Bid Docs_MEP DRAWINGS.pdf
PDF 9 MB Posted
- Solicitation number
- 36C25522R0033
About this file
This solicitation is for renovation services for Building 2 at the Jefferson Barracks Division VA Medical Center in St. Louis, Missouri. The contractor will renovate areas on the second floor north and all of the first floor, phasing work to complete the second floor followed by the first floor. The project costs range from $2 million to $5 million, with an estimated 457-day completion period. The NAICS code is 236220 with a small business size standard of $39.5 million. The solicitation will be posted to SAM on December 20, 2021. The successful offeror must perform at least 15% of construction labor. The award will use best value tradeoff and discussions are not planned but reserved if needed. The opportunity is a total SDVOSB set-aside following 38 USC 8127(d) and PL 109-461. Firms must register in SAM and VetBiz. A site visit will be scheduled and documented in the solicitation. Responses are due as specified therein.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 657-19-127JB_spec section 27 51 16.pdf | ||
| 36C25522R0033 0007.docx | DOCX document | |
| 657-19-127JB_Electrical plan changes.pdf | ||
| 657-19-127JB-2022.03.17_ADD-2.pdf | ||
| 36C25522R0033 0006.docx | DOCX document | |
| 1801901 Asbestos Mold Survey - Jefferson Building 2 (final).pdf | ||
| JB-2-Report.pdf | ||
| 36C25522R0033 0005.docx | DOCX document | |
| 36C25522R0033 0004.docx | DOCX document | |
| 36C25522R0033 0003.docx | DOCX document | |
| UpdatedSpecs_Vol1_revised 20211215.pdf | ||
| UpdatedSpecs_Vol2.pdf | ||
| 36C25522R0033.docx | DOCX document | |
| PastPerformanceQuestionnaire36C25522R0033Project657-19-127JB.docx | DOCX document | |
| Bid Docs_Arch.pdf |
Show all 15
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SPRINKLER HEADS TO BE INSTALLED IN
CENTER OF 2x2 CEILING TILES.
12"12"
SCALE: NONE
2x2 CEILING TILE DETAIL
12"
12"
RETURN BEND DETAIL
FIRE MAIN
SEMI RECESSED SPRINKLER
CEILING
SPRINKLER PIPE
SCALE: NONE
FIRE PROTECTION SYSTEM RISER
TO SPRINKLER HEADS IN
NEW ADDITION AND FUTURE
ADDITION.
TYPICAL MECHANICAL JOINT
COUPLING. REFER TO
SPECIFICATIONS.
ALARM CHECK VALVE WITH
PRESSURE GAUGES AND
SYSTEM MAIN DRAIN. REFER
TO SPECIFICATIONS.
SYSTEM DRAIN THRU
EXTERIOR WALL. REFER
TO FIRE PROTECTION
PLANS.
BUTTERFLY VALVE
WITH TAMPER SWITCH.
REFER TO SITE
UTILITIES PLAN FOR
CONTINUATION.
PROVIDE SPARE HEAD
CABINET WITH HEADS.
F P
F P
F P
TS
F S
ABBREVIATIONSGENERAL NOTES - FIRE PROTECTION
A. ALL AREAS SHALL BE PROTECTED BY A 100% WET PIPE FIRE SUPPRESSION
SYSTEM INSTALLED IN STRICT ACCORDANCE WITH NFPA-13, THE STATE
BUILDING CODES AND THE PROJECT SPECIFICATIONS.
B. ALL AREAS ARE PRESENTLY PROTECTED BY A 100% WET PIPE FIRE
SUPPRESSION SYSTEM. CONTRACTOR SHALL MODIFY THE SYSTEM AS
REQUIRED TO MAINTAIN 100% PROTECTION, IN ACCORDANCE WITH NFPA
13, STATE BUILDING CODE AND SPECIFICATIONS.
C. THE SUCCESSFUL FIRE PROTECTION CONTRACTOR SHALL OBTAIN AND
UTILIZE THE ARCHITECTURAL REFLECTED CEILING PLAN FOR LAYING OUT
THE SPRINKLER HEADS. THE REFLECTED CEILING PLANS SHOWN ARE TO
COORDINATE CEILING TYPES AND LOCATIONS. REFER TO THE MECHANICAL
AND ELECTRICAL DRAWINGS FOR CEILING DEVICE LOCATIONS. REFER TO
THE SPECIFICATIONS FOR COORDINATION DRAWING REQUIREMENTS.
D. INSTALL HEADS IN CENTER OF 2'X2' TILES. INSTALL HEADS ON 1/4 POINTS
OF THE 4' DIMENSION AND CENTER OF THE 2' DIMENSION IN 2'X4' TILES.
DO NOT MOUNT HEADS IN CENTER OF 2'X4' TILE IF IT IS SCORED TO LOOK
LIKE TWO 2'X2' TILES.
E. ALL SPRINKLER HEADS SHALL BE "SEMI-RECESSED", QUICK RESPONSE
SPRINKLER HEADS (UNLESS OTHERWISE NOTED ON THE PLANS.) HEADS
SHALL BE FED FROM A RETURN BEND ARRANGEMENT.
F. UTILIZE UPRIGHT AND/OR WALL-MOUNTED TYPE SPRINKLER HEADS IN
AREAS WITHOUT CEILINGS.
G. THE FIRE PROTECTION CONTRACTOR SHALL PERFORM HIS OWN FLOW TEST
PRIOR TO SUBMITTING SHOP DRAWINGS.
H. REFER TO A COMPLETE SET OF DOCUMENTS (ARCHITECTURAL,
STRUCTURAL, MECHANICAL AND ELECTRICAL PLANS AND SPECIFICAITONS)
FOR COORDINATION OF TRADES, ROOMS, STRUCTURE AND EQUIPMENT.
HVAC DUCTWORK MAINS SHALL BE INSTALLED PRIOR TO FIRE PROTECTION
PIPING. PROVIDE DRAIN VALVES IN THE FIRE PROTECTION SYSTEM WHERE
REQUIRED TO COMPLETELY DRAIN THE SYSTEM.
I. REFER TO THE SPECIFICATIONS FOR SPRINKLER HEAD TYPES.
J. PROVIDE ALL REQUIRED DRAIN PIPING TO TEST FLOW SWITCHES.
DISCHARGE DRAIN PIPING TO OUTDOORS OR A FLOOR DRAIN.
K. SIZE ALL FIRE PROTECTION PIPING IN ACCORDANCE WITH NFPA 13. PIPE
SIZING SHALL BE ACCOMPLISHED USING HYDRAULIC CALCULATIONS.
L. SUBMIT HYDRAULIC CALCULATIONS AND SYSTEMS DESIGN FOR REVIEW TO
THE M/E ENGINEER.
M. THE CONTRACTOR SHALL EXERCISE EXTREME CARE IN THE COURSE OF
THEIR WORK SO AS TO ENSURE THAT THEY DO NOT INTERRUPT ANY
EXISTING SERVICE. FOR SAFETY PURPOSES, PAY PARTICULAR ATTENTION
TO THIS PRECAUTION RELATIVE TO NATURAL GAS AND ELECTRICAL LINES.
VERIFY THE LOCATION, SIZE, TYPE, ETC., OF EACH UNDERGROUND OR
OVERHEAD UTILITY. ALL WORK SHALL BE PERFORMED IN ACCORD WITH
ALL FEDERAL, STATE AND/OR LOCAL RULES, REGULATIONS, STANDARD
AND SAFETY REQUIREMENTS.
N. WHERE WORK IS REQUIRED ABOVE EXISTING LAY-IN, PLASTER OR GYPSUM
BOARD CEILINGS, THE CONTRACTOR SHALL BE RESPONSIBLE FOR
REMOVAL AND REINSTALLATION (OR REPLACEMENT, IF DAMAGED) OF ALL
CEILING OR TILE AND GRID MEMBERS NECESSARY TO PERFORM HIS WORK.
NEW TILE AND GRID SHALL MATCH THE SURROUNDING AREAS. ALL
PATCHING WORK SHALL MATCH ADJACENT SURFACES.
O. ALL NEW WORK SHALL BE HUNG FROM STRUCTURE, NOT FROM THE WORK
OF OTHER TRADES, WHETHER EXISTING OR NEW.
P. COORDINATE ALL WORK WITH PROJECT PHASING REQUIREMENTS.
Q. PATCH, REPAIR AND PAINT OR PROVIDE WALL COVERING FOR (TO OWNER'S
STANDARDS) EXISTING WALLS, CEILINGS, ETC., THAT ARE TO REMAIN IF
DAMAGED DURING CONSTRUCTION. REPAIRS SHALL MATCH ADJACENT
SURFACES TO THE SATISFACTION OF THE ARCHITECT AND OWNER.
R. OBSERVE ALL APPLICABLE CODES, RULES AND REGULATIONS THAT MAY
APPLY TO THE WORK UNDER THIS CONTRACT. (CITY, COUNTY, LOCAL,
FEDERAL, MUNICIPALITY, UTILITY COMPANY, STATE, ETC.)
S. CONTRACTOR SHALL BE AWARE OF UNSEEN PLUMBING, HVAC AND
ELECTRICAL WORK DURING DEMOLITION. IF ITEMS ARE UNCOVERED
DURING DEMOLITION THEN FIELD VERIFY THE USE OF THE ITEMS AND
PLAN AN ALTERNATE ROUTE TO RUN THESE ITEMS. THEN CONTACT THE
ENGINEERS TO REVIEW THE ROUTING.
T. ALL PENETRATIONS OF FIRE AND SMOKE RATED ASSEMBLIES SHALL BE
APPROPRIATELY FIRE STOPPED PER AN APPROVED U.L. LISTED STANDARD.
CONTRACTOR SHALL PAY PARTICULAR ATTENTION TO INSULATED PIPING
PENETRATIONS.
U. ALL WORK REQUIRING DOWNTIME OF ANY AREA IN THE BUILDING SHALL
BE SCHEDULED 2 WEEKS IN ADVANCE, AND SHALL COMPLY WITH INTERIM
LIFE SAFETY MEASURES.
