B23-0302-EN Medford Floating Solar Permit Set - 09.19.23 (1).pdf
PDF 4 MB Posted
- Solicitation number
- S-Q10026-00009306
- Issued by
- Jackson County, Cheshire CDP, Oregon
About this file
This document is a permit set for the Medford Floating Solar project, which is being developed by the Farmers Conservation Alliance for a site located in Medford, Oregon. The permit set includes drawings, diagrams, and specifications for the electrical system components, including a 929.28 kW DC floating solar array with 88 strings of 242 solar modules each, 8 central inverters, and an interconnection to the local utility's 12.47 kV distribution system. The project will utilize a 1000 kVA pad-mounted transformer and a utility-owned recloser and revenue metering equipment. The electrical contractor is responsible for installing the transformer, primary disconnect switch, recloser, and relay, as well as providing the primary and secondary conductors and conduits. The utility will provide the interconnection equipment between the point of interconnection and the customer-provided pole.
The document also references a related state and local contract opportunity for the Medford Irrigation District Photovoltaic System Installation project. This RFP is seeking proposals for the installation of a photovoltaic system, with responses due by 2/26/2024. The project is located in Jackson County, Oregon, and the successful bidder will be responsible for providing all necessary equipment and services for the system installation.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
LOCATION MAPVICINITY MAP
MEDFORD OREGON
42.321705, -122.947866
MEDFORD FLOATING SOLAR
FARMERS CONSERVATION ALLIANCE
APPROVED BY:
CHECKED BY:
CAD FILE:
DRAWN BY:
PROJECT NUMBER:
DESIGNED BY:
THIS DOCUMENT, AND THE ASSOCIATED DESIGNS, IS AN
INSTRUMENT OF SERVICES FOR THIS PROJECT AND SHALL
NOT BE USED FOR ANY OTHER PURPOSE WITHOUT
WRITTEN AUTHORIZATION FROM OS ENGINEERING.
IF NOT ONE INCH ON THIS SHEET, ADJUST
SCALES ACCORDINGLY
BAR IS ONE INCH ON ORIGINAL DRAWING
DRAWING NO.SHEET SIZE
D
REVISIONS
DRAWING STATUS
STAMP
VERIFY SCALES
PROJECT
SHEET TITLE
PROJECT DATE:
PROJECT OWNER:
DESCRIPTIONNO. DATE BY
0 1"
PROJECT NAME:
COVER SHEET
FOR PERMITMC/WB08.30.230
1 - EG001 COVER SHEET
B230302EN-EG001 R0.dwg
08.30.23
M. CORWIN
M. CORWIN
WB
WB
EG001
FOR PERMIT
MEDFORD
FLOATING SOLAR
42.321705, -122.947866
MEDFORD OREGON
FARMERS
CONSERVATION
ALLIANCE
1919 LAURA STREET
SPRINGFIELD, OREGON 97477
PHONE: (541) 393-3345
WWW.OS-ENGR.COM
CRESWELL
ST. HELENS
ASTORIA
TILLAMOOK
ALBANY
NEWPORT
PRINEVILLE
BEND
LAKEVIEW
BURNS
PENDLETON
LA GRANDE
ENTERPRISE
VALE
PORTLAND
SALEM
EUGENE
ROSEBURG
REDMOND
KLAMATH FALLS
THE
DALLES
HOOD RIVER
GOLD
BEACH
OREGON
PA
CI
FIC
O
CE
AN
SISTERS
CALIFORNIA
WASHINGTON
MEDFORD
WILSONVILLE
PROJECT
SITE
72661PE
OREGON
ENG
INEER
JUNE 11, 20
RE
G I
ST
ERE
D PROFESS IONAL
W
AYLON BOW
ER
S
EXPIRES:12/31/2023
DRAWING LIST:
Sheet Number Sheet Title
1 EG001 COVER SHEET
2 EG002 NOTES AND LEGENDS
3 E-001 ONE-LINE DIAGRAM
4 E-002 CALCULATIONS
5 E-101 SITE PLAN
6 E-102 SITE PLAN-POINT OF INTERCONNECTION
7 E-201 - MAJOR EQUIPMENT
APPROVED BY:
CHECKED BY:
CAD FILE:
DRAWN BY:
PROJECT NUMBER:
DESIGNED BY:
THIS DOCUMENT, AND THE ASSOCIATED DESIGNS, IS AN
INSTRUMENT OF SERVICES FOR THIS PROJECT AND SHALL
NOT BE USED FOR ANY OTHER PURPOSE WITHOUT
WRITTEN AUTHORIZATION FROM OS ENGINEERING.
