BD7579A23_Duckett_Drawings.pdf

PDF 6 MB Posted

Attached to
Piezometer Automation at WSSC Water Dams
Solicitation number
1239
Issued by
Prince George's County, Maryland

About this file

This document comprises engineering drawings for the Automated Data Acquisition System (ADAS) of piezometers at T. Howard Duckett Dam in the Patuxent North basin, spanning Prince George's and Howard Counties, Maryland, prepared by AECOM Technical Services Inc. under contract for the Washington Suburban Sanitary Commission (WSSC Water). The project involves installing automated monitoring systems at four piezometer locations (D-1 through D-4) to collect real-time groundwater and seepage data from the dam. The scope of work includes extending existing piezometer riser pipes, attaching Keller terminal enclosures, installing liquid-tight and PVC Schedule 80 conduit runs from each piezometer location to a centralized PLC (Programmable Logic Controller) data logger housed in an existing utility shed on Buttress 8, and pulling sensor cables through the conduit network. The installation details specify varying riser pipe diameters (2.5 inches for D-1 and D-4; 3.0 inches for D-2 and D-3), with sensors positioned six inches above the bottom of each existing piezometer. The conduit routing follows the dam profile from individual piezometer locations to the catwalk system, with distances ranging from 11 feet to 25 feet from piezometer to buttress, and total cable lengths varying from approximately 358 feet to 459 feet depending on location.

The engineering plans detail comprehensive construction sequencing, material specifications, and system architecture requirements. All conduit must be PVC Schedule 80 with expansion fittings installed per NEMA PRP 4-2009 standards and National Electric Code Section 347-9. The Keller Acculevel sensors operate on 4-20mA output with a 0-50 PSI level sensing range, connected via two-wire current loop configuration to the central PLC enclosure. The contractor is responsible for verifying existing conditions prior to construction, conducting field surveys to establish as-built elevations and pressure sensor depths, and sensor accuracy verification under the direction of WSSC's process engineer. Cable penetrations into the PLC control enclosure must enter at the lowest possible point on the side or through the bottom, with three feet of slack cable left inside the enclosure for WSSC's connections, and all sensor cables must be permanently marked with corresponding piezometer identification numbers. Professional certification by Maryland-licensed Professional Engineer Bob Pinciotti (License No. 21984, expiration 05/24/2026) confirms compliance with state regulations and design standards.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ENGINEER:

MONTGOMERY CO.

ADEQUATE SURVEY

NO

200'S OF

CONTRACT

DATE

DATE STARTED

DATE FINALED

Drawing No.

FINALED BY

DATE COMPLETED

TYPE MANHOLES

TYPE PIPE W.

1. thru Plans/Profiles/Details

Description

P.G.CO.D.P.W.&T.

SED. CONTROL

CONTRACT MANAGER

INSPECTOR

CONTRACTOR

L & G

AS BUILT DATA

TOWN NOTIFICATION

STATE HGWY. ADM.

STATE BD. HEALTH

PERMIT REQUIREMENTS

FEDERAL AID

M.N.C.P.&P.C.

WETLANDS / WATERWAYS

TREE

DATE REVISIONS

PAGECo. GRID

VICINITY MAP

ON PROP. R/W REQ'D

OFF PROP. R/W REQ'D

S.

