657-19-127JB-2022.03.17_ADD-2.pdf

PDF 2 MB Posted

Attached to
Z2DA--FCA - Renovate Space for Domiciliary Providers, Building 2 PA:657-19-127JB
Solicitation number
36C25522R0033
Issued by

About this file

This federal contract opportunity solicitation seeks renovation services for Building 2 at the Jefferson Barracks Division VA Medical Center in St. Louis, Missouri. The project includes renovating areas on the second floor north and all of the first floor, with work phased to complete the second floor followed by the first floor. The project costs are estimated between $2 million to $5 million, with work expected to take 457 calendar days upon notice to proceed. The NAICS code is 236220 for general construction with a small business size standard of $39.5 million. The solicitation will be posted to SAM on or about December 20, 2021. Only one organized site visit will be scheduled. Questions must be emailed by December 20th. Pursuant to law, this is a total SDVOSB set-aside requiring at least 15% general construction labor by the prime contractor.

View the file

Other files

File Type Posted
657-19-127JB_spec section 27 51 16.pdf PDF
36C25522R0033 0007.docx DOCX document
657-19-127JB_Electrical plan changes.pdf PDF
36C25522R0033 0006.docx DOCX document
1801901 Asbestos Mold Survey - Jefferson Building 2 (final).pdf PDF
JB-2-Report.pdf PDF
36C25522R0033 0005.docx DOCX document
36C25522R0033 0004.docx DOCX document
36C25522R0033 0003.docx DOCX document
UpdatedSpecs_Vol1_revised 20211215.pdf PDF
UpdatedSpecs_Vol2.pdf PDF
36C25522R0033.docx DOCX document
PastPerformanceQuestionnaire36C25522R0033Project657-19-127JB.docx DOCX document
Bid Docs_Arch.pdf PDF
Bid Docs_MEP DRAWINGS.pdf PDF
Show all 15

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Department of Veterans Affairs March 17, 2022

Network Contracting Office NO. 9 Addendum #002

657-19-127JB Renovate Spaces for

Domiciliary Support

VAMC St. Louis – Jefferson Barracks

Addendum

Page | 1

Issue Date: March 17, 2022

Reference: Addendum #002

TITLE: Revisions and Updates

The following instructions herein and the listed documents below are hereby modified to be incorporated as part of the contract documents.

This Addendum consists of the summary of changes and the pertinent drawing and specification changes as noted below. This change consists of REVISIONS as follows:

SUMMARY OF CHANGES TO DRAWINGS:

Electrical

1. Sheet 02-ED-113 Systems Demolition Floor Plan – Floor 01 reissued

2. Sheet 02-ED-123 Systems Demolition Floor Plan – Floor 02 reissued

3. Sheet 02-EJ-001 Electrical Legend - reissued

4. Sheet 02-EJ-601 Partial Fire Alarm Riser Diagram - reissued

5. Sheet 02-ET-111 Systems Plan – Floor 01 reissued

6. Sheet 02-ET-121 Systems Plan – Floor 02 reissued

SUMMARY OF CHANGES TO SPECIFICATIONS:

7. Specification Section 27 51 16 Public Address Mass Notification Systems

a. Specification Section issued with this addendum.

- END OF ADDENDUM #2 -

F

F

W AP

F

F

W AP

F

SD

SFSSF

F

W AP

F

F

W AP

SD

F

V

VF

S S

F

W AP

FF

W AP

F

F

F

F

F

F

N A

C

TXT TXT

F

A

A

AAA

T X

T

TXT

T X

T

T E

L

T E

L

T E

L

EX

EX

EX

PANEL L1-4

TO BE REMOVED

PANEL L1-2

TO BE REMOVED

COAX PANEL

TO REMAIN

PANEL L1-3

TO BE REMOVED

PANEL L1-1

TO BE REMOVED

S2 S2

S2

S2 S2 S2 S2

S2 S2 S2 S2

S2 S2

S2

S2

S2

S2

S2

S2

S2

S2

S2

S2

S2

S2 S2 S2

E IN

I

HANS

ROBERT A.

EETT

SS

TATA

FF MOO

P O

F R

SO

S

I

U

R

R E

E

S

NA L

S IO ENG

NUMBER

PE-2006009888

10411 Meeting Street, Prospect, Kentucky 40059 502 326.3085 f 502 326.2691 www.cmta.com th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing # of

657-19-127JBFCA - RENOVATE SPACE FOR

DOMICILIARY PROVIDERS, BUILDING 2

5/1/2020

VA Health Care System Approval:

BID DOCUMENTS

ARCHITECT/ENGINEER:

A/E: PROJECT LEAD

Architect, Structural Engineer

Consultant:

CMTA CONSULTING ENGINEERS

10411 MEETING STREET

PROSPECT, KY 40059

502.326.3085

JEFFERSON BARRACKS

1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125

/1

/2

:1 :5

P

M

02-ED-113

SYSTEMS DEMOLITION PLAN - FLOOR 01

CMTACMTA

SCALE: 1/4" = 1'-0"02-ED-113

1 Systems Demolition Plan - Floor 01

ELECTRICAL DEMOLITION NOTES:

A. DOTTED LINES INDICATE ITEMS FOR REMOVAL (UON) AND THIN SOLID LINES INDICATE EXISTING ITEMS TO

REMAIN.

B. THE CONTRACTOR SHALL MAINTAIN THE CONTINUITY OF EXISTING CIRCUITS THAT CONTAIN DEVICES OR

EQUIPMENT THAT ARE TO REMAIN. W HEN DEMOLITION OF AN ELECTRICAL DEVICE (OR CIRCUIT) IS INDICATED ON THE DRAW INGS: THE CONTRACTOR SHALL ENSURE THAT OTHER DEVICES OR EQUIPMENT "UPSTREAM" OR "DOW NSTREAM" ON THE CIRCUITS SHALL REMAIN IN "PRE- DEMOLITION" W ORKING ORDER. "LEFT-OVER" CIRCUIT BREAKERS SHALL REMAIN, BE SW ITCHED TO OFF POSITION, AND BE LABELED AS SPARES IN THEIR

PANELS. PROVIDE NEW TYPEW RITTEN DIRECTORIES FOR ALL PANELS AFFECTED.

C. LOCATIONS OF DEVICES, CONNECTIONS, ETC., INDICATED ON THIS DRAW ING W ERE TAKEN FROM VARIOUS SOURCES. THEY ARE DIAGRAMMATIC ONLY AND ARE SUBJECT TO VARIATION FROM EXISTING CONDITIONS.

CERTAIN EXISTING ELEMENTS MAY NOT BE INDICATED AT ALL. THE CONTRACTOR PROPOSING TO DO ANY PART OF THE W ORK INDICATED HEREON SHALL VISIT THIS SITE AND DETERMINE TO HIS SATISFACTION THAT THEY

MAY COMPLETE ALL W ORK REQUIRED FOR THE BID W HICH HE PROPOSES.

D. REMOVE ALL ASSOCIATED BACKBOXES, CONDUIT AND CONDUCTORS FOR DEVICES / FIXTURES / ETC. BEING REMOVED (BACK TO SOURCE), W HETHER INDICATED OR NOT (UON). CONTRACTOR SHALL PATCH AND REPAIR ANY EXISTING W ALLS, FLOORS OR CEILINGS W HERE DEVICES ARE SHOW N TO BE REMOVED (PATCH AND

REPAIR TO RECEIVE NEW FINISHES - SEE ARCHITECTURAL PLANS).

E. COORDINATE DISPOSAL OF ALL FIXTURES, DEVICES, ETC. (INDICATED FOR DEMOLITION) W ITH OW NER. TURN

OVER ITEMS REMOVED TO OW NER AT THEIR OPTION.

F. COORDINATE W ITH OTHER TRADES FOR THE REMOVAL AND/OR RELOCATION OF ELECTRICAL DEVICES AND

CONNECTIONS ASSOCIATED W ITH THEIR EQUIPMENT.

G. PROVIDE TEMPORARY EMERGENCY EXIT LIGHTS AT CONSTRUCTION BARRIERS AS REQUIRED.

H. CONTRACTOR SHALL PATCH AND REPAIR ALL EXISTING W ALLS / CEILINGS AS REQUIRED W HERE DEVICES ARE

BEING REMOVED OR INSTALLED.

I. UNUSED/ABANDONED CONDUCTORS DISCOVERED ABOVE ACCESSIBLE CEILINGS SHALL BE REMOVED IN

ACCORDANCE W ITH NEC REQUIREMENTS.

J. EXISTING ELECTRICAL SYSTEMS IN CONFLICT W ITH CONSTRUCTION SHALL BE RELOCATED TO PERMIT

INSTALLATION OF DEVICES AND EQUIPMENT SHOW N ON PLANS.

K. ALL EXISTING PANELS AFFECTED BY THIS CONTRACTOR'S W ORK SHALL BE PROVIDED W ITH NEW TYPE-

W RITTEN PANEL DIRECTORIES AND INSERT SLEEVES. PANEL DIRECTORIES SHALL NOT USE ROOM NAMES OR NUMBERS FROM THESE DRAW INGS. DIRECTORIES SHALL BE DETAILED AND COORDINATED W ITH OW NER'S SUITE NUMBERS, FINAL ROOM NUMBERS, IT RACK NAMES, W ORKSTATION DESIGNATIONS, ETC. UNUSED

BREAKERS SHALL BE IN OFF POSITION.

L. ALL LIGHT SW ITCHES SHOW N ON W ALLS TO BE DEMOLISHED ARE TO BE REMOVED.

M. LIGHTING FIXTURES ARE TO BE SALVAGED FOR REUSE REFER TO NEW W ORK PLAN FOR ADDITIONAL DETAILS.

N

CRITICAL DEMOLITION NOTE:

COORDINATE REMOVAL OF CEILING MOUNTED ACCESS POINTS FOR W IDE AREA NETW ORK W ITH OW NER IMMEDIATELY AFTER AW ARDING OF PROJECT. (DEVICES ARE SHOW N AS EXISTING, BUT W ILL NEED TO BE REW ORKED FOR INSTALLATION OF NEW CEILING. COORDINATE REW ORK DETAILS W ITH OW NER.)

TAGGED NOTES

S2 FIRE ALARM DEVICE TO BE REMOVED, CLEANED, AND

REINSTALLED PER NEW WORK PLAN TO LIKE NEW CONDITION.

Revisions: Date:

FA CHANGES 2/18/2022

S

F

S

S

S

W AP

S

S

S

S

F

F

F

SD

F

F

W AP

F

W A

P

S

S

SS

S S

A A A

TXT TXT

A F

F

TXT

F

SD

A

A A

T E

L

S2 S2

S2

PANEL L2-1

TO BE REMOVED

COAX PANEL

TO REMAIN

S2

S2 S2 S2

S2

S2S2

S2 S2 S2

S2 S2

S2

E IN

I

HANS

ROBERT A.