IF NOT ONE INCH ON THIS SHEET, ADJUST
SCALES ACCORDINGLY
BAR IS ONE INCH ON ORIGINAL DRAWING
DRAWING NO.SHEET SIZE
D
REVISIONS
DRAWING STATUS
STAMP
VERIFY SCALES
PROJECT
SHEET TITLE
PROJECT DATE:
PROJECT OWNER:
DESCRIPTIONNO. DATE BY
0 1"
PROJECT NAME:
NOTES AND LEGENDS
FOR PERMITMC/WB08.30.230
B23-0302-EN
B230302EN-EG002 R0.dwg
08.30.23
M. CORWIN
M. CORWIN
WB
WB
EG002
FOR PERMIT
MEDFORD
FLOATING SOLAR
42.321705, -122.947866
MEDFORD OREGON
FARMERS
CONSERVATION
ALLIANCE
THERMAL MAGNETIC CIRCUIT BREAKER, SHOWN WITH RATING AND TRIP
SETTINGS, 'MCP' INDICATES MOTOR CONTROL CIRCUIT PROTECTOR
ONE-LINE LEGEND:
'X'
MPCB
MOTOR PROTECTION CIRCUIT PROTECTOR
DRAWOUT BREAKER SHOWN WITH RATING AND TRIP SETTINGS
GANG OPERATED DISCONNECT SWITCH
DISCONNECT SWITCH
FUSED CUT OUT
FUSE
F
DISCONNECT SWITCH
FUSED DISCONNECT SWITCH
COMBINATION DISCONNECT SWITCH AND MOTOR STARTER
FVR
FVNR
MOTOR STARTER, 'FVR' INDICATES FULL VOLTAGE, REVERSING , SIZE AND
RATINGS AS SPECIFIED ON THE DIAGRAM OR BY MOTOR RATINGS
FULL VOLTAGE, NON-REVERSING MOTOR STARTER, SIZE AND RATINGS AS
SPECIFIED ON THE DIAGRAM OR BY MOTOR RATINGS
OVERLOAD ELEMENT
SPD
VFD
SS
SURGE PROTECTION DEVICE
VARIABLE FREQUENCY DRIVE
SOFT STARTER
RESISTOR
LINE LOAD REACTOR
HRG HIGH RESISTANCE GROUNDING SYSTEM
SURGE ARRESTOR
GROUND
CAPACITOR
TRANSFORMER, NUMBER OF PHASES, CONFIGURATION, RATINGS, AND
IMPEDANCE AS INDICATED OR SPECIFIED
VOLTAGE TRANSFORMER
BUSHING MOUNTED CURRENT TRANSFORMER
CURRENT TRANSFORMER
ZERO SEQUENCE CURRENT TRANSFORMER
HP
XX MOTOR, HORSEPOWER AS INDICATED
WELDING RECEPTACLE
BACKUP GENERATOR
VOLTAGE REGULATOR
R RECLOSER
TRANSFER SWITCH
'X' 'V' INDICATES VOLT METER, 'PM' INDICATES POWER METER, 'A' INDICATES
AMP METER, 'AF' INDICATES ARC FLASH PROTECTION
UNDERGROUND CABLE TERMINATION
OVERHEAD CABLE TERMINATION
EQUIPMENT OUTLINE
GROUNDING TEST WELL ROD
GROUNDING LEGEND:
G
GROUNDING ROD
PIG TAIL
CABLE TO CABLE CONNECTION
UFER CONNECTION
GROUND BAR
CONDUIT STUB-UP
G BARE COPPER GROUND CABLE
UNDERGROUND CONDUIT
CONDUIT STUB-UP
OVERHEAD CONDUIT
CONDUIT LEGEND:
1. ELECTRICAL CONTRACTOR (EC) TO VERIFY AND INSTALL ALL IN SCOPE ELECTRICAL
EQUIPMENT AND COMPONENTS IN ACCORDANCE WITH NATIONAL ELECTRIC CODE
AND LOCAL REGULATIONS AND STANDARDS.
2. LEGENDS ARE FOR GENERAL INFORMATION AND MAY NOT BE USED IN ALL
PROJECTS.
3. BUILDING MATERIALS AND STRUCTURE TO BE DESIGNED AND INSTALLED BY
OTHERS. ALL ELECTRICAL EQUIPMENT AND HARDWARE TO BE INSTALLED BY THE EC.
4. ALL CONDUCTORS TO BE COPPER UNLESS NOTED OTHERWISE.
5. SEPARATELY DERIVED SYSTEMS SHALL BE PROPERLY GROUNDED PER NEC 250.30
(A)(1) THROUGH (A)(8).
6. ELECTRICAL PERMIT FOR IN SCOPE WORK IS REQUIRED TO BE PROVIDED BY THE EC.
GENERAL NOTES:
GROUNDING AND BONDING NOTES:
1. MAIN GROUND GRID CABLES BURIED TO A DEPTH OF NO LESS THAN 24".
2. GROUND WIRE AND GROUND RODS SHALL BE INSTALLED AT LEAST 24" FROM THE
FOUNDATION FOOTERS AND 18" OUTSIDE ROOF DRIPLINES.
