDING(S). ANY WORKER, OCCUPANT, VISITOR,

ETC., WHO ENCOUNTERS ANY MATERIAL OF WHOSE CONTENT THEY

ARE NOT CERTAIN SHALL PROMPTLY REPORT THE EXISTENCE AND

LOCATION OF THAT MATERIAL TO THE OWNER. FURTHERMORE, THE

CONTRACTOR SHALL INSURE THAT NO ONE COMES NEAR TO OR IN

CONTACT WITH ANY SUCH MATERIAL OR FUMES THEREFROM UNTIL ITS

CONTENT CAN BE ASCERTAINED TO BE NON-HAZARDOUS.

B. CMTA, INC. HAS NO EXPERTISE IN THE DETERMINATION OF THE

PRESENCE OF ANY HAZARDOUS MATERIAL. THEREFORE, NO ATTEMPT

HAS BEEN MADE BY CMTA TO IDENTIFY THE EXISTENCE OR LOCATION

OF ANY SUCH HAZARDOUS MATERIAL. FURTHERMORE, CMTA NOR ANY

AFFILIATE HEREOF WILL NOT OFFER OR MAKE ANY

RECOMMENDATIONS RELATIVE TO THE REMOVAL, HANDLING OR

DISPOSAL OF SUCH MATERIAL.

C. IF THE WORK WHICH IS TO BE PERFORMED INTERFACES, CONNECTS OR

RELATES IN ANY PHYSICAL WAY WITH OR TO EXISTING COMPONENTS

WHICH CONTAIN OR BEAR ANY HAZARDOUS MATERIAL, ASBESTOS

BEING ONE, THEN IT SHALL BE THE CONTRACTOR'S SOLE

RESPONSIBILITY TO CONTACT THE OWNER AND SO ADVISE HIM/HER

IMMEDIATELY.

D. THE CONTRACTOR BY EXECUTION OF THE CONTRACT FOR ANY WORK

AND/OR BY THE ACCOMPLISHMENT OF ANY WORK THEREBY AGREE TO

BRING NO CLAIM RELATIVE TO HAZARDOUS MATERIALS FOR

NEGLIGENCE, BREACH OF CONTRACT, INDEMNITY, OR ANY OTHER

SUCH ITEM AGAINST CMTA, ITS PRINCIPALS, EMPLOYEES, AGENTS OR

CONSULTANTS. ALSO, THE CONTRACTOR FURTHER AGREES TO

DEFEND, INDEMNIFY AND HOLD CMTA, ITS PRINCIPALS, EMPLOYEES,

AGENTS AND CONSULTANTS HARMLESS FROM ANY SUCH RELATED

CLAIMS WHICH MAY BE BROUGHT BY ANY SUBCONTRACTORS,

SUPPLIERS OR ANY OTHER THIRD PARTIES.

E. THE CONTRACTOR IS DIRECTED TO THE SPECIFICATIONS FOR FURTHER

INFORMATION.

PLUMBING GENERAL NOTES:

A. COORDINATE THE LOCATION OF DRAINS, THERMOSTATS, GAS

OUTLETS, ETC., WITH ALL CASEWORK EQUIPMENT,

MECHANICAL ROOM EQUIPMENT, ETC., PRIOR TO COMMENCING

INSTALLATION. WORK NOT SO COORDINATED SHALL BE

REMOVED AND PROPERLY INSTALLED AT THE EXPENSE OF THE

CONTRACTOR.

B. THE CONTRACTOR SHALL EXERCISE EXTREME CARE IN THE

COURSE OF THEIR WORK SO AS TO ENSURE THAT THEY DO

NOT INTERRUPT ANY EXISTING SERVICE. FOR SAFETY

PURPOSES, PAY PARTICULAR ATTENTION TO THIS PRECAUTION

RELATIVE TO NATURAL GAS AND ELECTRICAL LINES. VERIFY

THE LOCATION, SIZE, TYPE, ETC., OF EACH UNDERGROUND OR

OVERHEAD UTILITY. ALL WORK SHALL BE PERFORMED IN

ACCORD WITH ALL FEDERAL, STATE AND/OR LOCAL RULES,

REGULATIONS, STANDARD AND SAFETY REQUIREMENTS.

UTILITIES SHALL BE INSTALLED IN ACCORD WITH THE

APPLICABLE MUNICIPALITY OR UTILITY COMPANY STANDARDS.

IN ALL CASES, THE MOST STRINGENT REQUIREMENT SHALL

APPLY.

C. WHERE WORK IS REQUIRED ABOVE EXISTING LAY-IN, PLASTER

OR GYPSUM BOARD CEILINGS, THE CONTRACTOR SHALL BE

RESPONSIBLE FOR REMOVAL AND REINSTALLATION (OR

REPLACEMENT, IF DAMAGED) OF ALL CEILING OR TILE AND

GRID MEMBERS NECESSARY TO PERFORM HIS WORK. NEW

TILE AND GRID SHALL MATCH THE SURROUNDING AREAS. ALL

PATCHING WORK SHALL MATCH ADJACENT SURFACES.

D. ALL NEW WORK SHALL BE HUNG FROM STRUCTURE, NOT FROM

THE WORK OF OTHER TRADES, WHETHER EXISTING OR NEW.

E. COORDINATE ALL WORK WITH PROJECT PHASING

REQUIREMENTS.

F. PATCH, REPAIR AND PAINT OR PROVIDE WALL COVERING FOR

(TO OWNER'S STANDARDS) EXISTING WALLS, CEILINGS, ETC.,

THAT ARE TO REMAIN IF DAMAGED DURING CONSTRUCTION.

REPAIRS SHALL MATCH ADJACENT SURFACES TO THE

SATISFACTION OF THE ARCHITECT AND OWNER.

G. OBSERVE ALL APPLICABLE CODES, RULES AND REGULATIONS

THAT MAY APPLY TO THE WORK UNDER THIS CONTRACT.

(CITY, COUNTY, LOCAL, FEDERAL, MUNICIPALITY, UTILITY

COMPANY, ETC.)

