This document is Addendum No. 4 to the Invitation to Bid (ITB) for Project No. BC-730-241-003, "REPLACE EXTERIOR LIGHTING ELKTON DISTRICT COURT AND MULTI SERVICE BUILDING" in Elkton, Cecil County, Maryland, issued by the Maryland Department of General Services. The addendum clarifies and provides additional details on the scope of work, which includes replacing exterior lighting fixtures at the Elkton District Court and Multi-Service Building. The project requires the installation of 24 new pole light fixtures, as well as the replacement of 22 wall-mounted fixtures and 4 additional new wall-mounted fixtures. No drawings will be provided, but a detailed breakdown of the fixture types and quantities is included. The contract does not require prevailing wages or certified payroll reports.
The bid bond requirement is $100,000 and over, and a Performance and Payment (P&P) bond will be required upon award. No information is provided regarding set-asides, incumbents, funding sources, or renewal options.
View the file
Other files
Show all 16
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ADDENDUM NO. 4
March 18, 2024
STATE OF MARYLAND
DEPARTMENT OF GENERAL SERVICES
Design, Construction & Energy
PROJECT NO. BC-730-241-003
REPLACE EXTERIOR LIGHTING
ELKTON DISTRICT COURT AND MULTI SERVICE BUILDING
170 EAST MAIN STREET
ELKTON, CECIL COUNTY, MD 21921
TO ALL PROSPECTIVE BIDDERS: This Addendum is issued to clarify, add to, delete from, correct and/or change the Invitation to Bid (ITB) documents to the extent indicated and is hereby made a part of the said (ITB) documents of which the contract will be based. By submitting a bid for this solicitation you acknowledge receipt of this addendum. All questions must be in writing and addressed to Lakecia Dingle at Lakecia.Dingle@maryland.gov & Samantha Delp at Samantha.Delp@maryland.gov .
This Addendum includes the following:
Clarifications to the Specifications and Questions received.
1. Question: Provide the type of bulb that is in the wall sconces.
Answer: Please refer to Section B.2.d for the information on the proposed fixture.
2. Question: Please advise on the existing light bulbs in the wall sconces for potential rebates.
Answer: At present the State is not considering potential rebates for any work associated with this project
3. Question: Please clarify the scope of work at the pole light closest to the front door, is the light working, has power been checked, is the ground feed work located at the pole base, or is there a short in the line that needs to be located.
Answer: Section E. Method of Work. 2. states Excavate, by hand, as directed by Facility Manager around the light pole by the front entrance to the Court Building. Locate the existing underground feed for the light poles. Pull back wiring, install new splice box, provide, splice to existing wiring and install new wiring from splice box to light fixture. Back fill excavation.
The light works, power is present at the base, however the Facility Manager advises that there has been a “repair” close to the base of the pole, made prior to them being employed at this location. It is the intention to investigate and correct the repair in the manner as described above.
4. Question: When adding 24 new pole light fixtures “provide new wiring etc. and connect to existing electrical feed, does this mean the old wiring from inside each pole light needs to be removed and new wiring installed.
Answer: No, the only wiring needed would be that required to connect the additional fixtures to the supply at the base of the pole.
5. Question: The answer to question #1 in Addendum 3 states that the pole light fixture count is “24 four.” It also acknowledges that the two poles in the rear entrance were omitted in error and need two single Type A Fixtures (one for each pole.” Since the original pole light fixture requirement was 24 and two Type A Fixtures have now been added, is the Department requesting a cost for the installation of 26 pole light fixtures?
Answer: No, only 24 fixtures. See question 6 for a breakdown of fixtures.
6. Question: Given the confusion about pole light counts and how the Department is requesting more fixtures to be installed where currently there are only one or two, could the Department provide a drawing or breakdown identifying where and how many of each fixture type is to be installed? For example: Rear Entrance Sidewalk Pole A: one (1) Type A Fixture; Rear Entrance Sidewalk Pole B: one (1) Type A Fixture
Answer:
No Drawings will be provide, please see a breakdown of the fixtures below.
Type “A” Fixtures
Parking Lot Rear Currently there are 6 Poles with 12 fixtures, proposed is to replace fixtures adding 6 additional for a total of 18 fixtures
Rear Entrance Currently there are 2 poles with 2 fixtures, proposed is to replace fixtures.
Type “B” Fixtures
Front Entrance Currently there are 2 poles with 4 fixtures, proposed is to replace fixtures.
Total number of pole fixtures is 24 (twenty four)
Type “C” Fixtures
Front Entrance Sign Currently there is a three headed spotlight, again this is to be replaced by the fixtures specified.
Type “D” Fixtures
Wall Mounted Fixtures Currently there are 7 sconce type fixtures and 15 wall pack type fixtures, proposed it is to replace the fixtures with 22 new fixtures. Additionally there are 4 new fixtures to be added, with wiring and conduit to the East Exterior wall above the stairwells
7. Question: Is a bid bond required for all bids, or only if the bid exceeds $100,000?
Answer: Bid Bonds are required if the bid is $100,000 and over.
8. Question: Will a P&P Bond be required once awarded?
Answer: P&P are required when submitting documents during the solicitation process.
9. Question: Please confirm prevailing wages/certified payroll reports are not a requirement for this project.
Answer: Prevailing wages/certified payroll reports are not required for this project.
All other terms, conditions and specifications remain unchanged.
END OF ADDENDUM NO. 4