3. GROUND RODS ARE NOT TO SCALE.
4. GROUNDING TO BE PLACED IN CONDUIT TRENCH WHEN AVAILABLE.
5. ALL STUB UP'S TO BE PLACED IN 1' PVC.
6. GROUND RODS TO HAVE MAXIMUM SEPARATION OF 100' AROUND BUILDINGS.
7. GROUND TEST WELL GROUND RODS TO BE 3/4" X 20' ALL OTHER TO BE 3/4" X 10'.
8. TOP OF GROUND RODS TO BE BURIED 24" MINIMUM BELOW GRADE EXCEPT FOR
PGE PROVIDED GROUND ROD AT SERVICE TRANSFORMER. REFER TO PGE ESR
SECTION 6.4.1. THE TOP MUST BE AT LEAST 4" ABOVE FINAL GRADE AND AT LEAST
4" ON THE FIELD SIDE OF THE PRIMARY SOURCE.
9. ALL ELECTRIC AND COMMUNICATION VAULTS ARE TO BE BONDED TO THE
GROUNDING SYSTEM.
LIGHTING LEGEND:
S X Y
OS
BRANCH CIRCUIT ARROW INDICATES HOME RUN, SHORT TICK INDICATES
PHASE CONDUCTORS, LONG TICKS INDICATE NEUTRAL CONDUCTORS.
2' X 4' RECESSED LIGHT FIXTURE, HATCHING INDICATES EMERGENCY
2' X 2' RECESSED LIGHT FIXTURE, HATCHING INDICATES EMERGENCY
1' X 4' RECESSED LIGHT FIXTURE, HATCHING INDICATES EMERGENCY
1' X 4' RECESSED LIGHT FIXTURE, HATCHING INDICATES EMERGENCY
4' RECESSED LIGHT FIXTURE, HATCHING INDICATES EMERGENCY
2' RECESSED LIGHT FIXTURE, HATCHING INDICATES EMERGENCY
X" RECESSED CAN LIGHT
2' X 4' FLUSH MOUNT LIGHT FIXTURE, HATCHING INDICATES EMERGENCY
2' X 2' FLUSH MOUNT LIGHT FIXTURE, HATCHING INDICATES EMERGENCY
1' X 4' FLUSH MOUNT LIGHT FIXTURE, HATCHING INDICATES EMERGENCY
1' X 4' FLUSH MOUNT LIGHT FIXTURE, HATCHING INDICATES EMERGENCY
4' FLUSH MOUNT LIGHT FIXTURE, HATCHING INDICATES EMERGENCY
2' FLUSH MOUNT LIGHT FIXTURE, HATCHING INDICATES EMERGENCY
2' X 4' HI-BAY LIGHT FIXTURE, HATCHING INDICATES EMERGENCY
2' X 2' HI-BAY LIGHT FIXTURE, HATCHING INDICATES EMERGENCY
1' X 4' HI-BAY LIGHT FIXTURE, HATCHING INDICATES EMERGENCY
1' X 4' HI-BAY LIGHT FIXTURE, HATCHING INDICATES EMERGENCY
4' HI-BAY LIGHT FIXTURE, HATCHING INDICATES EMERGENCY
2' HI-BAY LIGHT FIXTURE, HATCHING INDICATES EMERGENCY
X" HI-BAY LIGHT FIXTURE, HATCHING INDICATES EMERGENCY
CEILING MOUNTED EXIT SIGN, DIRECTION OF ILLUMINATION NOTED BY
SHADED AREA, DIRECTION INDICATED BY ARROWS
WALL MOUNTED EXIT SIGN, DIRECTION OF ILLUMINATION NOTED BY
SHADED AREA, DIRECTION INDICATED BY ARROWS
DOUBLE BUG EYE EMERGENCY LIGHT FIXTURE
EXTERIOR WALL PACK LIGHT FIXTURE
EXTERIOR FLOOD LIGHT FIXTURE
PC
OCCUPANCY SENSOR
PHOTO CELL SENSOR
WALL MOUNTED SWITCH, 2 INDICATES 2 POLE, 3 INDICATES 3 POLE, O
INDICATES OCCUPANCY SENSOR, D INDICATES DIMMER
J JUNCTION BOX
RECEPTACLE LEGEND:
X
X
X
X
SINGLE RECEPTACLE OUTLET, 'GFCI' INDICATES GROUND FAULT CIRCUIT
INTERRUPTER, 'GFP' INDICATES GROUND FAULT PROTECTED, 'WP'
INDICATES WEATHER PROOF
DUPLEX RECEPTACLE OUTLET, 'GFCI' INDICATES GROUND FAULT CIRCUIT
INTERRUPTER, 'GFP' INDICATES GROUND FAULT PROTECTED, 'WP'
INDICATES WEATHER PROOF
TRIPLEX RECEPTACLE OUTLET, 'GFCI' INDICATES GROUND FAULT CIRCUIT
INTERRUPTER, 'GFP' INDICATES GROUND FAULT PROTECTED, 'WP'
INDICATES WEATHER PROOF
QUADRUPLEX RECEPTACLE OUTLET, 'GFCI' INDICATES GROUND FAULT
CIRCUIT INTERRUPTER, 'GFP' INDICATES GROUND FAULT PROTECTED, 'WP'
INDICATES WEATHER PROOF
DUPLEX FLOOR RECEPTACLE OUTLET, 'GFCI' INDICATES GROUND FAULT
CIRCUIT INTERRUPTER, 'WP' INDICATES WEATHER PROOF
QUADRUPLEX FLOOR RECEPTACLE OUTLET, 'GFCI' INDICATES GROUND
FAULT CIRCUIT INTERRUPTER, 'WP' INDICATES WEATHER PROOF
SPECIAL PURPOSE OUTLET
MULTI OUTLET ASSEMBLY, ARROW LENGTH INDICATES LENGTH OF
ASSEMBLY IN INCHESX"
X
X
BRANCH CIRCUIT ARROW INDICATES HOME RUN, SHORT TICK INDICATES
PHASE CONDUCTORS, LONG TICKS INDICATE NEUTRAL CONDUCTORS.