V. WHERE CEILINGS ARE INDICATED ALL SPRINKLER PIPING MUST BE
INSTALLED ABOVE CEILINGS. SPRINKLER PIPING MUST BE COORDINATED
WITH OTHER TRADES. PIPING MUST BE OFFSET TO AVOID CONFLICTS
WITH DUCTWORK, CONDUIT, ALL EQUIPMENT, ETC.
W. LOCATIONS OF PIPING, DUCTS AND EQUIPMENT ARE APPROXIMATE AND
SUBJECT TO MINOR ADJUSTMENTS IN THE FIELD. DO NOT SCALE THE
DRAWINGS.
X. ALL OFFSETS IN DUCTS AND PIPING ARE NOT NECESSARILY SHOWN.
PROVIDE ADDITIONAL OFFSETS WHERE NECESSARY.
Y. COORDINATE ALL HVAC WORK WITH ELECTRICAL, PLUMBING AND OTHER
TRADES TO AVOID INTERFERENCE WITH PIPING, DUCTS, CONDUIT AND
OTHER EQUIPMENT.
Z. SEAL AIRTIGHT AROUND ALL DUCTS AND PIPING PENETRATIONS THROUGH
WALLS, FLOORS AND ROOF. PROVIDE FIRE STOPPING IN FIRE PARTITION.
AA. THE CONTRACTOR SHALL RELOCATE OR AVOID ANY EXISTING EQUIPMENT
APPURTENANCES, ETC., THAT CONFLICT WITH NEW WORK.
BB. VALVES, BALANCING DAMPERS OR ANY MECHANICAL/ELECTRICAL ITEM
REQUIRING ACCESS SHALL NOT BE LOCATED ABOVE A HARD CEILING. IF
THIS IS NOT POSSIBLE, THEN AN APPROPRIATELY SIZED ACCESS DOOR
SHALL BE PLACED UNDER THE ITEM TO ALLOW EASY MAINTENANCE AND
ADJUSTMENT. ADDITIONALLY ALL SUCH ITEMS SHALL NOT BE LOCATED AN
UNREASONABLE DISTANCE ABOVE THE CEILINGS. IN GENERAL ALL SUCH
ITEMS UNLESS INDICATED OTHERWISE SHALL BE MOUNTED SIX TO TWELVE
INCHES ABOVE THE CEILING. IF IN DOUBT, CONTACT ENGINEER PRIOR TO
INSTALLING.
TAGGED NOTE DESIGNATOR
GENERAL SYMBOLS
X REVISION TRIANGLE
ROOM NAME
RM # ROOM TAG
AFF ABOVE FINISHED FLOOR
ADJ ADJUSTABLE
AHJ AUTHORITY HAVING JURISDICTION
ANSI AMERICAN NATIONAL STANDARD INSTITUTE
POINT OF CONNECTION / CONNECT TO EXISTING
POINT OF DEMOLITION
MECHANICAL PIPING LEGEND
ABBREVIATIONS (CONTINUED)
PIPE ELBOW TURNING DOWN
PIPE ELBOW TURNING UP
PIPE TEE; CONNECTION ON BOTTOM
PIPE TEE; CONNECTION ON TOP
EXISTING PIPING - (XXX) DENOTES SYSTEM
ABANDONED IN PLACE PIPING - (XXX) DENOTES SYSTEM
PIPING TO BE DEMOLISHED - (XXX) DENOTES SYSTEMD(XXX)
E(XXX)
A(XXX)
TS
FS
PS
CHECK VALVE
FLEXIBLE PIPE CONNECTION
FLOW SWITCH
PRESSURE SWTICH
TAMPER SWITCH
DOUBLE CHECK VALVE ASSEMBLY
PIPING UNION
PETE'S PLUG; TEMPERATURE/PRESSURE PORT
MANUAL ISOLATION VALVE
OS&Y (GATE) VALVE
STRAINER
PRESSURE REDUCING VALVE (STEAM, GAS, WATER, ETC.)
FIRE PROTECTION PIPINGFP
PIPE CAP
EQUIPMENT TAG
INSTANCE
TAG XXX-#
XXXX
CLG CEILING
CLR CLEAR
FLAT ON TOPFOT
FIRE PROTECTION CONTRACTORFPC
FEET OR FOOTFT
FUTUREFUT
GAGE/GAUGEGA
GALLON (-S)GAL
GENERAL CONTRACTORGC
HORIZONTALHORIZ
IRON PIPE SIZEIPS
INTER (-IOR, -ERVAL)INT
POUNDSLBS
LINEAR FEET/FOOTLF
MAXIMUMMAX
MANUFACTURERMFG
MIN (-IMUM, -UTE)MIN
MISCELLANEOUSMISC
MOUNTINGMTG
INCH (-ES)IN
ID I (-DENTIFICATION, -NSIDE DIAMETER, -NSIDE DIMENSION)
FLOORFL
FULL LOAD AMPSFLA
FLAT ON BOTTOMFOB
NOISE CRITERIA OR NORMALLY CLOSEDNC
NOT APPLICABLEN/A
NOT IN CONTRACTNIC
NORMALLY OPEN OR NUMBERNO
NOT TO SCALENTS
OUTSIDE DI (-AMETER, -MENSION)OD
CONTRACTOR FURNISHED, CONTRACTOR INSTALLEDCFCI
OWNER FURNISHED, CONTRACTOR INSTALLEDOFCI
OWNER FURNISHED, OWNER INSTALLEDOFOI
ON CENTEROC
PLUMBING CONTRACTORPC
PLUMBINGPLBG
PRESSURE REDUCING VALVE (STEAM, WATER, GAS)PRV
POUNDS PER SQUARE INCHPSI
POUNDS PER SQUARE FOOTPSF
PPSI GAUGEPSIG
TO BE DETERMINEDTBD
SQUARE FEET OR FOOTSQ FT
TOP ELEVATIONTE
TYPICALTYP
UNLESS NOTED OTHERWISEUNO
WEIGHTWT
WITHW/
WITHOUTW/O
PERCENT%
℄ CENTERLINE
DN DOWN
ENGR ENGINEER
EXT EXTERIOR
ETR EXISTING TO REMAIN
EQ EQUAL
FVC FIRE VALVE CABINET
SEMI-RECESSED SPRINKLER HEAD WITH REMOVABLE
ESCUTCHEON PLATE
UPRIGHT TYPE SPRINKLER HEAD
SIDEWALL TYPE SPRINKLER HEAD
E IN
I
SEIBERT
KENNETH L.
EETT
SS
TATA
FF MOO
P O
F R
SO
S
I
U
R
R E
E
S
NAL
SIO ENG
NUMBER
PE-2009005131
10411 Meeting Street, Prospect, Kentucky 40059 502 326.3085 f 502 326.2691 www.cmta.com th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing # of
657-19-127JBFCA - RENOVATE SPACE FOR
DOMICILIARY PROVIDERS, BUILDING 2
5/1/2020
VA Health Care System Approval:
BID DOCUMENTS
Revision: Date:
ARCHITECT/ENGINEER:
A/E: PROJECT LEAD
Architect, Structural Engineer
Consultant:
CMTA CONSULTING ENGINEERS
10411 MEETING STREET
PROSPECT, KY 40059
502.326.3085
JEFFERSON BARRACKS
1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125
/1
/2
:1
:1
A
M
02-FP-001
FIRE SUPPRESSION LEGEND
ISRBSB
MOST RECENT FLOW TEST DATE SHOWN BELOW.
INFORMATION IS OUTDATED AND LIMITED. SHOWN
FOR REFERENCE ONLY. CONTRACTOR TO PREFORM
NEW FLOW TEST AND SEND TO ENGINEER.
STATIC: 100 PSI
RESIDUAL: 85PSI
RECOVERY TIME: 1 SECOND
DATE: 6/16/2018
NEW FIRE SERVICE INTO BUILDING TO
SPRINKLER FIRST AND SECOND FLOOR
ONLY. THIRD FLOOR AND BASEMENT TO
BE SPRINKLERED IN FUTURE.
SPRINKLER
RISER
REFER TO SITE PLAN
FOR CONTINUATION.
E IN
I
SEIBERT
KENNETH L.
EETT
SS
TATA
FF MOO
P O
F R
SO
S
I
U
R
R E
E
S
NAL
SIO ENG
NUMBER
PE-2009005131
10411 Meeting Street, Prospect, Kentucky 40059 502 326.3085 f 502 326.2691 www.cmta.com th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing # of
657-19-127JBFCA - RENOVATE SPACE FOR
DOMICILIARY PROVIDERS, BUILDING 2
5/1/2020
VA Health Care System Approval:
BID DOCUMENTS
Revision: Date:
ARCHITECT/ENGINEER:
A/E: PROJECT LEAD
Architect, Structural Engineer
Consultant:
CMTA CONSULTING ENGINEERS
10411 MEETING STREET
PROSPECT, KY 40059
502.326.3085
JEFFERSON BARRACKS
1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125
/1
/2
:1
:1
A
M
02-FP-101
FIRE PROTECTION PLAN - FLOOR 00
ISRBSB
SCALE: 1/4" = 1'-0"02-FP-101
1 FIRE PROTECTION PLAN - FLOOR 00N
HATCHED AREA INDICATES AREA TO BE PROVIDED WITH A FULLY AUTOMATIC
WET SPRINKLER SYSTEM. ALL SPRINKLER RELATED WORK SHALL BE DONE IN
ACCORDANCE WITH NFPA 13 AND ALL STATE AND LOCAL CODES.
OFFICE
OFFICE
CORRIDOR
OFFICE
OFFICE
OFFICE
OFFICE
STORAGE/COPY
OFFICE
CORRIDOR
OFFICE
OFFICE
OFFICE
OFFICE
STAIR 1
VESTIBULE
ELEV LOBBY
ELEV LOBBY
ELEV
GROUP
COMPUTER
MECH
OIT
ELEC
MEN
WOMEN
OFFICE
MULTI-PURPOSE
STORAGE
STAIR 3
S103
STAIR 2
S133
CORRIDOR
INSTITUTIONAL SPRINKLERS ON FIRST FLOOR.
SPRINKLER
RISER, WITH
CONTROL
VALVE
LIGHT HAZARD
ORDINARY HAZARD,
GROUP 1
ORDINARY HAZARD,
GROUP 2
E IN
I
SEIBERT
KENNETH L.