THESE DOCUMENTS CONTAIN PRIVILEGED

AND CONFIDENTIAL INFORMATION WHICH

SHALL NOT BE REDISTRIBUTED WITHOUT

PRIOR WSSC APPROVAL

FOR LOCATION OF UTILITIES CALL 8-1-1 OR 1-800-257-7777

OR LOG ON TO www.call811.com or www.missutility.net 48

HOURS IN ADVANCE OF ANY WORK IN THIS VICINITY

OTHER UTILITIES

*TO BE ACQUIRED BY APPLICANT

PRINCE

GEORGE'S/

HOWARD PAGE# GRID#

DRAWING INDEX

TYPE OF PIPE TYPE OF PIPE

TYPE OF MANHOLES

DRAWN

CHECK

ENGINEERING & ENVIRONMENTAL

SERVICES DIVISION

SECTION MANAGER

CIVIL SUPPORT SERVICES SECTION

DRAWN

CHECK

DATE DIVISION MANAGER

VE

R

IF

Y

SC

AL

E

- B

AR

IS

O N

E

IN

C H

O N

O R

IG

IN

AL

D

R

AW

IN

G

IF

N

O T

O N

E

IN

C H

O N

T H

IS

S

H

EE

T, A

D

JU

ST

S

C

AL

ES

A

C C

O R

D

IN

G

LY

WASHINGTON SUBURBAN SANITARY COMMISSION

WSSC

DELIVERING THE ESSENTIAL

LOCATION MAP

WASHINGTON SUBURBAN SANITARY COMMISSION

14501 SWEITZER LANE, LAUREL MARYLAND 20707

AUTOMATED DATA ACQUISITION SYSTEM OF PIEZOMETERS

AT T. HOWARD DUCKETT DAM

BASIN: PATUXENT NORTH

PRINCE GEORGE'S / HOWARD COUNTIES, MARYLAND

SCALE: 1" = 2,000'

SCALE: 1" = 8 MILES

PROJECT LOCATION

DUCKETT DAM LOCATION

SHEET NUMBER

SHEET INDEX

SHEET TITLE

COVER SHEET

INSTRUMENTATION PLAN

PIEZOMETER INSTALLATION DETAILS D-1 THROUGH D-4

ADAS SYSTEM ARCHITECTURE

CONDUIT ROUTE ON PROFILE

WIRING AND CONDUIT SCHEDULE

REQUIRED - N

NOT APPLICABLE

REQUIRED - N

REQUIRED - N

REQUIRED - N

REQUIRED - N

REQUIRED - N

REQUIRED - N

REQUIRED - N

REQUIRED - N

BD7579A23

221NE07

ELECTION DISTRICT: 1

COVER SHEET

AUTOMATED DATA ACQUISITION SYSTEMS OF PIEZOMETERS AT

T. HOWARD DUCKETT DAM

BASIN: PATUXENT NORTH, PRINCE GEORGE'S COUNTIES, MARYLAND

PROFESSIONAL CERTIFICATION

I HEREBY CERTIFY THAT THESE DOCUMENTS WERE PREPARED

OR APPROVED BY ME, AND THAT I AM A DULY LICENSED

PROFESSIONAL ENGINEER UNDER THE LAWS OF THE STATE OF

MARYLAND.

LICENSE NO.: 21984 EXPIRATION DATE: 05/24/2026

Z:

\G

ER

M

AN

TO

W N

-U

SG

R M

2\ D

C S\

PR

O

JE

C

TS

\W

TR

\6

2_

_W

SS

C _D

AM

SB

O A_

TA

SK

O R

D

ER

_8 \9

_C

AD

_G

IS

\9

_C

AD

\D

U C

KE

TT

_D W

G _D

R

AW

IN

G

S\

_D U

C

KE

TT

_C

O

VE

R _S

H

EE

T.

D

W G

PA

TH

/F

IL

EN

AM

E:

NAME: AECOM TECHNICAL SERVICES INC.

ADDRESS: 12420 MILESTONE CENTER DRIVE, SUITE 150

GERMANTOWN, MD 20876

PHONE: 301-944-2545

CONTACT: BOB PINCIOTTI, P.E.

06/03/25 - PLOT DATE

Digitally signed by Pinciotti, Bob DN: cn=Pinciotti, Bob, ou=USGRM2, email=bob.pinciotti@aecom.com Date: 2025.06.03 15:11:35 -04'00'

Pinciotti, Bob

Docusign Envelope ID: DC2B040F-2F15-4264-9777-357212A59517

Jun 11, 2025 | 9:25 AM EDT

Jun 13, 2025 | 7:06 AM EDT

DATE REVISIONS

ADEQUATE SURVEY

NO

200'S OF

CONTRACT

ON PROP. R/W REQ'D

OFF PROP. R/W REQ'D

OTHER UTILITIES

DRAWN

CHECK

THESE DOCUMENTS CONTAIN PRIVILEGED

AND CONFIDENTIAL INFORMATION WHICH

SHALL NOT BE REDISTRIBUTED WITHOUT

PRIOR WSSC APPROVAL VE

R

IF

Y

SC

AL

E

- B

AR

IS

O

N E

IN

C

H O

N O

R

IG

IN

AL

D R

AW

IF

N O

T O

N E

IN

C

H O

N T

H

IS

S H

EE

T, A D

JU

ST

S C

AL

ES

A C

C O

R D

IN

G

LY

ENGINEER:

