B33805 Ice Machine Drawing Markup.pdf

PDF 6 MB Posted

Attached to
Ice Machine Install
Solicitation number
W9124926RA013
Issued by

About this file

This document set comprises architectural and engineering design drawings for an ice machine kiosk installation at a facility in Jacksonville, Florida. The drawings provide comprehensive specifications for plumbing, electrical, and site integration requirements necessary to install and operate a 16-foot IVK (Ice House America model) ice machine.

The plumbing design includes detailed layouts for water supply connections, filtration systems, and drainage infrastructure. Water supply components feature optional reverse osmosis systems, water softeners, sediment and carbon filters, and pressure regulators connecting to a 3/4-inch domestic water service line from the facility's water meter. The system incorporates multiple ball valves, solenoid valves, UV light treatment, and a flow meter to regulate water delivery to the ice maker and optional water dispenser. Drainage requirements specify 1.5-inch PVC drain lines from the ice maker, cooling unit, and filtration systems to the sanitary sewer, with provisions for trap primers and air gaps compliant with IPC 802.3.1. The water service detail mandates a double detector check valve/backflow preventer and pressure reducing valve installed on the incoming domestic water line. Electrical specifications call for either 240/120V or 208/120V, 3-phase, 4-wire service with a 60-amp 3-pole breaker for the ice maker and 125-amp 2-pole breaker for the kiosk, totaling approximately 22.5 kilowatts of connected load. Surface conduit must run from Electrical Room 159 to the ice machine location following the building exterior. Installation requires connections to the nearest available domestic water and sanitary sewer piping located in the scrub room (Room 166), with the ice machine kiosk positioned in the facility's common area as indicated on the first-floor plan.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Ice Machine

Electrical Room

Scrub Room (nearest sanitary and domestic)

2" FLOOR DRAIN TO

BOTTOM OF FRAME

WATER DISPENSER

DRAIN FROM BOTTOM OF

FRAME (1" AIR GAP)

UV LIGHT

4" BALL VALVE TO ICE MAKER

From RO Water Tank/ Softner

DRAIN LINE

WATER DISPENSER

(OPTIONAL)

COOLING UNIT

(ON ROOF)

ICE M

AKER

FLOOR DRAIN TROUGH

PRESSURE REGULATOR

FLOW SENSOR

SOLENOID VALVE

SEDIMENT FILTER

DECLORINATOR FILTER

WATER SOFTNER

(OPTIONAL)

RO SYSTEM (OPTIONAL)

W WWWW

W

WW

W

W

BRINE TANK

WATER TANK

GRUNDFOS PUMP

4" BALL VALVE

Y STRAINER

4" BALL VALVE FOR R.O.

SOFTNER BYPASS

2" SHUTOFF

D DD

D

D

D D

2" PEX PIPE (this side or other side)

D

WATER ENTRANCE

FROM BOTTOM OF FRAME

PRESSURE GUAGE

AIR GAP BEFORE TROUGH DRAIN

FOR ICE MAKER, COOLING UNIT,

WATER SOFTENER & RO

CARBON FILTER

(NOT SHOWN -

OPTIONAL)

W/ TRAP PRIMER OR

TRAP SEAL PROTECTION

Notes:

1. ALL AIR GAPS WILL BE A MINIMUM OF TWO PIPE DIAMETERS IN ACCORDANCE WITH IPC 802.3.1.

2. ALL INDIRECT WASTE IS IN THE INTERIOR OF THE BUILDING AND NOT LOCATED IN A WAY TO RECEIVE RAINWATER.

3. POTABLE WATER SUPPLY TO COFFEE MACHINES AND NONCARBONATED BEVERAGE DISPENSERS, ALONG WITH

CARBONATED BEVERAGE DISPENSERS, SHALL BE PROTECTED BY AN APPROVED VENTED BACKFLOW PREVENTION DEVICE (TWO INDEPENDENT CHECK VALVES WITH A VENT TO THE ATMOSPHERE) CONFORMING TO ASSE 1022 OR BY

AN AIR GAP

ICC-NTA, LLC, 305 N Oakland Ave Nappanee, Indiana 46550

COA: -

These documents are applicable only to the elements and loading criteria specifically provided herein. These documents shall not be construed in any way to specify, certify or design any aspects of the building not contained herein.

