B08d Attachment 4 DEVA 280631 TFP400 09 2019.pdf
PDF 280 KB Posted
- Solicitation number
- 140P8120Q0081
View the file
Other files
| File | Type | Posted |
|---|---|---|
| C55 Questions and Answers BH responses 2020_0811_0001.docx | DOCX document | |
| Sol_140P8120Q0081_Amd_0001.pdf | ||
| B08b Attachment 2 Sprinkler General Specs.docx | DOCX document | |
| B08o Attachment 16 Wage Determination CA20200020.pdf | ||
| B08j Attachment 10 Construction Invoice NPS 302 2 Invoice Payment Request.docx | DOCX document | |
| Sol_140P8120Q0081.pdf | ||
| B08f Attachment 6 DEVA 280631 Attach B SprinklerPhotos.docx | DOCX document | |
| B08 Solicitation.docx | DOCX document | |
| B08a Attachment 1 SOW.docx | DOCX document | |
| B08n Attachment 14 Release of Claims.pdf | ||
| B08e Attachment 5 DEVA 280631 Attach A Map.jpg | JPG image | |
| B08k Attachment 11 SF24 16.pdf | ||
| B08l Attachment 12 SF25A 16a.pdf | ||
| B08m Attachment 13 SF25 16a.pdf | ||
| B08c Attachment 15 sample price schedule.xlsx | XLSX spreadsheet | |
| B08i Attachment 9 Cow Creek Administrative Area Sat Map.pdf | ||
| B08g Attachment 7 DEVA 280631 Attach C Flow Info.xlsx | XLSX spreadsheet | |
| B08h Attachment 8 DEVA 280631 Map.png | PNG image |
Show all 18
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
RAPID RESPONSE Series LFII Residential
4.9 K-factor Pendent Sprinkler
Wet Pipe and Dry Pipe Systems
Page 1 of 6 SEPTEMBER 2019 TFP400
IMPORTANT
Refer to Technical Data Sheet TFP2300 for warnings pertaining to regulatory and health information.
Always refer to Technical Data Sheet TFP700 for the “INSTALLER WARNING” that provides cautions with respect to handling and instal-lation of sprinkler systems and com-ponents. Improper handling and installation can permanently damage a sprinkler system or its compo-nents and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely.
Worldwide Contacts www.tyco-fire.com
General Description TYCO RAPID RESPONSE Series LFII Residential 4.9K Pendent and Recessed Pendent Sprinklers (TY2234) are decorative, fast response, frangi-ble bulb sprinklers designed for use in residential occupancies such as homes, apartments, dormitories, and hotels. When aesthetics and optimized flow characteristics are the major con-sideration, the Series LFII Residential Sprinklers (TY2234) should be the first choice.
The Series LFII Residential Sprinklers are intended for use in the following scenarios:
• wet and dry pipe residential sprin-kler systems for one- and two-fam-ily dwellings and mobile homes per
NFPA 13D
• wet and dry pipe residential sprinkler systems for residential occupancies up to and including four stories in height per NFPA 13R
• wet and dry pipe sprinkler systems for the residential portions of any occupancy per NFPA 13
The recessed version of the Series LFII Residential Sprinklers is intended for use in areas with finished ceilings.
It employs a two-piece Style 20 Recessed Escutcheon. The Recessed Escutcheon provides 1/4 in. (6,4 mm) of recessed adjustment or up to 1/2 in.
(12,7 mm) of total adjustment from the flush ceiling position. The adjustment provided by the Recessed Escutcheon reduces the accuracy to which the pipe drops to the sprinklers must be cut.
The Series LFII Residential Sprinklers have been designed with heat sensi-tivity and water distribution charac-teristics proven to help in the control of residential fires and to improve the chance for occupants to escape or be evacuated.
Corrosion-resistant coatings, where applicable, are utilized to extend the life of copper alloy sprinklers beyond that which would otherwise be obtained when exposed to corrosive atmo-spheres. Although corrosion-resistant coated sprinklers have passed the standard corrosion tests of the appli-cable Approval agencies, the testing is not representative of all possible cor-rosive atmospheres. Consequently, it is recommended that the end user be consulted with respect to the suit-ability of these coatings for any given corrosive environment. The effects of ambient temperature, concentration of chemicals, and gas/chemical velocity should be considered, as a minimum, along with the corrosive nature of the chemical to which the sprinklers will be exposed.