EETT

SS

TATA

FF MOO

P O

F R

SO

S

I

U

R

R E

E

S

NA L

S IO ENG

NUMBER

PE-2006009888

10411 Meeting Street, Prospect, Kentucky 40059 502 326.3085 f 502 326.2691 www.cmta.com th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing # of

657-19-127JBFCA - RENOVATE SPACE FOR

DOMICILIARY PROVIDERS, BUILDING 2

5/1/2020

VA Health Care System Approval:

BID DOCUMENTS

ARCHITECT/ENGINEER:

A/E: PROJECT LEAD

Architect, Structural Engineer

Consultant:

CMTA CONSULTING ENGINEERS

10411 MEETING STREET

PROSPECT, KY 40059

502.326.3085

JEFFERSON BARRACKS

1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125

/1

/2

:1 :5

P

M

02-ED-123

SYSTEMS DEMOLITION PLAN - FLOOR 02

CMTACMTA

SCALE: 1/4" = 1'-0"02-ED-123

1 Systems Demolition Plan - Floor 02

ELECTRICAL DEMOLITION NOTES:

A. DOTTED LINES INDICATE ITEMS FOR REMOVAL (UON) AND THIN SOLID LINES INDICATE EXISTING ITEMS TO

REMAIN.

B. THE CONTRACTOR SHALL MAINTAIN THE CONTINUITY OF EXISTING CIRCUITS THAT CONTAIN DEVICES OR

EQUIPMENT THAT ARE TO REMAIN. W HEN DEMOLITION OF AN ELECTRICAL DEVICE (OR CIRCUIT) IS INDICATED ON THE DRAW INGS: THE CONTRACTOR SHALL ENSURE THAT OTHER DEVICES OR EQUIPMENT "UPSTREAM" OR "DOW NSTREAM" ON THE CIRCUITS SHALL REMAIN IN "PRE- DEMOLITION" W ORKING ORDER. "LEFT-OVER" CIRCUIT BREAKERS SHALL REMAIN, BE SW ITCHED TO OFF POSITION, AND BE LABELED AS SPARES IN THEIR

PANELS. PROVIDE NEW TYPEW RITTEN DIRECTORIES FOR ALL PANELS AFFECTED.

C. LOCATIONS OF DEVICES, CONNECTIONS, ETC., INDICATED ON THIS DRAW ING W ERE TAKEN FROM VARIOUS SOURCES. THEY ARE DIAGRAMMATIC ONLY AND ARE SUBJECT TO VARIATION FROM EXISTING CONDITIONS.

CERTAIN EXISTING ELEMENTS MAY NOT BE INDICATED AT ALL. THE CONTRACTOR PROPOSING TO DO ANY PART OF THE W ORK INDICATED HEREON SHALL VISIT THIS SITE AND DETERMINE TO HIS SATISFACTION THAT THEY

MAY COMPLETE ALL W ORK REQUIRED FOR THE BID W HICH HE PROPOSES.

D. REMOVE ALL ASSOCIATED BACKBOXES, CONDUIT AND CONDUCTORS FOR DEVICES / FIXTURES / ETC. BEING REMOVED (BACK TO SOURCE), W HETHER INDICATED OR NOT (UON). CONTRACTOR SHALL PATCH AND REPAIR ANY EXISTING W ALLS, FLOORS OR CEILINGS W HERE DEVICES ARE SHOW N TO BE REMOVED (PATCH AND

REPAIR TO RECEIVE NEW FINISHES - SEE ARCHITECTURAL PLANS).

E. COORDINATE DISPOSAL OF ALL FIXTURES, DEVICES, ETC. (INDICATED FOR DEMOLITION) W ITH OW NER. TURN

OVER ITEMS REMOVED TO OW NER AT THEIR OPTION.

F. COORDINATE W ITH OTHER TRADES FOR THE REMOVAL AND/OR RELOCATION OF ELECTRICAL DEVICES AND

CONNECTIONS ASSOCIATED W ITH THEIR EQUIPMENT.

G. PROVIDE TEMPORARY EMERGENCY EXIT LIGHTS AT CONSTRUCTION BARRIERS AS REQUIRED.

H. CONTRACTOR SHALL PATCH AND REPAIR ALL EXISTING W ALLS / CEILINGS AS REQUIRED W HERE DEVICES ARE

BEING REMOVED OR INSTALLED.

I. UNUSED/ABANDONED CONDUCTORS DISCOVERED ABOVE ACCESSIBLE CEILINGS SHALL BE REMOVED IN

ACCORDANCE W ITH NEC REQUIREMENTS.

J. EXISTING ELECTRICAL SYSTEMS IN CONFLICT W ITH CONSTRUCTION SHALL BE RELOCATED TO PERMIT

INSTALLATION OF DEVICES AND EQUIPMENT SHOW N ON PLANS.

K. ALL EXISTING PANELS AFFECTED BY THIS CONTRACTOR'S W ORK SHALL BE PROVIDED W ITH NEW TYPE-

W RITTEN PANEL DIRECTORIES AND INSERT SLEEVES. PANEL DIRECTORIES SHALL NOT USE ROOM NAMES OR NUMBERS FROM THESE DRAW INGS. DIRECTORIES SHALL BE DETAILED AND COORDINATED W ITH OW NER'S SUITE NUMBERS, FINAL ROOM NUMBERS, IT RACK NAMES, W ORKSTATION DESIGNATIONS, ETC. UNUSED

BREAKERS SHALL BE IN OFF POSITION.

L. ALL LIGHT SW ITCHES SHOW N ON W ALLS TO BE DEMOLISHED ARE TO BE REMOVED.

M. LIGHTING FIXTURES ARE TO BE SALVAGED FOR REUSE REFER TO NEW W ORK PLAN FOR ADDITIONAL DETAILS.

N

EX

TAGGED NOTES

S2 FIRE ALARM DEVICE TO BE REMOVED, CLEANED, AND

REINSTALLED PER NEW WORK PLAN TO LIKE NEW CONDITION.

CRITICAL DEMOLITION NOTE:

COORDINATE REMOVAL OF CEILING MOUNTED ACCESS POINTS FOR W IDE AREA NETW ORK W ITH OW NER IMMEDIATELY AFTER AW ARDING OF PROJECT. (DEVICES ARE SHOW N AS EXISTING, BUT W ILL NEED TO BE REW ORKED FOR INSTALLATION OF NEW CEILING. COORDINATE REW ORK DETAILS W ITH OW NER.)

C

SD

BL

UON

CFOI

OFOI

CFCI

OFCI

T

C/S

J

DESCRIPTION

DP

S

S

S 3

S D

S K

PC

S

S 4

S

U

N

OS

OS

S PL

IL

GROUND FAULT PROTECTED DUPLEX WITH WEATHER-

PROOF "WHILE IN USE" TYPE DIE-CAST METAL

COVERPLATE WITH LOCKABLE ENCLOSURE AT

OUTLET - SEE SPECIFICATIONS

W P

ER

DUPLEX FOR ELECTRIC W ATER COOLER:

COORDINATE EXACT LOCATION W ITH PLUMBING

CONTRACTOR TO CONCEAL OUTLET BEHIND COOLER,

PROVIDE READILY ACCESSIBLE GFI DEVICE AT 18"

ADJACENT TO W ATER COOLER

EW C

AUDIO/VIDEO INTERCOM MASTER STATION.

SAME AS ''IM'' EXCEPT W ALL MOUNTED W

DOOR RELEASE PUSH-PLATE / INFRA-RED OPERATOR

STATION. PROVIDE ANY ADDITIONAL ROUGH-IN FOR

''EMERGENCY RELEASE'' OPERATOR STATIONS AS

REQUIRED.

DOOR RELEASE CARD READER STATION. PROVIDE

ANY ADDITIONAL ROUGH-IN FOR ''EMERGENCY

RELEASE'' OPERATOR STATIONS AS REQUIRED.

AUTOMATIC DOOR CONNECTION (MAY ALSO HAVE

ELECTRIC STRIKE/MAG-LOCK/ELECTRIFIED PANIC

CONNECTION - SEE ARCHITECTURAL HARDWARE

SPECIFICATIONS)

FLOORBOX, COMBINATION POW ER AND LOW

VOLTAGE

B

SS

KEYED, LOCKED PULL STATION : DOUBLE ACTION.

STATION SHALL ONLY BE OPERABLE VIA KEY IN

POSSESSION OF STAFF.

CDCARBON MONOXIDE DUCT DETECTOR

POW ER SUPPLY/CONTROL FOR AUDIO/VISUAL DEVICES

SAME AS ''CR'' EXCEPT MULLION MOUNT M

SLASH THROUGH ANY DEVICE INDICATES MOUNTING

ABOVE COUNTERTOP 4" ABOVE BACKSPLASH, OR AT 46"

W HERE NO COUNTER IS PRESENT

OVERHEAD PROJECTOR: PROVIDE DUPLEX

RECEPTACLE, ONE DATA, HDMI, 3.5mm AUDIO, AND

VGA OUTLET ON (3) PLATES

CCTV CAMERA: CEILING MOUNT DOME

W P

''DOG-HOUSE'' TYPE TWIN DUPLEX RECEPTACLE

W ITH ONE DUPLEX RECEPTACLE ON BOTH SIDES

AUDIO/VIDEO INTERCOM REMOTE STATION.

