This document is a Clarifying Questions response and supporting architectural plans for Bid 2024-31, an interior remodel project for Lake Road Health Center managed by Clackamas County Behavioral Health in Milwaukie, Oregon. The project involves metal framing, insulation, and drywall work for a non-load-bearing interior renovation of an existing three-story office building totaling 41,739 square feet. The scope includes interior remodeling with non-load-bearing walls only, ADA accessibility upgrades, and required maintenance work, while mechanical, electrical, plumbing, fire alarm, and fire sprinkler systems are being handled under separate permits. The responding architect, Pinnacle Architecture Inc., provided 34 pages of building permit phase drawings in response to bidder inquiries requesting more comprehensive project documentation. The project contact is Jason Varga at Clackamas County Behavioral Health (503-351-4012), with Kalina Kunert serving as the architect contact at Pinnacle Architecture (541-388-9897), and structural engineering provided by Froelich Engineers.
The building is classified as Construction Type II-B with Business occupancy on a 2.37-acre lot zoned OC (Office Commercial) containing 140 existing parking spaces (5 accessible, 135 standard). The project includes three floors of interior renovation with specific attention to non-structural wall systems, suspended ceiling installations, and ADA barrier removal improvements including accessible restroom upgrades with three additional ADA-compliant restrooms, door hardware modifications to lever-type handles, accessible parking stall upgrades, and site path maintenance to meet current code slopes. The drawings establish code compliance under current Oregon Structural Specialty Code (OSSC), occupancy load calculations of 637 occupants across the business spaces, and fire-rated partition requirements. The building configuration indicates maximum travel distances ranging from 68 to 212 feet with sprinkler system protection, and detailed accessibility standards compliance per A117.1 ICC/ANSI standards including grab bar reinforcement specifications, accessible sink and restroom configurations, and signage requirements.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 00010179-RFP-Attachment_C.doc | DOC document | |
| 00010179_Q&A_Vol1~4.pdf | ||
| BID 2024-31 Lake Road Health Center Drywall.pdf | ||
| 00010179_Addendum_1.pdf | ||
| 00010179-RFP-Attachment_B.doc | DOC document | |
| 00010179-RFP-Attachment_H.pdf | ||
| 00010179-Full_RFP-Heavy_Truck_Tax_Comparison_Study.pdf | ||
| 00010179-RFP-Attachment_A.pdf | ||
| 00010179-RFP-Attachment_G.docx | DOCX document | |
| 00010179_CDM_Smith_Intent_to_Award.pdf | ||
| 00010179-RFP-Attachment_E.docx | DOCX document | |
| 00010179_Addendum_2.pdf |
Show all 12
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
INVITATION TO BID #2024-31
Metal Framing, Insulation and Drywall for Lake Road Health Center (“BID”)
RESPONSE TO CLARIFYING QUESTIONS #1
May 2, 2024
Note that these are questions submitted by interested firms to the above referenced solicitation.
The below answers are for clarification purposes only and in no way alter or amend the BID as published.
1. Are there any more plans for this building we could have access to, for a more complete view of the project?
Answer: Yes, Please see attached Building Set Plans (34 pages)
Attachments: Lake Road Health Center- Building Permit Phase- Drawing Set (34 Pages)
End of Clarifying Questions #1
PROJECT CONTACT INFORMATION
OWNER:
CLACKAMAS COUNTY BEHAVIORAL HEALTH
150 BEAVERCREEK ROAD
OREGON CITY, OR 97045
PHONE: 503-351-4012
CONTACT: JASON VARGA
ARCHITECT:
PINNACLE ARCHITECTURE, INC
1001 SW DISK DRIVE, SUITE 105
BEND, OREGON 97702
PHONE: (541) 388-9897
CONTACT: KALINA KUNERT
STRUCTURAL:
PROJECT INFORMATION
DESCRIPTION / SCOPE OF WORK:
INTERIOR REMODEL OF EXISTING 3-STORY OFFICE BUILDING. NON-LOAD BEARING WALLS ONLY. ALL MEP
WORK TO BE DONE UNDER SEPERATE PERMIT AS LISTED BELOW. NO EXTERIOR WORK OTHER THAN REQUIRED
ADA UPGRADES AND MAINTENANCE.
OCCUPANCY TYPE:
BUSINESS
CONSTRUCTION TYPE:
II-B
LEGAL DESCRIPTION:
TAX LOT 22E05B 00401
ZONING:
OC
LOT SIZE:
2.37 ACRES
PARKING:
ACCESSIBLE:
EXISTING PROVIDED: 5
STANDARD:
EXISTING PROVIDED: 135
TOTAL:
EXISTING PROVIDED: 140
SETBACKS:
FRONT: 15'-0" MIN - 20'-0" MAX.
SIDE: 10'-0"
SIDE: 10'-0"
REAR: 10'-0"
SEPERATE PERMITS:
FIRE ALARM
FIRE SPRINKLER
MECHANICAL
ELECTRICAL
PLUMBING
LOW VOLTAGE
FROELICH ENGINEERS
17700SW UPPER BOONES FERRY RD. SUITE 115
PORTLAND, OR 97224
PHONE: 503-624-7005
CONTACT: YASHAR SARRAFOUR
GENOA HEALTHCARE
CHICAGO IL
PHONE: (785) 221-5023
CONTACT: CODY HALTHAUS
EMAIL: CHOLTHAUS@GENOAHEALTHCARE.COM
PHARMACY DESIGN:
SITE
NORTH
SE LAKE RD
HWY 224 / MILWAUKIE EXPY
SE
W
EB
ST
ER
R
D
SE
R
U
SK
R D
SHEET LIST
Sheet Number Sheet Name
01 - GENERAL
G0.10 COVER
G0.11 NOTES & CONVENTIONS
G1.10 CODE PLAN
G5.10 GENERAL ACCESSIBILITY DETAILS
G6.10 EXISTING PHOTOS - REFERENCE ONLY
03 - SITE
AS1.10 ARCHITECTURAL SITE PLAN
05 - STRUCTURAL
S0.00 COVER SHEET
S0.01 GSN AND SPECIAL INSPECTION TABLES
S1.10 2ND FLOOR FRAMING PLAN
S1.11 3RD FLOOR FRAMING PLAN
S1.12 ROOF FRAMING PLAN
S6.00 NON-STRUCTURAL WALL DETAILS
S6.01 NON-STRUCTURAL WALL DETAILS
S6.10 SUSPENDED CEILING DETAILS
S6.11 SUSPENDED CEILING DETAILS
06 - ARCHITECTURAL DEMO
AD1.11 1ST FLOOR PLAN - DEMO
AD1.12 2ND FLOOR PLAN - DEMO
AD1.13 3RD FLOOR PLAN - DEMO
07 - ARCHITECTURAL
A1.10 1ST FLOOR PLAN
A1.11 2ND FLOOR PLAN
A1.12 3RD FLOOR PLAN
A1.20 1ST FLOOR EXISTING REFLECTED CEILING PLAN
A1.21 2ND FLOOR EXISTING REFLECTED CEILING PLAN
A1.22 3RD FLOOR EXISTING REFLECTED CEILING PLAN
A1.40 1ST FLOOR FINISH FLOOR PLAN
A1.41 2ND FLOOR FINISH FLOOR PLAN
A1.42 3RD FLOOR FINISH FLOOR PLAN
A1.43 INTERIOR FINISH SCHEDULES
A2.20 ENLARGED PLANS & INTERIOR ELEVATIONS
A2.21 ENLARGED PLANS & INTERIOR ELEVATIONS
A5.20 INTERIOR DETAILS - REFLECTED CEILING & DOOR DETAILS
A5.23 INTERIOR DETAILS - CASEWORK
A6.10 ASSEMBLIES
A6.20 DOORS & WINDOWS
DRAWING INDEX
1001 SW DISK DRIVE, SUITE 105
BEND OR 97702
541.388.9897
WWW.PINNACLEARCHITECTURE.COM
"ENHANCING LIVES AND COMMUNITIES"
CLIENT:
PROJECT ADDRESS:
PROJECT NO:
DRAWN BY:
CHECKED BY:
DATEAPPROVED FOR
© PINNACLE ARCHITECTURE, INC. 2024 ORIGINAL SHEET SIZE: 30"x42"
REV
DATEDESCRIPTION
BY
CLIENT:
VICINITY MAP
PHASE:
Autodesk Docs://2221.HCR Clackamas County Behavioral Health/2221.HCR Clackamas County Behavioral Health.rvt
2/5/2024 4:48:16 PM
LAKE ROAD HEALTH CENTER
CLACKAMAS COUNTY
6605 SE Lake Rd, Milwaukie, OR
97222
2221.HCR
BJL
COVER
G0.10
LAKE ROAD HEALTH CENTER
6605 SE Lake Rd, Milwaukie, OR 97222
CLACKAMAS COUNTY
BUILDING PERMIT
BUILDING PERMIT 02.02.24
PETER BAER
KK
BUILDING INFORMATION
Name Area
BUSINESS 41,739 SF
GRAND TOTAL 41,739 SF
1. THIS DESIGN IS AN ORIGINAL UNPUBLISHED WORK AND MAY NOT BE DUPLICATED, PUBLISHED AND/OR USED WITHOUT THE
WRITTEN CONSENT OF THE ARCHITECT.
2. THESE SHEETS - LISTED BY DRAWING INDEX , ALL ACCOMPANYING SPECIFICATIONS FOR MATERIALS, WORKMANSHIP QUALITY, AND
NOTES HAVE BEEN PREPARED SOLELY FOR THE CONSTRUCTION AND FINISH OF PROJECT IMPROVEMENTS.
3. ALL WORK IS TO BE PERFORMED IN ACCORDANCE WITH PERTINENT JURISDICTIONAL CODES, RESTRICTIONS, COVENANTS, AND/OR
ORDINANCES. ANY CONFLICT BETWEEN DESIGN AND REQUIREMENT SHALL BE REPORTED TO THE ARCHITECT BEFORE PROCEEDING.
ALL WORK SHALL BE INSPECTED BY GOVERNING AGENCIES IN ACCORDANCE WITH THEIR REQUIREMENTS. JURISDICTIONAL APPROVAL
SHALL BE SECURED BEFORE PROCEEDING WITH WORK.
4. ANY AND ALL PROPOSED CHANGES, MODIFICATIONS AND/OR SUBSTITUTIONS SHALL BE REPORTED TO THE ARCHITECT BEFORE
PROCEEDING. ANY DEVIATION FROM THE CONTRACT DOCUMENTS, WITHOUT THE EXPRESS WRITTEN AUTHORIZATION OF THE
ARCHITECT, BECOMES THE RESPONSIBILITY OF THE CONTRACTOR.
5. IN THE EVENT OF CONFLICT BETWEEN THE DESIGN DOCUMENTS AND/OR JURISDICTIONAL REQUIREMENTS, THE MORE RESTRICTIVE
FROM THE STANDPOINT OF SAFETY AND PHYSICAL SECURITY SHALL APPLY.
6. ANY INSTALLATION OR WORK NECESSARY TO THE FUNCTIONING, SAFETY AND/OR PHYSICAL SECURITY OF DESIGN THAT IS TO BE
ENCAPSULATED OR OTHERWISE PERMANENTLY OBSCURED FROM INSPECTION SHALL BE REPORTED TO THE ARCHITECT A MINIMUM
OF TWO (2) WORKING DAYS BEFORE ENCLOSURE.