EETT
SS
TATA
FF MOO
P O
F R
SO
S
I
U
R
R E
E
S
NAL
SIO ENG
NUMBER
PE-2009005131
10411 Meeting Street, Prospect, Kentucky 40059 502 326.3085 f 502 326.2691 www.cmta.com th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing # of
657-19-127JBFCA - RENOVATE SPACE FOR
DOMICILIARY PROVIDERS, BUILDING 2
5/1/2020
VA Health Care System Approval:
BID DOCUMENTS
Revision: Date:
ARCHITECT/ENGINEER:
A/E: PROJECT LEAD
Architect, Structural Engineer
Consultant:
CMTA CONSULTING ENGINEERS
10411 MEETING STREET
PROSPECT, KY 40059
502.326.3085
JEFFERSON BARRACKS
1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125
/1
/2
:1
:2
A
M
02-FP-111
FIRE PROTECTION PLAN - FLOOR 01
ISRBSB
SCALE: 1/4" = 1'-0"02-FP-111
1 FIRE PROTECTION PLAN - FLOOR 01N
HATCHED AREA INDICATES AREA TO BE PROVIDED WITH A FULLY AUTOMATIC
WET SPRINKLER SYSTEM. ALL SPRINKLER RELATED WORK SHALL BE DONE IN
ACCORDANCE WITH NFPA 13 AND ALL STATE AND LOCAL CODES.
OFFICE
OFFICE
OFFICE
MECH
CONFERENCE
KITCHENETTE
HAC
OIT
ELEC
ELEV
STORAGE
218A
STAIR 1
S200
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
WOMEN
MEN
SPRINKLER
RISER, WITH
CONTROL
VALVE
LIGHT HAZARD
ORDINARY HAZARD,
GROUP 1
COPY ROOM
E IN
I
SEIBERT
KENNETH L.
EETT
SS
TATA
FF MOO
P O
F R
SO
S
I
U
R
R E
E
S
NAL
SIO ENG
NUMBER
PE-2009005131
10411 Meeting Street, Prospect, Kentucky 40059 502 326.3085 f 502 326.2691 www.cmta.com th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing # of
657-19-127JBFCA - RENOVATE SPACE FOR
DOMICILIARY PROVIDERS, BUILDING 2
5/1/2020
VA Health Care System Approval:
BID DOCUMENTS
Revision: Date:
ARCHITECT/ENGINEER:
A/E: PROJECT LEAD
Architect, Structural Engineer
Consultant:
CMTA CONSULTING ENGINEERS
10411 MEETING STREET
PROSPECT, KY 40059
502.326.3085
JEFFERSON BARRACKS
1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125
/1
/2
:1
:2
A
M
02-FP-121
FIRE PROTECTION PLAN - FLOOR 02
ISRBSB
SCALE: 1/4" = 1'-0"02-FP-121
1 FIRE PROTECTION PLAN - FLOOR 02N
OFFICES
EXCLUDED FROM
SPRINKLER WORK.
P6
P7
P6
P8 P8
E (S
A N
E (S
A N
E(SAN)E(SAN)
E(CW)
E(SAN)
E(CW)
E(SAN)
E(CW)
E(SAN)
E(CW)
E (S
A N
E(S
AN
E (S
A N
E(CW)
6"ø
1 1/2"ø 1 1/2"ø
6"ø
1 1/2"ø
6"ø
E IN
I
SEIBERT
KENNETH L.
EETT
SS
TATA
FF MOO
P O
F R
SO
S
I
U
R
R E
E
S
NAL
SIO ENG
NUMBER
PE-2009005131
10411 Meeting Street, Prospect, Kentucky 40059 502 326.3085 f 502 326.2691 www.cmta.com th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing # of
657-19-127JBFCA - RENOVATE SPACE FOR
DOMICILIARY PROVIDERS, BUILDING 2
5/1/2020
VA Health Care System Approval:
BID DOCUMENTS
Revision: Date:
ARCHITECT/ENGINEER:
A/E: PROJECT LEAD
Architect, Structural Engineer
Consultant:
CMTA CONSULTING ENGINEERS
10411 MEETING STREET
PROSPECT, KY 40059
502.326.3085
JEFFERSON BARRACKS
1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125
/1
/2
:1
:2
A
M
02-PD-101
PLUMBING DEMOLITION PLAN - FLOOR
AuthorChecker
SCALE: 1/4" = 1'-0"02-PD-101
1 PLUMBING DEMOLITION PLAN - FLOOR 00
TAGGED NOTES
P6 DEMOLISH HOT WATER HEATER AND ALL HOT WATER PIPING
IN BASEMENT, FIRST FLOOR, AND SECOND FLOOR.
P7 DEMOLISH FIXTURE AND PIPING. CAP PIPING AT MAINS.
P8 DEMOLISH PIPING. CAP AT MAINS.
N
DEMOLITION NOTE: ALL DOMESTIC HOT WATER
PIPING SHALL BE DEMOLISHED. NEW WORK
INCLUDES POINT OF USE WATER HEATERS.
P7
P7
P8
P8
P8
P8
P8
P8
P8
P8
E IN
I
SEIBERT
KENNETH L.
EETT
SS
TATA
FF MOO
P O
F R
SO
S
I
U
R
R E
E
S
NAL
SIO ENG
NUMBER
PE-2009005131
10411 Meeting Street, Prospect, Kentucky 40059 502 326.3085 f 502 326.2691 www.cmta.com th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing # of
657-19-127JBFCA - RENOVATE SPACE FOR
DOMICILIARY PROVIDERS, BUILDING 2
5/1/2020
VA Health Care System Approval:
BID DOCUMENTS
Revision: Date:
ARCHITECT/ENGINEER:
A/E: PROJECT LEAD
Architect, Structural Engineer
Consultant:
CMTA CONSULTING ENGINEERS
10411 MEETING STREET
PROSPECT, KY 40059
502.326.3085
JEFFERSON BARRACKS
1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125
/1
/2
:1
:2
A
M
02-PD-111
PLUMBING DEMOLITION PLAN - FLOOR
AuthorChecker
SCALE: 1/4" = 1'-0"02-PD-111
1 PLUMBING DEMOLITION PLAN - FLOOR 01
TAGGED NOTES
P7 DEMOLISH FIXTURE AND PIPING. CAP PIPING AT MAINS.
P8 DEMOLISH PIPING. CAP AT MAINS.
N
P8
P1
P7
P7
P7
P7
P7
P7
P7
P7 P7 P8
P8
E IN
I
SEIBERT
KENNETH L.
EETT
SS
TATA
FF MOO
P O
F R
SO
S
I
U
R
R E
E
S
NAL
SIO ENG
NUMBER
PE-2009005131
10411 Meeting Street, Prospect, Kentucky 40059 502 326.3085 f 502 326.2691 www.cmta.com th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing # of
657-19-127JBFCA - RENOVATE SPACE FOR
DOMICILIARY PROVIDERS, BUILDING 2
5/1/2020
VA Health Care System Approval:
BID DOCUMENTS
Revision: Date:
ARCHITECT/ENGINEER:
A/E: PROJECT LEAD
Architect, Structural Engineer
Consultant:
CMTA CONSULTING ENGINEERS
10411 MEETING STREET
PROSPECT, KY 40059
502.326.3085
JEFFERSON BARRACKS
1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125
/1
/2
:1
:2
A
M
02-PD-121
PLUMBING DEMOLITION PLAN - FLOOR
AuthorChecker
SCALE: 1/4" = 1'-0"02-PD-121
1 PLUMBING DEMOLITION PLAN - FLOOR 02
TAGGED NOTES
P1 EXISTING FIXTURE TO REMAIN.
P7 DEMOLISH FIXTURE AND PIPING. CAP PIPING AT MAINS.
P8 DEMOLISH PIPING. CAP AT MAINS.
G
CA
FP
ORL
RL
GW
FM
SAN
SS
VT
E(NAME)
ABAN(NAME)
O
A
V
FD-#
RD-#
P-#
TS
FS
PS
BALANCING VALVE
BALL VALVE
CHECK VALVE
FLOW SWITCH
PRESSURE SWTICH
TAMPER SWITCH
THERMOMETER
DOUBLE CHECK VALVE ASSEMBLY
PIPING UNION
COMPRESSED AIR
FIRE PROTECTION LINE
SANITARY WASTE PIPING TO GREASE TRAP
OVERFLOW ROOF LEADER PIPING
ROOF LEADER PIPING
FORCED MAIN
GAS LINE
PETE'S PLUG
POINT OF CONNECTION
LIMIT OF DEMOLITION
OS&Y (GATE) VALVE
PIPE ELBOW TURNING UP/TURNING DOWN
PIPE TEE TURNING UP/TURNING DOWN
MEDICAL AIR
ABOVE FINISHED FLOOR
ABOVE FINISHED ROOFAFR
AFF
A, AIR
CARBON DIOXIDECO2
DOMESTIC COLD WATERCW
EVACUATION (WASTE ANESTHETIC GAS DISPOSAL)EV
FIRE HOSE VALVE WITH CABINETFHV
FREEZE PROOF WALL HYDRANTFPWH
HOSE BIBBHB
DOMESTIC HOT WATERHW
INSIDE DIMENSIONID
IN ACCORDANCE WITHIAW
INVERT ELEVATIONIE
LINE PRESSURE ALARM (MEDICAL GAS AREA ALARM)LPA
MANHOLEMH
MULTI-SINGLE ALARM (MEDICAL GAS MASTER ALARM)MSA
NOT TO SCALENTS
NOT IN CONTRACTNIC
NORMALLY OPENNO
NORMALLY CLOSEDNC
OXYGENO, OX
OUTSIDE DIMENSIONOD
OPEN RECEPTACLEOR
TOP ELEVATIONTE
TYPICALTYP
UNLESS OTHERWISE NOTEDUON
SANITARY WASTE PIPING
STORM SEWER PIPING
VENT PIPING
EXISTING PIPING (THIN LINE)
ABANDONED EXISTING PIPING (THIN LINE)
DOMESTIC COLD WATER PIPING
DOMESTIC HOT WATER SUPPLY
DOMESTIC RECIRCULATING HOT WATER
CLEANOUT IN CEILING SPACE
FLOOR CLEANOUT
EXTERIOR CLEANOUT
SYMBOLS & ABBREVIATIONS
CAST IRONC.I.