S VS

VS

LV

PILOT LIGHT SWITCH (ILLUMINATED WHEN LOAD IS ON)

ILLUMINATED HANDLE LIGHT SWITCH (ILLUMINATED

W HEN LOAD IS OFF)

EMERGENCY AUTOMATIC TRANSFER SWITCH

FOR LIGHTING CONTROLS (REFER TO DETAIL)

FILLED CENTER BAR INDICATES INTEGRAL GROUND

FAULT PROTECTION (GFCI)

GANG RECEPTACLE IN COMBINATION W ITH SW ITCH

(PROVIDE DIVIDER IF LIGHTING CIRCUIT IS 277V)

NON-REVERSING MOTOR STARTER SNAP SWITCH

CONTRACTOR FURNISHED OWNER INSTALLED

CONTRACTOR FURNISHED CONTRACTOR INSTALLED

OWNER FURNISHED OWNER INSTALLED

OWNER FURNISHED CONTRACTOR INSTALLED

FLUSH MOUNTED REMOTE ALARM INDICATING

STATION/TEST SW ITCH

CONNECTION TO SPRINKLER TAMPER

SW ITCH W ITH ADDRESSABLE MODULE

CONNECTION TO SPRINKLER FLOW

SW ITCH WITH ADDRESSABLE MODULE

PHOTO-ELECTRIC SMOKE DETECTOR

MAIN CONTROL PANEL CENTRAL PROCESSING

UNIT (CPU)

DOOR ALARM/POSITION SW ITCH

DOOR POWER SUPPLY

DOOR DELAYED EGRESS/ELECTRIFIED PANIC

MECHANISM

TELEVISION SYSTEM OUTLET W ITH DUPLEX

RECEPTACLE, COORDINATE LOCATION W ITH WALL

BRACKET WHERE APPLICABLE

LIGHT SW ITCH:GENERAL PURPOSE

AS NOTED

AS NOTED

LIGHT SW ITCH FOR UNDER-CABINET LIGHTS

6'-6'' TO

TOP

46" TO

LEVER

46" TO

LEVER

PULL STATION : DOUBLE ACTION

AUDIO-ONLY NOTIFICATION APPLIANCE

VISUAL-ONLY NOTIFICATION APPLIANCE

AUDIO/VISUAL NOTIFICATION APPLIANCE

BELL / LIGHT

BELL ONLY

HEAT DETECTOR

CARBON MONOXIDE ALARM: SINGLE STATION

W /SOUNDER BASE

CARBON MONOXIDE AUDIO/VISUAL NOTIFICATION

APPLIANCE

DOOR HOLDER : WALL TYPE

DOOR HOLDER : CLOSURE TYPE

DUCT SMOKE DETECTOR

PRESSURE SWITCH

REMOTE L.C.D. FIRE ALARM ANNUNCIATOR

POST INDICATOR VALVE

ISOLATION MODULE

H.V.A.C. SMOKE DAMPER CONNECTION

UNLESS OTHERW ISE NOTED

SURFACE PLUG-MOLD

SPECIAL OUTLETS

HD

ABV CLG

CM

F

DH

ABV DOOR DH

ABV CLG DD

FS

TS

PS

46"

I

ZONE ADDRESSABLE MODULE Z

SM

ABBREVIATIONS

DESCRIPTION

STRIP FIXTURE

CROSS-HATCHING INDICATES LIGHT IS POW ERED

FROM THE EMERGENCY-CRITICAL BRANCH

PARALLEL-HATCHING INDICATES LIGHT IS POW ERED

FROM THE EMERGENCY-LIFE SAFETY BRANCH

POWER OUTLETS

SIMPLEX RECEPTACLE

DUPLEX RECEPTACLE-SAFETY TYPE,

TAMPER-RESISTANT

DUPLEX RECEPTACLE

QUADRUPLEX RECEPTACLE

JUNCTION BOX, CEILING OR WALL

VOLTAGE/1PH RECEPTACLE, AS NOTED

VOLTAGE/3PH RECEPTACLE, AS NOTED

SS INDICATES SURGE SUPPRESION TYPE OUTLET(S)

NIGHT LIGHT SWITCH W ITH CONSTANTLY

ILLUMINATED HANDLE

DIMMER SW ITCH

THREE-W AY SW ITCH

FOUR-W AY SW ITCH

KEYED SW ITCH

OCCUPANCY OR VACANCY SENSOR SW ITCH

OCCUPANCY OR VACANCY SENSOR, CEILING MOUNT

LOW VOLTAGE MOMENTARY SWITCH

PHOTO-CELL AS NOTED

EXIT LIGHT (CEILING, END, W ALL MOUNT)

LIGHTING

REFER TO LUMINAIRE SCHEDULE FOR EXACT FIXTURE

SPECIFICATIONS, MOUNTING HEIGHTS, ETC.

SPECIAL VIDEO SYSTEM SIGNAL INPUT

SECURITY INTERCOM

SECURITY ACCESS CONTROL

SECURITY CCTV VIDEO SURVEILLANCE

DOOR RELEASE KEYSW ITCH STATION

DOOR RELEASE KEYPAD STATION

MOTION SENSOR DOOR CONTROL

REMOTE DOOR RELEASE PUSH-BUTTON

CCTV CAMERA: W ALL MOUNT DOME

CCTV POW ER SUPPLIES/CONTROL PANEL 46"

DOOR

FRAME

ABV DOOR

8" ACT

DESCRIPTION

W ALL, CLG

80"

CLG

CLG

CLG

W ALL

54"

46"

46"

46"

46"

46"

46"

46"

46"

46"

46"

46"

1'-6"

1'-6"

1'-6"

1'-6"

46"

1'-6"

1'-6"

ON CNTR.

2'-2"

CLG

AS NOTED

18''

46"

46"

CLG

46"

6'-0''

46"

46"

CEIL.

CLG

7'-0"

S

CLG

FLOOR

S

S

S M

TELEVISION SPLITTERS/AMPLIFIERS/DISTRIBUTION

TELEVISION

46" TV-HE

D R

A W

IN

G

Y

M B

O L

SURFACE OR SUSPENDED CEILING FIXTURE (SLASH

INDICATES RECESSED)

POLE MOUNTED AREA LIGHT

EMERGENCY BATTERY W ALL-PACK

W ALL MOUNT FIXTURE ,

FLOODLIGHT

V

A

F

F K

F

SCROLLING TEXTUAL APPLIANCE

RI

INDICATES VANDAL-PROOF POLYCARBONATE COVER,

VANDAL PROOF COVERS SHALL BE UL LISTED FOR USE

W ITH THE SPECIFIC DEVICE THEY ARE PROTECTING

PC

80"

W ALL

W ALL

7'-6''

FIREMAN'S PHONE JACK FP

ADDRESSABLE RELAY MODULE R

W ALL

ACCESS CONTROL POW ER SUPPLIES/CONTROL PANEL 46"

46"

ABV CLG

ELECTRIC STRIKE AT LATCH

MAGNETIC LOCK(S) ABV DOOR

INDICATES EXTERIOR CAMERA RATED FOR

CONDITIONS, W ET LOCATION LISTED, WITH

AUXILLARY HEATER

PTZINDICATES CAMERA WITH PAN/TILT/ZOOM FUNCTION

FLOORBOX, POW ER ONLY, AS SCHEDULED FLOOR

FIRE RATED POKE THOUGH FLOOR BOX, COORDINATE

EXACT COVER REQUIREMENTS W ITH ARCHITECTURAL

FINISHES, DEVICES AS SCHEDULED

DESCRIPTION

K

DB

DB

W P

DOORBELL PUSHBUTTON STATION, PROVIDE COMPLETE

W ITH TRANSFORMER (MOUNT ABOVE CEILING IN

CORRIDOR NEAR PUSH-BUTTON) AND ALL

ACCESSORIES, POW ER FROM NEAREST AVAILABLE 120V

NORMAL POWER GENERAL RECEPTACLE CIRCUIT,

NUTONE OR EQUAL

DOORBELL AUDIO/VISUAL STATION, PROVIDE PROVIDE

CONNECTION TO PUSHBUTTON STATION IN AREA.

COORDINATE EXACT AUDIO SOUND (CHIME, BUZZER,

ETC.) DESIRED W ITH OwNER/ARCHITECT, NUTONE OR

EQUAL

PLUMBING FIXTURE ELECTRIC EYE TRANSFORMER

CONNECTION. TRANSFORMER SHALL BE 120V-24V.

MOUNT ABOVE SUSPENDED ACCESSIBLE CEILING IN J-

BOX. PROVIDE ADDITIONAL TRANSFORMERS OF SAME

TYPE AS/IF NEEDED

PROVIDE CONNECTION TO HAND DRYER (SEE

ARCHITECTURAL SPECIFICATIONS)

VERIFY WITH

ARCHITECT

C

INDICATES MOUNTING ABOVE COUNTER-TOP,

2" ABOVE BACKSPLASH, NO HIGHER THAN 48''

W G

W IREGUARD - PROVIDE MANUFACTURER'S

SPECIFIC GUARD FOR DEVICE NOTED

BOX ON ANY DEVICE INDICATES SURFACE MOUNTED

BACKBOX/W IREMOLD

CONDUIT CONCEALED IN WALLS OR IN CEILING

SPACE: ARROW (S) INDICATE(S) HOME RUN & #

OF CIRCUITS: HASHMARKS INDICATE # OF

CONDUCTORS. DASHED LINE INDICATES

CONDUIT BELOW FLOOR.

W IREW AY WITH REMOVABLE COVER (SIZE AS NOTED)

PANELBOARD, SURFACE OR FLUSH MOUNTED,

HATCHING INDICATES EMERGENCY

EQUIPMENT TAG, REFER TO EQUIPMENT SCHEDULE

MECHANICAL EQUIPMENT DESIGNATOR

(SEE MECH. SCHEDULES)

EQUIPMENT HARDWIRE CONNECTION (SEE DETAIL)

KITCHEN EQUIPMENT OUTLET COUPLING

CONNECTION (SEE DETAIL)

AS SHOWN

AS SHOWN

AS NOTED

AS SHOWN

MISCELLANEOUS

DISCONNECT SWITCH

MAGNETIC STARTER

MAGNETIC COMBINATION STARTER

ENCLOSED FLUSH MTD. CIRCUIT BREAKER

W EATHERPROOF - NEMA-3R, W ET LOCATION LISTED.

PROVIDE COVERS, RATINGS, ETC, AS SUITABLE FOR

OUTDOORS.

TRENCH DUCT (SIZE AS NOTED)

PUSHBUTTON STATION

FLEXIBLE CONDUIT

TRANSFORMER

TAGGED NOTE

REVISION TAG

W IRE BASKET CABLE TRAY, SIZE AS NOTED

LOW VOLTAGE CABLE PATH

5'-0"

5'-0"

5'-0"

5'-0"

46"

46"

7'-6''

6'-6'' TO TOP

XPEXPLOSION PROOF - PROVIDE WIRING METHODS,

ENCLOSURES, RATINGS, ETC. AS SUITABLE FOR

HAZARDOUS LOCATION.

SURGE PROTECTION DEVICE

THERMOSTAT PROVIDED BY MECHANICAL

CONTRACTOR, ELECTRICAL CONTRACTOR SHALL

PROVIDE BACK-BOX CONDUIT STUB-UP, REFER TO

MECHANICAL DRAWINGS FOR LOCATIONS

DESCRIPTION

C A

B L

IN

G

/C O

N D

U C

T O

R S

O

F O

I

C A

B L

IN

G

/C O

N D

U C

T O

R S

O

F C

I

C A

B L

IN

G

/C O

N D

U C

T O

R S

C

F C

I

IT

E

M U

S E

D O

N P

R O

J E

C T

D E

V

IC

E S

O

F C

I

D E

V

IC

E S

C

F C

I

SYSTEM D

E

V

IC

E S

O

F O

I

SECURITY: ACCESS CONTROL

SECURITY: CCTV

SYSTEM

RESPONSIBILITY

MATRIX

OVERHEAD PAGING

FIRE ALARM

TELEVISION

DATA PROCESSING

SYSTEM RESPONSIBILITY GENERAL NOTES:

A. REFER TO VENDOR DRAW INGS FOR COMPLETE SCOPE OF W ORK RELATING TO

VENDOR-FURNISHED EQUIPMENT. ALL W ORK INDICATED ON VENDOR DRAW INGS

SHALL BE INCLUDED BY THE CONTRACTOR.