J JUNCTION BOX
WALL MOUNTED VOICE AND DATA PORT, 'X' INDICATES NUMBER OF
PORTS
WALL MOUNTED DATA PORT, 'X' INDICATES NUMBER OF PORTS
WALL MOUNTED VOICE PORT, 'X' INDICATES NUMBER OF PORTS
FLOOR MOUNTED VOICE AND DATA PORT, 'X' INDICATES NUMBER OF
PORTS
FLOOR MOUNTED DATA PORT, 'X' INDICATES NUMBER OF PORTS
FLOOR MOUNTED VOICE PORT, 'X' INDICATES NUMBER OF PORTS
CEILING DROP VOICE AND DATA PORT, 'X' INDICATES NUMBER OF PORTS
CEILING DROP DATA PORT, 'X' INDICATES NUMBER OF PORTS
CEILING DROP VOICE PORT, 'X' INDICATES NUMBER OF PORTS
DUPLEX FLOOR RECEPTACLE / VOICE AND DATA FLOOR PORT, 'X'
INDICATES NUMBER OF PORTS
DUPLEX FLOOR RECEPTACLE / DATA FLOOR PORT, 'X' INDICATES NUMBER
OF PORTS
DUPLEX FLOOR RECEPTACLE / VOICE FLOOR PORT, 'X' INDICATES NUMBER
OF PORTS
X
X
X
X
X
X
X
X
X
X
X
X
LIGHTING AND RECEPTACLE NOTES:
1. SWITCHES TO BE INSTALLED AT 36" FROM FINISHED FLOOR UNLESS OTHERWISE
NOTED.
2. RECEPTACLES TO BE INSTALLED AT 12-18" FROM FINISHED FLOOR UNLESS
OTHERWISE NOTED.
3. ALL DOWNSTREAM OUTLETS FROM GFCI TO BE WIRED FROM GFCI LOAD TERMINAL
FOR GROUND FAULT PROTECTION.
MEDIUM VOLTAGE RACK OUT POWER BREAKER
ABBREVIATIONS:
'CPP' - CLEAN POWER PANEL
'CPT' - CLEAN POWER TRANSFORMER
'DBM' - DETERMINED BY MANUFACTURER
'EL' - EGRESS LIGHTING
'FBO' - FURNISHED BY OTHERS
'LC' - LIGHTING CONTACTOR
'LP' - LIGHTING PANEL
'LT' - LIGHTING TRANSFORMER
'MLO' - MAIN LUG ONLY
'TBD' - TO BE DETERMINED
CABLE AND CONDUIT IDENTIFIERS:
'C' - CONTROL
'DISC' - DISCONNECT WITH 1 N/O AUX CONTACT
'ES' - E-STOP
'J' - JUNCTION BOX
'L' - POWER 120V/208V/240V
'P' - POWER 480V AND ABOVE
'U' - UTILITY AND SERVICE ENTRANCE
'X' - COMMUNICATIONS
1919 LAURA STREET
SPRINGFIELD, OREGON 97477
PHONE: (541) 393-3345
WWW.OS-ENGR.COM
72661PE
OREGON
ENG
INEER
JUNE 11, 20
RE
G I
ST
ERE
D PROFESS IONAL
W
AYLON BOW
ER
S
EXPIRES:12/31/2023
(6) 3" SCH40 PVC
(24) 300kcmil AL THWN-2
(6) 1/0 AWG AL SBJ
DISTRIBUTION TRANSFORMER
1000kVA, A-B-C 12.47kV: 480V, 60HZ H: 95kV BIL, X: 30kV BIL
KNAN, ~EST. 5.32 %Z
PACIFICORP EQUIPMENT
ELECTRICAL CONTRACTOR
ELECTRICAL CONTRACTOR
BY DC CONTRACTOR
V
A
T
MODBUS
RS-485
W
VAR
PF
VA
ARRAY 1
AC DISCONNECT
(4) #4/0 AL THWN-2
(1) #4 AWG AL THWN-2
(1) 2 1/2" SCH40 PVC
STRING #1
2C - #10 AWG CU
1500V, PV
242 PV MODULES
22 PV MODULES IN SERIES = 1 STRING
11 STRINGS IN PARALLEL
Voc_array = 1174.60 VDC
Isc_string = 11.12 A Isc_array = 122.32 A Vr_array = 997.26 V
Ir_array = 116.49A Pr_array = 116.17 kW
INVERTER 1
CPS-SCH100KTL-DO/US-480
Vmax_in = 1000 VDC Imax_in = 260 A