Specified design criteria are based solely on information provided by the client and must be verified and approved by the local authority having jurisdiction.

ICC-NTA, LLC is not responsible for fabrication or erection. If it is suspected that these documents have been modified, substituted or altered in any way, contact ICC-NTA, LLC at (574) 773-7975 to obtain a file copy.

TITLE:

MODEL:

APPROVED BY: JOB NO:

DRAWN BY: DRAWING NO:

REVISIONS: SCALE:

DATE:

3/14/24 LML 16' IVK

[PROJECT NUMBER]NTS

P-1

PLUMBING LAYOUT

Jacksonville, FL 32224 Ice House America-

4 Independence Way, Suite 401 Princeton, NJ 08540 +1 (609) 751-9655 office +1 (609) 751-9658 fax www.coolsysenergydesign.com

TBPE FIRM NO. F-19923

Water line connection located beneath ice machine

WATER TANK BRINE

TANK

WATER SOFTNER

Y-STRAINER

REVERSE

OSMOSIS

HOSE BIB LOCATED

FRONT OF MACHINE

PRESSURE GUAGE

WATER IN

ICE MAKER

20" 5

SEDIMENT FILTER

20" 0.5

CARBON FILTER

#2 34" PEX BALL VALVE

FOR RO BYPASS

(NC WHEN R.O. ON)

#7 12" PEX BALL VALVE

(LOCATED REAR END OF MACHINE)

#1 34" PEX BALL VALVE

UV BULB

FLOW METER

WATER

DISPENSOR

(OPTIONAL)

DISPENSING NOZZLE

(NOZZLE IS PROTECTED

FROM CONTAMINATION

VIA. EXTERNAL SHIELD)

RINSE CYLCE

METER BYPASS

SOLENOID VALVE

SOLENOID IS DRIVEN BY

PLC OUTPUT Y17 AND

WILL TURN OFF WITH UV

LIGHT UNDER ABNORMAL

CONDITIONS DEMA 38"

SOLENOID VALVE

#3 34" PEX

BALL VALVE

REVERSE OSMOSIS SYSTEM (OPTIONAL)

2" SHUTOFF VALVE

(LOCATED FRONT OF MACHINE)

PRESSURE GUAGE

8" Poly Tubing

2" Funny

Pipe 3 8" Poly Tubing

2" Pex Pipe

4" Pex Pipe

3 4" P ex P ip e

2" JG Tube

1 12" SCH40 Pipe

3 4" P ex P ip e

3 4" P ex P ip e

3 4" P ex P ip e

8" Poly Tubing

#4 34" PEX

BALL VALVE

ICE MAKER DRAIN

TO TROUGH

#5 34" PEX

BALL VALVE

RO water for Ice Maker & Water Dispenser Turn Off Valve # 2 & 5

Soften water for Ice Maker & RO Water for Water Dispenser Turn Off Valve # 2 & 4

Soften water for Ice Maker & Water Dispenser Turn Off Valve # 3

DELIVERY

PUMP

RO DRAIN TO TROUGH

WATER SOFTNER DRAIN

TO TROUGH

#6 12" PEX BALL VALVE

ROOF TOP

STERILIGHT UV LIGHT

HAS POWERED OUTPUT

(120V) INTO PLC INPUT

X17 WHICH WILL TURN

OFF UNDER ABNORMAL

CONDITIONS

WATER DISPENSER DRAIN

TO PIPE

GUAGE AND

PRESSURE REGULATORCOOLING UNIT

ON ROOF

COOLING UNIT DRAIN

TO TROUGH

HOSE BIB LOCATED

REAR OF MACHINE

ICC-NTA, LLC, 305 N Oakland Ave Nappanee, Indiana 46550

COA: -

These documents are applicable only to the elements and loading criteria specifically provided herein. These documents shall not be construed in any way to specify, certify or design any aspects of the building not contained herein.