B. REFER TO ARCHITECTURAL DOOR HARDW ARE SPECIFICATIONS FOR ACCESS

CONTROL DEVICE SPECIFICATIONS AND FURTHER REQUIREMENTS.

C. PROVIDE BACKBOXES AND CONDUIT W ITH PULL-STRINGS FOR ALL SYSTEMS.

CONTRACTOR SHALL VERIFY BACKBOX SIZES, CONDUIT, ETC. AND EXACT

INSTALLATION LOCATIONS/REQUIREMENTS WITH SUCCESSFUL VENDORS OF ALL

SYSTEMS PRIOR TO CONSTRUCTION.

D. AT ALL SYSTEMS EQUIPMENT CABINET/TERMINAL BOARD LOCATIONS,

CONTRACTOR SHALL PROVIDE SIZE AND NUMBER OF CONDUIT STUB-OUTS TO

CABLE PATHS AS REQUIRED BY SYSTEM VENDORS, TERMINATE CONDUITS AT

CABINETS/ON BACKBOARDS AS REQUIRED. COORDINATE EXACT REQUIREMENTS

W ITH APPROPRIATE VENDORS PRIOR TO CONSTRUCTION.

E. REFER TO SPECIFICATIONS FOR REQUIREMENTS APPLICABLE TO ALL SYSTEMS

INCLUDING CABLING, CABLE MANAGEMENT, INSTALLATION, GROUNDING, TESTING,

LABELING, ETC.

F. W HERE INDICATED AS CFCI, THE CONTRACTOR SHALL PROVIDE THE SYSTEM

COMPLETE, INCLUDING ALL ROUGH-INS, CABLING, DEVICES, POW ER, ETC. THE

CONTRACTOR SHALL CONTACT THE LISTED VENDOR FOR PRICING PRIOR TO BID.

ALL SYSTEMS SHALL MATCH EXISTING FACILITY STANDARDS AND BE FULLY

COMPATIBLE WITH ANY EXISTING SYSTEMS. ALL SYSTEM VENDORS SHALL

COORDINATE EXACT SYSTEM REQUIREMENTS WITH OW NER PRIOR TO BID. NEW

COMPONENTS SHALL BE INTERCONNECTED W ITH EXISTING SYSTEMS W HERE

POSSIBLE. ALL NEW SYSTEM DESIGNS AND PROGRAMMING SHALL BE

COORDINATED W ITH THE OW NER PRIOR TO ORDERING. ALL PROGRAMMING SHALL

BE INCLUDED AS REQUIRED BY THE OW NER. PROVIDE 4 HOURS OF TRAINING FOR

EACH SYSTEM.

PPPOW ER POLE AS NOTED

SWITCHES

MOMENTARY CONTACT SW ITCH

TIMER SW ITCH

S MC

S T

46"

46"

SV

S

S

VW ALL VOLUME CONTROL

PAGING SPEAKER: WALL

PAGING SPEAKER W / VOLUME CONTROL

PAGING SPEAKER: CEILING CLG

CLG

8'-0"

46"

OVERHEAD PAGING

RECESSED WALL MOUNTED PAGING SPEAKER

DUKANE 5A606 SPEAKER. ATLAS 417-8W D

LCD W ALL DISPLAY

8'-0" S

LD

R

FIRE ALARM

E,EMINDICATES EMERGENCY POW ER

SYSTEM

SYMBOL

PUSH-TO-EXIT BUTTON 46"

SURFACE W IRE-MOLD

PE

SPD

J

J

ML

ES

SEC-A

TXT

NAC

CC

CC

CR

RR

DP

DA

IM

KP

IR

KS

MS

PP

CR

DS

AD

IM

PIV

FAA

FACP

SEC-C

T

D R

A W

M B

O L

D R

A W

M B

O L

D R

A W

M B

O L

AS SHOWNLADDER CABLE TRAY, SIZE AS NOTED

AS SHOWNSOLID BOTTOM CABLE TRAY, SIZE AS NOTED

EQUIP-1

PLUMBING FIXTURE SOLENOID VALVE/ELECTRIC EYE

SENSOR CONNECTION. COORDINATE EXACT

CONNECTION REQUIREMENTS W ITH MANUFACTURER.

GROUND

NEUTRAL

PHASE

FIREMAN'S KNOX BOX CONNECTION KB

REMOTE FIRE ALARM ANNUNCIATOR W / MICROPHONE 54" FAAM

W ALL, CLG

W ALL, CLG V

A

F

CM

INDICATES CHIME AUDIBLE NOTIFACTION CH

DEVICE USED FOR ELEVATOR CONTROL EL

FIRE ALARM CONTROL EXTENDER EXT

4'-6''

TRANSPONDER CABINET 46" TRAN

BE , BR

PROJECTED BEAM SMOKE DETECTOR; EMITTER

(BE) AND RECEIVER (BR)

FLOOR

AV

AUDIO/VISUAL SYSTEM OUTLET W ITH DUPLEX

RECEPTACLE, REFER TO ASSOCIATED DETAIL FOR

ADDITIONAL INFORMATION

1'-6"

COMBINATION POW ER AND DATA OUTLET LOCATION,

REFER TO ASSOCIATED DETAIL FOR ADDITIONAL

INFORMATION

1'-6"

COMBINATION POWER AND DATA OUTLET LOCATION,

GFCI DUPLEX RECEPTACLE, REFER TO ASSOCIATED

DETAIL FOR ADDITIONAL INFORMATION

1'-6"

DEAD FRONT GFCI DEVICE, LABEL AND INSTALL IN

READILY ACCESSIBLE LOCATION

FILLED OUTER BARS INDICATES INTEGRAL INTEGRAL

USB OUTLETS IN ADDITION TO POW ER RECEPTACLES

1'-6"

, J

VARIABLE FREQUENCY DRIVE 5'-0"

CIRCLE ON ANY DEVICE INDICATES DEVICE FED FROM

STUB UP CONDUIT

MOTOR CONNECTION, REFER TO EQUIPMENT

CONNECTION SCHEDULE

DUPLEX RECEPTACLE, CEILING MOUNTED CLG

#D/#V

#D

INTERMEDIATE DISTRIBUTION FRAME - REFERENCE

DATA SYSTEM SCHEMATICS AND DETAILS FOR

ADDITIONAL REQUIREMENTS

MAIN DISTRIBUTION FRAME - REFERENCE DATA

SYSTEM SCHEMATICS AND DETAILS FOR ADDITIONAL

REQUIREMENTS

W IRELESS ACCESS POINT WITH PROVISIONS FOR (1)

DATA OUTLET FOR ANTENNA. PROVIDE A COMPLETE

DATA OUTLET W ITH FACEPLATE ABOVE CEILING,

MOUNTED AT AN ACCESSIBLE HEIGHT NO MORE THAN

24" ABOVE CEILING. AT EACH OUTLET, PROVIDE A 20'

COIL OF CABLE AHEAD OF THE OUTLET FOR

ADJUSTMENT OF FINAL OUTLET LOCATION. THE

CONTRACTOR SHALL COORDINATE EXACT LOCATIONS

W ITH THE OWNER AND ADJUST OUTLET LOCATIONS AT

SUBSTANTIAL COMPLETION TO ACCOMMODATE W AP

LOCATIONS.

TELECOMMUNICATIONS SYSTEM BACKBOARD. PROVIDE

96''H x 3/4''D FIRE-RETARDENT PLYW OOD BACKBOARD

W ITH TW O (2) COATS OF NON-C0NDUCTIVE, FIRE-

RETARDANT LIGHT GRAY PAINT, #3/0 TO GROUND BAR AT

MAIN SERVICE SW ITCHBOARD, 30-PT GROUND BAR AND

A 6'-0'', #3 AW G PIGTAIL AT BACKBOARD. INSTALL BOARD

AT 2' AFF. (LENGTH OF BOARD AS INDICATED ON FLOOR

PLAN)

W AP

DATA OUTLET : NUMBER BESIDE OUTLET

INDICATES NUMBER OF DATA JACKS

VOICE OUTLET : NUMBER BESIDE OUTLET

INDICATES NUMBER OF VOICE JACKS

COMBINATION OUTLET : #D INDICATES NUMBER OF

DATA JACKS, #V INDICATES NUMBER OF VOICE

JACKS.

DATA / VOICE

1'-6"

1'-6"

1'-6"

#V

MDF

IDF

TEL

CONDUIT UP

CONDUIT DOWN

GROUND BUS BAR ON INSULATED STANDOFFS 2'-0''

AS SHOWNBUS DUCT, AMPERAGES AS NOTED

M O

U N

T

IN

G H

E

IG

H T

(T O

C E

N T

E R

O F

B O

X

M O

U N

T

IN

G H

E

IG

C E

N T

E R

O F

B O

X

M O

U N

T

IN

G H

E

IG

C E

N T

E R

O F

B O

X

M O

U N

T

IN

G H

E

IG

C E

N T

E R

O F

B O

X

SLOW VOLTAGE THREE-WAY SW ITCH 46" LV3

SLOW VOLTAGE DIMMER THREE-W AY SW ITCH 46" LVD3

INDICATES MOUNTING FLUSH WITH CEILING. CLG

PANIC BUTTON 46" PB

SECURITY DURESS

E IN

I

HANS

ROBERT A.

EETT

SS

TATA

FF MOO

P O

F R

SO

S

I

U

R

R E

E

S

NA L

S IO ENG

NUMBER

PE-2006009888

10411 Meeting Street, Prospect, Kentucky 40059 502 326.3085 f 502 326.2691 www.cmta.com th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing # of

657-19-127JBFCA - RENOVATE SPACE FOR

DOMICILIARY PROVIDERS, BUILDING 2

5/1/2020

VA Health Care System Approval:

BID DOCUMENTS

ARCHITECT/ENGINEER:

A/E: PROJECT LEAD

Architect, Structural Engineer

Consultant:

CMTA CONSULTING ENGINEERS

10411 MEETING STREET

PROSPECT, KY 40059

502.326.3085

JEFFERSON BARRACKS

1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125

/1

/2

:1 :5

P

M

02-EJ-001

ELECTRICAL LEGEND

CMTACMTA

ELECTRICAL GENERAL NOTES:

A. EACH CONTRACTOR, PROPOSER, SUPPLIER AND/OR MANUFACTURER SHALL REFER TO ALL DOCUMENTS

PERTAINING TO THIS PROJECT AND COORDINATE ACCORDINGLY SO AS TO ENSURE ADEQUACY OF FIT, COMPLIANCE W ITH SPECIFICATIONS, PROPER VOLTAGE AND CURRENT CHARACTERISTICS TO AVOID

CONFLICT W ITH ANY OTHER BUILDINGS SYSTEMS. VERIFY SAME W ITH SHOP DRAW INGS.