Vr_max_in = 1000 VDC Vr_min_in = 195 VDC
Pr_max_out = 100 kW Vr_max_out = 480 VAC Ir_max_out = 120.3 A
PF = > 0.99, ADJ +/- 0.8
ɳ_min = 98.9%
Pdesign_out = 100 kW
O U
P G
P G
ANTI-
ISLAND
AFCI
100KTL
CENTRAL WIRE BOX
12.47KV LINE
UTILITY
R
15KV
RECLOSER, POLE MOUNT
REVENUE
METERING
PT 7.2kV/12.47kV Y -120V (60:1)
100:5
15.5kV, 800A, 12.5kAIC, 110kV BIL
(3) 0.3B0.5
SEL 651R
81 27 59
505146 67G
100:5MR
(1)
SET 50:5
51N
DS-POI
MDS1
MDS2
POLE MOUNT
SWITCHBOARD 1
1600A,480V, 3P,4W 30kAIC
TYPE 3R
GROUND BUS
#6 BARE CU
GROUNDING
ROD - 8' MIN
FLOATING ARRAY
(4) 3" SCH80 PVC
(4) MV-105 - #2AWG
NEUTRAL BUS
250kcmil CU SBJ
OR FACTORY INSTALLED
1600A 3P
CB
150A 3P
CB-1
TO
INVERTER 8
TO
INVERTER 7
DC COMBINER
STRING #11
2C - #10 AWG CU
1500V, PV
(2) - #1 AWG 1500V PV
242 MODULES PER INVERTER(S) 1-8
11 STRINGS PER INVERTER(S) 1-8
88 STRINGS TOTAL
1936 MODULES TOTAL
TOTAL POWER 929.28 kWDC
MODULE MODEL NUMBER: Q. PEAK DUO XL - G103/BFG - 480
(4) ACSR BARE AL #2 SPARROW
150A 3P
CB-2
150A
3P
CB-3
150A
3P
CB-4
150A
3P
CB-5
150A
3P
CB-6
150A
3P
CB-7
150A
3P
CB-8
TO
INVERTER 6
TO
INVERTER 5
TO
INVERTER 4
TO
INVERTER 3
TO
INVERTER 2
#6 CU AWG
GROUNDING
ROD - 8' MIN APPROVED BY:
CHECKED BY:
CAD FILE:
DRAWN BY:
PROJECT NUMBER:
DESIGNED BY:
THIS DOCUMENT, AND THE ASSOCIATED DESIGNS, IS AN
INSTRUMENT OF SERVICES FOR THIS PROJECT AND SHALL
NOT BE USED FOR ANY OTHER PURPOSE WITHOUT
WRITTEN AUTHORIZATION FROM OS ENGINEERING.
IF NOT ONE INCH ON THIS SHEET, ADJUST
SCALES ACCORDINGLY
BAR IS ONE INCH ON ORIGINAL DRAWING
DRAWING NO.SHEET SIZE
D
REVISIONS
DRAWING STATUS
STAMP
VERIFY SCALES
PROJECT
SHEET TITLE
PROJECT DATE:
PROJECT OWNER:
DESCRIPTIONNO. DATE BY
0 1"
PROJECT NAME:
ONE-LINE DIAGRAM
FOR PERMITMC/WB08.30.230
B23-0302-EN
B230302EN-E-001 R0.dwg
08.30.23
M. CORWIN
M. CORWIN
WB
WB
E-001
FOR PERMIT
MEDFORD
FLOATING SOLAR
42.321705, -122.947866
MEDFORD OREGON
FARMERS
CONSERVATION
ALLIANCE
1919 LAURA STREET
SPRINGFIELD, OREGON 97477
PHONE: (541) 393-3345
WWW.OS-ENGR.COM
1. ESTIMATED FAULT CURRENT CONTRIBUTION IS 23.02kA AT THE SERVICE
GEAR. PROVIDE PERMANENT LABEL WITH ACTUAL FAULT CURRENT FROM THE
UTILITY AT SERVICE ENTRANCE PRIOR TO FINAL INSPECTION, SEE NEC 110.24.
2. ELECTRICAL CONTRACTOR MUST PROVIDE PRIMARY AND SECONDARY
CONDUCTORS AND CONDUITS SPANNING FROM TRANSFORMER TO
CUSTOMER PROVIDED POLE.
3. ELECTRICAL CONTRACTOR WILL FURNISH AND INSTALL THE TRANSFORMER,
PRIMARY DISCONNECT SWITCH (MDS2), RECLOSER, AND 651-R RELAY. EC
MUST FURNISH AND INSTALL THE TRANSFORMER PAD.
