B54495 Q and A.docx
DOCX document 17 KB Posted
- Solicitation number
- 27-444DHS-MENTH-B-54495
- Issued by
- Madison County, Illinois
About this file
This is a Questions and Answers document related to a small purchase rebid by the Illinois Department of Mental Health at Chester Mental Health Center for replacement of sprinkler heads in the basement level of the hospital's wet pipe fire suppression system. The project requires furnishing and installing approximately 140 sprinkler heads (brass pendant, upright, and sidewall styles rated 160 degrees Fahrenheit and above, with 280-degree Fahrenheit rated heads for areas near heating equipment) in compliance with NFPA 13 and NFPA 25 standards and CMS Physical Environment requirements. Proposals were due October 26, 2026, and a mandatory onsite pre-bid meeting and walkthrough is required prior to bid submission. Work is restricted to Monday through Friday during designated windows (7:00 a.m. to 3:00 p.m. or 8:00 a.m. to 4:00 p.m.), with one-week advance notice required for initial start and one-workday notice for scheduled work. The facility will drain the system daily once the vendor arrives and will move items or materials blocking access to sprinkler heads as able; vendors may leave tools and a ladder in the unguarded basement at their own risk, with the facility accepting no responsibility for their safety.
The prime contractor must perform a minimum of 51 percent of total contract work on-site using directly employed workers and owned or rented equipment, with failure to meet this threshold constituting grounds for immediate termination for cause. The contractor must supply sprinkler head wrenches, spare wrenches to be turned over to the facility, and six spare heads of each type installed, as well as turn over all removed heads to the facility. Upon completion, the contractor must provide documentation to the Chief Engineer confirming all replacements, installed head specifications, and verification of post-work testing and system restoration. The project is subject to the Illinois Prevailing Wage Act, requiring payment of prevailing wage rates for the county where work is performed, with contractors required to certify prevailing wage compliance for bids to be considered responsive. During periods when Illinois unemployment exceeds 5 percent for two consecutive months, at least 90 percent of laborers must be Illinois residents; exceptions may be requested with supporting documentation. The contractor must be licensed and qualified in fire suppression system work, with NICET certification preferred.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Self-Performance Requirements~1.docx | DOCX document | |
| B-54191 Blue Print~1.pdf | ||
| RMU150~56.docx | DOCX document | |
| B54495 Specs for Sprinkler Head Replacments - Basement~1.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1. What about the system? Will it need to be drained every day, and will the facility be handling that?
· Yes, the facility will drain the system daily once the vendor has arrived, as we don’t want to drain it ahead of time in case an issue were to occur and the vendor did not show that day.
2. Do they need to be quick‑response heads?
· We have been told that quick‑response requirements fall under NFPA 13 and NFPA 25, which are required for the project. So yes, quick‑response heads are required because they are mandated by code.
3. Is 140 sprinkler heads the correct count?
· This number came from the facility trades, and at this time we believe that 140 heads is an accurate count. They have been counted twice, but that does not include the six extra of each style we are calling for.
4. If there are items or materials blocking access to the heads, will the facility move them out of the way?
· Yes, the facility will move whatever they are able to move out of the way.
5. Are we able to bring tools and a ladder into the basement and leave them there so we don’t have to bring them in and out daily?
· Yes, you can leave some tools and the ladder in the basement as long as they are not in the way. However, because there are no patients in the basement, it is an unguarded location, and we cannot guarantee their safety or take responsibility for them.
File details come from the government source that posted it. Updated .