B. ADDITIONAL ELECTRICAL REQUIREMENTS MAY BE SHOW N ON PLANS FROM OTHER DISCIPLINES IN THIS SET.

IT IS THE CONTRACTOR’S RESPONSIBILITY TO REVIEW ALL PLANS AND SPECIFICATIONS FOR A COMPLETE

UNDERSTANDING OF THE PROJECT REQUIREMENTS.

C. W ORK SHALL BE IN ACCORDANCE W ITH THE LATEST EDITION OF ALL LOCAL, STATE, AND NATIONAL CODES.

INCLUDING BUT NOT LIMITED TO NFPA 70 (NEC), NFPA 72, INTERNATIONAL BUILDING CODES, ETC.

D. CONTRACTOR SHALL FOLLOW SEISMIC RESTRAINT AND DESIGN REQUIREMENTS CONTAINED IN LATEST ADOPTED STATE AND INTERNATIONAL BUILDING CODES, W ITH ALL AMENDMENTS AS ADOPTED BY THE CURRENT LEGISLATION. REFER TO ELECTRICAL AND STRUCTURAL SPECIFICATIONS FOR ADDITIONAL

INFORMATION.

E. ALL OFFSETS, TURNS, FITTINGS, TRIM, DETAIL, ETC. MAY NOT BE INDICATED, BUT SHALL BE PROVIDED AS REQUIRED. ADDITIONAL ALLOW ANCES SHALL BE INCLUDED FOR SAME AT EACH PROPOSER’S DISCRETION.

F. INSTALL NO PIPING, CONDUIT, DUCTW ORK, ETC. IN A LOCATION OR IN A MANNER W HICH W ILL ALLOW FREEZING OR THE COLLECTION OF CONDENSATION THEREON. IF IN DOUBT, CONTACT THE ENGINEER.

G. ADVISE THE ENGINEER OF ANY CONFLICTS, ERRORS, OMISSIONS, ETC. AT LEAST TEN DAYS PRIOR TO BID

DATE, TO ALLOW CLARIFICATION BY W RITTEN ADDENDUM.

H. W HERE CONFLICTS ARE FOUND BETW EEN DRAW INGS, DETAILS, OR SPECIFICATIONS, THE MORE STRINGENT

REQUIREMENT SHALL APPLY. NOTIFY ARCHITECT OF DISCREPANCY IN W RITING.

I. DEVIATION FROM SPECIFICATIONS OR PLANS REQUIRES PRIOR W RITTEN APPROVAL FROM THE ENGINEERS

AND MUST BE SUBMITTED IN W RITING NO LATER THAN TEN DAYS PRIOR TO THE BID DATE.

J. OBSERVE ALL APPLICABLE CODES, RULES AND REGULATIONS THAT MAY APPLY TO THE W ORK UNDER THIS CONTRACT. (CITY, COUNTY, LOCAL, STATE, FEDERAL, MUNICIPALITY, UTILITY COMPANY, OSHA, ETC.).

K. MOUNTING HEIGHTS FOR W ALL MOUNTED DEVICES INDICATED ABOVE FINISHED FLOOR ARE TO CENTER OF DEVICE UNO. MOUNTING HEIGHTS TO CEILING SUSPENDED DEVICES ARE TO BOTTOM OF DEVICE UNO.

L. INSTALL EQUIPMENT, MATERIALS, ETC. IN STRICT ACCORDANCE W ITH MANUFACTURER’S

RECOMMENDATIONS AND DIRECTIONS. IF IN CONFLICT W ITH THE DESIGN INDICATED IN CONTRACT

DOCUMENTS, ADVISE THE ENGINEER PRIOR TO INSTALLATION FOR CLARIFICATION.

M. DO NOT RECESS PANELBOARD TUBS OR OTHER FLUSH-MOUNTED EQUIPMENT IN W ALLS THAT HAVE A FIRE RATING. NO INSTALLATION SHALL DIMINISH OR VOID FIRE RESISTIVE RATINGS IN ANYW AY.

N. THE PURPOSE AND INTENT OF ALL OF THE DOCUMENTS PERTAINING TO THIS PROJECT IS TO PROVIDE A COMPLETE, FUNCTIONAL, SAFE, LIKE-NEW FACILITY. ANYTHING LESS SHALL BE UNACCEPTABLE.

O. ALL SYSTEMS, EQUIPMENT AND MATERIALS ARE TO BE INSTALLED IN A NEAT AND W ORKMANLIKE MANNER.

W ORK NOT MEETING THIS CRITERION SHALL BE REMOVED AND REINSTALLED SATISFACTORILY. FINAL DETERMINATION OF THE ACCEPTABILITY OF THE QUALITY OF W ORK RESIDES W ITH THE ENGINEER

P. ALL W ORK, MATERIALS, EQUIPMENT, ETC. SHALL BE FULLY GUARANTEED FOR ONE FULL CALENDAR YEAR FROM THE DATE OF SUBSTANTIAL COMPLETION AS DOCUMENTED BY THE ENGINEER, UNLESS LONGER

W ARRANTY PERIODS FOR EQUIPMENT ARE SPECIFIED.

Q. UNLESS OTHERW ISE SPECIFIED OR INDICATED, ALL EQUIPMENT AND/OR MATERIALS W ITHIN OCCUPIED SPACES OR EXPOSED TO VIEW ON THE BUILDING EXTERIOR SHALL BE PRIMED AND FINISHED SO AS TO COMPLEMENT ADJACENT SURFACE, UNLESS OTHERW ISE NOTED. COORDINATE W ORK AND COLORS W ITH

ARCHITECT.

R. W HERE PENETRATING ROOFING MEMBRANE OR OTHER MATERIALS USED FOR W EATHERPROOFING THE BUILDING, MAKE SUCH PENETRATION IN A W AY THAT W ILL NOT VOID OR DIMINISH THE ROOFING W ARRANTY OR INTEGRITY IN ANYW AY. COORDINATE ALL SUCH PENETRATIONS W ITH THE ROOFING MANUFACTURER AND

ARCHITECT.

S. THE CONTRACTOR IS RESPONSIBLE FOR ALL UTILITY COMPANY FEES, CASH CONTRIBUTIONS OR OTHER COSTS THAT THE UTILITY COMPANY MAY REQUIRE TO COMPLETE THEIR W ORK. (ELECTRIC, TELEPHONE, TELEVISION, DATA, ETC.).

T. COORDINATE W ITH ARCHITECTURAL FLOOR PLANS, ELEVATIONS AND CASEW ORK DETAILS FOR LOCATION

OF ADDITIONAL RECEPTACLES, UTILITY OUTLETS, ELECTRICAL DEVICES, ETC.

U. CEILING-MOUNTED ELECTRICAL DEVICES SHALL BE CENTERED IN 2'X2' CEILING TILE AND INSTALLED CENTERED ON 2' DIMENSION OF 2'X4' TILE AND ON CENTERLINE OR A QUARTER POINT ON 4' DIMENSION.

V. ANY VIBRATING, OSCILLATING OR OTHER NOISE OR MOTION PRODUCING EQUIPMENT SHALL BE ISOLATED

FROM SURROUNDING SYSTEMS IN AN APPROVED MANNER. NOISY OR STRUCTURALLY DAMAGING

INSTALLATIONS SHALL BE SATISFACTORILY REPLACED OR REPAIRED AT THE INSTALLING CONTRACTORS' EXPENSE. THE FINAL DECISION ON THE SUITABILITY OF A PARTICULAR INSTALLATION'S ACCEPTABILITY SHALL

BE THAT OF THE ENGINEER.

W . CHECK ALL THREE PHASE MOTORS W ITH A PHASE ROTATION METER, PRIOR TO PLACING IN SERVICE.

X. PROVIDE DETAILED SHOP DRAW INGS TO ENGINEER PRIOR TO PURCHASING OR INSTALLING ANY EQUIPMENT Y. DEVIATIONS IN SIZES, CAPACITIES, FIT, FINISH, ETC. FOR EQUIPMENT FROM THAT PRIME SPECIFIED SHALL BE

THE RESPONSIBILITY OF THE PURCHASER OF THAT EQUIPMENT. ANY PROVISIONS REQUIRED TO

ACCOMMODATE A DEVIATION, W HETHER APPROVED BY THE ENGINEER OR NOT, SHALL BE THE

RESPONSIBILITY OF THE PURCHASER.

Z. THE CONSTRUCTION MANAGER, GENERAL CONTRACTOR, OR W HOMEVER HOLDS THE PRIME CONTRACT(S) FOR THIS CONSTRUCTION IS RESPONSIBLE FOR THE COORDINATION, APPEARANCE, SCHEDULING AND TIMELINESS OF THE W ORK OF ALL TRADES, CONTRACTORS, SUPPLIERS, INSTALLERS, ETC. POOR OR UNTIMELY W ORK ON THE PART OF ANY SUBCONTRACTOR SHALL BE RESOLVED BY THE PARTY W HO

ENGAGED THEM ON THIS PROJECT.

AA. W HERE MOUNTING HEIGHTS ARE NOT INDICATED OR ARE IN CONFLICT W ITH ANY OTHER BUILDING SYSTEM, CONTACT THE ENGINEER BEFORE AFFECTING INSTALLATION. REFER ALSO TO ARCHITECTURAL INTERIOR AND EXTERIOR ELEVATIONS, CEILING HEIGHTS AND OTHER DETAILS OF THESE DOCUMENTS, AS APPLICABLE.

BB. W HERE FIRE-RATED CEILING ASSEMBLIES ARE NOTED, PROVIDE UL-LISTED FIRE-RATED GYPSUM BOARD OR PRE-MANUFACTURED ENCLOSURES ABOVE LUMINAIRES, CEILING DEVICES, ETC. IN OR ON CEILING, AS

REQUIRED TO MAINTAIN CEILING RATINGS.

CC. COORDINATE THE LOCATION OF DRAINS, ELECTRICAL OUTLETS, GAS OUTLETS, ETC. W ITH ALL CASEW ORK, KITCHEN EQUIPMENT, MECHANICAL ROOM EQUIPMENT, ETC. PRIOR TO COMMENCING INSTALLATION. W ORK

NOT SO COORDINATED SHALL BE REMOVED AND PROPERLY INSTALLED AT THE EXPENSE OF THE

RESPONSIBLE CONTRACTOR(S).