Dry Pipe System Application The Series LFII Residential Pendent and Recessed Pendent Sprinklers offers a laboratory approved option for designing dry pipe residential sprin-kler systems, whereas, most residential sprinklers are laboratory approved for wet systems only.
Through extensive testing, it has been determined that the number of design sprinklers (hydraulic design area) for the Series LFII Residential Pendent and Recessed Pendent Sprinklers (TY2234) need not be increased over the number of design sprinklers (hydraulic design area) as specified for wet pipe sprinkler systems, as is accustomed for density/ area sprinkler systems designed per
NFPA 13.
Consequently, the Series LFII Resi-dential Sprinklers offer the features of non-water filled pipe in addition to not having to increase the number of design sprinklers (hydraulic design area) for systems designed to NFPA 13, 13D, or 13R.
NOTICE
The Series LFII Residential Pendent and Recessed Pendent Sprinklers (TY2234) described herein must be installed and maintained in compli-ance with this document and the appli-cable standards of the NATIONAL FIRE
PROTECTION ASSOCIATION (NFPA),
in addition to the standards of any authorities having jurisdiction. Failure to do so may impair the performance of these devices.
The owner is responsible for main-taining their fire protection system and devices in proper operating con-dition. Contact the installing contrac-tor or product manufacturer with any questions.
Sprinkler Identification Number (SIN)
TY2234
TFP400
Technical Data Approvals UL Listed (for use with wet pipe and dry pipe systems) C-UL Listed (for use only with wet pipe systems) Certified to all requirements of
NSF/ANSI 61
Australian WaterMark Certified
Note: Sprinklers with a polyester finish are UL Listed as corrosion-resistant sprinklers.
See the Design Criteria section for details on these approvals.
Maximum Working Pressure 175 psi (12,1 bar)
Discharge Coefficient K=4.9 GPM/psi½ (70,6 LPM/bar½)
Temperature Rating 155°F (68°C) or 175°F (79°C)
Finishes Natural Brass, Pure White Polyester Coated, Signal White Polyester Coated, or Chrome Plated
Physical Characteristics Frame . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Brass Button . . . . . . . . . . . . . . . . . . . . . . . . . . . Copper Sealing Assembly . . Beryllium Nickel w/TEFLON Bulb (3 mm) . . . . . . . . . . . . . . . . . . . . . . . . Glass Compression Screw . . . . . . . . . . . . . . . . .Bronze Deflector . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze
Operation The glass bulb contains a fluid that expands when exposed to heat. When the rated temperature is reached, the fluid expands sufficiently to shatter the glass bulb, allowing the sprinkler to activate and flow water.
Design Criteria The TYCO RAPID RESPONSE Series LFII Residential 4.9K Pendent and Recessed Pendent Sprinklers are UL and C-UL Listed for installation in accordance with this section.
Residential Sprinkler Design Guide When conditions exist that are outside the scope of the provided criteria, refer to the Residential Sprinkler Design Guide TFP490 for the manufactur-er’s recommendations that may be acceptable to the local authority having jurisdiction.
System Types Per the UL Listing, wet pipe and dry pipe systems may be utilized. Per the C-UL Listing, only wet pipe systems may be utilized.
Refer to Technical Data Sheet TFP485 for the use of residential sprinklers in residential dry pipe systems.
Ceiling Types Smooth flat horizontal, or beamed, or sloped, in accordance with the 2013 Edition of NFPA 13D, 13R, or 13, as applicable.
Hydraulic Design (NFPA 13D and 13R) For systems designed to NFPA 13D or NFPA 13R, the minimum re quired sprinkler flow rates are given in Tables A and B as a function of tem-perature rating and the maximum allowable coverage areas. The sprinkler flow rate is the minimum required discharge from each of the total number of design sprinklers as specified in NFPA 13D or NFPA 13R.
The number of design sprinklers speci-fied in NFPA 13D and 13R for wet pipe systems is to be applied when design-ing dry pipe systems.
Hydraulic Design
(NFPA 13)
For systems designed to NFPA 13, the number of design sprinklers is to be the four most hydraulically demanding sprinklers. The minimum required dis-charge from each of the four sprinklers is to be the greater of the following:
• The flow rates given in Table A or B as a function of temperature rating and the maximum allowable coverage area.
• A minimum discharge of 0.1 gpm/ft2 over the design area comprised of the four most hydraulically demanding sprinklers for actual coverage areas protected by the four sprinklers.