7. ANY INSTALLATION, FINISH, OR COMPONENT INTENDED TO PROVIDE ENCLOSURE, WEATHER ABILITY OR APPEARANCE QUALITY
SHALL BE PRODUCED AS A REPRESENTATIVE SAMPLE PRIOR TO PROCEEDING WITH COMPLETION. WORK PERFORMED WITHOUT
WRITTEN APPROVAL OF SUCH SAMPLE BY THE ARCHITECT SHALL BE DONE AT THE RISK OF THE CONTRACTOR. A MINIMUM OF TWO
(2) WORKING DAYS NOTICE SHALL BE GIVEN.
8. BUILDING DESIGN IS GENERALLY PREDICATED UPON PROVISIONS OF THE CURRENT EDITION OF THE IBC AND/OR AMENDMENTS AS
MAY HAVE BEEN LOCALLY ADOPTED. ALL REQUIREMENTS OF THE JURISDICTIONAL FIRE SAFETY/PREVENTION DISTRICT SHALL BE
ACCOMMODATED BY THIS DESIGN AND ANY CONSEQUENT CONSTRUCTION.
9. ANY DAMAGE, DISRUPTION OR COMPROMISE OF AMBIENT RIGHTS-OF-WAY, UTILITIES, OR ENVIRONMENTAL QUALITY SHALL BE
IMMEDIATELY RECTIFIED BY THE CONTRACTOR TO THE SATISFACTION OF THE ARCHITECT AT NO ADDITIONAL COST TO THE OWNER.
10. ALL PENETRATIONS OF RATED ASSEMBLIES SHALL BE PROTECTED BY MATERIALS AND CONSTRUCTION THAT CONFORMS TO
UNDERWRITERS LABORATORIES LISTINGS FOR "THROUGH-PENETRATION FIRE STOP SYSTEMS". THE CONTRACTOR SHALL SUBMIT SHOP
DRAWING DETAILS, PROVIDED BY THE SUPPLIER OF THE FIRE STOP MATERIAL, THAT INDICATE COMPLETE CONFORMANCE WITH THE
UL LISTING. DRAWINGS SHALL REMAIN AVAILABLE AT THE WORK SITE TO ARCHITECT, OWNER, AND INSPECTORS. DRAWINGS SHALL BE
SPECIFIC FOR EACH PENETRATION, WITH APPROPRIATE UL # AND ALL VARIATIONS CLEARLY DEFINED.
11. THIS DESIGN PURPORTS TO PERMIT FULL ACCOMMODATION ACCESS, AND/OR ADAPTABILITY FOR HANDICAPPED PERSONS AS
PROVIDED FOR BY PROVISIONS OF FEDERAL LAW AND LOCAL STIPULATION. ANY DEVIATION OR COMPROMISE SHALL BE REPORTED TO
THE ARCHITECT BEFORE PROCEEDING WITH WORK.
12. DIMENSIONS (ON ARCHITECTURAL DRAWINGS) ARE TAKEN TO:
A. COORDINATE GRID LINES
B. FACE OF CONCRETE OR CONCRETE MASONRY UNITS (CMU) - F.O.C.
C. FACE OF VERTICAL STUD OR COLUMN - F.O.S. UNLESS NOTATED WITH INDICATING THAT DIMENSION IS TO CENTERLINE.
D. TOP SURFACE OF FLOOR (WITHOUT FINISH), WALL, TRIM, CAP, RAILING, ETC. ABOVE NEAREST REFERENCE LEVEL - A.F.F.
E. CENTER OF HORIZONTAL OPENING OF DOOR & WINDOW LOCATIONS, UNLESS NOTED OTHERWISE.
13. DO NOT SCALE DRAWINGS.
GENERAL NOTES HATCH PATTERNS DRAWING SYMBOLS
ABBREVIATIONS
X
AX.XX
X
AX.XX
X
AX.XX
X
AX.XX
X
AX.XX
AX.XX
X1
X2
X3
X4
X
AX.XX
DETAIL NUMBER
SHEET UPON WHICH
DETAIL IS DRAWN
INTERIOR
ELEVATION
EXTERIOR
ELEVATION
DETAIL CUT
WALL SECTION
DETAIL NUMBER COORDINATES (HORIZONTAL REFERENCE)
NORTH/SOUTH GRID
EAST/WEST
GRID
XX
WINDOW TYPE
WINDOW TYPE
PLAN/SECTION ASSEMBLY TAGS
W1
F1
R1
COORDINATES (HORIZONTAL REFERENCE)
ELEVATION NAME -
INDICATED ON FLOOR PLANS
ELEVATION HEIGHT
NOTE: SEE ARCHITECTURAL SITE PLAN FOR
DATUM REFERENCE
MAIN FLOOR ACTUAL (REAL) ELEVATION = 100'-0" = DATUM
DOOR SYMBOL REFERENCE NOTES
125A
EX001
DOOR # - INDICATED ON
FLOOR PLANS
NOTES
KEYNOTES: NOTE NUMBER
OCCUPANCY LOAD (1004): FIRE, LIFE, SAFETY TAG
ROOM TAG
ROOM NAME
150 SF
FIRST LTR/# INDICATES LEVEL
ON WHICH ROOM OCCURS
ROOM SQUARE
FOOTAGE
DIMENSION LUMBER
CONTINUOUS BLOCKING
SLOPE SYMBOL REVISION NORTH ARROW
RUN
RISE X
LEVEL
ELEVATION
FLOOR TYPE
ROOF TYPE
BUILDING SECTION
DETAIL TAG
& AND
∠ ANGLE
@ AT
CENTERLINE
O DIAMETER
± PLUS OR MINUS
° DEGREE
# POUND OR NUMBER
(E) EXISTING
AB ANCHOR BOLT
A/C AIR CONDITIONING
ACST ACOUSTICAL
ACT ACOUSTICAL CEILING TILE
ACW ALUMINUM CURTAIN WALL
AD AREA DRAIN
ADJ ADJUSTABLE OR ADJACENT
AFF ABOVE FINISHED FLOOR
AGGR AGGREGATE
AHJ AUTHORITY HAVING JURISDICTION
AHU AIR HANDLING UNIT
ALUM ALUMINUM
APPROX APPROXIMATE
ARCH ARCHITECTURAL
ASF ALUMINUM STOREFRONT
ASPH ASPHALT
AWP ACOUSTICAL WALL PANEL
BCS BABY CHANGING STATION
BD BOARD
BLDG BUILDING
BLKG BLOCKING
BM BEAM
BOT BOTTOM
CAB CABINET
CB CATCH BASIN OR CHALKBOARD
CBB CEMENT BACKER BOARD
CEM CEMENT
CER CERAMIC
CFCI CONTRACTOR FURNISHED/
CONTRACTOR INSTALLED
CG CORNER GUARD
CI CAST IRON
CIP CAST-IN-PLACE
CJ CONSTRUCTION OR CONTROL JOINT
CLG CEILING
CLO CLOSET
CLR CLEAR
CMU CONCRETE MASONRY UNIT
CNTR COUNTER
CO CLEANOUT
COL COLUMN
CONC CONCRETE
CONN CONNECTION
CONSTR CONSTRUCTION
CONT CONTINUOUS
CORR CORRIDOR
CPT CARPET
CSK COUNTERSUNK
CT CERAMIC TILE
CTR CENTER
DBL DOUBLE
DEPT DEPARTMENT
DET DETAIL
DIA DIAMETER
DIM DIMENSION
DISP DISPENSER
DIV DIVISION OR DIVIDE
DN DOWN
DR DOOR
DS DOWNSPOUT
DWG DRAWING
DWR DRAWER
EA EACH
EF EACH FACE
EJ EXPANSION JOINT
EL ELEVATION
ELEC ELECTRICAL
ELEV ELEVATOR
EP ELECTRICAL PANEL
EPX EPOXY PAINT
EPX-F EPOXY FLOORING
EQ EQUAL
EQUIP EQUIPMENT
EST ESTIMATE
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WATER HEATER
EXH EXHAUST
(E) EXISTING
EXP EXPOSED OR EXPANSION
EXT EXTERIOR
FA FIRE ALARM
FB FLAT BAR
FC FIBER CEMENT
FD FLOOR DRAIN
FDTN FOUNDATION
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER CABINET
FGS FRAMELESS GLASS SYSTEM
FHC FIRE HOSE CABINET
FIN FINISH
FIN FLR FINISH FLOOR
FLR FLOOR
FLUOR FLUORESCENT
FMT FORMED METAL TRIM
FOC FACE OF CONCRETE OR CURB
FOF FACE OF FINISH
FOS FACE OF STUD
FP FIREPROOF
FT FOOT OR FEET
FTG FOOTING
FUS FOLDING UTILITY SHELF
G GROUND
GA GAUGE
GALV GALVANIZED
GB GRAB BAR
GL GLASS
GL BLK GLASS BLOCK
GLZ CMU GLAZED CMU
GR GRADE
GWB GYPSUM WALL BOARD
GWB-IR GYPSUM WALL BOARD -
IMPACT RESISTANT
GWB-WR GYPSUM WALL BOARD -
WATER RESISTANT
HB HOSE BIBB
HC HOLLOW CORE
HD HAND DRYER
HDWD HARDWOOD
HGT HEIGHT
HM HOLLOW METAL
HORIZ HORIZONTAL
HR HOUR
HVAC HEATING, VENTILATION,
AIR CONDITIONING
ID INSIDE DIAMETER
INSUL INSULATION
INT INTERIOR
JS JOINT SEALANT
JT JOINT
LAB LABORATORY
LINO LINOLEUM
LAM LAMINATE
LAV LAVATORY
LKR LOCKER
LS INTERIOR LIGHTSHELF
LT LIGHT
LVT LUXURY VINYL TILE / PLANK
MATL MATERIAL
MAX MAXIMUM
MB MARKER BOARD
MECH MECHANICAL
MEMB MEMBRANE
MFR MANUFACTURER
MH MANHOLE
MIN MINIMUM
MISC MISCELLANEOUS
MO MASONRY OPENING
MP METAL PANEL
MS METAL SIDING
MTD MOUNTED
MTL METAL
MU MIRROR UNIT
MULL MULLION
(N) NEW
NIC NOT IN CONTRACT
NO NUMBER
NOM NOMINAL
NTS NOT TO SCALE
OA OVERALL
OC ON CENTER
OD OUTSIDE DIAMETER
OFCI OWNER FURNISHED
CONTRACTOR INSTALLED
OFF OFFICE
OFOI OWNER FURNISHED
OWNER INSTALLED
OPNG OPENING
OPP OPPOSITE
OTC SAPP OREGON TRANSPORATION COMMISSION
STANDARDS FOR ACCESSIBLE PARKING
PLACES
P-? PAINT COLOR
PBD PARTICLE BOARD
PC PRECAST
PERF PERFORATED
PL PROPERTY LINE
PLAM PLASTIC LAMINATE
PLAS PLASTER
PLYWD PLYWOOD
PNL PANEL
PR PAIR
PS PROJECTION SCREEN
PT PRESSURE TREATED
PTAC PACKAGED TERMINAL
AIR CONDITIONER
PTD PAPER TOWEL DISPENSER
PTHP PACKAGED TERMINAL
HEAT PUMP
PTN PARTITION
Q QUARTZ
QT QUARRY TILE
R RADIUS OR RISER
RA RETURN AIR
RB RESILIENT BASE
RB HK ROBE HOOK
RCP REFLECTED CEILING PLAN
RD ROOF DRAIN
REF REFRIGERATOR
REINF REINFORCED
REQD REQUIRED
RESIL RESILIENT
RM ROOM
RO ROUGH OPENING
RT RUBBER / RESILIENT TILE