DATE REVISIONS

ADEQUATE SURVEY

NO

200'S OF

CONTRACT

ON PROP. R/W REQ'D

OFF PROP. R/W REQ'D

OTHER UTILITIES

DRAWN

CHECK

THESE DOCUMENTS CONTAIN PRIVILEGED

AND CONFIDENTIAL INFORMATION WHICH

SHALL NOT BE REDISTRIBUTED WITHOUT

PRIOR WSSC APPROVAL VE

R

IF

Y

SC

AL

E

- B

AR

IS

O

N E

IN

C

H O

N O

R

IG

IN

AL

D R

AW

IF

N O

T O

N E

IN

C

H O

N T

H

IS

S H

EE

T, A D

JU

ST

S C

AL

ES

A C

C O

R D

IN

G

LY

ENGINEERING & ENVIRONMENTAL

SERVICES DIVISION

WASHINGTON SUBURBAN SANITARY COMMISSION

WSSC

DELIVERING THE ESSENTIAL

NOTES:

1. At each piezometer location, piezometer sensor cable runs from the riser pipe to an enclosure mounted on the riser pipe. See Piezometer Installation Details.

2. Liquid-tight conduit runs from each riser-mounted enclosure to buttress. PVC conduit runs from buttress to catwalk.

3. PVC conduit runs along catwalk to the PLC location in the utility shed.

4. All conduit shall be PVC Schedule 80.

5. PLC/Data Logger and enclosure to be provided and installed by the WSSC.

6. Buttress are 30-feet center to center.

Legend

New Piezometer Sensor

Conduit Run

INSTRUMENTATION PLAN PIEZOMETERS

AND CONDUIT RUNS

PLC/datalogger located in existing utility shed

PROFESSIONAL CERTIFICATION

I HEREBY CERTIFY THAT THESE DOCUMENTS WERE PREPARED

OR APPROVED BY ME, AND THAT I AM A DULY LICENSED

PROFESSIONAL ENGINEER UNDER THE LAWS OF THE STATE OF

MARYLAND.

LICENSE NO.: 21984 EXPIRATION DATE: 05/24/2026

Z:

\G

ER

M

AN

TO

W N

-U

SG

R M

2\ D

C S\

PR

O

JE

C

TS

\W

TR

\6

2_

_W

SS

C _D

AM

SB

O A_

TA

SK

O R

D

ER

_8 \9

_C

AD

_G

IS

\9

_C

AD

\D

U C

KE

TT

_D W

G _D

R

AW

IN

G

S\

_D U

C

KE

TT

_I

N

ST

R _P

LA

N

.D W

G

PA

TH

/F

IL

EN

AM

E:

6221NE07

AUTOMATED DATA ACQUISITION SYSTEMS OF PIEZOMETERS AT

T. HOWARD DUCKETT DAM

BASIN: PATUXENT NORTH, PRINCE GEORGE'S COUNTIES, MARYLAND

BD7579A23

D-1 D-3

D-4

D-2

CatwalkCatwalk

NOTE:

EXISTING CONDITIONS/FACILITY SHOWN ON PLAN VIEW HEREON ARE BASED

ON AVAILABLE DESIGN RECORDS AND MAY NOT REFLECT CURRENT EXISTING

CONDITIONS. CONTRACTOR IS RESPONSIBLE FOR VERIFYING ALL EXISTING

CONDITIONS PRIOR TO ANY CONSTRUCTION WORK. CONTRACTOR TO NOTIFY

THE ENGINEER AND WSSC PROJECT MANAGER IF ANY DISCREPANCIES OR

CONFLICTS EXIST.

NAME: AECOM TECHNICAL SERVICES INC.

ADDRESS: 12420 MILESTONE CENTER DRIVE, SUITE 150

GERMANTOWN, MD 20876

PHONE: 301-944-2545

CONTACT: BOB PINCIOTTI, P.E.

SUGGESTED CONSTRUCTION SEQUENCE:

1. At Piezometer D-1 through D-4 location:

a. Extend existing piezometers at least one foot above the existing top of the piezometer pipe.

b. Attach the Keller terminal enclosures onto the piezometer pipe.

c. Install PVC conduit onto the nearest abutment wall, up to and then along downstream handrails of the concrete catwalk between enclosure locations.

2. Extend conduit from piezometer D-1 enclosure to the new PLC enclosure installed by WSSC in the existing utility shed located on Buttress 8.