H. CONTRACTOR SHALL BE AWARE OF UNSEEN PLUMBING WORK

DURING DEMOLITION. IF ITEMS ARE UNCOVERED DURING

DEMOLITION THEN FIELD VERIFY THE USE OF THE ITEMS AND

PLAN AN ALTERNATE ROUTE TO RUN THESE ITEMS. THEN

CONTACT THE ENGINEERS TO REVIEW THE ROUTING.

I. WHERE FIRE PROOFING IS SPRAYED ON EXISTING STRUCTURE

ALL EXISTING CONDUITS, WATER, HYDRONIC, STEAM, CHILLED

WATER, FIRE PROTECTION LINES, MED GAS, ETC. SHALL BE

LOWERED TO BE BELOW FULL THICKNESS OF FIRE PROOFING

WITH NO INTERFERENCE.

J. ALL PENETRATIONS OF FIRE AND SMOKE RATED ASSEMBLIES

SHALL BE APPROPRIATELY FIRE STOPPED PER AN APPROVED

U.L. LISTED STANDARD. CONTRACTOR SHALL PAY PARTICULAR

ATTENTION TO INSULATED PIPING PENETRATIONS.

K. ALL WORK REQUIRING DOWNTIME OF ANY AREA IN THE

BUILDING SHALL BE SCHEDULED 2 WEEKS IN ADVANCE, AND

SHALL COMPLY WITH INTERIM LIFE SAFETY MEASURES.

L. ALL PIPING IN ROOMS WITH CEILINGS SHALL BE ABOVE CEILING

EXCEPT AS NOTED.

M. LOCATIONS OF PIPING AND EQUIPMENT ARE APPROXIMATE AND

SUBJECT TO MINOR ADJUSTMENTS IN THE FIELD. DO NOT

SCALE THE DRAWINGS.

N. ALL OFFSETS IN PIPING ARE NOT NECESSARILY SHOWN.

PROVIDE ADDITIONAL OFFSETS WHERE NECESSARY.

O. THE CONTRACTOR IS RESPONSIBLE FOR ALL UTILITY COMPANY

FEES OR OTHER COSTS THAT ANY UTILITY COMPANY MAY

REQUIRE TO COMPLETE THEIR WORK. (GAS, SEWER, WATER,

ETC.).

P. WHERE MOUNTING HEIGHTS ARE NOT INDICATED OR ARE IN

CONFLICT WITH ANY OTHER BUILDING SYSTEM, CONTACT THE

ENGINEERS BEFORE INSTALLATION. REFER ALSO TO

ARCHITECTURAL WALL INTERIOR AND EXTERIOR WALL

ELEVATIONS, CEILING HEIGHTS AND OTHER DETAIL OF THESE

DOCUMENTS.

Q. DEVIATIONS IN SIZE, CAPACITIES, FIT, FINISH, ETC. FOR

EQUIPMENT FROM THAT USED AS BASIS OF DESIGN SHALL BE

THE RESPONSIBILITY OF THE PURCHASER OF THAT

EQUIPMENT. ANY PROVISIONS REQUIRED TO ACCOMMODATE A

DEVIATION, WHETHER APPROVED BY THE ENGINEERS OR NOT,

SHALL BE THE RESPONSIBILITY OF THE PURCHASER.

R. VALVES, BALANCING DAMPERS OR ANY

MECHANICAL/ELECTRICAL ITEM REQUIRING ACCESS SHALL NOT

BE LOCATED ABOVE A HARD CEILING. IF THIS IS NOT POSSIBLE,

THEN AN APPROPRIATELY SIZED ACCESS DOOR SHALL BE

PLACED UNDER THE ITEM TO ALLOW EASY MAINTENANCE AND

ADJUSTMENT. ADDITIONALLY ALL SUCH ITEMS SHALL NOT BE

LOCATED AN UNREASONABLE DISTANCE ABOVE THE CEILINGS.

IN GENERAL ALL SUCH ITEMS UNLESS INDICATED OTHERWISE

SHALL BE MOUNTED SIX TO TWELVE INCHES ABOVE THE

CEILING. IF IN DOUBT, CONTACT ENGINEER PRIOR TO

INSTALLING.

PLUMBING DEMOLITION NOTES:

A. THE CONTRACTOR SHALL REFER TO THE ARCHITECTURAL PLANS FOR

AREAS IN WHICH THE CEILING IS REMAINING. THE CONTRACTOR IS

RESPONSIBLE FOR REMOVING THE EXISTING CEILING AS REQUIRED AND

REINSTALLATION. TEMPORARILY SUPPORT LIGHTS, DIFFUSERS, CEILING

ETC. REPLACE BROKEN CEILING TILES WITH NEW AT NO ADDITIONAL COST

TO OWNER. FIELED VERIFY EXACT REQUIREMENTS.

B. ALL OUTAGES SHALL BE SCHEDULED THROUGH THE PROJECT

REPRESENTATIVE FOR PROPER COORDINATION. A REQUEST FOR AN

OUTAGE SHALL BE SUBMITTED IN WRITING A MINIMUM OF TWO WEEKS IN

ADVANCE.

C. DURING SPRINKLER SYSTEM OUTAGES THE CONTRACTORS SHALL

PROVIDE FIRE WATCH OF AREAS WITH OUTAGES.

D. ALL WALLS AND FLOOR SLABS SHALL BE REPAIRED TO MATCH EXISTING

AND TO A LIKE NEW CONDITION. ALL RATED WALLS AND FLOOR SLABS

SHALL BE PATCHED AND REPAIRED TO MAINTAIN RATING.

E. ALL EXISTING BUILDING FINISHES SHALL BE PROTECTED DURING THE

DEMOLITION PHASE.

F. HEAVY DASHED LINES INDICATE ITEMS FOR REMOVAL (U.O.N) AND LIGHT

SOLID LINES INDICATE EXISTING ITEMS TO REMAIN.

G. COORDINATE DISPOSAL OF ALL FIXTURES, DEVICES, ETC. (INDICATED FOR

DEMOLITION) WITH THE OWNER.