RVS REVERSED
RWL RAIN WATER LEADER
SAM SELF ADHERED MEMBRANE
SC SOLID CORE
SCHED SCHEDULE
SD STORM DRAIN OR SOAP DISPENSER
SECT SECTION
SHR SHOWER
SHT SHEET
SIM SIMILAR
SKLT SKYLIGHT
SLD SOLID SURFACE
SND SANITARY NAPKIN DISPOSAL
SNDU SANITARY NAPKIN DISPOSAL UNIT
SPEC SPECIFICATION
SQ SQUARE
SS SUNSCREEN
SST STAINLESS STEEL
ST STAIN
STA STATION
STD STANDARD
STL STEEL
STOR STORAGE
STRUCT STRUCTURAL
SUSP SUSPEND
SV SHEET VINYL
SYMM SYMMETRICAL
T TREAD
T&G TONGUE & GROOVE
TB TACKBOARD
TBD TO BE DETERMINED
TCD TOILET COVER DISPENSER
TEL TELEPHONE
THK THICKNESS
THRU THROUGH
TO TOP OF
TOC TOP OF CURB/CONCRETE
TOL TOLERANCE
TOS TOP OF STEEL
TOW TOP OF WALL
TPD TOILET PAPER DISPENSER
TPTN TOILET PARTITION
TR TRASH RECEPTACLE
TYP TYPICAL
UNFIN UNFINISHED
UNO UNLESS NOTED OTHERWISE
UR URINAL
US UTILITY SHELF
VCT VINYL COMPOSITION TILE
VERT VERTICAL
VEST VESTIBULE
VIF VERIFY IN FIELD
VINYL VINYL
W/ WITH
WD WOOD
WRB WEATHER RESISTIVE BARRIER
ACT-1 12'-0"CEILING TYPE
CEILING TYPE
AFF
DOOR EXIT QUANTITY
NUMBER OF OCCUPANTS
6-01 X
FIRE RESISTIVE
ASSEMBLY RATING
0 NO FIRE RATING
0.5 30 MIN ASSEMBLY
1 1 HR ASSEMBLY
2 2 HR ASSEMBLY
3 3 HR ASSEMBLY
4 4 HR ASSEMBLY
WALL TYPE
VALUES RANGE
FROM 00-99
STUD THICKNESS
X NOMINAL MATERIAL THICKNESS
CORE MATERIAL BY SPEC DIVISION
3 DIV 03 CONCRETE
4 DIV 04 MASONRY
6 DIV 06 WOOD
9 DIV 09 NON-STRUCTURAL METAL FRAMING
WALL ASSEMBLY TAG LEGEND
NORTH
ROOM SQUARE FOOTAGE
ROOM OCCUPANCY
LOAD FACTOR
FUNCTION OF SPACE
Square Footage Function of Space
Occ. Load Factor # Occupants
108 BUSINESS
ACTUAL # OF OCCUPANTS
ACT-1
CEILING TYPE DIRECT APPLIED
TO STRUCTURE
INDICATES CENTER OF WALL
OR COLUMN
INDICATES FACE OF WALL OR
COLUMN
SHEET DESIGNATION
EARTH
ROCK FILL
CONCRETE
CMU
MANUFACTURED STONE
MASONRY
STEEL
ALUMINUM
WOOD, FINISH
MDF
PLYWOOD
ACOUSTIC TILE
GYPSUM BOARD
INSULATION, BATT
INSULATION, RIGID
FIBER CEMENT
SECTION
GLULAM
LETTER DESIGNATION SUB
GROUP WHEN NEEDED.
SECOND AND THIRD DIGITS
IDENTIFY ROOM
HEAD CONDITION
A HEAD CONIDITION SEE: /3 A6.10
A
REVISED AREA
BRICK
CONCRETE BLOCK
SHAKE SHINGLES
VERTICAL SIDING
MANUFACTURED STONE
STUCCO
LAP SIDING
BOARD AND BATTEN
ASPHALT ROOFING
ELEVATION
METAL ROOFING
1001 SW DISK DRIVE, SUITE 105
BEND OR 97702
541.388.9897
WWW.PINNACLEARCHITECTURE.COM
"ENHANCING LIVES AND COMMUNITIES"
CLIENT:
PROJECT ADDRESS:
PROJECT NO:
DRAWN BY:
CHECKED BY:
DATEAPPROVED FOR
© PINNACLE ARCHITECTURE, INC. 2024 ORIGINAL SHEET SIZE: 30"x42"
REV
DATEDESCRIPTION
BY
Autodesk Docs://2221.HCR Clackamas County Behavioral Health/2221.HCR Clackamas County Behavioral Health.rvt
2/5/2024 4:48:17 PM
LAKE ROAD HEALTH CENTER
CLACKAMAS COUNTY
6605 SE Lake Rd, Milwaukie, OR
97222
2221.HCR
PETER BAER
MALLORY FAIR
NOTES & CONVENTIONS
G0.11
BUILDING PERMIT 02.02.24 KK
UP
F E
C
FEC FEC
F E
C
F E
C
F E
C
FEC FEC
F E
C
F E
C
FEC
F E
C
FEC
FEC
F E
C
FEC
F E
C
FEC
F E
C
FEC
FEC
F E
C
FEC
F E
C
LEGEND - CODE PLAN
PATH OF EGRESS
44" MINIMUM CLEAR WIDTH
ILLUMINATED EGRESS PATH
DIRECTIONAL EXIT SIGN
EXIT SIGN AT DOOR
FIRE EXTINGUISHER CABINET
FIRE EXTINGUISHER CABINET
SEMI RECESSED
356OCCUPANT LOAD
AT DOOR OPENING
FEC
FEC
75' RADIUS
1-HR FIRE RATED PARTITION
2-HR FIRE RATED PARTITION
# Occupants
Square Footage Function of Space
Occ. Load Factor
B
# Occupants
Square Footage Function of Space
Occ. Load Factor
B
# Occupants
Square Footage Function of Space
Occ. Load Factor
B
# Occupants
Square Footage Function of Space
Occ. Load Factor
B
# Occupants
Square Footage Function of Space
Occ. Load Factor
B
# Occupants
Square Footage Function of Space
Occ. Load Factor
B
# Occupants
Square Footage Function of Space
Occ. Load Factor
S
# Occupants
Square Footage Function of Space
Occ. Load Factor
S
# Occupants
Square Footage Function of Space
Occ. Load Factor
S
# Occupants
Square Footage Function of Space
Occ. Load Factor
B
# Occupants
Square Footage Function of Space
Occ. Load Factor
B
# Occupants
Square Footage Function of Space
Occ. Load Factor
B
# Occupants
Square Footage Function of Space
Occ. Load Factor
B
# Occupants
Square Footage Function of Space
Occ. Load Factor
B
# Occupants
Square Footage Function of Space
Occ. Load Factor
B
# Occupants
Square Footage Function of Space
Occ. Load Factor
BUSINESS
# Occupants
Square Footage Function of Space
Occ. Load Factor
BUSINESS
# Occupants
Square Footage Function of Space
Occ. Load Factor
S
# Occupants
Square Footage Function of Space
Occ. Load Factor
S
# Occupants
Square Footage Function of Space
Occ. Load Factor
S
# Occupants
Square Footage Function of Space
Occ. Load Factor
A
212'-6" TRAVEL DISTANCE
73'-0" COMMON PATH TRAVEL DISTANCE
37' - 9 1/2"
98'-0" TRAVEL DISTANCE
141'-0" TRAVEL DISTANCE
OCCUPANCY GROUP
BUSINESS
13994 SF
BUSINESS
BUILDING OCCUPANCY DATA (NON-SEPARATED USE: PER 508.3)
OCCUPANCY CLASSIFICATION (PER 302): B
CONSTRUCTION TYPE (PER 602): TYPE II B
BUILDING LIMITATIONS
BASE ALLOWABLE FLOOR AREA (TABLE 506.2) GROUP B/ TYPE II= 69,000 SF
ALLOWABLE AREA INCREASE NOT USED
ACTUAL BUILDING AREA 41,793 SF GROSS TOTAL
ACTUAL BUILDING BREAKDOWN:
ALLOWABLE BUILDING HEIGHT (TABLE 504.3 / 504.4) 4 STORIES ( 75' HEIGHT)
ACTUAL BUILDING HEIGHT 3 STORIES ( 40' - 11" HEIGHT)
FIRE RESISTIVE BUILDING ELEMENTS (RATING)
STRUCTURAL FRAME NOT RATED (NR)
EXTERIOR BEARING WALLS NR
INTERIOR BEARING WALLS NR
EXTERIOR NON-BEARING WALLS NR
INTERIOR NON-BEARING WALLS NR
FLOOR CONSTRUCTION NR
ROOF CONSTRUCTION NR
CORRIDORS (Table 1020.1) NR
FIRE PROTECTION SYSTEMS
FIRE SUPPRESSION AND DETECTING SYSTEMS
AUTOMATIC FIRE SPRINKLER SYSTEM (NFPA 13)
FIRE & SMOKE DETECTION (NFPA 72)
FIRE EXTINGUISHER
REFERENCE: PLANS FOR (E) EXTINGUISHER LOCATIONS
MEANS OF EGRESS - EGRESS WIDTH REQUIREMENT
MAIN LEVEL EGRESS REQUIREMENT
DOOR: 0.2" PER OCCUPANT PER 1005.3.2
3'-0" DOOR (32" MIN CLR WIDTH) 6'-0" DOOR (64" MIN CLR WIDTH)
DOOR WIDTH REQUIRED: 542 X 0.2 = 10.9"
REFERENCE: PLAN DIAGRAMS FOR EXIT REQUIREMENTS
MAXIMUM COMMON PATH OF TRAVEL (TABLE 1006.2.1)
OCC. W/ SPRINKLER SYS.
B 100'
MAXIMUM TRAVEL DISTANCE (TABLE 1017.2)
OCC. W/ SPRINKLER SYS.
B 300'
PLUMBING SYSTEMS
FIXTURE REQUIREMENTS (TABLE 2902.1)
MALE / FEMALE PLUMBING COUNTS
OCCUPANT LOAD / 2 = M AND F COUNTS
REQUIRED -
WATERCLOSET (W/C) = 1 PER 25 OCC FOR THE FIRST 50 AND 1 PER 50 FOR THE REMAINING OCCUPANTS
LAVATORY (L) = 1 PER 40 OCC FOR THE FIRST 80 AND 1 PER 80 FOR THE REMAINING OCCUPANTS
CLASS/OCCUPANTS W/C M F LAV. M F TUB/SHOWER
GROUP B/ 318 OCCUPANTS 8 8 5 5 0
PROVIDED
CLASS/OCCUPANTS W/C M F U LAV. M F U TUB/SHOWER
GROUP B/ 318 OCCUPANTS 6 9 3 6 6 3 0
A117.1 ICC/ANSI A117.1-CURRENT EDITION
ACCESSIBLE AND USABLE BUILDINGS AND FACILITIES
AMERICAN NATIONAL STANDARD, 2017 EDITION,
INTERNATIONAL CODE COUNCIL, INC.