3. Install cable between the piezometer locations by pulling cable through the conduit.

4. Install Keller piezometer transducers by measuring cable and marking depth of sensor from top of riser. Set cap with cable grip at the mark and lower transducer into well riser.

5. Splice the sensor cable to the cable that runs back to the datalogger/PLC in the existing utility shed.

6. Contractor shall verify the accuracy of all sensors at the direction of WSSC's process engineer.

30' between buttress center-lines (typ.)

06/03/25 - PLOT DATE

Digitally signed by Pinciotti, Bob DN: cn=Pinciotti, Bob, ou=USGRM2, email=bob.pinciotti@aecom.com Date: 2025.06.03 15:11:59 -04'00'

Pinciotti, Bob

Docusign Envelope ID: DC2B040F-2F15-4264-9777-357212A59517

ADEQUATE SURVEY

NO

200'S OF

CONTRACT

ON PROP. R/W REQ'D

OFF PROP. R/W REQ'D

OTHER UTILITIES

DRAWN

CHECK

THESE DOCUMENTS CONTAIN PRIVILEGED

AND CONFIDENTIAL INFORMATION WHICH

SHALL NOT BE REDISTRIBUTED WITHOUT

PRIOR WSSC APPROVAL VE

R

IF

Y

SC

AL

E

- B

AR

IS

O

N E

IN

C

H O

N O

R

IG

IN

AL

D R

AW

IF

N O

T O

N E

IN

C

H O

N T

H

IS

S H

EE

T, A D

JU

ST

S C

AL

ES

A C

C O

R D

IN

G

LY

ENGINEER:

DATE REVISIONS

ADEQUATE SURVEY

NO

200'S OF

CONTRACT

ON PROP. R/W REQ'D

OFF PROP. R/W REQ'D

OTHER UTILITIES

DRAWN

CHECK

THESE DOCUMENTS CONTAIN PRIVILEGED

AND CONFIDENTIAL INFORMATION WHICH

SHALL NOT BE REDISTRIBUTED WITHOUT

PRIOR WSSC APPROVAL VE

R

IF

Y

SC

AL

E

- B

AR

IS

O

N E

IN

C

H O

N O

R

IG

IN

AL

D R

AW

IF

N O

T O

N E

IN

C

H O

N T

H

IS

S H

EE

T, A D

JU

ST

S C

AL

ES

A C

C O

R D

IN

G

LY

ENGINEERING & ENVIRONMENTAL

SERVICES DIVISION

WASHINGTON SUBURBAN SANITARY COMMISSION

WSSC

DELIVERING THE ESSENTIAL

PROFESSIONAL CERTIFICATION

I HEREBY CERTIFY THAT THESE DOCUMENTS WERE PREPARED

OR APPROVED BY ME, AND THAT I AM A DULY LICENSED

PROFESSIONAL ENGINEER UNDER THE LAWS OF THE STATE OF

MARYLAND.

LICENSE NO.: 21984 EXPIRATION DATE: 05/24/2026

Z:

\G

ER

M

AN

TO

W N

-U

SG

R M

2\ D

C S\

PR

O

JE

C

TS

\W

TR

\6

2_

_W

SS

C _D

AM

SB

O A_

TA

SK

O R

D

ER

_8 \9

_C

AD

_G

IS

\9

_C

AD

\D

U C

KE

TT

_D W

G _D

R

AW

IN

G

S\

_D U

C

KE

TT

_P

IE

ZO

M

ET

ER

_D

ET

AI

L.

D

W G

PA

TH

/F

IL

EN

AM

E:

6221NE07

AUTOMATED DATA ACQUISITION SYSTEMS OF PIEZOMETERS AT

T. HOWARD DUCKETT DAM

BASIN: PATUXENT NORTH, PRINCE GEORGE'S COUNTIES, MARYLAND

BD7579A23

NOT TO SCALE

3/8" stainless steel U-bolt, nut, washer, and lock washer

½” liquid-tight conduit to the nearest buttress

¼” cable grip

Enclosure mounting plate

Signal cable

1.5” Brass Wye 1.5” x 0.25" Male to Female brass Hex reducing bushing

IP 68 cable gland 0.25" thread

Sensor cable routed to enclosure

Pipe fitted to 2.5" diameter for Piezometers D-1 & D-4 3.0" diameter for Piezometers D-2 & D-3

1.5” Brass nipple 3" long

1.5” Bronze ball valve with stainless steel ball

NOTES:

1. Piezometers D-1 and D-4 riser pipes are 2.5" diameter.

2. Piezometers D-2 and D-3 riser pipes are 3" diameter.

3. Liquid-tight conduit runs from each riser-mounted enclosure to buttress. PVC conduit runs from buttress to catwalk.

4. PVC conduit runs along catwalk to the PLC location in the utility shed.

Keller termination enclosure

PIEZOMETER INSTALLATION DETAILS

D-1 THROUGH D-4

2.5" to 1.5" reducer for Piezometers D-1 & D-4 3.0" to 1.5" reducer for Piezometers D-2 & D-3

7.