WATER HEATER SCHEDULE

TAG SERVING MANUFACTURER MODEL

WH-1 MOP SINKS AO SMITH DEL-10

WH-2 TWO SINKS CHRONOMITE CM-40L

WH-3 SINGLE SINK CHRONOMITE CM-20L

PLUMBING FIXTURE SCHEDULE

Mark Description Accessories

P-103 WATER CLOSET WALL CARRIER - 1.28 GPF

P-201 URINAL WALL CARRIER - .5 GPF

P-401 LAVATORY GRID STRAINER, P-TRAP, TRAP GUARD, CHROME ANGLE STOPS - 1.0 GPM

P-502 MOP SINK MOP HANGER - 3.0 GPM

P-524 KITCHEN SINK GRID STRAINER, P-TRAP, TRAP GUARD, CHROME ANGLE STOPS - 2.2 GPM

P-528 HAND SINK GRID STRAINER, P-TRAP, TRAP GUARD, CHROME ANGLE STOPS - 1.0 GPM

ALL SYMBOLS AND VALVE MAY NOT BE USED ON THIS PROJECT.

CAP

E(CW)

E (C

W

E (C

W

E (C

W

E(CW)

E (S

A N

E(CW)

E(CW)

CAP

P2

P2

P2

2" SAN

P4

P2

P1 P1

P4

E(SAN) E(SAN) E(SAN) E(SAN) E(SAN)

E

(SA

N

E(S

AN

E (S

A N

E (S

A N

E(S

AN

STORAGE

G07

MECH RM

G08

STORAGE

G06

STORAGE

G07A

HAC

G05B

TOILET

G05A

STORAGE

G05

CORRIDOR

H003

TRANSFORMER

G09

ELEV EQUIP

G01 ELEV

E-00

CORRIDOR

H002

STORAGE

G03

CORRIDOR

H001

OIT

G04

STORAGE

G02

STORAGE

G02B

STORAGE/COPY ROOM

G02A

WH-3

P3

E IN

I

SEIBERT

KENNETH L.

EETT

SS

TATA

FF MOO

P O

F R

SO

S

I

U

R

R E

E

S

NAL

SIO ENG

NUMBER

PE-2009005131

10411 Meeting Street, Prospect, Kentucky 40059 502 326.3085 f 502 326.2691 www.cmta.com th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing # of

657-19-127JBFCA - RENOVATE SPACE FOR

DOMICILIARY PROVIDERS, BUILDING 2

5/1/2020

VA Health Care System Approval:

BID DOCUMENTS

Revision: Date:

ARCHITECT/ENGINEER:

A/E: PROJECT LEAD

Architect, Structural Engineer

Consultant:

CMTA CONSULTING ENGINEERS

10411 MEETING STREET

PROSPECT, KY 40059

502.326.3085

JEFFERSON BARRACKS

1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125

/1

/2

:1

:2

A

M

02-PL-101

PLUMBING PLAN - FLOOR 00

ISRBSB

SCALE: 1/4" = 1'-0"02-PL-101

1 PLUMBING PLAN - FLOOR 00

TAGGED NOTES

P1 EXISTING FIXTURE TO REMAIN.

P2 CONNECT NEW PIPING INTO EXISTING PIPING AS SHOWN.

VERIFY EXACT LOCATION IN FIELD.

P3 INSTALL NEW POINT OF USE WATER HEATER (SEE SCHEDULE)

FOR FIXTURE AS SHOWN.

P4 CAP PIPING AT LOCATION SHOWN.

TMV'S SHALL BE INSTALLED ON ALL SINKS.

WH-1

P-103P-103

P-103

P-103

P-401

P-401

P-401

P-502

4" SAN

P-201

P-201

WH-3

WH-2

SAN UP

TO T12

SAN UP

TO SK1

P5

P3

P3

VENT UP

OFFICE

CORRIDOR

OFFICE

STORAGE/COPY

OFFICE

OFFICE

CORRIDOR

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

MECH

OIT

ELEC

ELEV LOBBY

ELEV

ELEV LOBBY

STAIR 1

GROUP

COMPUTER

WOMEN

MEN

MULTI-PURPOSE

STORAGE

JAN

3/4" CW

2" SAN

E IN

I

SEIBERT

KENNETH L.

EETT

SS

TATA

FF MOO

P O

F R

SO

S

I

U

R

R E

E

S

NAL

SIO ENG

NUMBER

PE-2009005131

10411 Meeting Street, Prospect, Kentucky 40059 502 326.3085 f 502 326.2691 www.cmta.com th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing # of

657-19-127JBFCA - RENOVATE SPACE FOR

DOMICILIARY PROVIDERS, BUILDING 2

5/1/2020

VA Health Care System Approval:

BID DOCUMENTS

Revision: Date:

ARCHITECT/ENGINEER:

A/E: PROJECT LEAD

Architect, Structural Engineer

Consultant:

CMTA CONSULTING ENGINEERS

10411 MEETING STREET

PROSPECT, KY 40059

502.326.3085

JEFFERSON BARRACKS

1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125

/1

/2

:1

:2

A

M

02-PL-111

PLUMBING PLAN - FLOOR 01

ISRBSB

SCALE: 1/4" = 1'-0"02-PL-111

1 PLUMBING PLAN - FLOOR 01

TAGGED NOTES

P3 INSTALL NEW POINT OF USE WATER HEATER (SEE SCHEDULE)

FOR FIXTURE AS SHOWN.

P5 INSTALL NEW TANK WATER HEATER ON SHELF ABOVE MOP

SINK TO SUPPLY MOP SINKS ON FLOORS 1 AND 2.

1 1/2" VT

3" VT

2" VT

WH-2

WH-3

P-502

P-103 P-103

P-103

P-103

P-401

P-401

P-401

P3

P3

P3

CUBICLE BAY

CORRIDOR

OFFICE

OFFICE

OFFICE

OFFICE

CONFERENCE

MECH

KITCHENETTE

HAC

COPY ROOM

ELEV

STORAGE

218A

OIT

ELEC

MEN

WOMEN

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

1 1/2" VT

3/4" CW

WH-3

P-524

PROVIDE DUAL CHECK VALVE

BEFORE CONNECTION TO

EQUIPMENT.

