This document contains an air flow table and specifications for isolation rooms on the fourth and fifth floors of a facility. It lists the room numbers, sizes, air flow rates, and other technical details for the existing and proposed new isolation rooms. The related federal contract opportunity is solicitation number 36C26123R0091 from the Department of Veterans Affairs for isolation room mitigation work at facility 654-23-011. The opportunity type is listed as a solicitation. The document provides technical requirements for isolation room upgrades at a Veterans Affairs medical center. It includes specifications for new air flow rates, control valves, minimum and maximum pressures for each room. This scope of work appears to be for heating, ventilation and air conditioning system upgrades to existing isolation rooms.

View the file

Other files

Show all 17

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

AREA

ROOM #S

NEW

ROOM #S

OLD

ROOM

NAME

TU # MODE S/A CFM E/A - A E/A - B

4TH FLR B4131 3C-107 ANTE 3.19 1 100

….A 3C-107A ISOL 3.19 1 400 460

….B 3C-107B BATH 1

B4131 3C-107 ANTE 3.19 2 100 230

….A 3C-107A ISOL 3.19 2 400 230

….B 3C-107B BATH 2

B4135 3C-112 ANTE 3.18 1 100

….A 3C-112A ISOL 3.18 1 400 460

….B 3C-112B BATH 1

B4135 3C-112 ANTE 2 100 230

….A 3C-112A ISOL 3.18 2 400 230

….B 3C-112B BATH 3.18 2

B4192 3C-134 ANTE 3.7 1 100

….A 3C-134A ISOL 3.7 1 620 720

….B 3C-134B BATH 1

B4192 3C-134 ANTE 3.7 2 100 280

….A 3C-134A ISOL 3.7 2 620 440

….B 3C-134B BATH 2

B4188 3C-139 ANTE 3.6 1 100

….A 3C-139A ISOL 3.6 1 620 720

….B 3C-139B BATH 1

B4188 3C-139 ANTE 3.6 2 100 280

….A 3C-139A ISOL 3.6 2 620 440

….B 3C-139B BATH 2

5TH FLR B5131 4C-107 ANTE 4.19 1 100

….A 4C-107A ISOL 4.19 1 400 460

….B 4C-107B BATH 1

B5131 4C-107 ANTE 4.19 2 100 230

….A 4C-107A ISOL 4.19 2 400 230

….B 4C-107B BATH 2

B5135 4C-112 ANTE 4.18 1 100

….A 4C-112A ISOL 4.18 1 400 460

….B 4C-112B BATH 1

B5135 4C-112 ANTE 4.18 2 100 230

….A 4C-112A ISOL 4.18 2 400 230

….B 4C-112B BATH 2

B5192 4C-134 ANTE 4.7 1 100

….A 4C-134A ISOL 4.7 1 620 720

….B 4C-134B BATH 1

B5192 4C-134 ANTE 4.7 2 100 280

….A 4C-134A ISOL 4.7 2 620 440

….B 4C-134B BATH 2

B5188 4C-139 ANTE 4.6 1 100

….A 4C-139A ISOL 4.6 1 620 720

….B 4C-139B BATH 1

B5188 4C-139 ANTE 4.6 2 100 280

….A 4C-139A ISOL 4.6 2 620 440

….B 4C-139B BATH 2

E/A - C POS or

NEG

AX.V AX.X AX.Z DIAGAM

P 2 N 460 2

90 N 90 2 N 230 2 P 230 2

90 N 90 2

P 2 N 460 2

90 N 90 2 N 230 2 P 230 2

90 N 90 2

P 2 N 720 2

90 N 90 2 N 280 2 P 440 2

90 N 90 2

P 2 N 720 2

90 N 90 2 N 280 2 P 440 2

90 N 90 2

P 2 N 460 2

90 N 90 2 N 230 2 P 230 2

90 N 90 2

P 2 N 460 2