" 3.74"

1.5” diameter

NAME: AECOM TECHNICAL SERVICES INC.

ADDRESS: 12420 MILESTONE CENTER DRIVE, SUITE 150

GERMANTOWN, MD 20876

PHONE: 301-944-2545

CONTACT: BOB PINCIOTTI, P.E.

As-Built top elevation

06/03/25 - PLOT DATE

Digitally signed by Pinciotti, Bob DN: cn=Pinciotti, Bob, ou=USGRM2, email=bob.pinciotti@aecom.com Date: 2025.06.03 15:12:18 -04'00'

Pinciotti, ADEQUATE SURVEY

NO

200'S OF

CONTRACT

ON PROP. R/W REQ'D

OFF PROP. R/W REQ'D

OTHER UTILITIES

DRAWN

CHECK

THESE DOCUMENTS CONTAIN PRIVILEGED

AND CONFIDENTIAL INFORMATION WHICH

SHALL NOT BE REDISTRIBUTED WITHOUT

PRIOR WSSC APPROVAL VE

R

IF

Y

SC

AL

E

- B

AR

IS

O

N E

IN

C

H O

N O

R

IG

IN

AL

D R

AW

IF

N O

T O

N E

IN

C

H O

N T

H

IS

S H

EE

T, A D

JU

ST

S C

AL

ES

A C

C O

R D

IN

G

LY

ENGINEER:

DATE REVISIONS

ADEQUATE SURVEY

NO

200'S OF

CONTRACT

ON PROP. R/W REQ'D

OFF PROP. R/W REQ'D

OTHER UTILITIES

DRAWN

CHECK

THESE DOCUMENTS CONTAIN PRIVILEGED

AND CONFIDENTIAL INFORMATION WHICH

SHALL NOT BE REDISTRIBUTED WITHOUT

PRIOR WSSC APPROVAL VE

R

IF

Y

SC

AL

E

- B

AR

IS

O

N E

IN

C

H O

N O

R

IG

IN

AL

D R

AW

IF

N O

T O

N E

IN

C

H O

N T

H

IS

S H

EE

T, A D

JU

ST

S C

AL

ES

A C

C O

R D

IN

G

LY

ENGINEERING & ENVIRONMENTAL

SERVICES DIVISION

WASHINGTON SUBURBAN SANITARY COMMISSION

WSSC

DELIVERING THE ESSENTIAL

PROFESSIONAL CERTIFICATION

I HEREBY CERTIFY THAT THESE DOCUMENTS WERE PREPARED

OR APPROVED BY ME, AND THAT I AM A DULY LICENSED

PROFESSIONAL ENGINEER UNDER THE LAWS OF THE STATE OF

MARYLAND.

LICENSE NO.: 21984 EXPIRATION DATE: 05/24/2026

Z:

\G

ER

M

AN

TO

W N

-U

SG

R M

2\ D

C S\

PR

O

JE

C

TS

\W

TR

\6

2_

_W

SS

C _D

AM

SB

O A_

TA

SK

O R

D

ER

_8 \9

_C

AD

_G

IS

\9

_C

AD

\D

U C

KE

TT

_D W

G _D

R

AW

IN

G

S\

_D U

C

KE

TT

_W

AL

L_

PR

O

FI

LE

_C O

N D

U

IT

.D W

G

PA

TH

/F

IL

EN

AM

E:

6221NE07

AUTOMATED DATA ACQUISITION SYSTEMS OF PIEZOMETERS AT

T. HOWARD DUCKETT DAM

BASIN: PATUXENT NORTH, PRINCE GEORGE'S COUNTIES, MARYLAND

BD7579A23

NOTES:

1. Piezometer sensor cable runs from the riser pipe to an enclosure mounted on the riser pipe. See Piezometer Installation Details.