E IN

I

SEIBERT

KENNETH L.

EETT

SS

TATA

FF MOO

P O

F R

SO

S

I

U

R

R E

E

S

NAL

SIO ENG

NUMBER

PE-2009005131

10411 Meeting Street, Prospect, Kentucky 40059 502 326.3085 f 502 326.2691 www.cmta.com th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing # of

657-19-127JBFCA - RENOVATE SPACE FOR

DOMICILIARY PROVIDERS, BUILDING 2

5/1/2020

VA Health Care System Approval:

BID DOCUMENTS

Revision: Date:

ARCHITECT/ENGINEER:

A/E: PROJECT LEAD

Architect, Structural Engineer

Consultant:

CMTA CONSULTING ENGINEERS

10411 MEETING STREET

PROSPECT, KY 40059

502.326.3085

JEFFERSON BARRACKS

1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125

/1

/2

:1

:2

A

M

02-PL-121

PLUMBING PLAN - FLOOR 02

ISRBSB

SCALE: 1/4" = 1'-0"02-PL-121

1 PLUMBING PLAN - FLOOR 02

TAGGED NOTES

P3 INSTALL NEW POINT OF USE WATER HEATER (SEE SCHEDULE)

FOR FIXTURE AS SHOWN.

WH-3

WH-3

4" VT

E(CW)

1/2" CW

P2

P3

P1

P1 P1 P3

OFFICE

OFFICE

OFFICE

310A

OFFICE

OFFICE

316A

OFFICE

OFFICE

TOILET

CORRIODR

H303

KITCHENETTE

STAIR 1

S301

MECH. RM

OFFICE

CORRIDOR

H302

OFFICE

OFFICE

OFFICE

302A

CORRIDOR

H301

OFFICE

OFFICE

OFFICE

307A

OFFICE

OFFICE

E IN

I

SEIBERT

KENNETH L.

EETT

SS

TATA

FF MOO

P O

F R

SO

S

I

U

R

R E

E

S

NAL

SIO ENG

NUMBER

PE-2009005131

10411 Meeting Street, Prospect, Kentucky 40059 502 326.3085 f 502 326.2691 www.cmta.com th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing # of

657-19-127JBFCA - RENOVATE SPACE FOR

DOMICILIARY PROVIDERS, BUILDING 2

5/1/2020

VA Health Care System Approval:

BID DOCUMENTS

Revision: Date:

ARCHITECT/ENGINEER:

A/E: PROJECT LEAD

Architect, Structural Engineer

Consultant:

CMTA CONSULTING ENGINEERS

10411 MEETING STREET

PROSPECT, KY 40059

502.326.3085

JEFFERSON BARRACKS

1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125

/1

/2

:1

:2

A

M

02-PL-131

PLUMBING PLAN - FLOOR 03

ISRBSB

SCALE: 1/4" = 1'-0"02-PL-131

1 PLUMBING PLAN - FLOOR 03

TAGGED NOTES

P1 EXISTING FIXTURE TO REMAIN.

P2 CONNECT NEW PIPING INTO EXISTING PIPING AS SHOWN.

VERIFY EXACT LOCATION IN FIELD.

P3 INSTALL NEW POINT OF USE WATER HEATER (SEE SCHEDULE)

FOR FIXTURE AS SHOWN.

S A

N

P-502

P-502

P-103

P-201 P-201

P-401

P-103

P-103

P-103 P-401

P-401

P-401 P-401

1 1/2" VT

1 1/2" VT1 1/2" VT

2" SAN

2" SAN

1 1/2" VT

1 1/2" VT

2" SAN

2" SAN

2" SAN

2" VT

3" VT

2" VT

1 1/2" VT

1 1/2" VT

1 1/2" VT

2" SAN

4" SAN

4" SAN

2" VT

2" VT

3" VT

3" VT

3" VT

VTR

E(S

AN)

E(S

AN)

E(SAN)

E (S

A N

E(S

AN)

E(SAN)

E(SAN)

E(S

AN)

E (S

A N

E (S

A N

E(SAN)

E(S

AN)

E (S

A N

)E(S

AN)

E(C W

E(C W

E(CW

E(CW

E (C

W

P-502

WH-3

P-502

WH-1

C W

3/4" CW

1 1/2" CW

3/4" CW

1/2" CW

1/2" CW

1/2" CW

1/2" CW

1/2" CW

WH-2

P-103

P-103 P-103

P-103

P-401 P-201

P-201

1 1/2" CW

1 1/2" CW

WH-3

WH-1

P-103 P-201

P-201 P-401

P-103

P-103 P-103 P-401

P-401

3/4" CW

WH-3

E(C W

E(C W

E(CW

E(C W

EX SINK

EX LAV

EX WC

E IN

I

SEIBERT

KENNETH L.

EETT

SS

TATA

FF MOO

P O

F R

SO

S

I

U

R

R E

E

S

NAL

SIO ENG

NUMBER

PE-2009005131

10411 Meeting Street, Prospect, Kentucky 40059 502 326.3085 f 502 326.2691 www.cmta.com th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing # of

657-19-127JBFCA - RENOVATE SPACE FOR

DOMICILIARY PROVIDERS, BUILDING 2

5/1/2020

VA Health Care System Approval:

BID DOCUMENTS

Revision: Date:

ARCHITECT/ENGINEER:

A/E: PROJECT LEAD

Architect, Structural Engineer

Consultant:

CMTA CONSULTING ENGINEERS

10411 MEETING STREET

PROSPECT, KY 40059

502.326.3085

JEFFERSON BARRACKS

1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125

/1

/2

:1

:3

A

M

02-PL-401

PLUMBING ISOMETRIC

ISRBSB

SCALE:02-PL-401

1 PLUMBING ISOMETRIC - WASTE & VENT

SCALE:02-PL-401

2 PLUMBING ISOMETRIC - UTILITIES

QUICK-COUPLE HOSE CONNECTOR

ANCHOR

REDUCER OR INCREASER

DIRECTION OF FLOW

SIDE CONNECTION

ECCENTRIC REDUCER

BOTTOM CONNECTION, 45° OR 90°

TOP CONNECTION, 45° OR 90°

DIRECTION OF PIPE PITCH (DOWN)