4. PACIFIC POWER WILL PROVIDE SPAN FROM POI TO CUSTOMER PROVIDED
POLE.
5. PACIFIC POWER WILL PROVIDE MDS1 DISCONNECT SWITCH.
6. DATALOGGING & COMMUNICATION SYSTEMS ARE BY OTHERS.
7. INVERTER(S) 1-8 HAVE IDENTICAL STRINGING
8. PV EQUIPMENT FLOATING ON OR ATTACHED TO STRUCTURES FLOATING ON
BODIES OF WATER MUST BE IDENTIFIED AS BEING SUITABLE FOR THE
PURPOSE AND MUST UTILIZE WIRING METHODS THAT ALLOW FOR ANY
EXPECTED MOVEMENT OF THE EQUIPMENT.
GENERAL NOTES:
72661PE
OREGON
ENG
INEER
JUNE 11, 20
RE
G I
ST
ERE
D PROFESS IONAL
W
AYLON BOW
ER
S
EXPIRES:12/31/2023
1. PROVIDE INSULATED CONDUCTOR FOR CORROSIVE ENVIRONMENTS. BOND
ALL MODULES. GROUNDING RODS ARE TO BE INSTALLED ON SHORE.
2. PROVIDE SIGNAGE IN ACCORDANCE WITH 2023 NEC ARTICLE 555.10 (1)(2)(3).
3. ALL DC WIRING MUST FOLLOW 2023 NEC ARTICLE 690.31
4. BECAUSE OF THE NATURAL ARTICULATION BETWEEN MODULES ON THE
FLOATING ARRAY, FLEXIBLE CABLES MUST BE USED. REFERENCE TABLE
690.31(C)(4). SAME RULE MUST BE FOLLOWED FOR ALL CABLING EXITING THE
ARRAY.
5. EACH ARRAY MUST INCORPORATE GFDI PROTECTION IN ACCORDANCE WITH
2023 NEC ARTICLE 690.41(B).
EQUIPMENT NOTES:
3 3
CAD FILE:
DRAWN BY:
PROJECT NUMBER:
DESIGNED BY:
THIS DOCUMENT, AND THE ASSOCIATED DESIGNS, IS AN
INSTRUMENT OF SERVICES FOR THIS PROJECT AND SHALL
NOT BE USED FOR ANY OTHER PURPOSE WITHOUT
WRITTEN AUTHORIZATION FROM OS ENGINEERING.
IF NOT ONE INCH ON THIS SHEET, ADJUST
SCALES ACCORDINGLY
BAR IS ONE INCH ON ORIGINAL DRAWING
DRAWING NO.SHEET SIZE
D
REVISIONS
DRAWING STATUS
STAMP
VERIFY SCALES
PROJECT
SHEET TITLE
PROJECT DATE:
PROJECT OWNER:
DESCRIPTIONNO. DATE BY
0 1"
PROJECT NAME:
CALCULATIONS
FOR PERMITMC/WB08.30.230
B23-0302-EN
B230302EN-E-002 R0.dwg
08.30.23
M. CORWIN
M. CORWIN
WB
WB
E-002
FOR PERMIT
MEDFORD
FLOATING SOLAR
42.321705, -122.947866
MEDFORD OREGON
FARMERS
CONSERVATION
ALLIANCE
1919 LAURA STREET
SPRINGFIELD, OREGON 97477
PHONE: (541) 393-3345
WWW.OS-ENGR.COM
ARRAY 1-8: 11 STRINGS (PER ARRAY, 88 STRINGS TOTAL)
SCALE: NOT TO SCALEC1
CAD FILE:
DRAWN BY:
PROJECT NUMBER:
DESIGNED BY:
THIS DOCUMENT, AND THE ASSOCIATED DESIGNS, IS AN
INSTRUMENT OF SERVICES FOR THIS PROJECT AND SHALL
NOT BE USED FOR ANY OTHER PURPOSE WITHOUT
WRITTEN AUTHORIZATION FROM OS ENGINEERING.
IF NOT ONE INCH ON THIS SHEET, ADJUST
SCALES ACCORDINGLY
BAR IS ONE INCH ON ORIGINAL DRAWING
DRAWING NO.SHEET SIZE
D
REVISIONS
DRAWING STATUS
STAMP
VERIFY SCALES
PROJECT
SHEET TITLE
PROJECT DATE:
PROJECT OWNER:
DESCRIPTIONNO. DATE BY
0 1"
PROJECT NAME:
SITE PLAN
FOR PERMITMC/WB08.30.230
B23-0302-EN
B230302EN-E-101 R0.dwg
08.30.23
M. CORWIN
M. CORWIN
WB
WB
E-101
FOR PERMIT
MEDFORD
FLOATING SOLAR
42.321705, -122.947866
MEDFORD OREGON
FARMERS
CONSERVATION
ALLIANCE
1919 LAURA STREET
SPRINGFIELD, OREGON 97477
PHONE: (541) 393-3345
WWW.OS-ENGR.COM
SITE PLAN
SCALE: 1" = 60'-0" 0 60' 120'A1
1. THE SITE PLAN IS NOT SURVEYED AND ALL LOCATIONS AND DIMENSIONS ARE
APPROXIMATE. FIELD VERIFY ALL ASPECTS OF THE INSTALLATION.