DOWNDN
OVERFLOW ROOF LEADERORL
PRESSURE REDUCING VALVE (STEAM, WATER, OR GAS)PRV
POUNDS PER SQUARE INCHPSI
DOMESTIC RECIRCULATING HOT WATERRHW
ROOF LEADERRL
SOFT DOMESTIC COLD WATERSCW
SANITARY RISERSR
THRUST BLOCKTB
TRAP PRIMERTP
VACUUMV, VAC
VENT THRU ROOFVTR
OWNER FURNISHED, CONTRACTOR INSTALLEDOFCI
OWNER FURNISHED, OWNER INSTALLEDOFOI
CONTRACTOR FURNISHED, CONTRACTOR INSTALLEDCFCI
CO
CO
ECO
OXYGEN PIPING
MEDICAL AIR
VACUUM PIPING
FLOOR DRAIN DESIGNATOR
ROOF DRAIN DESIGNATOR
PLUMBING FIXTURE DESIGNATOR
XXX
X
EQUIPMENT TAG DESIGNATOR
PRESSURE REDUCING VALVE (STEAM, GAS, WATER, ETC.)
STRAINER
X TAGGED NOTE DESIGNATOR
X REVISION DESIGNATOR
SAFETY RELIEF VALVE
SAFETY RELIEF VALVE
LIMITED AREA SPRINKLER HEAD
VACUUM BREAKERV
X S
TEMPERATURE SENSOR
HOSE BIB
MOP SINK DETAIL
PROVIDE CHECK
VALVES
BALL
3/4" HW AND CW
NOT TO SCALE
VALVES
WATER HAMMER
ARRESTOR (TYPICAL)
FAUCET WITH INTEGRAL
VACUUM BREAKER
MOP
BASIN
E IN
I
SEIBERT
KENNETH L.
EETT
SS
TATA
FF MOO
P O
F R
SO
S
I
U
R
R E
E
S
NAL
SIO ENG
NUMBER
PE-2009005131
10411 Meeting Street, Prospect, Kentucky 40059 502 326.3085 f 502 326.2691 www.cmta.com th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing # of
657-19-127JBFCA - RENOVATE SPACE FOR
DOMICILIARY PROVIDERS, BUILDING 2
5/1/2020
VA Health Care System Approval:
BID DOCUMENTS
Revision: Date:
ARCHITECT/ENGINEER:
A/E: PROJECT LEAD
Architect, Structural Engineer
Consultant:
CMTA CONSULTING ENGINEERS
10411 MEETING STREET
PROSPECT, KY 40059
502.326.3085
JEFFERSON BARRACKS
1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125
/1
/2
:1
:2
A
M
02-PL-001
PLUMBING LEGEND
ISRBSB
HAZARDOUS MATERIAL NOTE:
A. THE CONTRACTOR IT IS HEREBY ADVISED THAT IS POSSIBLE THAT
ASBESTOS AND/OR OTHER HAZARDOUS MATERIALS ARE OR WERE
PRESENT IN THIS BUILDING(S). ANY WORKER, OCCUPANT, VISITOR,
ETC., WHO ENCOUNTERS ANY MATERIAL OF WHOSE CONTENT THEY
ARE NOT CERTAIN SHALL PROMPTLY REPORT THE EXISTENCE AND
LOCATION OF THAT MATERIAL TO THE OWNER. FURTHERMORE, THE
CONTRACTOR SHALL INSURE THAT NO ONE COMES NEAR TO OR IN
CONTACT WITH ANY SUCH MATERIAL OR FUMES THEREFROM UNTIL ITS
CONTENT CAN BE ASCERTAINED TO BE NON-HAZARDOUS.
B. CMTA, INC. HAS NO EXPERTISE IN THE DETERMINATION OF THE
PRESENCE OF ANY HAZARDOUS MATERIAL. THEREFORE, NO ATTEMPT
HAS BEEN MADE BY CMTA TO IDENTIFY THE EXISTENCE OR LOCATION
OF ANY SUCH HAZARDOUS MATERIAL. FURTHERMORE, CMTA NOR ANY
AFFILIATE HEREOF WILL NOT OFFER OR MAKE ANY
RECOMMENDATIONS RELATIVE TO THE REMOVAL, HANDLING OR
DISPOSAL OF SUCH MATERIAL.
C. IF THE WORK WHICH IS TO BE PERFORMED INTERFACES, CONNECTS OR
RELATES IN ANY PHYSICAL WAY WITH OR TO EXISTING COMPONENTS
WHICH CONTAIN OR BEAR ANY HAZARDOUS MATERIAL, ASBESTOS
BEING ONE, THEN IT SHALL BE THE CONTRACTOR'S SOLE
RESPONSIBILITY TO CONTACT THE OWNER AND SO ADVISE HIM/HER
IMMEDIATELY.
D. THE CONTRACTOR BY EXECUTION OF THE CONTRACT FOR ANY WORK
AND/OR BY THE ACCOMPLISHMENT OF ANY WORK THEREBY AGREE TO
BRING NO CLAIM RELATIVE TO HAZARDOUS MATERIALS FOR
NEGLIGENCE, BREACH OF CONTRACT, INDEMNITY, OR ANY OTHER
SUCH ITEM AGAINST CMTA, ITS PRINCIPALS, EMPLOYEES, AGENTS OR
CONSULTANTS. ALSO, THE CONTRACTOR FURTHER AGREES TO
DEFEND, INDEMNIFY AND HOLD CMTA, ITS PRINCIPALS, EMPLOYEES,
AGENTS AND CONSULTANTS HARMLESS FROM ANY SUCH RELATED
CLAIMS WHICH MAY BE BROUGHT BY ANY SUBCONTRACTORS,
SUPPLIERS OR ANY OTHER THIRD PARTIES.
E. THE CONTRACTOR IS DIRECTED TO THE SPECIFICATIONS FOR FURTHER
INFORMATION.
PLUMBING GENERAL NOTES:
A. COORDINATE THE LOCATION OF DRAINS, THERMOSTATS, GAS
OUTLETS, ETC., WITH ALL CASEWORK EQUIPMENT,
MECHANICAL ROOM EQUIPMENT, ETC., PRIOR TO COMMENCING
INSTALLATION. WORK NOT SO COORDINATED SHALL BE
REMOVED AND PROPERLY INSTALLED AT THE EXPENSE OF THE
CONTRACTOR.
B. THE CONTRACTOR SHALL EXERCISE EXTREME CARE IN THE
COURSE OF THEIR WORK SO AS TO ENSURE THAT THEY DO
NOT INTERRUPT ANY EXISTING SERVICE. FOR SAFETY
PURPOSES, PAY PARTICULAR ATTENTION TO THIS PRECAUTION
RELATIVE TO NATURAL GAS AND ELECTRICAL LINES. VERIFY
THE LOCATION, SIZE, TYPE, ETC., OF EACH UNDERGROUND OR
OVERHEAD UTILITY. ALL WORK SHALL BE PERFORMED IN
ACCORD WITH ALL FEDERAL, STATE AND/OR LOCAL RULES,
REGULATIONS, STANDARD AND SAFETY REQUIREMENTS.
UTILITIES SHALL BE INSTALLED IN ACCORD WITH THE
APPLICABLE MUNICIPALITY OR UTILITY COMPANY STANDARDS.
IN ALL CASES, THE MOST STRINGENT REQUIREMENT SHALL
APPLY.
C. WHERE WORK IS REQUIRED ABOVE EXISTING LAY-IN, PLASTER
OR GYPSUM BOARD CEILINGS, THE CONTRACTOR SHALL BE
RESPONSIBLE FOR REMOVAL AND REINSTALLATION (OR
REPLACEMENT, IF DAMAGED) OF ALL CEILING OR TILE AND
GRID MEMBERS NECESSARY TO PERFORM HIS WORK. NEW
TILE AND GRID SHALL MATCH THE SURROUNDING AREAS. ALL
PATCHING WORK SHALL MATCH ADJACENT SURFACES.
D. ALL NEW WORK SHALL BE HUNG FROM STRUCTURE, NOT FROM
THE WORK OF OTHER TRADES, WHETHER EXISTING OR NEW.
E. COORDINATE ALL WORK WITH PROJECT PHASING
REQUIREMENTS.
F. PATCH, REPAIR AND PAINT OR PROVIDE WALL COVERING FOR
(TO OWNER'S STANDARDS) EXISTING WALLS, CEILINGS, ETC.,
THAT ARE TO REMAIN IF DAMAGED DURING CONSTRUCTION.
REPAIRS SHALL MATCH ADJACENT SURFACES TO THE
SATISFACTION OF THE ARCHITECT AND OWNER.
G. OBSERVE ALL APPLICABLE CODES, RULES AND REGULATIONS
THAT MAY APPLY TO THE WORK UNDER THIS CONTRACT.
(CITY, COUNTY, LOCAL, FEDERAL, MUNICIPALITY, UTILITY
COMPANY, ETC.)
H. CONTRACTOR SHALL BE AWARE OF UNSEEN PLUMBING WORK
DURING DEMOLITION. IF ITEMS ARE UNCOVERED DURING
DEMOLITION THEN FIELD VERIFY THE USE OF THE ITEMS AND
PLAN AN ALTERNATE ROUTE TO RUN THESE ITEMS. THEN
CONTACT THE ENGINEERS TO REVIEW THE ROUTING.
I. WHERE FIRE PROOFING IS SPRAYED ON EXISTING STRUCTURE
ALL EXISTING CONDUITS, WATER, HYDRONIC, STEAM, CHILLED
WATER, FIRE PROTECTION LINES, MED GAS, ETC. SHALL BE
LOWERED TO BE BELOW FULL THICKNESS OF FIRE PROOFING
WITH NO INTERFERENCE.
J. ALL PENETRATIONS OF FIRE AND SMOKE RATED ASSEMBLIES
SHALL BE APPROPRIATELY FIRE STOPPED PER AN APPROVED
U.L. LISTED STANDARD. CONTRACTOR SHALL PAY PARTICULAR
ATTENTION TO INSULATED PIPING PENETRATIONS.