NFPA NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
STANDARDS REFERENCED IN OUR STATE'S STATUTES AND REGULATION
GENERAL REFERENCES
REFERENCE CODES
CURRENT OSSC OREGON STRUCTURAL SPECIALTY CODE
(WITH OREGON AMENDMENTS) 2022
CURRENT OEESC OREGON ENERGY SPECIALTY CODE
(WITH OREGON AMENDMENTS)
CURRENT OPSC OREGON PLUMBING SPECIALTY CODE
(WITH OREGON AMENDMENTS)
CURRENT OESC OREGON ELECTRICAL SPECIALTY CODE
(WITH OREGON AMENDMENTS)
CURRENT NFPA 101 LSC
GENERAL
CLACKAMAS COUNTY, OR BUILDING DEPT.FIRE RESISTANCE CHART - BUILDING ELEMENTS
PRIMARY STRUCTURE (INCLUDING COLS., GIRDERS AND JOISTS)
EXTERIOR BEARING WALLS
INTERIOR BEARING WALLS
NON-BEARING EXTERIOR WALLS AND PARTITIONS
NON-BEARING INTERIOR WALLS AND PARTITIONS
FLOOR CONSTRUCTION (INCLUDING BEAMS & JOISTS)
ROOF CONSTRUCTION (INCLUDING BEAMS & JOISTS)
CONSTRUCTION ELEMENT - TYPE II RATING (HOURS)
(see TABLE 705.5)
X < 5'
5' ≤ X < 10'
10' ≤ X < 30'
X ≥ 30'
OSSC, TABLE 601 FIRE-RESISTANCE RATING REQUIREMENTS FOR BUILDING ELEMENTS (HOURS)
OSSC, TABLE 705.5 FIRE-RESISTANCE RATING REQUIREMENTS FOR EXTERIOR WALLS BASED ON FIRE
SEPARATION DISTANCE (FSD)
FSD (FEET) - TYPE B RATING (HOURS) - B OCCUPANCY
INTERIOR WALL AND CEILING FINISH REQUIREMENTS BY OCCUPANCY IN SPRINKLERED BUILDINGS
(TABLE 803.13)
GROUP INTERIOR STAIRWAYS CORRIDORS ROOMS
B B C C
SITE ELEMENTS:
- ACCESSIBLE SITE PATH MAINTENANCE,
DEMO AND REPLACE TO MEET CODE REQUIRED SLOPES
- ACCESSIBLE PARKING STALL,
DEMO AND REPLACE TO MEET CODE REQUIRED SLOPES
- ACCESSIBLE PARKING STALL,
REPAINTING AND WALKWAY REPAINTING
BUILDING INTERIOR:
- ACCESSIBLE RESTROOM UPGRADES,
ADDITIONAL (3) ADA RESTROOMS TO CURRENT REQUIRED CODE STANDARADS
- DOOR HARDWARE UPGRADES,
TO BE LEVER TYPES HANDLES FOR ADA COMPIANCE
ACCESSIBLE BARRIER REMOVAL PLAN
# Occupants
Square Footage Function of Space
Occ. Load Factor
B
# Occupants
Square Footage Function of Space
Occ. Load Factor
A
# Occupants
Square Footage Function of Space
Occ. Load Factor
S
# Occupants
Square Footage Function of Space
Occ. Load Factor
STORAGE
# Occupants
Square Footage Function of Space
Occ. Load Factor
B
# Occupants
Square Footage Function of Space
Occ. Load Factor
B
# Occupants
Square Footage Function of Space
Occ. Load Factor
B
# Occupants
Square Footage Function of Space
Occ. Load Factor
B
# Occupants
Square Footage Function of Space
Occ. Load Factor
B
# Occupants
Square Footage Function of Space
Occ. Load Factor
B
# Occupants
Square Footage Function of Space
Occ. Load Factor
B
# Occupants
Square Footage Function of Space
Occ. Load Factor
B
# Occupants
Square Footage Function of Space
Occ. Load Factor
B
# Occupants
Square Footage Function of Space
Occ. Load Factor
B
# Occupants
Square Footage Function of Space
Occ. Load Factor
# Occupants
Square Footage Function of Space
Occ. Load Factor
STORAGE
# Occupants
Square Footage Function of Space
Occ. Load Factor
B
# Occupants
Square Footage Function of Space
Occ. Load Factor
B
# Occupants
Square Footage Function of Space
Occ. Load Factor
B
138'-0" TRAVEL DISTANCE
162'-0" TRAVEL DISTANCE
103'-0" TRAVEL DISTANCE
# Occupants
Square Footage Function of Space
Occ. Load Factor
B
# Occupants
Square Footage Function of Space
Occ. Load Factor
B
# Occupants
Square Footage Function of Space
Occ. Load Factor
B
# Occupants
Square Footage Function of Space
Occ. Load Factor
B
# Occupants
Square Footage Function of Space
Occ. Load Factor
S
# Occupants
Square Footage Function of Space
Occ. Load Factor
B
# Occupants
Square Footage Function of Space
Occ. Load Factor
S
# Occupants
Square Footage Function of Space
Occ. Load Factor
S
# Occupants
Square Footage Function of Space
Occ. Load Factor
B
# Occupants
Square Footage Function of Space
Occ. Load Factor
S
# Occupants
Square Footage Function of Space
Occ. Load Factor
B
# Occupants
Square Footage Function of Space
Occ. Load Factor
B
# Occupants
Square Footage Function of Space
Occ. Load Factor
B
# Occupants
Square Footage Function of Space
Occ. Load Factor
B
# Occupants
Square Footage Function of Space
Occ. Load Factor
B
# Occupants
Square Footage Function of Space
Occ. Load Factor
B
# Occupants
Square Footage Function of Space
Occ. Load Factor
B
# Occupants
Square Footage Function of Space
Occ. Load Factor
S
# Occupants
Square Footage Function of Space
Occ. Load Factor
B
# Occupants
Square Footage Function of Space
Occ. Load Factor
B
# Occupants
Square Footage Function of Space
Occ. Load Factor
B
68'-0" TRAVEL DISTANCE
78'-0" TRAVEL DISTANCE
165'-0" TRAVEL DISTANCE
14238 SF
BUSINESS
13507 SF
BUSINESS
1001 SW DISK DRIVE, SUITE 105
BEND OR 97702
541.388.9897
WWW.PINNACLEARCHITECTURE.COM
"ENHANCING LIVES AND COMMUNITIES"
CLIENT:
PROJECT ADDRESS:
PROJECT NO:
DRAWN BY:
CHECKED BY:
DATEAPPROVED FOR
© PINNACLE ARCHITECTURE, INC. 2024 ORIGINAL SHEET SIZE: 30"x42"
REV
DATEDESCRIPTION
BY
Autodesk Docs://2221.HCR Clackamas County Behavioral Health/2221.HCR Clackamas County Behavioral Health.rvt
2/5/2024 4:48:27 PM
LAKE ROAD HEALTH CENTER
CLACKAMAS COUNTY
6605 SE Lake Rd, Milwaukie, OR
97222
2221.HCR
PETER BAER
BL
CODE PLAN
G1.10
BUILDING PERMIT 02.02.24 KK
1/16" = 1'-0"2
LEVEL_01 - OCCUPANT LOAD
1/32" = 1'-0"1
LEVEL_01 - OCCUPANCY GROUP
BUILDING INFORMATION
Name Area
BUSINESS 41,739 SF
GRAND TOTAL 41,739 SF
OSSC TABLE 1004.5
OCCUPANT LOAD
1/16" = 1'-0"5
LEVEL_02
1/16" = 1'-0"6
LEVEL_03
1/32" = 1'-0"3
LEVEL_02
1/32" = 1'-0"4
LEVEL_03
M
IN
MIN.
* 1' - 0"
* IF DOOR HAS BOTH A
CLOSER AND LATCH
* IF DOOR HAS BOTH A
CLOSER AND LATCH
MIN.
1' - 10"
M
IN
M
IN
*IF CLOSER IS PROVIDED
M
IN
MIN.
2' - 0"
(J)
LATCH SIDE APPROACH
SLIDING AND FOLDING DOORS
(D)
FRONT APPROACH SWINGING
DOORS
(E)
HINGE SIDE APPROACH SWINGING
DOORS
NOTE: 2 OPTIONS
(F)
LATCH SIDE APPROACH
SWINGING DOORS
(G)
FRONT APPROACH SLIDING/FOLDING
DOORS
M
IN
MIN.
2' - 0"
M
IN
M
IN
*IF CLOSER IS PROVIDED
O P
T B
M
IN
O P
T A
M
IN
OPT B: 3' - 6" MIN.
OPT A: 3' - 0" MIN.
MIN.
1' - 6"M
IN
MIN.
1' - 10"
M
IN
(H)
SLIDE SIDE APPROACH
SLIDING/FOLDING DOORS
M
IN
M
IN
MIN.
2' - 0"
(A)
FRONT APPROACH
(B)
HINGE SIDE APPROACH
(C)
LATCH SIDE APPROACH
10"3' - 10"
M A
X
M
IN
4" 1' - 2" 2' - 3"
REINFORCING FOR GRAB BARS AT WATER CLOSET
PROVIDE WOOD 2X GRAB BAR REINFORCEMENT AT WATER CLOSETS IN ACCESSIBLE UNITS PER
DRAWING ABOVE. PATCH AND PAINT WALLS AT NEW BLOCKING.
SHOWER STALLS TO HAVE BUILT-IN GRAB BARS IN ACCESSIBLE UNITS
BATHTUBS TO HAVE BUILT-IN GRAB BARS IN ACCESSIBLE UNITS
M
IN
M A
X
RAMP MEN'S RESTROOM WOMEN'S RESTROOM
1. ACCESSIBLE SIGNS IDENTIFY ROOMS AND SPACES, INCLUDING UNIT NUMBERS, LAUNDRY, PUBLIC
BATHROOM AND OFFICES.
A. LETTERS AND NUMERALS: RAISED 1/32 IN. MINIMUM, UPPERCASE, SANS SERIF, 5/8 TO 2
IN. IN HEIGHT, AND ACCOMPANIED BY GRADE 2 BRAILLE.
B. PICTOGRAM BORDERS AT LEAST 6 IN. HIGH.
C. SURFACES HAVE A NONGLARE FINISH; LEVEL OF SHEEN MUST BE "EGGSHELL" OR LESS.
D. PROVIDE CONTRAST BETWEEN THE CHARACTERS AND BACKGROUND.
E. MOUNTING: 60 IN. MAX ABOVE FINISHED FLOOR TO BASELINE OF LOWEST RAISED
CHARACTER, PREFERABLY ON THE LATCH SIDE OF DOOR OR THE CLOSEST WALL SPACE.
DO NOT MOUNT WITHIN THE SWINGING PATH OF A DOOR OR WHERE A PERSON
CANNOT APPROACH WITHIN 3 IN. OF THE SIGN.
F. CONTRACTOR TO COORDINATE BRAILLE LETTERING TO INDICATE CORRECT SIGNAGE
DESCRIPTION
2. IDENTIFY SUCH ACCESSIBLE FEATURES AS ASSISTIVE LISTENING DEVICES, PARKING, AND TEXT
TELEPHONES. WHEN NOT ALL SUCH FEATURES ARE ACCESSIBLE, IDENTIFY THE ACCESSIBLE ONES
(E.G., TOILET ROOMS AND PARKING) USE PICTOGRAMS AT LEAST 6 IN. HIGH ACCOMPANIED BY A
VERBAL DESCRIPTION.