2. ALL ELECTRICAL WORK FROM THE COMBINER, THROUGH THE INVERTERS, AND
TO THE SOLAR PANELS IS BY OTHERS INCLUDING SOLAR PANEL INSTALLATION.
GENERAL NOTES: KEYED NOTES:
1 NON-SERVICE ENTRANCE CONDUIT TRENCHING MAY BE 18' DEEP PER OESC TABLE
300.5
2 POTENTIAL POINT OF INTERCONNECTION & SERVICE TRANSFORMER LOCATIONS
PENDING PGE DESIGN.
72661PE
OREGON
ENG
INEER
JUNE 11, 20
RE
G I
ST
ERE
D PROFESS IONAL
W
AYLON BOW
ER
S
EXPIRES:12/31/2023
A1 E-102
C4 E-201
PROPERTY LINE
NORTH IRRIGATION POND
SOUTH IRRIGATION POND
FLOATING SOLAR SYSTEM. FLOATING SOLAR SYTEM IS BY OTHERS. FLOATING SOLAR
INCLUDES: ALL RACKING, WIRE ROUTING WITHIN AND EXITING ARRAY, DC
COMBINERS, AND SOLAR MODULES.
VICINITY MAP
PROJECT
SITE
SCALE: NOT TO SCALE
2' -0
CONCRETE PAD
7' -8
6"
10" WIREWAY
CENTRALIZED WIRE BOX
REF. E-201, DETAIL "C2"
INVERTER
REF. E-201, DETAIL "C2"
HATCHED AREAS INDICATE BACKSIDE OF
INVERTERS INSTALLED ON OPPOSITE SIDE
OF RACK
3"DIA
STEEL POSTS
AC COMBINER-SWITCHBOARD
REFERENCE E-001 FOR WIRING
1600A
MAIN
DISCONNECT
23'-0 1/2"
9' -4
2' -8
11'-9"
INVERTER(S) 1-4
INVERTER(S) 5-8
10" WIRE WAY
STRUCTURAL
SUPPORTS
(UNISTRUT)
10" WIRE WAY
HATCHED AREAS BOTTOM ROWS OF
INVERTERS.
SCALE: 1" = 5'-0" 0 60' 120'A1
1. THE SITE PLAN IS NOT SURVEYED AND ALL LOCATIONS AND DIMENSIONS ARE
APPROXIMATE. FIELD VERIFY ALL ASPECTS OF THE INSTALLATION.
2. ALL EQUIPMENT IS DEPENDENT UPON PACIFICORP REVIEW/DESIGN.
GENERAL NOTES:KEYED NOTES:
NEW SPAN FROM POINT OF INTERCONNECTION TO NEW POLE. SPAN PROVIDED BY
PACIFICORP.
POTENTIAL POINT OF INTERCONNECTION, SWITCH MDS1, & METER LOCATIONS
PENDING PGE DESIGN.
72661PE
OREGON
ENG
INEER
JUNE 11, 20
RE
G I
ST
ERE
D PROFESS IONAL
W
AYLON BOW
ER
S
EXPIRES:12/31/2023
AC COMBINER/INVERTER PAD - FRONT
SCALE: 1/2" = 1'-0" 0 1' 2' 4'A3
APPROVED BY:
CHECKED BY:
CAD FILE:
DRAWN BY:
PROJECT NUMBER:
DESIGNED BY:
THIS DOCUMENT, AND THE ASSOCIATED DESIGNS, IS AN
INSTRUMENT OF SERVICES FOR THIS PROJECT AND SHALL
NOT BE USED FOR ANY OTHER PURPOSE WITHOUT
WRITTEN AUTHORIZATION FROM OS ENGINEERING.
IF NOT ONE INCH ON THIS SHEET, ADJUST
SCALES ACCORDINGLY
BAR IS ONE INCH ON ORIGINAL DRAWING
DRAWING NO.SHEET SIZE
D
REVISIONS
DRAWING STATUS
STAMP
VERIFY SCALES
PROJECT
SHEET TITLE
PROJECT DATE:
PROJECT OWNER:
DESCRIPTIONNO. DATE BY
0 1"
PROJECT NAME:
SITE PLAN
FOR PERMITMC/WB08.30.230
B23-0302-EN
B230302EN-E-101 R0.dwg
08.30.23
M. CORWIN
M. CORWIN
WB
WB
E-102
FOR PERMIT
MEDFORD
FLOATING SOLAR
42.321705, -122.947866
MEDFORD OREGON
FARMERS
CONSERVATION
ALLIANCE
1919 LAURA STREET
SPRINGFIELD, OREGON 97477
PHONE: (541) 393-3345
WWW.OS-ENGR.COM
SITE PLAN - INVERTERS TO POINT OF INTERCONNECTION
NON-SERVICE ENTRANCE CONDUIT TRENCHING MAY BE 18' DEEP PER OESC TABLE
300.5
NEW POLE AND GUY LINE PROVIDED BY ELECTRICAL CONTRACTOR.3
SWITCH "MDS2" PROVIDED BY ELECTRICAL CONTRACTOR & OPERATED BY PACIFICORP.