UNION

RISE OR DROP IN PIPE

CAPPED OUTLET

PRESSURE GAGE

THERMOMETER

VENTURI FLOW METER

FLOAT & THERMOSTATIC TRAP SET INCLUDING

PIPING ACCESSORIES SEE DETAIL

PIPING ACCESSORIES SEE DETAIL

INVERTED BUCKET TRAP SET INCLUDING

PIPE UP

PIPE DOWN

REFRIGERANT SIGHT GLASS

TEST PLUG (PRESSURE/TEMPERATURE)

AUTOMATIC AIR VENT

AV

MANUAL AIR VENT

MV

THERMOSTATIC TRAP SET INCLUDING

PIPING ACCESSORIES SEE DETAIL

GENERAL PIPING SYMBOLS

HIGH PRESSURE STEAM CONDENSATE RETURN

HIGH PRESSURE STEAM (60 PSIG AND ABOVE)

HOT WATER HEATING SUPPLY

CONDENSATE PUMP DISCHARGE

LOW PRESSURE STEAM CONDENSATE RETURN

LOW PRESSURE STEAM (15 PSIG AND BELOW)

MEDIUM PRESSURE STEAM CONDENSATE RETURN

MEDIUM PRESSURE STEAM (16 PSIG THRU 59 PSIG)

VENT LINE

GLYCOL-WATER HEATING RETURN

GLYCOL-WATER HEATING SUPPLY

CHILLED WATER SUPPLY

CHILLED WATER RETURN

DRAIN LINE

MAKE-UP WATER

HOT WATER HEATING RETURN

S-60

CR-60

S-30

CR-30

S-15

CR-15

PC

HWS

HWR

GHS

GHR

V

CHR

CHS

MW

D

X EXISTING PIPE TO BE REMOVED

PIPING ABBREVIATIONS

PLUG VALVE

CONTROL VALVE (CV) - FLOAT-OPERATED

PRESSURE REDUCING VALVE (PRV)

WATER LEVEL CONTROLLER

FLOW METER

LC

M

BALL VALVE

GATE VALVE WITH 3/4" HOSE ADAPTER

CHECK VALVE

BUTTERFLY VALVE

MODULATING CONTROL VALVE

TWO POSITION CONTROL VALVE

THREE-WAY MODULATING CONTROL VALVE

AUTOMATIC BALANCING CONTROL VALVE

PRESSURE SAFETY VALVE

GATE VALVE - THREADED/FLANGED

PRESSURE REGULATING VALVE

THREE-WAY TWO POSITION CONTROL VALVE

WYE STRAINER (WITH BALL VALVE & HOSE CONNECTION)

FLEXIBLE CONNECTION

WATER BALANCE DEVICE

MODULATING CONTROL BUTTERFLY VALVE

CIRCUIT SETTER VALVE

WYE STRAINER WITH VALVED DRAIN AND QUICK-COUPLE

HOSE CONNECTOR

VALVE SYMBOLS

LIMIT OF DEMOLITION

DN

DN

UP

UP

SUPPLY DUCT (UP & DOWN)

EXHAUST DUCT (UP & DOWN)

4-WAY CEILING DIFFUSERS

CONNECT NEW DUCT TO EXISTING DUCT

DNUP RETURN DUCT (UP & DOWN)

DUCTWORK SYMBOLS

BACK DRAFT DAMPER

BDD

FC

10x8

FLEXIBLE CONNECTION, EQUIPMENT,

VANED ELBOW (PROVIDE ALL SQUARE OR

RECTANGULAR ELBOWS WITH VANES EVEN IF

SYMBOL IS MISSING)

VANED ELBOW (SHORT RADIUS)

STANDARD RADIUS ELBOW (LONG RADIUS)

NEW DUCT (INSIDE DIMENSIONS: WIDTH x DEPTH)

EXISTING DUCT TO REMAIN

FIRE DAMPER

FD

VD

MANUAL VOLUME DAMPER

EXISTING DUCT TO BE REMOVED

VIBRATION, OR SEISMIC

SUPPLY

RETURN

45°

RETURN, NO SPLITTER (45° TAP)

STANDARD BRANCH SUPPLY OR

45°

DRAWING SYMBOLS

26-SF 3

26-TU-I-I

DETAIL NUMBER

DRAWING NUMBER WHERE SHOWN

SECTION LETTER

TYPICAL UNIT NO.

BUILDING NO. WHERE EQUIPMENT IS LOCATED.

SUPPLY FAN NO. 3 IN BUILDING NO. 26

EQUIPMENT ABBREVIATION (SUPPLY FAN)

ITEM NUMBER (TERMINAL UNIT NO. 1)

ITEM (TERMINAL UNIT SHOWN)

SERVED BY AIR HANDLER UNIT NO. 1

DRAWING NUMBER WHERE DRAWN

BUILDING NO. WHERE EQUIPMENT IS LOCATED

H4

H7

A

GENERAL NOTES

1. ALL PIPING AND DUCTS IN FINISHED ROOMS OR SPACES SHALL BE CONCEALED IN A

FURRED CHASE OR ABOVE HARD SUSPENDED CEILING, OR ACOUSTICAL CEILING.

2. THE FIRST FIGURE OF DUCT SIZE INDICATES DIMENSION OF FACE SHOWN OR INDICATED.

DUCT SIZES ARE NET INSIDE DIMENSIONS.

3. ACCESS PANELS IN HARD SUSPENDED CEILINGS ARE REQUIRED FOR ALL VALVES, TRAPS,

DAMPERS, CLEANOUTS, CONTROLS, ETC. ACCESS PANELS SHALL BE FURNISHED AND

INSTALLED UNDER THE ARCHITECTURAL SPECIFICATIONS. COORDINATE LOCATION WITH

MECHANICAL INSTALLATION AND DEMONSTRATE ACCESS TO EQUIPMENT SERVED.