Specified design criteria are based solely on information provided by the client and must be verified and approved by the local authority having jurisdiction.

ICC-NTA, LLC is not responsible for fabrication or erection. If it is suspected that these documents have been modified, substituted or altered in any way, contact ICC-NTA, LLC at (574) 773-7975 to obtain a file copy.

TITLE:

MODEL:

APPROVED BY: JOB NO:

DRAWN BY: DRAWING NO:

REVISIONS: SCALE:

DATE:

3/14/24 LML 16' IVK

[PROJECT NUMBER]NTS

P-2

PLUMBING SCHEMATIC

Jacksonville, FL 32224 Ice House America-

4 Independence Way, Suite 401 Princeton, NJ 08540 +1 (609) 751-9655 office +1 (609) 751-9658 fax www.coolsysenergydesign.com

TBPE FIRM NO. F-19923

Water line connection located beneath ice machine

Scrub room with nearest available domestic water and sanitary sewer piping

Approximate location of ice machine kiosk

Nearest available domestic water piping

PLAN VIEW

SCALE 1 / 15

ELEVATION VIEW

SCALE 1 / 15

ICE BIN

ICE BAGGER

ICE MAKER COOLING UNIT

FILTRATION

SYSTEM

TYPICAL WATER DRAIN/ 'P' TRAP DIAGRAM

NO SCALE (REFER SITE SPECIFIC DWG/LOCAL CODE)

TO PUBLIC SEWER SYSTEM

OR PRIVATE DISPOSAL UNLESS

APPROVED BY LOCAL

AUTHORITIES OTHERWISE

TROUGH DRAIN FOR

ICE MAKER

COOLING UNIT

WATER SOFTNER

RO (OPTIONAL)

3" PVC MIN @ 18 FT

AAV VENT

2" PVC

1 12" PIPE DRAIN FOR

WATER DISPENSER

FROM FRONT OF UNIT

CLEAN OUT AT

EXTERIOR GRADE

SLOPE TO DRAIN

INSULATED FLOOR PANELS

4X4 STEEL BEAM UNDERNEATH

WATER SERVICE DETAIL

PRESSURE REDUCING VALVE

DOUBLE DETECTOR CHECK VALVE/ BACKFLOW PREVENTER

SHUT OFF VALVE, TYP

SHUT-OFF VALVE, TYP

3/4"

NO SCALE

DI

RE

CT

IO

N

OF

F

LO

W

3/4" DOMESTIC WATER SERVICE LINE FROM METER

SEE WATER DRAIN/ "P" TRAP DIAGRAM

BA

CK

O F

TH

E

UN

IT

ICC-NTA, LLC, 305 N Oakland Ave Nappanee, Indiana 46550

COA: -

These documents are applicable only to the elements and loading criteria specifically provided herein. These documents shall not be construed in any way to specify, certify or design any aspects of the building not contained herein.

Specified design criteria are based solely on information provided by the client and must be verified and approved by the local authority having jurisdiction.

ICC-NTA, LLC is not responsible for fabrication or erection. If it is suspected that these documents have been modified, substituted or altered in any way, contact ICC-NTA, LLC at (574) 773-7975 to obtain a file copy.

TITLE:

MODEL:

APPROVED BY: JOB NO:

DRAWN BY: DRAWING NO:

REVISIONS: SCALE:

DATE:

3/14/24 LML 16' IVK

[PROJECT NUMBER]

ARH

NTS

EQ-1A

EQUIPMENT INFORMATION W/ SEWER DRAINAGE

Jacksonville, FL 32224 Ice House America-

4 Independence Way, Suite 401 Princeton, NJ 08540 +1 (609) 751-9655 office +1 (609) 751-9658 fax www.coolsysenergydesign.com

TBPE FIRM NO. F-19923

Drain line to be installed by contractor

Connect to existing drain line

Nearest available sanitary sewer piping

Notes:

1. ALL ELECTRICAL EQUIPMENT SHALL MEET WORKING CLEARANCE REQUIREMENT.

2. ALL FIXTURES SHALL BE SECURED TO STRUCTURE.

3. ALL FLEX SHALL CONTAIN FULL SIZE GREEN GROUND. NO ALUMINUM BONDS OR CONDUCTORS.

4. GROUND PER NEC CODES.

5. LOAD & BREAKER TABLE IS FOR GENERAL REFERENCE ONLY.

CALCULATE LOAD SIZE BASED ON ACTUAL MACHINE SPECIFICATION.