K. ALL WORK REQUIRING DOWNTIME OF ANY AREA IN THE
BUILDING SHALL BE SCHEDULED 2 WEEKS IN ADVANCE, AND
SHALL COMPLY WITH INTERIM LIFE SAFETY MEASURES.
L. ALL PIPING IN ROOMS WITH CEILINGS SHALL BE ABOVE CEILING
EXCEPT AS NOTED.
M. LOCATIONS OF PIPING AND EQUIPMENT ARE APPROXIMATE AND
SUBJECT TO MINOR ADJUSTMENTS IN THE FIELD. DO NOT
SCALE THE DRAWINGS.
N. ALL OFFSETS IN PIPING ARE NOT NECESSARILY SHOWN.
PROVIDE ADDITIONAL OFFSETS WHERE NECESSARY.
O. THE CONTRACTOR IS RESPONSIBLE FOR ALL UTILITY COMPANY
FEES OR OTHER COSTS THAT ANY UTILITY COMPANY MAY
REQUIRE TO COMPLETE THEIR WORK. (GAS, SEWER, WATER,
ETC.).
P. WHERE MOUNTING HEIGHTS ARE NOT INDICATED OR ARE IN
CONFLICT WITH ANY OTHER BUILDING SYSTEM, CONTACT THE
ENGINEERS BEFORE INSTALLATION. REFER ALSO TO
ARCHITECTURAL WALL INTERIOR AND EXTERIOR WALL
ELEVATIONS, CEILING HEIGHTS AND OTHER DETAIL OF THESE
DOCUMENTS.
Q. DEVIATIONS IN SIZE, CAPACITIES, FIT, FINISH, ETC. FOR
EQUIPMENT FROM THAT USED AS BASIS OF DESIGN SHALL BE
THE RESPONSIBILITY OF THE PURCHASER OF THAT
EQUIPMENT. ANY PROVISIONS REQUIRED TO ACCOMMODATE A
DEVIATION, WHETHER APPROVED BY THE ENGINEERS OR NOT,
SHALL BE THE RESPONSIBILITY OF THE PURCHASER.
R. VALVES, BALANCING DAMPERS OR ANY
MECHANICAL/ELECTRICAL ITEM REQUIRING ACCESS SHALL NOT
BE LOCATED ABOVE A HARD CEILING. IF THIS IS NOT POSSIBLE,
THEN AN APPROPRIATELY SIZED ACCESS DOOR SHALL BE
PLACED UNDER THE ITEM TO ALLOW EASY MAINTENANCE AND
ADJUSTMENT. ADDITIONALLY ALL SUCH ITEMS SHALL NOT BE
LOCATED AN UNREASONABLE DISTANCE ABOVE THE CEILINGS.
IN GENERAL ALL SUCH ITEMS UNLESS INDICATED OTHERWISE
SHALL BE MOUNTED SIX TO TWELVE INCHES ABOVE THE
CEILING. IF IN DOUBT, CONTACT ENGINEER PRIOR TO
INSTALLING.
PLUMBING DEMOLITION NOTES:
A. THE CONTRACTOR SHALL REFER TO THE ARCHITECTURAL PLANS FOR
AREAS IN WHICH THE CEILING IS REMAINING. THE CONTRACTOR IS
RESPONSIBLE FOR REMOVING THE EXISTING CEILING AS REQUIRED AND
REINSTALLATION. TEMPORARILY SUPPORT LIGHTS, DIFFUSERS, CEILING
ETC. REPLACE BROKEN CEILING TILES WITH NEW AT NO ADDITIONAL COST
TO OWNER. FIELED VERIFY EXACT REQUIREMENTS.
B. ALL OUTAGES SHALL BE SCHEDULED THROUGH THE PROJECT
REPRESENTATIVE FOR PROPER COORDINATION. A REQUEST FOR AN
OUTAGE SHALL BE SUBMITTED IN WRITING A MINIMUM OF TWO WEEKS IN
ADVANCE.
C. DURING SPRINKLER SYSTEM OUTAGES THE CONTRACTORS SHALL
PROVIDE FIRE WATCH OF AREAS WITH OUTAGES.
D. ALL WALLS AND FLOOR SLABS SHALL BE REPAIRED TO MATCH EXISTING
AND TO A LIKE NEW CONDITION. ALL RATED WALLS AND FLOOR SLABS
SHALL BE PATCHED AND REPAIRED TO MAINTAIN RATING.
E. ALL EXISTING BUILDING FINISHES SHALL BE PROTECTED DURING THE
DEMOLITION PHASE.
F. HEAVY DASHED LINES INDICATE ITEMS FOR REMOVAL (U.O.N) AND LIGHT
SOLID LINES INDICATE EXISTING ITEMS TO REMAIN.
G. COORDINATE DISPOSAL OF ALL FIXTURES, DEVICES, ETC. (INDICATED FOR
DEMOLITION) WITH THE OWNER.
WATER HEATER SCHEDULE
TAG SERVING MANUFACTURER MODEL
WH-1 MOP SINKS AO SMITH DEL-10
WH-2 TWO SINKS CHRONOMITE CM-40L
WH-3 SINGLE SINK CHRONOMITE CM-20L
PLUMBING FIXTURE SCHEDULE
Mark Description Accessories
P-103 WATER CLOSET WALL CARRIER - 1.28 GPF
P-201 URINAL WALL CARRIER - .5 GPF
P-401 LAVATORY GRID STRAINER, P-TRAP, TRAP GUARD, CHROME ANGLE STOPS - 1.0 GPM
P-502 MOP SINK MOP HANGER - 3.0 GPM
P-524 KITCHEN SINK GRID STRAINER, P-TRAP, TRAP GUARD, CHROME ANGLE STOPS - 2.2 GPM
P-528 HAND SINK GRID STRAINER, P-TRAP, TRAP GUARD, CHROME ANGLE STOPS - 1.0 GPM
ALL SYMBOLS AND VALVE MAY NOT BE USED ON THIS PROJECT.
CAP
E(CW)
E (C
W
E (C
W
E (C
W
E(CW)
E (S
A N
E(CW)
E(CW)
CAP
P2
P2
P2
2" SAN
P4
P2
P1 P1
P4
E(SAN) E(SAN) E(SAN) E(SAN) E(SAN)
E
(SA
N
E(S
AN
E (S
A N
E (S
A N
E(S
AN
STORAGE
G07
MECH RM
G08
STORAGE
G06
STORAGE
G07A
HAC
G05B
TOILET
G05A
STORAGE
G05
CORRIDOR
H003
TRANSFORMER
G09
ELEV EQUIP
G01 ELEV
E-00
CORRIDOR
H002
STORAGE
G03
CORRIDOR
H001
OIT
G04
STORAGE
G02
STORAGE
G02B
STORAGE/COPY ROOM
G02A
WH-3
P3
E IN
I
SEIBERT
KENNETH L.
EETT
SS
TATA
FF MOO
P O
F R
SO
S
I
U
R
R E
E
S
NAL
SIO ENG
NUMBER
PE-2009005131
10411 Meeting Street, Prospect, Kentucky 40059 502 326.3085 f 502 326.2691 www.cmta.com th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing # of
657-19-127JBFCA - RENOVATE SPACE FOR
DOMICILIARY PROVIDERS, BUILDING 2
5/1/2020
VA Health Care System Approval:
BID DOCUMENTS
Revision: Date:
ARCHITECT/ENGINEER:
A/E: PROJECT LEAD
Architect, Structural Engineer
Consultant:
CMTA CONSULTING ENGINEERS
10411 MEETING STREET
PROSPECT, KY 40059
502.326.3085
JEFFERSON BARRACKS
1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125
/1
/2
:1
:2
A
M
02-PL-101
PLUMBING PLAN - FLOOR 00
ISRBSB
SCALE: 1/4" = 1'-0"02-PL-101
1 PLUMBING PLAN - FLOOR 00
TAGGED NOTES
P1 EXISTING FIXTURE TO REMAIN.
P2 CONNECT NEW PIPING INTO EXISTING PIPING AS SHOWN.
VERIFY EXACT LOCATION IN FIELD.
P3 INSTALL NEW POINT OF USE WATER HEATER (SEE SCHEDULE)
FOR FIXTURE AS SHOWN.
P4 CAP PIPING AT LOCATION SHOWN.
TMV'S SHALL BE INSTALLED ON ALL SINKS.
WH-1
P-103P-103
P-103
P-103
P-401
P-401
P-401
P-502
4" SAN
P-201
P-201
WH-3
WH-2
SAN UP
TO T12
SAN UP
TO SK1
P5
P3
P3
VENT UP
OFFICE
CORRIDOR
OFFICE
STORAGE/COPY
OFFICE
OFFICE
CORRIDOR
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
MECH
OIT
ELEC
ELEV LOBBY
ELEV
ELEV LOBBY
STAIR 1
GROUP
COMPUTER
WOMEN
MEN
MULTI-PURPOSE
STORAGE
JAN
3/4" CW
2" SAN
E IN
I
SEIBERT
KENNETH L.
EETT
SS
TATA
FF MOO
P O
F R
SO
S
I
U
R
R E
E
S
NAL
SIO ENG
NUMBER
PE-2009005131
10411 Meeting Street, Prospect, Kentucky 40059 502 326.3085 f 502 326.2691 www.cmta.com th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing # of
657-19-127JBFCA - RENOVATE SPACE FOR
DOMICILIARY PROVIDERS, BUILDING 2
5/1/2020
VA Health Care System Approval:
BID DOCUMENTS
Revision: Date:
ARCHITECT/ENGINEER:
A/E: PROJECT LEAD
Architect, Structural Engineer
Consultant:
CMTA CONSULTING ENGINEERS
10411 MEETING STREET
PROSPECT, KY 40059
502.326.3085
JEFFERSON BARRACKS
1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125
/1
/2
:1
:2
A
M
02-PL-111
PLUMBING PLAN - FLOOR 01
ISRBSB
SCALE: 1/4" = 1'-0"02-PL-111
1 PLUMBING PLAN - FLOOR 01
TAGGED NOTES
P3 INSTALL NEW POINT OF USE WATER HEATER (SEE SCHEDULE)
FOR FIXTURE AS SHOWN.