The number of design sprinklers speci-fied in NFPA 13 for wet pipe systems is to be applied when designing dry pipe systems.
Dry Pipe System Water Delivery When using the Series LFII Residential Sprinklers (TY2234) in dry pipe sprin-kler systems, the time for water deliv-ery must not exceed 15 seconds for the most remote operating sprinkler.
Obstruction to Water Distribution Sprinklers are to be located in accor-dance with the obstruction rules of NFPA 13D, 13R, and 13 as applicable for residential sprinklers as well as with the obstruction criteria described within the Technical Data Sheet TFP490.
Operational Sensitivity Sprinklers are to be installed with a deflector-to-ceiling distance of 1-1/4 in.
to 4 in.
SURFACE
ESCUTCHEON
PLATE SEATING
1-5/8" (41,3 mm)
-2 Button
Temperature rating is indicated on Deflector.
Deflector
Compression Screw
Bulb Sealing Assembly
-6
-4 5 -
3 -
Components:
Frame1 -
1/2"
NPT
7/16" (11,1 mm)
MAKE-IN
NOMINAL
ESCUTCHEON
STYLE 20
RECESSEDWRENCH
(57,2 mm) 2-1/4"
FLATS
(73,0 mm)
2-7/8" DIA.
CROSS SECTION PENDENT RECESSED PENDENT
FIGURE 1
RAPID RESPONSE SERIES LFII RESIDENTIAL
4.9K PENDENT AND RECESSED PENDENT SPRINKLERS (TY2234)
Maximum Coverage
Area (1) ft x ft (m x m)
WET PIPE SYSTEM
Minimum Flow and Residual Pressure (2)(3)
Ordinary Temperature Rating 155°F (68°C)
Intermediate Temperature Rating 175°F (79°C)
Deflector to Ceiling
Installation Type
Minimum Spacing ft (m)
Flow gpm
(l/min)
Pressure psi
(bar)
Flow gpm
(l/min)
Pressure psi
(bar)
12 x 12 (3,7 x 3,7)
(49,2)
7.0 (0,48)
(49,2)
7.0 (0,48) Smooth
Ceilings 1-1/4 in. to 4 in.
Beamed Ceilings per
NFPA 13D
or 13R 1-1/4 in. to
1-3/4 in. below bottom of beam.
Recessed using Style 20 Escutcheon or non-recessed per NFPA 13D, 13R, or 13
(2,4)
14 x 14 (4,3 x 4,3)
(49,2)
7.0 (0,48)
(49,2)
7.0 (0,48)
16 x 16 (4,9 x 4,9)
(49,2)
7.0 (0,48)
(49,2)
7.0 (0,48)
18 x 18 (5,5 x 5,5)
(64,3)
12.0 (0,83)
(64,3)
12.0 (0,83)
20 x 20 (6,1 x 6,1)
(75,7)
16.7 (1,15)
(75,7)
16.7 (1,15)
Notes:
1. For coverage area dimensions less than or between those indicated, use the minimum required flow for the next highest coverage area for which hydraulic design criteria are stated.
2. Requirement is based on minimum flow in gpm (lpm) from each sprinkler. The associated residual pressures are calculated using the nominal K-factor. See Hydraulic
Design under the Design Criteria section.
3. For NFPA 13 residential applications, the greater of 0.1 gpm/ft2 over the design area or the flow in accordance with the criteria in this table must be used.
Maximum Coverage
Area (1) ft x ft (m x m)
DRY PIPE SYSTEM
Minimum Flow and Residual Pressure (2)(3)
Ordinary Temperature Rating 155°F (68°C)
Intermediate Temperature Rating 175°F (79°C)
Deflector to Ceiling
Installation Type
Minimum Spacing ft (m)
Flow gpm
(l/min)
Pressure psi
(bar)
Flow gpm
(l/min)
Pressure psi
(bar)
12 x 12 (3,7 x 3,7)
(49,2)
7.0 (0,48)
(49,2)
7.0 (0,48) Smooth
Ceilings 1-1/4 in. to 4 in.
Beamed Ceilings per NFPA 13D or 13R
1-1/4 in. to 1-3/4 in. below bottom of beam.