DD. ALL ELECTRICAL COMPONENTS OR EQUIPMENT SHALL BE LISTED AND LABELED BY UNDERW RITER'S LABORATORIES OR OTHER APPROVED LISTING AGENCY. APPROVAL AND LABELING OF INDIVIDUAL COMPONENTS ON AN ASSEMBLY IS NOT ACCEPTABLE AS MEETING THIS REQUIREMENT, UNLESS W AIVED BY

THE ENGINEER IN W RITING.

EE. ALL W IRING SYSTEMS SHALL BE INSTALLED W ITH A MINIMUM OF SPLICES. CONDUCTORS, W HETHER SINGLE OR MULTI-PAIR, SHALL BE INSTALLED CONTINUOUS INSOFAR AS POSSIBLE FROM TERMINAL POINT TO

TERMINAL POINT.

FF. NO CONDUIT, SUPPORTS, ETC. SHALL BE RUN THROUGH ACCESS CLEARANCES OF EQUIPMENT BY OTHER

TRADES (I.E. VAV BOXES). COORDINATE W ITH ALL TRADES PRIOR TO CONSTRUCTION.

GG. ALL CONTRACTORS SHALL EXERCISE EXTREME CARE IN THE COURSE OF THEIR W ORK SO AS TO ENSURE THAT THEY DO NOT INTERRUPT ANY EXISTING SERVICE OR SUB-SERVICE FOR SAFETY PURPOSES. PAY PARTICULAR ATTENTION TO THIS PRECAUTION RELATIVE TO NATURAL GAS AND ELECTRICAL LINES. VERIFY THE LOCATION, SIZE, TYPE, ETC. OF EACH UNDERGROUND OR OVERHEAD UTILITY. ALL W ORK SHALL BE PERFORMED IN ACCORDANCE W ITH ALL FEDERAL, STATE AND/OR LOCAL RULES, REGULATIONS, STANDARD AND SAFETY REQUIREMENTS. UTILITIES SHALL BE INSTALLED IN ACCORDANCE W ITH THE APPLICABLE MUNICIPALITY OR UTILITY COMPANY STANDARDS. IN ALL CASES, THE MOST STRINGENT REQUIREMENT SHALL

APPLY.

HH. ALL SUPPORTS FOR EQUIPMENT, DEVICES OR FIXTURES SHALL BE UNIQUE, DIRECTLY FROM THE BUILDING STRUCTURE. DO NOT SUPPORT W ORK FROM OTHER TRADES EQUIPMENT OR SUPPORTS W ITHOUT W RITTEN

PERMISSION FROM THE ENGINEER AND CONSENT OF THE OTHER TRADE, IN W RITING.

II. W HERE INTERRUPTING AN EXISTING UTILITY OR SERVICE DELIBERATELY OR ACCIDENTALLY, THE RESPONSIBLE CONTRACTOR SHALL W ORK CONTINUOUSLY AS NEEDED TO RESTORE SAME, PROVIDING

PREMIUM TIME AS NEEDED.

JJ. REFER TO ARCHITECTURAL W ALL ELEVATIONS (W HERE GIVEN) FOR HEIGHTS AND MOUNTING RELATIONSHIP OF OUTLETS AND EQUIPMENT. IF IN DOUBT, CONTACT ENGINEER FOR DIRECTION PRIOR TO ROUGH IN.

KK. FLUSH OR PEDESTAL TYPE FLOOR OUTLETS/BOXES, AS INDICATED ON PLAN, SHALL BE LOCATED BY DIMENSIONS PROVIDED BY THE ARCHITECT, UNLESS OTHERW ISE SHOW N ON PLANS. IF IN DOUBT, CONTACT

THE ENGINEER PRIOR TO ROUGHING-IN ANY W ORK.

LL. AS APPLICABLE, REFER TO ARCHITECTURAL PHASING PLANS AND PHASING BOUNDARIES ON THESE DRAW INGS FOR SEQUENCING OF W ORK, FULL EXTENT OF AREAS INVOLVED, EXTENT OF CEILING W ORK, ETC.

PROVIDE TEMPORARY CONNECTIONS FOR CIRCUITS AND W ORK AS REQUIRED TO MAINTAIN SEQUENCE OF

THE W ORK FROM PHASE TO PHASE.

MM. THIS CONTRACTOR SHALL BE RESPONSIBLE FOR ALL CUTTING AND PATCHING REQUIRED FOR HIS W ORK.

ALL CUTTING AND PATCHING SHALL BE IN ACCORDANCE W ITH THE ARCHITECT'S STANDARDS FOR SUCH

W ORK.

NN. ALL W ORK SHALL BE CONCEALED UNLESS SPECIFICALLY INDICATED TO BE EXPOSED, OR REQUIRED TO BE EXPOSED. IF IN DOUBT, CONTACT THE ENGINEER FOR CLARIFICATIONS PRIOR TO INSTALLING ANY SUCH

W ORK.

OO. INTERRUPTION OF ANY EXISTING SERVICES SHALL BE COORDINATED W ITH THE OW NER, GENERAL CONTRACTOR, UTILITY COMPANY AS NECESSARY, AND THE ARCHITECT, AT LEAST TW O W EEKS IN ADVANCE OF ANTICIPATED INTERRUPTION. A SCHEDULE FOR THESE OUTAGES SHALL BE DEVELOPED AND AGREED UPON BETW EEN THE PARTIES MENTIONED TO AVOID UNNECESSARY INCONVENIENCE TO THE OW NER OR ANY AFFECTED PARTY. NOTIFY THE UTILITY COMPANY OF ANY ANTICIPATED SERVICES REQUIRED TW O W EEKS IN ADVANCE, IN W RITING. IF UTILITY COMPANY REQUIRES A LONGER NOTIFICATION PERIOD, SO

PROVIDE.

PP. W HERE BACKBOXES ARE LOCATED IN THE SAME VERTICAL CHANNEL/STUD SPACE ON OPPOSITE SIDES OF THE SAME W ALL, PROVIDE SOUND-INSULATING PUTTY AROUND BOXES AS REQUIRED TO ELIMINATE SOUND

TRANSMISSION FROM ROOM TO ROOM.

QQ. JUNCTION BOXES LOCATED ABOVE ACCESSIBLE CEILINGS SHALL BE LOCATED NO MORE THAN 36” ABOVE CEILING LEVEL. LABEL EACH BOX IN AREA OF W ORK W ITH A PERMANENT MARKER OR IN ACCORDANCE W ITH

SPECIFICATIONS, W HICHEVER IS MORE STRINGENT.

RR. ALL MATERIALS FURNISHED AND ALL W ORK INSTALLED SHALL COMPLY W ITH THE CURRENT EDITION OF THE NATIONAL ELECTRICAL CODES, NATIONAL FIRE CODES OF THE NATIONAL FIRE PROTECTION ASSOCIATION, THE REQUIREMENTS OF LOCAL UTILITY COMPANIES, AND W ITH THE REQUIREMENTS OF ALL GOVERNMENTAL AGENCIES OR DEPARTMENTS HAVING JURISDICTION. IF ANY CONFLICTS OR DISCREPANCIES OCCUR THE

MOST STRINGENT SHALL APPLY.

SS. DO NOT SCALE FROM DRAW INGS, AS PRINTING DISTORTS SCALE. W ORK SHALL BE LAID OUT FROM

DIMENSIONED DRAW INGS, OR DIMENSIONS SUPPLIED TO THE CONTRACTOR.

TT. NOISY W ORK, W ORK OUTSIDE CONSTRUCTION BARRIERS, W ORK IN OCCUPIED AREAS, ETC. SHALL BE PERFORMED AFTER HOURS OR ON W EEKENDS. COORDINATE EXACT SCHEDULING W ITH FACILITY PRIOR TO

CONSTRUCTION.

UU. ALL ITEMS HAVING KEYED LOCKS/OPERATORS SHALL HAVE CORED LOCKS/OPERATORS. ALL KEYING SHALL MATCH THE OW NER'S EXISTING KEY-W AYS. COORDINATE EXACT REQUIREMENTS W ITH OW NER PRIOR TO

CONSTRUCTION.

VV. REFER TO ARCHITECTURAL PLANS FOR PHASING REQUIREMENTS. W ORK SHALL BE COMPLETED IN PHASES PER THE PHASING PLAN AND AS COORDINATED W ITH OW NER AND GENERAL CONTRACTOR. PROVIDE ALL REQUIRED INCREMENTAL INSPECTIONS, CERTIFICATIONS, ETC. AND ALL TEMPORARY SERVICES AS

REQUIRED BY OW NER TO ACCOMPLISH THE PHASING PLAN.

PIV

FS

TS

FACP

DH

SS SS

SS SS

SS SS

SDSD

SDSD

SDSD

SDSD

SDSD

SDSD

FAA

DHDH

SD

F

S

FIRE ALARM POST INDICATING VALVE

FIRE ALARM MANUAL PULL STATION

CEILING SPEAKER

DUAL ALERT STROBE (VISUAL OUTPUT @ 110 CANDELAS)

FIRE ALARM TAMPER SW ITCH

FIRE ALARM FLOW SW ITCH

FIRE ALARM CONTROL PANEL

FIRE ALARM REMOTE ANNUNCIATOR

CEILING MOUNTED FIRE ALARM SMOKE DETECTOR

FIRE ALARM SYSTEM RISER LEGEND:

MAGNETIC DOOR HOLDER - RELEASES UPON FIRE ALARM ACTIVATION

COORDINATE ROUGH-IN LOCATION W ITH ARCHITECT

FIRE ALARM SYSTEM GENERAL NOTES:

EXISTING ADDRESSABLE

FIRE ALARM CONTROL

PANEL (FACP).

TS

TS

FS

FLOW SW ITCH ON

INCOMING FIRE

RISER (W ET-PIPE

SYSTEM)

INDICATING DEVICE CIRCUIT (LEVEL 02)

INDICATING DEVICE CIRCUIT (LEVEL 01)

FROM EXTERIOR FIRE

PIT TAMPER SW ITCHES

(2)

LIGHTNING ARRESTOR

FOR ALL EXTERIOR

UNDERGROUND

SIGNAL CIRCUITS.

4" SQUARE BOX

LEVEL 02

LEVEL 01

COORDINATE W ITH DRAW INGS

FOR ACTUAL NUMBER OF

TAMPER AND FLOW SW ITCHES

REQUIRED TO BE MONITORED

ON THE FIRE SUPPRESSION

RISER AND THE SUPPRESSION

ZONES ON EACH FLOOR.

MAGNETIC DOOR HOLD - TYPICAL PER ENTRANCES

INTO RATED STAIRW ELLS ON ALL FLOORS

1. EXISTING FIRE ALARM SYSTEM IS FIREFINDER MANUFACTURED BY SIEMENS.

2. PROVIDE ADDRESSABLE NOTIFICATION APPLIANCES W ITH THIS SYSTEM. THESE

APPLIANCES ARE TO BE W HITE W ITH RED LETTERING. AUDIBLE NOTIFICATION

APPLIANCES ARE TO UTILIZE A AUDIBLE HORN SETTING AT A MINMINUM OF 87dB.