INSULATED PIPE COVERS
@ ADA SINKS
2' - 6"
11" MAX
MIRROR
SOAP DISPENSER
MIRROR
CLEAR FLOOR SPACE:
30" WIDE x 52" DEEP
WALL MOUNT
SINK SIDE ELEVATION
SINK FRONT ELEVATION
M
A X
(A
D A
M
IN
M
IN
R E
F
LE
C T
IN
G
S U
R F
A C
E
M A
X
M
IN
MAX.
6"
MIN.
11"
MIN.
8"
25" MAX.
NOTE:
1. PROVIDE BACKING PLATES AND SUPPORT FOR ALL WALL MOUNTED ACCESSORIES.
2. FOLLOW MOUNTING HEIGHTS INDICATED IN THIS DETAIL UNLESS NOTED OTHERWISE IN PROJECT DETAILS. NOTIFY ARCHITECT OF DISCREPANCIES.
3. PROVIDE WOOD 2X REINFORCEMENT AT ALL GRAB BAR LOCATIONS & WALL MOUNTED ACCESSORIES.
HAND SHOWER,
BAR MOUNTED
CONTROL AREA
60" HOSE
GRAB BAR, TYP.
CONTROL WALL BACK WALL PLAN URINAL, FRONT ELEVATION TOILET, SIDE ELEVATION TOILET, FRONT ELEVATION DRINKING FOUNTAINS
LAVATORIES
RESTROOM CLEARANCES
CONTROL WALL
ADA STANDARD
WALL (WHERE OCCURS)
HANDLE TO FACE
ACCESSIBLE SIDE
GRAB BAR
TCD SND TPH
SE
A
T
FOLDING SEAT
1' - 3"
4" MAX.
15" MAX
/4
M
A X
T H
R E
S H
O
LD
M
IN
M
A X
T
O S
H O
W E
R C
U R
T A
IN
R
O D
1' - 6"
M
IN
52" MIN.
15"-16"
M A
X
.2-1/2" MAX.
-1
-1
/2
M A
X
22"-23"
36" CLEAR
C
LE
A R
M
A X
M
A X
A D
A
S T
A N
D A
R D
1' - 3"
2'-6" MIN. CLR. FLR.
(1
M
IN
M A
X
M
IN
3' - 6"
12" MAX.
-1
/2
C
LR
7" MIN. - 9" MAX.
24" - 42"
39" - 41"
3' - 0" MIN.
2' - 0" MIN.1' - 0" MIN.
M
IN
M
A X.
A D
A
ST
A
N D
A R
D
16" - 18"
M
IN
M
A X
T O
S P
O U
T
T
O S
P O
U T
SOAP DISPENSER
LEVER HANDLE
MIRROR OR
REFLECTIVE
SURFACE
INSULATED PIPE
COVER @
EXPOSED PIPES
25" MAX.
11" MAX.
M
IN
M
IN
M A
X
8" MIN
6" MAX
11 MIN.
R E
F
LE
C T
IN
G
S U
R F
A C
E
M
A X
T
O
M
IN
W
A
LL
H U
N G
M
IN
F
LO
O R
M O
U N
T E
D
60" MIN.
MAX.
4"
2' - 6"
REACH RANGES APPLY TO OPERABLE PARTS OF CONTROLS
UNOBSTRUCTED HIGH FORWARD REACH = 48" MAX.
UNOBSTRUCTED LOW FORWARD REACH = 15" MIN.
HIGH FORWARD REACH OVER OBSTRUCTION <20" = 48"
HIGH FORWARD REACH OVER OBSTRUCTION 20"-25" = 44"
UNOBSTRUCTED HIGH SIDE REACH = 48" MAX.
UNOBSTRUCTED LOW SIDE REACH = 15" MIN.
HIGH SIDE REACH OVER OBSTRUCTION 34" MAX. HIGH BY 10" MAX DEPTH = 48" MAX
HIGH SIDE REACH OVER OBSTRUCTION 34" MAX. HIGH BY 10-24" MAX DEPTH = 46" MAX
SIDE REACH:FORWARD REACH:
CONTROLS INCLUDING BUT NOT LIMITED TO:
FIRE PULLS
SWITCHES
OUTLETS
THERMOSTATS
DOOR BELLS
SECURITY CONTROLS
THERMOSTATS
DOOR BELLS
SECURITY CONTROLS
KEYPADS
A/V DOOR BELL STROBE,
A/V SMOKE DETECTOR STROBE
CONTROLS
ELECTRICAL PANEL OR
FIRE EXTINGUISHER
DUPLEX OUTLETDATA
OUTLET
SOAP
DISPENSER
PAPER TOWEL
DISPENSER
48"
44"
18"
84"
VENDING
CLOSETS
OVER AN OBSTRUCTION - FORWARD REACH:
HIGH FORWARD REACH OVER OBSTRUCTION <20" = 48"
HIGH FORWARD REACH OVER OBSTRUCTION 20"-25" = 44"
*WHEN COUNTERTOP DEPTH EXCEEDS 24" PROVIDE MOUNTING BLOCK FOR CONTROLS
SEE "MOUNTING BLOCK DETAIL" G5.10
SIDE REACH:
OVER AN OBSTRUCTION - SIDE REACH
HIGH SIDE REACH OVER OBSTRUCTION 34" MAX. HIGH BY 10" MAX. DEPTH = 48"
HIGH SIDE REACH OVER OBSTRUCTION 34" MAX. HIGH BY 10-24" MAX. DEPTH= 46"
*WHEN COUNTERTOP DEPTH EXCEEDS 24" PROVIDE MOUNTING BLOCK FOR CONTROLS
SEE "MOUNTING BLOCK DETAIL" G5.10
O U
TL
ET
S
SW
IT
C H
ES
O U
TL
ET
S
SW
IT
C H
ES
CLOSET SHELF
CLOSET ROD
1' - 0"
S T
A N
D A
R D
N
O N
-A C
C E
S S
IB
LE
/4
(A C
C E
S
SI
B
LE
M
IN
M
A X
M
A X
20" MAX. 20" - 25"
M
A X
M
A X
M
A X
10" MAX.
M
A X
M
A X
10" MIN. - 24" MAX.
O U
TL
ET
S
SW
IT
C H
ES
O U
TL
ET
S
SW
IT
C H
ES
> 24"
MOUNTING BLOCK DETAIL
BLOCKING FOR CONTROLS ARE REQUIRED FOR ALL COUNTERTOPS EXCEEDING 24", TWO
OPTIONS AVALIABLE DEPENDING ON COUNTERTOP HEIGHTS
OPTION 1: IF COUNTERTOP HEIGHT AND BACKSPLASH ARE BELOW MOUNTING HEIGHT
REQUIREMENTS OF OUTLETS OR SWITCHES THEN MOUNT ELECTRICAL OUTLETS OR
SWITCHES ON PAINTED BLOCK THAT REDUCES THE REACH RANGE TO UNDER 24". THE
BLOCK AND OUTLET MUST HAVE AT LEAST A 1/2" GAP AFTER INSTALL BETWEEN BLOCK AND
BACKSPLASH. 1/4" MOUNTING SURFACE MUST BE VISIBLE AROUND SWITH OR OUTLET AND
CENTER ON MOUNTING BLOCK.
OPTION 2: IF COUNTERTOP HEIGHT AND BACKSPLASH ARE WITHIN MOUNTING HEIGHT
REQUIREMENT OF OUTLETS OR SWITCHES THEN MOUNT ELECTRICAL OUTLETS OR SWITCHES
HORIZONTAL IN A 6" BACKSPLASH.
FRONT
BACKSPLASH
> 24"
E Q
E Q
FRONT
BACKSPLASH
/2
MOUNTING
BLOCKTYP
1/4"
OUTLET OR
SWITCH
OPTION 1 OPTION 2
(A C
C E
S
SI
B
LE
M
A X
1001 SW DISK DRIVE, SUITE 105
BEND OR 97702
541.388.9897
WWW.PINNACLEARCHITECTURE.COM
"ENHANCING LIVES AND COMMUNITIES"
CLIENT:
PROJECT ADDRESS:
PROJECT NO:
DRAWN BY:
CHECKED BY:
DATEAPPROVED FOR
© PINNACLE ARCHITECTURE, INC. 2024 ORIGINAL SHEET SIZE: 30"x42"
REV
DATEDESCRIPTION
BY
Autodesk Docs://2221.HCR Clackamas County Behavioral Health/2221.HCR Clackamas County Behavioral Health.rvt
2/5/2024 4:48:29 PM
LAKE ROAD HEALTH CENTER
CLACKAMAS COUNTY
6605 SE Lake Rd, Milwaukie, OR
97222
2221.HCR
PETER BAER
MALLORY FAIR
GENERAL ACCESSIBILITY DETAILS
G5.10
BUILDING PERMIT 02.02.24 KK
1/4" = 1'-0"2
DOOR MANUEVERING CLEARANCES
1/2" = 1'-0"3
GRAB BAR REINFORCING
NTS1
SIGNAGE
1/2" = 1'-0"4
SINK
1/2" = 1'-0"5
MOUNTING HEIGHTS
1/2" = 1'-0"6
REACH RANGES
EXISTING BRICK AT BUILDING ENTRANCE
EXISTING BRICK FEATURE TO
BE REMOVED FOR ADA
ACCESS, SEE SHEET AS1.10
EXISTING ELECTRICAL ON LEVEL 01 (IT 122)
(E) ELECTRICAL PANELS TO
REMAIN IN PLACE; MAINTAIN
MIN CLEARANCES IN FRONT
OF PANELS; SEE SHEETS
AD1.11 & A1.10
(E) DOOR AND
FRAME TO BE
REMOVED AND
INFILLED
EXISTING PARTIAL WALL IN LOBBY ON LEVEL 02 (LOBBY 201)
EXISTING PARTIAL WALL WITH
DECORATIVE LIGHTING TO BE
REMOVED IN ITS ENTIRETY; REFER TO
SHEETS AD1.12 & A2.21
SELECT DEMOLITION OF (E) WALL TO
OPEN TO OPEN OFFICES OTHER SIDE
OF WALL; REFER TO SHEET AD1.12
EXISTING CASEWORK TO BE
REMOVED IN ITS ENTIRETY
(E) FIRE ALARM CABINET TO
REMAIN IN PLACE
EXISTING LOBBY ON LEVEL 02 (LOBBY 201)
EXISTING DOORS, FRAME, AND
SIDELITE TO BE REMOVED IN THEIR
ENTIRETY
EXISTING DOOR AND FRAME TO
BE REMOVED IN ITS ENTIRETY
EXISTING WALL PANELING ON LEVEL 03 (Q&D TRAINING ROOM)
EXISTING WOOD WAINSCOT TO REMAIN
IN PLACE, NO WORK TO BE DONE;
PROTECT DURING CONSTRUCTION
EXISTING CARPET TO BE REMOVED
EXISTING CLERESTORY GLAZING ON LEVEL 03 (GROUP ROOM 324)
SELECT DEMOLITION OF (E) GLAZING
FOR (N) WALL CONNECTION; REFER
TO SHEETS AD1.13 & A1.12
(E) GLAZING TO REMAIN IN PLACE
GENERAL LOCATION OF
WOOD WAINSCOT IN
BUILDING ON LEVEL 03
1001 SW DISK DRIVE, SUITE 105
BEND OR 97702
541.388.9897
WWW.PINNACLEARCHITECTURE.COM
"ENHANCING LIVES AND COMMUNITIES"
CLIENT:
PROJECT ADDRESS:
PROJECT NO:
DRAWN BY:
CHECKED BY:
DATEAPPROVED FOR
© PINNACLE ARCHITECTURE, INC. 2024 ORIGINAL SHEET SIZE: 30"x42"
REV
DATEDESCRIPTION
BY
Autodesk Docs://2221.HCR Clackamas County Behavioral Health/2221.HCR Clackamas County Behavioral Health.rvt