4. TOTAL STATIC PRESSURE NOTED IN THE SCHEDULES INCLUDES DUCT SYSTEM, TERMINAL

UNITS, FILTERS, COILS, ETC. LOSS FOR FILTERS SHALL BE FOR FILTERS AT 50% LOADING.

5. FOR TYPICAL STEAM AND WATER PIPING CONNECTIONS TO EQUIPMENT, SEE STANDARD

EQUIPMENT DETAILS.

6. DIFFUSER, REGISTER AND GRILLE SIZES SHOWN ON FLOOR PLANS ARE NECK SIZES.

7. WATER PIPE CONNECTIONS TO AIR HEATING AND COOLING COILS SHALL BE MADE TO

PROVIDE COUNTER FLOW BETWEEN WATER AND AIR.

8. WALL TYPE EXHAUST REGISTERS NOTED AS "BR" ON DRAWINGS ARE TO BE INSTALLED

WITH BOTTOM ELEVATION OF REGISTER AT 175mm [7"] ABOVE FINISHED FLOOR.

9. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT LOCATIONS OF

CEILING DIFFUSERS, REGISTERS, AND GRILLES.

A/E ARCHITECT / ENGINEER

AAHX AIR TO AIR HEAT EXCHANGER

AAV AUTOMATIC AIR VENT

AB AIR BLENDER

ACC AIR COOLED CONDENSER

ACCH AIR COOLED CHILLER

ACCU AIR COOLED CONDENSING UNIT

ACD AUTOMATIC CONTROL DAMPER,

MODULATING

ACD-TP AUTOMATIC CONTROL DAMPER,

TWO POSITION

ACU AIR CONDITIONING UNIT

AD ACCESS DOOR

AF AFTER FILTER

AFCV AIR FLOW CONTROL VALVE

AFF ABOVE FINISHED FLOOR

AFMS AIR FLOW MEASURING STATION

AFW AIR FOIL WHEEL (FAN)

AHU AIR-HANDLING UNIT

AMP AMPERE

AP ACCESS PANEL

APD AIR PRESSURE DROP

AQST AQUASTAT

ARI AIR CONDITIONING AND REFRIGERATION INSTITUTE

AS AIR SEPARATOR

ASHRAE AMERICAN SOCIETY OF HEATING REFRIGERATION AIR

CONDITIONING ENGINEERS

ASME AMERICAN SOCIETY OF MECHANICAL ENGINEERS

AW AIR WASHER

AXF AXIAL FLOW

B BOILER

BD BUTTERFLY DAMPER

BDD BACKDRAFT DAMPER

BDR BASE BOARD RADIATOR

BFP BACKFLOW PREVENTER

BFT BOILER PLANT FIRE TUBE

BG BOTTOM GRILLE

BHP BRAKE HORSEPOWER

BHW HOT WATER HEATING BOILER

BHX BOILER BLOWDOWN HEAT EXCHANGER

BIW BACKWARD INCLINED WHEEL (FAN)

BMT BONE MARROW TRANSPLANT

BR BOTTOM REGISTER

BSC BIOLOGICAL SAFETY CABINETS

BT BLOWOFF TANK

BTC BLOWOFF TANK CONTROL VALVE

BTU BRITISH THERMAL UNIT

BTUH BRITISH THERMAL UNIT PER HOUR

BWT BOILER PLANT WATER TUBE

C CENTIGRADE (CELSIUS)

CAV CONSTANT AIR VOLUME

CC COOLING COIL

CCD COOLING COIL CONDENSATE DRAIN

CD CEILING DIFFUSER

CD-1 CONSTRUCTION DOCUMENTS (SUBMISSION1)

CD-2 CONSTRUCTION DOCUMENTS (SUBMISSION2)

CENT CENTRIFICAL

CFH CUBIC FEET PER HOUR

CFM CUBIC FEET PER MINUTE

CFT CUBIC FEET

CFP CHEMICAL FEED PUMP

CG CEILING GRILLE

CH CHILLER

CHP CHILLED WATER PUMP

CHW CHILLER WATER

CHR CHILLED WATER RETURN

CHS CHILLED WATER SUPPLY

CI CAST IRON

CM CARBON MONOXIDE

CM CUBIC METER

CM/S CUBIC METER PER SECOND

CO CLEAN OUT

CO2 CARBON DIOXODE

COMP COMPRESSOR UNIT

COP COEFFICIENT OF PERFORMANCE

CP CONDENSATE PUMP

CR CEILING REGISTER

CS CONDENSATE STORAGE TANK

CSG CLEAN STEAM GENERATOR

CT COOLING TOWER

CU CONDENSING UNIT

CUH CABINET UNIT HEATER

CV CONSTANT VOLUME

CW COLD WATER (POTABLE)

CWCC CHILLED WATER COOLING COIL

CWP CONDENSER WATER PUMP

CWR CONDENSER WATER RETURN (TO

COOLING TOWER)

CWS CONDENSER WATER SUPPLY (FROM

COOLING TOWER)

D DAMPER - AUTOMATIC

Db DRY-BULB TEMPERATURE

DB DECIBELS

DCW DOMESTIC COLD WATER

DD-1 DESIGN DEVELOPMENT (SUBMISSION 1)

DD-2 DESIGN DEVELOPMENT (SUBMISSION 2)

DDC DIRECT DIGITAL CONTROLS

DEG DEGREE

DF DIFFUSER

DHW DOMESTIC HOT WATER

DHWR DOMESTIC HOT WATER RETURN

DIA DIAMETER

DIW DEIONIZED WATER

DP DEW POINT TEMPERATURE

DP DIFFUSER PLATE

DPA DIFFERENTIAL PRESSURE ASSEMBLY

DPS DIFFERENTIAL PRESSURE SENSOR

DX DIRECT EXPANSION

DXCC DIRECT EXPANSION COOLING COIL

EA EXHAUST AIR

EAT ENTERING AIR TEMPERATURE

EC EVAPORATIVE COOLER

ECC ENGINEERING CONTROL CENTER

ECU EVAPORATIVE CONDENSER UNIT

EDH ELECTRIC DUCT HEATER

EER ENERGY EFFICIENCY RATIO

EF EXHAUST FAN

EG EXHAUST GRILLE

EGS EMERGENCY GAS SHUTOFF

EGT ENTERING GLYCOL TEMPERATURE

EH EXHAUST HOOD

EJ EXPANSION JOINT

EMD END OF MAIN DRIP (STEAM)