ICE MAKER

3P- DISC. SWITCH

NEMA 3R

COOLING

UNIT

240 / 120 V 3 Phase 4W

OR

208 / 120 V 3 PHASE 4 W

SERVICE BY UTILITY

FIELD CONNECTION

INSIDE

ELECTRICAL

PANEL

3 #6 THHN (CU),

#10 GD (CU), 1" C

STD KIOSK W/O OPTION:

3 #3 THHN (CU),

#8 GD (CU), 1.5" C

OR

REFER TABLE FOR DIFFERENT SPEC

60 Amp 3P

BREAKER FOR

ICE MAKER

OUTSIDE

ELECTRICAL

PANEL

FACTORY INSTALLED

2 #12 THHN (CU),

#12 GD (CU), 1/2" C

KIOSK WITH 5200 ARCTIC TEMP IM

1 PHASE POWER SUPPLY

#2(CU) SERVICE GD

TO GROUND ROD

METER

SEE TABLE TO

CALCULATE

BREAKER SIZE

C#20/22/24

C#1/3

NAME DETAIL WATTS VOLTAGE AMPERAGE WIRE GROUND CONDUIT

COOLING UNIT Cooling Unit 1886 230 8.2000 12 12 1

2" CONTROL PLC & All Prox Sensors 600 110 5 14 14 -

LIGHTS

7 LED RTFT Top hat Light 98 115 0.9500 14 14 1 2"

Inside Front Flood Lights 26 115 0.2500 14 14 1 2"

VF & Top Hat LED Module 158 115 1.5300 14 14 1 2"

Inside Rear Lights (Optional) 20 115 0.1900 14 14 1 2"

RECEPT

Air Compressor 1150 115 10 14 14 1 2"

MDB Pro 230 115 2 14 14 NA Router, Modem & (Optional) Camera 92 115 0.8000 14 14 NA

Audio Speaker (Optional) 3 24 0.1250 - - -

HEATERS

50W Heater (Ice MB) 50 115 0.5000 14 14 NA 50W Heater (Ele Cab) 50 115 0.5000 14 14 NA

Heater Inside Kiosk (Optional) 1500 115 12.5000 14 14 -

MOTORS

Bin Motor 621 230 2.7000 14 14 1

2" Rack Motor 1242 230 5.4000 14 14 1

2" Incline Auger Motor 1242 230 5.4000 14 14 1

2" ROOF TOP RECEPT Roof Heat tape (2x 18'L - Optional) 360 115 3.1300 14 14 -

WATER DISP.

Water Dispenser Controller

115 0.2000 14 14 -

50W Heater 115 0.5000 14 - NA UV Light 115 0.2000 14 14 -

WATER

SOFTENER/DELIVERY

PUMP

Water Softener 60 115 0.5000 14 14 1 2"

Scala Delivery Pump (Optional) 990 115 8.6200 12 14 1 2"

RO R4X40-1 RO System (Optional) 920 115 8 12 14 1 2"

BLOWER Bag Blower 1610 115 14 14 - 1 2"

(Optional)

13008 240 A SERVICE RATING

5200 Arctic Temp IM 9400 208-230 45.2000 6 10 1"

22408

22408 240 A SERVICE RATING

SERVICE FROM OUTSIDE ELECTRICAL PANEL

DOUBLE GANG RECEPTACLE FOR CWP (OPT.)