P5 INSTALL NEW TANK WATER HEATER ON SHELF ABOVE MOP
SINK TO SUPPLY MOP SINKS ON FLOORS 1 AND 2.
1 1/2" VT
3" VT
2" VT
WH-2
WH-3
P-502
P-103 P-103
P-103
P-103
P-401
P-401
P-401
P3
P3
P3
CUBICLE BAY
CORRIDOR
OFFICE
OFFICE
OFFICE
OFFICE
CONFERENCE
MECH
KITCHENETTE
HAC
COPY ROOM
ELEV
STORAGE
218A
OIT
ELEC
MEN
WOMEN
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
1 1/2" VT
3/4" CW
WH-3
P-524
PROVIDE DUAL CHECK VALVE
BEFORE CONNECTION TO
EQUIPMENT.
E IN
I
SEIBERT
KENNETH L.
EETT
SS
TATA
FF MOO
P O
F R
SO
S
I
U
R
R E
E
S
NAL
SIO ENG
NUMBER
PE-2009005131
10411 Meeting Street, Prospect, Kentucky 40059 502 326.3085 f 502 326.2691 www.cmta.com th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing # of
657-19-127JBFCA - RENOVATE SPACE FOR
DOMICILIARY PROVIDERS, BUILDING 2
5/1/2020
VA Health Care System Approval:
BID DOCUMENTS
Revision: Date:
ARCHITECT/ENGINEER:
A/E: PROJECT LEAD
Architect, Structural Engineer
Consultant:
CMTA CONSULTING ENGINEERS
10411 MEETING STREET
PROSPECT, KY 40059
502.326.3085
JEFFERSON BARRACKS
1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125
/1
/2
:1
:2
A
M
02-PL-121
PLUMBING PLAN - FLOOR 02
ISRBSB
SCALE: 1/4" = 1'-0"02-PL-121
1 PLUMBING PLAN - FLOOR 02
TAGGED NOTES
P3 INSTALL NEW POINT OF USE WATER HEATER (SEE SCHEDULE)
FOR FIXTURE AS SHOWN.
WH-3
WH-3
4" VT
E(CW)
1/2" CW
P2
P3
P1
P1 P1 P3
OFFICE
OFFICE
OFFICE
310A
OFFICE
OFFICE
316A
OFFICE
OFFICE
TOILET
CORRIODR
H303
KITCHENETTE
STAIR 1
S301
MECH. RM
OFFICE
CORRIDOR
H302
OFFICE
OFFICE
OFFICE
302A
CORRIDOR
H301
OFFICE
OFFICE
OFFICE
307A
OFFICE
OFFICE
E IN
I
SEIBERT
KENNETH L.
EETT
SS
TATA
FF MOO
P O
F R
SO
S
I
U
R
R E
E
S
NAL
SIO ENG
NUMBER
PE-2009005131
10411 Meeting Street, Prospect, Kentucky 40059 502 326.3085 f 502 326.2691 www.cmta.com th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing # of
657-19-127JBFCA - RENOVATE SPACE FOR
DOMICILIARY PROVIDERS, BUILDING 2
5/1/2020
VA Health Care System Approval:
BID DOCUMENTS
Revision: Date:
ARCHITECT/ENGINEER:
A/E: PROJECT LEAD
Architect, Structural Engineer
Consultant:
CMTA CONSULTING ENGINEERS
10411 MEETING STREET
PROSPECT, KY 40059
502.326.3085
JEFFERSON BARRACKS
1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125
/1
/2
:1
:2
A
M
02-PL-131
PLUMBING PLAN - FLOOR 03
ISRBSB
SCALE: 1/4" = 1'-0"02-PL-131
1 PLUMBING PLAN - FLOOR 03
TAGGED NOTES
P1 EXISTING FIXTURE TO REMAIN.
P2 CONNECT NEW PIPING INTO EXISTING PIPING AS SHOWN.
VERIFY EXACT LOCATION IN FIELD.
P3 INSTALL NEW POINT OF USE WATER HEATER (SEE SCHEDULE)
FOR FIXTURE AS SHOWN.
S A
N
P-502
P-502
P-103
P-201 P-201
P-401
P-103
P-103
P-103 P-401
P-401
P-401 P-401
1 1/2" VT
1 1/2" VT1 1/2" VT
2" SAN
2" SAN
1 1/2" VT
1 1/2" VT
2" SAN
2" SAN
2" SAN
2" VT
3" VT
2" VT
1 1/2" VT
1 1/2" VT
1 1/2" VT
2" SAN
4" SAN
4" SAN
2" VT
2" VT
3" VT
3" VT
3" VT
VTR
E(S
AN)
E(S
AN)
E(SAN)
E (S
A N
E(S
AN)
E(SAN)
E(SAN)
E(S
AN)
E (S
A N
E (S
A N
E(SAN)
E(S
AN)
E (S
A N
)E(S
AN)
E(C W
E(C W
E(CW
E(CW
E (C
W
P-502
WH-3
P-502
WH-1
C W
3/4" CW
1 1/2" CW
3/4" CW
1/2" CW
1/2" CW
1/2" CW
1/2" CW
1/2" CW
WH-2
P-103
P-103 P-103
P-103
P-401 P-201
P-201
1 1/2" CW
1 1/2" CW
WH-3
WH-1
P-103 P-201
P-201 P-401
P-103
P-103 P-103 P-401
P-401
3/4" CW
WH-3
E(C W
E(C W
E(CW
E(C W
EX SINK
EX LAV
EX WC
E IN
I
SEIBERT
KENNETH L.
EETT
SS
TATA
FF MOO
P O
F R
SO
S
I
U
R
R E
E
S
NAL
SIO ENG
NUMBER
PE-2009005131
10411 Meeting Street, Prospect, Kentucky 40059 502 326.3085 f 502 326.2691 www.cmta.com th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing # of
657-19-127JBFCA - RENOVATE SPACE FOR
DOMICILIARY PROVIDERS, BUILDING 2
5/1/2020
VA Health Care System Approval:
BID DOCUMENTS
Revision: Date:
ARCHITECT/ENGINEER:
A/E: PROJECT LEAD
Architect, Structural Engineer
Consultant:
CMTA CONSULTING ENGINEERS
10411 MEETING STREET
PROSPECT, KY 40059
502.326.3085
JEFFERSON BARRACKS
1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125
/1
/2
:1
:3
A
M
02-PL-401
PLUMBING ISOMETRIC
ISRBSB
SCALE:02-PL-401
1 PLUMBING ISOMETRIC - WASTE & VENT
SCALE:02-PL-401
2 PLUMBING ISOMETRIC - UTILITIES
QUICK-COUPLE HOSE CONNECTOR
ANCHOR
REDUCER OR INCREASER
DIRECTION OF FLOW
SIDE CONNECTION
ECCENTRIC REDUCER
BOTTOM CONNECTION, 45° OR 90°
TOP CONNECTION, 45° OR 90°
DIRECTION OF PIPE PITCH (DOWN)
UNION
RISE OR DROP IN PIPE
CAPPED OUTLET
PRESSURE GAGE
THERMOMETER
VENTURI FLOW METER
FLOAT & THERMOSTATIC TRAP SET INCLUDING
PIPING ACCESSORIES SEE DETAIL
PIPING ACCESSORIES SEE DETAIL
INVERTED BUCKET TRAP SET INCLUDING
PIPE UP
PIPE DOWN
REFRIGERANT SIGHT GLASS
TEST PLUG (PRESSURE/TEMPERATURE)
AUTOMATIC AIR VENT
AV
MANUAL AIR VENT
MV
THERMOSTATIC TRAP SET INCLUDING
PIPING ACCESSORIES SEE DETAIL
GENERAL PIPING SYMBOLS
HIGH PRESSURE STEAM CONDENSATE RETURN
HIGH PRESSURE STEAM (60 PSIG AND ABOVE)
HOT WATER HEATING SUPPLY
CONDENSATE PUMP DISCHARGE
LOW PRESSURE STEAM CONDENSATE RETURN
LOW PRESSURE STEAM (15 PSIG AND BELOW)
MEDIUM PRESSURE STEAM CONDENSATE RETURN
MEDIUM PRESSURE STEAM (16 PSIG THRU 59 PSIG)
VENT LINE
GLYCOL-WATER HEATING RETURN
GLYCOL-WATER HEATING SUPPLY
CHILLED WATER SUPPLY
CHILLED WATER RETURN
DRAIN LINE
MAKE-UP WATER
HOT WATER HEATING RETURN
S-60
CR-60
S-30
CR-30
S-15
CR-15
PC
HWS
HWR
GHS
GHR
V
CHR
CHS
MW
D
X EXISTING PIPE TO BE REMOVED
PIPING ABBREVIATIONS
PLUG VALVE
CONTROL VALVE (CV) - FLOAT-OPERATED
PRESSURE REDUCING VALVE (PRV)
WATER LEVEL CONTROLLER
FLOW METER
LC
M
BALL VALVE
GATE VALVE WITH 3/4" HOSE ADAPTER
CHECK VALVE
BUTTERFLY VALVE
MODULATING CONTROL VALVE
TWO POSITION CONTROL VALVE
THREE-WAY MODULATING CONTROL VALVE
AUTOMATIC BALANCING CONTROL VALVE
PRESSURE SAFETY VALVE
GATE VALVE - THREADED/FLANGED
PRESSURE REGULATING VALVE
THREE-WAY TWO POSITION CONTROL VALVE
WYE STRAINER (WITH BALL VALVE & HOSE CONNECTION)
FLEXIBLE CONNECTION
WATER BALANCE DEVICE
MODULATING CONTROL BUTTERFLY VALVE
CIRCUIT SETTER VALVE
WYE STRAINER WITH VALVED DRAIN AND QUICK-COUPLE
HOSE CONNECTOR
VALVE SYMBOLS
LIMIT OF DEMOLITION
DN
DN
UP
UP
SUPPLY DUCT (UP & DOWN)
EXHAUST DUCT (UP & DOWN)
4-WAY CEILING DIFFUSERS
CONNECT NEW DUCT TO EXISTING DUCT
DNUP RETURN DUCT (UP & DOWN)
DUCTWORK SYMBOLS
BACK DRAFT DAMPER
BDD
FC
10x8
FLEXIBLE CONNECTION, EQUIPMENT,
VANED ELBOW (PROVIDE ALL SQUARE OR
RECTANGULAR ELBOWS WITH VANES EVEN IF
SYMBOL IS MISSING)
VANED ELBOW (SHORT RADIUS)
STANDARD RADIUS ELBOW (LONG RADIUS)
NEW DUCT (INSIDE DIMENSIONS: WIDTH x DEPTH)
EXISTING DUCT TO REMAIN
FIRE DAMPER
FD
VD
MANUAL VOLUME DAMPER
EXISTING DUCT TO BE REMOVED
VIBRATION, OR SEISMIC
SUPPLY
RETURN
45°
RETURN, NO SPLITTER (45° TAP)
STANDARD BRANCH SUPPLY OR
45°
DRAWING SYMBOLS
26-SF 3
26-TU-I-I
DETAIL NUMBER
DRAWING NUMBER WHERE SHOWN
SECTION LETTER
TYPICAL UNIT NO.