2. Liquid-tight conduit runs from each riser-mounted enclosure to buttress. PVC conduit runs from buttress to catwalk.

3. See conduit and wiring schedules.

CATWALK

CONDUIT ROUTE ON DAM PROFILE

BUTTRESS 1118' FROM

PIEZOMETER

TO BUTTRESS

BUTTRESS D-1

NOT TO SCALE

BUTTRESS D-2

NOT TO SCALE

BUTTRESS D-3

NOT TO SCALE

BUTTRESS D-4

NOT TO SCALE

BUTTRESS 13

5' FROM

PIEZOMETER

TO BUTTRESS

BUTTRESS 15

20'± FROM

PIEZOMETER

TO BUTTRESS

BUTTRESS 16

25'± FROM

PIEZOMETER

TO BUTTRESS

NAME: AECOM TECHNICAL SERVICES INC.

ADDRESS: 12420 MILESTONE CENTER DRIVE, SUITE 150

GERMANTOWN, MD 20876

PHONE: 301-944-2545

CONTACT: BOB PINCIOTTI, P.E.

NOTES:

1. EXISTING CONDITIONS/ FACILITY SHOWN ON PLAN VIEW HEREON ARE BASED ON AVAILABLE DESIGN RECORDS AND MAY NOT REFLECT CURRENT EXISTING CONDITIONS. CONTRACTOR IS RESPONSIBLE FOR VERIFYING ALL EXISTING CONDITIONS PRIOR TO ANY CONSTRUCTION WORK. CONTRACTOR TO NOTIFY THE ENGINEER AND WSSC PROJECT MANAGER IF ANY DISCREPANCIES OR CONFLICTS EXIST.

2. DRAWING SHOWS THE GENERAL ALIGNMENT AND APPROXIMATE LENGTH OF THE CONDUIT FROM EACH PIEZOMETER TO THE PLC ENCLOSURE. THE EXACT ROUTES AND CABLE LENGTHS SHALL BE

DETERMINED IN THE FIELD BY THE CONTRACTOR AND MUST BE APPROVED BY WSSC.

Wall mount brackets to be field located by Contractor. Spacing shall comply with the National Electrical Code.

06/03/25 - PLOT DATE

Digitally signed by Pinciotti, Bob DN: cn=Pinciotti, Bob, ou=USGRM2, email=bob.pinciotti@aecom.com Date: 2025.06.03 15:12:33 -04'00'

Pinciotti, ADEQUATE SURVEY

NO

200'S OF

CONTRACT

ON PROP. R/W REQ'D

OFF PROP. R/W REQ'D

OTHER UTILITIES

DRAWN

CHECK

THESE DOCUMENTS CONTAIN PRIVILEGED

AND CONFIDENTIAL INFORMATION WHICH

SHALL NOT BE REDISTRIBUTED WITHOUT

PRIOR WSSC APPROVAL VE

R

IF

Y

SC

AL

E

- B

AR

IS

O

N E

IN

C

H O

N O

R

IG

IN

AL

D R

AW

IF

N O

T O

N E

IN

C

H O

N T

H

IS

S H

EE

T, A D

JU

ST

S C

AL

ES

A C

C O

R D

IN

G

LY

ENGINEER:

DATE REVISIONS

ADEQUATE SURVEY

NO

200'S OF

CONTRACT

ON PROP. R/W REQ'D

OFF PROP. R/W REQ'D

OTHER UTILITIES

DRAWN

CHECK

THESE DOCUMENTS CONTAIN PRIVILEGED

AND CONFIDENTIAL INFORMATION WHICH

SHALL NOT BE REDISTRIBUTED WITHOUT

PRIOR WSSC APPROVAL VE

R

IF

Y

SC

AL

E

- B

AR

IS

O

N E

IN

C

H O

N O

R

IG

IN

AL

D R

AW

IF

N O

T O

N E

IN

C

H O

N T

H

IS

S H

EE

T, A D

JU

ST

S C

AL

ES

A C

C O

R D

IN

G

LY

ENGINEERING & ENVIRONMENTAL

SERVICES DIVISION

WASHINGTON SUBURBAN SANITARY COMMISSION

WSSC

DELIVERING THE ESSENTIAL

PROFESSIONAL CERTIFICATION

I HEREBY CERTIFY THAT THESE DOCUMENTS WERE PREPARED

OR APPROVED BY ME, AND THAT I AM A DULY LICENSED

PROFESSIONAL ENGINEER UNDER THE LAWS OF THE STATE OF

MARYLAND.