VISUAL NOTIFICATION APPLIANCES SHALL BE CAPABLE OF MULTIPLE CANDELA

SETTINGS UP TO 110 CANDELAS. ALL CONDUIT IN THE FIRE ALARM SYSTEM SHALL BE

3/4" SIZE EXCEPT AS OTHERW ISE NOTED. PROVIDE LARGER CONDUIT IF REQUIRED TO

MAINTAIN CONDUCTORS AT 40% MAX. FILL.

3. THE ENTIRE FIRE ALARM SYSTEM INSTALLATION SHALL BE IN FULL ACCORDANCE W ITH

THE CURRENT EDITION OF THE NFPA, THE AMERICANS W ITH DISABILITIES ACT AND ALL

OTHER APPLICABLE CODES.

4. COORDINATE W ITH THE DOOR HARDW ARE SET SPECIFICATIONS AND THE OW NER'S

SECURITY REPRESENTATIVE TO VERIFY DOORS THAT W ILL REQUIRE CONNECTION TO

THE FIRE ALARM SYSTEM.

5. THE SENSITIVITY OF SMOKE DETECTORS SHALL BE ADJUSTED FOR THE SERVICE DUTY

IN THE AREA INDICATED, TO SUIT BUILDING OPERATIONAL CONDITIONS.

6. W IRE SIZE SELECTIONS FOR AUDIO/VISUAL UNITS SHALL BE CALCULATED AND SHALL

BE IN ACCORDANCE W ITH THE MANUFACTURER'S RECOMMENDATIONS.

7. RISER DIAGRAM FOR FIRE ALARM SYSTEM IS PARTIAL DIAGRAM FOR BID PURPOSES

ONLY. SYSTEM SHALL BE INSTALLED AND CONNECTED IN ACCORDANCE W ITH W IRING

DIAGRAMS OBTAINED FROM MANUFACTURER AND THAT HAVE BEEN APPROVED BY

THE STATE FIRE MARSHALL'S OFFICE OR THE LOCAL AUTHORITY HAVING JURISDICTION,

AS APPLICABLE. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO CONFIRM ALL

QUANITIES AND LOCATION OF FIRE ALARM DEVICES PRIOR TO SYSTEM ACTIVATION.

8. AUTOMATIC FIRE ALARM DETECTORS SHALL BE LOCATED SO AS TO PREVENT

SHIELDING BY DUCTW ORK, EQUIPMENT AND PIPING ON CEILING. SPACING BETW EEN

DETECTORS SHALL BE IN ACCORDANCE W ITH MANUFACTURER'S RECOMMENDATIONS

IN ANY CASE. ADDITIONAL DETECTORS SHALL BE PROVIDED IF NEEDED TO ENSURE

COMPLETE COVERAGE OF THE INDICATED SPACE.

9. FIRE ALARM SIGNALING DEVICES SHALL BE SEMI-FLUSH TYPE AUDIBLES W ITH

FLASHING LAMP MOUNTED ON SAME PLATE. SURFACE-MOUNTED UNITS MAY BE USED

IN UNFINISHED AREAS.

10. NO SMOKE DETECTORS SHALL BE LOCATED CLOSER THAN 36" TO SUPPLY, RETURN OR

EXHAUST AIR OPENINGS NOR CLOSER THAN 12" TO W ALL/CEILING INTERSECTIONS.

BASEMENT

INDICATING DEVICE CIRCUIT (BASEMENT)

TAMPER SW ITCH ON

INCOMING FIRE RISER

(W ET-PIPE SYSTEM)

TAMPER SW ITCH ON

INCOMING FIRE RISER

(W ET-PIPE SYSTEM)

CEILING

MOUNTED SMOKE

DETECTOR

CEILING

MOUNTED SMOKE

DETECTOR

CEILING

MOUNTED SMOKE

DETECTOR

CEILING

MOUNTED SMOKE

DETECTOR

CEILING

MOUNTED SMOKE

DETECTOR

CEILING

MOUNTED SMOKE

DETECTOR

A

A

A

TXT

A A

TXT

A A

TXT

TXT SCROLLING TEXTUAL APPLIANCE

E IN

I

HANS

ROBERT A.

EETT

SS

TATA

FF MOO

P O

F R

SO

S

I

U

R

R E

E

S

NA L

S IO ENG

NUMBER

PE-2006009888

10411 Meeting Street, Prospect, Kentucky 40059 502 326.3085 f 502 326.2691 www.cmta.com th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing # of

657-19-127JBFCA - RENOVATE SPACE FOR

DOMICILIARY PROVIDERS, BUILDING 2

5/1/2020

VA Health Care System Approval:

BID DOCUMENTS

ARCHITECT/ENGINEER:

A/E: PROJECT LEAD

Architect, Structural Engineer

Consultant:

CMTA CONSULTING ENGINEERS

10411 MEETING STREET

PROSPECT, KY 40059

502.326.3085

JEFFERSON BARRACKS

1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125

/1

/2

:1 :5

P

M

02-EJ-601

PARTIAL FIRE ALARM SYSTEM RISER

DIAGRAM

AuthorChecker

PARTIAL FIRE ALARM SYSTEM RISER DIAGRAM

SD

F

SD

F

F

S S

S

S S

S

S

S

W AP

W AP

W AP

N A

C

KP

CR

IR

IM

F

F F

F

F F

F

V V

FF

F

TS

FS

DS

PB

PB

PB PB

PB

PB

PB

PB

PB

PB

PB

PB

PB

PB PB

PBPB

PB

PB

PB

PB

PP PP

PPPP

ADAD

CC

CC

CC CC

CC

CC

CC

TXT TXT

T X

T

TXT

T X

T

A A A

A

A A A

A A

A

A A

F

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

123OFFICE

OFFICE

OFFICE

OFFICE

VESTIBULE

STAIR 1

ELEV LOBBY

MECH

ELEV

OIT

ELEC

JAN

GROUP

COMPUTER

MEN

W OMEN

CORRIDOR

CORRIDOR

MULTI-PURPOSE

STAIR 2

S133

STAIR 3

S103

CORRIDOR

STORAGE/COPY

T E

L

T E

L

EX

EX

EX

S3

S3

S3

S3 S3

S3

S3

S3

S3

S3

S3

S3

S3

S3

S3

S3

S3

S3S3

S3

2D/1V

2D/1V

2D/1V

2D/1V

2D/1V.

2D/1V

2D/1V

2D/1V

2D/1V

2D/1V

2D/1V

2D/1V

2D/1V

2D/1V

2D/1V

2D/1V

2D/1V

2D/1V

2D/1V

2D/1V

2D/1V

2D/1V

2D/1V

2D/1V

2D/1V .

2D/1V

2D/1V

S4

S4

2D/1V

2D/1V

2D/1V

2D/1V

2D/1V

S3

2D/1V

2D/1V

2D/1V

2D/1V

2D/1V

2D/1V

2D/1V

2D/1V

2D/1V

2D

S5

2D/1V

EXIST COAX

PANEL

PANEL L1-1

S7

S7

S7 S7

S7

S1

S1

S1

S1

S1 S1

S1

S9

S8

S10

S4

S11 S11

S11

S11

S11

S11

S11

S11

S11

S11

S11

DATA

RACK (TYP)

S12

S11

S11

S11

S11

S11

S11

S11

S11

-48L1-1

S11 S14

S14

S14

S15S15

SEC-A

-46L1-1

STORAGE

S1

S1 S1 S1 S1 S1

S1

S1 S1

E IN

I

HANS

ROBERT A.

EETT

SS

TATA

FF MOO

P O

F R

SO

S

I

U

R

R E

E

S

NA L

S IO ENG

NUMBER

PE-2006009888

10411 Meeting Street, Prospect, Kentucky 40059 502 326.3085 f 502 326.2691 www.cmta.com th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing # of

657-19-127JBFCA - RENOVATE SPACE FOR

DOMICILIARY PROVIDERS, BUILDING 2

5/1/2020

VA Health Care System Approval:

BID DOCUMENTS

ARCHITECT/ENGINEER:

A/E: PROJECT LEAD

Architect, Structural Engineer

Consultant:

CMTA CONSULTING ENGINEERS

10411 MEETING STREET

PROSPECT, KY 40059

502.326.3085

JEFFERSON BARRACKS

1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125

/1

/2

:1 :5

P

M

02-ET-111

SYSTEMS PLAN - FLOOR 01

CMTACMTA

SCALE: 1/4" = 1'-0"02-ET-111

1 Systems Plan - Floor 01

GENERAL NOTES (SYSTEMS):

A. REFER TO THE ARCHITECT'S REFLECTED CEILING PLANS, ELEVATIONS,

AND CASEW ORK DETAILS FOR EXACT LOCATIONS OF ALL W ALL AND

CEILING MOUNTED ELECTRICAL DEVICES.

B. CONTRACTOR SHALL FOLLOW BRANCH CIRCUITING LAY-OUT, AS

INDICATED ON THE FLOOR PLANS, W ITH A MAXIMUM OF THREE (3)

BRANCH CIRCUITS PER HOMERUN. EACH BRANCH CIRCUIT SHALL BE

PROVIDED W ITH A DEDICATED NEUTRAL CONDUCTOR. DEDICATED

NEUTRAL CONDUCTORS SHALL BE CONSIDERED CURRENT

CARRYING. IF ADDITIONAL CONDUCTORS ARE RAN IN THE SAME

CONDUIT W ITH THOSE INDICATED, CONTRACTOR SHALL DERATE ALL

CURRENT CARRYING CONDUCTORS PER NEC 310.15(B)(3), AND UPSIZE

CONDUIT AS REQUIRED PER NEC 300.17 AND ANNEX C. MULTIW IRE

BRANCH CIRCUITS AS DEFINED IN NEC 100 / 210.4 (CIRCUITS SHARING A

COMMON NEUTRAL CONDUCTOR) SHALL NOT BE PERMITTED.

C. IDENTIFY THE PANEL AND CIRCUIT NUMBER FOR ALL RECEPTACLES,

SW ITCHES, ETC. IN AREA OF CONSTRUCTION. PROVIDE CLEAR

ADHESIVE LABELS W ITH BLACK LETTERING. IN HEALTHCARE FACILITIES,

ENGRAVE EMERGENCY DEVICE COVERPLATES IN PATIENT CARE

AREAS. MARK INSIDES OF ALL DEVICE BOXES W ITH PANEL AND CIRCUIT

NUMBER.

D. REFER TO "SYSTEM INSTALLATION MATRIX" (ON SYSTEMS LEGEND

SHEET) AND SPECIFICATIONS FOR CONTRACTOR REQUIREMENTS OF

EACH SYSTEM.