90 N 90 2 N 230 2 P 230 2

90 N 90 2

P 2 N 720 2

ISOLATION ROOMS AIR FLOW TABLE

90 N 90 2 N 280 2 P 440 2

90 N 90 2

P 2 N 720 2

90 N 90 2 N 280 2 P 440 2

90 N 90 2

M/A CFM

N 100 TO B4131A

P 100 FROM B4131A; P 50 FRO CORR B4

P 90 FROM B4131A

P 80 FROM B4131A; P 50 FRO CORR B4

N 80 TO B4131; N 90 TO B4131B

P 90 FROM B4131A

N 100 TO B4135A

P 100 FROM B4135A; P 50 FRO CORR B4

P 90 FROM B4135A

P 80 FROM B4135A; P 50 FRO CORR B4

N 80 TO B4135; N 90 TO B4135B

P 90 FROM B4135A

N 100 TO B4192A

P 100 FROM B4192A; P 50 FRO CORR B4

P 90 FROM B4192A

P 80 FROM B4192A; P 50 FRO CORR B4

N 80 TO B4192; N 90 TO B4192B

P 90 FROM B4192A

N 100 TO B4188A

P 100 FROM B4188A; P 50 FRO CORR B4

P 90 FROM B4188A

P 80 FROM B4188A; P 50 FRO CORR B4

N 80 TO B4188; N 90 TO B4188B

P 90 FROM B4188A

N 100 TO B5131A

P 100 FROM B5131A; P 50 FRO CORR B5

P 90 FROM B5131A

P 80 FROM B5131A; P 50 FRO CORR B5

N 80 TO B5131; N 90 TO B5131B

P 90 FROM B5131A

N 100 TO B5135A

P 100 FROM B5135A; P 50 FRO CORR B5

P 90 FROM B5135A

P 80 FROM B5135A; P 50 FRO CORR B5

N 80 TO B5135; N 90 TO B5135B

P 90 FROM B5135A

N 100 TO B5192A

P 100 FROM B5192A; P 50 FRO CORR B5

P 90 FROM B5192A

P 80 FROM B5192A; P 50 FRO CORR B5

N 80 TO B5192; N 90 TO B5192B

P 90 FROM B5192A

N 100 TO B5188A

P 100 FROM B5188A; P 50 FRO CORR B5

P 90 FROM B5188A

P 80 FROM B5188A; P 50 FRO CORR B5

N 80 TO B5188; N 90 TO B5188B

P 90 FROM B5188A

MIN MAX

A2.1 12-AHU-3 460 230 0.12 10"

A2.2 12-AHU-3 230 0.12 10"

A2.3 12-AHU-3 90 90 0.12 6"

A2.4 12-AHU-3 460 230 0.12 10"

A2.5 12-AHU-3 230 0.12 10"

A2.6 12-AHU-3 90 90 0.12 6"

A2.7 12-AHU-3 720 440 0.12 10"

A2.8 12-AHU-3 280 0.12 10"

A2.9 12-AHU-3 90 90 0.12 6"

A2.10 12-AHU-3 720 440 0.12 10"

A2.11 12-AHU-3 280 0.12 10"

A2.12 12-AHU-3 90 90 0.12 6"

A3.1 12-AHU-4 460 230 0.12 10"

A3.2 12-AHU-4 230 0.12 10"

A3.3 12-AHU-4 90 90 0.12 6"

A3.4 12-AHU-4 460 230 0.12 10"

A3.5 12-AHU-4 230 0.12 10"

A3.6 12-AHU-4 90 90 0.12 6"

A3.7 12-AHU-4 720 440 0.12 10"

A3.8 12-AHU-4 280 0.12 10"

A3.9 12-AHU-4 90 90 0.12 6"

A3.10 12-AHU-4 720 440 0.12 10"

A3.11 12-AHU-4 280 0.12 10"

A3.12 12-AHU-4 90 90 0.12 6"

AIR FLOW CONTROL VALVES

CFM

SYSTEMAFCV UNIT # SP AT MAX CFM INLET SIZE

B4131 ISOL 3C-107

….A ANTI 3C-107A

….B BATH 3C-107B

B4135 ISOL 3C-112

….A ANTI 3C-112A

….B BATH 3C-112B

B4192 ISOL 3C-134

….A ANTI 3C-134A

….B BATH 3C-134B

B4188 ISOL 3C-139

….A ANTI 3C-139A

….B BATH 3C-139B

B5131 ISOL 4C-107

….A ANTI 4C-107A

….B BATH 4C-107B

B5135 ISOL 4C-112

….A ANTI 4C-112A

….B BATH 4C-112B

B5192 ISOL 4C-134

….A ANTI 4C-134A

….B BATH 4C-134B

B5188 ISOL 4C-139

….A ANTI 4C-139A

….B BATH 4C-139B

SERVICE

ROOM AIR FLOW
AFCV