2/5/2024 4:48:30 PM
LAKE ROAD HEALTH CENTER
CLACKAMAS COUNTY
6605 SE Lake Rd, Milwaukie, OR
97222
2221.HCR
PETER BAER
MALLORY FAIR
EXISTING PHOTOS - REFERENCE
ONLY
G6.10
BUILDING PERMIT 02.02.24 KK
REMOVE AND REPLACE EXISTING ASPHALT
WITH COMPLIANT ADA SLOPES
REMOVE AND REPLACE
EXISTING CONCRETE
PAVEMENT WITH
COMPLIANT ADA SLOPES
REMOVE AND REPLACE EXISTING CONCRETE
PAVEMENT WITH COMPLIANT ADA SLOPES,
SEE /4 AS1.10
(E) MONUMENT SIGN TO BE
UPDATED BY OTHERS
ACCESSIBLE SITE PATH
ACCESSIBLE PATH TO
BUILDING
AS1.10
AS1.10
AS1.10
PAINT STRIPING FOR
ACCESSIBLE WALKWAY
BUILDING AREA MIN. SPACES REQUIRED MAX. SPACES ALLOWED SPACES PROVIDED
VEHICLE PARKING INFORMATION
2.7 x 41.7 = 113 SPACES 3.4 x 41.7 = 141 SPACES 140 EXISTING SPACES
PER CLACKAMAS COUNTY ZONING DEPARTMENTS "OFFICE USES" PER TABLE 1015-1
41,739 SF / 1000 = 41.739
140 EXISTING SPACES PROVIDED REQUIRES 5 ADA SPACES PER TABLE 1106.2 = 5 ADA SPACES PROVIDED (2) VAN AND 3 STANDARD
GENERAL SITE PLAN NOTES
1. SITE LIGHTING TO REMAIN AS EXISTING.
NOTES:
1. SIGN TO BE PER LOCAL
JURISDICTION REQUIREMENTS.
VERIFY SIZE, SHAPE & WORDING.
2. PROVIDE SIGN AT EACH H.C. STALL
2" SQ. GALV. TUBE
w/ CAP, PAINT
12" DIA. CONCRETE PIER
OTC SAPP R7-8 MTL. SIGN, BOLT
TO STL. PIPE POST.
RESERVED
PARKING
STAINLESS STL.
FASTENERS TYP
VAN
ACCESSIBLE
LANDSCAPING
OTC SAPP R7-8P WHERE NOTED
DIA.
10"
A B
O V
E G
R A
D E
WHEELCHAIR
USER ONLY
OTC SAPP OR7-8C WHERE NOTED
SIGN
R7-8
SIGN
R7-8P
SIGN
OR7-8C
MAX 1:50
SLOPE IN ALL DIRECTIONS TYP.
FOR ADA PARKING STALL AND
ACCESS AISLE.
CENTERLINE
OF STALL
(E) CURB WHERE
OCCURS
MIN.
2' - 0" SIGN PLACEMENT
MIN.
2' - 0"
VAN ACCESS 8'-0" MIN 9' - 0" MIN
PROVIDE SIGN OTC SAPP
OR7-9 @ ACCESS AISLE
PROVIDE SIGN OTC SAPP OR7-8
VAN ACCESSIBLE SEE 3/AS5.10
PER OTC SAPP FIGURE 6"NO PARKING" PER OTC SAPP FIGURE 7
SEE OTHER SIDE FOR
REQUIREMENTS
PER OTC SAPP FIGURE 6
NOTE: MAX 1:50 SLOPE IN
ALL DIRECTIONS TYP. U.N.O.
PROVIDE SIGN OTC SAPP
R7-8, SEE 3/AS5.10
LA
N
D S C
A P
IN
G
M A
X
IN
S T
A
LL
I N
(E) CONC. SIDEWALK
MAX 1:50
SLOPE IN ALL DIRECTIONS TYP.
FOR ADA PARKING STALL AND
ACCESS AISLE.
CENTERLINE
OF STALL
(E) CURB
C
LR
M
IN
MIN.
2' - 0" SIGN PLACEMENT
MIN.
2' - 0"
1:50
MAX
SLOPE
VAN - 8' - 0" MIN 9' - 0" MIN
PROVIDE SIGN OTC SAPP
OR7-9 S ACCESS AISLE,
MOUNTED TO POST OR
BUILDING PER OWNER
PROVIDE SIGN OTC SAPP OR7-8
VAN ACCESSIBLE SEE 3/AS5.10
PER OTC SAPP FIGURE 6"NO PARKING" PER OTC SAPP FIGURE 7
SEE OTHER SIDE FOR
REQUIREMENTS
STANDARD 6' - 0" MIN.
1:12 MAX
SEE OTHER SIDE FOR
REQUIREMENTS
(E) CURB
PROVIDE SIGN OTC SAPP
OR7-9 S ACCESS AISLE,
MOUNTED TO POST OR
BUILDING PER OWNER
(E) BUILDING
"NO PARKING" PER OTC SAPP FIGURE 7 PER OTC SAPP FIGURE 6PER OTC SAPP FIGURE 6
LINE OF BUILDING
OVERHANG ABOVE
5' - 0"5' - 0"
BUILDING ENTRY
NOTE: MAX 1:50 SLOPE IN
ALL DIRECTIONS TYP. U.N.O.
1:12 MAX 1:50
MAX
SLOPE
1:12 MAX 1:12 MAX
PROVIDE SIGN OTC SAPP
R7-8, SEE 3/AS5.10
1:12 MAX
1:50
MAX
SLOPE
REMOVE EXISTING BRICK
FEATURE FOR ADA ACCESS
4' - 6" 4' - 6" 4' - 6" 4' - 6"
PRE MANUFACTURED CONCRETE BOLLARD;
BASIS OF DESIGN: LANDSCAPE FORMS,
ANNAPOLIS 12 INCH BOLLARD (NO LIGHT,
COUNTY STANDARD), SEE MANUFACTURER
FOR INSTALLATION REQUIREMENTS.
1:12 MAX
PAINT STRIPING FOR
ACCESSIBLE WALKWAY
EXISTING SIDEWALK
TO REMAIN
EXISTING SIDEWALK
BUILDING ENTRY
REPLACE EXISTING SIDEWALK
ENTRY, REGRADE TO MEET
ACCESSIBLE SLOPES
1:20
MAX
SLOPE
SCOPE OF CONCRETE REPLACEMENT
S C
O P
E O
F C
O N
C R
E T
E R
E P
LA
C
E M
E N
T
1001 SW DISK DRIVE, SUITE 105
BEND OR 97702
541.388.9897
WWW.PINNACLEARCHITECTURE.COM
"ENHANCING LIVES AND COMMUNITIES"
CLIENT:
PROJECT ADDRESS:
PROJECT NO:
DRAWN BY:
CHECKED BY:
DATEAPPROVED FOR
© PINNACLE ARCHITECTURE, INC. 2024 ORIGINAL SHEET SIZE: 30"x42"
REV
DATEDESCRIPTION
BY
Autodesk Docs://2221.HCR Clackamas County Behavioral Health/2221.HCR Clackamas County Behavioral Health.rvt
2/5/2024 4:48:36 PM
LAKE ROAD HEALTH CENTER
CLACKAMAS COUNTY
6605 SE Lake Rd, Milwaukie, OR
97222
2221.HCR
PETER BAER
BJL
ARCHITECTURAL SITE PLAN
AS1.10
BUILDING PERMIT 02.02.24 KK
1" = 20'-0"1
SITE PLAN
NTS3
TYP. PARKING SIGN
1/4" = 1'-0"4
TYPICAL H/C PARKING PLAN
NORTH
1/4" = 1'-0"5
TYPICAL H/C PARKING PLAN
1/4" = 1'-0"2
ENLARGED ENTRY PLAN
COMPLETE LEGEND
J# AT XX" OC
- INDICATES DIRECTION DECK OR
SHEATHING TO SPAN
- INDICATES JOIST TYPE AND
SPACING, REF PLANS & JOIST
FRAMING SCHEDULE
- INDICATES DIRECTION
TIMBER TO SPAN
- INDICATES KEYED NOTE
- INDICATES CHANGE IN SLOPE
- INDICATES STEP IN ELEVATION
- INDICATES MECHANICAL UNIT
- INDICATES NEW COLUMN BELOW
- INDICATES ELEVATION
- INDICATES EXISTING EXTERIOR
AND INTERIOR WALL
- INDICATES NEW INTERIOR WALL
- INDICATES EXISTING COLUMN BELOW
ROOF
ROOF
FRAMING
PLAN
PARAPET
HIGH ROOF
FRAMING
PLAN
LEVEL 3
FLOOR
FRAMING
PLAN
LEVEL 2
FLOOR
FRAMING
PLAN
LEVEL 1
FOUNDATION
PLAN
" INCH DBA DEFORMED BAR ANCHOR HAS HEADED ANCHOR STUD OD OUTSIDE DIAMETER THK THICK
# NUMBER, POUND DBL DOUBLE HC HOLLOW CORE OH OVERHEAD THRD THREADED
& AND DEFL DEFLECTION HCP HOLLOW CORE PLANK OPNG OPENING TOB TOP OF BEAM
' FEET DEMO DEMOLITION HDD HEADED ANCHOR STUD OPP OPPOSITE, OPPOSITE HAND TOC TOP OF COLUMN, TOP OF CURB
@ AT DEPT DEPARTMENT HDR HEADER OSWJ OPEN WEB STEEL JOIST TOF TOP OF FOOTING
(E) EXISTING DETL DETAIL HEX HEXAGONAL TOJ TOP OF JOIST
(N) NEW DF DOUG FIR (DOUGLAS FIR) HM HOLLOW METAL P/L PROPERTY LINE TOL TOP OF LINTEL, LANDING
DIA DIAMETER HORIZ HORIZONTAL PAF POWDER ACTUATED FASTENERS TOL TOLERANCE
AB ANCHOR BOLT DIAG DIAGONAL HSS HOLLOW STRUCTURAL SHAPE PC PRECAST TOP TOP OF PIER, TOP OF PLATE
ACI AMERICAN CONCRETE INSTITUTE DIAPH DIAPHRAGM HT HEIGHT PCF POUNDS PER CUBIC FOOT TOPV TOP OF PAVEMENT
ADD ADDENDUM, ADDITION DIM DIMENSION HVAC HEATING, VENTILATION, AIR CONDITIONING PERF PERFORATE, PERFORATED, PERFORMANCE TOS TOP OF SLAB, TOP OF STEEL
ADJ ADJUST, ADJUSTABLE DKG DECKING PERIM PERIMETER TOW TOP OF WALL
AESS ARCHITECTURALLY EXPOSED STRUCTURAL STEEL DL DEAD LOAD IBC INTERNATIONAL BUILDING CODE PE PROFESSIONAL ENGINEER TRANS TRANSVERSE
AFF ABOVE FINISH FLOOR DWG DRAWING ICF INSULATED CONCRETE FORMS PERP PERPENDICULAR TRANSL TRANSLUCENT
ALT ALTERNATE DWGS DRAWINGS ID INSIDE DIAMETER PL PLATE TYP TYPICAL
ALUM ALUMINUM DWL DOWEL IN INCH, INCHES PLF POUNDS PER LINEAL FOOT
APPROX APPROXIMATELY INFO INFORMATION PLWD PLYWOOD UNO UNLESS NOTED OTHERWISE
ARCH ARCHITECTURE EIFS EXTERIOR INSULATED FINISH SYSTEM INSP INSPECTION PNL PANEL UTIL UTILITY