REFERENCE SHEET E-201, DETAIL "B2."4
RECLOSER AND INTEGRATED "R1" RELAY. PROVIDED BY ELECTRICAL CONTRACTOR.
REFERENCE SHEET E-201, DETAIL "B1."5
TRENCHING, CONDUIT AND CONDUCTORS PROVIDED BY ELECTRICAL CONTRACTOR.
REFERENCE E-100 ONE-LINE DIAGRAM FOR DETAILS.
TRANSFORMER "T1" & TRANSFORMER PAD LOCATION. PROVIDED AND INSTALLED BY ELECTRICAL
CONTRACTOR. MAINTAINED BY CUSTOMER. REFERENCE SHEET E-201, DETAIL "B4."7
AC COMBINER/INVERTER EQUIPMENT PAD. PROVIDED BY ELECTRICAL CONTRACTOR.8
AC COMBINER-SWITCHBOARD. PROVIDED BY ELECTRICAL CONTRACTOR. REFERENCE
SHEET E-201, DETAIL "A1."9
INVERTER RACK. (8) TOTAL INVERTERS - (4) INSTALLED BACK TO BACK AND STAGGERED. REFERENCE DETAIL "A4." REFERENCE SHEET E-201, DETAIL "C2." REFERENCE INVERTER INSTALLATION MANUAL REV 1.8.
AC COMBINER/INVERTER PAD - TOP
SCALE: 1/2" = 1'-0" 0 1' 2' 4'B3
72661PE
OREGON
ENG
INEER
JUNE 11, 20
RE
G I
ST
ERE
D PROFESS IONAL
W
AYLON BOW
ER
S
EXPIRES:12/31/2023
APPROVED BY:
CHECKED BY:
CAD FILE:
DRAWN BY:
PROJECT NUMBER:
DESIGNED BY:
THIS DOCUMENT, AND THE ASSOCIATED DESIGNS, IS AN
INSTRUMENT OF SERVICES FOR THIS PROJECT AND SHALL
NOT BE USED FOR ANY OTHER PURPOSE WITHOUT
WRITTEN AUTHORIZATION FROM OS ENGINEERING.
IF NOT ONE INCH ON THIS SHEET, ADJUST
SCALES ACCORDINGLY
BAR IS ONE INCH ON ORIGINAL DRAWING
DRAWING NO.SHEET SIZE
D
REVISIONS
DRAWING STATUS
STAMP
VERIFY SCALES
PROJECT
SHEET TITLE
PROJECT DATE:
PROJECT OWNER:
DESCRIPTIONNO. DATE BY
0 1"
PROJECT NAME:
MAJOR EQUIPMENT
FOR PERMITMC/WB08.30.230
B23-0302-EN
B230302EN-E-101 R0.dwg
08.30.23
M. CORWIN
M. CORWIN
WB
WB
E-201
FOR PERMIT
MEDFORD
FLOATING SOLAR
42.321705, -122.947866
MEDFORD OREGON
FARMERS
CONSERVATION
ALLIANCE
1919 LAURA STREET
SPRINGFIELD, OREGON 97477
PHONE: (541) 393-3345
WWW.OS-ENGR.COM
TRANSFORMER
SCALE: NOT TO SCALEB4
SOLAR MODULE- 480W
SCALE: NOT TO SCALEC1 FLOATING PV-EXAMPLE ONLY
SCALE: NOT TO SCALEC4SOLAR INVERTER-100KW-WYE-NEUTRAL GROUNDED
SCALE: NOT TO SCALEC2
VIPER-ST POLE MOUNT RECLOSER W/ SEL 651-R RELAY
SCALE: NOT TO SCALEB1 MDS2-GANG OPERATED DISCONNECT
SCALE: NOT TO SCALEB2
AC COMBINER-SWITCHBOARD
SCALE: NOT TO SCALEA1
1. ALL EQUIPMENT MUST BE APPROVED BY SUBMITTAL TO OS ENGINEERING
PRIOR TO ORDERING. NO EXCEPTIONS.
GENERAL NOTES:
| Sheets and Views |
| 1 EG001 COVER SHEET |
| 2 EG002 NOTES AND LEGENDS |
| 3 E-001 ONE-LINE DIAGRAM |
| 4 E-002 CALCULATIONS |
| 5 E-101 SITE PLAN |
| 6 E-102 SITE PLAN-POINT OF INTERCONNECTION |
| 7 E-201 - MAJOR EQUIPMENT |
File details come from the government source that posted it. Updated .