ENT ENTERING

ER EXHAUST REGISTER

ERC ELECTRIC REHEAT COIL

ERP ELECTRIC RADIANT PANEL

ESP EXTERNAL STATIC PRESSURE

ET EXPANSION TANK

ETO ETHYLENE OXIDE

EUH ELECTRIC UNIT HEATER

EWC EVAPORATIVE WATER COOLER

EWT ENTERING WATER TEMPERATURE

EX EXISTING

F FAHRENHEIT

F&T FLOAT AND THERMOSTATIC

F/SDPR COMBINATION FIRE SMOKE DAMPER

FA FREE AREA

FC FLEXIBLE CONNECTION

FCU FAN COIL UNIT (4 PIPE)

FCUC FAN COIL UNIT COOLING ONLY

FCUH FAN COIL UNIT HEATING ONLY

FCW FORWARD CURVED WHEEL (FAN)

FD FLOOR DRAIN

FD FIRE DAMPER

FF FINAL FILTER

FHX FLUE GAS/FEEDWATER HEAT EXCHANGER

FM FLOW METER

FOP FUEL OIL PUMP

FOT FUEL OIL TANK

FOHX FUEL OIL HEAT EXCHANGER

FPM FEET PER MINUTE

FPS FEET PER SECOND

FPTU FAN POWERED TERMINAL UNIT

FR FLOOR REGISTER

FRP FIBER REINFORCED POLYESTER

FS FLOW SWITCH

FSTAT FREEZESTAT

FT FEET

FT WC FEET OF WATER COLUMN

FT-LB FOOT-POUND

FTR FIN TUBE RADIATION

FV FACE VELOCITY

GA GAUGE

GAL GALLONS

GH GRAVITY HOOD

GPD GALLONS PER DAY

GPH GALLONS PER HOUR

GPM GALLONS PER MINUTE

GPR GAS PRESSURE REGULATOR

GS GALVANIZED STEEL

H HUMIDIFER

HAC HOUSEKEEPING AID CLOSET

HB HOSE BIBB

HC HEATING COIL

HD HOOD

HOA HAND/OFF/AUTOMATIC

HP HEAT PUMP

HP HORSEPOWER

HPDT HIGH PRESSURE DRIP TRAP

HPR HIGH PRESSURE RETURN (STEAM CONDENSATE)

HPS HIGH PRESSURE SUPPLY (STEAM)

HRC HEAT RECOVERY COIL

HRD HEAT RECOVERY DEVICE

HRP HYDRONIC RADIANT (CEILING) PANEL

HRW HEAT RECOVERY WHEEL

HSTAT HUMIDISTAT

HTM HUMIDIFIER TERMINAL

HUM HUMIDIFIER UNIT MOUNTED

HVU HEATING AND VENTILATING UNIT

HW HOT WATER

HWC HOT WATER COIL

HWHC HOT WATER HEATING COIL

HWP HEATING HOT WATER PUMP

HWR HEATING HOT WATER RETURN

HWS HEATING HOT WATER SUPPLY

HWUH HOT WATER UNIT HEATER

HVD HOISTWAY VENT DAMPER

HX HEAT EXCHANGER

HZ HERTZ

I/O INPUT/OUTPUT

IAQ INDOOR AIR QUALITY

IBT INVERTED BUCKET TRAP

ICF IN-LINE CENTRIFUGAL FAN

ICU INTENSIVE CARE UNIT

ID INSIDE DIAMETER

IFB INTEGRAL FACE AND BYPASS

IN INCHES

IN HG INCHES OF MERCURY

IN WC INCH WATER COLUMN

IN WG INCH WATER GAUGE

IN-LB INCH-POUND

IPLV INTERGRATED PART LOAD VALUE

IRH INTRARED HEATER

IS INSECT SCREEN

IU INDUCTION UNIT

IV INLET VANES

J INTENTIALLY LEFT BLANK

KG KILOGRAM

KG/HR KILOGRAM PER HOUR

kPa KILOPASCAL

KW KILOWATT

KWH KILOWATT HOUR

L LITER

L/h LITERS PER HOUR (or LITERS/HOUR) L/m LITERS PER MINUTE (or LITERS/MINUTE) L/s LITERS PER SECOND (or LITERS/SECOND)

LAT LEAVING AIR TEMPERATURE

LBS/HR POUNDS PER HOUR

LF LINEAR FOOT (FEET)

LGT LEAVING GLYCOL TEMPERATURE

LH LATENT HEAT

LPG LIQUEFIED PETROLEUM GAS

LPR LOW PRESSURE RETURN (STEAM CONDENSATE)

LPRC LOW PRESSURE STEAM RETURN (CLEAN)

LLHX LIQUID TO LIQUID HEAT EXCHANGER

LPS LOW PRESSURE STEAM

LPSC LOW PRESSURE STEAM (CLEAN)

LSD LINEAR SLOT DIFFUSER

LTCP LOCAL TEMPERATURE CONTROL PANEL

LVG LEAVING

LVR LOUVER

LWT LEAVING WATER TEMPERATURE

M METER, SI UNIT

M/S METERS PER SECOND (OR

METERS/SECOND)

MA MIXED AIR

MAT MIXED AIR TEMPERATURE

MAU MAKE-UP AIR UNIT

MAV MANUAL AIR VENT

MAX MAXIMUM

MB MIXING BOX

MBH 1,000 BTUH

MCA MINIMUM BRANCH CIRCUIT AMPACITY

MER MECHANICAL EQUIPMENT ROOM

MERV MINIMUM EFFICIENCY REPORTING VALUE

MH MANHOLE

MHP MOTOR HORSEPOWER

MIN MINIMUM

MM MILLIMETER

MOV MOTOR OPERATED VALVE

MPR MEDIUM PRESSURE RETURN (STEAM CONDENSATE)