Recessed using Style 20 Escutcheon or non-recessed per NFPA 13D, 13R, or 13
(2,4)
14 x 14 (4,3 x 4,3)
(53,0)
8.2 (0,57)
(53,0)
8.2 (0,57)
16 x 16 (4,9 x 4,9)
(56,8)
9.4 (0,65)
(56,8)
9.4 (0,65)
18 x 18 (5,5 x 5,5)
(68,1)
13.5 (0,93)
(68,1)
13.5 (0,93)
20 x 20 (6,1 x 6,1)
(79,5)
18.4 (1,27)
(79,5)
18.4 (1,27)
Notes:
1. For coverage area dimensions less than or between those indicated, use the minimum required flow for the next highest coverage area for which hydraulic design criteria are stated.
2. Requirement is based on minimum flow in gpm (lpm) from each sprinkler. The associated residual pressures are calculated using the nominal K-factor. See Hydraulic
Design under the Design Criteria section.
3. For NFPA 13 residential applications, the greater of 0.1 gpm/ft2 over the design area or the flow in accordance with the criteria in this table must be used.
TABLE A
WET PIPE SYSTEM
SERIES LFII RESIDENTIAL 4.9K PENDENT AND RECESSED PENDENT SPRINKLERS (TY2234)
NFPA 13D, 13R, AND 13 HYDRAULIC DESIGN CRITERIA
TABLE B
DRY PIPE SYSTEM
SERIES LFII RESIDENTIAL 4.9K PENDENT AND RECESSED PENDENT SPRINKLERS (TY2234)
NFPA 13D, 13R, AND 13 HYDRAULIC DESIGN CRITERIA
Sprinkler Spacing The minimum spacing between sprin-klers is 8 ft (2,4 m). The maximum spacing between sprinklers cannot exceed the length of the coverage area (Table A or B) being hydraulically calcu-lated, for example, maximum 12 ft for a 12 ft x 12 ft coverage area, or 20 ft for a 20 ft x 20 ft coverage area.
Installation TYCO RAPID RESPONSE Series LFII Residential 4.9K Pendent and Recessed Pendent Sprinklers must be installed in accordance with this section.
General Instructions Do not install any bulb type sprinkler if the bulb is cracked or there is a loss of liquid from the bulb. With the sprin-kler held horizontally, a small air bubble should be present. The diameter of the air bubble is approximately 1/16 in.
(1,6 mm).
A leak-tight 1/2 in. NPT sprinkler joint should be obtained by applying a min-imum-to-maximum torque of 7 to 14 lb-ft (9,5 to 19,0 N∙m). Higher levels of torque can distort the sprinkler Inlet with consequent leakage or impairment of the sprinkler.
Do not attempt to compensate for insufficient adjustment in an Escutch-eon Plate by under- or over- tightening the sprinkler. Re-adjust the position of the sprinkler fitting to suit.
Pendent Sprinklers The Series LFII Residential Pendent Sprinklers must be installed in accor-dance with the following instructions:
Step 1. Install pendent sprinklers in the pendent position with the deflector par-allel to the ceiling.
Step 2. With pipe thread sealant applied to the pipe threads, hand-tighten the sprinkler into the sprinkler fitting.
Step 3. Tighten the sprinkler into the sprinkler fitting using only the W-Type 6 Sprinkler Wrench (Figure 3). With ref-erence to Figure 1, apply the W-Type 6 Sprinkler Wrench to the wrench flats.
Recessed Pendent Sprinklers The Series LFII Residential Recessed Pendent Sprinklers must be installed in accordance with the following instructions:
Step A. Install recessed pendent sprin-klers in the pendent position with the deflector parallel to the ceiling.
Step B. After installing the Style 20 Mounting Plate over the sprinkler threads and with pipe thread sealant applied to the pipe threads, hand-tighten the sprinkler into the sprinkler fitting.
Step C. Tighten the sprinkler into the sprinkler fitting using only the W-Type 7 Recessed Sprinkler Wrench (Figure 4).
With reference to Figure 1, apply the W-Type 7 Recessed Sprinkler Wrench to the sprinkler wrench flats.
Step D. After the ceiling has been installed or the finish coat has been applied, slide on the Style 20 Closure over the Series LFII Residential Sprin-kler and push the Closure over the Mounting Plate until its flange comes in contact with the ceiling.
TY2234
2-7/8" DIA.
(73,0 mm)
(57,2 mm)
2-1/4" DIA.