E. THE CONTRACTOR SHALL ROUTE ALL ''SYSTEM CONDUIT STUB-UPS'' TO

THE NEAREST CORRIDOR CABLING PATH (SEE ''STUB-UP'' DETAILS).

REFER TO CABLING PATH INSTALLATION DETAIL FOR ADDITIONAL

REQUIREMENTS.

F. CONTRACTOR SHALL PAINT ALL SYSTEMS CONDUIT STUB-UPS LIGHT

BLUE FOR SYSTEMS CABLING INTO THE CORRIDOR CABLING PATH.

PROVIDE PULL STRINGS IN ALL NEW CONDUIT RUNS FOR SYSTEM

CABLING INSTALLATION.

N

TAGGED NOTES

S1 NEW LOCATION FOR EXISTING CEILING MOUNTED FIRE ALARM

DEVICE. SALVAGED ROM DEMOLITION. CONNECT TO

EXISTING FIRE ALARM SYSTEM AS REQUIRED.

S3 DEVICE TO BE INCLUDED IN THE BID DEDUCT.

S4 PROVIDE (2)-4" CONDUIT SLEEVES THROUGH WALLS

INDICATED. INSTALL BOTTOM OF SLEEVES AT A HEIGHT NO

LOWER THAN THE TOP OF THE CABLE TRAY. REFER TO WALL

PENETRATION FIRE PROOFING DETAIL ON SHEET EJ-501.

S5 PROVIDE DATA OUTLET WITH TWO DATA CONNCTIONS FOR

CONNECTION TO PROJECTOR. COORDINATE EXACT

MOUNTING LOCATION WITH PROJECTOR INSTALLER/OWNER.

S7 PROPOSED CABLING PATH - COORDINATE ALL PATHS WITH

PIPING, DUCTWORK, ETC. (NOTE : STUB-UP CONDUITS SHALL

BE ROUTED TO THESE CABLING PATHS). PROVIDE CABLE

TRAY ALONG ALL REQUIRED CABLING PATHS. WHERE

CABLING PATH IS INTERRUPTED BY DUCTWORK, PIPING, ETC,

PROVIDE CABLE TRAY PATH BELOW AS REQUIRED TO

MAINTAIN A CONTINUOUS CABLING PATH - REFER TO

INSTALLATION DETAILS FOR FURTHER REQUIREMENTS.

CABLE TRAY IN OIT ROOMS ARE TO BE INSTALLED AROUND

PERIMETER OF ROOM PER VA OIT DEISGN GUIDE TEMPLATES;

PROVIDE AS REQUIRED.

S8 AUDIO/VIDEO INTERCOM MASTER STATION WITH DOOR

RELEASE FOR CONTROL OF FRONT DOOR. PROVIDE POWER

SUPPLIES & DOOR RELAY CONTACTS, ALL CABLING,

CONNECTORS, RELAYS, ETC. AS REQUIRED FOR A COMPLETE

AND OPERATIONAL SYSTEM. AUDIO/VIDEO INTERCOM UNIT TO

BE AIPHONE#AX-8MV OR APPROVED EQUIVALENT. COLOR TO

BE SELECTED BY COR.

S9 AUDIO/VIDEO INTERCOM REMOTE STATION WITH FLUSH-MTD

S.S. ENCLOSURE. REMOTE STATION TO BE AIPHONE #AX-DVF

OR APPROVED EQUIVALENT.

S10 PROVIDE (4)-4" CONDUIT SLEEVES THROUGH WALLS

INDICATED. INSTALL BOTTOM OF SLEEVES AT A HEIGHT NO

LOWER THAN THE TOP OF THE CABLE TRAY. REFER TO WALL

PENETRATION FIRE PROOFING DETAIL ON SHEET EJ-501 FOR

ADDITIONAL DETAILS.

S11 PROVIDE PANIC BUTTON AND ASSOCIATED ROUGH-IN PER

VENDOR REQUIREMENTS. COORDINATE LOCATION WITH

OWNER/VENDOR PRIOR TO ROUGH-IN.

S12 PROVIDE THE FOLLOWING CABLING SYSTEM ROUTED FROM

DATA RACK:

a). TWO 12-STRAND FIBER OPTIC CABLE ASSEMBLY WITH

MULTI-FIBER PUSH-ON CONNECTORS ROUTED TO THE DATA

RACK LOCATED IN THE BASEMENT O.I.T. CLOSET G04.

PROVIDE TWO CASSETTES WITH 12 DUPLEX LC INTERFACES IN

BOTH THE BASEMENT AND NEW O.I.T. CLOSET DATA RACKS

FOR CABLING TERMINATIONS.

b). ONE 100 PAIR COPPER CABLE FROM NEW DATA RACK TO

110 BLOCK(S) INSTALLED IN ADJACENT MECHANICAL ROOM.

CONTRACTOR PROVIDE 110 BLOCKS AND TERMINATIONS AS

REQUIRED.

S14 PROVIDE 360 DEGREE CCTV CAMERA.

S15 PROVIDE CCTV CAMERA FOR STAIRWELL COVERAGE AS

REQUIRED; COORDINATE DETAILS WITH COR.

CRITICAL WIDE AREA NETWORK GENERAL NOTE:

COORDINATE REINSTALLATION OF CEILING MOUNTED ACCESS POINTS FOR W IDE AREA NETW ORK W ITH OW NER.

(DEVICES ARE SHOW N AS EXISTING, BUT W ILL NEED TO BE REW ORKED FOR INSTALLATION OF NEW CEILING.

COORDINATE REW ORK DETAILS W ITH OW NER.)

Revisions: Date:

ADDENDUM #1 1/21/2022

F

F

F

F

F

S

S

S S

S

S

S

W AP

W AP

W AP

F

CR

DS

DS

CR

CR

F

F

F

V V

FS

TS

SD

PB

PP

PPPP

PP

ADAD

TXT TXT

SD

TXT

F

A A A A

F

T E

L

STAIR 3

STAIR 2

OIT

ELEV

HAC

MECH

STORAGE

218A

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

ELEC

OFFICE

COPY ROOM

STAIR 1

S200

CONFERENCE

MEN

W OMEN

CORRIDOR

CUBICLE BAY

OFFICE

W ORKSTATION

OFFICE

OFFICE

KITCHENETTE

S1

S1

S1

S1

S3

S3 S3 S3

S3

S3

2D/1V

2D/1V

2D/1V 2D/1V

2D/1V

2D/1V

2D/1V

2D/1V

2D/1V

2D/1V

2D/1V

2D/1V

2D/1V

2D/1V

S4

S4

2D/1V

2D/1V

2D

S5

S6

EXIST COAX

PANEL

PANEL L2-1

S7

S7

S7

S1

S11

EX.

S13

DATA

RACK (TYP)

S12

-36L2-1

2D/1V.

2D/1V

-37L2-1

SEC-A

S1

S1

S1

S1

S1

S1

S1 S1

S1 S1

S1

E IN

I

HANS

ROBERT A.

EETT

SS

TATA

FF MOO

P O

F R

SO

S

I

U

R

R E

E

S

NA L

S IO ENG

NUMBER

PE-2006009888

10411 Meeting Street, Prospect, Kentucky 40059 502 326.3085 f 502 326.2691 www.cmta.com th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing # of

657-19-127JBFCA - RENOVATE SPACE FOR

DOMICILIARY PROVIDERS, BUILDING 2

5/1/2020

VA Health Care System Approval:

BID DOCUMENTS

ARCHITECT/ENGINEER:

A/E: PROJECT LEAD

Architect, Structural Engineer

Consultant:

CMTA CONSULTING ENGINEERS

10411 MEETING STREET

PROSPECT, KY 40059

502.326.3085

JEFFERSON BARRACKS

1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125

/1

/2

:1 :5

P

M

02-ET-121

SYSTEMS PLAN - FLOOR 02

CMTACMTA

SCALE: 1/4" = 1'-0"02-ET-121

1 Systems Plan - Floor 02

GENERAL NOTES (SYSTEMS):

A. REFER TO THE ARCHITECT'S REFLECTED CEILING PLANS, ELEVATIONS,

AND CASEW ORK DETAILS FOR EXACT LOCATIONS OF ALL W ALL AND

CEILING MOUNTED ELECTRICAL DEVICES.

B. CONTRACTOR SHALL FOLLOW BRANCH CIRCUITING LAY-OUT, AS

INDICATED ON THE FLOOR PLANS, W ITH A MAXIMUM OF THREE (3)

BRANCH CIRCUITS PER HOMERUN. EACH BRANCH CIRCUIT SHALL BE

PROVIDED W ITH A DEDICATED NEUTRAL CONDUCTOR. DEDICATED

NEUTRAL CONDUCTORS SHALL BE CONSIDERED CURRENT

CARRYING. IF ADDITIONAL CONDUCTORS ARE RAN IN THE SAME

CONDUIT W ITH THOSE INDICATED, CONTRACTOR SHALL DERATE ALL

CURRENT CARRYING CONDUCTORS PER NEC 310.15(B)(3), AND UPSIZE

CONDUIT AS REQUIRED PER NEC 300.17 AND ANNEX C. MULTIW IRE

BRANCH CIRCUITS AS DEFINED IN NEC 100 / 210.4 (CIRCUITS SHARING A

COMMON NEUTRAL CONDUCTOR) SHALL NOT BE PERMITTED.

C. IDENTIFY THE PANEL AND CIRCUIT NUMBER FOR ALL RECEPTACLES,

SW ITCHES, ETC. IN AREA OF CONSTRUCTION. PROVIDE CLEAR

ADHESIVE LABELS W ITH BLACK LETTERING. IN HEALTHCARE FACILITIES,

ENGRAVE EMERGENCY DEVICE COVERPLATES IN PATIENT CARE

AREAS. MARK INSIDES OF ALL DEVICE BOXES W ITH PANEL AND CIRCUIT

NUMBER.

D. REFER TO "SYSTEM INSTALLATION MATRIX" (ON SYSTEMS LEGEND

SHEET) AND SPECIFICATIONS FOR CONTRACTOR REQUIREMENTS OF

EACH SYSTEM.

E. THE CONTRACTOR SHALL ROUTE ALL ''SYSTEM CONDUIT STUB-UPS'' TO

THE NEAREST CORRIDOR CABLING PATH (SEE ''STUB-UP'' DETAILS).

REFER TO CABLING PATH INSTALLATION DETAIL FOR ADDITIONAL

REQUIREMENTS.

F. CONTRACTOR SHALL PAINT ALL SYSTEMS CONDUIT STUB-UPS LIGHT

BLUE FOR SYSTEMS CABLING INTO THE CORRIDOR CABLING PATH.

PROVIDE PULL STRINGS IN ALL NEW CONDUIT RUNS FOR SYSTEM

CABL…

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .