This is a technical specifications document for Bid #2630 issued by the University of Southern Mississippi for the procurement of aquaculture water temperature control equipment for an Oyster Hatchery and Research Center. The university is soliciting sealed bids for drop-in water chillers, air-cooled reversible heat pump units, and commercial-duty heat/chill pump systems. The equipment specifications call for three low-profile drop-in water chillers with 6,000 BTUH cooling capacity and 115V single-phase electrical service; four air-cooled reversible heat pump/chiller units with identical cooling capacity and electrical requirements; six medium-capacity units rated at 5 tons (60,000 BTUH) with 208-240V single-phase power; two large-capacity units rated at 7.5 tons (90,000 BTUH) with 208-240V three-phase power; and two extra-large capacity units rated at 10 tons (120,000 BTUH) with 208-240V three-phase power, for a total of 17 units. All equipment must be new, unused, current production models suitable for marine and freshwater aquaculture research environments capable of continuous-duty operation in humid, corrosive coastal conditions.
The specifications require all equipment to feature titanium heat exchangers suitable for saltwater use, corrosion-resistant construction, digital temperature controllers, and integrated safety flow switches. Units requiring refrigerant must include pricing for low-global warming potential refrigerant systems such as R454B or approved equivalents. Delivery is FOB destination to the University of Southern Mississippi with full assembly required where practical and advance coordination mandated prior to shipment. The university identifies Aqua Logic Inc., a manufacturer of titanium heat pumps and water chillers, as an acceptable manufacturer, though comparable quality products meeting the established specifications will be considered. The document reserves the university's right to determine product equivalency, allowing flexibility in bidder submissions while maintaining established performance and quality standards.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 26-30 ADDENDUM 1.pdf | ||
| 26-30 HEATER CHILLER OHRC BID COVERSHEET.pdf | ||
| download.pdf | ||
| BID 26_30 LEGAL AD_SH.pdf | ||
| download (1).pdf | ||
| BID 26-30 BID PACKET.pdf | ||
| RFP URL.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Bid # 26‐30
RFX 3160007920
University of Southern Mississippi
Heater Chiller System for Oyster Hatchery and Research Center
Technical Specifications – Aquaculture Water Temperature Control Equipment
1. General Requirements
The University of Southern Mississippi is soliciting sealed bids for the purchase and delivery of drop-in water chillers, air-cooled reversible heat pumps, and commercial-duty heat/chill pump units suitable for use in a research aquaculture facility.
All equipment shall be new, unused, and of current production.
Equipment specified herein establishes the minimum acceptable performance and quality standards. Equivalent products meeting or exceeding these specifications shall be accepted.
The University reserves the right to determine equivalency.
2. Intended Application
Equipment will be used in a marine and freshwater aquaculture research environment and operate reliably in humid and corrosive coastal conditions must:
• Be suitable for freshwater and saltwater systems
• Maintain stable process water temperatures
• Be appropriate for continuous-duty commercial/research operation
• Be rated for outdoor or sheltered exterior installation where specified
3A. Low-Profile Drop-In Water Chillers (Quantity: 3)
Minimum Requirements:
• Compact, low-profile drop-in configuration
• Air-cooled design
• Nominal cooling capacity ≈ 6,000 BTUH
• Motor rating approximately 0.5 HP
• Electrical service: 115V, single phase
• Maximum operating current approx. 9.5 amps
• Power consumption approx. 1,100 watts
• Integrated digital temperature controller
• Single-stage control operation Hydraulic Performance:
o Water flow range: 12–25 GPM Air-cooled design Approximate Dimensions:
▪ Length: 17–18 in.
▪ Width: 15–16 in.
▪ Height: 13–14 in.
3B. Air-Cooled Reversible Heat Pump / Chiller Units (Quantity: 4)
Minimum Requirements:
• Air-cooled reversible heat pump capable of heating and chilling
• Cooling/heating capacity ≈ 6,000 BTUH
• Motor rating approximately 0.5 HP
• Electrical service: 115V, single phase
• Maximum operating current approx. 9.5 amps
• Digital temperature control
• Continuous-duty operation capability Hydraulic Performance:
o Water flow range: 12–25 GPM Approximate Dimensions:
▪ Length: ~24 in.
▪ Width: ~15–16 in.
▪ Height: ~15–16 in.
3C. Commercial Aquaculture Heat/Chill Pump Units – General Requirements
Applies to all units below:
• Heat or chill capability in a single unit
• Titanium heat exchanger suitable for saltwater use
• Corrosion-resistant construction
• Digital temperature controller
• Outdoor-rated control enclosure (NEMA 4X or equivalent)
• Integrated safety flow switch
• Stainless steel or corrosion-resistant stand
• Suitable for freshwater and saltwater aquaculture systems
• Outdoor installation capable
3C1. Medium Capacity Units (Quantity: 6)
• Nominal capacity: 5 tons (~60,000 BTUH)
• Electrical: 208–240V, single phase
• Operating amperage approx. 25 amps
• Water flow: 30–60 GPM
• Air output approx. 3,700 CFM
• Dimensions approx.: 51" L x 38" W x 75" H
3C2. Large Capacity Units (Quantity: 2)
• Nominal capacity: 7.5 tons (~90,000 BTUH)
• Electrical: 208–240V, three phase
• Operating amperage approx. 29 amps
• Water flow: 60–120 GPM
• Air output approx. 5,200 CFM
• Dimensions approx.: 51" L x 42" W x 65" H
3C3. Extra Large Capacity Units (Quantity: 2)
• Nominal capacity: 10 tons (~120,000 BTUH)
• Electrical: 208–240V, three phase
• Operating amperage approx. 40 amps
• Water flow: 60–120 GPM
• Air output approx. 5,200 CFM
• Dimensions approx.: 61" L x 46" W x 74" H
3D. Refrigerant Requirements
Units requiring refrigerant upgrades shall include pricing for systems utilizing low-GWP refrigerant (R454B or approved equivalent) compatible with listed equipment capacities.
4. Delivery Requirements
FOB Destination: University of Southern Mississippi.
Equipment shall be fully assembled where practical.
Delivery coordination required prior to shipment.
5. Acceptable Manufacturers
Aqua Logic Inc., manufacturer of titanium heat pumps and water chillers, or comparable quality product suitable for use in an aquaculture facility.