MOUNTING
SPRINKLER
CLOSURE
SURFACE
FITTING
FACE OF
(11,1±3,2 mm) 7/16±1/8"
MOUNTING
PLATE
1-3/8" (34,9 mm)
1-1/8" (28,6 mm)
(3,2 mm) 1/8"
1/2" (12,7 mm)
1/4" (6,4 mm)
RECESS
WRENCH
WITH SPRINKLER
ENGAGEMENT
IN TO ENSURE
WRENCHING AREA
PUSH WRENCH
WRENCH RECESS
(END "A" USED
FOR TY2234)
FIGURE 2
STYLE 20 RECESSED ESCUTCHEON FOR USE WITH THE
RAPID RESPONSE SERIES LFII RESIDENTIAL PENDENT SPRINKLER
FIGURE 4
W-TYPE 7 RECESSED
SPRINKLER WRENCH
FIGURE 3
W-TYPE 6
SPRINKLER WRENCH
Care and Maintenance TYCO RAPID RESPONSE Series LFII Residential 4.9K Pendent and Recessed Pendent Sprinklers must be maintained and serviced in accordance with this section:
Before closing a fire protection system main control valve for maintenance work on the fire protection system that it controls, permission to shut down the affected fire protection system must be obtained from the proper authorities and notify all personnel who may be affected by this action.
Absence of the outer piece of an escutcheon, which is used to cover a clearance hole, can delay sprinkler operation in a fire situation.
The owner must assure that the sprin-klers are not used for hanging any objects and that the sprinklers are only cleaned by means of gently dusting with a feather duster; otherwise, non-operation in the event of a fire or inad-vertent operation may result.
Sprinklers which are found to be leaking or exhibiting visible signs of corrosion must be replaced.
Automatic sprinklers must never be painted, plated, coated, or other-wise altered after leaving the factory.
Modified sprinklers must be replaced.
Sprinklers that have been exposed to corrosive products of combustion, but have not operated, should be replaced if they cannot be completely cleaned by wiping the sprinkler with a cloth or by brushing it with a soft bristle brush.
Care must be exercised to avoid damage to the sprinklers before, during, and after installation. Sprin-klers damaged by dropping, striking, wrench twist/slippage, or the like, must be replaced. Also, replace any sprinkler that has a cracked bulb or that has lost liquid from its bulb. See the Installation section.
The owner is responsible for the inspection, testing, and maintenance of their fire protection system and devices in compliance with this document, as well as with the applicable standards of the NATIONAL FIRE PROTECTION ASSOCIATION, for example, NFPA 25, in addition to the standards of any authorities having jurisdiction. Contact the installing contractor or product manufacturer with any questions.
Automatic sprinkler systems are rec-ommended to be inspected, tested, and maintained by a qualified Inspec-tion Service in accordance with local requirements and/or national codes.
Limited Warranty For warranty terms and conditions, visit www.tyco-fire.com.
Ordering Procedure Contact your local distributor for avail-ability. When placing an order, indicate the full product name and part number (P/N).
Sprinkler Assemblies Specify: Series LFII 4.9K Residential Pendent Sprinkler (TY2234), (specify temperature rating), with (specify) finish, P/N (specify):
155°F (68°C) Natural Brass . . . . . . . . . . . . . . . . . 51-201-1-155 Pure White (RAL 9010) Polyester1, 2 . . . . . . . . . . . . . . . . . . 51-201-3-155 Signal White (RAL 9003) Polyester1. . . . . . . . . . . . . . . . . . . . 51-201-4-155 Chrome Plated . . . . . . . . . . . . . . . . 51-201-9-155
175°F (79°C) Natural Brass . . . . . . . . . . . . . . . . . 51-201-1-175 Pure White (RAL 9010) Polyester1, 2 . . . . . . . . . . . . . . . . . . 51-201-3-175 Signal White (RAL 9003) Polyester1. . . . . . . . . . . . . . . . . . . . 51-201-4-175 Chrome Plated . . . . . . . . . . . . . . . . 51-201-9-175
1. UL Listed as corrosion-resistant.
2. Eastern Hemisphere sales only.
Recessed Escutcheon Specify: Style 20 Recessed Escutch-eon with (specify*) finish, P/N (specify*)
* Refer to Technical Data Sheet TFP770.
Sprinkler Wrenches Specify: W-Type 6 Sprinkler Wrench, P/N 56-000-6-387
Specify: W-Type 7 Sprinkler Wrench, P/N 56-850-4-001
NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association;
TEFLON is a registered trademark of DuPont
1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700
© 2019 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.