MPS MEDIUM PRESSURE STEAM

MRI MAGNETIC RESONANCE IMAGING

MTD MEAN TEMPERATURE DIFFERENCE

MVD MANUAL VOLUME DAMPER

MZ MULTI-ZONE

NA NOT APPLICABLE

NC NOISE CRITERIA

NC NORMALLY CLOSED

NG NATURAL GAS

NGFM NATURAL GAS FLOWMETER

Nm NEWTON METER

NO NORMALLY OPEN

NOAA NATIONAL OCEANIC & ATMOSPHERIC

ADMINISTRATION

NOM NOMINAL

NPLV NON-STANDARD PART LOAD VALUE

NPSH NET POSITIVE SUCTION HEAD

NPSHA NET POSITIVE SUCTION HEAD AVAILABLE

NPSHR NET POSITIVE SUCTION HEAD REQUIRED

NTS NOT TO SCALE

OA OUTSIDE AIR

OAD OUTDOOR AIR DAMPER

OAG OUTSIDE AIR GRILLE

OAI OUTSIDE AIR INTAKE

OD OUTSIDE DIAMETER

OFM OIL FLOWMETER

OR OPERATING ROOM

UC UNDER CUT

UC UNIT COOLER

UH UNIT HEATER

U UNDERWRITERS LABORATORY

URV UPBLAST UNIT VENTILATOR

P PUMP

Pa PASCAL

PC PUMPED CONDENSATE

PCF POUNDS PER CUBIC FOOT (FEET)

PD PRESSURE DROP

PEF PROPELLER (TYPE) EXHAUST FAN

PF PRE-FILTER

PG PRESSURE GAGE

PGW PROPYLENE GLYCOL-WATER (SOLUTION)

PHC PREHEAT COIL

PPM PARTS PER MILLION

PRS PRESSURE REGULATING (VALVE) STATION

PRV PRESSURE REGULATING VALVE

PSI POUNDS PER SQUARE INCH

PSIA POUNDS PER SQUARE INCH – ABSOLUTE

PSIG POUNDS PER SQUARE INCH – GAGE

PSS PRIMARY SECONDARY SYSTEM

PSV PRESSURE SAFETY VALVE

PTAC PACKAGED TERMINAL AIR CONDITIONER

R/E RETURN OR EXHAUST

RA RETURN AIR

RAD RETURN AIR DAMPER

RAF RADIO FREQUENCY

RAHX ROTARY AIR HEAT EXCHANGER

RAT RETURN AIR TEMPERATURE

RCCH REMOTE CONDENSER CHILLER

RCU RECIPROCATING CHILLER UNIT

RD REFRIGERANT DISCHARGE

RDS ROOM DATA SHEETS

REA RELIEF AIR

RELAD RELIEF AIR DAMPER

RF RETURN FAN

RG RETURN GRILLE

RH RELATIVE HUMIDITY

RHC REHEAT COIL

RHG REFRIGERANT HOT GAS

RL REFRIGERANT LIQUID LINE

RLA RUN LOAD AMPERE

RO REVERSE OSMOSIS

RPM REVOLUTIONS PER MINUTE

RR RETURN REGISTER

RS REFRIGERANT SUCTION

RTU ROOF TOP UNIT

RV RELIEF VALVE

SA SUPPLY AIR

SAD SOUND ATTENUATING DEVICE

SAT SUPPLY AIR TEMPERATURE

SC SHADING COEFFICIENT

SCFM STANDARD CUBIC FEET PER MINUTE

SCI SPINAL CODE INJURY

SCR SILICON CONTROLLED RECTIFIER

SD SMOKE DETECTOR

SD SUPPLY AIR DIFFUSER

SD-1 SCHEMATIC DESIGN (SUBMISSION1)

SD-2 SCHEMATIC DESIGN (SUBMISSION2)

SDPR SMOKE DAMPER

SDR SMOKE DAMPER (RETURN)

SDS SMOKE DAMPER (SUPPLY)

SEN SENSIBLE HEAT

SF SUPPLY FAN

SG SUPPLY AIR GRILLE

SH STEAM HUMIDIFIER

SHC STEAM HEATING COIL

SI SQUARE INCHES

SP STATIC PRESSURE

SP GR SPECIFIC GRAVITY

SPD SUPPLY PROCESS AND DISTRIBUTION

SPRV STEAM PRESSURE REDUCING VALVE

SPS STATIC PRESSURE SENSOR

SQ FT SQUARE FOOT (FEET)

SR SUPPLY AIR REGISTER

SS STAINLESS STEEL

SSHX STEAM TO STEAM HEAT EXCHANGER

SSR SOLID SEPARATOR

ST STEAM TRAP

SUH STEAM UNIT HEATER

SV STEAM PRESSURE REDUCING VALVE

SVS STEAM VENT SILENCER

SW SOFTWATER

SWHX STEAM TO WATER HEAT EXCHANGER

T&PCV TEMPERATURE AND PRESSURE

CONTROL VALVE

TAB TESTING, ADJUSTING, BALANCE

TD TEMPERATURE DIFFERENCE

TDH TOTAL DYNAMIC HEAD

TDS TOTAL DISSOLVED SOLIDS

TG TRANSFER GRILLE

TP TRAP

TR TOP REGISTER

TSP TOTAL STATIC PRESSURE

TSTAT THERMOSTAT

TU TERMINAL UNIT

TWU THRU-WALL UNIT

UC UNDER CUT

UC UNIT COOLER

UH UNIT HEATER

U UNDERWRITERS LABORATORY

URV UPBLAST UNIT VENTILATOR

V VALVE

VAF VANE-AXIAL FAN

VAV VARIABLE AIR VOLUME

VD VOLUME DAMPER (MANUAL OPPOSED

BLADE)

VFD VARIABLE FREQUENCY…