BUILDING NO. WHERE EQUIPMENT IS LOCATED.
SUPPLY FAN NO. 3 IN BUILDING NO. 26
EQUIPMENT ABBREVIATION (SUPPLY FAN)
ITEM NUMBER (TERMINAL UNIT NO. 1)
ITEM (TERMINAL UNIT SHOWN)
SERVED BY AIR HANDLER UNIT NO. 1
DRAWING NUMBER WHERE DRAWN
BUILDING NO. WHERE EQUIPMENT IS LOCATED
H4
H7
A
GENERAL NOTES
1. ALL PIPING AND DUCTS IN FINISHED ROOMS OR SPACES SHALL BE CONCEALED IN A
FURRED CHASE OR ABOVE HARD SUSPENDED CEILING, OR ACOUSTICAL CEILING.
2. THE FIRST FIGURE OF DUCT SIZE INDICATES DIMENSION OF FACE SHOWN OR INDICATED.
DUCT SIZES ARE NET INSIDE DIMENSIONS.
3. ACCESS PANELS IN HARD SUSPENDED CEILINGS ARE REQUIRED FOR ALL VALVES, TRAPS,
DAMPERS, CLEANOUTS, CONTROLS, ETC. ACCESS PANELS SHALL BE FURNISHED AND
INSTALLED UNDER THE ARCHITECTURAL SPECIFICATIONS. COORDINATE LOCATION WITH
MECHANICAL INSTALLATION AND DEMONSTRATE ACCESS TO EQUIPMENT SERVED.
4. TOTAL STATIC PRESSURE NOTED IN THE SCHEDULES INCLUDES DUCT SYSTEM, TERMINAL
UNITS, FILTERS, COILS, ETC. LOSS FOR FILTERS SHALL BE FOR FILTERS AT 50% LOADING.
5. FOR TYPICAL STEAM AND WATER PIPING CONNECTIONS TO EQUIPMENT, SEE STANDARD
EQUIPMENT DETAILS.
6. DIFFUSER, REGISTER AND GRILLE SIZES SHOWN ON FLOOR PLANS ARE NECK SIZES.
7. WATER PIPE CONNECTIONS TO AIR HEATING AND COOLING COILS SHALL BE MADE TO
PROVIDE COUNTER FLOW BETWEEN WATER AND AIR.
8. WALL TYPE EXHAUST REGISTERS NOTED AS "BR" ON DRAWINGS ARE TO BE INSTALLED
WITH BOTTOM ELEVATION OF REGISTER AT 175mm [7"] ABOVE FINISHED FLOOR.
9. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT LOCATIONS OF
CEILING DIFFUSERS, REGISTERS, AND GRILLES.
A/E ARCHITECT / ENGINEER
AAHX AIR TO AIR HEAT EXCHANGER
AAV AUTOMATIC AIR VENT
AB AIR BLENDER
ACC AIR COOLED CONDENSER
ACCH AIR COOLED CHILLER
ACCU AIR COOLED CONDENSING UNIT
ACD AUTOMATIC CONTROL DAMPER,
MODULATING
ACD-TP AUTOMATIC CONTROL DAMPER,
TWO POSITION
ACU AIR CONDITIONING UNIT
AD ACCESS DOOR
AF AFTER FILTER
AFCV AIR FLOW CONTROL VALVE
AFF ABOVE FINISHED FLOOR
AFMS AIR FLOW MEASURING STATION
AFW AIR FOIL WHEEL (FAN)
AHU AIR-HANDLING UNIT
AMP AMPERE
AP ACCESS PANEL
APD AIR PRESSURE DROP
AQST AQUASTAT
ARI AIR CONDITIONING AND REFRIGERATION INSTITUTE
AS AIR SEPARATOR
ASHRAE AMERICAN SOCIETY OF HEATING REFRIGERATION AIR
CONDITIONING ENGINEERS
ASME AMERICAN SOCIETY OF MECHANICAL ENGINEERS
AW AIR WASHER
AXF AXIAL FLOW
B BOILER
BD BUTTERFLY DAMPER
BDD BACKDRAFT DAMPER
BDR BASE BOARD RADIATOR
BFP BACKFLOW PREVENTER
BFT BOILER PLANT FIRE TUBE
BG BOTTOM GRILLE
BHP BRAKE HORSEPOWER
BHW HOT WATER HEATING BOILER
BHX BOILER BLOWDOWN HEAT EXCHANGER
BIW BACKWARD INCLINED WHEEL (FAN)
BMT BONE MARROW TRANSPLANT
BR BOTTOM REGISTER
BSC BIOLOGICAL SAFETY CABINETS
BT BLOWOFF TANK
BTC BLOWOFF TANK CONTROL VALVE
BTU BRITISH THERMAL UNIT
BTUH BRITISH THERMAL UNIT PER HOUR
BWT BOILER PLANT WATER TUBE
C CENTIGRADE (CELSIUS)
CAV CONSTANT AIR VOLUME
CC COOLING COIL
CCD COOLING COIL CONDENSATE DRAIN
CD CEILING DIFFUSER
CD-1 CONSTRUCTION DOCUMENTS (SUBMISSION1)
CD-2 CONSTRUCTION DOCUMENTS (SUBMISSION2)
CENT CENTRIFICAL
CFH CUBIC FEET PER HOUR
CFM CUBIC FEET PER MINUTE
CFT CUBIC FEET
CFP CHEMICAL FEED PUMP
CG CEILING GRILLE
CH CHILLER
CHP CHILLED WATER PUMP
CHW CHILLER WATER
CHR CHILLED WATER RETURN
CHS CHILLED WATER SUPPLY
CI CAST IRON
CM CARBON MONOXIDE
CM CUBIC METER
CM/S CUBIC METER PER SECOND
CO CLEAN OUT
CO2 CARBON DIOXODE
COMP COMPRESSOR UNIT
COP COEFFICIENT OF PERFORMANCE
CP CONDENSATE PUMP
CR CEILING REGISTER
CS CONDENSATE STORAGE TANK
CSG CLEAN STEAM GENERATOR
CT COOLING TOWER
CU CONDENSING UNIT
CUH CABINET UNIT HEATER
CV CONSTANT VOLUME
CW COLD WATER (POTABLE)
CWCC CHILLED WATER COOLING COIL
CWP CONDENSER WATER PUMP
CWR CONDENSER WATER RETURN (TO
COOLING TOWER)
CWS CONDENSER WATER SUPPLY (FROM
COOLING TOWER)
D DAMPER - AUTOMATIC
Db DRY-BULB TEMPERATURE
DB DECIBELS
DCW DOMESTIC COLD WATER
DD-1 DESIGN DEVELOPMENT (SUBMISSION 1)
DD-2 DESIGN DEVELOPMENT (SUBMISSION 2)
DDC DIRECT DIGITAL CONTROLS
DEG DEGREE
DF DIFFUSER
DHW DOMESTIC HOT WATER
DHWR DOMESTIC HOT WATER RETURN
DIA DIAMETER
DIW DEIONIZED WATER
DP DEW POINT TEMPERATURE
DP DIFFUSER PLATE
DPA DIFFERENTIAL PRESSURE ASSEMBLY
DPS DIFFERENTIAL PRESSURE SENSOR
DX DIRECT EXPANSION
DXCC DIRECT EXPANSION COOLING COIL
EA EXHAUST AIR
EAT ENTERING AIR TEMPERATURE
EC EVAPORATIVE COOLER
ECC ENGINEERING CONTROL CENTER
ECU EVAPORATIVE CONDENSER UNIT
EDH ELECTRIC DUCT HEATER
EER ENERGY EFFICIENCY RATIO
EF EXHAUST FAN
EG EXHAUST GRILLE
EGS EMERGENCY GAS SHUTOFF
EGT ENTERING GLYCOL TEMPERATURE
EH EXHAUST HOOD
EJ EXPANSION JOINT
EMD END OF MAIN DRIP (STEAM)
ENT ENTERING
ER EXHAUST REGISTER
ERC ELECTRIC REHEAT COIL
ERP ELECTRIC RADIANT PANEL
ESP EXTERNAL STATIC PRESSURE
ET EXPANSION TANK
ETO ETHYLENE OXIDE
EUH ELECTRIC UNIT HEATER
EWC EVAPORATIVE WATER COOLER
EWT ENTERING WATER TEMPERATURE
EX EXISTING
F FAHRENHEIT
F&T FLOAT AND THERMOSTATIC
F/SDPR COMBINATION FIRE SMOKE DAMPER
FA FREE AREA
FC FLEXIBLE CONNECTION
FCU FAN COIL UNIT (4 PIPE)
FCUC FAN COIL UNIT COOLING ONLY
FCUH FAN COIL UNIT HEATING ONLY
FCW FORWARD CURVED WHEEL (FAN)
FD FLOOR DRAIN
FD FIRE DAMPER
FF FINAL FILTER
FHX FLUE GAS/FEEDWATER HEAT EXCHANGER
FM FLOW METER
FOP FUEL OIL PUMP
FOT FUEL OIL TANK
FOHX FUEL OIL HEAT EXCHANGER
FPM FEET PER MINUTE
FPS FEET PER SECOND
FPTU FAN POWERED TERMINAL UNIT
FR FLOOR REGISTER
FRP FIBER REINFORCED POLYESTER
FS FLOW SWITCH
FSTAT FREEZESTAT
FT FEET
FT WC FEET OF WATER COLUMN
FT-LB FOOT-POUND
FTR FIN TUBE RADIATION
FV FACE VELOCITY
GA GAUGE
GAL GALLONS
GH GRAVITY HOOD
GPD GALLONS PER DAY
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
GPR GAS PRESSURE REGULATOR
GS GALVANIZED STEEL
H HUMIDIFER
HAC HOUSEKEEPING AID CLOSET
HB HOSE BIBB
HC HEATING COIL
HD HOOD
HOA HAND/OFF/AUTOMATIC
HP HEAT PUMP
HP HORSEPOWER
HPDT HIGH PRESSURE DRIP TRAP
HPR HIGH PRESSURE RETURN (STEAM CONDENSATE)
HPS HIGH PRESSURE SUPPLY (STEAM)
HRC HEAT RECOVERY COIL
HRD HEAT RECOVERY DEVICE
HRP HYDRONIC RADIANT (CEILING) PANEL
HRW HEAT RECOVERY WHEEL
HSTAT HUMIDISTAT
HTM HUMIDIFIER TERMINAL
HUM HUMIDIFIER UNIT MOUNTED
HVU HEATING AND VENTILATING UNIT
HW HOT WATER
HWC HOT WATER COIL
HWHC HOT WATER HEATING COIL
HWP HEATING HOT WATER PUMP
HWR HEATING HOT WATER RETURN
HWS HEATING HOT WATER SUPPLY
HWUH HOT WATER UNIT HEATER
HVD HOISTWAY VENT DAMPER
HX HEAT EXCHANGER
HZ HERTZ
I/O INPUT/OUTPUT
IAQ INDOOR AIR QUALITY
IBT INVERTED BUCKET TRAP
ICF IN-LINE CENTRIFUGAL FAN
ICU INTENSIVE CARE UNIT
ID INSIDE DIAMETER
IFB INTEGRAL FACE AND BYPASS
IN INCHES
IN HG INCHES OF MERCURY
IN WC INCH WATER COLUMN
IN WG INCH WATER GAUGE
IN-LB INCH-POUND
IPLV INTERGRATED PART LOAD VALUE
IRH INTRARED HEATER
IS INSECT SCREEN
IU INDUCTION UNIT
IV INLET VANES
J INTENTIALLY LEFT BLANK
KG KILOGRAM
KG/HR KILOGRAM PER HOUR
kPa KILOPASCAL
KW KILOWATT
KWH KILOWATT HOUR
L LITER
L/h LITERS PER HOUR (or LITERS/HOUR) L/m LITERS PER MINUTE (or LITERS/MINUTE) L/s LITERS PER SECOND (or LITERS/SECOND)
LAT LEAVING AIR TEMPERATURE
LBS/HR POUNDS PER HOUR
LF LINEAR FOOT (FEET)
LGT LEAVING GLYCOL TEMPERATURE
LH LATENT HEAT
LPG LIQUEFIED PETROLEUM GAS
LPR LOW PRESSURE RETURN (STEAM CONDENSATE)
LPRC LOW PRESSURE STEAM RETURN (CLEAN)
LLHX LIQUID TO LIQUID HEAT EXCHANGER
LPS LOW PRESSURE STEAM
LPSC LOW PRESSURE STEAM (CLEAN)
LSD LINEAR SLOT DIFFUSER
LTCP LOCAL TEMPERATURE CONTROL PANEL
LVG LEAVING
LVR LOUVER
LWT LEAVING WATER TEMPERATURE
M METER, SI UNIT
M/S METERS PER SECOND (OR
METERS/SECOND)
MA MIXED AIR
MAT MIXED AIR TEMPERATURE
MAU MAKE-UP AIR UNIT
MAV MANUAL AIR VENT
MAX MAXIMUM
MB MIXING BOX
MBH 1,000 BTUH
MCA MINIMUM BRANCH CIRCUIT AMPACITY
MER MECHANICAL EQUIPMENT ROOM
MERV MINIMUM EFFICIENCY REPORTING VALUE
MH MANHOLE
MHP MOTOR HORSEPOWER
MIN MINIMUM
MM MILLIMETER
MOV MOTOR OPERATED VALVE
MPR MEDIUM PRESSURE RETURN (STEAM CONDENSATE)
MPS MEDIUM PRESSURE STEAM
MRI MAGNETIC RESONANCE IMAGING
MTD MEAN TEMPERATURE DIFFERENCE
MVD MANUAL VOLUME DAMPER
MZ MULTI-ZONE
NA NOT APPLICABLE
NC NOISE CRITERIA
NC NORMALLY CLOSED
NG NATURAL GAS
NGFM NATURAL GAS FLOWMETER
Nm NEWTON METER
NO NORMALLY OPEN
NOAA NATIONAL OCEANIC & ATMOSPHERIC
ADMINISTRATION
NOM NOMINAL
NPLV NON-STANDARD PART LOAD VALUE
NPSH NET POSITIVE SUCTION HEAD
NPSHA NET POSITIVE SUCTION HEAD AVAILABLE
NPSHR NET POSITIVE SUCTION HEAD REQUIRED
NTS NOT TO SCALE
OA OUTSIDE AIR
OAD OUTDOOR AIR DAMPER
OAG OUTSIDE AIR GRILLE
OAI OUTSIDE AIR INTAKE
OD OUTSIDE DIAMETER
OFM OIL FLOWMETER
OR OPERATING ROOM
UC UNDER CUT
UC UNIT COOLER
UH UNIT HEATER
U UNDERWRITERS LABORATORY
URV UPBLAST UNIT VENTILATOR
P PUMP
Pa PASCAL
PC PUMPED CONDENSATE
PCF POUNDS PER CUBIC FOOT (FEET)
PD PRESSURE DROP
PEF PROPELLER (TYPE) EXHAUST FAN
PF PRE-FILTER
PG PRESSURE GAGE
PGW PROPYLENE GLYCOL-WATER (SOLUTION)
PHC PREHEAT COIL
PPM PARTS PER MILLION
PRS PRESSURE REGULATING (VALVE) STATION
PRV PRESSURE REGULATING VALVE
PSI POUNDS PER SQUARE INCH
PSIA POUNDS PER SQUARE INCH – ABSOLUTE
PSIG POUNDS PER SQUARE INCH – GAGE
PSS PRIMARY SECONDARY SYSTEM
PSV PRESSURE SAFETY VALVE
PTAC PACKAGED TERMINAL AIR CONDITIONER
R/E RETURN OR EXHAUST
RA RETURN AIR
RAD RETURN AIR DAMPER
RAF RADIO FREQUENCY
RAHX ROTARY AIR HEAT EXCHANGER
RAT RETURN AIR TEMPERATURE
RCCH REMOTE CONDENSER CHILLER
RCU RECIPROCATING CHILLER UNIT
RD REFRIGERANT DISCHARGE
RDS ROOM DATA SHEETS
REA RELIEF AIR
RELAD RELIEF AIR DAMPER
RF RETURN FAN
RG RETURN GRILLE
RH RELATIVE HUMIDITY
RHC REHEAT COIL
RHG REFRIGERANT HOT GAS
RL REFRIGERANT LIQUID LINE
RLA RUN LOAD AMPERE
RO REVERSE OSMOSIS
RPM REVOLUTIONS PER MINUTE
RR RETURN REGISTER
RS REFRIGERANT SUCTION
RTU ROOF TOP UNIT
RV RELIEF VALVE
SA SUPPLY AIR
SAD SOUND ATTENUATING DEVICE
SAT SUPPLY AIR TEMPERATURE
SC SHADING COEFFICIENT
SCFM STANDARD CUBIC FEET PER MINUTE
SCI SPINAL CODE INJURY
SCR SILICON CONTROLLED RECTIFIER
SD SMOKE DETECTOR
SD SUPPLY AIR DIFFUSER
SD-1 SCHEMATIC DESIGN (SUBMISSION1)
SD-2 SCHEMATIC DESIGN (SUBMISSION2)
SDPR SMOKE DAMPER
SDR SMOKE DAMPER (RETURN)
SDS SMOKE DAMPER (SUPPLY)
SEN SENSIBLE HEAT
SF SUPPLY FAN
SG SUPPLY AIR GRILLE
SH STEAM HUMIDIFIER
SHC STEAM HEATING COIL
SI SQUARE INCHES
SP STATIC PRESSURE
SP GR SPECIFIC GRAVITY
SPD SUPPLY PROCESS AND DISTRIBUTION
SPRV STEAM PRESSURE REDUCING VALVE
SPS STATIC PRESSURE SENSOR
SQ FT SQUARE FOOT (FEET)
SR SUPPLY AIR REGISTER
SS STAINLESS STEEL
SSHX STEAM TO STEAM HEAT EXCHANGER
SSR SOLID SEPARATOR
ST STEAM TRAP
SUH STEAM UNIT HEATER
SV STEAM PRESSURE REDUCING VALVE
SVS STEAM VENT SILENCER
SW SOFTWATER
SWHX STEAM TO WATER HEAT EXCHANGER
T&PCV TEMPERATURE AND PRESSURE
CONTROL VALVE
TAB TESTING, ADJUSTING, BALANCE
TD TEMPERATURE DIFFERENCE
TDH TOTAL DYNAMIC HEAD
TDS TOTAL DISSOLVED SOLIDS
TG TRANSFER GRILLE
TP TRAP
TR TOP REGISTER
TSP TOTAL STATIC PRESSURE
TSTAT THERMOSTAT
TU TERMINAL UNIT
TWU THRU-WALL UNIT
UC UNDER CUT
UC UNIT COOLER
UH UNIT HEATER
U UNDERWRITERS LABORATORY
URV UPBLAST UNIT VENTILATOR
V VALVE
VAF VANE-AXIAL FAN
VAV VARIABLE AIR VOLUME
VD VOLUME DAMPER (MANUAL OPPOSED
BLADE)
VFD VARIABLE FREQUENCY…
This is the start of the file's text. The full file is on GovTribe.