LICENSE NO.: 21984 EXPIRATION DATE: 05/24/2026

Z:

\G

ER

M

AN

TO

W N

-U

SG

R M

2\ D

C S\

PR

O

JE

C

TS

\W

TR

\6

2_

_W

SS

C _D

AM

SB

O A_

TA

SK

O R

D

ER

_8 \9

_C

AD

_G

IS

\9

_C

AD

\D

U C

KE

TT

_D W

G _D

R

AW

IN

G

S\

_D U

C

KE

TT

_A

D

AS

S

YS

TE

M

A R

C H

ET

C

U R

E.

D

W G

PA

TH

/F

IL

EN

AM

E:

6221NE07

AUTOMATED DATA ACQUISITION SYSTEMS OF PIEZOMETERS AT

T. HOWARD DUCKETT DAM

BASIN: PATUXENT NORTH, PRINCE GEORGE'S COUNTIES, MARYLAND

BD7579A23

D-1

D-2 D-3

D-4

ADAS SYSTEM ARCHITECTURE

Terminal Enclosure

Terminal Enclosure

Terminal Enclosure

Terminal Enclosure

Duckett Dam

NAME: AECOM TECHNICAL SERVICES INC.

ADDRESS: 12420 MILESTONE CENTER DRIVE, SUITE 150

GERMANTOWN, MD 20876

PHONE: 301-944-2545

CONTACT: BOB PINCIOTTI, P.E.

NOTES:

1. Keller Acculevel sensors have 4-20mA output and a 0-50PSI level sensing range.

(Item number: 0507.00203.051305.13)

2. The PLC Control Enclosure, PLC, instrumentation power, and barometer will be provided and installed by the WSSC.

3. Contractor shall verify the accuracy of all sensors at the direction of WSSC's process engineer.

4. Contractor shall connect the PVC conduit(s) to the PLC Control Enclosure and pull the sensor cables into the enclosure and leave three feet of sensor cable inside the enclosure for connection of the sensor cables to the PLC by the WSSC.

5. All sensor cables pulled into the PLC Control Enclosure shall be clearly and permanently marked with the appropriate piezometer number.

6. Conduit shall enters the PLC enclosure through a penetration at the lowest point possible on the side of the enclosure and if it is possible penetrate through the bottom of the enclosure. No top penetration of any conduit through enclosure shall be allowed. Locations of penetrations must be approved by WSSC.

2-wire current loop

(NTS)

2-wire current loop

(NTS)

PLC Controller Enclosure

Barometer

06/03/25 - PLOT DATE

Digitally signed by Pinciotti, Bob DN: cn=Pinciotti, Bob, ou=USGRM2, email=bob.pinciotti@aecom.com Date: 2025.06.03 15:12:53 -04'00'

Pinciotti, ADEQUATE SURVEY

NO

200'S OF

CONTRACT

ON PROP. R/W REQ'D

OFF PROP. R/W REQ'D

OTHER UTILITIES

DRAWN

CHECK

THESE DOCUMENTS CONTAIN PRIVILEGED

AND CONFIDENTIAL INFORMATION WHICH

SHALL NOT BE REDISTRIBUTED WITHOUT

PRIOR WSSC APPROVAL VE

R

IF

Y

SC

AL

E

- B

AR

IS

O

N E

IN

C

H O

N O

R

IG

IN

AL

D R

AW

IF

N O

T O

N E

IN

C

H O

N T

H

IS

S H

EE

T, A D

JU

ST

S C

AL

ES

A C

C O

R D

IN

G

LY

ENGINEER:

DATE REVISIONS

ADEQUATE SURVEY

NO

200'S OF

CONTRACT

ON PROP. R/W REQ'D

OFF PROP. R/W REQ'D

OTHER UTILITIES

DRAWN

CHECK

THESE DOCUMENTS CONTAIN PRIVILEGED

AND CONFIDENTIAL INFORMATION WHICH

SHALL NOT BE REDISTRIBUTED WITHOUT

PRIOR WSSC APPROVAL VE

R

IF

Y

SC

AL

E

- B

AR

IS

O

N E

IN

C

H O

N O

R

IG

IN

AL

D R

AW

IF

N O

T O

N E

IN

C

H O

N T

H

IS

S H

EE

T, A D

JU

ST

S C

AL

ES

A C

C O

R D

IN

G

LY

ENGINEERING & ENVIRONMENTAL

SERVICES DIVISION

WASHINGTON SUBURBAN SANITARY COMMISSION

WSSC

DELIVERING THE ESSENTIAL

PROFESSIONAL CERTIFICATION

I HEREBY CERTIFY THAT THESE DOCUMENTS WERE PREPARED

OR APPROVED BY ME, AND THAT I AM A DULY LICENSED

PROFESSIONAL ENGINEER UNDER THE LAWS OF THE STATE OF

MARYLAND.