ASTM AMERICAN SOCIETY FOR TESTING AND MATERIALS ELEV ELEVATOR INSUL INSULATION PREFAB PREFABRICATED
AVG AVERAGE ENGR ENGINEER INT INTERIOR PREFIN PREFINISHED VERT VERTICAL
AWS AMERICAN WELDING SOCIETY EOR ENGINEER OF RECORD PSF POUNDS PER SQUARE FOOT VFY VERIFY
EQ EQUAL JST JOIST PSI POUNDS PER SQUARE INCH VIF VERIFY IN FIELD
BALC BALCONY EQPT EQUIPMENT JT JOINT, JOINTS PSL PARALLEL STRAND LUMBER
BD BOARD ES EACH SIDE PT PRESERVATIVE TREATED, POST-TENSIONED W/ WITH
BEV BEVEL EW EACH WAY K KILOPOUND (1000 POUNDS) W/O WITHOUT
BKR BACKER EXIST EXISTING KIP KILOPOUND (1000 POUNDS) QTY QUANTITY WD WOOD
BLDG BUILDING EXP EXPANSION WF WIDE FLANGE (STRUCTURAL STEEL)
BLK BLOCK EXPO EXPOSED L ANGLE, LEFT, LENGTH RAD RADIUS WP WORK POINT OR WORKING POINT
BLKG BLOCKING EXT EXTERIOR LAM LAMINATE, LAMINATED RCP REFLECTED CEILING PLAN WR WATER RESISTANT, WATER RESISTIVE
BM BEAM LAT LATERAL RD ROOF DRAIN WS WATERSTOP
BOC BOTTOM OF CURB F TO F FACE TO FACE LB POUND REF REFERENCE WT WEIGHT
BOT/BTM BOTTOM FAB FABRICATIONS / FABRICATED LF LINEAL FEET, LINEAR FOOTAGE REINF REINFORCED, REINFORCING WWF WOVEN WIRE FABRIC
BOW BOTTOM OF WALL FB FLAT BAR LIN LINEAR REQ REQUIREMENTS
BP BASE PLATE FDTN FOUNDATION LIN FT LINEAL FEET, LINEAR FOOTAGE REQD REQUIRED
BRDG BRIDGE, BRIDGING FE FROELICH ENGINEERS LL LIVE LOAD REV REVISION
BRG BEARING FF FINISH FLOOR LLH LONG LEG HORIZONTAL RO ROUGH OPENING
BRK BRICK FFE FINISH FLOOR ELEVATION LLV LONG LEG VERTICAL
BSMT BASEMENT FIN FINISH LNTL LINTEL SCHED SCHEDULE
BU BUILT-UP FLR FLOOR LONG LONGITUDINAL SE STRUCTURAL ENGINEER
FOC FACE OF CONCRETE LSL LAMINATED STRAND LUMBER SECT SECTION
CEM CEMENT, CEMENTITIOUS FOF FACE OF FINISH LT WT LIGHTWEIGHT SF SQUARE FEET
CGS CENTER OF GRAVITY OF STRAND FOM FACE OF MASONRY LVL LAMINATED VENEER LUMBER SGL SINGLE
CIP CAST IN PLACE FOS FACE OF STUD SHT SHEET
CJ CONTROL JOINT FR FIRE RATED, FIRE RESISTIVE MANUF MANUFACTURER, MANUFACTURED SHTG SHEATHING
CL CENTER LINE FRM FRAMED, FRAMING MAX MAXIMUM SIM SIMILAR
CLG CEILING FRR FIRE RESISTANCE RATED MB MACHINE BOLT SIMP SIMPSON STRONG TIE
CLR CLEAR FRT FIRE RETARDANT TREATED MECH MECHANICAL SL SNOW LOAD
CMU CONCRETE MASONRY UNIT FT FOOT, FEET MEZZ MEZZANINE SOG SLAB ON GRADE
COL COLUMN FTG FOOTING MFR MANUFACTURER, MANUFACTURED SPEC SPECIFICATION, SPECIFICATIONS
COMP COMPOSITE, COMPENSATION FURRG FURRING MIN MINIMUM SQ SQUARE
CONC CONCRETE FUT FUTURE MISC MISCELLANEOUS SS STAINLESS STEEL
COND CONDITION MTL METAL STD STANDARD
CONN CONNECTION GA GAUGE MUL MULLION STIFF STIFFENER
CONSTR CONSTRUCTION GALV GALVANIZED STL STEEL
CONT CONTINUOUS GC GENERAL CONTRACTOR N NORTH STRUCT STRUCTURAL
CORR CORRIDOR GEN GENERAL NIC NOT IN CONTRACT SUSP SUSPENDED
CTR CENTER GL GLU-LAMINATED NO NUMBER SYM SYMMETRICAL
CTRL CONTROL GLB GLU-LAMINATED BEAM NOM NOMINAL
CTSK COUNTERSINK GND GROUND NTS NOT TO SCALE T AND B TOP AND BOTTOM
CU CUBIC GR GRADE T AND G TONGUE AND GROOVE
CUST CUSTOM GT GIRDER TRUSS OC ON CENTER TAN TANGENT
GYP GYPSUM
GYP BD GYPSUM BOARD
froelich-engineers.com | Portland, OR | Bend, OR | Denver, CO
1001 SW DISK DRIVE, SUITE 105
BEND OR 97702
541.388.9897
WWW.PINNACLEARCHITECTURE.COM
"ENHANCING LIVES AND COMMUNITIES"
CLIENT:
PROJECT ADDRESS:
PROJECT NO:
DRAWN BY:
CHECKED BY:
DATEAPPROVED FOR
© PINNACLE ARCHITECTURE, INC. 2023 ORIGINAL SHEET SIZE: 30"x42"
REV
DATEDESCRIPTION
BY
FE# 23-T126
C:\Users\FCE-CAD-8B\Documents\2221.HCR Clackamas County Behavioral Health_Struct_R23_aparkerLUWV6.rvt
2/5/2024 3:39:22 PM
CLACKAMAS COUNTY BEHAVIORAL
HEALTH
CLACKAMAS COUNTY
6605 SE Lake Rd, Milwaukie, OR
97222
2221.HCR
Checker
Author
COVER SHEET
S0.00
PERMIT DOCUMENTS 2.5.2024 Approver
Sheet Number Sheet Name
S0.00 COVER SHEET
S0.01 GSN AND SPECIAL INSPECTION TABLES
S1.10 2ND FLOOR FRAMING PLAN
S1.11 3RD FLOOR FRAMING PLAN
S1.12 ROOF FRAMING PLAN
S6.00 NON-STRUCTURAL WALL DETAILS
S6.01 NON-STRUCTURAL WALL DETAILS
S6.10 SUSPENDED CEILING DETAILS
S6.11 SUSPENDED CEILING DETAILS
FOUNDATION AND FRAMING PLAN CUTS - ELEVATION DIAGRAM
EXPIRES: ob/ c / 2'7
PROJECT DESCRIPTION:
● TENANT IMPROVEMENT OF AN EXISTING 3-STORY OFFICE BUILDING
● CEILING AND NON-BEARING WALL DESIGN
GENERAL:
1. THE STRUCTURAL DRAWINGS ARE A PORTION OF THE CONTRACT DOCUMENTS AND
ARE INTENDED TO BE USED IN CONJUNCTION WITH THE ARCHITECTURAL, CIVIL,
MECHANICAL, AND ELECTRICAL DRAWINGS. THE CONTRACTOR IS RESPONSIBLE FOR
COORDINATING THE REQUIREMENTS FROM THE ENTIRE SET OF CONTRACT
DOCUMENTS (INCLUDING THE PROJECT SPECIFICATIONS) INTO THEIR WORK.
2. THESE GENERAL NOTES SUPPLEMENT THE PROJECT SPECIFICATIONS. REFER TO THE
PROJECT SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
3. NOTES AND DETAILS ON THE STRUCTURAL DRAWINGS SHALL TAKE PRECEDENCE
OVER THE GENERAL STRUCTURAL NOTES AND TYPICAL DETAILS.
4. CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND ELEVATIONS PROVIDED ON
STRUCTURAL DRAWINGS WITH ALL DISCIPLINES INCLUDING, BUT NOT LIMITED TO
ARCHITECTURAL, GEOTECHNICAL ENGINEER, AND CIVIL ENGINEER PRIOR TO
CONSTRUCTION.
5. DETAILS ON THESE PLANS ARE INTENDED TO DEPICT THE GENERAL CONSTRUCTION
METHODS FOR THIS STRUCTURE. CONNECTIONS, DETAILS AND CONDITIONS NOT
SPECIFICALLY SHOWN THAT ARE SIMILAR TO THOSE THAT ARE SPECIFIED SHALL BE
ASSUMED ONE AND THE SAME. IF QUESTIONS REGARDING THE APPLICATION OF
DETAILS ARE ENCOUNTERED, NOTIFY THE ARCHITECT/ENGINEER FOR CLARIFICATION
IN A TIMELY MANNER PRIOR TO BID OPENING.
CODE REQUIREMENTS:
1. CONFORM TO THE 2022 OREGON STRUCTURAL SPECIALTY CODE (OSSC), BASED UPON
THE 2021 INTERNATIONAL BUILDING CODE (IBC).
2. ALL REFERENCE TO OTHER CODES AND STANDARDS (ACI, AISC, AWS, NDS, ASTM, ETC.)
SHALL BE FOR THE EDITIONS NOTED IN CHAPTER 35 OF THE IBC/OSCC.
TEMPORARY CONDITIONS:
1. THE STRUCTURE HAS BEEN DESIGNED TO FUNCTION AS A UNIT UPON COMPLETION.
THE CONTRACTOR IS RESPONSIBLE FOR FURNISHING ALL TEMPORARY BRACING AND /
OR SUPPORT REQUIRED AS A RESULT OF THE CONTRACTOR’S CONSTRUCTION
METHODS AND / OR SEQUENCES.
2. CONTRACTOR’S CONSTRUCTION METHODS AND / OR SEQUENCES SHALL RECOGNIZE
AND CONSIDER THE EFFECTS OF THERMAL MOVEMENTS OF STRUCTURAL ELEMENTS
DURING THE CONSTRUCTION PERIOD.
3. RETAINING WALLS THAT TIE TO UPPER SLABS SHALL NOT BE BACKFILLED UNTIL THE
UPPER SLABS REACH FULL STRENGTH UNLESS ADEQUATE BRACING IS PROVIDED AT
THE TOP OF THE WALL.