SINGLE GANG RECEPTACLE (STANDARD) FOR

AIR COMPRESSOR

INCLINED AUGER MOTOR SWITCH

BLOWER MOTOR SWITCH

C#11

C#6

C#4

C#5

TO SENSORS

BIN FLOOR MOTOR SWITCH

RAKE MOTOR SWITCH

INSIDE LIGHT

C#6 C#6

C#3

REAR JUNCTION BOX FOR RO

REAR JUNCTION BOX

SINGLE GANG RECEPTACLE

(STANDARD) FOR WATER

SOFTENER/RO DELIVERY PUMP

DOUBLE GANG RECEPTACLE FOR CWP (OPT.)

C#5

C#9

C#10

TO ROOF TOP

ELECTRICAL

CONTROL

CABINET

TO WATER

DISPENSOR

C#8

ROOF LINEROOF LINE

ROOF TOP JUNCTION BOX-2ROOF TOP JUNCTION BOX-1

ROOF TOP RECEPTACLE

C#7

TO ICE MAKER

TO COOLING UNIT

C#1

TO TOP HAT LIGHT

C#3

125 AMP DISCONNECT SWITCH

CONTROL PANEL SCHEDULE (INSIDE KIOSK)

VOLTAGE: 240 /120, 1PH., 4 WIRE

PHASE LOAD TOTALS

C# LOAD TRIP POLE A B POLE TRIP LOAD C#

1 COOLING UNIT 20 2

<-- 943 <-- 943

1 20 CONTROL 2600 -->

3 LIGHTS (TOP HAT, VF, INSIDE) 20 1

<-- 300

1 20 RECEPTACLE (AIR COMP) 41475 -->

5 HEATERS (ELE CAB & MB CAB HEATER & COLD

WEATHER 20 1

<-- 1660

2 20 MOTORS (BIN, RAKE & AUGER) 6

1553 --> 1553 -->

7 ROOF TOP RECEPT 1 (ROOF HEAT TAPE) 20 1

360 -->

1 20 WATER DISPENSER 8

<-- 100

9 WATER SOFTNER & DELIVERY PUMP (OPTIONAL) 20 1 1 20 RO (OPTIONAL) 101050 -->

<-- 920

11 BLOWER 20 1

<-- 1610

13 14

PHASE LOAD TOTALS

A B

11486 10981

TOTAL CONNECTED LOAD = 22.5 KW TOTAL CONNECTED AMPS= 108 A

ICC-NTA, LLC, 305 N Oakland Ave Nappanee, Indiana 46550

COA: -

These documents are applicable only to the elements and loading criteria specifically provided herein. These documents shall not be construed in any way to specify, certify or design any aspects of the building not contained herein.

Specified design criteria are based solely on information provided by the client and must be verified and approved by the local authority having jurisdiction.

ICC-NTA, LLC is not responsible for fabrication or erection. If it is suspected that these documents have been modified, substituted or altered in any way, contact ICC-NTA, LLC at (574) 773-7975 to obtain a file copy.

TITLE:

MODEL:

APPROVED BY: JOB NO:

DRAWN BY: DRAWING NO:

REVISIONS: SCALE:

DATE:

3/14/24 LML 16' IVK

[PROJECT NUMBER]NTS

E-2B

ELECTRICAL RISER 5200 ARTIC TEMP IM 3 PHASE

Jacksonville, FL 32224 Ice House America-

4 Independence Way, Suite 401 Princeton, NJ 08540 +1 (609) 751-9655 office +1 (609) 751-9658 fax www.coolsysenergydesign.com

TBPE FIRM NO. F-19923

Electrical Room

RM 159

Scrub Room

RM 166

Electrical Panel

DP1

Install 60A 3-pole breaker on CKTs 14,16,18 for the ice maker

Install 125A 2-pole breaker on CKTs 22,24 for the ice machine kiosk

Install surface conduit from RM 159 to the ice machine, following the building exterior.

204.78 197.79 714.05

598.43 427.79

739.27 195.86 707.08 719.80 514.55

54.45 54.20

50.82

Install 60A 3-pole breaker on CKTs 14,16,18 for the ice maker

Install 125A 2-pole breaker on CKTs 22,24 for the ice machine kiosk

3.15 3.15

3.15

6.50 6.50

54.20 451.69

54.45

240.59 442.65 453.77423.49

159.47

50.82

86.68