LICENSE NO.: 21984 EXPIRATION DATE: 05/24/2026

Z:

\G

ER

M

AN

TO

W N

-U

SG

R M

2\ D

C S\

PR

O

JE

C

TS

\W

TR

\6

2_

_W

SS

C _D

AM

SB

O A_

TA

SK

O R

D

ER

_8 \9

_C

AD

_G

IS

\9

_C

AD

\D

U C

KE

TT

_D W

G _D

R

AW

IN

G

S\

_D U

C

KE

TT

_W

IR

E_

AN

D

_C O

N D

U

IT

_S C

H

ED

U

LE

.D W

G

PA

TH

/F

IL

EN

AM

E:

6221NE07

AUTOMATED DATA ACQUISITION SYSTEMS OF PIEZOMETERS AT

T. HOWARD DUCKETT DAM

BASIN: PATUXENT NORTH, PRINCE GEORGE'S COUNTIES, MARYLAND

BD7579A23

NOTES:

1. At each piezometer location, piezometer sensor cable runs from the riser pipe to an enclosure mounted on the riser pipe. See Piezometer Installation Details Drawing 03.

2. Liquid-tight conduit runs from each riser-mounted enclosure to buttress. PVC conduit runs from buttress to catwalk. And PVC conduit runs along the catwalk to the utility shed.

3. All PVC conduits to be Schedule 80.

4. Expansion fittings shall be included on PVC conduit runs in accordance with NEMA PRP 4-2009 (R2016) guidance and Section 347-9 of the National Electric Code.

5. Piezometer sensor shall be set 6-inches above the bottom of the existing piezometer.

6. Contractor shall survey as-built location, bottom elevation, top elevation of completed installation and calculate the elevation of the piezometer pressure sensor. Survey benchmarks are shown in the table below.

7. Drawing shows the general alignment and approximate length of the conduit from each piezometer to the PLC enclosure. The exact routes and cable lengths shall be determined in the field by the Contractor and must be approved by WSSC.

WIRING AND CONDUIT SCHEDULE

Duckett Dam Wiring Schedule

Well ID:

Top Elevation (ft)

Bottom Elevation (ft)

Cable length in standpipe (ft)

Total cable length (ft)

Cable length: standpipe to outside utility (ft)

D-1

195.3

151.0

44.3

358.3

314.0

D-2

192.0

123.8

68.2

456.2

388.0

D-3

174.5

139.3

35.2

434.2

399.0

D-4

176.5

148.9

27.6

458.6

431.0

Sch40 PVC Section

D-4 to Catwalk

1/2" Diameter

72.0 86.0

96.0

368.0 221.0

Duckett Dam Conduit Schedule

3/4" Diameter 90 Deg Turns Condulet T

Total conduit length (ft)

114.0

211.0 10.0

D-3 to Catwalk D-2 to Catwalk D-1 to Catwalk Catwalk section 15 to 08 Catwalk to PLC

Feet Feet Qty Qty

NAME: AECOM TECHNICAL SERVICES INC.

ADDRESS: 12420 MILESTONE CENTER DRIVE, SUITE 150

GERMANTOWN, MD 20876

PHONE: 301-944-2545

CONTACT: BOB PINCIOTTI, P.E.

06/03/25 - PLOT DATE

Digitally signed by Pinciotti, Bob DN: cn=Pinciotti, Bob, ou=USGRM2, email=bob.pinciotti@aecom.com Date: 2025.06.03 15:13:21 -04'00'

Pinciotti,

Sheets and Views
Layout
Sheets and Views
Layout1
Sheets and Views
Layout1
Sheets and Views
Layout1
Sheets and Views
Layout1
Sheets and Views
Layout1
2025-06-13T05:57:04-0700
Digitally verifiable PDF exported from www.docusign.com

File details come from the government source that posted it. Updated .