4. FOR EXISTING BUILDINGS, ADDED STRUCTURAL MEMBERS, HARDWARE,
CONNECTORS, STRAPS, FASTENERS, ETC. SHOWN ON THE STRUCTURAL DRAWINGS
MAY NECESSITATE THE UNCOVERING / EXPOSURE OF PART OF THE EXISTING
STRUCTURAL SYSTEM. THIS MAY INCLUDE, BUT SHALL NOT BE LIMITED TO PARTIAL
DEMOLITION OF ELEMENTS SUCH AS CLADDING, FINISHES, CEILING, ROOFING,
INSULATION, ELECTRICAL, PLUMBING, MECHANICAL, SPRINKLERS, ARCHITECTURAL,
STRUCTURAL, ETC. THE CONTRACTOR IS RESPONSIBLE FOR DETERMINING THE
MEANS, METHODS, AND EXTENT OF EXPOSURE / DEMOLITION REQUIRED TO EXECUTE
AND INSTALL ELEMENTS SHOWN ON THE STRUCTURAL DRAWINGS. REMOVED /
DEMOLISHED ELEMENTS AS PREVIOUSLY NOTED THAT ARE PART OF THE FINAL
PRODUCT SHALL BE RESTORED TO THEIR ORIGINAL STATE UPON COMPLETION AND
SHALL COMPLY WITH REQUIREMENTS OF THE SPECIFICATIONS, ARCHITECT, OTHER
DISCIPLINES AND CURRENT BUILDING CODES AND STANDARDS.
5. FOR EXISTING BUILDINGS, SHORING OF PORTIONS OF THE EXISTING STRUCTURE MAY
BE NECESSARY PRIOR TO REMOVAL / DEMOLITION. CARE SHALL BE TAKEN TO AVOID
DAMAGE AND DISTRESS TO THE EXISTING STRUCTURE BEYOND THE DEMOLITION
EXTENTS INDICATED. THE CONTRACTOR SHALL BE RESPONSIBLE FOR AND PROVIDE
ALL MEASURES NECESSARY TO PROTECT THE STRUCTURE (EXISTING AND NEW)
DURING CONSTRUCTION. THE CONTRACTOR IS RESPONSIBLE FOR FURNISHING ALL
TEMPORARY BRACING AND / OR SUPPORT REQUIRED AS A RESULT OF THE
CONTRACTOR’S CONSTRUCTION METHODS AND / OR SEQUENCES.
EXISTING CONDITIONS:
1. ALL EXISTING CONDITIONS, DIMENSIONS, AND ELEVATIONS SHALL BE FIELD VERIFIED -
ONLY FIELD VERIFIED DIMENSIONS SHALL BE USED IN CREATION OF THE SHOP
DRAWINGS. THE CONTRACTOR SHALL NOTIFY THE ARCHITECT AND ENGINEER OF ANY
SIGNIFICANT DISCREPANCIES FROM DIMENSIONS AND CONDITIONS SHOWN ON THE
DRAWINGS.
2. X-RAY OR GPR SHALL BE USED PRIOR TO DRILLING OR CUTTING INTO CONCRETE
CONSTRUCTION TO LOCATE AND AVOID REINFORCEMENT AND/OR TENDONS.
APPROVED HOLES (APPROVED BY FROELICH ENGINEERS) THROUGH EXISTING
CONCRETE CONSTRUCTION SHALL BE CORE-DRILLED OR SAWCUT. DO NOT CUT
THROUGH ANY REINFORCING STEEL OR POST-TENSIONED TENDONS.
3. APPROVED HOLES (APPROVED BY FROELICH ENGINEERS) THROUGH EXISTING STEEL
STRUCTURE SHALL BE CUT CAREFULLY AND CLEANLY. DO NOT TORCH OR FLAME CUT.
4. DUE TO LIMITED OBSERVATION AND ACCESS TO THE EXISTING STRUCTURE PRIOR TO
THE PREPARATION OF THE STRUCTURAL DRAWINGS, FROELICH ENGINEERS ASSUMES
THAT THE EXISTING STRUCTURE IS IN LIKE-NEW CONDITION WITH NO CORROSION,
DETERIORATION, DAMAGE, ETC. AND WAS CONSTRUCTED IN ACCORDANCE WITH THE
ORIGINAL CONSTRUCTION DOCUMENTS (IF AVAILABLE). GENERAL CONTRACTOR SHALL
VERIFY THE ABOVE ASSUMPTIONS AND NOTIFY THE ENGINEER OF RECORD OF
CONCERNS, DAMAGE, OR DISCREPANCIES.
5. FOR NEW EQUIPMENT OR CONSTRUCTION ADDED ATOP OR BENEATH EXISTING
CONSTRUCTION, THE GENERAL CONTRACTOR SHALL VERIFY THAT PROPER ROOF
SLOPE AND DRAINAGE IS STILL IN PLACE.
DESIGN CRITERIA:
1. DESIGN WAS BASED ON THE STRENGTH AND DEFLECTION CRITERIA OF THE IBC/OSSC.
IN ADDITION TO THE DEAD LOADS, THE FOLLOWING LOADS AND ALLOWANCES WERE
USED FOR DESIGN, WITH LIVE LOADS (LL) REDUCED IN ACCORDANCE WITH THE IBC:
DESIGN CRITERIA
GEOTECHNICAL CRITERIA
2500 PSF (MIN) PER GEOTECHNICAL REPORT DATED DECEMBER 3, 2021
BUILDING RISK CATEGORY
RISK CATEGORY II
LIVE LOAD CRITERIA
FLOOR DESIGN IS NOT IN FROELICH ENGINEERS SCOPE OF WORK
ROOF CRITERIA
ROOF DESIGN IS NOT IN FROELICH ENGINEERS SCOPE OF WORK
SEISMIC CRITERIA
ANALYSIS PROCEDURE EQUIVALENT LATERAL FORCE, REF ASCE 7-16 SECTION 13
SITE CLASS D
IMPORTANCE FACTOR I P = 1.00
SEISMIC DESIGN CATEGORY D
MCE SPECTRAL
ACCELERATIONS S
S = 0.94
DESIGN SPECTRAL
ACCELERATIONS S
DS
0.76
RESPONSE MODIFICATION
FACTOR R
p = 2.5
COMPONENT AMPLIFICATION
FACTOR a
P = 1.0
WEIGHT OF CEILING (MAX.) W = 4 PSF
CEILING PLAN GENERAL NOTES
1. THIS DRAWING IS FOR INTERIOR APPLICATION ONLY.
2. THE CEILING WEIGHTS SHALL NOT EXCEED 4 PSF.
3. REFER TO SHEET S4.01 FOR TYPICAL CONNECTION DETAILS
4. A HEAVY DUTY T-BAR GRID SYSTEM SHALL BE USED.
5. FOR CEILING AREAS EXCEEDING 1,000 SQ. FT. , HORIZONTAL RESTRAINT OF CEILING TO THE
STRUCTURAL SYSTEM SHALL BE PROVIDED. THE TRIBUTARY AREAS OF THE HORIZONTAL
RESTRAINTS BE APPROXIMATELY EQUAL. WHERE CEILING AREAS ARE LESS THAN OR EQUAL TO 1,000 SQ. FT. , BOUNDARY ELEMENTS SUCH AS WALLS SHALL BE ADEQUATELY BRACED BY OTHERS TO
RESIST THE LATERAL CEILING FORCES EXERTED UPON IT.
6. CEILING WITH INTERSTITAL SPACES LESS THAN 12 INCHES TO FRAMING ARE NOT REQUIRED TO HAVE
LATERAL FORCE BRACING.
7. SPRINKLER HEADS AND OTHER PENETRATIONS SHALL HAVE 2" OVERSIZED RING THROUGH THE TILE
TO ALLOW 1" OF FREE MOVEMENT IN ALL DIRECTION - REF TO TYPICAL DETAIL
8. THESE DRAWINGS ASSUME THAT THE STRUCTURE CAN SUPPORT ALL VERTICAL (STRUT, DROP, ETC.)
AND LATERAL LOADS (SPLAYS, ETC.) EXERTED UPON IT.
9. LATERAL BRACING REQUIRMENTS (SPLAY WIRES, KICKERS & COMPRESSION POSTS/STRUTS) SHOWN
ON TYPICAL DETAILS ARE NOT REQUIRED FOR GYPSUM CEILING ON ONE LEVEL THAT ARE
SURROUNDED BY BOUNDRY ELEMENTS THAT ARE LATERALY SUPPORTED AND BRACED TO
STRUCTURE ABOVE.
SUBMITTALS:
1. REVIEW OF THE SUBMITTALS IS ONLY FOR REVIEW OF GENERAL CONFORMANCE WITH THE DESIGN
CONCEPT OF THE PROJECT AND GENERAL COMPLIANCE WITH THE INFORMATION GIVEN IN THE
CONTRACT DOCUMENTS. NO RESPONSIBILITY IS ASSUMED BY THE STRUCTURAL ENGINEER FOR
CORRECTNESS, DIMENSIONS OR DETAILS CONTAINED WITHIN THE SUBMITTALS. THE CONTRACTOR IS SOLEY RESPONSIBLE FOR CONFIRMING AND CORRELATING ALL QUANTITIES AND DIMENSIONS;
SELECTING FABRICATION PROCESSES AND TECHNIQUES OF CONSTRUCTION; COORDINATING
THEIR WORK WITH THAT OF ALL OTHER TRADES; AND PERFORMING THEIR WORK IN A SAFE AND
SATISFACTORY MANNER.
2. REVIEW OF THE SUBMITTALS DOES NOT RELIEVE THE CONTRACTOR FROM COMPLIANCE WITH THE
REQUIREMENTS OF CONTRACT DOCUMENTS AND SPECIFICATIONS. THE REVIEW OF A SUBMITTAL
SHALL NOT BE CONSIDERED A WAIVER OF THE REQUIREMENT OF STRICT COMPLIANCE WITH THE
CONTRACT DOCUMENTS AND INTENT OF THE PROJECT. ALL MINIMUM CONDITIONS AND
REQUIREMENTS SPECIFIED ON THE STRUCTURAL DRAWINGS, GOVERNING BUILDING CODES, AND
REFERENCED STANDARDS SHALL BE MET REGARDLESS OF THE INFORMATION INDICATED ON THE
SUBMITTALS.
3. REVIEW OF SUBMITTALS WILL BE REVIEWED A MAXIMUM OF TWO ITERATIONS / ROUNDS BY
FROELICH ENGINEERS, INC. FURTHER REVIEW OF STRUCTURAL SUBMITTALS WILL BE BILLED AT AN
HOURLY RATE IN ADDITION TO PROJECT FEE, ACCORDING TO RATES NOTED IN THE PROJECT
CONTRACT. REVIEW OF SUBMITTALS BEYOND OUR SCOPE WILL BE BILLED AT AN HOURLY RATE IN
ADDITION TO PROJECT FEE, ACCORDING TO RATES NOTED IN THE PROJECT CONTRACT.
4. SUBMITTALS AND DRAWINGS SHALL BE GENERATED BY AND ORIGINATE FROM THE CONTRACTOR.
STRUCTURAL AUTOCAD/REVIT BACKGROUNDS WILL NOT BE RELEASED BY FE AND MAY NOT BE
USED FOR THE GENERATION OF SUBMITTALS AND DRAWINGS. IT IS THE CONTRACTOR'S
RESPONSIBILITY TO GENERATE THEIR SUBMITTALS AND DRAWINGS.
5. SUBMITTALS SHALL BE REVIEWED FOR CONFORMANCE WITH THE CONTRACT DOCUMENTS AND
STAMPED BY THE GENERAL CONTRACTOR PRIOR TO SUBMISSION TO THE DESIGN TEAM.
SUBMITTALS THAT ARE NOT REVIEWED AND STAMPED BY THE GENERAL CONTRACTOR WILL BE
RETURNED WITHOUT REVIEW.
6. REQUESTS FOR SUBSTITUTIONS OR MODIFICATION OF PLANS OR SPECIFICATIONS SHALL BE SUBMITTED IN WRITING.